INSTALLATION INSTRUCTIONS FOR TRIMLESS IN DRYWALL: FIRE-FX2™ FIRE-RATED CABINETS
1. NOTE that trimless cabinets for drywall are designed to be
installed after the first layer of drywall, but prior to the second
layer.
2. Remove all hardware and glazing, unlock cabinet if lock provided.
3. Install a framed opening above, below and at both sides of cabinet
opening at specified location. Wall opening width, height and
depth must correspond with dimensions indicated in catalog or
detail and submittal sheet.
4. Cabinet must be installed after the first layer of drywall has been
put up. The cabinet wall flange will lay on top of that layer of dry-
wall.
5. Use holes provided in cabinet tub for attaching to stud or substrate
material. If wall configuration does not allow for that, then follow
step 6 below; otherwise, skip to step 7.
6. [Drilling Additional Holes in Tub] Drill (2) 1/8” (3.2 mm) holes
through tub on each side of cabinet.
7. Place cabinet in position and attach with Universal # 6 x 2-1/2” (6.4
cm) self-drilling screws. Be sure not to over-tighten on either side, which could pull the cabinet out of position in the opening and result in an exposed gap between
the cabinet frame and wall opening.
8. Start the screw without completely tightening; then start a screw on the opposite side of the tub. One all screws are started, tighten each screw in a “criss-cross”
pattern. A torque setting of 4-6 is recommended if using a screw gun.
9. Once screws are fully tightened, check cabinet for square and plumb. Adjust if necessary. All interior sides should be straight with no bowing or warping.
10. Check cabinet door assembly for freedom of movement. If it binds, shim as necessary to remove any racking of tub at attachments of stud. Cabinet will need to be
removed temporarily in order to add shims.
11. Finish wall construction and install final top layer of drywall. The opening left in this layer of drywall for the FIRE-FX2™ cabinet should be 2” less in width and
height than the opening originally made ins in step 3 above;; or 1” all around. The top layer of drywall will therefore cover the cabinet wall flange, resulting in a
“trimless” appearance.
12. Remove protective plastic from acrylic or glass and install decal if intended for glass. (Panorama Models Glazing is Pre-Installed)
13. Align glazing on inside of door, holding in place while installing glass mounting clips on inside of door. Do not over-tighten.
14. Install handle and roller catch or SAF-T-LOK™ in door. Check alarm if provided.
© Activar Construction Products Group, Inc 2015
FIRE-FX2™ AND SAF-T-LOK™ ARE TRADEMARKS OF ACTIVAR, INC.
Fire-Rating: Fire-FX2™ cabinets are fabricated in accordance with the UL label for
one and two hour combustible and non-combustible wall system building codes.
The fire testing has met the requirement of ANSI/UL 1479 (ASTM –E814) and
ULC/CAN S115 for membrane and penetration firestops.
Installation instructions must be strictly adhered to in order to obtain the fire rating.
HEADQUARTERS & CUSTOMER SERVICE: 9702 NEWTON AV S, BLOOMINGTON, MN 55431 PH: 800-554-6077 FAX: 952-835-2218 EMAIL: [email protected] WWW.ACTIVARCPG.COM
ACPG WEST COAST/SAMSON: COMMERCE, CA WAREHOUSES: DALLAS TX, FORT MYERS FL, LANCASTER PA, ATLANTA GA, CHICAGO, IL, SEATTLE WA, OMAHA NE, FARGO ND 12/10/2014 14I-103 REV B
Note: Drawings shown on this page are examples only of typical installation in a fire-rated wall, and are not to be used as recommendations for wall construction.
Distributed by:
Safety Emporium
PO Box 1003
Blackwood, NJ 08012
Ph: (866) 326-5412 toll-free
Fax: (856) 553-6154
[email protected]
www. safetyemporium.com
INSTALLATION INSTRUCTIONS FOR PLASTER/STUCCO WALLS: FIRE-FX2™ FIRE-RATED CABINETS
© Activar Construction Products Group, Inc 2015
FIRE-FX2™ AND SAF-T-LOK™ ARE TRADEMARKS OF ACTIVAR, INC.
Fire-Rating: Fire-FX2™ cabinets are fabricated in accordance with the UL label for
one and two hour combustible and non-combustible wall system building codes.
The fire testing has met the requirement of ANSI/UL 1479 (ASTM –E814) and
ULC/CAN S115 for membrane and penetration firestops.
Installation instructions must be strictly adhered to in order to obtain the fire rating.
HEADQUARTERS & CUSTOMER SERVICE: 9702 NEWTON AV S, BLOOMINGTON, MN 55431 PH: 800-554-6077 FAX: 952-835-2218 EMAIL: [email protected] WWW.ACTIVARCPG.COM
ACPG WEST COAST/SAMSON: COMMERCE, CA WAREHOUSES: DALLAS TX, FORT MYERS FL, LANCASTER PA, ATLANTA GA, CHICAGO, IL, SEATTLE WA, OMAHA NE, FARGO ND 12/10/2014 14I-103 REV B
Note: Drawings shown on this page are examples only of typical installation in a fire-rated wall, and are not to be used as recommendations for wall construction.
1. NOTE these trimless cabinets are designed to be installed in
plaster/stucco wall conditions prior to the application of lath
and plaster/stucco.
2. Remove all hardware and glazing, unlock cabinet if lock provid-
ed.
3. Install a framed opening above, below and at both sides of cabi-
net opening at specified location. Wall opening width, height and
depth must correspond with dimensions indicated in catalog or
detail and submittal sheet.
4. Use holes provided in cabinet tub for attaching to stud or sub-
strate material. If wall configuration does not allow for that, then
follow step 6 below; otherwise, skip to step 7.
5. [Drilling Additional Holes in Tub] Drill (2) 1/8” (3.2 mm) holes
through tub on each side of cabinet.
6. Place cabinet in position and attach with Universal # 6 x 2-
1/2” (6.4 cm) self-drilling screws. Be sure not to over-tighten on
either side, which could pull the cabinet out of position in the
opening and result in an exposed gap between the cabinet frame
and wall opening.
7. Start the screw without completely tightening; then start a screw
on the opposite side of the tub. One all screws are started, tighten each screw in a “criss-cross” pattern. A torque setting of 4-6 is recommended if using a screw gun.
8. Once screws are fully tightened, check cabinet for square and plumb. Adjust if necessary. All interior sides should be straight with no bowing or warping.
9. Check cabinet door assembly for freedom of movement. If it binds, shim as necessary to remove any racking of tub at attachments of stud. Cabinet will need to be removed
temporarily in order to add shims.
10. Finish wall construction. Lay metal lath material over substrate and fasten securely. Ensure that lath extends over the wall flange at the perimeter of the Fire-FX2™ .
11. Apply plaster and/or stucco over metal lath as per manufacturer’s instructions and job specifications. Use the forward-projecting edge of the FIRE-FX2™ cabinet as a
“plaster stop”, for a smooth and flush final installation
12. Remove protective plastic from acrylic or glass and install decal if intended for glass. (Panorama Models Glazing is Pre-Installed)
13. Align glazing on inside of door, holding in place while installing glass mounting clips on inside of door. Do not over-tighten.
14. Install handle and roller catch or SAF-T-LOK™ in door. Check alarm if provided.