More than just power.TM

Power Supply/Chargers Installation Guide Models Include: eFlow4N/eFlow4NX - 4A @ 12VDC or 24VDC Class 2 Power-Limited Output eFlow4N8/eFlow4NX8 - 4A @ 12VDC or 24VDC - Eight (8) Class 2 Power-Limited Fused Outputs eFlow4N8D/eFlow4NX8D - 4A @ 12VDC or 24VDC - Eight (8) Class 2 Power-Limited PTC Outputs Installing Company: _________________ Service Rep. Name: _______________________________________ Address: ____________________________________________________ Phone #: ______________________ Altronix Corp. 140 58th St. Brooklyn, NY all-guide s.com

- 2 -

eFlow4N Series Overview: Altronix eFlow4N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). eFlow4N Series Power Supply Configuration Reference Chart: Altronix Model Number Nominal DC Outputs Maximum Supply Current for Main and Aux. Outputs (A) Power-Limited Output Input Rating: 120VAC, 60Hz Input Fuse Rating Battery Fuse Rating Ripple Voltage (mV) Under low battery condition Power Distribution Modiule Number of Outputs Fused Outputs Ratings Auto-Resettable PTC Outputs Ratings Accommodates up to 7AH Batteries Accommodates up to 12AH Batteries [DC] [AUX] 12VDC Output Range (V) 24VDC Output Range (V) 12VDC Output Range (V) 24VDC Output Range (V) eFlow4N 10.1- 13.2 20.28- 26.4 10.05- 13.2 20.2- 26.4 4A P 3.5A 5A/ 250V 5A/ 32V 730 N/A 1 – – P – eFlow4NX – – – P eFlow4N8 10.1- 13.2 20.28- 26.4 10.05- 13.2 20.2- 26.4 4A P 3.5A 5A/ 250V 5A/ 32V 730 PD8UL 8 2.5A – P – eFlow4NX8 2.5A – – P eFlow4N8D 9.78- 13.2 20.0- 26.4 10.05- 13.2 20.2- 26.4 4A P 3.5A 5A/ 250V 5A/ 32V 730 PD8ULCB 8 – 2A P – eFlow4NX8D – 2A – P These units are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable to power: sensors, electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/NFPA70/NFPA72 and the Canadian Electrical Code, Part 1. UL Listings for US Installations: UL 294 - UL Listed for Access Control System Units. UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems. UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems. UL Listings for Canadian Installations: ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control. California State Fire Marshal European Conformity Stand-by Specifications: Battery Burg. Applications 4 hr. Stand-by/ 15 min. Alarm Fire Applications 24 hr. Stand-by/ 5 min. Alarm Access Control Applications Stand-by 7AH 0.4A/4A N/A 15 Mins./4A 12AH 1A/4A 0.3A/4A 35 Mins./4A 40AH (for eFlow4NX refer to Fig. 7, pg. 10) 4A/4A 1.2A/4A Over 4 Hours/4A 65AH (for eFlow4NX refer to Fig. 7, pg. 10) 4A/4A 1.5A/4A Over 4 Hours/4A Altronix Corp. 140 58th St. Brooklyn, NY

- 3 -

Specifications: Installation Instructions: Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Ca- nadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises. 1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground. 2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board (Fig. 1i, pg. 5). 3. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12). 4. Measure output voltage before connecting devices. This helps avoiding potential damage. 5. Connect devices to be powered: a. For eFlow4N/eFlow4NX connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) carefully observing correct polarity. For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5). 6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating. 7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory relay outputs. Input: • 120VAC, 60Hz. Output: • For output voltage and supply current refer to eFlow4N series Power Supply Configuration Reference Chart, pg. 2. • Auxiliary Class 2 power-limited output rated @ 1A (unswitched). • Overvoltage protection. Battery Backup: • Built-in charger for sealed lead acid or gel type batteries. • Maximum charge current 1.54A. • Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption. Fire Alarm Disconnect: • Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger. Supervision: • AC fail supervision (form “C” contacts). • Battery fail & presence supervision (form “C” contacts). • Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge. Fuse/PTC Ratings: • Refer to eFlow4N Series Power Supply Configuration Reference Chart, pg. 2. Visual Indicators: • Green AC Power LED indicates 120VAC present. • AC input and DC output LED indicators. Additional Features: • Short circuit and overload protection. • Unit is complete with power supply, enclosure, battery leads, and cam lock. Enclosure Dimensions (approximate H x W x D): eFlow4N, eFlow4N8, eFlow4N48D: 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm). eFlow4NX, eFlow4NX8, eFlow4NX8D: 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).

- 4 -

eFlow4N Series 8. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5). To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5). Note: Must be set to ON position for Burglar Alarm Applications. 9. To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5). To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position (Fig. 1c, pg. 5). 10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Fig. 1d, pg. 5). 11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Fig. 1e, pg. 5). 12. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Fig. 4, pg. 7 or Fig. 6, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. Wiring: Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow4N: 12VDC or 24VDC nominal rated @ 4A max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires. Note: Maximum charging current under discharges is 1.54A. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. LED Diagnostics: Power Supply/Charger Red (DC) Green (AC/AC1) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output. Power Distribution Module Green (AC) Power Distribution Module Status ON Normal operating condition. OFF No Power Output.

- 5 -

Terminal Identification: Power Supply/Charger Terminal Legend Function/Description L, N Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) (Fig. 1a, pg. 5). – DC + 12VDC or 24VDC nominal @ 4A continuous output (power-limited output) (Fig. 1h, pg. 5). Trigger EOL Supervised Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5). NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5). + AUX – Auxiliary Class 2 power-limited output rated @ 1A (unswitched) (Fig. 1f, pg. 5). AC Fail NC, C, NO Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5). Bat Fail NC, C, NO Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5). – BAT + Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 5). Power Distribution Module Terminal Legend PD8UL/PD8ULCB Function/Description 1P to 8P Positive DC power outputs. 1N to 8N Negative DC power outputs. Fig. 1 - eFlow4N Board configuration Trouble/Time Limited Warning of Stand-by Batteries: For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation. L G N NC C NO NC C NO BAT FAIL AC FAIL --- DC + AC AC1 DC --- BAT + + AUX – TRIGGER EOL SUPERVISED 5A 250V 5A 250V 5A 32V 5A NO GND RESET enable disable 1 min. 2 hr. AC DELAY SHUTDOWN O N 1a 1b 1g 1h 1e 1f 1d 1c 1i OFF --- 24V ON --- 12V ON

- 6 -

eFlow4N Series Fig. 2 - Battery trouble indication - For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6). NC C NO NC C NO BAT FAIL AC FAIL POWER SOURCE RED INDICATING LAMP Power Distribution Module(s): Fig. 3a - PD8UL Power Distribution Board Fig. 3b - PD8ULCB - Power Distribution Board N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board (Factory Installed) Replace fuses with the same type and rating 3.5A, 250V. DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs ( ) N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board (Factory Installed) DC Output to devices 1P-8P Power Outputs, 1N-8N Common Outputs ( ) all-guide s.com

- 7 -

Fig. 4 - eFlow4N configuration L G N NC C NO NC C NO BAT FAIL AC FAIL --- DC + AC AC1 DC --- BAT + – AUX + TRIGGER EOL SUPERVISED 5A 250V RESET GND NO disable enable 2 hr. 1 min. AC DELAY SHUTDOWN O N Door Wire Strap (from Enclosure to Door) CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries. Switch Detail Green Lead (ground) Power- limited 120VAC power mains Non Power- limited Battery & AC Supervision Circuit (Power-limited) Battery Connections (Non Power-limited) Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for UL603, UL1481 and Canadian installations. Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for UL603, UL1481 and Canadian installations. PD8UL/PD8ULCB DC Output to devices (refer to Fig. 3a or 3b for board configuration pg. 6) OFF --- 24V ON --- 12V ON ON 1 Switch On - 12V Switch Off - 24V Edge of Enclosure to Access Control Panel or U.L. Listed Reporting Device Enclosure Tamper Switch (Not Included)

- 8 -

eFlow4N Series NEC Power-Limited Wiring Requirements for eFlow4N Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ- ent conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-­limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a). Fig. 5 Fig. 5a 120VAC Input 60Hz (non power-limited) Optional UL Listed Battery Enclosure (non power-limited) Supervisory, Fire Alarm Interface and Aux. output Connections (power-limited) External Jacketed Shield Incorrect Wire Handling Correct Wire Handling Pull back external jacketed shield approx. 1/2”. Wire Insulation Solid Copper Conductors DC Outputs (power-limited) Power Distribution (power- limited) Battery Connections (non power-limited)

- 9 -

Fig. 6 - eFlow4NX configuration PD8UL/PD8ULCB DC Output to devices (refer to Fig. 3a or 3b for board configuration pg. 6) Door Wire Strap (from Enclosure to Door) Battery & AC Supervision Circuit (power-limited) CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. A UL Listed external battery enclosure must be used if using the 40AH or 65AH batteries. Switch Detail L G N NC C NO NC C NO BAT FAIL AC FAIL --- DC + AC AC1 DC --- BAT + – AUX + TRIGGER EOL SUPERVISED 5A 250V RESET GND NO disable enable 2 hr. 1 min. AC DELAY SHUTDOWN O N 120VAC power mains (non power-limited) Class 1 Power-limited Green Lead (ground) Battery connections (non power-limited) Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for UL603, UL1481 and Canadian installations. Optional Rechargeable Stand-by Battery for UL294 Applications. Note: 12V batteries required for UL603, UL1481 and Canadian installations. OFF --- 24V ON --- 12V ON ON 1 Switch On - 12V Switch Off - 24V Edge of Enclosure to Access Control Panel or U.L. Listed Reporting Device Enclosure Tamper Switch (Not Included)

- 10 -

eFlow4N Series NEC Power-Limited Wiring Requirements for eFlow4NX Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ- ent conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power-­limited applications use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a). Fig. 7 Fig. 7a External Jacketed Shield Incorrect Wire Handling Correct Wire Handling Pull back external jacketed shield approx. 1/2”. Wire Insulation Solid Copper Conductors 120VAC Input 60Hz (non power- limited) Supervisory, Fire Alarm Interface and Aux. output Connections (power-limited) Battery Connections (non power- limited) DC Output (power-limited) Power Distribution (power-limited) Optional UL Listed Battery Enclosure (non power-limited)

- 11 -

Enclosure Dimensions (BC300): eFlow4N, eFlow4N8, eFlow4N8D 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm) 1.40” (36mm) 1.40” (36mm) 4.85” (123mm) 4.85” (123mm) 1.40” (36mm) 1.40” (36mm) 5.10” (130mm) 5.10” (130mm) 13.0” (330mm) 5.10” (130mm) 6.5625” (167mm) 1.20” (31mm) 1.20” (31mm) 1.20” (31mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 3.25” (83mm) 1.0” (25mm) 1.0” (25mm) 10.5” (267mm) 1.0” (25mm) 1.0” (25mm) 0.75” (19mm) 0.75” (19mm) 0.9375” (24mm) 0.9375” (24mm) 11.0” (279mm) 12.5” (318mm) all-guide s.com

- 12 -

eFlow4N Series 1.5” (38.1mm) 1.5” (38.1mm) 1.5” (38.1mm) 5.0” (127.0mm) 5.0” (127.0mm) 1.5” (38.1mm) 2.0” (50.8mm) 2.0” (50.8mm) 1.75” (44.45mm) 1.75” (44.45mm) 4.5” (114.3mm) 1.25” (31.75mm) 4.5” (114.3mm) 1.25” (31.75mm) 1.25” (31.75mm) 1.25” (31.75mm) 1.1” (27.94mm) 1.1” (27.94mm) 0.79” (20.06mm) 1.1” (27.94mm) 0.91” (23.114mm) 0.91” (23.114mm) 1.375” (34.925mm) 1.125” (28.575mm) 15.5” (393.7mm) 4.615” (117.22mm) 12.23” (310.64mm) 4.615” (117.22mm) 1.5” (38.1mm) 1.5” (38.1mm) 4.615” (117.22mm) 4.615” (117.22mm) Enclosure Dimensions (BC400): eFlow4NX, eFlow4NX8, eFlow4NX8D 15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

- 13 -

Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow4N output. System Sensor Smoke Detector/Base Detector Type Max Stand-by Current (mA) Alarm Current (mA) B112LP Base 0.12 36 B114LP Base * * B404B Base * * DH100ACDC Photoelectric 0.15 0.70 DH100ACDCLP Photoelectric 0.15 0.70 DH100ACDCLPW Photoelectric 0.15 0.70 DH400ACDCI Ionization Duct 25 95 DH400ACDCP Photoelectric Duct 25 95 1112/24/D Ionization 0.05 50 1424 Ionization 0.10 41 1451 (w/B402B Base) Ionization 0.10 39 2112/24ATR Photoelectric 0.50 60/70 2112/24AITR Photoelectric 0.50 60/70 2112/24/D Photoelectric 0.05 50 2112/24T/D Photoelectric w/135 o Thermal 0.05 50 2112/24TSRB Photoelectric w/135 o Thermal Supervisory Relay 15 45 2312/24TB Photoelectric 0.12 50 2412 (12 volt) Photoelectric 0.12 77 2424 Photoelectric 0.10 41 2451 Photoelectric 0.10 39 2451TH (with/B402B Base) Photoelectric 0.10 39 2W-MOD Loop Test/Maintenance Mod. 30 50 4W-B (12/24 volt) Photoelectric I3 0.05 23 4WT-B (12/24 volt) Photoelectric I3 w/Therm 0.05 23 4WTA-B (12/24 volt) I3 Photo w/Therm/Sounder 0.05 35 4WTR-B (12/24 volt) I3 Photo w/Therm/Relay 0.05 35 4WITAR-B (12/24 volt) I3 Photo w/Isolated Therm/Sounder/Relay 0.05 50 2W-MOD2 I3 Loop Test/Maintenance Mod. 0.05 * RRS-MOD I3 Reversing Relay/Sync Module 0.05 * 6424 Projected Beam 10 28.4 Beam 1224(S) Projected Beam 17 38.5 * Contact manufacturer for current draws. A.2 Relays Table A-2 below lists relays compatible with eFlow4N output. Manufacturer Model Current (mA) Manufacturer Model Current (mA) System Sensor PR-1** PR-2* PR-3* EOLR-1 R-10T** R-14T** 15 30 30 30 23 23 System Sensor R-20T** R-24T** R-10E** R-14E** R-20E** R-24E** 40 40 23 23 40 40 * Compatible only with eFlow4N, eFlow4NX, eFlow4N8, eFlow4NX8. ** Compatible only when unit is set for 24VDC.

- 14 -

eFlow4N Series eFlow Power Supply/Chargers can be Controlled and Monitored while Reporting Power/Diagnostics from Anywhere over the Network... LINQ2 Mounts Inside any eFlow Enclosure LINQ2 - Network Communication Module LINQ2 provides remote IP access to real-time data from eFlow power supply/chargers to help keep systems up and running at optimal levels. It facilitates fast and easy installation and set-up, minimizes system downtime, and eliminates unnecessary service calls, which helps reduce Total Cost of Ownership (TCO) - as well as creating a new source of Recurring Monthly Revenue (RMR). LINQ2 Features: - UL Listed in the U.S. and Canada. - Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN. - Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service, input trigger state change, output state change and unit temperature. - Access control and user managment: Restrict read/write, Restrict users to specific resources - Two (2) integral network controlled Form “C” Relays. - Three (3) programmable input triggers: Control relays and power supplies via external hardware sources. - Email and Windows Dashboard notifications - Event log tracks history. - Secure Socket Layer (SSL). - Programmable via USB or web browser - includes operating software and 6 ft. USB cable. LINQ2 Module Network Connection: Installation, Programming and Monitoring L G N NC C NO NC C NO BAT FAIL AC FAIL AC AC1 DC TRIGGER EOL SUPERVISED disable enable 2 hr. 1 min. AC DELAY SHUTDOWN O N eFlow Power Supply/Charger

- 15 -

Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A. IIeFlow4N Series B27R MEMBER Notes:

CUT ALONG DOTTED LINE

Power Supply/Chargers Operating Guide Models Include: Model Input 120VAC, 60Hz Output Power- Limited Auxiliary Power-Limited Output (unswitched) Ripple Voltage 12VDC 24VDC eFlow4N, eFlow4N8, eFlow4N8D 3.5A 4A 4A P 1A 730mV eFlow4NX, eFlow4NX8, eFlow4NX8D Overview: The eFlow4N series power supply/chargers convert a 120VAC, 60Hz input to a 12VDC or 24VDC output. Stand-by Specifications: Battery Burg. Applications 4 hr. Stand-by/ 15 min. Alarm Fire Applications 24 hr. Stand-by/ 5 min. Alarm Access Control Applications Stand-by 7AH 0.4A/4A N/A 15 Mins./4A 12AH 1A/4A 0.3A/4A 35 Mins./4A 40AH 4A/4A 1.2A/4A Over 4 Hours/4A 65AH 4A/4A 1.5A/4A Over 4 Hours/4A Battery Backup: • Built-in charger for sealed lead acid or gel type batteries. • Maximum charge current 1.54A. • Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous with no interruption. LED Diagnostics: Red (DC) Green (AC/AC1) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC. Stand-by battery supplying power. OFF ON No DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output. Installing Company: _________________ Service Rep. Name: _______________________________________ Address: ____________________________________________________ Phone #: ______________________ Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow4N Series, Rev. 4NRP052213 for complete instructions. This sheet is to be removed, framed and posted next to the unit. Rev. 4NRP052213 all-guide s.com