ABB TCC300 Quick Start Manual

Brand: ABB
Category: Controller
Model: TCC300 (Quick Start Manual)
File Type: PDF
File Size: —
Pages: 12
Text of ABB TCC300 Quick Start Manual

ABB TCC300 Quick Start Guide

TCC300 Tapchanger Control 1 LCD SCREEN Pressing any push button will wake up the LCD and display the heading corresponding to the “Hot Button” label inside the push button - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR. 2 EXIT/WAKE Push button The EXIT WAKE Push button wakes the LCD from sleep mode and begins scrolling through a list of user pro- grammed metered/calculated values. 3 VR Pushbutton Activates the user defined Voltage Reduct

Out of Band Low Voltage

LOWER LED Out of Band High Voltage REV PWR LED Indicates reverse power flow OK LED Illuminates to indicate the micro controller is functioning properly and is extin- guished when a Motor Seal-in Failure Block is in effect COM1 TX/RX LEDS Indicates when control is transmitting and/or receiving data ALARM LED Indicates any of the programmable alarms are activated V/RED LED Indicates voltage reduction has been invoked

ABB TCC300 24-Pin Connector (P2)

Voltage Input (Polarity) Neutral Load Current (Return) Load Current (Polarity) Circulating Current (Polarity) Circulating Current (Return) Tapchanger Raise Output Motor Power Input Voltage Reduction Step #2 or Contact KeepTrack 1R1L/1N Input Contact "Wetting" Supply + 12 Vdc Operations Counter/ Switch Status Input #1 Operations Counter/ Switch Status Input #2 Input 1 Motor Seal-in/ Switch Status Neutral Position Detector #1 Neutral

Death or severe electrical shock can occur

In no case should the line current circuit be interrupted with the regulator or transformer energized. Do not remove auxiliary current transformers without shorting the current inputs. Exercise care during installation, operation and maintenance procedures The equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified per- sonnel should in

ABB TCC300 Press EXIT to go to the Menu Header.

Press either ← or → to move sideways to the adjacent Menu Header. Press ENT to view Tapchanger Status Press ENT to view Alarm Status Press ENT to view Input Status Press ENT to view Output Status Peak RMS Curr x.x mA (x.x) T Avg RMS Curr x.x mA (xx.x) T Profile Duration xxx.x ms(xxx.x) T Peak Motor Current E x.x mA Voltage % THD x.x % Current % THD xx.x % Press ENT to view Voltage Harmonics Press

ABB TCC300 * Power Flow Reverse setting screens are only available when the “Reverse Power Operation” selection under “Common Settings”

is selected to either: REGULATE REVERSE,REG. R MEASURED SRC, DISTRIBUTED GENERATION, AUTO DETERMINE orAUTO DETERMINE MEASURED. If Distributed Generation is selected, then only LDC values can be set.Selecting BLOCK, IGNORE or RETURN TO NEUTRAL disables the Power Flow Reverse setting screens. Menu screens Active Setpoint Pro

Remote Voltage Bias

Enable/Disable disable RVB HB Timer 5 Secs RVB Scale Factor 1.0 Rev RVB Scale Factor 1.0 Run Through Neutral Enable/Disable disable Reset RTN Succ Ctr Press ENT to begin Max Allowed Taps 4 Max RTN Standby Ops 20 Taps Between Runs 1000 Max Load Current 50 mA Nameplate Auto/Man Sw Type SCAMP SWITCH Scamp Init Pwrup AUTO MODE Auto/Man Sw Type NONE/TOGGLE Comm Block A

Auto/Man Switch Type set to SCAMP

Programmable Alarm Prog Alarm Function –<0000000000000000 Prog Alarm Function NORMAL/ASDEADMANOUT OpCount Signal Alrm 0 Clear Sealin Alarm Ready Press ENTER Clr Low Current Blk Ready Press ENTER Clr RTN Fail To Opr Ready Press ENTER System Clock Set Date and Time 08/26/13 15:41:29 Daylight Savings disable Input Selection Input Selection 1 SWITCH STATUS Input Selection 2 NONSEQ INPUT Input Selection 3 VOLT

ABB TCC300 If Memory Card is present, the first menu

displayed under Communication is the Memory Card menu, otherwise the Memory Card menu is not displayed. If IEC 61850 is purchased COMMUNICATION CNFG UTIL Memory Card Load Setpoints Press ENT to begin Save Setpoints Press ENT to begin Save Datalog Press ENT to begin Save seq. of events Press ENT to begin Save oscillograph Press ENT to begin Clone save Press ENT to begin Clone load Press ENT t

Volt Cal Coefficient

32767 X Volt RMS Coefficient 32762 X Control Load I x.x mA Lag/Lead Curr Cal Coefficient 32767 X Power Factor X.XXX Lag/Lead I Sin Coefficient 0 X I Cos Coefficient 8192 X Motor Current x.xx mA Mtr Cal. Coefficient 8192 X Mtr Sin Coefficient 0 X Mtr Cos Coefficient 8192 X Calibration/Test Mtr RMS Coefficient 8192

1VAC384810-RG A © Copyright 2016 ABB. All rights reserved.

Contact us ABB Inc. EPMV Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone +1 (800) 523-2620 Phone +1 954-752-6700 Fax +1 954 345-5329 www.abb.com/substationautomation