ABB COMMANDER 360 Operation & User’s Manual
Text of the manual
ABB Instrumentation
User Guide
COMMANDER 360
Profile Controller
COMMANDER 360
X
PV
SP
W
360.0
360.0
36
OP1
M
OP2
SEQ
PRG
BS EN ISO 9001
St Neots, U.K. – Cert. No. Q5907
Stonehouse, U.K. – Cert. No. FM 21106
The Company
ABB Instrumentation is an established world force in the design and
manufacture of instrumentation for industrial process control, flow
measurement, gas and liquid analysis and environmental applications.
As a part of ABB, a world leader in process automation technology, we offer
customers application expertise, service and support worldwide.
We are committed to teamwork, high quality manufacturing, advanced
technology and unrivalled service and support.
The quality, accuracy and performance of the Company’s products result
from over 100 years experience, combined with a continuous program of
innovative design and development to incorporate the latest technology.
The NAMAS Calibration Laboratory No. 0255(B) is just one of the ten flow
calibration plants operated by the Company, and is indicative of ABB
Instrumentations dedication to quality and accuracy.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in
accordance with the information given.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in
conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal
safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets (where
applicable) may be obtained from the Company address on the back cover, together with servicing and spares
information.
Use of Instructions
Warning.
An instruction that draws attention to the risk of injury
or death.
Caution.
An instruction that draws attention to the risk of
damage to the product, process or surroundings.
1
Note.
Clarification of an instruction or additional information.
Information.
Further reference for more detailed information or
technical details.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property
damage, it must be understood that operation of damaged equipment could, under certain operational conditions, result in
degraded process system performance leading to personal injury or death. Therefore, comply fully with all Warning and
Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this
manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior
approval of Technical Communications Department, ABB Instrumentation.
Stonehouse, U.K. – Cert. No. 0255
EN 29001 (ISO 9001)
Lenno, Italy – Cert. No. 9/90A
R
E
G
I
S
T
E
R
E
D
F
I
R
M
The COMMANDER 360 can be configured and made ready for operation in three easy
steps. This 'Getting Started' guide provides an overview of these steps and, where
necessary, refers to the relevant section of the manual.
Step 1
–
Decide on the Application Template and the Output
Configuration required
Step 2
–
Connect the process inputs and outputs
Step 3
–
Power up the instrument, set the template number and the
output configuration details
Your COMMANDER 360 is now ready for operation
Step 1 – Application Template and Output Configuration
•
Choose the Template which best suits your application from the list in Table A,
located on the rear fold-out.
•
Choose the Control Output Type required from the list of options in Table B on the
rear foldout.
Step 2 – Electrical Connections
Using the labels on the back of the instrument as a guide, connect the process inputs,
outputs and power supplies. Refer to Section 6.2 of this manual (Electrical Installation)
for more information.
Continued…
GETTING STARTED
Fig. GS.1 Setting the Parameters
Note.
With
the
above
configuration,
no alarms, limits or
ramp / soak profiles
have been set and
advanced functionality
(gain scheduling, set
point sources etc.) has
not been enabled.
Step 3 – Setting the Parameters (Fig. GS.1)
A Power-up the instrument. Press the
and
keys simultaneously and hold for
3 seconds to advance directly to Level 6 – Basic Configuration.
B Set the appropriate application template, output type and control action. Use the
key to advance between frames and upper
and
keys to adjust the
default values – see Section 5.2 for further information.
Note. When the output type has been selected, the available inputs and outputs
default to the settings shown in Table B on the rear fold-out.
C If you are not using 4 to 20mA inputs, then select Level 7 using the upper
and
keys and set up Analog Inputs I/P1 to I/P3 to suit your process – see Section 5.3.
D Controller templates only:
Select Level 2 using the upper
and
keys and set the tune parameters:
• Analog or Motorized Valve Control – set the Proportional, Integral and
Derivative terms.
• Time Proportioning Control – set the Cycle Time, Hysteresis and P, I & D Terms
• Heat/Cool Outputs – set the points at which the Output 1 and Output 2
become active.
E Press
to return to the Operating displays.
F Adjust the set point to the required value.
Your COMMANDER 360 is now in operation
APPL
LEV.6
INPt
LEV.7
tUNE
LEV2
B
C
D
+
A
01.SL
t.APP
ANLG
O.tYP
rEV
C.ACt
50
FrEJ
E
F
360.0
361.5
70
360.0
361.5
70
360.0
361.5
70
GETTING STARTED
Fig. 3 Accessories
This manual is divided into 6 sections which contain all the information needed to install, configure,
commission and operate the COMMANDER 360. Each section is identified clearly by a symbol as
shown in Fig. 1.
Fig. 1 Overview of Contents
Displays and Controls
• Displays and Function Keys
• LED Indication
• Error Messages
Operator Mode (Level 1)
• Single Loop Controller
• Cascade Controllers
Profile Mode
(Levels P, r and t)
• Level P – Profile States
• Level r
– Profile Control
• Level t
– Profile Program
Set Up Mode (Levels 2 to 5)
• Level 2 – Tuning
• Level 3 – Set Points
• Level 4 – Alarm Trip Points
• Level 5 – Valve Setup
8
Configuration Mode (Levels 6 to E)
• Level 6 – Basic Configuration
• Level 7
–
Input Configuration
• Level 8
–
Alarm Configuration
• Level 9
–
Set Point Configuration
• Level A –
Control Configuration
• Level B
–
Operator Configuration
• Level C
–
Output Configuration
• Level D
–
Serial Communications
• Level E
–
System Calibration
Installation
• Siting
• Mounting
• Electrical Connections
Fig. 2 Foldouts
Getting
Started
Getting
Started
Table
A – Template Application
B – Output Sources
Table
C – Digital Sources
D – Analog Sources
Shunt Resistors
3 x 100Ω
Panel Clamps
x2
CJ Sensor
x2
OVERVIEW .................................................... 1
1
DISPLAYS AND FUNCTION KEYS ......... 3
1.1 Introduction ........................................ 3
1.2 Use of Function Keys ........................ 4
1.3 Secret-til-Lit Indicators ....................... 7
1.4 Character Set ..................................... 7
1.5 Error Messages ................................. 8
1.6 Processor Watchdog ......................... 9
1.7 Loop Break Monitor ........................... 9
1.8 Glossary of Abbreviations .................. 9
2
OPERATOR LEVEL ................................ 10
2.1 Introduction ...................................... 10
2.2 Single Loop Controller (Template 1) 11
2.3 Cascade Control (Template 11) ....... 13
2.4 Heat/Cool Output Types .................. 16
2.5 Motorized Valve Output Types ........ 17
2.6 Alarm Acknowledgement ................. 18
2.7 Auto-tune ......................................... 19
2.8 Control Efficiency Monitor ............... 22
3
PROFILES ............................................... 25
3.1 Introduction ...................................... 25
3.2 Introduction to Ramp/Soak Profile
Control.............................................. 26
3.2.1 Ramp Types ........................... 26
3.2.2 Guaranteed Ramp/Soak ........ 27
3.2.3 Power Recovery Function ..... 27
3.2.4 Self-seeking Set Point ........... 28
3.2.5 Retort Function ...................... 28
3.2.6 Time Events ........................... 29
3.2.7 End of Profile State ............... 29
3.2.8 Current Segment Time
Adjustment ............................. 30
3.3 Profile States ................................... 31
3.4 Ramp/Soak Profile Control .............. 32
3.5 Ramp/Soak Profile Program ............ 36
4
SET UP MODE ........................................ 39
4.1 Introduction ...................................... 39
4.2 Level 2 – Tune ................................. 40
4.3 Level 3 – Set Points ......................... 44
4.4 Level 4 – Alarm Trip Points.............. 46
4.5 Level 5 – Valve Setup ...................... 47
Section
Page
5
CONFIGURATION MODE ...................... 50
5.1 Introduction ...................................... 50
5.2 Level 6 – Basic Configuration ......... 51
5.3 Level 7 – Analog Inputs ................... 55
5.4 Level 8 – Alarms .............................. 59
5.5 Level 9 – Set Point Configuration.... 63
5.6 Level A – Control Configuration ....... 65
5.7 Level B – Operator Configuration.... 70
5.8 Level C – Output Assignment
Configuration ................................... 72
5.8.1 Digital Output 1 ...................... 73
5.8.2 Analog Output 1 ..................... 74
5.8.3 Analog Output 2 ..................... 75
5.8.4 Relay Outputs 1 to 4 .............. 76
5.9 Level D – Serial Communications
Configuration ................................... 78
5.10 Level E – Calibration ....................... 79
6
INSTALLATION ....................................... 82
6.1 Mechanical Installation .................... 82
6.2 Electrical Installation ........................ 86
6.3 Relays .............................................. 89
6.4 Digital Output ................................... 89
6.5 Control or Retransmission Analog
Output .............................................. 89
6.6 Motorized Valve Connections .......... 90
6.7 Input Connections ............................ 90
6.8 Output Connections ......................... 91
6.9 Power Supply Connections ............. 91
APPENDIX A – CONTROL TEMPLATES ... 92
A1
Single Loop Controller (Template 1) 92
A2
Cascade Controller (Template 11) ... 93
APPENDIX B – COMMANDER
CONFIGURATION EDITOR ......................... 94
B1
Introduction ...................................... 94
B2
Analog Input Customization ............ 94
B3
Four Programmable Maths Blocks .. 94
B4
Six Logic Equations ......................... 94
B5
Process Alarm Customization ......... 94
B6
Two Real Time Alarms ..................... 94
B7
Two Delay Timers ............................ 95
B8
Two Custom Linearizers .................. 95
B9
Template Customization .................. 95
B10 Connecting the COMMANDER PC
Configurator ..................................... 95
FRAMES INDEX .......................................... 96
Profile Frames ......................................... 96
Set Up Frames ........................................ 97
Configuration Frames .............................. 98
INDEX
....................................................... 100
Fig. 1.1 Front Panel Displays and Function Keys
1
DISPLAYS AND FUNCTION KEYS
1.1
Introduction
The COMMANDER 360 front panel displays, function keys and LED indicators are shown in Fig. 1.1.
70
PRG
SEG
OP1
OP2
M
COMMANDER 360
PV
SP
X
361.5
Function Keys
Auto/manual
Raise
Parameter
Advance
Stop
Run/Hold
Lower
Up
Down
W
360.0
DISPLAYS AND FUNCTION KEYS
1.2
Use of Function Keys
Fig. 1.2a Use of Function Keys
A – Raise and Lower Keys
Use to change/set a parameter value…
…move between levels
and…
C – Parameter Advance Key
Use to advance to the next
frame within a level…
or…
…select the top (LEV.x) frame
from within a level
Note. This key also stores any changes made in the previous frame
LEV2
tUNE
CYCl
5.0
Frame 2
Frame 1
(top of level)
B – Up and Down Keys
and…
bIAS
50.0
51.0
49.0
+
–
LEV1
OPEr
LEVP
PrFL
…move between frames within a Setup
or Configuration level. Any changes made
on the current frame are stored when the
next frame is selected.
LEV2
tUNE
CYCl
5.0
Frame 2
Frame 1
(top of level)
Press and hold
LEVx
1001
1002
1003
Use to adjust the profile
parameters, the output value…
700
710
690
+
–
2.00
2.01
Use of Function Keys
Fig. 1.2b Use of Function Keys
1
DISPLAYS AND FUNCTION KEYS…
360.0
361.5
70
E – Run / Hold Key
F – Stop Key
Use to stop a profile program that is running
(This is equivalent to putting a program in Hold mode and then resetting the
program)
The local set point will revert to the starting value for the program.
Use to start a profile program. Pressing the key when a profile is active toggles
the profile between the run and hold states.
Program
Stopped
Program
Running
Program
on Hold
Program
Running
360.0
361.5
70
360.0
361.5
70
360.0
361.5
70
D – Auto/Manual Key
Use to select Auto or Manual control mode
Auto
Manual
Process Variable
Control Set Point
Control Output (%)
M
360.0
361.5
70
DISPLAYS AND FUNCTION KEYS
…1.2
Use of Function Keys
Note. This Short-cut key operates
only when the Configuration password is
set to '0'.
Fig. 1.2c Use of Function Keys
G – Short-cut Keys
Press to move from anywhere in
the Configuration level to the first
frame in the Operator level
Press to move from
anywhere in the
Operator or Setup
levels to the first page
of the Configuration
level
LEVA
CntL
361.5
360.0
LEV6
APPL
Press simultaneously and
hold for 3 seconds
+
Press to move from the Operator Level to the
Security Code Frame and then to other levels:
Tune Level – See Section 2.7.3
Profiles Level – See Fig. 3.1
Set Up Level – See Fig. 4.1
Configuration Level – See Fig. 5.1
COdE
0
360.0
361.5
70
360.0
361.5
70
DISPLAYS AND FUNCTION KEYS…
360.0
70
PRG
SEG
360.0
361.5
70
OP1
OP2
M
PRG
SEG
OFF
Auto control
selected
ON
Output 1 (heat)
value displayed
Output 2 (cool)
value displayed
Manual control
selected
Program on Hold
Current program
number displayed
Current program
segment displayed
Time remaining in
current segment
displayed
Flashing
Autotune in
progress
OFF
No alarms active
ON
All active alarms
acknowledged
Profile is
ramping down
Profile is
ramping up
Profile
performing a
soak
Flashing
One or more
alarms active and
unacknowledged
A – Upper Display
B – Lower Display
OP1
OP2
M
1.4
Character Set – Fig. 1.4
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
R
S
T
U
V
Y
A
b
C
D
E
F
G
H
I
J
K
L
M
N
O
P
r
S
t
U
V
Y
Fig. 1.3 Secret-til-lit Indicators
Fig. 1.4 Character Set
DISPLAYS AND FUNCTION KEYS
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
350.0
351.5
Error/Action
Non-volatile Memory Error
x = 1: Processor Board Memory
x = 3: Power Supply Board Memory
Turn mains power off and on again
(if the error persists, check
configuration/setup settings).
A to D Converter Fault
The analog to digital converter is not
communicating correctly.
Input Value Over/Under Range
Auto-tune Error
The number displayed indicates the
type of error present – see Table 2.1
on page 19.
Cold Junction Failed
Cold junction sensor is faulty or has
not been fitted correctly.
Valve Sticking
Motorized valve not moving at the
speed expected. Valve may be
sticking.
Position Feedback Fail
Input value is over- or under-range.
Only appears if output type set to
'PFb' – motorized valve with feeback.
To clear the display:
Press and hold the
key
Contact the Customer
Support Organization
Restore valid input
Press and hold the
key
Check connections or replace
if faulty.
Check that the correct
Regulator Travel Time has
been set – see Section 4.5.
Check the valve.
Restore valid input
Display
9999
t.Err
1
StK
A-d
Err
Err
NVx
CJ.F
1
999
The instrument's processor activity is monitored by an independent watchdog device. When the
output of the watchdog is assigned to a relay or digital output, the relay/digital output de-energizes
if the instrument fails to function correctly.
1.7
Loop Break Monitor
Analog output 1 is monitored continuously to detect a loop break. A warning signal or other action can
be initiated by assigning the loop break signal to relays or digital outputs.
1.8
Glossary of Abbreviations
Table 1.1 Glossary of Abbreviations
Abbrevia it on
Desc ir p it on
Abbrevia it on
esc ir p it on
D
PV
elb
Process Va air
1id
Ila nput 1
tigi
D
LSPt
Loc la Set P nio t V ula e
2id
Ila nput 2
tigi
D
LSP1
Loc la Set P nio t 1 V ula e
3id
Ila nput 3
tigi
D
LSP2
Loc la Set P nio t 2 V ula e
4id
Ila nput 4
tigi
D
LSP3
Loc la Set P nio t 3 V ula e
ao1
n ola g Output 1
A
LSP4
Loc la Set P nio t 4 V ula e
ao2
n ola g Output 2
A
P.SPt
Set P nio t V ula e
Pro elif
do1
la Output 1
tigi
D
PID O/P
Output of the PID A gl o tir hm
M.PV
elb
a ts er Process Va air
M
OP1
r Output 1 (hea )t
ello
Con rt
M.SPt
lo Set P nio t
a ts er Con rt
M
OP2
r Output 2 (co )lo
ello
Con rt
M.OP
a ts er PID Output
M
/I P1
An ola g Input 1
S.SPt
al ve Set P nio t
S
/I P2
An ola g Input 2
S.PV
elb
al ve Process Va air
S
/I P3
n ola g Input 3
A
1
DISPLAYS AND FUNCTION KEYS
The Operator level (Level 1) is the normal day-to-day mode of the COMMANDER 360. This section
describes the operator facilities available on each frame depending on the control template and
output type selected.
The template types available on COMMANDER 360 instruments, and detailed in this section, are:
•
Single loop controller
•
Cascade control
Note. Only the frames relevant to the selected template are displayed – see Section 5.
In addition, frames used to view the Control Efficiency Monitor and operate motorized valve and heat/
cool output types are also described.
Profile operation and setting up is detailed in Section 3.
2
OPERATOR LEVEL
Fig. 2.1 Power-up Displays
01.SL
C360
Model – C360
Template (see rear fold-out)
Software series
Software version
01
2001
PV – CSPt
Deviation
•1
PRG
SEG
X.NN
Current Segment Number
Current Program Number
•2 •3
2
OPERATOR LEVEL…
Fig. 2.2 Single Loop Controller
2.2
Single Loop Controller (Template 1)
The single loop controller is a basic feedback control system using three-term PID or on/off control.
PID
Control Loop
PID O/P
CSPt
PV
I/P1
Manual Output
OP1
Process Variable Input
Local Set Point
Control
Output
Profile Set Point
LSPt 1
Process Variable
Control Set Point
['SPt.L' to 'SPt.H' – see Section 5.5]
Adjustable only when profile is not running.
Local Set Point 1 is used for the profile set point and
is selected automatically when a profile is run.
Current Program/Segment
[1.01 to L.99 ]
When the profile is in Run or Hold mode:
Press
to skip forward to the start of the next
segment.
Press
to skip back to the start of the current
segment.
When the profile is Stopped:
Press
or
to select the profile program to
be run.
Note. Only valid programs (i.e. those not
switched off) can be selected.
Continued on next page
•1
With the Ramping Set Point function enabled (see Section 4.3, Set Points/ Ramp Rate), the
deviation bargraph shows the difference between the process variable and the actual (ramping)
set point value. The digital display shows the target set point value.
•2
Program selection can only be adjusted when the current program is stopped and program
selection is enabled – see Section 3.4/Profile Control/ Front Panel Program Select.
•3
Segments can only be skipped if a program is in Run or Hold mode and Segment Skip is enabled
– see Section 3.4/Profile Control/ Front Panel Skip Enable.
Time Remaining in Current Segment
[0.0 to 99.9 hours or minutes]
Allows the total segment time to be increased or
decreased by the Time Adjust value set in the Profile
Control Level. If the current segment is a ramp, it will
change the ramp rate.
Time units are set in the Profile Control Level – see
Section 3.4/Profile Control/ Program Time Units.
99.9 is displayed if the time remaining is greater
than 99.9 hours or minutes.
Control Output
[0 to 100% (digital/relay outputs),
–10 to 110% (analog outputs)]
Adjustable in manual mode only. With on/off control
selected, 0% = control output off, 100% = control
output on. In manual mode, intermediate values can
be selected. These use 'time proportioning' with a
60s cycle time, e.g. 25% = 15s on, 45s off.
Note. This frame is displayed automatically
when manual mode is selected from the front panel.
Return to top of page
…2.2
Single Loop Controller (Template 1)
•1
Adjustment can be disabled in the Profile Control Level
Current Segment Number
Current Program Number
2
OPERATOR LEVEL…
2.3
Cascade Control (Template 11)
For cascade control, two internally-linked PID controllers are used, with the first (master) PID
controller providing the set point for the second (slave) controller. The master output is weighted
using the cascade ratio (C.rtO) and bias (C.bIA) values to create the slave set point value.
Fig. 2.3 Cascade Controller
Master Process Variable (MPV)
Master Control Set Point (MSPt)
['SPt.L' to 'SPt.H' – see Section 5.5]
Adjustable in local control only.
Local Set Point 1 is used for the profile set point and
is selected automatically when a profile is run.
Current Program/Segment
[1.01 to L.99 ]
When the profile is in Run or Hold mode:
Press
to skip forward to the start of the next
segment.
Press
to skip back to the start of the current
segment.
When the profile is Stopped:
Press
or
to select the profile program to
be run.
Note. Only valid programs (i.e. those not
switched off) can be selected.
Continued on next page
•1
With the Ramping Set Point function enabled (see Section 4.3, Set Points/ Ramp Rate), the
deviation bargraph shows the difference between the process variable and the actual (ramping)
set point value. The digital display shows the target set point value.
•2
Program selection can only be adjusted when the current program is stopped and program
selection is enabled – see Section 3.4/Profile Control/ Front Panel Program Select.
•3
Segments can only be skipped if a program is in Run or Hold mode and Segment Skip is enabled
– see Section 3.4/Profile Control/ Front Panel Skip Enable.
MSPt
I/P1
I/P2
OP1
Local
Set Point
Master PV Input
Slave PV Input
Slave Set
Point
Slave PID
Control Loop
SPV
Master
PID
Control Loop
LSPt 1
SSPt
Manual Output
M.OP x
CrtO + CbIA
S.SPt
M.OP
LOC
CAS
MPV
Profile Set Point
Cascade Control (Template 11)
…2
OPERATOR LEVEL
Time Remaining in Current Segment
[0.0 to 99.9 hours or minutes]
Allows the total segment time to be increased or
decreased by the Time Adjust value set in the Profile
Control Level. If the current segment is a ramp, it will
change the ramp rate.
Time units are set in the Profile Control Level – see
Section 3.4/Profile Control/ Program Time Units.
99.9 is displayed if the time remaining is greater
than 99.9 hours or minutes.
Slave Control Output
[0 to 100% (digital/relay outputs),
–10 to 110% (analog outputs)]
Adjustable in manual mode only. With on/off control
selected, 0% = control output off, 100% = control
output on. In manual mode, intermediate values can
be selected. These use 'time proportioning' with a
60s cycle time, e.g. 25% = 15s on, 45s off.
Note. This frame is displayed automatically
when manual mode is selected from the front panel.
Slave Process Variable
Slave Control Set Point (SSPt)
['SSP.L' to 'SSP.H' – see Section 5.5]
Adjustable in local control only.
Continued…
36.00
36.02
SLV
Slave
Deviation
70
OP1
888
•1
•1
Adjustment can be disabled in the Profile Control Level
Cascade Control (Template 11)
Slave Set Point Select
Use this frame to select between local and cascade
slave set points.
[CASC or LOCL]
'CASC' =
Slave
set
point
derived
from
Master Output
'LOCL' =
Slave
set
point
independent
of
Master Output
Cascade Slave Set Point Ratio
[0.001 to 9.999]
Slave set point (SSPt) value =
(ratio x master ouput) + bias [in engineering units]
Cascade Slave Set Point Bias
[In engineering units]
Return to Master Process Variable (MPV) display
•1
Only displayed if ratio/bias display enabled – see Section 5.7, Operator Configuration.
1.000
C.rtO
SLV
•1
0.0
C.bIA
SLV
•1
CASC
SEt.P
SLV
Heat/Cool Output Types
2.4.1
Reverse (Heat)/Direct (Cool) or Direct (Heat)/Reverse (Cool)
The active output, either OP1 (Heat) or OP2 (Cool) is displayed and may be adjusted in manual
mode. The OP1 and OP2 l.e.d.s indicate which output is changing.
Output Positive (Heat Output Active)
Heat output
[0 to 100% (0 to 110% for analog output)]
Adjustable in manual mode only.
Output Negative (Cool Output Active)
Cool output
[–100 to 0% (–110 to 0% for analog output)]
Adjustable in manual mode only.
OP2 (cool)
OP1 (heat)
Y2.St
Y1.St
PID O/P
0%
–100%
100%
+100%
50
-50
•1
•2
OP1
OP2
Fig. 2.4 Typical Response – Reverse/Direct or Direct/Reverse Control Action
•1
0 to 100% for heat/cool analog output
•2
–100 to 0% for heat/cool analog output
Reverse (Heat)/Reverse (Cool) or Direct (Heat)/Direct (Cool)
It is not possible to view or adjust the heat/cool outputs directly. The PID output (0 to 100%), used to
calculate the heat (OP1) and cool (OP2) outputs, is displayed and may be adjusted in manual mode.
The OP1 and OP2 l.e.d.s indicate which output is changing.
2.5
Motorized Valve Output Types
2.5.1
Motorized Valve with Feedback
Valve Position Display
[0 to 100% of travel]
Note. In manual mode, the
and
keys
can be used to drive the valve open and valve close
relays directly.
2.5.2
Motorized Valve without Feedback (Boundless)
Valve State Display
OPN
Valve opening
StP
Valve stopped
CLS
Valve closing
Note. In manual mode, the
and
keys
can be used to drive the valve open and valve close
relays directly.
OP2
(cool)
OP1
(heat)
Y2.St
Y1.St
PID O/P
OP2 l.e.d. lit
OP1 l.e.d. lit
100%
0%
0%
100%
70
StP
Fig. 2.5 Typical Response – Reverse/Reverse or Direct/Direct Control Action
Fig. 2.6 Alarm Acknowledgement
Any active,
unacknowledged
alarms
All active
alarms
acknowledged
(Flashing)
200.3
1.HP1
2003
1HP1
ACt
ACK
LAt
or
CLr
ACK
LAt
or
200.3
2.xxx
ACt
1
2
3
4
Unacknowledged
alarms only
(On continuously)
(Off)
No active
alarms present
Pressing again acknowledges the displayed alarm.
Lower display changes to reflect new status.
3
Next active and unacknowledged alarm is displayed. If no alarms
are active, the next enabled alarm is displayed.
4
None
High Output
High Process, PV
Low Output
Low Process, PV
Power Failure Time
High Latch, PV
Maths Block 1 High
Low Latch, PV
Maths Block 1 Low
High Deviation
Maths Block 2 High
Low Deviation
Maths Block 2 Low
High Process I/P1
Maths Block 3 High
Low Process I/P1
Maths Block 3 Low
High Process I/P2
Maths Block 4 High
Low Process I/P2
Maths Block 4 Low
High Process I/P3
Low Process I/P3
The first active and unacknowledged alarm is displayed
(or if no alarms are active, the first enabled alarm is displayed)
1
The lower display shows alarm status:
ACt
Alarm active and unacknowledged
ACK
Alarm active and acknowledged
CLr
Cleared or Inactive alarm
LAt
Unacknowledged latched alarm
2
NONE
HO
HPV
LO
LPV
PF.t
HLP
Hb1
LLP
Lb1
Hd
Hb2
Ld
Lb2
HP1
Hb3
LP1
Lb3
HP2
Hb4
LP2
Lb4
HP3
LP3
Note. The time of the
power failure, PFt, is shown
in the set point display.
360.0
361.5
70
360.0
361.5
70
Press
and
hold
0
COdE
Security Access – see
Sections 3, 4 & 5
Note. Auto-tune is not available while a profile is running or when boundless or heat/cool
control types are selected.
Information.
• Auto-tune optimizes process control by manipulating the COMMANDER 360 output and then
monitoring the process response.
• At the end of an auto-tune, the control parameters are updated automatically.
• Before starting auto-tune, the process variable must be stable.
• The COMMANDER 360 monitors the noise level of the process variable for 30 seconds and if
it is greater than 2% of the engineering range the auto-tune is aborted.
• The COMMANDER 360 selects either 'start-up' or 'at set point' tuning automatically, depending
upon the level of the process variable relative to the control set point.
2.7.1
Start-up Auto-tune
If the process variable is more than ±10% from the set point, 'start-up' tuning is carried out.
•
'Start-up' tuning – steps the output to drive the process towards the set point. The process
response to this step change is monitored and PID parameters are calculated.
•
The output step applied = % deviation from the set point x 5.
•
If no errors exist, the COMMANDER 360 enters auto mode and begins to control the process
using the new PID parameters.
•
If an error occurs during the auto-tune, the COMMANDER 360 reverts to manual mode with the
control output set to the default output value. An error message is displayed in the operator
level – see Table 2.1.
2
OPERATOR LEVEL…
+2%
– 2%
t
A – Stable process before auto-tune
SPT
PV
B – Process response during auto-tune
t
PV
1/4 wave
damping
Controlling to Set Point
Auto-tune complete
SPT
>10% span
E rr or
Desc ir p it on
E rr or
esc ir p it on
D
1
d du nir g auto t- une
elia
PV f
7
alu ted out
A res tlu ant P, I or D v ula e was c cla
f range
o
2
Auto t- une has it med out du nir g an auto t- une
ts ep
8
V il m ti exceeded '( Sta tr u 'p auto t- une)
P
3
Process too n sio y to auto t- une
9
to con gif ura oit n mode
r pu nit
ello
on rt
C
4
Process too fa ts to auto t- une
10
uto t- une term ni ated by user
A
5
ols w to auto t- une (max 12 hours
Process too
cy elc s .)
-fla
between h
11
n du nir g
oitc
rid e
the wrong
PV si chan nig g ni
ep te ts
ts
6
PV de aiv ted rf om set p nio t by >25% eng.
pan du nir g rf equency response te ts
s
Fig 2.7a Typical Start-up Auto-tune Cycles
Table 2.1 Auto-tune Error Codes
Note. The time taken to complete auto-tune depends upon the system response time.
Notes For Special Cases.
Cascade Control – the slave loop must be tuned before the master loop. The slave must be
placed into local set point mode (cascade disabled) and the slave set point adjusted to the
required value prior to tuning.
Time Proportioning – the cycle time must be set prior to running an auto-tune. The cycle time is
not changed by the auto-tune.
2.7.2
'At Set Point' Auto-tune
If the process variable is within 10% of the set point, 'at set point' tuning is carried out.
•
'At set point' tuning – manipulates the control output to produce a controlled oscillation of the
process.
•
A step change of ±10% of the starting output value is applied initially. This is adjusted to give an
amplitude of oscillation 3 times the noise level.
•
Once the amplitude and period of oscillation are consistent (minimum 2 cycles, maximum 4
cycles) PID parameters are calculated.
•
If no errors exist the controller enters auto mode and begins to control the process using the new
PID parameters.
•
If an error occurs during the auto-tune, the controller reverts to manual mode with the control
output set to the default output value. An error message is displayed in the operator level –
see Table 2.1.
t
SPT
PV
Auto-tune
complete
Controlling to
Set Point
B – Process response during auto-tune
+2%
– 2%
t
PV
A – Stable process before auto-tune
SPT
< ±10 span
12 hours max.
Fig 2.7b Typical ‘At Set Point’ Auto-tune Cycles
Accessing the Auto-tune Facility
From any operating frame, press and hold the
key
until the 'COdE' frame is displayed.
Set the correct auto-tune password.
Auto-tune Enable
Select the type of auto-tune required.
Single Loop Templates
Cascade Templates
OFF –
Off
SLV.A –
Slave type A
A –
Type A
SLV.b –
Slave type B
b –
Type B
MSt.A –
Master type A
MSt.b –
Master type B
Auto-tune is started automatically when the
key is
pressed. Auto-tune can be stopped at any time by
pressing the
key.
Note. Profile program – If a profile is running, the
auto-tune feature cannot be started. When the
key
is pressed, the display reverts to 'OFF'.
Note. Slave control loops only – place the slave
into local set point mode and adjust the set point to the
required value prior to autotuning.
Note. P + I control only – set the derivative term
to 'OFF' in the Tuning Level – see Section 4.2.
Return to the Operating Level.
2
OPERATOR LEVEL…
Set point
PV
x1
x2
x2
x1
1
4
=
Type A – 1/4 wave damping
Type B – Minimum Overshoot
Set point
PV
Fig. 2.8 Autotune Types
Control Efficiency Monitor
Note. With cascade control, the Control Efficiency Monitor is applicable only to the master
controller.
The Control Efficiency Monitor can be used either to compare the relative performance with different
tuning parameters, or when fine tuning the PID settings, to give optimum control.
When the set point is changed, auto mode is selected or following a power failure, input failure or a
large load disturbance, the control monitor performs a series of measurements to indicate the
effectiveness of the current control parameters.
General guidelines are shown in Table 2.2.
Action
•
Decrease proportional band
•
Decrease integral time
•
Increase derivative time
•
Increase proportional band
•
Increase derivative time
•
Increase proportional band
•
Increase integral time
•
Increase proportional band
•
Decrease integral time
If large overshoot and
oscillatory then:
•
Increase proportional band
•
Increase integral time
•
Increase derivative time
If slow approach and
overdamped then:
•
Decrease proportional band
•
Decrease integral time
Ideal
Setting
Fast
Small
Small
Short
Small
Parameter
Rate of
Approach
Overshoot
Decay Ratio
Settling Time
Error Integral
Actual
Setting
Too slow
Too large
Too large
(Oscill-
atory)
Too long
Too large
Effect on Response
Table 2.2 Control Efficiency Monitor Settings
Control Efficiency Monitor
2.8.1
Manual Tuning
The Control Efficiency Monitor may be used for manually tuning the PID parameters. The following
method describes how to tune the controller for 1/4 wave damping:
a)
Set the integral and derivative action times to OFF.
b)
Set the proportional band (PB) to a low setting.
c)
Apply a small set point change.
d)
Use the Control Efficiency Monitor to note the decay ratio.
e)
If the decay ratio > 0.25, increase the Proportional Band until decay ratio = 0.25
If the decay ratio < 0.25, decrease the Proportional Band until decay ratio = 0.25
f)
Leave the proportional band at the setting which gives 0.25 decay ratio and, using the Control
Efficiency Monitor, note the period between peaks.
g)
Calculate and set the following parameters:
Integral action time = Period/1.5
Derivative action time = Period/6
Note. The manual tuning facility must not be used with boundless motorized valve control, as
an Integral Action Time is required for these applications.
2
OPERATOR LEVEL…
Set Point
x1
x2
y1
y2
95%
5%
tperiod
PV
Start of
Calculation
t
+2%
–2%
tsettle
tapproach
Fig. 2.9 Control Efficiency Monitor Parameters
Using the Control Efficiency Monitor
Press and hold the lower
and
keys for 2 seconds.
Note.
If the front panel keys are not operated for 60 seconds while any
Control Efficiency Monitor frame is being displayed, the instrument
reverts to the first operating frame.
Rate of Approach to Set Point
The rate of change of the process variable between 5 and 95% of the
step change (Y2), measured in engineering units per minute.
Rate of approach =
Y1
tapproach
Overshoot
The maximum error, expressed as a percentage of the set point.
Overshoot =
X1
Set Point x100
Decay Ratio
The ratio of the amplitude of the first and second overshoots.
Ratio = X2
X1
Period
The time (in seconds) between the first two peaks (tperiod).
Settling Time
The time taken (in minutes) for the process variable to settle within
±2% of the set point value (tsettle).
Error Integral
The integral of the error value until the process variable settles to
within ±2% of the set point value in 'engineering-unit hours'.
Error integral = |PV – SP|dt
0
tsettle
Return to the first operating frame.
+
10.1
rAtE
10
OVEr
0.25
rAtO
35
Prd
0.3
SEtL
2.1
IAE
351.5
350.0
360.0
361.5
70
…2
OPERATOR LEVEL
To access the Profile operating and configuration modes (Levels P, r and t ) the correct password must be entered
in the security code frame.
Fig. 3.1 Set Up Mode – Overview
LEVt
P.PrG
LEVr
LEVP
Pr.St
360.0
361.5
70
360.0
361.5
70
50
COdE
OFF
AtNE
LEV1
OPEr
LEVP
LEVr
Pr.St
P.CtL
LEV1
OPEr
Profile States
Program Select
Run/Hold
Reset Profile
Skip Segment
Profile Control Level
Time Units
Program select source
Run/hold sources
Skip forwards/backwards source
Reset source
End of profile reset source
Soak time increment/decrement
source
Profile Program Level
Program Begin/End
Segment Start/End Value
Soak time
Ramp Rate
Guaranteed Ramp/Soak
Time Events
Program Repeats
Program Source
Press
and hold
Invalid
password
LEV.t
P.PrG
LEV2
tUNE
Valid Set Up or Configuration Password
Valid Profile Configuration Password
Valid Profile
Operator Password
P.CtL
200.3
1.HP1
Alarm Acknowledgement –
see Section 2.6
360.0
361.5
70
360.0
361.5
70
Pr.St
LEVP
1
PrG
P.01
Frame number
P.xx – Level P
r.xx – Level r etc.
Parameter
Parameter
adjustment
P.00
Default
value
360.0
361.5
70
Fig. 3.2 – Scroll Display Overview
Fig 3.3 Ramp Types
3.2
Introduction to Ramp/Soak Profile Control
Information.
• 20 programs.
• Digital State program selection – allows digital inputs to select program to be run.
• 99 programmable segments – can be shared between programs
• Programmable time units – can be programmed in hours or minutes.
• Programmable Ramps – can be programmed as rates or in time units.
• Program repeat – 0 to 99 times or continuously.
• Program holdback hysteresis
– separate settings for ramping segments and soak segments.
– can be applied above, below or above and below the set point.
• 6 types of ramp/soak generated events – segment active event, program active event, end of program
event, holdback event, hold active event and time events.
• 6 ramp/soak commands – can be selected from the front panel or via digital signals to run/hold
programs, reset programs, skip forward to next segment, skip backwards to beginning of segment,
increase soak time or decrease soak time (refer to Fig. 3.8 for ramp/soak adjust example).
• 4 time event states – common to each segment
• Self-seeking set point function – avoids unnecessary delays when a program is started – see Fig. 3.5.
• Retort function – ensures safe operation under fault conditions – see Fig. 3.6.
• Power recovery function – determines ramp/soak profile restart position.
• End of Profile State – latched ‘ON’ until reset
The Ramp/Soak facility is a set point profile generator which can be used with any type of control process for more
complex control. A Profile Program is made up of Ramps (the set point is increased or decreased at a linear rate
until it reaches the desired value) and Soaks (the set point is maintained at a fixed value for a set time duration).
3.2.1
Ramp Types – Fig. 3.3
The profile set point can be configured to increment in one of two ways: for a fixed period of time or for a number
of engineering units per hour.
Seg. 1
Start
value
End
value
Start
value
End
value
Start
value
End
value
Seg. 2
Seg. 3
Time
Strt
ENd
tIME
Time
Time
Seg. 1
Start
value
End
value
Start
value
End
value
Start
value
End
value
Seg. 2
Seg. 3
Strt
ENd
rAtE
Ramp
Rate
Ramp
Rate
A – Time Units
B – Rate of Change
If the process variable deviates from the set point by more than the hysteresis value, the program status is set to
‘HOLD’ and Guaranteed ramp/soak is applied automatically. Each program has two associated hysteresis values:
HYS.r
–
applied to ramping segments, and
HYS.S
–
applied to soak segments.
The hysteresis value can be set within the limits ‘0’ to ‘9999’ where a setting of ‘0’ implies that no deviation from
the set point value can be tolerated.
Hysteresis can be applied in one of four ways, with individual settings for each segment:
OFF
–
hysteresis not applied, ramp/soak not guaranteed.
HI
–
hysteresis applied above set point ( Holdback (‘HOLD’) set if PV > [SP + Hysteresis]).
LO
–
hysteresis applied below set point ( ‘HOLD’ set if PV < [SP – Hysteresis]).
HI.LO
–
hysteresis applied above and below set point
( ‘HOLD’ set if PV > [SP + Hysteresis] or PV < [SP – Hysteresis]).
Set
Point
Time (Hours or Minutes)
Process
Seg. 1
Seg. 2
Seg. 4
Seg. 5
End of Profile (revert
to Local Set Point or
repeat of profile)
Set Point (Eng. Units)
Adjustable Holdback Hysteresis
1. for Ramp segments
2. for Soak segments
Adjustable ramp rates
Skip Forward
Manual
Pause
Holdback Active
outside hysteresis
limits
Hysteresis applied Hi-Lo
(above and below the set point)
Hysteresis applied Hi
(above the set point)
Start
Seg. 3
Note. Ramping segments can have a different hysteresis to soak segments.
Fig 3.4 Typical 6-segment Ramp/Soak Profile
3.2.3
Power Recovery Function
The Power Recovery function allows pre-selection of the restart position within a ramp/soak profile when power is
restored after a failure.
With options A, b or C, if power is restored before the Power Down Time expires, the ramp/soak profile continues
from the point at which power failed. If power is restored after the Power Down Time has expired, the profile resumes
from one of the following user-selected points: start of the current program; start of the current segment or from the
profile position at the time of failure. In all three cases the controller restarts in HOLD mode.
With option d, the profile continues in run mode from the position on the profile that would have been reached had
the power failure not occurred.
Self-seeking Set Point – Fig. 3.5
The Self-seeking Set Point function reduces the delay between the end of a program and the beginning of the next
program. The process variable value is used as the program start point and the set point steps up to the process
variable value. This has the effect of changing the overall segment time and maintains a constant ramp rate.
Set
Point
Process
Variable
Seg. 1
Seg. 2
Seg. 3
Current Process Variable
inserted as Program Start Level
Seg. 1
Seg. 2 Seg. 3
Seg. 1
Seg.
2
Seg. 3
Program
Status
Current Process
Variable Inserted as
Program Start Level
Run
Stop
Run
Stop
Run
Start
Start
Start
Stop
Fig 3.5 Self-seeking Set Point
3.2.5
Retort Function – Fig. 3.6
The Retort function ensures safe operation of retort vessels under fault conditions. If the heat source fails during
a soak segment, the process variable will inevitably fall. When the process variable falls below the holdback
hysteresis value the program is put on HOLD (as for normal operation). The set point then follows the process
variable as it continues to fall (Retort Hold).
Set Point = Process Variable + Hysteresis value
Upon recovery of the heat source, the process is controlled at the new set point value. When the process variable
reaches the set point it is then ramped back to the initial soak value at the rate of the previous ramp (Retort Ramp).
When the soak level is reached the program is released from its hold state and the segment is either completed
or repeated from the beginning, depending on the retort mode selected.
The retort mode is selected in the Ramp/Soak Profile Page.
Note. For the retort function to operate, either LO or HI-LO hysteresis must be applied to the soak
segments.
Process Variable
Seg. 1
Seg. 2
Set Point
Program on Hold
Hysteresis applied to
Soak segment
Recovery of heat source
Failure of heat source
1
2
3
4
1
2
3
4
When the process variable reaches the
set point, the set point is ramped back to
the soak level at the rate of the previous
ramp.
Upon reaching the soak level, 'HOLD' is
released and the segment is completed
or repeated.
The program is put on HOLD when the
process variable falls below the holdback
hysteresis
The setpoint follows the process variable
as it continues to fall. (SP = PV +
hysteresis). The set point 'tracks the lowest
value of the process variable.
Fig 3.6 Retort Function
Time Events – Fig. 3.7
Each state generates a source (‘tEV.1’ to ‘‘tEV.4’) which can be assigned to relays, digital outputs, logic
equations etc. in the same way as any other digital signal.
Time event states are provided in addition to program and segment events states and do not affect their operation.
Each segment has an associated ‘EV.Nt’ setting which is used to control the Time-event states.
Temperature
Time
Vent
Period
Air (event 3)
Raise to
Cook
Temp
Cook Period
Cook
Time
Ext
Cool
Period
End of
Cycle
Purge and Vent (event 1)
All events switched off when
program complete
12--
EV.Nt
-2--
EV.Nt
-2-4
EV.Nt
-2--
EV.Nt
--34
EV.Nt
Water (event 4)
Steam (event 2)
Fig 3.7 Time Events
3.2.7
End of Profile State
The end of profile state is a digital source which can be assigned in the same manner as any other digital signal.
The state is set automatically when the program is complete and remains set until a reset signal is received. The
state can be configured to reset via a digital source or to reset automatically after two seconds – see Section 3.4/
Profile Control/ End of Profile Reset Source.
Current Segment Time Adjustment – Fig. 3.8 & 3.9
The Time Adjust function allows the time of a segment to be extended or reduced by a value preset in the ‘t.Adj’
frame – see Ramp/Soak Profile Control Page. The segment time can be adjusted repeatedly (in preset
incements) while the segment is running, either from the controller faceplate or by a digital signal (assigned in the
‘Inc.S’ or ‘dEc.S’ frames).
Note. Any changes made to the segment time using this function are not saved in the program memory.
At the end of the program, all segment times are reset to their original values.
Fig. 3.8a Time Adjustment on a Soak Segment
x3
Initial 40 minutes Ramp
Time. Lower display
shows time remaining
Ramp Time extended by
10 minutes to 50 minutes.
30 minutes remaining.
Ramp Time extended
a further 10 minutes
to 60 minutes. 40
minutes remaining
Ramp Time reduced by
30 minutes to 30 minutes,
10 minutes less than the
initial Ramp Time. 10
minutes remaining.
275.0
275.0
20.0
30.0
40.0
10.0
0
40
20
0
50
20
0
60
20
0
30
20
x3
Initial 60 minutes Soak
Time. Lower display
shows time remaining
Soak Time extended by
5 minutes to 65 minutes.
35 minutes remaining
Soak Time extended a
further 5 minutes to 70
minutes. 40 minutes
remaining
Soak Time reduced by
15 minutes to 55 minutes,
5 minutes less than the
initial Soak Time
275.0
275.0
30.0
35.0
40.0
25.0
0
30
60
0
30
65
0
30
70
0
30 55
Fig. 3.8b Time Adjustment on a Ramp Segment
E or S
P.02
YES
•2
•2
SKPN
•1
P.00
P.00...P.04
3
PROFILES…
3.3
Profile States
Level P – Profile States
Program Select
Select the program to be run
Note. This frame is only displayed if no other program is running.
[1 to 9, A to L]
Run/Hold Action
[xxxx = current profile status: rUN – running, StOP – stopped, ENd – end,
O.HLd – operator hold, _.HLd – manual hold, H.Hld – holdback hold]
rUN
– Starts the selected program.
HOLd
– Activates the Operator Hold.
Note. If a digital input assigned to the run/hold function has been
used to run a program, the user is prevented from activating the operator
hold.
Profile Reset
Select YES to restart the profile at the beginning of the program.
YES – restart the profile
NO – do not restart the profile
Note. To end a program, select HOLd at the Profile Status frame (see
above) and then select YES at this frame. The local set point value takes
the value of the first level of the selected program and the profile status
reverts to 'StOP'.
Skip Segment
The current segment number (or NN) is shown in the upper display.
SKP.F +
Skip Forward – abandon current segment and start the
next segment.
SKP.N
Do Not Skip – maintain control using current segment.
SKP.b +
Skip Back – return to beginning of current segment.
Return to top of Page
•1
Only displayed if the current profile status is Stopped.
•2
Not displayed if the current profile state is Stopped or End.
Ramp/Soak Profile Control
Level r – Profile Control
Program Time Units
Select the time units required
hrS – Hours
MINS – Minutes
The time base selected applies to all segments.
Select Ramp Type
Select the ramp type required
tIME – Ramp time
rAtE – Ramp rate
The ramp type selected applies to all segments.
Next Program Select Source
See Rear Fold-out/Table D –
Digital Sources
Only programs which have been set up in the profile program level, level
t, can be selected.
Program Run/Hold Source
The run/hold source is level triggered i.e. the active logic state must be
maintained to select the alternative function.
See Rear Fold-out/Table D –
Digital Sources
Note. If a program is run using Program Run/Hold Source, 'Operator
Hold' is disabled until the Program Run/Hold Source has been de-activated.
The Program Hold Source and front panel switches have no effect.
Program Run Source
The run source is leading edge triggered i.e. the active logic state can be
removed after the function is selected.
See Rear Fold-out/Table D,
Digital Sources
Continued…
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
Reset End of Profile State
Reset Program
Skip Backward
Skip Forward
•1
•1
•1
•1
•1
3
PROFILES…
Program Hold Source
The hold source is leading edge triggered.
See Rear Fold-out/Table D,
Digital Sources.
The program is restarted using the Program Run Source or the front panel
keys.
Segment Skip Forward Source
Select the source required to skip to the next segment.
See Rear Fold-out/Table D,
Digital Sources.
Note. If the segment running is the last segment of the program, the
program is stopped. The skip source is leading edge triggered.
Segment Skip Backward Source
Select the source required to skip back to the beginning of the ramp/soak
segment running. The skip source is leading edge triggered.
See Rear Fold-out/Table D,
Digital Sources.
Program Reset Source
Select the source required to reset a running program. The reset source
is leading edge triggered.
See Rear Fold-out/Table D,
Digital Sources.
Note. If the program is running normally and is reset, the program
returns to the beginning of the first segment and continues to run. If the
program is on hold and is reset, the program returns to the beginning of
the first segment and stops. No action is taken if a program has already
finished.
End of Profile Reset Source
The end of profile state is set automatically when the program is
complete. A digital source can be activated to cause the end of profile
state to be reset.
Select the source required to reset the end of profile state.
See Rear Fold-out/Table D,
Digital Sources.
Note. If ‘NONE’ is selected, the end of profile output is reset after 2
seconds.
Continued…
…3.4
Ramp/Soak Profile Control
r.06...r.10
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
Increment Segment Time
Decrement Segment Time
NO
PG.SL
r.16
Segment Time Increment Source (Current Segment)
The time of the current segment can be increased (by an amount set in the
Segment Time Adjust frame) each time the source is activated. (ie. the
source is leading edge triggered).
See Rear Fold-out/Table D,
Digital Sources.
Segment Time Decrement Source (Current Segment)
The time of the current segment can be decreased (by an amount set in
the Segment Time Adjust frame) each time the source is activated. (ie. the
source is leading edge triggered).
See Rear Fold-out/Table D,
Digital Sources.
Segment Time Adjust Value (Current Segment)
The value set is added to or subtracted from the remaining time of a
running segment via a digital signal or from front panel keys, when in the
Time Remaining in Current Segment frame of the Operating Page.
[0.1 to 100.0 or OFF]
The time units are set in the Time Units frame. If OFF is selected, this
function is disabled.
Front Panel Run/Hold Enable
YES –
Enabled
NO
–
Disabled
Front Panel Stop Key Enable
YES –
Enabled
NO
–
Disabled
Front Panel Program Select Enable
YES –
Operator level program select enabled
NO
–
Operator level program select disabled
Continued…
…3
PROFILES
r.11...r.16
…3.4
Ramp/Soak Profile Control
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
Front Panel Segment Skip Enable
Fd.bK
–
Operator level segment skip forwards & backwards enabled
bK
–
Operator level segment skip backwards enabled
Fd
–
Operator level segment skip forwards enabled
NO
–
Operator level segment skip disabled
Front Panel Segment Time Adjustment Enable
UP.dN –
Operator level time increment and decrement enabled
dN
–
Operator level time decrement enabled
UP
–
Operator level time increment enabled
NO
–
Operator level time adjust disabled
Power-down Recovery Option
Select the profile restart position when power is restored after a failure and
the Power Down Time Period (see below) has expired. See Section 3.2.3.
A – Start of the current program, profile set to operator hold mode
b – start of the current segment, profile set to operator hold mode
C – profile position unchanged, profile set to operator hold mode
d – calculated position in profile had the power not failed
Note. Option d does not work with segments of more than 24 hours
duration or if the power down time is greater than 24 hours. When power
is restored, the profile is set to operator hold mode and the profile position
is unchanged.
Power-down Time Period (Power-down recovery options A, b & C)
Set the time period during which, if power is restored, the profile continues
from the point at which power failed. If the Power-down Time is exceeded
the Power-down Recovery Option, selected above, is invoked.
[0.0 to 99.9 minutes]
Self-Seeking Set Point
YES
–
Enable self-seeking set point
NO
–
Disable self-seeking set point
When enabled, the controller uses the current process variable value as
the starting point of the first profile segment – see Section 3.2.4.
Retort Function
See Section 3.2.5
OFF
–
Disable retort function
A
–
Complete soak segment
b
–
Repeat soak segment
Return to the top of the Profile Control Page.
3
PROFILES…
…3.4
Ramp/Soak Profile Control
•1
Not displayed if power down recovery option d is selected.
0.0
P.PEr
r.20
LEVr
P.CtL
A
P.rEC
r.19
NO
t.Ad.E
r.18
NO
SKP.E
r.17
OFF
rEtO
r.22
NO
SSSP
r.21
•1
Level t – Profile Program.
Select Program
Select the program to be configured
[1 to 9, A to L excluding I]
Program Begin
Select the program start segment
[1 to 99 or OFF]
Setting this parameter to OFF, prevents the program being selected.
Note. Program 1 cannot be switched off.
Program End
Select the program end segment
[1 to 99]
Note. If the program end segment is less than the program start
segment, the display reverts to the Program Begin frame.
Select Segment
Select the segment to be programmed
[Valid segments of selected program or NONE]
When all segments have been programmed, select NONE to advance to
Repeat Program frame.
Continued…
3.5
Ramp/Soak Profile Program
…3
PROFILES
t.00...t.04
Segment Start Value
The segment start value can only be set if it is the first segment of a program.
[–999 to 9999 in engineering units]
Note. A Ramp has different start and end set point values. A Soak has
the same start and end set point values. Adjacent segments of different
Ramp or Soak programs MUST have the same start and end values, unless
an intermediate ‘spacer’ segment is used.
The start value of a segment can only be adjusted if the segment is the first
of the selected program.
Segment End Value
[–999 to 9999 in engineering units]
If segment start/end values are the same or the ramp type is set to 'tIME',
advance to the Segment Time frame. If segment start/end values are
different and the ramp type is set to 'rAtE', advance to the Ramp Rate
frame.
Segment Time
[0 to 999.9]
The time units (hours or minutes) are configured in Ramp/Soak Time Units
frame, Profile Control Page.
Ramp Rate
[0.001 to 9999 engineering units per time period]
The time period (hours or minutes) is set in the Ramp/Soak Time Units
frame, Profile Control Page.
Example – If a ramp of 10°F at 2° every minute is required, the ramp rate
value entered is 2.0 (in the minutes time base).
Note. If the Program Time Units parameter is set to minutes, the
engineering units value is displayed to an extra decimal place.
Guaranteed Ramp/Soak Hysteresis
HI.LO – hysteresis applied above and below set point
(‘H.HLD’ set if PV > [SP + Hysteresis] or
PV < [SP + Hysteresis])
LO
– hysteresis applied below set point
(‘H.HLD’ set if PV < [SP – Hysteresis])
HI
– hysteresis applied above set point
(‘H.HLD’ set if PV > [SP + Hysteresis])
OFF
– hysteresis not applied, ramp/soak not guaranteed.
Continued…
3
PROFILES…
…3.5
Ramp/Soak Profile Program
0
rAtE
t.07
0.0
tIME
t.07
0
ENd
t.06
0
Strt
t.05
OFF
GUAr
t.08
•1
•2
•1
Only displayed if segment start and end values are the same, or the Ramp Type is set to 'tIME'.
•2
Only displayed if segment start and end values are different and the Ramp Type is set to 'rAtE'.
Ramp/Soak Profile Program
Time Events
Up to four time-events can be assigned to the segment currently being
programmed – see Fig. 3.7on page 29.
Press the
key to turn event 1 ON.
Press the
key to turn event 1 OFF.
Press the
key to advance to the next event.
Example. ‘12-4’ indicates time events 1, 2, and 4 are active during this
segment and time event 3 is inactive
Repeat Program Profile
[0 to 99 or INFN]
If 'INFN' (infinity) is selected, the program is repeated until stopped by the
operator.
Guaranteed Ramp Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Guaranteed Soak Hysteresis
[0.001 and 9999 in engineering units or '0' if no deviation from the profile
is allowed]
Program Source
The program source is leading edge triggered i.e. the active logic state
can be removed after the function is selected.
See Rear Fold-out/Table D,
Digital Sources.
Return to Select Program frame.
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
…3
PROFILES
SET UP MODE
4.1
Introduction
To access the Set Up mode (Levels 2 to 5) the correct password must be entered in the security code frame.
Fig. 4.1 Set Up Mode – Overview
LEV2
Tuning
Cycle time, output 1 & 2
On/off hysteresis values
Proportional bands 1 to 4
Integral action times 1 to 4
Derivative action times 1 & 2
Manual reset value
Feedforward gain and bias
Control deadband
Heat Cool Output 1 & 2 Start
LEV3
Set Points
Local set point values 1 to 4
Slave set point value
Remote set point ratio/bias
Cascade set point ratio/bias
Ramp rate
LEV4
Alarm Trip Points
Alarm 1 to 8 trip points
LEV5
Motorized Valve Set Up
With feedback:
Feedback ratio/bias
Deadband
Regulator travel time
Boundless:
Deadband
Regulator travel time
360.0
361.5
70
360.0
361.5
70
50
COdE
OFF
AtNE
LEV1
OPEr
LEV.t
LEV2
Pr.St
tUNE
LEV1
OPEr
Press
and hold
Invalid
password
LEV.5
VLVE
LEV6
APPL
Valid Configuration Password
Valid Set Up Password
Valid
Profile Configuration
Password
200.3
1.HP1
Alarm Acknowledgement –
see Section 2.7
350.0
351.5
70
350.0
351.5
70
tUNE
LEV.2
1.0
CYC.1
2.01
Frame number
2.xx – Level 2
3.xx – Level 3 etc.
Parameter
Parameter
adjustment
2.00
Default
value
350.0
351.5
70
Fig. 4.2 – Scroll Display Overview
SET UP MODE
4.2
Level 2 – Tune
•1
Only displayed if Relay or Digital output type is selected – see section 5.2, Basic Configuration/ Output Type.
•2
Only displayed if Heat/Cool output type is selected.
•3
Only if On/Off control is selected – see Section 5, Configuration.
•4
Only displayed if Heat/Cool output type is select and the 'CYC.2' parameter is set to 'OnOF'.
tUNE
LEV.2
2.00
0
HYS1
2.03
1.0
CYC.2
2.02
1.0
CYC.1
2.01
•1
•1
•2
0
HYS2
2.04
100%
Output 1
Y1.St
Y2.St
Output 2
PID output
Hys 2
•3
•4
Set Point
Reverse Acting
Control Output
PV
OFF
ON
Hysteresis
Value
Set Point
Direct Acting
Control Output
PV
OFF
ON
Hysteresis
Value
Level 2 – Tune
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Cycle Time Output 1
[1.0 to 300.0 seconds for time proportioning or 'OnOF' for on/off control]
Note. On/off Control is not available on output 1 with heat/cool
control or with cascade templates.
Cycle Time Output 2 (Cool)
[1.0 to 300.0 seconds for time proportioning or 'OnOF' for on/off control]
Note. On/off Control is not available on output 2 with cascade
templates.
Output 1 On/Off Hysteresis Value
[In engineering units]
Output 2 On/Off Hysteresis Value
[0% to (Y1.St – Y2.St)%] – see parameters 2.22 and 2.23 below
Continued on next page
SET UP MODE…
…4.2
Level 2 – Tune
Proportional Band 1
Enter the value for Proportional Band 1.
[0.1% to 999.9%]
'Pb-1' is the default proportional band and is the proportional band for the
master controller if a cascade template is selected – see Section 5.2,
Basic Configuration/ Template Application.
Proportional Band 2, 3 and 4
Enter the value for Proportional Band 2, 3 and/or 4.
[0.1% to 999.9%]
'Pb-2' is the proportional band for the slave controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Integral Action Time 1
[1 to 7200 seconds or 'OFF']
'IAt.1' is the default integral action time and is the integral action time for
the master controller if a cascade template is selected – see Section 5.2,
Basic Configuration/ Template Application.
Integral Action Time 2, 3 and 4
[1 to 7200 seconds or 'OFF']
'IAt.2' is the integral action time for the slave controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Derivative Action Time 1
[0.1 to 999.9 seconds or 'OFF']
'drV.1' is the derivative action time for the master controller if a cascade
template is selected – see Section 5.2, Basic Configuration/ Template
Application.
Continued on next page.
•1
Heat/cool outputs use a common proportional band. The default is 'Pb-1'.
•2
Only displayed if the cascade template or a tune parameter source is selected – see Section 5.2, Basic
Configuration/ Template Application and Section 5.6, Control Configuration/ Tune Parameter Source.
•3
Only displayed if a tune parameter source is selected – see Section 5.6, Control Configuration/ Tune
Parameter Source.
OFF
IAt.4
2.12
OFF
IAt.2
2.10
OFF
IAt.1
2.09
•2
•3
•1
100.0
Pb-2
2.06
100.0
Pb-1
2.05
Pb-4
2.08
100.0
•3
OFF
drV1
2.13
•1
•2
SET UP MODE
Derivative Action Time 2
[0.1 to 999.9 seconds or 'OFF']
The derivative action time for the slave controller if a cascade template is
selected – see Section 5.2, Basic Configuration/ Template Application.
Approach Band 1
[0.1 to 3.0 proportional bands]
This parameter limits when derivative action time 1 is applied. When the
process variable is outside the approach band, derivative action is not applied.
Approach Band 2
[0.1 to 3.0 proportional bands]
This parameter limits when derivative action time 2 is applied to the slave
control loop when a cascade template is selected.
Manual Reset Value 1
The value applied to bring the master control output to the zero error point
under normal load conditions (integral action disabled) or the offset
applied to the control output (integral action enabled).
[0.0 to 100%]
Note. Manual reset is applied whether integral action is selected
ON or OFF.
Manual Reset Value 2
As Manual Reset Value 1, but applied to the slave output.
[0.0 to 100%]
Note. Manual reset is applied whether or not an integral action time
is set.
Continued on next page.
…4.2
Level 2 – Tune
•1
Only displayed if a cascade template is selected – see Section 5.2, Basic Configuration/ Template
Application.
•2
Not displayed if the associated derivative action time is set to OFF.
•3
If manual control is selected and no integral action time is set, the manual reset value is calculated
automatically to give bumpless transfer into auto control.
2.14...2.18
When the process variable is in the deadband, changes to the control
output due to proportional and integral action are suppressed. When a
cascade template is selected, the control deadband is applied to the
master output only.
[In engineering units or 'OFF']
Heat/Cool Output 1 Start
This parameter defines the PID output value above which Output 1 (heat)
becomes active.
[0.0 to 100.0%]
Heat/Cool Output 2 Start
This parameter defines the PID output value below which Output 2 (cool)
becomes active.
[0.0 to ≤ Y1st %] – see Heat/Cool Output 1
Return to top of page
4
SET UP MODE…
2.21...2.23
…4.2
Level 2 – Tune
50.0
Y2.St
2.23
50.0
Y1.St
2.22
OFF
Cbnd
2.21
Deadband
Set Point
LEV2
tUNE
Process Variable
Control Output
•1
•1
•1
Only displayed if a Heat/Cool output type is selected – see Section 5.2, Basic Configuration/ Output Type.
Output 2
PID Output
0%
100%
100%
0%
Y2.St
Y1.St
Output 1
Output 2
PID Output
0%
100%
100%
0%
Y2.St
Y1.St
Output 1
Reverse-direct
or direct-reverse
Reverse-reverse
or direct-direct
Level 3 – Set Points
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Local Set Point Value 1
Set the default local set point value
[Within set point high and low limits, in engineering units – see Level 9]
Note. This set point is modified by the profile and is selected
automatically when a profile program is run.
Local Set Point Values 2 to 4
[Within set point high and low limits, in engineering units – see Level 9]
Cascade Slave Set Point Value
Set the slave set point value.
[Within slave set point high and low limits, in engineering units]
Only adjustable in Manual mode.
Continued…
SEtP
LEV.3
3.00
400
LSP4
3.04
200
LSP2
3.02
500
LSP1
3.01
•1
•1
300
S.SPt
3.05
•2
…4
SET UP MODE
•1
Displayed only if a local set point source is selected – see Section 5.5/ Set Point Configuration/ Local/Remote
Set Point Source.
•2
Only displayed if the cascade template is selected
4.3
Level 3 – Set Points
Cascade Set Point Ratio
In automatic mode, the slave set point value is:
(ratio x master output) + bias.
[0.001 to 9.999]
Cascade Set Point Bias
[In engineering units]
Ramp Rate
[1 to 9999 engineering units per hour, or OFF]
The Ramping Set Point facility can be used to prevent a large disturbance
to the control output when the set point value is changed. The rate set
applies to both the local and the remote set points.
Return to top of page.
…4.3
Level 3 – Set Points
4
SET UP MODE…
3.08...3.10
•1
Displayed only if the Cascade template is selected – see Section 5.2, Basic Configuration/ Template
Application.
1.000
C.rtO
3.08
OFF
r.rtE
3.10
0
C.bIA
3.09
•1
•1
Actual (Ramping) Set Point Value
used by PID Algorithm*
0
100
200
300
1 Hour
Displayed Local Set Point Value
Time
PV
* e.g. Ramp Rate = 200 Increments/Hour
LEV3
SEt.P
Level 4 – Alarm Trip Points
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Alarm 1 Trip
Alarm Number and Type
Trip Value
[In engineering units]
Alarm 2 to Alarm 8 Trip
Alarm Number and Type
See Alarm 1.
Trip Value
[In engineering units]
Return to top of page.
…4
SET UP MODE
•1
Not displayed if alarm type set to 'None' – see Section 5.4, Alarms/ Alarm Type.
•2
Applies to PID output with single or heat/cool outputs.
4.4
Level 4 – Alarm Trip Points
Note. Level 4 is not applicable if all alarm types are set to 'None' – see Section 5.4, Alarms/ Alarm Type.
Display
Desc ir p it on
Display
Desc ir p it on
NONE
None
LP3
Low Process /I P3
HPV
H gi h Proces ,s PV
HO
H gi h Output
•2
LPV
Low Proces ,s PV
LO
Low Output
•2
HLP
H gi h La ct h, PV
Hb1
Maths B ol ck 1 H gi h
LLP
Low La ct h, PV
Lb1
Maths B ol ck 1 Low
Hd
oit n
H gi h De aiv
Hb2
Maths B ol ck 2 H gi h
Ld
oit n
Low De aiv
Lb2
Maths B ol ck 2 Low
HP1
H gi h Process /I P1
Hb3
Maths B ol ck 3 H gi h
LP1
Low Process /I P1
Lb3
Maths B ol ck 3 Low
HP2
H gi h Process /I P2
Hb4
Maths B ol ck 4 H gi h
LP2
Low Process /I P2
Lb4
Maths B ol ck 4 Low
HP3
gi h Process /I P3
H
Required valve position
Deadband
(centered around
required position)
LEV.5
VLVE
5.00...5.04
4
SET UP MODE…
Level 5 – Valve Setup
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Motorized Valve Ratio and Bias
Desired valve position = (Ratio x PID output) + Bias
Motorized Valve Ratio
[0.01 to 10.00]
Motorized Valve Bias
[–100.0 to 100.0%]
Motorized Valve Deadband
[0.0 to 100% of the position feedback span]
Example. If the valve is set to be driven to the 50% open position and the
deadband is set to 4%, the motor stops driving when the position feedback
is 48%. The deadband is between 48% and 52%.
Regulator Travel Time
The time entered is compared with the actual travel time. If the valve is
sticking an error message is generated.
[0 to 5000 seconds, 0 = no check]
Return to top of page.
PID
Control
Terms
PV
SPt
Process
Open relay
Valve
Controller
Position Feedback
Close relay
PID
Output
(PID O/P x V.rAt)
+ V.bIA
4.5.1
Valve Setup (Feedback Types)
4.5
Level 5 – Valve Setup
Note. Level 5 is applicable only for a motorized valve output type – see Section 5.2, Basic Configuration/
Output Type.
Fig. 4.3 Motorized Valve Output with Feedback – Schematic
Valve Setup (Boundless Types) – Fig. 4.4
A ‘boundless’ process controller provides an output that is effectively the time derivative of the required regulator
position, i.e. the COMMANDER 360 signals the regulator, not where to go to (position derivative), but in which
direction to travel and how far to move, by a series of integral action pulses. Thus, the COMMANDER 360 does
not need to know the absolute regulator position and is unaffected when regulator reaches the upper or lower limit,
as determined by the regulator’s limit switches (giving rise to the term ‘boundless’).
When a deviation from set point is introduced the regulator is driven, for a length of time equivalent to the
proportional step. The regulator is then driven by integral action pulses until the deviation is within the deadband
setting.
…4
SET UP MODE
Proportional
Step
Time
Control
Deviation
Raise
Lower
Time
Integral
Action Pulses
Proportional
Step
Proportional
Step
Integral
Action Pulses
+
–
Calculation for Control Pulses (Boundless Control)
The following calculations are shown for guidance when setting deadband, proportional and integral values. They
can be used to check the suitability of boundless control for a particular actuator/application.
Minimum 'ON' time of integral action pulses (for a fixed control deviation).
=
Travel Time x Deadband %
% Proportional Band
(in seconds)
Minimum (approximate) time between integral action pulses (for a fixed control deviation)
=
Integral Action Time x Deadband %
2 x % Control Deviation
(in seconds)
Duration of the proportional step
= 2 x
% Control Deviation
% Proportional Band
x Travel Time in Seconds
% Control Deviation
=
Set Point – Process Variable
Eng Hi – Eng Lo
x 100%
% Deadband
=
Deadband (eng units)
Eng Hi – Eng Lo
x 100%
Fig. 4.4 Boundless Control Action
Valve Setup (Boundless Types)
Level 5 – Valve Setup
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Boundless Deadband
[In engineering units]
Regulator Travel Time
The time taken for the regulator to travel from the fully open to the fully
closed position.
[1 to 5000 seconds]
Return to top of page.
U.LU.E
LEV.5
5.00
0
r.trU.
5.03
5.04
0
d.bnd
Position %
Control Set Point
Deadband
(centered around
Set Point)
LEV.5
VLVE
4
SET UP MODE
Fig. 5.1 Configuration Mode – Summary
5.1
Introduction
To access the Configuration mode (Levels 6 to E) the correct password must be entered in the security code
frame.
Note. When in the configuration mode, all relays and digital outputs are de-
energized and all analog outputs revert to the set minimum current output.
LEV6
Basic Configuration
Template application
Output type
Control action
Mains rejection frequency
LEV7
Analog Inputs 1 to 3
Type
Electrical range
Decimal places
Engineering range
Broken sensor drive
Input filter time constant
LEV9
Set Points
Tracking enable
Set point limits
Local set point sources 1 to 4
LEV8
Alarms 1 to 8
Type
Trip level
Hysteresis band
LEVA
Control Configuration
Power fail recovery action
Output high/low limits
Slew rate + disable
Configured outputs 1 to 3
Manual output selection sources
Auto mode selection source
Tune parameter sources 1 to 4
LEVb
Operator Configuration
Auto/manual key enables
Alarm acknowledge key enable
Operator set point adjust enable
Operator ratio/bias enable
Password settings
Clock settings
LEVC
Output Assignment
Outputs 1 and 2 type
Digital output
Assignment source
Polarity
Analog output
Assignment source
Electrical range
Engineering range
Relay outputs 1 to 4
Assignment source
Polarity
LEVd
Serial Communications
2-/4-wire connection
2400/9600/19200 baud rate
Parity
MODBUS address
LEVE
Calibration
Offset/span adjustment
Motorized valve feedback
APPL
INPt
SEt.P
ALr
CNtL
OPEr
ASSN
SErL
CAL
360.0
361.5
70
360.0
361.5
70
50
COdE
OFF
AtNE
LEV1
OPEr
LEV.t
LEV5
Pr.St
VLVE
LEV1
OPEr
Press
and hold
Invalid
password
LEV6
APPL
LEVE
CAL
Valid Configuration Password
Valid Set Up Password
Valid
Profile Configuration
Password
200.3
1.HP1
Alarm Acknowledgement –
see Section 2.6
Level 6 – Basic Configuration
6.00...6.01
5
CONFIGURATION MODE…
Level 6 – Basic Configuration
Template Application
Templates are provided to make the basic configuration for a particular
application as simple as possible. The appropriate template should be
selected before any other parameters are configured. When a template is
selected, the COMMANDER 360 assumes the preset form for that
template (see Appendix A). The inputs and software blocks are
automatically soft-wired to perform the selected function.
Select the Template required
Note 1. When a template is selected, the following default values
apply: The 'Analog Input Type' of all inputs used by the template defaults
to '2', i.e. 4 to 20mA; The engineering ranges of all inputs used default to
'0.0 to 100.0'. All other inputs are set to 'OFF'.
Note 2. Templates customized using the PC Configurator are
identified by the letter 'U' in the template code – i.e. template '01.SL'
becomes '01.U'.
Continued…
APPL
LEV.6
6.00
1.SL
t.APP
6.01
Display
emplate Desc ir p it on
T
0 S.1 L
ol op w ti h ol c la set p nio t o yln
elg
ni
S
1 C.1 C
ascade w ti h ol c la set p nio t o yln
C
Level 6 – Basic Configuration
Control Output Type
The appropriate relays, digital outputs and analog outputs are assigned to
the control output variables. The other hardware outputs are provisionally
assigned to alarm and retransmission functions but these may be
changed in the output assignment level – see Section 5.8, Output
Assignment Configuration.
Select the Output Type required – see also Fig. 5.2 overleaf and Rear
Fold-out/ Table B.
Continued…
ANLG
O.tYP
6.02
•1
•2
6.02
…5
CONFIGURATION MODE
•1
Analog Input 3 Type defaults to '11' – Resistance Feedback.
Display
utput Type
O
NONE
one
N
ANLG
lo output = ao1)
n ola g output (Con rt
A
rLY
lo output = RLY1)
ale y output (Con rt
R
dIG
lo output = do1)
la output (Con rt
tigi
D
PFb
Moto zir ed v vla e w ti h feedback
(Open = RLY1, C ol se = RLY2)
1
•
bNd
Moto zir ed v vla e w ti hout feedback
Open = RLY1, C ol se = RLY2)
(
H r.C r
,y OP2 = r ale y
ea c/t o lo w ti h OP1 = r ale
H
H r.C d
la output
tigid
,y OP2 =
ea c/t o lo w ti h OP1 = r ale
H
H d.C r
la outpu ,t OP2 = r ale y
tigid
ea c/t o lo w ti h OP1 =
H
H A.C r
ea c/t o lo w ti h OP1 = an ola g, OP2 = r ale y
H
H A.C A
ea c/t o lo w ti h OP1 = an ola g, OP2 = an ola g
H
Level 6 – Basic Configuration
5
CONFIGURATION MODE…
A – Single Output
Control
Algorithm
PV
SPt
Process
Relay Output
Digital Output
Analog Output
ANLG
rLY
dIG
Output Types:
Process
Open relay
Close relay
Valve
Controller
Position Feedback
Control
Algorithm
PV
SPt
B – Motorized Valve Output with Feedback
PFb
Output Type:
C – Motorized Valve Output without Feedback (Boundless)
Process
Open relay
Close relay
Valve
Controller
Control
Algorithm
PV
SPt
bNd
Output Type:
HC.rr
HC.rd
HC.dr
HC.Ar
HC.AA
Output Types:
D – Heat/cool Output
PV
Relay or
Digital or
Analog Output
Process
Heat Output
Cool Output
Relay or
Digital or
Analog Output
Control
Algorithm
SPt
Fig 5.2 Output Type Schematic Diagrams
Level 6 – Basic Configuration
6.03...6.06
Control Action
Control Action (Master Loop)
rEV –
Reverse
dIr –
Direct
Control Action (Slave Loop)
[Options as frame 6.03 above]
Mains Rejection Frequency
Used to filter mains frequency pick-up on external analog input wiring.
[50 or 60Hz]
Return to top of page.
•1
Only displayed if a Cascade template is selected.
•2
Not displayed if Heat/Cool output types selected – see parameter 6.02.
•3
Only displayed if Heat/Cool output types selected – see parameter 6.02.
50
F.rEJ
6.06
rEU
C.ACt
6.03
LEV.6
APPL
rEV
ACt1
6.04
rEV
ACt2
6.05
•1
•1
…5
CONFIGURATION MODE
Single Loop
utput 1
O
•2
rEV
everse
R
•3
dir
ri e tc
D
Hea /t Cool
Output 1 (Hea )t
utput 2 (Coo )l
O
•3
r-d
Reverse
ri e tc
D
•3
r-r
Reverse
everse
R
•3
d-r
D ri e tc
everse
R
•3
d-d
D ri e tc
ri e tc
D
Level 7 – Analog Inputs
7.00...7.03
Level 7 – Analog Inputs
Note. Refer also to Table A, Input Assignments on the rear fold-out.
Analog Input 1 (I/P1) Type & Electrical Range
Temperature Units (I/P1)
C
–
THC/PT100 readings displayed in degrees Centigrade
F
–
THC/PT100 readings displayed in degrees Farenheit
Decimal Places (Engineering Range, I/P1)
0
XXXX
1
XXX.X
2
XX.XX
3
X.XXX
Continued…
5
CONFIGURATION MODE…
INPt
LEV.7
7.00
0
dP.1
7.03
C
UNt.1
7.02
2
tYP.1
7.01
•1
•1
Only displayed if THC or RTD input types are selected
Display
Desc ir p it on
Display
Desc ir p it on
OFF
Not Used
P
PT100 RTD
b
THC Type B
1
0 to 20mA
E
THC Type E
2
4 to 20mA
J
THC Type J
3
0 to 5V
K
THC Type K
4
1 to 5V
L
THC Type L
6
0 to 50mV
N
THC Type N
7
ea zir er
nilt
4 to 20mA square roo
r
THC Type R
8
4 to 20mA power 3/2
S
THC Type S
9
4 to 20mA power 5/2
t
THC Type T
U
u ts om
C
Level 7 – Analog Inputs
7.04...7.07
Engineering High (I/P1)
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Table 5.1 Engineering Limits, THC & RTD Inputs
Engineering Low (I/P1)
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Broken Sensor Drive (I/P1)
NONE
– No action. Actual input values remain valid.
UP
– Input driven to the maximum upscale value (999)
dN
– Input driven to the minimum downscale value (–999)
In the event of a fault being detected on the input, the input is driven in the
direction selected.
Input Filter Time Constant (I/P1)
The input values are averaged over the time set.
[0 to 60 seconds]
Continued…
…5
CONFIGURATION MODE
THC /RTD Type
°C
°F
Min.
Max.
Min. Span
Min.
Max.
Min. Span
Type B
–18
1800
710
0
3272
1278
Type E
–100
900
45
–148
1652
81
Type J
–100
900
50
–148
1652
90
Type K
–100
1300
65
–148
2372
117
Type L
–100
900
50
–148
1652
90
Type N
–200
1300
90
–328
2372
162
Type R & S
–18
1700
320
0
3092
576
Type T
–250
300
60
–418
572
108
Pt100
–200
600
25
–328
1112
45
Level 7 – Analog Inputs
1000
EN2.H
7.11
0
dP.2
7.10
C
UNt.2
7.09
2
tYP.2
7.08
0
EN2.L
7.12
•1
•2
UP
bSd.2
7.13
0
FLt.2
7.14
7.08...7.14
Analog Input Type & Electrical Range (I/P2)
Note. THC inputs can only be used on I/P2 if I/P1 is also set to THC.
Temperature Units (I/P2)
C
–
THC readings displayed in °C
F
–
THC readings displayed in °F
Decimal Places (Engineering Range, I/P2)
0
XXXX
1
XXX.X
2
XX.XX
3
X.XXX
Engineering High (I/P2)
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value when
THC input type is selected – see Table 5.1.
Engineering Low (I/P2)
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC input is selected – see Table 5.1.
Broken Sensor Drive (I/P2)
NONE
– No action. Actual input values remain valid.
UP
– Input driven to the maximum upscale value (999)
dN
– Input driven to the minimum downscale value (–999)
Filter Time Constant (I/P2)
The input values are averaged over the time set.
[0 to 60 seconds]
Continued…
5
CONFIGURATION MODE…
•1
Frames 7.09 to 7.14 are not displayed if Analog Input Type 2 is set to 'OFF'.
•2
Only displayed if THC input type is selected.
Display
Desc ir p it on
Display
Desc ir p it on
OFF
Not Used
t
THC Type 1
b
THC Type B
1
0 to 20mA
E
THC Type E
2
4 to 20mA
J
THC Type J
6
0 to 50mV
K
THC Type K
7
ea zir er
nilt
4 to 20mA square roo
L
THC Type L
8
4 to 20mA power
3/2
N
THC Type N
9
4 to 20mA power
5/2
r
THC Type R
U
Cu ts om
S
HC Type S
T
Level 7 – Analog Inputs
7.15...7.21
Analog Input Type & Electrical Range (I/P3)
Temperature Units
C
–
THC readings displayed in °C
F
–
THC readings displayed in °F
Decimal Places
0 – XXXX; 1 – XXX.X; 2 – XX.XX; 3 – X.XXX
Engineering High
[–999 to 9999]
Note. This parameter defaults to the maximum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Engineering Low
[–999 to 9999]
Note. This parameter defaults to the minimum allowed value when
THC or RTD inputs are selected – see Table 5.1.
Broken Sensor Drive (I/P3)
NONE
– No action. Actual input values remain valid.
UP
– Input driven to the maximum upscale value (999)
dN
– Input driven to the minimum downscale value (–999)
Filter Time Constant (I/P3)
The input values are averaged over the time set.
[0 to 60 seconds]
Return to top of page.
…5
CONFIGURATION MODE
•1
Frames 7.16 to 7.21 are not displayed if Analog Input Type 3 is set to 'OFF'.
•2
Only displayed if THC or RTD input types are selected.
•3
If I/P3 is used as a remote set point input, then the number of decimal places is the same as the number of
decimal places on the process variable input.
1000
EN3.H
7.18
0
dP.3
7.17
C
UNt.3
7.16
2
tYP.3
7.15
0
EN3.L
7.19
•1
•2
UP
bSd.3
7.20
0
FLt.3
7.21
LEV7
INPt
•3
Display
Desc ir p it on
Display
Desc ir p it on
OFF
Not Used
1
0 to 20mA
b
THC Type B
2
4 to 20mA
E
THC Type E
3
0 to 5V
J
THC Type J
4
1 to 5V
K
THC Type K
6
0 to 50mV
L
THC Type L
7
ea zir er
nilt
4 to 20mA square roo
N
THC Type N
8
4 to 20mA power 3/2
r
THC Type R
9
4 to 20mA power 5/2
S
THC Type S
11
ance feedback for
tsis
Re
t
THC Type T
moto zir ed v vla e
P
PT100 RTD
U
u ts om
C
Level 8 – Alarms
Note. Any type of alarm can be used to sound an annunciator (klaxon/horn) which is disabled when the
alarm is acknowledged. This is achieved by assigning the relay to the acknowledge state of the alarm instead
of the actual alarm state.
Trip point
Operator
acknowledges
alarm
Alarm State
(A.x)
Acknowledge State
(ACK.x)
Process
Variable
On
Off
On
Off
rLY.x
ACK.x
RLY.x
Horn
Relay assigment
frame in Level C,
Output Assignment.
Alarm On
Alarm Off
Negative
Trip Value
Positive Trip Value
Low Deviation Alarm
Control Set Point
Hysteresis
Low Deviation
+ve Trip Value
Alarm On
Alarm Off
Hysteresis
Low Deviation
–ve Trip Value
Process
Variable
High Deviation
+ve Trip Value
Hysteresis
Alarm On
Alarm Off
Control Set Point
Alarm On
Alarm Off
Positive
Trip Value
Negative
Trip Value
High Deviation
–ve Trip Value
High Deviation Alarm
Hysteresis
Process Variable
Fig 5.3 Using an Alarm to Sound a Horn
Fig 5.4 High and Low Deviation Alarm Action
Level 8 – Alarms
Trip Point
Alarm On
Alarm Off
Alarm Latched
Alarm acknowledged
by operator
Hysteresis
Process
Variable
Trip Point
Alarm On
Alarm Off
Alarm Latched
Alarm acknowledged
by operator
Hysteresis
Process
Variable
High Latch Alarm Action
Low Latch Alarm Action
Trip Point
Alarm On
Alarm Off
Alarm On
Alarm Off
High Process
Low Process
Hysteresis
Hysteresis
Process
Variable
Fig 5.5 High and Low Process Alarm Action
Fig 5.6 High and Low Latch Alarm Action
Level 8 – Alarms
Level 8 – Alarms
Note. To select this frame from anywhere in this page, press the
key for a few seconds.
Alarm 1 Type
See Figs. 5.3 to 5.6
Alarm 1 Trip
Alarm Number
Trip Value
[In engineering units]
Alarm 1 Hysteresis
Set the hysteresis value (in engineering units) for Alarm 1.
The alarm is activated at the trip level but is only deactivated when the
process variable has moved into the safe region by an amount equal to the
hysteresis value – see Figs. 5.4 to 5.6.
[In engineering units]
Note. Time hysteresis is set using the PC Configurator.
Continued…
8.00...8.03
5
CONFIGURATION MODE…
•1
Applies to the PID output with single or heat/cool output types selected.
Display
Desc ir p it on
Display
Desc ir p it on
NONE
None
LP3
Low Process /I P3
HPV
H gi h Proces ,s PV
HO
H gi h Output
•1
LPV
Low Proces ,s PV
LO
Low Output
•1
HLP
H gi h La ct h, PV
Hb1
Maths B ol ck 1 H gi h
LLP
Low La ct h, PV
Lb1
Maths B ol ck 1 Low
Hd
oit n
H gi h De aiv
Hb2
Maths B ol ck 2 H gi h
Ld
oit n
Low De aiv
Lb2
Maths B ol ck 2 Low
HP1
H gi h Process /I P1
Hb3
Maths B ol ck 3 H gi h
LP1
Low Process /I P1
Lb3
Maths B ol ck 3 Low
HP2
H gi h Process /I P2
Hb4
Maths B ol ck 4 H gi h
LP2
Low Process /I P2
Lb4
Maths B ol ck 4 Low
HP3
gi h Process /I P3
H
Alarm Type 2 (Alarms 2 to 8)
[see Alarm 1 Type]
Alarm 2 to Alarm 8 Trip
Alarm Number and Type
[see Alarm 1 Trip]
Trip Value
[In engineering units]
Alarm 2 to Alarm 8 Hysteresis
Set the hysteresis value (in engineering units) – see Alarm 1 Hysteresis.
[In engineering units]
Return to top of page.
… 5.4
Level 8 – Alarms
…5
CONFIGURATION MODE
8.04...8.24
0
trP.x
8.05
8.06
8.07
NONE
tYPx
8.04
8.10
8.13
8.16
8.19
8.22
8.08
8.11
8.14
8.17
8.20
8.23
0
HYS.x
8.09
8.12
8.15
8.18
8.21
8.24
LEV8
ALr
Level 9 – Set Point Configuration
9.00...9.05
5
CONFIGURATION MODE…
Level 9 – Set Point Configuration
Note. To select this frame from anywhere in this page, press and hold
the
key for a few seconds.
Set Point Tracking Enable
Local Set Point Tracking – the local set point tracks the process variable
when manual mode is selected. Applies to master and slave set points
with cascade templates.
Set Point Limits
The set point limits define the maximum and minimum values to which the
local and/or remote set points can be adjusted.The set point limits do not
apply when in Manual mode with local set point tracking enabled. If the set
point is outside its limits when Automatic mode is selected, the set point
value can only be adjusted towards its limits. Once within the limits they
apply as normal.
Control Set Point (CSPT) or Master Set Point (MSPT) High Limit
[–999 to 9999 in engineering units]
Control Set Point (CSPT) or Master Set Point (MSPT) Low Limit
[–999 to 9999 in engineering units]
Note. Operator level adjustment of the set point can be disabled –
see Section 5.7, Operator Configuration/ Set Point Adjustment Enable.
High Limit for Slave Set Point
[In engineering units]
Low Limit for Slave Set Point
[In engineering units]
Continued…
•1
Only displayed if the Cascade template is selected.
Display
Local Set Point Tracking
OFF
OFF
LOC
N
O
Level 9 – Set Point Configuration
9.08...9.11
…5
CONFIGURATION MODE
Local Set Point Source 1
The source required to select local set point 1 (LSP1) as the current local
set point.
See Rear Fold-out/
Table D – Digital Sources.
Local Set Point Source 2
The source required to select local set point 2 (LSP2) as the current local
set point.
See Rear Fold-out/
Table D – Digital Sources.
Local Set Point Source 3
The source required to select local set point 3 (LSP3) as the current local
set point.
See Rear Fold-out/
Table D – Digital Sources.
Local Set Point Source 4
The source required to select local set point 4 (LSP4) as the current local
set point.
See Rear Fold-out/
Table D – Digital Sources.
Return to top of Set Point Configuration page.
OFF
L.Sr2
9.09
OFF
L.Sr1
9.08
OFF
L.Sr3
OFF
L.Sr4
9.10
9.11
LSP1
LSP2
LSP3
LSP4
•1
•1
•1
•1
SEt.P
LEV9
•2
•2
•2
•2
•1
A digital input becomes active when a volt-free contact is closed or a low TTL signal is applied.
•2
Local Set Point 1 is selected automatically when a profile program is running. No other local set point can be
selected until the profile program is stopped.
Level A – Control Configuration
5
CONFIGURATION MODE…
Level A – Control Configuration
Note. To select this frame from anywhere in this page, press and hold
the
key for a few seconds.
Power Fail Recovery Mode
Select the default power failure mode required following a power
interruption or failure.
Note. For profile power recovery options, refer to Section 3.4/ Profile
Control/ Power Down Recovery Option.
Recovery Time
If power is restored within the recovery time, the controller continues in the
last mode when power fail recovery modes 7 or 8 are selected.
[0 to 9999 seconds]
Continued…
CntL
LEVA
A.00
0
rEC.t
A.02
0
P.rEC
A.01
•1
A.00...A.02
Display
Se itt ng
Display
e itt ng
S
0
La ts mode
5
Auto mode,
tla erm reset
tegr
ni
1
Manu la mode,
ts output
u nis g al
6
Auto mode,
tla erm
tegr
nits
nis g al
u
2
Manu la mode w ti h
0.0% output
7
Power outage
≤
Recovery it me: Auto
mode. Power outage >
Recovery it me: Manu la
ts output
ode al,
m
3
Manu la mode w ti h
100.0% output
8
Power outage
≤
Recovery it me: Auto
mode. Power outage >
Recovery it me: Manu la
ode, con gif ured output
m
4
Manu la mode w ti h
on gif ured output
c
Process Variable Fail Action
Determines controller output when the process variable input fails.
NONE
No action
HOLd
Put into Manual mode
dFLt
Put into Manual mode and select default output
Default Output
This output is used in conjunction with Power Recovery mode 8 and
Process Variable Fail action.
[0 to 100%] (–100% to +100% for heat/cool)
Output High Limit – Single Output Control
Limits the high level of the control output in automatic mode. If the control
output is above this limit when automatic mode is selected, the current
output value becomes the high limit until the value falls below the limit set.
[0.0 to 100.0%]
Output Low Limit – Single Output Control
Limits the low level of the control output in automatic mode. If the control
output is below this limit when automatic mode is selected, the current
output value becomes the low limit until the value rises above the limit set.
[0.0 to 100.0%]
Output 1 (Heat) High Limit – Heat/Cool Control
Limits the high level of control output 1 in automatic mode. If the control
output is above this limit when automatic mode is selected, the current
output value becomes the high limit until the value falls below the limit set.
[0.0 to 100.0%]
Output 2 (Cool) High Limit – Heat/Cool Control
Limits the high level of Control Output 2 in automatic mode, when
'reverse-direct' or 'direct-reverse' control action selected in the Basic
Configuration level. If the control output is above this limit when automatic
mode is selected, the current output value becomes the high limit until the
value falls below the limit set.
[0.0 to –100.0%]
Continued…
…5.6
Level A – Control Configuration
•1
Only displayed if a single output type is selected.
•2
Only displayed if a heat/cool output type is selected.
100
OP.HI
A.05
0
dF.OP
A.04
NONE
PVFA
A.03
•1
0
OP.L0
A.06
•1
100.0
OP1H
A.07
•2
100
OP2H
A.08
•2
OP1
OP2
OP2H
–100%
+100%
0
0
Slew rate disabled
OFF
OP.Sr
A.10
0
OP2L
A.09
•1
OP1
OP2
OP2L
time
Enabled
Enabled
Auto
Manual with
output = C.OP1
•2
+100%
+100%
0
0
…5.6
Level A – Control Configuration
Output 2 (Cool) Low Limit – Heat/Cool Control
Limits the low level of control output 2 in automatic mode, when 'reverse-
reverse' or 'direct-direct' control action is selected in the Basic
Configuration level. If the control output is below this limit when automatic
mode is selected, the current output value becomes the low limit until the
value rises above the limit set.
[0 to 100%]
Output Slew Rate
The maximum rate of change of the control output (or both control outputs
for heat/cool).
[0.01 to 99.99% change per
second or 'OFF']
Note. The default slew rate setting is applied to both increasing and
decreasing output values. The slew rate setting can be applied to either
increasing values only or decreasing values only using the PC
Configurator.
Slew Rate Disable Source
The digital source required to disable slew rate control of the output.
See Rear Fold-out/ Table D –
Digital Sources.
Manual 1 Mode Selection Source
The digital source required to select manual mode and Configured
Output 1.
See Rear Fold-out/ Table D –
Digital Sources.
Continued…
5
CONFIGURATION MODE…
A.09...A.12
•1
Only displayed if reverse-reverse or direct-direct control actions are selected.
•2
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied.
Manual with output = C.OP2
•1
Auto
Manual with output = C.OP3
•1
Auto
…5
CONFIGURATION MODE
…5.6
Level A – Control Configuration
Configured Output 1
The control output value required when manual is selected by manual
mode source 1.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Manual Mode Selection Source 2
The digital source required to select manual mode and Configured
Output 2.
See Rear Fold-out/ Table D –
Digital Sources.
Configured Output 2
The control output value required when manual is selected by manual
mode source 2.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Auto/Manual Selection Source
Used with auto/manual station.
The source required to lock into manual mode with Configured Output 3.
Switching from manual to auto is not possible via the front panel.
See Rear Fold-out/ Table D –
Digital Sources.
Configured Output 3
The control output value required when manual mode is selected by the
auto/manual selection source.
[0 to 100% or LAST (non-heat/cool)]
[–100 to 100% (heat/cool only)]
Continued…
A.13...A.17
•1
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied
Level A – Control Configuration
A.18...A.22
5
CONFIGURATION MODE…
Auto Mode Selection Source
Select the digital source used to activate auto mode.
See Rear Fold-out/ Table D –
Digital Sources.
Tune Parameter Source 1 (Gain Scheduling)
Determine the digital source used to select the proportional 1 and integral
1 terms as the tuning parameters.
See Rear Fold-out/ Table D –
Digital Sources.
Tune Parameter Source 2 (Gain Scheduling)
Determine the digital source used to select the proportional 2 and integral
2 terms as the tuning parameters.
See Rear Fold-out/ Table D –
Digital Sources.
Tune Parameter Source 3 (Gain Scheduling)
Determine the digital source used to select the proportional 3 and integral
3 terms as the tuning parameters..
See Rear Fold-out/ Table D –
Digital Sources.
Tune Parameter Source 4 (Gain Scheduling)
Determine the digital source used to select the proportional 4 and integral
4 terms as the tuning parameters.
See Rear Fold-out/ Table D –
Digital Sources.
Return to top of page.
NONE
A.5rC
A.18
NONE
t4.Sr
A.22
NONE
t3.5r
A.21
NONE
t2.Sr
A.20
NONE
t1.Sr
A.19
•2
•2
•2
Select Pb-1 and INt.1
•2
Manual
•1
Auto
LEVA
CNtL
•1
Select Pb-2 and INt.2
•1
Select Pb-3 and INt.3
•1
Select Pb-4 and INt4
•1
•1
Digital inputs are active when a volt free contact is closed or a low TTL signal is applied.
•2
PB–x and INt.x values are set in Level 2 – see Section 4.2, Tune/Proportional Band x and Integral Action
Time x. This function is not available with Cascade control.
Level B – Operator Configuration
Level B – Operator Configuration
Note. To select this frame from anywhere in this page, press and hold
the
key for a few seconds.
Front Panel Auto/Manual Key Enable
YES –
Enabled
NO
–
Disabled
Local / Cascade Display
YES –
Slave set point displayed in operator level
NO
–
Slave set point not displayed in operator level
Front Panel Alarm Acknowledge Enable
YES –
Enabled
NO
–
Disabled
Operator Level Set Point Adjustment Enable
YES –
Enabled
NO
–
Disabled
Note. Applies to master and slave set points in cascade mode.
Operator Ratio Display
YES –
Ratio setting for Cascade set point displayed in
operator level.
NO
–
Ratio setting for Cascade set point not displayed
in operator level.
Operator Bias Display
YES –
Bias setting for Cascade set point displayed in
operator level.
NO
–
Bias setting for Cascade set point not displayed
in operator level.
Auto-tune Password
Enables access to the auto-tune facility in the operator level.
[0 to 9999 (default 0)]
Continued…
…5
CONFIGURATION MODE
•1
Only displayed if the cascade template is selected.
OPEr
LEVb
b.00
NO
r.d15
NO
b.d15
b.05
b.06
YES
S.AdJ
b.04
YES
FPAK
b.03
YES
FP.AM
b.01
•1
•1
NO
LC.dS
b.02
•1
0
A.PA5
b.07
b.00...b.07
Level B – Operator Configuration
Profile Operator Password
Enables access to the profile states level (level P) and the autotune
facility.
[0 to 9999 (default 0)]
Profile Configuration Password
Enables access to the profile states, profile control and profile program
levels (levels P, r and t) and the autotune facility.
[0 to 9999 (default 0)]
Set Up Password
Enables access to the set up levels (levels 2, 3, 4 and 5) and the autotune
facility.
[0 to 9999 (default 0)]
Configuration Password
Enables access to the configuration levels, set up levels and the autotune
facility.
[0 to 9999 (default 0)]
Day Setting
Use to set the weekday of the on-board clock.
[1 to 7. 1 = Sunday, 7= Saturday]
Hour Setting
Use to set the hour of the on-board clock.
[0 to 23]
Minute Setting
Use to set the minute of the on-board clock.
[0 to 59]
Current Time
Actual on-board clock time.
[Hours : Mins]
Bargraph Increment
Deviation represented by each bargraph element.
[1 to 10% of Engineering Range]
Return to top of page.
Level C – Output Assignment Configuration
Note. The Output Assignment default settings are preconfigured to each template – see Table B, Output
Sources on the rear fold-out.
Level C – Output Assignment
Analog/Digital Output 1 (ao1/do1) Type
Select the output type for Output 1.
ANLG
–
Analog
dIG
–
Digital
Press
to advance to Analog Output 1 Assignment Source.
Press
to advance to Digital Output 1 Assignment Source.
Continued…
C.00, C01
…5
CONFIGURATION MODE
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
Digital Output 1
Digital Output 1 (do1) Assignment Source
Select the source required to activate Digital Output 1
See Rear Fold-out/ Table D – Digital Sources.
Digital Output 1 (do1) Polarity
The output can be set to energize for either an active or inactive digital
signal.
POS –
Output energized when source is active.
NEG –
Output energized when source is inactive.
Continued…
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not applicable if digital output 1 is assigned to a control output.
tYP1
dIG
NONE
dGI.A
C.07
POS
dG1.P
C.08
AN2.A
NONE
•1
•2
C07, C08
Analog Output 1
Analog Output 1 (ao1) Assignment Source
Select the source required to activate Analog Output 1
See Rear Fold-out/ Table C – Analog Sources.
Analog Output 1 (ao1) Electrical High
The maximum current output required for the analog output.
[0.0 to 22.0mA]
Analog Output 1 (ao1) Electrical Low
The minimum current output required for the analog output.
[0.0 to 22.0mA]
Retransmission 1 Engineering High
The engineering range value at which maximum output is required.
[In engineering units]
Retransmission 1 Engineering Low
The engineering range value at which minimum output is required.
[In engineering units]
Continued…
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not applicable if analog output 1 is assigned to a control output.
tYP1
ANLG
NONE
ANI.A
100.0
r1.H
C.02
C.05
0.0
r1.L
C.06
20.0
AN1.H
C.03
4.0
AN1.L
C.04
AN2.A
NONE
•1
•2
•2
Analog Output 2
Analog Output 2 (ao2) Assignment Source
Select the source required to activate Analog Output 2
See Rear Fold-out/ Table C – Analog Sources.
Analog Output 2 (ao2) Electrical High
The maximum current output required for the retransmission range.
[0.0 to 20.0mA]
Analog Output 2 (ao2) Electrical Low
The minimum current output required for the retransmission range.
[0.0 to 20.0mA]
Retransmission 2 Engineering High
The engineering range value at which maximum output is required.
[In engineering units]
Retransmission 2 Engineering Low
The engineering range value at which minimum output is required.
[In engineering units]
Continued…
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not applicable if analog output 2 is assigned to a control output.
Relay Outputs 1 to 4
Relay 1 Assignment Source
Select the source required to activate relay output 1.
See Rear Fold-out/ Table D – Digital Sources.
Relay 1 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
POS –
Relay energized when source is active.
NEG –
Relay energized when source is inactive.
Relay 2 Assignment Source
Select the source required to activate relay output 2
See Rear Fold-out/ Table D – Digital Sources.
Relay 2 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
POS –
Relay energized when source is active.
NEG –
Relay energized when source is inactive.
Relay 3 Assignment Source
Select the source required to activate relay output 3
See Rear Fold-out/ Table D – Digital Sources.
Relay 3 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
POS –
Relay energized when source is active.
NEG –
Relay energized when source is inactive.
Continued…
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not displayed if relay is assigned to a control output signal.
•3
Not applicable if relay is assigned to a control output.
•4
Only displayed if optional relay ouput is fitted.
Relay 4 Assignment Source
Select the source required to activate relay output 4
See Rear Fold-out/ Table D – Digital Sources.
Relay 4 Polarity
The relay can be set to energize for either an active or inactive digital
signal.
POS –
Relay energized when source is active.
NEG –
Relay energized when source is inactive.
Return to top of page.
NONE
rL4.A
C.23
POS
rL4.P
C.24
•1
•2
•3
LEVC
ASSN
•4
•4
•1
If the output is assigned to a control output by the control type, the setting displayed cannot be changed – see
Section 5.2, Basic Configuration/Control Output Type.
•2
Not displayed if relay is assigned to a control output signal.
•3
Not applicable if relay is assigned to a control output.
•4
Only displayed if relay ouput is fitted.
…5.8.4
Relay Outputs 1 to 4
Level D – Serial Communications Configuration
Note. To select this frame from anywhere in this page, press and hold
the
key for a few seconds.
Serial Configuration
0 –
Off
1 –
2-wire connection, 2400 baud rate
2 –
4-wire connection, 2400 baud rate
3 –
4-wire connection, 9600 baud rate
4 –
4-wire connection, 9600 baud rate
5 –
2-wire connection, 19200 baud rate
6 –
4-wire connection, 19200 baud rate
Parity
NONE
–
None
Odd
–
Odd
EVEN
–
Even
MODBUSTM Address
Each slave on a MODBUS link must be assigned a unique address – see
IM/C360–MOD.
[1 to 99]
Return to top of page.
5.9
Level D – Serial Communications Configuration
Note. Level D is only applicable if the serial communications option is fitted.
d.00...d.03
…5
CONFIGURATION MODE
Level E – Calibration
Note. This page enables fine tuning of the inputs to eliminate system errors.
E.00...E.04
Level E – Calibration
Note. To select this frame from anywhere in this page, press the
key for a few seconds.
Analog Input 1 Offset Calibration
Analog Input 1 Value in Engineering Units
Offset [in engineering Units]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
Analog Input 1 Span Calibration
Analog Input 1 Value in Engineering Units
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds the display
reverts to the span value only.
Analog Input 2 Offset Calibration
Analog Input 2 Value in Engineering Units
Offset [In engineering Units]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
Analog Input 2 Span Calibration
Analog Input 2 Value in Engineering Units
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
Continued…
5
CONFIGURATION MODE…
Analog Input 3 Offset Calibration
Analog Input 3 Value in Engineering Units
Offset [In engineering Units]
If the
and
keys are not operated for three seconds the display
reverts to the offset value only.
Analog Input 3 Span Calibration
Analog Input 3 Value in Engineering Units
Span Adjustment
[0.750 to 1.250]
If the
and
keys are not operated for three seconds thedisplay
reverts to the offset value only.
Position Feedback Calibration
Select the calibration required.
NO
–
No Calibration
AUtO –
Auto Calibration
_AN
–
Manual Calibration
Regulator Travel Time
[0 to 5000 seconds]
Ensure that the value entered is compatible with the regulator motor, as
this is used to determine the length of travel of the feedback mechanism.
Motorized Valve Feedback – Fully-closed Position
NO
No action
YES Fully closes the valve automatically and sets the electrical input
to low range value.
Note. Input value flashes when calibration is in progress.
Motorized Valve Feedback – Fully-open Position
NO
No action
YES Fully opens the valve automatically and sets the electrical input
to high range value.
Note. Input value flashes when calibration is in progress.
Continued in Cold Junction Reference Value frame.
…5.10
Level E – Calibration
E.05...E.10
…5
CONFIGURATION MODE
•1
Only displayed if Motorized Valve with feedback output type is selected – see Section 5.2, Basic Configuration.
Level E – Calibration
Position Feedback Electrical Range Low
Set the minimum electrical input value.
[0.0 to 999.9]
For resistance input types, no decimal places are displayed. For all other
input types, 1 decimal place is displayed.
Position Feedback Electrical Range High
Set the maximum electrical input value.
[0.0 to 999.9]
Continued in Cold Junction Reference Value frame.
Cold Junction Reference Value
This value should only be changed if a new CJ sensor is supplied with a CJ
reference value different to 2700.
The resistance (in Ohms) of the CJ sensor at 25°C.
Cold Junction Beta Value
This value should only be changed if a new CJ sensor is supplied with a CJ
Beta value different to 3977.
The beta value of the CJ sensor.
Cold Junction Reading – I/P1 and I/P2
The temperature measured by the cold junction sensor is displayed in °C.
Cold Junction Reading – I/P3
The temperature measured by the cold junction sensor is displayed in °C.
Return to top of Calibration Level.
100.0
Fb.LO
E11
500.0
Fb.HI
E.12
FCAL
MAN
rEF
2700
Fb.HI
500
2700
rEF
E.13
3977
bEtA
E.14
25.2
CJ3
E.16
LEV.E
CAL
O.CAL
NO
FCAL
NO
•1
•1
25.2
CJ1
E.15
•2
•2
5
CONFIGURATION MODE
E.11...E.16
•1
Only displayed if Motorized Valve with feedback output type is selected – see Section 5.2, Basic Configuration.
•2
Only displayed if corresponding input type is set to 'THC'.
EC Directive 89/336/EEC
In order to meet the requirements of the EC
Directive 89/336/EEC for EMC regulations, this
product must not be used in a non-industrial
environment.
End of Life Disposal
This instrument does not contain any substance
that will cause undue harm to the environment.
However, the unit contains a small lithium battery.
This should be removed and disposed of
responsibly
in
accordance
with
local
environmental regulations. The remainder of the
unit can be safely considered as normal waste and
disposed of accordingly.
6.1
Mechanical Installation
6.1.1
Siting – Figs. 6.1 and 6.2
Sensor
Minimum
55°C
Max.
0°C
Min.
IP66/
NEMA4X
(front panel)
IP20
(rear)
0 to 90% RH
+
A – Close to Sensor
Fig. 6.2 Environmental Requirements
Caution. Select a location away
from strong electrical and magnetic
fields. If these cannot be avoided,
particularly in applications where ‘walkie
talkies’
are
used,
connect
using
screened cables within grounded metal
conduit.
A – Within Temperature Limits
B – Within Humidity Limits
C – Within Protection Rating Limits
D – Use Screened Cables
B – At Eye-level Location
C – Avoid Vibration
Fig. 6.1 General Requirements
Mounting – Figs. 6.3 to 6.5
The instrument is designed for panel mounting (Fig. 6.4). Overall dimensions are shown in Fig. 6.3.
Note. For NEMA4X protection, a minimum panel thickness of 2.5mm is recommended.
96
(3.78)
122.5 (4.82)
17.5
(0.69)
Dimensions in mm (in.)
96 (3.78)
Panel
Cut-out
30 (1.18)
92
+0.8
–0.0
(3.622 )
–0.0
+0.03
14 (0.55)
91.8 (3.61)
5.0
(0.2)
92
+0.8
–0.0
(3.622 )
–0.0
+0.03
Fig. 6.3 Overall Dimensions
Mounting – Figs. 6.3 to 6.5
1
2
3
4
3
Cut a hole in the panel
(see Fig. 6.3 for dimensions).
Instruments may be close
stacked to DIN 43835
Insert the instrument
into the panel cut-out
Fit the panel clamps, ensuring that the
lugs are located correctly in their slots
Secure the panel clamp using the retaining screws.
The rubber friction sleeve prevents over-tightening.
Fig. 6.4 Mounting
Mounting – Figs. 6.3 to 6.5
1
2
Turn the jacking screw anticlockwise to pull
the instrument from the case
Release the jacking screw cover
Note. Refitting is the reversal of removal.
Fig. 6.5 Inserting/Removing the Instrument from the Case
Refer to the Template Applications table and Output Sources table on the rear fold-out to determine the
input and output connections to be made.
Warning. Before making any connections, ensure that the power supply, any powered control circuits
and high common mode voltages are switched off.
Note.
•
Always route signal leads and power cables separately, preferably in grounded metal conduit.
•
It is strongly recommended that screened cable is used for signal inputs and relay connections. Connect
the screen to the ground stud – see Fig. 6.6.
Information. Use cable appropriate for the load currents. The terminals accept cables up to 14AWG
(2.5mm2).
…6
INSTALLATION
Analog Output 2
(ao2)
Relay 1 (RLY1)
1
2
3
4
5
6
7
8
9
10
11
12
Live (1A fuse)
Neutral
25
26
27
28
29
30
31
32
34
35
36
33
15
16
17
18
19
20
21
22
23
24
13
14
Relay 2 (RLY2)
Digital Input 3 (di3)
Digital Input Common
Digital Input 4 (di4)
–
+
+
NO/NC
C
NO/NC
C
COM
Rx+
Rx–
Tx+
Tx–
Relay 3 (RLY3)
Relay 4 (RLY4)
RS485
–
+
+
–
+
RTD1
–
+
–
+
RTD2
+
Transmitter PSU
Analog Input 3 (I/P3)
Analog Input 1 (I/P1)
Analog Input 2 (I/P2)
See
Fig. 6.7
Digital Input Common
Digital Input 1 (di1)
Digital Input 2 (di2)
Output/Power
Supply Board
Option Board
Input Board
Terminal blocks
viewed from rear
of case
Digital / Analog Output 1
(ao1 /do1)
6.2.1
Electrical Connections – Figs 6.6 to 6.8
Caution.
The
Power Supply ground
cable
must
be
connected
to
the
Ground Stud.
Fig. 6.6 Electrical Connections – General
Electrical Connections – Figs. 6.6 to 6.8
*
Using internal transmitter power supply
**
Use 100Ω shunt resistor provided with instrument
***
Fit 100kΩ pull-up resistor for correct broken sensor operation with voltage inputs
#
Fit the CJ sensor supplied if I/P1 or I/P2 are THC inputs
##
I/P2 can only be used with THC inputs if I/P1 is also used as a THC input
### Fit the CJ sensor supplied if I/P3 is a THC input
–
+
THC
milliVolts
and volts
RTD –
3rd lead
RTD +
3-lead
RTD
–
+
milliAmps
28
29
30
31
–
+
* milliAmps
2-wire
Transmitter
RTD –
RTD –
RTD +
2-lead RTD
and Resistance
**100Ω
**100Ω
Tx
Milliamps
–
+
**100Ω
–
+
2-wire
Transmitter
**100Ω
–
+
Millivolts
Tx
32
36
CJ Sensor#
(I/P 1)
(I/P 2)
THC##
–
+
Analog
Input 1
Analog
Input 2
–
+
THC
milliVolts
and volts
RTD –
3rd lead
RTD +
3-lead
RTD
–
+
milliAmps
33
34
35
–
+
* milliAmps
2-wire
Transmitter
RTD –
RTD –
RTD +
2-lead RTD
and Resistance
**100Ω
**100Ω
Tx
CJ Sensor###
(I/P 3)
Analog
Input 3
Transmitter
Power
Supply
* milliAmps
***100kΩ
Pull-up Resistor
***100kΩ
Pull-up Resistor
Volt free
Inactive
Active
TTL
Inactive
Active
5V
0V
Fig. 6.7 Electrical Connections – Analog Inputs
Fig. 6.8 Electrical Connections – Digital Inputs
Table B for default relay assigments.
Relay contacts are rated at:
115/230V a.c. at 5A (non-inductive)
250V d.c. 25W max.
6.3.1
Setting the Relay Links – Fig. 6.9
Set the links on the option board (if fitted).
6.4
Digital Output
15V d.c. min. at 20mA
Min. load 750Ω
6.5
Control or Retransmission
Analog Output
Max. load 15V (750Ω at 20mA).
Isolated from analog input, dielectric strength
500V for 1 minute.
6
INSTALLATION…
LK3
LK4
LK3 = Relay 3
LK4 = Relay 4
Normally open
Normally closed
Note. The default setting for the relay links is 'Normally Open' (N/O).
Fig. 6.9 Relay Links
Make connections to each input – see Fig 6.7.
Refer to Table A on the rear fold-out for the
default input assignment settings.
6.7.1
Thermocouple (THC) Inputs
Note. Use the correct compensating cable
between the THC and the terminals – see
Table 6.1.
Automatic Cold Junction Compensation (ACJC) is
incorporated by use of CJ sensors wired across the
input terminals of I/P1 and I/P3 – see Fig. 6.11.
Alternatively, the CJ sensor can be mounted remotely
at the point where the thermocouple cable terminates
into copper cable, e.g. where cables enter an
instrument panel – see Fig. 6.12.
It is possible to use an external fixed cold (reference)
junction, if the instrument is programmed for use with
millivolt inputs and the appropriate thermocouple
linearizer is selected. This is only possible via the PC
Configurator.
…6
INSTALLATION
0%
100%
Motorized
Valve
Drive
(N)
N
L
(L)
Motorized Valve
Drive
Valve
Positioner
Power
Supply
0%
100%
Link
0%
100%
34
33
35
8
9
5
6
–
+
A – Relay Connections
Motorized Valve
Drive
B – Feedback Connections
(V, mA or mV Input Types)
C – Feedback Slidewire
Connection
100Ω
(mA inputs
only)
33
34
35
D – Alternative Feedback
Slidewire Connection
34
33
Motorized Valve
Drive
Link
–
+
28
29
30
Copper
cable
I/P1
Compensating
cable
–
+
33
34
35
I/P3
6.6
Motorized Valve Connections – Fig. 6.10
Note. Relays used to drive the motorized
valve must be set for 'Normally Open' operation –
see Section 6.3.1.
Note. The wire link must be
connected at the motorized valve end,
NOT to the instrument terminals.
Fig. 6.10 Motorized Valve Connections
Fig. 6.11 CJ Sensor – Connections
Fig. 6.12 Remote-mounted CJ Sensor –
Connections
ompensa it ng Cable
C
BS1843
ANSI MC 96.1
DIN 43714
S4937 Pa tr No.30
B
+
–
Case
+
–
Case
+
–
Case
+
–
ase
C
N -i C /r N -i Al
(K)
Brown
B ul e
Red
w
olle
Y
Red
w
olle
Y
Red
Green
Green
Green
W tih e
reen *
G
lisi
N
/lisir
N ci
(N)
Orange
B ul e
Orange
Orange
Red
Orange
—
P ni k
W tih e
ni k *
P
P /t P -t Rh
(R and S)
W tih e
B ul e
Green
B al ck
Red
Green
Red
W tih e
W tih e
Orange
W tih e
range *
O
P -t Rh/P -t Rh
(B)
–
–
–
Grey
W tih e
rey *
G
Cu/Cu-Ni (T)
W tih e
B ul e
B ul e
B ul e
Red
B ul e
Red
Brown
Brown
Brown
W tih e
rown *
B
Fe/Con (J)
w
olle
Y
B ul e
B al ck
W tih e
Red
B al ck
Red
B ul e
B ul e
B al ck
W tih e
al ck *
B
stiu
ric c
safe
ylla
cis
nirt
Case B ul e for ni
*
Fe/Con (L)
–
—
DIN 43710
—
(DIN 43710)
B ul e/
red
B ul e
ul e
B
6.7.2
3-lead Resistance
Thermometer (RTD) Inputs
The three leads must have equal resistance, not
exceeding 50Ω each.
6.7.3
2-lead Resistance
Thermometer (RTD) Inputs
If long leads are necessary it is preferable to use a
3-lead RTD. If the RTD is to be used in a hazardous
area, a 3-lead RTD connected via a suitable Zener
barrier, must be used.
6.8
Output Connections
Make connections as shown in Fig. 6.6.
Refer to Table A on the rear fold-out for the
default output assignment settings.
6.9
Power Supply Connections
Warning.
•
A 1A fuse must be fitted in the live (+ve) supply line.
•
The ground line must be connected to the
ground studs on the terminal block – see
Fig. 6.6.
•
Do not disturb the link between the two ground
studs.
•
The type of power supply required (a.c. or d.c.)
is stated at the time of order and can be
identified from the instrument code number:
C36X/XX0X/STD = 85 to 265V a.c.
C36X/XX1X/STD = 24V d.c.
Table 6.1 Thermocouple Compensating Cable
Single Loop Controller (Template 1)
APPENDIX A – CONTROL TEMPLATES
LSPt
PID
Control Loop
PID O/P
CSPt
PV
Manual Output
OP1
Process Variable Input
Set Point
Ramp
I/P1
Local Set Point
PV–
CSPt
Profile
Program
Single Loop Control provides basic feedback control using three term PID or On/off control. The controller output is calculated from the difference
between the process variable and the control set point. The control set point can be a fixed value entered by the user or a value derived by the profile
control algorithm.
APPENDIX A – CONTROL TEMPLATES
LSPt
MSPt
M.OP x C.rtO + C.bIA
I/P1
I/P2
OP1
Master Process Variable Input
Slave Process Variable Input
Slave Set Point
Slave
PID
Control Loop
MPV
Master
PID
Control Loop
Set Point
Ramp
Manual Output
MOP
SPV
SSPt
Local Set Point
MPV–
MSPt
SPV–
SSPt
Profile
Program
LOC
CAS
A2
Cascade Controller (Template 11)
Cascade Controller. Two PID controllers are used with the first (master) controller providing the set point for the second (slave) controller. The
two controllers are linked internally. The master output can be weighted using the cascade ratio (C.rto) and bias (C.bia) values to create the slave set
point value. When the auto/manual mode is changed (from the front panel or by a digital signal) both the master and slave controllers change mode. In
manual the slave set point can be adjusted by the user and the value is tracked by the master controller to ensure bumpless transfer back into auto. The
slave can also be taken out of cascade mode by selecting local mode using the front panel keys.
APPENDIX B – COMMANDER CONFIGURATION EDITOR
B1
Introduction
Using the COMMANDER Configurator the COMMANDER 360 can be programmed without using any of the front
panel keys.
In addition to the standard settings, the Configurator also gives access to more advanced features not accessible
via the front panel keys. These are summarized below.
For information on using individual features, refer to the on-line help facility.
Note. The instrument must be in Configuration Mode (Level 6 or above) when uploading or downloading
from the PC Configurator.
B2
Analog Input Customization
•
Custom mA, mV, Voltage and Resistance ranges
•
Standard Linearizers can be assigned to electrical inputs (eg. allowing transmitter inputs to have
thermocouple or resistance linearizers to be applied)
•
Programmable fault detection levels (default = 10%)
Standard A tir hme it c
olb c ,k w ti h the
each
Up to 4 operands and 3 operators can be com nib ed ni
.yllait
alu ted sequen
perands b nie g c cla
o
Operator :s
,tc
w s ele
ol,tc
gih h s ele
,ylpitlu
e, m
divid
add, sub rt a ,tc
tc
e aid n s ele
m
Operand :s
gis n sla
la
tigid
any an ola g or
)'0'
or
'1'
have the v ula e
gis n sla
la
tigid
(
Average
la
tigid
it me pe oir d, reset by
tc a elb
gis n la over a s ele
The average v ula e of an an ola g
n la
gis
Maximum detec it on
gis n la
la
tigid
gis n ,la reset by
he ma ix mum v ula e of an an ola g
T
Minimum detec it on
gis n la
la
tigid
gis n ,la reset by
he m ini mum v ula e of an an ola g
T
Rela it ve humid ti y
temperature sensors
alu ted rf om wet and dry b blu
cla
C
Square root
gis n la
he square root v ula e of any an ola g
T
Input mu itl plexer
gis n la
la
tigid
elb s u nis g a
n of one or two an ola g va air
oitc
ele
S
B3
Four Programmable Maths Blocks
One of seven types can be assigned to each maths block:
Elements
p to 15 per equa oit n
U
Operators
p to 7 per equa oit n: OR, AND, NOR, NAND, NOT, EXOR
U
Operands
gis n .la
la
tigid
Up to 8 per equa oit n: any
.sla
gis n
la
tigid
he NOT operator can be used to ni ve tr
T
B4
Six Logic Equations
B5
Process Alarm Customization
•
Time Hysteresis, 0 to 9999 seconds
•
Alarm Disable Source
B6
Two Real Time Alarms
•
Programmable ON days, hours, minutes and duration (00:00 to 23:59)
•
Wildcard (*) to allow operation every x minutes past the hour
Fig. B1 Connecting the COMMANDER PC Configurator
B7
Two Delay Timers
•
Programmable delay and duration (0 to 9999 seconds)
B8
Two Custom Linearizers
•
15 breakpoints per linearizer
•
The source can be any analog signal
B9
Template Customization
Each template can be customized by changing the sources for various functions in the COMMANDER 360. This
allows maths blocks and custom linearizers to be added into the standard template format.
The following sources can be programmed:
•
process variable inputs
•
set point inputs
•
position feedback input
•
input to ratio/bias block
•
ratio inputs
•
bias inputs
•
profiles
B10
Connecting the COMMANDER PC Configurator
APPENDIX B – COMMANDER CONFIGURATION EDITOR
Note. The COMMANDER 360 must be in
Configuration Mode (levels 6 to E) when using the
PC Configurator.
351.5
350.
50
COMMANDER 350
End of Profile Reset Source
F
Front Panel
Program Select Enable
Front Panel
Run/Hold Enable
Front Panel
Segment Skip Enable
Front Panel Segment Time
Adjustment Enable
Front Panel
Stop Key Enable
G
Guaranteed Ramp Hysteresis
Guaranteed Ramp/Soak
Hysteresis
Guaranteed Soak Hysteresis
L
Level P – Profile States
Level r – Profile Control
Level t – Profile Program
N
Next Program Select Source
P
Power-down
Recovery Option
Power-down Time Period
Profile Reset
Program Begin
Program End
Program Hold Source
Program Reset Source
Program Run Source
Program Run/Hold Source
Program Select
Program Source
Program Time Units
R
Ramp Rate
Repeat Program Profile
Retort Function
Run/Hold Action
S
Segment
End Value
Skip Backward Source
Skip Forward Source
Start Value
Segment Time
Adjust Value
(Current Segment)
Decrement Source
(Current Segment)
Increment Source
(Current Segment)
Select Program
Select Ramp Type
Select Segment
Self-Seeking Set Point
Skip Segment
T
Time Events
rAtE
t.07
rPtS
t.10
rEtO
r.22
ACtx
P.02
ENd
t.06
SKP.b
r.08
SKP.F
r.07
Strt
t.05
tIME
t.07
t.ADJ
r.13
dEC.S
r.12
INC.S
r.11
PrGM
t.01
rAMP
r.02
SEGM
t.04
SSSP
r.21
SGxx
P.04
EVNt
t.09