Brief Operating Instructions
Micropilot FMR50
Level radar
These Instructions are Brief Operating Instructions; they do not
replace the Operating Instructions included in the scope of
supply.
For detailed information, refer to the Operating Instructions
and other documentation on the CD-ROM provided or visit
"www.endress.com/deviceviewer".
KA01128F/00/EN/01.13
71217610
Table of contents
Micropilot FMR50
2
Endress+Hauser
Table of contents
1
Important document information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
1.1
Document conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
2
Basic safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.1
Requirements for the personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.2
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.3
Workplace safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
2.4
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
2.5
Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
3
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
3.1
Product design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
4
Incoming acceptance and product identification . . . . . . . . . . . . . . . . . . . . . . . . . .
10
4.1
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
4.2
Product identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
5
Storage, Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
5.1
Storage conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
5.2
Transport product to the measuring point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.1
Installation conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
6.2
Measuring conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
6.3
Installation in vessel (free space) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
6.4
Installation in stilling well . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
6.5
Installation in bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
6.6
Vessels with heat insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
6.7
Turning the transmitter housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
6.8
Turning the display module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
6.9
Post-installation check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
7
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
7.1
Connection conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
7.2
Connecting the measuring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
7.3
Post-connection check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
8
Integration into a PROFIBUS network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8.1
Overview of the device database files (GSD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
8.2
Set device address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
9
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
9.1
Display and operating module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
43
9.2
Operating menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
9.3
Unlock the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
9.4
Setting the operating language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
9.5
Configuration of a level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
47
9.6
User-specific applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
49
Important document information
Endress+Hauser
3
1
Important document information
1.1
Document conventions
1.1.1
Safety symbols
Symbol
Meaning
DANGER
A0011189-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTICE
A0011192-EN
NOTICE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
1.1.2
Electrical symbols
Symbol
Meaning
A0011197
Direct current
A terminal to which DC voltage is applied or through which direct current flows.
A0011198
Alternating current
A terminal to which alternating voltage is applied or through which alternating current flows.
A0017381
Direct current and alternating current
• A terminal to which alternating voltage or DC voltage is applied.
• A terminal through which alternating current or direct current flows.
A0011200
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding
system.
A0011199
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0011201
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
equalization line or a star grounding system depending on national or company codes of
practice.
Important document information
Micropilot FMR50
4
Endress+Hauser
1.1.3
Tool symbols
A0011219
A0011220
A0013442
A0011221
A0011222
Cross-head
screwdriver
Flat blade
screwdriver
Torx screwdriver
Allen key
Hexagon wrench
1.1.4
Symbols for certain types of information
Symbol
Meaning
A0011182
Allowed
Indicates procedures, processes or actions that are allowed.
A0011183
Preferred
Indicates procedures, processes or actions that are preferred.
A0011184
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011193
Tip
Indicates additional information.
A0011194
Reference to documentation
Refers to the corresponding device documentation.
A0011195
Reference to page
Refers to the corresponding page number.
A0011196
Reference to graphic
Refers to the corresponding graphic number and page number.
,
…
,
Series of steps
Result of a sequence of actions
1.1.5
Symbols in graphics
Symbol
Meaning
1, 2, 3 ...
Item numbers
,
…
,
Series of steps
A, B, C, ...
Views
A-A, B-B, C-C, ...
Sections
Important document information
Endress+Hauser
5
Symbol
Meaning
-
A0011187
Hazardous area
Indicates a hazardous area.
.
A0011188
Safe area (non-hazardous area)
Indicates a non-hazardous location.
1.1.6
Symbols at the device
Symbol
Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Basic safety instructions
Micropilot FMR50
6
Endress+Hauser
2
Basic safety instructions
2.1
Requirements for the personnel
The personnel must fulfill the following requirements for its tasks:
‣ Trained, qualified specialists must have a relevant qualification for this specific
function and task
‣ Are authorized by the plant owner/operator
‣ Are familiar with federal/national regulations
‣ Before beginning work, the specialist staff must have read and understood the
instructions in the Operating Instructions and supplementary documentation as well
as in the certificates (depending on the application)
‣ Following instructions and basic conditions
2.2
Designated use
Application and measured materials
The measuring device described in these Operating Instructions is intended for the
continuous, contactless level measurement of liquids, pastes and sludge. The device can
also be freely mounted outside closed metal vessels because of its operating frequency
of about 26 GHz, a maximum radiated pulsed power of 5.7 mW and an average power
output of 0.015 mW (for the version with advanced dynamics: maximum pulse power:
23.3 mW; average power: 0.076 mW). Operation is completely harmless to humans
and animals.
Observing the limit values specified in the "Technical data" and listed in the Operating
Instructions and supplementary documentation, the measuring device may be used for
the following measurements only:
‣ Measured process variables: level, distance, signal strength
‣ Calculated process variables: Volume or mass in arbitrarily shaped vessels; flow
through measuring weirs or flumes (calculated from the level by the linearization
functionality)
To ensure that the measuring device remains in proper condition for the operation
time:
‣ Use the measuring device only for measured materials against which the process-
wetted materials are adequately resistant.
‣ Observe the limit values in "Technical data".
Incorrect use
The manufacturer is not liable for damage caused by improper or non-designated use.
Verification for borderline cases:
‣ For special measured materials and cleaning agents, Endress+Hauser is glad to
provide assistance in verifying the corrosion resistance of wetted materials, but does
not accept any warranty or liability.
Residual risk
The electronics housing and its built-in components such as display module, main
electronics module and I/O electronics module may heat to 80 °C (176 °F) during
Basic safety instructions
Endress+Hauser
7
operation through heat transfer from the process as well as power dissipation within
the electronics. During operation the sensor may assume a temperature near the
temperature of the measured material.
Danger of burns due to heated surfaces!
‣ For high process temperatures: Install protection against contact in order to prevent
burns.
2.3
Workplace safety
For work on and with the device:
‣ Wear the required personal protective equipment according to federal/national
regulations.
2.4
Operational safety
Risk of injury.
‣ Operate the device in proper technical condition and fail-safe condition only.
‣ The operator is responsible for interference-free operation of the device.
Conversions to the device
Unauthorized modifications to the device are not permitted and can lead to
unforeseeable dangers.
‣ If, despite this, modifications are required, consult with the manufacturer.
Repair
To ensure continued operational safety and reliability,
‣ Carry out repairs on the device only if they are expressly permitted.
‣ Observe federal/national regulations pertaining to repair of an electrical device.
‣ Use original spare parts and accessories from the manufacturer only.
Hazardous area
To eliminate a danger for persons or for the facility when the device is used in the
hazardous area (e.g. explosion protection, pressure vessel safety):
‣ Based on the nameplate, check whether the ordered device is permitted for the
intended use in the hazardous area.
‣ Observe the specifications in the separate supplementary documentation that is an
integral part of these Instructions.
2.5
Product safety
This measuring device is designed in accordance with good engineering practice to
meet state-of-the-art safety requirements, has been tested, and left the factory in a
condition in which they are safe to operate.
It meets general safety standards and legal requirements. It also complies with the EC
directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser
confirms this by affixing the CE mark to the device.
Design of the Micropilot FMR50 (26 GHz)
1
Electronics housing
2
Process connection (Thread)
3
Horn antenna 40 mm (1-1/2 in), PVDF encapsulated
4
Horn antenna 80mm/100 mm (3in/4 in), PP cladded
5
Slip-on flange
6
Mounting bracket
Design of the electronics housing
1
Electronics compartment cover
2
Display module
3
Main electronics module
4
Cable glands (1 or 2, depending on instrument version)
5
Nameplate
6
I/O electronics module
7
Terminals (pluggable spring terminals)
8
Connection compartment cover
9
Grounding terminal
Incoming acceptance and product identification
Micropilot FMR50
10
Endress+Hauser
4
Incoming acceptance and product identification
4.1
Incoming acceptance
A0013696
DELIVERY NOTE
1 = 2
A0016870
A0016871
A0013696
A0016872
Incoming acceptance and product identification
Endress+Hauser
11
A0013696
DELIVERY NOTE
Made in Germany, 79689 Maulburg
A0014038
A0013696
A0014037
If one of the conditions does not comply, contact your Endress+Hauser distributor.
Incoming acceptance and product identification
Micropilot FMR50
12
Endress+Hauser
4.2
Product identification
The following options are available for identification of the measuring device:
• Nameplate specifications
• Extended order code with breakdown of the device features on the delivery note
• Enter serial numbers from nameplates in W@M Device Viewer
( www.endress.com/deviceviewer ): All information about the measuring device is
displayed.
For an overview of the scope of the Technical Documentation provided, refer to the
following: enter serial numbers from nameplates in W@M Device Viewer
( www.endress.com/deviceviewer )
4.2.1
Nameplate
Order�code:
Ext.�ord.�cd.:
Ser.�no.:
1
2
3
A0014103
3
Example of a nameplate
1
Order code
2
Serial number (Ser. no.)
3
Extended order code (Ext. ord. cd.)
For detailed information about interpreting the nameplate specifications, refer to
the Operating Instructions for the device on the CD-ROM provided.
Only 33 digits of the extended order code can be indicated on the nameplate. If
the extended order code exceeds 33 digits, the rest will not be shown. However,
the complete extended order code can be viewed in the operating menu of the
device (Diagnostics → Device info → Extended order code 1/2/3).
• Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use the original packaging.
5.2
Transport product to the measuring point
NOTICE
Housing or antenna horn may be damaged or break away.
Risk of injury!
‣ Transport the measuring device to the measuring point in its original packaging or
at the process connection.
‣ Do not fasten lifting devices (hoisting slings, lifting eyes etc.) at the housing or the
antenna horn but at the process connection. Take into account the mass center of
the device in order to avoid unintended tilting.
‣ Comply with the safety instructions, transport conditions for devices over 18kg
(39.6lbs).
A0016875
• Recommended distance A from
wall to outer edge of nozzle: ~
1/6 of tank diameter.
Nevertheless the device should
not be installed closer than
15 cm (5.91 in) to the tank
wall.
• Not in the center (2), as
interference can cause signal
loss.
• Not above the fill stream (3).
• It is recommended to us a
weather protection cover (1) in
order to protect the device from
direct sun or rain.
Avoid any installations (limit
switches, temperature sensors,
braces, vacuum rings, heating
coils, baffles etc.) inside the
signal beam. Take into account
the beam angle (→ 19).
Reduction of interference echoes
A0016890
Metallic screens mounted at
a slope spread the radar
signal and can, therefore,
reduce interference echoes.
6.1.4
Measurement in a plastic vessel
If the outer wall of the vessel is made of a non-conductive material (e.g. GRP),
microwaves can also be reflected off interfering installations outside the signal beam
(e.g. metallic pipes (1), ladders (2), grates (3), ...). Therefore, there should be no such
interfering installations in the signal beam. Please contact Endress+Hauser for further
information.
• Antenna size
The bigger the antenna, the smaller the beam angle α and the fewer interference
echoes (→ 19).
• Mapping
The measurement can be optimized by means of electronic suppression of
interference echoes.
• Antenna alignment
Take into account the marker on the flange or threaded connection (→ 22)
(→ 24) .
• Stilling well
A stilling well can be applied to avoid interferences (→ 27).
• Metallic screens mounted at a slope
They spread the radar signals and can, therefore, reduce interference echoes.
Relationship between beam angle α, distance D and beamwidth diameter W
The beam angle is defined as the angle α where the energy density of the radar waves
reaches half the value of the maximum energy density (3-dB-width). Microwaves are
also emitted outside the signal beam and can be reflected off interfering installations.
Beam diameter W as a function of beam angle α and measuring distance D:
FMR50
Antenna size
40 mm (¹-¹⁄₂ in)
80 mm (3 in)
100 mm (4 in)
Beam angle α
23°
10°
8°
Measuring distance (D)
Beamwidth diameter W
3 m (9.8 ft)
1.22 m (4 ft)
0.53 m (1.7 ft)
0.42 m (1.4 ft)
6 m (20 ft)
2.44 m (8 ft)
1.05 m (3.4 ft)
0.84 m (2.8 ft)
9 m (30 ft)
3.66 m (12 ft)
1.58 m (5.2 ft)
1.26 m (4.1 ft)
12 m (39 ft)
4.88 m (16 ft)
2.1 m (6.9 ft)
1.68 m (5.5 ft)
15 m (49 ft)
6.1 m (20 ft)
2.63 m (8.6 ft)
2.10 m (6.9 ft)
20 m (66 ft)
8.14 m (27 ft)
3.50 m (11 ft)
2.80 m (9.2 ft)
25 m (82 ft)
10.17 m (33 ft)
4.37 m (14 ft)
3.50 m (11 ft)
30 m (98 ft)
-
5.25 m (17 ft)
4.20 m (14 ft)
35 m (115 ft)
-
6.12 m (20 ft)
4.89 m (16 ft)
40 m (131 ft)
-
7.00 m (23 ft)
5.59 m (18 ft)
• In case of boiling surfaces, bubbling or tendency for foaming use FMR53 or
FMR54. Depending on its consistence, foam can either absorb microwaves or reflect
them off the foam surface. Measurement is possible under certain conditions. For
FMR50, FMR51 and FMR52, the additional option "Advanced dynamics" is
recommended in these cases (feature 540: "Application Package", option EM).
• In case of heavy steam development or condensate, the maximum measuring range
of FMR50, FMR51 and FMR52 may decrease depending on density, temperature and
composition of the steam → use FMR53 or FMR54.
• For the measurement of absorbing gases such as ammonia NH3 or some
fluorocarbons 1), please use Levelflex or Micropilot FMR54 in a stilling well.
• The measuring range begins, where the beam hits the tank bottom. Particularly with
dish bottoms or conical outlets the level cannot be detected below this point.
• For stilling well applications, the zero should be positioned at the end of the tube, as
the electromagnetic waves do not propagate completely outside the tube. It must be
taken into account that the accuracy may be reduced in the area C. In order to
guarantee the required accuracy in these cases, it is recommended to position the
zero-point at a distance C above the end of the tube (see figure).
• In case of media with a low dielectric constant (εr = 1.5 to 4) 2) the tank bottom can
be visible through the medium at low levels (low height C). Reduced accuracy has to
be expected in this range. If this is not acceptable, we recommend positioning the
zero point at a distance C (see figure) above the tank bottom in these applications.
• In principle it is possible to measure up to the tip of the antenna with FMR51,
FMR53 and FMR54. However, due to considerations regarding corrosion and build-
up, the end of the measuring range should not be chosen any closer than A (see
figure) to the tip of the antenna.
• When using FMR54 with planar antenna, especially for media with low dielectric
constants, the end of the measuring range should not be closer than 1 m (3.28 ft) to
the flange.
• The smallest possible measuring range B depends on the antenna version (see
figure).
• The tank height should be at least H (see table).
1)
Affected compounds are e.g. R134a, R227, Dymel 152a.
2)
Dielectric constants of important media commonly used in the industry are summarized in the document
SD106F, which can be downloaded from the Endress+Hauser web page (www.endress.com).
A [mm (in)]
B [m (ft)]
C [mm (in)]
H [m (ft)]
FMR50
150 (
5.91)
> 0.2 (0.7)
50 to 250 (1.97 to 9.84)
> 0.3 (1.0)
Installation in vessel (free space)
6.3.1
Horn antenna encapsulated (FMR50)
Alignment
• Align the antenna vertically to the product surface.
• A marking at the threaded connection enables alignment of the antenna. This
marking must be aligned towards the tank wall as well as possible.
90°
90°
90°
90°
90°
A0019434
Nozzle mounting
For optimum measurement, the tip of the antenna should extend below the nozzle.
Nozzle heights up to 500 mm (19.7 in) can be accepted if this should not be possible
due to mechanical reasons.
Nozzle height and diameter for horn antenna, encapsulated (FMR50)
Antenna size
40 mm (1½ in)
D
39 mm (1.54 in)
H
< 60 mm (2.36 in)
Please contact Endress+Hauser for applications with higher nozzle.
Threaded connection
• Tighten with the hexagonal nut only.
• Tool : Hexagonal wrench 50 mm
• Maximum permissible torque: 35 Nm (26 lbf ft)
Horn antenna with slip-on flange (FMR50)
Alignment
When using the Micropilot with a slip-on flange in explosion-hazardous areas,
strictly observe all specifications in the relevant Safety Instructions (XA).
• Align the antenna vertically to the product surface.
Optionally, a variable flange seal, which is available as an accessory, can be used for
alignment (see Technical Information BA01048F, chapter "Accessories").
• A marking at the feedthrough enables alignment of the antenna. This marking must
be aligned towards the tank wall as well as possible.
90°
90°
90°
90°
90°
A0019439
Nozzle height and diameter for horn antenna with slip-on flange (FMR50/FMR56)
Antenna
size
80 mm (3 in)
100 mm (4 in)
D
80 mm (3.15 in)
100 mm (3.94 in)
150 mm (5.91 in)
100 mm (3.94 in)
150 mm (5.91 in)
H
<
500 mm (19.7 in)
<
500 mm (19.7 in)
<
500 mm (19.7 in)
<
500 mm (19.7 in)
<
500 mm (19.7 in)
Horn antenna with mounting bracket (FMR50)
A0016865
7
Installation of the horn antenna with mounting bracket (FMR50/FMR56)
Align the antenna vertically to the product surface using the mounting bracket.
NOTICE
The mounting bracket has no conductive connection to the transmitter housing.
Danger of electrostatic charge
‣ Connect the mounting bracket to the local potential equalization system.
Installation in stilling well
1
90°
A0016841
8
Installation in stilling well
1
Marking for antenna alignment
• For horn antenna: Align the marking towards the slots of the stilling well.
• Measurements can be performed through an open full bore ball valve without any
problems.
• After mounting, the housing can be turned 350° in order to simplify access to the
display and the terminal compartment (→ 29).
Installation in bypass
1
2
2
90°
90°
A0019446
9
Installation in bypass
1
Marking for antenna alignment
2
Tank connectors
• Alighn the marker perpendicular (90°) to the tank connectors.
• Measurements can be performed through an open full bore ball valve without any
problems.
• After mounting, the housing can be turned 350° in order to simplify access to the
display and the terminal compartment (→ 29).
Vessels with heat insulation
1
2
A0019141
If process temperatures are high, the device must be included in normal tank insulation
to prevent the electronics heating up as a result of heat radiation or convection. The
insulation may not exceed beyond the neck of the housing.
6.7
Turning the transmitter housing
To provide easier access to the connection compartment or display module, the
transmitter housing can be turned:
max.�350°
8�mm
8�mm
A0013713
1.
Unscrew the securing screw using an open-ended wrench.
2.
Rotate the housing in the desired direction.
Tighten the securing screw (1,5 Nm for plastics housing; 2,5 Nm for aluminium
or stainless steel housing).
6.8
Turning the display module
+
E
–
1
3�mm
A0013905
1.
Loosen the screw of the securing clamp of the electronics compartment cover
using an Allen key and turn the clamp 90° conterclockwise.
2.
Unscrew cover of the electronics compartment from the transmitter housing.
3.
Pull out the display module with a gentle rotation movement.
4.
Rotate the display module into the desired position: Max. 8 × 45 ° in each
direction.
5.
Feed the spiral cable into the gap between the housing and main electronics
module and plug the display module into the electronics compartment until it
engages.
6.
Screw the cover of the electronics compartment firmly back onto the transmitter
housing.
7.
Tighten the securing clamp again using the Allen key.
6.9
Post-installation check
m
Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"
document)
• Ambient temperature range
• Measuring range
m
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
m
Are the securing screw and securing clamp tightened securely?
For ambient temperature TU≥60 °C (140 °F): use cable for temperature TU +20 K.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions
BA00034S "Guidelines for planning and commissioning PROFIBUS DP/PA", PNO
Guideline 2.092 "PROFIBUS PA User and Installation Guideline" and IEC61158-2
(MBP).
PROFIBUS PA / FOUNDATION Fieldbus
1
3
+
+
2
4
FIELDBUS
2-channel overvoltage protection
-
-
71128619
[17]
4-20mA/
4-20mA/
B
1
1
+
+
2
2
FIELDBUS
Spare part
71023457
PA/FF
[06/07]
FIELDBUS
-
-
1
3
+
+
2
4
PA/FF
10 mm
Spare part
71108xxx
2- wire level
4-20 mA
PFS
FIELDBUS
[26/27]
open
-
-
A
4
1
1
2
3
6
5
3+
3+
4-
4-
A0011341
10
Terminal assignment PROFIBUS PA / FOUNDATION Fieldbus
A
Without integrated overvoltage protection
B
With integrated overvoltage protection
1
Cable screen: Observe cable specifications (→ 32)
2
Terminals for switch output (open collector)
3
Terminals PROFIBUS PA / FOUNDATION Fieldbus
4
Terminal for potential equalization line
5
Cable entries
6
Overvoltage protection module
Connection examples for the switch output
3+
+-
4-
A0015909
11
Connection of a relay
Suitable relays (examples):
• Solid-state relay: Phoenix Contact OV-24DC/480AC/5 with
mounting rail connector UMK-1 OM-R/AMS
• Electromechanical relay: Phoenix Contact PLC-
RSC-12DC/21
3+
2
1
+
4-
A0015910
12
Connection of a digital input
1
Pull-up resistor
2
Digital input
Device plug connectors
For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be
connected without opening the housing.
Pin assignment of the M12 plug connector
2
1
3
4
A0011175
Pin
Meaning
1
Signal +
2
not connected
3
Signal -
4
Ground
Pin assignment of the 7/8" plug connector
2
1
4
3
A0011176
Pin
Meaning
1
Signal -
2
Signal +
3
Screen
4
Not connected
PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; Output" 1)
"Approval" 2)
Terminal voltage
E: 2-wire; FOUNDATION Fieldbus, switch output (in
preparation)
G: 2-wire; PROFIBUS PA, switch output
• Non-Ex
• Ex nA
• Ex nA(ia)
• Ex ic
• Ex ic(ia)
• Ex d(ia) / XP
• Ex ta / DIP
• CSA GP
9 to 32 V 3)
• Ex ia / IS
• Ex ia + Ex d(ia) / IS + XP
9 to 30 V 3)
1)
Feature 020 of the product structure
2)
Feature 010 of the product structure
3)
Input voltages up to 35 V will not spoil the device.
Polarity sensitive
No
FISCO/FNICO compliant
according to IEC 60079-27
Yes
If the measuring device is used for level measurement in flammable liquids which
requires the use of overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be
ensured by an integrated or external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage
protection".
Technical data
Resistance per channel
2 * 0.5 Ω max
Threshold DC voltage
400 to 700 V
Threshold impulse voltage
< 800 V
Capacitance at 1 MHz
< 1.5 pF
Nominal arrest impulse voltage (⁸⁄₂₀ μs)
10 kA
External overvoltage protection
HAW562 or HAW569 from Endress+Hauser are suited as external overvoltage
protection.
For detailed information please refer to the following documents:
• HAW562: TI01012K
• HAW569: TI01013K
Connecting the measuring device
!WARNING
Explosion hazard!
‣ Comply with the relevant national standards.
‣ Observe the specifications in the Safety Instructions (XA).
‣ Only use the specified cable glands.
‣ Check whether the supply voltage matches the specifications on the nameplate.
‣ Before connecting the device: Switch the supply voltage off.
‣ Before switching on the supply voltage: Connect the potential bonding line to the
exterior ground terminal.
Required tools and accessories:
• For instruments with safety pin for the lid: AF 3 Allen key
• Wire stripping pliers
• When using stranded wires: Wire end sleeves.
1.
2.
3.
10 (0.4)
10 (0.4)
mm (in)
4.
5.
5.
A0012619
1.
Loosen the screw of the securing clamp of the connection compartment cover and
turn the clamp 90° counterclockwise.
2.
Unscrew the connection compartment cover.
3.
Push the cable through the cable entry. To ensure tight sealing, do not remove
the sealing ring from the cable entry.
4.
Strip the cable.
5.
Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end
ferrules.
6.
Firmly tighten the cable glands.
Connect the cable in accordance with the terminal assignment (→ 33).
8.
When using screened cable: Connect the cable screen to the ground terminal.
9.
Screw the cover onto the connection compartment.
10.
For instruments with safety pin for the lid: Adjust the safety pin so that its edge
is over the edge of the display lid. Tighten the safety pin.
Pluggable spring-force terminals
Instruments without integrated overvoltage protection have pluggable spring-
force terminals. Rigid conductors or flexible conductors with cable sleeve can
directly be inserted and are contacted automatically.
To remove cables from the terminal: Press on the groove between the terminals
using a flat-tip screwdriver ≤ 3 mm (0.12 inch) while pulling the cables out of the
terminals.
Integration into a PROFIBUS network
Endress+Hauser
41
7.3
Post-connection check
m
Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Is the terminal assignment correct (→ 33)?
m
If required: Is the protective earth connected correctly (→ 33)?
m
If supply voltage is present: Is the device ready for operation and do values appear on the
display module?
m
Are all housing covers installed and firmly tightened?
m
Is the securing clamp tightened correctly?
8
Integration into a PROFIBUS network
8.1
Overview of the device database files (GSD)
Manufacturer ID
17 (0x11)
Ident number
0x1559
Profile version
3.02
GSD file
Information and files under:
• www.endress.com
• www.profibus.org
GSD file version
8.2
Set device address
2
98
3
4
5
6
7
8
1
DIP
ON
A0015686
13
Address switches in terminal compartment
Integration into a PROFIBUS network
Micropilot FMR50
42
Endress+Hauser
8.2.1
Hardware adressing
1.
Set switch 8 to "OFF".
2.
Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts
automatically.
Switch
1
2
3
4
5
6
7
Value in position "ON"
1
2
4
8
16
32
64
Value in position "OFF"
0
0
0
0
0
0
0
2
98
3
4
5
6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
14
Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the
address.
8.2.2
Software addressing
1.
Set switch 8 to "ON".
2.
The device restarts automatically. The address remains the same as before
(factory setting: 126).
3.
Set the required address via the operating menu: Setup → Device address
2
98
3
4
5
6
7
8
1
DIP
ON
A0015903
15
Example of software addressing; switch 8 is in position "ON"; the address is defined in the
operating menu (Setup → Device address)
Display and operating module
9.1.1
Display appearance
3.1
3.2
2.1
2.2
2.4
2.5
1.1
1.2
1.3
1.4
2.3
2.6
1
2
3
4
5
ESC
OPEN
OPEN
E
ABC_
DEFG
User
HIJK
LMNO
PQRS
TUVW
XYZ
Aa1
3
4
0
1
2
9
5
6
8
7
20
A0012635
16
Appearance of the display and operation module for on-site operation
1
Measured value display (1 value max. size)
1.1
Header containing tag and error symbol (if an error is active)
1.2
Measured value symbols
1.3
Measured value
1.4
Unit
2
Measured value display (1 bargraph + 1 value)
2.1
Bargraph for measured value 1
2.2
Measured value 1 (including unit)
2.3
Measured value symbols for measured value 1
2.4
Measured value 2
2.5
Unit for measured value 2
2.6
Measured value symbols for measured value 2
3
Representation of a parameter (here: a parameter with selection list)
3.1
Header containing parameter name and error symbol (if an error is active)
3.2
Selection list; marks the current parameter value.
4
Input matrix for numbers
5
Input matrix for alphanumeric and special characters
For menu, submenu
Moves the selection bar upwards in a picklist.
For text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
A0013970
Plus key
For menu, submenu
Moves the selection bar downwards in a picklist.
For text and numeric editor
In the input mask, moves the selection bar to the right (forwards).
A0013952
Enter key
For measured value display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
For menu, submenu
• Pressing the key briefly
Opens the selected menu, submenu or parameter.
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
For text and numeric editor
• Pressing the key briefly
– Opens the selected group.
– Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
+
A0013971
Escape key combination (press keys simultaneously)
For menu, submenu
• Pressing the key briefly
– Exits the current menu level and takes you to the next higher level.
– If help text is open, closes the help text of the parameter.
• Pressing the key for 2 s returns you to the measured value display
("home position").
For text and numeric editor
Closes the text or numeric editor without applying changes.
+
A0013953
Minus/Enter key combination (press and hold down the keys
simultaneously)
Reduces the contrast (brighter setting).
+
A0013954
Plus/Enter key combination (press and hold down the keys
simultaneously)
Increases the contrast (darker setting).
+
+
A0013955
Minus/Plus/Enter key combination (press and hold down the keys
simultaneously)
For measured value display
Enables or disables the keypad lock.
Defines the operating
language of the on-site
display.
BA01124F (FMR50, PROFIBUS PA)
Setup
When appropriate values
have been assigned toall
setup parameters, the
measured should be
completely configured in a
standard application.
Setup → Mapping
Interference echo suppression
Setup → Advanced setup
Contains further submenus
and parameters:
• to adapt the device to
special measuring
conditions.
• to process the measured
value (scaling,
linearization).
• to configure the signal
output.
Diagnostics
Contains the most important
parameters needed to detect
and analyze operational
errors.
Expert 2)
Contains all parameters of
the device (including those
which are already contained
in one of the above
submenus). This menu is
organized according to the
function blocks of the device.
GP01018F/00/DE (Description of Device
Parameters, FMR5x, PROFIBUS PA)
1)
In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup →
Advanced Setup → Display"
2)
On entering the "Expert" menu, a access code is always requested. If a customer specific access code has
not been defined, "0000" has to be entered.
Unlock the device
If the device has been locked, it must be unlocked before the measurement can be
configured.
For details refer to the Operating Instructions of the device:
BA01124F (FMR50, PROFIBUS PA)
9.4
Setting the operating language
Factory setting: English or ordered local language
XXXX
XXXX
X
20.50
Display/operat.
Setup
Main menu
0104-1
Language
English
Español
Français
Language
English
Deutsch
Ã
0104-1
Ã
Español
Français
Language
English
Deutsch
0104-1
Anzeige/Betrieb
Setup
Hauptmenü
Sprache
Deutsch
0104-1
XX
XX
A0013996
17
Taking the example of the local display
Configuration of a level measurement
F
L
D
E
100%
0%
R
A0016933
1.
Setup → Tag description
Enter tag for measuring point.
2.
Setup → Device address
Enter bus address of the device (only in case of software addressing).
3.
Setup → Distance unit
Select distance unit.
4.
Setup → Tank type
Select tank type.
5.
Setup → Tube diameter (only for "Tank type" = "Bypass/pipe")
Enter the diameter of the stilling well or bypass.
6.
Setup → Medium group
Specify medium group ("Water based": DC>4 or "Others": DC>1,9)
7.
Setup → Empty calibration
Enter empty distance E (Distance from reference point R to the 0% level) 3).
3)
If, for example, the measuring range covers only an upper part of the tank (E << tank height), it is
mandatory to enter the acutal tank height into the "Setup → Advanced Setup → Level → Tank/silo height"
parameter.
Setup → Full calibration
Enter full distance F (Distance from the 0% to the 100% level).
9.
Setup → Level
Indicates the measrued level L.
10.
Setup → Distance
Indicates the measured distance from the reference point R to the level L.
11.
Setup → Signal quality
Indicates the quality of the evaluated level echo.
12.
Setup → Mapping → Confirm distance
Compare distance indicated on the display to real distance in order to start
the recording of an interference echo map.
13.
Setup → Advanced setup →Level → Level unit
Select level unit: %, m, mm, ft, in (Factory setting: %)
The response time of the device is preset by the Tank type parameter. An
enhanced setting is possible in the Advanced setup submenu.
For details of setting the parameters of user-specific applications, see separate
documentation:
BA01124F (Operating Instructions, FMR50, PROFIBUS PA)
For the Expert submenu refer to:
GP01018F/00/EN (Description of Device Parameters, FMR5x, PROFIBUS PA)