This is the programming manual for the RY-IP44 only. Refer to the Installation and Setting
Manuals for the series being integrated with for complete installation/programming information
on each system (IX, IS-IP, IPW-1A).
0517
Input/Output Network Adaptor
ATTENTION:
#95101
6 Screw Terminal Blocks
•
MAC Address Label
Overview / Description
2 | RY-IP44 Programming Manual
Package Contents
The RY-IP44 is a Barix Barionet 50 with proprietary firmware installed for the device to function with the Aiphone IX
Series, IS-IP Series stations, or IPW-1A systems.
The 4 relay outputs can be programmed to trigger for door release, while calling, while communicating, or while calling
and communicating.
The 4 contact inputs can be programmed to trigger a call with the IX or IS-IP systems. Examples of when this could be
used are: an invalid card swipe, motion detector activation, or selective calling from multiple call buttons.
The RY-IP44 is also used as the Mobile App Server when using IX Mobile. One RY-IP44 is needed for every eight IX
Mobile devices and will alert the mobile device if it goes out of wireless network range.
If only using the RY-IP44 for IX Mobile, configure the adaptor as shown on page 5, then skip to page 11 (IX Mobile
Server). The SIF.ini file is not needed when only using the adaptor for IX Mobile. Refer to pages 11-15 for steps on
adding a mobile device to the IX Series using the IX Support Tool and for setting up the mobile device.
The RY-IP44 is not a PoE device and requires a dedicated 9-30V DC power supply. Use the Aiphone PS-1225UL
power supply (sold separately).
•
General understanding of IX Series, IS-IP Series, or
IPW-1A programming
•
9-30V DC power supply (sold separately)
•
Unique IP address for each adaptor
Installation Requirements
Creating the SIF.ini File (For IX and IS-IP only)
Creating a simple line of code, in the form of a .ini file, is required to allow an IX or IS-IP device to communicate to the
RY-IP44. The example below is shown using a common text editor (i.e. Notepad), and saving it with an .ini extension.
Program Type:
A binary number between 0100 and 1111.
RY-IP44 IP Address:
IP address assigned to the RY-IP44 (Must be unique for each RY-IP44).
Destination Port:
Port number assigned on the RY-IP44. The default port is 10000. This can be
set in the range from 1 to 65535 (Must be unique for each RY-IP44).
SSL Y/N :
This device does not use SSL. Input 0 for no.
Example Text File: 0100,192.168.1.45,10000,0
Save the SIF file with a .ini extension (.ini must be typed manually) to a location on the PC being used for programming the IX
Series or IS-IP Series stations. This file must be uploaded to each device associated with the RY-IP44 using the instructions
that follow.
Program
Type
RY-IP44
IP Address
Destination
Port
SSL
Y/N
Important:
The intercom system should be fully programmed and operational prior to programming the RY-IP44 adaptor.
IX Series: Uploading SIF.ini File
A. Open IX Support Tool and select the system to be edited (File, Select Existing System).
B. Expand the Function Settings tree on the left and select SIF Integration.
C. Choose the station to be edited from the Number drop down menu, then click the Select button.
NOTE: When using the RY-IP44 for door release, the SIF.ini file must be uploaded to the door station.
D. Select the Enable radio button for both the CGI Integration and SIF Integration.
Click Browse and navigate to where the .ini file is saved and select it. Click Upload to send to the station.
E. Click Update to save the changes for the station.
F. After completing steps C, D, and E for each station, upload the changes. Click File, Upload Settings to Station.
Select the stations to upload to and click Start Upload.
Upload the SIF.ini file to each IX Series station associated with the RY-IP44 adaptor.
Important:
The intercom system should be fully programmed and operational prior to uploading the SIF.ini file.
RY-IP44
IS-IP Series
IX Series
4 | RY-IP44 Programming Manual
IS-IP Series: Uploading SIF.ini File
Upload the SIF.ini file to each IS-IP Series station associated with the RY-IP44 adaptor.
! Note that the IP address for each station will be unique for your network settings.
Important:
The intercom system should be fully programmed and operational prior to uploading the SIF.ini file.
A. Open a web browser and type https://[ip address]/sif in the address bar.
[ip address] = static IP address assigned to the station being programmed.
B. A security certificate error message will appear. Select “Continue to the website.”
C. Enter the administrator ID and password.
Default ID:
aiphone
Default Password: aiphone
D. Select Transmission setting under Uploading SIF setting data from the menu on the left side of the screen.
E. Click the Upload button. A new window will open.
F. Click the Browse button and navigate to the .ini file saved on the PC.
G. Click the Upload button. A message will appear stating the settings will not be applied until the system is updated.
H. Click Updating the system from the menu on the left. Click the Update button and the unit will update and restart
itself.
I.
Repeat this process for each door and master station associated with the RY-IP44 adaptor.
RY-IP44
IX Series
IS-IP Series
Configuring the RY-IP44 (assigning IP address and system use)
Relay status and control.
Click on each LED to verify
relay function.
Digital input status
Configuration button
The RY-IP44 has a default IP address of 192.168.1.45. Open a web browser and point the address bar to 192.168.1.45
for access to the adaptor. The first screen to appear will be the Device Status screen.
Click the CONFIGURATION button to open the Device Configuration screen. This is where a unique IP Address,
Netmask, and Gateway can be assigned to the adaptor. Consult with your IT department for these settings.
Settings not utilized for Aiphone
functionality. Do not adjust.
SECURITY: For creating a password for
access to the web browser interface.
The Aiphone system type that the adaptor is being integrated with will need to be selected. Click the AIPHONE tab. Use the
drop down by System Type to select the appropriate system. Enter the SIF Socket Local Port number that was assigned
in the SIF.ini file (Destination Port). When done, click OK. Click Reboot on the next screen to restart the adaptor.
System Type: Select IX, IS, or IPW-1A
SIF Socket Local Port: Enter the port number
that was entered in the SIF.ini file. Leave at “0” to
use default 10000 port.
Username & Password: For IX/IS, enter
system’s username and password. Leave blank if
using default (IX = admin, IS = aiphone).
IX Mobile App Server Port: Enter the port number
that will be assigned in the IX Mobile app(s). Enter
“0” if default port (5061) is to be used.
UDP Protocol Port: Used for IPW-1A only. Enter
“0” if default port (1724) is to be used.
AIPHONE: Select the Aiphone system
type the relay is to be used with.
Enter IP Address that was entered in
the SIF.ini file.
IX Series
IS-IP Series
RY-IP44
6 | RY-IP44 Programming Manual
The RY-IP44 has 4 relays that can be programmed to trigger while calling, while communicating, or while calling and
communicating with a specific station. The relays can also be programmed for door release.
Set the RY-IP44 for use with the IX Series (refer to page 5).
From the DEVICE CONFIGURATION screen, click APPLICATION SETUP.
APPLICATION SETUP button
When the relay action is set for Door Release, the station number to be entered will always be that of the door station.
The door station is the device that will be sending the SIF command/event to the RY-IP44 adaptor that its relay status
has changed.
•
Enter the Station number of the station to be associated with the relay.
•
Select the relay condition from the Relay Action drop down menu.
•
Click on Apply Settings, then click Reboot to restart the adaptor with the saved changes.
When the entered station is active, the associated relay will trigger based on the Relay Action settings.
Relay Action options:
•
Door Release - Normally-Open
•
Door Release - Normally-Closed
•
Active while Calling from Source
•
Active while Communicating
•
Active during Calling and Communicating
When the relay action is set for one of the “Door Release” options, the relay on the RY-IP44 will trigger when the
associated station’s door release contact is triggered.
When the relay action is set for any of the “Active While” options, the relay will trigger when the associated station calls
or communicates at any priority level.
Relay will trigger when the associated station’s door release contact is triggered.
Relay will trigger when the associated station calls or communicates.
}
}
IX Series: Relay Output Programming
RY-IP44
IS-IP Series
IX Series
IX Series: Input Programming
The RY-IP44 adaptor has 4 inputs that can be programmed to trigger a call-in from a specific door station or master
station to a specific master station or group of master stations.
Note: The RY-IP44 inputs can have different calling rules than the default calling rule set for a station during the IX Series programming.
•
Select the call-in priority level for each input using the Priority drop down menu.
•
Enter the target IP address of the station for remote call-in (station that will be placing the call, i.e. door station)
•
Click Apply Settings to save the changes. Do not reboot the adaptor at this time.
•
Click APPLICATION SETUP to return to the Application Configuration Screen.
•
Click on Destinations next to the input being configured. Another window will open. Enter the station number of the
master station(s) to be called when the input is triggered.
•
When the target IP address is a door station, a maximum of 20 master stations can be entered.
•
When the target IP address is a master station, a maximum of 20 master stations or 1 group can be entered. A group
can consist of up to 50 master stations and must be created using the IX Support Tool.
•
Check the Enable box beside each station entered.
Click on Apply Settings, then click Reboot to restart the adaptor with the changes.
The RY-IP44 has 4 relays that can be programmed to trigger when a specific door station is calling, while in
communication, or while calling and communicating. The relays can also be programmed for door release from one or
multiple IP master station(s).
Set the RY-IP44 for use with the IS-IP Series (refer to page 5).
From the Device Configuration screen, click APPLICATION SETUP.
Application Setup button
IS-IP Series: Relay Output Programming
Station Placing Call
RY-IP44
IS-IP Series
IX Series
RY-IP44
IX Series
IS-IP Series
8 | RY-IP44 Programming Manual
Linked Stations Table:
Enter the IP address and TermID for each IS-IP station in the IS configuration. This table is used as a reference for
each station in the system that will be able to communicate with the RY-IP44 adaptor.
A TermID identifies the location of an IS-IP station in the IS Series configuration. It also distinguishes between master
stations and door stations. A master station TermID will be xx-001 and a door station TermID will be xx-101. “xx”
represents the line in which the station resides under “IP Unit Registration” in the IS Host programming.
Example:
01-101: Door station in address location 1.
03-001: Master station in address location 3.
Definition: TermID
Relay Functionality:
Enter the TermID for the door station to be associated to the relay.
Select the relay action from the drop down menu.
Relay Action options:
•
Door Release - Normally-Open
•
Door Release - Normally-Closed
•
Active while Calling from source
•
Active while in Communication with source
•
Active during Calling and Communication
Relay will trigger when a configured master station pushes the door release button
for the associated door.
Relay will trigger when the associated door station calls or communicates.
}
}
IS-IP Series: Relay Output Programming (cont.)
After inputting each IP address and TermID, click Apply Settings at the bottom of the page to save the settings to
memory. Return to the Application Screen or reboot adaptor by clicking the Reboot button. Rebooting must occur to
update adaptor settings.
RY-IP44
IX Series
IS-IP Series
When the relay action is set for the “Door Release” options, the relay will trigger when the associated door station is in
communication, and a master station within the configuration list requests door release.
When the relay action is set for any of the “Active While” options, the relay will trigger when the associated door station
calls or communicates at any priority level.
After the Door TermID and Relay Action has been set, click Apply Settings at the bottom of the screen to save the
settings to memory. Return to the Application Screen or reboot adaptor by clicking on the Reboot button.
To program a master station to control door release, click on the Configure button. A new window will open and the
table shown below will be populated based on the entries made in the Linked Stations Table (see page 8).
Check the Flag box beside each master station that will be “allowed” to trigger this relay for door release. Once all
master stations have been checked, click Apply Settings at the bottom of this window to save the settings to memory.
Reboot to update adaptor settings.
Note: The IS-SOFT software master stations can NOT be enabled for door release using the RY-IP44.
IS-IP Series: Input Programming
The RY-IP44 adaptor has 4 inputs that can be programmed to trigger a call-in from a specific door station to a specific
master station or group of master stations (max. 20). The RY-IP44 inputs can have different calling rules than the default
calling rule set under Advanced Station Settings in the IS Host Programming.
Choose the Call-In priority level for each input using the Priority drop down menu. Enter the target IP address of the
door station for remote call-in.
Click Apply Settings to save the changes. Do not reboot the adaptor at this time.
Click APPLICATION SETUP to return to the Application Configuration screen.
Station Placing Call
RY-IP44
IX Series
IS-IP Series
10 | RY-IP44 Programming Manual
The RY-IP44 has 4 relays that can be programmed to trigger while calling, while in communication, or while calling and
communicating with a specific door station. The relays can also be programmed for door release.
Set the RY-IP44 for use with the IPW-1A (refer to page 5).
Application Setup button
From the Device Configuration screen, click APPLICATION SETUP.
Relay Action options:
•
Door Release - Normally-Open
•
Door Release - Normally-Closed
•
Active while Calling from source
•
Active while in Communication with source
•
Active during Calling and Communication
•
Active While Any Station Calling
*Relay will trigger when the PC master station pushes the door release button.
}
Relay will trigger when the associated door station calls or communicates.
}
Relay triggers when any station calls. No assignment required.
}
IN0 IN1
NO
C
NC
* When using the RY-IP44 for door release, the relay on the IPW-1A must be set to door release and the relay
must be jumpered to the sensor input as shown below.
IS-IP Series: Input Programming (cont.)
•
Click on Destinations next to the input being configured. A new window will open.
•
Enter the TermID for each master station to be called (see page 8 for TermID information). A maximum of 20
master station TermID’s can be entered.
•
Check the Enable box beside each TermID entered to allow the master to be called.
•
Once all master station TermID’s have been entered and enabled, click Apply Settings at the bottom of this
window to save the settings to memory. Reboot to update adaptor settings.
IPW-1A: Relay Output Programming
RY-IP44
IX Series
IS-IP Series
Enter the Station ID for the IPW-1A to be associated with each relay on the RY-IP44. Select the relay condition from the
Relay Action drop down menu. When done, click on Apply Settings. Click Reboot on the next screen to restart the
adaptor with the applied settings.
Configuring the IX Mobile Server
The RY-IP44 adaptor is used as a server for up to 8 mobile devices when using IX Mobile.
Set the RY-IP44 for use with the IX Series (refer to page 5).
Enter the IP address for each of the mobile devices in the IX Mobile Server Functionality table.
Click on Apply Settings, then click Reboot to restart the adaptor with the changes.
Refer to pages 12-15 for steps on adding a mobile device to the IX system using the IX Support Tool and for setting
up the mobile device.
IX-Mobile
The IX Mobile app allows an iPhone®, iPad®, or iPod touch® running Apple® iOS versions 8.0 or higher or mobile
devices running Android™ 4.1 or higher to be used as an IX Series sub master station. The following steps will be
used to configure the IX Series system and to prepare the mobile device(s) for connection over a constant network
(WiFi or VPN). Note: At least one IX-MV must be installed in the IX Series system in order for the app to function.
IX Series
IS-IP Series
RY-IP44
12 | RY-IP44 Programming Manual
• Open the IX Support Tool and log in to the system being programmed.
Expand the 1 Station Information tree and click on 2 Identification.
On the next available line, 3 assign a Number*, Name*, and select Master Station as the Type for the mobile app.
Repeat steps 1-3 for each instance of IX Mobile app that needs to be added to the system.
• Expand the 4 Network Settings tree and click on 5 IP Address.
The IP Address of the added device(s) will be blank. Enter an 6 IP Address* and Subnet Mask
within the same range as the other devices in the system.
1
2
3
4
5
6
Click the
button to save changes.
Click the
button to save changes.
Note Station Information here to refer to later
Number
Name
IP Address
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
* For Programmers/Installers:
We recommend writing the station Number,
Name, and IP Address into this table for
reference when setting up the IX Mobile app.
• Expand the 7 Function Settings tree and click on 8 Door Release Settings.
Click the 9 Individual Master Station Door Release Settings button.
7
8
9
10
11
12
10 Select the newly added mobile master from the drop down. Click 11 Select. To enable door release for all stations for
this selected master station, click the 12 Apply button.
Adding a Mobile Device to the IX Support Tool
RY-IP44
IS-IP Series
IX Series
• Navigate to “C:\Program Files(x86)\Support Tool\System Data\(name of system)\Setting” and select the
configuration file that is associated with the mobile device. It will be identified by the Station Number that was
assigned to it in the IX Support Tool. Copy the configuration file to a location on the programming PC that can easily
be transferred to the mobile device.
• The folder containing the configuration file may be hidden. To show hidden folders, open Windows Explorer and
click 1 Organize (Windows 7), or File (Windows 10). Click 2 Folder and search options. Select the 3 View
tab and select the radio button beside 4 Show hidden files, folders, and drives, then click 5 OK.
Note: If using a 32-bit operating system, navigate to C:\Program Files\Support Tool\System Data\(name of system)\Setting
The IX Support Tool creates a configuration file for each device in the system and saves it to a folder within the
Support Tool program folder. Once all programming changes have been made and uploaded, the configuration file
will need to be copied to the mobile device.
• Click 15 File, then 16 Upload Settings To Station.
17 Select the hardware stations from the list and click 18 Start Upload. Click 19 OK on the pop-up to upload the settings.
13
14
• A pop-up will appear saying “All stations will be set for door release. Continue?” Click 13 OK. Another pop-up will
appear saying “Door release settings complete.” Click 14 OK.
Repeat the process for each mobile master station added to the system.
15
16
18
19
17
Verify success or failure of upload to each device in the Status column.
Configuration File
1
2
Windows 7
Windows 10
14 | RY-IP44 Programming Manual
Download IX Mobile from the App StoreSM
Connect to the WiFi network associated with the IX Series
system installation. Once connected, tap on the connected network.
Tap Static and enter the IP Address that was assigned when
configuring the app with the IX Support Tool.
Connect the mobile device to the PC that has iTunes installed.
Open iTunes and click File Sharing. Select IX Mobile. Click
Add File and navigate to where the configuration file is saved.
Select the file and click Open.
1
2
3
4
5
1
2
3
4
5
Launch the application on the mobile device.
Tap the
Menu icon.
6
6
7
Tap Setup.
Enter the Admin ID and Password and tap OK.
Default ID: admin
Default Password: admin
7
8
8
A pop-up will appear stating “New configuration applied.”
9 To unlock the app, call the mobile device from a master station
in the system.
App Store is a service mark of Apple Inc.
Tap Import from File.
Select the configuration file that was transferred to this device
in Step 3. Tap OK.
Tap App Server. Enter the IP Address and Port Number for
the App Server (RY-IP44). Refer to page 11 for information on
setting up the App Server.
Apple, the Apple logo, iPhone, iPad, iPod touch, and iTunes are trademarks of Apple Inc., registered in the U.S. and other countries. The App Store
is a service mark of Apple Inc.
App Installation and Setup for Apple
Download IX Mobile using Google PlayTM
Connect to the WiFi network associated with the IX Series
system installation. Once connected, tap and hold on the
connected network.
A pop-up will appear. Tap Modify network config.
Check the box beside Show advanced options.
Under IP settings, select Static and enter the IP Address that
was assigned when configuring the app with the IX Support
Tool. Once entered, tap Save.
Connect the mobile device to the PC used for programming the
system. Using the PC, navigate to the mobile device and locate
the ixapp_settings folder. Paste/transfer the configuration file
saved from the IX Support Tool to this folder.
1
2
3
4
5
1
2
3
4
5
Launch the application on the mobile device.
Tap the
Menu icon, then tap Settings.
6
6
7
Tap Setup.
Enter the Admin ID and Password and tap OK.
Default ID: admin
Default Password: admin
7
Tap Import from File.
Select the configuration file that was transferred to this device
in Step 5. Tap OK.
9
9
A pop-up will appear stating “Service started with a new config.”
11 To unlock the app, call the mobile device from a master station
in the system.
10
10
Tap App Server. Enter the IP Address and Port Number for
the App Server (RY-IP44). Refer to page11 for information on
setting up the App Server.
8
8
Android, Google Play, and the Google Play logo are trademarks of Google Inc.
App Installation and Setup for Android
Note: On Android devices running version 7.0 or newer, battery optimization must
be disabled for the IX Mobile app to maintain network connection.
16 | RY-IP44 Programming Manual
Aiphone Corporation
www.aiphone.com
[email protected]
800-692-0200
RY-IP44 Dimensions
4-1/8”
3-5/16”
Mounting:
The RY-IP44 adaptor mounts to an Aiphone
W-DIN11 mounting rail (sold separately).
Depth:
1-1/4”
Door release:
External signaling:
Inputs:
Connect a normally open (N/O) contact across any
input and ground.
Power:
Use a 9-30V DC (300mA @ 12VDC) power supply to
power the RY-IP44 adaptor. Use the Aiphone
PS-1225UL power supply (sold separately).
R1
NO
R3
NO
PT
Door
Strike
Bell
= Power Transformer (use proper power for the strike, mag lock, or external signaling device being used).
PS-1225UL
PT
PT
R2
NO
R4
NO
R1
NO
R3
NO
R2
NO
R4
NO
+
-
+
-
I1
I2
G
G
I3
I4
Input 1
Input 2
Input 3
Input 4
Ground {
{
{
{
{
Relay 1
Relay 2
Relay 3
Relay 4
{
{
{
{
Relay 1
Relay 2
Relay 3
Relay 4
{
Power
Relay contact rating: 30V DC, 0.5A.
FCC WARNING:
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference that may cause undesired operation.
•
For proper regulatory compliance, the drain wire should be disconnected at the power supply end of the cable.
•
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s
authority to operate the equipment.
0517 #95101