Honeywell TB7300A5014B Installation Instructions Manual
Read Online
Read the Honeywell TB7300A5014B Installation Instructions Manual online using the built-in PDF viewer.
Text of the manual
Place Bar Code Here
62-2018-05
TB7300 Series Communicating
Fan Coil Thermostats
24 VAC/FOR COMMERCIAL AND LODGING HVAC
APPLICATIONS
APPLICATION
The TB7300 PI thermostat family is specifically designed for
fan coil control. The TB7300 Series are communicating
thermostats with models available in BACnet® MS/TP and
ZigBee® wireless mesh protocols and can be easily
integrated into a WEBs-AX building automation system based
on the NiagaraAX® platform.
Thermostats equipped with an occupancy sensor cover
provide advanced active occupancy logic, which will
automatically switch occupancy levels from Occupied to
Stand-By and Unoccupied as required by local activity being
present or not. This advanced occupancy functionality
provides advantageous energy savings during occupied
hours without sacrificing occupant comfort. All thermostats
are PIR ready and can be ordered with or without Honeywell
occupancy sensor. The occupancy sensor cover is available
to order separately if a PIR is needed at a later time.
FEATURES
•
Available in BACnet MS/TP and Zigbee wireless protocols
•
Backlit LCD display with dedicated function menu keys for simple operation
•
Internal humidity sensing for increased occupant comfort through dehumidification on some models
•
Fully integrated advanced occupancy functionality with a PIR cover provides energy savings opportunity on
select models; all other models are PIR ready and can have an optional occupancy sensor cover added
•
Configurable sequences of operation
•
Configurable fan button allows thermostat to meet more applications with a single model
•
Password protection to minimize parameter tampering
•
Six levels of keypad lockout to limit access to change user parameters such as setpoints, system mode, etc.
•
Auto Fan speed mode increases occupant comfort in cooling mode by reducing humidity and reduces fan
noise
•
Available for 24 Vac on/off, floating or analog control meets advanced applications requirements
•
Three inputs for monitoring and other advanced functions
•
SPST auxiliary output that can be used for lighting or auxiliary reheat
•
All wiring connections are made to removable terminal blocks simplifying installation
TB7300 Series
Commercial
Thermostat
TB7300 Series Hotel
Thermostat with
Occupancy Sensor
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
2
TB7300 Series Model Selection
Product Number
Description
Outputs
Occupancy
Sensor1
BACnet Models
TB7300A5014B
Commercial Fan Coil Unit
2 digital + 1 Aux
Ready
TB7300A5514B
Commercial Fan Coil Unit
2 digital + 1 Aux
Yes
TB7300C5014B
Commercial Fan Coil Unit
2 floating + 1 Aux
Ready
TB7300C5514B
Commercial Fan Coil Unit
2 floating + 1 Aux
Yes
TB7300F5014B
Commercial Fan Coil Unit
2 analog + 1 Aux
Ready
TB7300F5514B
Commercial Fan Coil Unit
2 analog + 1 Aux
Yes
TB7350C5014B
Commercial Fan Coil Unit
2 floating + 1 Aux + RH Ready
TB7350C5514B
Commercial Fan Coil Unit
2 floating + 1 Aux + RH Yes
TB7350F5014B
Commercial Fan Coil Unit
2 analog + 1 Aux + RH Ready
TB7350F5514B
Commercial Fan Coil Unit
2 analog + 1 Aux + RH Yes
TB7305A5014B
Hotel Fan Coil Unit
2 digital + 1 Aux
Ready
TB7305A5514B
Hotel Fan Coil Unit
2 digital + 1 Aux
Yes
TB7305C5014B
Hotel Fan Coil Unit
2 floating + 1 Aux
Ready
TB7305C5514B
Hotel Fan Coil Unit
2 floating + 1 Aux
Yes
TB7305F5014B
Hotel Fan Coil Unit
2 analog + 1 Aux
Ready
TB7305F5514B
Hotel Fan Coil Unit
2 analog + 1 Aux
Yes
TB7355C5014B
Hotel Fan Coil Unit
2 floating + 1 Aux + RH Ready
TB7355C5514B
Hotel Fan Coil Unit
2 floating + 1 Aux + RH Yes
TB7355F5014B
Hotel Fan Coil Unit
2 analog + 1 Aux + RH Ready
TB7355F5514B
Hotel Fan Coil Unit
2 analog + 1 Aux + RH Yes
Wireless Models
TB7300A5014W
Commercial Fan Coil Unit
2 digital + 1 Aux
Ready
TB7300A5514W
Commercial Fan Coil Unit
2 digital + 1 Aux
Yes
TB7300C5014W
Commercial Fan Coil Unit
2 floating + 1 Aux
Ready
TB7300C5514W
Commercial Fan Coil Unit
2 floating + 1 Aux
Yes
TB7300F5014W
Commercial Fan Coil Unit
2 analog + 1 Aux
Ready
TB7300F5514W
Commercial Fan Coil Unit
2 analog + 1 Aux
Yes
TB7350A5014W
Commercial Fan Coil Unit
2 floating + 1 Aux + RH Ready
TB7350A5514W
Commercial Fan Coil Unit
2 floating + 1 Aux + RH Yes
TB7350F5014W
Commercial Fan Coil Unit
2 analog + 1 Aux + RH Ready
TB7350F5514W
Commercial Fan Coil Unit
2 analog + 1 Aux + RH Yes
TB7305A5014W
Hotel Fan Coil Unit
2 digital + 1 Aux
Ready
TB7305A5514W
Hotel Fan Coil Unit
2 digital + 1 Aux
Yes
TB7305C5014W
Hotel Fan Coil Unit
2 floating + 1 Aux
Ready
TB7305C5514W
Hotel Fan Coil Unit
2 floating + 1 Aux
Yes
TB7305F5014W
Hotel Fan Coil Unit
2 analog + 1 Aux
Ready
TB7305F5514W
Hotel Fan Coil Unit
2 analog + 1 Aux
Yes
TB7355C5014W
Hotel Fan Coil Unit
2 floating + 1 Aux + RH Ready
TB7355C5514W
Hotel Fan Coil Unit
2 floating + 1 Aux + RH Yes
TB7355F5014W
Hotel Fan Coil Unit
2 analog + 1 Aux + RH
Ready
TB7355F5514W
Hotel Fan Coil Unit
2 analog + 1 Aux + RH
Yes
Accessories
TB-PIR-FCU
FCU Occupancy Sensor Cover
TB-RA-1014
Wireless Remote Antenna Base
TB-RP5000W
Wireless Repeater for TB7XXX Series Wireless
Thermostats
TBST-5014W
ZigBee Wireless Survey Toolkit
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
3
62-2018—05
1 Thermostats ordered without an occupancy sensor cover can be retrofitted with an occupancy sensor cover later if
needed.
More Information
We recommend downloading the appropriate integration reference document (wireless or BACnet) and if installing
thermostats with occupancy sensor covers, then also downloading the PIR Application Guide before you begin
installation. All documentation is available on http://customer.honeywell.com.
— BACnet Integration Manual for TB7200 and TB7300 Series Thermostats (Form No. 63-4524)
— Wireless Installation and Integration Reference Guide for TB7200, TB7300, and TB7600 Thermostats
(Form No. 63-4522)
— PIR Application Guide for TB7200 and TB7300 Series Thermostats (Form No. 63-4526)
— Sensors Product Overview Brochure (Form 63-9285) provides a complete listing of 10K NTC Type II sensors.
INSTALLATION AND WIRING
Mounting Locations
•
Do not install on an outside wall.
•
Must be installed away from any heat source.
•
Should not be installed near an air discharge grill.
•
Should not be mounted in direct sun radiation.
•
Nothing must restrain vertical air circulation to the thermostat.
•
Wall surface must be flat and clean.
IMPORTANT
•
If replacing an old thermostat, label the wires before removal of the old thermostat.
CAUTION
•
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing
the thermostat.
•
Short circuit or wrong wiring may permanently damage the thermostat or the equipment.
•
Anti-short cycling can be set to 0 minutes for equipment that has an anti-cycling timer. Do not set to 0 unless
the equipment has internal anti-cycling timer or damage to equipment can occur.
•
All TB7300 Series thermostats are to be used only as operating controls. Whenever a control failure could
lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices
and/or alarm system to protect against such catastrophic failures.
TB-VWG-APP-1014
TB7XXX Series Wireless Communication Card
TB-WALL-1014
Room Sensor 10K NTC Type 2
TB-WALLOVR-1014
Room Sensor with Override 10K NTC Type 2
Product Number
Description
Outputs
Occupancy
Sensor1
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
4
Thermostat Installation
1.
Open up by pulling on the bottom side of thermostat.
(Fig. 1)
2.
Remove wiring terminals.
3.
Open the thermostat PCB to the left by pressing the PCB
retaining tabs. (Fig. 2).
4.
Pull cables 6 inches out of the wall.
5.
Thread cable through the central hole of the base.
6.
Align the base and mark the location of the two mounting
holes on the wall. Install proper side of base up.
7.
Install anchors in the wall.
8.
Insert screws through the mounting holes on each side of
the base and mount base on wall. (Fig. 2).
9.
Gently swing back the circuit board back to the base and
push on it until the tabs lock it in place.
10.
Strip each wire 1/4 inch.
11.
Wire the terminals for the desired application. See Table 1
for terminal descriptions and wiring diagrams.
12.
Gently push back excess cable into hole.
13.
Install wiring terminals in correct location (Fig. 3).
14.
Reinstall the cover (top first).
15.
Install security screw.
°C
°F
M21300
Fig. 1. Remove cover of thermostat
PCB
RETAINING
TABS
PCB
RETAINING
TABS
M21301
Fig. 2. Location of PCB retaining tabs and
mounting screws
TOP LEFT
5 POLE
CONNECTOR
BOTTOM
8 POLE
CONNECTOR
TOP RIGHT
3 POLE
CONNECTOR
M21302
Fig. 3. Re-install terminal blocks
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
5
62-2018—05
Thermostat Terminals
Table 1. Terminal identification
For information on configuration options for the binary inputs (B1 and B2) and the universal input (U3) see Table 11.
Configuration Parameters.
Sensor Wiring for all Thermostat Models
Remote sensors
Remote mount temperature sensors use 10K type 2 NTC thermistors. See Remote Inputs wiring diagram below for
wiring information.
•
Each sensor can be configured for various averaging combinations
•
Optional occupancy led
•
Optional override key
•
Remote mount temperature sensors use 10K type 2 NTC thermistors.
Table 2. Temperature vs Resistance for 10 Kohm NTC thermistor (R25°C = 10KW±3%, B25/85°C = 3975K±1.5%)
Fig. 4. Remote input
Terminal
Description
TB73xxA5x14(x)
2 and 4 Pipe on/
off
TB73xxC5x14(x)
2 and 4 Pipe floating
2 and 4 Pipe on/off
Terminal
Description
TB73xxF5x14(x)
2 and 4 Pipe analog
Internal
Temperature
X
X
Internal
Temperature
X
Internal Humidity
Model Dependent Internal Humidity
Model Dependent
1- High Fan Speed
Fan-H
Fan-H
1- High Fan Speed
Fan-H
2- Medium Fan
Speed
Fan-M
Fan-M
2- Medium Fan
Speed
Fan-M
3- Low Fan Speed
Fan-L
Fan-L
3- Low Fan Speed
Fan-L
4- 24 V~ Hot
24 V~ Hot
24 V~ Hot
4- 24 V~ Hot
24 V~ Hot
5- 24 V~ Com
24 V~ Com
24 V~ Com
5- 24 V~ Com
24 V~ Com
6- Aux BO 5
BO 5-Aux
BO 5-Aux
6- Aux BO 5
BO 5-Aux
7- Aux BO 5
BO 5-Aux
BO 5-Aux
7- Aux BO 5
BO 5-Aux
8- BO 3 Open Heat
BO 3
BO 3
Blank
9- BO 4 Close Heat
BO 4
9- AO 2 Heat
AO 2
10- BO 1 Open Cool
BO 1
10- AO 1 Cool
AO 1
11- BO 2 Close Cool
BO 2
BO 2
Not used Blank
Blank
12- BI #1
BI 1
BI 1
12- BI #1
BI 1
13- RS
RS
RS
13- RS
RS
14- Scom
Scom
Scom
14- Scom
Scom
15- BI #2
BI 2
BI 2
15- BI #2
BI 2
16- UI #3 COS/COC/
SS
UI 3
UI 3
16- UI #3 COS/COC/
SS
UI 3
ºF
ºC
Kohm
ºF
ºC
Kohm
ºF
ºC
Kohm
ºF
ºC
Kohm
ºF
ºC
Kohm
-40
-40
324.3197
-4
-20
94.5149
32
0
32.1910
68
20
12.4601
104
40
5.3467
-31
-35
234.4009
5
-15
71.2430
41
5
25.1119
77
25
10.0000
113
45
4.3881
-22
-30
171.3474
14
-10
54.1988
50
10
19.7390
86
30
8.0694
122
50
3.6202
-13
-25
126.6109
23
-5
41.5956
59
15
15.6286
95
35
6.5499
131
55
3.0016
BI 1
RS
Scom
BI 2
UI 3
REMOTE
WALL SENSOR
CONTACT
—REM NSB
—MOTION
—WINDOW
SS (SUPPLY SENSOR)
COS (CHANGEOVER
SENSOR)
COC/NH
—NORMALLY HEAT
—CLOSED CONTACT = COLD WATER
COC/NC
—NORMALLY COOL
—CLOSED CONTACT = HEAT WATER
CONTACT
—DOOR
—REMOTE OVERRIDE
—FILTER ALARM
—SERVICE ALARM
OR
M16948
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
6
If LED indicator is desired at the TB-WALL-OVR-1014:
1.
Set the Aux Cont installer parameter (which controls BO5) to option 2, Auxiliary NC.
2.
Install a jumper across the BO5 terminal and 24 Vac Hot.
Fig. 5. Wiring example of single remote wall mounted room sensor
Fig. 6. Wiring examples of two remote wall mounted room sensors for averaging applications
Fig. 7. Wiring examples of three remote wall mounted room sensors for averaging applications
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
Scom
RS
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
TB-WALLOVR-1014
TB-WALL-1014
DIP SWITCHES
S1 = ON S2 = ON
DIP SWITCHES
S1 = ON S2 = ON
REMOTE WIRING 1 SENSOR
M32847A
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
Scom
RS
TB-WALLOVR-1014
TB-WALL-1014
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
REMOTE WIRING 2 SENSORS
M32848A
Scom
RS
TB-WALL-1014
Scom
RS
TB-WALL-1014
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
1
1
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
DIP SWITCHES
S1 = ON
S2 = OFF
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
DIP SWITCHES
S1 = ON
S2 = OFF
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
AUX
C
DI
TB-WALLOVR-1014
DIP SWITCHES
S1 = OFF
S2 = OFF
ALL DIP SWITCHES
S1 = OFF
S2 = OFF
REMOTE WIRING 3 SENSORS
M32849A
Scom
RS
TB-WALL-1014
Scom
RS
TB-WALL-1014
TB-WALL-1014
TB-WALL-1014
Scom
RS
TB-WALL-1014
TB7200/TB7300
THERMOSTAT
TB7200/TB7300
THERMOSTAT
Scom
RS
Scom
RS
Scom
RS
BO 5
24 VAC
COM
BI 2
Scom
RS
BO 5
24 VAC
COM
BI 2
DIP SWITCHES
S1 = OFF
S2 = OFF
TB-WALL-1014 AND TB-WALLOVR-1014 CAN BE MIXED AND MATCHED
TB-WALL-1014 AND TB-WALLOVR-1014 ARE TO BE WIRED IN PARALLELL
ENSURE THE DIP SWITCH SETTINGS ARE CORRECT IN EACH REMOTE SENSOR
1
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
7
62-2018—05
Fan and Auxiliary Output Wiring
Main outputs wiring
Fig. 8. Power fan
Fig. 9. Auxiliary output
2 Pipe applications
4 Pipe applications
On/Off control
TB7300A5x14(x) and TB7305AC5x14(x)
On/Off control
TB7300C5x14(x), TB7305C5x14(x), TB7350C5x14(x) and TB7355C5x14(x)
Floating control
TB7300C5x14(x), TB7305C5x14(x), TB7350C5x14(x) and TB7355C5x14(x)
24 V ~ COM
24 V ~ HOT
FAN-H
FAN-M
FAN-L
24 V~ TRANSFORMER RELAY PACK
3 SPEED
2 SPEED
SINGLE
SPEED
M16947
HIGH
MED
LOW
HIGH
HIGH
LOW
DRY CONTACT TO END DEVICE 24 V~ MAXIMUM
24 VAC POWER TO RELAY
#4 24 V~ HOT
#5 24 V~ COM
#6
#7
#4 24 V~ HOT
#5 24 V~ COM
#6
#7
R
R
M16949
24 V~ HOT
24 V ~ COM
N.C. HEATING/
COOLING VALVE
BO 2
24 VAC
COM
M16960
24 V~ HOT
24 V ~ COM
N.O. HEATING VALVE
BO 3
24 VAC
COM
BO 2
N.C. COOLING VALVE
24 VAC
COM
M16961
24 V~ HOT
24 V ~ COM
HEATING/COOLING VALVE
BO1
BO2
IF N.O.
IF N.C.
24 VAC
COM
OR
M16924
24 V~ HOT
24 V ~ COM
HEATING VALVE
COOLING VALVE
BO3
BO4
BO1
BO2
IF N.O.
IF N.C.
24 VAC
COM
24 VAC
COM
OR
IF N.O.
IF N.C.
OR
M16917
24 V~ HOT
24 V ~ COM
HEATING/COOLING VALVE
BO1
BO2
OPEN
COM
CLOSE
M16925
24 V~ HOT
24 V ~ COM
HEATING VALVE
COOLING VALVE
BO3
BO4
BO1
BO2
OPEN
COM
CLOSE
OPEN
COM
CLOSE
M16918
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
8
Typical applications
Analog control
TB7300F5x14(x), TB7305F5x14(x), TB7350F5x14(x) and TB7355F5x14(x)
Schematic
Wiring
Settings
2 pipe system cooling and/or heating: TB7300A5x14(x), TB7300C5x14(x) and TB7305C5x14(x) on/off N.C.
actuator
Normally closed on/off valve
cooling and/or heating
Mandatory
•
Pipe no = 2 pipes
•
CntrltTyp = On/Off
•
Fan Menu = 0 (L-M-H)
•
FL time = as per actuator
If cooling only set:
•
SeqOpera = 0 Cooling only
If heating only set:
•
SeqOpera = 1 Heating only
If heat/cool auto-changeover
with a local water temperature
sensor set:
•
SeqOpera = 0 Cooling only
•
UI3 = COS
2 pipe system cooling and/or heating: TB7300C5x14(x) and TB7305C5x14(x) floating actuator
Modulating floating valve
cooling and/or heating
Mandatory
•
Pipe no = 2 pipes
•
CntrltTyp = Floating
•
Fan Menu = 0 (L-M-H)
•
FL time = as per actuator
If cooling only set:
•
SeqOpera = 0 Cooling only
If heating only set:
•
SeqOpera = 1 Heating only
If heat/cool auto-changeover
with a local water temperature
sensor set:
•
SeqOpera = 0 Cooling only
•
UI3 = COS
2 Pipe applications
4 Pipe applications
24 V~ HOT
24 V ~ COM
HEATING/COOLING VALVE
AO 1
COM
24 VAC
0-10 VDC
M16926
24 V~ HOT
24 V ~ COM
HEATING VALVE
COOLING VALVE
AO 2
AO 1
COM
24 VAC
0-10 VDC
COM
24 VAC
0-10 VDC
M16919
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16950
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
UI 3 COS
24 V~ COM
24 V ~ HOT
BO 2 N.C.
OPTIONAL SUPPLY WATER
TEMPERATURE SENSOR
M16953
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16950
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
UI 3 COS
24 V~ COM
24 V ~ HOT
BO 2 CLOSE
BO 1 OPEN
OPTIONAL SUPPLY WATER
TEMPERATURE SENSOR
M16954
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
9
62-2018—05
2 pipe system cooling and/or heating: TB7300F5x14(x) and TB7305F5x14(x) analog actuator
Modulating analog valve
cooling and/or heating
Mandatory
•
Pipe no = 2 pipes
•
Fan Menu = 0 (L-M-H)
•
RA/DA = as per actuator
If cooling only set:
•
SeqOpera = 0 Cooling only
If heating only set:
•
SeqOpera = 1 Heating only
If heat/cool auto-changeover
with a local water temperature
sensor set:
•
SeqOpera = 0 Cooling only
•
UI3 = COS
4 pipe system cooling and heating: TB7300C5x14(x) and TB7305C5x14(x) on/off N.C. actuators
Normally closed on/off valve
cooling and heating
Mandatory
•
Pipe no = 4 pipes
•
CntrltTyp = On/Off
•
Fan Menu = 0 (L-M-H)
•
FL time = as per actuator
•
SeqOpera = 4 Cool/Heat
4 pipe system cooling and heating: TB7300C5x14(x) and TB7305C5x14(x) floating actuators
Modulating floating valve
cooling and heating
Mandatory
•
Pipe no = 4 pipes
•
CntrltTyp = Floating
•
Fan Menu = 0 (L-M-H)
•
FL time = as per actuator
•
SeqOpera = 4 Cool/Heat
4 pipe system cooling and heating: TB7300F5x14(x) and TB7305F5x14(x) analog actuators
Modulating analog valve
cooling and heating
Mandatory
•
Pipe no = 4 pipes
•
Fan Menu = 0 (L-M-H)
•
RA/DA = as per actuator
•
SeqOpera = 4 Cool/Heat
Schematic
Wiring
Settings
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16950
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
UI 3 COS
0 V~ COM
24 V ~ HOT
AO 1
OPTIONAL SUPPLY WATER
TEMPERATURE SENSOR
M16955
0 TO 10
VDC
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16951
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
24 V~ COM
24 V ~ HOT
BO 2 CLOSE
BO 4 CLOSE
M16956
HEATING
COOLING
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16951
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
24 V~ COM
24 V ~ HOT
BO 1 OPEN
BO 2 CLOSE
BO 3 OPEN
BO 4 CLOSE
M16957
HEATING
COOLING
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
M16951
24 VAC FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
FAN-L
24 V~ COM
24 V ~ HOT
AO 1
AO 2
M16958
HEATING
COOLING
0 TO 10
VDC
0 TO 10
VDC
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
10
THERMOSTAT USER INTERFACE
The thermostat features a two-line, eight-character display. There is a low level backlight level that is always active and
can only be seen at night. To turn on the back light to high level, press any key on the front panel. The back lit display
will return to low level when the thermostat is left unattended for 45 seconds
When left unattended, the thermostat has an auto scrolling display that shows the actual status of the system. Use the
MenuScro in the configuration menu to lockout the scrolling display and to only present the room temperature and
conditional outdoor temperature to the user. With this option enabled, no local status is given on the system mode or
occupancy.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to
come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic
status display scrolling.
Table 3. Sequence and possible display options for the auto-scroll display
* Network value only
**If humidity display is enabled
***If humidity display is not enabled
% RH DISPLAY IS CONDITIONAL TO:
•
Models with RH sensor built in.
•
Display function can be enabled with RH display parameter. Displayed range is 10 to 90% RH.
OUTDOOR AIR TEMPERATURE
•
Display is only enabled when outdoor air temperature network variable is received.
OCCUPANCY STATUS
•
Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling display.
ALARMS
•
If alarms are detected, they will automatically be displayed at the end of the status display scroll.
•
During an alarm message display, the backlit screen will light up at the same time as the message and shut off
during the rest of the status display.
•
Two alarms maximum can appear at any given time. The priority for the alarms is as follows:
2 pipe system cooling or heating with reheat: TB7300C5x14(x) and TB7305C5x14(x) floating actuator
Modulating floating valve
cooling and/or heating
Mandatory
•
Pipe no = 2 pipes
•
CntrltTyp = Floating
•
Fan Menu = 0 (L-M-H)
•
FL time = as per actuator
•
SeqOpera = 2 Cool/Reheat
•
UI3 = COS
Room Temp and
Humidity
>
System mode
>
Schedule status >
Outdoor Temp*
>
Alarms
x.x °C or °F
xx % RH**
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
Service
RoomTemp
x.x °C or °F***
Sys mode
cool
Stand-By
Filter
Sys mode
heat
Unoccup
Window
Sys mode
off
Override
Schematic
Wiring
Settings
ROOM TEMPERATURE
CONTROL THERMOSTAT
3 SPEED FAN
ELECTRIC
REHEAT
M16952
24 VAC
FAN RELAYS
HIGH
MED
LOW
FAN-H
FAN-M
BO 5
BO 5
FAN-L
UI 3 COS
24 V~ COM
24 V ~ HOT
BO 2 CLOSE
BO 1 OPEN
OPTIONAL SUPPLY WATER
TEMPERATURE SENSOR
M16959
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
11
62-2018—05
STATUS LED’S
The three LEDs on the thermostat cover are used to indicate the status of the fan (any speed), a call for heat, or a call
for cooling.
•
When any of the fan speeds are ON, the FAN LED will illuminate.
•
When heating and reheat is ON, the HEAT LED will illuminate.
•
When cooling is ON, the COOL LED will illuminate.
Fig. 10. Fan coil thermostat buttons and display
User Control Options
Unoccupied mode Override
An Override can be made on commercial models during an Unoccupied period. If the Override option is enabled in the
Lockout parameter, pressing the middle override button will resume occupied setpoints for a time specified by
parameter TOccTime
Table 4. Keypad interface
Any setpoint change can be permanent or temporary based on parameter Set Type (setpoint type).
Any setpoint written through the network, will be permanent and cancel any active temporary setpoints.
Lockouts of access to certain functions is made with parameter (Lockout).
Service
Indicates that there is a service alarm as per one of the programmable binary input (BI2)
Filter
Indicates that the filters are dirty as per one of the programmable binary input (BI2)
Window
Indicates that the outside window or door is opened and that the thermostat has cancelled any cooling or
heating action (BI1)
System
Is used to toggle between the different system modes available as per sequence and menu selected.
Pressing repetitively the button will toggle between all the available modes.
Available menus are dependent on selected sequence of operation.
Fan
Is used to toggle between the different fan modes available per sequence and menu selected.
Pressing repetitively the button will toggle between all the available modes.
Available menus are dependent on selected sequence of operation and menu selected for Fan.
°C/°F
Override
Middle key is
•
°C/°F for Hotel models.
•
Override for commercial models.
Down
Adjust the setpoints down
•
In cooling mode only the cooling setpoint is displayed.
•
In heating mode only the heating setpoint is displayed.
•
In auto mode (see below).
Up
Adjust the setpoints up
•
In cooling mode only the cooling setpoint is displayed.
•
In heating mode only the heating setpoint is displayed.
•
In auto mode (see below).
MODE
FAN
M16982
°C
°F
Hotel models °C/°F
MODE
FAN
M16983
OVERRIDE
Commercial models with Override
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
12
LOCAL SETPOINT ADJUSTMENT WHEN “STP FUNC” = DUAL STP
(DUAL OCCUPIED SETPOINTS ADJUSTMENT)
Table 5. Occupied setpoint adjustments
Heat/Cool setpoint toggle with MODE button is active only in AUTO mode.
If cooling, heating or off mode are active, this function is disabled
LOCAL SETPOINT ADJUSTMENT WHEN “STP FUNC” = ATTCHSTP
(SINGLE OCCUPIED SETPOINT ADJUSTMENT)
Table 6. Occupied setpoint adjustments
Unoccupied and Stand-By setpoints adjustments
Setting the stand-by and unoccupied setpoints is done through the network or through configuration setup only.
Cooling
mode
Heating
mode
Off mode
Auto Mode
•
Setpoint presented to user is the setpoint from the last action taken by
the thermostat or the one currently in use.
•
If the other setpoint is the one desired, then the MODE button is used
to toggle between the current displayed one and the other.
Cool XX.X
°F or °C
Heat XX.X
°F or °C
No access to
setpoint
Cool XX.X °F or °C or Heat XX.X °F or °C
Toggle to (Heat or Cool) with MODE button
Cooling
mode
Heating
mode
Off mode
Auto Mode
•
Setpoint presented to user is the setpoint from the last action taken by
the thermostat or the one currently in use.
•
Both heating and cooling setpoints are changed simultaneously while
respecting the minimum configured deadband.
•
If the other setpoint is the one desired, then the MODE button is used
to toggle between the current displayed one and the other.
Cool XX.X
°F or °C
Heat XX.X
°F or °C
No access to
setpoint
Cool XX.X °F or °C and Heat XX.X °F or °C
Both heating and cooling setpoints are change simultaneously.
Toggle to (Heat or Cool) with MODE button.
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
13
62-2018—05
Mode button menu sequence.
•
Modes presented to the user are dependent on sequence of operation selected.
•
Default mode is in bold when sequence of operation parameter is changed.
Table 7. Auto Mode set to On = Auto system mode active.
Table 8. Auto Mode set to Off = Auto system mode NOT active.
Fan button menu sequences
Table 9. Available fan button menu sequences.
Auto speed fan mode is also offered in heating mode applications; it will not however have any effect on
dehumidification. It will be strictly for noise comfort issues
Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter. When Auto Fan is set to:
•
AS (Default) = Auto Speed during occupied periods. Fan is always on during occupied periods. Low, medium and
high speeds operate on temperature offset from setpoint.
•
AS AD = Auto Speed/Auto Demand during occupied periods.
—
Medium and high speeds operate on temperature offset from setpoint.
—
Low speed operates on demand and will shut down when no demand is present
Sequence selected
Mode Menu
0 = Cooling only
Off - Cool
1 = Heating only
Off - Heat
2 = Cooling With Reheat
Off – Auto – Heat – Cool
3 = Heating With Reheat
Off - Heat
4 = Cooling/Heating 4 pipes
Off – Auto – Heat – Cool
5 = Cooling/Heating 4 pipes with Reheat
Off – Auto – Heat – Cool
Sequence selected
Mode Menu
0 = Cooling only
Off - Cool
1 = Heating only
Off - Heat
2 = Cooling With Reheat
Off – Heat – Cool
3 = Heating With Reheat
Off - Heat
4 = Cooling/Heating 4 pipes
Off – Heat – Cool
5 = Cooling/Heating 4 pipes with Reheat
Off – Heat – Cool
Fan button menu
configuration
Menu presented are dependent on model used
and sequence of operation selected
Default value when
sequence toggled
0 Low-Med-High
3 Speed configuration using 3 fan relays (L-M-H)
High
1 Low-High
2 Speed configuration using 2 fan relays (L-H)
High
2 Low-Med-High-Auto 3 Speed configuration with Auto fan speed mode using 3 fan relays
(L-M-H)
High
3 Low-High-Auto
2 Speed configuration with Auto fan speed mode using 2 fan relays
(L-H)
High
4 On-Auto
Single Speed configuration. Auto is for Fan on demand/On is On all
the time
Auto
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
14
INSTALLER CONFIGURATION PARAMETER MENU
This section describes the parameters available for TB7300 Series thermostat configuration. The TB7300 Series can
be programmed at the thermostat or through WEBStation-AX, with the following exception: Wireless models must have
the Com Addr, PAN ID, and Channel set at the thermostat before adding to the wireless network or doing any
programming in WEBStation-AX.
To program the thermostat through WEBStation-AX, refer to the BACnet Integration Reference Guide for BACnet
models (Form No. 63-4524) or the Wireless Installation and Integration Reference Guide for TB7200, TB7300, TB7600
Thermostats (Form No. 63-4522) for wireless models.
Local configuration:
1.
To enter configuration, press and hold the middle button (°C/°F or Override) for 8 seconds
2.
If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down” arrows
and press the middle button again to gain access to all configuration properties of the thermostat. A wrong pass-
word entered will prevent local access to the configuration menu.
3.
Press the same middle button repetitively to scroll between all the available parameters
4.
Use the up and down key to change the parameter to the desired value.
5.
To acknowledge and save the new value, press the middle button again.
6.
The next listed parameter is now displayed.
Table 10. Configuration interface
Fan
Re-starts the configuration parameter list at the beginning.
°C/°F
Override
Enters the configuration mode. Press and hold for 8 seconds.
Pressing repetitively will scroll all available parameters one by one.
Down
Adjust parameter value down.
Up
Adjust parameter value up.
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
PswrdSet
Configuration parameters menu
access password
Default value = 0
Range is: 0 to 1000
This parameter sets a protective access password to prevent
unauthorized access to the configuration menu parameters. A default
value of “0” will not prompt a password or lock the access to the
configuration menu.
Range is: 0 to 1000
Com Addr
Thermostat networking address
Default value = 254
Range is: 0 to 254
If the thermostat is installed as a stand-alone unit, this parameter
will not be used or displayed
For BACnet models valid range to use is from 0 to 127. Default value
of 254 disables BACnet communication for the thermostat.
For wireless models valid range is 0 to 254 with a maximum of 30
thermostats per WEB-2xx controller and 50 thermostats per WEB-
6xx/-7xx controller.
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to wireless models (TB73xxX5x14W)
This parameter will only appear on wireless thermostats. If the
thermostat is BACnet, this parameter will not be used or displayed
This parameter (Personal Area Network Identification) is used to link
specific thermostats to a single specific WEBs controller with a
wireless communication card (TB-VWG-APP-1014). For every
thermostat reporting to a WEBs controller and wireless
communication card (maximum of 30 thermostats per WEB-2xx
controller and 50 thermostats per WEB-6xx/-7xx controller) be sure
you set the SAME PAN ID value both at the wireless communication
card and the thermostat(s).
The default value of 0 is NOT a valid PAN ID. The valid range of
available PAN ID is from 1 to 500
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
15
62-2018—05
Channel
Channel selection
Default value = 10
Set to: 15 or 25
Range is: 10 to 26
Conditional parameter to wireless models (TB73xxX5x14W)
This parameter will only appear when a wireless network adapter is
present. If the thermostat is installed as a stand-alone unit or is a
BACnet model, this parameter will not be used or displayed
This parameter (Channel) is used to link specific thermostats to a
specific WEBs controller with a wireless communication card. For
every thermostat reporting to a gateway (maximum of 30
thermostats per WEB-2xx controller and 50 thermostats per WEB-
6xx/-7xx controller) be sure you set the SAME channel value both at
the wireless communication card and the thermostat(s).
Honeywell recommends using only the channels 15 (2425 MHz)
or 25 (2575 MHz).
The default value of 10 is NOT a valid channel. Although the valid
range of available channels is from 11 to 26 use only channel 15 or
25 to avoid interference with other wireless devices.
Get From
Default value = 255
Range is: 0-254
Conditional parameter to wireless models (TB73xxX5x14W)
This parameter is only available for wireless thermostats. This
parameter lets you to copy the configuration parameter settings from
a like Honeywell TB7200 thermostat. To use this command, the
thermostat you want to copy parameters from must be on the
wireless network with a network address (Com addr) and must be
the same model number as the thermostat you want to copy to.
On the thermostat you want to copy parameters to, enter the network
address (Com addr) of the thermostat you want to copy parameters
from. This process can be completed locally at the thermostat or
using the WEBStation-AX.
If the parameters copy successfully, the Get From address returns to
255. If the parameters do not copy successfully, 254 is displayed. If
the copy was not successful, verify the following:
•
The thermostat to be copied is the same model as the one being
copied to.
•
The thermostat to be copied is on the network.
•
The correct network address (Com addr) value for the thermostat
to be copied was entered.
Leaving the Get From parameter value at 255 means that
configuration parameters will be set manually.
BI1
Binary input no.1 configuration
Default value = None
(None): No function will be associated with the input
(Rem NSB): remote NSB timer clock input. The scheduling will now
be set as per the binary input. It provides low cost setback operation
via a dry contact
•
Contact opened = Occupied
•
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions
using a Normally Open (NO) or Normally Closed (NC) remote PIR
motion sensor. Occupancy mode is now set as per applied PIR
function and configuration.
Application information is available in the PIR Application Guide for
TB7300 Series Thermostats (Form No. 63-4526). This document
provides installers and system designers with detailed examples on
applications, parameter configuration, sequence of operations,
troubleshooting and diagnostic help required for proper use of
occupancy sensor models.
(Window) EMS: Forces the system to disable any current heating or
cooling action by the thermostat. The mode stays the same and the
current setpoints are the same Occupied setpoints. Only the outputs
are disabled. There is a Door/Window alarm displayed on the
thermostat to indicate to the local tenant that the door/window needs
to be closed for cooling or heating to resume.
NOTE:
These settings will disable the local override function
on the thermostat.
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
16
BI2
Binary input no.2 configuration
Default value = None
None): No function will be associated with the input
(Door Dry) Door contact and Motion detector: This configuration
is only functional if binary input #1 is set to Motion N.O. or Motion
N.C. or a PIR accessory cover is used.
With this sequence enabled, the occupancy is now dictated through
those 2 inputs. Any motion detected will set the zone to occupied
status. The zone will remain permanently in occupied mode until the
door contact switch opens momentarily. The thermostat will then go
in stand-by mode. If more movements are detected, the occupied
mode will resume. While the door is opened, any movements
detected by the remote PIR sensor or the PIR accessory cover will
be ignored. Use a Normally Closed contact switching device.
•
Contact opened = Door opened
•
Contact closed = Door closed
(RemOVR): temporary occupancy remote override contact. This
function disables the central button override function on the
thermostat. The override function is now controlled by a manual
remote momentarily closed contact. When configured in this mode,
the input operates in a toggle mode.
It is now possible to toggle between unoccupied and occupied
setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
(Filter): a backlit flashing Filter alarm will be displayed on the
thermostat LCD screen when the input is energized. It can be tied to
a differential pressure switch that monitor filters
•
Contact opened = No alarm
•
Contact closed = Alarm displayed
(Service): a backlit flashing Service alarm will be displayed on the
thermostat LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of
malfunction.
•
Contact opened = No alarm
•
Contact closed = Alarm displayed
UI3
Universal input no.3
configuration
Default value = None
(None): No function will be associated with the input
(COC/NH) Change over dry contact. Normally Heat: Used when
both heating and cooling are controlled from the same thermostat
output. Contact closes when cold air/water is present. Only used and
valid if system parameter (Out1Conf) is set at 2.0
(COC/NC) Change over dry contact. Normally Cool: Used when
both heating and cooling are controlled from the same thermostat
output. Contact closes when hot air/water is present. Only used and
valid if system parameter (Out1Conf) is set at 2.0
(COS) Change over analog sensor: Used where heating and
cooling are controlled from the same output. Temperature in duct/
pipe determines control mode (heat/cool). Only used and valid if
system parameter (Out1Conf) is set at 2.0
(SS) Supply air sensor monitoring: Used for supply air
temperature monitoring.
Only used for network reporting of the supply air temperature.
Has no internal function in the thermostat
MenuScro
Menu scroll
Default value = On = Scroll
active
Removes the scrolling display and only presents the room
temperature to the user. With this option enabled, no status is given
of mode, schedule and outdoor temperature. Outdoor temperature
only displays if a network variable is received.
On = Scroll active
Off = Scroll not active
AutoMode
Enables Auto menu for Mode
button
Default value = On
Enables Auto function for the mode button
For sequences 2, 4 and 5 only
On = Auto active (Off-Cool-Heat-Auto)
Off = auto not active (Off-Cool-Heat)
C or F
Sets scale of the thermostat
Default value = °F
°F for Fahrenheit scale
°C for Celsius scale
On hotel models, this sets the default value when the thermostat
powers up
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
17
62-2018—05
%RH disp
Local %RH Display
Default value = OFF
Models with Humidity sensor
only
TB735xX5x14(x) models only
Enables the display of humidity below the room temperature on the
display
ON = Display %RH
OFF = No display of %RH
Lockout
Keypad lockout levels
Default value = 0 No lock
See Table 12 for Lockout level details
Pipe No
System type installation
Number of pipes
Default value = 4.0 Pipes
Defines the type of system installed
2.0 Pipes, will limit the number of sequences of operation available
from 0 to 3. Will enable heat/cool operation from the same output
(refer to wiring diagram)
4.0 Pipes, can access all the sequences of operation from 0 to 5. Will
enable heat/cool operation from different output (refer to wiring
diagram)
SeqOpera
Sequence of operation
Default value = Sequence #1
Fan Menu
Mode button menu
configuration
Default value = Menu #4
Menu presented is dependent on model used and sequence of
operation selected
Auto Mode operation for sequences 2 and 3 is dependent on Auto
Fan parameter
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
Table 12. Keypad Lockout Levels
Level
Occupied temperature
setpoints
System mode setting
Fan mode setting
Unoccupied Override
0
Yes access
Yes access
Yes access
Yes access
1
Yes access
Yes access
Yes access
No access
2
Yes access
No access
No access
Yes access
3
Yes access
No access
No access
No access
4
No access
No access
No access
Yes access
5
No access
No access
No access
No access
Default value = Sequence #1
System =
2 Pipes
System =
4 Pipes
0 = Cooling Only
Yes access
Yes access
1 = Heating only
Yes access
Yes access
2 = Cooling With Reheat
Yes access
Yes access
3 = Heating With Reheat
Yes access
Yes access
4 = Cooling/Heating 4 pipes
No access
Yes access
5 = Cooling/Heating 4 pipes with
Reheat
No access
Yes access
For single output applications, the system access is also
limited if UI3 is configured for local changeover COS, COC/NC
or COC/NC. The current water temperature detected by the
UI3 then limits the system mode available for the local
configuration or network write.
0 = Low-Med-High
3 Speed configuration using 3 fan
relays (L-M-H)
1 = Low-High
2 Speed configuration using 2 fan
relays (L-H)
2 = Low-Med-High-Auto 3 Speed configuration with Auto fan
speed mode using 3 fan relays (L-M-H)
3 = Low-High-Auto
2 Speed configuration with Auto fan
speed mode using 2 fan relays (L-H)
4 = On-Auto
Single Speed configuration. Auto is for
Fan on demand/On is On all the time
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
18
DHumiLCK
Dehumidification lockout
Default value = On =
Authorized
TB735xX5x14(x) models only
Typically toggled through the network.
This variable enables or disables dehumidification based on central
network requirements from the BAS front end.
On = Dehumidification Authorized
Off = Dehumidification Not Authorized
%RH set
Dehumidification setpoint
Default value = 50% RH
TB735xX5x14(x) models only
Used only if dehumidification sequence is enabled:
Range is: 30-95% RH
DehuHyst
Dehumidification Hysteresis
Default value = 5% RH
TB735xX5x14(x) models only
Humidity control hysteresis. Used only if dehumidification sequence
is enabled:
Range is: 2 to 20% RH
DehuCool
Maximum Dehumidification
Cooling output
Default value = 100%
TB735xX5x14(x) models only
Maximum cooling valve position when dehumidification is enabled.
This can be used to balance smaller reheat loads installed in regards
to the capacity of the cooling coil.
Range is: 20 to 100%
St-By TM
Stand-by Timer value
Default value = 0.5 hours
Time delay between the moment where the PIR cover detected the
last movement in the area and the time which the thermostat stand-
by mode and setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5 hr increments
Unocc TM
Unoccupied Timer value
Default value = 0.0 hours
Time delay between the moment where the thermostat toggles to
stand-by mode and the time which the thermostat unoccupied mode
and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its default
value of 0.0 hours disables the unoccupied timer. This prevents the
thermostat to drift from stand-by mode to unoccupied mode when
PIR functions are used
Range is: 0.0 to 24.0 hours in 0.5 hr increments
St-By HT
Stand-by heating setpoint
Default value = 69 F
The value of this parameter should reside between the occupied and
unoccupied heating setpoints and make sure that the difference
between the stand-by and occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Stand-by heating setpoint range is: 40 to 90 F (4.5 to 32.0 C)
St-By CL
Stand-by cooling setpoint limit
Default value = 78 F
The value of this parameter should reside between the occupied and
unoccupied cooling setpoints and make sure that the difference
between the stand-by and occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range is: 54 to 100 F (12.0 to 37.5 C)
Unocc HT
Unoccupied heating setpoint
Default value = 62 F
Unoccupied heating setpoint range is: 40 to 90 F (4.5 to 32.0 C)
Unocc CL
Unoccupied cooling setpoint
limit
Default value = 80 F
Unoccupied cooling setpoint range is: 54 to 100 F (12.0 to 37.5 C)
Heat max
Maximum heating setpoint limit
Default value = 90 F (32 C)
Maximum occupied and unoccupied heating setpoint adjustment.
Heating setpoint range is: 40 to 90 F (4.5 to 32.0 C)
Cool min
Minimum cooling setpoint limit
Default value = 54 F (12 C)
Minimum occupied and unoccupied cooling setpoint adjustment.
Cooling setpoint range is: 54 to 100 F (12.0 to 37.5 C)
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
19
62-2018—05
Pband
Proportional band setting
Default value = 3
Adjust the proportional band used by the thermostat PI control loop.
CAUTION
Note that the default value of 3.0 F (1.2 C) gives satisfactory
operation in most normal installation cases. The use of a
superior proportional band different than the factory one is
normally warranted in applications where the thermostat
location is problematic and leads to unwanted cycling of the
unit. A typical example is a wall mounted unit where the
thermostat is installed between the return and supply air
feeds and is directly influenced by the supply air stream of
the unit.
Set Type
Temporary setpoint enable
Default value = Permnent
Enables temporary setpoints
feature to any change of
occupied or unoccupied
setpoint.
Temporar: (temporary) Local changes to the heating or cooling
setpoints by the user are temporary. They will remain effective for the
duration specified by ToccTime. Setpoints will revert back to their
default value after internal timer ToccTime expires.
To change setpoints permanently, revert to No this variable or write
setpoints through the network. Any setpoints written through the
network will be permanent ones and saved to EEPROM.
Permnent: (permanent) Any change of occupied or unoccupied
setpoints through the keypad by the user are permanent and saved
to and EEPROM.
Spt Func
Local setpoint settings
Default value = Dual Spt
Set the local setpoint interface for the user.
Dual Spt (Dual Occupied Setpoints Adjustment)
Attch Spt (Single Occupied Setpoint Adjustment)
TOccTime
Temporary occupancy time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints when
override function is enabled.
When the thermostat is in unoccupied mode, function is enabled with
either the menu or UI2 configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, and up to 24 hours
Deadband
Minimum deadband
Default value = 2.0 F (1.0 C)
Minimum deadband value between the heating and cooling
setpoints. If modified, it will be applied only when any of the setpoints
are modified.
Range is: 2, 3, 4 or 5 F, 1.0 F increments (1.0 to 2.5 C, 0.5 C
increments)
Cal RS
Room temperature sensor
calibration
Default value = 0.0 F or C
Offset that can be added/subtracted to actual displayed room
temperature .
Range is: ± 5.0 F, 1.0 F increments (± 2.5 C, 0.5 C increments)
Cal RH
Humidity sensor calibration
Default value = 0%RH
Offset that can be added/subtracted to actual displayed humidity by
± 15.0 %RH.
Range is : ± 15.0 %RH
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
Value
F scale Pband
C scale Pband
3
3 F
1.7 C
4
4 F
2.2 C
5
5 F
2.8 C
6
6 F
3.3 C
7
7 F
3.9 C
8
8 F
4.4 C
9
9 F
5.0 C
10
10 F
5.6 C
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
20
Aux cont
Auxiliary contact function and
configuration
Default value = 0 Not Used
0 Aux contact function used for reheat.
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK OR
LOCAL, Ignore this parameter.
The output will directly follow the occupancy of the thermostat
1 Auxiliary NO, Occ or St-By = Contact Closed/Unoccupied =
Contact Opened
2 Auxiliary NC, Occ or St-By = Contact Opened/Unoccupied =
Contact Closed
Output to follow directly main occupancy and Fan on command
Typically used for 2 position fresh air damper applications.
3 Auxiliary NO, Occ or St-By and Fan On = Contact Closed/
Unoccupied and Fan On or Off = Contact Opened
4 Auxiliary NC, Occ or St-By and Fan On = Contact Opened/
Unoccupied and Fan On or Off = Contact Closed
Output to follow secondary network occupancy command
5 Auxiliary on/off control through auxiliary network command. The
output can be commanded through the network for any required
auxiliary functions through a separate and dedicated network
variable.
Auto Fan
Auto Fan Function
Default value = AS
Auto Speed Fan Mode operation for Fan Sequences 2 and 3.
AS = Auto Speed during occupied periods. Fan is always on during
occupied periods.
AS AD = Auto Speed/Auto Demand during occupied periods.
FL time
Floating actuator timing
Default value = 1.5 minutes
For floating models TB73xxC5x14(x) only
Maximum stroke time of floating valve actuator.
Range is: 0.5 to 9.0 minutes in 0.5 minutes increment
cph
On/Off devices cycles per hour
Default value = 4 cph
For on/off models and sequences TB73xxC5x14(x) only
Will set the maximum number cycles per hour under normal control
operation. It represents the maximum number of cycles that the
equipment will turn ON and OFF in one hour.
Note that a higher cph will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
Range is: 3, 4, 5, 6,7 and 8 cph
RA/DA
Reverse acting or Direct acting
signal
Default value = DA signal
For analog models TB73xxF5x14(x) only
Reverse acting or Direct acting signal for analog output signals
DA = Direct acting, 0 to 100% = 0 to 10 Vdc
RA = Reverse acting, 0 to 100% = 10 to 0 Vdc
Reheat
Sets the reheat output time
base
Default value = 0 = 15 minute
Valid only if reheat sequences are enabled
0 = 15 minutes
1 = 10 seconds for Solid state relays
UI3 dis
Display UI3 value.
Used as diagnostic/service help to troubleshoot and diagnose
sensor operation.
Supply or change over temperature when UI3 is configured as an
analog input .
(SS or COS)
Table 11. Configuration parameters
Configuration
parameters
Default value
Significance and adjustments
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
21
62-2018—05
SPECIFICATIONS
Network Protocol: Models available in BACnet MS/TP or ZigBee wireless mesh
WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and WEB-7xx
Platform:
WEB-2xx and WEB-6xx - WEBStation-AX 3.0 or later
WEB-7xx - WEBStation-AX 3.5 or later
Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA Class 2
Operating conditions:
32 F to 122 F (0 C to 50 C)
0% to 95% R.H. non-condensing
Storage conditions:
-22 F to 122 F (-30 C to 50 C)
0% to 95% R.H. non-condensing
Temperature sensor: 10 K NTC thermistor on board
Temperate sensor resolution: ± 0.2 F (± 0.1 C)
Temperature control accuracy: ± 0.9 F (± 0.5 C) @ 70 F (21 C) typical calibrated
Humidity sensor and calibration: Single point calibrated bulk polymer type sensor
Humidity sensor precision:
Reading range from 10-90% R.H. non-condensing
10 to 20% precision is 10%
20% to 80% precision is 5%
80% to 90% precision is 10%
Humidity sensor stability Less than 1.0% yearly (typical drift)
Dehumidification setpoint range: 30% to 95% R.H.
Occ. Stand-By and Unocc cooling setpoint range: 54 to 100 F (12.0 to 37.5 C)
Occ. Stand-By and Unocc heating setpoint range: 40 F to 90 F (4.5 C to 32 C)
Room and outdoor air temperature display range -40 F to 122 F (-40 C to 50 C)
Proportional band for room temperature control: Cooling and Heating: 3.2 F (1.8 C)
Binary inputs: Dry contact across terminal BI1, BI2 and UI3 to Scom
Contact output rating:
Fan relay output: 30 Vac, 1 Amp. Maximum, 3 Amp. in-rush
Valve triac output: 30 Vac, 1 Amp. Maximum, 3 Amp. in-rush
Valve analog: 0 to 10 Vdc into 2KW resistance min.
Wire gauge 18 gauge maximum, 22 gauge recommended
Dimensions: See Fig. 11
Approximate shipping weight: 0.75 lb (0.34 kg )
TB7300 SERIES COMMUNICATING FAN COIL THERMOSTATS
62-2018—05
22
Fig. 11. Thermostat dimensions in inches (mm)
Agency Approvals all models:
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
C-Tick: EN55022:2006, IEC 61326-1:2005
Agency Approvals all models
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
CE: EMC Directive 89/336/EEC (Europe Union)
Agency Approvals wireless models
FCC: Compliant to: Part 15, Subpart C
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Agency Approvals BACnet models
BTL
IMPORTANT
All TB7300 series controls are for use as operating controls only and are not safety devices. These instru-
ments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable opera-
tion in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the
responsibility of the user/installer/electrical system designer to incorporate safety devices (such as relays, flow
switch, thermal protections, etc…) and/or alarm system to protect the entire system against such catastrophic
failures. Tampering of the devices or miss application of the device will void warranty.
5
(125)
3-2/5 (86)
1-3/20 (29)
M21304