ABB REV615 Product Manual
Read Online
Read the ABB REV615 Product Manual online using the built-in PDF viewer.
Text of the manual
2. Standard configurations................................................. 3
3. Protection functions........................................................7
4. Application..................................................................... 7
5. Supported ABB solutions............................................. 10
6. Control......................................................................... 11
7. Measurements............................................................. 12
8. Power quality................................................................12
9. Disturbance recorder....................................................12
10. Event log.....................................................................12
11. Recorded data............................................................ 12
12. Condition monitoring .................................................. 13
13. Trip-circuit supervision.................................................13
14. Self-supervision...........................................................14
15. Fuse failure supervision............................................... 14
16. Current circuit supervision........................................... 14
17. Access control............................................................ 14
18. Inputs and outputs...................................................... 14
19. Station communication................................................15
20. Technical data.............................................................20
21. Local HMI....................................................................46
22. Mounting methods...................................................... 47
23. Relay case and plug-in unit......................................... 47
24. Selection and ordering data.........................................47
25. Accessories and ordering data.................................... 48
26. Tools...........................................................................49
27. Cyber security............................................................. 50
28. Terminal diagrams.......................................................51
29. Certificates.................................................................. 53
30. References..................................................................53
31. Functions, codes and symbols....................................54
32. Document revision history........................................... 57
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2018 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
2
ABB
REV615 is a dedicated capacitor bank relay designed for the
protection, control, measurement and supervision of capacitor
banks used for compensation of reactive power in utility
substations and industrial power systems. REV615 can also be
used for protection of harmonic filter circuits, if the highest
significant harmonic component is the 11th. REV615 is a
member of ABB’s Relion® product family and part of its 615
protection and control product series. The 615 series relays are
characterized by their compactness and withdrawable-unit
design.
Re-engineered from the ground up, the 615 series has been
designed to unleash the full potential of the IEC 61850 standard
for communication and interoperability between substation
automation devices.
The relay provides main protection for single star, double star,
and H-bridge connected capacitor banks and harmonic filters
in distribution networks.
Depending on the chosen standard configuration, the relay is
adapted for the protection of H-bridge connected or double
star connected shunt capacitor banks. Once the standard
configuration relay has been given the application-specific
settings, it can directly be put into service.
The 615 series relays support a range of communication
protocols including IEC 61850 with Edition 2 support, process
bus according to IEC 61850-9-2 LE, IEC 60870-5-103,
Modbus® and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.
2. Standard configurations
REV615 is available in two alternative standard configurations.
The standard signal configuration can be altered by means of
the signal matrix or the graphical application functionality of the
Protection and Control IED Manager PCM600. Further, the
application configuration functionality of PCM600 supports the
creation of multi-layer logic functions using various logical
elements, including timers and flip-flops. By combining
protection functions with logic function blocks, the relay
configuration can be adapted to user-specific application
requirements.
The relay is delivered from the factory with default connections
described in the functional diagrams for binary inputs, binary
outputs, function-to-function connections and alarm LEDs.
Some of the supported functions in REV615 must be added
with the Application Configuration tool to be available in the
Signal Matrix tool and in the relay. The positive measuring
direction of directional protection functions is towards the
outgoing feeder.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
Issued: 2018-12-20
Revision: D
ABB
3
CONTROL AND INDICATION 1)
MEASUREMENT
CAPACITOR BANK PROTECTION AND CONTROL RELAY
STANDARD
CONFIGURATION
PROTECTION
LOCAL HMI
Object
Ctrl 2)
Ind 3)
CB
DC
ES
1) Check availability of binary inputs/outputs
from technical documentation
2) Control and indication function for
primary object
3) Status indication function for
primary object
R
L
Clear
ESC
I
O
Configuration
A
System
HMI
Time
Authorization
R
L
Clear
ESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
REMARKS
Optional
function
No. of
instances
Alternative
function to be
defined when
ordering
OR
Io/Uo
Calculated
value
3×
REV615
A
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass fiber (ST),
RS-485, RS-232
Redundant protocols:
HSR
PRP
RSTP
- I, Io
- Limit value supervision
- Load profile record
- RTD/mA measurement (optional)
- Symmetrical components
7
-
Analog interface types
1)
Current transformer
Voltage transformer
1) Conventional transformer inputs
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
- High-Speed Output module (optional)
- Local/Remote push button on LHMI
- Self-supervision
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
- Web HMI
2×
I2>
46
3I>>>
50P/51P
3×
ARC
50L/50NL
Master Trip
Lockout relay
94/86
3I>/Io>BF
51BF/51NBF
PQM3I
PQM3I
2×
TCS
TCM
MCS 3I
MCS 3I
CBCM
CBCM
OPTS
OPTM
18×
MAP
MAP
6xRTD
2xmA
3I>
51P-1
2×
3I>>
51P-2
TD>
55TD
3I>3I<
51C
Io>>
51N-2
Io>>>
50N/51N
2×
Io>
51N-1
3dI>C
51NC-2
dI>C
51NC-1
3Ith>T/G/C
49T/G/C
Io
Io
3Iunb
Io
1
-
2
3
1
2
Master Trip
Lockout relay
94/86
3×
2×
3×
GUID-DFC320F5-AD45-4D28-8632-C3FB2CFDCB06 V3 EN
Figure 1.
Functionality overview for standard configuration A
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
4
ABB
CONTROL AND INDICATION 1)
MEASUREMENT
CAPACITOR BANK PROTECTION AND CONTROL RELAY
STANDARD
CONFIGURATION
PROTECTION
LOCAL HMI
Object
Ctrl 2)
Ind 3)
CB
DC
ES
1) Check availability of binary inputs/outputs
from technical documentation
2) Control and indication function for
primary object
3) Status indication function for
primary object
R
L
Clear
ESC
I
O
Configuration
A
System
HMI
Time
Authorization
R
L
Clear
ESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
REMARKS
Optional
function
No. of
instances
Alternative
function to be
defined when
ordering
OR
Io/Uo
Calculated
value
3×
REV615
B
COMMUNICATION
Protocols:
IEC 61850-8-1/-9-2LE
Modbus®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial:
Serial glass fiber (ST),
RS-485, RS-232
Redundant protocols:
HSR
PRP
RSTP
- I, U, Io, Uo, P, Q, E, pf, f
- Limit value supervision
- Load profile record
- RTD/mA measurement (optional)
- Symmetrical components
7
5
Analog interface types
1)
Current transformer
Voltage transformer
1) Conventional transformer inputs
1
-
2
3
1
2
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
- High-Speed Output module (optional)
- Local/Remote push button on LHMI
- Self-supervision
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
- Web HMI
Master Trip
Lockout relay
94/86
PQM3I
PQM3I
2×
TCS
TCM
MCS 3I
MCS 3I
CBCM
CBCM
OPTS
OPTM
18×
MAP
MAP
2xRTD
1xmA
Io>>
51N-2
2×
Io>→
67N-1
Io>>→
67N-2
2×
3U<
27
U2>
47O-
U1<
47U+
2×
3U>
59
Uo>
59G
FUSEF
60
2×
I2>
46
3I>>>
50P/51P
3×
ARC
50L/50NL
3I>/Io>BF
51BF/51NBF
3I>
51P-1
2×
3I>>
51P-2
TD>
55TD
3I>3I<
51C
3dI>C
51NC-2
dI>C
51NC-1
PQM3U
PQM3V
PQMU
PQMV
Uo>
59G
3Ith>T/G/C
49T/G/C
3I
3I
Io
Io
Io
Iunb
Io>IEF→
67NIEF
UL1UL2UL3
UL1UL2UL3
UL1UL2UL3
Uo
Uo
3×
2×
Uo
Master Trip
Lockout relay
94/86
3×
2×
PQUUB
PQVUB
GUID-393D9B25-06C8-42AE-A7D0-642BBCB89DBE V2 EN
Figure 2.
Functionality overview for standard configuration B
Table 1. Standard configurations
Description
Std. conf.
Capacitor bank overload and unbalance protection, non-directional overcurrent and earth-fault protection and circuit-breaker
condition monitoring
A
Capacitor bank overload and unbalance protection, non-directional overcurrent and directional earth-fault protection, voltage and
frequency based protection and measurements, and circuit-breaker condition monitoring
B
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
5
Table 2. Supported functions
Function
IEC 61850
A
B
Protection
Three-phase non-directional overcurrent protection, low stage
PHLPTOC
1
1
Three-phase non-directional overcurrent protection, high stage
PHHPTOC
2
2
Three-phase non-directional overcurrent protection, instantaneous stage
PHIPTOC
1
1
Non-directional earth-fault protection, low stage
EFLPTOC
2
Non-directional earth-fault protection, high stage
EFHPTOC
1
1
Non-directional earth-fault protection, instantaneous stage
EFIPTOC
1
Directional earth-fault protection, low stage
DEFLPDEF
2
Directional earth-fault protection, high stage
DEFHPDEF
1
Transient/intermittent earth-fault protection
INTRPTEF
1 1)
Negative-sequence overcurrent protection
NSPTOC
2
2
Residual overvoltage protection
ROVPTOV
1
22)
Three-phase undervoltage protection
PHPTUV
2
Three-phase overvoltage protection
PHPTOV
2
Positive-sequence undervoltage protection
PSPTUV
1
Negative-sequence overvoltage protection
NSPTOV
1
Three-phase thermal overload protection, two time constants
T2PTTR
1
1
Circuit breaker failure protection
CCBRBRF
1
1
Master trip
TRPPTRC
2
(3) 3)
2
(3) 3)
Arc protection
ARCSARC
(3)
(3)
Multipurpose protection
MAPGAPC
18
18
Three-phase overload protection for shunt capacitor banks
COLPTOC
1
1
Current unbalance protection for shunt capacitor banks
CUBPTOC
1 4)
1 4)
Three-phase current unbalance protection for shunt capacitor banks
HCUBPTOC
1 4)
1 4)
Shunt capacitor bank switching resonance protection, current based
SRCPTOC
1
1
Power quality
Current total demand distortion
CMHAI
(1) 5)
(1) 6)
Voltage total harmonic distortion
VMHAI
(1) 6)
Voltage variation
PHQVVR
(1) 6)
Voltage unbalance
VSQVUB
(1) 6)
Control
Circuit-breaker control
CBXCBR
1
1
Disconnector control
DCXSWI
2
2
Earthing switch control
ESXSWI
1
1
Disconnector position indication
DCSXSWI
3
3
Earthing switch indication
ESSXSWI
2
2
Condition monitoring and supervision
Circuit-breaker condition monitoring
SSCBR
1
1
Trip circuit supervision
TCSSCBR
2
2
Current circuit supervision
CCSPVC
1
1
Fuse failure supervision
SEQSPVC
1
Runtime counter for machines and devices
MDSOPT
1
1
Measurement
Disturbance recorder
RDRE
1
1
Load profile record
LDPRLRC
1
1
Fault record
FLTRFRC
1
1
Three-phase current measurement
CMMXU
1
1
Sequence current measurement
CSMSQI
1
1
Residual current measurement
RESCMMXU
1
1
Three-phase voltage measurement
VMMXU
1
Residual voltage measurement
RESVMMXU
2
Sequence voltage measurement
VSMSQI
1
Three-phase power and energy measurement
PEMMXU
1
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
6
ABB
Table 2. Supported functions, continued
Function
IEC 61850
A
B
RTD/mA measurement
XRGGIO130
(1)
(1)
Frequency measurement
FMMXU
1
IEC 61850-9-2 LE sampled value sending 7)8)
SMVSENDER
(1)
IEC 61850-9-2 LE sampled value receiving (voltage sharing) 7)8)
SMVRCV
(1)
Other
Minimum pulse timer (2 pcs)
TPGAPC
4
4
Minimum pulse timer (2 pcs, second resolution)
TPSGAPC
1
1
Minimum pulse timer (2 pcs, minute resolution)
TPMGAPC
1
1
Pulse timer (8 pcs)
PTGAPC
2
2
Time delay off (8 pcs)
TOFGAPC
4
4
Time delay on (8 pcs)
TONGAPC
4
4
Set-reset (8 pcs)
SRGAPC
4
4
Move (8 pcs)
MVGAPC
2
2
Generic control point (16 pcs)
SPCGAPC
2
2
Analog value scaling (4 pcs)
SCA4GAPC
4
4
Integer value move (4 pcs)
MVI4GAPC
1
1
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in the standard
configuration.
() = optional
1)
"Io measured" is always used.
2)
"Uob measured" is always used.
3)
Master trip is included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If additionally the ARC option is selected, ARCSARC is
connected to the corresponding master trip input in the configuration.
4)
The Iunb measurement values are taken from this block and put in the Measurent view.
5)
Power quality option includes only current total demand distortion.
6)
Power quality option includes current total demand distortion, voltage total harmonic distortion, voltage variation and voltage unbalance.
7)
Available only with IEC 61850-9-2
8)
Available only with COM0031-0037
3. Protection functions
The relay offers three-phase overload protection with
undercurrent and reconnection inhibit functionality for
capacitors, single or three-phase current-based unbalance
protection for capacitors including compensation for natural
unbalance and a current-based switching resonance
protection.
The relay features non-directional overcurrent and thermal
overload protection as well as non-directional earth-fault
protection.
Additionally, the standard configuration B includes directional
earth-fault protection, residual voltage protection, overvoltage
protection and undervoltage protection functions.
Enhanced with optional hardware and software, the relay also
features three light detection channels for arc fault protection of
the circuit breaker, busbar and cable compartment of metal-
enclosed indoor switchgear.
The arc-fault protection sensor interface is available on the
optional communication module. Fast tripping increases staff
safety and security and limits material damage in an arc fault
situation. A binary input and output module can be selected as
an option - having three high speed binary outputs (HSO) it
further decreases the total operate time with typically 4...6 ms
compared to the normal power outputs.
4. Application
REV615 is intended for the protection of capacitor banks used
for reactive power compensation in utility substations and
industrial power systems. REV615 offers protection
functionality especially for H-bridge, double star and single star
connected capacitor banks and the feeder cable.
The protection relay can also be used for the protection of
harmonic filter circuits, if the highest significant harmonic
component is the 11th.
Standard configurations A and B offer three-phase overload
protection, unbalance protection with compensation for natural
unbalance and switching resonance protection for capacitor
banks. An integrated undercurrent function in the overload
protection function block detects the disconnection of a
capacitor bank and inhibits the closing of the circuit breaker as
long as the capacitor bank is still partially discharged. A three-
phase thermal overload protection can be used for the thermal
protection of the reactors and resistors in the harmonic filter
circuits. The relay features non-directional overcurrent and
earth-fault protection for the feeder cable and the capacitor
bank.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
7
Standard configuration A is pre-configured for H-bridge
connected capacitor banks. Three-phase current unbalance
protection is used for unbalance.
Standard configuration B offers directional earth-fault
protection, residual voltage protection, overvoltage protection
and undervoltage protection functions. It is pre-configured for
double star connected capacitor banks. Single current
unbalance protection is used for unbalance.
The second and third stage of the residual voltage protection in
the standard configuration B can be used as voltage-based
unbalance protection mainly for single star connected capacitor
banks, with unearthed star point. Dedicated voltage input Uob
is used for this purpose. This functionality is available in
standard configuration B and needs to be configured before it is
taken into use.
3I
R
L
Clear
ESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
REV615
Std. conf.
ANSI
IEC
50L/50NL
50P/51P
51C
51NC-2
51P/51N
55TD
ARC
3I>>>
3I> 3I<
3dI>C
3I>/Io>
TD>
A
Io
3Iunb
GUID-B7F0755C-006A-4806-91D3-8C290EE3ECA0 V1 EN
Figure 3.
Protection of a H-bridge connected capacitor bank
Figure 3 illustrates the protection of an H-bridge connected
capacitor bank. Standard configuration A is used with overload,
three-phase connected current unbalance and undercurrent
protection for the capacitor bank. Overcurrent and earth-fault
protection functions are used for protecting the feeder cable
and capacitor bank combination.
3I
REV615
Std. conf.
ANSI
IEC
27/59/59G
50L/50NL
50P/51P
51C
51NC-1
51P/51N
55TD
67N
3U3U>/Uo>
ARC
3I>>>
3I> 3I<
dI>C
3I>/Io>
TD>
Io>→
B
3U
Uo
R
L
Clear
ESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
Io
Iunb
GUID-5F33A1B7-2B6F-4CFA-9DD6-71E633C46846 V1 EN
Figure 4.
Protection of a double star connected capacitor bank in a distribution network with a compensated or isolated neutral
Protection of a double star connected capacitor bank in a
distribution network with a compensated or isolated neutral is
shown in Figure 4. Standard configuration B is used with
overload, single phase connected current unbalance and
undercurrent protection for the capacitor bank. Overcurrent
and directional earth-fault protetion functions are used for
protecting the feeder cable and capacitor bank combination.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
8
ABB
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
3I
REV615
Std. conf.
ANSI
IEC
27/59/59G
49T
50L/50NL
50P/51P
51C
51NC-2
51P/51N
55TD
3U3U>/Uo>
3Ith>T
ARC
3I>>>
3I> 3I<
3dI>C
3I>/Io>
TD>
B
Io
3Iunb
GUID-30461537-C53B-460B-BA27-9667D6977F77 V1 EN
Figure 5.
Protection of a harmonic filter circuit in an industrial network
Figure 5 illustrates the protection of a harmonic filter circuit in an
industrial network. Standard configuration B is used with
overload, three-phase connected current unbalance and
undercurrent protection for the harmonic filter and with an
additional thermal protection mainly for the coil. Overcurrent
and earth-fault protection functions are used for protecting the
feeder cable and harmonic filter circuit combination.
3U
Uo
R
L
Clear
ESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
3I
REV615
Std. conf.
ANSI
IEC
27/59/59G
50L/50NL
50P/51P
51C
51P
55TD
67N
3U3U>/Uo>
ARC
3I>>>
3I> 3I<
3I>
TD>
Io>→
B
Uob
Io
GUID-9C6F9938-FB13-4615-842A-9606411B47FC V1 EN
Figure 6.
Protection of a single star connected capacitor bank
The protection of a single star connected capacitor bank is
shown in Figure 6. Standard configuration B is used with
overload, voltage-based unbalance (Uob) and undercurrent
protection for the capacitor bank. Overcurrent and earth-fault
protection functions are used for protecting the feeder cable
and the capacitor bank combination.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
9
5. Supported ABB solutions
The 615 series protection relays together with the Substation
Management Unit COM600S constitute a genuine IEC 61850
solution for reliable power distribution in utility and industrial
power systems. To facilitate the system engineering, ABB's
relays are supplied with connectivity packages. The
connectivity packages include a compilation of software and
relay-specific information, including single-line diagram
templates and a full relay data model. The data model includes
event and parameter lists. With the connectivity packages, the
relays can be readily configured using PCM600 and integrated
with COM600S or the network control and management
system MicroSCADA Pro.
The 615 series relays offer native support for IEC 61850 Edition
2 also including binary and analog horizontal GOOSE
messaging. In addition, process bus with the sending of
sampled values of analog currents and voltages and the
receiving of sampled values of voltages is supported.
Compared to traditional hard-wired, inter-device signaling,
peer-to-peer communication over a switched Ethernet LAN
offers an advanced and versatile platform for power system
protection. Among the distinctive features of the protection
system approach, enabled by the full implementation of the IEC
61850 substation automation standard, are fast
communication capability, continuous supervision of the
protection and communication system's integrity, and an
inherent flexibility regarding reconfiguration and upgrades.This
protection relay series is able to optimally utilize interoperability
provided by the IEC 61850 Edition 2 features.
At substation level, COM600S uses the data content of the bay-
level devices to enhance substation level functionality.
COM600S features a Web browser-based HMI, which provides
a customizable graphical display for visualizing single-line
mimic diagrams for switchgear bay solutions. The SLD feature
is especially useful when 615 series relays without the optional
single-line diagram feature are used. The Web HMI of
COM600S also provides an overview of the whole substation,
including relay-specific single-line diagrams, which makes
information easily accessible. Substation devices and
processes can also be remotely accessed through the Web
HMI, which improves personnel safety.
In addition, COM600S can be used as a local data warehouse
for the substation's technical documentation and for the
network data collected by the devices. The collected network
data facilitates extensive reporting and analyzing of network
fault situations by using the data historian and event handling
features of COM600S. The historical data can be used for
accurate monitoring of process and equipment performance,
using calculations based on both real-time and historical
values. A better understanding of the process dynamics is
achieved by combining time-based process measurements
with production and maintenance events.
COM600S can also function as a gateway and provide
seamless connectivity between the substation devices and
network-level control and management systems, such as
MicroSCADA Pro and System 800xA.
GOOSE Analyzer interface in COM600S enables the following
and analyzing the horizontal IEC 61850 application during
commissioning and operation at station level. It logs all GOOSE
events during substation operation to enable improved system
supervision.
Table 3. Supported ABB solutions
Product
Version
Substation Management Unit COM600S
4.0 SP1 or later
4.1 or later (Edition 2)
MicroSCADA Pro SYS 600
9.3 FP2 or later
9.4 or later (Edition 2)
System 800xA
5.1 or later
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
10
ABB
Utility: IEC 60870-5-104
Industry: OPC
COM600S
Web HMI
ABB
MicroSCADA Pro/
System 800xA
Analog and binary horizontal
GOOSE communication
IEC 61850
PCM600
Ethernet switch
COM600S
Web HMI
Analog and binary horizontal
GOOSE communication
IEC 61850
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN
Figure 7.
ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA
6. Control
REV615 integrates functionality for the control of a circuit
breaker via the front panel HMI or by means of remote controls.
In addition to the circuit breaker control the relay features two
control blocks intended for motor-operated control of
disconnectors or circuit breaker truck and their position
indications.
The relay has one control block intended for motor-operated
control of one earthing switch control and its position
indication. Two physical binary inputs and two physical binary
outputs are needed in the relay for each controllable primary
device taken into use. The number of unused binary inputs and
binary outputs varies, depending on the chosen standard
configuration of the relay. Further, some standard
configurations offer optional hardware modules that increase
the number of available binary inputs and outputs.
If the amount of available binary inputs or outputs of the chosen
standard configuration is not sufficient, the standard
configuration can be modified to release some binary inputs or
outputs which have originally been configured for other
purposes, when applicable, or an external input or output
module, for example, RIO600 can be integrated to the relay.
The binary inputs and outputs of the external I/O module can be
used for the less time critical binary signals of the application.
The integration enables releasing of some initially reserved
binary inputs and outputs of the relay in the standard
configuration.
The suitability of the binary outputs of the relay which have been
selected for controlling of primary devices should be carefully
verified, for example the make and carry as well as the breaking
capacity. If the requirements for the control-circuit of the
primary device are not met, the use of external auxiliary relays
should be considered.
The optional large graphical LCD of the relay's HMI includes a
single-line diagram (SLD) with position indication for the
relevant primary devices. Interlocking schemes required by the
application are configured using the signal matrix or the
application configuration functionality of PCM600.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
11
The relay continuously measures the phase currents, the single
or three-phase unbalance currents (with the natural unbalance
current compensated), the symmetrical components of the
phase currents and the residual current.
The standard configuration B includes voltage measurements.
It measures the residual voltage, the phase voltages, the
voltage sequence components and frequency. It also measures
the capacitor bank unbalance voltage if the Uob is connected
and the relay is configured accordingly. This voltage
measurement is called residual voltage measurement, instance
2. The relay offers three-phase power and energy measurement
including power factor.
In addition, the relay calculates the demand value of current
over a user-selectable preset time frames, the thermal overload
of the protected object, and the phase unbalance value based
on the ratio between the negative-sequence and positive-
sequence current.
The measured values can be accessed via the local HMI or
remotely via the communication interface of the relay. The
values can also be accessed locally or remotely using the Web
HMI.
The relay is provided with a load profile recorder. The load
profile feature stores the historical load data captured at a
periodical time interval (demand interval). The records are in
COMTRADE format.
8. Power quality
In the EN standards, power quality is defined through the
characteristics of the supply voltage. Transients, short-duration
and long-duration voltage variations and unbalance and
waveform distortions are the key characteristics describing
power quality. The distortion monitoring functions are used for
monitoring the current total demand distortion and the voltage
total harmonic distortion.
Power quality monitoring is an essential service that utilities can
provide for their industrial and key customers. A monitoring
system can provide information about system disturbances and
their possible causes. It can also detect problem conditions
throughout the system before they cause customer complaints,
equipment malfunctions and even equipment damage or
failure. Power quality problems are not limited to the utility side
of the system. In fact, the majority of power quality problems
are localized within customer facilities. Thus, power quality
monitoring is not only an effective customer service strategy but
also a way to protect a utility's reputation for quality power and
service.
The protection relay has the following power quality monitoring
functions.
• Voltage variation
• Voltage unbalance
• Current harmonics
• Voltage harmonics
The voltage unbalance and voltage variation functions are used
for measuring short-duration voltage variations and monitoring
voltage unbalance conditions in power transmission and
distribution networks.
The voltage and current harmonics functions provide a method
for monitoring the power quality by means of the current
waveform distortion and voltage waveform distortion. The
functions provides a short-term three-second average and a
long-term demand for total demand distortion TDD and total
harmonic distortion THD.
9. Disturbance recorder
The relay is provided with a disturbance recorder featuring up to
12 analog and 64 binary signal channels.The analog channels
can be set to record either the waveform or the trend of the
currents and voltages measured.
The analog channels can be set to trigger the recording function
when the measured value falls below or exceeds the set values.
The binary signal channels can be set to start a recording either
on the rising or the falling edge of the binary signal or on both.
By default, the binary channels are set to record external or
internal relay signals, for example, the start or trip signals of the
relay stages, or external blocking or control signals. Binary relay
signals, such as protection start and trip signals, or an external
relay control signal via a binary input, can be set to trigger the
recording. Recorded information is stored in a nonvolatile
memory and can be uploaded for subsequent fault analysis.
10. Event log
To collect sequence-of-events information, the relay has a non-
volatile memory capable of storing 1024 events with the
associated time stamps. The non-volatile memory retains its
data even if the relay temporarily loses its auxiliary supply. The
event log facilitates detailed pre- and post-fault analyses of
feeder faults and disturbances. The considerable capacity to
process and store data and events in the relay facilitates
meeting the growing information demand of future network
configurations.
The sequence-of-events information can be accessed either via
local HMI or remotely via the communication interface of the
relay. The information can also be accessed locally or remotely
using the Web HMI.
11. Recorded data
The relay has the capacity to store the records of the 128 latest
fault events. The records can be used to analyze the power
system events. Each record includes, for example, current,
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
12
ABB
voltage and angle values and a time stamp. The fault recording
can be triggered by the start or the trip signal of a protection
block, or by both. The available measurement modes include
DFT, RMS and peak-to-peak. Fault records store relay
measurement values at the moment when any protection
function starts. In addition, the maximum demand current with
time stamp is separately recorded. The records are stored in
the non-volatile memory.
1024
PROCESS LEVEL
USER LEVEL
Fault summary;
Trip timestamp, Function, Currents, Voltages, etc.
BASIC FUNCTIONS
IEC 61850-8-1
Modbus
IEC 103
DNP3
LHMI
WHMI
PCM600
Process
events
(FIFO)
128
Fault
records
(FIFO)
System and security-related events;
Configuration changes, Control, Login, etc.
2048
Audit
trail
events
(FIFO)
n…100
Disturbance
records
...7 yrs
Load profile
record
Historical load data captured at a periodical
time interval (Demand interval 1 ...180min)
Function specific data
Min/max demand currents, Operation counters, etc.
History view
GUID-CDF1DC16-AF90-406F-B21B-EF6C7F60BCCA V1 EN
Figure 8.
Recording and event capabilities overview
12. Condition monitoring
The condition monitoring functions of the relay constantly
monitor the performance and the condition of the circuit
breaker. The monitoring comprises the spring charging time,
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
The monitoring functions provide operational circuit breaker
history data, which can be used for scheduling preventive
circuit breaker maintenance.
In addition, the relay includes a runtime counter for monitoring
of how many hours a protected device has been in operation
thus enabling scheduling of time-based preventive
maintenance of the device.
13. Trip-circuit supervision
The trip-circuit supervision continuously monitors the
availability and operability of the trip circuit. It provides open-
circuit monitoring both when the circuit breaker is in its closed
and in its open position. It also detects loss of circuit-breaker
control voltage.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
13
The relay’s built-in self-supervision system continuously
monitors the state of the relay hardware and the operation of
the relay software. Any fault or malfunction detected is used for
alerting the operator.
A permanent relay fault blocks the protection functions to
prevent incorrect operation.
15. Fuse failure supervision
In the standard configuration B, the relay includes fuse failure
supervision functionality. The fuse failure supervision detects
failures between the voltage measurement circuit and the relay.
The failures are detected either by the negative sequence-
based algorithm or by the delta voltage and delta current
algorithm. Upon the detection of a failure, the fuse failure
supervision function activates an alarm and blocks voltage-
dependent protection functions from unintended operation.
16. Current circuit supervision
The relay includes current circuit supervision. Current circuit
supervision is used for detecting faults in the current
transformer secondary circuits. On detecting of a fault the
current circuit supervision function activates an alarm LED and
blocks certain protection functions to avoid unintended
operation. The current circuit supervision function calculates
the sum of the phase currents from the protection cores and
compares the sum with the measured single reference current
from a core balance current transformer or from separate cores
in the phase current transformers.
17. Access control
To protect the relay from unauthorized access and to maintain
information integrity, the relay is provided with a four-level, role-
based authentication system with administrator-programmable
individual passwords for the viewer, operator, engineer and
administrator levels. The access control applies to the local
HMI, the Web HMI and PCM600.
18. Inputs and outputs
The relay is equipped with three phase-current inputs, three
unbalance-current inputs and one residual-current input for
non-directional earth-fault protection.
In the standard configuration B, the relay is additionally
equipped with three phase-voltage inputs, one residual voltage
input for directional earth-fault protection and one voltage input
(Uob) that can be used for voltage based unbalance protection.
The rated level of the current inputs is 1/5 A and selectable in
the relay software. The three phase-voltage inputs and the
residual-voltage inputs cover the rated voltages 60-210 V. Both
phase-to-phase voltages and phase-to-earth voltages can be
connected. The binary input thresholds 16…176 V DC are
selected by adjusting the relay’s parameter settings.
All binary input and output contacts are freely configurable with
the signal matrix or application configuration functionality of
PCM600.
See the Input/output overview table and the terminal diagrams
for more information about the inputs and outputs.
Optionally, a binary input and output module can be selected. It
has three high speed binary outputs (HSO) and it decreases the
total operate time with typically 4...6 ms compared to the
normal power outputs.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
14
ABB
Table 4. Input/output overview
Std. conf.
Order code digit
Analog channels
Binary channels
5-6
7-8
CT
VT
BI
BO
RTD
mA
A
BA
BA
7
-
8
4 PO + 6 SO
-
-
BB
7
-
14
4 PO + 9 SO
-
-
FD
7
-
8
4 PO + 2 SO
+ 3 HSO
-
-
FF
7
-
14
4 PO + 5 SO
+ 3 HSO
-
-
BG
BA
7
-
8
4 PO + 6 SO
6
2
FD
7
-
8
4 PO + 2 SO
+ 3 HSO
6
2
B
BC
AD
7
5
12
4 PO + 6 SO
-
-
FE
7
5
12
4 PO + 2 SO
+ 3 HSO
-
-
BE
BA
7
5
8
4 PO + 6 SO
2
1
FD
7
5
8
4 PO + 2 SO
+ 3 HSO
2
1
As an option for standard configuration B, the relay has two
RTD inputs and 1 mA input. The relay measures signals such as
temperature via the two RTD inputs and mA inputs using a
transducer. The values can, apart from measuring and
monitoring purposes, be used for tripping and alarm purposes
using the multipurpose protection functions. The temperature
signal can also be used for ambient temperature information for
the thermal protection function.
19. Station communication
The relay supports a range of communication protocols
including IEC 61850 Edition 2, IEC 61850-9-2 LE, IEC
60870-5-103, Modbus® and DNP3. Profibus DPV1
communication protocol is supported with using the protocol
converter SPA-ZC 302. Operational information and controls
are available through these protocols. However, some
communication functionality, for example, horizontal
communication between the relays, is only enabled by the IEC
61850 communication protocol.
The IEC 61850 protocol is a core part of the relay as the
protection and control application is fully based on standard
modelling. The relay supports Edition 2 and Edition 1 versions
of the standard. With Edition 2 support, the relay has the latest
functionality modelling for substation applications and the best
interoperability for modern substations. It incorporates also the
full support of standard device mode functionality supporting
different test applications. Control applications can utilize the
new safe and advanced station control authority feature.
The IEC 61850 communication implementation supports
monitoring and control functions. Additionally, parameter
settings, disturbance recordings and fault records can be
accessed using the IEC 61850 protocol. Disturbance
recordings are available to any Ethernet-based application in
the standard COMTRADE file format. The relay supports
simultaneous event reporting to five different clients on the
station bus. The relay can exchange data with other devices
using the IEC 61850 protocol.
The relay can send binary and analog signals to other devices
using the IEC 61850-8-1 GOOSE (Generic Object Oriented
Substation Event) profile. Binary GOOSE messaging can, for
example, be employed for protection and interlocking-based
protection schemes. The relay meets the GOOSE performance
requirements for tripping applications in distribution
substations, as defined by the IEC 61850 standard (<10 ms
data exchange between the devices). The relay also supports
the sending and receiving of analog values using GOOSE
messaging. Analog GOOSE messaging enables easy transfer of
analog measurement values over the station bus, thus
facilitating for example the sending of measurement values
between the relays when controlling parallel running
transformers.
The relay also supports IEC 61850 process bus by sending
sampled values of analog currents and voltages and by
receiving sampled values of voltages. With this functionality the
galvanic interpanel wiring can be replaced with Ethernet
communication. The measured values are transferred as
sampled values using IEC 61850-9-2 LE protocol. The intended
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
15
application for sampled values shares the voltages to other 615
series relays, having voltage based functions and 9-2 support.
615 relays with process bus based applications use IEEE 1588
for high accuracy time synchronization.
For redundant Ethernet communication, the relay offers either
two optical or two galvanic Ethernet network interfaces. A third
port with galvanic Ethernet network interface is also available.
The third Ethernet interface provides connectivity for any other
Ethernet device to an IEC 61850 station bus inside a switchgear
bay, for example connection of a Remote I/O. Ethernet network
redundancy can be achieved using the high-availability
seamless redundancy (HSR) protocol or the parallel
redundancy protocol (PRP) or a with self-healing ring using
RSTP in managed switches. Ethernet redundancy can be
applied to Ethernet-based IEC 61850, Modbus and DNP3
protocols.
The IEC 61850 standard specifies network redundancy which
improves the system availability for the substation
communication. The network redundancy is based on two
complementary protocols defined in the IEC 62439-3 standard:
PRP and HSR protocols. Both the protocols are able to
overcome a failure of a link or switch with a zero switch-over
time. In both the protocols, each network node has two
identical Ethernet ports dedicated for one network connection.
The protocols rely on the duplication of all transmitted
information and provide a zero switch-over time if the links or
switches fail, thus fulfilling all the stringent real-time
requirements of substation automation.
In PRP, each network node is attached to two independent
networks operated in parallel. The networks are completely
separated to ensure failure independence and can have
different topologies. The networks operate in parallel, thus
providing zero-time recovery and continuous checking of
redundancy to avoid failures.
Ethernet switch
IEC 61850 PRP
Ethernet switch
SCADA
COM600
GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V2 EN
Figure 9.
Parallel redundancy protocol (PRP) solution
HSR applies the PRP principle of parallel operation to a single
ring. For each message sent, the node sends two frames, one
through each port. Both the frames circulate in opposite
directions over the ring. Every node forwards the frames it
receives from one port to another to reach the next node. When
the originating sender node receives the frame it sent, the
sender node discards the frame to avoid loops. The HSR ring
with 615 series relays supports the connection of up to 30
relays. If more than 30 relays are to be connected, it is
recommended to split the network into several rings to
guarantee the performance for real-time applications.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
16
ABB
IEC 61850 HSR
Redundancy
Box
Redundancy
Box
REF615
REF620
RET620
REM620
REF615
SCADA
Devices not supporting HSR
COM600
GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN
Figure 10.
High availability seamless redundancy (HSR) solution
The choice between the HSR and PRP redundancy protocols
depends on the required functionality, cost and complexity.
The self-healing Ethernet ring solution enables a cost-efficient
communication ring controlled by a managed switch with
standard Rapid Spanning Tree Protocol (RSTP) support. The
managed switch controls the consistency of the loop, routes
the data and corrects the data flow in case of a communication
switch-over. The relays in the ring topology act as unmanaged
switches forwarding unrelated data traffic. The Ethernet ring
solution supports the connection of up to 30 615 series relays.
If more than 30 relays are to be connected, it is recommended
to split the network into several rings. The self-healing Ethernet
ring solution avoids single point of failure concerns and
improves the reliability of the communication.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
17
Managed Ethernet switch
with RSTP support
Managed Ethernet switch
with RSTP support
Client B
Client A
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
Figure 11.
Self-healing Ethernet ring solution
All communication connectors, except for the front port
connector, are placed on integrated optional communication
modules. The relay can be connected to Ethernet-based
communication systems via the RJ-45 connector (100Base-TX)
or the fiber optic LC connector (100Base-FX). If connection to
serial bus is required, the 9-pin RS-485 screw-terminal can be
used. An optional serial interface is available for RS-232
communication.
Modbus implementation supports RTU, ASCII and TCP modes.
Besides standard Modbus functionality, the relay supports
retrieval of time-stamped events, changing the active setting
group and uploading of the latest fault records. If a Modbus
TCP connection is used, five clients can be connected to the
relay simultaneously. Further, Modbus serial and Modbus TCP
can be used in parallel, and if required both IEC 61850 and
Modbus protocols can be run simultaneously.
The IEC 60870-5-103 implementation supports two parallel
serial bus connections to two different masters. Besides basic
standard functionality, the relay supports changing of the active
setting group and uploading of disturbance recordings in IEC
60870-5-103 format. Further, IEC 60870-5-103 can be used at
the same time with the IEC 61850 protocol.
DNP3 supports both serial and TCP modes for connection up
to five masters. Changing of the active setting and reading fault
records are supported. DNP serial and DNP TCP can be used in
parallel. If required, both IEC 61850 and DNP protocols can be
run simultaneously.
615 series supports Profibus DPV1 with support of SPA-ZC
302 Profibus adapter. If Profibus is required the relay must be
ordered with Modbus serial options. Modbus implementation
includes SPA-protocol emulation functionality. This
functionality enables connection to SPA-ZC 302.
When the relay uses the RS-485 bus for the serial
communication, both two- and four wire connections are
supported. Termination and pull-up/down resistors can be
configured with jumpers on the communication card so external
resistors are not needed.
The relay supports the following time synchronization methods
with a time-stamping resolution of 1 ms.
Ethernet-based
• SNTP (Simple Network Time Protocol)
With special time synchronization wiring
• IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
18
ABB
The relay supports the following high accuracy time
synchronization method with a time-stamping resolution of 4 µs
required especially in process bus applications.
• PTP (IEEE 1588) v2 with Power Profile
The IEEE 1588 support is included in all variants having a
redundant Ethernet communication module.
IEEE 1588 v2 features
• Ordinary Clock with Best Master Clock algorithm
• One-step Transparent Clock for Ethernet ring topology
• 1588 v2 Power Profile
• Receive (slave): 1-step/2-step
• Transmit (master): 1-step
• Layer 2 mapping
• Peer to peer delay calculation
• Multicast operation
Required accuracy of grandmaster clock is +/-1 µs. The relay
can work as a master clock per BMC algorithm if the external
grandmaster clock is not available for short term.
The IEEE 1588 support is included in all variants having a
redundant Ethernet communication module.
In addition, the relay supports time synchronization via
Modbus, DNP3 and IEC 60870-5-103 serial communication
protocols.
Table 5. Supported station communication interfaces and protocols
Interfaces/Protocols
Ethernet
Serial
100BASE-TX RJ-45
100BASE-FX LC
RS-232/RS-485
Fiber optic ST
IEC 61850-8-1
●
●
-
-
IEC 61850-9-2 LE
●
●
-
-
MODBUS RTU/ASCII
-
-
●
●
MODBUS TCP/IP
●
●
-
-
DNP3 (serial)
-
-
●
●
DNP3 TCP/IP
●
●
-
-
IEC 60870-5-103
-
-
●
●
● = Supported
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
19
20. Technical data
Table 6. Dimensions
Description
Value
Width
Frame
177 mm
Case
164 mm
Height
Frame
177 mm (4U)
Case
160 mm
Depth
201 mm (153 + 48 mm)
Weight
Complete protection relay
4.1 kg
Plug-in unit only
2.1 kg
Table 7. Power supply
Description
Type 1
Type 2
Nominal auxiliary voltage Un
100, 110, 120, 220, 240 V AC, 50 and 60 Hz
24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the auxiliary DC
voltage without resetting the relay
50 ms at Un
Auxiliary voltage variation
38...110% of Un (38...264 V AC)
50...120% of Un (12...72 V DC)
80...120% of Un (38.4...300 V DC)
Start-up threshold
19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage supply under
quiescent (Pq)/operating condition
DC <13.0 W (nominal)/<18.0 W (max.)
AC <16.0 W (nominal)/<21.0 W (max.)
DC <13.0 W (nominal)/<18.0 W (max.)
Ripple in the DC auxiliary voltage
Max 15% of the DC value (at frequency of 100 Hz)
Fuse type
T4A/250 V
Table 8. Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, In
0.2/1 A1)
1/5 A2)
Thermal withstand capability:
• Continuously
4 A
20 A
• For 1 s
100 A
500 A
Dynamic current withstand:
• Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Voltage inputs
Rated voltage
60...210 V AC
Voltage withstand:
• Continuous
240 V AC
• For 10 s
360 V AC
Burden at rated voltage
<0.05 VA
1)
Ordering option for residual current input
2)
Residual current and/or phase current
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
20
ABB
Table 9. Binary inputs
Description
Value
Operating range
±20% of the rated voltage
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
Table 10. RTD/mA measurement (XRGGIO130)
Description
Value
RTD inputs
Supported RTD sensors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Supported resistance range
0...2 kΩ
Maximum lead resistance (three-
wire measurement)
25 Ω per lead
Isolation
2 kV (inputs to protective earth)
Response time
<4 s
RTD/resistance sensing current
Maximum 0.33 mA rms
Operation accuracy
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
mA inputs
Supported current range
0…20 mA
Current input impedance
44 Ω ± 0.1%
Operation accuracy
±0.5% or ±0.01 mA
Table 11. Signal output X100: SO1
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
21
Table 12. Signal outputs and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
15 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
10 mA at 5 V AC/DC
Table 13. Double-pole power output relays with TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC (two contacts connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
• Control voltage range
20...250 V AC/DC
• Current drain through the supervision circuit
~1.5 mA
• Minimum voltage over the TCS contact
20 V AC/DC (15...20 V)
Table 14. Single-pole power output relays
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
22
ABB
Table 15. High-speed output HSO with BIO0007
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
6 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Operate time
<1 ms
Reset
<20 ms, resistive load
Table 16. Front port Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
Front
TCP/IP protocol
Standard Ethernet CAT 5 cable with RJ-45 connector
10 MBits/s
Table 17. IRIG-B
Description
Value
IRIG time code format
B004, B0051)
Isolation
500V 1 min
Modulation
Unmodulated
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1)
According to the 200-04 IRIG standard
Table 18. Degree of protection of flush-mounted protection relay
Description
Value
Front side
IP 54
Rear side, connection terminals
IP 20
Table 19. Environmental conditions
Description
Value
Operating temperature range
-25...+55ºC (continuous)
Short-time service temperature range
-40...+85ºC (<16h)1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
Transport and storage temperature range
-40...+85ºC
1)
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2)
For relays with an LC communication interface the maximum operating temperature is +70 ºC
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
23
Table 20. Electromagnetic compatibility tests
Description
Type test value
Reference
1 MHz/100 kHz burst disturbance test
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2002
• Common mode
2.5 kV
• Differential mode
2.5 kV
3 MHz, 10 MHz and 30 MHz burst disturbance
test
IEC 61000-4-18
IEC 60255-26, class III
• Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference test
10 V (rms)
f = 150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
• All ports
4 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-26
• Communication
1 kV, line-to-earth
• Other ports
4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz) magnetic field
immunity test
IEC 61000-4-8
• Continuous
• 1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field immunity test
IEC 61000-4-10
• 2 s
100 A/m
• 1 MHz
400 transients/s
Voltage dips and short interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
24
ABB
Table 20. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
Power frequency immunity test
Binary inputs only
IEC 61000-4-16
IEC 60255-26, class A
• Common mode
300 V rms
• Differential mode
150 V rms
Conducted common mode disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
• Conducted
0.15...0.50 MHz
<79 dB (µV) quasi peak
<66 dB (µV) average
0.5...30 MHz
<73 dB (µV) quasi peak
<60 dB (µV) average
• Radiated
30...230 MHz
<40 dB (µV/m) quasi peak, measured at 10 m
distance
230...1000 MHz
<47 dB (µV/m) quasi peak, measured at 10 m
distance
1…3 GHz
<76 dB (µV/m) peak
<56 dB (µV/m) average, measured at 3 m
distance
3…6 GHz
<80 dB (µV/m) peak
<60 dB (µV/m) average, measured at 3 m
distance
Table 21. Insulation tests
Description
Type test value
Reference
Dielectric tests
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
IEC 60255-27
Impulse voltage test
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
IEC 60255-27
Insulation resistance measurements
>100 MΩ, 500 V DC
IEC 60255-27
Protective bonding resistance
<0.1 Ω, 4 A, 60 s
IEC 60255-27
Table 22. Mechanical tests
Description
Requirement
Reference
Vibration tests (sinusoidal)
Class 2
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Shock and bump test
Class 2
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Seismic test
Class 2
IEC 60255-21-3
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
25
Table 23. Environmental tests
Description
Type test value
Reference
Dry heat test
• 96 h at +55ºC
IEC 60068-2-2
Dry cold test
• 96 h at -25ºC
• 16 h at -40ºC
IEC 60068-2-1
Damp heat test
• 6 cycles (12 h + 12 h) at +25°C…+55°C,
humidity >93%
IEC 60068-2-30
Change of temperature test
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
IEC60068-2-14
Storage test
• 96 h at -40ºC
• 96 h at +85ºC
IEC 60068-2-1
IEC 60068-2-2
Table 24. Product safety
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2013)
EN 60255-1 (2009)
Table 25. EMC compliance
Description
Reference
EMC directive
2004/108/EC
Standard
EN 60255-26 (2013)
Table 26. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
26
ABB
Table 27. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
PHLPTOC
±1.5% of the set value or ±0.002 × In
PHHPTOC
and
PHIPTOC
±1.5% of set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Start time 1)2)
Minimum
Typical
Maximum
PHIPTOC:
IFault = 2 × set Start value
IFault = 10 × set Start value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
PHHPTOC and PHLPTOC:
IFault = 2 × set Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Includes the delay of the heavy-duty output contact
Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
PHLPTOC
0.05...5.00 × In
0.01
PHHPTOC
0.10...40.00 × In
0.01
PHIPTOC
1.00...40.00 × In
0.01
Time multiplier
PHLPTOC and PHHPTOC
0.05...15.00
0.01
Operate delay time
PHLPTOC and PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
Operating curve type1)
PHLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
PHHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
PHIPTOC
Definite time
1)
For further reference, see the Operation characteristics table
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
27
Table 29. Non-directional earth-fault protection (EFxPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
EFLPTOC
±1.5% of the set value or ±0.002 × In
EFHPTOC
and
EFIPTOC
±1.5% of set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Start time 1)2)
Minimum
Typical
Maximum
EFIPTOC:
IFault = 2 × set Start value
IFault = 10 × set Start value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and EFLPTOC:
IFault = 2 × set Start value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
Table 30. Non-directional earth-fault protection (EFxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 × In
0.005
EFHPTOC
0.10...40.00 × In
0.01
EFIPTOC
1.00...40.00 × In
0.01
Time multiplier
EFLPTOC and EFHPTOC
0.05...15.00
0.01
Operate delay time
EFLPTOC and EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
Operating curve type1)
EFLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
EFHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
EFIPTOC
Definite time
1)
For further reference, see the Operation characteristics table
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
28
ABB
Table 31. Directional earth-fault protection (DEFxPDEF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
DEFLPDEF
Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DEFHPDEF
Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
Start time 1)2)
Minimum
Typical
Maximum
DEFHPDEF
IFault = 2 × set Start value
42 ms
46 ms
49 ms
DEFLPDEF
IFault = 2 × set Start value
58 ms
62 ms
66 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Set Operate delay time = 0.06 s,Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
29
Table 32. Directional earth-fault protection (DEFxPDEF) main settings
Parameter
Function
Value (Range)
Step
Start value
DEFLPDEF
0.010...5.000 × In
0.005
DEFHPDEF
0.10...40.00 × In
0.01
Directional mode
DEFLPDEF and DEFHPDEF
1 = Non-directional
2 = Forward
3 = Reverse
-
Time multiplier
DEFLPDEF
0.05...15.00
0.01
DEFHPDEF
0.05...15.00
0.01
Operate delay time
DEFLPDEF
50...200000 ms
10
DEFHPDEF
40...200000 ms
10
Operating curve type1)
DEFLPDEF
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
DEFHPDEF
Definite or inverse time
Curve type: 1, 3, 5, 15, 17
Operation mode
DEFxPDEF
1 = Phase angle
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
-
1)
For further reference, see the Operating characteristics table
Table 33. Transient/intermittent earth-fault protection (INTRPTEF)
Characteristic
Value
Operation accuracy (Uo criteria with transient protection)
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × Uo
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5
Table 34. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter
Function
Value (Range)
Step
Directional mode
INTRPTEF
1 = Non-directional
2 = Forward
3 = Reverse
-
Operate delay time
INTRPTEF
40...1200000 ms
10
Voltage start value
INTRPTEF
0.05...0.50 × Un
0.01
Operation mode
INTRPTEF
1 = Intermittent EF
2 = Transient EF
-
Peak counter limit
INTRPTEF
2...20
1
Min operate current
INTRPTEF
0.01...1.00 × In
0.01
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
30
ABB
Table 35. Negative-sequence overcurrent protection (NSPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn
±1.5% of the set value or ±0.002 × In
Start time 1)2)
Minimum
Typical
Maximum
IFault = 2 × set Start value
IFault = 10 × set Start value
23 ms
15 ms
26 ms
18 ms
28 ms
20 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 3)
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20
Table 36. Negative-sequence overcurrent protection (NSPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 × In
0.01
Time multiplier
NSPTOC
0.05...15.00
0.01
Operate delay time
NSPTOC
40...200000 ms
10
Operating curve type1)
NSPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
1)
For further reference, see the Operation characteristics table
Table 37. Residual overvoltage protection (ROVPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time1)2)
Minimum
Typical
Maximum
UFault = 2 × set Start value
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Residual voltage before fault = 0.0 × Un, fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2)
Includes the delay of the signal output contact
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
31
Table 38. Residual overvoltage protection (ROVPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 × Un
0.001
Operate delay time
ROVPTOV
40...300000 ms
1
Table 39. Three-phase undervoltage protection (PHPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time1)2)
Minimum
Typical
Maximum
UFault = 0.9 × set Start value
62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms3)
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Table 40. Three-phase undervoltage protection (PHPTUV) main settings
Parameter
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 × Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
Operate delay time
PHPTUV
60...300000 ms
10
Operating curve type1)
PHPTUV
Definite or inverse time
Curve type: 5, 15, 21, 22, 23
1)
For further reference, see the Operation characteristics table
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
32
ABB
Table 41. Three-phase overvoltage protection (PHPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time1)2)
Minimum
Typical
Maximum
UFault = 1.1 × set Start value
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms3)
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × Un, Voltage before fault = 0.9 × Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Maximum Start value = 1.20 × Un, Start value multiples in range of 1.10...2.00
Table 42. Three-phase overvoltage protection (PHPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 × Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.01
Operate delay time
PHPTOV
40...300000 ms
10
Operating curve type1)
PHPTOV
Definite or inverse time
Curve type: 5, 15, 17, 18, 19, 20
1)
For further reference, see the Operation characteristics table
Table 43. Positive-sequence undervoltage protection (PSPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: fn ±2 Hz
±1.5% of the set value or ±0.002 × Un
Start time1)2)
Minimum
Typical
Maximum
UFault = 0.99 × set Start value
UFault = 0.9 × set Start value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × Un, positive-sequence voltage before fault = 1.1 × Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
33
Table 44. Positive-sequence undervoltage protection (PSPTUV) main settings
Parameter
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 × Un
0.001
Operate delay time
PSPTUV
40...120000 ms
10
Voltage block value
PSPTUV
0.01...1.00 × Un
0.01
Table 45. Negative-sequence overvoltage protection (NSPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: fn
±1.5% of the set value or ±0.002 × Un
Start time1)2)
Minimum
Typical
Maximum
UFault = 1.1 × set Start value
UFault = 2.0 × set Start value
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
Negative-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Table 46. Negative-sequence overvoltage protection (NSPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 × Un
0.001
Operate delay time
NSPTOV
40...120000 ms
1
Table 47. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
Current measurement: ±1.5% of the set value or ±0.002 x In (at currents
in the range of 0.01...4.00 x In)
Operate time accuracy1)
±2.0% of the theoretical value or ±0.50 s
1)
Overload current > 1.2 x Operate level temperature
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
34
ABB
Table 48. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0°C
0.1
Max temperature
T2PTTR
0.0...200.0°C
0.1
Operate temperature
T2PTTR
80.0...120.0%
0.1
Short time constant
T2PTTR
6...60000 s
1
Weighting factor p
T2PTTR
0.00...1.00
0.01
Current reference
T2PTTR
0.05...4.00 × In
0.01
Operation
T2PTTR
1 = on
5 = off
-
Table 49. Circuit breaker failure protection (CCBRBRF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
±1.5% of the set value or ±0.002 × In
Operate time accuracy
±1.0% of the set value or ±20 ms
Reset time
Typically 40 ms
Retardation time
<20 ms
Table 50. Circuit breaker failure protection (CCBRBRF) main settings
Parameter
Function
Value (Range)
Step
Current value
CCBRBRF
0.05...2.00 × In
0.05
Current value Res
CCBRBRF
0.05...2.00 × In
0.05
CB failure mode
CCBRBRF
1 = Current
2 = Breaker status
3 = Both
-
CB fail trip mode
CCBRBRF
1 = Off
2 = Without check
3 = Current check
-
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
35
Table 51. Arc protection (ARCSARC)
Characteristic
Value
Operation accuracy
±3% of the set value or ±0.01 × In
Operate time
Minimum
Typical
Maximum
Operation mode = "Light
+current"1)2)
9 ms3)
4 ms4)
12 ms3)
6 ms4)
15 ms 3)
9 ms4)
Operation mode = "Light only"2)
9 ms3)
4 ms4)
10 ms3)
6 ms4)
12 ms3)
7 ms4)
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
1)
Phase start value = 1.0 × In, current before fault = 2.0 × set Phase start value, fn = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
2)
Includes the delay of the heavy-duty output contact
3)
Normal power output
4)
High-speed output
Table 52. Arc protection (ARCSARC) main settings
Parameter
Function
Value (Range)
Step
Phase start value
ARCSARC
0.50...40.00 × In
0.01
Ground start value
ARCSARC
0.05...8.00 × In
0.01
Operation mode
ARCSARC
2 = Light only
3 = BI controlled
-
Table 53. Multipurpose protection (MAPGAPC)
Characteristic
Value
Operation accuracy
±1.0% of the set value or ±20 ms
Table 54. Multipurpose protection (MAPGAPC) main settings
Parameter
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
Operate delay time
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
1 = Over
2 = Under
-
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
36
ABB
Table 55. Three-phase overload protection for shunt capacitor banks (COLPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz, and no
harmonics
5% of the set value or 0.002 × In
Start time for overload stage1)2)
Typically 75 ms
Start time for under current stage2)3)
Typically 26 ms
Reset time for overload and alarm stage
Typically 60 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
1% of the set value or ±20 ms
Operate time accuracy in inverse time mode
10% of the theoretical value or ±20 ms
Suppression of harmonics for under current stage
DFT: -50 dB at f = n × fn, where n = 2,3,4,5,..
1)
Harmonics current before fault = 0.5 × In, harmonics fault current 1.5 × Start value, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Harmonics current before fault = 1.2 × In, harmonics fault current 0.8 × Start value, results based on statistical distribution of 1000 measurements
Table 56. Three-phase overload protection for shunt capacitor banks (COLPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value overload
COLPTOC
0.30...1.50 × In
0.01
Alarm start value
COLPTOC
80...120%
1
Start value Un Cur
COLPTOC
0.10...0.70 × In
0.01
Time multiplier
COLPTOC
0.05...2.00
0.01
Alarm delay time
COLPTOC
500...6000000 ms
100
Un Cur delay time
COLPTOC
100...120000 ms
100
Table 57. Current unbalance protection for shunt capacitor banks (CUBPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
1.5% of the set value or 0.002 × In
Start time1)2)
Typically 26 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
1% of the theoretical value or ±20 ms
Operate time accuracy in inverse definite minimum time mode
5% of the theoretical value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2,3,4,5,..
1)
Fundamental frequency current = 1.0 × In, current before fault = 0.0 × In, fault current = 2.0 × Start value, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
37
Table 58. Current unbalance protection for shunt capacitor banks (CUBPTOC) main settings
Parameter
Function
Value (Range)
Step
Alarm mode
CUBPTOC
1 = Normal
2 = Element counter
-
Start value
CUBPTOC
0.01...1.00 × In
0.01
Alarm start value
CUBPTOC
0.01...1.00 × In
0.01
Time multiplier
CUBPTOC
0.05...15.00
0.01
Operating curve type1)
CUBPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Operate delay time
CUBPTOC
50...200000 ms
10
Alarm delay time
CUBPTOC
50...200000 ms
10
1)
For further reference, refer to the Operating characteristics table
Table 59. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
1.5% of the set value or 0.002 × In
Start time1)2)
Typically 26 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
1% of the theoretical value or ±20 ms
Operate time accuracy in IDMT mode
5% of the theoretical value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2,3,4,5,..
1)
Fundamental frequency current = 1.0 × In, current before fault = 0.0 × In, fault current = 2.0 × Start value, results based on statistical distribution of 1000 measurements
2)
Includes the delay of the signal output contact
Table 60. Three-phase current unbalance protection for shunt capacitor banks (HCUBPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
HCUBPTOC
0.01...1.00 × In
0.01
Alarm start value
HCUBPTOC
0.01...1.00 × In
0.01
Time multiplier
HCUBPTOC
0.05...15.00
0.01
Operating curve type 1)
HCUBPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19
Operate delay time
HCUBPTOC
40...200000 ms
10
Alarm delay time
HCUBPTOC
40...200000 ms
10
1)
For further reference, refer to the Operating characteristics table
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
38
ABB
Table 61. Shunt capacitor bank switching resonance protection, current based (SRCPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
Operate value accuracy:
±3% of the set value or ±0.002 × In (for 2nd order Harmonics)
±1.5% of the set value or ±0.002 × In (for 3rd order < Harmonics < 10th
order)
±6% of the set value or ±0.004 × In (for Harmonics >= 10th order)
Reset time
Typically 45 ms or maximum 50 ms
Retardation time
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = fn
Table 62. Shunt capacitor bank switching resonance protection, current based (SRCPTOC) main settings
Parameter
Function
Value (Range)
Step
Alarm start value
SRCPTOC
0.03...0.50 × In
0.01
Start value
SRCPTOC
0.03...0.50 × In
0.01
Tuning harmonic Num
SRCPTOC
1...11
1
Operate delay time
SRCPTOC
120...360000 ms
1
Alarm delay time
SRCPTOC
120...360000 ms
1
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
39
Table 63. Operation characteristics
Parameter
Value (Range)
Operating curve type
1 = ANSI Ext. inv.
2 = ANSI Very. inv.
3 = ANSI Norm. inv.
4 = ANSI Mod inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv
15 = IEC Def. Time
17 = Programmable
18 = RI type
19 = RD type
Operating curve type (voltage protection)
5 = ANSI Def. Time
15 = IEC Def. Time
17 = Inv. Curve A
18 = Inv. Curve B
19 = Inv. Curve C
20 = Programmable
21 = Inv. Curve A
22 = Inv. Curve B
23 = Programmable
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
40
ABB
Power quality functions
Table 64. Voltage variation (PHQVVR)
Characteristic
Value
Operation accuracy
±1.5% of the set value or ±0.2% of reference voltage
Reset ratio
Typically 0.96 (Swell), 1.04 (Dip, Interruption)
Table 65. Voltage unbalance (VSQVUB)
Characteristic
Value
Operation accuracy
±1.5% of the set value or ±0.002 × Un
Reset ratio
Typically 0.96
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
41
Condition and supervision functions
Table 66. Circuit-breaker condition monitoring (SSCBR)
Characteristic
Value
Current measuring accuracy
±1.5% or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0%
(at currents in the range of 10…40 × In)
Operate time accuracy
±1.0% of the set value or ±20 ms
Travelling time measurement
+10 ms / -0 ms
Table 67. Current circuit supervision (CCSPVC)
Characteristic
Value
Operate time 1)
<30 ms
1)
Including the delay of the output contact
Table 68. Current circuit supervision (CCSPVC) main settings
Parameter
Function
Value (Range)
Step
Start value
CCSPVC
0.05...0.20 × In
0.01
Max operate current
CCSPVC
1.00...5.00 × In
0.01
Table 69. Fuse failure supervision (SEQSPVC)
Characteristic
Value
Operate time1)
NPS function
UFault = 1.1 × set Neg Seq voltage
Lev
<33 ms
UFault = 5.0 × set Neg Seq voltage
Lev
<18 ms
Delta function
ΔU = 1.1 × set Voltage change rate
<30 ms
ΔU = 2.0 × set Voltage change rate
<24 ms
1)
Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Table 70. Runtime counter for machines and devices (MDSOPT)
Description
Value
Motor runtime measurement accuracy1)
±0.5%
1)
Of the reading, for a stand-alone relay, without time synchronization
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
42
ABB
Table 71. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: fn ±2 Hz
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 72. Sequence current measurement (CSMSQI)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f/fn = ±2 Hz
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Table 73. Residual current measurement (RESCMMXU)
Characteristic
Value
Operation accuracy
Depending on the frequency of the current measured: f/fn = ±2 Hz
±0.5% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 74. Three-phase voltage measurement (VMMXU)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: fn ±2 Hz
At voltages in range 0.01…1.15 × Un
±0.5% or ±0.002 × Un
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Table 75. Residual voltage measurement (RESVMMXU)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: f/fn = ±2 Hz
±0.5% or ±0.002 × Un
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
RMS: No suppression
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
43
Table 76. Sequence voltage measurement (VSMSQI)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: fn ±2 Hz
At voltages in range 0.01…1.15 × Un
±1.0% or ±0.002 × Un
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Table 77. Three-phase power and energy measurement (PEMMXU)
Characteristic
Value
Operation accuracy
At all three currents in range 0.10…1.20 × In
At all three voltages in range 0.50…1.15 × Un
At the frequency fn ±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy1)
±1.5% for reactive power Q and reactive energy2)
±0.015 for power factor
Suppression of harmonics
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
1)
|PF| >0.5 which equals |cosφ| >0.5
2)
|PF| <0.86 which equals |sinφ| >0.5
Table 78. RTD/mA measurement (XRGGIO130)
Description
Value
RTD inputs
Supported RTD sensors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Supported resistance range
0...2 kΩ
Maximum lead resistance (three-
wire measurement)
25 Ω per lead
Isolation
2 kV (inputs to protective earth)
Response time
<4 s
RTD/resistance sensing current
Maximum 0.33 mA rms
Operation accuracy
Resistance
Temperature
± 2.0% or ±1 Ω
±1°C
10 Ω copper: ±2°C
mA inputs
Supported current range
0…20 mA
Current input impedance
44 Ω ± 0.1%
Operation accuracy
±0.5% or ±0.01 mA
Table 79. Frequency measurement (FMMXU)
Characteristic
Value
Operation accuracy
±5 mHz
(in measurement range 35...75 Hz)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
44
ABB
Table 80. Pulse timer (PTGAPC)
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
Table 81. Time delay off (8 pcs) (TOFPAGC)
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
Table 82. Time delay on (8 pcs) (TONGAPC)
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
45
21. Local HMI
The relay is available with two optional displays, a large one and
a small one. The large display is suited for relay installations
where the front panel user interface is frequently used and a
single line diagram is required. The small display is suited for
remotely controlled substations where the relay is only
occasionally accessed locally via the front panel user interface.
Both LCD displays offer front-panel user interface functionality
with menu navigation and menu views. However, the large
display offers increased front-panel usability with less menu
scrolling and improved information overview. In addition, the
large display includes a user-configurable single line diagram
(SLD) with position indication for the associated primary
equipment. Depending on the chosen standard configuration,
the relay displays the related measuring values, apart from the
default single line diagram. The SLD view can also be accessed
using the Web browser-based user interface. The default SLD
can be modified according to user requirements by using the
Graphical Display Editor in PCM600. The user can create up to
10 SLD pages.
The local HMI includes a push button (L/R) for local/remote
operation of the relay. When the relay is in the local mode, it can
be operated only by using the local front panel user interface.
When the relay is in the remote mode, it can execute
commands sent from a remote location. The relay supports the
remote selection of local/remote mode via a binary input. This
feature facilitates, for example, the use of an external switch at
the substation to ensure that all relays are in the local mode
during maintenance work and that the circuit breakers cannot
be operated remotely from the network control center.
IECA070904 V3 EN
Figure 12.
Small display
IECA070901 V3 EN
Figure 13.
Large display
Table 83. Small display
Character size1)
Rows in the view
Characters per row
Small, mono-spaced (6 × 12 pixels)
5
20
Large, variable width (13 × 14 pixels)
3
8 or more
1)
Depending on the selected language
Table 84. Large display
Character size1)
Rows in the view
Characters per row
Small, mono-spaced (6 × 12 pixels)
10
20
Large, variable width (13 × 14 pixels)
7
8 or more
1)
Depending on the selected language
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
46
ABB
22. Mounting methods
By means of appropriate mounting accessories, the standard
relay case can be flush mounted, semi-flush mounted or wall
mounted. The flush mounted and wall mounted relay cases can
also be mounted in a tilted position (25°) using special
accessories.
Further, the relays can be mounted in any standard 19”
instrument cabinet by means of 19” mounting panels available
with cut-outs for one or two relays.Alternatively, the relays can
be mounted in 19” instrument cabinets by means of 4U
Combiflex equipment frames.
For routine testing purposes, the relay cases can be equipped
with test switches, type RTXP 18, which can be mounted side
by side with the relay cases.
Mounting methods
• Flush mounting
• Semi-flush mounting
• Semi-flush mounting in a 25° tilt
• Rack mounting
• Wall mounting
• Mounting to a 19" equipment frame
• Mounting with an RTXP 18 test switch to a 19" rack
Panel cut-out for flush mounting
• Height: 161.5 ±1 mm
• Width: 165.5 ±1 mm
48
177
160
177
153
164
IECA070900 V4 EN
Figure 14.
Flush mounting
98
177
160
186
103
IECA070903 V4 EN
Figure 15.
Semi-flush mounting
230
107
25°
133
190
IECA070902 V4 EN
Figure 16.
Semi-flush mounting in a 25º tilt
23. Relay case and plug-in unit
The relay cases are assigned to a certain type of plug-in unit.
For safety reasons, the relay cases for current measuring relays
are provided with automatically operating contacts for short-
circuiting the CT secondary circuits when a relay unit is
withdrawn from its case. The relay case is further provided with
a mechanical coding system preventing the current measuring
relay units from being inserted into relay cases intended for
voltage measuring relay units.
24. Selection and ordering data
Use ABB Library to access the selection and ordering
information and to generate the order number.
Product Selection Tool (PST), a Next-Generation Order Number
Tool, supports order code creation for ABB Distribution
Automation IEC products with emphasis on, but not exclusively
for, the Relion product family. PST is an easy-to-use, online tool
always containing the latest product information. The complete
order code can be created with detailed specification and the
result can be printed and mailed. Registration is required.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
47
25. Accessories and ordering data
Table 85. Cables
Item
Order number
Optical sensor for arc protection, cable length 1.5 m
1MRS120534-1.5
Optical sensor for arc protection, cable length 3.0 m
1MRS120534-3
Optical sensor for arc protection, cable length 5.0 m
1MRS120534-5
Optical sensor for arc protection, cable length 7.0 m
1MRS120534-7
Optical sensor for arc protection, cable length 10.0 m
1MRS120534-10
Optical sensor for arc protection, cable length 15.0 m
1MRS120534-15
Optical sensor for arc protection, cable length 20.0 m
1MRS120534-20
Optical sensor for arc protection, cable length 25.0 m
1MRS120534-25
Optical sensor for arc protection, cable length 30.0 m
1MRS120534-30
Table 86. Mounting accessories
Item
Order number
Semi-flush mounting kit
1MRS050696
Wall mounting kit
1MRS050697
Inclined semi-flush mounting kit
1MRS050831
19” rack mounting kit with cut-out for one relay
1MRS050694
19” rack mounting kit with cut-out for two relays
1MRS050695
Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19” variant C)
2RCA022642P0001
Mounting bracket for one relay in 4U Combiflex (RHGT 19” variant C)
2RCA022643P0001
19” rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the delivery)
2RCA021952A0003
19” rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the delivery)
2RCA022561A0003
Functional earthing flange for RTD modules1)
2RCA036978A0001
Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the installation plate)
2RCA027871A0001
Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of the installation plate)
2RCA027874A0001
Replacement kit for two Strömberg SP_J3 series relays
2RCA027880A0001
19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out)
2RCA027894A0001
19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs)
2RCA027897A0001
Replacement kit for a Strömberg SP_J6 series relay
2RCA027881A0001
Replacement kit for three BBC S_ series relays
2RCA027882A0001
Replacement kit for a SPA 300 series relay
2RCA027885A0001
1)
Cannot be used when the protection relay is mounted with the Combiflex 19" equipment frame (2RCA032826A0001)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
48
ABB
The protection relay is delivered as a preconfigured unit. The
default parameter setting values can be changed from the front-
panel user interface (local HMI), the Web browser-based user
interface (Web HMI) or Protection and Control IED Manager
PCM600 in combination with the relay-specific connectivity
package.
PCM600 offers extensive relay configuration functions. For
example, depending on the protection relay, the relay signals,
application, graphical display and single-line diagram, and IEC
61850 communication, including horizontal GOOSE
communication, can be modified with PCM600.
When the Web HMI is used, the protection relay can be
accessed either locally or remotely using a Web browser
(Internet Explorer). For security reasons, the Web HMI is
disabled by default but it can be enabled via the local HMI. The
Web HMI functionality can be limited to read-only access.
The relay connectivity package is a collection of software and
specific relay information, which enables system products and
tools to connect and interact with the protection relay. The
connectivity packages reduce the risk of errors in system
integration, minimizing device configuration and setup times.
Further, the connectivity packages for protection relays of this
product series include a flexible update tool for adding one
additional local HMI language to the protection relay. The
update tool is activated using PCM600, and it enables multiple
updates of the additional HMI language, thus offering flexible
means for possible future language updates.
Table 87. Tools
Description
Version
PCM600
2.6 (Rollup 20150626) or later
Web browser
IE 8.0, IE 9.0, IE 10.0 or IE 11.0
REV615 Connectivity Package
5.1 or later
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
49
Table 88. Supported functions
Function
Web HMI
PCM600
Relay parameter setting
●
●
Saving of relay parameter settings in the relay
●
●
Signal monitoring
●
●
Disturbance recorder handling
●
●
Alarm LED viewing
●
●
Access control management
●
●
Relay signal configuration (Signal Matrix)
-
●
Modbus® communication configuration (communication management)
-
●
DNP3 communication configuration (communication management)
-
●
IEC 60870-5-103 communication configuration (communication
management)
-
●
Saving of relay parameter settings in the tool
-
●
Disturbance record analysis
-
●
XRIO parameter export/import
●
●
Graphical display configuration
-
●
Application configuration
-
●
IEC 61850 communication configuration, GOOSE (communication
configuration)
-
●
Phasor diagram viewing
●
-
Event viewing
●
●
Saving of event data on the user's PC
●
●
Online monitoring
-
●
● = Supported
27. Cyber security
The relay supports role based user authentication and
authorization. It can store 2048 audit trail events to a non-
volatile memory. The non-volatile memory is based on a
memory type which does not need battery backup or regular
component exchange to maintain the memory storage. FTP
and Web HMI use TLS encryption with a minimum of 128 bit key
length protecting the data in transit. In this case the used
communication protocols are FTPS and HTTPS. All rear
communication ports and optional protocol services can be
deactivated according to the required system setup.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
50
ABB
28. Terminal diagrams
REV615
X13
Light sensor input 1 1)
X14
Light sensor input 2 1)
X15
Light sensor input 3 1)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) BIO0005 Module (8BI+4BO)
Alternative Module BIO0007 (8BI+3HSO)
4) BIO0006 Module (6BI+3BO)
Alternative Module RTD0001 (6RTD+2mA)
16
17
19
18
X100
6
7
8
9
10
11
12
13
15
14
2
1
3
4
5
22
21
23
24
SO2
TCS2
PO4
SO1
TCS1
PO3
PO2
PO1
IRF
+
-
Uaux
20
X110
3
4
5
6
7
8
9
10
BI 6
BI 5
BI 4
BI 3
BI 2
BI 8
BI 7
12
13
11
BI 1
1
2
X110
16
14
15
19
17
18
22
20
21
SO3
SO2
SO1
23
SO4
24
2)
X120
1
2
3
4
5
6
7
8
9
10
11
12
13
14
IL1unb
1/5A
N
IL2unb
IL1
IL2
IL3
Io
1/5A
N
1/5A
N
1/5A
N
1/5A
N
1/5A
N
1/5A
N
IL3unb
3)
3)
X130
1
2
3
4
5
6
BI 4
BI 3
BI 2
BI 1
BI 6
BI 5
8
9
7
X130
12
10
11
15
13
14
18
16
17
SO3
SO2
SO1
4)
4)
GUID-E075C9E1-5D32-4556-ADD7-8B64EF861FA8 V1 EN
Figure 17.
Terminal diagram for standard configuration A
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
51
Light sensor input 1 1)
X14
Light sensor input 2 1)
X15
Light sensor input 3 1)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) BIO0005 Module (8BI+4BO)
Alternative Module BIO0007 (8BI+3HSO)
4) AIM0006 Module (5U+4BI)
Alternative Module AIM0003 (5U+2RTD+1mA)
16
17
19
18
X100
6
7
8
9
10
11
12
13
15
14
2
1
3
4
5
22
21
23
24
SO2
TCS2
PO4
SO1
TCS1
PO3
PO2
PO1
IRF
+
-
Uaux
20
X110
3
4
5
6
7
8
9
10
BI 6
BI 5
BI 4
BI 3
BI 2
BI 8
BI 7
12
13
11
BI 1
1
2
X110
16
14
15
19
17
18
22
20
21
SO3
SO2
SO1
23
SO4
24
2)
X120
1
2
3
4
5
6
7
8
9
10
11
12
13
14
IL1unb
1/5A
N
IL2unb
IL1
IL2
IL3
Io
1/5A
N
1/5A
N
1/5A
N
1/5A
N
1/5A
N
1/5A
N
IL3unb
3)
3)
X130
1
2
3
4
5
6
BI 4
BI 3
BI 2
BI 1
8
7
9
10
11
12
UoB
13
14
U1
15
16
U2
17
18
U3
Uo
N
N
N
N
60 -
N
210V
60 -
210V
60 -
210V
60 -
210V
60 -
210V
4)
GUID-71A7F7FA-9605-46FE-A7EF-B53142C4EE9F V1 EN
Figure 18.
Terminal diagram for standard configuration B
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
52
ABB
DNV GL has issued an IEC 61850 Edition 2 Certificate Level A1
for Relion® 615 series. Certificate number: 7410570I-OPE/INC
15-1136.
DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1
for Relion® 615 series. Certificate number: 74105701-OPE/INC
15-1145.
Additional certificates can be found on the product page.
30. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
The latest relevant information on the REV615 protection and
control relay is found on the product page. Scroll down the
page to find and download the related documentation.
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
53
31. Functions, codes and symbols
Table 89. Functions included in the relay
Function
IEC 61850
IEC 60617
IEC-ANSI
Protection
Three-phase non-directional overcurrent protection, low
stage
PHLPTOC1
3I> (1)
51P-1 (1)
Three-phase non-directional overcurrent protection, high
stage
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent protection,
instantaneous stage
PHIPTOC1
3I>>> (1)
50P/51P (1)
Non-directional earth-fault protection, low stage
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
Non-directional earth-fault protection, high stage
EFHPTOC1
Io>> (1)
51N-2 (1)
Non-directional earth-fault protection, instantaneous stage
EFIPTOC1
Io>>> (1)
50N/51N (1)
Directional earth-fault protection, low stage
DEFLPDEF1
Io> -> (1)
67N-1 (1)
DEFLPDEF2
Io> -> (2)
67N-1 (2)
Directional earth-fault protection, high stage
DEFHPDEF1
Io>> -> (1)
67N-2 (1)
Transient/intermittent earth-fault protection
INTRPTEF1
Io> -> IEF (1)
67NIEF (1)
Negative-sequence overcurrent protection
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
Residual overvoltage protection
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
Three-phase undervoltage protection
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
Three-phase overvoltage protection
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
Positive-sequence undervoltage protection
PSPTUV1
U1< (1)
47U+ (1)
Negative-sequence overvoltage protection
NSPTOV1
U2> (1)
47O- (1)
Three-phase thermal overload protection, two time
constants
T2PTTR1
3Ith>T/G/C (1)
49T/G/C (1)
Circuit breaker failure protection
CCBRBRF1
3I>/Io>BF (1)
51BF/51NBF (1)
Master trip
TRPPTRC1
Master Trip (1)
94/86 (1)
TRPPTRC2
Master Trip (2)
94/86 (2)
TRPPTRC3
Master Trip (3)
94/86 (3)
TRPPTRC4
Master Trip (4)
94/86 (4)
TRPPTRC5
Master Trip (5)
94/86 (5)
Arc protection
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
54
ABB
Table 89. Functions included in the relay, continued
Function
IEC 61850
IEC 60617
IEC-ANSI
Multipurpose protection
MAPGAPC1
MAP (1)
MAP (1)
MAPGAPC2
MAP (2)
MAP (2)
MAPGAPC3
MAP (3)
MAP (3)
MAPGAPC4
MAP (4)
MAP (4)
MAPGAPC5
MAP (5)
MAP (5)
MAPGAPC6
MAP (6)
MAP (6)
MAPGAPC7
MAP (7)
MAP (7)
MAPGAPC8
MAP (8)
MAP (8)
MAPGAPC9
MAP (9)
MAP (9)
MAPGAPC10
MAP (10)
MAP (10)
MAPGAPC11
MAP (11)
MAP (11)
MAPGAPC12
MAP (12)
MAP (12)
MAPGAPC13
MAP (13)
MAP (13)
MAPGAPC14
MAP (14)
MAP (14)
MAPGAPC15
MAP (15)
MAP (15)
MAPGAPC16
MAP (16)
MAP (16)
MAPGAPC17
MAP (17)
MAP (17)
MAPGAPC18
MAP (18)
MAP (18)
Three-phase overload protection for shunt capacitor banks
COLPTOC1
3I> 3I< (1)
51C/37 (1)
Current unbalance protection for shunt capacitor banks
CUBPTOC1
dI>C (1)
51NC-1 (1)
Three-phase current unbalance protection for shunt
capacitor banks
HCUBPTOC1
3dI>C (1)
51NC-2 (1)
Shunt capacitor bank switching resonance protection,
current based
SRCPTOC1
TD> (1)
55TD (1)
Power quality
Current total demand distortion
CMHAI1
PQM3I (1)
PQM3I (1)
Voltage total harmonic distortion
VMHAI1
PQM3U (1)
PQM3V (1)
Voltage variation
PHQVVR1
PQMU (1)
PQMV (1)
Voltage unbalance
VSQVUB1
PQUUB (1)
PQVUB (1)
Control
Circuit-breaker control
CBXCBR1
I <-> O CB (1)
I <-> O CB (1)
Disconnector control
DCXSWI1
I <-> O DCC (1)
I <-> O DCC (1)
DCXSWI2
I <-> O DCC (2)
I <-> O DCC (2)
Earthing switch control
ESXSWI1
I <-> O ESC (1)
I <-> O ESC (1)
Disconnector position indication
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
55
Table 89. Functions included in the relay, continued
Function
IEC 61850
IEC 60617
IEC-ANSI
Earthing switch indication
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
Condition monitoring and supervision
Circuit-breaker condition monitoring
SSCBR1
CBCM (1)
CBCM (1)
Trip circuit supervision
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
Current circuit supervision
CCSPVC1
MCS 3I (1)
MCS 3I (1)
Fuse failure supervision
SEQSPVC1
FUSEF (1)
60 (1)
Runtime counter for machines and devices
MDSOPT1
OPTS (1)
OPTM (1)
Measurement
Disturbance recorder
RDRE1
DR (1)
DFR (1)
Load profile record
LDPRLRC1
LOADPROF (1)
LOADPROF (1)
Fault record
FLTRFRC1
FAULTREC (1)
FAULTREC (1)
Three-phase current measurement
CMMXU1
3I (1)
3I (1)
Sequence current measurement
CSMSQI1
I1, I2, I0 (1)
I1, I2, I0 (1)
Residual current measurement
RESCMMXU1
Io (1)
In (1)
Three-phase voltage measurement
VMMXU1
3U (1)
3V (1)
Residual voltage measurement
RESVMMXU1
Uo (1)
Vn (1)
RESVMMXU2
Uo (2)
Vn (2)
Sequence voltage measurement
VSMSQI1
U1, U2, U0 (1)
V1, V2, V0 (1)
Three-phase power and energy measurement
PEMMXU1
P, E (1)
P, E (1)
RTD/mA measurement
XRGGIO130
X130 (RTD) (1)
X130 (RTD) (1)
Frequency measurement
FMMXU1
f (1)
f (1)
IEC 61850-9-2 LE sampled value sending
SMVSENDER
SMVSENDER
SMVSENDER
IEC 61850-9-2 LE sampled value receiving (voltage
sharing)
SMVRCV
SMVRCV
SMVRCV
Other
Minimum pulse timer (2 pcs)
TPGAPC1
TP (1)
TP (1)
TPGAPC2
TP (2)
TP (2)
TPGAPC3
TP (3)
TP (3)
TPGAPC4
TP (4)
TP (4)
Minimum pulse timer (2 pcs, second resolution)
TPSGAPC1
TPS (1)
TPS (1)
Minimum pulse timer (2 pcs, minute resolution)
TPMGAPC1
TPM (1)
TPM (1)
Pulse timer (8 pcs)
PTGAPC1
PT (1)
PT (1)
PTGAPC2
PT (2)
PT (2)
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
56
ABB
Table 89. Functions included in the relay, continued
Function
IEC 61850
IEC 60617
IEC-ANSI
Time delay off (8 pcs)
TOFGAPC1
TOF (1)
TOF (1)
TOFGAPC2
TOF (2)
TOF (2)
TOFGAPC3
TOF (3)
TOF (3)
TOFGAPC4
TOF (4)
TOF (4)
Time delay on (8 pcs)
TONGAPC1
TON (1)
TON (1)
TONGAPC2
TON (2)
TON (2)
TONGAPC3
TON (3)
TON (3)
TONGAPC4
TON (4)
TON (4)
Set-reset (8 pcs)
SRGAPC1
SR (1)
SR (1)
SRGAPC2
SR (2)
SR (2)
SRGAPC3
SR (3)
SR (3)
SRGAPC4
SR (4)
SR (4)
Move (8 pcs)
MVGAPC1
MV (1)
MV (1)
MVGAPC2
MV (2)
MV (2)
Generic control point (16 pcs)
SPCGAPC1
SPC (1)
SPC (1)
SPCGAPC2
SPC (2)
SPC (2)
Analog value scaling
SCA4GAPC1
SCA4 (1)
SCA4 (1)
SCA4GAPC2
SCA4 (2)
SCA4 (2)
SCA4GAPC3
SCA4 (3)
SCA4 (3)
SCA4GAPC4
SCA4 (4)
SCA4 (4)
Integer value move
MVI4GAPC1
MVI4 (1)
MVI4 (1)
32. Document revision history
Document revision/date
Product version
History
A/2014-01-24
5.0
First release
B/2015-10-30
5.0 FP1
Content updated to correspond to the product version
C/2016-05-20
5.0 FP1
Content updated
D/2018-12-20
5.0 FP1
Content updated
Capacitor Bank Protection and Control
1MRS757952 D
REV615
Product version: 5.0 FP1
ABB
57
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
ABB Distribution Automation
Maneja Works
Vadodara-390013, India
Phone
+91 265 2604386
Fax
+91 265 2638922
www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation
—
© Copyright 2018 ABB. All rights reserved.
1MRS757952 D