IFM E89005 Operating Instructions Manual
Read Online
Read the IFM E89005 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Electronic Preset Counter
with two presets
LCD positive, green backlighting
relay outputs
E89005
7390806 / 00
09 / 2017
UK
ecomat 200
E89005
Electronic Preset Counter E89005
2
Contents
1 Preliminary note � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
1�1 Symbols used� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
1�2 Warning signs used � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
2 Safety instructions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 5
3 Functions and features � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
3�1 General description � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
3�1�1 Input modes � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 6
3�1�2 Output operations � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2 Inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2�1 INP A, INP B� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2�2 RESET � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2�3 GATE � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2�4 LOCK INPUT � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�2�5 MPI� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 7
3�3 Outputs� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
3�3�1 Active Outputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
4 Mounting� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8
5 Electrical connection� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
5�1 Advice on noise immunity� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
5�2 Connections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
5�2�1 Signal and control inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
5�2�2 Supply voltage and outputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 10
6 Operating and display elements � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �11
6�1 Error message � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �11
7 Programming � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�1 Entering the programming � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�2 Choice of main menu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�3 Entering a submenu � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�4 Selecting the menu items� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12
7�5 Setting the menu items� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
7�6 Accepting the setting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
7�7 Ending the programming � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13
7�8 Setting the presets � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
7�8�1 Setting via Decade Keys � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
7�8�2 Setting via Teach-in function � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
7�8�3 Setting the tracking presets (trail) � � � � � � � � � � � � � � � � � � � � � � � � � � 16
7�9 Set Function � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 17
8 Parameters � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
8�1 Default parameters� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
8�2 Table: Default Parameter Sets � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 18
8�3 Setting the basic function of the device � � � � � � � � � � � � � � � � � � � � � � � � � � 19
Electronic Preset Counter E89005
3
8�4 Pulse counter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20
8�4�1 Input � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 20
8�4�2 Mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 21
8�4�3 Config� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 23
8�4�4 Reset mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 24
8�4�5 Preset 1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 24
8�4�6 Preset 2 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 25
8�5 Timer � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 27
8�5�1 Input � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 27
8�5�2 Mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 28
8�5�3 Config� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 30
8�5�4 Reset mode � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 30
8�5�5 Preset 1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 31
8�5�6 Preset 2 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 32
8�6 Tacho/Frequency meter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 34
8�6�1 Input � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 34
8�6�2 Config� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 35
8�6�3 Preset 1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 36
8�6�4 Preset 2 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 37
9 Diagrams � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39
9�1 Input modes � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39
9�1�1 Pulse counting � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 39
9�1�2 Timing� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 41
9�1�3 Frequency meter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 42
9�2 Output operations� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 43
9�2�1 Add modes � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 43
9�2�2 Sub modes� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 44
9�2�3 Trail modes� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 45
10 Dimensions� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 46
11 Technical data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 47
11�1 General Data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 47
11�2 Pulse counter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 47
11�3 Tacho/Frequency meter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 47
11�4 Timer� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 48
11�5 Signal and Control inputs � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 48
11�6 Outputs� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 48
11�6�1 Output 1 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 48
11�6�2 Output 2 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 49
11�7 Supply voltage � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 49
11�8 Sensor supply� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 49
11�9 Climatic Conditions� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 49
11�10 EMC � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 49
11�11 Device safety � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 50
11�12 Mechanical Data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 50
Electronic Preset Counter E89005
4
11�13 Connections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 50
12 Maintenance, repair and disposal� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 50
13 Approvals/standards � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 51
14 Attachement � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 51
Electronic Preset Counter E89005
5
1 Preliminary note
Please read this instruction manual carefully before installation and start-up�
Please observe all warnings and advice, both for your own safety and for general
plant safety� If the device is not used in accordance with this instruction manual,
then the intended protection can be impaired�
1.1 Symbols used
►
Instructions
>
Reaction, result
[…]
Designation of keys, buttons or indications
→
Cross-reference
Important note
Non-compliance can result in malfunction or interference�
Information
Supplementary note
1.2 Warning signs used
WARNING
Warning of serious personal injury�
Death or serious irreversible injuries may result�
CAUTION
Warning of personal injury�
Slight reversible injuries may result�
NOTE
Warning of damage to property�
2 Safety instructions
Please use the device only if its technical condition is perfect� It should be used
only for its intended purpose�
Please bear in mind safety aspects and potential dangers and adhere to the
operating instructions at all times�
WARNING
If the device is used to monitor machines or processes in which, in the event of
a failure of the device or an error made by the operator, there might be the risk
of damaging the machine or causing an accident to the operators, then it is your
responsibility to take the appropriate safety measures�
Electronic Preset Counter E89005
6
3 Functions and features
The preset counter detects and measures pulses, times and frequencies and
offers a wide variety of different operating modes� At the same time, the preset
counter processes programmed presets�
The application area for this device lies in industrial processes and controls, in the
fields of manufacturing lines for the metal, wood, plastics, paper, glass, textile and
other like industries�
Use for any purpose over and beyond this will be deemed as not in accordance
with its intended purpose and thus not complying with the requirements�
Overvoltages at the terminals of the device must be kept within the limits of Over-
voltage Category II�
The device must only be operated when mounted in a panel in the correct way and
in accordance with the section "Technical Data" (→ 11 Technical data)�
Correct operation of the device requires the mandatory use of the appropriate
external safety fuse� Advice concerning the recommended fuseprotection can be
found under (→ 11.7 Supply voltage)�
The device is not suitable for use in hazardous areas and for areas excluded in EN
61010 Part 1�
3.1 General description
●
6-digit multifunction LCD display
●
2-line LCD-display with annunciators for both the displayed preset and the
status of the two outputs
●
Simultaneous display of the actual value and of the presets or auxiliary
counters
●
Backlit display
●
Add�/Sub� Preset counter with two presets
●
Relay outputs
●
Preset entry via the front keys or via the Teach-In function
●
Step or tracking preset
●
Pulse, frequency, time or batch counter
●
Preset counter, Batch counter or Total Counter (cumulative count)
●
Set function for pulse and time counter
●
Multiplication and division factor (00�0001���99�9999) for pulse counter and
frequency meter
●
Averaging and Start Delay for frequency meter
●
4-stage RESET-Mode
●
3-stage keypad locking (Lock)
●
MPI input for Display Latch, Teach-In function or Set function
3.1.1 Input modes
●
Pulse counter: cnt�dir, up�dn, up�up, quad, quad2, quad4, A/B, (A-B)/Ax100%
●
Timer: FrErun, Auto, InpA�InpB, InpB�InpB
●
Frequency meter: A, A-B, A+B, quad, A/B, (A-B)/Ax100%
Electronic Preset Counter E89005
7
3.1.2 Output operations
●
Add, Sub, AddAr, SubAr, AddBat, SubBat, AddTot, SubTot, Trail, TrailAr
3.2 Inputs
3.2.1 INP A, INP B
Signal inputs: function acc� to operating mode�
Max� frequency 60 kHz, can be damped in the programming menu to 30 Hz�
●
Pulse counter: Count inputs
●
Timer: Start input or Start/Stop inputs
●
Frequency meter: Frequency inputs
3.2.2 RESET
Dynamic reset input: resets the pulse counter or timer to zero (adding mode)
or to preset value 2 (subtracting mode)� The reset input can be inhibited in the
programming menu�
●
Pulse counter: RESET input
●
Timer: RESET input
●
Frequency meter: no function
3.2.3 GATE
Static gate input: function depending on operating mode�
●
Pulse counter: no counting while active
●
Timer: no time measurement while active (Gate�hi), no time measurement while
not active (Gate�Lo)�
●
Frequency meter: no counting while active
3.2.4 LOCK INPUT
Static keypad lock input for presets or programming� Lock-out level can be set in
the programming menu�
3.2.5 MPI
Input� Programmable as Display Latch, Set or Teach-In input�
Electronic Preset Counter E89005
8
3.3 Outputs
2 relay outputs with potential-free contacts (→ 11.6 Outputs)�
3.3.1 Active Outputs
An active output will be shown on the display�
6 Outputs
6.1
Output 1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2
Output 2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
g
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6
Accepting the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
�
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
�
The security prompt
appears in the display
Seite 6
/
6 Outputs
6.1
Output 1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2
Output 2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
g
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6
Accepting the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
�
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
�
The security prompt
appears in the display
Seite 6
For safety switching the relay outputs can be inverted, i�e� the relay will be
deenergized when the presets are reached� To do this, the parameters Pr�OUT1
and Pr�OUT2 must be set to
6.1
Output 1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2
Output 2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
The sub-menu is opened with the
Prog/Mode key and the first
menu item is displayed.
7.4
Selecting the menu items
The Prog/Mode key is used to
select a menu item within the
sub-menu
7.5
Setting the menu items
The T2 key is used to select the
individual settings for the menu
items
When setting count values, each
decade has a key assigned to it.
Each time the key is pressed,
the value increments by one
7.6
Accepting the setting
Pressing the Prog/Mode key
causes the current setting to be
accepted. Programming then
switches to the next menu item.
7.7
Ending the programming
During programming, it is possible to exit the
programming at each menu item by pressing the
reset key.
Press the Reset key
�
The security prompt
appears in the display
Pressing the Prog/Mode key
acknowledges this prompt and
causes the programming menu
to start again from the beginning.
The previously-programmed
values are preserved. These can
now be changed or checked
again.
Pressing the decade key T2
selects the termination of the
programming
�
The security prompt
appears in the display
Seite 6
(for permanent signal) or
6.1
Output 1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2
Output 2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.4
Se
7.5
Se
7.6
A
7.7
E
During prog
programmin
reset key.
Seite 6
or
6.1
Output 1
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector
6.2
Output 2
Relay with potential-free make (NO) contact or
optocoupler with open emitter and collector.
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
7.4
S
7.5
S
7.6
A
7.7
E
During pro
programm
reset key.
Seite 6
(for timed
signal)� See (→ 2 Safety instructions)�
4 Mounting
CAUTION
Mount the device away from heat sources and avoid direct contact with corrosive
liquids, hot steam or similar�
► Remove mounting clip from the device�
► Insert the device from the front into the panel cut-out, ensuring the front-panel
gasket is correctly seated�
► Slide the fixing clip from the rear onto the housing, until the spring clamps are
under tension and the upper and lower latching lugs have snapped into place�
Electronic Preset Counter E89005
9
5 Electrical connection
WARNING
The device must be disconnected from the power supply, before any installation
or maintenance work is carried out�
AC-powered devices must only be connected to the lowvoltage network via a
switch or circuit breaker�
Installation or maintenance work must only be carried out by qualified personnel�
5.1 Advice on noise immunity
All connections are protected against external sources of interference�
The installation location should be chosen so that inductive or capacitive
interference does not affect the device or its connecting lines! Interference (e�g�
from switchmode power supplies, motors, clocked controllers or contactors) can be
reduced by means of appropriate cable routing and wiring�
Measures to be taken:
► Connect the terminal 2 (GND) with ground�
► Use only shielded cable for signal and control lines�
► Connect cable shield at both ends�
► The conductor cross-section of the cables should be a minimum of 0�4 mm²�
► The shield connection to the equipotential bonding should be as short as
possible and with a contact area as large as possible (low-impedance)�
► Only connect the shields to the control panel, if the latter is also earthed�
► Install the device as far away as possible from noise-containing cables�
► Avoid routing signal or control cables parallel to power lines�
► Cables and their insulation should be in accordance with the intended
temperature and voltage ranges�
Electronic Preset Counter E89005
10
5.2 Connections
9 Connections
9.1
Signal and Control Inputs
N° Designation
Function
1
24 VDC/80 mA
Sensor supply
voltage
2
GND (0 VDC)
Common connection
Signal and Control
inputs
3
INP A
Signal input A
4
INP B
Signal input B
5
RESET
Reset input
6
LOCK
Keypad lock
7
GATE
Gate input
8
MPI
User input
9.2
Supply voltage and Outputs
9.2.1 Version with relays
N° Designation
Function
9
Relay contact C.1
10 Relay contact N.O.1
Output 1
11 Relay contact C.2
12 Relay contact N.O.2
13 Relay contact N.C.2
Output 2
14 AC: 90..260 VAC N~ Supply voltage
15 AC: 90..260 VAC L~
Supply voltage
10 Technical Data
10.1
General Data
Display
LCD positive backlite
2 x 6-digit
Digit height
upper line
9 mm
lower line
7 mm
special characters
2 mm
Overload/
Blinking, 1 s
Underload
Counter loses up to 1 decade
no pulses
Data retention
> 10 years, EEPROM
Operation
8 keys
10.2
Pulse counter
Count frequency max. 55 kHz (see section 13.
frequencies typ.)
Response time of the outputs:
Relays
Add/Sub/Trail
< 7 ms
With automatic repeat
< 7 ms
A/B ; (A-B)/A
< 29 ms
10.3
Tacho/Frequency meter
Frequency range
0,01 Hz to 65 kHz (see
section 13. frequencies typ.)
Measuring
� 76.3 Hz Time interval
principle
(period measurement)
> 76.3 Hz Gate time
Gate time approx.13.1 ms
Measuring error
< 0.1% per channel
Response time of the outputs:
1-channel operation < 100 ms @ 40 kHz
< 350 ms @ 65 kHz
2-channel operation < 150 ms @ 40 kHz
< 600 ms @ 65 kHz
10.4
Timer
Seconds
0.001 s ... 999 999 s
Minutes
0.001 min ... 999 999 min
Hours
0.001 h .. 999 999 h
h.min.s
00h.00min.01s ...
99h.59min.59s
Min. time measurable
500µs
Measuring error
< 50 ppm
Response time of the outputs:
Relays
< 7 ms
Terminals
5.2.1 Signal and control inputs
Terminal
Designation
Function
1
24 V DC / 80 mA
Sensor supply voltage
2
GND (0 VDC)
Common connection signal and control inputs
3
INP A
Signal input A
4
INP B
Signal input B
5
RESET
Reset input
6
LOCK
Keypad lock
7
GATE
Gate input
8
MPI
User input
5.2.2 Supply voltage and outputs
Terminal
Designation
Function
9
Relay contact C1
Output 1
10
Relay contact NO1
11
Relay contact C2
Output 2 (changeover contact)
12
Relay contact NO2
13
Relay contact NC2
Electronic Preset Counter E89005
11
Terminal
Designation
Function
14
90���260 V AC N
Supply voltage
15
90���260 V AC L
NO= normally open
NC = normally closed
C = common
6 Operating and display elements
Frequency meter: A , A � B , A + B , quad , A/B ,
(A-B)/Ax100%
Timer: FrErun , Auto , InpA.InpB , InpB.InpB
Output operations:
Add , Sub , AddAr, SubAr , AddBat , SubBat ,
AddTot , SubTot , Trail , TrailAr
4-stage RESET-Mode
3-stage keypad locking (Lock)
MPI input for Display Latch, Teach-In function or
Set function
Supply voltage 90 .. 260 VAC
4 Display/Operating elements
5.2
RESET
Dynamic reset input: re
timer to zero (adding m
(subtracting mode). The
in the programming me
Pulse counter:
R
Frequency meter:
no
Timer:
R
5.3
GATE
Static gate input: functio
mode.
Pulse counter:
no
Frequency meter:
no
Timer:
no
ac
no
no
5.4
LOCK INPU
Static keypad lock inpu
programming. Lock-out
programming menu.
5.5
MPI
Input. Programmable a
Teach-In input.
R
P
T1-6
Reset key [R]
Prog/Mode key [P]
Decade keys [T���]
8
9
10
11
12
Current count value / main counter
Preset value / Total count / Batch counter
Run display for Timer
Shows which preset value is being displayed
Shows which preset output is active
Pr
Keys necessary for programming the parameters (highlighted in grey)
[R], [P], [T1], [T2]
6.1 Error message
Err 1
Set value is outside the permitted range�
Electronic Preset Counter E89005
12
7 Programming
7.1 Entering the programming
► Press [R] and [P] simultaneously for 3 s
>
The security prompt appears in the display�
Programming can be exited again using [P]�
permanent signal) or
signal).
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
► Press [T2] to continue with the programming�
>
The security prompt appears in the display�
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
► Enter the main menu by pressing [P]�
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7.2 Choice of main menu
► The menus are selected using [T2] (next) and [T1] (back)�
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7.3 Entering a submenu
► The submenu is opened with [P] and the first menu item is
displayed�
or
.
For safety switching the rela
outputs can be inverted, i.e
energized or the optocouple
the presets are reached. To
Pr.OUT1 and Pr.OUT2 mus
permanent signal) or
signal).
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7.4 Selecting the menu items
► [P] is used to select a menu item within the sub-menu�
p
Relay with potential-free ma
optocoupler with open emitt
6.3
Active Output
An active output will be sho
or
.
For safety switching the rela
outputs can be inverted, i.e
energized or the optocouple
the presets are reached. To
Pr.OUT1 and Pr.OUT2 mus
permanent signal) or
signal).
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Electronic Preset Counter E89005
13
7.5 Setting the menu items
► [T2] is used to select the individual settings for the menu
items�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
When setting count values, each decade has a key assigned
to it� Each time the key is pressed, the value increments by
one�
p
p
p
6.3
Active Outputs
An active output will be shown on the display as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
sub menu
7.5
Setting the men
The T2 key
individual se
items
When settin
decade has
Each time th
the value in
7.6
Accepting the se
Pressing the
causes the c
accepted. P
switches to t
7.7
Ending the prog
During programming, it is poss
programming at each menu ite
reset key.
Press the R
�
The
app
Pressing the
acknowledg
causes the p
to start agai
The previou
values are p
now be chan
again.
Pressing the
selects the t
programmin
�
The
app
Seite 6
7.6 Accepting the setting
► Pressing [P] causes the current setting to be accepted�
Programming then switches to the next menu item�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
7.7 Ending the programming
During programming, it is possible to exit the programming at each menu item by
pressing the reset key�
► Press [R]�
>
The security prompt appears in the display�
ac
e ou pu
be s o
o
e d sp ay as
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
The T2 k
individua
items
When se
decade h
Each tim
the value
7.6
Accepting the
Pressing
causes th
accepted
switches
7.7
Ending the pr
During programming, it is p
programming at each menu
reset key.
Press the
�
Pressing
acknowle
causes th
to start a
The prev
values ar
now be c
again.
Pressing
selects th
programm
�
Seite 6
or
.
For safety switching the relays or optocoupler
outputs can be inverted, i.e. the relay will be de-
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
individua
items
When se
decade h
Each tim
the value
7.6
Accepting the
Pressing
causes th
accepted
switches
7.7
Ending the pro
During programming, it is po
programming at each menu
reset key.
Press the
�
Pressing
acknowle
causes th
to start ag
The prev
values ar
now be c
again.
Pressing
selects th
programm
�
Seite 6
► Pressing [P] acknowledges this prompt and causes the
programming menu to start again from the beginning�
>
The previously-programmed values are preserved�
These can now be changed or checked again�
energized or the optocouple
the presets are reached. To
Pr.OUT1 and Pr.OUT2 mus
permanent signal) or
signal).
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
► Pressing [T2] selects the termination of the programming�
>
The security prompt appears in the display�
y
p
optocoupler with open emitt
6.2
Output 2
Relay with potential-free ma
optocoupler with open emitt
6.3
Active Output
An active output will be sho
or
.
For safety switching the rela
outputs can be inverted, i.e
energized or the optocouple
the presets are reached. To
Pr.OUT1 and Pr.OUT2 mus
permanent signal) or
signal).
7 Programming
7.1
Entering the p
Press the
Prog/Mod
for 3 s
�
Program
again usi
Press ke
programm
�
Enter the
the Prog/
7.2
Choice of mai
The men
energized or the optocoupler output disabled when
the presets are reached. To do this, the parameters
Pr.OUT1 and Pr.OUT2 must be set to
(for
permanent signal) or
or
(for timed
signal).
7 Programming
7.1
Entering the programming
Press the Reset key and
Prog/Mode key simultaneously
for 3 s
�
The security prompt
appears in the display
Programming can be exited
again using the Prog/Mode key.
Press key T2 to continue with the
programming
�
The security prompt
appears in the display
Enter the main menu by pressing
the Prog/Mode key
7.2
Choice of main menus
The menus are selected using
the keys T2 (next) and T1 (back)
When se
decade h
Each tim
the value
7.6
Accepting the
Pressing
causes th
accepted
switches
7.7
Ending the pro
During programming, it is po
programming at each menu
reset key.
Press the
�
Pressing
acknowle
causes th
to start ag
The prev
values ar
now be c
again.
Pressing
selects th
programm
�
Seite 6
Electronic Preset Counter E89005
14
► Pressing [P] acknowledges this prompt and terminates the
programming�
>
The modified settings are saved in the EEPROM�
The text SAVE is displayed for 2 s�
�
Enter the
the Prog/
7.2
Choice of mai
The men
the keys
Seite 6
Pressing
acknowle
terminate
modified
the EEPR
�
7.8
Programming
7.8.1 Default paramet
Note: Th
sets hav
stored; th
required
acknowle
paramete
will be re
in the tab
The dEF
freely pro
Menu Pa
Default s
Paramete
Default s
Paramete
Default s
Paramete
Freely pr
User sett
Complete parameter structure and menues see attachement�
Electronic Preset Counter E89005
15
7.8 Setting the presets
7.8.1 Setting via Decade Keys
In programming mode Preset 2 will always be displayed in the lower line� This is
except for the output operations AddBat, SubBat,AddTot and SubTot�
► Press [P] until the preset to be changed is displayed�
(
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ramming mode Preset 2 will always be
ed in the lower line. This is except for the
operations AddBat, SubBat,AddTot and
t.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
value will be accepted and the
counter will switch back to
operating mode.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
6
or
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ogramming mode Preset 2 will always be
ayed in the lower line. This is except for the
ut operations AddBat, SubBat,AddTot and
ot.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
�
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
�
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
value will be accepted and the
counter will switch back to
operating mode.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
16
)
7.9
Setting the pr
7.9.1 Setting via Deca
In programming mode Pres
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Approx. 3
the deca
the Rese
value wil
counter w
operating
Seite 16
► Press any decade key�
>
Display switches to the editor mode�
7.9
Setting the pr
7.9.1 Setting via Deca
In programming mode Pres
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Approx. 3
the deca
the Rese
value wil
counter w
operating
Seite 16
► Set the desired preset value using the decade keys�
7.9.1 Setting via Deca
In programming mode Pres
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Approx. 3
the deca
the Rese
value wil
counter w
operating
Seite 16
► Press [P] to confirm the value and save it�
>
Display switches to the editor mode of the next preset�
(
timed signal at Output 2,
becomes passive with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed output is post-triggered.
Active:
Relay or optocoupler are
activated when the preset value
is reached.
Passive:
Relay becomes de-energized or
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ramming mode Preset 2 will always be
ed in the lower line. This is except for the
operations AddBat, SubBat,AddTot and
t.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
value will be accepted and the
counter will switch back to
operating mode.
7.9.2 Setting with Teach-In Function
Program the MPI input to tEAch
In programming mode, select the
preset to be changed using the
Prog/Mode key
Briefly activate the MPI (NPN or PNP input logic)
�
The current count value will be adopted as
the new preset value
The preset value can subsequently be
further modified via the decade keypad.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
6
or
timed signal at Output 2,
becomes passive with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed output is post-triggered.
Active:
Relay or optocoupler are
activated when the preset value
is reached.
Passive:
Relay becomes de-energized or
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ogramming mode Preset 2 will always be
ayed in the lower line. This is except for the
ut operations AddBat, SubBat,AddTot and
ot.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
�
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
�
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
value will be accepted and the
counter will switch back to
operating mode.
7.9.2 Setting with Teach-In Function
Program the MPI input to tEAch
In programming mode, select the
preset to be changed using the
Prog/Mode key
Briefly activate the MPI (NPN or PNP input logic)
�
The current count value will be adopted as
the new preset value
The preset value can subsequently be
further modified via the decade keypad.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
16
)
7.9.1 Setting via Deca
In programming mode Pres
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Approx. 3
the deca
the Rese
value wil
counter w
operating
Seite 16
>
Approx� 3 s after the last press of the decade keys or by
pressing [R] key the new preset value will be accepted
and the counter will switch back to operating mode�
p
g
g
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Approx. 3
the deca
the Rese
value wil
counter w
operating
Seite 16
7.8.2 Setting via Teach-in function
► Programme the MPI input to tEAch�
Zählerstand < Null passiv und
anschließend bei positiver
Richtung und Zählerstand > Null
passiv
Dauer des Wischsignals von
Ausgang 2, einstellbar von 00.01
bis 99.99 s.
Wischsignal wird nachgetriggert.
Aktiv:
Relais bzw. Optokoppler werden
bei Erreichen des Vorwahlwerts
angesteuert.
Passiv:
Relais wird bei Erreichen des
Vorwahlwert spannungslos bzw.
der Optokoppler gesperrt.
7.9
Vorwahleinstellung
7.9.2 Einstellung mit T
MPI-Eing
programm
Im Betrie
Prog/Mod
ändernde
MPI-Eingang (NPN oder P
kurzzeitig aktivieren
�
der aktuelle Zähle
Vorwahlwert übern
Der Vorwahlwert k
weiter mit den Dek
werden
7.9.3 Einstellung bei S
► Press [P] until the preset to be changed is displayed�
(
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes passive with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed output is post-triggered.
Active:
Relay or optocoupler are
activated when the preset value
is reached.
Passive:
Relay becomes de-energized or
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ramming mode Preset 2 will always be
ed in the lower line. This is except for the
operations AddBat, SubBat,AddTot and
t.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
7.9.2 Setting with Teach-In Function
Program the MPI input to tEAch
In programming mode, select the
preset to be changed using the
Prog/Mode key
Briefly activate the MPI (NPN or PNP input logic)
�
The current count value will be adopted as
the new preset value
The preset value can subsequently be
further modified via the decade keypad.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
or
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes passive with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed output is post-triggered.
Active:
Relay or optocoupler are
activated when the preset value
is reached.
Passive:
Relay becomes de-energized or
the optocoupler disabled when
the preset value is reached.
Setting the presets
Setting via Decade Keys
ogramming mode Preset 2 will always be
ayed in the lower line. This is except for the
ut operations AddBat, SubBat,AddTot and
ot.
Press the Prog/Mode key until
the preset to be changed is
displayed -
or
.
Press any decade key
�
Display switches to the editor mode
Set the desired preset value
using the decade keys
Press the Prog/Mode key to
confirm the value and save it
�
Display switches to the editor mode of the
next preset
or
Approx. 3 s after the last press of
the decade keys or by pressing
the Reset key the new preset
7.9.2 Setting with Teach-In Function
Program the MPI input to tEAch
In programming mode, select the
preset to be changed using the
Prog/Mode key
Briefly activate the MPI (NPN or PNP input logic)
�
The current count value will be adopted as
the new preset value
The preset value can subsequently be
further modified via the decade keypad.
7.9.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the
value for Preset 2 can be set either via the decade
keypad or via the Teach-IN function.
However the value for Preset 1 must be entered via
the decade keypad. In this instance, it is not
possible to use the Teach-In function.
7.10
Set Function
Both the pulse counter and the timer can be set to
a default value by means of the Set function.
Programme the MPI input to SEt
Set menu item SEtPt to the
desired value
Briefly activate the MPI (NPN or PNP input logic)
�
For add. output operations the pulse
counter or timer will be set to the SEtPt
default value
�
For sub. output operations the pulse
counter or timer will be set to the
difference between the value of Preset 2
and the value of SEtPt .
8 Error message
Err 1
Set value is outside the permitted range
)
► Briefly activate the MPI (NPN or PNP input logic)�
>
The current count value will be adopted as the new preset
value�
Zählerstand < Null passiv und
anschließend bei positiver
Richtung und Zählerstand > Null
passiv
Dauer des Wischsignals von
Ausgang 2, einstellbar von 00.01
bis 99.99 s.
Wischsignal wird nachgetriggert.
Aktiv:
Relais bzw. Optokoppler werden
bei Erreichen des Vorwahlwerts
angesteuert.
Passiv:
Relais wird bei Erreichen des
Vorwahlwert spannungslos bzw.
der Optokoppler gesperrt.
7 9
V
hl i
t ll
7.9.2 Einstellung mit T
MPI-Eing
programm
Im Betrie
Prog/Mod
ändernde
MPI-Eingang (NPN oder P
kurzzeitig aktivieren
�
der aktuelle Zähle
Vorwahlwert übern
Der Vorwahlwert k
weiter mit den Dek
werden
7.9.3 Einstellung bei S
► The preset value can subsequently be further modified via
the decade keypad�
SUB mod
timed sig
becomes
direction
and subs
direction
Duration
Output 1
00.01 to
Timed ou
Active:
Relay or
activated
is reache
Passive:
Relay be
the optoc
the prese
7.9
Setting the pr
7.9.1 Setting via Deca
In programming mode Pres
displayed in the lower line.
output operations AddBat, S
SubTot.
Press the
the prese
displayed
Press an
�
Display switches t
Set the d
using the
Press the
confirm t
�
Display switches t
next preset
Electronic Preset Counter E89005
16
7.8.3 Setting the tracking presets (trail)
If a tracking preset has been programmed, the value for Preset 2 can be set either
via the decade keypad or via the Teach-In function�
However the value for Preset 1 must be entered via the decade keypad� In this
instance, it is not possible to use the Teach-In function�
Electronic Preset Counter E89005
17
7.9 Set Function
Both the pulse counter and the timer can be set to a default value by means of the
Set function�
► Programme the MPI input to SEt�
Preset 2 angezeigt. Ausnahme sind die
Ausgangsoperationen AddBat, SubBat,AddTot und
SubTot.
Prog/Mode-Taste betätigen bis
die zu ändernde Vorwahl
oder
angezeigt wird.
Beliebige Dekadentaste
betätigen
�
Anzeige schaltet in den Editiermode
Mit Dekadentasten gewünschten
Vorwahlwert einstellen
Prog/Mode-Taste betätigen um
den Wert zu bestätigen und zu
speichern
�
Anzeige schaltet in den Editiermode der
nächsten Vorwahl
oder
Ca. 3 s nach dem letzten
Betätigen der Dekadentasten
oder durch Betätigen der Reset-
Taste wird der neue Vorwahlwert
übernommen und in den
Betriebsmode zurück geschaltet.
Dekadenschalter eingestellt
Teach-Funktion ausgescha
7.10
Setz-Funktion
Impulszähler und Zeitzähler
Setzfunktion auf einen Wert
MPI-Eing
programm
Menuepu
gewünsc
MPI-Eingang (NPN oder P
kurzzeitig aktivieren
�
Impulszähler bzw.
Ausgangsoperatio
SEtPt voreingeste
Ausgangsoperatio
von Vorwahl 2 und
8 Fehlermeldung
Err 1
Setzwert außerhalb
Bereichs
Seite 16
► Set menu item SEtPt to the desired value�
► Briefly activate the MPI (NPN or PNP input logic)�
>
For add� output operations the pulse counter or timer will
be set to the SEtPt default value�
For sub� output operations the pulse counter or timer will
be set to the difference between the value of Preset 2 and
the value of SEtPt�
Preset 2 angezeigt. Ausnahme sind die
Ausgangsoperationen AddBat, SubBat,AddTot und
SubTot.
Prog/Mode-Taste betätigen bis
die zu ändernde Vorwahl
oder
angezeigt wird.
Beliebige Dekadentaste
betätigen
�
Anzeige schaltet in den Editiermode
Mit Dekadentasten gewünschten
Vorwahlwert einstellen
Prog/Mode-Taste betätigen um
den Wert zu bestätigen und zu
speichern
�
Anzeige schaltet in den Editiermode der
nächsten Vorwahl
oder
Ca. 3 s nach dem letzten
Betätigen der Dekadentasten
oder durch Betätigen der Reset-
Taste wird der neue Vorwahlwert
übernommen und in den
Betriebsmode zurück geschaltet.
Dekadenschalter eingestellt
Teach-Funktion ausgescha
7.10
Setz-Funktion
Impulszähler und Zeitzähler
Setzfunktion auf einen Wert
MPI-Eing
programm
Menuepu
gewünsc
MPI-Eingang (NPN oder P
kurzzeitig aktivieren
�
Impulszähler bzw.
Ausgangsoperatio
SEtPt voreingeste
Ausgangsoperatio
von Vorwahl 2 und
8 Fehlermeldung
Err 1
Setzwert außerhalb
Bereichs
Seite 16
Electronic Preset Counter E89005
18
8 Parameters
8.1 Default parameters
Three default parameter sets have been permanently stored; these can be
adapted as required� With each acknowledgment of the parameter sets, all
parameters will be reset to the values listed in the table�
The default parameter set P�USEr can be freely programmed�
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
rESmd
Man.EL
Man
PrES 1
on
on
Pr.Out 1
t.Out 1
00.1
Pr.Out 2
t.Out 2
00.1
7.8.3 Setting the Basic
Basic funct
Programmi
Pulse coun
Programmi
Timer/Hour
Programmi
Tacho/Freq
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
t.Out 1
Pr.Out 2
t.Out 2
7.8.3 Setti
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are
in grey
8.2 Table: Default Parameter Sets
Display
Description
P.SEt 1
P.SEt 2
P.SET 3
P.USEr
Func
Basic function of the device
Count
Count
Count
Freely programmable
User settings
InP.PoL
Input polarity
PnP
PnP
PnP
FiLtEr
Filter for the signal inputs InpA and InpB
on
oFF
oFF
Count
Count input mode
Cnt�dir
uP�dn
Quad
MPi
User input
LAtch
LAtch
Set
Loc.InP
Lock input
ProG
ProG
ProG
ModE
Mode
Add
Sub
TrAiL
FActor
Multiplication factor
01�0000
01�0000
01�0000
diViSo
Division factor
01�0000
01�0000
01�0000
dP
Decimal point
0
0
0�00
SEtPt
Set value
000000
000000
0000�00
CoLor
Display colour
red�Grn
red�Grn
red�Grn
rESmd
Reset mode
Man�EL
Man�EL
Man�EL
PrES 1
Preset 1
on
on
on
Pr.Out 1
Preset output 1
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
F
i
hi hli h
d
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
english
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
english
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
F
i
hi hli h
d
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
english
t.Out 1
Duration of timed signal of output 1
-
00�10
-
Pr.Out 2
Preset output 2
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
english
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
english
Pressing the Prog/Mode key
acknowledges this prompt and
terminates the programming; the
modified settings are saved in
the EEPROM.
�
The text SAVE is
displayed for 2 s
7.8
Programming Menu
7.8.1 Default parameters
Note: Three default parameter
sets have been permanently
stored; these can be adapted as
required. With each
acknowledgment of the
parameter sets, all parameters
will be reset to the values listed
in the table.
The dEFAuL P.USEr can be
freely programmed.
Menu Parameter Sets
Default setting
Parameter set 1
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
7.8.2 Table: Parameter Sets
P.SEt 1
P.SEt 2
P.SET 3
Func
Count
Count
Count
InP.PoL
PnP
PnP
PnP
FiLtEr
on
oFF
oFF
Count
Cnt.dir
uP.dn
Quad
MPi
LAtch
LAtch
Set
Loc.InP
ProG
ProG
ProG
ModE
Add
Sub
TrAiL
FActor
01.0000
01.0000
01.0000
diViSo
01.0000
01.0000
01.0000
dP
0
0
0.00
SEtPt
000000
000000
0000.00
CoLor
red.Grn
red.Grn
red.Grn
rESmd
Man.EL
Man.EL
Man.EL
PrES 1
on
on
on
Pr.Out 1
t.Out 1
00.10
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
english
t.Out 2
Duration of timed signal of output 1
-
00�10
00�10
factory settings are highlighted in grey
Complete parameter structure and menues see attachement�
Electronic Preset Counter E89005
19
8.3 Setting the basic function of the device
hted
Pr.Out 2
t.Out 2
00.10
00.10
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
Seite 7
ing
set 1
ing
set 2
ing
set 3
rammable
gs
tings are highlighted
7.8.3 Setting the Basic Function
Basic function menu
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
Seite 7
Default setting
Parameter set 2
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
Programming menu
Pulse counter (7.8.4)
Programming menu
Timer/Hour meter (7.8.6)
Programming menu
Tacho/Frequency meter (7.8.5)
Seite 7
Default setting
Parameter set 3
Freely programmable
User settings
Factory settings are highlighted
in grey
Programming menu
Timer/Hour meter (7.
Programming menu
Tacho/Frequency me
Parameters and submenues of the basic functions
●
Pulse counter (→ 8.4)
●
Timer/Hour meter (→ 8.5)
●
Tacho/Frequency meter (→ 8.6)
Electronic Preset Counter E89005
20
8.4 Pulse counter
8.4.1 Input
Submenues for the signal and control inputs�
Display
Description
Submenu
Value
InP.PoL
Input polarity
PnP
PNP: switching to Plus for all inputs in common
nPn
NPN: switching to 0 V for all inputs in common
FiLtEr
Filter for the signal inputs InpA and InpB
oFF
Maximum count frequency
on
Damped to approx� 30 Hz (for control with mechanical contacts)
Count
Count input mode
Cnt.Dir
Count/Direction
INP A: count input
INP B: count direction input
uP.dn
Differential counting [A-B]
INP A: count input add
INP B: count input sub
uP.uP
Totalising [A+B]
INP A: count input add
INP B: count input add
quAd
Quadrature input
INP A: count input 0°
INP B: count input 90°
quA2
Quadrature with pulse doubling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A will be counted
quA4
Quadrature x4
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A and INP B will be counted�
A / B
Ratio measurement [A/B]
Inp A: count input A
Inp B: count input B
A % b
Percentage differential counting
[(A-B) / A in %]
Inp A: count input A
Inp B: count input B
Electronic Preset Counter E89005
21
Display
Description
Submenu
Value
MPi
User input
LAtch
When the MPI input is activated the display is “frozen” and remains “frozen”
until the MPI input is deactivated�
Internally the preset counter continues counting�
tEAch
When the MPI input is activated the current count value for the preset that
has just been selected will be adopted as the new preset value�
SEt
When the MPI input is activated the preset counter will be set to the value
specified in the parameter SEtPt�
Loc.InP
Lock input
ProG
When the lock input is activated the programming is inhibited�
PrESET
When the lock input is activated the setting of the preset values is inhibited�
PrG.PrE
When the lock input is activated the setting of the preset values and the
programming are both inhibited�
factory settings are highlighted in grey
8.4.2 Mode
Submenues for output operations�
Display
Description
Submenu
Value
ModE
Submenu for determining the operation of the outputs
Add
Count mode ADD
Outputs active when count status ≥ preset value
Reset to zero�
Sub
Count mode SUBTRACT
Output 1 active when count status ≤ preset value 1.
Output 2 active when count status ≤ 0.
Reset to preset 2
AddAr
Count mode ADDING with automatic reset
Output 1 active when count status ≥ preset value 1.
Output 2 (timed signal) active when count status = preset value 2�
Automatic reset to zero when count status = preset value 2�
Reset to zero�
SubAr
Count mode SUBTRACTING with automatic reset
Output 1 active when count status ≤ preset value 1.
Output 2 (timed signal) active when count status = 0�
Automatic reset to preset 2 when count status = 0�
Reset to preset 2�
Electronic Preset Counter E89005
22
Display
Description
Submenu
Value
AddbAt
Count mode ADDING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = preset value 2�
Automatic reset to zero when main counter = preset 2�
Batch counter counts the number of automatic repetitions of preset 2�
Output 1 active when Batch counter ≥ preset 1.
Manual reset sets both counters to zero�
Electrical reset only sets the main counter to zero�
SubbAt
Count mode SUBTRACTING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = zero�
Automatic reset to preset 2 when main counter = zero�
Batch counter counts the number of automatic repetitions of preset 2�
Output 1 active when Batch counter ≥ preset 1.
Manual reset sets main counter to preset value 2, batch counter to zero�
Electrical reset only sets the main counter to preset value 2�
Addtot
Count mode ADDING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = preset value 2�
Automatic reset to zero when main counter = preset value 2�
Total counter counts all the count pulses from the main counter�
Output 1 active when total counter ≥ preset value 1.
Manual reset sets both counters to zero�
Electrical reset only sets the main counter to zero�
Subtot
Count mode SUBTRACTING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = zero�
Automatic reset to preset value 2 when main counter = zero�
Total counter counts (sub from preset value 1) all count pulses from main
counter�
Output 1 active when Total counter ≤ zero.
Manual reset sets both counters to the preset values�
Electrical reset sets only main counter to preset value 2�
trAiL
Tracking Preset mode
When preset 2 is changed then preset 1 automatically tracks it�
Reset to zero�
Preset 1 relative to preset 2�
tr_Ar
Tracking Preset mode with automatic reset
When preset 2 is changed then preset 1 automatically tracks it�
Reset to zero�
Automatic reset to zero when main counter = preset value�
factory settings are highlighted in grey
Electronic Preset Counter E89005
23
8.4.3 Config
Submenues for matching the input pulses and display�
Display
Description
Submenu
Value
FActor
Multiplication factor
01.0000
Factory setting
00.0001...
99.9999
Multiplication factor can be programmed from 00�0001 to 99�9999�
The setting 00�0000 will not beaccepted�
diViSo
Division factor
01.0000
Factory setting
01.0000...
99.9999
Division factor can be programmed from 01�0000 to 99�9999�
The setting < 01�0000 will not be accepted�
dp
Decimal point setting (only optical function)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
0.0000
4 decimal places
0.00000
5 decimal places
SetPt
Set value
000000
Factory setting
000000...
999999
Set value can be programmed from 000000 to 999999�
A previously programmed decimal point will be displayed�
CoLor
Display colour (not supported)
rEd
Upper line red�
Lower line red�
rEdGrn
Upper line red
Lower line green
factory settings are highlighted in grey
Electronic Preset Counter E89005
24
8.4.4 Reset mode
Submenues for reset mode�
Display
Description
Submenu
Value
rESmd
Setting the reset mode
Man.EL
Manual reset (with red key) and electrical reset (reset input)�
no rES
No reset possible (red key and reset input inhibited)�
EL.rEs
Only electrical reset possible (reset input)�
MAnrE
Only manual reset possible (red key)�
factory settings are highlighted in grey
8.4.5 Preset 1
Submenues for preset 1�
Display
Description
Submenu
Value
PrES 1
Submenu for turning preset 1 ON/OFF
on
Preset 1 ON
off
Preset 1 OFF and no function
Pr.Out 1
Preset output 1
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes active when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes active when count ≤ Preset 1
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes passive when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes passive when count ≤ Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
P
t 2 (D
ti
ti
l i
english
ADD mode output operations:
timed signal at Output 1, becomes active when count ≥ Preset 1.
(Activation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes active when count ≤ Preset 1
(Activation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
P
t 2 (D
ti
ti
l i
english
ADD mode output operations:
timed signal at Output 1, becomes passive when count ≥ Preset 1.
(Deactivation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes passive when count ≤ Preset 1.
(Deactivation only in negative direction)
Electronic Preset Counter E89005
25
Display
Description
Submenu
Value
g
)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes active with positive direction and when
count ≥ Preset 1 and subsequently active with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed signal at Output 1, becomes active with negative direction and when
count ≤ Preset 1 and subsequently active with positive direction and when
count ≥ Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes passive with positive direction and when
count ≥ Preset 1 and subsequently passive with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed output at Output 1, becomes passive with negative direction and when
count ≤ Preset 1 and subsequently passive with positive direction and when
count ≥ Preset 1
t.Out 1
Duration of timed signal of Output 1
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
8.4.6 Preset 2
Submenues for preset 2�
Display
Description
Submenu
Value
PrES 2
Submenu for Preset 2
Pr.Out 2
Preset output 2
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes active when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes passive when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
english
ADD mode output operations:
timed signal at Output 2, becomes active when count ≥ Preset 2
(Activation only in positive direction)�
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
(Activation only in negative direction)
Electronic Preset Counter E89005
26
Display
Description
Submenu
Value
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes passive when count ≥ Preset 2
(Deactivation only in positive direction)
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
(Deactivation only in negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes active with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes active with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
p
p
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes passive with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes passive with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
t.Out 2
Duration of timed signal of Output 2
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
Active: Relay is activated when the preset value is reached�
Passive: Relay becomes de-energized when the preset value is reached�
Electronic Preset Counter E89005
27
8.5 Timer
8.5.1 Input
Submenues for the signal and control inputs�
Display
Description
Submenu
Value
InP.PoL
Input polarity
PnP
PNP: switching to Plus for all inputs in common
nPn
NPN: switching to 0 V for all inputs in common
FiLtEr
Filter for the signal inputs InpA and InpB
oFF
For electronic control of the signal inputs�
on
For mechanical control of the signal inputs (for control with mechanical
contacts)�
StArt
Input mode time measurement
InA.Inb
Start: Edge to Inp A
Stop: Edge to Inp B
Inb.Inb
Start: 1� Edge to Inp B
Stop: 2� Edge to Inp B
FrErun
Timing can only be controlled via the Gate input�
Inp A and Inp B: no function�
Auto
The timer is reset by means of a RESET (to zero when adding, to preset 2
when subtracting) and then starts timing again�
Timing is stopped with adding operations when preset 2 is reached�
Timing is stopped with subtracting operations when zero is reached�
A RESET during the timing process also causes this to stop�
Inp A and Inp B: no function�
GAtE
Gate control for timing
GAtE.Lo
Timing takes place when the Gate input is not active�
GAtE.hi
Timing takes place when the Gate input is active�
MPi
User input
LAtch
When the MPI input is activated the display is “frozen” and remains “frozen”
until the MPI input is deactivated�
Internally the preset counter continues counting�
tEAch
When the MPI input is activated the current count value for the preset that
has just been selected will be adopted as the new preset value�
SEt
When the MPI input is activated the preset counter will be set to the value
specified in the parameter SEtPt�
Electronic Preset Counter E89005
28
Display
Description
Submenu
Value
Loc.InP
Lock input
ProG
When the lock input is activated the programming is inhibited�
PrESET
When the lock input is activated the setting of the preset values is inhibited�
PrG.PrE
When the lock input is activated the setting of the preset values and the
programming are both inhibited�
factory settings are highlighted in grey
8.5.2 Mode
Submenues for output operations�
Display
Description
Submenu
Value
ModE
Submenu for determining the operation of the outputs
Add
Count mode ADD
Outputs active when count status ≥ preset value
Reset to zero�
Sub
Count mode SUBTRACT
Output 1 active when count status ≤ preset value 1.
Output 2 active when count status ≤ 0.
Reset to preset 2
AddAr
Count mode ADDING with automatic reset
Output 1 active when count status ≥ preset value 1.
Output 2 (timed signal) active when count status = preset value 2�
Automatic reset to zero when count status = preset value 2�
Reset to zero�
SubAr
Count mode SUBTRACTING with automatic reset
Output 1 active when count status ≤ preset value 1.
Output 2 (timed signal) active when count status = 0�
Automatic reset to preset 2 when count status = 0�
Reset to preset 2�
AddbAt
Count mode ADDING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = preset value 2�
Automatic reset to zero when main counter = preset 2�
Batch counter counts the number of automatic repetitions of preset 2�
Output 1 active when Batch counter ≥ preset 1.
Manual reset sets both counters to zero�
Electrical reset only sets the main counter to zero�
Electronic Preset Counter E89005
29
Display
Description
Submenu
Value
SubbAt
Count mode SUBTRACTING with automatic reset and Batch counter
Output 2 (timed signal) active when main counter = zero�
Automatic reset to preset 2 when main counter = zero�
Batch counter counts the number of automatic repetitions of preset 2�
Output 1 active when Batch counter ≥ preset 1.
Manual reset sets main counter to preset value 2, batch counter to zero�
Electrical reset only sets the main counter to preset value 2�
Addtot
Count mode ADDING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = preset value 2�
Automatic reset to zero when main counter = preset value 2�
Total counter counts all the count pulses from the main counter�
Output 1 active when total counter ≥ preset value 1.
Manual reset sets both counters to zero�
Electrical reset only sets the main counter to zero�
Subtot
Count mode SUBTRACTING with automatic reset and Total counter
Output 2 (timed signal) active when main counter = zero�
Automatic reset to preset value 2 when main counter = zero�
Total counter counts (sub from preset value 1) all count pulses from main
counter�
Output 1 active when Total counter ≤ zero.
Manual reset sets both counters to the preset values�
Electrical reset sets only main counter to preset value 2�
trAiL
Tracking Preset mode
When preset 2 is changed then preset 1 automatically tracks it�
Reset to zero�
Preset 1 relative to preset 2�
tr_Ar
Tracking Preset mode with automatic reset
When preset 2 is changed then preset 1 automatically tracks it�
Reset to zero�
Automatic reset to zero when main counter = preset value�
factory settings are highlighted in grey
Electronic Preset Counter E89005
30
8.5.3 Config
Submenues for matching the input pulses and display�
Display
Description
Submenu
Value
tModE
Unit of time
SEC
Unit of time: seconds
Decimal point setting determines the resolution�
Min
Unit of time: minutes
Decimal point setting determines the resolution�
hour
Unit of time: hours
Decimal point setting determines the resolution�
h.Min.S
Unit of time: Hrs� Min� Sec�
dp
Decimal point setting (only optical function)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
SetPt
Set value
000000
Factory setting
000000...
999999
Set value can be programmed from 000000 to 999999�
A previously programmed decimal point will be displayed�
CoLor
Display colour (not supported)
rEd
Upper line red�
Lower line red�
rEdGrn
Upper line red
Lower line green
factory settings are highlighted in grey
8.5.4 Reset mode
Submenues for reset mode�
Display
Description
Submenu
Value
rESmd
Setting the reset mode
Man.EL
Manual reset (with red key) and electrical reset (reset input)�
no rES
No reset possible (red key and reset input inhibited)�
EL.rEs
Only electrical reset possible (reset input)�
MAnrE
Only manual reset possible (red key)�
factory settings are highlighted in grey
Electronic Preset Counter E89005
31
8.5.5 Preset 1
Submenues for preset 1�
Display
Description
Submenu
Value
PrES 1
Submenu for turning preset 1 ON/OFF
on
Preset 1 ON
off
Preset 1 OFF and no function
Pr.Out 1
Preset output 1
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
o ese poss b e ( ed ey a d
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes active when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes active when count ≤ Preset 1
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
p
)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes passive when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes passive when count ≤ Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 1, becomes active when count ≥ Preset 1.
(Activation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes active when count ≤ Preset 1
(Activation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 1, becomes passive when count ≥ Preset 1.
(Deactivation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes passive when count ≤ Preset 1.
(Deactivation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes active with positive direction and when
count ≥ Preset 1 and subsequently active with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed signal at Output 1, becomes active with negative direction and when
count ≤ Preset 1 and subsequently active with positive direction and when
count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes passive with positive direction and when
count ≥ Preset 1 and subsequently passive with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed output at Output 1, becomes passive with negative direction and when
count ≤ Preset 1 and subsequently passive with positive direction and when
count ≥ Preset 1
Electronic Preset Counter E89005
32
Display
Description
Submenu
Value
t.Out 1
Duration of timed signal of Output 1
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
8.5.6 Preset 2
Submenues for preset 2�
Display
Description
Submenu
Value
PrES 2
Submenu for Preset 2
Pr.Out 2
Preset output 2
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
p y
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes active when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
pp
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes passive when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
english
ADD mode output operations:
timed signal at Output 2, becomes active when count ≥ Preset 2
(Activation only in positive direction)�
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
(Activation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
english
ADD mode output operations:
timed signal at Output 2, becomes passive when count ≥ Preset 2
(Deactivation only in positive direction)
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
(Deactivation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
english
ADD mode output operations:
timed signal at Output 2, becomes active with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes active with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
Electronic Preset Counter E89005
33
Display
Description
Submenu
Value
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes passive with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes passive with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
t.Out 2
Duration of timed signal of Output 2
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
Active: Relay is activated when the preset value is reached�
Passive: Relay becomes de-energized when the preset value is reached�
Electronic Preset Counter E89005
34
8.6 Tacho/Frequency meter
8.6.1 Input
Submenues for the signal and control inputs�
Display
Description
Submenu
Value
InP.PoL
Input polarity
PnP
PNP: switching to Plus for all inputs in common
nPn
NPN: switching to 0 V for all inputs in common
FiLtEr
Filter for the signal inputs InpA and InpB
oFF
Maximum count frequency
on
Damped to approx� 30 Hz (for control with mechanical contacts)
InPut
Input mode frequency feasurement
A
Simple frequency measurement
Inp A: frequency input
Inp B: no function
ASub b
Differential measurement [A-B]
Inp A: frequency input A
Inp B: frequency input B
AAdd b
Total measurement [A+B]
Inp A: Frequency input A
Inp B: Frequency input B
quAd
Frequency measurement with direction recognition [Quad]
Inp A: Frequency input 0°
Inp B: Frequency input 90°
A / B
Ratio measurement [A/B]
Inp A: Frequency input A
Inp B: Frequency input B
A % b
Percentage differential measurement [(A-B) / A in %]
Inp A: Frequency input A
Inp B: Frequency input B
MPi
User input
LAtch
When the MPI input is activated the display is “frozen” and remains “frozen”
until the MPI input is deactivated�
Internally the frequency meter continues running�
tEAch
When the MPI input is activated the current frequency for the preset that has
just been selected will be adopted as the new preset value�
Electronic Preset Counter E89005
35
Display
Description
Submenu
Value
Loc.InP
Lock input
ProG
When the lock input is activated the programming is inhibited�
PrESET
When the lock input is activated the setting of the preset values is inhibited�
PrG.PrE
When the lock input is activated the setting of the preset values and the
programming are both inhibited�
factory settings are highlighted in grey
8.6.2 Config
Submenues for matching the input pulses and display�
Display
Description
Submenu
Value
FActor
Multiplication factor
01.0000
Factory setting
00.0001...
99.9999
Multiplication factor can be programmed from 00�0001 to 99�9999�
The setting 00�0000 will not beaccepted�
diViSo
Division factor
01.0000
Factory setting
01.0000...
99.9999
Division factor can be programmed from 01�0000 to 99�9999�
The setting < 01�0000 will not be accepted�
tModE
Display mode (time mode)
SEC -1
Calculation and display of the frequency or speed in 1/s�
Min -1
Calculation and display of the frequency or speed in 1/min�
dp
Decimal point setting (only optical function)�
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
AVG
Moving average
oFF
Moving average off
AVG 2
Moving average on, calculated over 2 measurements�
AVG 5
Moving average on, calculated over 5 measurements�
AVG 10
Moving average on, calculated over 10 measurements�
AVG 20
Moving average on, calculated over 20 measurements�
Electronic Preset Counter E89005
36
Display
Description
Submenu
Value
StArt
Start delay
00.0
Factory setting
00.0...99.9
Programmable from 00�0 to 99�9 s�
At the start of a measurement the measurement results within this time-
period are ignored�
WAit0
Waiting time
00.1
Factory setting
00.1...99.0
Programmable from 00�1 to 99�9 s�
This value specifies how much time should elapse, after the last valid edge,
before zero is to be displayed�
CoLor
Display colour (not supported)
rEd
Upper line red�
Lower line red�
rEdGrn
Upper line red
Lower line green
factory settings are highlighted in grey
8.6.3 Preset 1
Submenues for preset 1�
Display
Description
Submenu
Value
PrES 1
Submenu for turning preset 1 ON/OFF
on
Preset 1 ON
off
Preset 1 OFF and no function
Pr.Out 1
Preset output 1
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes active when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes active when count ≤ Preset 1
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 1, becomes passive when count ≥ Preset 1
SUB mode output operations:
permanent signal at Output 1, becomes passive when count ≤ Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
b
i
h
t
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
english
ADD mode output operations:
timed signal at Output 1, becomes active when count ≥ Preset 1.
(Activation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes active when count ≤ Preset 1
(Activation only in negative direction)
Electronic Preset Counter E89005
37
Display
Description
Submenu
Value
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 1, becomes passive when count ≥ Preset 1.
(Deactivation only in positive direction)
SUB mode output operations:
timed output at Output 1, becomes passive when count ≤ Preset 1.
(Deactivation only in negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes active with positive direction and when
count ≥ Preset 1 and subsequently active with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed signal at Output 1, becomes active with negative direction and when
count ≤ Preset 1 and subsequently active with positive direction and when
count ≥ Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output1, becomes passive with positive direction and when
count ≥ Preset 1 and subsequently passive with negative direction and when
count ≤ Preset 1
SUB mode output operations:
timed output at Output 1, becomes passive with negative direction and when
count ≤ Preset 1 and subsequently passive with positive direction and when
count ≥ Preset 1
t.Out 1
Duration of timed signal of Output 1
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
8.6.4 Preset 2
Submenues for preset 2�
Display
Description
Submenu
Value
PrES 2
Submenu for Preset 2
Pr.Out 2
Preset output 2
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes active when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
eset mode
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero
Preset 1 relative to preset 2 (see
also section 17. Output
operations)
Tracking Preset mode with
automatic reset
When preset 2 is changed then
preset 1 automatically tracks it.
Reset to zero.
Automatic reset to zero when
main counter = preset value 2.
Preset 1 relative to Preset 2
(see also section 17. Output
operations)
Submenu for configuration
Submenu for matching the time
ranges and display
Unit of time
Unit of time: seconds
Decimal point setting determines
the resolution
Unit of time: minutes
Decimal point setting determines
the resolution
Unit of time: hours
Decimal point setting determines
the resolution
Unit of time: Hrs. Min. Sec.
nt setting (Resolution)
Decimal place
(determines the resolution)
0
no decimal place
0.0
1 decimal place
0.00
2 decimal places
0.000
3 decimal places
Set value can be programmed
from 000000 to 999999
A previously programmed
decimal point will be displayed
Display colour (for 6.92x.x1x3.xx0]
Display colour
upper line
red
lower line
red
Display colour
upper line
red
lower line
green
7.8.6.4 Submenu for reset mode
Setting the reset mode
Manual reset (with red key) and
electrical reset (reset input)
No reset possible (red key and
reset input inhibited)
Only electrical reset possible
(reset input)
Only manual reset possible (red
key)
7.8.6.5 Submenu for Preset 1
Submenu for turning preset 1
ON/OFF
Preset 1 ON
Preset 1 OFF and no function
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes active when count <
Preset 1
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
ADD mode output operations:
permanent signal at Output 2, becomes passive when count ≥ Preset 2
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
Electronic Preset Counter E89005
38
Display
Description
Submenu
Value
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes active when count ≥ Preset 2
(Activation only in positive direction)�
SUB mode output operations:
permanent signal at Output 2, becomes active when count ≤ zero
(Activation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes passive when count ≥ Preset 2
(Deactivation only in positive direction)
SUB mode output operations:
permanent signal at Output 2, becomes passive when count ≤ zero
(Deactivation only in negative direction)
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes active with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes active with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1. (Activation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (Activation only in
negative direction)
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1. (Deactivation only in
positive direction)
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1. (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
with positive direction and when
count > Preset 1
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1, programmable from
00.01 to 99.99 s.
Timed signal is post-triggered
7.8.6.6 Submenu for Preset 2
Submenu for Preset 2
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (Activation only in
positive direction).
SUB mode output operations:
permanent signal at Output 2,
becomes active when count <
zero (Activation only in negative
direction)
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (Deactivation only in
positive direction)
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero (Deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output 2,
becomes active with positive
direction and when count >
Preset 2 and subsequently with
negative direction and when
count < Preset 2
SUB mode output operations:
timed signal at Output 2,
becomes active with negative
direction and when count < zero
and subsequently with positive
direction and when count > zero
ADD mode output operations:
timed signal at Output 2,
becomes passive with positive
direction and when count >
english
Seite 15
ADD mode output operations:
timed signal at Output 2, becomes passive with positive direction and when
count ≥ Preset 2 and subsequently with negative direction and when count
≤ Preset 2
SUB mode output operations:
timed signal at Output 2, becomes passive with negative direction and when
count ≤ zero and subsequently with positive direction and when count ≥ zero
t.Out 2
Duration of timed signal of Output 2
Timed signal is post-triggered
00.01
Factory setting
00.01...
99.99
Programmable from 00�01 to 99�99 s
factory settings are highlighted in grey
Active: Relay is activated when the preset value is reached�
Passive: Relay becomes de-energized when the preset value is reached�
Electronic Preset Counter E89005
39
9 Diagrams
9.1 Input modes
9.1.1 Pulse counting
Function
Diagram
Cnt.Dir
14 Input modes: Pulse counting
Function
Diagram
Note: No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Cnt.Dir
Inp A: Count input
Inp B: Count direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Dn
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Up
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 --> Preset
Quad
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Quad 2
A 90° B
Inp A: Count input
Count on rising and on falling
edges
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 20
Inp A: Count input
Inp B: Count direction
Add: Display 0 → Preset
Sub: Display Preset → 0
Up.Dn
14 Input modes: Pulse counting
Function
Diagram
Note: No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Cnt.Dir
Inp A: Count input
Inp B: Count direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Dn
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Up
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 --> Preset
Quad
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Quad 2
A 90° B
Inp A: Count input
Count on rising and on falling
edges
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 20
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 → Preset
Sub: Display Preset → 0
Up.Up
14 Input modes: Pulse counting
Function
Diagram
Note: No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Cnt.Dir
Inp A: Count input
Inp B: Count direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Dn
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Up
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 --> Preset
Quad
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Quad 2
A 90° B
Inp A: Count input
Count on rising and on falling
edges
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 20
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 → Preset
Quad
14 Input modes: Pulse counting
Function
Diagram
Note: No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Cnt.Dir
Inp A: Count input
Inp B: Count direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Dn
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Up
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 --> Preset
Quad
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Quad 2
A 90° B
Inp A: Count input
Count on rising and on falling
edges
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 20
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 → Preset
Sub: Display Preset → 0
Quad 2
14 Input modes: Pulse counting
Function
Diagram
Note: No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Cnt.Dir
Inp A: Count input
Inp B: Count direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Dn
Inp A: Count input add
Inp B: Count input sub
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Up.Up
Inp A: Count input 1 add
Inp B: Count input 2 add
Add: Display 0 --> Preset
Quad
A 90° B
Inp A: Count input
Count on one edge
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Quad 2
A 90° B
Inp A: Count input
Count on rising and on falling
edges
Inp B: Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 20
A 90° B
Inp A: Count input
Count on rising and on
falling edges
Inp B: Reverse direction
Add: Display 0 → Preset
Sub: Display Preset → 0
Electronic Preset Counter E89005
40
Function
Diagram
Quad 4
Function
Diagram
Note: No counting when GATE input is active
PNP: Count on rising edge
NPN: Count on falling edge
Quad 4
A 90° B
Inp A: Count input
Count on rising and on
falling edges
Inp B: Count input
Count on rising and on
falling edges,
Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
A / B
Inp A: Count input 1
Inp B: Count input 2
Formula:
A / B
(A-B)/A
Inp A: Count input 1
Inp B: Count input 2
Formula:
(A � B)/A x100
english
Seite 21
A 90° B
Inp A: Count input
Count on rising and on
falling edges
Inp B: Count input
Count on rising and on
falling edges,
Reverse direction
Add: Display 0 → Preset
Sub: Display Preset → 0
A / B
Function
Diagram
Note: No counting when GATE input is active
PNP: Count on rising edge
NPN: Count on falling edge
Quad 4
A 90° B
Inp A: Count input
Count on rising and on
falling edges
Inp B: Count input
Count on rising and on
falling edges,
Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
A / B
Inp A: Count input 1
Inp B: Count input 2
Formula:
A / B
(A-B)/A
Inp A: Count input 1
Inp B: Count input 2
Formula:
(A � B)/A x100
english
Seite 21
Inp A: Count input 1
Inp B: Count input 2
Formula:
A/B
(A-B)/A
Function
Diagram
Note: No counting when GATE input is active
PNP: Count on rising edge
NPN: Count on falling edge
Quad 4
A 90° B
Inp A: Count input
Count on rising and on
falling edges
Inp B: Count input
Count on rising and on
falling edges,
Reverse direction
Add: Display 0 --> Preset
Sub: Display Preset -> 0
A / B
Inp A: Count input 1
Inp B: Count input 2
Formula:
A / B
(A-B)/A
Inp A: Count input 1
Inp B: Count input 2
Formula:
(A � B)/A x100
english
Seite 21
Inp A: Count input 1
Inp B: Count input 2
Formula:
(A-B)/A x100
No counting when GATE input is active
P = Preset
PNP: Count on rising edge
NPN: Count on falling edge
Electronic Preset Counter E89005
41
9.1.2 Timing
Function
Diagram
InA.InB
15 Input modes: Timing
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
InA.InB
Inp A: Start
Inp B: Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
InB.InB
Inp A: no function
Inp B: Start/Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
FrRrun
Inp A: no function
Inp B: no function
Control of the timing only
via the GATE input
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Auto
Inp A: no function
Inp B: no function
Control of the timing via
RESET (manual or
electrical)
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 22
Inp A: Start
Inp B: Stop
Add: Display 0 → Preset
Sub: Display Preset → 0
InB.InB
15 Input modes: Timing
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
InA.InB
Inp A: Start
Inp B: Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
InB.InB
Inp A: no function
Inp B: Start/Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
FrRrun
Inp A: no function
Inp B: no function
Control of the timing only
via the GATE input
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Auto
Inp A: no function
Inp B: no function
Control of the timing via
RESET (manual or
electrical)
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 22
Inp A: no function
Inp B: Start/Stop
Add: Display 0 → Preset
Sub: Display Preset → 0
FrRrun
15 Input modes: Timing
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
InA.InB
Inp A: Start
Inp B: Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
InB.InB
Inp A: no function
Inp B: Start/Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
FrRrun
Inp A: no function
Inp B: no function
Control of the timing only
via the GATE input
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Auto
Inp A: no function
Inp B: no function
Control of the timing via
RESET (manual or
electrical)
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 22
Inp A: no function
Inp B: no function
Control of the timing only via
the GATE input
Add: Display 0 → Preset
Sub: Display Preset → 0
Auto
15 Input modes: Timing
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
InA.InB
Inp A: Start
Inp B: Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
InB.InB
Inp A: no function
Inp B: Start/Stop
Add: Display 0 --> Preset
Sub: Display Preset -> 0
FrRrun
Inp A: no function
Inp B: no function
Control of the timing only
via the GATE input
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Auto
Inp A: no function
Inp B: no function
Control of the timing via
RESET (manual or
electrical)
Add: Display 0 --> Preset
Sub: Display Preset -> 0
Seite 22
Inp A: no function
Inp B: no function
Control of the timing via RESET
(manual or electrical)
Add: Display 0 → Preset
Sub: Display Preset → 0
PNP: Count on rising edge
NPN: Count on falling edge
Electronic Preset Counter E89005
42
9.1.3 Frequency meter
Function
Diagram
A
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
Inp A: Frequency input
Inp B: no function
AsubB
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A-B
AaddB
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A+B
Quad
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A/B
(A-B)/A
16 Input modes: Frequency meter
Function
Diagram
PNP: Count on rising edge
NPN: Count on falling edge
A
Inp A: Frequency input
Inp B: no function
AsubB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A - B
AaddB
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A + B
Quad
A 90° B
Inp A: Frequency input 1
Inp B: Reverse direction
A / B
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
A / B
(A-B)/A
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A � B)/A x100
english
Seite 23
Inp A: Frequency input 1
Inp B: Frequency input 2
Formula:
(A-B)/A x100
PNP: Count on rising edge
NPN: Count on falling edge
Electronic Preset Counter E89005
43
9.2 Output operations
9.2.1 Add modes
Mode
Diagram
Add
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
AddAr
SubAr
AddBat
SubBat
AddTot
SubTot
Seite 24
AddAr
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
AddAr
SubAr
AddBat
SubBat
AddTot
SubTot
Seite 24
AddBat
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
AddAr
SubAr
AddBat
SubBat
AddTot
SubTot
Seite 24
AddTot
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
AddAr
SubAr
AddBat
SubBat
AddTot
SubTot
Seite 24
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
only in this modes
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
/
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
Mode
Diagram
Additionally in the mode
and
Sub
additionally in this modes
put operations
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Sub
/
t operations
gram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Sub
Electronic Preset Counter E89005
44
9.2.2 Sub modes
Mode
Diagram
Sub
Mode
Diagram
and
Additionally in the mode
and
Sub
SubAr
SubBat
SubTot
SubAr
Mode
Diagram
and
Additionally in the mode
and
Sub
SubAr
SubBat
SubTot
SubBat
Mode
Diagram
and
Additionally in the mode
and
Sub
SubAr
SubBat
SubTot
SubTot
Mode
Diagram
and
Additionally in the mode
and
Sub
SubAr
SubBat
SubTot
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
only in this modes
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
/
17 Output operations
Mode
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Add
Sub
Mode
Diagram
Additionally in the mode
and
Sub
additionally in this modes
put operations
Diagram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Sub
/
t operations
gram
Mode
Diagram
Only in the mode
and
Additionally in the mode
and
Sub
Electronic Preset Counter E89005
45
9.2.3 Trail modes
Mode
Diagram
Trail
Mode
Diagram
Trail
TrailAr
Seite
TrailAr
Mode
Diagram
Trail
TrailAr
Seite
Electronic Preset Counter E89005
46
10 Dimensions
18 Dimensional Drawings
Panel cut-out
Seite 26
E89005
18 Dimensional Drawings
Panel cut-out
Seite 26
Panel cut-out
Electronic Preset Counter E89005
47
11 Technical data
11.1 General Data
Display
LCD positive backlite, 2 x 6-digit
Digit height
Upper line
9 mm
Lower line
7 mm
Special characters
2 mm
Overload
Blinking, 1 s
Underload
Counter loses up to 1 decade, no pulses
Data retention
> 10 years, EEPROM
Operation
8 keys
11.2 Pulse counter
Count frequency
max� 55 kHz
Response time of the relay outputs
Add/Sub/Trail
< 7 ms
With automatic repeat
< 7 ms
A/B; (A-B)/A
< 29 ms
Frequencies (typical)
13 Frequencies (typical)
13.1
Pulse counter
HTL level
AC supply
typ. Low
2,5 V
typ. High
22 V
Add
Sub
Trail
AddAr
SubAr
AddBat
SubBat
TrailAr
AddTot
SubTot
Cnt.Dir
55 kHz
2,8 kHz
2,7 kHz
Up.Dn
Up.Up
29 kHz
2,8 kHz
2,7 kHz
Quad
Quad 2
28 kHz
1,4 kHz
1,3 kHz
Quad 4
18 kHz
1,2 kHz
0,9 kHz
A/B
(A-B)/A
29 kHz
13.2
Frequency meter
HTL level
AC supply
typ. Low
2,5 V
typ. High
22 V
HTL
5V
A
65 kHz
9 kHz
A � B
A + B
A / B
65 kHz
9 kHz
english
11.3 Tacho/Frequency meter
Frequency range
0,01 Hz to 65 kHz
Measuring principle
≤ 76.3 Hz time interval (period measurement)
> 76�3 Hz gate time (gate time approx�13�1 ms)
Measuring error
< 0�1 % per channel
Electronic Preset Counter E89005
48
Response time of the relay outputs
1-channel operation
< 100 ms @ 40 kHz
< 350 ms @ 65 kHz
2-channel operation
< 150 ms @ 40 kHz
< 600 ms @ 65 kHz
Frequencies (typical)
Up.Up
29 kHz
2,8 kHz
2,7 kHz
Quad
Quad 2
28 kHz
1,4 kHz
1,3 kHz
Quad 4
18 kHz
1,2 kHz
0,9 kHz
A/B
(A-B)/A
29 kHz
13.2
Frequency meter
HTL level
AC supply
typ. Low
2,5 V
typ. High
22 V
HTL
5V
A
65 kHz
9 kHz
A � B
A + B
A / B
(A-B)/A
65 kHz
9 kHz
Quad
30 kHz
9 kHz
NOTE: Switching levels of the input
Switching levels with AC supply:
HTL level
Low:
0 .. 4 VDC
High:
12 .. 30 VDC
english
Seite 19
11.4 Timer
Seconds
0�001���999 999 s
Minutes
0�001���999 999 min
Hours
0�001���999 999 h
h�min�s
00h�00min�01s���99h�59min�59s
Min� time measurable
500 μs
Measuring error
< 50 ppm
Response time of the relay outputs
< 7 ms
11.5 Signal and Control inputs
Polarity
programmable NPN/PNP (for all inputs in common)
Input resistance
5 kΩ
Pulse shape
any
Switching level with AC supply
HTL level Low
0���4 V DC
HTL level High
12���30 V DC
Min� pulse length of the reset input
1 ms
Min� pulse length of the control inputs
10 ms
11.6 Outputs
11.6.1 Output 1
Type
relay with make contact, programmable as NC or NO
Switching voltage
max� 250 V AC / 110 V DC
Electronic Preset Counter E89005
49
Switching current
max� 3 A AC / DC
min� 30 mA DC
Switching capacity
max� 750 VA / 90 W
Mechanical switching cycles
2 x 107
N° of switching cycles
1 x 105 (at 3 A / 250 V AC)
N° of switching cycles
1 x 105 (at 3 A / 30 V DC)
11.6.2 Output 2
Type
relay with changeover contact
Switching voltage
max� 250 V AC/ 150 V DC
Switching current
max� 3 A AC / DC
min� 30 mA DC
Switching capacity
max� 750 VA / 90 W
Mechanical switching cycles
2 x 106
N° of switching cycles
5 x 104 (at 3 A / 250 V AC)
N° of switching cycles
5 x 104 (at 3 A / 30 V DC)
11.7 Supply voltage
Supply voltage
90���260 V AC, max� 8 VA
Frequency
50���60 Hz
Ext� fuse protection
T 0�1 A
11.8 Sensor supply
Sensor supply voltage
24 V DC, ± 15%
Current
80 mA
11.9 Climatic Conditions
Operating temperature
-20���65 °C
Storage temperature
-25���75 °C
Relative humidity
93 % at 40 °C, non-condensing
Altitude
to 2000 m
11.10 EMC
Noise immunity
EN 61000-6-2 with shielded signal and control cables
Noise emission
EN 55011 Class B
Electronic Preset Counter E89005
50
11.11 Device safety
Design to
EN 61010 Part 1
Protection Class
2
Application area
Soiling Level 2
11.12 Mechanical Data
Housing
panel-mount housing to DIN 43 700, RAL 7021
Dimensions
48 x 48 x 91 mm
Panel cut-out
45+0,6 x 45+0,6 mm
Installation depth
ca� 107 mm incl� terminals
Weight
ca� 125 g
Protection
IP 65 (front)
Housing material
Polycarbonate UL94 V-2
Vibration resistance (EN 60068-2-6)
10���55 Hz / 1 mm / XYZ
30 min in each direction
Shock resistance (EN 60068-2-27)
100 g / XYZ
3 times in each directio
Cleaning
The front of the unit should only be cleaned using a soft damp
(water!) cloth�
11.13 Connections
Supply voltage and relay outputs
Plug-in screw terminal
7-pin, RM 5�08
Core cross section
max� 2�5 mm²
Signal and control inputs
Plug-in screw terminal
8-pin, RM 3�81
Core cross section
max� 1�5 mm²
12 Maintenance, repair and disposal
The unit is maintenance-free�
► Do not open the housing as the device does not contain any components
which can be repaired by the user� The device must only be repaired by the
manufacturer�
► Dispose of the device in accordance with the national environmental
regulations�
Electronic Preset Counter E89005
51
13 Approvals/standards
The EC declaration of conformity and approvals can be found at:
www�ifm�com
14 Attachement
Parameter structure (see next pages)
00.00 .. 99.99
PrES 2
Pr.Out 2
Pr.Out 2
Pr.Out 2
Pr.Out 2
Pr.Out 2
Pr.Out 2
Pr.Out 2
T2
P
P
P
EndPro
no
EndPro
YES
T2
P
Save
Run
P
T1
T2
T1
R
P
1
2
Funct
P
T2
1
InPut
InP.PoL
PnP
FiLtEr
oFF
Count
Cnt.Dir
MPi
LAtch
Loc.InP
PrESET
P
P
P
P
P
InP.PoL
nPn
T2
FiLtEr
on
T2
T2
MPi
tEAch
MPi
SEt
Loc.InP
PrG.PrE
Loc.InP
ProG
T2
T2
P
ModE
ModE
Add
P
ModE
Sub
ModE
AddAr
ModE
SubAr
ModE
AddbAt
ModE
SubbAt
ModE
Addtot
ModE
Subtot
ModE
trAiL
ModE
tr_Ar
T2
ConFiG
P
rESmd
P
rESmd
Man.EL
rESmd
no rES
rESmd
EL.rEs
rESmd
MAnrE
T2
4
Funct
Count
Count
uP.dn
Count
uP.uP
Count
quAd
Count
quAd 2
Count
quAd 4
Count
A / B
Count
A° / b
FActor
dp
0
CoLor
rEd
P
P
P
00.0001 ...
99.9999
T2
dp
0.0
dp
0.00
dp
0.000
T2
CoLor
rEdGrn
T2
SetPt
000000
P
000000 ...
999999
T2
diViSo
P
01.0000 ...
99.9999
T2
°
3
t.Out 2
00.01
00.00 .. 99.99
T2
T2
4
T2
T1
T2
T1
T2
T1
T2
T1
T2
T1
dp
0.0000
dp
0.00000
START
Run
T2
P
ProG
no
ProG
Yes
P
P R
T2
T1
R600318.001
R61318.9416
E89005
E89005
A / B
InPut
A° / b
°
ConFiG
P
FActor
dp
0
StArt
00.0
P
P
P
00.0001 ...
99.9999
T2
dp
0.0
dp
0.00
dp
0.000
T2
00.0
99.9
T2
AVG
oFF
P
T2
diViSo
P
01.0000 ...
99.9999
T2
4
tModE
SEC -1
P
tModE
Min -1
T2
P
AVG
AVG 2
AVG
AVG 5
AVG
AVG 10
AVG
AVG 20
P
WAit0
00.1
00.1
99.0
T2
P
CoLor
rEd
CoLor
rEdGrn
P
2
Funct
timEr
InPut
InP.PoL
PnP
FiLtEr
oFF
StArt
InA.Inb
GAtE
GAtE.Lo
MPi
LAtch
Loc.InP
PrESET
P
P
P
P
P
InP.PoL
nPn
T2
FiLtEr
on
T2
StArt
Inb.Inb
StArt
FrErun
StArt
Auto
T2
GAtE
GAtE.hi
T2
MPi
tEAch
MPi
SEt
Loc.InP
PrG.PrE
Loc.InP
ProG
T2
T2
P
ModE
ModE
Add
P
ModE
Sub
ModE
AddAr
ModE
SubAr
ModE
AddbAt
ModE
SubbAt
ModE
Addtot
ModE
Subtot
ModE
trAiL
ModE
tr_Ar
T2
ConFiG
tModE
SEC
dp
0
CoLor
rEd
P
P
P
P
tModE
Min
tModE
hour
tModE
h.Min.S
T2
dp
0.0
dp
0.00
dp
0.000
T2
CoLor
rEdGrn
T2
rESmd
P
rESmd
Man.EL
rESmd
no rES
rESmd
EL.rEs
rESmd
MAnrE
T2
4
T2
T1
SetPt
000000
P
000000 ...
999999
T2
T2
T2
T1
T2
T1
T2
T1
P
R600318.001
R61318.9416
ifm weltweit - ifm worldwide - ifm à l’échelle internationale
http://www.ifm.com e-mail: [email protected]
Service-Hotline: 0800 16 16 16 4 (nur Deutschland, Mo-Fr von 7.00-18.00 Uhr)
i
ifm electronic gmbh • 1120 Wien • Tel. +43 16 17 45 00
A
+60 7 / 331 5022
M