Fujitsu AOYA18LALL Installation And Operating Manual

Specifications

Brand: Fujitsu
Category: Heat Pump
Model: AOYA18LALL
File Type: PDF
File Size: —
Pages: 60

Read Online

Read the Fujitsu AOYA18LALL Installation And Operating Manual online using the built-in PDF viewer.

Text of the manual

Document n° 1350-2 ~ 15/01/2009

Fujitsu General (Euro) GmbH Werftstrasse 20 40549 Düsseldorf - Germany Subject to modifications without notice. Non contractual document. Heat pump air/water split single service Installation and operating manual intended for professionals To be saved for future consultation FR EN NL IT DE

Installation and operating manual “1350-EN”

Heat pump, Split, single service Packing list Heat pump Outside unit Hydraulic module Designation Code Model Code Model Code AOYA18LALL WSYA 050 DA 023600 AOYA18LALL WSYA 065 DA 023601 AOYA24LALL WSYA 080 DA 023602 AOYA30LBTL WSYA 095 DA 023603 AOYA45LATL AOYA45LBTL WSYA 128 DA 023604 AOY54LJBYL WSYA 155 DA 023605 Optional equipment • 2nd circuit kit (UTW-KZSXA) - for connecting 2 heating circuits • DHW kit (UTW-KDWXA) - for connecting a DHW tank (with built-in electrical backups) • Boiler connection kit (UTW-KBSXA) - for connecting a boiler to the heat pump • Room thermostat (UTW-C55XA) - For correcting the ambient temperature • Remote control (UTW-C75XA) - For correcting the ambient temperature and programming the heat pump. • Cooling kit (UTW-KCLXA) • Swimming pool kit (UTW-KSPXA) • High flow rate circulating pump kit (UTW-PHFXA) For the installation of 1 circuit floor heating with model 128 and 155 • Cooling kit (UTW-KCHXA) compatible with high flow rate circulating pump (128 and 155) Scope of application This heat pump provides: - Heating in winter, - Control of two heating circuits*, - Production of domestic hot water* (provided that combined with a DHW tank). - Cooling in summer*. - Installation with boiler connection as a supplementary heating for the coldest days*. * : These options require the use of additional kits (see § “Optional equipment”).

Installation and operating manual “1350-EN”

3 Heat pump, Split, single service Contents Description of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 4 Package . . . . . . . . . . . . . . . . . . P. 4 Definitions . . . . . . . . . . . . . . . . . P. 4 Specifications . . . . . . . . . . . . . . . P. 5 Heating power curve . . . . . . . . . . . P. 6 Description. . . . . . . . . . . . . . . . P. 11 Operating principle . . . . . . . . . . . P. 12 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 14 Regulation installation and maintenance conditions . . . . . . . . . . . . . . . . P. 14 Unpacking and reservations . . . . . . P. 14 Receipt . . . . . . . . . . . . . . . . . . . . P. 14 Handling . . . . . . . . . . . . . . . . . . . P. 14 Accessories provided. . . . . . . . . . . . . P. 14 Installation position . . . . . . . . . . . P. 14 Installation of the outside unit . . . . . P. 14 Installation precautions . . . . . . . . . . . P. 14 Outside unit positioning . . . . . . . . . . . P. 16 Condensate drain hose. . . . . . . . . . . . P. 16 Installing the hydraulic module . . . . . P. 17 Installation precautions . . . . . . . . . . . P. 17 Positioning the hydraulic module. . . . . . . P. 17 Refrigeration connections. . . . . . . . P. 18 Rules and precautions . . . . . . . . . . . . P. 18 Refrigeration connections . . . . . . . . . . P. 18 Creating the flarings . . . . . . . . . . . . . P. 18 Shaping the refrigeration pipes . . . . . . . P. 19 Connecting the flared connections . . . . . P. 19 Filling the installation with gas . . . . . P. 21 Creating a vacuum and filling the refrigeration connections with gas . . . . . . . . . . . . . P. 21 Sealing test . . . . . . . . . . . . . . . . . . P. 21 Additional charge . . . . . . . . . . . . . . . P. 22 Connecting the heating circuit hydraulically . . . . P. 23 General . . . . . . . . . . . . . . . . . . . . P. 23 Rinsing out the installation . . . . . . . . . . P. 23 Filling and purging the installation . . . . . . P. 23 Electrical connections . . . . . . . . . P. 24 Characteristic of the electrical supply . . . . P. 24 General remarks on electrical connections . P. 24 Overview of all the electrical connections . . P. 25 Cable section and protection rating . . . . . P. 25 Electrical connections on outside unit side . P. 26 Electrical connections on the hydraulic module side . . . . . . . . . . . . . . . . . . . . . . P. 27 Outdoor sensor . . . . . . . . . . . . . P. 29 Room thermostat and/or remote control P. 29 Start-up . . . . . . . . . . . . . . . . . P. 30 Configuring the room thermostat . . . . P. 30 Configuring remote control . . . . . . . P. 30 Regulation system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 31 User interface and remote control (Option) . . . . . . . . . . . . . . . . . P. 31 Room thermostat (Option) . . . . . . . P. 32 Temperature control. . . . . . . . . . . P. 32 Manual adjustment . . . . . . . . . . . P. 32 Self-adaptation . . . . . . . . . . . . . P. 32 Parametering the setting . . . . . . . . P. 34 General . . . . . . . . . . . . . . . . . . . . P. 34 Setting parameters . . . . . . . . . . . . . . P. 34 List of function lines (settings, diagnosis, status) . . . . . . . . . P. 34

Installation and operating manual “1350-EN”

Heat pump, Split, single service Configuring the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 46 Configuration 1, 2, 3 or 4: heat pumps with electric back-ups . . P. 47 Hydraulic connections . . . . . . . . . . . P. 47 Electrical connections . . . . . . . . . . P. 47 Parametering the setting . . . . . . . . . P. 47 Special cases . . . . . . . . . . . . . . . P. 47 Electrical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 52 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 57 Faults displayed on hydraulic module . P. 57 Faults displayed on the outside unit . . P. 58 Information display . . . . . . . . . . . P. 59 Instructions for the user . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P. 60 1 Description of the unit 1.1 Package • 1 package: Outside unit • 1 package: hydraulic module and outdoor sensor 1.2 Definitions Split: The heat pump consists of two elements (an outside unit for outside and a hydraulic module for inside the dwelling). Air/water: The surrounding air is the energy source. This energy is transmitted to the water in the heating circuit by the heat pump. Inverter: the fan and compressor speeds are modulated according to the heating requirements. This technology enables you to save on energy and operate on a single-phase power supply, whatever the heat pump’s output, by avoiding heavy intensities on start-up. COP (coefficient of performance): this is the relationship between the energy transmitted to the heating circuit and electrical energy consumed.

Designation, Model . . . . . . . . . . . . . . . . . . . . . . . . 050 . . . . 065 . . . . 080 . . . . 095 . . . . 128 . . . . 155

Nominal heating performances (outside temperature/ initial temperature) Heat output +7 °C / +35 °C - Floor heating system . . . . kW . . . . . . 5 . . . . . 6,5 . . . . . 8 . . . . . 10,3 . . . . 12,8 . . . . 15,5 -7 °C / +35 °C - Floor heating system . . . . kW. . . . . . 4,8 . . . . . 5,6 . . . . . 7 . . . . . 8,1 . . . . . 11. . . . . 13,8 +7 °C / +45 °C - Low temperature radiator . kW . . . . . 4,15 . . . . 5,4 . . . . . 6,2 . . . . . 8,3 . . . . . 9,7 . . . . 13,3 -7 °C / +45 °C - Low temperature radiator . . kW . . . . . 4,05 . . . . 5,1 . . . . . 5,9 . . . . . 7,3 . . . . . 8,3 . . . . . 11 Power absorbed +7 °C / +35 °C - Floor heating system . . . . kW . . . . . 1,16 . . . . 1,63 . . . . 1,88 . . . . 2,57 . . . . 3,12 . . . . 3,88 -7 °C / +35 °C - Floor heating system . . . . kW . . . . . 1,75 . . . . 2,24 . . . . 2,54 . . . . 3,52 . . . . 3,79 . . . . 5,3 +7 °C / +45 °C - Low temperature radiator . . kW . . . . . 1,15 . . . . 1,61 . . . . 1,88 . . . . 2,51 . . . . 3,13 . . . . 4,09 -7 °C / +45 °C - Low temperature radiator . . kW . . . . . 1,72 . . . . 2,32 . . . . 2,62 . . . . 3,48 . . . . 4,61 . . . . 5,37 Nominal coefficient of performance (COP) (+7 °C / + 35 °C) . . . . . . . . . . . . . . . . . . -. . . . . . 4,3 . . . . . 4 . . . . . 4,25 . . . . . 4 . . . . . 4,1 . . . . . 4 Electrical characteristics Supply voltage (50 HZ) . . . . . . . . . . . . . . . V . . . . . 230 . . . . 230 . . . . 230 . . . . 230 . . . . 230 . . . . 230 Maximum start-up current of the appliance . . . . A . . . . . 10,5 . . . . 10,5 . . . . 12,9 . . . . 15,3 . . . . 22,6 . . . . 25,9 Nominal intensity . . . . . . . . . . . . . . . . . . A. . . . . . 8,3 . . . . . 8,3 . . . . 10,6 . . . . 11,7 . . . . 16,7 . . . . 20,6 Maximum current of the electrical back-ups . . . . A . . . . . . 13 . . . . . 13 . . . . . 13. . . . . 26,1 . . . . 26,1 . . . . 26,1 Power of the electrical back-ups . . . . . . . . . kW . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 6 . . . . . . 6 . . . . . . 6 Real power absorbed - By the fan . . . . . . . . . . . . . . . . . . . W . . . . . . 54 . . . . . 54 . . . . . 65 . . . . . 103 . . . . 2x103 . . . 2x103 - By the circulation pump . . . . . . . . . . . . W . . . . . 113 . . . . 113 . . . . 113 . . . . 113 . . . . 151 . . . . 151 Maximum power absorption - By the outside unit . . . . . . . . . . . . . . . W . . . . . 2600 . . . . 2600 . . . . 2930 . . . . 3500 . . . . 5150 . . . . 5900 Hydraulic circuit Maximum operating pressure . . . . . . . . . . . bar . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3 . . . . . . 3 Hydraulic system flow rate 4°C<t<8°C (nominal conditions) - minimum . . . . . . . . . . . . . . . . . . . . . l/h . . . . . 540 . . . . 600 . . . . 860 . . . . 1000 . . . . 1380 . . . . 1670 - maximum . . . . . . . . . . . . . . . . . . . . . l/h . . . . . 1100 . . . . 1400 . . . . 1700 . . . . 2100 . . . . 2700 . . . . 3300 Various Weight of outside unit . . . . . . . . . . . . . . . kg . . . . . . 40 . . . . . 40 . . . . . 44 . . . . . 64 . . . . . 98 . . . . . 105 Noise level at 5 meters (outside unit) . . . . . . . dB . . . . . . 39 . . . . . 39 . . . . . 40 . . . . . 41 . . . . . 40 . . . . . 40 Weight of hydraulic module (empty/full of water). kg. . . . 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5. 52,5 / 77,5 Water capacity of the hydraulic module . . . . . . . l . . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25 . . . . . 25 Heating system operating limits Exterior temp mini/maxi . . . . . . . . . . . . . . °C . . . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24 . . -15/+24 Initial max. heating water temperature - Floor heating system . . . . . . . . . . . . . . °C . . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 - Low temperature radiator . . . . . . . . . . . °C . . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52 . . . . . 52 Initial min. heating water temperature. . . . . . . °C . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8 . . . . . . 8 Refrigeration circuit Diameter of gas pipes . . . . . . . . . . . . . inches. . . . . . 1/2 . . . . . 1/2 . . . . . 5/8 . . . . . 5/8 . . . . . 5/8 . . . . . 5/8 Diameter of fluid pipes. . . . . . . . . . . . . inches . . . . . . ¼ . . . . . ¼ . . . . . ¼ . . . . . 3/8 . . . . . 3/8 . . . . . 3/8 Factory charge of refrigerant R410A . . . . . . . . g . . . . . 1250 . . . . 1250 . . . . 1700 . . . . 2100 . . . . 3350 . . . . 3400 Maximum operating pressure . . . . . . . . . . . bar . . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 . . . . . 45 Minimum length of pipes . . . . . . . . . . . . . . m . . . . . . 0 . . . . . . 0 . . . . . . 5 . . . . . . 5 . . . . . . 5 . . . . . . 5 Maximum length of pipes* . . . . . . . . . . . . . m . . . . . . 10 . . . . . 10 . . . . . 15 . . . . . 20 . . . . . 20 . . . . . 20 Maximum length of pipes** . . . . . . . . . . . . . m . . . . . . 20 . . . . . 20 . . . . . 30 . . . . . 40 . . . . . 40 . . . . . 40 Maximum level difference**. . . . . . . . . . . . . m . . . . . . 15 . . . . . 15 . . . . . 20 . . . . . 30 . . . . . 30 . . . . . 30 * Factory charge of refrigerant R410A ** Taking into account the possible additional load of refrigeration fluid R410A (see p. 22) Installation and operating manual “1350-EN” 5 Heat pump, Split, single service

Installation and operating manual “1350-EN”

Heat pump, Split, single service 5 1,00 2,00 3,00 4,00 5,00 6,00 7,00 8,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Floor heating system Very low temperature radiator Heat output Power absorbed 6 1,00 2,00 3,00 4,00 5,00 6,00 7,00 8,00 9,00 10,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Heat output Power absorbed Floor heating system Very low temperature radiator 8 1,00 2,00 3,00 4,00 5,00 6,00 7,00 8,00 9,00 10,00 11,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Heat output Power absorbed Floor heating system Very low temperature radiator 1.4 Heating power curve Values according to standard EN 14511, for which it is necessary to add the power absorbed by the heating circulation pump 080 065 050

Installation and operating manual “1350-EN”

7 Heat pump, Split, single service 10 1,00 3,00 5,00 7,00 9,00 11,00 13,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Heat output Power absorbed Floor heating system Very low temperature radiator 13 1,00 3,00 5,00 7,00 9,00 11,00 13,00 15,00 17,00 19,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Heat output Power absorbed Floor heating system Very low temperature radiator 16 1,00 3,00 5,00 7,00 9,00 11,00 13,00 15,00 17,00 19,00 21,00 -20 -15 -10 -5 0 5 10 15 20 Outside temperature (°C) Power (kW) Heat output Power absorbed Floor heating system Very low temperature radiator 155 128 095

Installation and operating manual “1350-EN”

Heat pump, Split, single service Figure 1 - Dimensions in mm 540 66 790 10 347 300 189 177 578 320 121 184 A B A B S8 S5 S6 1/4” 1/4” 1/2” 5/8” Top view Front view Sight of lower part Overflow hole (Ø 20) 4 Holes Ø 10) AIR Side view AIR 050 065 080  Outside unit, Model 050, 065, 080 77 900 830 21 9 400 330 31 12 196 147 170 99 3/8” 5/8” 370 650 AIR Front view Side view Top view AIR Overflow hole (Ø 20) 4 Ø 10) Holes Sight of lower part  Outside unit, Model 095

Installation and operating manual “1350-EN”

9 Heat pump, Split, single service Figure 2 - Dimensions in mm 31 77 900 330 12 9 400 650 21 1290 147 170 196 370 99 3/8” 5/8” Air Overflow hole (Ø 20) 4 Ø 10) Holes Top view Front view Sight of lower part Side view Air Air  Outside unit, Model 128, 155 480 88 235 450 1034 1000 Front view Side view Heating flow Ø M 26x34 Heating return Ø M 26x34 Figure 3 - Dimensions in mm  Hydraulic module

Installation and operating manual “1350-EN”

Heat pump, Split, single service Fig. 4 - Hydraulic pressures and flow rates available Fig. 5 - Ohmic values of the sensors (Hydraulic module) 0,8 1 1,2 1,4 1,6 0 100 200 300 400 500 600 mbar 1 mbar = 10 mmCE = 100 Pa 1,8 m /h 3 0,6 0,4 1 2 3 0 2500 5000 7500 10000 12500 15000 17500 20000 22500 25000 27500 30000 32500 0 10 20 30 40 50 60 70 80 90 100 °C Ω 10 k 25°C Ω, -50 1000 10000 43907 2490 338 -25 0 25 50 75 ° C Ω 1 k 25°C Ω, Outdoor sensor QAC34 Condensation sensor Heat pump return sensor Heat pump flow sensor 10000 1000 100 10 1 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 Ω Ohmic value (k ) - Evaporator outlet - Evaporator centre - Compressor casing - Outside - Compressor - Discharge Temperature °C Fig.6 - Ohmic values of the sensors (outside unit)

Installation and operating manual “1350-EN”

11 Heat pump, Split, single service Figure 7 - Outside unit components  Model 050, 065, 080  Model 128, 155 13 1 2 12 11 10 9 8 7 6 5 4 3 13 1 2 12 11 10 9 8 7 6 5 3  Model 095 13 1 2 12 11 10 9 8 7 6 5 4 3 Legend 1 - Low-noise, high-output coil 2 - Electric variable speed "inverter" motor 3 - "Inverter" control module 4 - Vacuum start (pump down) and control light 5 - Connection terminal blocks (power and interconnection) 6 - Refrigerant accumulator bottle 7 - Cycle reversing valve 8 - Anti-corrosion treated bodywork 9 - Electronic expansion valve 10 - Noise and temperature insulated "inverter" compressor 11 - Refrigeration connection valves (flared connectors) with protective caps 12 - Holding tank with condensate drain hole 13 - High-performance exchange surface evaporator; anti-corrosion treated hydrophilic aluminium fins and grooved copper tubes.

Installation and operating manual “1350-EN”

Heat pump, Split, single service 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Front view Side view Identification plate Figure 8 - Hydraulic module components Legend 1 - Electric box 2 - Regulator / User interface 3 - Start/stop switch 4 - Heating circulation pump 5 - Initial heating 6 - Gas refrigeration connection 7 - Fluid refrigeration connection 8 - Heating return 9 - Drain valve 10 - Safety valve 11 - Safety thermostat () 12 - Manometer 13 - Manual drainer 14 - Expansion vessel 15 - Condenser 16 - Electric back-ups 1.6 Operating principle The heat pump transmits the energy contained in the surrounding air into the dwelling to be heated. The heat pump consists of four main elements, in which a refrigerant fluid (R410A) circulates. - In the evaporator (rep. 13, fig 7, page 11): The energy is taken from the surrounding air and is transmitted to the refrigerant. - Because it has a low boiling point, it changes from the liquid state to the vapour state, even in cold weather (down to -15 °C outside temperature). - In the compressor (rep. 10, fig 7, page 11): The vaporised refrigerant brought to high pressure and takes on more calories. - In the condenser (rep. 15, fig 8, page 12): The energy in the refrigerant is transmitted to the heating circuit. The refrigerant returns to liquid state. - In the expansion valve (rep. 9, fig 7, page 11): The liquefied refrigerant is brought back to low pressure and returns to its initial temperature and pressure. The heat pump is equipped with a controller, which controls the internal temperature based on the outside temperature measurement and governed by the temperature control. The room thermostat (optional) provides a corrective action for the temperature control The hydraulic module is equipped with an electric back-ups system, which is triggered to provide additional heat during the coldest periods. Regulation functions - The heating circuit’s initial temperature is controlled by the temperature control. - The power of the outside unit is modulated according to initial heating temperature via the “inverter” compressor. - Control of the electric back-up heating. - The daily timer program enables you to define the periods for comfortable or reduced ambient temperature. - Summer/winter mode switchover is automatic. - Control of the supplementary boiler* (the electric back-ups are deactivated). - The room thermostat* (optional) provides a corrective action for the temperature control - Control of a second heating circuit*. - Domestic hot water: Heating time programme, control of the operation of the DHW circulation pump. - Control of swimming pool heating*. Protection functions - Anti-legionella cycle for domestic hot water. * If the heat pump is equipped with optional equipment and the associated kits.

Domestic hot water (DHW) operating principle

Two domestic hot water (DHW) temperatures can be parametered: comfort temperature (line 1610 to 60 °C) and reduced temperature (line 1612 to 40 °C). Setting for reduced temperature can be useful to prevent the DHW from switching on too often and for too long during the day. The production of domestic hot water (DHW) is triggered when the temperature in the tank falls 7°C (setting from line 5024) below the set temperature. The heat pump produces the domestic hot water, which is then supplemented, if required, by electrical backup heating from the tank. Depending on how the parameter (1620) is set, comfort temperature can be reached 24h/day or only at night or depending on the heat pump programme. If the contract concluded with the energy provider includes a subscription to day/night tariff, the electrical backup is subordinate to the supplier’s power tariff and the comfort temperature may only be reached at night. If no particular contract is concluded, the comfort temperature can be reached at any time, including during the day The production of DHW takes priority over heating; nevertheless the production of DHW is controlled by cycles that control the times assigned to the heating and the production of DHW in the event of simultaneous demand. A DHW “ boost” function is available on the front of the user interface (see ref. 1, fig. 39, p 31). This DHW boost enables the DHW to be heated to the comfort temperature at any time during the day. The boost function is cancelled automatically when the demand for hot water has been met. If the heating installation is equipped with a DHW circulation pump, the pump’s operation during DHW cycles can be parametered. Anti-legionella cycles can be programmed. Installation and operating manual “1350-EN” 13 Heat pump, Split, single service Ev Dt Cn Cp PAC 1 kW COP 4 4 kW 20 °C Electrical energy consumed Energy from the air Heat produced Heat produced Figure 9 - Heat pump operating principle PAC - Heat pump Ev - Evaporator Cp - Compressor Cn - Condenser Dt - Expansion valve

Regulation installation and

maintenance conditions The appliance must be installed and the maintained by an approved professional in accordance with the prevailing regulations and code of practice, in particular: The legislation on the handling of refrigerants. 2.2 Unpacking and reservations 2.2.1 Receipt Carefully check, in the carrier’s presence, the general appearance of the appliances and check that the outside unit is not laid on its side or back. In the case of any dispute, state any appropriate reservations to the carrier in writing within 48 hours and send a copy of this letter to the After-Sales service. 2.2.2 Handling The outside unit should not be laid on its side or back during transport. Laying the unit down during transport is likely to damage the internal tubes and the compressor suspensions. Any damage caused by transportation of the unit lying down is not covered by the warranty. If necessary the outside unit may be tilted only during manual handling (to go through a door or use a staircase). This operation must be conducted very carefully and the appliance must be immediately restored to upright position. 2.2.3 Accessories provided Accessories provided with the outside unit (figure 10). Accessories provided with the hydraulic module (figure 11) 2.3 Installation position The choice of the position for installation is particularly important insofar as any later movement is a delicate operation requiring the intervention of a qualified person. Choose the site of the outside unit and the hydraulic module after discussion with the customer. Observe the maximum and minimum distances between the hydraulic module and the outside unit (Figure 13); the guarantee of the performances and the system’s service life depend on this. 2.4 Installation of the outside unit 2.4.1 Installation precautions  The outside unit must only be installed outside (outdoors). If a shelter is required, it must have broad openings on the 4 walls and observe the installation clearances (fig. 12). • Choose a site that is preferably sunny and sheltered from strong cold predominant winds (mistral, tramontana, etc…). • The unit must be easily accessible for future installation and maintenance work (fig. 12). • Ensure that it is possible to make the connections to the hydraulic module easily. 14 Installation and operating manual “1350-EN” Heat pump, Split, single service 1 3 2 4 Figure 10 - Accessories provided with the outside unit 8 5 6 7 Figure 11 - Accessories provided with the hydraulic module 1 Elbow For draining away the condensates 2 Plug (x 2) (Depending on the model) 3 Flexible i n s u l a t i o n plate For filling the empty space at the input to the interconnection cable 4 Hex / Allen key To open the valves 5 Bracket To secure the hydraulic model 6 Outdoor sensor To monitor the outside temp 7 1/2" - 5/8" and/or 1/4" - 3/8" adapter To connect the flared connection and the hydraulic model 8 Nut (1/2" and/or) 1/4"

Installation and operating manual “1350-EN”

15 Heat pump, Split, single service AIR 100 mm 100 mm 600 mm 100 à 300 mm 300 mm 300 mm 250 mm For access 250 mm For access 250 mm For access AIR AIR AIR minimum 600 mm AIR Figure 12 - Minimum installation clearances around outside unit (All models) • The outside unit is able to withstand bad weather but avoid installing in a position where it is likely to be exposed to significant dirt or flowing water (under a defective gutter for example). • Water may drain away from the outside unit when it is operating. You can let this defrosted water run off over a gravel or sand bed or a concrete slab with a diamond point and a sinkhole in the ground. If the installation is in an area where the temperature can be lower than 0°C for a long period, check that the presence of ice does not present any danger. A drainage pipe can also be connected to outside unit (see § 2.4.3, page 16). • Nothing should obstruct the air circulation through the evaporator and from the fan (fig. 12). • Keep the outside unit away from heat sources and inflammable products. • Make sure the appliance not disturb the surrounding area or users (noise level, draught generated, low temperature of the air being blown out, with the risk of freezing plants in its path). The surface receiving the outside unit must be able generally to support its weight; provide a solid fixing and do not transmit any vibration to the dwelling.

Anti-vibratory blocks are available, please consult

your retailer (Atlantic). 2.4.2 Outside unit positioning The outside unit must be raised at least 50mm above the ground. In snowy areas, this height must be increased (figure 14) Fasten the outside unit by means of screws and rubber tightening or toothed lock washers to avoid their coming loose. 2.4.3 Condensate drain hose (see figure 14). If the use of a discharge pipe is imperative: Use the elbow provided (C) to connect a 16mm-diameter hose for draining away the condensate. Use the stopper or stoppers provided (B) to block the opening of the condensate tank. Allow for the condensate to flow away under the force of gravity (waste water, rain water, gravel bed).  If the installation is made in an area where the temperature can be lower than 0°C for a long period, provide the drain pipe with a trace resistance to avoid it icing up. The trace resistance must heat not only the pipe but also the bottom of the appliance’s condensate collection tank. 16 Installation and operating manual “1350-EN” Heat pump, Split, single service PAC Unité extérieure PAC Module hydraulique D L mini 5 m Figure 13 - Pipe diameters (in inches) and permissible lengths (in metres) Heat pump Gas and fluid conduits model Gas Fluid M i n i m u m length (L) *Maximum length (L) **Maxi level difference (D) 050 065 1/2" ¼" 0 10 15 080 5/8" ¼" 5 15 20 095 128 155 5/8" 3/8" 5 20 30 * : Without additional charge of R410A ** : Taking into account the possible additional load of refrigeration fluid R410A (see § 2.7.3, page 22). S B C B H > 50 mm * (Ø 12 mm) (Ø 10 mm) Depending on the model Depending on the model * In regions subject to frequent snow, (H) must be greater than the average snow layer . 4 holes 4 holes Figure 14 - Positioning of the outside unit, draining away the condensate

Installing the hydraulic module

2.5.1 Installation precautions • The room in which the appliance operates must comply with the prevailing regulations. • To facilitate maintenance and to allow access to the various components, we recommend that you provide sufficient space all around the hydraulic module (figure 15). • Be careful not to bring inflammable gas near to the heat pump during its installation, in particular when it requires brazing The appliances are not fireproof and should not therefore be installed in a potentially explosive atmosphere. 2.5.2 Positioning the hydraulic module - 1, 2, 3 : Remove the front panel (2 screws A, figure 16) - 4, 5 : Remove the sides (4 screws B, figure 17). - Fix the support solidly (3 screws and plugs) to a flat, hard-wearing wall (not a light partition) ensuring that it is correctly levelled. - Hook the appliance onto its support. - Refit the sides. - Refit the front facing. Installation and operating manual “1350-EN” 17 Heat pump, Split, single service 200 mm 1000 mm 150 mm 150 mm Figure 15 - Minimum installation clearances around the hydraulic module and distances to the combustible partitions 1 3 2 A Figure 16 - Removing the front facing 90 mm (S) 505 mm 240 mm 150 mm 200 mm 305 mm Figure 17 - Removing the sides and fixing the support (S) B B (S) 5 5 4

 This appliance uses refrigerant R410A.

Comply with the legislation for handling refrigeration fluids. 2.6.1 Rules and precautions • After every intervention on the refrigeration circuit and before final connection, take care to replace the plugs in order to avoid any pollution from the refrigeration circuit. • Tools Set of manometers with hoses exclusively reserved for HFCs (Hydrofluorocarbons). Vacuum pump specially for HFCs. Provision on using tools that have been in contact with HCFCs (R22 for example) or CFCs. Use of a traditional vacuum pump is authorized if, and only if, it is fitted with a non-return valve on the suction side. The manufacturer declines any liability with regard to the guarantee if the above instructions are not observed. • Flared connections  Lubrication with mineral oil (for R12, R22) is forbidden. - Only lubricate with polyolester refrigeration oil (POE). If POE is not available, fit without lubrication. • Brazing on the refrigeration circuit (if necessary) - Silver brazing (40% minimum recommended). - Brazing only under dry nitrogen internal flux. • To eliminate any filings in the pipes, use dry nitrogen to avoid introducing any humidity that may adversely affect the appliances operation. In general, take every precaution to avoid humidity penetrating into the appliance. Proceed to insulate the gas and liquid pipes to avoid any condensation. Use insulating sleeves resistant to temperatures over 120°C. In addition if the humidity level in the areas where the refrigeration pipes pass risks exceeding 70%, protect the pipes with insulating sleeves. Use a sleeve thicker than 15mm if the humidity reaches 80%, and a sleeve thicker than 20mm if the humidity exceeds 80%. If the recommended thicknesses are not observed under the conditions described above, condensation will form on the surface of the insulation material. Lastly, take care to use insulating sleeves whose thermal conductivity is 0.045 W/mK or less when the temperature is 20°C. The insulation must be impermeable to resist the passage of steam during the defrosting cycles (fibreglass wool is prohibited). 2.6.2 Refrigeration connections The outside unit must be connected to the hydraulic module with copper pipes and connections (refrigeration quality), insulated separately. Comply with the pipe diameters and the permitted pipe lengths (figure 13). The minimum length of the refrigeration connections is 5m for correct operation. The appliance will be excluded from guarantee if it is used with refrigeration connections less than 5m long. Manipulate the pipes and take them through walls with protective plugs in place. If the distance between the outside unit and the hydraulic module exceeds the length of the maximum conduits indicated in the table, an additional charge of R410A must be loaded. The quantity of R410A added must be adapted to the length of the refrigeration circuit in order to the heat pump’s performance without damaging the compressor (figure 23). 2.6.3 Creating the flarings - Cut the pipe to an appropriate length with a pipe-cutter without deforming it. - Carefully deburr it, holding the pipe towards the bottom to avoid introducing filings into the pipe. - Remove the flared connection nut situated on the valve to be connected and slip the pipe into the nut. - Proceed to flare, letting the pipe overflow the flaring tool. - After flaring, check the condition of the working radius (L). This must not show any scratch or trace of any fracturing. Also check the dimension (B). 18 Installation and operating manual “1350-EN” Heat pump, Split, single service B L C L B 0 - 0,4 C 6,35 (1/4”) 15,88 (5/8”) 1,8 2 → 2,9 3,1 → 9,1 19,7 17 29 9,52 (3/8”) 2,5 2,7 → 13,2 22 12,7 (1/2”) 2,6 2,9 → 16,6 26 Ø Hose Dimensions in mm Flaring tool Hose Flare nut Figure 18 - Flaring for flare connections

2.6.4 Shaping the refrigeration pipes

The refrigeration pipes must be shaped only on a bending machine or with a bending spring in order to avoid any risk of crushing or breaking them.  Warning • Remove the insulation material locally to bend the pipes. • Do not bend the copper to any angle over 90°. • Never bend pipes more than 3 times in the same position otherwise traces of fracturing may appear (from strain-hardening the metal). 2.6.5 Connecting the flared connections  The small pipe must always be connected before the large one.  Take particular care positioning the tube opposite its connector so as not to risk damaging the threads. A carefully aligned connector can be fitted easily by hand without much force being required.  The refrigeration circuit is very sensitive to dust and humidity: check that the area around the connection is clean and dry before removing the plugs protecting the refrigeration connectors. Installation and operating manual “1350-EN” 19 Heat pump, Split, single service Liquid valve Flare nut Liquid refrigeration connexion Diameter D2 “Gas” refrigeration connexion D1 Diameter Gas valve Flare nut Flare nut Flare nut Adapter R2, depending on the model Adapter R1, depending on the model Outside unit Hydraulic module Figure 19 - Connecting the flared connections Outside unit connections Diameter of refrigeration connections Male-female adapter (reduction) Hydraulic module connections Model 050 Model 065 Gas 1/2" (D1) 1/2" (R1) 1/2"-5/8" 5/8" Fluid ¼" (D2) ¼" (R2) ¼"-3/8" 3/8" Model 080 Gas 5/8" (D1) 5/8" None 5/8" Fluid ¼" (D2) ¼" (R2) ¼"-3/8" 3/8" Model 095 Model 128 Model 155 Gas 5/8" (D1) 5/8" None 5/8" Fluid 3/8" (D2) 3/8" None 3/8"

- Depending on the case, connect an adapter

(reducer) ¼’’- 3/8’’ or 1/2’’- 5/8’’. (see figure 19). - Remove the plugs from the pipes and the refrigeration connections. - Present the pipe to the flared connector and screw the nut by hand while holding the connector with a wrench until contact. - Comply with the recommended tightening torques. (see figure 21). 20 Installation and operating manual “1350-EN” Heat pump, Split, single service Coat the flared surface with POE refrigeration oil Do not use mineral oil. Figure 20 - Prevention of gas leaks Holding wrench Torque wrench Designation Flare nut 6,35 mm (1/4”) Flare nut 9,52 mm (3/8”) Flare nut 12,7 mm (1/2”) Flare nut 15,88 mm (5/8”) Plug (A) 3/8”, 1/4” Plug (A) 1/2” Plug (B) 3/8”, 5/8” Tightening torque 14 to 18 Nm 33 to 42 Nm 50 to 62 Nm 63 to 77 Nm 20 to 25 Nm 25 to 30 Nm 10 to 12 Nm Plug (A) 5/8” 30 to 35 Nm Plug (B) 1/2”, 1/4” 12,5 to 16 Nm Figure 21 - Tightening torque

Filling the installation with gas

 This operation is reserved for installers familiar with the legislation for handling refrigeration fluids.  Creating a vacuum with a vacuum pump is essential.  Never use equipment used beforehand with any refrigerant other than a HFC. 2.7.1 Creating a vacuum and filling the refrigeration connections with gas (see figure 22). - Remove the protective plugs (B) from the charging hole (Schrader) in the gas valve (large diameter). - Connect the blue hose (on the side with a valve pusher in good condition) from the set of manometers (manifold). - Connect the yellow hose to a vacuum pump and open the blue valve on the set of manometers. - Create a vacuum until the residual pressure in the circuit falls below 0.01 bar. - Let the pump continue to operate for another 15 minutes after reaching the vacuum. - Close the blue valve on the set of manometers and then stop the vacuum pump w ithout disconnecting any of the hoses in place. - Wait 10 minutes. If the pressure rises during this 10-minute period, there is a leak in the circuit. Trace it and repair it: then start again. When the pressure has remained stable for 10 minutes after the vacuum pump stops, the circuit is considered to be gas-tight. - Remove the access plugs (A) from the valve controls.  If an additional charge is requires, add the additional charge before filling the hydraulic module with gas. Please refer to the section (“Additional charge”, page 22). - First of all fully open the small valve and then the large one using a hex key (counterclockwise direction) without forcing excessively against the stop. - Remove the blue hose rapidly. - Refit the 2 plugs and tighten them to the recommended tightening torque (see figure 21). The outside unit does not contain any additional refrigerant, enabling the installation to be purged. Flushing is strictly forbidden. 2.7.2 Sealing test Once the refrigeration circuit has been gassed as described above, check that all the refrigeration connectors are gas-tight: 6 connectors for models 050 and 065, 5 connectors for model 080 and 4 connectors for models 095, 128 and 155. The sealing test must be performed with an approved gas detector. If the flarings have been made correctly, there should be no leaks. If there is a leak, make the connection again. Installation and operating manual “1350-EN” 21 Heat pump, Split, single service Figure 22 - Extraction under vacuum and gassing Lo Hi Manometer kit (manifold) Vacuum pump Service hose Low pressure High pressure Gas valve Large diameter Vacuum meter Refrigeration connexion Plug (A) Hex / Allen key of 4 mm 3-way valve Load orifice Plug (B) Service hose (blue) fitted with valve push-button

2.7.3 Additional charge

The charge in the outside units corresponds to the maximum distances between the outside unit and the hydraulic module defined in Figure 13. If the distances are greater, an additional charge of R410A is required. The additional charge depends on the distance between the outside unit and the hydraulic module for each type of appliance (Fig. 23) The additional charge of R410A must necessarily be made by an approved refrigeration engineer. • Example for a heat pump model 155 An outside unit 32m away from the hydraulic module will require an additional charge of: Additional charge = (32 - 20) x 40 = 480 g The charge must be introduced after creating the vacuum and before the hydraulic module is filled with gas, as follows: - Disconnect the vacuum pump (yellow hose) and connect a bottle of R410A instead in the fluid extraction position. - Open the bottle’s valve. - Bleed the yellow hose by loosening it slightly on the manifold side. - Place the bottle on scales with a minimum accuracy of 10g. Note the weight. - Carefully open the blue valve slightly and check the value shown on the scales. - As soon as the value displayed has dropped by the value for the calculated additional charge, close the bottle and disconnect it. - Then rapidly disconnect the hose connected to the appliance. - Proceed to fill the hydraulic module with gas.  Warning • Only use R410A! • Only use tools suitable for R410A (set of manometers). • Always charge in the fluid phase. • Never exceed the length or the maximum difference in level. 22 Installation and operating manual “1350-EN” Heat pump, Split, single service Model 050 - Model 065 20 g of R410A per additional meter Length of the connections 10 m 15 m 20 m Additional charge none 100 g 200 g Model 080 20 g of R410A per additional meter Length of the connections 15 m 20 m 25 m 30 m Additional charge none 100 g 200 g 300 g Model 095 40 g of R410A per additional meter Length of the connections 15 m 20 m 30 m 40 m Additional charge none 200 g 600 g 1000 g Model 128 50 g of R410A per additional meter Length of the connections 20 m 30 m 40 m Additional charge none 500 g 1000 g Model 155 40 g of R410A per additional meter Length of the connections 20 m 30 m 40 m Additional charge none 400 g 800 g Figure 23 - Additional charge R410A Gas Fluid Figure 24 - Gas bottle R410A

the heating circuit hydraulically

2.8.1 General The connection must comply with good trade practice according to local building regulations. The heating circulating pump is built into the hydraulic module. Connect the central heating pipes to the hydraulic module, complying with the direction of circulation. The diameter of the pipes between the hydraulic module and the heating collector must be at least 1 inch (24x36mm). Calculate the diameter of the pipes according to the flow rates and the lengths of the hydraulic systems. Use union connectors to facilitate removing the hydraulic module. Preferentially use connection hoses to avoid transmitting noise and vibrations to the building. Connect the drains from the drain valve and the safety valve to the main sewer system. Reminder: Seal everything when fitting in accordance with prevailing trade practice for plumbing work: - Use suitable seals (fibre seals, o-rings). - Use Teflon tape or hemp. - Use sealing paste (synthetic depending on the case). The use of glycol is not necessary. If you are using a glycol/water mix, provide for an annual check on the quantity of glycol. In certain installations, the presence of different metals can cause corrosion problems; the formation of metal particles and sludge in the hydraulic circuit is then seen. In this case, it is advisable to use a corrosion inhibitor in the proportions indicated by its manufacturer. It is also necessary to ensure that the treated water does not become aggressive. 2.8.2 Rinsing out the installation Before connecting the hydraulic module to the installation, rinse out the heating system correctly to eliminate any particles that may affect the appliance’s correct operation. Do not use solvents or aromatic hydrocarbons (petrol, paraffin, etc.). In the case of an old installation, provide a sufficiently large decanting pot with a drain on the return from the boiler and at the lowest point in the system in order to collect and remove the impurities. Add an alkaline product to the water and a dispersant. Rinse the installation several times before filling it definitively. 2.8.3 Filling and purging the installation Check the pipe fixings, the tightness of the connectors and the stability of the hydraulic module. Check the direction in which the water is circulating and that all the valves open. Proceed to fill the installation. Do not operate the circulating pump while filling. Open all the drain valves in the installation and the bleed valve for the hydraulic module to remove the air contained in the conduits. Close the drain and bleed valves and add water until the pressure in the hydraulic circuit reaches 1.5 bar. If the pressure is lower than 0,5 bar, the Heat Pump stops and posts error 369. Check that the hydraulic circuit has been purged correctly. Check that there are no leaks and that the circulating pumps are not seized (if need be, release them). After the “Start-up” stage (see p. 30), once the machine has started, purge the hydraulic module again (2 litres of water). Installation and operating manual “1350-EN” 23 Heat pump, Split, single service Figure 25 - Release of the circulation pump II S 5 S 6 S 8 S 10 III S 13 S 16 Figure 26 - Recommended circulation speed (for radiator) (P) Figure 27 - (P) Hydraulic module bleeder valve II 050 065 080 095 III 128 155

Ensure that the general electrical power supply has

been cut off before starting any repair work. 2.9.1 Characteristic of the electrical supply The electrical installation must be conducted in accordance with the prevailing regulations. The electrical connections must only be made when all the other fitting operations have been completed (fixing, assembly, etc.).  Warning The contract concluded with the energy provider must be sufficient not only to cover the heat pump’s power but also the combined sum of all the appliances likely to be operating at the same time. When the voltage is too low, check with your energy provider the value subscribed to in your contract. Never use a socket for the power supply. The heat pump must be supplied with power by special protected leads from the electric panel via 2-pole circuit breakers specially dedicated to the heat pump: Curve D for the outside unit, curve C for the electric heating and domestic water back-ups (see tables on page 25). The electrical installation must necessarily be equipped with a 30mA differential protection. Use a flexible cable of H07 RN-F type. This appliance is intended to operate under a nominal voltage of 230V +/- 10%, 50 Hz. 2.9.2 General remarks on electrical connections Tighten the screws on the terminal blocks perfectly. Unsufficient tightening can cause overheating, leading to breakdown or even a fire. Use cable clamps to prevent the conductors from being disconnected accidentally. Connection to Earth and Earth bonding continuity are essential. • Connecting to screw terminals Rigid wires (A, fig. 28). Rigid wires are always preferable for fixed installations, particularly in a building. - Always select a wire that complies with the prevailing standards. - Strip away around 25 mm from the end of the wire. - With round end pliers, form a loop with a diameter corresponding to the tightening screws on the terminal. - Tighten the terminal screw firmly onto the loop created. Flexible wires (B, fig. 28) H07RNF type flexible wire can be used with certain precautions: - Strip away around 10mm from the end of the wire. - With tightening pliers, fit a round tag with a diameter corresponding to the terminal screw’s diameter on the end of the wire. - Tighten the tag firmly onto the terminal with a screwdriver. - We strongly advise against using flexible wires without round tags. - Always protect the cables when passing them through cable clamps with PVC protective conduit 0.5 to 1mm thick. • Connecting to regulation cards - Remove the corresponding connector and make the connection. • Connecting to spring terminals (fig. 30) Rigid wires - Strip away around 10mm from the end of the wire. - Slide the wire into the opening provided for this purpose. - Push the spring with a screwdriver so that the wire enters the cage. - Remove the screwdriver and then check that the wire is jammed in the cage by pulling on it. Flexible wires - Use the ends and proceed as before. 24 Installation and operating manual “1350-EN” Heat pump, Split, single service 25 mm 10 mm A : Rigid wires B : Flexible wires Loop Round terminal tightened Special screw and washer Terminal block Figure 28 - Outside unit terminal block Figure 29 - Regulation connector Figure 30 - Hydraulic module terminal block

Installation and operating manual “1350-EN”

25 Heat pump, Split, single service Interconnection between the external unit and the hydraulic module Phase, Neutral, Earth, Communication bus Cable 4 x 1.5 mm² General electrical supply Phase, Neutral, Earth Cable 3 x 1.5 to 4 mm² (depending on heat pump power) Power supply to the electrical back-ups Phase, Neutral, Earth Cable 3 x 2.5 to 6 mm² (depending on heat pump power) Room thermostat (option) cable 2 x 0.5 mm² Outdoor sensor Cable 2 x 0.75 mm² Electric panel Remote control (option) : cable 3 x 0.5 mm² Figure 31 - Overall layout of the electrical connections for a simple installation (1 heating circuit) 2.9.3 Overview of all the electrical connections The wiring diagram for the hydraulic module is shown in detail on page 56. 2.9.4 Cable section and protection rating The cable sections are given for information purposes only and do not exempt the installer from checking that these sections correspond to the requirements and comply with the prevailing standards. • Power supply to outside unit Heat pump Electricity supply 230 V - 50 Hz Model Power absorbed Cable connection (Phase, Neutral, Earth) Curve D circuit breaker size (A) 050, 065 1860 W 3 x 1,5 mm² 16 080 2210 W 3 x 2,5 mm² 16 095 2680 W 3 x 2,5 mm² 20 128 3770 W 3 x 4 mm² 25 155 4700 W 3 x 4 mm² 32 Interconnection between the outside unit and the hydraulic module. The hydraulic module is powered by the outside unit by means of a 4 x 1.5 mm² cable (Phase, Neutral, Earth, Communication bus). • Power supply to the electrical back-ups The hydraulic module contains two stages of electrical back-ups installed in a heat exchange cylinder. Heat pump Electric back-ups Power supply to the electrical back-ups Model Power Nominal intensity Cable connection (Phase, Neutral, Earth) Curve C circuit breaker size (A) 050, 065, 080 2 x 1,5 kW 13 A 3 x 2,5 mm² 16 095, 128, 155 2 x 3 kW 26,1 A 3 x 4 mm² 3 x 6 mm² 32 Outdoor sensor, ambient air sensor, remote control For the room thermostat, use a 2 x 0.5 mm² telephone type cable. For the remote control, use a 3 x 0.5 mm² telephone type cable. For the outdoor sensor, use a 2 x 0.75 mm² cable.

2.9.5 Electrical connections on outside unit

side Access to the connection terminals • Model 050, 065, 080 - Remove the cap (figure 32). • Model 095, 128, 155 - Remove the front panel - Remove the cap (figure 34). Make the connections in accordance with the diagram(s) Fig. 33. Use cable clamps to prevent the conductors from being disconnected accidentally. Fill in the space where the cables enter the outside unit with the insulating plate (fig. 35). 26 Installation and operating manual “1350-EN” Heat pump, Split, single service Remove the cap (1 screw) Figure 32 - Access to outside unit’s terminal block (model 050, 065, 080) General electrical supply Terminal block Interconnection between the external unit and the hydraulic module Figure 33 - Connections to outside unit’s terminal block Remove the front panel (2 screws) Remove the front panel (2 screws) Remove the cap (1 screw) Figure 34 - Access to outside unit’s terminal block (model 095, 128, 155)

2.9.6 Electrical connections on the hydraulic

module side Access to the connection terminals - Remove the front panel (2 screws) (fig. 16, p. 17) - Remove the cover of the electric box. - Make the connections in accordance with the diagram(s) Fig. 37. Do not place the sensor lines and the sector supply lines in parallel in order to avoid causing inadvertent interference due to voltage points in the sector supply. Ensure that all the electrical cables are housed in the spaces provided for this purpose inside the lifting handles. Installation and operating manual “1350-EN” 27 Heat pump, Split, single service Release Cable clamp Cable clamp Flexible insulation plate Cables (supply and interconnection) Cables Gas valve Figure 35 - Finalisation of connection to outside unit Transformer Power card Interface card Heat pump regulator Terminal blocks Power relay Cable grommet (Power) Cable grommet (low voltage) Safety thermostat Figure 36 - Access to hydraulic model electric box and description

• Interconnection between the outside unit and

the hydraulic module Comply with the correspondence between the markings on the hydraulic module’s terminals and those on the outside unit when connecting the interconnection cables. A connection error could cause the destruction of one or other of the units. • Electric back-ups If the heat pump is not installed with a boiler connection: Connect the electrical supply for the back-ups (terminals 9, 10 and 11) to the electrical panel. • Boiler connection - Please refer to the instructions supplied with the boiler connection kit. - Please refer to the instructions supplied with the boiler. • Domectic hot water tank If the installation is fitted with a DHW tank with electrical back-up heating: Please refer to the instructions supplied with the DWH kit. Please refer to the instructions supplied with the DWH tank. Second heating circuit Please refer to the instructions supplied with the second circuit kit. • Contract with the power provider The heat pump’s operation can be controlled to suit special contracts (e.g. off-peak, day/night). In particular, domestic hot water (DHW) at Comfort temperature will be produced during the off-peak hours when electricity is cheaper. - Connect the “Power Provider” contact to input EX5 or EX4. - Set the parameter (1620) to “Off-peak hours”. • 230V on input EX5 = “Peak hours” information activated. • Power limitation or EJP (peak day removal) Power limitation is intended to reduce electrical consumption when this is too high compared to the contract with the power provider. - Connect the power limiting device to input EX4 (E6), the back-ups for the heat pump and the DHW stop in the event of over-consumption by the dwelling. 230 V on input EX4 (E6) = power limitation in progress. (Operating line 2920) 28 Installation and operating manual “1350-EN” Heat pump, Split, single service Rp ECS 1 2 3 4 5 6 7 8 9 10 11 12131415161718 Rp 1 Rp 2 L N 19 L N L N L N N L Interconnection between the outside unit and the hydraulic module Electricity supply 230 V Outside unit Hydraulic module DHW Resistance of the back-up unit 1 Resistance of the back-up unit 2 Boiler room thermostat terminals 3 way distribution valve (deviation boiler) Opening signal (230V) Power supply to the electrical back-ups Power supply to the electrical back-ups Connexion to the DHW tank resistance HP and electric back-ups HP and boiler connection Figure 37 - Connection to terminal block and power relays

• External faults the heat pump

Any component of carryforward of information (thermostat, pressure switch, etc.) may signal an external problem and stop the heat pump. E.g.: A thermostat on the heating floor will stop the heat pump if the temperature in the floor is too high - Connect the safety component to input EX6. • 230 V on input EX6 = stoppage of heat pump (the system displays Error 369). 2.10 Outdoor sensor The outdoor sensor is required for the heat pump to operate correctly. Consult the fitting instructions on the sensor’s packaging. Place the sensor on the coldest part, generally the northern or north-eastern side. In any case, it must not be exposed to the morning sun. It must be installed so as to be easily accessible but at least 2.5m from the floor. It is essential that it avoid any sources of heat such as flues, the upper parts of doors and windows, proximity to extraction vents, the underneath of balconies and under-eave areas which would isolate the sensor from variations in the outside air temperature. - Connect the outdoor sensor to the M and B9 terminals on the heat pump control board (fig. 38, p. 29). 2.11 Room thermostat and/or remote control The room thermostat (remote control) is optional. Consult the fitting instructions on the sensor’s packaging. The sensor must be installed in the living room area on a very uncluttered wall, 1.5m above the floor. Avoid direct sources of heat (chimney/flue, television, cooking hobs), draughty areas (ventilation, door, etc.). Air leaks in the seals in the constructions are often translated into cold air blowing through the electrical conduits. Lag the electrical conduits if there is a cold draught on the back of the IR sensor. Installation and operating manual “1350-EN” 29 Heat pump, Split, single service 2 1 M B9 CL- CL+ 3 2 CL- CL+ EX6 EX5 EX4 5 6 2 1 1 CL- CL+ G+ Outdoor sensor Room thermostat circuit 1 or External fault Tariffs, day / night, Power shedding or EJP (peak day removal) peak times/off-peak times External component contact* (faults, load shedder, power meter) * If the control component does not provide a spare potential contact, the contact must be relayed to create equivalent wiring. In all cases, please refer to the instruction manuals for the external components (load limiting device, power meters) to create the wiring. Remote control Room thermostat circuit 2 Figure 38 - Connections to the heat pump regulator (accessories and options)

• Installation equipped with two room thermostats

- Connect each of the sensors to one of the CL+ or CL- terminals on the heat pump control board (fig. 38, p. 29) using the connector supplied. • Installation equipped with a room thermostat and a remote control - Connect the sensor to one of the CL+ or CL- terminals on the heat pump control board (fig. 38, p. 29). - Connect the remote control to the other CL+, CL- terminals and to G+. 2.12 Start-up - Close the installation’s main circuit breaker. On first commissioning (or in winter), in order to allow the compressor to pre-heat, engage the installation’s main circuit breaker (power supply to the outside unit) some hours before starting up the tests. - Engage the heat pump’s ON/OFF button. When the power is switched on and every time that the ON/OFF button is switched off and then switched on again, the outside unit will take approximately 4 minutes to start up, even if the setting is requesting heating. - Make all the specific adjustments to the setting (configuring the installation). - Press the key - Hold down the key for 3s and select the level of access used with the aid of the knob . - Confirm with the key - Parameter the heat pump’s setting - Consult the settings’ list (page 34). On commissioning (or the case of error 10), the electrical backup heaters are liable to start up even if the outside temperature at the time is above the heaters’ trigger temperature. The regulating system uses an average initial outside temperature of 0°C and requires some time to update this temperature. To mitigate this situation, the sensor must be connected correctly. Re-initialise parameter 8703 (implementation level, consumer diagnostic menu). 2.13 Configuring the room thermostat Room thermostat To configure the room thermostat and connect it to the appropriate heating zone: - Hold down the presence key for more than 3 seconds. The room thermostat displays RU and a number flashes. - Turn the wheel to choose the zone (1, 2).  If the installation is fitted with 2 room thermostats, - First connect one room thermostat and configure it in zone 2 - Then connect the other room thermostat and configure it as default in zone 1. - Hold down the presence key; the room thermostat displays P1 and a flashing number. 1: Automatic recording: a correction of the setting with the button is adopted without any particular confirmation (timeout) or by pressing the regime key. 2: Recording with confirmation: a correction of the setting with the button is not adopted until the regime key is pressed. - Press the presence key again; the room thermostat displays P2 and a flashing number. 0: OFF: all the operating elements are engaged. 1: ON; the following operating elements are locked: Switching over the heating circuit’s operating mode Adjusting the comfort setting Changing the operating level The room thermostat displays OFF for 3 seconds when a locked button is pressed. 2.14 Configuring remote control Remote control During commissioning, after an initialisation period of approx. 3 minutes, the user’s language must be set: Press the key “OK” Choose menu “Bedieneinheit” Choose language (Sprache) Select the language (english, français, nederlands, español, etc) 30 Installation and operating manual “1350-EN” Heat pump, Split, single service OK OK

Installation and operating manual “1350-EN”

31 Heat pump, Split, single service Ref. Function - Definitions 1 Selection of the DHW operating regime (Domestic hot water) - If the installation is fitted with a DHW tank. - ON: Production of DHW according to the time program. - Off: Preparing the domestic hot water for stopping with the anti-frost function active. - Boost: Hold down the DHW key for 3 seconds. Immediate DHW operation after use of the electrical back-ups until the DHW comfort setting has been reached 2 Digital display - Operating control. Readout of the current temperature, of the heating regime and of any faults . - View the settings 3 Exit "ESC" - Quit the menu. 4 Navigation and setting - Selecting the menu. - Setting parameters. - Adjusting the ambient temperature setpoint. 5 Selecting the heating regime - Heating operating according to the heating programme (Summer/winter mode switchover is automatic). - Constant comfort temperature. - Constant reduced temperature. - Stand-by regime with anti-frost protection (Provided that the heat pump's electrical power supply is not interrupted). 6 Information display - Various data (please see page 59). - Reading error codes (please see page 57). - Information concerning maintenance, special regime. 7 Confirm "OK" - Input into the selected menu. - Confirmation of the parameter settings. - Confirmation of the adjustment to the comfort temp. setting. 8 Selecting cooling mode - If the installation is fitted with the cooling kit: - Cooling operating according to the heating programme (Summer/winter mode switchover is automatic). 9 RESET button (Hold down the "RESET" key for 3 seconds). - Reinitialising the parameters and cancelling error messages. Do not use during normal operation. 3 Regulation system 3.1 User interface and remote control (Option) Figure 39 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 13 ON Off

Room thermostat (Option)

3.3 Temperature control The heat pump’s operation is subject to the temperature control. The set temperature for the water in the heating circuit is adjusted according to the outside temperature The temperature control may be chosen automatically by the machine (self-adaptation) or set manually by the installer (Parameters 720, 721 and 726). If there are thermostatic valves on the installation, these must be fully open or adjusted for higher than the normal set temperature. 3.4 Manual adjustment During installation, the temperature control must be parametered according to the heat emitters and the dwelling’s insulation. The temperature control’ curves (Fig. 41) refer to an ambient setting of 20°C. The slope of the temperature control (parameter 720) determines the impact of the variations in the outside temperature on the initial heating temperature variations. The higher the slope, the more a slight reduction in the outside temperature causes a significant increase in the initial water temperature in the heating circuit. The off-set in the temperature control (parameter 721) alters the initial temperature of all the curves, without altering the slope (Fig. 42). The corrective actions in the case of any inconvenience are detailed in the table (Figure 43). 3.5 Self-adaptation When this function is active (parameter 726), the temperature control are automatically adjusted; it is therefore futile to alter the slope or the off-set in the temperature control (parameters 720 and 721). When this function is first activated, the end user may experience some inconvenience for a few days. This period of no more than a week is required by the regulator to determine the slope and off-set in the temperature control. We advise against changing the temperature settings during this period. The following instructions must be observed for the self-adaptation system to operate correctly: - A room thermostat must be connected. - The influence of the ambient temperature" (parameter 750) must be set between 1 and 100%. - Depending on the installation, the room thermostat may have a greater or lesser influence on the temperature control. - The room in which the room thermostat is installed must not contain any thermostatic valves. If this is the case, the valves must be open fully. 32 Installation and operating manual “1350-EN” Heat pump, Split, single service °C 10 12 13 11 Figure 40 - Room thermostat (option) Ref. Function - Definitions 10 Selecting the heating regime - Heating operating according to the heating programme (Summer/winter mode switchover is automatic). - Constant comfort temperature. - Constant reduced temperature. - Stand-by regime with anti-frost protection (Provided that the heat pump's electrical power supply is not interrupted). 11 Digital display - Operating control. Readout of the current temperature, of the heating regime and of any faults . 12 Control knob - Adjusting the ambient temperature setpoint 13 Presence key - Comfort / Reduced switchover

Installation and operating manual “1350-EN”

33 Heat pump, Split, single service 30 40 50 60 70 -20 -15 -10 -5 0 5 10 15 20 20 0,25 0,5 0,75 1 1,25 External temperature (°C) Heating flow temperature (°C) Heating curve slope Low temperature radiator Floor heating system Boiler connexion application Heat pump application only Figure 41 - Heating curve slope (line 720) 40 50 60 70 -20 -15 -10 -5 5 10 -4,5 +4,5 20 0,5 0 10 30 0 30 External temperature (°C) Heating flow temperature (°C) Heating curve slope Curve off-set Figure 42 - Off-set of the heating curve (line 721) Sensations... Corrective actions on the temperature control: ...in mild weather ...in cold weather Curve slope (line ) 720 Curve off-set (line ) 721 and and and and and and and and and No correction No correction No correction No correction No correction No correction OK Cold Cold Cold OK OK Hot Hot Hot OK Hot OK Cold Hot Cold Hot OK Cold Figure 43 - Corrective actions in the case of discomfort

Installation and operating manual “1350-EN”

Heat pump, Split, single service Line Function Setting range or display Setting increment Basic setting Date and time 1 U Hours / minutes 00:00… 23:59 1 2 U Day / Month 01.01… 31.12 1 3 U Year 1900… 2099 1 5 S Start of Summer time (Day / Month) 01.01...31.12 1 25.03 6 S End of Winter time (Day / Month) 01.01...31.12 1 25.10 The change of hour will appear at 3:00 first Sunday after the regulated date User interface 20 U Language English, ... 22 I Info Temporary | Permanent Temporary 26 S Operation locking On | Off Off 27 S Programming locking On | Off Off 28 S Direct setting Saving... ...automatic | ...with confirmation ...with confirmation Hours / minutes Day / Month Year Hours 1...24 h Minutes 0...60 min End user 1 2 3 Time and date User interface CC1 time programme ... Press for 3 seconds OEM Specialist Start-up End user Hours / minutes Day / Month Year Start of Summer time End of Winter time 01.01...31.12 1 2 3 4 5 Date and time User interface CC1 time programme ... Brief press Basic display 3.6 Parametering the setting 3.6.1 General Only the parameters accessible to levels: U End user I Start-up S Specialist Are described in this document. The access levels are specified in the second column of the table by means of the letters U, I and S. The OEM parameters are not described and require a manufacturer’s access code. 3.6.2 Setting parameters - Choose the desired level. - Scroll the menu list. - Choose the desired menu. - Scroll the function lines. - Choose the desired line. - Adjust the parameter - Check the setting by pressing OK - To return the menu, press ESC If no setting is made for 8 minutes, the screen returns automatically to the basic display. 3.6.3 List of function lines (settings, diagnosis, status)

Installation and operating manual “1350-EN”

35 Heat pump, Split, single service 44 I Operation HC2 Jointly with HC1 | Independent Jointly with HC1 This function enables you to choose whether you wish the room thermostat (as an option) to act on both zones or just a single zone. 46 I Operation HCP Jointly with HC1 | Independent Jointly with HC1 70 S Software version Heating time programme, circuit 1 500 U Pre-selection (day / week) Mon-Sun Mon-Fri Sat-Sun Monday Tuesday… Mon-Sun 501 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00 502 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00 503 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- - 504 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 505 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- - 506 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 516 U Standard values, Circuit 1 no, yes no Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating programmes. Your customised settings are therefore lost. Heating time programme, circuit 2 Only with the 2nd circuit kit option 520 U Pre-selection (day / week) Mon-Sun Mon-Fri Sat-Sun Monday Tuesday… Mon-Sun 521 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00 522 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00 523 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- - 524 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 525 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- - 526 U 3rd phase Off (end) 00 : 00… - -:- - 10 mn - -:- - 536 U Standard values, Circuit 2 no, yes no Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating programmes. Your customised settings are therefore lost. Time programme 4 / DHW If the installation is fitted with a DHW tank. (Only with the DWH kit option) 560 U Pre-selection (day / week) Mon-Sun Mon-Fri Sat-Sun Monday Tuesday… Mon-Sun 561 U 1st phase On (start) 00 : 00… - -:- - 10 min 00 : 00 562 U 1st phase Off (end) 00 : 00… - -:- - 10 min 05: 00 563 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- - 564 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 565 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- - 566 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- - Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 576 U Standard values no, yes no Time programme 5 / Cooling If the installation is fitted with the cooling kit (Only with the cooling kit option) 600 U Pre-selection (day / week) Mon-Sun Mon-Fri Sat-Sun Monday Tuesday… Mon-Sun 601 U 1st phase On (start) 00 : 00… - -:- - 10 min 6 : 00 602 U 1st phase Off (end) 00 : 00… - -:- - 10 min 22 : 00 603 U 2nd phase On (start) 00 : 00… - -:- - 10 min - -:- - 604 U 2nd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 605 U 3rd phase On (start) 00 : 00… - -:- - 10 min - -:- - 606 U 3rd phase Off (end) 00 : 00… - -:- - 10 min - -:- - 616 U Standard values no, yes no Yes + OK: The standard values memorised in the regulator replace and cancel the customised heating programmes. Your customised settings are therefore lost. Holidays, heating circuit 1 641 U Preselection Period 1 to 8 Period 1 642 U Date holidays start (Day / Month) 01.01… 31.12 1 643 U Date holidays end (Day / Month) 01.01… 31.12 1 648 U Heating schedule during the holidays Frost protection, Reduced Frost protection Holidays, heating circuit 2 If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option) 651 U Preselection Period 1 to 8 Period 1 652 U Date holidays start (Day / Month) 01.01… 31.12 1 653 U Date holidays end (Day / Month) 01.01… 31.12 1 658 U Heating schedule during the holidays Frost protection, Reduced Frost protection Heating adjustment, circuit 1 710 U Comfort ambient temperature setpoint From reduced temperature to 35°C 0,5 °C 20 °C 712 U Reduced ambient temperature setpoint from frost-free temp… to comfort temperature 0,5 °C 18 °C 714 U Frost-free ambient temperature setpoint from 4°C… to reduced temperature 0,5 °C 8 °C 716 S Maximum comfort setpoint 20 °C… 35 °C 1 °C 28 °C 720 I Heating curve slope (See Figure 41) 0.1... 4 0,02 0.5 721 I Off-set of the heating curve (See Figure 42) -4.50 °C… 4.5 °C 0,5 °C 0 °C 726 S Auto-adaptation of the heating curve (see § 3.3.2) off, on on 730 I Summer/Winter heating limits 8 °C … 30 °C 0,5 °C 18 °C When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating (as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode. Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

37 Heat pump, Split, single service 732 S Limit of daily heating -10 °C … 10 °C 1 °C -3 °C This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons. Increasing the value delays the switchover to summer regime. Decreasing the value advances the switchover to summer regime. This function is only active in automatic mode. 750 I Influence of the ambient temperature 1%... 100% 1% 20% If the installation is fitted with a room thermostat: This function enables you to choose the ambient temperature's influence on the setting. If no value is entered, the setting is made based on the temperature control. If the parameter is set at 100%, the setting is only based on the ambient temperature. 790 S Maximum optimisation on switch-on 0 … 360 min 10 min 120 min 791 Maximum optimisation on switch-off 0 … 360 min 10 120 min 800 S Start of increase in reduced functioning mode - 30 … 10 °C 1 °C --- 801 S End of increase in reduced functioning mode - 30 … 10 °C 1 °C -5 °C 830 S Mixer valve boost 0...50 °C 1 °C 0 832 S Type of servomotor 2-pos, 3-pos 2-pos 833 S Switching differential 2-pos 0 … 20 °C 0,5 °C 2 °C 834 S Servomotor travel time 30 … 873 s 1 s 240 s 850 I Floor controlled drying (fig. 44) off – off: Early interruption of the current programme, programme inactive – Operational heating – Heating ready for occupation – Operational heating + ready heating – Ready heating + operational heating – Manual Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after 25 days. 851 I Manual floor drying setpoint (if line 850 = manual) 0 °C… 95°C 1 °C 25 °C This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The concrete slab-drying programme stops automatically after running for 25 days. 856 I Current drying day 0 ... 32 857 I Terminated drying days 0 ... 32 50 45 40 35 30 20 5 0 25 55 1 1 5 7 X 10 18 25 15 1 Day Operational heating Heating flow temperature °C Heating ready for occupation Operational heating + Heating ready for occupation Figure 44 - Diagram of the concrete slab drying programmes  Please comply with the standards and instructions of the manufacturer of the building! A good performance of this function is only possible with an installation correctly implemented (hydraulic, electricity and adjustments)! This function can be stopped by anticipation when setting the adjustment on “Stop”. Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 900 S Change of regime None, Protection mode, Reduced, Comfort, Automatic 1 Protection mode Operating mode at end of concrete slab drying period Cooling circuit 1 901 U Regime off, Automatic off 902 U Comfort ambient temperature setpoint 17...40 °C 0,5 °C 24 °C 907 U Release 24h/day, Time programme HC, Time programme 5 / Refresh 24h/day 908 I Flow temp setp at OT 25°C 6...35 °C 0,5 °C 20 °C 909 I Flow temp setp at OT 35°C 6...35 °C 0,5 °C 16 °C 912 I Cooling limit at OT - - -, 8...35 °C 0,5 °C 24 °C 913 S Lock time at end of heating - - -, 8...100 1 h 24 918 S Summer comp start at OT 20...50 °C 1 °C 26 °C 919 S Summer comp end at OT 20...50 °C 1 °C 40 °C 920 S Summer comp setp increase - - -, 1...10 °C 1 °C 4 °C 923 S Flow temp setp min OT 25°C 6...35 °C 0,5 °C 18 °C 924 S Flow temp setp min OT 35°C 6...35 °C 0,5 °C 18 °C 928 I Influence of the ambient temperature - - -, 1...100 % 1 % 80 % If the installation is fitted with an room sensor: This function enables you to choose the ambient temperature's influence on the setting. If no value is entered, the setting is made based on the temperature control. If the parameter is set at 100%, the setting is only based on the ambient temperature. 932 S Room temp limitation - - -, 0,5...4 0,5 °C 0,5 °C 938 S Mixing valve decrease 0...20 °C 1 °C 0 °C 939 S Type of servomotor 2-pos, 3-pos 3-pos 940 S Switching differential 2-pos 0...20 °C 0,5 °C 2,5 °C 941 S Servomotor travel time 30...873 s 1 s 240 s 945 S Mixing valve in heating mode Control, Open Control 946 S Lock time dewpoint limiter - - -, 10...600 min 10 min 60 min 947 S Flow temp setp incr hygro - - -, 1...20 °C 1 °C 10 °C 948 S Flow setp incr start at r.h. 0...100 % 1 % 60 % 950 S Flow temp diff dewpoint ---, 0...5 °C 1 °C 2 °C 963 S With prim contr/system pump No, Yes No* *Basic setting : 1 circuit = No ; 2 circuits = Yes 969 S Change of regime None, off, Automatic off Heating adjustment, Circuit 2 If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option) 1010 U Comfort ambient temperature setpoint From reduced temperature to 35°C 0,5 °C 20 °C 1012 U Reduced ambient temperature setpoint from frost-free temp… to comfort temperature 0,5 °C 18 °C Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

39 Heat pump, Split, single service 1014 U Frost-free ambient temperature setpoint from 4°C… to reduced temperature 0,5 °C 8 °C 1016 S Maximum comfort setpoint 20…35 °C 1 °C 28 °C 1020 I Heating curve slope 0.1... 4 0,02 0.5 1021 I Off-set of the heating curve -4.50 °C… 4.5 °C 0,5 °C 0 °C 1026 S Adaptation of the heating curve (see § 3.3.2) off, ON off 1030 I Summer/Winter heating limits 8 °C … 30 °C 0,5 °C 18 °C When the average of the outside temperatures over the past 24 hours reaches 18°C, the regulator switches off the heating (as an economy measure). During summer mode, the display shows "Eco". This function is only active in automatic mode. 1032 S Limit of daily heating -10 °C … 10 °C 1 °C -3 °C This function enables you partially to offset the automatic summer/winter switchover during the intermediate seasons. Increasing the value delays the switchover to summer regime. Decreasing the value advances the switchover to summer regime. This function is only active in automatic mode. 1050 I Influence of the ambient temperature 1%... 100% 1% 20% If the installation is fitted with a room thermostat: This function enables you to choose the ambient temperature's influence on the setting. If no value is entered, the setting is made based on the temperature control. If the parameter is set at 100%, the setting is only based on the ambient temperature. 1090 S Maximum optimisation on switch-on 0 … 360 min 10 min 120 min 1091 S Maximum optimisation on switch-off 0 … 360 min 10 min 120 min 1100 S Start of increase in reduced functioning mode - 30 … 10 °C, --- °C 1 °C --- 1101 S End of increase in reduced functioning mode - 30 … 10 °C, --- °C 1 °C - 5 °C 1130 S Mixer valve increase 0 … 50 °C 1 °C 0 °C 1132 S Type of servomotor 2-pos, 3-pos 3-pos 1133 S Switching differential 2-pos 0 … 20 °C 0,5 °C 2 °C 1134 S Servomotor travel time 30 … 873 s 1 s 240 s 1150 I Floor controlled drying (fig. 44) off – off: Early interruption of the current programme, programme inactive – Operational heating – Heating ready for occupation – Operational heating + ready heating – Ready heating + operational heating – Manual Manual mode enables you to programme your own concrete slab drying time.The function ends automatically after 25 days. 1151 I Manual floor drying setpoint (if line 850 = manual) 0 °C… 95°C 1 °C 25 °C This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed. The concrete slab-drying programme stops automatically after running for 25 days. 1156 I Current drying day 0 ... 32 1157 I Terminated drying days 0 ... 32 1161 S Excess heat evacuation off, Heating regime, Permanent Permanent Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 1200 S Change of regime None, Protection mode, Reduced, Comfort, Automatic 1 Protection mode Operating mode at end of concrete slab drying period DHW setting (domestic hot water) (Only with the DWH kit option) 1610 U Comfort setting Reduced setting (line 1612)… to 65 °C 1 60 °C The backup electrical system is required to reach this level. 1612 U Reduced setting 8 °C,,,to Comfort setting (line 1610) 1 40 °C 1620 I Release of DHW load 24h/day Heating circuit time programme Programme 4/DHW Off-peak tariff (Off-peak) Programme 4/DHW and Off-peak Programme 4/DHW 24h/day: The temperature of the DHW is constantly maintained at the DHW comfort setting. Heating circuit time programme: The DHW is produced according to the programming for the ambient temperature (with 1 hour in advance when switched on). Programme 4/DHW: The DHW programme is separate form the heating circuit programme. Off-peak tariff*: The electrical backup heating is only authorised to operate during the off-peak period. Programme 4/DHW and Off-peak*: The electrical backup heating is authorised to operate during the comfort period or off peak. * - Connect the "Power Provider" contact to input EX5 or EX4.. (See Figure 38, page 29). In the case of a day /night contract, the electric back-ups for the DHW tank are subject to the power supplier's tariffs. Switching on the electric back-up for the DHW tank is only authorised during off-peak hours. 1640 I Anti-legionella function off, Periodic (depending on the line setting 1641) Set day of the week (depending on the line setting 1642) off 1641 I Intervals for the anti-legionella cycles 1 to 7 1 day 7 1642 I Weekday anti-legionella cycle run Monday, Tuesday,... Saturday 1644 I Hour of anti-legionella cycle run --:--, 00 :00… 23 :50 --:-- If no value is entered, no anti-legionella cycle has been run. 1645 I Anti-legionella setting 55 °C… 95 °C 65 °C 1646 I Duration of anti-legionella cycle --:--, 10 min… 360 min 30 1647 I Circulating pump anti-legionella cycle ON, off ON 1660 I Release of circulating pump Programme 3/HCP, Release of DHW, Programme 4/DHW Release of DHW Swimming pool (Only with swimming pool kit option) 2056 U Generator heating setting 8...35 22 Heat pump 2884 I Release el flow below OT Electrical release - start-up with outside temperature -30...30 °C 2 °C Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

41 Heat pump, Split, single service 2920 S With electrical utility lock (EX4) Locked, Released Released Released : HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON Locked : HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON Additional generator (Boiler connection) 3700 S Release under outside temperature --- , -50 … 50 °C 0,5 °C 2 °C 3705 I Time delay on stopping 0 … 120 min 1 min 20 Domestic hot water (DHW) (Only with the DWH kit option) 5020 S Overheight initial setting 0 … 30°C 1 °C 5 °C 5024 S Differential 0 … 20°C 1 °C 7 °C 5030 S Limitation on load duration 10 … 600 min 10 min 90 min 5060 S Electrical resistance regime Replacement, Summer, Always, Cooling regime Replacement 5061 S Release of electrical resistance 24h/day, Release of DHW, Programme 4/DHW Release of DHW Installation configuration 5700 I Pre-setting 1,2,3...12 1 1 This control enables you to choose one of the 8 pre-selected installation configurations. The hydraulic layouts for the various configurations are detailed in the section: "Installation Configurations". – Pre-setting 1 : 1 heating circuit – Pre-setting 2 : 1 heating circuit and DHW tank. – Pre-setting 3 : 2 heating circuits. – Pre-setting 4 : 2 heating circuits and DHW tank. – Pre-setting 5 : Boiler connection and 1 heating circuit. – Pre-setting 6 : Boiler connection and 2 heating circuits – Pre-setting 7 : Boiler connection, 1 heating circuit and DHW tank. – Pre-setting 8 : Boiler connection, 2 heating circuits and DHW tank. – Pre-setting 9 to 12 : Do not use for heat pump model "S". Reserved only for heat pump model "Duo" 5711 S Cooling circuit 1 Off, System with 4 tubes, System with 2 tubes Off 5870 S Combined DHW tank no, yes No 6046 I Function input H2 1 - Operating mode change HCs + DHW 2 - Operating mode change HCs 3 - Operating mode change HC1 4 - Operating mode change HC2 6 - Error/alarm message 9 - Dew point monitoring 16 - Swimming pool release 1 … 16 1 9 6047 I Contact type H2 NC - Normally-closed, NO - Normally-opened NC, NO NO 6100 S Outside temperature sensor correction -3 … 3 °C 0,1 °C 0 °C 6120 S Installation frost-free mode ON, Off ON 6205 S Re-initialise parameters No, yes No 6220 S oftware version (RVS) 0...99 0 Error 6711 U Heat pump Reset No, yes No 6740 S Temperature alarm initiation CC1 ---, 10… 240 min 10 min --- Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 6741 S Temperature alarm initiation CC2 ---, 10… 240 min 10 min --- 6745 S DHW load alarm ---, 1… 48 h 1 h --- 6746 S Temperature alarm initiation Cold 1 ---, 10… 240 min 10 min --- 6800 S History 1 Time, Date, Error code 6802 S History 2 Time, Date, Error code 6804 S History 3 Time, Date, Error code 6806 S History 4 Time, Date, Error code 6808 S History 5 Time, Date, Error code 6810 S History 6 Time, Date, Error code 6812 S History 7 Time, Date, Error code 6814 S History 8 Time, Date, Error code 6816 S History 9 Time, Date, Error code 6818 S History 10 Time, Date, Error code Maintenance / special regime 7070 I Interval time for maintenance HP --- , 1… 240 1 Month --- 7071 I Operating time HP since last maintenance. Reset ? (no, yes) 0… 240 1 Month 0 7072 I Maximum number of starting of the compressor 1, authorized per hour of operation. --- , 0,1 … 12 0,1 --- 7073 I Average number of starts of the compressor per hour of operation, since the 6 last weeks. Reset ? (no, yes) 0 … 12 0 7076 I Maximum discrepancy condens / week --- , 1… 250 1 --- 7077 I Current maximum discrepancy condens / week Reset ? (no, yes) 0… 250 7078 I Minimum discrepancy condens / week --- , 1… 250 1 --- 7079 I Current minimum discrepancy condens / week Reset ? (no, yes) 0… 250 0 7090 I DHW tank period --- , 1… 240 1 Month --- 7091 I DHW tank since maintenance Reset ? (no, yes) 0… 240 0 7092 I Heat pump DHW min load temperature 5… 80 °C 1 5 °C 7141 U Emergency regime Off, ON Off Off: The heat pump does not use the backup electrical heating system or the boiler connection when a fault occurs (error 370) ON: The heat pump uses the backup electrical system or the boiler connection when a fault occurs (error 370). In the "ON" position, the energy costs can be onerous if the error is not eliminated. 7142 S Emergency service operating type Manual, Automatic Manual Manual: Emergency mode is not active when a fault occurs. (Emergency mode = OFF) Automatic: Emergency mode is active when a fault occurs. (Emergency mode = ON) In automatic position, the energy cost can be onerous if the error is not detected and eliminated. 7150 I Outside temperature simulation --- , -50 … 50 °C 0,5 --- 7181 I Contact's telephone 1 0 … 255 7183 I Contact's telephone 2 0 … 255 Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

43 Heat pump, Split, single service Inputs / outputs test 7700 I Relay test No test This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly. – No test _ Everything is on STOP _ Relay output QX23, QX22, QX21 module 1 _ Relay output QX1 to QX6 _ Relay output QX23, QX21, QX22 module 2 _ Relay output QX7 The display shows the “Key” symbol. Pressing the Info button displays “Error 368” Warning: The component being tested is receiving electrical power throughout the test. 7710 I Output (Ux) test --- , 0 … 100 % 1 --- 7711 I Voltage (Ux) value 0 … 10 Volt 0 7720 I Digital outputs test 0 = No test 1 = Everything is on STOP 2 = Digital output DO1 3 = Digital output DO No test 7721 I Digital output DO1 Cooling regime, Heating regime Heating regime 7722 I Digital output DO2 Off, ON ON 7730 I Outside temperature (B9) -50 … 50 °C 0 7820 I Sensor temperature BX1 -28 … 350 °C 0 7823 I Sensor temperature BX4 -28 … 350 °C 0 7824 I Sensor temperature BX5 -28 … 350 °C 0 7830 I Sensor temperature BX21 module 1 -28 … 350 °C 0 7831 I Sensor temperature BX22 module 1 -28 … 350 °C 0 7832 I Sensor temperature BX21 module 2 -28 … 350 °C 0 7833 I Sensor temperature BX22 module 2 -28 … 350 °C 0 7841 I Contact status H1 Open, Closed Open 7846 I Contact status H2 Open, Closed Open 7855 I Contact status H3 Open, Closed Open 7914 I Input EX4 0, 230 V 0 7915 I Input EX5 0, 230 V 0 7916 I Input EX6 0, 230 V 0 Etat 8000 I State heating circuit 1 0 8001 I State heating circuit 2 0 8003 I State DHW 0 8004 I State cooling circuit 1 0 8006 I State heat pump 0 8011 I State swimming pool 0 8022 I State supplementary source 0 8050 I History 1 Time, Date, State code 8052 I History 2 Time, Date, State code 8054 I History 3 Time, Date, State code 8056 I History 4 Time, Date, State code Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 8058 I History 5 Time, Date, State code 8060 I History 6 Time, Date, State code 8062 I History 7 Time, Date, State code 8064 I History 8 Time, Date, State code 8066 I History 9 Time, Date, State code 8068 I History 10 Time, Date, State code Generator diagnosis 8402 I Electrical resistance flow 1 Off, ON Off 8403 I Electrical resistance flow 2 Off, ON Off 8406 I Condenser pump Off, ON Off 8410 U Heat pump return temperature 0 … 140 °C Setpoint (flow) HP 0 … 140 °C 8412 U Heat pump flow temperature 0 … 140 °C Setpoint (flow) HP 0 … 140 °C 8413 U Compressor modulation 0 … 100% 8425 I Condenser temperature difference -50 … 140 °C 8440 I Min forced stop, compressor 1 0 … 255 min 8454 S Locking time Heat Pump Reset ? (no, yes) 0 … 2730 h 8455 S Heat pump stops counter Reset ? (no, yes) 0 … 65535 8456 S Hours run electrical flow Reset ? (no, yes) 0 … 2730 h 8457 S Start counter electrical flow Reset ? (no, yes) 0 … 65535 Diagnostics consumers 8700 U Outside temperature -50 .. 50 °C 8701 U Minimum outside temperature Reset ? (no, yes) -50 .. 50 °C 8702 U Maximum outside temperature Reset ? (no, yes) -50 .. 50 °C 8703 I Attenuated outside temperature Reset ? (no, yes) -50 .. 50 °C This is the average of the outside temperature over a 24-hour period. This value is used for automatic Summer / Winter switchover (line 730) 8704 I Mixed outside temperature -50 .. 50 °C The mixed outside temperature is a combination of the current outside temperature and the average outside temperature calculated by the regulator. This value is used for calculating the initial temperature. 8720 I Ambient relative humidity 0 … 100 % 8721 U Room temperature 0 .. 50 °C 8722 I Dew point 1 0 … 50 °C 8730 I Circulation pump, circuit 1 Off, ON Off 8731 I Mixer valve HC1 open Off, ON Off 8732 I Mixer valve HC1 closed Off, ON Off Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

45 Heat pump, Split, single service 8740 U Room temperature 1 0 … 50 °C 20 °C Ambient temperature setting 1 4 … 35 °C 20 8743 U Flow temperature 1 0 … 140 °C 50 Flow temperature setpoint 1 0 … 140 °C 50 8756 U Cooling flow temperature 1 0 … 140 °C 0 Cooling flow temperature setpoint 1 0 … 140 °C 0 8760 I Circulation pump, circuit 2 Off, ON Off 8761 I Mixer valve HC2 open Off, ON Off 8762 I Mixer valve HC2 closed Off, ON Off 8770 U Room temperature 2 0 … 50 °C 20 Ambient temperature setpoint 2 4 … 35 °C 20 8773 U Flow temperature 2 0 … 140 °C 50 Flow temperature setpoint 2 0 … 140 °C 50 8820 I DHW pump Off, ON Off 8821 I DHW electrical resistance Off, ON Off 8830 U DHW (domestic hot water) temperature 0 … 140 °C DHW temperature setpoint 5 … 80 °C 50 8840 S DHW pump operating times Reset ? (no, yes) 0 … 2730 h 8841 S DHW pump start-ups counter 0 … 2730 h 8842 S DHW electric operating times 0 … 2730 h 8843 DHW electric start-ups counter 0 … 65535 8900 U Swimming pool temperature 0 … 140 °C Swimming pool temperature setpoint 0 … 80 °C 24 8950 I Common flow temperature 0 … 140 °C I Common flow temperature setpoint 0 … 140 °C 0 8957 I Common flow setpoint, refrigeration 0 … 140 °C 9031 I Relay output QX1 Off, ON Off 9032 I Relay output QX2 Off, ON Off 9033 I Relay output QX3 Off, ON Off 9034 I Relay output QX4 Off, ON Off 9035 I Relay output QX5 Off, ON Off 9036 I Relay output QX6 Off, ON Off 9037 I Relay output QX7 Off, ON Off 9050 I Relay output QX21 module 1 Off, ON Off 9051 I Relay output QX22 module 1 Off, ON Off 9052 I Relay output QX23 module 1 Off, ON Off 9053 S Relay output QX21 module 2 Off, ON Off 9054 I Relay output QX22 module 2 Off, ON Off 9055 I Relay output QX23 module 2 Off, ON Off Line Function Setting range or display Setting increment Basic setting

Installation and operating manual “1350-EN”

Heat pump, Split, single service 4 Configuring the installation  Optional DHW kit DHW tank control (with electrical back-up) requires the use of the DWH kit. Warning: The tank must be fitted with an electric back-up, particularly for anti-legionella cycles. Please refer to section (Operating principle, page 13)  Optional 2nd circuit kit The control of 2 heating circuits requires the installation of the 2nd circuit. If the installation consists of radiators (or fan-convectors) and a heated floor, zone 2 will correspond to the radiator (or fan-convectors) zone and zone 1 to the heated floor zone.  Optional boiler connection kit The connection of an oil or gas boiler to the heat pump requires the installation of the boiler connection kit. When a boiler is connected to the heat pump, the heat pump’s electric back-ups must not be connected. It is the boiler that provides the heating back-up on the coldest days. The boiler is controlled by the heat pump. Please refer to the instructions supplied with the boiler connection kit.  Swimming pool kit option Please refer to the instructions supplied with the swimming pool kit. Configuration (Parameter 5700) Type of installation Page Pre-setting 1 1 heating circuit 48 Pre-setting 2 1 heating circuit and DHW tank 49 Pre-setting 3 2 heating circuits 50 Pre-setting 4 2 heating circuits and DHW tank 51 Pre-setting 5 Boiler connection and 1 heating circuit Please refer to the instructions supplied with the boiler connection kit. Pre-setting 6 Boiler connection and 2 heating circuits Pre-setting 7 Boiler connection, 1 heating circuit and DHW tank Pre-setting 8 Boiler connection, 2 heating circuits and DHW tank Pre-setting 9 Do not use for heat pump single service. Reserved only for heat pump 2 services Pre-setting 10 Pre-setting 11 Pre-setting 12  Please consult us regarding any other installation configuration.

Installation and operating manual “1350-EN”

47 Heat pump, Split, single service 4.1 Configuration 1, 2, 3 or 4: heat pumps with electric back-ups DHW tank control (with electrical back-up) requires the use of the DWH kit. The control of 2 heating circuits requires the installation of the 2nd circuit. 4.1.1 Hydraulic connections  In the case of a mixed DHW tank Install the directional valve on the heating circuit (on circuit 2 if it exists).  In the case of 2 heating circuits With the 2nd circuit kit, the hydraulic module’s circulation pump (CC1) must be moved and installed in a box of the 2nd circuit kit (CC1). 4.1.2 Electrical connections • 1 - Power supply to outside unit Please refer to section (Electrical connections on the outside unit side page 26). • 2 - Interconnection between the outside unit and the hydraulic module (See fig. 37, p. 28). • 3 - Power supply to the electrical back-ups: - Connect the electrical supply for the back-ups (terminals 9, 10 and 11) to the electrical panel. (see fig. 37, p. 28). • 4 - Outdoor sensor (see fig. 37, p. 28). • 5 - Air thermostat and/or remote control (Option, See fig. 38, p. 29). • 6 - Contract with the power provider: - Connect the “Power Provider” contact to input EX5 or EX4. (see fig. 38, p. 29)  In the case of a mixed DHW tank Please refer to the instructions supplied with the DWH kit. • 7 - Connect the directional valve to connector QX4, (See fig. 38, p. 29). • 8 - Connect the domestic water sensor to terminal BX1 on the heat pump’s control panel (see fig. 38, p. 29). • 9 - Connect the back-up resistance to terminal 19 (Earth) and relay RP DHW to terminals 2 (L) and 4 (N). (see fig. 37, p. 28) • 10 - Connect the electrical power supply for the domestic water back-up (terminals 17, 18 and 19) to the electric panel. (see fig. 37, p. 28)  In the case of 2 heating circuits Please refer to the instructions supplied with the second circuit kit. 11 - Circulation pump 12 - Circulation pump 13 - Mixer valve 14 - Initial sensor () - Interconnection between RVS and AVS  In the case of a heated floor Heated floor thermal safety fuse • 20 - Thermal safety will stop the heat pump if the temperature in the floor is too high. 4.1.3 Parametering the setting • Adjust the configuration: 1, 2, 3 or 4, Line 5700. • Adjust the DHW programme (Line 1610 to 1661) • 1 heating circuit Adjust the heating curve slope. Line 720 • 2 heating circuits Adjust the heating curve slope. Line 720 (Circuit 1) Line 1020 (Circuit 2) 4.1.4 Special cases Please consult us regarding any other installation configuration  Parameter 5700 Configuration 1 : 1 heating circuit (See Figure page 48) Configuration 2 : 1 heating circuit and DHW tank. (See Figure page 49) Configuration 3 : 2 heating circuits (See Figure page 50) Configuration 4 : 2 heating circuits and DHW tank. (See Figure page 51)

Installation and operating manual “1350-EN”

Heat pump, Split, single service CC SA SE R SP CC SA SE R SP 1 2 3 6 5 4 20 Legend CC - Heating circulation pump R - Radiators (or fan convectors) SA - Room thermostat (option) SE - Outdoor sensor SP - Heated floor thermal safety fuse Configuration 1 : 1 heating circuit.  See detailed instructions on Page 47 Overview of all the electrical connections Overall hydraulic layout

Installation and operating manual “1350-EN”

49 Heat pump, Split, single service M CC VD SA KS SSa SE AE R SP CAR M CC VD SA KS SSa SE AE R SP 1 2 3 4 5 7 8 9 10 6 20 Legend CAR - Non-return valve AE - Electric back-up CC - Heating circulation pump KS - DHW kit R - Radiators (or fan convectors) SA - Room thermostat (option) SE - Outdoor sensor SP - Heated floor thermal safety fuse SSa - DWH sensor VD - Distribution valve Configuration 2 : 1 heating circuit and DHW tank. Overview of all the electrical connections Overall hydraulic layout  See detailed instructions on Page 47

Installation and operating manual “1350-EN”

Heat pump, Split, single service Configuration 3 : 2 heating circuits Circuit 2 Circuit 1 CC2 M VM1 CC1 SA2 SA1 K2c SDp1 SE R SP CAR CAR Circuit 2 Circuit 1 CC2 M VM1 CC1 SA2 SA1 K2c SDp1 SE R SP 1 2 3 4 5 11 12 13 14 5 6 AVS 20 Legend CAR - Non-return valve CC1 - Heating circulation pump, Circuit 1 (Remote heat pump circulation pump) CC2 - Heating circulation pump, Circuit 2 K2c - 2nd circuit kit R - Radiators (or fan convectors) SA1 - Room thermostat, Circuit 1 (option) SA2 - Room thermostat, Circuit 2 (option) SE - Outdoor sensor SDp1 - Flow sensor, Circuit 1 SP - Heated floor thermal safety fuse VM1 - Mixer valve, Circuit 1 Overview of all the electrical connections Overall hydraulic layout  See detailed instructions on Page 47

Installation and operating manual “1350-EN”

51 Heat pump, Split, single service Circuit 2 Circuit 1 M CC2 VD M VM1 CC1 SA2 SA1 K2c SDp1 KS SSa SE AE R SP R CAR CAR Circuit 2 Circuit 1 M CC2 VD M VM1 CC1 SA2 SA1 K2c SDp1 KS SSa SE AE R SP R 1 2 3 4 5 7 8 9 10 6 11 12 13 14 5 AVS 20 Legend AE - Electric back-up CAR - Non-return valve CC1 - Heating circulation pump, Circuit 1 (Remote heat pump circulation pump) CC2 - Heating circulation pump, Circuit 2 KS - DHW kit K2c - 2nd circuit kit R - Radiators (or fan convectors) SA1 - Room thermostat, Circuit 1 (option) SA2 - Room thermostat, Circuit 2 (option) SE - Outdoor sensor SDp1 - Flow sensor, Circuit 1 SSa - DWH sensor SP - Heated floor thermal safety fuse VD - Distribution valve VM1 - Mixer valve, Circuit Configuration 4 2 heating circuits and DHW tank. Overview of all the electrical connections Overall hydraulic layout  See detailed instructions on Page 47

Installation and operating manual “1350-EN”

Heat pump, Split, single service 5 Electrical wiring diagrams Green 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 2 1 2 1 2 1 2 3 4 1 2 3 4 1 2 1 2 1 2 3 1 2 3 CN71 CN73 CN72 CN70 W4 W2 W1 W3 W11 W10 CN40 CN801 W7 W8 W9 CN30 4WV PMV F M S (S) C (T) R (R) C M 2 ( N ) 1 3 L N 15A 250V 3.15A 250V Black Red White Yellow Blue Red White Black Red Brown Blue Orange Yellow White Black Black Black Black Black Black Black White White Red Brown Brown Brown Brown Black Black White Red Yellow Yellow Black Black Black Red White Black 4-way valve Ventilator Electronic expansion valve Compressor Reactance Evaporator outlet Discharge Compressor Outside Fuse 250V 5A Terminal block Interconnection between the outside unit and the hydraulic module Electricity supply Fuse 250V 20A Regulation board Fuse Fuse Temperature sensors Evaporator centre Figure 45 - Electrical wiring of outside unit Model 050, 065, 080

Installation and operating manual “1350-EN”

53 Heat pump, Split, single service 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 3 2 1 3 2 1 2 1 2 1 2 1 7 6 5 4 3 2 1 2 1 2 1 6 5 4 3 2 1 7 6 5 4 3 2 1 6 5 4 3 2 1 3 2 1 3 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 CN700 CN801 CN500 CN110 CN1 CN400 CN200 CN11 CN60 CN61 CN62 CN64 CN90 CN40 CN42 CN303 CN301 W306 W307 W302 W301 W17 W16 TM102 TM101 W303 W W304 V W305 U W8 W7 W13 W12 L2 L1 + P N1 N2 L0 TM600 TM601 W4 R C S CN100 1 2 W29 W28 W25 W26 W21 W20 W9 W17 W3 W18 W2 W1 W19 1 2 3 L N F M PMV 4WV C M Klemmenstrook ACTPM I P M PCB Red Red Brown Brown Blue Blue Black Black Brown Brown Black Black White Yellow Orange Blue Brown Red Red Red Black Green Black White White Black Purple White Yellow Yellow Blue Blue Black Red Brown Orange Black Black White White Red Red Orange Orange Black White Brown Red Brown Red Orange Yellow Green Blue Purple Grey Black White Brown Red Orange Yellow Black Black White Grey White White White White Terminal block Fuse 250V 25A HP pressure switch Coil Posistor Compressor Terminal block Capacitor PCB Power card Regulation board Evaporator centre Discharge Compressor Outside Temperature sensors 4-way valve Electronic expansion valve Electricity supply Interconnection between the outside unit and the hydraulic module Brown Yellow White Black Ventilator Figure 46 - Electrical wiring of outside unit Model 095

Installation and operating manual “1350-EN”

Heat pump, Split, single service R(R) S(S) C(T) Temperature sensors Discharge Compressor Outside Compressor Terminal block Coil Red White Black White Red Black Module filtre actif Brown Red Orange Yellow Yellow Blue Posistor Orange Orange Red Black White Black White Brown Black Fuse 25 A White Black Green Terminal block Red White Electrical cabling Black Red White Black Brown HP pressure switch 4-way valve Electronic expansion valve Fuse Fuse Ventilator 1 Ventilator 2 Red Red Black Black Red White Yellow Brown Red Brown Blue Orange Yellow White Black Red White Yellow Brown Black Black Black Black Brown Brown Blue Filter Evaporator outlet Evaporator centre Compressor casing Interconnection between the outside unit and the hydraulic module Regulation board Fuse 10 A Figure 47 - Electrical wiring of outside unit Model 128

Installation and operating manual “1350-EN”

55 Heat pump, Split, single service Temperature sensors Discharge Evaporator Compressor Outside Compressor Regulation board Terminal block Coil Posistor Terminal block Electricity supply HP pressure switch 4-way valve Electronic expansion valve Fuse Ventilator 1 Ventilator 2 Black Brown Brown Blue Black Active filter unit White Brown Filter EMI Filter EMI Connector Yellow Blue Orange Red Red Brown Yellow Diode bridge Relay Red White Red White Black Grey Grey Black Red Filter EMI Filter Filter EMI Red Red Black Yellow Brown White Orange Blue Black Red Black Yellow Brown White Black Yellow Brown White Red White Black White Black White Black Green White Black Black Red Brown Compressor casing Interconnection between the outside unit and the hydraulic module Filter EMI White Violet Terminal block Black Black Orange Orange Filter EMI Fuse 10 A Red Figure 48 - Electrical wiring of outside unit Model 155

Installation and operating manual “1350-EN”

Heat pump, Split, single service CN9 CN1 CN2 CN4 CN5 CN14 CN15 CN7 CN8 CN103 CN106 CN114 CN105 CN113 CN116 CN104 M BX5 M BX4 M DO2 M DO1 QX7 QX6 QX5 QX3 N N L Uref UX H3 M H1 A1 A2 B1 B2 A1 A2 B1 B2 2a 2b 1a 1b 1 2 3 4 5 6 7 8 9 10 11 121314151617 1819 RpECS Rp1 Rp2 X50 ou X30 Condensation sensor Return sensor Flow sensor Heating circulation pump Resistance 2 of the back-up unit Resistance 1 of the back-up unit Safety thermostat Start/stop switch Timed fuse 3,15 A - 250V Figure 49 - Electrical wiring, Hydraulic module (Except installer's connections) Connection to terminal block and power relays (see figure 37, page 28) Connections to the heat pump regulator (accessories and options) (see figure 38, page 29)

Depending on whether the fault comes from the

outside unit or the hydraulic module, the fault may be indicated by the digital display or the diode on the interface cards. 6.1 Faults displayed on hydraulic module Faults or breakdowns on the hydraulic mode are indicated by the display on the user interface. The display shows the “Bell” symbol . Press the Info key for more details on the origin of the fault. When the error has been resolved, the faults are re-initialised at zero automatically. Installation and operating manual “1350-EN” 57 Heat pump, Split, single service Hydraulic module : Fault visible on the digital display Error number Error description Error location Heat pump operation despite the error - No connection Failure to comply with room thermostat's polarity No 10 Outdoor sensor B9 Yes with OT = 0 °C 33 Heat pump initial temperature sensor error B21 Yes 44 Heat pump return temperature sensor error B71 Yes 50 DHW temperature sensor B3 Yes 60 Ambient temperature sensor 1 Yes 65 Ambient temperature sensor 2 Yes 105 Maintenance message Yes 121 Flow temperature for (HC1) not reached Yes 122 Flow temperature for (HC2) not reached Yes 127 Anti-legionella temperature not reached Yes 369 External fault (safety component) No 370 Outside unit connection error See below and fig. 58 and 59 No Hydraulic module : Flashing of the diode visible on the interface card Diode display Erroneous element 1 Flash Transmission error, "hydraulic module - outside unit" 2 Flashes Abnormal discharge temperature or defective discharge sensor 3 Flashes Defective exchanger sensor 4 Flashes Defective outside temperature sensor 5 Flashes Abnormal compressor temperature or defective compressor temperature sensor 6 Flashes HP pressure switch cut off 7 Flashes Abnormal current quality 8 Flashes Current quality detection circuit defective 9 Flashes Active filter error 10 Flashes Compressor is not operating 11 Flashes External fan error 12 Flashes Compressor casing resistance fault 13 Flashes Active filter cut off for over-intensity CN9 CN1 CN2 CN4 CN5 CN14 CN15 CN7 CN8

Installation and operating manual “1350-EN”

Heat pump, Split, single service Outside unit, Reference AOYA18LALL (Model 050 and 065) and Reference AOYA24LALL (Model 080) Diode display Erroneous element 0,1 seconds lit and 0,1 seconds unlit Defective temperature sensor (see hydraulic module) 0,5 seconds lit and 0,5 seconds unlit Abnormal intensity detector error 2 seconds lit and 2 seconds unlit Electric current circuit breaker error 5 seconds lit and 5 seconds unlit Defective fan motor 0,1 seconds lit and 2 seconds unlit Position of the compressor’s rotor not detected 5 seconds lit and 0,1 seconds unlit Abnormal PAM circuit voltage 1 seconds lit and 0,1 seconds unlit Timer cut off 2 seconds lit and 5 seconds unlit Abnormal compressor temperature 5 seconds lit and 2 seconds unlit Active filter error Permanently lit Abnormal discharge temperature Outside unit, Reference AOYA30LBTL (Model 095) Diode display Erroneous element 0,1 seconds lit and 0,1 seconds unlit Defective temperature sensor (see hydraulic module) 0,5 seconds lit and 0,5 seconds unlit Defective IPM card 2 seconds lit and 2 seconds unlit Communication serial bus error (terminals 3 outside unit & hydraulic module) 5 seconds lit and 5 seconds unlit Defective fan motor 0,1 seconds lit and 2 seconds unlit Position of the compressor’s rotor not detected 5 seconds lit and 0,1 seconds unlit Defective ACTPM card Permanently lit Abnormal discharge temperature 6.2 Faults displayed on the outside unit To access the electronic board, you must remove the front (right-hand) facing from the outside unit. Faults are coded by diode flashes.

Various data can be displayed by pressing the info

button. Depending on the type of unit, configuration and operating state, some of the info lines listed below may not appear. - Possible error messages from the error code list (See table, page 57). - Possible service messages from the maintenance code list. - Possible special mode messages. - Various data (See below). Designation Line Floor drying current setpoint - Current drying day - Terminated drying days - Room temperature 8721 State heat pump 8006 State supplementary source 8022 State DHW 8003 State swimming pool 8011 State heating circuit 1 8000 State cooling circuit 1 8001 State heating circuit 2 8004 Outside temperature 8700 Room setpoint 1 8740 Flow temperature 1 8743 Flow temperature setpoint1 Room setpoint 2 8771 Flow temperature 2 8773 Flow temperature setpoint 2 DHW (domestic hot water) temperature 8830 Heat pump return temperature 8410 Setpoint (flow) HP Heat pump flow temperature 8412 Setpoint (flow) HP Swimming pool temperature 8900 Swimming pool temperature setpoint Installation and operating manual “1350-EN” 59 Heat pump, Split, single service Outside unit, Reference AOYA45LATL, AOYA45LBTL (Model 128) and Reference AOY54LJBYL (Model 155) Diode display Erroneous element 1 Flash Transmission error, "hydraulic module - outside unit" 2 Flashes Defective “discharge” temperature sensor 3 Flashes Defective “evaporator” temperature sensor 4 Flashes Defective “outside” temperature sensor 5 Flashes (Model 128) Defective “evaporator centre” temperature sensor 6 Flashes (Model 128) Abnormal discharge temperature 7 Flashes Defective compressor temperature sensor 8 Flashes Defective “compressor casing” temperature sensor 9 Flashes Defective HP pressure switch 10 Flashes (Model 128) Abnormal compressor temperature 12 Flashes Defective IPM card 13 Flashes Position of the compressor’s rotor not detected 14 Flashes Compressor is not operating 15 Flashes Defective upper fan motor 16 Flashes Defective lower fan motor 5 seconds lit and 1 seconds unlit Switched to safety mode 1 seconds lit and 1 seconds unlit (Model 128) Switched to vacuum Permanently lit No error

Instructions for the user

Explain to the user how his installation operates, in particular the functions of the room thermostat and the programmes accessible to him from the user interface. Emphasise that a heated floor has significant inertia and that therefore any adjustments must be made progressively Also explain to the user how to check the filling of the heating circuit 60 Installation and operating manual “1350-EN” Heat pump, Split, single service Complies with : - Low tension Directive 73/23/CEE, under standard NF-EN60335-1. - Electromagnetic compatibility Diretive 89/336/CEE - Directive 98/37/EC, - Directive for pressurised equipment 97/23/EC, - Directive for labelling energy consumption 2002/31/EC This appliance also conforms to: - Decree No. 92-1271 (and its modifications) relating to certain refrigeration fluids used in refrigerating and air conditioning equipment. - The standards relating to the product and the testing methods used: Air-conditioners, refrigeration units and heat pumps with compressor driven by electric motor for heating and refrigeration EN 14511-1, 14511-2, 14511-3, and 14511-4 - To standard XP ENV 12102: Air-conditioners, heat pumps and dehumidifiers with compressor driven by electric motor. Measurement of airborne noise. Determination of acoustic power level.