Hardware Reference Guide
This guide describes the hardware features and specifications of the Hitachi Virtual
Storage Platform G400 and the Hitachi Virtual Storage Platform G600 storage systems.
MK-94HM8022-10
October 2017
Hitachi Virtual Storage Platform
G400 and G600
83-04-4x or later
© 2017 Hitachi Vantara Corporation. All rights reserved.
No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, including
photocopying and recording, or stored in a database or retrieval system for commercial purposes without the express written permission
of Hitachi, Ltd., or Hitachi Vantara Corporation (collectively, “Hitachi”). Licensee may make copies of the Materials provided that any
such copy is: (i) created as an essential step in utilization of the Software as licensed and is used in no other manner; or (ii) used for
archival purposes. Licensee may not make any other copies of the Materials. "Materials" mean text, data, photographs, graphics, audio,
video and documents.
Hitachi reserves the right to make changes to this Material at any time without notice and assumes no responsibility for its use. The
Materials contain the most current information available at the time of publication.
Some of the features described in the Materials might not be currently available. Refer to the most recent product announcement
for information about feature and product availability, or contact Hitachi Vantara Corporation at https://support.HitachiVantara.com/
en_us/contact-us.html.
Notice: Hitachi products and services can be ordered only under the terms and conditions of the applicable Hitachi agreements. The
use of Hitachi products is governed by the terms of your agreements with Hitachi Vantara Corporation.
By using this software, you agree that you are responsible for:
1) Acquiring the relevant consents as may be required under local privacy laws or otherwise from authorized employees and other
individuals to access relevant data; and
2) Verifying that data continues to be held, retrieved, deleted, or otherwise processed in accordance with relevant laws.
Notice on Export Controls. The technical data and technology inherent in this Document may be subject to U.S. export control laws,
including the U.S. Export Administration Act and its associated regulations, and may be subject to export or import regulations in
other countries. Reader agrees to comply strictly with all such regulations and acknowledges that Reader has the responsibility to
obtain licenses to export, re-export, or import the Document and any Compliant Products.
EXPORT CONTROLS - Licensee will comply fully with all applicable export laws and regulations of the United States and other
countries, and Licensee shall not export, or allow the export or re-export of, the Software, API, or Materials in violation of any such laws
or regulations. By downloading or using the Software, API, or Materials, Licensee agrees to the foregoing and represents and
warrants that Licensee is not located in, under the control of, or a national or resident of any embargoed or restricted country.
Hitachi is a registered trademark of Hitachi, Ltd., in the United States and other countries.
AIX, AS/400e, DB2, Domino, DS6000, DS8000, Enterprise Storage Server, eServer, FICON, FlashCopy, IBM, Lotus, MVS, OS/390,
PowerPC, RS6000, S/390, System z9, System z10, Tivoli, z/OS, z9, z10, z13, z/VM, and z/VSE are registered trademarks or
trademarks of International Business Machines Corporation.
Active Directory, ActiveX, Bing, Excel, Hyper-V, Internet Explorer, the Internet Explorer logo, Microsoft, the Microsoft Corporate Logo,
MS-DOS, Outlook, PowerPoint, SharePoint, Silverlight, SmartScreen, SQL Server, Visual Basic, Visual C++, Visual Studio,
Windows, the Windows logo, Windows Azure, Windows PowerShell, Windows Server, the Windows start button, and Windows Vista
are registered trademarks or trademarks of Microsoft Corporation. Microsoft product screen shots are reprinted with permission from
Microsoft Corporation.
All other trademarks, service marks, and company names in this document or web site are properties of their respective owners.
Intended audience................................................................................................... 8
Safety and environmental notices..............................................................................8
Product version........................................................................................................9
Release notes........................................................................................................ 10
Changes in this revision..........................................................................................10
Document conventions........................................................................................... 10
Conventions for storage capacity values...................................................................11
Accessing product documentation........................................................................... 12
Getting help...........................................................................................................12
Comments.............................................................................................................12
1
Hitachi Virtual Storage Platform G400, G600 hardware overview............. 13
Block configuration.................................................................................................15
Unified configuration.............................................................................................. 15
VSP G400 model.................................................................................................... 15
VSP G600 model.................................................................................................... 17
Features................................................................................................................18
Scalability..............................................................................................................19
Examples of supported VSP G400 configurations.................................................19
Examples of supported VSP G600 configurations.................................................19
Maximum number of mounted drive trays...........................................................20
2
Virtual Storage Platform G400, G600 controller..................................... 23
CBLM controller......................................................................................................24
CBLM with front panel bezel.............................................................................. 24
CBLM front panel LEDs (without bezel)...............................................................25
CBLM rear panel...............................................................................................26
CBLM power supply unit LEDs and connectors.................................................... 28
Host, Network, and Drive Tray Ports and LEDs..........................................................28
Front end module descriptions...........................................................................28
10-Gbps iSCSI board LEDs and connectors (optical).......................................29
3
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
10-Gbps iSCSI board LEDs and connectors (copper)...................................... 29
8-Gbps, 16-Gbps, or 32-Gbps Fibre Channel (4-port) board LEDs and connectors
..................................................................................................................30
16-Gbps Fibre Channel (2-port) board LEDs and connectors...........................32
LAN blade LEDs and connectors.........................................................................33
Back end module LEDs and connectors.............................................................. 34
3
Storage system drive trays.................................................................. 37
Small form-factor (SFF) drive tray............................................................................38
SFF with front panel bezel.................................................................................38
SFF front panel without bezel............................................................................ 38
SFF rear panel..................................................................................................39
Large form-factor (LFF) drive tray............................................................................40
LFF with front panel bezel................................................................................. 40
LFF front panel without bezel.............................................................................41
LFF rear panel.................................................................................................. 42
Flash module drive (FMD) tray................................................................................ 43
FMD with front panel bezel................................................................................43
FMD front panel without bezel........................................................................... 44
FMD rear panel.................................................................................................45
Dense intermix drive tray........................................................................................46
Dense intermix drive tray with front panel bezel..................................................46
Dense intermix drive tray display LEDs............................................................... 47
Dense intermix drive tray rear panel...................................................................48
SFF and LFF AC power supply unit LEDs and connectors........................................... 49
4
Host port expansion chassis..................................................................51
Host port expansion chassis front panel bezel LEDs.................................................. 52
PCIe switchboard................................................................................................... 52
Host port expansion chassis fan.............................................................................. 53
PCIe cable connector..............................................................................................53
Host port expansion chassis power supply............................................................... 55
5
NAS module........................................................................................ 57
NAS Module Ports and LEDs....................................................................................58
6
VSP service processor server................................................................ 59
Service processor description.................................................................................. 60
SVP front panel......................................................................................................60
SVP rear panel.......................................................................................................61
Service processor hardware specifications................................................................62
7
Maintaining the storage system.............................................................63
Storing the storage system..................................................................................... 64
Powering off the storage system............................................................................. 64
Removing cables....................................................................................................64
4
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Mechanical specifications for VSP G400, G600 ......................................67
VSP G400 and VSP G600 mechanical specifications...................................................68
B
Electrical specifications for VSP G400, G600...........................................75
Electrical specifications........................................................................................... 76
C
Environmental specifications for VSP G400, G600...................................77
Environmental specifications................................................................................... 78
D iSCSI standards and specifications........................................................ 83
iSCSI standards......................................................................................................84
iSCSI specifications................................................................................................ 84
E
Replacement parts...............................................................................87
Battery unit........................................................................................................... 88
F
Data and power cables.........................................................................89
Fibre Channel cables.............................................................................................. 90
iSCSI cables...........................................................................................................93
Managing data cables.............................................................................................95
AC power cables.................................................................................................... 97
Power cable assemblies.....................................................................................97
AC connections.................................................................................................99
Power cable usage guidelines.......................................................................... 100
Three-phase power considerations for racks......................................................100
Cable management.........................................................................................101
Cable retention...............................................................................................101
G Port address mapping.........................................................................103
Port address mapping...........................................................................................104
H Third-party racks................................................................................105
Third-party rack support for VSP Gx00 models........................................................106
Hitachi Universal V2 Rack rail kits.......................................................................... 106
Hitachi Universal V2 Rack accessories.................................................................... 106
Third-party rack support for DB60 dense intermix drive trays...................................107
I
Hitachi Universal V2 Rack power distribution units................................109
Americas single-phase PDU 1P30A-8C13-3C19UL.P.................................................110
Americas single-phase PDU 1P30A-15C13-3C19UL.P............................................... 110
Americas three-phase PDU 3P30A-8C13-3C19UL.P..................................................111
Americas three-phase PDU 3P30A-15C13-3C19UL.P................................................111
Americas three-phase PDU 3P30A-24C13-6C19UL.P................................................112
APAC and EMEA single-phase PDU 1P32A-9C13-3C19CE.P.......................................113
APAC and EMEA single-phase PDU 1P32A-18C13-3C19CE.P.....................................113
5
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
APAC and EMEA three-phase PDU 3P16A-9C13-3C19CE.P........................................114
APAC and EMEA three-phase PDU 3P16A-15C13-3C19CE.P......................................114
APAC and EMEA three-phase PDU 3P32A-24C13-6C19CE.P......................................115
J
Regulatory compliance....................................................................... 117
Index................................................................................................119
6
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
This guide describes the hardware features and specifications of the VSP
Gx00 models.
□
Intended audience
□
Safety and environmental notices
□
Product version
□
Release notes
□
Changes in this revision
□
Document conventions
□
Conventions for storage capacity values
□
Accessing product documentation
□
Getting help
□
Comments
Preface
7
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
This document is intended for customers inquiring about the features and
specifications of the VSP Gx00 models.
Readers of this document should be familiar with the following:
•
Data processing and RAID storage systems and their basic functions.
•
The operating system and web browser software on the system hosting
the storage management software.
Safety and environmental notices
Equipment warranty
The term of guarantee of normal operation of the storage system and free service is one year from
date of purchase.
If a failure occurs multiple times, the storage system might shut off to avoid a serious accident.
Notice of export controls
Export of technical data contained in this document might require an export license from the United
States government, the government of Japan. or both. Contact the Hitachi Legal Department for
guidance about any export compliance questions.
Backup
Hitachi cannot guarantee against data loss due to failures. Therefore, back up your data to minimize
chances for data loss.
Data backup is also critical when hardware components are added or replaced, because performing
such hardware procedures restores parameter settings that can affect how data is managed on the
storage systems.
Disposal
This symbol on the product or on its packaging means that your electrical and electronic equipment
should be disposed at the end of life separately from your household wastes.
There are separate collection systems for recycling in the European Union. For more information,
contact the local authority or the dealer where you purchased the product.
Recycling
A nickel-metal hydride battery is used in the Cache Backup Battery.
A nickel-metal hydride battery is a resource that can be recycled. When you want to replace the
Cache Backup Battery, call the service personnel. They will dispose of it for you. This nickel-metal
hydride battery, which is designated as recycling product by a recycling promotion low, must be
recycled.
The mark posted on the Cache Backup Battery is a three-arrow mark that indicates a recyclable part.
8
Preface
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
UEFI Development Kit 2010
This product includes UEFI Development Kit 2010 written by the UEFI Open Source Community. For
more information, see the UEFI Development Kit website:
http://sourceforge.net/apps/mediawiki/tianocore/index.php?title=UDK2010
© 2004, Intel Corporation.
All rights reserved.
Redistribution and use in source and binary forms, with or without modification, are permitted
provided that the following conditions are met:
Redistributions of source code must retain the above copyright notice, this list of conditions and the
following disclaimer.
Redistributions in binary form must reproduce the above copyright notice, this list of conditions and
the following disclaimer in the documentation and/or other materials provided with the distribution.
Neither the name of the Intel Corporation nor the names of its contributors might be used to endorse
or promote products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS “AS IS” AND ANY
EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT
SHALL THE COPYRIGHT OWNER OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED
TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR
BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY
WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH
DAMAGE.
FDA radiation regulation
The array complies with FDA radiation performance standard 21 CFR subchapter J.
EMI regulation
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference in which case the user will
be required to correct the interference at his own expense. Testing was done with shielded cables.
Therefore, in order to comply with the FCC regulations, you must use shielded cables with your
installation.
The electromagnetic interference (EMI) test was done in the following configuration.
This product must not be used in residential areas.
This is a class A product. In a domestic environment this product can cause radio interference in
which case the user can be required to take adequate measures.
Product version
This document revision applies to the following product versions:
Preface
9
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
VSP G400, G600 firmware 83-04-4x or later
•
Hitachi Storage Virtualization Operating System (SVOS) 7.2 or later
•
Hitachi NAS firmware version 13.1 or later
Release notes
Read the release notes before installing and using this product. They may
contain requirements or restrictions that are not fully described in this
document or updates or corrections to this document. Release notes are
available on Hitachi Data Systems Support Connect: https://
knowledge.hds.com/Documents.
Changes in this revision
•
Added new single- and three-phase power distribution units and
specifications
•
Added third-party rack information
Document conventions
This document uses the following typographic conventions:
Convention
Description
Bold
•
Indicates text in a window, including window titles, menus, menu options,
buttons, fields, and labels. Example:
Click OK.
•
Indicates emphasized words in list items.
Italic
•
Indicates a document title or emphasized words in text.
•
Indicates a variable, which is a placeholder for actual text provided by the
user or for output by the system. Example:
pairdisplay -g group
(For exceptions to this convention for variables, see the entry for angle
brackets.)
Monospace
Indicates text that is displayed on screen or entered by the user. Example:
pairdisplay -g oradb
< > angle brackets
Indicates variables in the following scenarios:
•
Variables are not clearly separated from the surrounding text or from
other variables. Example:
Status-.csv
•
Variables in headings.
[ ] square brackets
Indicates optional values. Example: [ a | b ] indicates that you can choose a,
b, or nothing.
10
Preface
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
{ } braces
Indicates required or expected values. Example: { a | b } indicates that you
must choose either a or b.
| vertical bar
Indicates that you have a choice between two or more options or arguments.
Examples:
[ a | b ] indicates that you can choose a, b, or nothing.
{ a | b } indicates that you must choose either a or b.
This document uses the following icons to draw attention to information:
Icon
Label
Description
Note
Calls attention to important or additional information.
Tip
Provides helpful information, guidelines, or suggestions for performing
tasks more effectively.
Caution
Warns the user of adverse conditions and/or consequences (for
example, disruptive operations, data loss, or a system crash).
WARNING
Warns the user of a hazardous situation which, if not avoided, could
result in death or serious injury.
Conventions for storage capacity values
Physical storage capacity values (for example, disk drive capacity) are
calculated based on the following values:
Physical capacity unit
Value
1 kilobyte (KB)
1,000 (10 3) bytes
1 megabyte (MB)
1,000 KB or 1,0002 bytes
1 gigabyte (GB)
1,000 MB or 1,0003 bytes
1 terabyte (TB)
1,000 GB or 1,0004 bytes
1 petabyte (PB)
1,000 TB or 1,0005 bytes
1 exabyte (EB)
1,000 PB or 1,0006 bytes
Logical capacity values (for example, logical device capacity, cache memory
capacity) are calculated based on the following values:
Logical capacity unit
Value
1 block
512 bytes
Preface
11
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Logical capacity unit
Value
1 cylinder
Mainframe: 870 KB
Open-systems:
•
OPEN-V: 960 KB
•
Others: 720 KB
1 KB
1,024 (210) bytes
1 MB
1,024 KB or 1,0242 bytes
1 GB
1,024 MB or 1,0243 bytes
1 TB
1,024 GB or 1,0244 bytes
1 PB
1,024 TB or 1,0245 bytes
1 EB
1,024 PB or 1,0246 bytes
Accessing product documentation
Product user documentation is available on Hitachi Data Systems Support
Connect: https://knowledge.hds.com/Documents. Check this site for the
most current documentation, including important updates that may have
been made after the release of the product.
Getting help
Hitachi Data Systems Support Connect is the destination for technical support
of products and solutions sold by Hitachi Data Systems. To contact technical
support, log on to Hitachi Data Systems Support Connect for contact
information: https://support.hds.com/en_us/contact-us.html.
Hitachi Data Systems Community is a global online community for HDS
customers, partners, independent software vendors, employees, and
prospects. It is the destination to get answers, discover insights, and make
connections. Join the conversation today! Go to community.hds.com,
register, and complete your profile.
Comments
Please send us your comments on this document to [email protected].
Include the document title and number, including the revision level (for
example, -07), and refer to specific sections and paragraphs whenever
possible. All comments become the property of Hitachi Data Systems
Corporation.
Thank you!
12
Preface
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Hitachi Virtual Storage Platform G400,
G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 are modular, rack-mountable,
all-flash arrays that deliver high performance, high reliability, and flash-
accelerated scalability.
The storage system contain dual controllers, each controller contains its own
processor, dual in-line cache memory modules (DIMMs), cache flash memory
(CFM), battery, fans and iSCSI and Fibre Channel I/O modules. Each
controller also has an Ethernet connection for out-of-band management. If
the data path through one controller fails, all data drives remain available to
data hosts using a redundant data path through the other controller.
The storage system can be equipped with embedded network-attached
storage (NAS) modules. The NAS modules provide file access through CIFS
and NFS protocols and block access by using iSCSI protocols.
All storage system models allow defective drives to be replaced without the
interruption of data availability to hosts. A hot spare drive can be configured
to replace a failed drive automatically, securing the fault-tolerant integrity of
the logical drives. Self-contained, hardware-based RAID logical drives provide
maximum performance in compact external enclosures.
Essential hardware components are implemented with a redundant
configuration so that the storage system can remain operational if a
component fails. Adding and replacing components, along with firmware
upgrades, can be conducted while the storage system is active.
□
Block configuration
□
Unified configuration
□
VSP G400 model
□
VSP G600 model
Hitachi Virtual Storage Platform G400, G600 hardware overview
13
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Hitachi Virtual Storage Platform G400, G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
A storage system configured for block-level storage provides the ability to
access and provision raw storage volumes using protocols such as Fibre
Channel and iSCSI.
A block configuration consists of the following:
•
Two controllers
•
One or more drive trays
•
One 1U service processor server (SVP)
Unified configuration
A unified configuration includes embedded NAS modules that support file
system protocols such as CIFS and NFS and operate across a block-level
setup using iSCSI or FC connections.
•
Two controllers
•
Two NAS modules for file operations and storage
•
One or more drive trays for block-level storage
•
One 1U block service processor server (SVP)
VSP G400 model
The VSP G400 is a highly reliable storage system that offers high storage
capacity with full redundancy to better protect data and manage storage
operations.
The storage system consists of a 4U enclosure that includes two controllers,
two optional NAS modules to support file operations. Drives are supported
using drive trays connected to the controllers. The maximum number of
drives supported is 384 (480 with dense intermix drive tray).
The storage system supports 128 GB of high-speed cache memory. The
DIMMs are arranged as 64 GB per controller.
Storage system interfaces consist of:
•
10-Gbps iSCSI: 28 ports per system (or 32 ports per systems for systems
without drives or 12 ports per systems when NAS Modules are installed)
•
10-Gbps iSCSI (Copper): 28 ports per system (or 32 ports per systems for
systems without drives or 12 ports per systems when NAS Modules are
installed)
•
8-Gbps Fibre Channel: 56 ports per system (or 64 ports per systems for
systems without drives or 24 ports per systems when NAS Modules are
installed)
Hitachi Virtual Storage Platform G400, G600 hardware overview
15
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
16-Gbps Fibre Channel (2-port): 28 ports per system (or 32 ports per
systems for systems without drives or 12 ports per systems when NAS
Modules are installed)
•
16-Gbps Fibre Channel (4-port): 56 ports per system (or 64 ports per
systems for systems without drives or 24 ports per systems when NAS
Modules are installed)
•
32-Gbps Fibre Channel (4-port): 56 ports per system (or 64 ports per
systems for systems without drives or 24 ports per systems when NAS
Modules are installed)
Controller
Controller chassis
Controller model
Height
CBLM
DW800-CBL
DW-F800-CTLM
4U (174.3 mm)
Controller
Model number
Description
NAS
DW-F800-NAS
Optional component for file
storage configuration. NAS
modules only provide file
support.
Drive tray
Drive tray model
name
Supported drive
type
Number of drives
supported
Height
SFF drive tray
•
DW-F800-DBS
(power supply,
contains
BNST)
•
DW-F800-
DBSC
2.5-inch SFF
24
2U (86.2 mm)
LFF drive tray
•
DW-F800-DBL
(power supply,
contains
BNST)
•
DW-F800-
DBLC
3.5-inch LFF
12
2U (86.2 mm)
FMD tray
•
DW-F800-DBF
5.25-inch FMD
12
2U (86.2 mm)
Dense intermix
drive tray
•
DW-F800-
DB60 (power
supply,
contains
BNST)
•
DW-F800-
DB60C
3.5-inch LFF
60
4U (174.3 mm)
Related references
•
Examples of supported VSP G400 configurations on page 19
16
Hitachi Virtual Storage Platform G400, G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
VSP G600 model
The VSP G600 is a highly reliable storage system that offers high storage
capacity with full redundancy to better protect data and manage storage
operations.
The storage system consists of a 4U enclosure that includes two controllers,
two optional NAS modules to support file operations. Drives are supported
using drive trays connected to the controllers. The maximum number of
drives supported is 576 (720 with dense intermix drive tray).
The storage system supports 256 GB of high-speed cache memory. The
DIMMs are arranged as 128 GB per controller.
Storage system interfaces consist of:
•
10-Gbps iSCSI: 28 ports per system (or 32 ports per systems for systems
without drives or 12 ports per systems when NAS Modules are installed)
•
10-Gbps iSCSI (Copper): 28 ports per system (or 32 ports per systems for
systems without drives or 12 ports per systems when NAS Modules are
installed)
•
8-Gbps Fibre Channel: 56 ports per system (or 64 ports per systems for
systems without drives or 24 ports per systems when NAS Modules are
installed)
•
16-Gbps Fibre Channel (2-port): 28 ports per system (or 32 ports per
systems for systems without drives or 12 ports per systems when NAS
Modules are installed)
•
16-Gbps Fibre Channel (4-port): 56 ports per system (or 64 ports per
systems for systems without drives or 24 ports per systems when NAS
Modules are installed)
•
32-Gbps Fibre Channel (4-port): 56 ports per system (or 64 ports per
systems for systems without drives or 24 ports per systems when NAS
Modules are installed)
Controller
Controller chassis
Controller model
Height
CBLM
DW800-CBL
DW-F800-CTLM
4U (174.3 mm)
Controller
Model number
Description
NAS
DW-F800-NAS
Optional component for file
storage configuration. NAS
modules only provide file
support.
Hitachi Virtual Storage Platform G400, G600 hardware overview
17
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Drive tray model
name
Supported drive
type
Number of drives
supported
Height
SFF drive tray
•
DW-F800-DBS
(power supply,
contains
BNST)
•
DW-F800-
DBSC
2.5-inch SFF
24
2U (86.2 mm)
LFF drive tray
•
DW-F800-DBL
(power supply,
contains
BNST)
•
DW-F800-
DBLC
3.5-inch LFF
12
2U (86.2 mm)
FMD tray
•
DW-F800-DBF
5.25-inch FMD
12
2U (86.2 mm)
Dense intermix
drive tray
•
DW-F800-
DB60 (power
supply,
contains
BNST)
•
DW-F800-
DB60C
3.5-inch LFF
60
4U (174.3 mm)
Related references
•
Examples of supported VSP G600 configurations on page 19
Features
The features described in the table are included with VSP G400 and VSP
G600.
Feature
Value
Maximum cache memory supported
VSP G400:128 GB
VSP G600: 256 GB
Maximum number of spare drives
32
Maximum number of RAID groups
VSP G400: 240
VSP G600: 240
Maximum volume size
3 TB (4 TB when using the LDEVs of other
Storage Systems)
Maximum number of volumes per RAID group
2,048
Maximum number of DP pool volumes
4,096
Maximum number of DP pools
64
Maximum number of iSCSI hosts connected
through a network switch
255
18
Hitachi Virtual Storage Platform G400, G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maximum number of Fibre Channel devices
connected through a Fibre Channel switch
255
Scalability
All storage systems offer pay-as-you-grow scalability by allowing you to hot-
add drives as you need them.
Examples of supported VSP G400 configurations
The following table lists the maximum number of drive trays and drives
supported in a system configuration. A diskless configuration does not include
any drive trays.
Drive tray
Maximum number of
drive trays supported
Maximum number of drives supported
SFF drive tray
16
384 HDDs or SSDs
LFF drive tray
16
192 HDDs or SSDs
FMD tray
16
192 Hitachi Accelerated Flash (HAF) flash
module drives
Dense intermix drive tray
8
-
Note: If a drive is inserted into a slot of a dense intermix drive tray when the
installed number of drives exceeds 240 slots per path, the drive is blocked.
Related references
•
VSP G400 model on page 15
Examples of supported VSP G600 configurations
The following table lists the maximum number of drive trays and drives
supported in a system configuration. A diskless configuration does not include
any drive trays.
Drive tray
Maximum number of
drive trays supported
Maximum number of drives supported
SFF drive tray
24
576 HDDs or SSDs
LFF drive tray
24
288 HDDs or SSDs
FMD drive tray
24
288 HAF flash module drives
Dense intermix drive tray
12
-
Hitachi Virtual Storage Platform G400, G600 hardware overview
19
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Note: If a drive is inserted into a slot of a dense intermix drive tray when the
installed number of drives exceeds 240 slots per path, the drive is blocked.
Related references
•
VSP G600 model on page 17
Maximum number of mounted drive trays
The following table lists the maximum number of mountable drive trays and
mountable drives for each drive type.
Note: If a drive is inserted into a slot of a dense intermix drive tray when the
installed number of drives exceeds 240 slots per path, the drive is blocked.
VSP G400 controller
Drive trays
Maximum number of
trays
Maximum number of
drives
CBLM
SFF
16
384 HDDs or SSDs
LFF
16
192 HDDs or SSDs
FMD
16
192 FMDs (HAF)
4
48 FMDs
FMD
1
8 FMDs + 1 spare
(DC2)
Dense intermix drive
tray
8
480 HDDs or SSDs1
Note:
1The following SSD capacities (200 GB and 400 GB) are supported in a dense intermix drive tray.
VSP G600 controller
Drive trays
Maximum number of
trays
Maximum number of
drives
CBLM
SFF
24
576 HDDs or SSDs
LFF
24
288 HDDs or SSDs
FMD
24
288 FMDs (HAF)
4
48 FMDs
FMD
2
16 FMDs + 1 spare
(DC2)
Dense intermix drive
tray
12
720 HDDs or SSDs1
Note:
1The following SSD capacities (200 GB and 400 GB) are supported in a dense intermix drive tray.
20
Hitachi Virtual Storage Platform G400, G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Number of mounted drive trays
(Maximum 12 per path)
Maximum number of mounted drives
SFF, LFF drives
Dense intermix
drive tray
SFF drive +
dense intermix
drive tray
LFF drive +
dense intermix
drive tray
CBLM
16
0
384
192
13
1
372
216
12
2
408
264
9
3
396
288
8
4
432
336
5
5
420
360
4
6
456
408
1
7
444
432
0
8
480
480
VSP G600
controller
Number of mounted drive trays
(Maximum 12 per path)
Maximum number of mounted drives
SFF, LFF drives
Dense intermix
drive tray
SFF drive +
dense intermix
drive tray
LFF drive +
dense intermix
drive tray
CBLM
24
0
576
288
21
1
564
312
20
2
600
360
17
3
588
384
16
4
624
432
13
5
612
456
12
6
648
504
9
7
636
528
8
8
672
576
5
9
660
600
4
10
696
648
1
11
684
672
0
12
720
720
Hitachi Virtual Storage Platform G400, G600 hardware overview
21
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Hitachi Virtual Storage Platform G400, G600 hardware overview
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Virtual Storage Platform G400, G600
controller
The Virtual Storage Platform G400, G600 models are equipped with dual
controllers for communicating with a data host.
Each controller includes the following internal components such as a
processor, dual in-line cache memory modules (DIMMs), cache flash memory
(CFM), battery, and fans. The controller has an Ethernet connection for out-
of-band management using Hitachi Device Manager - Storage Navigator. If
the data path through one controller fails, all drives remain available to data
hosts using a redundant data path through the other controller. The controller
is equipped with LED indicators for monitoring its operating conditions and
notifying possible component replacement.
□
CBLM controller
□
Host, Network, and Drive Tray Ports and LEDs
Virtual Storage Platform G400, G600 controller
23
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
The CBLM controller includes specific functional LEDs located on the front and
rear of controller and power supplies to provide its operating status.
CBLM with front panel bezel
The following table describes the definitions of the CBLM controller front
panel bezel LEDs.
Number
Item
Description
1
POWER LED
Green: Storage system is
powered on.
Amber: Storage system is
receiving power.
2
READY LED
Green: Normal operation.
3
WARNING LED
Off: Normal operation.
Amber: Component requires
maintenance.
Blink: Failure requires
maintenance.
Note: When System Option
Mode 1097 is set to ON, the
WARNING LED does not blink,
even if the following failure
service information messages
(SIM) are issued: 452xxx,
462xxx, 3077xx, 4100xx, and
410100.
LED might turn off during user
maintenance.
4
ALARM LED
Off: Normal operation.
24
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Red: Processor failure (system
might be down). Go to the
Customer Contact Us page at
https://support.hds.com/
en_us/contact-us.html.
5
POWER ON/OFF (main switch)
Powers the storage system.
6
Lock
Locks and unlocks the front
panel bezel by using the
supplied key.
Note: Removing a controller can cause the POWER, READY, WARNING, and
ALARM LEDs on the front panel to turn off. These LEDs return to the on status
after the storage system recovers from the controller replacement.
CBLM front panel LEDs (without bezel)
The following table describes the definitions of the CBLM controller front
panel LEDs.
Number
Item
Description
1
POWER ON/OFF (main switch)
Powers the storage system.
2
POWER, READY, WARNING, and
ALARM LEDs
Note: When System Option
Mode 1097 is set to ON, the
WARNING LED does not blink,
even if the following failure
service information messages
(SIM) are issued: 452xxx,
462xxx, 3077xx, 4100xx, and
410100.
3
Controllers
Controller 1 (bottom) and
Controller 2 (top).
Virtual Storage Platform G400, G600 controller
25
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Power restoration in
progress following power
outage.
Fast blink green: Restoring.
Slow blink green: Restoring, or
sequential shutdown in
progress.
6
Cache flash memory
N/A
7
ALM LED (for cache flash
memory)
Red: Cache flash memory can
be removed.
8
CTL ALM LED
Red: Controller can be
removed.
Blink red: Failure with the
power supply unit of the
controller.
Amber: LAN reset switch was
pressed.
9
LAN-RST switch
Use only when instructed by
customer support.
10
STATUS LED (for BKMF)
Green: Charging of the battery
in the backup module is
complete.
Red: Backup module can be
removed.
Blink red one time: Main
battery failure.
Blink red two times: Backup
battery failure.
Blink red three times: Both
batteries failed or preventive
maintenance replacement of
batteries can run.
Off: Battery is not mounted,
battery-mounting failure
occurred, or firmware is being
upgraded. Off is normal status
for configurations without
batteries (for example,
BKMF-10 and BKMF-20).
CBLM rear panel
The following table describes the definitions of the CBLM controller rear panel
LEDs.
26
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Power supply unit
2
Front end module
3
Back end module
4
LAN blade
Rear view (includes NAS modules)
Virtual Storage Platform G400, G600 controller
27
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Front end module
3
Back end module
4
LAN blade
5
Power supply unit
CBLM power supply unit LEDs and connectors
The following table lists the definitions of the CBLM power supply unit LEDs
and connectors.
Number
Item
Description
1
ALM/RDY LED
Red: Power supply unit can be
replaced.
2
Receptacle
Connects to the power cable
provided with the storage
system.
3
RDY LED
Green: Normal operation.
Host, Network, and Drive Tray Ports and LEDs
The controllers are equipped with specific interfaces for connecting,
powering, configuring, and managing the storage system. The component
LEDs display the operating status of the storage system.
Front end module descriptions
The front end module LEDs display the operating status of the module.
28
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
10-Gbps iSCSI board LEDs and connectors (optical)
Number
Item
Description
1
STATUS LED
Green: Front end module is in
the power-on state.
Red: Front end module can be
removed safely.
2
PORT LED
Red: Small form factor
pluggable can be removed.
Blue: Normal link status.
Blink blue: Front end module is
in communication status.
3
iSCSI connectors
Connect to Ethernet LAN
cables.
10-Gbps iSCSI board LEDs and connectors (copper)
Virtual Storage Platform G400, G600 controller
29
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Front end module is in
the power-on state.
Red: Front end module can be
removed safely.
2
PORT (Link/Speed) LED
Yellow: 1-Gbps link.
Green: 10-Gbps link.
Off: No link connection.
3
PORT LED
Green: Link connection is
established.
Blinking: Communication is in
progress.
Off: No link connection or not
ready to communicate.
4
iSCSI connectors
Connect to Ethernet LAN
cables.
8-Gbps, 16-Gbps, or 32-Gbps Fibre Channel (4-port) board LEDs and connectors
30
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Table 1 8-Gbps Fibre Channel
Number
Item
Description
1
Fibre Channel connectors
Connect to Fibre Channel
cables.
2
STATUS LED
Green: Front end module is in
power-on state.
Red: Front end module can be
removed safely.
3
PORT LED
Red: Small form factor
pluggable can be removed.
Blue: Normal link status at 8-
Gbps.
Green: Normal link status at 2-
Gbps or 4-Gbps.
Table 2 32-Gbps, 16-Gbps Fibre Channel
Number
Item
Description
1
Fibre Channel connectors
Connect to Fibre Channel
cables.
2
STATUS LED
Green: Front end module is in
power-on state.
Red: Front end module can be
removed safely.
3
PORT LED
Red: Small form factor
pluggable can be removed.
Blue: Normal link status at 16-
Gbps (16-Gbps).
Blue: Normal link status at 32-
Gbps (32-Gbps).
Virtual Storage Platform G400, G600 controller
31
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Normal link status at 4-
Gbps or 8-Gbps (16-Gbps).
Green: Normal link status at 8-
Gbps or 16-Gbps (32-Gbps).
Port assignments
CHB number
8-Gbps, 16-Gbps, or 32-Gbps Fibre Channel Ports (left to right)
Port 1
Port 2
Port 3
Port 4
CHB-1A
1A
3A
5A
7A
CHB-1B
1B
3B
5B
7B
CHB-1C
1C
3C
5C
7C
CHB-1D
1D
3D
5D
7D
CHB-1E
1E
3E
5E
7E
CHB-1F
1F
3F
5F
7F
CHB-1G
1G
3G
5G
7G
CHB-1H
1H
3H
5H
7H
CHB-2A
2A
4A
6A
8A
CHB-2B
2B
4B
6B
8B
CHB-2C
2C
4C
6C
8C
CHB-2D
2D
4D
6D
8D
CHB-2E
2E
4E
6E
8E
CHB-2F
2F
4F
6F
8F
CHB-2G
2G
4G
6G
8G
CHB-2H
2H
4H
6H
8H
16-Gbps Fibre Channel (2-port) board LEDs and connectors
32
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Front end module is in
the power-on state.
Red: Front end module can be
removed safely.
2
PORT LED
Red: Small form factor
pluggable can be removed.
Blue: Normal link status at 16-
Gbps.
Green: Normal link status at 4-
Gbps or 8-Gbps.
3
Fibre Channel connectors
Connect to Fibre Channel
cables.
Port assignments
CHB number
16-Gbps Fibre Channel Ports (left to right)
Port 1
Port 2
CHB-1A
1A
3A
CHB-1B
1B
3B
CHB-1C
1C
3C
CHB-1D
1D
3D
CHB-1E
1E
3E
CHB-1F
1F
3F
CHB-1G
1G
3G
CHB-1H
1H
3H
CHB-2A
2A
4A
CHB-2B
2B
4B
CHB-2C
2C
4C
CHB-2D
2D
4D
CHB-2E
2E
4E
CHB-2F
2F
4F
CHB-2G
2G
4G
CHB-2H
2H
4H
LAN blade LEDs and connectors
Virtual Storage Platform G400, G600 controller
33
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Data is being
transferred.
2
LINK LED
Green: Link status is normal.
3
LAN 2
LAN port used by the user.
4
LAN 1
Maintenance LAN port used by
service personnel.
5
LAN ALARM LED
Red: LAN blade can be
removed.
6
Uninterruptible power supply
(UPS) port
N/A
Back end module LEDs and connectors
The back end module LEDs display the operating status of the module.
34
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Back end module is in
the power-on state.
Red: Back end module can be
removed safely.
2
Port LED
Blue: Link status is normal.
3
PATH 0 connector
Connect to a drive tray.
4
PATH 1 connector
Connects to a drive tray.
Virtual Storage Platform G400, G600 controller
35
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Virtual Storage Platform G400, G600 controller
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Storage system drive trays
The drive trays contain drives, power supplies, fans, and status LEDs. Each
drive tray provides interfaces for connecting to controllers and other drive
trays. The all-flash storage arrays have various fixed storage capacity
configurations with FMD DC2 flash storage devices. To deliver consistent low
latency host response times and highest IOP performance across all host
connection ports, conventional HDDs are not included or configurable with
all-flash arrays.
□
Small form-factor (SFF) drive tray
□
Large form-factor (LFF) drive tray
□
Flash module drive (FMD) tray
□
Dense intermix drive tray
□
SFF and LFF AC power supply unit LEDs and connectors
Storage system drive trays
37
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Small form-factor (SFF) drive tray
SFF with front panel bezel
Number
Item
Description
1
POWER LED
Green: Drive tray is powered
on.
2
READY LED
Green: Drive tray is
operational.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
Lock
Locks and unlocks the front
panel bezel by using the
supplied key.
SFF front panel without bezel
38
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Normal operation.
Blink green: Drive is being
accessed.
2
ALM LED
Red: Drive stopped due to a
failure and can be replaced.
3
POWER, READY, and LOCATE LEDs
Green: Drive tray is powered
on.
Green: Drive tray is
operational.
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
Small form factor drives
The twenty-four 2.5-inch small
form factor drives are
positioned vertically. The slots
are organized from 0 to 23.
SFF rear panel
Storage system drive trays
39
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: ENC is in the power-on
state.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
ALARM LED
Red: ENC can be replaced.
5
PATH (IN) LED
Blue: IN side port is linked up.
6
PATH (IN) connector
Connects to a controller or
drive tray.
7
PATH (OUT)LED
Blue: OUT side port is linked
up.
8
PATH (OUT) connector
Connects to a drive tray.
9
Console
This port is reserved.
10
Power supply unit
N/A
11
Receptacle
Connects to the power cable
provided with the storage
system.
12
AC IN LED
Green: Normal operation.
13
ALM LED
Red: Power supply unit can be
replaced.
14
RDY LED
Green: Normal operation.
Large form-factor (LFF) drive tray
LFF with front panel bezel
40
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Drive tray is powered
on.
2
READY LED
Green: Drive tray is
operational.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
Lock
Locks and unlocks the front
panel bezel by using the
supplied key.
LFF front panel without bezel
Number
Item
Description
1
POWER, READY, and LOCATE LEDs
Green: Drive tray is powered
on.
Green: Drive tray is
operational.
Amber:
Storage system drive trays
41
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
2
ACT LED
Green: Normal operation.
Blink green: Drive is being
accessed.
3
ALM LED
Red: Drive stopped due to a
failure and can be replaced.
4
Large form factor drives
The twelve 3.5-inch large form
factor drives are positioned
horizontally. The slots are
organized in the following
order:
8 9 10 11
4 5 6 7
0 1 2 3
LFF rear panel
Number
Item
Description
1
ENC
N/A
2
POWER LED
Green: ENC is in the power-on
state.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
ALARM LED
Red: ENC can be replaced.
5
PATH (IN) LED
Blue: IN side port is linked up.
42
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
PATH (IN) connector
Connects to a controller or
drive tray.
7
PATH (OUT)LED
Blue: OUT side port is linked
up.
8
PATH (OUT) connector
Connects to a drive tray.
9
Console
This port is reserved.
10
Power supply unit
N/A
11
Receptacle
Connects to the power cable
provided with the storage
system.
12
AC IN LED
Green: Normal operation.
13
ALM LED
Red: Power supply unit can be
replaced.
14
RDY LED
Green: Normal operation.
Flash module drive (FMD) tray
FMD with front panel bezel
Number
Item
Description
1
POWER LED
Green: Drive tray is powered
on.
2
READY LED
Green: Drive tray is
operational.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
Storage system drive trays
43
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Locks and unlocks the front
panel bezel by using the
supplied key.
FMD front panel without bezel
Number
Item
Description
1, 2
ACT LED
Green: Normal operation.
Blink: Drive is being accessed.
Slow blink:
•
DKC-F710I-1R6FM/3R2FM:
Insufficient battery capacity
in the flash module drive.
•
DKC-F810I-1R6FN/3R2FN/
6R4FN: Flash module drive
built-in capacitor is charged.
If the storage system is
turned on, the LED stops
blinking when the capacitor
is finished charging
(approximately two
minutes).
Note: ACT indicator is only
printed on some types of FMDs.
44
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Red: Drive stopped due to a
failure and can be replaced.
Note: ACT indicator is only
printed on some types of FMDs.
3
POWER, READY, and LOCATE LEDs
Green: Drive tray is powered
on.
Green: Drive tray is
operational.
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
Flash module drives
Twelve flash module drives.
Slots are organized the
following way:
9, 10, 11
6, 7, 8
3, 4, 5
0, 1, 2
FMD rear panel
Number
Item
Description
1
ENC
N/A
2
POWER LED
Green: ENC is in the power-on
state.
3
LOCATE LED
Amber:
Storage system drive trays
45
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
ALARM LED
Red: ENC can be replaced.
5
PATH (IN) LED
Blue: IN side port is linked up.
6
PATH (IN) connector
Connects to a controller or
drive tray.
7
PATH (OUT)LED
Blue: OUT side port is linked
up.
8
PATH (OUT) connector
Connect to a drive tray.
9
Console
This port is reserved.
10
Receptacle
Connects to the power cable
provided with the storage
system.
11
Three LEDS, top to bottom:
RDY LED
AC IN LED
ALM REPLACE LED
Green: Power supply unit is
operating normally.
Green: Power supply unit is
operating normally.
Red: Power supply unit can be
replaced.
Dense intermix drive tray
Dense intermix drive tray with front panel bezel
46
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: Drive tray is powered
on.
2
READY LED
Green: Drive tray is
operational.
3
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
4
Lock
Locks and unlocks the front
panel bezel by using the
supplied key.
Dense intermix drive tray display LEDs
Number
Item
Description
1
ACT
Green: Normal operation.
Blink green: Drive is being
accessed.
2
ALM LED
Red: Drive stopped due to a
failure and can be replaced.
Storage system drive trays
47
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Note: At the rear of the drive tray, the drives are organized from left to right.
On the left side of the preceding figure, the rear of the drive tray is at the
top.
•
Rear of drive tray: 48-59
•
36-47
•
24-35
•
12-23
•
Front of drive tray: 00-11
Dense intermix drive tray rear panel
Number
Item
Description
1
Power supply unit
N/A
2
RDY LED
Green: Normal operation.
3
AC IN LED
Green: Normal operation.
4
ALM LED
Red: Power supply unit can be
replaced.
5
Receptacle
Connects to the power cable
provided with the storage
system.
6
ENC
N/A
7
PATH (OUT)LED
Blue: OUT side port is linked
up.
8
PATH (OUT) connector
Connect to a drive tray.
9
PATH (IN) LED
Blue: IN side port is linked up.
10
PATH (IN) connector
Connects to a controller or
drive tray.
48
Storage system drive trays
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
This port is reserved.
12
ALARM LED
Red: ENC can be replaced.
13
LOCATE LED
Amber:
•
Indicates the location of the
chassis.
•
Can be turned on or turned
off by the maintenance
utility.
14
POWER LED
Green: ENC is in the power-on
state.
SFF and LFF AC power supply unit LEDs and connectors
Both SFF and LFF drive trays are equipped with AC power supply units. The
AC power supply units include LEDs to display its operating status.
Number
Item
Description
1
RDY LED
Green: Normal operation.
2
AC IN LED
Green: AC input is operating
normally.
3
ALM LED
Red: Power supply unit can be
replaced.
Storage system drive trays
49
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Host port expansion chassis
The host port expansion chassis contains various interconnect adapters that
connect a host system to storage and other network devices. The
interconnect adapters include PCIe boards, iSCSI and FC cards. For more
information, contact customer support.
□
Host port expansion chassis front panel bezel LEDs
□
PCIe switchboard
□
Host port expansion chassis fan
□
PCIe cable connector
□
Host port expansion chassis power supply
Host port expansion chassis
51
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Host port expansion chassis front panel bezel LEDs
Number
Item
Description
1
POWER LED
Green: Host port expansion is
turned on.
Amber: PCIe module is turned
on.
Off: PCIe module is turned off.
2
Safety lock
Lock or unlock the front bezel.
PCIe switchboard
52
Host port expansion chassis
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: PCIe switchboard is
powered on.
Red: PCIe switchboard can be
replaced safely.
Off: PCIe switchboard is
powered off.
Host port expansion chassis fan
Number
Item
Description
1
ALM LED
Red: Fan failure has occurred.
Off: Normal operation.
PCIe cable connector
Host port expansion chassis
53
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Green: PCIe cable connector is
powered on.
Red: PCIe cable connector can
be replaced safely.
Off: PCIe cable connector is
powered off.
2
Link Basic LED
Green: Basic PCIe Gen-3.0 (8-
Gbps) is linked up normally.
Off: Basic PCIe is not linked up
(PCIe cable might not be
connected). If a cable is
connected, it can be removed
safely.
3
InAct Basic LED
Amber: Basic PCIe status
changed from link up to link
down and cables. Cables can be
removed safely.
Off: Basic PCIe is normal or not
set.
4
Link Option LED
Green: Option PCIe Gen-3.0 (8-
Gbps) is linked up normally.
Off: Option PCIe is not linked
up (PCIe cable might not be
54
Host port expansion chassis
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
connected). If a cable is
connected, it can be removed
safely.
5
InAct Option LED
Amber: Option PCIe status
changed from link up to link
down and cables. Cables can be
removed safely.
Off: Option PCIe is normal or
not set.
Host port expansion chassis power supply
Number
Item
Description
1
ALM/RDY LED
Red: Host port expansion
chassis power supply can be
replaced safely.
Green: Normal operation.
2
AC IN LED
Blue: AC input is normal.
Host port expansion chassis
55
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Host port expansion chassis
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
The NAS module provides communication ports to support file system
protocols in a block- or file-system configuration.
Note: The NAS module is not supported on the VSP G200 storage system.
□
NAS Module Ports and LEDs
NAS module
57
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
NAS Module Ports and LEDs
Legend
Name
Color
Description
1
User LAN port
-
This is used with the
file level access.
1.
Target group 1
2.
Target group 2
3.
Target group 3
4.
Target group 4
5.
Target group 5
6.
Target group 6
2
Cluster port
-
Reserved for future use
3
Status LED
Green
NAS modules are
functioning normally.
Red
NAS modules can be
removed.
4
Link LED
Blue
Displays link status.
5
Fail LED
Red
A failure has occurred.
58
NAS module
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
VSP service processor server
The VSP Gx00 models include a separate, dedicated 1U service processor
(SVP) to host an element manager (Storage Navigator). The SVP (model
number 3919435.P) operates independently from the CPU of the storage
system and operating system, and provides out‑of‑band configuration and
management of the storage system. The SVP also monitors and collects
performance data for key components of the storage system to enable
diagnostic testing and analysis for customer support.
The SVP is available as:
•
A physical 1U management server provided by Hitachi Data Systems that
runs Windows Embedded Standard 7.
•
A software application that runs Windows 7 Professional x64 Service Pack
1 (64-bit) on a customer-supplied server hardware, a VMware ESXi host,
or Linux KVM host.
•
A software application that runs Microsoft Hyper-V Windows Server 2012
R2 on a customer-supplied server hardware running one of the following
64-bit operating systems:
○ Windows 10 Professional
○ Windows 10 Enterprise
○ Windows Server 2012
○ Windows Server 2012 R2
□
Service processor description
□
SVP front panel
□
SVP rear panel
□
Service processor hardware specifications
VSP service processor server
59
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Service processor description
The SVP provides four RJ-45 ports:
•
Two ports connect to the storage system controllers (one port for each
controller).
•
One port connects to the IP network of the user.
•
One port connects to a user-supplied management console PC.
Note: This product is also designed for IT power distribution systems with
phase-to-phase voltage.
Three of the four RJ-45 ports (which connect to the controllers and the IP
network) are configured as a bridge. The SVP can be addressed using the
default IP address 192.168.0.15.
In the unlikely event you cannot connect to the SVP using the default IP
address, use the following emergency login: http:///dev/storage//
emergency.do. For example:
Storage system model number
Storage system serial number
URL
8320004
456789
http://192.168.0.15/dev/
storage/8320004456789/
emergency.do
8340004
456789
http://192.168.0.15/dev/
storage/8340004456789/
emergency.do
8360004
456789
http://192.168.0.15/dev/
storage/8360004456789/
emergency.do
Users are responsible for adopting the appropriate security procedures with
the SVP, including:
•
Applying Windows security patches.
•
Turning on automatic Windows updates or using the manual Windows
update method.
•
Installing antivirus software that has been tested and approved by Hitachi.
SVP front panel
The front panel of the physical SVP is equipped with LEDs, a reset button,
and a power button.
60
VSP service processor server
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
LEDs. From left to right, the LEDs are:
•
BMC Heartbeat
•
LAN card 2
•
LAN card 1
•
Hard drive
•
System standby power
2
Reset button.
3
Power button. Applies power to or removes
power from the SVP.
SVP rear panel
The only ports used on the rear panel of the physical SVP are the power
socket and the four LAN ports.
Number
Description
1
Power socket. Attach the power cable supplied
with the SVP.
2
Four LAN ports arranged as follows:
LAN3 LAN4
LAN1 LAN2
VSP service processor server
61
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
These ports connect to your IP network, the
management console PC, and the user LAN port
on each storage system controller.
Note: After the Initial Startup Wizard is run, the SVP can be used in non-
bridge mode. In this mode, the cables can be removed from SVP ports LAN3
and LAN4 and attached to switches. For more information, contact customer
support.
Service processor hardware specifications
The following table lists the hardware specifications for the service processor
(SVP) provided by Hitachi Data Systems.
Caution: The SVP is not supported in high-temperature environments. Do
not operate it in locations with temperatures of 40°C or higher.
Item
Specification
Dimensions
Height: 1.7 inches (43 mm)
Width: 17.2 inches (437 mm)
Depth: 14.5 inches (369 mm)
Weight: 14 lbs (6.4 kg)
Processor
Celeron G1820 2.7-GHz 2M, 2C, 2T
•
Cores: 2
•
Instruction set: 64-bit
•
SmartCache: 2 MB
•
Maximum memory size: 32 GB
•
Memory types: DDR3-1333, DDR3L-1333 @
1.5V
Memory
8-GB RAM DDR3
Hard drive
2 TB
Network interface card
x4 ports (on-board NIC) +
x1 IPMI (BMC) port
Fans
2 x 4-cm 4-pin PWM fans
Operating system
Windows Embedded Standard 7
62
VSP service processor server
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maintaining the storage system
Ongoing proper maintenance of the storage system maintains the reliability
of the storage system and its constant availability to all hosts connected to it.
For more complex maintenance activities, contact customer support.
□
Storing the storage system
□
Powering off the storage system
□
Removing cables
Maintaining the storage system
63
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Storing the storage system
If the storage system does not receive power for more than six months, the
battery can become discharged and possibly damaged. To avoid this
situation, charge the battery for more than three hours at least once every
six months.
Note: Do not store the equipment in an environment with temperatures of
104ºF (40ºC) or higher because battery life will be shortened.
Powering off the storage system
Procedure
1.
Press the main switch for three seconds until the POWER LED blinks.
2.
Verify the POWER LED on the front of the storage system changes from
green to amber.
Wait 25 minutes to 4 hours for the POWER LED to turn amber, depending
on the system configuration (check after 33 minutes).
3.
To stop the power supply, remove the power cables from the power
supply units on the controller chassis and drive box.
If the storage system is connected to a PDU, you can stop the power
supply by turning off the PDU breaker.
Note: If the storage system does not receive power for more than
six months, the battery can become discharged and possibly
damaged. To avoid this situation, charge the battery for more than
three hours at least once every six months.
Removing cables
Observe the following instructions when removing cables form the storage
system.
To remove a SAS cable, pull the tab of the SAS cable (1) to release the latch
and remove the SAS cable (2).
64
Maintaining the storage system
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
To remove an optical cable, push the top of the connector of the optical cable
(1) to release the latch and remove the SAS cable (2).
To remove a LAN cable, push the top of the LAN cable connector (1) to
release the latch and remove the LAN cable (2).
Maintaining the storage system
65
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maintaining the storage system
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Mechanical specifications for VSP G400,
G600
The storage system mechanical specifications are described for VSP G400,
G600 .
□
VSP G400 and VSP G600 mechanical specifications
Mechanical specifications for VSP G400, G600
67
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
VSP G400 and VSP G600 mechanical specifications
Controller
Quantity
Component
Description
1
CBLM
A 4U controller chassis
consisting of controllers,
channel boards, disk boards,
NAS module (optional), AC or
DC power supplies, and
batteries with cooling fans.
Drive trays
Quantity
Component
Description
1
SFF drive tray
A drive tray that supports 2.5-
inch disk drives and 2.5-inch
flash drives. The drive tray
consists of an ENC, cooling
fans, and AC-DC power supplies
or DC-DC power supplies.
1
LFF drive tray
A drive tray that supports 3.5-
inch disk drives and 3.5-inch
flash drives. The drive tray
consists of an ENC, cooling
fans, and AC-DC power supplies
or DC-DC power supplies.
1
FMD tray
A drive tray that supports flash
module drives and consists of
an ENC and AC-DC power
supplies equipped with built-in
cooling fans.
1
Dense intermix drive tray
A drive chassis that supports a
variety of drive types such as
2.5-inch drives, 3.5-inch drives,
and flash drives. The chassis
consists of an ENC and AC-DC
power supplies equipped with
built-in cooling fans.
NAS module
Component
Description
NAS module
Optional component for block and file storage
configuration
68
Mechanical specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
2.5-inch drive (SFF)
3.21 x 8.10 x 0.74 inches (81.6 x 205.7 x 18.7 mm)
3.5-inch drive (LFF and dense intermix
drive tray)
4 x 5.78 x 1.02 inches (101.6 x 147.0 x 26.1 mm)
Flash Module Drive (flash module drive
tray)
5.74 x 14.44 x 0.78 inches (146 x 366.8 x 19.8 mm)
Data capacity (GB)
Component
Specification
2.5-inch drive (SFF)
196.92, 288.20, 393.85, 472.61, 576.39,
945.23, 1152.79, 1729.29, 1890.46, 3780.92
GB
3.5-inch drive (LFF and dense intermix drive
tray)
393.85, 1152.79, 1729.29, 3916.14, 5874.22,
9790.36 GB
Flash Module Drive (flash module drive tray)
1759.21, 3518.43 , 7036.87, 14073.74 GB
Rotational speed (min-1)
Component
Specification
2.5-inch drive (SFF)
288.20 GB: 15,000 RPM
576.39 GB: 10,000 or 15,000 RPM
1152.79 GB: 10,000 RPM
1729.29 GB: 10,000 RPM
3.5-inch drive (LFF and dense intermix drive
tray)
3916.14 GB: 7,200 RPM
5874.22 GB: 7,200 RPM
9790.36 GB: 7,200 RPM
Maximum mountable quantity
Mixing SFF, LFF, FMD, and dense intermix drive trays might affect the maximum number of drives that
can be mounted.
Component
Specification
SFF
24
LFF
12
Mechanical specifications for VSP G400, G600
69
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Flash module drive (flash module drive tray)
12
Dense intermix drive tray
60
Battery specifications
Storage system intake temperature
CBLM
Up to 75.2º F (24º C)
5 years
Up to 86º F (30º C)
5 years
Up to 93.2º (34º C)
4 years
Up to 104º (40º C)
3 years
Host interface
Item
Component
Specification
Interface type
Fibre Channel optical
8-Gbps, 16-Gbps, 32-Gbps
iSCSI optical
10-Gbps
iSCSI copper
10-Gbps
NAS module
10-Gbps (Fibre Channel optical)
Data transfer speed (maximum
speed for transfer to host)
Fibre Channel optical
800-Mbps (Fibre Channel)
1600-Mbps (Fibre Channel)
3200-Mbps (Fibre Channel)
iSCSI optical
10-Gbps (iSCSI optical)
iSCSI copper
10-Gbps (iSCSI copper)
NAS module (Fibre Channel)
1000 Mbs
Number of ports
8-Gbps Fibre Channel optical
64
16-Gbps Fibre Channel optical
(2-port)
32
16-Gbps Fibre Channel optical
(4-port)
64
32-Gbps Fibre Channel optical
(4-port)
64
10-Gbps optical iSCSI
32
10-Gbps copper iSCSI
32
Number of ports (NAS Module
not installed)
8-Gbps Fibre Channel optical
64
16-Gbps Fibre Channel optical
(2-port)
32
16-Gbps Fibre Channel optical
(4-port)
64
70
Mechanical specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
32-Gbps Fibre Channel optical
(4-port)
64
10-Gbps optical iSCSI
32
10-Gbps copper iSCSI
32
Number of ports (NAS Module
installed)
8-Gbps Fibre Channel optical
24
16-Gbps Fibre Channel optical
(2-port)
12
16-Gbps Fibre Channel optical
(4-port)
24
32-Gbps Fibre Channel optical
(4-port)
24
10-Gbps optical iSCSI
12
10-Gbps copper iSCSI
12
10-Gbps Fibre Channel optical
12
Transferred block size
512 bytes
Maximum number of hosts
using a Fibre Channel switch
255
Maximum number of hosts
using a network switch
255
RAID specifications
D: Data drive, P: Parity drive.
Although the storage system with a configuration of RAID 1, RAID 5, or RAID
6 provides data reliability enhanced by redundancy, there is a chance that
user data could be lost due to an unexpected host, storage system hardware,
or software failure. Therefore, users are requested to back up all data.
RAID Level
SAS, SAS 7.2k, flash drives mounted
RAID 1
2D+2D, 4D+4D
RAID 5
3D+1P, 4D+1P, 6D+1P, 7D+1P
RAID 6
6D+2P, 12D+2P, 14D+2P
Item
Specification
Maximum number of RAID groups
VSP G400:160
VSP G600:240
Maximum volume size
3 TB (or 4 TB when using the LDEVs of other
storage systems)
Maximum volumes/host groups and iSCSI
targets
2048
Maximum number of volumes per RAID group
2048
Mechanical specifications for VSP G400, G600
71
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Shared memory and data assurance
Item
Specification
Flash memory
32 MB
L3 Cache memory
4 MB
SDRAM
1 GB
Data bus
Parity
Cache memory
ECC (1 bit for correction, 2 bits for detection)
Drive
Data assurance code
Start-up time
Item
Standard: 5-to-8 minutes.
The start-up time may be longer in proportion to the number of drive trays connected. With a
maximum configuration 1 controller tray and 19 drive trays, start-up time is approximately 8
minutes.
Chassis size
Component
Specification (WxDxH)
CBLM
19.01 x 35.10 x 6.86 inches (483 x 891.7 x
174.3 mm)
SFF/LFF
18.97 x 22.24 x 3.47 inches (482 x 565 x 88.2
mm)
DBF
19.01 x 30 x 3.42 inches (483 x 762 x 87 mm)
Dense intermix drive tray
18.97 x 40.51 x 6.92 inches (482 x 1,029 x 176
mm)
(includes the depth of the cable-management
arms)
Mass
The table lists the values of a maximum configuration when all controllers and drives are mounted.
Component
Specification
CBLM
187.39 pounds (85 kg)
SFF
Approx 50.70 inches (23 kg)
LFF
Approx 59.52 inches (27 kg)
DBF
Approx. 83.77 pounds (38 kg)
72
Mechanical specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Dense intermix drive tray
Approx. 198.41 pounds (90 kg)
Required height
Component
Specification
CBLM
4 U
SFF
2 U
LFF
2 U
DBF
2 U
Dense intermix drive tray
4 U
If a drive is inserted into a slot of a dense
intermix drive tray when the installed number of
drives exceeds 240 slots per path, the drive is
blocked.
Cache specifications
Item
Specification
Capacity (GB)
VSP G400: 128
VSP G600: 256
NAS module Cache Capacity
DDR3 DIMM 8GB x 12 [Slot]
Note:
•
All 12 slots must be fully installed with
DIMMs.
•
Each DIMM is replaceable when they fail.
•
The DIMM is not common and cannot be
used with DKC DIMM.
Control method
Read LRU, Write after
Battery backup
Provided
Backup duration
Unrestricted (saving to a nonvolatile memory)
Data in the cache memory is preserved against power failures. If a power
outage occurs, data in cache memory is written to drives.
When the storage system enters Cache Backup mode, the amber WARNING
LED goes on to when the system starts. This warning indicates that the
battery charge has dropped significantly and the remaining battery capacity
is not sufficient; the storage system will continue operating with the Write
Cache function disabled.
When the battery is charged, the warning indication disappears, and the
storage system continues the operation in the Write Cache function.
Mechanical specifications for VSP G400, G600
73
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
The warning indication disappears within six hours. Even when the warning is
shown, normal operation is assured in Write-Through. Read and write
performance is lowered because the Write Cache function is disabled.
If the storage system is not charged for more than six months, the battery
can become overcharged and sustain unrecoverable damage. To avoid this
situation, charge the battery more than 3 hours every six months.
Insulation performance
Item
Specification
Insulation withstand voltage
AC 1,500 V (100 mA, 1 min)
Insulation resistance
DC 500 V, 10 M Ω or more
74
Mechanical specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Electrical specifications for VSP G400,
G600
The electrical specifications are described for the storage systems.
□
Electrical specifications
Electrical specifications for VSP G400, G600
75
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Input voltage (operable voltage
range) (V)
AC 200-240 +6%/-11%
SFF, LFF, FMD, and dense
intermix drive tray: AC 200-240
+6%/-11%
Frequency (Hz)
50/60 ±1
Number of phases, cabling
Single-phase with protective grounding
Steady-state current 100V/
200V1, 2
CBLM: 4.0x2
SFF drive tray: 2.4x2/1.2x2
LFF drive tray: 1.9x2/1.0x2
FMD drive tray: 2.6x2/1.3x2
Dense intermix drive tray: -/
3.0x2
Current rating of breaker/fuse
(A)
16.0 (each electrical)
Heat value (normal) (kJ/h)
CBLM: 2160 or less
SFF drive tray: 1120 or less
LFF drive tray: 940 or less
FMD drive tray: 1520 or less
Dense intermix drive tray: 3460
or less
Steady-state power (VA/W)3
CBLM: 1600/1560 or less
SFF drive tray: 480/460 or less
LFF drive tray: 380/350 or less
FMD drive tray: 520/490 or less
Dense intermix drive tray:
1200/1160 or less
Power consumption (VA/W)
CBLM: 640/600 or less
SFF drive tray: 320/310 or less
LFF drive tray: 280/260 or less
FMD drive tray: 440/420 or less
Dense intermix drive tray:
1000/960 or less
Notes:
1.
The power current of Nx2 described in this table is required for a single power unit.
2.
If one power unit fails, another power unit requires electric current for the two power units.
Therefore, plan the power supply facility so that the current-carrying capacity for one power
unit can provide the total capacity for two power units.
3.
This table shows the power requirement (100 V or 200 V) for the maximum configuration .
The actual required power might exceed the value shown in the table when the tolerance is
included.
76
Electrical specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Environmental specifications for VSP
G400, G600
The environmental specifications are described for the storage systems.
□
Environmental specifications
Environmental specifications for VSP G400, G600
77
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Caution: The following VSP Gx00/Fx00 storage system components are not
supported in high-temperature environments. Do not operate the following
components at temperatures of 40°C or higher:
•
DB60 dense drive tray
•
HDS provided service processor (SVP) server
•
First-generation FMDs (non-DC2 FMDs)
State
Controller
SFF, LFF drive
trays
Dense intermix drive tray
Operating
50°F to 104°F
(10°C to 40°C)
50°F to 104°F
(10°C to 40°C)
50°F to 95°F (10°C to 35°C)
Non-operating
14°F to 122°F
(-10°C to 50°C)
14°F to 122°F
(-10°C to 50°C)
14°F to 122°F (-10°C to 50°C)
Transport, storage
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F (-30°C to 60°C)
Temperature
change rate
(°C/h)
10 or less
State
Controller
FMD drive trays
Operating
50°F to 104°F
(10°C to 40°C)
DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed:
50°F to 95°F (10°C to 35°C)
Operating
50°F to 104°F
(10°C to 40°C)
DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is
installed: 50°F to 104°F (10°C to 40°C)
Non-operating
14°F to 122°F
(-10°C to 50°C)
14°F to 95°F (-10°C to 35°C)
Transport, storage
-22°F to 140°F
(-30°C to 60°C)
-22°F to 122°F (-30°C to 50°C)
Temperature
change rate
(°C/h)
10 or less
Humidity
State
Percentage
Operating
8 to 80
78
Environmental specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
8 to 90
Transport, storage (%)
5 to 95
Maximum wet bulb temperature (°C)
29 (non-condensing)
Vibration
State
m/s2
Operating
2.5 or less
Within 5 seconds (resonance point: 10 Hz or
less)
Non-operating
5.0 or less at 5 Hz to 300 Hz (no damage to
product)
9.8 (1.0 G)
Within 5 seconds (resonance point: 10 Hz or
less)
Transport (packed)
5.0 or less
Impact
State
m/s2
Operating
20 or less
(10 ms, half sine wave)
Non-operating
50 or less
(10 ms, half sine wave)
Transport (packed)
80 or less
Altitude
State
Controller
FMD drive
Operating (m)
3,000
(Environmental
temperature:
10°C to 32°C)
900
(Environmental
temperature:
10°C to 40°C)
3,000 (Environmental temperature 10°C to 32°C)
OR
900 (Environmental temperature: 10°C to 35°C) when
DKC-F710I-1R6FM or DKC-F710I-3R2FM drive is installed.
Operating (m)
3,000
(Environmental
temperature:
10°C to 32°C)
3,000 (Environmental temperature: 10°C to 32°C)
OR
Environmental specifications for VSP G400, G600
79
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
10°C to 40°C)
900 (Environmental temperature: 10°C to 40°C) when
DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP drive is
installed.
Non-operating
(m)
-60 to 12,000
N/A
State
Controller
SFF and LFF drives
Dense intermix
drive tray
Operating (m)
3,000
(Environmenta
l temperature:
10°C to 32°C)
3,000 (Environmental temperature: 10°C to
32°C)
3,000
(Environmental
temperature:
10°C to 28°C)
1,000
(Environmental
temperature:
10°C to 35°C)
900
(Environmenta
l temperature:
10°C to 40°C)
900 (Environmental temperature: 10°C to
40°C)
Non-operating
(m)
N/A
Atmosphere
Avoid areas exposed to corrosive gas and salty air.
Acoustic Noise
State
Controller
SFF, LFF
Dense intermix drive tray
Operati
ng
60 dB (Environmental temperature
32°C or less)1
60 dB
(Environmental
temperature
32°C or less)1
71 dB (Environmental
temperature 32°C or less)1, 2,
3, 4
Non-
operati
ng
55 dB
55 dB
71 dB (Environmental
temperature 32°C or less)1, 2,
3, 4
Notes:
1.
The system's internal temperature controls the rotating speed of the fan module. Therefore,
this standard value might be exceeded if the maximum load continues under high-
temperature environment or if a failure occurs in the system.
2.
Sound pressure level (LA) changes from 66 dB or 75 dB, according to the ambient
temperature, drive configuration, and operating status. Maximum volume can reach 79 dB
during maintenance procedure for a failed ENC or power supply.
3.
Acoustic power level (LwA) measured by the ISO 7779 standard is 7.2 B. This value changes
from 7.2 B to 8.1 B, according to the ambient temperature, drive configuration, and operating
status.
4.
When accessing the dense intermix drive tray, do not work for long times at the rear of the
rack.
80
Environmental specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
60 dB (Environmental temperature
32°C or less)1
60 dB (Environmental temperature 32°C or
less)1, 2, 3
(When accessing the dense intermix drive tray,
do not work for long times at the rear of the
rack.)
Non-
operati
ng
55 dB (Environmental temperature 32°C or less)1, 2, 3, 4 55 dB
Notes:
1.
The system's internal temperature controls the rotating speed of the fan module. Therefore,
this standard value might be exceeded if the maximum load continues under high-
temperature environment or if a failure occurs in the system.
2.
Sound pressure level (LA) changes from 66 dB or 75 dB, according to the ambient
temperature, drive configuration, and operating status. Maximum volume can reach 79 dB
during maintenance procedure for a failed ENC or power supply.
3.
Acoustic power level (LwA) measured by the ISO 7779 standard is 7.2 B. This value changes
from 7.2 B to 8.1 B, according to the ambient temperature, drive configuration, and operating
status.
Environmental specifications for VSP G400, G600
81
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Environmental specifications for VSP G400, G600
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
iSCSI standards and specifications
The following tables describe the standards and specifications for using iSCSI
in a hosting environment.
□
iSCSI standards
□
iSCSI specifications
iSCSI standards and specifications
83
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
The following standards apply to the management, maintenance, and iSCSI
data ports. To configure this system, use switches that comply with the
following standards:
•
IEEE 802.1D STP
•
IEEE 802.1w RSTP
•
IEEE 802.3 CSMA/CD
•
IEEE 802.3u Fast Ethernet
•
IEEE 802.3z 1000 BASE-X
•
IEEE 802.1Q Virtual LANs
•
IEEE 802.3ae 10 Gigabit Ethernet
•
RFC 768 UDP
•
RFC 783 TFTP
•
RFC 791 IP
•
RFC 793 TCP
•
RFC 1157 SNMP v1
•
RFC 1231 MIB II
•
RFC 1757 RMON
•
RFC 1901 SNMPv2
iSCSI specifications
Item
Specification
Comments
iSCSI target function
Supported
N/A
iSCSI target function
Supported
TrueCopy® only
iSCSI ports
2 per interface board
VSP Gx00 models: Maximum 32
per iSCSI system
Connection methods
Direct and switch connections
Host connections
255 (maximum per iSCSI port)
With Linux software initiator,
the maximum number
decreases.
Path failover
HDLM1
Supports Microsoft MPIO (Multi
Path I/O)
Link
10 Gbps SFP+
N/A
Transfer speed
10 Gbps
N/A
Connector type
LC
N/A
Cable
Optical OM3, OM2 MMF cable
N/A
Network switch
L2 or L3 switch
Should comply with
IEEE802.3ae
84
iSCSI standards and specifications
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maximum: 5 switches or fewer
Minimum number of cascading
switches is recommended.
MAC address
Per port (fixed value)
Factory setting: World Wide
Unique value. Cannot be
changed.
Maximum transfer unit (MTU)
1,500, 4,500, 9,000 bytes
(Ethernet frame)
Jumbo frame, MTU size greater
than 1500
Link aggregation
Not supported
N/A
Tagged VLAN
Supported
N/A
IPv4
Supported
N/A
IPv6
Supported
Note the following precautions:
•
When iSCSI Port IPv6 is set
to Enabled, if the IPv6
global address is set to
automatic, the address is
determined by acquiring a
prefix from an IPv6 router.
•
If the IPv6 router does not
exist in the network, the
address cannot be
determined. As a result, an
iSCSI connection might be
delayed. When an iSCSI
Port IPv6 is set to Enabled,
verify the IPv6 router is
connected to the same
network, and then set IPv6
global address
automatically.
Subnet mask
Supported
N/A
Gateway address
Supported
N/A
DHCP
N/A
N/A
DNS
N/A
N/A
Ping (ICMP ECHO) Transmit,
Receive
Supported
N/A
IPsec2
N/A
N/A
TCP port number
3260
Changeable among 1 to
65,535. Observe the following if
changing values:
•
The setting of the
corresponding host should
also be changed to log in
the new port number.
•
The new port number might
conflict with other network
communication or be
iSCSI standards and specifications
85
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
filtered on some network
equipment, preventing the
storage system from
communicating through the
new port number.
iSCSI name
Both iqn3 and eui4 types are
supported
The unique iqn value is
automatically set when a target
is made. iSCSI name is
configurable.
Error recovery level
0 (zero)
Error recovery by retrying from
host. Does not support Level 1
and Level 2.
Header digest
Supported
Detects header error or data
error with iSCSI
communication. The storage
system follows the host's digest
setting. If digest is enabled, the
performance degrades. The
amount of the degradation
depends on factors such as host
performance of host and
transaction pattern.
Data digest
Supported
Maximum iSCSI connections at
one time
255 per iSCSI port
N/A
CHAP
Supported
Authentication: login request is
sent properly from host to
storage. CHAP is not supported
during discovery session.
Mutual (2-way) CHAP
Supported (not available if
connected to Linux software
initiator)
Authentication: login request is
sent properly from host to
storage.
CHAP user registration
Max 512 users per iSCSI port
N/A
iSNS
Supported
With iSNS (name service), a
host can discover a target
without knowing the target's IP
address.
Note:
1.
JP1, HiCommand Dynamic Link Manager. Pass switching is achieved. Not supported on
Windows Vista and Windows 7 operating systems.
2.
IP Security. Authentication and encryption of IP packets. The storage system does not
support IPsec.
3.
iqn: iSCSI Qualified Name. The iqn consists of a type identifier, "iqn," a date of domain
acquisition, a domain name, and a character string given by the individual who acquired the
domain. Example: iqn.1994-04.jp.co.hitachi:rsd.d7m.t.10020.1b000.tar
4.
eui: 64-bit Extended Unique Identifier. The eui consists of a type identifier, "eui," and an
ASCII-coded, hexadecimal, EUI-64 identifier. Example: eui.0123456789abcdef
86
iSCSI standards and specifications
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Part replacement is essential for maintaining the high performance of the
system. Replacing system components is covered by the maintenance service
contract.
□
Battery unit
Replacement parts
87
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Use the storage system in a place where the ambient temperature is 86°F
(30°C) or less on average.
Periodic parts replacement is required. For customers with maintenance
service contracts, parts are replaced periodically in keeping with the terms of
the contract.
Note: The battery protects the data in the cache memory in an emergency,
such as a sudden power failure. In these cases, follow the normal power
down procedure. If not, the battery might reach its lifespan earlier than
expected and become unusable within three years. When replacing the
battery, follow the given procedure for disposing a used battery.
88
Replacement parts
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Data and power cables
The storage system supports a variety of data and power cables for specific
hosting environments.
□
Fibre Channel cables
□
iSCSI cables
□
Managing data cables
□
AC power cables
Data and power cables
89
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Fibre Channel cables
When constructing a system with the direct connection or Fibre Channel
switch connection, consider the following:
•
If you connect a storage system to a FC host adapter through a switch, set
Fabric = ON and set to Point-to-Point.
•
If you connect a storage system directly to FC host adapter with the
following fabric topology:
○ For 2, 4 or 8 Gbps, set the storage port to Fabric = OFF and Connection
Type FC-AL (Fibre Channel Arbitrated Loop).
○ For 16 or 32 Gbps, set the storage port to Fabric = OFF and Connection
Type P-to-P (Point-to-Point).
For the 8-Gbps Fibre Channel ports, the combinations between data-
transfer speeds and connection types are as follows:
Connection type
Data transfer speeds for 8-Gbps ports
2 Gbps
4 Gbps
8 Gbps
Auto
FC-AL
Available
Available
Available
Available
(default)
P-to-P
Available
Available
Available
Available
Fabric
Available
Available
Available
Available
For the 16-Gbps Fibre Channel ports and for 16-Gbps SFP added to the 4-
port FC 32-Gbps package, the combinations between data-transfer speeds
and connection types are as follows:
Connectio
n type
Data transfer speeds for 16-Gbps ports/SFPs
2 Gbps
4 Gbps
8 Gbps
16 Gbps
32 Gbps
Auto
FC-AL
No
available
Available
Available
Not
available
Not available
Available1
P-to-P
No
available
Available
Available
Available
Not available
Available
(default2)
Fabric
Available
Available
Available
Available
Not available
Available
Notes:
1.
If this combination is specified, the maximum transfer speed automatically specified is 8
Gbps.
2.
If this default value is set, Fabric is set to ON automatically.
Note: To connect to the server by the 16-Gbps direct connection,
the Fabric Emulation function of the Hitachi host adapter is required.
90
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
For the direct connection using the Fabric Emulation function, set
the Fabric setting of the Fibre Channel port of the Storage System to
ON.
For the 32-Gbps SFP added to the 4-port FC 32-Gbps package, the
combinations between data-transfer speeds and connection types are as
follows:
Connectio
n type
Data transfer speeds for 32-Gbps ports
2 Gbps
4 Gbps
8 Gbps
16 Gbps
32 Gbps
Auto
FC-AL
No available
No available
Available
Not
available
Not
available
Available1
P-to-P
No available
No available
Available
Available
Available
Available
(default2)
Fabric
Available
Available
Available
Available
Available
Available
Notes:
1.
If this combination is specified, the maximum transfer speed automatically specified is 8
Gbps.
2.
If this default value is set, Fabric is set to ON automatically.
Note: The five Hitachi FC HBAs also have an alternate option of
Fabric Emulation. When the HBA is configured to use this mode,
treat it as an attached switch and set the storage port to Fabric =
On and Connection Type = P-to-P.
•
Due to high-speed serial data transfer is performed via Fibre Channel, use
high-quality Fibre Channel cables that comply with the Fibre Channel-PH
standard.
Data and power cables
91
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maximum length of cable
Multimode cable
Single mode
cable
OM2
OM3
OM4
2 Gbps
984.25 ft (300 m)
1640.4 ft (500 m)
—
3280.8 ft (10 km)
4 Gbps
493 ft (150 m)
1246.72 ft (380
m)
1312.3 ft (400 m)
8 Gbps
164.04 ft (50 m)
493 ft (150 m)
623.36 ft (190 m)
16 Gbps
114.8 ft (35 m)
328.08 ft (100 m)
410.1 ft (125 m)
—
32 Gbps
65.62 ft (20 m)
229.7 ft (70 m)
328.08 ft (100 m)
—
The following table lists specifications of the Fibre Channel interface cable.
Cable type
Interface
Cable mode
name
Nominal
Cable
Connector
One side
Other side
LC-LC cable
(shortwave)
Optical
Equivalent to
DXLC-2P-PC-
xxM-GC50,
125-2SR
(OMx)
50, 125 μm,
62.5, 125 μm
Multimode
Wavelength:
850 nm
LC connector
LC connector
92
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
The following figure shows the connector used for optical interfaces.
The following figure shows the type of optical connector that connects the
storage system Fibre Channel ports.
•
LC connector type
•
Connector type: LC duplex receptacle connector
•
Interval: 6.25 mm flat type, two rows
iSCSI cables
When constructing an iSCSI system with a direct connection or switch
connection, consider the following:
Data and power cables
93
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Maximum length of cable
Multimode cable
Single mode
cable
OM2
OM3
OM4
10 Gbps (FCoE)
269.02 ft (82 m)
984.25 ft (300 m)
1804.46 ft (550
m)
—
Cable specifications for iSCSI optical interface
Cable type
Interface
Cable mode
name
Nominal
Cable
Connector
One side
Other side
LC-LC cable
Optical
Equivalent to
DXLC-2P-PC-
xxM-GC50,
125-2SR
(OMx)
50, 125 mm
Multimode
Wavelength:
850 nm
LC connector
LC connector
The following figure shows the connector used for optical interfaces.
The following figure shows the type of optical connector that connects the
storage system optical iSCSI ports.
•
LC connector type
•
Connector type: LC duplex receptacle connector
•
Interval: 6.25 mm flat type, two rows
94
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Cable specifications for 10 Gbps iSCSI copper interface
Cable type
Maximum
cable
connection
length
Data transfer
Transmission
band
Cable
Connector
Category 5e or
6a LAN cable
100 m
1 Gbps
1000BASE-T
STP ( use an
STP cable that
suppresses
radio noise)
RJ-45
Category 6a
LAN cable
50 m
10 Gbps
10GBASE-T
STP ( use an
STP cable that
suppresses
radio noise)
RJ-45
The following figure shows a 10 Gbps iSCSI cable.
Managing data cables
Organize data cables to protect the integrity of your connections and allow
proper airflow around your storage system.
Observing bend radius values
Never bend cables beyond their recommended bend radius. The following
table provides general guidelines for minimum bend radius values, but you
should consult the recommendation of your cable manufacturer.
Cable type
Minimum bend radius values
Fibre Channel
1.73 inch (40 mm)
iSCSI optical
1.73 inch (40 mm)
Category 5 Ethernet
Four times the outside diameter
of the cable
SAS
1.73 inch (40 mm)
Protecting cables
Damage to your Fibre Channel and Ethernet cables can affect the
performance of your storage system. Observe the following guidelines to
protect cables
Data and power cables
95
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Keep cables away from sharp edges or metal corners.
•
When bundling cables, do not pinch or constrict the cables.
•
Do not use zip ties to bundle cables. Instead, use Velcro hook-and-loop
ties that do not have hard edges and which you can remove without
cutting.
•
Never bundle network cables with power cables. If network and power
cables are not bundled separately, electromagnetic interference (EMI) can
affect your data stream.
•
If you run cables from overhead supports or from below a raised floor,
include vertical distances when calculating necessary cable lengths.
•
If you use overhead cable supports:
○ Verify that your supports are anchored adequately to withstand the
weight of bundled cables.
○ Gravity can stretch and damage cables over time. Therefore, do not
allow cables to sag through gaps in your supports.
○ Place drop points in your supports that permit cables to reach racks
without bending or pulling.
Cabling full-width modules
When cabling full-width modules, such as NAS modules as shown in the
following figure, route the cables horizontally, so that they do not interfere
when replacing a module.
96
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Ensuring adequate airflow
Bundled cables can obstruct the movement of conditioned air around your
storage system.
•
Secure cables away from fans.
•
Keep cables away from the intake holes at the front of the storage system.
•
Use flooring seals or grommets to keep conditioned air from escaping
through cable holes.
Preparing for future maintenance
Design your cable infrastructure to accommodate future work on the storage
system. Give thought to future tasks that will be performed on the storage
system, such as locating specific pathways or connections, isolating a fault,
or adding or removing components.
•
Purchase colored cables or apply colored tags.
•
Label both ends of every cable to denote the port to which it connects.
AC power cables
Utility AC power standards for connector types and voltage levels vary by
country. Hitachi provides a variety of power cables that facilitate using
storage systems around the world. Hitachi power cables meet the safety
standards for the country for which they are intended.
Power cable assemblies
For information about racks and power distribution units (PDUs), refer to the
Hitachi Universal V2 Rack Reference Guide.
Hitachi power cables consist of three parts:
•
Plug: Male connector for insertion into the AC outlet providing power. The
physical design and layout of the plug's contact meet a specific standard.
•
Cord: Main section of insulated wires of varying length, whose thickness is
determined by its current rating.
•
Receptacle: Female connector to which the equipment attaches. The
physical design and layout of the receptacle's contacts meet a specific
standard. Common standards are the IEC C13 receptacle for loads up to
10 amperes (A) and the IEC C19 receptacle for loads up to 15 A.
Data and power cables
97
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
CEE 7, 7
105
India
200-240
6, 16
IS-1293
South Africa
200-240
10, 16
SABS-164
11
Switzerland
200-240
10
SEV 1011
126
International
200-240
20
IEC 309
137
United Kingdom
200-240
13
BS-1363
International
200-240
20
IEC 309
148
International
200-240
30
IEC 309
Notes:
1.
Also used for 200-240 VAC applications in Korea and Philippines.
2.
Three-phase AC.
3.
Also Malaysia and Ireland.
4.
Also known as "Schuko" connector and used in Austria, Belgium, Finland, France, Germany,
Greece, Hungary, Indonesia, Netherlands, Norway, Poland, Portugal, Russia, Spain, and
Sweden.
98
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Supersedes type BS 546.
6.
3-wire (two-phase and earth). Physical variations (connector size and color) indicate
amperage rating. Used in Switzerland for a true 16 A application.
7.
4-wire (three-phase and earth). Physical variations (connector size and color) indicate
amperage rating.
8.
5-wire (three-phase, earth and neutral). Physical variations (connector size and color)
indicate amperage rating.
AC connections
The following table shows and describes the types of AC connections on your
storage system.
Description
Receptacle (male end)
Input rating
Reference standards
NEMA 5-15P
100V-120V (standard
attachment)
1 ANSI C73.11
2 NEMA 5-15P
3 IEC 83
NEMA L6-20P
200V-240V
1 ANSI C73.11
2 NEMA 6-15P
3 IEC 83
CEE 7/7
200V-240V
4 CEE (7) II, IV, VII
3 IEC 83
BS-1363
200V-240V
5 BS 1365
3IEC 83
Data and power cables
99
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Receptacle (male end)
Input rating
Reference standards
AS-3112
200V-240V
6 AS C112
Power cable usage guidelines
Hitachi storage systems are intended for rack installation and ship with power
cords. Installation and service requirements may require additional cords and
cables to be ordered. The type of power cable required by a given installation
is determined primarily by the:
•
Type of AC line feed provided by the facility.
•
Type of AC source (wall outlet or modular and monitored PDU) to be used.
•
Serviceability of components to be connected.
Storage systems require a country-specific power cable for direct connection
to a facility AC feed.
Storage systems are designed to allow replacement of hot-pluggable
components without removing the chassis from the rack. As a result, power
cables can be short because cable movement is of minimal consideration.
Three-phase power considerations for racks
Increasing power requirements for racks are making the use of three-phase
power at the rack level compelling.
•
With single-phase power, at any given time the voltage across the hot and
neutral conductors can be anywhere between its peak (maximum) and
zero. Electrical conductors must be large to meet high amperage
requirements.
•
Three-phase power uses three cycles that are 120 degrees out of phase,
which never allows the voltage to drop to zero. The more consistent
voltage derived from the three hot conductors results in smoother current
flow and allows small-gauge conductors to be used to distribute the same
amount of AC power. As a result, the load balancing and increased power
100
Data and power cables
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide