ABB TZIDC Commissioning Instructions
Read Online
Read the ABB TZIDC Commissioning Instructions online using the built-in PDF viewer.
Text of the manual
TZIDC, TZIDC-110, TZIDC-120
For 4 ... 20 mA two-wire technology,
HART, PROFIBUS PA,
FOUNDATION fieldbus
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Electro-Pneumatic Positioner
TZIDC, TZIDC-110, TZIDC-120
Commissioning Instruction
CI/TZIDC/110/120-EN
03.2013
Rev. C
Translation of the original instruction
Manufacturer:
ABB Automation Products GmbH
Process Automation
Schillerstraße 72
32425 Minden
Germany
Tel.: +49 551 905-534
Fax: +49 551 905-555
Customer service center
Phone: +49 180 5 222 580
Fax: +49 621 381 931-29031
[email protected]
© Copyright 2013 by ABB Automation Products GmbH
Subject to changes without notice
This document is protected by copyright. It assists the user in safe and efficient operation of the device. The contents of this
document, whether whole or in part, may not be copied or reproduced without prior approval by the copyright holder.
Contents
TZIDC, TZIDC-110, TZIDC-120
3
1
Safety ............................................................................................................................................................. 5
1.1
General information and notes for the reader ................................................................................................ 5
1.2
Intended use ................................................................................................................................................... 5
1.3
Target groups and qualifications .................................................................................................................... 5
1.4
Warranty provisions ........................................................................................................................................ 6
1.5
Plates and symbols ........................................................................................................................................ 6
1.5.1
Safety- / warning symbols, note symbols ................................................................................................ 6
1.5.2
Name plate .............................................................................................................................................. 7
1.6
Transport safety information........................................................................................................................... 7
1.7
Storage conditions .......................................................................................................................................... 7
1.8
Installation safety information ......................................................................................................................... 8
1.9
Safety information for electrical installation .................................................................................................... 8
1.10
Operating safety information .......................................................................................................................... 8
1.11
Returning devices ........................................................................................................................................... 9
1.12
Integrated management system ..................................................................................................................... 9
1.13
Disposal .......................................................................................................................................................... 9
1.13.1
Information on WEEE Directive 2002/96/EC (Waste Electrical and Electronic Equipment) ................... 9
1.13.2
RoHS Directive 2002/95/EC ................................................................................................................. 10
2
Ex relevant safety instructions ................................................................................................................. 10
3
Mounting ..................................................................................................................................................... 11
3.1
Operating conditions at installation site ........................................................................................................ 11
3.2
Mechanical mount ........................................................................................................................................ 11
3.2.1
General information ............................................................................................................................... 11
3.2.2
Mounting on linear actuators ................................................................................................................. 13
3.2.3
Mounting on rotary actuators ................................................................................................................ 17
4
Electrical connections ............................................................................................................................... 20
4.1
Screw terminal assignments ........................................................................................................................ 22
4.2
Jumper configuration on mainboard (TZIDC-120 only) ................................................................................ 23
4.3
Cable entry ................................................................................................................................................... 24
4.4
"TZIDC with remote position sensor" ........................................................................................................... 25
4.4.1
Electrical connection of TZIDC with remote position sensor ................................................................ 26
4.5
"TZIDC for remote position sensor" ............................................................................................................. 27
4.5.1
Electrical connection of TZIDC for remote position sensor ................................................................... 28
5
Pneumatic connection ............................................................................................................................... 29
6
Commissioning .......................................................................................................................................... 31
6.1
TZIDC ........................................................................................................................................................... 31
6.1.1
Operating modes ................................................................................................................................... 32
6.2
TZIDC-110 / TZIDC-120 ............................................................................................................................... 33
6.2.1
Operating modes ................................................................................................................................... 34
7
Ex relevant specifications ......................................................................................................................... 35
7.1
TZIDC ........................................................................................................................................................... 35
7.1.1
ATEX Ex i .............................................................................................................................................. 35
7.1.2
ATEX Ex n ............................................................................................................................................. 38
7.1.3
IECEx .................................................................................................................................................... 39
7.1.4
IECEx i .................................................................................................................................................. 40
7.1.5
IECEx n ................................................................................................................................................. 41
7.1.6
CSA International .................................................................................................................................. 41
7.1.7
CSA Certification Record ...................................................................................................................... 43
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.1.8
FM Approvals ........................................................................................................................................ 44
7.1.9
FM Control Document ........................................................................................................................... 45
7.2
TZIDC-110 .................................................................................................................................................... 49
7.2.1
ATEX Ex i .............................................................................................................................................. 49
7.2.2
ATEX Ex n ............................................................................................................................................. 50
7.2.3
IECEx .................................................................................................................................................... 51
7.2.4
IECEx i .................................................................................................................................................. 51
7.2.5
IECEx n ................................................................................................................................................. 52
7.2.6
CSA International .................................................................................................................................. 53
7.2.7
CSA Certification Record ...................................................................................................................... 54
7.2.8
FM Approvals ........................................................................................................................................ 55
7.2.9
FM Control Document ........................................................................................................................... 56
7.3
TZIDC-120 .................................................................................................................................................... 59
7.3.1
ATEX Ex i .............................................................................................................................................. 59
7.3.2
ATEX Ex n ............................................................................................................................................. 60
7.3.3
IECEx .................................................................................................................................................... 61
7.3.4
IECEx i .................................................................................................................................................. 61
7.3.5
IECEx n ................................................................................................................................................. 62
7.3.6
CSA International .................................................................................................................................. 63
7.3.7
CSA Certification Record ...................................................................................................................... 64
7.3.8
FM Approvals ........................................................................................................................................ 65
7.3.9
FM Control Document ........................................................................................................................... 66
8
Appendix ..................................................................................................................................................... 69
8.1
Approvals and certifications ......................................................................................................................... 69
TZIDC, TZIDC-110, TZIDC-120
5
1
Safety
1.1
General information and notes for the reader
You must read these instructions carefully prior to installing and commissioning the device.
These instructions are an important part of the product and must be kept for future reference.
These instructions are intended as an overview and do not contain detailed information on all
designs for this product or every possible aspect of installation, operation and maintenance.
For additional information or if specific problems occur that are not discussed in these
instructions, contact the manufacturer.
The content of these instructions is neither part of any previous or existing agreement, promise
or legal relationship nor is it intended to change the same.
This product is built based on state-of-the-art technology and is operationally safe. It has been
tested and left the factory in perfect working order from a safety perspective. The information in
the manual must be observed and followed in order to maintain this state throughout the period
of operation.
Modifications and repairs to the product may only be performed if expressly permitted by these
instructions.
Only by observing all of the safety instructions and all safety/warning symbols in these
instructions can optimum protection of both personnel and the environment, as well as safe and
fault-free operation of the device, be ensured.
Information and symbols directly on the product must be observed. They may not be removed
and must be fully legible at all times.
1.2
Intended use
TZIDC, TZIDC-110, TZIDC-120 positioners are electro-pneumatic positioning devices for use
with pneumatically controlled actuators.
The device may only be used for the applications listed in these operating instructions and in
the data sheet.
• The maximum operating temperature must not be exceeded.
• The permissible operating temperature must not be exceeded.
• The housing protection type must be observed during operation.
1.3
Target groups and qualifications
Installation, commissioning, and maintenance of the product may only be performed by trained
specialist personnel who have been authorized by the plant operator to do so. The specialist
personnel must have read and understood the manual and comply with its instructions.
Prior to using corrosive and abrasive materials for measurement purposes, the operator must
check the level of resistance of all parts coming into contact with the materials to be measured.
ABB Automation Products GmbH will gladly support you in selecting the materials, but cannot
accept any liability in doing so.
The operators must strictly observe the applicable national regulations with regards to
installation, function tests, repairs, and maintenance of electrical products.
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
1.4
Warranty provisions
Using the device in a manner that does not fall within the scope of its intended use, disregarding
this instruction, using underqualified personnel, or making unauthorized alterations releases the
manufacturer from liability for any resulting damage. This renders the manufacturer's warranty
null and void.
1.5
Plates and symbols
1.5.1
Safety- / warning symbols, note symbols
DANGER –
This symbol in conjunction with the signal word "Danger" indicates an imminent danger.
Failure to observe this safety information will result in death or severe injury.
DANGER –
This symbol in conjunction with the signal word "Danger" indicates an imminent electrical
hazard. Failure to observe this safety information will result in death or severe injury.
WARNING –
This symbol in conjunction with the signal word “Warning“ indicates a possibly dangerous
situation. Failure to observe this safety information may result in death or severe injury.
WARNING –
This symbol in conjunction with the signal word "Warning" indicates a potential electrical
hazard. Failure to observe this safety information may result in death or severe injury.
CAUTION –
This symbol in conjunction with the signal word “Caution“ indicates a possibly dangerous
situation. Failure to observe this safety information may result in minor or moderate injury.
This may also be used for property damage warnings.
NOTICE – !
The symbol indicates a potentially damaging situation.
Failure to observe this safety information may result in damage to or destruction of the product
and/or other system components.
IMPORTANT (NOTE)
This symbol indicates operator tips, particularly useful information, or important information
about the product or its further uses. It does not indicate a dangerous or damaging situation.
TZIDC, TZIDC-110, TZIDC-120
7
1.5.2
Name plate
M00406
Type:
Softw.-Rev.:
Serial no./Seriennr.:
NL-No.:
Year/Baujahr:
Supplypress: 20 ... 90 psi
Input: analog 4 - 20 mA
Eingang:
V18345 -
Zuluftdruck: 1,4 ... 6 bar
TZIDC
Output / Ausgang:
Loss of electr. supply/ Stromlos:
Options/ Optionen
ABB Automation Products GmbH
D - 32425 Minden
Made in Germany
0044
analog feedback
electr. limit switch
mech. limit switch
FSK
position indicator
safety shut down
1
2
3
4
5
8
9
10
6
7
Fig. 1: Name plate
1 Complete model name
2 Software version
3 Serial number
4 NL number
5 Year
6 Supply pressure
7 Input
8 Output
9 Dead
10Options
1.6
Transport safety information
Check the devices for possible damage that may have occurred during transport. Damages in
transit must be recorded on the transport documents. All claims for damages must be claimed
without delay against the shipper and before the installation.
1.7
Storage conditions
The unit must be stored in dry and dust-free conditions. The unit is also protected by a
dessicant in the packaging.
The storage temperature should be between -40 ... 85 °C (-40 ... 185 °F).
The storage time is basically indefinite. However, the warranty conditions stipulated in the order
confirmation of the supplier are valid.
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
1.8
Installation safety information
CAUTION - Risk of injury!
Incorrect parameter values can cause the valve to move unexpectedly. This can lead to
process failures and result in injuries.
Before recommissioning a TZIDC, TZIDC-110, TZIDC-120 positioner that was used at another
location, the device must always be reset to factory settings. Never start Autoadjust before
restoring factory settings.
• Only qualified specialists who have been trained for these tasks are authorized to mount and
adjust the unit, and to make the electrical connection.
• When working on the unit always observe the locally valid accident prevention regulations
and the regulations concerning the construction of technical installations.
1.9
Safety information for electrical installation
o
• The electrical connection may only be made by authorized specialist personnel and in
accordance with the electrical circuit diagrams.
• The electrical connection information in the manual must be observed; otherwise, the type of
electrical protection may be adversely affected.
• Safe isolation of electrical circuits which are dangerous if touched is only guaranteed if the
connected devices satisfy the requirements of DIN EN 61140 (VDE 0140 Part 1) (basic
requirements for safe isolation).
• To ensure safe isolation, install supply lines so that they are separate from electrical circuits
which are dangerous if touched, or implement additional isolation measures for them.
1.10 Operating safety information
Before switching on the unit make sure that your installation complies with the environmental
conditions listed in the chapter "Technical data" or in the data sheet.
If there is a chance that safe operation is no longer possible, take the unit out of operation and
secure against unintended startup.
When mounting the unit in areas that may be accessed by unauthorized persons, take the
required protective measures.
Prior to installation, check the devices for any damage that may have occurred as a result of
improper transport. Details of any damage that has occurred in transit must be recorded on the
transport documents. All claims for damages must be submitted to the shipper without delay
and before installation.
TZIDC, TZIDC-110, TZIDC-120
9
1.11 Returning devices
Use the original packaging or suitably secure shipping containers if you need to return the
device for repair or recalibration purposes. Fill out the return form (see the Appendix) and
include this with the device.
According to EC guidelines for hazardous materials, the owner of hazardous waste is
responsible for its disposal or must observe the following regulations for shipping purposes:
All devices delivered to ABB Automation Products GmbH must be free from any hazardous
materials (acids, alkalis, solvents, etc.).
Please
Please contact Customer Center Service acc. to page 2 for nearest service location.
1.12 Integrated management system
ABB Automation Products GmbH operates an integrated management system, consisting of:
• Quality management system to ISO 9001:2008
• Environmental management system to ISO 14001:2004
• Occupational health and safety management system to BS OHSAS 18001:2007 and
• Data and information protection management system
Environmental awareness is an important part of our company policy.
Our products and solutions are intended to have a minimal impact on the environment and on
people during manufacturing, storage, transport, use, and disposal.
This includes the environmentally-friendly use of natural resources. We conducts an open
dialog with the public through our publications.
1.13 Disposal
This product is manufactured from materials that can be reused by specialist recycling
companies.
1.13.1 Information on WEEE Directive 2002/96/EC (Waste Electrical and Electronic Equipment)
This product is not subject to WEEE Directive 2002/96/EC or relevant national laws
(e.g., ElektroG in Germany).
The product must be disposed of at a specialist recycling facility. Do not use municipal garbage
collection points. According to the WEEE Directive 2002/96/EC, only products used in private
applications may be disposed of at municipal garbage facilities. Proper disposal prevents
negative effects on people and the environment, and supports the reuse of valuable raw
materials.
If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of
returns for a fee.
Ex relevant safety instructions
10
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
1.13.2 RoHS Directive 2002/95/EC
With the Electrical and Electronic Equipment Act (ElektroG) in Germany, the European
Directives 2002/96/EC (WEEE) and 2002/95/EC (RoHS) are translated into national law.
ElektroG defines the products that are subject to regulated collection and disposal or reuse in
the event of disposal or at the end of their service life. ElektroG also prohibits the marketing of
electrical and electronic equipment that contains certain amounts of lead, cadmium, mercury,
hexavalent chromium, polybrominated biphenyls (PBB), and polybrominated diphenyl ethers
(PBDE) (also known as hazardous substances with restricted uses).
The products provided by ABB Automation Products GmbH do not fall within the current scope
of the directive on waste from electrical and electronic equipment according to ElektroG. If the
necessary components are available on the market at the right time, in the future these
substances will no longer be used in new product development.
2
Ex relevant safety instructions
Depending on the type of explosion protection, an Ex label is attached to the left of the
positioner beside the main name plate. It indicates the level of explosion protection and the
device's relevant Ex certificate.
Requirements / preconditions for safe operation of the positioner:
IMPORTANT (NOTE)
Observe the device's applicable technical data and special conditions in accordance with the
relevant certificate.
• Manipulation of the device by users is not permitted. Modifications to the unit may only be
performed by the manufacturer or an explosion protection specialist.
• The splash guard cap must be screwed in place to achieve IP 65 / NEMA 4x protection
class. Operating the unit without splash guard cap is prohibited.
• The device may only be supplied with instrument air that is free of oil, water, and dust. The
use of flammable gas, oxygen, or oxygen-enriched gas is not permitted.
• Exception: The version of the TZIDC that is designed for operation with flammable gas, group
IIA, temperature class T1 ((see IMPORTANT (NOTE) in 7 "Ex relevant specifications“ ).
TZIDC, TZIDC-110, TZIDC-120
11
3
Mounting
CAUTION - Risk of injury!
Incorrect parameter values can cause the valve to move unexpectedly. This can lead to
process failures and result in injuries.
Before recommissioning a TZIDC, TZIDC-110, TZIDC-120 positioner that was used at another
location, the device must always be reset to factory settings. Never start Autoadjust before
restoring factory settings.
3.1
Operating conditions at installation site
IMPORTANT (NOTE)
Before installation, check whether the TZIDC, TZIDC-110, TZIDC-120 positioner meets the
control and safety requirements for the installation location (actuator or valve).
See the „Specifications“ chapter in the operating instructions or on the data sheet.
3.2
Mechanical mount
3.2.1
General information
Fig. 2: Operating range
The arrow (1) on the positioner feedback shaft (and the lever) must move through the area
marked by the arrows (2).
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
M00410
1
2
3
4
+30°
+60°
-60°
-30°
+100%
+100%
0%
0%
TZID-C
Fig. 3: Positioner range
1 Sensor range for linear actuators
2 Sensor range for part-turn actuators
3 Restricted working range
4 Working range
IMPORTANT (NOTE)
During installation make sure that the actuator travel or rotation angle for position feedback is
implemented correctly.
The maximum rotation angle for position feedback is 60° when installed on linear actuators and
120° on part-turn actuators. The minimum angle is always 25°.
TZIDC, TZIDC-110, TZIDC-120
13
3.2.2
Mounting on linear actuators
For mounting on a linear actuator in accordance with DIN / IEC 534 (lateral mount per NAMUR)
a complete mounting kit is available, and consists of the items in the following table:
Fig. 4: Mounting kit for linear actuators
• Lever (4) with follower pin, for stroke adjustment 10 ... 35 mm (0.39 ... 1.38 inch) or
20 ... 100 mm (0.79 ... 3.94 inch)
• Follower guide (13) with two screws (10), spring washers (11) and clamp plates (12)
• Mount bracket (3) with two screws (6) and two shims (5)
• Screw (1) and shim (2) for mounting to cast iron yoke
• Two U-bolts (7) with two shims (8) and two nuts (9) for mounting to columnar yoke
Required tools:
-
Wrench, size 10 / 13
-
Allen key, size 4
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Procedure:
1. Attach follower guide to actuator
Fig. 5
IMPORTANT (NOTE)
Hand tighten the screws.
• Attach the follower guide (1) and clamp plates (2) with screws (4) and spring washers (3) to
the actuator stem
2. Mount the lever and bracket on the positioner
Fig. 6
• Attach the lever (6) to the feedback shaft (5) of the positioner (can only be mounted in one
position due to the flat on the side of the shaft)
• Using the arrow marks (4) check whether the lever moves within the operating range
(between the arrows)
• Hand-tighten the screw (7) on the lever
• Hold the prepared positioner with loose mount bracket (1) to the actuator so that the follower
pin for the lever enters the follower guide to determine which holes on the positioner must be
used for the mount bracket
• Attach the mount bracket (1) with screws (2) and shims (3) to the proper holes on the
positioner housing. Tighten the screws as evenly as possible to ensure subsequent linearity.
Align the mount bracket in the oblong hole to ensure that the operating range is symmetrical
(lever moves between the arrows (4))
TZIDC, TZIDC-110, TZIDC-120
15
3.a Mounting on cast iron yoke
Fig. 7
• Attach the mount bracket (2) with screw (4) and shim (3) to the cast iron yoke (1)
or
3.b Mounting on columnar yoke
Fig. 8
• Hold the mount bracket (3) in the proper position on the columnar yoke (2)
• Insert the U-bolts (1) from the inside of the columnar yoke (2) through the holes for the
mount bracket
• Add the washers (4) and nuts (5). Hand tighten the nuts
IMPORTANT (NOTE)
Adjust the height of the positioner on the cast iron yoke or columnar yoke until the lever is
horizontal (based on visual check) at half stroke of the valve.
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Fig. 9: Linkage for positioner
1 larger
2 smaller
The scale on the lever indicates the link point for the various stroke ranges of the valve.
Move the bolt with the follower guide into the oblong hole of the lever to adjust the stroke range
of the valve to the operating range for the position sensor.
Moving the link point inward increases the rotation angle of the sensor. Moving the link point
outward reduces the sensor's rotation angle.
Adjust the actuator stroke to make use of as large an angle of rotation as possible (symmetrical
around the center position).
Recommended range for linear actuators:
between -28 ... 28°
Minimum angle:
25°
IMPORTANT (NOTE)
After mounting the unit check whether the positioner is operating within the sensor range.
TZIDC, TZIDC-110, TZIDC-120
17
3.2.3
Mounting on rotary actuators
For mounting on rotary actuators in accordance with VDI / VDE 3845, the following mounting kit
is available:
Fig. 10
• Adapter (1) with spring (5)
• each four screws M6 (4), spring washers (3) and shim (2) to attach the mounting bracket (6)
on the positioner
• each four screws M5 (7), spring washers (8) and shim (9) to attach the mounting bracket on
the actuator
Required tools:
-
Wrench, size 10 / 13
-
Allen key, size 3
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Procedure:
1. Mounting the adapter on the positioner
Fig. 11
• Determine the mounting position (parallel to actuator or at 90° angle)
• Calculate the rotational direction of the actuator (right or left)
• Move the rotary actuator into home position
• Based on the mounting position as well as the home position and rotational direction of the
actuator, determine in which position the feedback shaft (1) for the positioner must be pre-
adjusted and in which position the adapter (2) must be placed to enable the positioner to
travel within the proper range (the arrow on the rear of the device must travel within the
admissible range, see Fig. 2)
• Pre-adjust feedback shaft
• Place the adapter in the proper position on the feedback shaft and fasten with set screws (3).
One of the set screws must be locked in place on the flat side of the feedback shaft
TZIDC, TZIDC-110, TZIDC-120
19
2. Attach mounting bracket on the positioner
Fig. 12
1 Mounting bracket
3. Attach positioner to the actuator
Fig. 13
IMPORTANT (NOTE)
After mounting the unit check whether the operating range for the actuator matches the sensor
range on the positioner.
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
4
Electrical connections
DANGER! Risk of explosion! (TZIDC only)
It is prohibited to use the integrated communication interface (LKS) in an Ex area.
Never use the integrated communication interface (LKS) on the mainboard with a positioner
that is being used in an explosion risk area.
1. Strip the wire by approx. 6 mm (0.24 inch).
2. To connect the signal lines, the emergency shutdown module and the proximity switches or
micro switches, insert the wire ends from the left into the respective screw terminals and
hand-tighten the screws (access from above). To connect a plug-in module, insert the wire
ends from above in the appropriate screw terminals and hand-tighten the screws (access
from the side).
Fig. 14: Control unit connection diagram
A Basic device
B Options
1 Analog input / Bus connection
2 Binary input 1)
3 Binary input 1)
4 Digital feedback 1)
5 Analog feedback 1)
6 Emergency shutdown module
7 Remote sensor
1) TZIDC only
+11 -12 +81-82 +83 -84
+51-52 +41-42
+31 -32
+85 -86
24 V DC (20 V ... 30 V)
L = <1 mA; H = >2 mA
5 ... 11 V DC
L = <1 mA; H = >2 mA
5 ... 11 V DC
L = <1 mA; H = >2 mA
5 ... 11 V DC
24 V DC (12 ... 30 V)
4 ... 20 mA
AI
DI
DO
SW 2
SW 1
AO
A
M00766
4 ... 20 mA
10 ... 30 V DC
1
2
3
4
5
6
+51-52 +41-42
L = <1 mA; H = >2 mA
5 ... 11 V DC
L = <1 mA; H = >2 mA
5 ... 11 V DC
SW 2
SW 1
4
1 2
3
A
D
7
B
TZIDC, TZIDC-110, TZIDC-120
21
Fig. 15: Remote sensor connection diagram
A Basic device
B Options
1 Control unit
2 Proximity switches
3 Microswitches
IMPORTANT (NOTE)
Keep cable shields as short as possible and connect on both sides.
M00767
3
1 2
+51-52
+41-42
515253
41 42 43
max. 24 V
max. 2 A
L = <1 mA; H = >2 mA
5 ... 11 V DC
Position sensor
Limit 1
Limit 2
Limit 1
Limit 2
L = <1 mA; H = >2 mA
5 ... 11 V DC
1
2
3
B
A
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
4.1
Screw terminal assignments
Fig. 16
1 Module for analog position feedback 1)
2 Module for digital feedback 1) or service switch of
emergency shutdown module
3 Module for digital position feedback 1) or terminals of
the shutdown module
4 Installation kit for digital position feedback, either
proximity switches or 24 V microswitches
5 Same as 4
6 Digital output DO 1)
7 Digital input DI 1)
8 Signal 4 ... 20 mA / Bus connector
9 Grounding screw
1) TZIDC only
TZIDC, TZIDC-110, TZIDC-120
23
4.2
Jumper configuration on mainboard (TZIDC-120 only)
M00494
1
2
Fig. 17
1 Simulation
2 Write access
There are two jumpers on the mainboard that can be used to activate or block simulation mode
and write access. Set the jumpers as shown below:
M00495
1
2
Fig. 18
1 Block (Simulation blocked 1))
2 Activate (Write access enabled 1))
1) Default setting (complies with Fieldbus Foundation standard)
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
4.3
Cable entry
IMPORTANT (NOTE)
The cable terminals are delivered closed and must be unscrewed before inserting the cable.
For the cable entry into the housing, on the left-hand side of the housing there are two tap holes
in four thread combinations to accommodate the cable entry and pneumatic connection.
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
As an option, one thread can be fitted with a cable gland and the other with a pipe plug if
necessary.
Fig. 19: Cable entry
1 Pipe plug
2 Cable gland
TZIDC, TZIDC-110, TZIDC-120
25
4.4
"TZIDC with remote position sensor"
In the TZIDC designed with a remote position sensor, the components are accommodated in
two housings, which together form one harmonized unit.
Housing 1 (control unit) contains the electronics and pneumatics along with the following
options (where applicable):
• Analog position feedback
• Digital position feedback
• Shutdown module
Housing 2 (remote sensor) contains the position sensor and is suitable for mounting on linear
and part-turn actuators.
The following options can be installed if required:
• Optical position indicator
• Mechanical feedback contacts designed as proximity switches or microswitches.
The two housings can be or are connected to a shielded 3-wire cable. The maximum cable
length is 10 m.
Installation and commissioning procedures are described in chapters 3 "Mounting", 5
"Pneumatic connection" and 6 "Commissioning".
Procedures for connecting the electronic unit (housing 1) and the options (housings 1 and 2) are
described in chapter 4 "Electrical connections".
With remote sensors designed to protection class IP 67, ensure that the cover screws are pre-
tightened with approx. 50 Ncm and then firmly tightened with 250 ± 30 Ncm.
IMPORTANT (NOTE)
If the device is being operated on a cylinder, for reasons associated with linearity you should
run the Auto Adjust function for part-turn actuators.
Fig. 20: TZIDC with remote position sensor
1 Housing 1 (control unit)
2 Setpoint signal
3 Connecting cable
4 Housing 2 (remote sensor)
5 Pneumatic output 2
6 Pneumatic output 1
7 Air supply
8 Pneumatic drive
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
4.4.1
Electrical connection of TZIDC with remote position sensor
TZIDC control unit
TZIDC remote sensor
M00759
+31 -32
3
+51 -52
1 2
+11 -12
+83 -84
+81 - 82
+41 -42
+41 -42
Limit 2
Limit 1
+51 -52
1 2
3
1
2
4
7
9
8
10
5
6
3
11
12
10
Fig. 21
1 Analog position feedback
2 Digital position feedback switch 1
3 Digital position feedback switch 2
4 Connecting cable for remote position sensor
5 Connecting cable for remote position sensor
6 Connecting cable for remote position sensor
7 Binary output
8 Binary input
9 Setpoint input
10 Ground connection
11 Proximity switches/Microswitches, switch 1
12 Proximity switches/Microswitches, switch 2
IMPORTANT (NOTE)
The sensor and the electronics have been carefully matched. Therefore, during installation,
please make sure that devices are only connected if they have the same serial number.
Connect the connecting cable shield to both housings using EMC cable glands.
The pneumatic outputs must be connected to the drive using cables at least 6 mm in diameter.
If the control unit is attached so that it is it non-conductive, the housing must be grounded
(control unit and remote sensor housing at same electrical level); otherwise, control deviations
could occur with regard to analog position feedback.
TZIDC, TZIDC-110, TZIDC-120
27
4.5
"TZIDC for remote position sensor"
With the TZIDC designed for remote position sensors, the positioner is supplied without position
detection.
The housing (control unit) contains the electronics and pneumatics along with the following
options (where applicable):
• Analog position feedback
• Digital position feedback
• Shutdown module
The TZIDC designed for remote position sensors can be connected to any position sensor
(4 to 30 kΩ, with open circuit detection 4 to 18 kΩ).
The maximum length of the shielded 3-wire cable is 10 m.
Installation and commissioning procedures are described in chapters 3 "Mounting", 5
"Pneumatic connection" and 6 "Commissioning".
Procedures for connecting the electronic unit (housing 1) and the options are described in
chapter 4 "Electrical connections".
IMPORTANT (NOTE)
If the device is being operated on a cylinder, for reasons associated with linearity you should
run the Auto Adjust function for part-turn actuators.
Fig. 22: TZIDC for remote position sensor
1 Housing (control unit)
2 Setpoint signal
3 Connecting cable
4 Remote position sensor
5 Pneumatic output 2
6 Pneumatic output 1
7 Air supply
8 Pneumatic drive
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
4.5.1
Electrical connection of TZIDC for remote position sensor
M00760
+31 -32
3
+51 -52
1 2
+11 -12
+83 -84
+81 - 82
+41 -42
1
2
4
7
9
8
10
5
6
11
3
Fig. 23: TZIDC control unit
1 Analog position feedback
2 Digital position feedback switch 1
3 Digital position feedback switch 2
4 Connecting cable for remote position sensor
5 Connecting cable for remote position sensor
6 Connecting cable for remote position sensor
7 Binary output
8 Binary input
9 Setpoint input
10 Ground connection
11 Remote position sensor
IMPORTANT (NOTE)
Connect the connecting cable shield to both housings using EMC cable glands.
If the control unit is attached so that it is it non-conductive, the housing must be grounded
(control unit and remote sensor housing at same electrical level); otherwise control deviations
could occur with regard to analog position feedback.
The pneumatic outputs must be connected to the drive using cables at least 6 mm in diameter.
TZIDC, TZIDC-110, TZIDC-120
29
5
Pneumatic connection
IMPORTANT (NOTE)
The TZIDC, TZIDC-110, TZIDC-120 positioner must be supplied with instrument air that is free
of oil, water and dust.
The purity and oil content should meet the requirements of Class 3 according to
DIN/ISO 8573-1.
NOTICE - Potential damage to parts!
Impurities on the pipe and positioner can damage components.
The recommended pipe dimension is 6 x 1 mm. Dust, splinters or any other particles must be
blown off the pipe before connecting.
To connect the air pipes, G1/4 or 1/4-18 NPT tap holes are provided. We recommend that you
use a line with the 6 x 1 mm dimensions.
NOTICE - Potential damage to parts!
Pressure above 6 bar (90 psi) can damage the positioner or actuator.
Provisions should be made to ensure that in the event of an error the pressure does not rise
above 6 bar (90 psi).
Fig. 24: Pneumatic connections
1 Pneumatic outputs
2 Supply air
M00763
1
2
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
All pneumatic piping connections are located on the right-hand side of the positioner. Tapped
holes are provided to connect the pneumatic pipes, G1/4 or 1/4-18 NPT. The positioner is
labeled according to the available tapped holes. The corresponding pipe connections must be
included.
The level of supply air pressure required to apply the actuating force should be adjusted
according to the actuating pressure in the actuator. The positioner operating range is between
1.4 ... 6 bar (20 ... 90 psi).
IMPORTANT (NOTE)
With control systems for double-acting spring return actuators, modulation problems may
occur due to the spring force combining with the compression force. The pressure values in
the springless chamber may exceed those of the supply air as a result of the compression
induced by the spring force. This may cause two effects:
Effect 1
The pressure values in the springless chamber exceed the max. permissible limit values.
The diaphragms in the I/P module or the actuator may sustain damage leading to device
failure as a result.
Effect 2
The pressure in the springless chamber is higher than the service pressure.
If this is the case and if the line to the springless chamber is actuated by the positioner, the
excess pressure will first be redirected towards the supply air, and the actuator will move
briefly (and inadvertently) in the wrong direction.
In order to ensure that this behavior cannot occur, it is recommended to install a pressure
compensation valve between the springless chamber and the supply air for these types of
applications. It enables the increased pressure to be transferred back to the air inlet line.
The opening pressure of the check valve should be < 250 mbar.
Join the pipe connections according to the following designation:
Designation
Pipe connection
-
Supply air, pressure 1.4 ... 6 bar (20 ... 90 psi)
OUT1
Actuating pressure for actuator
OUT2
Actuating pressure for actuator (2nd connection with double-acting actuator)
TZIDC, TZIDC-110, TZIDC-120
31
6
Commissioning
6.1
TZIDC
bieten
1. Feed in pneumatic supply power
2. Feed in electrical supply power
• Feed in setpoint current 4 ... 20 mA (terminals +11 / -12)
3. Check mount:
• Press and hold
, plus or until operating mode 1.3 (manual adjustment within
the sensor range) is displayed. Release
• Press or to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees; for high-speed mode, press and
simultaneously
Recommended range:
-
between -28 ... 28° for linear actuators
-
between -57 ... 57° for part-turn actuators
Minimum angle: 25°
4. Run Autoadjust
IMPORTANT (NOTE)
Autoadjust is available for software version 2.XX and higher.
For linear actuators 1):
• Press and hold down
until
is displayed; release the control button
• Press
again and hold down until the countdown ends
• Release
; this starts Autoadjust
For part-turn actuators 1):
• Press
and hold down until
is displayed; release the control button
• Press
again and hold down until the countdown ends
• Release
; this starts Autoadjust
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down or for approximately three seconds. The unit will switch
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
IMPORTANT (NOTE)
Autoadjust does not always result in optimum control conditions.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for part-turn actuators).
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
6.1.1
Operating modes
Selection from the operating level:
• Press and hold down
.
• Press and release rapidly as often as required. The selected operating mode is displayed.
• Release
.
• The position is displayed in % or as a rotation angle.
Operating mode
Mode indicator
Position indicator
1.0
Control mode1)
with adaptation (the control parameter)
1.1
Control mode1)
without adaptation (the control parameter)
1.2
Manual adjustment 2) in the operating range.
Adjust with or 3)
1.3
Manual adjustment 2) in the sensor range.
Adjust with or 3)
1) Since self-optimization in operating mode 1.0 is subject to several factors during control operation with adaptation,
incorrect adjustments could be made over an extended period.
2) Position not active
3) For high-speed mode: Press
and
simultaneously
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
TZIDC, TZIDC-110, TZIDC-120
33
6.2
TZIDC-110 / TZIDC-120
bieten
1. Feed in pneumatic supply power
2. Connect the bus to the bus terminals with any polarity (or supply power 9 ... 32 V DC)
is displayed
3. Check mount:
• Press and hold down
and
; once the countdown has gone from 3 to 0,
release
and
; the unit switches to the operating level, mode 1.x
• Press and hold down
and
.
• Additionally, press or until operating mode 1.3 (manual adjustment within the sensor
range) is displayed. Release
• Press or to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees (for high-speed mode, press and
simultaneously)
Recommended range:
-
between -28 ... 28° for linear actuators
-
between -57 ... 57° for rotary actuators
Minimum angle: 25°
4. Go back to the bus level:
• Press and hold down
and
; once the countdown has gone from 3 to 0,
release
and
is displayed.
5. Run Autoadjust
• Check that the unit is on the bus level ("REMOTE")
For linear actuators 1):
• Press and hold down
until
is displayed. Release the control button
• Press
again and hold down until the countdown ends
• Release
; this starts Autoadjust
For rotary actuators 1):
• Press and hold down
until
is displayed. Release the control button
• Press
again and hold down until the countdown ends
• Release
; this starts Autoadjust
mA
% C
°
mA
% C
°
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down or for approximately three seconds. The unit will switch
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
6. Set potential dead band and tolerance band
This step is only required for critical (e.g., very small) actuators. It is not necessary under
normal circumstances.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for rotary actuators).
6.2.1
Operating modes
Selection from the operating level:
• Press and hold down
• Press and release as often as required to display the selected operating mode
• Release
• The position is displayed in % or as a rotation angle
Operating mode
Mode indicator
Position indicator
1.1
Positioning with fixed setpoint
Use or to adjust the setpoint
1.2
Manual adjustment 1) in the operating range
Adjust with or 2)
1.3
Manual adjustment 1) in the sensor range
Adjust with or 2)
1) Positioning not active.
2) for high-speed mode: Press
and
simultaneously.
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
conf
mA
% C
°
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
35
7
Ex relevant specifications
IMPORTANT (NOTE)
The values indicated here are taken from the respective certificates. Always observe the
specifications and supplements in the explosion protection certificates.
7.1
TZIDC
: s
7.1.1
ATEX Ex i
Designation:
II 2 G Ex ia IIC T6 resp. T4 Gb
II 2 G Ex ib IIC T6 resp. T4 Gb
II 2 D Ex ia IIIC T51°C resp. 81°C Db
Type Examination Test Certificate:
TÜV 04 ATEX 2702 X
Type:
Intrinsically safe equipment
Device class:
II 2G
Standards:
Device class:
Standards:
EN 60079-0:2009
EN 60079-11:2012
II 2D
EN 60079-0:2009
EN 61241-11:2006
II 2 G
Temperature class
Ta
Ambient temperature range
T4
-40 ... 85 °C
T5
-40 ... 50 °C
T6 1)
-40 ... 40 °C
1) When using the "digital feedback" plug-in module in temperature class T6, the maximum permissible ambient
temperature range is -40 ... 35 °C.
II 2 D
Housing surface temperature
Ta
Ambient temperature range (II 2 D)
T81 °C
-40 ... 70 °C
T61 °C
-40 ... 50 °C
T51 °C
-40 ... 40 °C
Ex relevant specifications
36
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Electrical data
With the intrinsically safe Ex ib IIC, Ex ia IIC or Ex ia IIIC type of
ignition protection, only for connection to a certified intrinsically
safe circuit.
Signal circuit
(terminal +11 / -12)
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Contact input
(terminal +81 / -82)
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 4.2 nF
Li negligibly small
Switch output
(terminal +83 / -84)
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 500 mW
Ci = 4.2 nF
Li negligibly small
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
For max. values, see EC type examination test certificate
number PTB 00 ATEX 2049 X
Proximity switches manuf. by Pepperl & Fuchs
Plug-in module for digital
position feedback
(terminal +51 / -52 or
+41 / -42)
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 500 mW
Ci = 3.7 nF
Li negligibly small
Plug-in module for analog
position feedback
(terminal +31 / -32)
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Plug-in module for shutdown
contact input
(terminal +51 / -52 or
+85 / -86)
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 3.7 nF
Li negligibly small
Optional interface to remote
sensor
(terminal X2-2: +Uref
X3-2: GND
X3-1: Signal
Maximum values:
U0 = 5.4 V
I0 = 74 mA
P0 = 100 mW
Ci negligibly small
Li negligibly small
Ex ia or Ex ib type of ignition protection
IIC:
L0 = 5mH
C0 = 2 µF
IIB:
L0 = 5mH
C0 = 10 µF
Local communication
interface (LKS)
Only for connection to a programmer outside the potentially
explosive area.
(See special conditions)
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
37
Special conditions
• The local communication interface (LKS) may only be operated at Um ≤ 30 V DC outside the
potentially explosive area.
• Variants with special certification confirming that they meet the requirements for the
"flameproof enclosure" type of ignition protection may not be used as "intrinsically safe", if
they have been previously used as a flameproof type of ignition protection.
• When used with gases from group IIA and a temperature class of T1 for auxiliary power, the
TZIDC positioner may only be used outdoors or inside sufficiently ventilated buildings.
• The gas supplied must be kept sufficiently free of air and oxygen to prevent an ignitable
atmosphere from forming.
• The equipment may only be used as a II 2 D type device in areas where the level of
mechanical hazard is "low".
• Cable and wire entries that meet the requirements of EN 61241-11 for Category II 2 D as
well as the ambient temperature range must be used.
• Prevent electrostatic charging due to propagating brush discharge when the equipment is
used for applications involving combustible dust.
Ex relevant specifications
38
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.1.2
ATEX Ex n
Designation:
II 3 G Ex nA IIC T6 resp. T4 Gc
Declaration of conformity:
TÜV 02 ATEX 1943 X
Type:
"n" type of protection
Device class:
II 3 G
Standards:
EN 60079-15:2010
EN 60079-0:2009
II 3 G
Temperature class
Ta
Ambient temperature range
T4
-40 ... 85 °C
T6
-40 ... 50 °C
Electrical data
Signal circuit
(terminal +11 / -12)
U = 9.7 V DC
I = 4 ... 20 mA, max. 21.5 mA
Contact input
(terminal +81 / -82)
U = 12 ... to 24 V DC; 4 mA
Switch output
(terminal +83 / -84)
U = 11 V DC
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
U = 5 to 11 V DC
Plug-in module for digital position feedback
(terminal +51 / -52 or +41 / -42)
U = 5 to 11 V DC
Plug-in module for analog position feedback
(terminal +31 / -32)
U = 10 ... 30 V DC
I = 4 ... 20 mA, max. 21.5 mA
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
39
7.1.3
IECEx
Designation:
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
Ex nA IIC T6 or T4 Gc
Certificate No.:
IECEx TUN 04.0015X
Issue No.:
5
Type:
Intrinsic safety "i" or "n" type of protection
Standards:
IEC 60079-0:2011
IEC 60079-11:2011
IEC 60079-15:2010
Type and
designation
TZIDC Ex ia IIC or Ex ib IIC
Temperature class
Ambient temperature range
T4
-40 ... 85 °C
-40 ... 85 °C
T6 1)
-40 ... 40 °C
-40 ... 50 °C
1) When using the "digital feedback" plug-in module in temperature class T6, the maximum permissible ambient
temperature range is -40 ... 35 °C.
Ex relevant specifications
40
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.1.4
IECEx i
Electrical data for a TZIDC designated as Ex ia IIC or Ex ib IIC
With the intrinsically safe Ex ib IIC or Ex ia IIC type of ignition
protection, only for connection to a certified intrinsically safe
circuit.
Signal circuit
(terminal +11 / -12)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Contact input
(terminal +81 / -82)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 4.2 nF
Li negligibly small
Switch output
(terminal +83 / -84)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 500 mW
Ci = 4.2 nF
Li negligibly small
Local communication
interface (LKS)
Only for connection to a programmer outside the potentially
explosive area.
(See Special conditions)
The following modules may be operated as an option:
Plug-in module for digital
position feedback
(terminal +51 / -52 or
+41 / -42)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 500 mW
Ci = 3.7 nF
Li negligibly small
Plug-in module for analog
position feedback
(terminal +31 / -32)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 mW
Ci = 6.6 nF
Li negligibly small
Plug-in module for shutdown
contact input
(terminal +51 / -52 or
+85 / -86)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 mW
Ci = 3.7 nF
Li negligibly small
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
41
7.1.5
IECEx n
Electrical data
Signal circuit
(terminal +11 / -12)
U = 9.7 V DC
I = 4 ... 20 mA, max. 21.5 mA
Contact input
(terminal +81 / -82)
U = 12 ... 24 V DC; 4 mA
Switch output
(terminal +83 / -84)
U = 11 V DC
The following modules may be operated with the TZIDC as an option:
Plug-in module for digital position feedback
(terminal +51 / -52 or +41 / -42)
U = 5 ... 11 V DC
Plug-in module for analog position feedback
(terminal +31 / -32)
U = 10 ... 30 V DC
I = 4 ... 20 mA, max. 21.5 mA
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
U = 5 ... 11 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
7.1.6
CSA International
Certificate:
1052414
Class 2258 02
PROCESS CONTROL EQUIPMENT –
For Hazardous Locations
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X:
Ex relevant specifications
42
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
30 V DC; max. 4 ... 20 mA
Max output pressure
90 psi
Max. ambient
85 Deg C
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F and G
Class III, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner intrinsically safe with entity
parameters of:
Terminals 11 / 12
V max = 30 V
I max = 104 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 81 / 82
V max = 30 V
I max = 110 mA
Ci = 4.2 nF
Li = 0 uH
Terminals 83 / 84
V max = 30 V
I max = 90 mA
Ci = 4.2 nF
Li = 0 uH
Terminals 31 / 32
V max = 30 V
I max = 110 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 41 / 42 and
51 / 52
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals Limit2 41 / 42 and
Limit1 51 / 52
V max = 15.5 V
I max = 52 mA
Ci = 20 nF
Li = 30 uH
When installed per installation Drawing No 901064
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
43
7.1.7
CSA Certification Record
Certificate:
1649904 (LR 20312)
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
30 V DC; max.4 … 20 mA
Output pressure
Max. 90 psi
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 30 V
I max = 104 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 81 / 82
V max = 30 V
I max = 110 mA
Ci = 3.7 nF
Li = 0 uH
Terminals 83 / 84
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals 31 / 32
V max = 30 V
I max = 110 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 41 / 42 and
51 / 52
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals Limit2 41 / 42 and
Limit1 51 / 52
V max = 15.5 V
I max = 52 mA
Ci = 20 nF
Li = 30 uH
When installed per installation Drawing No 901064
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
44
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.1.8
FM Approvals
TZIDC Positioner, Model V18345-a0b2c2de0f
IS/I,II,III/1/ABCDEFG/T4 Ta = 85 °C – 901064/7/4; Enity; NI/I/2/ABCD/T4 Ta = 85 °C;
S/II,III/2/FG/T4 Ta =85 °C; Type 4XMax Enity Parameters: Per Control Drawings
a = Case/mounting – 1, 2, 3, 4 or 9
b = Input/communication port – 1 or 2
c = Output/safe protection – 1, 2, 4 or 5
d = Option modules for analog or digital position feedback – 0, 1, 3 or 5
e = Mechanical kit (proximity swiches) for digital position feedback (option) – 0, 1 or 3
f = Design (varnish/coding) – 1 or 2
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
45
7.1.9
FM Control Document
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
49
7.2
TZIDC-110
7.2.1
ATEX Ex i
Designation:
II 2 G Ex ia IIC T6 resp. T4 Gb
II 3 G Ex ic IIC T6 resp. T4 Gc
Type Examination Test Certificate:
TÜV 02 ATEX 1831 X
Type:
Intrinsically safe equipment
Standards:
EN 60079-0:2009
EN 60079-11:2007
EN 60079-27:2008
Temperature class
Ambient temperature range
T4
-40 ... 85 °C
T6
-40 ... 40 °C
Electrical data for ia/ib/ic for groups IIB/IIC
With the intrinsically safe Ex i IIC type of ignition
protection, only for connection to a certified FISCO power
supply unit, a barrier, or a power supply unit with linear
characteristics and the following maximum values:
Signal circuit
(terminal +11 / -12 or + / -)
Ui = 24 V
li = 250 mA
Pi = 1.2 W
Characteristic curve: linear
Li < 10 µH
Ci < 5 nF
With the intrinsically safe Ex i IIC type of ignition
protection, only for connection to a certified intrinsically
safe circuit with maximum values
Shutdown contact input
(terminal +85 / -86)
Ui = 30 V
Ci = 3.7 nF
Li negligibly small
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
For max. values, see EC type examination test certificate
number PTB 00 ATEX 2049 X
Ex relevant specifications
50
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.2.2
ATEX Ex n
Designation:
II 3 G Ex nA IIC T6 resp. T4 Gc
Declaration of conformity:
TÜV 02 ATEX 1943 X
Type:
"n" type of protection
Device class:
II 3 G
Standards:
EN 60079-15:2010
EN 60079-0:2009
II 3 G
Temperature class
Ta
Ambient temperature range
T4
-40 ... 85 °C
T6
-40 ... 50 °C
Electrical data for II 3 G Ex nA IIC T6 or T4 Gc
Signal circuit
(terminal +11 / -12)
U = 9 to 32 V DC
I = 10.5 mA
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
U = 5 ... 11 V DC
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
51
7.2.3
IECEx
Designation:
Ex ia IIC T6 resp. T4 Gb
Ex ib IIC T6 resp. T4 Gb
Ex ic IIC T6 resp. T4 Gc
Ex nA IIC T6 resp. T4 Gc
Certificate No.
IECEx TUN 04.0015X
Issue No.:
5
Type:
Intrinsic safety "i" or Type of protection "n"
Standards:
IEC 60079-0:2011
IEC 60079-11:2011
IEC 60079-15:2010
Type and
designation
TZIDC-110
Ex i IIC
TZIDC-110
Ex nA IIC
Temperature class
Ambient temperature range
T4
-40 ... 85 °C
-40 ... 85 °C
T6
-40 ... 40 °C
-40 ... 50 °C
7.2.4
IECEx i
Electrical data for TZIDC-110 for ia/ib/ic designated as Ex i IIC T6 or T4 Gb
With the intrinsically safe Ex i IIC type of ignition
protection, only for connection to a certified FISCO
power supply unit, a barrier, or a power supply unit
with linear characteristics and the following maximum
values:
Signal circuit
(terminal +11 / -12 or + / -)
Ui = 24 V
li = 250 mA
Pi = 1.2 W
Characteristic curve: linear
The following modules may be used as an option: Ex nA IIC T6 or T4 Gc:
With the intrinsically safe Ex ia IIC or Ex ib type of
ignition protection, only for connection to a certified
intrinsically safe circuit with maximum values
Shutdown contact input
(terminals: +51,-52 or +85 / -86)
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 3.7 nF
Li negligibly small
Ex relevant specifications
52
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.2.5
IECEx n
Electrical data for TZIDC-110 designated as Ex nA IIC T6 or T4 Gc
Signal circuit
(terminal +11 / -12)
U = 9 ... 32 V DC
I = 10.5 mA
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
U = 5 ... 11 V DC
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
53
7.2.6
CSA International
Certificate:
1649904 (LR 20312)
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class 2258 02
PROCESS CONTROL EQUIPMENT –
For Hazardous Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X:
Model TZIDC-110, P/N V18346-x032x2xx0x Intelligent Positioner
Input rated
32 V DC; max.15 mA (powered by a SELV
circuit)
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 24 V
I max = 250 mA
Ci = 2.8 nF
Li = 7.2 uH
Terminals 85 / 86
U max = 30 V
I max = 50 mA
Ci = 3.8 nF
Li = 0 uH
Terminals 41 / 42
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
Terminals 51 / 52
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
When installed per installation Drawing No 901265
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
54
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.2.7
CSA Certification Record
Certificate:
1649904 (LR 20312)
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-110, P/N V18346-x032x2xx0x Intelligent Positioner
Input rated
32 V DC; max. 15 mA (powered by a SELV
Circuit)
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 24 V
I max = 250 mA
Ci = 2.8 nF
Li = 7.2 uH
Terminals 85 / 86
U max = 30 V
I max = 50 mA
Ci = 3.8 nF
Li = 0 uH
Terminals 41 / 42
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
When installed per installation Drawing No 901265
Temperature Code
T4
Max. Ambient
85 Deg C
Notice
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
55
7.2.8
FM Approvals
TZIDC-110 Positioner, Model V18346-a032b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO
Entity and FISCO Parameters
Terminals
Type
Groups
Parameters
Vmax
Imax
Pi
Ci
Li
+11 / -12
Entity
A-G
24 V
250 mA
1.2 W
2.8 nF
7.2 uH
+11 / -12
FISCO
A-G
17.5 V
360 mA
2.52 W
2.8 nF
7.2 uH
+11 / -12
FISCO
C-G
17.5 V
380 mA
5.32 W
2.8 nF
7.2 uH
+51 / -52
Entity
A-G
16 V
20 mA
-
60 nF
100 uH
+41 / -42
Entity
A-G
16 V
20 mA
-
60 nF
100 uH
+85 / -86
Entity
A-G
30 V
-
-
3.7 nF
< 1 uH
NI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = Option modules (shutdown) – 0 or 4
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-110
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I, Division 2,
Group E, F and G hazardous (classified) indoor and outdoor NEMA 4x locations.
The following temperature code ratings were assigned for the equipment and protection
methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C
Ex relevant specifications
56
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.2.9
FM Control Document
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
59
7.3
TZIDC-120
cht
7.3.1
ATEX Ex i
Designation:
II 2 G Ex ia IIC T6 resp. T4 Gb
II 3 G Ex ic IIC T6 resp. T4 Gc
Type Examination Test Certificate:
TÜV 02 ATEX 1834 X
Type:
Intrinsically safe equipment
Standards:
EN 60079-0:2009
EN 60079-11:2007
EN 60079-27:2008
Temperature class
Ambient temperature range
T4
-40 ... 85 °C
T5
-40 ... 55 °C
T6
-40 ... 40 °C
Electrical data for ia/ib/ic for groups IIB/IIC
With the intrinsically safe Ex i IIC type of ignition protection,
only for connection to a certified FISCO power supply unit, a
barrier, or a power supply unit with linear characteristics and
the following maximum values:
Signal circuit
(terminal +11 / -12 or + / -)
Ui = 24 V
li = 250 mA
Pi = 1.2 W
Characteristic curve: linear
Li < 10 µH
Ci < 5 nF
With the intrinsically safe Ex ia IIC or Ex ib IIC type of ignition
protection, only for connection to a certified intrinsically-safe
circuit with maximum values
Shutdown contact input
(terminal +85 / -86)
Ui = 30 V
Ci = 3.7 nF
Li negligibly small
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
For maximum values, see EC type examination test certificate
number PTB 00 ATEX 2049 X
Ex relevant specifications
60
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.3.2
ATEX Ex n
Designation:
II 3 G Ex nA IIC T6 resp. T4 Gc
Declaration of conformity:
TÜV 02 ATEX 1943 X
Type:
Type of ignition protection "n"
Device class:
II 3 G
Standards:
EN 60079-15:2010
EN 60079-0:2009
II 3 G
Temperature class
Ta
Ambient temperature range
T4
-40 ... 85 °C
T6
-40 ... 50 °C
Electrical data for II 3 G Ex nA IIC T6 or T4 Gc
Signal circuit
(terminal +11 / -12)
U = 9 ... 32 V DC
I = 11.5 mA
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
U = 5 ... 11 V DC
Plug-in module for shutdown contact input
(terminal+51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
61
7.3.3
IECEx
Designation:
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
Ex ic IIC T6 or T4 Gc
Ex nA IIC T6 or T4 Gc
Certificate No.:
IECEx TUN 04.0015X
Issue No.:
5
Type:
Intrinsic safety "i" or "n" type of protection
Standards:
IEC 60079-0:2011
IEC 60079-11:2011
IEC 60079-15:2010
Type and
designation
TZIDC-120
Ex i IIC
TZIDC-120
Ex nA IIC
Temperature class
Ambient temperature range
T4
-40 … 85 °C
-40 … 85 °C
T6
-40 … 40 °C
-40 … 50 °C
7.3.4
IECEx i
Electrical data for TZIDC-110 for ia/ib/ic designated as Ex i IIC T6 or T4 Gb
With the intrinsically safe Ex i IIC type of ignition
protection, only for connection to a certified FISCO
power supply unit, a barrier, or a power supply unit with
linear characteristics and the following maximum values:
Signal circuit
(terminal +11 / -12 or + / -)
Ui = 24 V
li = 250 mA
Pi = 1.2 W
Characteristic curve: linear
The following modules may be used as an option: Ex nA IIC T6 or T4 Gc
With the intrinsically safe Ex ia IIC or Ex ib type of
ignition protection, only for connection to a certified
intrinsically safe circuit with maximum values:
Shutdown contact input
(terminals: +51,-52 or +85 / -86)
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 3.7 nF
Li negligibly small
Ex relevant specifications
62
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.3.5
IECEx n
Electrical data for TZIDC-120 designated as Ex nA IIC T6 or T4 Gc
Signal circuit
(terminal +11 / -12)
U = 9 ... 32 V DC
I = 11.5 mA
Mechanical digital feedback
(terminal limit1 +51 / -52 or limit2 +41 / -42)
U = 5 to 11 V DC
Plug-in module for shutdown contact input
(terminal +51 / -52 or +85 / -86)
U = 20 ... 30 V DC
Special conditions
• Devices may only be connected to circuits in zone 2 if they are suitable for operation in zone
2 potentially explosive atmospheres and for the conditions prevailing at the installation
location (manufacturer's declaration or certificate from an inspection authority).
• For the "digital feedback with proximity switches" circuit, external measures must be
implemented to prevent the rated voltage from being exceeded by more than 40 % in the
event of transient disturbances.
• It is only permissible to connect, disconnect, and switch live circuits during installation or
maintenance, or for the purpose of carrying out repairs. Comment: It is considered very
unlikely that a potentially explosive atmosphere would be present in zone 2 at the same time
that installation or maintenance/repair work was being carried out.
• Only non-flammable gases may be used for the pneumatic auxiliary power.
• Only use suitable cable entries which meet the requirements of IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may only be operated at an
ambient temperature range from -25 ... 85 °C.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
63
7.3.6
CSA International
Certificate:
1649904 (LR 20312)
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class 2258 02
PROCESS CONTROL EQUIPMENT –
For Hazardous Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X:
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
Input rated
32 V DC; max.15 mA (powered by a SELV
circuit)
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 24 V
I max = 250 mA
Ci = 2.8 nF
Li = 7.2 uH
Terminals 85 / 86
U max = 30 V
I max = 50 mA
Ci = 3.8 nF
Li = 0 uH
Terminals 41 / 42
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
Terminals 51 / 52
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
When installed per installation Drawing No 901265
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
64
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.3.7
CSA Certification Record
Certificate:
1649904 (LR 20312)
Class 2258 04
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC-120, P/N V18347-x042x2xx0x Intelligent Positioner
Input rated
32 V DC; max. 15 mA (powered by a SELV
Circuit)
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 24 V
I max = 250 mA
Ci = 2.8 nF
Li = 7.2 uH
Terminals 85 / 86
U max = 30 V
I max = 50 mA
Ci = 3.8 nF
Li = 0 uH
Terminals 41 / 42
U max = 16 V
I max = 20 mA
Ci = 60 nF
Li = 100 uH
When installed per installation Drawing No 901265
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or optional features.
• Do not use the local communication interface (LKS) in hazardous areas.
• Each pair of conductors for each intrinsic safety circuit must be shielded.
Ex relevant specifications
CI/TZIDC/110/120-EN
TZIDC, TZIDC-110, TZIDC-120
65
7.3.8
FM Approvals
TZIDC-120 Positioner, Model V18347-a042b2cd0e
IS/I,II,III/1/ABCDEFG/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C-901265 Entity, FISCO
Entity and FISCO Parameters
Terminals
Type
Groups
Parameters
Vmax
Imax
Pi
Ci
Li
+11 / -12
Entity
A-G
24 V
250 mA
1.2 W
2.8 nF
7.2 uH
+11 / -12
FISCO
A-G
17.5 V
360 mA
2.52 W
2.8 nF
7.2 uH
+11 / -12
FISCO
C-G
17.5 V
380 mA
5.32 W
2.8 nF
7.2 uH
+51 / -52
Entity
A-G
16 V
20 mA
-
60 nF
100 uH
+41 / -42
Entity
A-G
16 V
20 mA
-
60 nF
100 uH
+85 / -86
Entity
A-G
30 V
-
-
3.7 nF
< 1 uH
NI/I/2/ABCD/T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
S/II,III/2/EFG//T6,T5,T4 Ta = 40 °C, 55 °C, 85 °C
Enclosure type 4x
a = Case/mounting – 1, 2, 5 or 6
b = Output/safe protection – 1, 2, 4 or 5
c = Option modules (shutdown) – 0 or 4
d = Optional mechanical kit for digital position feedback – 0, 1 or 3
e = Design (varnish/coding) – 1 or E
Equipment Ratings:
TZIDC-120 Positioners
Intrinsically safe, Entity and FISCO, for Class I, II and III, Division 1,
Applicable Groups A, B, C, D, E, F, G; nonincendive for Class I, Division 2,
Group E, F and G hazardous (classified) indoor and outdoor NEMA 4x locations.
The following temperature code ratings were assigned for the equipment and protection
methods described above:
T6 in ambient temperatures of 40 °C
T5 in ambient temperatures of 55 °C
T4 in ambient temperatures of 85 °C
Ex relevant specifications
66
TZIDC, TZIDC-110, TZIDC-120
CI/TZIDC/110/120-EN
7.3.9
FM Control Document
TZIDC, TZIDC-110, TZIDC-120
69
8
Appendix
8.1
Approvals and certifications
CE mark
The version of the meter in your possession meets the requirements of the
following European directives:
-
EMC directive 2004/108/EC
-
ATEX directive 94/9/EC
Explosion
Protection
Identification for intended use in potentially explosive atmospheres according
to:
-
ATEX directive (marking in addition to CE marking)
-
IEC standards
-
FM Approvals (US)
-
CSA International (Canada)
IMPORTANT (NOTE)
All documentation, declarations of conformity and certificates are available in ABB's download
area.
www.abb.com/instrumentation
TZIDC, TZIDC-110, TZIDC-120
71
Statement on the contamination of devices and components
Repair and / or maintenance work will only be performed on devices and components if a statement form has been
completed and submitted.
Otherwise, the device / component returned may be rejected. This statement form may only be completed and
signed by authorized specialist personnel employed by the operator.
Customer details:
Company:
Address:
Contact person:
Telephone:
Fax:
E-mail:
Device details:
Type:
Serial no.:
Reason for the return/description of the defect:
Was this device used in conjunction with substances which pose a threat or risk to health?
Yes
No
If yes, which type of contamination (please place an X next to the applicable items)?
Biological
Corrosive / irritating
Combustible (highly / extremely combustible)
Toxic
Explosive
Other toxic substances
Radioactive
Which substances have come into contact with the device?
1.
2.
3.
We hereby state that the devices / components shipped have been cleaned and are free from any dangerous or
poisonous substances.
Town/city, date
Signature and company stamp
n
ABB has Sales & Customer Support expertise in over
100 countries worldwide.
www.abb.com/instrumentation
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in the Fed. Rep. of Germany (03.2013)
© ABB 2013
CI/TZIDC/110/120 -EN Rev. C
3KXE341007R4401