Text of ABB TCC300 Quick Start Manual
ABB TCC300 Quick Start Guide
TCC300 Tapchanger Control
1
LCD SCREEN
Pressing any push button will wake up the LCD and display the heading corresponding to the “Hot Button” label
inside the push button - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR.
2
EXIT/WAKE
Push button
The EXIT WAKE Push button wakes the LCD from sleep mode and begins scrolling through a list of user pro-
grammed metered/calculated values.
3
VR Pushbutton
Activates the user defined Voltage Reduct
Out of Band Low Voltage
LOWER LED
Out of Band High Voltage
REV PWR LED
Indicates reverse power flow
OK LED
Illuminates to indicate the micro controller is functioning properly and is extin-
guished when a Motor Seal-in Failure Block is in effect
COM1 TX/RX LEDS
Indicates when control is transmitting and/or receiving data
ALARM LED
Indicates any of the programmable alarms are activated
V/RED LED
Indicates voltage reduction has been invoked
ABB TCC300 24-Pin Connector (P2)
Voltage Input (Polarity)
Neutral
Load Current (Return)
Load Current (Polarity)
Circulating Current (Polarity)
Circulating Current (Return)
Tapchanger Raise Output
Motor Power Input
Voltage Reduction Step #2 or
Contact KeepTrack 1R1L/1N Input
Contact "Wetting"
Supply + 12 Vdc
Operations Counter/
Switch Status Input #1
Operations Counter/
Switch Status Input #2
Input 1 Motor Seal-in/
Switch Status
Neutral Position Detector #1
Neutral
Death or severe electrical shock can occur
In no case should the line current circuit be interrupted with the regulator or transformer energized. Do not remove auxiliary
current transformers without shorting the current inputs.
Exercise care during installation, operation and maintenance procedures
The equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified per-
sonnel should in
ABB TCC300 Press EXIT to go to the Menu Header.
Press either ← or → to move sideways to the adjacent Menu Header.
Press ENT to view
Tapchanger Status
Press ENT to view
Alarm Status
Press ENT to view
Input Status
Press ENT to view
Output Status
Peak RMS Curr
x.x mA (x.x) T
Avg RMS Curr
x.x mA (xx.x) T
Profile Duration
xxx.x ms(xxx.x) T
Peak Motor Current E
x.x mA
Voltage % THD
x.x %
Current % THD
xx.x %
Press ENT to view
Voltage Harmonics
Press
ABB TCC300 * Power Flow Reverse setting screens are only available when the “Reverse Power Operation” selection under “Common Settings”
is selected to either: REGULATE REVERSE,REG. R MEASURED SRC, DISTRIBUTED GENERATION, AUTO DETERMINE orAUTO
DETERMINE MEASURED. If Distributed Generation is selected, then only LDC values can be set.Selecting BLOCK, IGNORE or
RETURN TO NEUTRAL disables the Power Flow Reverse setting screens.
Menu screens
Active Setpoint Pro
Remote Voltage Bias
Enable/Disable
disable
RVB HB Timer
5 Secs
RVB Scale Factor
1.0
Rev RVB Scale Factor
1.0
Run Through Neutral
Enable/Disable
disable
Reset RTN Succ Ctr
Press ENT to begin
Max Allowed Taps
4
Max RTN Standby Ops
20
Taps Between Runs
1000
Max Load Current
50 mA
Nameplate
Auto/Man Sw Type
SCAMP SWITCH
Scamp Init Pwrup
AUTO MODE
Auto/Man Sw Type
NONE/TOGGLE
Comm Block A
Auto/Man Switch Type set to SCAMP
Programmable Alarm
Prog Alarm Function
–<0000000000000000
Prog Alarm Function
NORMAL/ASDEADMANOUT
OpCount Signal Alrm
0
Clear Sealin Alarm
Ready Press ENTER
Clr Low Current Blk
Ready Press ENTER
Clr RTN Fail To Opr
Ready Press ENTER
System Clock
Set Date and Time
08/26/13 15:41:29
Daylight Savings
disable
Input Selection
Input Selection 1
SWITCH STATUS
Input Selection 2
NONSEQ INPUT
Input Selection 3
VOLT
ABB TCC300 If Memory Card is present, the first menu
displayed under Communication is the
Memory Card menu, otherwise the
Memory Card menu is not displayed.
If IEC 61850 is purchased
COMMUNICATION
CNFG UTIL
Memory Card
Load Setpoints
Press ENT to begin
Save Setpoints
Press ENT to begin
Save Datalog
Press ENT to begin
Save seq. of events
Press ENT to begin
Save oscillograph
Press ENT to begin
Clone save
Press ENT to begin
Clone load
Press ENT t
Volt Cal Coefficient
32767 X
Volt RMS Coefficient
32762 X
Control Load I
x.x mA Lag/Lead
Curr Cal Coefficient
32767 X
Power Factor
X.XXX Lag/Lead
I Sin Coefficient
0 X
I Cos Coefficient
8192 X
Motor Current
x.xx mA
Mtr Cal. Coefficient
8192 X
Mtr Sin Coefficient
0 X
Mtr Cos Coefficient
8192 X
Calibration/Test
Mtr RMS Coefficient
8192
1VAC384810-RG A © Copyright 2016 ABB. All rights reserved.
Contact us
ABB Inc.
EPMV Distribution Automation
4300 Coral Ridge Drive
Coral Springs, FL 33065, USA
Phone +1 (800) 523-2620
Phone +1 954-752-6700
Fax +1 954 345-5329
www.abb.com/substationautomation
ABB Controller Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
RELION 650 SERIES |
Guide: ABB RELION 650 SERIES (7YZ3XV, Upd.18-06-2026) |
110 | 636 | 147 | 18-06-2026 | |
6128/10 Series |
6128/10 Series (Controller ePDF Manual, #WU47QY) |
67 | 923 | 176 | 26-07-2026 |