INTRODUCTION
The
AVC63-2.5
Voltage
Regulators
are
designed for use on 50/60 Hz brushless
generators. The regulator includes frequency
compensation, a solid-state build-up circuit,
EMI filtering, and remote adjust capability.
Warning
To prevent personal injury or equipment
damage, only qualified technicians or
operators should install, operate, or
service this device.
ELECTRICAL SPECIFICATIONS
Dc Output Power:
2.5 Adc at 63 Vdc (157.5W) maximum
continuous,
3.97 Adc at 100 Vdc (397W) forcing one
minute
(at 240 Vac input).
Exciter Field Dc Resistance:
25.2 ohms minimum.
Ac Power Input:
Operating range: 171 to 264 Vac, +10%,
Single phase, 50/60 Hz, Burden: 350 VA.
Sensing Input:
171-264 Vac, +10%, Single phase, 50/60 Hz,
Burden: 350 VA.
Regulation Accuracy:
Better than ±1.0% no load to full load.
EMI Suppression:
Internal electromagnetic interference filter
(EMI filter).
Voltage Build-up:
Internal provisions for automatic voltage build-
up from generator residual voltages as low as
10 Vac.
Terminations:
1/4 inch "Fast-On" terminals.
PHYSICAL SPECIFICATIONS
Operating Temperature:
-40° C (-40° F) to +60° C (+140° F).
Storage Temperature:
-40° C (-40° F) to +85° C (+185° F).
Vibration:
Withstands 1.5 Gs at 5 to 29 Hz; 0.036"
double amplitude at 29 to 52 Hz; and 5 Gs at
52 to 500 Hz.
Shock:
Withstands up to 15 Gs in each of three
mutually perpendicular axes.
Weight:
3.8 oz. (0.107 kg) Net.
FUSES
It is recommended that fuses with high
interruption capability be installed per the
interconnection diagram to protect wiring from
faults before the regulator. Refer to the
Interconnection Drawings.
NOTE
Fuse
must
be
installed
per
the
interconnection diagrams to avoid inter-
rupting the field current.
AVC63-2.5 Outline Diagram (Top View)
AVC63-2.5 Outline Diagram (Side View)
V/HZ "CORNER FREQUENCY" SELECTION
AND ADJUSTMENT
The corner frequency can be adjusted by the
UF ADJ rheostat on the AVR. Clockwise
rotation results in raising the corner frequency
(shifting the curve to the right). To set the UF
rheostat:
1. Adjust the UF Rheostat fully CCW.
2. Start the generator and set at rated voltage.
3. Adjust the generator frequency to the
desired kneepoint frequency.
4. Slowly
adjust
the
UF
ADJ
rheostat
clockwise (CW) until the generator voltage
just begins to decrease.
Typical Frequency Compensation Curves
OPERATION
The following system operation procedures
provide instructions for adjusting the AVC63-
2.5 voltage regulator. Symptoms resulting
from a faulty regulator and certain generator
system problems are included, together with
suggested remedies.
Complete
the
following
steps
before
proceeding with the system start-up.
CAUTION
Meggers
and
high
potential
test
equipment must not be used. Incorrect
use of such equipment could damage the
semiconductors
contained
in
the
regulator.
PRELIMINARY SET-UP
1. Verify
that
the
voltage
regulator
specifications conform with the generator
system requirements.
2. Ensure the voltage regulator is correctly
connected to the generator system.
3. Install the fuses as described in Fuses.
4. Set the regulator VOLT ADJ and
external VOLT ADJ (if used) as follows:
Regulator VOLT ADJ: Fully CCW
Remote VOLT ADJ:
Centered
SYSTEM START-UP
1. Perform preliminary set-up as described
in the above paragraphs.
NOTE
All voltage readings are to be taken with
an average reading voltmeter.
2. Start prime mover and bring up to rated
speed.
RESULT: Voltage should build up. If not,
perform Field Flashing.
3. Slowly adjust the regulator VOLT ADJ CW
until the generator output voltage reaches
the nominal value. If used, adjust the
remote VOLT ADJ to set the generator
voltage to the exact value desired.
RESULT: Voltage should build up to rated
value. If voltage does not build up to rated
value, check generator for short or excessive
load.
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL.
IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT
TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE
USED IN ANY MANNER DETRIMENTAL TO THE
INTEREST OF BASLER ELECTRIC COMPANY.
Publication:
9 3183 00 991
© 1998, Basler Electric Co., Highland, IL 62249
First Printing January 1998
Revision: A
March 1998
INSTRUCTION MANUAL
FOR
VOLTAGE REGULATOR
Model: AVC63-2.5
Part Number: 9 3183 00 101
4. Check regulator under normal operating
and loading conditions.
RESULT: Voltage regulation should be better
than ±1.0% no-load to full-load. If regulation
is not within this range, perform the following
steps:
1. Voltage reduction under load may be due to
speed change from no load to full load,
causing the frequency compensation (V/Hz)
circuit
to
reduce
voltage
at
lower
frequencies.
2. Replace voltage regulator.
OPERATIONAL TEST
1. Connect the test setup as shown in the
following figure, Operational Test. Do not
apply power. Ensure that the light bulb is
rated for 120 V and is less than 100 W.
2. Adjust the regulator VOLT ADJ and/or
remote VOLT ADJ to maximum CW.
3. Apply 240 V, 50/60 Hz power to the
regulator. The light bulb should illuminate.
4. Slowly adjust the regulator VOLT ADJ
control CCW. At the regulation point, the light
bulb should extinquish.
The following notes (∆) apply to the intercon-
nection diagrams:
1. If external pot is not used, short terminals 6
and 7.
2. Item not supplied by Basler Electric.
3. Select fuses with high interrupting capacity.
4. Excitation On/Off Switch (If Used).
Operational Test
Interconnection Diagram, 277/480 V Nominal, 3-Phase, 4-Wire, Wye
Connection
Interconnection Diagram, 120/240 V Nominal, 1-Phase, 3-Wire
Interconnection Diagram, 120/208 V Nominal, 3-Phase, 4-Wire, Wye
Connection
Potentiometer and Connector Locations