Ariston microGENUS 23 MFFI Servicing Instructions
Read Online
Read the Ariston microGENUS 23 MFFI Servicing Instructions online using the built-in PDF viewer.
Text of the manual
Type C Boilers
G.C.N:
47-116-14
47-116-15
LEAVE THESE INSTRUCTIONS
WITH THE END-USER
Country of destination: GB
REPLACEMENT OF PARTS
1.2
TO GAIN GENERAL ACCESS
- Removing the front panel
- Removing the sealed chamber frontal cover
- Removing the side panels
1.3
ACCESS TO THE COMBUSTION CHAMBER
- Removing the combustion cover
- Removing the burner and jets
- Removing the electrodes
- Removing the main heat exchanger
- Removing the air pressure switch
- Removing the fan
- Removing the venturi device
1.4
SERVICING AND REMOVAL OF THE GAS VALVE
- Setting the gas pressures
- Removing the spark generator
- Removing the gas valve
1.5
ACCESS TO THE WATER CIRCUIT
- Removing the D.H.W. (secondary) exchanger
- Removing the safety valve
- Removing the automatic air vent
- Removing the main circuit flow switch
- Removing the pump
- Removing the pressure gauge
- Removing the expansion vessel
- Removing the overheat thermostat
- Removing the heating temperature sensor (N.T.C.)
- Removing the D.H.W. temperature sensor (N.T.C.)
- Removing the divertor valve actuator
- Removing the D.H.W. flow switch
1.6
ACCESS TO THE CONTROL SYSTEM
- Checking the fuses
- Removing the time clock
- Removing the P.C.B.
2.
FAULT FINDING
2.1
FAULT FINDING GUIDE (FLOW-CHART)
3.
ELECTRICAL DIAGRAMS
4.
SHORT SPARE PARTS LIST
TABLE OF CONTENTS
2. The control panel moves downward and when pulled forward,
rotates on two lateral hinges; the panel stays in a semi-
horizontal position, which allows access to the inner parts of
the boiler (FIG. 1.2);
3. In order to increase the manouvering space, it is possible to
raise the control panel and rotate it to a fully horizontal position
(FIG. 1.3);
4. Remove the screws “B” from the front panel bottom lip
(FIG. 1.4);
5. Lift the front panel from the raised screws at the the top of the
casing (FIG. 1.5).
FIG. 1.4
B
FIG. 1.5
3
B063
1.
SERVICING INSTRUCTIONS
The life of individual components varies and they will need
servicing or replacing as and when faults develop.
The fault finding sequence chart in chapter 2 will help to locate
which component is the cause of any malfunction, and instructions
for removal, inspection and replacement of the individual parts are
given in the following pages.
1.1
REPLACEMENT OF PARTS
1.2
TO GAIN GENERAL ACCESS
All testing and maintenance operations on the boiler require the
control panel to be lowered. This will also require the removal of
the casing.
Removing the front panel
1. Loosen the fastening screws “A” of the control panel located on
the lower part of the panel itself. (FIG. 1.1);
A
FIG. 1.3
FIG. 1.1
FIG. 1.2
To ensure efficient safe operation, it is recommended that the
boiler is serviced annually by a competent person.
Before starting any servicing work, ensure both the gas and
electrical supplies to the boiler are isolated and the boiler is
cool.
Before and after servicing, a combustion analysis should be made
via the flue sampling point (please refer to the Installation Manual
for further details).
After servicing, preliminary electrical system checks must be
carried out to ensure electrical safety (i.e. polarity, earth continuity,
resistance to earth and short circuit).
19.eps
14.eps
13.eps
FO016A/15.eps
16.eps
Removing the sealed chamber frontal cover
1. Remove the screws “C” (FIG. 1.6);
2. Lift the sealed chamber frontal cover from the locating pins
(FIG. 1.7).
FIG. 1.6
C
C
FIG. 1.7
Removing the side panels
1. Remove the four screws “D” for each side panel (FIG.1.8);
2. Pull the panel away from the boiler, then lift the panel up and
remove from the boiler (FIG.1.9).
D
D
D
FIG. 1.8
FIG. 1.9
18.eps
98.tif
17 eps
97.tif
Removing the electrodes
Before carrying out this procedure, unscrew and slide the
burner forward (see previous section).
1. Remove rubber gasket “G” (Fig. 1.13);
2. To remove the detection electrode disconnect the cable
at its connection point close to the P.C.B. (Fig. 1.14);
FIG. 1.13
G
FIG. 1.14
Removing the burner and jets
1. Remove the screws “F” from the burner (FIG. 1.11);
2. Remove the burner (FIG. 1.12);
3. Remove the jets using a No. 7 socket spanner;
4. Replace in reverse order.
5
B063
Removing the combustion cover
1. Remove the screws “E” (FIG. 1.10);
2. Lift off the combustion cover.
1.3
ACCESS TO THE COMBUSTION CHAMBER
E
E
E
FIG. 1.10
FIG. 1.11
Fig. 1.12
F
F
99.tif
12 eps
78 eps
49 eps
50 eps
3. Remove screw “H” (FIG. 1.15);
4. Gently slide the electrode downward (FIG. 1.16).
To replace, repeat the steps in reverse order, paying
particular attention to the following:
a -Centre the electrode in the positioning hole carefully,
otherwise the electrode may break;
b -Check that the cables have been connected correctly;
c -Check that the rubber gasket covers the cable/ electrode
connection point completely.
FIG. 1.15
FIG. 1.16
H
1. Drain the boiler of water;
2. Release the overheat thermostat sensor “I” (FIG. 1.17);
3. Release the two connection nuts “J” connecting the
exchanger to the flow and return pipes (FIG. 1.18);
4. Pull it straight out (FIG. 1.19).
Removing the main heat exchanger
FIG. 1.18
J
Fig. 1.17
I
FIG. 1.19
51 eps
11 eps
52 eps
75 eps
76 eps
6 eps
1. Disconnect electrical connections “N” and silicon pipes
“O” (FIG.1.23);
2. Remove screw “P” and remove the fan collar clamp “Q”
(FIG.1.24);
3. Remove screws “R” (FIG.1.25);
4. Remove fan and mounting plate (FIG.1.26).
Removing the fan
1. Disconnect the electrical connections “K” and silicon pipes
“L” from their connection points (FIG. 1.20);
2. Remove screws “M” on the top of the sealed chamber
(FIG. 1.21);
3. Unscrew to remove switch from the plate (FIG. 1.22).
FIG. 1.21
FIG. 1.20
7
B063
Removing the air pressure switch
L
K
M
M
FIG. 1.22
FIG. 1.25
R
R
FIG. 1.24
P
Q
FIG. 1.23
N
N
O
FIG. 1.26
91.tif
90.tif
93.tif
94.tif
95.tif
96.tif
SERVICING AND REMOVAL
OF THE GAS VALVE
Setting the gas pressures
1
2
Recommended pressure for
soft-light ignition
8 mbar
NATURAL GAS (G20)
BUTANE GAS (G30)
PROPANE GAS (G31)
16 mbar
16 mbar
3
4
A
B
C
E
F
D
Setting the minimum and the maximum power of the boiler
1. Check that the supply pressure to the gas valve is a minimum of 20 mbar
for natural gas.
2. To do this, remove the screw “A”.
Fit the pipe of the pressure gauge to the pressure connection of the gas
valve “B”.
When you have completed this operation, replace the screw “A” securely
into its housing to seal off the gas.
3. To check the pressure supplied by the gas valve to the burner, remove the
screw “C”. Fit the pipe of the pressure gauge to the pressure outlet of the
gas valve “D”.
Disconnect the compensation pipe either from the gas valve or from the
sealed chamber.
4. Set the On/Off button to position < I > and the “summer/winter” switch to
the winter position.
To set the maximum power, turn on the hot water tap and allow the hot
water tap to run at a rate of about 8 litres/minute so that the main burner
lights.
Adjust nut “E” on the modureg to set the gas pressure (displayed on the
pressure gauge) corresponding to the maximum power (see TABLE “A” page
9).
5. To set the minimum power, disconnect a supply terminal from the modureg
and adjust screw “F”.
Turn the screw clockwise to increase the pressure and coun-
ter-clockwise
to
decrease
the
pressure
(displayed
on
the
pressure gauge) corresponding to the minimum power (see TABLE“A” page
9).
6. When you have completed the above operations, turn off the
hot water tap, re-connect the supply terminal to the modureg
on the gas valve and replace the cap on the screw of the
modureg.
Setting the maximum heating circuit power
7. To
set
the
maximum
heating
circuit
power,
place
the
On/Off button to position < I > and the “summer/winter” switch to winter
position.
Turn the knob of the heating thermostat clockwise to maximum.
8. Remove the inspection panel of the P.C.B. and fit a small cross-head
screwdriver in to the right hand potentiometer. Turn clockwise to increase
the pressure or counter-clockwise to reduce the pressure. Adjust the
setting to the required heating pressure value (displayed on the pressure
gauge), as indicated in the diagrams shown in page 10.
9. Turn off the boiler by placing the main switch to the "Off" position.
Setting pressure for soft ignition.
Disconnect the detection electrode connection from the P.C.B..
Start the boiler and during the ignition sequence adjust the left hand
potentiometer until the gas pressure reads the required gas pressure as
per the table below.
Once the gas pressure is set turn off the boiler and re-connect the
connection to the P.C.B.
NB.: It may be necessary to reset the flame failure reset a number of times
during this operation.
VG001Aa
VG001Ac
VG001Ab
VG001Ad
Regulating the heating power for
natural gas (G20)
model 23
model 27
Regulating the heating power for
butane gas (G30)
model 23
model 27
34
36
38
40
Regulating the heating power for
propane gas (G31)
23 MFFI
2.70
20
11.0
2.0
1.16
2.01 Kg/h
0.87 Kg/h
27.7 mbar
6.0 mbar
28 mbar
12 x 0.77
2.00 Kg/h
0.85 Kg/h
35.5 mbar
7.3 mbar
37 mbar
12 x 0.77
27 MFFI
3.15
20
11.0
1.6
1.26
2.34 Kg/h
0.94 Kg/h
27.7 mbar
4.6 mbar
28 mbar
2.31 Kg/h
0.93 Kg/h
35.5 mbar
6.0 mbar
37 mbar
14 x 1.30
14 x 0.77
14 x 0.77
TABLE “A”
CG007A
CG008A
CG009A
TB012A
Removing the spark generator
1. Disconnect ignition leads “T” by pulling upward
(FIG. 1.27);
2. Remove the screw “V” (FIG. 1.28);
3. Remove the spark generator (FIG. 1.29).
10. Remove the pipe from the pressure gauge and connect
screw “C” to the pressure outlet in order to seal off the
gas.
11. Carefully check the pressure outlets for gas leaks (valve
inlet and outlet).
IMPORTANT!
Whenever you disassemble and reassemble the gas
connections, always check for leaks using a soap and water
solution.
FIG. 1.27
FIG. 1.28
FIG. 1.29
T
V
Soft-light
Adjustment
Max Heating
Adjustment
61.eps
45.eps
43.eps
44.eps
VR015A.eps
Important! Before any component is removed, the boiler
must be drained of all water.
Removing the D.H.W. (secondary) exchanger
1.Remove the screws “Y” (FIG 1.33 + FIG 1.34);
2.Push the exchanger towards the rear of the boiler, and lift
upwards and remove out of the front of the boiler
(FIG 1.35);
3.Before replacing the exchanger ensure that the O-rings
are in good condition and replace if necessary.
1.6
ACCESS TO THE WATER CIRCUIT
FIG. 1.30
FIG. 1.31
FIG. 1.32
FIG. 1.33
W
X
X
Removing the gas valve
1. Disconnect all the cables from the solenoid and
modureg;
2. Remove the spark generator (see previous section);
3. Release the top nut “W” (FIG. 1.30);
4. Remove the screws “X” from the bottom of the gas valve
pipe (FIG. 1.31);
5. Remove the gas valve (FIG. 1.32).
Y
FIG. 1.34
FIG. 1.35
Y
47.eps
48.eps
38.eps
22.eps
21.eps
68.eps
Removing the safety valve
1. Loosen nut “Z” (FIG. 1.36);
2. Unscrew and remove the valve (FIG. 1.37).
Removing the automatic air vent
1. Unscrew valve top “A1” (FIG. 1.38);
2. Remove valve (Fig 1.39).
Removing the main circuit flow switch
1. Remove the cable of the main circuit flow switch “B1”
(FIG. 1.40);
2. Remove the screws “C1” (FIG. 1.41);
3. Remove the main circuit flow switch.
FIG. 1.36
Fig. 1.38
FIG. 1.40
Z
B1
C1
C1
FIG. 1.37
A1
Fig. 1.39
FIG. 1.41
40.eps
37.eps
39.eps
41.eps
53.eps
54.eps
Removing the pump
1. Remove the U-clip “ D1” (FIG. 1.41);
2. Remove the retaining clip “E1” (FIG. 1.42);
3. Remove the U-clip “ F1” (FIG. 1.43);
4. Release the nut “G1” (FIG. 1.44);
5. Remove the pipe “H1” (FIG. 1.45);
6. Remove the screws “I1” (FIG. 1.46);
7. Remove the pump (FIG. 1.47).
D1
FIG. 1.41
FIG. 1.42
FIG. 1.43
FIG. 1.44
E1
F1
FIG. 1.45
FIG. 1.46
FIG. 1.47
G1
H1
I1
I1
31.eps
33.eps
34.eps
42.eps
32.eps
35.eps
25.eps
Removing the expansion vessel
1. Loosen nuts “K1” and remove the gas pipe (FIG. 1.50);
2. Loosen nut “L1” (FIG. 1.51);
3. Remove back nut “M1” (FIG. 1.52);
4. Remove the expansion vessel (FIG. 1.53).
Removing the pressure gauge
1. Remove the U-clip “J1” and remove the pressure gauge
coupling (FIG. 1.48);
2. Push the pressure gauge through the control panel from
the rear (FIG. 1.49).
FIG. 1.48
FIG. 1.50
J1
FIG. 1.49
K1
L1
FIG. 1.51
FIG. 1.52
FIG. 1.53
K1
M1
34.eps
27.eps
77.eps
57.eps
58.eps
59.eps
Removing the overheat thermostat
1. Disconnect
the
overheat
thermostat
electrical
connections “N1” (FIG. 1.54);
2. Then remove the thermostat from its mounting by
releasing the securing clip (FIG. 1.55).
Removing the heating temperature sensor (N.T.C.)
1. Pull off the electrical connector “P1” and unscrew the
sensor probe using a suitable spanner (FIG. 1.56).
FIG. 1.54
FIG. 1.55
Removing the D.H.W. temperature sensor (N.T.C.)
1. Pull off the electrical connector “Q1” and unscrew the
sensor probe using a suitable spanner (FIG. 1.57).
FIG. 1.57
Removing the divertor valve actuator
1. Unplug the electrical connector “R1” (FIG. 1.58);
2. Release the retaining clip “S1” and remove the divertor
valve actuator.
FIG. 1.58
Removing the D.H.W. flow switch
1. Unplug the electrical connector “T1” (FIG. 1.59);
2. Release the retaining clip “V1” and remove the D.H.W.
flow switch.
FIG. 1.59
N1
P1
Q1
S1
R1
FIG. 1.56
T1
V1
80.eps
83.eps
87.eps
60.eps
74.eps
30.eps
Checking the fuses
1. Remove the inspection cover on the reverse of the
control panel (FIG. 1.60);
2. Remove the fuses (FIG. 1.61).
1.6
ACCESS TO THE CONTROL SYSTEM
Removing the time clock
1. Unplug electrical connection “W1” from the clock (FIG.
1.62);
2. Remove the screws “W2” (see fig. 1.63);
3. Remove the clock from the panel (see fig. 1.64).
FIG. 1.60
FIG. 1.62
FIG. 1.61
FIG. 1.64
W1
72.eps
61.eps
69.eps
1190.tif
FIG. 1.63
1189.jpg
W2
Removing the P.C.B.
1. Isolate electricity;
2. Remove the inspection cover from the reverse of the
control panel;
3. Unplug all electrical connections from the P.C.B. (FIG.
1.65);
4. Remove the screws “X1” (FIG. 1.66);
5. Separate the facia panel from the rear of the control
panel (FIG. 1.67);
7. Remove the screws “Y1” and remove the P.C.B. (FIG.
1.68).
FIG. 1.66
X1
X1
X1
X1
X1
X1
FIG. 1.65
FIG. 1.67
FIG. 1.68
Y1
Y1
64.eps
1187.eps
65.eps
82.eps
MAKE SURE THAT:
IS
THE POWER
L.E.D.
ON?
POSTION
OF THE
SELECTOR
NO
NO
WINTER
ESTAT E
SUMMER
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
1 - Check the fuses
2 - Check the power supply
cable, plug and outlet
3 - Check/replace the power
supply to the P.C.B.
TURN ON THE ON/OFF
SWITCH
D.H.W. IS
BEING DRAWN?
D.H.W. IS
BEING DRAWN?
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5°C
FOR BOILERS
WITH ELECTRONIC
ANTI-FROST DEVICE:
PROTECTION IS ACTIVATED
IF HEATING TEMP
IS < 5°C
MUST
TIME CLOCK
AND/OR ROOM
THERMOSTAT
BE ACTIVATED?
A
ECONOMY/
COMFORT
SELECTOR
TEMP.
C.H. < 34°C
Comfort
Comfort
Economy
Economy
1 - There is sufficient water in
the system
2 - The gas is turned on
3 - The electrical supply is
turned on
1 - Check/reset system
pressure
2 - Check/restore gas
supply
3 - Check/replace short-
circuited heating probe
4 - Check/replace siezed
pump
1 - Check/reset the
system pressure
2 - Check/restore
gas supply
3 - Check/replace short-
circuited heating probe
4 - Check/replace
siezed pump
TEMP.
C.H. < 34°C
ECONOMY/
COMFORT
SELECTOR
It is possible to detect and correct any defect by using the standard fault
finding diagrams described in this chapter.
2.1
FAULT FINDING GUIDE
(FLOW-CHARTS)
FC004Aa
IS THE PUMP
RUNNING?
YES
NO
NO
NO
YES
YES
YES
POWER TO
THE PUMP?
DOES THE
"NO WATER" L.E.D.
ILLUMINATE
(WITHIN 40 SECS)?
1 - Check if there is air in the
system
2 - Check main circuit flow switch
operation
3 - Check pressure on the water
gauge and fill system to return
to 1 bar
1 - Turn the boiler off then on
(protection reset)
1 - Check that the pump
is not stuck
2 - Release/replace pump
1 - Check pump cable
2 - Check/replace P.C.B.
3 - Check main flow main
switch operation when
drawing D.H.W.
A
B
FC004Ab
IS THE FAN
RUNNING?
BOILER
SHUTDOWN?
POWER
TO FAN?
NO
YES
YES
YES
NO
YES
NO
NO
NO
YES
1 - Check/replace main
circuit flow switch
2 - Check/replace
connection cable
3 - Check/replace P.C.B.
1 - Check/replace air
pressure switch
2 - Check if reset button
is jammed
3 - Check/replace flame
detection electrodes
1 - Check/replace
connection cable
2 - Check/replace P.C.B.
3 - Check/replace air
pressure switch
1 - Replace fan
1 - Reset the boiler
PUMP PROTECTION
ACTIVATED?
INTERNAL
P.C.B. PROTECTION
ACTIVATED?
B
C
FC004Ac
IS THE BURNER
ALIGHT?
YES
NO
YES
YES
YES
NO
NO
NO
NO
YES
1 - Check/replace ignition
electrode
2 - Check ignition cable
3 - Check spark generator
4 - Check ignition electrode
cable
5 - Check/replace P.C.B.
1 - Check if flame strikes
detection electrode
2 - Check soft-light gas
pressure
3 - Check/replace detection
electrode
4 - Check/replace P.C.B.
1 - Check power supply of
gas valve
2 - Check/replace P.C.B.
3 - Check efficiency of
gas valve
4 - Replace gas valve
Shutdown L.E.D. off
fan restarts
IS THE
AIR PRESSURE SWITCH
ACTIVATED?
CHECK
∆P ON TEST
PRESSURE
INTAKE
IS FLUE
DISCHARGE
NORMAL?
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
1 - Check exhaust discharge
2 - Check venturi & pipes
3 - Check fan efficiency
1 - Check A.P. switch cable
2 - Check/replace A.P. switch
3 - Check/replace P.C.B.
C
D
P 1.2 mbar
P 1.2 mbar
∆
∆
∅
≤
FC004Ad
When you turn on a tap
burner switches off
Drawing D.H.W:
radiators heat up in summer mode
Drawing D.H.W:
insufficient hot water
temperature
Drawing D.H.W:
noisy operation
Decrease/increase
heating circuit pressure
Repeated shutdowns
Repeated intervention of safety thermostat
When cold water tap turned off, the boiler
ignites
Insufficient radiator temperature
- air in secondary heat exchanger
- faulty main circuit flow switch
- faulty D.H.W. flow switch
- faulty 3-way valve
- check C.H./D.H.W. temperature probes
- check gas pressures
- check water flow rate
- check secondary heat exchanger
- primary heat exchanger faulty or
lime-scale deposits
- low heating system water pressure
- check gas pressures
- check C.H./D.H.W. temperature probes
- check for leaks on the heating circuit
- faulty filling-loop
- faulty secondary heat exchanger
- expansion vessel faulty
- faulty detection electrodes
- check gas settings
- check flame detection electric circuit
- C.H./D.H.W. temperature probes open circuit
- overheat thermostat not calibrated correctly
- air in primary water circuit
- drop in pressure in the water mains, with
consequent water hammer
- check C.H. temperature probe
- check by-pass
- check gas pressures
FC004Ae
Time Clock Connector
B
=
Central Heating Selection (Winter) and
Temperature Adjustment
C
=
Connector for Total Check System
D
=
Domestic Hot Water Temperature Adjustment
E
=
Soft-light Adjustment
F
=
Maximum Heating Adjustment
G
=
On/Off Switch
H
=
On/Off L.E.D.
I
=
Fume Sensor L.E.D.
J
=
Ignition Failure (Lockout) L.E.D.
K
=
Low System Water Level/Lack of Circulation L.E.D.
L
=
Reset Button
M
=
Economy/Comfort Selector
N
=
Overheat L.E.D.
O
=
Temperature L.E.D.s
P
=
Transformer
Q
=
Circulation Pump Relay
R
=
Fan Relay
S
=
Gas Valve Relay
T
=
Motorised Diverter Valve Relay
V
=
Spark Generator
U
=
Anti-cycling Device Adjustment for Heating
A01
=
Circulation Pump
A02
=
Fan
A03
=
Spark Generator/Gas Valve Supply
A04
=
Motorised Diverter Valve
A05
=
Flame Detection Circuit
A06
=
Detection Electrode
A07
=
Main Circuit Temperature Probe
A08
=
Domestic Hot Water Temperature Probe
A09
=
Domestic Hot Water Flow Switch
A10
=
Main Circuit Flow Switch
A11
= Modulator
A12
=
Air Pressure Switch
A13
=
Safety Thermostat
A14
=
External (Room) Thermostat
Colours:
Gry
=
Grey
Wh
=
White
Pnk
=
Pink
Brn
=
Brown
Bl
=
Blue
Blk
=
Black
Rd/Blk
=
Red/Black
microGENUS 23/27 MFFI
J
K
Blk
Blk
Gry
Gry
Pnk
Pnk
Pnk
Gry
Gry
Wh
Wh
Wh
Wh
Wh
Wh
Wh
Rd/Blk
Rd/Blk
Rd/Blk
Blk
Blk
Blk
Brn
Brn
Brn
Brn
Blk
Blk
SE017A
U
J
K
M
L
R
S
Q
T
O
N
SF014A
MICROGENUS 23 MFFI
METHANE
2320005600001
A
MICROGENUS 23 MFFI
LPG
2320005600001
B
MICROGENUS 27 MFFI
METHANE
2320005600001
C
MICROGENUS 27 MFFI
LPG
2320005600001
D
999091
4.
SHORT SPARE
PARTS LIST
microGENUS 23/27 MFFI
microGENUS 23/27 MFFI
998616
573521
998077
573520
997147
997077
569236
998613
571547
998099
998940
998424
574279
998645
997089
998836
999091
999599
998947
999245
573989
571651
999397
998894
997206
998620
998893
998618
998669
998887
998939
571646
573295
573825
573172
998623
998622
998624
998941
997029
998490
998718
998975
998974
998644
998643
998738
998961
999207
571547
571772
571771
571770
998172
998716
998717
Key
no.
G.C. part
no.
ARISTON
Part No.
Description
2
5
12
14
16
17
18
19
20
21
24
25
26
27
28
33 AB
33 CD
38
41
43
52AB
52CD
66AB
66CD
72
74AB
74CD
75C
75D
76AB
76CD
75A
75B
77
79
98
99
100
311
321
331
332
333
334
351
352
353
354 AB
354 CD
371
372
373
374
375
381
382
379816
E61 468
164 282
E61 475
164 225
E25 427
E61 429
164 338
E61 478
E24 077
E61 479
E61 482
E61 483
E25 529
E61 848
E61 485
E61 490
E61 881
E61 519
E61 520
E61 530
E03 818
E61 967
E25 425
E61 546
E61 547
E61 549
E61 972
E61 974
E26 767
E26 657
E26 658
E26 378
E61 565
E61 567
E61 569
E25 582
E61 647
E61 648
E61 649
E61 650
E61 652
E61 654
E61 656
E61 660
E62 030
E24 077
E24 077
E24 076
E24 075
E61 663
E61 665
E61 667
Expansion vessel
Gasket 3/8"
O-ring
Gasket 3/4"
Motor (3- Way valve)
Fixing clip (motor)
Temperature probe (C.H.W.)
Flow group
Diaphragm (main flow switch)
Main circuit flow switch
Return group
O-ring
Gasket
Spark generator
Gas valve (SIT 845 SIGMA)
Pump
Pump
Time clock
P.C.B. (CMP1-FFI)
Pressure gauge
Air pressure switch
Air pressure switch
Fan
Fan
Thermostat (overheat)
Main exchanger
Main exchanger
Burner 12 ramp (natural gas)
Burner 12 ramp (LPG)
Burner 14 ramp (natural gas)
Burner 14 ramp (LPG)
Secondary exchanger (p-type 23kW)
Secondary exchanger (p-type 27kW)
O-ring (secondary exchanger)
Safety valve (1/2" 3 bar)
Electrode (Ignition R.H.)
Electrode (Ignition L.H.)
Detection electrode
D.H.W. actuator kit
Operator coils (SIT SIGMA)
Central heating by-pass kit
Heating spring kit
3-way spring kit
Actuator bush
Gasket (auto air vent)
Auto air vent
Gasket (pump head)
Pump head (Gold 15/5)
Pump head
Diaphragm (main flow switch)
Magnet (main flow switch)
Spring (main flow switch)
Main flow switch top cap
Main flow switch reed system
Burner jet 1.25 full kit (Natural gas)
Burner jet 0.72 full kit (LPG)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
23 99 84 1470 312 -
Stampa: Bieffe Recanati
Manufacturer:
Merloni TermoSanitari SpA - Italy
Commercial subsidiary: MTS (GB) LIMITED
MTS Building
Hughenden Avenue
High Wycombe
Bucks HP13 5FT
Telephone: (01494) 755600
Fax: (01494) 459775
internet: http://www.mtsgb.ltd.uk
E-mail: [email protected]
Technical Service Hot Line: (01494) 539579