Endress+Hauser Cerabar S Operating Instructions Manual
Read Online
Read the Endress+Hauser Cerabar S Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Software version 02.10
Hardware version 02.00
Operating Instructions – Description of device functions
Cerabar S/Deltabar S/Deltapilot S
Pressure and Differential pressure transmitters
6
Cerabar S/Deltabar S/Deltapilot S
2
Overview documentation
Device
Documentation
Content
Remarks
Cerabar S
4 to 20 mA HART
Technical Information TI383P
Technical data
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA271P
– Identification
– Installation
– Wiring
– Operation
– Commissioning, Description of
Quick Setup menus
– Maintenance
– Trouble-shooting and spare parts
– Appendix: Illustration of menu
– The documentation is supplied with the
device.
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA274P
– Examples of configuration for
pressure and level measurement
– Description of parameters
– Trouble-shooting
– Appendix: Illustration of menu
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Brief Operating Instructions KA218P
– Wiring
– Operation without on-site
display
– Description of Quick Setup menus
– Operation HistoROM®/M-DAT
– The documentation is supplied with the
device. See cover of the terminal
compartment.
Functional Safety Manual SD190P
– Safety function with Cerabar S
– Behaviour in operation and failure
– Commissioning and iterative tests
– Settings
– Technical safety characteristic
quantities
– Management Summary
– The documentation is supplied with the
devices showing version "E" in feature 100
"Additional options 1" or in feature 110
"Additional options 2".
→ See also Technical Information TI383P,
chapter "Ordering information".
Cerabar S/Deltabar S/Deltapilot S
Overview documentation
3
Device
Documentation
Content
Remarks
Deltabar S
4 to 20 mA HART
Technical Information TI382P
Technical data
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA270P
– Identification
– Installation
– Wiring
– Operation
– Commissioning, Description of
Quick Setup menus
– Maintenance
– Trouble-shooting and spare parts
– Appendix: Illustration of menu
– The documentation is supplied with the
device.
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA274P
– Examples of configuration for
pressure, level and flow
measurement
– Description of parameters
– Trouble-shooting
– Appendix: Illustration of menu
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Brief Operating Instructions KA218P
– Wiring
– Operation without on-site
display
– Description of Quick Setup menus
– Operation HistoROM®/M-DAT
– The documentation is supplied with the
device. See cover of the terminal
compartment.
Functional Safety Manual SD189P
– Safety function with Deltabar S
– Behaviour in operation and failure
– Commissioning and iterative tests
– Settings
– Technical safety characteristic
quantities
– Management Summary
– The documentation is supplied with the
devices showing version "E" in feature 100
"Additional options 1" or in feature 110
"Additional options 2".
→ See also Technical Information TI382P,
chapter "Ordering information".
Cerabar S/Deltabar S/Deltapilot S
4
Device
Documentation
Content
Remarks
Deltapilot S
4 to 20 mA HART
Technical Information TI416P
Technical data
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA332P
– Identification
– Installation
– Wiring
– Operation
– Commissioning, Description of
Quick Setup menus
– Maintenance
– Trouble-shooting and spare parts
– Appendix: Illustration of menu
– The documentation is supplied with the
device.
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Operating Instructions BA274P
– Examples of configuration for
pressure and level measurement
– Description of parameters
– Trouble-shooting
– Appendix: Illustration of menu
– The documentation is located on the ToF Tool
CD. The CD is enclosed with every device
ordered with the "HistoROM/M-DAT"
option. The "HistoROM/M-DAT" option is
selected in the order code via feature 100
Additional option 1" or 110 "Additional
option 2", version "N".
– The documentation is also available via the
Internet. → See: www.endress.com →
Download
Brief Operating Instructions KA218P
– Wiring
– Operation without on-site
display
– Description of Quick Setup menus
– Operation HistoROM®/M-DAT
– The documentation is supplied with the
device. See cover of the terminal
compartment.
Functional Safety Manual SD213P
– Safety function with Deltapilot S
– Behaviour in operation and failure
– Commissioning and iterative tests
– Settings
– Technical safety characteristic
quantities
– Management Summary
– The documentation is supplied with the
devices showing version "E" in feature 100
"Additional options 1" or in feature 110
"Additional options 2".
→ See also Technical Information TI416P,
chapter "Ordering information".
Cerabar S/Deltabar S/Deltapilot S
Table of contents
5
Table of contents
1
Notes on use . . . . . . . . . . . . . . . . . . . . 6
1.1
Finding parameter description using ID numbers . . . 6
1.2
Finding function group using graphic representation 6
1.3
Finding parameter description using parameter names
(index) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2
Finding parameter description using
ID numbers . . . . . . . . . . . . . . . . . . . . . 7
3
Graphic representation of
function groups . . . . . . . . . . . . . . . . . 12
4
Pressure measurement. . . . . . . . . . . . 13
4.1
Calibration with reference pressure . . . . . . . . . . . . 13
4.2
Calibration without reference pressure . . . . . . . . . 14
5
Level measurement . . . . . . . . . . . . . . 16
5.1
Overview of level measurement . . . . . . . . . . . . . . 16
5.2
"Level Easy Pressure" level selection . . . . . . . . . . . 17
5.3
"Level Easy Height" level selection . . . . . . . . . . . . . 21
5.4
"Level Standard" level selection,
"Linear" level type . . . . . . . . . . . . . . . . . . . . . . . . 25
5.5
"Level Standard" level selection,
"Pressure Linearized" level type . . . . . . . . . . . . . . 29
5.6
"Level Standard" level selection,
"Height Linearized" level type . . . . . . . . . . . . . . . . 34
6
Flow measurement. . . . . . . . . . . . . . . 41
6.1
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.2
Totalizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7
Description of parameters . . . . . . . . . 44
8
Trouble-shooting . . . . . . . . . . . . . . . 131
8.1
Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
8.2
Response of outputs to errors . . . . . . . . . . . . . . . . 138
8.3
Confirming messages . . . . . . . . . . . . . . . . . . . . . . 139
9
Appendix . . . . . . . . . . . . . . . . . . . . . 139
9.1
Operating menu for on-site display, ToF Tool,
FieldCare and HART handheld terminal . . . . . . . . 139
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Notes on use
Cerabar S/Deltabar S/Deltapilot S
6
1
Notes on use
Section 7 describes all the parameters in order of how they appear in the menu. Sections 4 to 6
provide typical examples of configuration.
Sections 1.1 to 1.3 describe ways of finding a certain parameter description more easily.
1.1
Finding parameter description using ID numbers
Each parameter is shown on the on-site display with a unique identification number (ID). Section 2
lists all the parameters in numerical order. The page reference/link takes you to the parameter in
question.
In the ToF Tool, additional parameters and, to an extent, other parameters are displayed. These
parameters are not listed in Section 2. You can find these parameters by means of the index. → See
also Section 1.3.
1.2
Finding function group using graphic representation
All the function groups are shown in table form in Section 3. The page reference/link takes you to
the function group in question. In Section 7, all the parameters of a function group are compiled in
a table.
1.3
Finding parameter description using parameter names
(index)
The index lists all the parameters in alphabetical order. The page reference/link takes you to the
parameter in question.
Cerabar S/Deltabar S/Deltapilot S
Finding parameter description using ID numbers
7
2
Finding parameter description using
ID numbers
ID number
Parameter name
Description, see page
001
DENSITY UNIT – Level Selection "Level Easy Pressure"
64 or 97
003
HEIGHT UNIT
64
004
FULL CALIB. – QUICK SETUP
51
004
FULL CALIB. – Level Selection "Level Easy Pressure"
61
004
FULL CALIB. – Level Selection "Level Easy Height"
65
005
FULL PRESSURE
61
006
FULL HEIGHT
66
007
ADJUST DENSITY – Level Selection "Level Easy Height"
64 or 97
008
CALIBRATION MODE – Level Selection "Level Easy Pressure"
60
008
CALIBRATION MODE – Level Selection "Level Easy Height"
64
009
EMPTY HEIGHT
65
010
EMPTY CALIB. – QUICK SETUP
50
010
EMPTY CALIB. – Level Selection "Level Easy Pressure"
60 or 61
010
EMPTY CALIB. – Level Selection "Level Easy Height"
65
011
EMPTY PRESSURE
61
012
SET URV – Level Selection "Level Easy Pressure"
61
012
SET URV – Level Selection "Level Easy Height"
66
013
SET LRV – Level Selection "Level Easy Pressure"
61
013
SET LRV – Level Selection "Level Easy Height"
66
014
DOWNLOAD SELECT
125
015
FULL PRESSURE
See 1
1)
See Safety Manual SD189P for Deltabar S, SD190P for Cerabar S and SD213P for Deltapilot S.
016
EMPTY PRESSURE
See 1
017
FULL CALIB.
See 1
018
EMPTY CALIB.
See 1
020
LEVEL SELECTION
46
021
SET LRV
See 1
022
SET URV
See 1
023
OUTPUT UNIT – Level Selection "Level Easy Pressure"
60
023
OUTPUT UNIT – Level Selection "Level Easy Height"
64
025
PROCESS DENSITY – Level Selection "Level Easy Pressure"
97
036
PREAMBLE NUMBER
115
042
CURR. TRIM 20mA
130
043
OFFSET 4mA TRIM
130
044
OFFSET 20mA TRIM
130
045
CURR. TRIM 4mA
130
046
ALARM STATUS
127
047
ENTER RESET CODE
125
048
INSERT PIN No
125
050
LEVEL BEFORE LIN
122
055
CUST. TAG NUMBER
116
060
PRESS. ENG. UNIT
56, 59, 63, 67 or 92
075
CUSTOMER UNIT P
56, 59, 63, 67 or 92
079
LANGUAGE
45
245
SET LRV – "Pressure" measuring mode
48 or 56
246
SET URV – "Pressure" measuring mode
48 or 56
247
DAMPING VALUE
48, 51, 53, 57, 61, 66, 77, 81, 90 or 95
250
SENSOR SER. No.
119
251
Pmin SENS. DAMAGE
119
252
Pmax SENS. DAMAGE
119
254
OUTPUT CURRENT
112
264
SOFTWARE VERSION
116
266
HARDWARE REV.
116
270
SIM. CURRENT
127
271
HART MESSAGE
115
272
ADDITIONAL INFO.
116
301
PRESSURE – "Pressure" measuring mode
121
PRESSURE – "Level" measuring mode
121
PRESSURE – "Flow" measuring mode
122
305
LONG TAG NUMBER
116
Finding parameter description using ID numbers
Cerabar S/Deltabar S/Deltapilot S
8
ID number
Parameter name
Description, see page
309
GET LRV
57
310
GET URV
57
311
MAX. FLOW
52 or 95
313
UNIT VOLUME – "Linear" level type
71 or 75
UNIT VOLUME – "Pressure Linearized" level type
79
UNIT VOLUME – "Height Linearized" level type
84
314
EMPTY CALIB. – QUICK SETUP
50
EMPTY CALIB. – "Linear" level type
73
EMPTY CALIB. – "Height Linearized" level type
87
315
FULL CALIB. – QUICK SETUP
51
FULL CALIB. – "Pressure Linearized" level type
74
FULL CALIB. – "Height Linearized" level type
87
316
ADJUST DENSITY – "Linear" level type
74
ADJUST DENSITY – "Height Linearized" level type
88
ADJUST DENSITY– "Level" extended setup
97
317
CUST. UNIT FACT. P
56, 68 or 93
318
TEMP. ENG. UNIT – "Pressure" measuring mode
96
TEMP. ENG. UNIT – "Level" measuring mode
96
TEMP. ENG. UNIT – "Flow" measuring mode
98
319
CALIB. OFFSET
54
323
SET. L. FL. CUT-OFF
99
329
FACT. U. U. TOTAL. 1
108
330
FACT. U. U. TOTAL. 2
109
331
RESET TOTALIZER1
108
332
Pmin ALARM WINDOW
129
333
Pmax ALARM WINDOW
129
334
Tmin ALARM WINDOW
129
335
Tmax ALARM WINDOW
129
336
ALARM DELAY
128
339
DISPLAY CONTRAST
111
342
SET MAX. ALARM
113
343
SET MIN. CURRENT
113
345
BUS ADDRESS
114
350
DEVICE DESIGN.
116
351
DEVICE TYPE, Deltabar S
114
352
CONFIG RECORDER
117
354
DEVICE SERIAL No
116
357
PCB TEMPERATURE
117
358
ALLOWED MIN. TEMP
117
359
ALLOWED MAX. TEMP
117
360
MAT. PROC. CONN. +
118
361
MAT. PROC. CONN. -
118
362
SEAL TYPE
118
363
DIP STATUS
117
365
MAT. MEMBRANE
119
366
FILLING FLUID
120
367
SENSOR TEMP.
121 or 122
368
Tmin SENSOR
120
369
Tmax SENSOR
120
370
TANK CONTENT
122
375
SUPPRESSED FLOW
123
378
MEAS. VAL. TREND
121 or 122
380
COUNTER:P > Pmax
123
382
RESET PEAKHOLD
124
383
MAX. MEAS. PRESS.
123
386
ELECTR. SERIAL No
116
388
OUTPUT FAIL MODE
112
389
MEASURING MODE
45
390
LINEAR/SQROOT
113
391
UNIT FLOW
93
392
CALIBRATION MODE – "Linear" level type
73
CALIBRATION MODE – "Height Linearized" level type
87
397
LIN. EDIT MODE
101
398
TOTALIZER 1 UNIT – "Volume p. cond." flow type
107
399
TOTALIZER 2 UNIT – "Volume p. cond." flow type
108
400
NEG. FLOW TOT. 1
108
401
ACK. ALARM MODE
127
Cerabar S/Deltabar S/Deltapilot S
Finding parameter description using ID numbers
9
ID number
Parameter name
Description, see page
404
COUNTER:T > Tmax
123
409
OPERATING HOURS
125
413
SIMULATION MODE
126
414
SIM. PRESSURE
126
416
NEG. FLOW TOT. 2
109
419
MENU DESCRIPTOR
110
423
ALTERNATE DATA
110
432
MANUFACTOR ID
115
434
CORRECTED PRESS. – "Pressure" measuring mode
121
CORRECTED PRESS. – "Level" measuring mode
122
CORRECTED PRESS. – "Flow" measuring mode
122
442
LOW FLOW CUT-OFF
98
467
COUNTER:P < Pmin
123
469
MIN. MEAS. PRESS.
123
471
MAX. MEAS. TEMP.
123
472
COUNTER:T < Tmin
123
474
MIN. MEAS. TEMP.
123
476
SIM. ERROR NO.
127
480
ALARM DISPL. TIME
128
481
HART DATE
115
482
PROC. CONN. TYPE
117
484
PRESS. SENS LOLIM
119
485
PRESS. SENS HILIM
119
487
SENS H/WARE REV
120
488
PCB COUNT:T > Tmax
123
490
PCB MAX. TEMP.
123
492
PCB COUNT:T < Tmin
123
494
PCB MIN. TEMP.
123
500
ACK. ALARM
128
549
MEASURING TABLE (display)
103
549
EDITOR TABLE, LINE-NUMB (enter values)
102
550
EDITOR TABLE, X-VAL. (enter values)
102
551
EDITOR TABLE, Y-VAL. (enter values)
102, 102
563
POS. INPUT VALUE
48, 50 or 54
564
LAST DIAG. CODE
127
570
Pmax PROC. CONN.
117
571
MASS FLOW UNIT
94
581
SENSOR MEAS.TYPE
119
584
SENSOR PRESSURE – "Pressure" measuring mode
121
SENSOR PRESSURE – "Level" measuring mode
122
SENSOR PRESSURE – "Flow" measuring mode
122
591
MINIMUM SPAN
119
595
SELECT ALARMTYPE
128
597
ALT. CURR. OUTPUT
113
600
SELECT ALARMTYPE
128
603
RESET ALL ALARMS
128
607
CUST. UNIT FACT. V – "Linear" level type
72
CUST. UNIT FACT. V – "Pressure Linearized" level type
79
CUST. UNIT FACT. V – "Height Linearized" level type
85
608
CUSTOMER UNIT V – "Linear" level type
71
CUSTOMER UNIT V – "Pressure Linearized" level type
79
CUSTOMER UNIT V – "Height Linearized" level type
85
609
CUST. UNIT FACT. F
95
610
CUSTOMER UNIT F
94
627
TOT. 1 USER UNIT
108
628
TOT. 2 USER UNIT
109
634
MAX PRESS. FLOW
53 or 95
637
SET LRV – "Flow" extended setup
99
638
SET URV – "Flow" extended setup
99
639
SIM.FLOW VALUE
126
640
FLOW-MEAS. TYPE
93
652
TOTALIZER 1
123
655
TOTAL. 1 OVERFLOW
123
657
TOTALIZER 2
123
658
TOTAL. 2 OVERFLOW
123
660
STD. FLOW UNIT
94
661
NORM FLOW UNIT
93
Finding parameter description using ID numbers
Cerabar S/Deltabar S/Deltapilot S
10
ID number
Parameter name
Description, see page
662
TOTALIZER 1 UNIT – "Mass" flow type
107
663
TOTALIZER 2 UNIT – "Mass" flow type
108
664
TOTALIZER 1 UNIT – "Gas. std. conditions" flow type
107
665
TOTALIZER 2 UNIT – "Gas. std. conditions" flow type
108
666
TOTALIZER 1 UNIT – "Gas. norm conditions" flow type
107
667
TOTALIZER 2 UNIT – "Gas. norm conditions" flow type
108
679
MEASURED VALUE – "Pressure"
121
MEASURED VALUE – "Level"
121
MEASURED VALUE – "Flow"
122
685
POS. ZERO ADJUST
48, 50, 52 or 54
688
MAIN DATA FORMAT
110
694
CURR. CHARACT. – "Pressure"
112
695
CURR. CHARACT. – "Flow"
112
696
CURR. CHARACT. – "Height"
112
699
DEVICE REVISION
115
703
CUST. UNIT FACT. M – "Linear" level type
73
CUST. UNIT FACT. M – "Pressure Linearized" level type
80
CUST. UNIT FACT. M – "Height Linearized" level type
86
704
CUSTOMER UNIT M – "Linear" level type
72
CUSTOMER UNIT M – "Pressure Linearized" level type
80
CUSTOMER UNIT M – "Height Linearized" level type
86
705
CUST. UNIT FACT. H – "Linear" level type
71 or 76
CUST. UNIT FACT. H – "Height Linearized" level type
84 or 89
706
CUSTOMER UNIT H – "Linear" level type
70 or 76
CUSTOMER UNIT H – "Height Linearized" level type
84 or 89
708
HEIGHT UNIT – "Linear" level type
70 or 76
HEIGHT UNIT – "Height Linearized" level type
83 or 88
709
MASS UNIT – "Linear" level type
72
MASS UNIT – "Pressure Linearized" level type
80
MASS UNIT – "Height Linearized" level type
85
710
EMPTY PRESSURE – "Linear" level type
74
EMPTY PRESSURE – "Height Linearized" level type
87
711
FULL PRESSURE – "Linear" level type
74
FULL PRESSURE – "Height Linearized" level type
87
712
LEVEL MAX
86
713
TANK CONTENT MAX
101
714
SIM. LEVEL
126
715
SIM. TANK CONT.
127
717
MEASURING TABLE (selection)
103
718
LEVEL MODE
68
719
SET LRV – "Level" basic setup
77
720
SET URV – "Level" basic setup
77
755
LEVEL MIN
86
759
TANK CONTENT MIN
100
760
ASSIGN CURRENT
113
761
HYDR. PRESS MAX.
81
762
SET LRV – "Level" extended setup
97
763
SET URV – "Level" extended setup
98
764
CURR. CHARACT. – "Tank content"
112
770
EDITOR TABLE (continue entry)
102
775
HYDR. PRESS MIN.
80
802
DEVICE TYPE, Cerabar S
114
804
LIN. MEASURAND
70
805
LINd. MEASURAND
79
806
COMB. MEASURAND
83
808
TABLE SELECTION
101
809
EDITOR TABLE (select table)
101
810
ADJUSTED DENSITY – "Linear" level type
74
ADJUSTED DENSITY – "Height Linearized" level type
87
811
PROCESS DENSITY
97
812
DENSITY UNIT – "Linear" level type
74
DENSITY UNIT – "Height Linearized" level type
88
813
100 % POINT – "Linear" level type
77
100 % POINT – "Height Linearized" level type
89
Cerabar S/Deltabar S/Deltapilot S
Finding parameter description using ID numbers
11
ID number
Parameter name
Description, see page
814
ZERO POSITION – "Linear" level type
77
ZERO POSITION – "Height Linearized" level type
90
815
TANK DESCRIPTION
103
831
HistoROM AVAIL.
125
832
HistoROM CONTROL
126
836
SAFETY LOCKSTATE
See 1
1)
See Safety Manual SD189P for Deltabar S, SD190P for Cerabar S and SD213P for Deltapilot S.
SAFETY LOCK
838
SAFETY PASSWORD
See 1
840
DIGIT SETS
111
841
DIGIT SETS
See 1
844
ACK. ALARM MODE
See 1
845
MEASURING MODE
See 1
847
CALIB. OFFSET
See 1
848
MAX. FLOW
See 1
849
MAX PRESS. FLOW
See 1
850
LOW FLOW CUT-OFF
See 1
851
SET. L. FL. CUT-OFF
See 1
852
SET LRV
See 1
853
SET URV
See 1
854
LINEAR/SQROOT.
See 1
855
DAMPING VALUE
See 1
856
CONF. PASSWORD
See 1
858
TANK VOLUME
75
859
TANK HEIGHT
76
875
CURRENT OUTPUT
See 1
Graphic representation of function groups
Cerabar S/Deltabar S/Deltapilot S
12
3
Graphic representation of function groups
!
Note!
The "Flow" measuring mode is only available for the Deltabar S differential pressure transmitter. The
groups marked with "*" are only displayed for Deltabar S.
1st selection level
2nd selection level (groups)
Function groups
Description,
see page
LANGUAGE
LANGUAGE (079)
→
45
MEASURING MODE
MEASURING MODE (389)
→
45
QUICK SETUP pressure
→
47
QUICK SETUP level
→
49
QUICK SETUP flow*
→
52
OPERATING MENU (555)
→ SETTINGS (557)
→ POSITION ADJUSTMENT
→
53
→ BASIC SETUP pressure
→
55
→ BASIC SETUP level,
"Level Easy Pressure"
→
58
→ BASIC SETUP level,
"Level Easy Height"
→
62
→ BASIC SETUP level,
"Level Easy Standard"
→
67
→ BASIC SETUP flow*
→
91
→ EXTENDED SETUP pressure
→
96
→ EXTENDED SETUP level
→
96
→ EXTENDED SETUP
flow*
→
98
→ LINEARISATION –
on-site display
→
100
→ LINEARISATION –
ToF Tool, HART handheld terminal
→
103
→ TOTALIZER SETUP *
→
107
→ SAFETY CONFIRM.
→
See 1
→ DISPLAY (558)
→
110
→ OUTPUT (559)
→
112
→ TRANSMITTER INFO (560)
→ HART DATA
→
114
→ TRANSMITTER DATA
→
116
→ PROCESS CONNECTION
→
117
→ SENSOR DATA
→
119
→ PROCESSINFO (561)
→ PROCESS VALUES pressure
→
120
→ PROCESS VALUES level
→
121
→ PROCESS VALUES flow*
→
122
→ PEAK HOLD INDICATOR
→
123
→ OPERATING
→
125
→ DIAGNOSTICS (562)
→ SIMULATION
→
126
→ MESSAGES
→
127
→ USER LIMITS
→
129
→ SERVICE (561)
→ SYSTEM 2
→
130
1)
See Safety Manual SD189P for Deltabar S, SD190P for Cerabar S and for SD213P Deltapilot S.
Cerabar S/Deltabar S/Deltapilot S
Pressure measurement
13
4
Pressure measurement
4.1
Calibration with reference pressure
Example:
In this example, a device with a 500 mbar sensor is configured for the 0...+300 mbar measuring
range, i.e. 0 mbar and 300 mbar are assigned to the 4 mA value and 20 mA value respectively.
Prerequisite:
• The pressure values 0 mbar and 300 mbar can be specified. The device is already installed, for
example.
!
Note!
• See also Operating Instructions Deltabar S (BA270P), Section 6.6 "Differential pressure
measurement", Cerabar S (BA271P), Section 6.4 "Pressure measurement" or Deltapilot S
(BA332P), Section 6.5 "Pressure measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 55, Table 7: BASIC SETUP.
• For a description of further relevant parameters, see
– Page 96, Table 15: EXTENDED SETUP
– Page 120, Table 25: PROCESS VALUES.
Description
1
Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and
filled with fluid. See Operating Instructions BA270P,
Section 6.6.
P01-PMD75xxx-19-xx-xx-xx-000
P01-xxxxxxxx-05-xx-xx-xx-010
Fig. 1:
Calibration with reference pressure
1
See table, step 6.
2
See table, step 7.
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
3
If necessary, select the "Pressure" measuring mode via
the MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
4
On-site display:
Select BASIC SETUP function group.
Menu path: GROUP SELECTION → OPERATING
MENU → SETTINGS → BASIC SETUP
5
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
6
The pressure for the lower range value (4 mA value) is
present at the device, here 0 mbar for example.
Select GET LRV parameter.
Confirm value present. The pressure value present is
assigned to the lower current value (4 mA).
+
–
20
4
I
[mA]
0
300
p
[mbar]
➀
➁
Cerabar S/Deltabar S/Deltapilot S
14
!
Note!
• You can also specify a customer-specific unit. See parameter description for PRESS. ENG. UNIT
(→ Page 56).
4.2
Calibration without reference pressure
Example:
In this example, a device with a 400 mbar sensor is configured for the 0...+300 mbar measuring
range, i.e. 0 mbar and 300 mbar are assigned to the 4 mA value and 20 mA value respectively.
Prerequisite:
• This is a theoretical calibration, i.e. the pressure values for the
lower range and upper range value are known.
!
Note!
• See also Operating Instructions Deltabar S (BA270P), Section 6.6 "Differential pressure
measurement", Cerabar S (BA271P), Section 6.4 "Pressure measurement" or Deltapilot S
(BA332P), Section 6.5 "Pressure measurement".
• Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. → To perform a
position adjustment see also Page 53, Table 6: Position adjustment.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 55, Table 7: BASIC SETUP.
• For a description of further relevant parameters, see
– Page 96, Table 15: EXTENDED SETUP
– Page 120, Table 27: PROCESS VALUES.
7
The pressure for the upper range value (20 mA value) is
present at the device, here 300 mbar for example.
Select GET URV parameter.
Confirm value present. The pressure value present is
assigned to the upper current value (20 mA).
8
Result:
The measuring range is set for 0...+300 mbar.
Description
Cerabar S/Deltabar S/Deltapilot S
Pressure measurement
15
!
Note!
• You can also perform calibration without reference pressure by means of the QUICK SETUP
menu. → See Page 47 ff, Table 3: QUICK SETUP menu.
• You can also specify a customer-specific unit. See parameter description for PRESS. ENG. UNIT
(→ Page 56).
Description
1
If necessary, select the "Pressure" measuring mode via
the MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
P01-PMP71xxx-19-xx-xx-xx-000
P01-xxxxxxxx-05-xx-xx-xx-010
Fig. 2:
Calibration without reference pressure
1
See table, step 4.
2
See table, step 5.
2
On-site display:
Select BASIC SETUP function group.
Menu path: GROUP SELECTION → OPERATING
MENU → SETTINGS → BASIC SETUP
3
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
4
Select SET LRV parameter.
Enter value, here 0 mbar, for the SET LRV parameter
and confirm. This pressure value is assigned to the lower
current value (4 mA).
5
Select SET URV parameter.
Enter value, here 300 mbar, for the SET URV parameter
and confirm. This pressure value is assigned to the upper
current value (20 mA).
6
Result:
The measuring range is set for 0...+300 mbar.
20
4
I
[mA]
0
300
p
[mbar]
➀
➁
Cerabar S/Deltabar S/Deltapilot S
16
5
Level measurement
5.1
Overview of level measurement
Measuring task
LEVEL
SELECTION/
LEVEL MODE
Measured
variable options
Description
Comment
Measured value display
The measured variable is
in direct proportion to the
measured pressure.
Calibration is performed
by entering two pressure-
level value pairs.
LEVEL SELECTION:
Level Easy Pressure
Via OUTPUT UNIT
parameter: %, level,
volume or mass
units.
– Calibration with
reference pressure –
wet calibration, see
Page 17, Section 5.2.1
– Calibration without
reference pressure – dry
calibration, see Page 19,
Section 5.2.2
– Incorrect entries are
possible
– SIL mode possible
– Customised units are
not possible
The measured value display
and the LEVEL BEFORE
LIN parameter show the
measured value.
The measured variable is
in direct proportion to the
measured pressure.
Calibration is performed
by entering the density
and two height-level value
pairs.
LEVEL SELECTION:
Level Easy Height
Via OUTPUT UNIT
parameter: %, level,
volume or mass
units.
– Calibration with
reference pressure –
wet calibration, see
Page 21, Section 5.3.1
– Calibration without
reference pressure – dry
calibration, see Page 23,
Section 5.3.2
– Incorrect entries are
possible
– SIL mode not possible
– Customised units are
not possible
The measured value display
and the LEVEL BEFORE
LIN parameter show the
measured value.
The measured variable is
in direct proportion to the
measured pressure.
LEVEL SELECTION:
Level standard/
LEVEL MODE:
Linear
Via LIN.
MEASURAND
parameter:
– % (Level)
– Level
– Volume
– Mass
– Calibration with
reference pressure –
wet calibration, see
Page 25, Section 5.4.1
– Calibration without
reference pressure – dry
calibration, see Page 27,
Section 5.4.2
– Incorrect entries are
rejected by the device
– SIL mode not possible
– Customised level,
volume and mass units
are possible
The measured value display
and the LEVEL BEFORE
LIN parameter show the
measured value.
The measured variable is
not in direct proportion to
the measured pressure as,
for example, with
containers with a conical
outlet. A
linearisation table must be
entered for the calibration.
LEVEL SELECTION:
Level standard/
LEVEL MODE:
Pressure Linearized
Via LINd
MEASURAND
parameter:
– Pressure + %
– Pressure +
Volume
– Pressure + Mass
– Calibration with
reference pressure:
semiautomatic entry of
linearisation table, see
Page 29, Section 5.5.1
– Calibration without
reference pressure:
manual entry of
linearisation table, see
Page 32, Section 5.5.2
– Incorrect entries are
rejected by the device
– SIL mode not possible
– Customised level,
volume and mass units
are possible
The measured value display
and the TANK CONTENT
parameter show the
measured value.
– Two measured variables
are required or
– The container shape is
given by value pairs,
such as height and
volume.
The 1st measured variable
%-height or height must be
in direct proportion to the
measured pressure. The
2nd measured variable
volume, mass or % must
not be in direct proportion
to the measured pressure.
A linearisation table must
be entered for the 2nd
measured variable. The
2nd measured variable is
assigned to the 1st
measured variable by
means of this table.
LEVEL SELECTION:
Level standard/
LEVEL MODE:
Height Linearized
Via COMB.
MEASURAND
parameter:
– Height + Volume
– Height + Mass
– Height + %
– %-Height +
Volume
– %-Height + Mass
– %-Height + %
– Calibration with
reference pressure: wet
calibration and
semiautomatic entry of
linearisation table, see
Page 34, Section 5.6.1
– Calibration without
reference pressure: dry
calibration and manual
entry of linearisation
table, see Page 38,
Section 5.6.2
– Incorrect entries are
rejected by the device
– SIL mode not possible
– Customised level,
volume and mass units
are possible
The measured value display
and the TANK CONTENT
parameter show the 2nd
measured value (volume,
mass or %).
The LEVEL BEFORE LIN
parameter displays the 1st
measured value (%-height
or height).
Cerabar S/Deltabar S/Deltapilot S
Level measurement
17
5.2
"Level Easy Pressure" level selection
5.2.1
Calibration with reference pressure – wet calibration
Example:
In this example, the level in a tank should be measured in m3. The maximum level is 3 m. The
pressure range is set to 0 to 300 mbar.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled or emptied.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• The values entered for EMPTY CALIB./FULL CALIB. and SET LRV/SET URV must have a
minimum interval of 1% for the "Level Easy Pressure" level mode. The value will be rejected with
a warning message if the values are too close together. Further limit values are not checked; i.e.
the values entered must be appropriate for the sensor and the measuring task so that the
measuring device can measure correctly.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 58, Table 8: LEVEL SELECTION "Level Easy Pressure"
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Deltabar S: Before you configure the device for your
application, the pressure piping must be cleaned and
filled with medium. See Operating Instructions BA270P,
Section 6.5.1
P01-PMP75xxx-19-xx-xx-xx-008
Fig. 3:
Calibration with reference pressure –
wet calibration
1
See Table, Step 9.
2
See Table, Step 10.
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
3
If necessary, select the "Level" measuring mode via the
MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP→ MEASURING MODE
4
If necessary, select "Level Easy Pressure" level mode
using the LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
➀
➁
0 mbar
300 mbar
3 m
0 m
Cerabar S/Deltabar S/Deltapilot S
18
!
Note!
1.
You can also perform calibration with reference pressure by means of the QUICK SETUP
menu. → See Page 49 ff, Table 4: QUICK SETUP menu.
2.
You also have the possibility of specifying customised pressure units via the PRESS. ENG. UNIT
parameter (→ Page 59).
3.
For this level mode, the measured variables %, level, volume and mass are available. → See
also parameter description for OUTPUT UNIT, Page 60.
4.
For operation using the on-site display, the parameters EMPTY CALIB. (→ Page 61) and FULL
CALIB. (→ Page 61) also show the respective pressure present at the device. For operation
using the ToF Tool und HART handheld terminal, the pressure present at the device is
displayed in the PROCESS VALUES group (menu path: OPERATING MENU→
PROCESSINFO → PROCESS VALUES).
5
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
P01-xxxxxxxx-05-xx-xx-xx-011
P01-xxxxxxxx-05-xx-xx-xx-014
Fig. 4:
Calibration with reference pressure –
wet calibration
1
See Table, Step 9.
2
See Table, Step 10.
3
See Table, Step 11.
4
See Table, Step 12.
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
7
Select a level unit via the OUTPUT UNIT parameter,
here m for example.
8
Select the "Wet" option by means of the CALIBRATION
MODE parameter.
9
Hydrostatic pressure for the lower calibration point is
present at the device, here 0 mbar for example.
Select EMPTY CALIB. parameter.
Enter the level value, here 0 m for example. Confirm the
value to assign the pressure value present to the lower
level value.
10
Hydrostatic pressure for the upper calibration point is
present at the device, here 300 mbar for example.
Select FULL CALIB. parameter.
Enter the level value, here 3 m for example. Confirm the
value to assign the pressure value present to the upper
level value.
11
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
12
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
13
Result:
The measuring range is set for 0 to 3 m.
Description
3
0
h
[m]
0
300
p
[mbar]
➀
➁
20
4
I
[mA]
0.5
4.5
h
[m]
➂
➃
Cerabar S/Deltabar S/Deltapilot S
Level measurement
19
5.2.2
Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in litres (l). The maximum volume is
1000 l (litres), and the maximum height is 4 m. The density of the fluid is
1 kg/dm3. The device is mounted below the level lower range value.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the pressure and volume values for the lower and upper
calibration point must be known.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• The values entered for EMPTY CALIB./FULL CALIB. and SET LRV/SET URV must have a
minimum interval of 1% for the "Level Easy Pressure" level mode. The value will be rejected with
a warning message if the values are too close together. Further limit values are not checked; i.e.
the values entered must be appropriate for the sensor and the measuring task so that the
measuring device can measure correctly.
• Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. → To perform a
position adjustment see also Page 53, Table 6: Position adjustment.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 58, Table 8: LEVEL SELECTION "Level Easy Pressure"
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Select the "Level" measuring mode via the MEASURING
MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP→ MEASURING MODE
P01-PMC71xxx-19-xx-xx-xx-000
Fig. 5:
Calibration without reference pressure –
dry calibration
1
See Table, Step 10.
2
See Table, Step 11.
3
See Table, Step 12.
4
See Table, Step 13.
2
If necessary, select "Level Easy Pressure" level mode
using the LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
3
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
1000 l
0.5 m
➁
4 m
0 l
ρ = 1 kg
dm3
➀
Cerabar S/Deltabar S/Deltapilot S
20
!
Note!
1.
For this level mode, the measured variables %, level, volume and mass are available. → See
also parameter description for OUTPUT UNIT, Page 60.
2.
You also have the possibility of specifying customised pressure units via the PRESS. ENG. UNIT
parameter (→ Page 59).
4
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
P01-xxxxxxxx-05-xx-xx-xx-026
P01-xxxxxxxx-05-xx-xx-xx-028
Fig. 6:
Calibration with reference pressure –
wet calibration
1
See Table, Step 7.
2
See Table, Step 8.
3
See Table, Step 9.
4
See Table, Step 10.
5
See Table, Step 11.
6
See Table, Step 12.
5
Select a volume unit via the OUTPUT UNIT parameter,
here l (litres) for example..
6
Select the "Dry" option by means of the CALIBRATION
MODE parameter.
7
Enter the volume value for the lower calibration point
via the EMPTY CALIB. parameter, here 0 l for example.
8
Enter the pressure value for the lower calibration point
via the EMPTY PRESSURE parameter, here 50 mbar for
example.
9
Enter the volume value for the upper calibration point
via the FULL CALIB. parameter, here 1000 l for
example.
10
Enter the pressure value for the upper calibration point
via the FULL PRESSURE parameter, here 450 mbar for
example.
11
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
12
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
13
Result:
The measuring range is set for 0 to 1000 l.
Description
1000
0
V
[l]
50
450
p
[mbar]
➀
➁
➂
➃
20
4
I
[mA]
0
1000
V
[l]
➄
➅
Cerabar S/Deltabar S/Deltapilot S
Level measurement
21
5.3
"Level Easy Height" level selection
5.3.1
Calibration with reference pressure – wet calibration
Example:
In this example, the volume in a tank should be measured in l (litres). The maximum volume is
1000 l (litres), and the maximum height is 4 m. The density of the fluid is 1 kg/dm3. The device is
mounted below the level lower range value.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled or emptied.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• The values entered for EMPTY CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE,
EMPTY HEIGHT/FULL HEIGHT and SET LRV/SET URV must have a minimum interval of 1%
for the "Level Easy Height" level mode. The value will be rejected with a warning message if the
values are too close together. Further limit values are not checked; i.e. the values entered must
be appropriate for the sensor and the measuring task so that the measuring device can measure
correctly.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 62, Table 9: LEVEL SELECTION "Level Easy Height"
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Deltabar S: Before you configure the device for your
application, the pressure piping must be cleaned and
filled with medium. See Operating Instructions BA270P,
Section 6.5.1
P01-PMC71xxx-19-xx-xx-xx-001
Fig. 7:
Calibration with reference pressure –
wet calibration
1
See Table, Steps 10 and 11.
2
See Table, Step 12.
3
See Table, Step 13.
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
3
Select the "Level" measuring mode via the MEASURING
MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP→ MEASURING MODE
4
If necessary, select the "Level Easy Height" level mode
using the LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
4
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
1000 l
0.5 m
4 m
0 l
ρ = 1 kg
dm3
➁
➀
➂
Cerabar S/Deltabar S/Deltapilot S
22
!
Note!
1.
For this level mode, the measured variables %, level, volume and mass are available. → See
also parameter description for OUTPUT UNIT, Page 64.
2.
You also have the possibility of specifying customised pressure units via the PRESS. ENG. UNIT
parameter (→ Page 63).
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
P01-xxxxxxxx-05-xx-xx-xx-029
P01-xxxxxxxx-05-xx-xx-xx-030
P01-xxxxxxxx-05-xx-xx-xx-031
Fig. 8:
Calibration with reference pressure –
wet calibration
1
See Table, Steps 10 and 11.
2
See Table, Step 12.
3
See Table, Step 13.
4
See Table, Step 14.
5
See Table, Step 15.
7
Select a volume unit via the OUTPUT UNIT parameter,
here l (litres) for example..
8
Select a height unit via the HEIGHT UNIT parameter,
here m for example.
9
Select the "Wet" option via the CALIBRATION MODE
parameter.
10
Select a density unit via the DENSITY UNIT parameter,
here kg/dm3 for example.
11
Enter the density of the fluid using the ADJUST
DENSITY parameter, here 1 (litre) for example.
12
Enter the volume value for the lower calibration point
via the EMPTY CALIB. parameter, here 0 l for example.
(The currently measured hydrostatic pressure is
displayed as height, here 0.5 m for example.)
13
Enter the volume value for the upper calibration point
via the FULL CALIB. parameter, here 1000 l for
example. (The currently measured hydrostatic pressure
is displayed as height, here 4.5 m for example.)
14
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
15
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
16
Result:
The measuring range is set for 0 to 1000 l.
Description
4.5
0.5
h
[m]
50
450
p
[mbar]
h =
p
ρ · g
ρ = 1 kg
dm3
➀
1000
0
V
[l]
0.5
4.5
➁
➂
h =
p
ρ · g
h
[m]
20
4
I
[mA]
0
1000
V
[l]
➃
➄
Cerabar S/Deltabar S/Deltapilot S
Level measurement
23
5.3.2
Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in l (litres). The maximum volume is
1000 l, and the maximum height is 4 m. The density of the fluid is 1 kg/dm3. The device is mounted
below the level lower range value.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration i.e. the height and volume values for the lower and upper
calibration point must be known.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• The values entered for EMPTY CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE,
EMPTY HEIGHT/FULL HEIGHT and SET LRV/SET URV must have a minimum interval of 1%
for the "Level Easy Height" level mode. The value will be rejected with a warning message if the
values are too close together. Further limit values are not checked; i.e. the values entered must
be appropriate for the sensor and the measuring task so that the measuring device can measure
correctly.
• Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. → To perform a
position adjustment see also Page , Table 6: Position adjustment.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 62, Table 9: LEVEL SELECTION "Level Easy Height"
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Select the "Level" measuring mode via the MEASURING
MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP→ MEASURING MODE
P01-PMC71xxx-19-xx-xx-xx-007
Fig. 9:
Calibration without reference pressure –
dry calibration
1
See Table, Step 11.
2
See Table, Steps 13 and 14.
3
See Table, Steps 15 and 16.
2
If necessary, select "Level Easy Height" level mode using
the LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
3
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
1000 l
0.5 m
➂
➁
4 m
0 l
ρ = 1 kg
dm3
➀
Cerabar S/Deltabar S/Deltapilot S
24
!
Note!
1.
For this level mode, the measured variables %, level, volume and mass are available. → See
also parameter description for OUTPUT UNIT, Page 64.
2.
You also have the possibility of specifying customised pressure units via the PRESS. ENG. UNIT
parameter (→ Page 63).
4
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
P01-xxxxxxxx-05-xx-xx-xx-029
P01-xxxxxxxx-05-xx-xx-xx-032
P01-xxxxxxxx-05-xx-xx-xx-033
Fig. 10:
Calibration with reference pressure –
wet calibration
1
See Table, Steps 8 and 9.
2
See Table, Step 10.
3
See Table, Step 11.
4
See Table, Step 12.
5
See Table, Step 13.
6
See Table, Step 14.
7
See Table, Step 15.
5
Select a volume unit via the OUTPUT UNIT parameter,
here l (litres) for example..
6
Select a height unit via the HEIGHT UNIT parameter,
here m for example.
7
Select the "Wet" option via the CALIBRATION MODE
parameter.
8
Select a density unit via the DENSITY UNIT parameter,
here kg/dm3 for example.
9
Enter the density of the fluid using the ADJUST
DENSITY parameter, here 1 (litre) for example.
10
Enter the volume value for the lower calibration point
via the EMPTY CALIB. parameter, here 0 l for example.
11
Enter the height value for the lower calibration point via
the EMPTY HEIGHT parameter, here 0.5 mbar for
example.
12
Enter the volume value for the upper calibration point
via the FULL CALIB. parameter, here 1000 l (litres) for
example.
13
Enter the height value for the upper calibration point via
the FULL HEIGHT parameter, here 4.5 mbar for
example.
14
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
15
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
16
Result:
The measuring range is set for 0 to 1000 l (litres).
Description
4.5
0.5
h
[m]
50
450
p
[mbar]
h =
p
ρ · g
ρ = 1 kg
dm3
➀
1000
0
V
[l]
0.5
4.5
➁
➂
h =
p
ρ · g
h
[m]
➃
➄
20
4
I
[mA]
0
1000
V
[l]
➅
➆
Cerabar S/Deltabar S/Deltapilot S
Level measurement
25
5.4
"Level Standard" level selection,
"Linear" level type
5.4.1
Calibration with reference pressure – wet calibration
Example:
In this example, the level in a tank should be measured in m3. The maximum level is 3 m. The
pressure range is set to 0 to 300 mbar.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• The tank can be filled or emptied.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 67, Table 10: BASIC SETUP
– Page 70, Table 11: BASIC SETUP – "Linear" level type.
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and the
device filled with fluid. See Operating Instructions
BA270P, Section 6.5.1
P01-PMC71xxx-19-xx-xx-xx-006
Fig. 11:
Calibration with reference pressure –
wet calibration
1
See table, step 11.
2
See table, step 12.
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
3
If necessary, select the "Level" measuring mode via the
MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
4
If necessary, select "Level Standard" level mode using the
LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
450 mbar
0.5 m
4 m
50 mbar
ρ = 1 kg
dm3
➁
➀
Cerabar S/Deltabar S/Deltapilot S
26
!
Note!
1.
You can also perform calibration with reference pressure by means of the QUICK SETUP
menu. → See Page 49 ff, Table 4: QUICK SETUP menu.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 70), UNIT VOLUME (→ Page 71) and MASS UNIT
(→ Page 72).
3.
For this level type, the measured variables %, level, volume and mass are available.
→ See Page 70 ff.
4.
The EMPTY PRESSURE (→ Page 74) and FULL PRESSURE (→ Page 74) parameters display
the pressure values belonging to the EMPTY CALIB. and FULL CALIB. parameters.
5
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
P01-xxxxxxxx-05-xx-xx-xx-034
P01-xxxxxxxx-05-xx-xx-xx-014
Fig. 12:
Calibration with reference pressure –
wet calibration
1
See table, step 11.
2
See table, step 12.
3
See table, step 13.
4
See table, step 14.
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
7
Select the "Linear" option by means of the LEVEL MODE
parameter.
8
Select the "Level" option by means of the LIN.
MEASURAND parameter.
9
Select a level unit via the HEIGHT UNIT parameter, here
m for example.
10
Select the "Wet" option by means of the CALIBRATION
MODE parameter.
11
The pressure for the lower calibration point is present at
the device, here 50 mbar for example.
Select EMPTY CALIB. parameter.
Enter the level value, here 0 m for example. Confirm the
value to assign the pressure value present to the lower
level value.
12
The pressure for the upper calibration point is present at
the device, here 450 mbar for example.
Select FULL CALIB. parameter.
Enter the level value, here 3 m for example. Confirm the
value to assign the pressure value present to the upper
level value.
13
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
14
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
15
Result:
The measuring range is set for 0...3 m.
Description
4
0
h
[m]
50
450
p
[mbar]
➀
➁
20
4
I
[mA]
0.5
4.5
h
[m]
➂
➃
Cerabar S/Deltabar S/Deltapilot S
Level measurement
27
5.4.2
Calibration without reference pressure – dry calibration
Example:
In this example, the volume in a tank should be measured in m3. The maximum volume is 5 m3
and the maximum height 4 m. The density of the fluid is 1 kg/dm3. The device is mounted below
the level lower range value.
Prerequisite:
• The measured variable is in direct proportion to the pressure.
• This is a theoretical calibration, i.e. the tank volume, tank height and density of the fluid are
known.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• Due to the orientation of the device, there may be a shift in the measured value, i.e. when the
container is empty, the MEASURED VALUE parameter does not display zero. → To perform a
position adjustment see also Page , Table 6: Position adjustment.
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 67, Table 10: BASIC SETUP
– Page 70, Table 11: BASIC SETUP – "Linear" level type.
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 26: PROCESS VALUES.
Description
1
Select the "Level" measuring mode via the MEASURING
MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
P01-PMP75xxx-19-xx-xx-xx-003
Fig. 13:
Calibration without reference pressure –
dry calibration
1
See table, step 9.
2
See table, step 10.
3
See table, step 11.
4
See table, step 12.
2
If necessary, select "Level Standard" level mode using the
LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
3
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
4 m
–0.5 m
➂
➃
➁
ρ = 1 kg
dm3
V = 5 m3
➀
Cerabar S/Deltabar S/Deltapilot S
28
!
Note!
1.
For this level type, the measured variables %, level, volume and mass are available.
→ See Page 70 ff.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 70), UNIT VOLUME
(→ Page 71) and MASS UNIT (→ Page 72).
3.
A level value is assigned to the lower and upper current value by means of the SET LRV
(→ Page 77) and SET URV (→ Page 77) parameters respectively. Once you have selected the
"Dry" calibration mode, the error message A711 "LRV or URV out of edit limits" can appear.
The error message goes out as soon as level values which are within the editing limits are
entered for the SET LRV and SET URV parameters.
By means of the ENTER RESET CODE parameter (→ Page 125), you can use the code 2710
to automatically set the SET LRV and SET URV parameters to level values which are within
the editing limits.
4
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
P01-xxxx xxxx-19-xx-xx-xx-012
Fig. 14:
Current output calibration
5
See table, step 13.
6
See table, step 14.
5
Select the "Linear" option by means of the LEVEL MODE
parameter.
6
Select the "Volume" option by means of the LIN.
MEASURAND parameter.
7
Select a volume unit via the UNIT VOLUME parameter,
here m3 for example.
8
Select the "Dry" option by means of the CALIBRATION
MODE parameter. See also the following note, point 3.
9
Enter the value for density via the ADJUST DENSITY
parameter, here 1 kg/dm3 for example.
10
Enter the tank volume via the TANK VOLUME
parameter, here 5 m3 for example.
11
Enter the tank height via the TANK HEIGHT parameter,
here 4 m for example.
12
Enter the level offset via the ZERO POSITION
parameter, here –0.5 m for example.
13
Set the value for the lower current value (4 mA) by
means of the SET LRV parameter.
14
Set the value for the upper current value (20 mA) by
means of the SET URV parameter.
15
Result:
The measuring range is set for 0...5 m3.
Description
20
4
I
[mA]
0
5
V
[m ]
3
➀
➁
Cerabar S/Deltabar S/Deltapilot S
Level measurement
29
5.5
"Level Standard" level selection,
"Pressure Linearized" level type
5.5.1
Semiautomatic entry of the linearisation table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
Prerequisite:
• The tank can be filled. The linearisation characteristic must rise continuously.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 67, Table 10: BASIC SETUP
– Page 78, Table 11: BASIC SETUP – "Pressure Linearized" level type
– Page 100, Table 18: LINEARISATION – on-site operation
– Page 103, Table 19: LINEARISATION – ToF Tool, HART handheld terminal.
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 26: PROCESS VALUES.
Description
1
Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and
filled with fluid. See Operating Instructions BA270P,
Section 6.5.1.
P01-PMP75xxx-19-xx-xx-xx-002
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
Carry out basic setup:
3
If necessary, select the "Level" measuring mode via the
MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
4
If necessary, select "Level Standard" level mode using the
LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
3.5
0
0
350
V
[m ]
3
p
[mbar]
Cerabar S/Deltabar S/Deltapilot S
30
5
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
7
Select the "Pressure Linearized" option by means of the
LEVEL MODE parameter. See also the following note,
point 3.
8
Select the "Volume" option by means of the LINd.
MEASURAND parameter.
9
Select a volume unit via the UNIT VOLUME parameter,
here m3 for example.
10
Select HYDR. PRESS MIN. parameter.
Enter the minimum hydrostatic pressure to be expected,
here 0 mbar for example.
11
Select HYDR. PRESS MAX .
Enter the maximum hydrostatic pressure to be expected.
Carry out linearisation:
12
Change the function group:
Menu path: (GROUP SELECTION →) OPERATING
MENU → SETTINGS → LINEARISATION
13
Select TANK CONTENT MIN parameter.
Specify the minimum tank contents to be expected, here
0 m3 for example.
14
Select TANK CONTENT MAX parameter.
Specify the maximum tank contents to be expected, here
3.5 m3 for example.
15
On-site display:
Select the "Editor table" option by means of the TABLE
SELECTION parameter.
16
Select the "Semiautomatic" option by means of the LIN.
EDIT MODE parameter.
17
Select the "New table" option by means of the EDITOR
TABLE parameter.
Description
Cerabar S/Deltabar S/Deltapilot S
Level measurement
31
!
Note!
1.
For this level type, the measured variables %, volume and mass are available.
→ See Page 78 ff.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 79), UNIT VOLUME (→ Page 79) and MASS UNIT
(→ Page 80).
18
Enter linearisation table (min. 2 points, max. 32 points).
P01-xxxxxxxx-05-xx-xx-xx-015
P01-xxxxxxxx-05-xx-xx-xx-016
Fig. 15:
Semiautomatic entry of the linearisation
table
1
See table, step 10.
2
See table, step 11.
3
See table, step 13.
4
See table, step 14.
5
See table, steps 15 – 19.
6
See the following note, point 4.
7
See the following note, point 4
Fill the tank to the height of the 1st point.
LINE-NUMB: confirm value displayed.
X-VAL.: the hydrostatic pressure present is displayed.
On-site display, ToF Tool:
The X-VAL. displayed is saved by confirming the Y-
value. See following line, Y-VAL.
HART handheld terminal:
Confirm X-VAL. displayed.
Y-VAL.: enter the volume value, here 0 m3 for example,
and confirm the value.
19
On-site display:
If you want to enter another point for the linearisation
table, select the "Next point" option and enter the point
as described in step 18.
If you want to finish entering the values and activate the
linearisation table, select the "Accept input table" option.
ToF Tool, FieldCare, HART handheld terminal:
You can enter further points for the linearisation table as
explained in step 18. Once all the points have been
entered, the table must be activated by means of the
TAB. ACTIVATE parameter.
19
Result:
The linearisation table has been entered.
Description
➀
3.5
0
0
350
V
[m ]
3
p
[mbar]
➂
➁
➃
➄
20
4
I
[mA]
0
3.5
V
[m ]
3
➆
➅
Cerabar S/Deltabar S/Deltapilot S
32
3.
Once you have selected the "Pressure Linearized" level type, the warning message "W710 Set
span too small. Not allowed." can appear. At this stage the linearisation table already consists
of two points as standard. It could be the case that the 2nd value, and thus the highest X-VAL.
of the linearisation table, is smaller than the minimum span permitted (→ MINIMUM SPAN,
Page 119). The message goes out as soon as the highest X-VAL. is larger than the minimum
span.
4.
A level value is assigned to both the lower and upper current value with the SET LRV
(→ Page 97) and SET URV (→ Page 98) parameters. If you enter values for TANK CONTENT
MIN (→ Page 100 or 104) and TANK CONTENT MAX (→ Page 101 or 104), the SET LRV
and SET URV parameters are also changed. If you want to assign values other than those for
TANK CONTENT MIN and TANK CONTENT MAX to the lower and upper current values,
the desired values must be entered for SET LRV and SET URV.
5.5.2
Manual entry of the linearisation table
Example:
In this example, the volume in a tank with a conical outlet should be measured in m3.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearisation table are known.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 67, Table 10: BASIC SETUP
– Page 78, Table 12: BASIC SETUP – "Pressure Linearized" level type
– Page 100, Table 18: LINEARISATION – on-site operation
– Page 103, Table 19: LINEARISATION – ToF Tool, HART handheld terminal.
• For a description of further relevant parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Perform basic setup as per Section 5.3.1, steps 2 to 10.
P01-PMP75xxx-19-xx-xx-xx-002
Carry out linearisation:
2
Change the function group:
Menu path: (GROUP SELECTION →) OPERATING
MENU → SETTINGS → LINEARISATION
3
Select TANK CONTENT MIN parameter .
Specify the minimum tank contents to be expected, here
0 m3 for example.
4
Select TANK CONTENT MAX parameter .
Specify the maximum tank contents to be expected, here
3.5 m3 for example.
3.5
0
0
350
V
[m ]
3
p
[mbar]
Cerabar S/Deltabar S/Deltapilot S
Level measurement
33
!
Note!
1.
For this level type, the measured variables %, volume and mass are available.
→ See Page 78 ff.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 79), UNIT VOLUME (→ Page 79) and MASS UNIT
(→ Page 80).
3.
Once you have selected the "Pressure Linearized" level type, the warning message "W710 Set
span too small. Not allowed." can appear. At this stage the linearisation table already consists
of two points as standard. It could be the case that the 2nd value, and thus the highest X-VAL.
of the linearisation table, is smaller than the minimum span permitted (→ MINIMUM SPAN,
Page 119). The message goes out as soon as the highest X-VAL. is larger than the minimum
span.
4.
A level value is assigned to both the lower and upper current value with the SET LRV
(→ Page 97) and SET URV (→ Page 98) parameters. If you enter values for TANK CONTENT
MIN (→ Page 100 or 104) and TANK CONTENT MAX (→ Page 101 or 104), the SET LRV
and SET URV parameters are also changed. If you want to assign values other than those for
TANK CONTENT MIN and TANK CONTENT MAX to the lower and upper current values,
the desired values must be entered for SET LRV and SET URV.
5
On-site display:
Select the "Editor table" option by means of the TABLE
SELECTION parameter.
P01-xxxxxxxx-05-xx-xx-xx-015
P01-xxxxxxxx-05-xx-xx-xx-016
Fig. 16:
Manual entry of the linearisation table
1
See Section 5.3.1, table, step 9.
2
See Section 5.3.1, table, step 10.
3
See table, step 3.
4
See table, step 4.
5
See table, steps 5 – 9.
6
See the following note, point 4.
7
See the following note, point 4.
6
Select the "Manual" option by means of the LIN. EDIT
MODE parameter.
7
Select the "New table" option by means of the EDITOR
TABLE parameter.
8
Enter linearisation table (min. 2 points, max. 32 points).
LINE-NUMB: confirm value displayed.
X-VAL.: enter the pressure value and confirm.
Y-VAL.: enter the volume value, here 0 m3 for example,
and confirm.
9
On-site display
If you want to enter another point for the linearisation
table, select the "Next point" option and enter the point
as described in step 8.
If you want to finish entering the values and activate the
linearisation table, select the "Accept input table" option.
ToF Tool, FieldCare, HART handheld terminal:
You can enter further points for the linearisation table as
explained in step 8. Once all the points have been
entered, the table must be activated by means of the
TAB. ACTIVATE parameter.
10
Result:
The linearisation table has been entered.
Description
➀
3.5
0
0
350
V
[m ]
3
p
[mbar]
➂
➁
➃
➄
20
4
I
[mA]
0
3.5
V
[m ]
3
➆
➅
Cerabar S/Deltabar S/Deltapilot S
34
5.6
"Level Standard" level selection,
"Height Linearized" level type
5.6.1
Wet calibration and semiautomatic entry of the linearisation
table
Example:
In this example, the height and the volume should be measured at the same time.
Prerequisite:
• The tank can be filled. The linearisation characteristic must rise continuously.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 67, Table 10: BASIC SETUP
– Page 83, Table 13: BASIC SETUP – "Height Linearized" level type
– Page 100, Table 18: LINEARISATION – on-site operation
– Page 103, Table 19: LINEARISATION – ToF Tool, HART handheld terminal.
• For a description of further parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
1
Deltabar S: before configuring the device for your
application, the pressure piping must be cleaned and
filled with fluid. See Operating Instructions BA270P,
Section 6.5.1
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
Perform calibration for the 1st measured variable:
3
If necessary, select the "Level" measuring mode via the
MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
4
If necessary, select "Level Standard" level mode using the
LEVEL SELECTION parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE "Level" → LEVEL SELECTION
ToF Tool, FieldCare, HART handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE "Level" →
LEVEL SELECTION
5
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION →OPERATING MENU →
SETTINGS → BASIC SETUP
6
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
Cerabar S/Deltabar S/Deltapilot S
Level measurement
35
7
Select the "Height Linearized" option by means of the
LEVEL MODE parameter.
P01-PMP75xxx-19-xx-xx-xx-004
P01-xxxxxxxx-05-xx-xx-xx-017
Fig. 17:
Calibrating the 1st measured variable
1
See table, step 11.
2
See table, step 12.
3
See table, step 14.
4
See Table, step 15.
8
Select the "Height + Volume" option by means of the
COMB. MEASURAND parameter.
9
Select the unit for the 1st measured value via the
HEIGHT UNIT parameter, here m for example.
10
Select the unit for the 2nd measured variable via the
UNIT VOLUME parameter, here m3 for example.
12
Select LEVEL MIN parameter.
Enter the minimum level to be expected, here 0 m for
example.
13
Select LEVEL MAX parameter.
Enter the maximum level to be expected, here 3 m for
example.
14
Select the "Wet" option via the CALIBRATION MODE
parameter (calibration mode for the 1st measured
variable).
15
The pressure for the lower calibration point is present at
the device, here 0 mbar for example.
Select EMPTY CALIB. parameter.
Enter the level value, here 0 m for example. Confirm the
value to assign the pressure value present to the lower
level value.
16
The pressure for the upper calibration point is present at
the device, here 300 mbar for example.
Select FULL CALIB. parameter.
Enter the level value, here 3 m for example. Confirm the
value to assign the pressure value present to the upper
level value.
17
Result:
The calibration for the 1st measured variable is carried
out.
Description
➂
➃
➀
➁
p
[mbar]
➂
➀
➁ ➃ 3
0
h
[m]
0
300
Cerabar S/Deltabar S/Deltapilot S
36
Perform linearisation (calibration for the 2nd
measured variable)
P01-PMP75xxx-19-xx-xx-xx-005
P01-xxxxxxxx-05-xx-xx-xx-018
P01-xxxxxxxx-05-xx-xx-xx-019
Fig. 18:
Calibrating the 2nd measured variable
5
See table, step 18.
6
See table, step 19.
7
See table, steps 20 – 24.
8
See the following note, point 4.
9
See the following note, point 4.
16
Change the function group.
Menu path: (GROUP SELECTION →) OPERATING
MENU → SETTINGS → LINEARISATION
17
Select TANK CONTENT MIN parameter.
Specify the minimum tank contents to be expected, here
0 m3 for example.
18
Select TANK CONTENT MAX parameter.
Specify the maximum tank contents to be expected, here
5 m3 for example.
19
On-site display:
Select the "Editor table" option by means of the TABLE
SELECTION parameter.
20
Select the "Semiautomatic" option by means of the LIN.
EDIT MODE parameter.
21
Select the "New table" option by means of the EDITOR
TABLE parameter.
22
Enter linearisation table (min. 2 points, max. 32 points).
Fill the tank to the height of the 1st point.
LINE-NUMB: confirm value displayed.
X-VAL.: the hydrostatic pressure present is measured
and converted to the corresponding level and displayed.
On-site display, ToF Tool:
The X-VAL. displayed is saved by confirming the
Y-value. See following line, Y-VAL.
HART handheld terminal:
Confirm X-VAL. displayed.
Y-VAL.: enter the volume value, here 0 m3 for example,
and confirm the value.
23
On-site display
If you want to enter another point for the linearisation
table, select the "Next point" option and enter the point
as described in step 23.
If you want to finish entering the values and activate the
linearisation table, select the "Accept input table" option.
ToF Tool, HART handheld terminal:
You can enter further points for the linearisation table as
explained in step 23. Once all the points have been
entered, the table must be activated by means of the
TAB. ACTIVATE parameter.
24
Result:
– The linearisation table has been entered.
– The measured value display and the
TANK CONTENT parameter display the 2nd
measured value (here the volume).
– The LEVEL BEFORE LIN parameter displays the 1st
measured value (here the height). See also the
following note, point 5.
Description
5
0
0
3
V
[m ]
3
h
[m]
5
0
0
3
V
[m ]
3
h
[m]
➄
➆
➅
20
4
I
[mA]
0
5
V
[m ]
3
➈
➇
Cerabar S/Deltabar S/Deltapilot S
Level measurement
37
!
Note!
1.
For this level type, the measured variables "Height + %", "Height + Volume", "Height + Mass",
"%-Height + %", "%-Height + Volume" and "%-Height + Mass" are available. → See Page 79 ff.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 83), UNIT VOLUME (→ Page 84) and MASS UNIT
(→ Page 85).
3.
Once you have selected the "Pressure Linearized" level type, the warning message "W710 Set
span too small. Not allowed." can appear. At this stage the linearisation table already consists
of two points as standard. It could be the case that the 2nd value, and thus the highest X-VAL.
of the linearisation table, is smaller than the minimum span permitted (→ MINIMUM SPAN,
Page 119). The message goes out as soon as the highest X-VAL. is larger than the minimum
span.
4.
A level value is assigned to both the lower and upper current value with the SET LRV
(→ Page 97) and SET URV (→ Page 98) parameters.
You can use the ASSIGN CURRENT parameter (→ Page 113) to specify whether the current
output should depict the 1st or 2nd measured variable. Depending on the setting of the
ASSIGN CURRENT parameter, enter the following values for SET LRV and SET URV:
– ASSIGN CURRENT = tank content (factory setting) ⇒ %-value, volume value or
mass value
– ASSIGNMENT = height ⇒ level value
The following applies for the setting ASSIGN CURRENT "Tank content":
If you enter values for TANK CONTENT MIN (→ Page 100 or 104) and TANK CONTENT
MAX (→ Page 101 or 104), the SET LRV and SET URV parameters are also changed. If you
want to assign values other than those for TANK CONTENT MIN and TANK CONTENT MAX
to the lower and upper current values, the desired values must be entered for SET LRV and
SET URV.
The following applies for the setting ASSIGN CURRENT "Height":
If you enter values for LEVEL MIN (→ Page 86) and LEVEL MAX (→ Page 86), the SET LRV
and SET URV parameters are also changed. If you want to assign values other than those for
LEVEL MIN and LEVEL MAX to the lower and upper current values, the desired values must
be entered for SET LRV and SET URV.
5.
You can use the MENU DESCRIPTOR parameter (→ Page 110) to specify which measured
value should be displayed on the on-site display.
Cerabar S/Deltabar S/Deltapilot S
38
5.6.2
Dry calibration and manual entry of the linearisation table
Example:
In this example, the height and the volume should be measured at the same time.
Prerequisite:
• This is a theoretical calibration, i.e. the points for the linearisation table are known.
!
Note!
• See also Operating Instructions for Deltabar S (BA270P) or Cerabar S (BA271P), Section 6.5
"Level measurement" or Deltapilot S (BA332P), Section 6.4 "Level measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 67, Table 10: BASIC SETUP
– Page 83, Table 12: BASIC SETUP – "Height Linearized" level type
– Page 100, Table 18: LINEARISATION – on-site operation
– Page 103, Table 19: LINEARISATION – ToF Tool, HART handheld terminal.
• For a description of further parameters, see
– Page 96, Table 16: EXTENDED SETUP
– Page 121, Table 28: PROCESS VALUES.
Description
Perform calibration for the 1st measured variable:
P01-PMP75xxx-19-xx-xx-xx-005
1
Perform calibration as per Section 5.4.1, steps 3 to 12.
2
Select the "Dry" option via the CALIBRATION MODE
parameter (calibration mode for the 1st measured
variable).
3
Enter the density of the fluid via the ADJUST DENSITY
parameter, here 1 kg/dm3 for example.
4
If necessary, enter a level offset via the ZERO POSITION
parameter, here 0 m for example.
5
Result:
The calibration for the 1st measured variable is carried
out.
5
0
0
3
V
[m ]
3
h
[m]
Cerabar S/Deltabar S/Deltapilot S
Level measurement
39
!
Note!
1.
For this level type, the measured variables "Height + %", "Height + Volume", "Height + Mass",
"%-Height + %", "%-Height + Volume" and "%-Height + Mass" are available. → See Page 79 ff.
2.
You can also specify customer-specific units. See parameter description for PRESS. ENG. UNIT
(→ Page 67), HEIGHT UNIT (→ Page 83), UNIT VOLUME (→ Page 84) and MASS UNIT
(→ Page 85).
3.
Once you have selected the "Pressure Linearized" level type, the warning message "W710 Set
span too small. Not allowed." can appear. At this stage the linearisation table already consists
of two points as standard. It could be the case that the 2nd value, and thus the highest X-VAL.
of the linearisation table, is smaller than the minimum span permitted (→ MINIMUM SPAN,
Page 119). The message goes out as soon as the highest X-VAL. is larger than the minimum
span.
Perform linearisation (calibration for the 2nd
measured variable)
P01-xxxxxxxx-05-xx-xx-xx-018
P01-xxxxxxxx-05-xx-xx-xx-019
Fig. 19:
Calibrating the 2nd measured variable
5
See table, step 7.
6
See table, step 8.
7
See table, steps 9 – 13.
8
See the following note, point 4.
9
See the following note, point 4.
6
Change the function group.
Menu path: (GROUP SELECTION →) OPERATING
MENU → SETTINGS → LINEARISATION
7
Select TANK CONTENT MIN parameter.
Specify the minimum tank contents to be expected, here
0 m3 for example.
8
Select TANK CONTENT MAX parameter.
Specify the maximum tank contents to be expected, here
5 m3 for example.
9
On-site display:
Select the "Editor table" option by means of the TABLE
SELECTION parameter.
10
Select the "Manual" option by means of the LIN. EDIT
MODE parameter.
11
Select the "New table" option by means of the EDITOR
TABLE parameter.
12
Enter linearisation table (min. 2 points, max. 32 points).
LINE-NUMB: confirm value displayed.
X-VAL.: enter the height value and confirm.
Y-VAL.: enter the volume value, here 0 m3 for example,
and confirm.
13
On-site display
If you want to enter another point for the linearisation
table, select the "Next point" option and enter the point
as described in step 12.
If you want to finish entering the values and activate the
linearisation table, select the "Accept input table" option.
ToF Tool, HART handheld terminal:
You can enter further points for the linearisation table as
explained in step 12. Once all the points have been
entered, the table must be activated by means of the
TAB. ACTIVATE parameter.
14
Result:
– The linearisation table has been entered.
– The measured value display and the
TANK CONTENT parameter display the 2nd
measured value (here the volume).
– The LEVEL BEFORE LIN parameter displays the 1st
measured value (here the height). See also the
following note, point 5.
Description
5
0
0
3
V
[m ]
3
h
[m]
➄
➆
➅
20
4
I
[mA]
0
5
V
[m ]
3
➈
➇
Cerabar S/Deltabar S/Deltapilot S
40
4.
A level value is assigned to both the lower and upper current value with the SET LRV
(→ Page 97) and SET URV (→ Page 98) parameters.
You can use the ASSIGN CURRENT parameter (→ Page 113) to specify whether the current
output should depict the 1st or 2nd measured variable. Depending on the setting of the
ASSIGN CURRENT parameter, enter the following values for SET LRV and SET URV:
– ASSIGN CURRENT = tank content (factory setting) ⇒ %- value, volume value or
mass value
– ASSIGNMENT = height ⇒ level value
The following applies for the setting ASSIGN CURRENT "Tank content":
If you enter values for TANK CONTENT MIN (→ Page 100 or 104) and TANK CONTENT
MAX (→ Page 101 or 104), the SET LRV and SET URV parameters are also changed. If you
want to assign values other than those for TANK CONTENT MIN and TANK CONTENT MAX
to the lower and upper current values, the desired values must be entered for SET LRV and
SET URV.
The following applies for the setting ASSIGN CURRENT "Height":
If you enter values for LEVEL MIN (→ Page 86) and LEVEL MAX (→ Page 86), the SET LRV
and SET URV parameters are also changed. If you want to assign values other than those for
LEVEL MIN and LEVEL MAX to the lower and upper current values, the desired values must
be entered for SET LRV and SET URV.
5.
You can use the MENU DESCRIPTOR parameter (→ Page 110) to specify which measured
value should be displayed on the on-site display.
Cerabar S/Deltabar S/Deltapilot S
Flow measurement
41
6
Flow measurement
6.1
Calibration
Example:
In this example, a volume flow should be measured in m3/s.
!
Note!
• The "Flow measurement" measuring mode is only available for the Deltabar S differential pressure
transmitter.
• See also Operating Instructions BA270P Deltabar S, Section 6.4 "Flow measurement".
• For a description of the parameters mentioned, see
– Page 45, Table 2: MEASURING MODE
– Page 53, Table 6: POSITION ADJUSTMENT
– Page 91 ff, Table 12: BASIC SETUP
– Page 98 ff, Table 15: EXTENDED SETUP.
• For a description of further parameters, see
– Page 98, Table 15: EXTENDED SETUP
– Page 122, Table 29: PROCESS VALUES.
Description
1
Before configuring the device for your application, the
pressure piping must be cleaned and the device filled
with fluid. See Operating Instructions BA270P, Section
6.4.1.
P01-xxxxxxxx-19-xx-xx-xx-013
Fig. 20:
Flow measurement calibration
1
See table, step 8.
2
See table, step 9.
3
See the following note, point 4.
4
See the following note, point 4.
2
Carry out position adjustment if necessary. See Page 53,
Table 6: POSITION ADJUSTMENT.
3
If necessary, select the "Flow" measuring mode via the
MEASURING MODE parameter.
On-site display:
Menu path: GROUP SELECTION → MEASURING
MODE
ToF Tool, FieldCare, handheld terminal:
Menu path: OPERATING MENU → SETTINGS →
BASIC SETUP → MEASURING MODE
4
On-site display:
Select BASIC SETUP function group. Menu path:
GROUP SELECTION → OPERATING MENU →
SETTINGS → BASIC SETUP
5
Select a pressure unit via the PRESS. ENG. UNIT
parameter, here mbar for example.
6
Select the "Volume p. cond." option by means of the
FLOW-MEAS. TYPE parameter.
7
Select a flow unit via the UNIT FLOW parameter, here
m3/h for example.
8
Select MAX. FLOW parameter.
Enter the maximum flow value of the primary element,
here 6000 m3/h for example. See also layout sheet of
primary element.
9
Select MAX PRESS. FLOW parameter.
Enter the maximum pressure, here 400 mbar for
example. See also layout sheet of primary element.
10
Result:
The device is configured for flow measurement.
20
0
I
[mA]
0
6000
➀
p
[mbar]
➂
➁
➃
6000
0
0
400
[m /h]
3V
[m /h]
3V
Cerabar S/Deltabar S/Deltapilot S
42
!
Note!
1.
You can also perform calibration by means of the QUICK SETUP menu. → See Page 52 ff,
Table 5: QUICK SETUP menu.
2.
Using the FLOW-MEAS. TYPE parameter, you can choose between the following flow types:
– Volume p. cond. (volume under operating conditions)
– Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0°C))
– Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar (14.7 psi)
and 288. 15 K (15°C/59°F))
– Mass
3.
Depending on the flow type selected, you can choose between various units. You can also
specify a customer-specific unit.
See parameter description for PRESS. ENG. UNIT (→ Page 92), UNIT FLOW (→ Page 93),
NORM FLOW UNIT (→ Page 93), STD. FLOW UNIT (→ Page 94) and MASS FLOW UNIT
(→ Page 94).
4.
A flow value or a pressure value is assigned to both the lower and upper current value with
the SET LRV (→ Page 99) and SET URV (→ Page 99) parameters.
You can use the LINEAR/SQROOT parameter (→ Page 113) to specify whether the current
output should depict the linear pressure signal or the Flow (square root) flow signal. Depending
on the setting of the LINEAR/SQROOT parameter, enter the following values for SET LRV and
SET URV:
– LINEAR/SQROOT = Flow (square root) (factory setting) ⇒ flow value
– LINEAR/SQROOT = Differential pres. ⇒ pressure value
The following applies for the setting LINEAR/SQROOT "Flow (square root)":
As per the factory settings, the lower current value is set to equal zero and the upper current
value is set to the MAX. FLOW value. If you enter a value for MAX. FLOW, the SET URV
parameter is also changed. If you want to assign values other than zero and MAX. FLOW to
the lower and upper current values, the desired values must be entered for SET LRV and SET
URV.
The following applies for the setting LINEAR/SQROOT "Differential pres.":
As per the factory settings, the lower current value is set to equal zero and the upper current
value is set to the MAX. FLOW value. If you enter a value for MAX PRESS. FLOW, the SET
URV parameter is also changed. If you want to assign values other than zero and MAX PRESS.
FLOW to the lower and upper current values, the desired values must be entered for SET LRV
and SET URV.
5.
In the lower measuring range, small flow quantities (creepages) can lead to large measured
value fluctuations. You can activate low flow cut-off via the LOW FLOW CUT-OFF parameter
(→ Page 98).
Cerabar S/Deltabar S/Deltapilot S
Flow measurement
43
6.2
Totalizers
Example:
In this example, the volume flow should be totalised and displayed in the unit m3E3. Negative flows
should be added to the flow rate.
!
Note!
• For a description of the parameters mentioned, see
– Page 107 ff, Table 18: TOTALIZER SETUP
– Page 122 ff, Table 29: PROCESS VALUES
• Totalizer 1 can be reset. Totalizer 2 cannot be reset.
!
Note!
• You can also specify a customer-specific unit. → See parameter description for TOTALIZER 1
UNIT (→ Page 107) and TOTALIZER 2 UNIT (→ Page 108).
• The TOTALIZER 1 and TOTAL. 1 OVERFLOW parameters display the totalised flow value of the
first totalizer. The TOTALIZER 2 and TOTAL. 2 OVERFLOW parameters display the totalised
flow value of the second totalizer. → See Page 122 ff, PROCESS VALUES function group.
• You can use the MENU DESCRIPTOR parameter (→ Page 110) to specify which measured value
should be displayed on the on-site display.
Description
1
Calibrate the device as per Section 6.1.
2
Change the function group:
(GROUP SELECTION →) OPERATING MENU →
SETTINGS → TOTALIZER SETUP
3
Select a flow unit via the TOTALIZER 1 UNIT
parameter, here m3 E3 for example.
4
Use the NEG. FLOW TOT. 1 parameter to specify the
totalising mode for negative flows, here the "Positive"
option for example.
5
Reset totalizer 1 to zero via the RESET TOTALIZER
parameter.
6
Result:
The TOTALIZER 1 and TOTAL. 1 OVERFLOW
parameters display the totalised volume flow.
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
44
7
Description of parameters
!
Note!
• The following tables list all the parameters as per the menu structure. Each table corresponds to
a function group in the menu tree. The overall menu structure is illustrated in Section 9.1.
• The menu structure for on-site operation and the ToF Tool are slightly different. The differences
mainly affect the MEASURING MODE and LANGUAGE parameters and the LINEARISATION
function group.
• In the ToF Tool or HART handheld terminal, additional parameters are displayed. These
parameters are marked accordingly.
• The menu path is indicated in the header of each table. You can use this path to get to the
parameters in question.
• The menu has a different structure depending on the measuring mode selected. This means that
some function groups are only displayed for one measuring mode, e.g. the "LINEARISATION"
function group for the "Level" measuring mode. If certain requirements have to be met for a
function group, these are listed in the first row of the table.
• Some parameters are only displayed if other parameters are appropriately configured. For
example, the EMPTY CALIB. parameter is not displayed in the Quick Setup menu ("Level"
measuring mode) unless the "Linear" option was selected for the LEVEL MODE parameter and
the "Wet" option was selected for the CALIBRATION MODE parameter. There is a comment in
the parameter description here stating: Note: prerequisite: LEVEL MODE = Linear and
CALIBRATION MODE = Wet.
• Parameter names are written in upper case in the text.
• In the "Parameter name" column, the unique identification number (ID) of the parameter is
indicated in brackets. This ID only appears on the on-site display.
P01-xxxxxxxx-19-xx-xx-xx-079
Fig. 21:
1st selection level in menu, LANGUAGE (→ see Page 45, Table 1) and MEASURING MODE (→ see Page 45,
Table 2)
1)
1)
1)
2)
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Pressure
Level
Flow
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE
MEASURING MODE
QUICK SETUP
MEASURING MODE
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
45
P01-xxxxxxxx-19-xx-xx-xx-135
Fig. 22:
"Level" measuring mode, LEVEL SELECTION parameter
Table 1: GROUP SELECTION → LANGUAGE – on-site operation
Parameter name
Description
LANGUAGE (079)
Selection
Select the menu language for the on-site display.
!
Note!
• In the ToF Tool and in the HART handheld terminal, the LANGUAGE parameter is
arranged in the DISPLAY function group.
• Select the menu language for the ToF Tool via the "Options" menu → "Settings" →
"Language" tab → "Tool language" field.
Options:
• Deutsch
• English
• Français
• Italiano
• Español
• Nederlands
• Chinese (CHS)
• Japanese (JPN)
Factory setting:
English
1)
2)
1)
1)
2)
1)
LEVEL SELECTION
Level Standard
Level Easy Pressure
Level Easy Height
Flow
Pressure
Level
Level Standard
Level Easy Pressure
Level Easy Height
LEVEL SELECTION
Flow
Pressure
Level
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE
MEASURING MODE
QUICK SETUP
MEASURING MODE
1) Display via on-site display only
2) Display via ToF Tool, FeildCare
or HART handheld terminal
Table 2: GROUP SELECTION → MEASURING MODE – on-site operation
Parameter name
Description
MEASURING MODE (389)
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
• When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
• The MEASURING MODE parameter is displayed in the ToF Tool and in the HART
handheld terminal in the QUICK SETUP menus and in the BASIC SETUP function
group (OPERATING MENU → SETTINGS → BASIC SETUP).
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
46
LEVEL SELECTION (020)
Options
Select level mode.
Prerequisite:
• MEASURING MODE = Level
!
Note!
• In the "Level Easy Pressure" and "Level Easy Height" level modes, the values entered
are not tested as extensively as in the "Level Standard" level mode. The values entered
for EMPTY CALIB./FULL CALIB., EMPTY PRESSURE/FULL PRESSURE, EMPTY
HEIGHT/FULL HEIGHT and SET LRV/SET URV must have a minimum interval of 1%
for the "Level Easy Pressure" and "Level Easy Height" level modes. The value will be
rejected with a warning message if the values are too close together. Further limit
values are not checked; i.e. the values entered must be appropriate for the sensor and
the measuring task so that the measuring device can measure correctly.
→ For an overview of the different level modes and types, see Page 16, Section 5.1
"Overview of level measurement".
• The "Level Easy Pressure" and "Level Easy Height" level modes encompass fewer
parameters than the "Level Standard" mode and are used for quick and easy
configuration of a level application.
• Customer-specific units of fill level, volume and mass or a linearization table may only
be entered in the "Level Standard" level mode.
• Where the device is intended for use as a subsystem in a safety function (SIL), a
"Device configuration with enhanced parameter security" (SAFETY CONFIRM.) is only
possible for the "Level" operating mode in the "Level Easy Pressure" level mode. All
parameters previously entered are checked after a password is entered. Once the
"Level Easy Height" or "Level Standard" has been selected, the configuration will first
have to be reset to the ex-works setting using the RESET parameter (menu path:
(GROUP SELECTION →) OPERATING MENU → OPERATION) using the reset code
"7864".
→ For additional information, see the Safety Manual for Deltabar S (SD189), Cerabar S
(SD190) or Deltapilot S (SD213P).
Options:
• Level Easy Pressure
Specify two pressure-level value pairs for this level mode. The pressure measured value
is converted directly to the unit which is selected via the OUTPUT UNIT parameter
(→ Page 60). Two calibration modes, "Wet" and "Dry", are available.
– Wet calibration takes place by filling and emptying the container. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to
the pressure measured at this point in time.
– Dry calibration is a theoretical calibration. For this calibration, specify two pressure-
level value pairs via the EMPTY CALIB., EMPTY PRESSURE, FULL CALIB. and
FULL PRESSURE parameters. → Parameter descriptions see Page 61 ff.
• Level Easy Height
For this level mode, specify a height unit, density and two height-level value pairs. The
pressure measured value is converted to a height value using the density entered and
the height unit. Two calibration modes, "Wet" and "Dry", are available.
– Wet calibration takes place by filling and emptying the container. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to
the converted height value.
– Dry calibration is a theoretical calibration. For this calibration, specify two height-
level value pairs via the EMPTY CALIB., EMPTY HEIGHT, FULL CALIB. and FULL
HEIGHT parameters. → Parameter descriptions see Page 65 ff.
• Level standard
Once you have selected this level mode, you can use the LEVEL MODE parameter
(→ Page 68) to choose between "Linear", "Pressure Linearized" and "Height
Linearized".
Factory setting:
Level Easy Pressure
→ For LEVEL SELECTION = "Level Easy Pressure" see Page 58, Table 8.
→ For LEVEL SELECTION = "Level Easy Height" see Page 62, Table 9.
→ For LEVEL SELECTION = "Level standard" see Page 67, Table 10.
Table 2: GROUP SELECTION → MEASURING MODE – on-site operation
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
47
P01-xxxxxxxx-19-xx-xx-xx-080
Fig. 23:
Quick Setup menu for the "Pressure" measuring mode
1)
1)
2)
1)
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Deltabar S,
Cerabar S – gauge pressure sensors,
Deltapilot S
Cerabar S – absolut pressure sensors
SET LRV
SET URV
POS. ZERO ADJUST
DAMPING VALUE
POS. INPUT VALUE
Flow
Pressure
Level
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE
MEASURING MODE
QUICK SETUP
MEASURING MODE
Table 3: (GROUP SELECTION →) QUICK SETUP "Pressure"
Parameter name
Description
This menu displays the most important parameters for the "Pressure" measuring mode.
Prerequisite:
• MEASURING MODE = Pressure (→ see also Page 45).
Note:
See also
– Page 55 ff, Table 7: BASIC SETUP
– Page 96, Table 15: EXTENDED SETUP
– Page 120 ff, Table 27: PROCESS VALUES
– Page 13 ff, Section 4 "Pressure measurement".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisite:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
48
POS. ZERO ADJUST (685)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Due to the orientation of the device, there may be a shift in the measured value, i.e. for
example, when the container is empty, the MEASURED VALUE parameter does not
display zero.
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
– The current value is also corrected.
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Prerequisite:
• This parameter is displayed for Deltabar S, Cerabar S with gauge pressure sensor and
Deltapilot S.
Options:
• Abort
• Confirm
Factory setting:
0
POS. INPUT VALUE (563)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Due to the orientation of the device, there may be a shift in the measured value, i.e. for
example, when the container is empty, the MEASURED VALUE parameter does not
display zero or the desired value.
Example:
– MEASURED VALUE = 0.5 mbar
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2 mbar.
(MEASURED VALUEnew = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUE old – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
– The current value is also corrected.
Prerequisite:
• This parameter is displayed for Cerabar S with absolute pressure sensors.
Factory setting:
0.0
SET LRV (245)
Entry
Set lower range value – without reference pressure.
Enter pressure value for the lower current value (4 mA).
Factory setting:
0.0 or as per order specifications
SET URV (246)
Entry
Set upper range value – without reference pressure.
Enter pressure value for the upper current value (20 mA).
Factory setting:
High sensor limit (→ see PRESS. SENS HILIM, Page 119) or as per order specifications
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 3: (GROUP SELECTION →) QUICK SETUP "Pressure"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
49
P01-xxxxxxxx-19-xx-xx-xx-081
Fig. 24:
Quick Setup menu for the "Level" measuring mode
*
*
1)
1)
2)
1)
2)
LEVEL SELECTION
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
POS. ZERO ADJUST
EMPTY CALIB.
FULL CALIB.
POS. INPUT VALUE
DAMPING VALUE
Cerabar S –
absolut pressure sensors
Deltabar S,
Cerabar S –
gauge pressure sensors,
Deltapilot S
Flow
Pressure
Level
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE
MEASURING MODE
QUICK SETUP
MEASURING MODE
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Table 4: (GROUP SELECTION →) QUICK SETUP "Level"
Parameter name
Description
This menu displays the most important parameters for the "Level" measuring mode.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
Note:
See also
– Page 67 ff, Tables 10 to 13: BASIC SETUP
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 100 ff, Table 18: LINEARISATION – on-site operation
– Page 103 ff, Table 19: LINEARISATION – ToF Tool and HART handheld terminal
– Page 121 ff, Table 28: PROCESS VALUES
– Page 16 ff, Section 5 "Level measurement".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisite:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
LEVEL SELECTION (020)
Options
Select level mode.
→ Parameter description, see Page 46.
Factory setting:
Level Easy Pressure
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
50
POS. ZERO ADJUST (685)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Due to the orientation of the device, there may be a shift in the measured value, i.e. when
the container is empty, the MEASURED VALUE parameter does not display zero.
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
– The current value is also corrected.
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Prerequisite:
• This parameter is displayed for Deltabar S, Cerabar S with gauge pressure sensor and
Deltapilot S.
Options:
• Abort
• Confirm
Factory setting:
0
POS. INPUT VALUE (563)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Due to the orientation of the device, there may be a shift in the measured value, i.e. when
the container is empty, the MEASURED VALUE parameter does not display zero or the
desired value.
Example:
– MEASURED VALUE = 0.5 mbar
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2 mbar.
(MEASURED VALUE new = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUEold – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
– The current value is also corrected.
Prerequisite:
• This parameter is displayed for Cerabar S with absolute pressure sensors.
Factory setting:
0.0
EMPTY CALIB. (314)/(010)
Entry
Enter level value for the lower calibration point (container empty).
The container is either empty or part full. By entering a value for this parameter, you are
assigning a level value to the pressure present at the device.
Prerequisite:
• LEVEL SELECTION = Level Easy Pressure (→ see also Page 46),
CALIBRATION MODE = Wet (→ see also Page 60)
• LEVEL SELECTION = Level Standard (→ see also Page),
LEVEL MODE = Linear (→ see also Page 68),
CALIBRATION MODE = Wet (→ see also Page 73)
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
Table 4: (GROUP SELECTION →) QUICK SETUP "Level"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
51
P01-xxxxxxxx-19-xx-xx-xx-082
Fig. 25:
Quick Setup menu, "Flow" measuring mode
FULL CALIB. (315)/(004)
Entry
Enter level value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you are assigning a level value to the pressure present at the device.
Prerequisite:
• LEVEL SELECTION = Level Easy Pressure (→ see also Page 46),
CALIBRATION MODE = Wet (→ see also Page 60)
• LEVEL SELECTION = Level Standard,
LEVEL MODE = Linear (→ see also Page 68),
CALIBRATION MODE = Wet (→ see also Page 73)
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 4: (GROUP SELECTION →) QUICK SETUP "Level"
Parameter name
Description
1)
1)
2)
1)
MAX. FLOW
MAX. PRESS. FLOW
POS. ZERO ADJUST
DAMPING VALUE
Flow
Pressure
Level
OPERATING MENU
Measured value
GROUP SELECTION
LANGUAGE
MEASURING MODE
QUICK SETUP
MEASURING MODE
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
52
Table 5: (GROUP SELECTION →) QUICK SETUP "Flow"
Parameter name
Description
This menu displays the most important parameters for the "Flow" measuring mode.
Prerequisite:
• Deltabar S differential pressure transmitter
• MEASURING MODE = Flow (→ see also Page 45).
Note:
See also
– Page 91, Table 14: BASIC SETUP
– Page 98, Table 17: EXTENDED SETUP
– Page 107, Table 20: TOTALIZER SETUP
– Page 41 ff, Section 6 "Flow measurement".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisites:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
POS. ZERO ADJUST (685)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Due to the orientation of the device, there may be a shift in the measured value, i.e. when
the container is empty, the MEASURED VALUE parameter does not display zero.
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
– The current value is also corrected.
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Selection:
• Abort
• Confirm
Factory setting:
0
MAX. FLOW (311)
Entry
Enter maximum flow of primary element.
See also layout sheet of primary element. The maximum flow is assigned to the maximum
pressure which you enter via MAX PRESS. FLOW.
!
Note!
Use the LINEAR/SQROOT parameter (→ Page 113) to specify the current signal for the
"Flow" measuring mode. The following applies for the "Flow (square root)" setting:
If you enter a new value for MAX. FLOW, the value for SET URV is also changed. Use
SET URV to assign a flow to the upper current value. If you want to assign the upper
current value a value other than that for MAX. FLOW, you must enter the desired value
for SET URV. (→ SET URV, Page 99).
Factory setting:
1.0
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
53
P01-xxxxxxxx-19-xx-xx-xx-083
Fig. 26:
POSITION ADJUSTMENT function group
MAX PRESS. FLOW (634)
Entry
Enter maximum pressure of primary element.
→ See layout sheet of primary element. This value is assigned to the maximum flow value
(→ see MAX. FLOW).
!
Note!
Use the LINEAR/SQROOT parameter (→ Page 113) to specify the current signal for the
"Flow" measuring mode. The following applies for the "Differential pres." setting:
If you enter a new value for MAX PRESS. FLOW, the value for SET URV is also changed.
Use SET URV to assign a pressure value to the upper current value. If you want to assign
the upper current value a value other than that for MAX PRESS. FLOW, you must enter
the desired value for SET URV. (→ SET URV, Page 99).
Factory setting:
High sensor limit (→ See PRESS. SENS HILIM, Page 119)
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 5: (GROUP SELECTION →) QUICK SETUP "Flow"
Parameter name
Description
1)
1)
LANGUAGE
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
EXTENDED SETUP
CALIB. OFFSET
POS. ZERO ADJUST
POS. INPUT VALUE
1) Display via
on-site display only
Table 6: (GROUP SELECTION →) OPERATING MENU → SETTINGS → POSITION ADJUSTMENT
Parameter name
Description
Due to the orientation of the device, there may be a shift in the measured value, i.e. when the container is empty, the
measured value does not display zero. Deltabar S and Cerabar S offer three different ways of performing a position
adjustment.
Recommendation:
• The pressure difference between zero (set point) and the measured pressure need not be known.
– POS. ZERO ADJUST: Deltabar S or Cerabar S with gauge pressure sensor or Deltapilot S.
– POS. INPUT VALUE: Cerabar S with absolute pressure sensor.
• The pressure difference between zero (set point) and the measured pressure is known.
– CALIB. OFFSET: Deltabar S, Cerabar S with gauge pressure sensor, Cerabar S with absolute pressure sensor or
Deltapilot S.
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
54
POS. ZERO ADJUST (685)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Example:
– MEASURED VALUE = 2.2 mbar
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
– The current value is also corrected.
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by which
the MEASURED VALUE was corrected.
Selection:
• Abort
• Confirm
Factory setting:
0
POS. INPUT VALUE (563)
Entry
Position adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known. (A reference pressure is present at the device.)
Example:
– MEASURED VALUE = 0.5 mbar
– For the POS. INPUT VALUE parameter, specify the desired set point for the
MEASURED VALUE, e.g. 2 mbar.
(MEASURED VALUEnew = POS. INPUT VALUE)
– MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar
– The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
CALIB. OFFSET = MEASURED VALUEold – POS. INPUT VALUE,
here: CALIB. OFFSET = 0.5 mbar – 2.0 mbar = – 1.5 mbar)
– The current value is also corrected.
Factory setting:
0.0
CALIB. OFFSET (319)
Entry
Position adjustment - the pressure difference between zero (set point) and the measured
pressure is known.
Example:
– MEASURED VALUE = 2.2 mbar
– Via the CALIB. OFFSET parameter, enter the value by which the MEASURED VALUE
should be corrected. To correct the MEASURED VALUE to 0.0 mbar, you must enter
the value 2.2 here.
(MEASURED VALUEnew = MEASURED VALUEold – CALIB. OFFSET)
– MEASURED VALUE (after entry for calib. offset) = 0.0 mbar
– The current value is also corrected.
Factory setting:
0.0
Table 6: (GROUP SELECTION →) OPERATING MENU → SETTINGS → POSITION ADJUSTMENT
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
55
P01-xxxxxxxx-19-xx-xx-xx-084
Fig. 27:
BASIC SETUP function group for the "Pressure" measuring mode
*
*
1)
2)
1)
*
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
LANGUAGE
Flow
Pressure
Level
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
SET LRV
DAMPING VALUE
GET LRV
GET URV
SET URV
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Table 7: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Pressure"
Parameter name
Description
Prerequisite:
• MEASURING MODE = Pressure (→ see also Page 45).
Note:
See also
– Page 47, Table 3: QUICK SETUP
– Page 96, Table 15: EXTENDED SETUP
– Page 120 ff, Table 27: PROCESS VALUES
– Page 13 ff, Section 4 "Pressure measurement".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisite:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
56
PRESS. ENG. UNIT (060)
Selection
Select pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
• psi
• mmHg, inHg
• Torr
• g/cm2, kg/cm2
• lb/ft2
• atm
• gf/cm2, kgf/cm2
• User unit, → See also the following parameter description for CUSTOMER UNIT P and
CUST. UNIT FACT. P.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT P parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. P (317)
Entry
Enter conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
SET LRV (245)
Entry
Set lower range value – without reference pressure.
Enter pressure value for the lower current value (4 mA).
Factory setting:
0.0 or as per order specifications
SET URV (246)
Entry
Set upper range value – without reference pressure.
Enter pressure value for the upper current value (20 mA).
Factory setting:
High sensor limit (→ See PRESS. SENS HILIM, Page 119)
Table 7: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Pressure"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
57
GET LRV (309)
Entry
Set lower range value – reference pressure is present at device.
The pressure for the lower current value (4 mA) is present at device. With the "Confirm"
option, you assign the lower current value to the pressure value present.
On-site display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
GET URV (310)
Entry
Set upper range value – reference pressure is present at device.
The pressure for the upper current value (20 mA) is present at device. With the "Confirm"
option, you assign the upper current value to the pressure value present.
On-site display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 7: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Pressure"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
58
P01-xxxxxxxx-19-xx-xx-xx-136
Fig. 28:
BASIC SETUP function group for the "Level" measuring mode and "Level Easy Pressure" level selection
1)
2)
1)
*
*
2)
*
Level Standard
Level Easy
Height
Level Easy Pressure
LANGUAGE
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Dry
Wet
Flow
Pressure
Level
SET LRV
SET URV
DAMPING VALUE
EMPTY CALIB.
FULL PRESSURE
EMPTY PRESSURE
FULL CALIB.
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
EMPTY CALIB.
FULL CALIB.
LEVEL SELECTION
OUTPUT UNIT
CALIBRATION MODE
Table 8: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Pressure"
The following parameters are displayed if you have selected the "Level Easy Pressure" option for the LEVEL SELECTION
parameter. Specify two pressure-level value pairs for this level mode. Two calibration modes, "Wet" and "Dry", are
available.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45.)
• LEVEL SELECTION = Level Easy Pressure (→ See also Page 46.)
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
59
PRESS. ENG. UNIT (060)
Selection
Select pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
• psi
• mmHg, inHg
• Torr
• g/cm2, kg/cm2
• lb/ft2
• atm
• gf/cm2, kgf/cm2
• User unit, → see also the following parameter descriptions for CUSTOMER UNIT P
and CUST. UNIT FACT. P.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT P parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. P (317)
Entry
Enter conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
Table 8: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Pressure"
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
60
OUTPUT UNIT (023)
Selection
Select unit for measured value display and MEASURED VALUE parameter (→ Page 121).
!
Note!
The selected unit is used only to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Example:
• current measured value: 0.3 ft
• new output unit: m
• new measured value: 0.3 m
Options
• %
• mm, cm, dm, m
• ft, inch
• cm3, dm3, m3,m3 E3
• l, hl
• ft3, ft3 E3
• gal, bbl, Igal
• g, kg, t
• lb, ton, oz
Factory setting:
%
CALIBRATION MODE (008)
Selection
Select calibration mode.
Options:
• Wet
Wet calibration takes place by filling and emptying the container. In the case of two
different levels, the level, volume, mass or percentage value entered is assigned to the
pressure measured at this point in time. (→ See also this table, parameter descriptions
for EMPTY CALIB. and FULL CALIB.)
• Dry
Dry calibration is a theoretical calibration. For this calibration, specify two pressure-
level value pairs via the following parameters: EMPTY CALIB., EMPTY PRESSURE,
FULL CALIB. and FULL PRESSURE.
Factory setting:
Wet
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The container is either empty or part full. By entering a value for this parameter, you
assign a level, volume, mass or percentage value to the pressure present at the device.
The unit is selected via the OUTPUT UNIT parameter (→ Page 60).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter height, volume or mass value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you assign a height, volume or mass value to the pressure present at the device. The unit
is selected via the OUTPUT UNIT parameter (→ Page 60).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
Table 8: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Pressure"
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
61
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The values entered for the EMPTY CALIB. and EMPTY PRESSURE parameters form the
pressure-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter (→ Page 60).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY PRESSURE (011)
Entry
Enter pressure value for the lower calibration point (container empty).
→ See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter height, volume, mass or percentage value for the upper calibration point (container
full).
The values entered for the FULL CALIB. and FULL PRESSURE parameters form the
pressure-level value pair for the upper calibration point. The unit is selected via the
OUTPUT UNIT parameter (→ Page 60).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
FULL PRESSURE (005)
Entry
Enter pressure value for the upper calibration point (container full).
→ See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
SET LRV (013)
Entry
Enter value for the lower current value (4 mA). The unit is selected via the OUTPUT
UNIT parameter (→ Page 60).
Factory setting:
0.0
SET URV (012)
Entry
Enter value for the upper current value (20 mA). The unit is selected via the OUTPUT
UNIT parameter (→ Page 60).
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 8: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Pressure"
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
62
P01-xxxxxxxx-19-xx-xx-xx-137
Fig. 29:
BASIC SETUP function group for "Level" measuring mode and "Level Easy Height" level selection
1)
2)
1)
2)
*
*
Level Easy Pressure
Level Standard
Level Easy Height
LANGUAGE
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Dry
Wet
Flow
Pressure
Level
SET LRV
SET URV
DAMPING VALUE
DENSITY UNIT
EMPTY HEIGHT
ADJUST DENSITY
EMPTY CALIB.
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
LEVEL SELECTION
OUTPUT UNIT
CALIBRATION MODE
HEIGHT UNIT
FULL HEIGHT
DENSITY UNIT
ADJUST DENSITY
EMPTY CALIB.
FULL CALIB.
FULL CALIB.
Table 9: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"
The following parameters are displayed if you have selected the "Level Easy Height" option for the LEVEL SELECTION
parameter. For this level mode, specify a height unit, density and two height-level value pairs. The pressure measured
value is converted to a height value using the density entered and the height. Two calibration modes, "Wet" and "Dry",
are available.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45.)
• LEVEL SELECTION = Level Easy Height (→ See also Page 46.)
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
63
PRESS. ENG. UNIT (060)
Options
Select pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
• psi
• mmHg, inHg
• Torr
• g/cm2, kg/cm2
• lb/ft2
• atm
• gf/cm2, kgf/cm2
• User unit, → see also the following parameter descriptions for CUSTOMER UNIT P
and CUST. UNIT FACT. P.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customised pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customised unit is displayed only in the CUSTOMER
UNIT P parameter. The measured value is displayed with the additional text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. P (317)
Entry
Enter conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
Table 9: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
64
OUTPUT UNIT (023)
Options
Select unit for measured value display and MEASURED VALUE parameter (→ Page 121).
!
Note!
The selected unit is used only to describe the measured value. This means that when
selecting a new output unit, the measured value is not converted.
Example:
• current measured value: 0.3 ft
• new output unit: m
• new measured value: 0.3 m
Options:
• %
• mm, cm, dm, m
• ft, inch
• cm3, dm3, m3,m3 E3
• l, hl
• ft3, ft3 E3
• gal, bbl, Igal
• g, kg, t
• lb, ton, oz
Factory setting:
%
HEIGHT UNIT (003)
Options
Select height unit. The measured pressure is converted to the chosen height unit using
the DENSITY UNIT and ADJUST DENSITY parameters.
Options:
• mm
• cm
• dm
• m
• inch
• ft
Factory setting:
m
CALIBRATION MODE (008)
Options
Select calibration mode.
Options:
• Wet
Wet calibration takes place by filling and emptying the container. The measured
pressure is converted to the chosen height unit using the HEIGHT UNIT, DENSITY
UNIT and ADJUST DENSITY parameters. In the case of two different levels, the level,
volume, mass or percentage value entered is assigned to the converted height value.
• Dry
Dry calibration is a theoretical calibration. For this calibration, specify two height-level
value pairs via the EMPTY CALIB., EMPTY HEIGHT, FULL CALIB. and FULL
HEIGHT parameters.
Factory setting:
Dry
DENSITY UNIT (001)
Options
Select density unit. The measured pressure is converted to a height using the HEIGHT
UNIT, DENSITY UNIT and ADJUST DENSITY parameters.
Options:
• g/cm3
• kg/dm3
• kg/m3
• US lb/in3
• US lb/ft3
Factory setting:
kg/dm3
ADJUST DENSITY (007)
Entry
Enter density of fluid. The measured pressure is converted to a height using the HEIGHT
UNIT, DENSITY UNIT and ADJUST DENSITY parameters.
Factory setting:
1.0
Table 9: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
65
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The container is either empty or part full. The measured pressure is converted to a height
value using the HEIGHT UNIT, DENSITY UNIT and ADJUST DENSITY parameters and
displayed. Using the parameter EMPTY CALIB., you assign a level, volume, mass or
percentage value to the height value. The unit is selected via the OUTPUT UNIT
parameter (→ Page 64).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
FULL CALIB. (004)
Entry
Enter level, volume, mass or percentage value for the upper calibration point (container
full).
The container is either completely or almost full. Using the parameters HEIGHT UNIT,
DENSITY UNIT and ADJUST DENSITY, the measured pressure is converted to a height
value and displayed. Using the parameter FULL CALIB., you assign a level, volume, mass
or percentage value to the height value. The unit is selected via the OUTPUT UNIT
parameter (→ Page 64).
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
EMPTY CALIB. (010)
Entry
Enter level, volume, mass or percentage value for the lower calibration point (container
empty).
The values entered for the EMPTY CALIB. and EMPTY HEIGHT parameters form the
height-level value pair for the lower calibration point. The unit is selected via the
OUTPUT UNIT parameter (→ Page 64).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
EMPTY HEIGHT (009)
Entry
Height value for the lower calibration point (container empty). The unit is selected via the
HEIGHT UNIT parameter (→ Page 64).
→ See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
Upper range limit (URL) coverted to an height unit
FULL CALIB. (004)
Entry
Enter level, volume, mass or percentage value for the upper calibration point (container
full).
The values entered for the FULL CALIB. and FULL HEIGHT parameters form the height-
level value pair for the upper calibration point. The unit is selected via the OUTPUT UNIT
parameter (→ Page 64).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
100.0
Table 9: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
66
P01-xxxxxxxx-19-xx-xx-xx-085
Fig. 30:
BASIC SETUP function group for the "Level" measuring mode,
depending on the setting for the LEVEL MODE parameter
→ See Page 69, Fig. 31 for LEVEL MODE = Linear,
→ See Page 78, Fig. 33 for LEVEL MODE = Pressure Linearized,
→ See Page 82, Fig. 34 for LEVEL MODE = Height Linearized
FULL HEIGHT (006)
Entry
Enter height value for the upper calibration point (container full). The unit is selected via
the HEIGHT UNIT parameter (→ Page 64).
→ See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
SET LRV (013)
Entry
Enter level, volume, mass or percentage value for the lower current value (4 mA). The
unit is selected via the OUTPUT UNIT parameter (→ Page 64).
Factory setting:
0.0
SET URV (012)
Entry
Enter level, volume, mass or percentage value for the upper current value (20 mA). The
unit is selected via the OUTPUT UNIT parameter (→ Page 64).
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 9: (GROUP SELECTION→
→
→
→) OPERATING MENU →
→
→
→ SETTINGS →
→
→
→ BASIC SETUP "Level",
LEVEL SELECTION "Level Easy Height"
*
*
1)
2)
1)
*
2)
LEVEL SELECTION
LANGUAGE
Linear
Pressure
Linearized
Height
Linearized
Flow
Pressure
Level
LEVEL MODE
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
67
Table 10: (GROUP SELECTION → ) OPERATING MENU → SETTINGS → BASIC SETUP "Level"
Parameter name
Description
Prerequisite:
• MEASURING MODE = level (→ see also Page 45).
Note:
See also
– Page 70 ff, Tables 11 to 13: BASIC SETUP – contd.
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 100 ff, Table 18: LINEARISATION – on-site operation
– Page 103 ff, Table 19: LINEARISATION – ToF Tool and HART handheld terminal
– Page 121 ff, Table 28: PROCESS VALUES
– Page 16 ff, Section 5 "Level measurement".
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisite:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
Pressure
PRESS. ENG. UNIT (060)
Selection
Select pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
• psi
• mmHg, inHg
• Torr
• g/cm2, kg/cm2
• lb/ft2
• atm
• gf/cm2, kgf/cm2
• User unit, → See also the following parameter description for CUSTOMER UNIT P and
CUST. UNIT FACT. P.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT P parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
68
CUST. UNIT FACT. P (317)
Entry
Enter conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
LEVEL MODE (718)
Selection
Select level type.
Options:
• Linear: the measured variable (level, volume, mass or %) is in direct proportion to the
measured pressure. → See also Page 70 ff, Table 9.
• Pressure Linearized: the measured variable (volume, mass or %) is not in direct
proportion to the measured pressure such as in the case of containers with a conical
outlet. For the calibration, enter a linearisation table with at least 2 and not more than
32 points. → See also Page 78 ff, Table 10.
• Height Linearized: select this level type if you require two measured variables or if the
container shape is given with value pairs, e.g. height and volume.
The following combinations are possible:
– Height + Volume
– Height + Mass
– Height + %
– %-Height + Volume
– %-Height + Mass
– %-Height + %
Perform two calibrations for this level type. First for the measured variable height or %-
height like for the "Linear" option and then for the measured variable volume, mass or
% like for the "Pressure Linearized" option. → See also Page 83 ff, Table 11.
Factory setting:
Linear
→ For LEVEL MODE = Linear, see Page 70, Table 9.
→ For LEVEL MODE = Pressure Linearized, see Page 78, Table 10.
→ For LEVEL MODE = Height Linearized, see Page 83, Table 11.
Table 10: (GROUP SELECTION → ) OPERATING MENU → SETTINGS → BASIC SETUP "Level"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
69
P01-xxxxxxxx-19-xx-xx-xx-087
Fig. 31:
BASIC SETUP function group for the "Level" measuring mode and "Linear" level type
*
1)
2)
1)
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
2)
PRESS. ENG. UNIT
CUST. UNIT FACT. V
VOLUME UNIT
CUSTOMER UNIT V
LANGUAGE
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Dry
Wet
Mass
Volume
Height
%
Linear
Pressure
Linearized
Height
Linearized
Flow
Pressure
Level
TANK VOLUME
TANK HEIGHT
SET LRV
SET URV
MASS UNIT
CUSTOMER UNIT M
CUST. UNIT FACT. M
DAMPING VALUE
EMPTY CALIB.
DENSITY UNIT
ADJUST DENSITY
HEIGHT UNIT
100% POINT
ZERO POSITION
CUSTOMER UNIT H
CUST. UNIT FACT. H
FULL PRESSURE
EMPTY PRESSURE
FULL CALIB.
ADJUSTED DENSITY
CALIBRATION MODE
HEIGHT UNIT
CUSTOMER UNIT H
CUST. UNIT FACT. H
VOLUME UNIT
CUSTOMER UNIT V
CUST. UNIT FACT. V
LIN. MEASURAND
LEVEL MODE
LEVEL SELECTION
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
70
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
The following parameters are displayed if you selected the "Linear" option for the LEVEL MODE parameter. For this level
type, the measured variable (level, volume, mass or %) is in direct proportion to the measured pressure.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
• LEVEL SELECTION = Level Standard (→ see also Page 46).
• LEVEL MODE = Linear (→ see also Page 68).
Note:
See also
– Page 67 ff, Table 10: BASIC SETUP – general
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 121 ff, Table 28: PROCESS VALUES
– Page 16 ff, Section 5 "Level measurement".
LIN. MEASURAND (804)
Selection
Select measured variable.
Options:
• Level
• Volume
• Mass
• % (Level)
Factory setting:
% (Level)
HEIGHT UNIT (708)
Selection
Select level unit.
Prerequisite:
• LIN. MEASURAND = Level
Options:
• mm
• cm
• dm
• m
• inch
• ft
• User unit, → see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. H.
Prerequisite:
• LIN. MEASURAND = Level, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
71
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
→ See also CUSTOMER UNIT H.
Prerequisite:
• LIN. MEASURAND = Level, HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m i 1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select volume unit.
Prerequisite:
• LIN. MEASURAND = Volume
Options:
• l
• hl
• cm3
• dm3
• m3
• m3 E3
• ft
• ft3 E3
• gal
• Igal
• bbl
• User unit, → see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m3
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. V
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
72
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m3".
→ See also CUSTOMER UNIT V.
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3 i 1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
MASS UNIT (709)
Selection
Select mass unit.
Prerequisite:
• LIN. MEASURAND = Mass
Options:
• g
• kg
• t
• oz
• lb
• ton
• User unit, → see also the following parameter description for CUSTOMER UNIT M
and CUST. UNIT FACT. M.
Factory setting:
kg
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. M.
Prerequisite:
• LIN. MEASURAND = Mass, MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
73
CUST. UNIT FACT. M (703)
Entry
Enter conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg".
→ See also CUSTOMER UNIT M.
Prerequisite:
• LIN. MEASURAND = Mass, MASS UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 10 kg i 1 bucket
– Entry CUSTOMER UNIT M: bucket
– Entry CUST. UNIT FACT. M: 0.1
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
CALIBRATION MODE (392)
Selection
Select calibration mode.
Options:
• Wet
Wet calibration takes place by filling and emptying the container. This calibration mode
requires two pressure-level value pairs to be entered. In the case of two different levels,
the level value is entered and the pressure measured at this moment is assigned to the
level value. → See also the following parameter description for EMPTY CALIB.,
EMPTY PRESSURE, FULL CALIB. and FULL PRESSURE.
• Dry
Dry calibration is a theoretical calibration which you can carry out even if the device is
not mounted or the container is empty.
– For the "Level" measured variable, the density of the fluid (→ see Page 74, ADJUST
DENSITY) must be entered.
– For the "Volume" measured variable, the density of the fluid and the tank volume
and tank height must be entered (→ see Page 74, ADJUST DENSITY, TANK
VOLUME and TANK HEIGHT).
– For the "Mass" measured variable, the tank volume and the tank height must be
entered (→ see Page 75, TANK VOLUME and TANK HEIGHT). The density must
also be entered in the case of a zero point shift (level offset) (→ see Page 74,
ADJUST DENSITY).
– For the "%" measured variable, the density of the fluid must be entered and a level
assigned to the 100 % point (→ see Page 74 and 77, ADJUST DENSITY and 100%
POINT).
If the measurement should not start at the mounting location of the device, a level
offset must be entered (→ see Page 77, ZERO POSITION).
!
Note!
LIN. MEASURAND: "% (Level)", "Mass" and "Volume":
If the change to dry calibration is made after a wet calibration, the density must be
entered correctly using the ADJUST DENSITY and DENSITY PROCESS parameter before
changing the calibration mode. → See also Page 97.
Factory setting:
Wet
EMPTY CALIB. (314)
Entry
Enter level value for the lower calibration point (container empty).
The container is either empty or part full. By entering a value for this parameter, you are
assigning a level value to the pressure present at the device. → See also EMPTY
PRESSURE.
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
0.0
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
74
EMPTY PRESSURE (710)
Display
Displays the pressure value for the lower calibration point (container empty).
→ See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
0.0
FULL CALIB. (315)
Entry
Enter level value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you are assigning a level value to the pressure present at the device. → See also FULL
PRESSURE.
Prerequisite:
• CALIBRATION MODE = Wet
!
Note!
For this parameter, the on-site display shows the level value to be entered and the
pressure present at the device. In order for the level value to be saved together with the
pressure present at the device, the entry field for the level value must first be activated
using the "+"- or "–" key before confirming with the "E" key. This applies also if the level
value is to remain unchanged.
Factory setting:
100.0
FULL PRESSURE (711)
Display
Displays the pressure value for the upper calibration point (container full).
→ See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
High sensor limit (→ see PRESS. SENS HILIM, Page 119)
ADJUSTED DENSITY (810)
Display
Displays the density calculated from the upper and lower level point.
Prerequisite:
• CALIBRATION MODE = Wet, LIN. MEASURAND = Level
DENSITY UNIT (812)
Selection
Select density unit.
Prerequisite:
• LIN. MEASURAND = Level, CALIBRATION MODE = Dry
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Options:
• g/cm3
• kg/dm3
• kg/m3
• US lb/in3
• US lb/ft3
Factory setting:
kg/dm3
ADJUST DENSITY (316)
Entry
Enter density of fluid.
Prerequisite:
• LIN. MEASURAND = Level, CALIBRATION MODE = Dry
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1000.0
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
75
UNIT VOLUME (313)
Selection
Select volume unit.
Prerequisite:
• LIN. MEASURAND = Volume
Options:
• l
• hl
• cm3
• dm3
• m3
• m3 E3
• ft
• ft3 E3
• gal
• Igal
• bbl
• User unit, → see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m3
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. V
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m3".
→ See also CUSTOMER UNIT V.
Prerequisite:
• LIN. MEASURAND = Volume, UNIT VOLUME = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3 i 1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
TANK VOLUME (858)
Entry
Enter tank volume.
Prerequisite:
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1.0 m3
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
76
HEIGHT UNIT (708)
Selection
Select level unit.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
Options:
• mm
• dm
• cm
• m
• inch
• ft
• User unit, → see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. H.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m".
→ See also CUSTOMER UNIT H.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m i 1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
TANK HEIGHT (859)
Entry
Enter tank height.
Prerequisite:
• LIN. MEASURAND = Volume, CALIBRATION MODE = Dry
• LIN. MEASURAND = Mass, CALIBRATION MODE = Dry
Factory setting:
1.0 m
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
77
100% POINT (813)
Entry
Enter level value for 100% point.
Prerequisite:
• LIN. MEASURAND = % (Level), CALIBRATION MODE = Dry
Example:
– The 100 %-point should correspond to 4 m.
– Select the "m" unit via the HEIGHT UNIT parameter.
– Enter the value "4" for this parameter (100% POINT).
Factory setting:
1.0
ZERO POSITION (814)
Entry
Enter value for level offset.
If the measurement should not start at the mounting location of the device, e.g. for
containers with a sump, carry out zero point shift (level offset).
Prerequisite:
• CALIBRATION MODE = Dry
Factory setting:
0.0
P01-PMP75xxx-19-xx-xx-xx-001
Fig. 32:
Zero point shift
1
Device is mounted above the level lower range value: a positive value has to be
entered for ZERO POSITION.
2
Device is mounted below the level lower range value: a negative value has to be
entered for ZERO POSITION.
SET LRV (719)
Entry
Enter level value for the lower current value (4 mA).
Factory setting:
0.0
SET URV (720)
Entry
Enter level value for the upper current value (20 mA).
Factory setting:
100.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 11: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Linear"
Parameter name
Description
➀
➁
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
78
P01-xxxxxxxx-19-xx-xx-xx-088
Fig. 33:
BASIC SETUP function group for the "Level" measuring mode and the "Pressure Linearized" level type,
continue calibration with LINEARISATION function group
→ See Page 100 ff for on-site operation and Page 103 ff for operation with ToF Tool or HART handheld
terminal.
*
1)
1)
2)
*
*
*
*
*
*
2)
PRESS. ENG. UNIT
LEVEL SELECTION
Mass
Volume
%
MASS UNIT
CUSTOMER UNIT M
CUST. UNIT FACT. M
HYDR. PRESS MIN.
HYDR. PRESS MAX.
DAMPING VALUE
VOLUME UNIT
CUSTOMER UNIT V
CUST. UNIT FACT. V
LINd MEASURAND
LANGUAGE
Linear
Pressure
Linearized
Height
Linearized
Flow
Pressure
Level
LEVEL MODE
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Table 12: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Pressure Linearized"
Parameter name
Description
The following parameters are displayed if you selected the "Pressure Linearized" option for the LEVEL MODE parameter.
For this level type, the measured variable (volume, mass or %) is not in direct proportion to the measured pressure. For
the calibration, enter a linearisation table with at least 2 and not more than 32 points.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
• LEVEL SELECTION = Level Standard (→ see also Page 46).
• LEVEL MODE = Pressure Linearized (→ see also Page 68).
Note:
See also
– Page 67 ff, Table 10: BASIC SETUP – general
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 100 ff, Table 18: LINEARISATION – on-site operation
– Page 103 ff, Table 19: LINEARISATION – ToF Tool and HART handheld terminal
– Page 121 ff, Table 28: PROCESS VALUES
– Page 16 ff, Section 5 "Level measurement".
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
79
LINd. MEASURAND (805)
Selection
Select measured variable.
Options:
• Pressure and Volume
• Pressure and Mass
• Pressure and %
Factory setting:
Pressure and %
UNIT VOLUME (313)
Selection
Select volume unit.
Prerequisite:
• LINd. MEASURAND = Pressure and Volume
Options:
• l
• hl
• cm3
• dm3
• m3
• m3 E3
• ft
• ft3 E3
• gal
• Igal
• bbl
• User unit, → see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m3
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. V
Prerequisite:
• LINd. MEASURAND = Pressure and Volume,
UNIT VOLUME = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT V parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m3". → See also
CUSTOMER UNIT V.
Prerequisite:
• LINd. MEASURAND = Pressure and Volume,
UNIT VOLUME = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3 i 1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
Table 12: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Pressure Linearized"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
80
MASS UNIT (709)
Selection
Select mass unit.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass
Options:
• g
• kg
• t
• oz
• lb
• ton
• User unit, → see also the following parameter description for CUSTOMER UNIT M
and CUST. UNIT FACT. M.
Factory setting:
kg
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. M.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass,
MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. M (703)
Entry
Enter conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg". → See also
CUSTOMER UNIT M.
Prerequisite:
• LINd. MEASURAND = Pressure and Mass,
MASS UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 10 kg i 1 bucket
– Entry CUSTOMER UNIT M: bucket
– Entry CUST. UNIT FACT. M: 0.1
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
HYDR. PRESS MIN. (775)
Entry
Enter the minimum hydrostatic pressure to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum hydrostatic pressure to be
expected, the more accurate the measurement result.
Factory setting:
0.0
Table 12: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Pressure Linearized"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
81
HYDR. PRESS MAX. (761)
Entry
Enter the maximum hydrostatic pressure to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the maximum hydrostatic pressure to be
expected, the more accurate the measurement result.
Factory setting:
High sensor limit (→ See PRESS. SENS HILIM, Page 119)
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 12: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Pressure Linearized"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
82
P01-xxxxxxxx-19-xx-xx-xx-089
Fig. 34:
BASIC SETUP function group for the "Level" measuring mode and the "Height Linearized" level type, continue
calibration with LINEARISATION function group → See Page 100 ff for on-site operation and Page 103 ff for
operation with ToF Tool and HART handheld terminal.
1)
2)
1)
*
*
*
*
*
*
*
*
*
*
*
*
*
*
2)
LEVEL SELECTION
GROUP SELECTION
VOLUME UNIT
CUSTOMER UNIT M
CUST. UNIT FACT. V
LEVEL MIN
LEVEL MAX
...+Volume
...+Mass
...+%
Height+...
%-Height+...
Dry
Wet
Linear
Pressure
Linearized
Height
Linearized
Flow
Pressure
Level
MASS UNIT
CUSTOMER UNIT V
CUST. UNIT FACT. M
DAMPING VALUE
EMPTY CALIB.
DENSITY UNIT
ADJUST DENSITY
HEIGHT UNIT
100% POINT
ZERO POSITION
CUSTOMER UNIT H
CUST. UNIT FACT. H
FULL PRESSURE
EMPTY PRESSURE
FULL CALIB.
ADJUSTED DENSITY
CALIBRATION MODE
HEIGHT UNIT
CUSTOMER UNIT H
CUST. UNIT FACT. H
COMB. MEASURAND
LEVEL MODE
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
LANGUAGE
Measured value
MEASURING MODE
EXTENDED SETUP
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
83
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
The following parameters are displayed if you selected the "Height Linearized" option for the LEVEL MODE parameter.
Select this level type if you require two measured variables or if the container shape is given with value pairs, e.g. height
and volume.
The following combinations are possible:
• Height + Volume
• Height + Mass
• Height + %
• %-Height + Volume
• %-Height + Mass
• %-Height + %
The 1st measured variable (%-Height or Height) must be in direct proportion to the measured pressure. The 2nd
measured variable (Volume, Mass or %) must not be in direct proportion. A linearisation table must be entered for the
2nd measured variable. The 2nd measured variable is assigned to the 1st measured variable by means of this table.
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
• LEVEL SELECTION = Level Standard (→ see also Page 46).
• LEVEL MODE = Height Linearized (→ see also Page 68).
Note:
See also
– Page 67 ff, Table 10: BASIC SETUP – general
– Page 96 ff, Table 16: EXTENDED SETUP
– Page 100 ff, Table 18: LINEARISATION – on-site operation
– Page 103 ff, Table 19: LINEARISATION – ToF Tool and HART handheld terminal
– Page 121 ff, Table 28: PROCESS VALUES
– Page 16 ff, Section 5 "Level measurement".
COMB. MEASURAND (806)
Selection
Select measured variable.
Options:
• Height and Volume
• Height and Mass
• Height and %
• %-Height and Volume
• %-Height and Mass
• %-Height and %
Factory setting:
%-Height and %
HEIGHT UNIT (708)
Selection
Select level unit for the 1st measured variable.
Prerequisite:
• COMB. MEASURAND = Height and Volume, Height and Mass or Height and %
Options:
• mm
• dm
• cm
• m
• inch
• ft
• User unit, → see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
84
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. H.
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and Mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m". → See also
CUSTOMER UNIT H.
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and Mass, HEIGHT UNIT = User unit
• COMB. MEASURAND = Height and %, HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m i 1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
UNIT VOLUME (313)
Selection
Select the volume unit for the 2nd measured value.
Prerequisite:
• COMB. MEASURAND = Height and Volume or %-Height and Volume
Options:
• l
• hl
• cm3
• dm3
• m3
• m3 E3
• ft
• ft3 E3
• gal
• Igal
• bbl
• User unit, → see also the following parameter description for CUSTOMER UNIT V and
CUST. UNIT FACT. V.
Factory setting:
m3
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
85
CUSTOMER UNIT V (608)
Entry
Enter text (unit) for customer-specific volume unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. V
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and Volume,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT V parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. V (607)
Entry
Enter conversion factor for a customer-specific volume unit.
The conversion factor must be entered in relation to the SI unit "m3". → See also
CUSTOMER UNIT V.
Prerequisite:
• COMB. MEASURAND = Height and Volume, HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and Volume,
HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 0.01 m3 i 1 bucket
– Entry CUSTOMER UNIT V: bucket
– Entry CUST. UNIT FACT. V: 100
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
MASS UNIT (709)
Selection
Select the mass unit for the 2nd measured value.
Prerequisite:
• COMB. MEASURAND = Height and Mass or %-Height and Mass
Options:
• g
• kg
• t
• oz
• lb
• ton
• User unit, → see also the following parameter description for CUSTOMER UNIT M
and CUST. UNIT FACT. M.
Factory setting:
kg
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
86
CUSTOMER UNIT M (704)
Entry
Enter text (unit) for customer-specific mass unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. M.
Prerequisite:
• COMB. MEASURAND = Height and Mass, MASS UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, MASS UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT M parameter. The measured value is displayed with the additional
text "User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. M (703)
Entry
Enter conversion factor for a customer-specific mass unit.
The conversion factor must be entered in relation to the SI unit "kg". → See also
CUSTOMER UNIT M.
Prerequisite:
• COMB. MEASURAND = Height and Mass, MASS UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, MASS UNIT = User unit
Example:
– You want the measured value to be displayed in "buckets".
– MEASURED VALUE = 10 kg i 1 bucket
– Entry CUSTOMER UNIT M: bucket
– Entry CUST. UNIT FACT. M: 0.1
– Result: MEASURED VALUE = 1 bucket
Factory setting:
1.0
LEVEL MIN (755)
Entry
Enter the minimum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum level to be expected, the more
accurate the measurement result.
!
Note!
• The following applies for the setting LEVEL MODE "Height Linearized" and ASSIGN
CURRENT "Linear":
If you enter a new value for LEVEL MIN, the value for SET LRV is also changed. Use
SET LRV to assign a height to the lower current value. If you want to assign the lower
current value a value other than that for LEVEL MIN, you must enter the desired value
for SET LRV. (→ SET LRV, Page 97 and ASSIGN CURRENT, Page 113)
Factory setting:
0.0
LEVEL MAX (712)
Entry
Enter the maximum level to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the maximum level to be expected, the more
accurate the measurement result.
!
Note!
• The following applies for the setting LEVEL MODE "Height Linearized" and ASSIGN
CURRENT "Linear":
If you enter a new value for LEVEL MAX, the value for SET URV is also changed. Use
SET URV to assign a height to the upper current value. If you want to assign the upper
current value a value other than that for LEVEL MAX, you must enter the desired
value for SET URV. (→ SET URV, Page 98 and ASSIGN CURRENT, Page 113)
Factory setting:
100.0
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
87
CALIBRATION MODE (392)
Selection
Select the calibration mode for the calibration of the 1st measured variable.
Options:
• Wet
Wet calibration takes place by filling the container. This calibration mode requires two
pressure-level value pairs to be entered. In the case of two different levels, the level
value is entered and the pressure measured at this moment is assigned to the level
value.
→ See also the following parameter description for EMPTY CALIB., EMPTY
PRESSURE, FULL CALIB. and FULL PRESSURE.
• Dry
Dry calibration is a theoretical calibration which you can carry out even if the device is
not mounted or the container is empty.
– For the "Level" measured variable, the density of the fluid (→ see Page 88, ADJUST
DENSITY) must be entered.
– For the "%" measured variable, the density of the fluid must be entered and a level
assigned to the 100 % point (→ see Page 88, ADJUST DENSITY and 100% POINT).
If the measurement should not start at the mounting location of the device, a level
offset must be entered (→ see Page 90, ZERO POSITION).
!
Note!
If the change to dry calibration is made after a wet calibration, the density must be
entered correctly using the ADJUST DENSITY and DENSITY PROCESS parameter before
changing the calibration mode. → See also Page 97.
Factory setting:
Wet
EMPTY CALIB. (314)
Entry
Enter level value for the lower calibration point (container empty).
The container is either empty or part full. By entering a value for this parameter, you are
assigning a level value to the pressure present at the device. → See also EMPTY
PRESSURE.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
0.0
EMPTY PRESSURE (710)
Display
Displays the pressure value for the lower calibration point (container empty).
→ See also EMPTY CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
FULL CALIB. (315)
Entry
Enter level value for the upper calibration point (container full).
The container is either completely or almost full. By entering a value for this parameter,
you are assigning a level value to the pressure present at the device. → See also FULL
PRESSURE.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
100.0
FULL PRESSURE (711)
Display
Displays the pressure value for the upper calibration point (container full).
→ See also FULL CALIB.
Prerequisite:
• CALIBRATION MODE = Wet
Factory setting:
High sensor limit (→ see PRESS. SENS HILIM, Page 119)
ADJUSTED DENSITY (810)
Display
Displays the density calculated from the upper and lower level point.
Prerequisite:
• COMB. MEASURAND = Height and Volume, CALIBRATION MODE = Wet
• COMB. MEASURAND = Height and Mass, CALIBRATION MODE = Wet
• COMB. MEASURAND = Height and %, CALIBRATION MODE = Wet
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
88
DENSITY UNIT (812)
Selection
Select density unit.
Prerequisite:
• COMB. MEASURAND = %-Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and Mass, CALIBRATION MODE = Dry
Options:
• g/cm3
• kg/dm3
• kg/m3
• US lb/in3
• US lb/ft3
Factory setting:
kg/dm3
ADJUST DENSITY (316)
Entry
Enter density of fluid.
Prerequisite:
• COMB. MEASURAND = %-Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and %, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = Height and Mass, CALIBRATION MODE = Dry
Factory setting:
1.0
HEIGHT UNIT (708)
Selection
Select level unit.
Prerequisite:
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height + %, CALIBRATION MODE = Dry
Options:
• mm
• dm
• cm
• m
• inch
• ft
• User unit, → see also the following parameter description for CUSTOMER UNIT H
and CUST. UNIT FACT. H.
Factory setting:
m
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
89
CUSTOMER UNIT H (706)
Entry
Enter text (unit) for customer-specific level unit.
You can enter a maximum of eight alphanumeric characters here.
→ See also CUST. UNIT FACT. H.
Prerequisite:
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and %, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT H parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
CUST. UNIT FACT. H (705)
Entry
Enter conversion factor for a customer-specific level unit.
The conversion factor must be entered in relation to the SI unit "m". → See also
CUSTOMER UNIT H.
Prerequisite:
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
• COMB. MEASURAND = %-Height and %, CALIBRATION MODE = Dry,
HEIGHT UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE = 0.5 m i 1 PU
– Entry CUSTOMER UNIT H: PU
– Entry CUST. UNIT FACT. H: 2
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
100% POINT (813)
Entry
Enter level value for 100% point.
Prerequisite:
• COMB. MEASURAND = %-Height and Volume, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height and Mass, CALIBRATION MODE = Dry
• COMB. MEASURAND = %-Height + %, CALIBRATION MODE = Dry
Example:
– The 100 %-point should correspond to 4 m.
– Select the "m" unit via the HEIGHT UNIT parameter.
– Enter the value "4" for this parameter (100% POINT).
Factory setting:
1.0
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
90
ZERO POSITION (814)
Entry
Enter value for level offset.
If the measurement should not start at the mounting location of the device, e.g. for
containers with a sump, carry out zero point shift (level offset).
Prerequisite:
• CALIBRATION MODE = Dry
P01-PMP75xxx-19-xx-xx-xx-001
Fig. 35:
Zero point shift
1
Device is mounted above the level lower range value: a positive value has to be
entered for ZERO POSITION.
2
Device is mounted below the level lower range value: a negative value has to be
entered for ZERO POSITION.
Factory setting:
0.0
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 13: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Level",
LEVEL MODE "Height Linearized"
Parameter name
Description
➀
➁
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
91
P01-xxxxxxxx-19-xx-xx-xx-086
Fig. 36:
BASIC SETUP function group for the "Flow" measuring mode
*
*
*
*
1)
2)
1)
*
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
1) Display via on-site display only
2) Display via ToF Tool, FieldCare
or HART handheld terminal
Gas
std. cond.
Volume
p. cond.
Gas
norm cond.
Mass
DAMPING VALUE
MAX FLOW
MAX. PRESS. FLOW
CUST. UNIT. FACT. F
CUSTOMER UNIT F.
LANGUAGE
Flow
Pressure
Level
FLOW-MEAS. TYPE
PRESS. ENG. UNIT
CUSTOMER UNIT P
CUST. UNIT FACT. P
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
MEASURING MODE
EXTENDED SETUP
UNIT FLOW
NORM FLOW UNIT
STD. FLOW UNIT
MASS FLOW UNIT
Table 14: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name
Description
Prerequisite:
• MEASURING MODE = Flow (→ see also Page 45).
Note:
See also
– Page 52, Table 5: QUICK SETUP
– Page 98, Table 15: EXTENDED SETUP
– Page 107, Table 18: TOTALIZER SETUP
– Page 122, Table 27: PROCESS VALUES.
– Page 41 ff, Section 6 "Flow measurement".
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
92
MEASURING MODE
Selection
Select the measuring mode.
The operating menu is structured according to the selected measuring mode.
!
Note!
When the measuring mode is changed, no conversion takes place. The device has to be
recalibrated if the measuring mode is changed.
Prerequisite:
• ToF Tool, FieldCare or HART handheld terminal
Options:
• Pressure
• Level
• Deltabar S: Flow
Factory setting:
• Cerabar S and Deltabar S: Pressure
• Deltapilot S: Level
PRESS. ENG. UNIT (060)
Selection
Select pressure unit.
If a new pressure unit is selected, all pressure-specific parameters are converted and
displayed with the new unit.
Options:
• mbar, bar
• mmH2O, mH2O, inH2O, ftH2O
• Pa, hPa, kPa, MPa
• psi
• mmHg, inHg
• Torr
• g/cm2, kg/cm2
• lb/ft2
• atm
• gf/cm2, kgf/cm2
• User unit, → see also the following parameter description for CUSTOMER UNIT P and
CUST. UNIT FACT. P.
Factory setting:
Depends on the sensor nominal measuring range mbar or bar or as per order
specifications
CUSTOMER UNIT P (075)
Entry
Enter text (unit) for customer-specific pressure unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT P parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 14: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
93
CUST. UNIT FACT. P (317)
Entry
Enter conversion factor for a customer-specific pressure unit.
The conversion factor must be entered in relation to the SI unit "Pa". → See also
CUSTOMER UNIT P.
Prerequisite:
• PRESS. ENG. UNIT = User unit
Example:
– You want the measured value to be displayed in "PU" (PU: packing unit).
– MEASURED VALUE =10000 Pa i 1 PU
– Entry CUSTOMER UNIT P: PU
– Entry CUST. UNIT FACT. P: 0.0001
– Result: MEASURED VALUE = 1 PU
Factory setting:
1.0
FLOW-MEAS. TYPE (640)
Selection
Select the flow type.
Options:
• Volume p. cond. (volume under operating conditions)
• Gas norm. cond. (norm volume under norm conditions in Europe: 1013.25 mbar and
273.15 K (0°C))
• Gas std. cond. (standard volume under standard conditions in USA: 1013.25 mbar
(14.7 psi) and 288.15 K (15°C/59°F))
• Mass (mass under operating conditions)
Factory setting:
Volume p. cond.
UNIT FLOW (391)
Selection
Select volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Volume p. cond.
Options:
• m3/s, m3/min, m3/h, m3/day
• l/s, l/min, l/h
• hl/s, hl/min, hl/day
• ft3/s, ft3/min, ft3/h, ft3/day
• ACFS, ACFM, ACFH, ACFD
• ozf/s, ozf/min
• US Gal/s, US Gal/min, US Gal/h, US Gal/day
• Imp. Gal/s, Imp. Gal/min, Imp. Gal/h
• bbl/s, bbl/min, bbl/h, bbl/day
• User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
m3/s
NORM FLOW UNIT (661)
Selection
Select norm volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Gas norm conditions
Options:
• Nm3/s, Nm3/min, Nm3/h, Nm3/day
• User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
Nm3/s
Table 14: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
94
STD. FLOW UNIT (660)
Selection
Select standard volume flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Gas std. conditions
Options:
• Sm3/s, Sm3/min, Sm3/h, Sm3/day
• SCFS, SCFM, SCFH, SCFD
• User unit, → see also this table, parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
Sm3/s
MASS FLOW UNIT (571)
Selection
Select mass flow unit.
When a new flow unit is selected, all flow-specific parameters are converted and
displayed with the new unit within a flow mode (FLOW-MEAS. TYPE). When the flow
mode is changed, conversion is not possible.
Prerequisite:
• FLOW-MEAS. TYPE = Mass
Options:
• g/s, kg/s, kg/min, kg/min, kg/h
• t/s, t/min, t/h, t/day
• oz/s, oz/min
• lb/s, lb/min, lb/h
• ton/s, ton/min, ton/h, ton/day
• User unit, → see also the following parameter description for CUSTOMER UNIT F and
CUST. UNIT FACT. F
Factory setting:
kg/s
CUSTOMER UNIT F (610)
Entry
Enter text (unit) for customer-specific flow unit.
You can enter a maximum of eight alphanumeric characters here. → See also CUST.
UNIT FACT. F.
Prerequisite:
• UNIT FLOW = User unit
• NORM FLOW UNIT = User unit
• STD. FLOW UNIT = User unit
• MASS FLOW UNIT = User unit
!
Note!
Only the first five characters are shown on the on-site display. For example, if "crates" is
specified as the customer-specific unit, "crate" is displayed.
If the unit contains a slash, up to eight characters can be shown on the on-site display.
The maximum number of characters in the counter is again limited to five. For example,
if "crates/m2" is specified as the customer-specific unit, "crate/m2" is displayed. In the
ToF Tool and FieldCare, all eight characters are displayed.
In the HART handheld terminal, the customer-specific unit is only displayed in the
CUSTOMER UNIT F parameter. The measured value is displayed with the additional text
"User Unit".
Factory setting:
_ _ _ _ _ _ _ _
Table 14: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
95
CUST. UNIT FACT. F (609)
Entry
Enter conversion factor for a customer-specific flow unit. The conversion factor must be
entered in relation to an appropriate SI unit, e.g. m3/s for the "Volume p. cond." flow
mode. → See also CUSTOMER UNIT F.
Prerequisite:
• UNIT FLOW = User unit
• NORM FLOW UNIT = User unit
• STD. FLOW UNIT = User unit
• MASS FLOW UNIT = User unit
Example:
– You want the measured value to be displayed in "bucket/h".
– MEASURED VALUE =0.01 m3/s i 3600 bucket/h
– Entry CUSTOMER UNIT F: bucket/h
– Entry CUST. UNIT FACT. F: 360000
– Result: MEASURED VALUE = 3600 bucket/h
Factory setting:
1.0
MAX. FLOW (311)
Entry
Enter maximum flow of primary element.
→ See also layout sheet of primary element. The maximum flow is assigned to the
maximum pressure which you enter via MAX PRESS. FLOW.
!
Note!
Use the LINEAR/SQROOT parameter (→ Page 113) to specify the current signal for the
"Flow" measuring mode. The following applies for the "Flow (square root)" setting:
If you enter a new value for MAX. FLOW, the value for SET URV is also changed. Use
SET URV to assign a flow to the upper current value. If you want to assign the upper
current value a value other than that for MAX. FLOW, you must enter the desired value
for SET URV. (→ SET URV, Page 99).
Factory setting:
1.0
MAX PRESS. FLOW (634)
Entry
Enter maximum pressure of primary element.
→ See layout sheet of primary element. This value is assigned to the maximum flow value
(→ see MAX. FLOW).
!
Note!
Use the LINEAR/SQROOT parameter (→ Page 113) to specify the current signal for the
"Flow" measuring mode. The following applies for the "Differential pres." setting:
If you enter a new value for MAX PRESS. FLOW, the value for SET URV is also changed.
Use SET URV to assign a pressure value to the upper current value. If you want to assign
the upper current value a value other than that for MAX PRESS. FLOW, you must enter
the desired value for SET URV. (→ SET URV, Page 99).
Factory setting:
High sensor limit (→ see PRESS. SENS HILIM, Page 119)
DAMPING VALUE (247)
Entry
Enter damping time (time constant τ).
The damping affects the speed at which all subsequent elements, such as the on-site
display, measured value and current output react to a change in the pressure.
Input range:
0.0...999.0 s
Factory setting:
2.0 s or as per order specifications
Table 14: (GROUP SELECTION →) OPERATING MENU → SETTINGS → BASIC SETUP "Flow"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
96
P01-xxxxxxxx-19-xx-xx-xx-090
Fig. 37:
EXTENDED SETUP function group
→ For the "Pressure" measuring mode, see Page 96, Table 15
→ For the "Level" measuring mode, see Page 96, Table 16
→ For the "Flow" measuring mode, see Page 98, Table 17
*
*
*
1)
1)
*
LANGUAGE
Flow
Pressure
Level
BASIC SETUP
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
EXTENDED SETUP
TEMP. ENG. UNIT
TEMP. ENG. UNIT
LOW FLOW CUT-OFF
SET L. FL. CUT-OFF
SET LRV
SET URV
ADJUST DENSITY
PROCESS DENSITY
SET LRV
SET URV
TEMP. ENG. UNIT
1) Display via on-site display only
Parameters marked with an asterisk "*"
are not always displayed. The display
depends on the settings of other parameters,
see the following Table.
Table 15: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Pressure"
Parameter name
Description
Prerequisite:
• MEASURING MODE = Pressure (→ see also Page 45).
Note:
• See also Page 13 ff, Section 4 "Pressure measurement".
TEMP. ENG. UNIT (318)
Selection
Select the unit for the temperature measured values.
→ See also PCB TEMPERATURE (Page 117) and SENSOR TEMP. (Page 121).
Options:
• °C
• °F
• K
• R
Factory setting:
°C
Table 16: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
Parameter name
Description
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
Note:
• See also Page 16 ff, Section 5 "Level measurement".
TEMP. ENG. UNIT (318)
Selection
Select the unit for the temperature measured values.
→ See also PCB TEMPERATURE (Page 117) and SENSOR TEMP. (Page 122).
Options:
• °C
• °F
• K
• R
Factory setting:
°C
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
97
DENSITY UNIT (001)/(812)
Options
Select density unit.
Options:
• g/cm3
• kg/dm3
• kg/m3
• US lb/in3
• US lb/ft3
Factory setting:
kg/dm3
ADJUST DENSITY
(007)/(316)
Entry
Enter density of fluid.
!
Note!
LIN. MEASURAND: "% (Level)", "Mass" and "Volume" and MEASUAND KOMB.:
If a change to dry calibration is made after a wet calibration using the CALIBRATION
MODE parameter (→ Page 73 or 87), the density for this parameter must be entered
correctly before changing the calibration mode. In the event that the pressure falls with
increasing levels (LIN. MEASURED: Volume), such as in the case of a residual volume
measurement, a negative value shall be entered for this parameter.
Factory setting:
1.0
PROCESS DENSITY
(025)/(811)
Entry
Enter a new density value for density correction.
The calibration was carried out with the medium water, for example. Now the container
is to be used for another fluid with another density. The calibration is corrected
appropriately by entering the new density value in the PROCESS DENSITY parameter.
!
Note!
LIN. MEASURAND: "% (Level)", "Mass" and "Volume" and MEASUAND KOMB.:
If a change to dry calibration is made after a wet calibration using the CALIBRATION
MODE parameter (→ Page 73 or 87), the density for this parameter must be entered
correctly before changing the calibration mode. In the event that the pressure falls with
increasing levels (LIN. MEASURED: Volume), such as in the case of a residual volume
measurement, a negative value shall be entered for this parameter.
Factory setting:
1.0
SET LRV (762)
Entry
Enter value for the lower current value (4 mA).
Prerequisite:
• LEVEL MODE = Pressure Linearized or Height Linearized
!
Note!
• For the LEVEL MODE "Height Linearized", you can use the ASSIGN CURRENT
parameter (→ Page 113) to specify whether the current output should depict the 1st or
2nd measured variable (height or tank content). Depending on the setting of the
ASSIGN CURRENT parameter, enter the following value for SET LRV:
– ASSIGN CURRENT = tank content (factory setting) ⇒ %- value, volume value or
mass value
– ASSIGN CURRENT = height ⇒ level value
The following applies for the LEVEL MODE "Pressure Linearized" or LEVEL MODE
"Height Linearized" + ASSIGN CURRENT "Tank content":
• If you enter a new value for TANK CONTENT MIN, the value for SET LRV is also
changed. If you want to assign the lower current value a value other than that for
TANK CONTENT MIN, you must enter the desired value for SET LRV. (→ TANK
CONTENT MIN, Page 100 or 104.)
The following applies for the LEVEL MODE "Height Linearized" + ASSIGN CURRENT
"Height":
• If you enter a new value for LEVEL MIN, the value for SET LRV is also changed. If you
want to assign the lower current value a value other than that for LEVEL MIN, you
must enter the desired value for SET LRV. (→ LEVEL MIN, Page 86.)
Factory setting:
0.0
Table 16: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
Parameter name
Description
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
98
SET URV (763)
Entry
Enter value for the upper current value (20 mA).
Prerequisite:
• LEVEL MODE = Pressure Linearized or Height Linearized
!
Note!
• For the LEVEL MODE "Height Linearized", you can use the ASSIGN CURRENT
parameter (→ Page 113) to specify whether the current output should depict the 1st or
2nd measured variable (height or tank content). Depending on the setting of the
ASSIGN CURRENT parameter, enter the following value for SET URV:
– ASSIGN CURRENT = tank content (factory setting) ⇒ %- value, volume value or
mass value
– ASSIGN CURRENT = height ⇒ level value
The following applies for the LEVEL MODE "Pressure Linearized" or LEVEL MODE
"Height Linearized" + ASSIGN CURRENT "Tank content":
• If you enter a new value for TANK CONTENT MAX, the value for SET URV is also
changed. If you want to assign the upper current value a value other than that for
TANK CONTENT MAX, you must enter the desired value for SET URV. (→ TANK
CONTENT MAX, Page 101 or 104.)
The following applies for the LEVEL MODE "Height Linearized" + ASSIGN CURRENT
"Height":
• If you enter a new value for LEVEL MAX, the value for SET URV is also changed. If you
want to assign the lower current value a value other than that for LEVEL MAX, you
must enter the desired value for SET URV.
(→ LEVEL MAX, Page 86.)
Factory setting:
100.0
Table 17: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Flow"
Parameter name
Description
Prerequisite:
• MEASURING MODE = Flow (→ see also Page 45).
Note:
• See also Page 41 ff, Section 6 "Flow measurement".
TEMP. ENG. UNIT (318)
Selection
Select the unit for the temperature measured value.
→ See also PCB TEMPERATURE (Page 117) and SENSOR TEMP. (Page 122).
Options:
• °C
• °F
• K
• R
Factory setting:
°C
LOW FLOW CUT-OFF (442)
Selection
Switches "low flow cut-off" function on and off.
In the lower measuring range, small flow quantities (creepages) can lead to large
measured value fluctuations. Switching on this function stops these flow quantities from
being recorded. → See also SET. L. FL. CUT-OFF.
Options:
• Off
• On
Factory setting:
Off
Table 16: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Level"
Parameter name
Description
Cerabar S/Deltabar S/Deltapilot S
Description of parameters
99
SET. L. FL. CUT-OFF (323)
Entry
Enter switch-off point of low flow cut-off.
The hysteresis between the switch-on point and the switch-off point is always 1 % of the
end flow value. → See also LOW FLOW CUT-OFF.
Prerequisite:
• LOW FLOW CUT-OFF = on
Input range:
Switch-off point: 0...50 % of end flow value (→ MAX. FLOW).
P01-PMD7xxxx-05-xx-xx-xx-000
Factory setting:
5 % (of end flow value)
SET LRV (637)
Entry
Depending on the setting in the LINEAR/SQROOT parameter (→ Page 113), enter a flow
value or a pressure value for the lower current value (4 mA) here.
• LINEAR/SQROOT = Flow (square root) (factory setting) ⇒ flow value
• LINEAR/SQROOT = Differential pres. ⇒ pressure value
Factory setting:
0
SET URV (638)
Entry
Depending on the setting in the LINEAR/SQROOT parameter (→ Page 113), enter a flow
value or a pressure value for the upper current value (20 mA) here.
• LINEAR/SQROOT = Flow (square root) (factory setting) ⇒ flow value
• LINEAR/SQROOT = Differential pres. ⇒ pressure value
The following applies for the setting LINEAR/SQROOT "Flow (square root)":
• If you enter a new value for MAX. FLOW, the value for SET URV is also changed. If
you want to assign the upper current value a value other than that for MAX. FLOW,
you must enter the desired value for SET URV. (→ MAX. FLOW, Page 95).
The following applies for the setting LINEAR/SQROOT "Differential pres.":
• If you enter a new value for MAX PRESS. FLOW, the SET URV value is also changed. If
you want to assign the upper current value a value other than that for MAX PRESS.
FLOW, you must enter the desired value for SET URV. (→ MAX PRESS. FLOW,
Page 95).
Factory setting:
MAX. FLOW
Table 17: (GROUP SELECTION →) OPERATING MENU → SETTINGS → EXTENDED SETUP "Flow"
Parameter name
Description
6%
5%
➀
➁
0%
0%
Q
Qmax
Q
Qmax
∆p
∆p
Description of parameters
Cerabar S/Deltabar S/Deltapilot S
100
P01-xxxxxxxx-19-xx-xx-xx-091
Fig. 38:
LINEARISATION function group for on-site operation
1)
1)
EDITOR TABLE
EDITOR TABLE
MEASURING TABLE
Editor Table
Measuring Table
EDITOR TABLE
TANK CONTENT MIN
LIN. EDIT MODE
TANK DESCRIBTION
TANK CONTENT MAX
TABLE SELECTION
MEASURING TABLE
LANGUAGE
DISPLAY
SETTINGS
POSITION ADJUSTMENT
OPERATING MENU
GROUP SELECTION
Measured value
LINEARIZATION
Level measuring
mode only
1) Display via on-site display only
Table 18: (GROUP SELECTION →) OPERATING MENU → SETTINGS → LINEARISATION
– on-site operation
Parameter name
Description
Prerequisite:
• MEASURING MODE = Level (→ see also Page 45).
• LEVEL MODE = Pressure Linearized or Height Linearized (→ see also Page 68).
Note:
– See also Page 16 ff, Section 5 "Level measurement".
TANK CONTENT MIN (759)
Entry
Enter the minimum tank contents to be expected.
The input limits for the calibration (editing limits) are derived from the value entered. The
closer the value entered corresponds to the minimum tank content to be expected, the
more accurate the measurement result.
!
Note!
• If you enter a new value for TANK CONTENT MIN, the value for SET LRV is also
changed. Use SET LRV to assign a %-value, volume value or mass value to the lower
current value. If you want to assign the lower current value a value other than that for
TANK CONTENT MIN, you must enter the desired value for SET LRV. (→ SET LRV,
Page 97).
• For the setting LEVEL MODE "Height Linearized" and ASSIGN CURRENT "Linear",
the TANK CONTENT MIN parameter does not affect the SET LRV parameter. (→ SET
LRV, Page 97 and ASSIGN CURRENT, Page 113)
Factory setting:
0.0