Emerson Rosemount 752 FOUNDATION Reference Manual
Read Online
Read the Emerson Rosemount 752 FOUNDATION Reference Manual online using the built-in PDF viewer.
Text of the manual
00809-0100-4377, Rev CA
January 2018
Rosemount™ 752 Remote Indicator
with FOUNDATION™ Fieldbus protocol
00809-0100-4377, Rev CA
Contents
January 2018
Contents
1Section 1: Introduction
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Device description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Node address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2Section 2: Configuration
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Operation and Maintenance of the Rosemount 752. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 General considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5 Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 General block information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Foundation Fieldbus function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.8 Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.9 LCD transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3Section 3: Operation and Maintenance
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3 Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4 Software upgrade in the field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.5 Service support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4Section 4: Troubleshooting
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.3 Troubleshooting guides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4 Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.5 LCD transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
AAppendix A: Reference Data
A.1 Block Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
A.2 Ordering Information, Specifications, and Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
BAppendix B: Block Information
Contents
00809-0100-4377, Rev CA
Contents
January 2018
Contents
B.1 Block configuration33
B.2 LCD transducer block39
00809-0100-4377, Rev CA
Title Page
January 2018
Title Page
Rosemount™ 752 Remote Indicator with
FOUNDATION™ Fieldbus Protocol
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum
product performance, make sure you thoroughly understand the contents before installing, using, or
maintaining this product.
Within the United States, Rosemount Inc. has two toll-free assistance numbers:
Customer Central
Technical support, quoting, and order-related questions.
1-800-999-9307 (7:00 am to 7:00 pm CST)
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of the United States, contact your local Emerson™ representative.
Explosions can result in death or serious injury.
Do not remove the indicator covers in explosive environments when the circuit is live.
Indicator covers must be fully engaged to meet explosion proof requirements.
Before connecting a configuration tool in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
The products described in this document are NOT designed for nuclear-qualified applications. Using
non-nuclear qualified products in applications that require nuclear-qualified hardware or products may
cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Sales
Representative.
00809-0100-4377, Rev CA
Introduction
January 2018
1
Introduction
Section 1
Introduction
1.1
Using this manual
The sections in this manual provide information on configuring, troubleshooting, operating and
maintaining the Rosemount™ 752 Remote Indicator with FOUNDATION™ Fieldbus protocol.
The sections in this manual are organized as follows:
Section 2: Configuration provides instruction on configuration of the Rosemount 752 Remote Indicator
with FOUNDATION Fieldbus Protocol. Information on software functions, configuration parameters, and
other variables are also included.
Section 3: Operation and Maintenance contains operation and maintenance techniques.
Section 4: Troubleshooting provides troubleshooting techniques for the most common operating
problems.
Section A: Reference Data supplies procedure on how to get the specifications, ordering information,
and product certification.
Section B: Block Information supplies reference block information such as parameter tables.
1.2
Device description
efore configuring the device, ensure the host has the appropriate Device Description (DD) or Device Type
Manager (DTM™) file revision for this device. The device descriptor can be found on Fieldbus.org. The
DTM can be found at Emerson.com.
1.3
Node address
The indicator is shipped at a temporary (248) address. This will enable FOUNDATION Fieldbus host systems
to automatically recognize the device and move it to a permanent address.
00809-0100-4377, Rev CA
Configuration
January 2018
3
Configuration
Section 2
Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
General considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Connect wiring and power up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
General block information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
LCD transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
2.1
Overview
This section covers basic operation, software functionality, and basic configuration procedures for the
Rosemount™ 752 Remote Indicator with FOUNDATION™ Fieldbus Protocol. This section is organized by
block information. For detailed information about the function blocks used in the Rosemount 752
Remote Indicator, refer to “Block Information” on page 33 and the Foundation Fieldbus Block Reference
Manual.
2.2
Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol (
). Refer to the following safety messages before performing an operation preceded
by this symbol.
Explosions can result in death or serious injury.
Do not remove the indicator covers in explosive environments when the circuit is live.
Indicator covers must be fully engaged to meet explosion proof requirements.
Before connecting a configuration tool in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
2.3
Operation and Maintenance of the Rosemount 752
2.3.1
Set switches
Security (write protect)
Changes can be prevented to the indicator configuration data with the write protection Plantweb
housing switches. Security is controlled by the security (write protect) switch/jumper located on the
interface assembly or terminal block. Position the switch/jumper in the “ON” position to prevent
accidental or deliberate change of configuration data.
If the indicator write protection switch/jumper is in the “ON” position, the indicator will not accept any
“writes” to its memory. Configuration changes cannot take place when the indicator security is on.
To reposition the switches/jumpers, follow the procedure described below. (Simulate = Fieldbus
protocol)
1. Set the loop to manual and remove power.
2. Remove the electronics compartment cover, opposite the field terminal side on the PlantWeb
housing. Do not remove the indicator covers in explosive atmospheres when the circuit is live.
3. Slide the security and simulate switches into the preferred position by using a small screwdriver.
Re-install the indicator cover. Indicator covers must be fully engaged to meet explosion-proof
requirements.
Figure 2-1. Plantweb Housing Switches
A. Security
B. Alarm/simulate
2.3.2
Connect wiring and power up
Wiring for Fieldbus protocol
1. Remove the housing cover on terminal compartment side. Do not remove the cover in explosive
atmospheres when the circuit is live. Signal wiring supplies all power to the indicator.
2. Connect the power leads to the terminals marked “FIELDBUS WIRING” as shown in Figure 2-2. The
power terminals are not polarity sensitive.
3. Plug and seal unused conduit connections on the indicator housing to avoid moisture accumulation
in the terminal side. If you do not seal unused connections, mount the indicator with the electrical
housing positioned downward for drainage. Install wiring with a drip loop. Arrange the drip loop so
the bottom is lower than the conduit connections and the indicator housing.
A
B
See “Safety messages” on page 3 for complete warning
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
Note
Do not apply high voltage (e.g. ac line voltage) to the indicator terminals. Abnormally high voltage can
damage the unit. (Indicator power terminals are rated to 32 V dc).
Figure 2-2. Fieldbus Terminal Block
Electrical considerations
Proper electrical Operation and Maintenance is necessary to prevent errors due to improper grounding
and electrical noise. Shielded, twisted pair cable should be used for best results in electrically noisy
environments. Cable Type A is recommended by FOUNDATION Fieldbus.
Power supply
The indicator requires between 9 and 32 V dc (9 and 15 V dc for FISCO) to operate and provide complete
functionality. The dc power supply should provide power with less than 2% ripple.
Power conditioner
A fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the
segment from other segments attached to the same power supply.
Grounding
Signal wiring of the fieldbus segment can not be grounded. Grounding out one of the signal wires will
shut down the entire fieldbus segment.
Shield wire ground
To protect the fieldbus segment from noise, grounding techniques for shield wire usually require a single
grounding point for shield wire to avoid creating a ground loop. The ground point is typically at the
power supply.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
Figure 2-3. Fieldbus Indicator Field Wiring
A. Integrated Power Conditioner and Filter
B. 6234 ft. (1900 m) max (depending upon cable characteristics)
C. Terminators
D. Fieldbus segment
E. Trunk(1)
F. Spur
G. Signal wiring
H. Fieldbus devices on segment
Surges/transients
The indicator will withstand electrical transients of the energy level usually encountered in static
discharges or induced switching transients. However, high-energy transients, such as those induced in
wiring from nearby lightning strikes, can damage the indicator.
Optional transient protection terminal block
The transient protection terminal block can be ordered as an installed option (Option code T1 in the
indicator model number) or as a spare part. The spare part number is 03151-4134-0002. The lightning
bolt symbol shown identifies it as a transient protection terminal block.
Note
The fieldbus physical layer specification requires indicator communication during extreme operating
conditions of 250 Vrms common mode signal. The transient terminal block was designed to limit
common mode voltages to 90 V and cannot be used in these extreme operating conditions.
1,
The power supply, filter, first terminator, and configuration tool are typically located in the control room.
G
H
F
F
E
A
B
C
D
Power
supply
FOUNDATION
Fieldbus
configuration
tool
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
2.4
General considerations
2.4.1
Tagging
Commissioning (paper) tag on a fieldbus segment
When commissioning more than one device on a Fieldbus segment, it can be difficult to identify which
device is at a particular location. A removable tag provided with the indicator can aid in this process by
linking the Device ID and a physical location. The Device ID is a unique code that identifies a particular
device in the absence of a device tag. The device tag is used by the customer as an operational
identification for the device and is usually defined by the Piping and Instrumentation Diagram (P & ID).
The installer should note the physical location in both places on the removable commissioning tag and
tear off the bottom portion. This should be done for each device on the segment. The bottom portion of
the tags can be used for commissioning the segment in the control system, providing a direct link
between the Device ID and the tag location.
2.5
Hazardous locations
The Rosemount 752 Remote Indicator has explosion-proof housing and circuitry suitable for intrinsically
safe and non-incendive operation. Individual indicators are clearly marked with a tag indicating the
certifications they carry.
Note
Once a device labeled with multiple approvals is installed, it should not be reinstalled using any other
approval type(s). Permanently mark the certification label to distinguish the installed approval type from
unused approval types.
COMMISSIONING TAG
Device ID:
00BBXXXXXX010001440-121698091725
PD Tag:
PT- 101
Revision: 7.2
Support files available at
www.rosemount.com
Revision: 7.2
Support files available at
www.rosemount.com
Device Serial Number:
XXXXXXXXXX
Device ID:
00XXXXX010001440-121698091725
PD Tag:
PT- 101
Tear Here
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
2.5.1
Grounding the indicator case
Always ground the indicator case in accordance with national and local electrical codes. The most
effective indicator case grounding method is a direct connection to earth ground with minimal
impedance. Methods for grounding the indicator case include:
Internal ground connection: The internal ground connection screw is inside the terminal side of the
electronics housing. The screw is identified by a ground symbol (
), and is standard on the
Rosemount 752 Remote Indicators.
External ground assembly: Ground screw is located at the bottom of the mounting bracket.
Note
Grounding the indicator case using the threaded conduit connection may not provide a sufficient
ground. The transient protection terminal block (Option Code T1) will not provide transient protection
unless the indicator case is properly grounded. Use the above guidelines to ground the indicator case. Do
not run transient protection ground wire with signal wiring; the ground wire may carry excessive current
if a lightning strike occurs.
2.6
General block information
2.6.1
Modes
The Resource, Transducer, and all function blocks in the device have modes of operation. These modes
govern the operation of the block. Every block supports both automatic (AUTO) and out of service (OOS)
modes. Other modes may also be supported.
Changing modes
To change the operating mode, set the MODE_BLK.TARGET to the desired mode. After a short delay, the
parameter MODE_BLOCK.ACTUAL should reflect the mode change if the block is operating properly.
Permitted modes
It is possible to prevent unauthorized changes to the operating mode of a block. To do this, configure
MODE_BLOCK.PERMITTED to allow only the desired operating modes. It is recommended to always
select OOS as one of the permitted modes.
Types of modes
For the procedures described in this manual, it will be helpful to understand the following modes:
AUTO
The functions performed by the block will execute. If the block has any outputs, these will continue to
update. This is typically the normal operating mode.
Out of service (OOS)
The functions performed by the block will not execute. If the block has any outputs, these will typically
not update and the status of any values passed to downstream blocks will be “BAD”. To make some
changes to the configuration of the block, change the mode of the block to OOS. When the changes are
complete, change the mode back to AUTO.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
MAN
In this mode, variables that are passed out of the block can be manually set for testing or override
purposes.
Other types of modes
Other types of modes are Cas, RCas, ROut, IMan and LO. Some of these may be supported by different
function blocks in the Rosemount 752. For more information, see the Function Block Reference Manual.
Note
When an upstream block is set to OOS, this will impact the output status of all downstream blocks. The
figure below depicts the hierarchy of blocks:
2.6.2
Link active scheduler (LAS)
The Rosemount 752 can be designated to act as the backup LAS in the event that the LAS is disconnected
from the segment. As the backup LAS, the Rosemount 752 will take over the management of
communications until the host is restored.
The host system may provide a configuration tool specifically designed to designate a particular device
as a backup LAS. Otherwise, this can be configured manually as follows:
1. Access the Management Information Base (MIB) for the Rosemount 752.
2. To activate the LAS capability, write 0x02 to the BOOT_OPERAT_FUNCTIONAL_CLASS object (Index
605). To deactivate, write 0x01.
3. Restart the processor.
2.6.3
Block instantiation
Rosemount devices are pre-configured with function blocks at the factory, the default permanent
configuration for the Rosemount 752 is listed below. The Rosemount 752 can have up to nine additional
instantiated function blocks.
1 Proportional/integral/derivative block (tag name PID_1600)
1 Input selector block (tag name ISEL_1700)
1 Signal characterizer block (tag name CHAR_1800)
1 Arithmetic block (tag name ARITH_1900)
1 Integrator block (tag name INTEG_2000)
The Rosemount 752 supports the use of Function Block Instantiation. When a device supports block
instantiation, the number of blocks and block types can be defined to match specific application
needs.The number of blocks that can be instantiated is only limited by the amount of memory within the
device and the block types that are supported by the device. Instantiation does not apply to standard
device blocks like the Resource and LCD Transducer Block.
By reading the parameter “FREE_SPACE” in the Resource block you can determine how many blocks you
can instantiate. Each block that you instantiate takes up 4.5573% of the “FREE_SPACE”.
Resource block
Transducer
block
Analog Input
(AI block)
Other
function
blocks
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
Block instantiation is done by the host control system or configuration tool, but not all hosts are required
to implement this functionality. Please refer to your specific host or configuration tool manual for more
information.
2.6.4
Capabilities
Virtual Communication Relationship (VCRs)
There are a total of 20 VCRs. One is permanent and 19 are fully configurable by the host system. Thirty
link objects are available.
Host timer recommendations
T1 = 96000
T2 = 1920000
T3 = 480000
Block execution times
PID = 10 ms
Arithmetic = 10 ms
Input selection = 10 ms
Signal characterizer = 10 ms
Integrator = 10 ms
Network parameter
Value
Slot time
6
Maximum response delay
4
Maximum inactivity to claim LAS delay
60
Minimum Inter DLPDU delay
7
Time sync class
4 (1ms)
Maximum scheduling overhead
21
Per CLPDU PhL overhead
4
Maximum inter-channel signal skew
0
Required number of post-transmission-gab-ext units
0
Required number of preamble-extension units
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
2.7
FOUNDATION Fieldbus function blocks
For reference information on the LCD Transducer and Advanced Diagnostics Transducer blocks refer to
“Foundation Fieldbus Block Information” on Rosemount 3051S Series Pressure Transmitter Family with
FOUNDATION Fieldbus protocol” Product Data Sheet available on Emerson.com/Rosemount-3051S.
Reference information on the ISEL, INT, ARTH, SGCR and PID blocks can be found in the Function Block
Reference Manual.
Resource block (1000)
The Resource block contains diagnostic, hardware and electronics information. There are no linkable
inputs or outputs to the Resource Block.
LCD transducer block (1100)
The LCD Transducer Block is used to configure the LCD meter.
PID block (1200)
The PID Function Block combines all of the necessary logic to perform proportional/integral/derivative
(PID) control. The block supports mode control, signal scaling and limiting, feed forward control,
override tracking, alarm limit detection, and signal status propagation.
The block supports two forms of the PID equation: Standard and Series. You can select the appropriate
equation using the MATHFORM parameter. The Standard ISA PID equation is the default selection.
Input selector block (1300)
The Input Selector (ISEL) Function Block can be used to select the first good, Hot Backup, maximum,
minimum, or average of as many as eight input values and place it at the output. The block supports
signal status propagation.
Signal characterizer block (1400)
The Signal Characterizer (SGCR) Function Block characterizes or approximates any function that defines
an input/output relationship. The function is defined by configuring as many as twenty X,Y coordinates.
The block interpolates an output value for a given input value using the curve defined by the configured
coordinates. Two separate analog input signals can be processed simultaneously to give two
corresponding separate output values using the same defined curve.
Arithmetic block (1500)
The Arithmetic (ARTH) Function Block provides the ability to configure a range extension function for a
primary input. It can also be used to compute nine different arithmetic functions.
Integrator block (1600)
The Integrator (INT) Function Block integrates one or two variables over time. The block compares the
integrated or accumulated value to pre-trip and trip limits and generates discrete output signals when
the limits are reached.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
2.8
Resource block
2.8.1
FEATURES and FEATURES_SEL
The parameters FEATURES and FEATURE_SEL determine optional behavior of the Rosemount 752.
FEATURES
The FEATURES parameter is read only and defines which features are supported by the Rosemount 752.
Below is a list of the FEATURES the Rosemount 752 supports.
UNICODE
All configurable string variables in the Rosemount 752, except tag names, are octet strings. Either ASCII
or Unicode may be used. If the configuration device is generating Unicode octet strings, you must set the
Unicode option bit.
REPORTS
The Rosemount 752 supports alert reports. The Reports option bit must be set in the features bit string
to use this feature. If it is not set, the host must poll for alerts.
SOFT W LOCK and HARD W LOCK
Inputs to the security and write lock functions include the hardware security switch, the hardware and
software write lock bits of the FEATURE_SEL parameter, the WRITE_LOCK parameter, and the
DEFINE_WRITE_LOCK parameter.
The WRITE_LOCK parameter prevents modification of parameters within the device except to clear the
WRITE_LOCK parameter. During this time, the block will function normally updating inputs and outputs
and executing algorithms. When the WRITE_LOCK condition is cleared, a WRITE_ALM alert is generated
with a priority that corresponds to the WRITE_PRI parameter.
The FEATURE_SEL parameter enables the user to select a hardware or software write lock or no write lock
capability. To enable the hardware security function, enable the HW_SEL bit in the FEATURE_SEL
parameter. When this bit has been enabled the WRITE_LOCK parameter becomes read only and will
reflect the state of the hardware switch. In order to enable the software write lock, the SW_SEL bit must
be set in the FEATURE_SEL parameter. Once this bit is set, the WRITE_LOCK parameter may be set to
“Locked” or “Not Locked.” Once the WRITE_LOCK parameter is set to “Locked” by either the software or
the hardware lock, all user requested writes as determined by the DEFINE_WRITE_LOCK parameter shall
be rejected.
The DEFINE_WRITE_LOCK parameter allows the user to configure whether the write lock functions (both
software and hardware) will control writing to all blocks, or only to the resource and transducer blocks.
Internally updated data such as process variables and diagnostics will not be restricted by the security
switch.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
The following table displays all possible configurations of the WRITE_LOCK parameter.
FEATURES_SEL
FEATURES_SEL is used to turn on any of the supported features. The default setting of the Rosemount
752 does not select any of these features. Choose one of the supported features if any.
2.8.2
MAX_NOTIFY
The MAX_NOTIFY parameter value is the maximum number of alert reports that the resource can have
sent without getting a confirmation, corresponding to the amount of buffer space available for alert
messages. The number can be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
2.8.3
Plantweb™ alarms
The alarms and recommended actions should be used in conjunction with Section 4: Troubleshooting.
The Resource Block will act as a coordinator for PlantWeb alarms. There will be three alarm parameters
(FAILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which will contain information regarding some of
the device errors which are detected by the indicator software. There will be a RECOMMENDED_ACTION
parameter which will be used to display the recommended action text for the highest priority alarm.
FAILED_ALARM will have the highest priority followed by MAINT_ALARM and ADVISE_ALARM will be the
lowest priority.
FEATURE_SEL
HW_SEL bit
FEATURE_SEL
SW_SEL bit
SECURITY
SWITCH
WRITE_LOCK
WRITE_LOCK
Read/Write
DEFINE_WRITE_
LOCK
Write
access to
blocks
0 (off)
0 (off)
N/A
1 (unlocked)
Read only
N/A
All
0 (off)
1 (on)
N/A
1 (unlocked)
Read/write
N/A
All
0 (off)
1 (on)
N/A
2 (locked)
Read/write
Physical
Function
Blocks only
0 (off)
1 (on)
N/A
2 (locked)
Read/write
Everything
None
1 (on)
0 (off)(1)
1.
The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit if set to 1 (on), the
SW_SEL bit is automatically set to 0 (off) and is read only.
0 (unlocked)
1 (unlocked)
Read only
N/A
All
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Physical
Function
Blocks only
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Everything
None
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device or some part of the device
non-operational. This implies that the device is in need of repair and must be fixed immediately. There
are five parameters associated with FAILED_ALARMS specifically, they are described below:
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the device non-operational that will
cause an alarm to be sent. Below is a list of the failures with the highest priority first.
FAILED_MASK
This parameter will mask any of the failed conditions listed in FAILED_ENABLED. A bit on means that the
condition is masked out from alarming and will not be reported.
FAILED_PRI
Designates the alarming priority of the FAILED_ALM, see “ADVISE_PRI” on page 15. The default is 0 and
the recommended value are between eight and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with the highest priority will be
displayed. This priority is not the same as the FAILED_PRI parameter described above. This priority is hard
coded within the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs maintenance soon. If the
condition is ignored, the device will eventually fail. There are five parameters associated with
MAINT_ALARMS, they are described below:
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device or some part of the
device needs maintenance soon. If the condition is ignored, the device will eventually fail.
MAINT_MASK
The MAINT_MASK parameter will mask any of the failed conditions listed in MAINT_ENABLED. A bit on
means that the condition is masked out from alarming and will not be reported.
MAINT_PRI
MAINT_PRI designates the alarming priority of the MAINT_ALM, “MAINT_ALM” on page 15. The default
is zero and the recommended values is three to seven.
Alarm
Priority
Electronics failure
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
MAINT_ACTIVE
The MAINT_ACTIVE parameter displays which of the alarms is active. Only the condition with the highest
priority will be displayed. This priority is not the same as the MAINT_PRI parameter described above. This
priority is hard coded within the device and is not user configurable.
MAINT_ALM
An alarm indicating the device needs maintenance soon. If the condition is ignored, the device will
eventually fail.
Advisory alarms
An advisory alarm indicates informative conditions that do not have a direct impact on the device's
primary functions There are five parameters associated with ADVISE_ALARMS, they are described below:
ADVISE_ENABLED
The ADVISE_ENABLED parameter contains a list of informative conditions that do not have a direct
impact on the device's primary functions.
ADVISE_MASK
The ADVISE_MASK parameter will mask any of the failed conditions listed in ADVISE_ENABLED. A bit on
means the condition is masked out from alarming and will not be reported.
ADVISE_PRI
ADVISE_PRI designates the alarming priority of the ADVISE_ALM, see “ADVISE_PRI” on page 15. The
default is zero and the recommended values are one or two.
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is active. Only the advisory with the
highest priority will be displayed. This priority is not the same as the ADVISE_PRI parameter described
above. This priority is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do not have a direct impact on the
process or device integrity.
Alarm
Priority
LOI failure
1
Check
2
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
Recommended actions for Plantweb alarms
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give a recommended course of
action to take based on which type and which specific event of the Plantweb alarms is active.
Table 2-1. RB.RECOMMENDED_ACTION
2.8.4
Field diagnostics alerts
The Resource Block will act as a coordinator for Field Diagnostic Alerts. There will be four alarm
parameters (FD_FAILED_ALARM, FD_OFFSPEC_ALARM, FD_MAINT_ALARM, and FD_CHECK_ALARM)
that will contain information regarding some of the device errors that are detected by the transmitter
software. There will be a RECOMMENDED_ACTION parameter that will be used to display the
recommended action text for the highest priority alarm and a HEALTH_INDEX parameters (0–100)
indicating the overall health of the transmitter. FD_FAILED_ALARM will have the highest priority followed
by FD_OFFSPEC_ALARM, FD_MAINT_ALARM and FD_CHECK_ALARM will be the lowest priority.
FD failed alarms
A failure alarm indicates a failure within a device that will make the device or some part of the device
non-operational. This implies that the device is in need of repair and must be fixed immediately. There
are five parameters associated with FD_FAILED_ALARMS specifically, they are described below:
FD_FAILED_MAP
FD_FAIL_MAP parameter maps conditions to be detected as active for FD_FAIL_ALARM category. Thus
the same condition may be active in all, some, or none of the four alarm categories. Below is a list of the
failures with the highest priority first:
FD_FAILED_MASK
FD_FAIL_MASK parameter will mask any of the failed conditions listed in FD_FAILED_MAP. A bit on
means the condition is masked out from alarming and will not be reported.
FD_FAILED_PRI
Designates the alerting priority of the FD_FAILED_ALM, see Table B-3 on page 38 The default is zero and
the recommended value are between eight and 15.
FD_FAILED_ACTIVE
FD_FAIL_ACTIVE parameter displays the active alarms is active that are being selected for this category.
Only the alarm with the highest priority will be displayed. This priority is not the same as the
FD_FAILED_PRI parameter described above. This priority is hard coded within the device and is not user
configurable.
Failed/maint/advise active event
Recommended action text string
None
No action required
LOI failure
Check display connections and sensor connections
Electronics failure
Replace the Fieldbus electronics board
Table 2-2. FD Failure Alarms
Alarm
Priority
Electronics failure
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
FD_FAILED_ALM
FD_FAIL_ALM indicates a failure within a device which makes the device non-operational. FD_FAIL_ALM
parameter is used primarily to broadcast a change in the associated active conditions, which are not
masked, for this alarm category to a Host System.
FD OFFSPEC ALARMS
An offspec alarm indicates that the device or some part of the device needs maintenance soon, if the
condition is ignored the device will eventually fail. There are five parameters associated with FD OFFSPEC
ALARMS, they are described below:
FD_OFFSPEC_MAP
FD_OFFSPEC_MAP parameter maps conditions to be detected as active for FD_ OFFSPEC_ALARM
category. Thus the same condition may be active in all, some, or none of the four alarm categories.
FD_ OFFSPEC _MASK
The FD_OFFSPEC_MASK parameter will mask any of the failed conditions listed inFD_OFFSPEC_MAP. A
bit on means the condition is masked out from alarming and will not be reported.
FD_ OFFSPEC _PRI
FD_OFFSPEC_PRI designates the alarming priority of the FD_OFFSPEC _ALM, Table B-3 on page 38 The
default is zero and the recommended values are three to seven.
FD_ OFFSPEC _ACTIVE
FD_ OFFSPEC _ACTIVE parameter displays the active alarms is active that are being selected for this
category. Only the alarm with the highest priority will be displayed. This priority is not the same as the
FD_ OFFSPEC _PRI parameter described above. This priority is hard coded within the device and is not
user configurable.
FD_ OFFSPEC _ALM
An alarm indicating the device needs maintenance soon. If the condition is ignored, the device will
eventually fail. FD_ OFFSPEC _ALM parameter is used primarily to broadcast a change in the associated
active conditions, which are not masked, for this alarm category to a Host System.
FD MAINT ALARMS
A maintenance alarm indicates informative conditions that do not have a direct impact on the device's
primary function(s).There are five parameters associated with MAINT_ALARMS, they are described
below:
FD_MAINT_MAP
The FD_MAINT_MAP parameter contains a list of conditions that do not have a direct impact on the
device's primary function(s).
FD_MAINT_MASK
The FD_MAINT_MASK parameter will mask any of the failed conditions listed in FD_MAINT_ENABLED. A
bit on means that the condition is masked out from alarming and will not be reported.
Table 2-3. Maintenance Alarms/Priority Alarm
Failed/maintain/advise active event
Priority
LOI failure
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
FD_MAINT_PRI
FD_MAINT_PRI designates the alarming priority of the MAINT_ALM, alarm categories.
FD_ OFFSPEC _MASK
The FD_OFFSPEC_MASK parameter will mask any of the failed conditions listed inFD_OFFSPEC_MAP. A
bit on means the condition is masked out from alarming and will not be reported.
FD_ OFFSPEC _PRI
FD_OFFSPEC_PRI designates the alarming priority of the FD_OFFSPEC _ALM, Table B-3 on page 38 The
default is zero and the recommended values are three to seven.
FD_ OFFSPEC _ACTIVE
FD_ OFFSPEC _ACTIVE parameter displays the active alarms is active that are being selected for this
category. Only the alarm with the highest priority will be displayed. This priority is not the same as the
FD_ OFFSPEC _PRI parameter described above. This priority is hard coded within the device and is not
user configurable.
FD_ OFFSPEC _ALM
An alarm indicating the device needs maintenance soon. If the condition is ignored, the device will
eventually fail. FD_ OFFSPEC _ALM parameter is used primarily to broadcast a change in the associated
active conditions, which are not masked, for this alarm category to a Host System.
FD MAINT ALARMS
A maintenance alarm indicates informative conditions that do not have a direct impact on the device's
primary function(s).There are five parameters associated with MAINT_ALARMS, they are described
below:
FD_MAINT_MAP
The FD_MAINT_MAP parameter contains a list of conditions that do not have a direct impact on the
device's primary function(s).
FD_MAINT_MASK
This parameter will mask any of the failed conditions listed in FAILED_ENABLED. A bit on means that the
condition is masked out from alarming and will not be reported.
FD_MAINT_ACTIVE
FD_ MAINT_ACTIVE parameter displays the active alarms is active that are being selected for this
category. Only the alarm with the highest priority will be displayed. This priority is not the same as the
FD_ MAINT_PRI parameter described above. This priority is hard coded within the device and is not user
configurable.
FD_MAINT_ALM
FD_ MAINT_ALM indicates advisory alarms. These conditions do not have a direct impact on the process
or device integrity.
Table 2-4. Maintenance Alarms/Priority Alarm
Failed/maintain/advise active event
Priority
LOI failure
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
FD CHECK ALARMS
An advisory alarm indicates informative conditions that do not have a direct impact on the device's
primary functions. There are five parameters associated with ADVISE_ALARMS, they are described
below:
FD_CHECK_MAP
The FD_CHECK_MAP parameter contains a list of informative conditions that do not have a direct impact
on the device's primary functions. Below is a list of the advisories with the highest priority first:
FD_ CHECK _MASK
The FD_CHECK _MASK parameter will mask any of the failed conditions listed in FD_CHECK _MAP. A bit
on means the condition is masked out from alarming and will not be reported.
FD_ CHECK _PRI
FD_CHECK _PRI designates the alarming priority of the ADVISE_ALM, seeTable B-3 on page 38. The
default is zero and the recommended values is one.
FD_ CHECK _ACTIVE
The FD_CHECK _ACTIVE parameter displays which of the advisories is active. Only the advisory with the
highest priority will be displayed. This priority is not the same as the FD_CHECK _PRI parameter
described above. This priority is hard coded within the device and is not user configurable.
FD_ CHECK _ALM
FD_CHECK _ALM is an alarm indicating advisory alarms. These conditions do not have a direct impact on
the process or device integrity.
Recommended actions for field diagnostics alerts
FD_ RECOMMEN _ACT
The FD_RECOMMEN_ACT parameter displays a text string that will give a recommended course of action
to take based on which type and which specific event of the Field Diagnostics alerts are active. See Table
2-1 on page 16 for more information.
2.9
LCD transducer block
The LCD meter connects directly to the Rosemount 752 electronics FOUNDATION Fieldbus output board.
The meter indicates output and abbreviated diagnostic messages.
The meter features a four-line display and alarm. The 0–100 percent scaled bar graph is not used in the
Rosemount 752. The first line of five characters displays the output description, the second line of seven
digits displays the actual value, the third line of six characters displays engineering units and the fourth
line displays “Error” when the indicator is in alarm. The LCD meter can also display diagnostic messages.
Each parameter configured for display will appear on the LCD for a brief period before the next parameter
is displayed. If the status of the parameter goes bad, the LCD will also cycle diagnostics following the
displayed variable:
Table 2-5. Check Alarms
Alarm
Priority
Check
1
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
Figure 2-4. LCD Messaging
2.9.1
Custom meter configuration
To configure parameters 1–8, use the configuration parameters below:
The LCD Transducer Block can be configured to sequence eight different process variables.
The output from blocks in other devices on the segment can be linked to one of the inputs of the ISEL
block and then displayed on the LCD. The LCD would then be configured to display the Block Tag of the
ISEL block and the input parameter.
Configuration Parameters(1)
DISPLAY_PARAM_SEL
The DISPLAY_PARAM_SEL parameter specifies how many process variables will be displayed. Select up to
eight display parameters.
BLK_TAG_#(2)
Enter the Block Tag of the function block that contains the parameter to be displayed. The default
function block tags from the factory are:
PID_1200_XXXX(3)
ISEL_1300_XXXX(3)
CHAR_1400_XXXX(3)
ARITH_1500_XXXX(3)
INTEG_1600_XXXX(3)
BLK_TYPE_#(2)
Enter the Block Type of the function block that contains the parameter to be displayed. This parameter is
generally selected via a drop-down menu with a list of possible function block types. (e.g. ISEL PID, etc.)
PARAM_INDEX_#(2)
The PARAM_INDEX_# parameter is generally selected via a drop-down menu with a list of possible
parameter names based upon what is available in the function block type selected. Choose the
parameter to be displayed.
CUSTOM_TAG_#(2)
The CUSTOM_TAG_# is an optional user-specified tag identifier that can be configured to be displayed
with the parameter in place of the block tag. Enter a tag of up to five characters.
1,
Some host systems may ask for the device's capability level during commissioning. If prompted, the correct value to enter for the Rosemount 752 is 1.
2,
_# represents the specified parameter number.
3,
XXXX represents the last 4 digits of the device ID.
00809-0100-4377, Rev CA
Configuration
January 2018
Configuration
UNITS_TYPE_#(2)
The UNITS_TYPE_# parameter is generally selected via a drop-down menu with three options: AUTO,
CUSTOM, or NONE. Select AUTO only when the parameter to be displayed is pressure, temperature, or
percent. For other parameters, select CUSTOM and be sure to configure the CUSTOM_UNITS_#
parameter. Select NONE if the parameter is to be displayed without associated units.
CUSTOM_UNITS_#(2)
Specify custom units to be displayed with the parameter. Enter up to six characters. To display Custom
Units the UNITS_TYPE_# must be set to CUSTOM.
Figure 2-5. Configuring the LCD to Display Data from a Different Device on the Fieldbus Segment
PID
LCD
Configuration Block
TT102
71.2
DEG C
Characterizer
DISPLAY_PARAM_SEL = n n= 1 - 8
For each value displayed:
BLK_TAG_n
BLK_TYPE_n
PARAM_INDEX_n
CUSTOM_TAG_n
UNITS_TYPE_n
CUSTOM_UNITS_n
Arithmetic
Input Selector
TAG= ISEL 1300
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
OUT
Example: Display Value #1
BLK_TAG_1
= ISEL 1300
BLK_TYPE_1
= Input Selector
PARAM_INDEX_1
= IN_1
CUSTOM_TAG_1
= TT102
UNITS_TYPE_1
= CUSTOM
CUSTOM_UNITS_1 = DEG C
Linked from AI Block in
Temperature Transmtter TT102
IN_1
IN_2
IN_3
IN_4
IN_1
IN_2
Integrator
IN_1
IN_2
OUT
OUT
OUT
OUT_1
OUT_1
PV
SP
IN
CAS_IN
BKCAL_OUT
BKCAL_IN
RCAS_IN
ROUT_IN
RCAS_OUT
ROUT_OUT
TRK_VAL
FF_VAL
00809-0100-4377, Rev CA
Operation and Maintenance
January 2018
23
Operation and Maintenance
Section 3
Operation and Maintenance
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
Software upgrade in the field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 24
3.1
Overview
This section contains information on operation and maintenance procedures.
Methods and Manual Operation
Each FOUNDATION™ Fieldbus host or configuration tool has different ways of displaying and performing
operations. Some hosts will use Device Descriptions (DD) and DD Methods to complete device
configuration and will display data consistently across platforms. The DD can found on Emerson.com.
There is no requirement that a host or configuration tool support these features.
The information in this section will describe how to use methods in a general fashion. In addition, if your
host or configuration tool does not support methods this section will cover manually configuring the
parameters involved with each method operation. For more detailed information on the use of methods,
see your host or configuration tool manual.
3.2
Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol (
). Refer to the following safety messages before performing an operation preceded
by this symbol
Explosions can result in death or serious injury.
Do not remove the indicator covers in explosive environments when the circuit is live.
Indicators covers must be fully engaged to meet explosion proof requirements.
Before connecting a communicator in an explosive atmosphere, make sure the instruments in the
loop are installed in accordance with intrinsically safe or nonincendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause
electrical shock.
Performing a 'Restart with defaults' will set all function block information in the device to factory
defaults. This includes the clearing of all function block links and schedule, as well as defaulting all
Resource and Transducer Block user data (Advanced Diagnostic Block algorithm configurations, LCD
Transducer Block parameter configuration, etc.).
00809-0100-4377, Rev CA
Operation and Maintenance
January 2018
Operation and Maintenance
3.3
Resource block
3.3.1
Master reset method
To perform a master reset, run the Master Reset Method. If your system does not support methods,
manually configure the Resource Block parameters listed below.
1. Set the RESTART to one of the options below:
Set Run to nominal state when not restarting (default)
“Resource is not used by device”
Defaults set all device parameters to FOUNDATION Fieldbus default values
The Processor does a software reset of the CPU
3.4
Software upgrade in the field
Software for the Rosemount™ 752 with FOUNDATION™ Fieldbus is easy to upgrade in the field using the
FOUNDATION Fieldbus Common Device Software Download procedure.
3.5
Service support
To expedite the return process outside of the United States, contact the nearest Rosemount
representative.
Within the United States, call the Rosemount National Response Center using the 1-800-654-RSMT
(7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information
or materials.
The center will ask for product model and serial numbers, and will provide a Return Material
Authorization (RMA) number. The center will also ask for the process material to which the product was
last exposed.
Rosemount National Response Center representatives will explain the additional information and
procedures necessary to return goods exposed to hazardous substances.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are
informed of and understand the hazard. If the product being returned was exposed to a hazardous
substance as defined by OSHA, a copy of the required Safety Data Sheet (SDS) for each hazardous
substance identified must be included with the returned goods.
00809-0100-4377, Rev CA
Troubleshooting
January 2018
25
Troubleshooting
Section 4
Troubleshooting
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
Troubleshooting guides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Resource block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
LCD transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
4.1
Overview
This section provides summarized troubleshooting suggestions for the most common operating
problems. This section contains Rosemount™ 752 Remote Indicator with FOUNDATION™ Fieldbus
protocol troubleshooting information only.
Follow the procedures described here to verify that indicator hardware and process connections are in
good working order. Always deal with the most likely checkpoints first.
4.2
Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol (
). Refer to the following safety messages before performing an operation preceded
by this symbol.
Explosions can result in death or serious injury.
Do not remove the indicator covers in explosive environments when the circuit is live.
Indicator covers must be fully engaged to meet explosion proof requirements.
Before connecting a communicator in an explosive atmosphere, make sure that the instruments in
the loop are installed according to intrinsically safe or nonincendive field wiring practices.
Static electricity can damage sensitive components.
Observe safe handling precautions for static-sensitive components.
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
4.3
Troubleshooting guides
Figure 4-1. Rosemount 752 Troubleshooting Flowchart
PROBLEMS WITH COMMUNICATIONS
Device does not appear
on segment.
1. Check wiring to device.
2. Recycle power to device.
3. Electronic failure.
Refer to Device does not show up on
segment in Table 4-1 for more information.
Problem Identified?
Yes
No
Perform Recommended
Action, see Table 4-1.
Check Segment, see Device does not
stay on segment in Table 4-1 for
more information.
Problem Identified?
Yes
No
Perform Recommended
Action, see page 13.
If the problem persists
contact your local Rosemount
representative.
Device does not
stay on segment.
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
Figure 4-2. Problems with Communications Flowchart
COMMUNICATIONS ESTABLISHED BUT HAVE
“BLOCK_ERR” OR AN “ALARM” CONDITION.
See “Plantweb™ alarms” on page 13
Read the following parameters in the Resource
Block to determine the recommended action.
BLOCK_ERR (see Table 4-2)
SUMMARY_STATUS (see Table 4-3)
DETAILED_STATUS (see Table 4-4)
Problem identified?
Yes
No
Perform recommended
action, see Table 4-4.
For more detailed
information
Perform the following steps in the LCD
Transducer Block to determine the
recommended action.
BLOCK_ERR (see page 29)
If error condition does not exist in the
Resource Block then it is a
configuration problem, see Block
errors in Table 4-2
Problem identified?
Yes
No
If the problem persists
contact your local Rosemount
representative.
Problem identified?
Perform recommended
action
Yes
No
Perform recommended
action
Yes
No
Perform recommended
action, see Table 2-1.
Problem identified?
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
Table 4-1. Troubleshooting guide.
Symptom(1)
1.
The corrective actions should be done with consultation of your system integrator.
Cause
Recommended Actions
Device does not show up on
segment
Unknown
Recycle power to device
No power to device
1. Ensure the device is connected to the segment.
2. Check voltage at terminals. There should be 9–32
Vdc.
3. Check to ensure the device is drawing current. There
should be approximately 17 mA.
Segment problems
Electronics failing
1. Electronics board loose in housing.
2. Replace electronics.
Incompatible network settings
Change host network parameters.
Refer to host documentation for procedure.
Device does not stay on
segment(2)
2.
Wiring and installation 31.25 kbit/s, voltage mode, wire medium application guide AG-140 available from the fieldbus Foundation.
Incorrect signal levels.
Refer to host documentation for
procedure.
1. Check for two terminators.
2. Excess cable length.
3. Bad Power supply or conditioner
Excess noise on segment.
Refer to host documentation for
procedure.
1. Check for incorrect grounding.
2. Check for correct shielded wire.
3. Tighten wire connections.
4. Check for corrosion or moisture on terminals.
5. Check for Bad power supply.
Electronics failing
1. Tighten electronics board.
2. Replace electronics.
Other
1. Check for water in the terminal housing.
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
4.4
Resource block
This section describes error conditions found in the Resource block. Read Table 4-2 through Table 4-4 to
determine the appropriate corrective action.
Block errors
Table 4-2 lists conditions reported in the BLOCK_ERR parameter.
Table 4-2. Resource Block BLOCK_ERR Messages
Table 4-3. Resource Block Extended Status (FD_EXTENDED_ACTIVE_1) with Recommended Action
Messages
Condition Name and Description
Other
Simulate active: this indicates that the simulation switch is in place. this is not an indication that the i/o
blocks are using simulated data.
Memory failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Device needs maintenance now
Out of service: the actual mode is out of service.
Condition name
Recommended action
LOI error
1. Restart processor
2. Check display connection
3. Call service center
Manufacturing Block integrity error
1. Restart processor
2. Call service center
NV integrity error
1. Restart processor
2. Call service center
ROM integrity error
1. Restart processor
2. Call service center
00809-0100-4377, Rev CA
Troubleshooting
January 2018
Troubleshooting
4.5
LCD transducer block
This section describes error conditions found in the LCD Transducer Block. Read Table 4-4 and to
determine the appropriate corrective action.
Table 4-4. LCD Transducer Block BLOCK_ERR messages
Condition Name and Description
Other
Out of Service: The actual mode is out of service.
Symptom
Possible Causes
Recommended Action
The LCD displays “DSPLY#INVLID.” Read the
BLOCK_ERR and if it says “BLOCK CONFIGURATION”
perform the Recommended Action
One or more of the display parameters
are not configured properly.
See “LCD transducer block” on
page 39.
“752” is being displayed or not all of the values are
being displayed.
The LCD block parameter
“DISPLAY_PARAMETER_SELECT is not
properly configured.
See “LCD transducer block” on
page 39.
The display reads OOS
The resource and or the LCD Transducer
block are OOS.
Verify that both blocks are in
“AUTO,”
The display is hard to read.
Some of the LCD segments may have
gone bad.
See Self Test procedure above. If
some of the segment is bad,
replace the LCD.
Device is out of the temperature limit
for the LCD. (-20 to 85 °C)
Check ambient temperature of
the device.
Specifications and Reference Data
Reference Manual
00809-0100-4377, Rev CA
Reference Data
January 2018
31
Appendix A
Reference Data
Block Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 31
Ordering Information, Specifications, and Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 31
A.1 Block Information
To view current Rosemount™ 752 Remote Indicator Block
Information, follow these steps:
1. Go to Emerson.com/Rosemount/Rosemount-752.
2. Scroll as needed to the green menu bar and click
Documents & Drawings.
3. Click Manuals & Guides.
4. Select the appropriate Quick Start Guide.
A.2 Ordering Information,
Specifications, and
Drawings
To view current Rosemount 752 Remote Indicator Ordering
Information, Specifications, and Drawings, follow these
steps:
1. Go to Emerson.com/Rosemount/Rosemount-752.
2. Scroll as needed to the green menu bar and click
Documents & Drawings.
3. For installation drawings, click Drawings &
Schematics and select the appropriate document.
4. For ordering information, specifications, and
dimensional drawings, click Data Sheets & Bulletins.
5. Select the appropriate Product Data Sheet.
00809-0100-4377, Rev CA
Specifications and Reference Data
32
00809-0100-4377, Rev CA
Block Information
January 2018
33
Appendix B
Block Information
Block configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 33
LCD transducer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
B.1
Block configuration
B.1.1
Resource block
The resource block defines the physical resources of the device including type of measurement,
memory, etc. The resource block also defines functionality, such as shed times, that is common across
multiple blocks. The block has no linkable inputs or outputs and it performs memory-level diagnostics.
Table B-1. Resource Block Parameters
Number
Parameter
Description
01
ST_REV
The revision level of the static data associated with the function block.
02
TAG_DESC
The user description of the intended application of the block.
03
STRATEGY
The strategy field can be used to identify grouping of blocks.
04
ALERT_KEY
The identification number of the plant unit.
05
MODE_BLK
The actual, target, permitted, and normal modes of the block. For further description, see
the Mode parameter formal model in FF-890.
06
BLOCK_ERR
This parameter reflects the error status associated with the hardware or software
components associated with a block. Multiple errors may be shown. For a list of enumeration
values, see FF-890, Block_Err formal model.
07
RS_STATE
State of the function block application state machine. For a list of enumeration values, see
FF-890.
08
TEST_RW
Read/write test parameter - used only for conformance testing.
09
DD_RESOURCE
String identifying the tag of the resource which contains the Device Description for the
resource.
10
MANUFAC_ID
Manufacturer identification number - used by an interface device to locate the DD file for the
resource.
11
DEV_TYPE
Manufacturer's model number associated with the resource - used by interface devices to
locate the DD file for the resource.
12
DEV_REV
Manufacturer revision number associated with the resource - used by an interface device to
locate the DD file for the resource.
13
DD_REV
Revision of the DD associated with the resource - used by the interface device to locate the
DD file for the resource.
14
GRANT_DENY
Options for controlling access of host computer and local control panels to operating, tuning
and alarm parameters of the block.
15
HARD_TYPES
The types of hardware available as channel numbers. The supported hardware type is:
SCALAR_INPUT
16
RESTART
Allows a manual restart to be initiated.
1. Run: This is passive state of this parameter.
2. Restart resource: To clear up the problems like garbage collection.
3. Restart with defaults: reset all configurable function block application objects to their
initial value i.e. their value before any configuration was done by the user. This will also
remove appended serial numbers of function block tags
4. Restart processor: provides a way to hit the reset button on the processor associated with
the resource.
5. Restart to append serial number: Appends serial number to function block tags.
11. Restart default blocks: defaults manufacturer pre-instantiated blocks.
00809-0100-4377, Rev CA
Block Information
34
17
FEATURES
Used to show supported resource block options. The supported features are:
SOFT_WRITE_LOCK_SUPPORT, HARD_WRITE_LOCK_SUPPORT, REPORTS, UNICODE,
MULTI_BIT_ALARM_SUPPORT and FB_ACTION_RESTART_RELINK
18
FEATURE_SEL
Used to select resource block options.
19
CYCLE_TYPE
Identifies the block execution methods available for this resource. The supported cycle
types are: SCHEDULED, and COMPLETION_OF_BLOCK_EXECUTION
20
CYCLE_SEL
Used to select the block execution method for this resource.
21
MIN_CYCLE_T
Time duration of the shortest cycle interval of which the resource is capable.
22
MEMORY_SIZE
Available configuration memory in the empty resource. To be checked before attempting a
download.
23
NV_CYCLE_T
Minimum time interval specified by the manufacturer for writing copies of NV parameters to
non-volatile memory. Zero means it will never be automatically copied. At the end of
NV_CYCLE_T, only those parameters which have changed need to be updated in NVRAM.
24
FREE_SPACE
Percent of memory available for further configuration. Zero in preconfigured resource.
25
FREE_TIME
Percent of the block processing time that is free to process additional blocks.
26
SHED_RCAS
Time duration at which to give up on computer writes to function block RCas locations. Shed
from RCas will never happen when SHED_RCAS = 0.
27
SHED_ROUT
Time duration at which to give up on computer writes to function block ROut locations.
Shed from ROut will never happen when SHED_ROUT = 0.
28
FAULT_STATE
Condition set by loss of communication to an output block, fault promoted to an output
block or physical contact. When FAIL_SAFE condition is set, then output function blocks will
perform their FAIL_SAFE actions.
29
SET_FSTATE
Allows the FAIL_SAFE condition to be manually initiated by selecting Set.
30
CLR_FSTATE
Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has
cleared.
31
MAX_NOTIFY
Maximum number of unconfirmed notify messages possible.
32
LIM_NOTIFY
Maximum number of unconfirmed alert notify messages allowed.
33
CONFIRM_TIME
The time the resource will wait for confirmation of receipt of a report before trying again.
Retry will not happen when CONFIRM_TIME=0.
34
WRITE_LOCK
If set, all writes to static and non-volatile parameters are prohibited, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
35
UPDATE_EVT
This alert is generated by any change to the static data.
36
BLOCK_ALM
The BLOCK_ALM is used for all configuration, hardware, connection failure or system
problems in the block. The cause of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
37
ALARM_SUM
The current alert status, unacknowledged states, unreported states, and disabled states of
the alarms associated with the function block.
38
ACK_OPTION
Selection of whether alarms associated with the block will be automatically acknowledged.
39
WRITE_PRI
Priority of the alarm generated by clearing the write lock.
40
WRITE_ALM
This alert is generated if the write lock parameter is cleared.
41
ITK_VER
Major revision number of the interoperability test case used in certifying this device as
interoperable. The format and range are controlled by the fieldbus FOUNDATION.
42
FD_VER
This parameter's value equals the value of the major version of the Field Diagnostics
specification that this device was designed to.
43
FD_FAIL_ACTIVE
Reflects the error conditions that are being detected as active as selected for this category. It
is a bit string, so that multiple conditions may be shown.
44
FD_OFFSPEC_ACTIVE
Reflects the error conditions that are being detected as active as selected for this category. It
is a bit string, so that multiple conditions may be shown.
45
FD_MAINT_ACTIVE
Reflects the error conditions that are being detected as active as selected for this category. It
is a bit string, so that multiple conditions may be shown.
Table B-1. Resource Block Parameters
Number
Parameter
Description
00809-0100-4377, Rev CA
46
FD_CHECK_ACTIVE
Reflects the error conditions that are being detected as active as selected for this category. It
is a bit string, so that multiple conditions may be shown.
47
FD_FAIL_MAP
Maps conditions to be detected as active for this alarm category. Thus the same condition
may be active in all, some, or none of the 4 alarm categories.
48
FD_OFFSPEC_MAP
Maps conditions to be detected as active for this alarm category. Thus the same condition
may be active in all, some, or none of the 4 alarm categories.
49
FD_MAINT_MAP
Maps conditions to be detected as active for this alarm category. Thus the same condition
may be active in all, some, or none of the 4 alarm categories.
50
FD_CHECK_MAP
Maps conditions to be detected as active for this alarm category. Thus the same condition
may be active in all, some, or none of the 4 alarm categories.
51
FD_FAIL_MASK
Allows the user to suppress any single or multiple conditions that are active, in this category,
from being broadcast to the host through the alarm parameter. A bit equal to ‘1’ will mask
i.e. inhibit the broadcast of a condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast
of a condition.
52
FD_OFFSPEC_MASK
Allows the user to suppress any single or multiple conditions that are active, in this category,
from being broadcast to the host through the alarm parameter. A bit equal to ‘1’ will mask
i.e. inhibit the broadcast of a condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast
of a condition.
53
FD_MAINT_MASK
Allows the user to suppress any single or multiple conditions that are active, in this category,
from being broadcast to the host through the alarm parameter. A bit equal to ‘1’ will mask
i.e. inhibit the broadcast of a condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast
of a condition.
54
FD_CHECK_MASK
Allows the user to suppress any single or multiple conditions that are active, in this category,
from being broadcast to the host through the alarm parameter. A bit equal to ‘1’ will mask
i.e. inhibit the broadcast of a condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast
of a condition.
55
FD_FAIL_ALM
Used primarily to broadcast a change in the associated active conditions, which are not
masked, for this alarm category to a Host System.
56
FD_OFFSPEC_ALM
Used primarily to broadcast a change in the associated active conditions, which are not
masked, for this alarm category to a Host System.
57
FD_MAINT_ALM
Used primarily to broadcast a change in the associated active conditions, which are not
masked, for this alarm category to a Host System.
58
FD_CHECK_ALM
Used primarily to broadcast a change in the associated active conditions, which are not
masked, for this alarm category to a Host System.
59
FD_FAIL_PRI
Allows the user to specify the priority of this alarm category.
60
FD_OFFSPEC_PRI
Allows the user to specify the priority of this alarm category.
61
FD_MAINT_PRI
Allows the user to specify the priority of this alarm category.
62
FD_CHECK_PRI
Allows the user to specify the priority of this alarm category.
63
FD_SIMULATE
Allows the conditions to be manually supplied when simulation is enabled. When simulation
is disabled both the diagnostic simulate value and the diagnostic value track the actual
conditions. The simulate jumper is required for simulation to be enabled and while
simulation is enabled the recommended action will show that simulation is active.
64
FD_RECOMMEN_ACT
A device enumerated summarization of the most severe condition or conditions detected.
The DD help should describe by enumerated action, what should be done to alleviate the
condition or conditions. 0 is defined as Not Initialized, 1 is defined as No Action Required, all
others defined by manufacturer.
65
FD_EXTENDED_ACTIVE_1
An optional parameter or parameters to allow the user finer detail on conditions causing an
active condition in the FD_*_ACTIVE parameters.
66
FD_EXTENDED_MAP_1
An optional parameter or parameters to allow the user finer control on enabling conditions
contributing to the conditions in FD_*_ACTIVE parameters.
67
COMPATIBILITY_REV
Optionally used when replacing field devices. The correct usage of this parameter presumes
the COMPATIBILITY_REV value of the replacing device should be equal or lower than the
DEV_REV value of the replaced device.
68
HARDWARE_REVISION
Manufacturer hardware revision
69
SOFTWARE_REV
Manufacturer hardware revision
Table B-1. Resource Block Parameters
Number
Parameter
Description
00809-0100-4377, Rev CA
Block Information
36
70
PD_TAG
PD tag description of device
71
DEV_STRING
Used to load new licensing into the device. The value can be written but will always read
back with a value of 0.
72
DEV_OPTIONS
Indicates which miscellaneous and diagnostic device licensing options are enabled. It also
indicates Transducer options.
73
OUTPUT_BOARD_SN
Output board serial number
74
FINAL_ASSY_NUM
Same final assembly number placed on the neck label
75
DOWNLOAD_MODE
Gives access to the boot block code for over the wire downloads
76
HEALTH_INDEX
Parameter shall be set based on the active FD alarms or PWA alarms. HEALTH_INDEX will
show 100 if target mode of block is OOS or there are no active alarms in device. The table
below represents HEALTH_INDEX value when FD or PWA alarms are active in a device.
77
FAILED_PRI
Designates the alarming priority of the FAILED_ALM and also used as switch b/w FD and
legacy PWA. If value is greater than or equal to 1 then PWA alerts will be active in device else
device will have FD alerts.
78
RECOMMENDED_ACTION
Enumerated list of recommended actions displayed with a device alert
79
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational
80
MAINT _ALM
Alarm indicating the device needs maintenance soon. If the condition is ignored, the device
will eventually fail.
81
ADVISE _ALM
Alarm indicating advisory alarms. These conditions do not have a direct impact on the
process or device integrity.
82
FAILED_ENABLE
Enabled FAILED_ALM alarm conditions. Corresponds bit for bit to the FAILED_ACTIVE. A bit
on means that the corresponding alarm condition is enabled and will be detected. A bit off
means the corresponding alarm condition is disabled and will not be detected. This
parameter is the Read Only copy of FD_FAIL_MAP.
83
FAILED_MASK
Mask of Failure Alarm. Corresponds bit for bit to the FAILED_ACTIVE. A bit on means that the
failure is masked out from alarming. This parameter is the Read Only copy of FD_FAIL_MASK.
84
FAILED_ACTIVE
Enumerated list of failure conditions within a device. All open bits are free to be used as
appropriate for each specific device.This parameter is the Read Only copy of
FD_FAIL_ACTIVE.
85
MAINT_PRI
Designates the alarming priority of the MAINT_ALM
86
MAINT_ENABLE
Enabled MAINT_ALM alarm conditions. Corresponds bit for bit to the MAINT_ACTIVE. A bit
on means that the corresponding alarm condition is enabled and will be detected. A bit off
means the corresponding alarm condition is disabled and will not be detected.This
parameter is the Read Only copy of FD_OFFSPEC_MAP.
87
MAINT_MASK
Mask of Maintenance Alarm. Corresponds bit for bit to the MAINT_ACTIVE. A bit on means
that the failure is masked out from alarming.This parameter is the Read Only copy of
FD_OFFSPEC_MASK.
88
MAINT_ACTIVE
Enumerated list of maintenance conditions within a device. All open bits are free to be used
as appropriate for each specific device. This parameter is the Read Only copy of
FD_OFFSPEC_ACTIVE.
89
ADVISE_PRI
Designates the alarming priority of the ADVISE_ALM
90
ADVISE_ENABLE
Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE. A bit
on means that the corresponding alarm condition is enabled and will be detected. A bit off
means the corresponding alarm condition is disabled and will not be detected.This
parameter is the Read Only copy of FD_MAINT_MAP & FD_CHECK_MAP.
91
ADVISE_MASK
Mask of Advisory Alarm. Corresponds bit for bit to the ADVISE_ACTIVE. A bit on means that
the failure is masked out from alarming.This parameter is the Read Only copy of
FD_MAINT_MASK & FD_CHECK_MASK.
92
ADVISE_ACTIVE
Enumerated list of advisory conditions within a device. All open bits are free to be used as
appropriate for each specific device. This parameter is the Read Only copy of
FD_MAINT_ACTIVE & FD_CHECK_ACTIVE.
93
DEVICE_INFO
Group of device specific informational parameters – software download class, address, and
maximum current.
94
SWITCHES_STATE
The state of hardware simulation and write lock security switches.
Table B-1. Resource Block Parameters
Number
Parameter
Description
00809-0100-4377, Rev CA
Block errors
The table below lists conditions reported in the BLOCK_ERR parameter.
Modes
The resource block supports two modes of operation as defined by the MODE_BLK parameter:
Automatic (Auto)
The block is processing its normal background memory checks.
Out of service (OOS)
The block is not processing its tasks. When the resource block is in OOS, all blocks within the resource (device) are forced
into OOS. The BLOCK_ERR parameter shows Out of Service. In this mode, changes can be made to all configurable
parameters. The target mode of a block may be restricted to one or more of the supported modes.
Table B-2. BLOCK_ERR Conditions
Number
Name and description
0
Other
1
Block Configuration Error: A feature in CYCLE_SEL is set that is not supported by CYCLE_TYPE.
3
Simulate Active: This indicates that the simulation jumper is in place. This is not an indication that the I/O blocks are using
simulated data.
6
Device needs maintenance soon
7
Input failure/process variable has bad status
9
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory.
10
Lost Static Data: Static data that is stored in non-volatile memory
has been lost.
11
Lost NV Data: Non-volatile data that is stored in non-volatile memory
has been lost.
13
Device Needs Maintenance Now
14
Power Up: The device was just powered-up.
15
OOS: The actual mode is out of service.
00809-0100-4377, Rev CA
Block Information
38
Alarm detection
A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of block error for the resource block
are defined above. A write alarm is generated whenever the WRITE_LOCK parameter is cleared. The priority of the write
alarm is set in the following parameter:
WRITE_PRI
Status handling
There are no status parameters associated with the resource block.
Table B-3. Alarm Priority Levels
Number
Description
0
The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.
1
An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
2
An alarm condition with a priority of 2 is reported to the operator, but does not require operator attention (such as
diagnostics and system alerts).
3-7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
8-15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
00809-0100-4377, Rev CA
B.2 LCD transducer block
Parameter
Index
Description
ALERT_KEY
4
The identification number of the plant unit.
BLK_TAG_1
16
The tag of the block containing DP1.
BLK_TAG_2
22
The tag of the block containing DP2.
BLK_TAG_3
28
The tag of the block containing DP3.
BLK_TAG_4
34
The tag of the block containing DP4.
BLK_TAG_5
40
The tag of the block containing DP5.
BLK_TAG_6
46
The tag of the block containing DP6.
BLK_TAG_7
52
The tag of the block containing DP7.
BLK_TAG_8
58
The tag of the block containing DP8.
BLK_TYPE_1
15
The enumerated block type for DP1's block.
BLK_TYPE_2
21
The enumerated block type for DP2's block.
BLK_TYPE_3
27
The enumerated block type for DP3's block.
BLK_TYPE_4
33
The enumerated block type for DP4's block.
BLK_TYPE_5
39
The enumerated block type for DP5's block.
BLK_TYPE_6
45
The enumerated block type for DP3's block.
BLK_TYPE_7
51
The enumerated block type for DP7's block.
BLK_TYPE_8
57
The enumerated block type for DP8's block.
BLOCK_ALM
8
The BLOCK_ALM is used for all configuration, hardware, connection failure or system
problems in the block. The cause of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status attribute. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may be reported without
clearing the Active status, if the subcode has changed.
BLOCK_ERR
6
This parameter reflects the error status associated with the hardware or software
components associated with a block. it is a bit string, so that multiple errors may be shown.
COLLECTION_DIRECTORY
13
A directory that specifies the number, starting indicies, and DD Item ID's of the data
collections in each transducer block.
CUSTOM_TAG_1
18
The block description that is displayed for DP1.
CUSTOM_TAG _2
24
The block description that is displayed for DP2.
CUSTOM_TAG _3
30
The block description that is displayed for DP3.
CUSTOM_TAG _4
36
The block description that is displayed for DP4.
CUSTOM_TAG_5
42
The block description that is displayed for DP5.
CUSTOM_TAG_6
48
The block description that is displayed for DP6.
CUSTOM_TAG_7
54
The block description that is displayed for DP7.
CUSTOM_TAG_8
60
The block description that is displayed for DP8.
CUSTOM_UNITS_1
20
This is the user entered units that are displayed when UNITS_TYPE_1=Custom.
CUSTOM_UNITS _2
26
This is the user entered units that are displayed when UNITS_TYPE_2=Custom.
CUSTOM_UNITS _3
32
This is the user entered units that are displayed when UNITS_TYPE_3=Custom.
CUSTOM_UNITS _4
38
This is the user entered units that are displayed when UNITS_TYPE_4=Custom.
00809-0100-4377, Rev CA
Block Information
40
CUSTOM_UNITS_5
44
This is the user entered units that are displayed when UNITS_TYPE_5=Custom.
CUSTOM_UNITS_6
50
This is the user entered units that are displayed when UNITS_TYPE_6=Custom.
CUSTOM_UNITS_7
56
This is the user entered units that are displayed when UNITS_TYPE_7=Custom.
CUSTOM_UNITS_8
62
This is the user entered units that are displayed when UNITS_TYPE_8=Custom.
DISPLAY_PARAM_SEL
14
This will determine which Display Parameters are active.
Bit 0 = DP1
Bit 1 = DP2
Bit 2 = DP3
Bit 3 = DP4
Bit 4 = DP5
Bit 5 = DP6
Bit 6 = DP7
Bit 8 = DP8
MODE_BLK
5
The actual, target, permitted, and normal modes of the block.
PARAM_INDEX_1
17
The relative index of DP1 within its block.
PARAM_INDEX_2
23
The relative index of DP2 within its block.
PARAM_INDEX_3
27
The relative index of DP3 within its block.
PARAM_INDEX_4
35
The relative index of DP4 within its block.
PARAM_INDEX_5
41
The relative index of DP5 within its block.
PARAM_INDEX_6
47
The relative index of DP6 within its block.
PARAM_INDEX_7
53
The relative index of DP7 within its block.
PARAM_INDEX_8
59
The relative index of DP8 within its block.
ST_REV
1
The revision level of the static data associated with the function block.
STRATEGY
3
The strategy field can be used to identify grouping of blocks.
TAG_DESC
2
The user description of the intended application of the block.
TRANSDUCER_DIRCTORY
9
A directory that specifies the number and starting indicies of the transducers in the
transducer block.
TRANSDUCER_TYPE
10
Identifies the transducer that follows.
UNITS_TYPE_1
19
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_2
25
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_3
31
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_4
37
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_5
43
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_6
49
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_7
55
This parameter determines where the units for the display parameter come from.
UNITS_TYPE_8
61
This parameter determines where the units for the display parameter come from.
UPDATE_EVT
7
This alert is generated by any change to the staic data.
XD_ERROR
12
Provides additional error codes related to transducer blocks.
TRANSDUCER_TYPE_VER
11
Version of transducer identified by TRANSDUCER_TYPE
Parameter
Index
Description
00809-0100-4377, Rev CA
January 2018
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
[email protected]
Europe Regional Office
Emerson Automation Solutions Europe GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
[email protected]
Asia Pacific Regional Office
Emerson Automation Solutions
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
[email protected]
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
[email protected]
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Terms and Conditions of
Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Plantweb, Rosemount, and Rosemount logotype are trademarks of Emerson.
FOUNDATION Fieldbus is a trademark of FieldComm Group.
DTM is a trademark of FDT group.
All other marks are the property of their respective owners.
© 2018 Emerson. All rights reserved.