Endress+Hauser PROline promag 53 Safety Instructions
Read Online
Read the Endress+Hauser PROline promag 53 Safety Instructions online using the built-in PDF viewer.
Text of the manual
This document is an integral part of the following Operating Instructions:
Safety Instructions
XA00126D/06/EN/13.12
71195714
Ex documentation
Proline Promag 53
HART, PROFIBUS DP/PA, FOUNDATION Fieldbus, Modbus RS485
NEPSI Zone 1, Zone 21
• BA00047D, Proline Promag 53 HART
• BA00051D, Proline Promag 53 FOUNDATION Fieldbus
• BA00053D, Proline Promag 53 PROFIBBUS DP/PA
• BA00117D, Proline Promag 53 Modbus RS485
Contents
General warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Special conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
COC certificates of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Description of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Nameplates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Type code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Temperature table compact version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Temperature table remote version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas and dust explosion protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Design of measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable entries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connection of remote version connecting cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terminal assignment and connection data, power supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terminal assignment and connection data for signal circuits (intrinsically safe circuits) . . . . . . . . . . . . . . . . . . . 12
Terminal assignment and connection data for signal circuits (non-intrinsically safe circuits) . . . . . . . . . . . . . . . 14
Service adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Device fuse. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
0NEPSI Zone 1, Zone 21
Proline Promag 53
2
Endress+Hauser
General warnings
• For installation, use and maintenance of the flow meter, the instruction manual and the following standards
shall be observed:
– GB50257-1996 "Code for construction and acceptance of electric device for explosive atmospheres and
fire hazard electrical equipment installation engineering"
– GB3836.13-1997 "Electrical apparatus for explosive gas atmospheres – Part 13: Repair and overhaul for
apparatus used in explosive gas atmospheres"
– GB3836.15-2000 "Electrical apparatus for explosive gas atmospheres – Part 15: Electrical installations in
hazardous area (other than mines)"
– GB3836.16-2006 "Electrical apparatus for explosive gas atmospheres – Part 16: Inspection and
maintenance of electrical installation (other than mines)"
– GB15577-2007: Safety regulations for dust explosion prevention and protection". (Only if installed in
dust hazardous areas.)
– GB12476.2-2006 "Electrical apparatus for use in the presence combustible dust – Part 1-2: Electrical
apparatus protected by enclosures and surface temperature limitation – selection, installation and
maintenance" (only if installed in dust hazardous areas).
• The flow meter shall not be modified in order to ensure the explosion protection performance of the
equipment. Any change may impair safety.
• Installation, connection to the electricity supply, commissioning and maintenance of the devices must be
carried out by qualified specialists trained to work on Ex-rated devices.
• Compliance with all of the technical data of the device (see nameplate) is mandatory.
• Open the device only when it is de-energized (and after a delay of at least 10 minutes following shutdown
of the power supply) or in non-hazardous (classified) locations.
• It is not permissible to connect the service adapter whilst the atmosphere is considered to be explosive.
• Opening the transmitter housing and the connection housing of the remote version is only permitted for a
brief time. During this time, ensure that no dust or water enters the housing.
• To guarantee resistance to dust and water, the transmitter housing, the connection housing of the remote
version and the cable entries must be tightly sealed.
• The suitability of the device in the event of simultaneous occurrence of gas-air and dust-air mixtures
requires an additional assessment.
Special conditions
• The device must be integrated into the potential equalization system. Potential must be equalized along
the intrinsically safe sensor circuits. Further information is provided in the "Potential equalization" section
on Page 9.
• The sensors may only be used for those media, for which the wetted parts are known to be suitable.
• For the application of the transmitters in an ambient temperature of less than –20 °C suitable cables and
cable entries certified for this condition shall be used. Entry holes which are not needed, shall be closed by
stopping plugs separately certified for this purpose.
Installation instructions
• For terminals No. 20 to No. 27 of the transmitter, only devices with ratings Um 260 V and Im 500 mA
are allowed to be connected (does not apply to intrinsically safe circuits).
• The measuring device must only be used in the permitted temperature class.
The values of the individual temperature classes can be found in the temperature tables on Page 6.
For Zone 21: The surface temperature of the measuring device must not exceed 2/3 of the ignition
temperature of a dust cloud. The maximum surface temperature must maintain a safe distance of 75 °C to
the smolder temperature of a dust layer of 5 mm.
Example: Operation in temperature class T4 (135 °C) is, therefore, suitable for dust with an ignition
temperature of 202.5 °C (1.5 × 135 °C or 135 °C = 2/3 of 202.5 °C) and a smolder temperature of
210 °C (135 °C + 75 °C).
• The following applies when using the terminal compartment in type of protection "flameproof/Ex d":
Only cable entries and cable glands, which are approved by NEPSI in accordance with GB3836.1-2010 and
GB3836.2-2010 and which are suitable for an operating temperature of up to 80 °C, they shall be used.
• The following applies when using the terminal compartment in type of protection "increased safety/Ex e":
Only cable entries, cable glands and blanking plugs, which are approved by NEPSI in accordance with
GB3836.1-2010 and GB3836.3-2010 and which are suitable for an operating temperature of up to 80 °C
and for an ingress protection of IP67, they shall be used. Alternatively Ex e cable glands specified or provided
by Endress+Hauser Flowtec AG can be used. The cables must be installed in such a way, that they are fixed
in place in order to ensure adequate strain relief.
• Suitable cables and suitable, certified cable glands, cable entries and blanking plugs must be used for
measuring devices operated at temperatures below –20 °C.
• The cable entries and openings not used must be sealed tight with suitable components.
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
3
Installation instructions
(continued)
• Turning the local display:
the screw cap has to be removed before the local display can be turned, and this must be done with the
device de-energized (and after a delay of at least 10 minutes following shutdown of the power supply) or
when the area is known to be non-hazardous.
" Caution!
The explosion group for the measuring device can be IIC. However, it is reduced to IIB if the permitted,
external capacitance/inductance for the intrinsically safe communication circuits is increased (see Page 13).
# Warning!
For entity concept, the criteria for interconnection between the I/O circuits and the associated circuits is as
follow:
• Uo Ui
• Io Ii
• Po Pi
• Co Ci + Cc
• Lo Li + Lc
Cc and Lc stand for the distributed capacitance and distributed inductance of the cable.
Turning the transmitter housing
1.
Unscrew the grub screw.
2.
Rotate the transmitter housing cautiously clockwise until the end stop (end of the thread).
3.
Rotate the transmitter housing counter-clockwise (max. 360°) in the wanted position.
4.
Tighten the grub screw properly after each manipulation
# Warning!
Ensure that the grub screw is tightened properly.
A0006944
Fig. 1:
Turning the transmitter housing
COC certificates of
conformity
COC certificates of conformity
By affixing the certification number the product conforms with the following standards:
Certification numbers:
Inspection body
NEPSI, National Supervision and Inspection Centre for Explosion Protection and Safety of Instrumentation
Description of measuring
system
The measuring system consists of transmitters and sensors.
Two versions are available:
• Compact version: transmitters and sensors form a mechanical unit.
• Remote version: transmitters and sensors are installed separately and connected to each other via
connecting cables.
N
ic
ht
u
nt
e
r
S
p
a
n
n
un
g
öf
f
ne
n
K
e
e
p
c
o
v
er
ti
g
ht
w
h
il
e
ci
r
c
u
it
s
a
re
al
i
v
e
N
e
p
a
s
o
u
v
ri
r
l’
ap
p
ar
ei
l
s
o
u
s
t
e
n
si
o
n
K
e
e
p
co
v
e
r t
ig
ht
w
hi
l
e
ci
r
c
u
it
s
a
re
al
i
v
e
max. 360°
Nicht-eigensichere
Stromkreise durch
IP40-Abdeckung geschützt
Non-intrinsically safe
circuits Ip40 protected
Boucles de courant
sans sécurité intrinsèque
protégées par Ip40
1
2
3
4
• GB3836.1-4 – 2010
• GB3836.20 – 2010
• GB12476.1 – 2000
• GYJ12.1047X
0NEPSI Zone 1, Zone 21
Proline Promag 53
4
Endress+Hauser
Nameplates
The nameplates, which are mounted in a clearly visible position on the transmitter and sensor, contain all of
the relevant information about the measuring system.
A0008261
Fig. 2:
Example for nameplates of a transmitter and of a sensor
A
Transmitter nameplate
B
Sensor nameplate
1
Manufacturer / Certificate recipient
2
Transmitter or sensor type
3
Order code and serial number
4
Power supply, frequency and power consumption
5
Additional specification, e.g. ECC = Electrode cleaning circuitry, EPD = empty pipe detection,
R/B = reference electrode, etc. (only if present)
6
Available inputs/outputs
7
Space for additional information on special products
8
Year of manufacture
9
Type of enclosure protection
10 Type of protection
11 Number of the NEPSI certificate of conformity
12 Space for notes, e.g. delays, etc. (only if necessary)
13 Ambient temperature range
14 C-Tick symbol
15 NEPSI Symbol
16 Associated Ex documentation
17 Space for other approval specifications and certificates, e.g. PROFIBUS, etc. (only if present)
18 Calibration factor/zero point
19 Nominal diameter/nominal pressure
20 Fluid temperature range
21 Materials in contact with the medium
22 Measuring electrode material
23 Calibration tolerance
24 Direction of flow
A
B
Order Code:
Ser.No.:
TAG No.:
XXXXX-XXXXXXXXXXXX
12345678901
ABCDEFGHJKLMNPQRST
20-55VAC/16-62VDC
50-60Hz
15VA/W
IP67
XA...D/06/../....
4153 Reinach
Switzerland
2007
i
Promag 5X
I-OUT (HART), f-OUT
RELAY, STATUS-IN
N12895
1
3
13
12
9
10
11
16
14
17
15
2
4
6
7
8
18
20
21
2
3
1
8
14
16
15
-20°C(-4°F)
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
5
Type code
The type code describes the exact design and the equipment of the measuring system.
It can be read on the nameplate of the transmitter and sensor and is structured as follows:
Electronics (Item No. 2 in type code)
Sensor (Item No. 3 in type code)
Approvals (Item No. 12 in type code)
P
R
O
M
A
G
5
*
*
*
*
–
*
*
*
*
*
*
*
*
*
*
*
*
Pos. no.:
1 Instrument family
2 Electronics
3 Sensor
4 to 5 Nominal diameter
6 Hyphen
7 Lining/process connection
8 Process connection/seal
9 Electrodes / material
10 Calibration
11 Factory certificates
12 Approvals
13 Version (compact/remote)
14 Remote version cable
15 Type of cable entry
16 Display, operation, power
17 Software
18 Outputs/inputs
*
Transmitter
Type of explosion protection
3
Promag 53
• Transmitter electronics: [Ex ia] IIC
• Transmitter housing: Ex d or Ex de IIC
*
Sensor
Lining
W,
P,
H
Promag W
• Hard rubber
• Polyurethane
Promag P
• PFA
• PTFE
Promag H
• PFA
*
Type of explosion protection
Transmitter
Sensor
Remote version
Compact version with Ex ia
input/output
Compact version other
K 1) Ex de[ia Ga] IIC/IIB T6 Gb
DIP A21 Ta, T6 IP6X
Ex deia[ia Ga] IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
Ex deia IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
Ex eia IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
S 2) Ex de[ia Ga] IIC/IIB T6 Gb
DIP A21 Ta, T6 IP6X
Ex deia[ia Ga] IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
Ex deia IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
Ex eia IIC/IIB T1~T6 Gb
DIP A21 Ta, T6 IP6X
1) Terminal compartment in type of protection Ex d
2) Terminal compartment in type of protection Ex e
0NEPSI Zone 1, Zone 21
Proline Promag 53
6
Endress+Hauser
Type (compact/remote; Item No. 13 in type code)
Type of cable entry (Item No. 15 in type code)
Display, operation, power supply (Item No. 16 in type code)
Outputs/inputs (Item No. 18 in type code)
!Note!
A detailed explanation of these values, regarding the available outputs and inputs, as well as a description of
the associated terminal assignments and connection data can be found from Page 11 onwards.
Temperature table
compact version
Max. medium temperature [°C] for T1 ~ T6 in relation to the maximum ambient temperature Ta
1) with polyurethane lining; 2) with hard rubber lining
1) with PFA lining; 2) with PTFE lining
The minimum ambient temperature is –20 °C.
A version for ambient temperatures up to –40 °C is optionally available
*
Type
Min. ambient temperature Ta min
A, P, U
Compact
–20 °C
V, 6
–40 °C
G, N, T, W
Remote
–20 °C
7, 8
–40 °C
*
Thread form
A
M20 × 1.5
B
NPT ½"
C
G ½"
*
Thread form
A, C, E, G, P, R, 0, 2, 4, 7
85 – 260 V AC
B, D, F, H, Q, S, 1, 3, 5, 8
20 – 55 V AC/16 – 62 V DC
*
Type of protection
A, B, C, D, J, K, L, M, N, P, Q, V, 2, 4, 5, 7
non Ex ia (intrinsically safe) input /output
F, G, S, T
Ex ia (intrinsically safe) input /output
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*W**-************
25 to 1200 1)
+50 °C
50
50
50
50
50
50
50 to 2000 2)
+50 °C
80
80
80
80
80
80
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*P**-************
25 to 200 1)
+40 °C
80
95
130
150
150
150
15 to 600 2)
130
130
130
25 to 200 1)
+45 °C
80
95
130
130
130
130
15 to 600 2)
25 to 200 1)
+50 °C
80
95
95
95
95
95
15 to 600 2)
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*H**-************
2 to 150
+40 °C
80
95
130
150
150
150
+45 °C
80
95
130
130
130
130
+50 °C
80
95
95
95
95
95
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
7
Temperature table remote
version
Sensor
Max. medium temperature [°C] for T1 ~ T6 in relation to the maximum ambient temperature Ta
1) with polyurethane lining; 2) with hard rubber lining
1) with PFA lining; 2) with PTFE lining; 3) versions in IP 68 are limited to 130 °C.
The minimum ambient temperature is –20 °C.
A version for ambient temperatures up to –40 °C is optionally available.
Transmitter
The transmitter of the remote version has the temperature class T6 when installing into the Ex d housing up
to an ambient temperature of Ta = 60 °C.
The maximum ambient temperature range is –20 to +60 °C.
A version for ambient temperatures up to –40 °C is optionally available.
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*W**-************
25 to 1200 1)
+50 °C
50
50
50
50
50
50
50 to 2000 2)
+60 °C
80
80
80
80
80
80
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*P**-************
25 to 200 1)
+50 °C
80
95
130
150 3)
150 3)
150 3)
15 to 600 2)
130
130
130
25 to 200 1)
+60 °C
80
95
130
130
130
130
15 to 600 2)
DN
Ta
T6
(85 °C)
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
Promag 5*H**-************
2 to 150
+50 °C
80
95
130
150
150
150
2 to 25
+60 °C
80
95
130
130
130
130
40 to 150
80
95
130
150
150
150
0NEPSI Zone 1, Zone 21
Proline Promag 53
8
Endress+Hauser
Gas and dust explosion
protection
Determine the temperature class for gas in relation to the ambient Ta and medium temperature TM
Determine the maximum surface temperature for dust in relation to the max. ambient temperature Ta and
max. medium temperature TM
Example
Device: compact version, Promag 53 , DN 25, PTFE
Max. ambient temperature: Ta = 45°C
Max. medium temperature: TM = 110 °C
A0005216
Fig. 3:
Procedure for calculating the max. surface temperature
1.
In the associated temperature table (compact version), the selection of the measuring device
(Promag 53P), the nominal diameter (DN 25), the lining material (PTFE) and the ambient temperature
Ta (45 °C) determine the line in which the max. medium temperature can be found.
2.
The fluid temperature TM (110 °C), which is smaller or equal to the max. fluid temperature, determines
the column, i.e. the temperature class, for gas (110 °C 130 °C T4).
3.
The maximum temperature of the calculated temperature class corresponds to the maximum surface
temperature (T4 = 135 °C = maximum surface temperature for dust).
Design of measuring
system
A0005610
Fig. 4:
Design of the measuring system, compact/remote version
A
Transmitter housing (compact version)
B
Transmitter housing on connection housing, remote version
C
Sensor connection housing, remote version, Promag W/P
D
Sensor connection housing, remote version, Promag H, DN
E
Sensor connection housing, remote version, Promag H, DN 40
a
Screw terminal for connecting to the potential equalization
b
Connection compartment cover
c
Connecting cable, coil current cable
d
Connecting cable, signal cable
m to n see following chapter "Cable entries"
!Note!
Connection of remote version connecting cable Page 10
Promag 5*P**-************
DN
T
T6
(85 °C)
a
T5
(100 °C)
T4
(135 °C)
T3
(200 °C)
T2
(300 °C)
T1
(450 °C)
25...200 1)
2)
15...600
25...200 1)
15...600 2)
25...200 1)
2)
15...600
+40 °C
+45 °C
+50 °C
80
80
80
80
80
80
95
95
95
95
95
95
130
130
130
130
95
95
150
130
130
130
95
95
150
130
130
130
95
95
150
130
130
130
95
95
1) PFA;
PTFE
2)
DN 25
PTFE
Ta= 45 °C
TM = 110 °C
� 130 °C)
(
A
B
C
b
D
E
a
b
b
a
a
a
c
d
c
d
c
d
N
ic
h
t
u
nt
e
r
S
p
a
n
n
u
n
g
öf
f
n
e
n
K
e
e
p
c
o
v
e
r
ti
g
h
t
w
hi
le
ci
r
cu
it
s
a
re
a
li
v
e
N
e
p
a
s
o
uv
ri
r l
’a
p
p
ar
e
il
so
u
s
t
e
n
s
io
n
K
e
e
p
c
o
v
er
ti
gh
t
w
h
il
e
ci
rc
ui
ts
ar
e
a
li
v
e
N
ic
h
t
u
nt
e
r
S
p
a
n
n
u
n
g
ö
ff
n
e
n
K
e
e
p
c
o
v
er
ti
g
ht
w
hi
le
ci
rc
ui
ts
a
re
a
li
v
e
N
e
p
a
s
o
uv
ri
r l
’a
p
p
ar
ei
l
s
o
u
s
t
e
n
s
io
n
K
e
e
p
c
o
v
e
r
ti
g
ht
w
h
il
e
ci
r
cu
it
s
ar
e
a
li
v
e
m
m
n
m
n
n
n
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
9
Cable entries
• m for connection compartment (Ex d version): power supply cable and cable of the communication circuit
Choice of thread for cable entries M20 × 1.5, ½" NPT or G ½".
Make sure that the Ex d cable glands/entries are secured to prevent working loose and that the seals are
installed immediately adjacent to the housing.
• m for connection compartment (Ex e version): power supply cable and cable of the communication circuit
Choice of cable gland M20 × 1.5 or thread for cable entries ½" NPT or G ½".
The cables must be installed such that they are fixed in place. Adequate strain relief must be ensured.
• n for remote version connecting cable:
Choice of cable gland M20 × 1.5 or thread for cable entries ½" NPT or G ½"
# Warning!
The leak-tight of the cable glands and cable entries is to ensure.
Cable specification
You can find information about the cable specification in the associated Operating Instructions.
Potential equalization
• The transmitter (compact and remote version) is to be securely connected to the potential equalization
system using the screw terminal on the outside of the transmitter housing. Alternatively, the transmitter of
the compact version as of serial number 4Axxxxxx000 can be connected to the potential equalization
system via the pipeline if a ground connection via the pipeline according to regulations can be assured.
• When using the remote version, the connection housing of the sensor must be grounded via the external
screw terminal. Alternatively, the sensor can be integrated into the potential equalization via the pipeline
as long as the pipeline provides a ground connection conforming to regulations.
!Note!
Further information about potential equalization, shielding and grounding can be found in the associated
Operating Instructions.
Potential equalization with shield grounded at both sides for fieldbus version
A0005215
Fig. 5:
Example for connecting potential equalization lines
1
Distributor/T-Box
2
Bus devices for potentially explosive atmospheres
3.1 Bus terminator PROFIBUS PA and FOUNDATION Fieldbus
3.2 Bus terminator PROFIBUS DP and Modbus
4
Bus supply unit or automation system
4a
Potential equalization line is fed out into the safe area
!Note!
The length of the spur must be observed.
1
1
2
2
3.1
4
4a
EX
EX
R
C
3.2
R
GND
+5 V
R
R
0NEPSI Zone 1, Zone 21
Proline Promag 53
10
Endress+Hauser
Connection of remote
version connecting cable
A0005614
Fig. 6:
Connection of remote version connecting cable
A
Transmitter housing on connection housing, remote version
B
Sensor connection housing, remote version, Promag W/P
C
Sensor connection housing, remote version, Promag H, DN
D
Sensor connection housing, remote version, Promag H, DN 40
a
Ground terminals (are provided for connecting a potential equalization connection)
b
Connecting cable, coil circuit
c
Signal circuit connecting cable (electrodes)
n.c. not connected, insulated cable screening
Wire colors terminal number: 5/6 = brown, 7/8 = white, 4 = green, 37/38 = yellow
Terminal assignment and connection data
The connection of the remote version, between sensor and transmitter, is carried out in the explosion
protections Ex i (signal circuit) and Ex e (coil circuit).
When using the connecting cable supplied by Endress+Hauser, the intrinsic safety of the circuit is ensured at
a maximum cable length of 90 m (for IIC) and 200 m (for IIB).
" Caution!
Only preterminated connecting cables supplied by Endress+Hauser must be used.
Terminal
6
5
7
8
4
37
36
42
41
S1
E1
E2
S2
GND
E
S
2
1
Designation
Measured variable
Pipe
EPD
Signal circuit
Coil circuit
Functional values
U = 60 V
P = 2.5 W
Electric circuit
[Ex ia] IIC/IIB
Ex e
UO
37 V
IO
25 mA
PO
138 mW
LO
LO IIC = 50 mH / LO IIB = 200 mH
CO
CO IIC = 39 nF / CO IIB = 353 nF
A
B
b
C
D
c
b
c
a
b
b
c
6
5
5
7
7
8
4
4
37
37
36
42
42
41
41
E1 E2 GNDE
2
1
S1 E1 E2 S2GND E S
n.c.
n.c.
n.c.
n.c.
n.c.
n.c.
a
N
ic
h
t
u
nt
e
r
S
p
a
n
n
u
n
g
öf
f
n
e
n
K
e
e
p
c
o
v
e
r
ti
g
h
t
w
hi
le
ci
r
cu
it
s
a
re
a
li
v
e
N
e
p
a
s
o
uv
ri
r l
’a
p
p
ar
e
il
so
u
s
t
e
n
s
io
n
K
e
e
p
c
o
v
er
ti
gh
t
w
h
il
e
ci
rc
ui
ts
ar
e
a
li
v
e
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
11
Electrical connection
Connection compartment
Transmitter housing compact/remote version (terminal assignment, connection data Page 11 ff.)
Fig. 7:
Electrical connections
*)
Fixed communication boards (permanent assignment)
**) Flexible communication boards
a
Power supply cable (terminal assignment, connection data Page 11)
b
Signal cable (terminal assignment, connection data Page 12ff.)
c
Ground terminal for signal cable shield / fieldbus cable / RS485 line
d
Ground terminal for protective ground
e
Service adapter for connecting service interface FXA 193 (Fieldcheck, FieldCare)
f
Further connections:
– PROFIBUS DP *: Cable for external termination, optional (terminal assignment, connection data Page 11)
– PROFIBUS DP **/ Modbus RS485 */**: Signal cable (terminal assignment, connection data Page 12)
Terminal assignment and
connection data, power
supply
Terminal assignment and connection data
4 to 20 mA HART
A0005611
PROFIBUS PA Ex ia *
FOUNDATION Fieldbus *
A0005613
PROFIBUS DP */**
Modbus RS485 */**
A0005617
1
2
L1 (L+)
N (L–)
20
21
22
23
24
25
26
27
e
b
c
a
+
–
+
–
+
–
+
–
d
1
2
L1 (L+)
N (L–)
20
21
22
23
24
25
26
27
e
3
b
c
a
+
–
+
–
+
–
+
–
d
1
2
L1 (L+)
N (L–)
20
21
22
23
24
25
26
27
e
3
b
c
a
+
–
+
–
+
–
+
–
f
d
All transmitters
1 L (+)
2 N (–)
*
Designation
Supply voltage
Protective earth
Functional values
AC: U = 85 to 260 V;
AC: U = 20 to 55 V
DC: U = 16 to 62 V
Power consumption: 15 VA / 15 W
Caution!
Observe the
grounding plans
of the system!
Intrinsically safe circuit
no
Um
260 V AC
0NEPSI Zone 1, Zone 21
Proline Promag 53
12
Endress+Hauser
Terminal assignment and
connection data for signal
circuits (intrinsically safe
circuits)
!Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
A graphic representation of the electrical connections can be found on Page 11.
The communication circuits, option F and G, they meet all requirements for a FISCO Field Device
(IEC 60079-27).
Terminal assignment of transmitter 53***-***********F
Terminal assignment of transmitter 53***-***********G
Transmitter
Terminal no. (inputs/outputs)
20 (+)
21 (–)
22 (+)
23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
–
PROFIBUS PA
passive
PA +
PA –
Electric circuit
–
–
–
Ex ia
Safety-related
values
–
–
–
Ui
Ii
Pi
Li
Ci
FISCO
30 V DC
600 mA
8.5 W
10 μH
5 nF
Field device
Functional
values
–
–
–
galvanically isolated,
UBus
9 to 32 V DC
IBus
11 mA
IEC 61158-2 (MBP)
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
–
FOUNDATION Fieldbus
passive
FF +
FF –
Electric circuit
–
–
–
Ex ia
Safety-related
values
–
–
–
Ui
Ii
Pi
Li
Ci
FISCO
30 V DC
600 mA
8.5 W
10 μH
5 nF
Field device
Functional
values
–
–
–
galvanically isolated,
UBus
9 to 32 V DC
IBus
12 mA
IEC 61158-2 (MBP)
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
13
Terminal assignment of transmitter 53***-***********S
Terminal assignment of transmitter 53***-***********T
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
Pulse/frequency output,
passive
Current output HART,
active
Electric circuit
–
–
Ex ia
Ex ia
Safety-related
values
–
–
Ui
Ii
Pi
Li
Ci
30 V DC
500 mA
600 mW
negligible
6 nF
Uo
Io
Po
Lo IIC/IIB
Co IIC/IIB
1) Lo IIC/IIB
1) Co IIC/IIB
Ui
Ii
Pi
Li
Ci
21.8 V DC
90 mA
491 mW
4.1 mH/15 mH
160 nF/1160 nF
2 mH/10 mH
80 nF/300 nF
30 V DC 2)
10 mA 2)
0.3 W 2)
negligible
6 nF
Functional
values
–
–
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
active: 0/4 to 20 mA
RL < 400
RL HART 250
1) Permitted values in the event of simultaneous occurrence of concentrated inductances and capacitances.
2) The interconnection must be assessed according to the valid construction provisions.
Transmitter
Terminal no. (inputs/outputs)
20 (+) 21 (–) 22 (+) 23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Assignment
–
–
Pulse/frequency output,
passive
Current output HART,
passive
Electric circuit
–
–
Ex ia
Ex ia
Safety-related
values
–
–
Ui
Ii
Pi
Li
Ci
30 V DC
500 mA
600 mW
negligible
6 nF
Ui
Ii
Pi
Li
Ci
30 V DC
100 mA
1.25 W
negligible
6 nF
Functional
values
–
–
galvanically isolated,
passive: 30 V DC / 250 mA
Open Collector
Full scale frequency
2 to 5000 Hz
galvanically isolated,
passive: 4 to 20 mA
voltage drop 9 V
RL < [(Vp. supply – 9 V) ÷ 25 mA]
0NEPSI Zone 1, Zone 21
Proline Promag 53
14
Endress+Hauser
Terminal assignment and
connection data for signal
circuits (non-intrinsically
safe circuits)
!Note!
The following tables contain values/specifications, which are dependent on the type code (type of measuring
device). Please compare the following type code to the one shown on the nameplate of your measuring device.
A graphic representation of the electrical connections can be found on Page 11.
Terminal assignment
Transmitter
Terminal no. (inputs/outputs)
20 (+)
21 (–)
22 (+)
23 (–)
24 (+)
25 (–)
26 (+)
27 (–)
Non-convertible communication boards (fixed assignment)
53***-*…*A
–
–
Pulse/frequency output
Current output
HART
53***-*…*B
Relay output 2
Relay output 1
Pulse/frequency output
Current output
HART
53***-*…*J
–
–
External termination
PROFIBUS DP *
+5 V
DGND
B
A
53***-*…*K
–
–
–
FOUNDATION
Fieldbus
FF +
FF –
53***-*…*Q
–
–
Status input
Modbus RS485 *
B
A
Convertible communication boards
53***-*…*C
Relay output 2
Relay output 1
Pulse/frequency output
Current output
HART
53***-*…*D
Status input
Relay output
Pulse/frequency output
Current output
HART
53***-*…*L
Status input
Relay output 2
Relay output 1
Current output
HART
53***-*…*M
Status input
Pulse/frequency output Pulse/frequency output
Current output
HART
53***-*…*N
Current output
Pulse/frequency output
Status input
Modbus RS485 *
B
A
53***-*…*P
Current output
Pulse/frequency output
Status input
PROFIBUS DP *
B
A
53***-*…*V
Relay output 2
Relay output 1
Status input
PROFIBUS DP *
B
A
53***-*…*2
Relay output
Current output
Pulse/frequency output
Current output
HART
53***- *…*4
Current input
Relay output
Pulse/frequency output
Current output
HART
53***-*…*5
Status input
Current input
Pulse/frequency output
Current output
HART
53***-*…*7
Relay output 2
Relay output 1
Status input
Modbus RS485 *
B
A
Safety-related and functional values of signal circuits Page 15
* PROFIBUS DP, Modbus RS485:
– terminal 26 (+) B (RxD/TxD-P)
– terminal 27 (–) A (RxD/TxD-N)
Proline Promag 53
NEPSI Zone 1, Zone 21 0
Endress+Hauser
15
Safety-related and functional values of signal circuits
Signal circuits
Functional values
Safety-related values
Current output HART
galvanically isolated,
active/passive can be selected:
• active: 0/4 to 20 mA
RL < 700 , RL HART 250
• passive: 4 to 20 mA
Vs = 18 to 30 V DC, Ri 150
intrinsically safe
Um
Im
= no
= 260 V
= 500 mA
Current output
galvanically isolated,
active/passive can be selected:
• active: 0/4 to 20 mA
RL < 700
• passive: 4 to 20 mA
Vs = 18 to 30 V DC, Ri 150
Pulse/frequency output
galvanically isolated,
active/passive can be selected:
• active: 24 V DC / 25 mA
(max. 250 mA during 20 ms)
RL > 100
• passive: 30 V DC / 250 mA
Open Collector
Full scale frequency 2 to 10000 Hz
(fmax = 12500 Hz)
Status output
galvanically isolated,
Open Collector
max. 30 V AC / 250 mA
Relay output
galvanically isolated,
max. 30 V AC / 500 mA
max. 60 V DC / 100 mA
Current input
galvanically isolated,
active/passive can be selected:
• active: 4 to 20 mA
Ri 150
Uout = 24 V DC, short-circuit proof
• passive: 0/4 to 20 mA
Ri 150
Umax = 30 V DC
Status input
(53***-*...*D, L, M)
galvanically isolated,
3 to 30 V DC
Ri = 5 k
Status input
(53***-*...*N, P, Q, V, 7)
galvanically isolated,
Independent of polarity,
3 to 30 V DC
Ri = 3 k
PROFIBUS DP
galvanically isolated,
RS485 as per Standard EIA/TIA-485
FOUNDATION Fieldbus
galvanically isolated,
UBus = 9 to 32 V DC
IBus = 12 mA
IEC 61158-2 (MBP)
Modbus RS485
galvanically isolated,
RS485 as per Standard EIA/TIA-485
0NEPSI Zone 1, Zone 21
Proline Promag 53
16
Endress+Hauser
Service adapter
The service adapter is only used for connecting service interfaces approved by Endress+Hauser.
# Warning!
It is not permissible to connect the service adapter whilst the atmosphere is considered to be explosive.
Device fuse
# Warning!
Use only fuses of the following types; the fuses are installed on the power supply board:
• Voltage 20 to 55 V AC / 16 to 62 V DC:
fuse 2.0 A slow-blow, disconnect capacity 1500 A
(Schurter, 0001.2503 or Wickmann, Standard Type 181 2.0 A)
• Voltage 85 to 260 V AC:
fuse 0.8 A slow-blow, disconnect capacity 1500 A
(Schurter, 0001.2507 or Wickmann, Standard Type 181 0.8 A)
Technical Data
Dimensions
Please refer to the respective Technical Information for these dimensions:
• Promag 50W, 53W TI00046D
• Promag 50P, 53P TI00047D
• Promag 50H, 53H TI00048D
Weight
The weight of the Ex d version is approx. 2 kg greater than that of the standard version.