Belimo Gateway MP to Modbus RTU

16 / 20 T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes www.belimo.com Diagnostics and testing tool A PC-based tool is available for diagnostics and tests which can be utilised as a Modbus Master and which uses graphics elements to depict the actuator information. The UK24MOD Tool can be obtained through the Internet: www.belimo.eu | Products … | Download Center Connecting the PC-Tool for parameterisation of the MP/MFT(2) actuators The MP network can be scanned, actuators can be addressed and actuator-specific parameters (e.g. running tim ...

Belimo Gateway MP to Modbus RTU

www.belimo.com T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes 15 / 20 Modbus register description (continued) Register 12: Actuator type Actuator type; the allocation may deviate from the basic category with some actuators. Actuator type 0 Actuator not connected / not known 1 Air/water actuators with/without safety function 2 Valve actuator, linear 3 Valve actuator, rotary 4 Fire damper actuator 5 VAV controller / EPIV 6 MPL actuator Note: In the event of a communications interruption, the Gateway will discard the affected actuator after 1 ...

Belimo Gateway MP to Modbus RTU

12 / 20 T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes www.belimo.com Modbus register overview (continued) Service register Note Devices with V1.06 and older use registers register 161 – 164 for service information. Register Number High Byte Low Byte 1001 Modbus baud rate 1002 Modbus address 1003 Response delay [ms] 1004 Firmware Version The response delay (Register 1003) is backed up continuously. ...

Belimo Gateway MP to Modbus RTU

18 / 20 T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes www.belimo.com ...

Belimo Gateway MP to Modbus RTU

www.belimo.com T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes 7 / 20 Electrical installation (continued) With DC 24 V supply: Calculation of the maximum signal conductor lengths To be read out from the mass of curves: For cables with wire-Ø [mm²] Cable length [m] 0.75 55 1.00 75 1.50 110 2.50 190 The power consumption [W] of the MP/MPL/MFT(2) actuators used is to be added, and the corresponding signal conductor lengths are to be read from the diagram. Example: The following is connected to the MP-Bus: 1 pc. NM24A-MP, 1 pc. SM24A-MP, 1 pc ...

Belimo Gateway MP to Modbus RTU

2 / 20 T9-UK24MOD • en • v1.7 • 02.2014 • Subject to changes www.belimo.com Complete overview Gateway MP / Modbus RTU Suitable MP/MPL/MFT(2) Actuators Damper actuators Fire damper actuators VAV actuators Actuators for characterised control valve, butterfly valves and globe valves EPIV actuators MPL Actuators ...

Belimo UK24MOD user guide recommended for: G100 SERIES, CELLINE AS, LOGIC io, BulletPlus, G201N4.

⚠️ Download Safety

The Gateway Product information (20 pages) is completely safe to download (last scan date: 02/03/2026).

Related PDF Instructions for Belimo UK24MOD:

Gateway Equipment: Frequently Requested

Have some Questions about Belimo UK24MOD Device?

Get valuable and actionable advices from other Belimo UK24MOD device users. Describe your problem or question, regarding the using of UK24MOD, in as much detail as possible, and other users will be able to answer you.