Altronix eFlow Series Installation Manual
Read Online
Read the Altronix eFlow Series Installation Manual online using the built-in PDF viewer.
Text of the manual
More than just power.TM
Power Supply/Chargers
Installation Guide
Models Include:
eFlow4N/eFlow4NX
- 4A @ 12VDC or 24VDC Class 2 Power-Limited Output
eFlow4N8/eFlow4NX8
- 4A @ 12VDC or 24VDC
- Eight (8) Class 2 Power-Limited Fused Outputs
eFlow4N8D/eFlow4NX8D
- 4A @ 12VDC or 24VDC
- Eight (8) Class 2 Power-Limited PTC Outputs
Installing Company: _________________ Service Rep. Name: _______________________________________
Address: ____________________________________________________ Phone #: ______________________
Altronix Corp.
140 58th St. Brooklyn, NY
all-guide
s.com
- 2 -
eFlow4N Series
Overview:
Altronix eFlow4N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output
(see Power Supply Configuration Reference Chart and Specifications).
eFlow4N Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Nominal DC Outputs
Maximum Supply Current for
Main and Aux. Outputs (A)
Power-Limited Output
Input Rating:
120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution
Modiule
Number of Outputs
Fused Outputs Ratings
Auto-Resettable
PTC Outputs Ratings
Accommodates up to
7AH Batteries
Accommodates up to
12AH Batteries
[DC]
[AUX]
12VDC Output
Range (V)
24VDC Output
Range (V)
12VDC Output
Range (V)
24VDC Output
Range (V)
eFlow4N
10.1-
13.2
20.28-
26.4
10.05-
13.2
20.2-
26.4
4A
P
3.5A
5A/
250V
5A/
32V
730
N/A
1
–
–
P
–
eFlow4NX
–
–
–
P
eFlow4N8
10.1-
13.2
20.28-
26.4
10.05-
13.2
20.2-
26.4
4A
P
3.5A
5A/
250V
5A/
32V
730
PD8UL
8
2.5A
–
P
–
eFlow4NX8
2.5A
–
–
P
eFlow4N8D
9.78-
13.2
20.0-
26.4
10.05-
13.2
20.2-
26.4
4A
P
3.5A
5A/
250V
5A/
32V
730
PD8ULCB 8
–
2A
P
–
eFlow4NX8D
–
2A
–
P
These units are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable to power:
sensors, electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/NFPA70/NFPA72 and the
Canadian Electrical Code, Part 1.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
California State Fire Marshal
European Conformity
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH
0.4A/4A
N/A
15 Mins./4A
12AH
1A/4A
0.3A/4A
35 Mins./4A
40AH (for eFlow4NX refer to
Fig. 7, pg. 10)
4A/4A
1.2A/4A
Over 4 Hours/4A
65AH (for eFlow4NX refer to
Fig. 7, pg. 10)
4A/4A
1.5A/4A
Over 4 Hours/4A
Altronix Corp.
140 58th St. Brooklyn, NY
- 3 -
Specifications:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Ca-
nadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be
located indoors within the protected premises.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in
the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two
holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pgs. 11-12). Secure enclosure to earth ground.
2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board
(Fig. 1i, pg. 5).
3. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 1a, pg. 5). Use 14 AWG
or larger for all power connections. Secure green wire lead to earth ground.
Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to
qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 12).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered:
a. For eFlow4N/eFlow4NX connect devices to terminals marked [– DC +] (Fig. 1h, pg. 5).
b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked
[1P & 1N] through [8P & 8N] (Fig. 3a & 3b, pg. 6) carefully observing correct polarity.
For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm
Interface. Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel
type. Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 5). Use two (2) 12VDC batteries
connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH),
CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2
batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory
relay outputs.
Input:
• 120VAC, 60Hz.
Output:
• For output voltage and supply current refer to
eFlow4N series Power Supply Configuration
Reference Chart, pg. 2.
• Auxiliary Class 2 power-limited output
rated @ 1A (unswitched).
• Overvoltage protection.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when
AC fails.
Transfer to stand-by battery power is instantaneous
with no interruption.
Fire Alarm Disconnect:
• Supervised Fire Alarm disconnect (latching or
non-latching) 10K EOL resistor. Operates on a
normally open (NO) or normally closed (NC) trigger.
Supervision:
• AC fail supervision (form “C” contacts).
• Battery fail & presence supervision
(form “C” contacts).
• Low power shutdown. Shuts down DC output
terminals if battery voltage drops below 71-73% for
12V units and 70-75% for 24V units (depending on
the power supply). Prevents deep battery discharge.
Fuse/PTC Ratings:
• Refer to eFlow4N Series Power Supply
Configuration Reference Chart, pg. 2.
Visual Indicators:
• Green AC Power LED indicates 120VAC present.
• AC input and DC output LED indicators.
Additional Features:
• Short circuit and overload protection.
• Unit is complete with power supply, enclosure,
battery leads, and cam lock.
Enclosure Dimensions (approximate H x W x D):
eFlow4N, eFlow4N8, eFlow4N48D:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm).
eFlow4NX, eFlow4NX8, eFlow4NX8D:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
- 4 -
eFlow4N Series
8. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Fig. 1c, pg. 5).
To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Fig. 1c, pg. 5).
Note: Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position (Fig. 1c, pg. 5).
To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position (Fig. 1c, pg. 5).
10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 1d, pg. 5).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 1e, pg. 5).
12. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the
top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right
side (Fig. 4, pg. 7 or Fig. 6, pg. 9). Connect tamper switch wiring to the Access Control Panel input or the
appropriate UL Listed reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper
voltage level eFlow4N: 12VDC or 24VDC nominal rated @ 4A max.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage
(12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54A.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC)
Green (AC/AC1)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC)
Power Distribution Module Status
ON
Normal operating condition.
OFF
No Power Output.
- 5 -
Terminal Identification:
Power Supply/Charger
Terminal Legend
Function/Description
L, N
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited)
(Fig. 1a, pg. 5).
– DC +
12VDC or 24VDC nominal @ 4A continuous output (power-limited output) (Fig. 1h, pg. 5).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally
open, normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).
NO, GND RESET
FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
+ AUX –
Auxiliary Class 2 power-limited output rated @ 1A (unswitched) (Fig. 1f, pg. 5).
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 5).
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 1g, pg. 5).
Power Distribution Module
Terminal Legend
PD8UL/PD8ULCB
Function/Description
1P to 8P
Positive DC power outputs.
1N to 8N
Negative DC power outputs.
Fig. 1 - eFlow4N Board configuration
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote
annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of
the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate
input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed
for local annunciation.
L
G
N
NC C NO
NC C NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX –
TRIGGER EOL
SUPERVISED
5A 250V
5A 250V
5A 32V
5A
NO GND
RESET
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
O
N
1a
1b
1g
1h
1e
1f
1d
1c
1i
OFF --- 24V
ON --- 12V
ON
- 6 -
eFlow4N Series
Fig. 2 - Battery trouble indication -
For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure.
Wire one leg of a UL Listed, power-limited power source to the indicating lamp.
Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact
terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6).
NC C NO
NC C NO
BAT FAIL
AC FAIL
POWER
SOURCE
RED INDICATING
LAMP
Power Distribution Module(s):
Fig. 3a - PD8UL Power Distribution Board
Fig. 3b - PD8ULCB - Power Distribution Board
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1
2
3
4
5
6
7
8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Replace fuses with the same type and rating 3.5A, 250V.
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
(
)
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1
2
3
4
5
6
7
8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
(
)
all-guide
s.com
- 7 -
Fig. 4 - eFlow4N configuration
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +
TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
Door
Wire
Strap
(from
Enclosure
to Door)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Switch Detail
Green
Lead
(ground)
Power-
limited
120VAC
power mains
Non Power-
limited
Battery & AC
Supervision
Circuit
(Power-limited)
Battery
Connections
(Non
Power-limited)
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
PD8UL/PD8ULCB
DC Output to devices
(refer to Fig. 3a or 3b
for board configuration pg. 6)
OFF --- 24V
ON --- 12V
ON
ON
1
Switch On - 12V
Switch Off - 24V
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Tamper Switch
(Not Included)
- 8 -
eFlow4N Series
NEC Power-Limited Wiring Requirements for eFlow4N Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 5a).
Fig. 5
Fig. 5a
120VAC Input 60Hz
(non power-limited)
Optional UL Listed
Battery Enclosure
(non power-limited)
Supervisory,
Fire Alarm
Interface and
Aux. output
Connections
(power-limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
DC Outputs
(power-limited)
Power
Distribution
(power-
limited)
Battery Connections
(non power-limited)
- 9 -
Fig. 6 - eFlow4NX configuration
PD8UL/PD8ULCB
DC Output to devices
(refer to Fig. 3a or 3b
for board configuration pg. 6)
Door
Wire Strap
(from
Enclosure
to Door)
Battery & AC Supervision
Circuit (power-limited)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using the 40AH or 65AH batteries.
Switch Detail
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +
TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
120VAC power mains
(non power-limited)
Class 1
Power-limited
Green
Lead
(ground)
Battery connections
(non power-limited)
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
OFF --- 24V
ON --- 12V
ON
ON
1
Switch On - 12V
Switch Off - 24V
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Tamper Switch
(Not Included)
- 10 -
eFlow4N Series
NEC Power-Limited Wiring Requirements for eFlow4NX Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 7a).
Fig. 7
Fig. 7a
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
120VAC Input
60Hz
(non power-
limited)
Supervisory, Fire Alarm Interface
and Aux. output Connections
(power-limited)
Battery
Connections
(non power-
limited)
DC Output
(power-limited)
Power
Distribution
(power-limited)
Optional UL Listed
Battery Enclosure
(non power-limited)
- 11 -
Enclosure Dimensions (BC300):
eFlow4N, eFlow4N8, eFlow4N8D
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)
1.40”
(36mm)
1.40”
(36mm)
4.85”
(123mm)
4.85”
(123mm)
1.40”
(36mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
13.0”
(330mm)
5.10”
(130mm)
6.5625”
(167mm)
1.20”
(31mm)
1.20”
(31mm)
1.20”
(31mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
(25mm)
10.5”
(267mm)
1.0”
(25mm)
1.0”
(25mm)
0.75”
(19mm)
0.75”
(19mm)
0.9375”
(24mm)
0.9375”
(24mm)
11.0”
(279mm)
12.5”
(318mm)
all-guide
s.com
- 12 -
eFlow4N Series
1.5”
(38.1mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
1.75”
(44.45mm)
1.75”
(44.45mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.25”
(31.75mm)
1.1”
(27.94mm)
1.1”
(27.94mm)
0.79”
(20.06mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
0.91”
(23.114mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
15.5”
(393.7mm)
4.615”
(117.22mm)
12.23”
(310.64mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
Enclosure Dimensions (BC400):
eFlow4NX, eFlow4NX8, eFlow4NX8D
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
- 13 -
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with eFlow4N output.
System Sensor Smoke
Detector/Base
Detector Type
Max
Stand-by
Current
(mA)
Alarm
Current
(mA)
B112LP
Base
0.12
36
B114LP
Base
*
*
B404B
Base
*
*
DH100ACDC
Photoelectric
0.15
0.70
DH100ACDCLP
Photoelectric
0.15
0.70
DH100ACDCLPW
Photoelectric
0.15
0.70
DH400ACDCI
Ionization Duct
25
95
DH400ACDCP
Photoelectric Duct
25
95
1112/24/D
Ionization
0.05
50
1424
Ionization
0.10
41
1451 (w/B402B Base)
Ionization
0.10
39
2112/24ATR
Photoelectric
0.50
60/70
2112/24AITR
Photoelectric
0.50
60/70
2112/24/D
Photoelectric
0.05
50
2112/24T/D
Photoelectric w/135
o Thermal
0.05
50
2112/24TSRB
Photoelectric w/135
o Thermal Supervisory Relay
15
45
2312/24TB
Photoelectric
0.12
50
2412 (12 volt)
Photoelectric
0.12
77
2424
Photoelectric
0.10
41
2451
Photoelectric
0.10
39
2451TH (with/B402B Base)
Photoelectric
0.10
39
2W-MOD
Loop Test/Maintenance Mod.
30
50
4W-B (12/24 volt)
Photoelectric I3
0.05
23
4WT-B (12/24 volt)
Photoelectric I3 w/Therm
0.05
23
4WTA-B (12/24 volt)
I3 Photo w/Therm/Sounder
0.05
35
4WTR-B (12/24 volt)
I3 Photo w/Therm/Relay
0.05
35
4WITAR-B (12/24 volt)
I3 Photo w/Isolated Therm/Sounder/Relay
0.05
50
2W-MOD2
I3 Loop Test/Maintenance Mod.
0.05
*
RRS-MOD
I3 Reversing Relay/Sync Module
0.05
*
6424
Projected Beam
10
28.4
Beam 1224(S)
Projected Beam
17
38.5
* Contact manufacturer for current draws.
A.2 Relays
Table A-2 below lists relays compatible with eFlow4N output.
Manufacturer
Model
Current (mA)
Manufacturer
Model
Current (mA)
System Sensor
PR-1**
PR-2*
PR-3*
EOLR-1
R-10T**
R-14T**
15
30
30
30
23
23
System Sensor
R-20T**
R-24T**
R-10E**
R-14E**
R-20E**
R-24E**
40
40
23
23
40
40
* Compatible only with eFlow4N, eFlow4NX, eFlow4N8, eFlow4NX8.
** Compatible only when unit is set for 24VDC.
- 14 -
eFlow4N Series
eFlow Power Supply/Chargers can be
Controlled and Monitored while Reporting
Power/Diagnostics from Anywhere
over the Network...
LINQ2 Mounts Inside any eFlow Enclosure
LINQ2 - Network Communication Module
LINQ2 provides remote IP access to real-time data from eFlow power
supply/chargers to help keep systems up and running at optimal
levels. It facilitates fast and easy installation and set-up, minimizes
system downtime, and eliminates unnecessary service calls, which
helps reduce Total Cost of Ownership (TCO) - as well as creating a
new source of Recurring Monthly Revenue (RMR).
LINQ2
Features:
- UL Listed in the U.S. and Canada.
- Local or remote control of up to (2) two Altronix eFlow power output(s) via LAN and/or WAN.
- Monitor real time diagnostics: DC output voltage, output current, AC & battery status/service,
input trigger state change, output state change and unit temperature.
- Access control and user managment: Restrict read/write, Restrict users to specific resources
- Two (2) integral network controlled Form “C” Relays.
- Three (3) programmable input triggers: Control relays and power supplies via external hardware sources.
- Email and Windows Dashboard notifications
- Event log tracks history.
- Secure Socket Layer (SSL).
- Programmable via USB or web browser - includes operating software and 6 ft. USB cable.
LINQ2 Module
Network
Connection:
Installation,
Programming
and Monitoring
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL
AC FAIL
AC
AC1
DC
TRIGGER EOL
SUPERVISED
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
eFlow
Power
Supply/Charger
- 15 -
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIeFlow4N Series
B27R
MEMBER
Notes:
CUT ALONG DOTTED LINE
Power Supply/Chargers Operating Guide
Models Include:
Model
Input
120VAC,
60Hz
Output
Power-
Limited
Auxiliary
Power-Limited
Output (unswitched)
Ripple
Voltage
12VDC
24VDC
eFlow4N,
eFlow4N8,
eFlow4N8D
3.5A
4A
4A
P
1A
730mV
eFlow4NX,
eFlow4NX8,
eFlow4NX8D
Overview:
The eFlow4N series power supply/chargers convert a 120VAC, 60Hz input to a 12VDC or 24VDC output.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications Stand-by
7AH
0.4A/4A
N/A
15 Mins./4A
12AH
1A/4A
0.3A/4A
35 Mins./4A
40AH
4A/4A
1.2A/4A
Over 4 Hours/4A
65AH
4A/4A
1.5A/4A
Over 4 Hours/4A
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when AC fails.
Transfer to stand-by battery power is instantaneous with no interruption.
LED Diagnostics:
Red (DC)
Green (AC/AC1)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Installing Company: _________________ Service Rep. Name: _______________________________________
Address: ____________________________________________________ Phone #: ______________________
Refer to the eFlow Power Supply/Chargers Installation Guide: IIeFlow4N Series, Rev. 4NRP052213 for complete
instructions. This sheet is to be removed, framed and posted next to the unit.
Rev. 4NRP052213
all-guide
s.com