ABB COMMANDER 300 Programming Manual
Read Online
Read the ABB COMMANDER 300 Programming Manual online using the built-in PDF viewer.
Text of the manual
ABB Instrumentation
Programming Guide
COMMANDER 300/310
Universal
Process Controllers
COMMANDER 310
COMMANDER 300
A1
A2
L
R
ST
M
47.5
50.0
A1
A2
L
R
ST
M
47.5
50.0
all-guide
s.com
BS EN ISO 9001
St Neots, U.K. – Cert. No. Q5907
Stonehouse, U.K. – Cert. No. FM 21106
The Company
ABB Instrumentation is an established world force in the design and
manufacture of instrumentation for industrial process control, flow
measurement, gas and liquid analysis and environmental
applications.
As a part of ABB, a world leader in process automation technology,
we offer customers application expertise, service and support
worldwide.
We are committed to teamwork, high quality manufacturing,
advanced technology and unrivalled service and support.
The quality, accuracy and performance of the Company’s products
result from over 100 years experience, combined with a continuous
program of innovative design and development to incorporate the
latest technology.
The NAMAS Calibration Laboratory No. 0255 is just one of the ten
flow calibration plants operated by the Company, and is indicative of
ABB Instrumentation's dedication to quality and accuracy.
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and
in accordance with the information given.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in
conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry.
Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets
(where applicable) may be obtained from the Company address on the back cover, together with servicing and
spares information.
✶
Note.
Clarification of an instruction or additional
information.
Information.
Further reference for more detailed information or
technical details.
Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or
property damage, it must be understood that operation of damaged equipment could, under certain operational
conditions, result in degraded process system performance leading to personal injury or death. Therefore, comply
fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use
of this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or
part without prior approval of Technical Communications Department, ABB Instrumentation.
EN 29001 (ISO 9001)
Lenno, Italy – Cert. No. 9/90A
Use of Instructions
Warning.
An instruction that draws attention to the risk of
injury or death.
Caution.
An instruction that draws attention to the risk of
damage to the product, process or surroundings.
Stonehouse, U.K.
0255
R
E
G
I
S
T
E
R
E
D
INTRODUCTION .................................. 2
2
GENERAL PROGRAMMING ............... 2
2.1
Preparation for Changes
to the Parameters ........................ 2
3
SELECTING CONTROL TYPE ............ 3
4
CONFIGURATION ................................ 4
4.1
Profile Program Page................... 4
4.2
Set Points Page ........................... 6
4.3
Motorized Valve Control............. 11
4.3.1
Position
Feedback Page .............. 12
4.4
Motorized Valve Control
without Feedback (Boundless) ... 13
4.4.1
Calculation for Control
Pulses, Steps and
Deviation (Boundless
Control only) ................... 13
4.4.2
Regulator Data Page ...... 14
4.5
Set Up Process Variable ............ 15
4.5.1
Set Up Process
Variable Input Page
(COMMANDER 300) ...... 16
4.6
Set Up Remote Set Point Page . 20
4.7
Set Up Position
Feedback Page .......................... 22
4.8
Set Up Display Page .................. 24
4.9
Current Proportioning
Output Page ............................... 25
4.10 Set Up Control Page .................. 28
4.11 Set Up Alarms Page .................. 37
4.12 Retransmission Output Page ..... 44
4.13 Cool Output Page ...................... 44
4.14 Scale Adjustment Page .............. 45
4.15 Access Page .............................. 48
4.16 Set Up Process
Variable Input Page
(COMMANDER 301 only) ......... 49
Preparation for Changes to
the Parameters
Ensure that the external alarm/control
circuits
are
isolated
if
inadvertent
operation
during
programming
is
undesirable.
Any change to the operating parameters
are implemented using the
or
switches – see Section 3 of the Operating
Guide.
Note. The instrument responds
instantly to parameter changes which
are saved when the
switch is
pressed.
2
GENERAL PROGRAMMING
1
INTRODUCTION
The
COMMANDER
300
Series
of
documentation is shown in Fig. 1.1. The
Standard Manuals, including the specification
sheet, are supplied with all instruments. The
Modbus
Supplement
is
supplied
with
instruments configured for Modbus Serial
Communication.
The
Installation
manual
includes
an
Installation
Record
which
should
be
completed as a log of the electrical
installation. The record is useful when
carrying out initial instrument programming
and can be retained for future reference
PROGRAMMING
Part No.
IM/C300–PG
Basic Config. Level
Advanced Config.
Level
OPERATION
Setting Up
Displays & Controls
Operating Level
Simple Fault Finding
Part No.
IM/C300–OG
Part No. IM/C300–INS
or IM/C310–INS
INSTALLATION
Product Identification
Siting
Mounting
Electrical Connections
Installation Record
MODBUS (RTU).
Serial Adaptors
Serial Connections
Programming Page
Part No. IM/C300–MOD
or IM/C310–MOD
SPECIFICATION SHT.
Full Specification
Part No. SS C300
or SS C310
Modbus Registers
Standard Manuals
Modbus Supplement
Fig. 1.1 Commander 300 Documentation
SELECTING CONTROL TYPE
SEtUP
CONtrL
Page Header – Set Up Control.
C–tYPE
Control Type – see Section 4.10
t–PrOP
P–PrOP
Select the control type required:
–
–
–
–
current
proportioning.
time proportioning.
position proportioning –
motorised valve with
position feedback.
boundless – motorised
valve without position
feedback.
C–PrOP
t–PrOP
P–PrOP
bndLSS
Press then to return to the
Operating Page.
dISPLY
bndLSS
PAGE
C–ProP
OUtPUt
or
C–PrOP
100.3
110.5
ACKNLG
ALArMS
P-StAt
PAGE
PrOFLE
StAtES
SECOdE
PAGE
SELF
tunE
ContrL
PAGE
PrOFLE
PrOGr
SEt
POINtS
POStN
F-bACK
rEGLtr
dAtA
SEtUP
PrCESS
SEtUP
rSPt
SEtUP
PSN-Fb
or
SEtUP
ALArMS
ACCESS
PAGE
SCALE
AdJUSt
rEtrAN
COOL
OUtPUt
or
OUtPUt
Operating Page
Fig. 3.1 Selecting the Control Type
Note. It is recommended that the
control type is set up before the
instrument is configured.
Profile Program Page
Information.
•
This page is inaccessible when a profile is running.
•
Up to 9 programs for the C300/C310 (3 for the C301, 20 for the C302).
•
Total of 30 segments for the C300/C310 (12 for the C301, 99 for the C302).
•
Guaranteed Ramp/Soak feature.
•
Repeat facility for each program.
Eng.
Units
S1
S2
S3
S4
S5
L1
L2
L3
L4
L5
Program 1
Program 2
Start at S1
Start at S2
End at S5
Time
Overall Profile
End at S3
Segment
Numbers
L0
Levels:
Page Header – Profile Program.
Profile Enable
Select the profile function, on or OFF.
Program Select
Select the program required, between 1 and 9 (3 for C301, 20
for C302).
A program consists of up to 30 (12 for C301, 99 for C302)
segments. Each segment has a starting and finishing set
point level, giving a maximum of 31 (13 for C301, 100 for
C302) levels. For identification purposes these levels are
numbered 0 to 30 (12 for C301, 99 for C302), e.g.:
Level 1 is the finishing level of segment 1 and the
starting level of segment 2
Level 10 is the finishing level of segment 10 and the
starting level of segment 11.
Program Begin (start level)
This is the first level number of the program selected at
Program Select above.
Set the program start level number for the program chosen
at Program Select, between 0 and 29 (11 for C301, 98 for
C302).
Continued on next page.
OFF
1
PrOFLE
PrOFLE
ON
OFF
0
PG–bEG
PrOGrM
PrOGrM
all-guide
s.com
– – – –
0
xx
Last segment
More
segments
to set up
rEPEAt
HYSt
0
SEt
POINtS
30
LEU.L 0x
PG –ENd
1.0
x
tIME
…4.1
Profile Program Page
4
CONFIGURATION…
Program End (finish level)
Set the program end level number for the program chosen
at Program Select, between 1 and 30 (12 for C301, 99 for
C302).
Program First Segment Start Level
The number shown in the upper display is the start level
number for the first segment.
Set the required value for the start level.
The units are display units between Display Zero and
Display Full Scale.
Segment Time Period
The time number of the currently selected segment is
shown in the upper display.
Set the required time period, between 0 and 999.9 minutes
in 0.1 minute increments.
Segment Finish/Start Level
The number shown in the upper display is the finish level
number for the currently selected segment and the start
number for the next segment.
Set the required value for the segment finish/start level. The
units are display units between display zero and full scale.
Advance to the next parameter, Segment Time Period, if
more segments are to be set-up or Repeat if the current
segment is the last segment.
Program Repeat
Each program can be set to repeat up to 99 times or
continuously.
Set the required repeat count, between 0 and 99, or
InFntE for continuous repeats.
Program Hysteresis Value (for guaranteed ramp/soak)
A hysteresis value can be set in engineering units. Setting
the value to zero turns the guaranteed ramp/soak facility
off. If the process variable deviates beyond the value set,
the program is suspended but continues automatically
when the process variable returns within the set limits. The
hysteresis value applies above and below set point under
all program conditions.
Set the hysteresis value required, within the display range
limits.
Return to top of Profile Program Page
or
advance to Set Points Page.
Set Points Page
Information.
•
Two local set points – Local and Dual.
•
Remote set point facility – with Ratio and Bias.
•
Remote set point tracking options – for bumpless Remote-to-Local set point transfers.
•
Adjustable high and low limits for all set point types.
•
Set point tracking for bumpless Manual-to-Auto transfers.
90
10
Dual
Remote
Local Set Point
Programmable Set Point Types
Ratio
Bias
Limits
Fixed Set Point 1
Fixed Set Point 2
Digitally Selectable Set Points
Adjustable limits
Adjustable limits
Engineering Range
Ratio Setting
(0.010 to 9.999)
Bias Setting
(within Eng. range)
Limits
(within Eng. range)
100
Set
Point 50
0
1.5
0.1
1.0
SP = 50
SP = 5
SP = 75
SP = 10
SP = 30
SP = 85
+5
–20
+10
* Set Point cannot be adjusted outside the limits set
High Limit*
Low Limit*
Dual
Second
Set Point
Control
Set Point
Limits
Limits
Fig. 4.1 Set Point Types
Set Points Page
To gain access to this and subsequent pages the correct Configuration code must first be set
in the Security Code Page – see Section 5.5 of the Operating Guide.
SEt
SP–AdJ
YES
LSP–HI
1000
LSP–LO
0
LSPt
500
SPt–SL
YES
POINtS
SP–trK
no
Page Header – Set Points.
Set Point Adjustment Enable
This frame allows display and adjustment of the set point in
the Operating Page Displays (see Section 5.2 of the
Operating Guide). Select YES to enable or no to disable.
Set Point High Limit
This is the maximum value to which the local set point can
be adjusted.
Set the value required. The decimal point position is set
automatically.
Set Point Low Limit
This is the minimum value to which the local set point can
be adjusted.
Set the value required. The decimal point position is set
automatically.
Local Set Point Value
Set the value required, within the limits set above. The
decimal point position is set automatically to that set in the
Set Up Display Page – see Section 4.8.
Set Point Tracking Enable
If Set Point Tracking is enabled and the controller is in
Manual mode the local set point tracks the process
variable. When the controller is in Set Point Tracking mode
the local set point limits can be exceeded. If the local set
point is outside of its limits when the tracking mode is
disabled, the local set point value can only be adjusted
towards its limits. Once within the limits they apply as
normal.
Select YES to enable or no to disable.
Set Point Select
This frame enables selection of set point type from the
Operating Page i.e., LOCAL, rEMOtE, or dUAL as
applicable – see Set Point Type Selection (Section 5.2 of the
Operating Guide).
Select YES to enable, or no to disable.
Continued on next page.
Set Points Page
Second Set Point Type
This frame enables the setting up of a Second set point in
addition to the Local set point.
Select the second set point type, NONE (no Second set
point), dUAL (Dual set point) or rEMOtE (Remote set
point).
Dual Set Point High Limit
This is the maximum value to which the Dual set point can
be adjusted.
Select the value required. The decimal point position is set
automatically.
Dual Set Point Low Limit
This is the minimum value to which the Dual set point can
be adjusted.
Select the value required. The decimal point position is set
automatically.
Adjustable Dual Set Point Value
Set the value required, restricted to the limits set in Dual Set
Point High Limit and Dual Set Point Low Limit above.
Advance to Set Point Type Selection on page 10.
Remote Set Point Tracking Enable
If Remote Set Point Tracking is enabled and the controller is
in Remote mode the Local set point tracks the remote set
point. When the controller is in Remote Set Point Tracking
mode the local set point limits can be exceeded. If the local
set point is outside of its limits when the tracking mode is
disabled, the Local set point value can only be adjusted
towards its limits. Once within the limits they apply as
normal. With Remote set point tracking enabled; if the
controller is put into Manual mode, the set point reverts
from remote to Local.
Select YES to enable or no to disable.
Remote Set Point High Limit
This is the maximum value to which the Remote set point
can be adjusted.
Select the value required. The decimal point position is set
automatically.
Continued on next page.
dSP–HI
1000
dSP–LO
0
d U A L
NONE
or
rEMOtE
d–SPt
500
1000
NONE
rEMOtE
rSP–HI
YES
rSPtrK
2nd–SP
rEMOtE
Set Points Page
4
CONFIGURATION…
Remote Set Point Low Limit
This is the minimum value to which the remote set point
can be adjusted.
Select the value required. The decimal point position is set
automatically.
Remote Set Point Ratio Adjust Enable
This frame enables or disables the display and adjustment
of the remote set point ratio in the Operating Page (see
Section 5.2 of the Operating Guide).
Select YES to enable or no to disable.
Remote Set Point Ratio
This is a scaling factor, i.e. multiplies the remote set point
input by the ratio value set. Set the required remote set
point ratio, between 0.010 and 9.999 in 0.001 increments.
Remote Set Point Bias Adjust Enable
This frame enables or disables the display and adjustment
of the remote set point bias in the Operating Page (see
Section 5.2 of the Operating Guide).
Select YES to enable or no to disable.
Remote Set Point Bias
This is an offset value set as a proportion of display span
(may be ± the span value).
Set the remote set point bias in engineering units.
Continued on next Page.
b–AdJ
bIAS
0
no
1.000
rAtIO
0
rSP–LO
r–AdJ
no
dUAL
NONE
all-guide
s.com
– – – – – –
SEt UP
PrCESS
LOCAL
bALNCE
rEMOtE
or
dUAL
POStn
F–bACK
rEGLtr
dAtA
or
or
– – – – – –
…4.2
Set Points Page
Set Point Type Selection
This frame displays the current set point type, or bALNCE
and value – see Set Point Type Selection frame in the
Operating Page – see Section 5.2 of the Operating Guide.
Upper Display – displays the set point type, or bALNCE:
LOCAL
–
Local set point
bALNCE –
Balance, the difference between the
Local and Remote (or Dual) set point
values
rEMOtE –
Remote set point on controllers with
Remote set point facility
dUAL
–
Dual set point
Lower Display – displays the value of the set point type
shown in the upper display, but if the set point type is
changed from Local to Remote (or Dual) the display shows
the difference (bALNCE) between the Local set point
value and the Remote (or Dual) set point value.
When Remote set point is selected and if Remote set point
tracking is enabled the Local set point value tracks the
Remote set point value. The Local set point limits do not
apply in this mode. If the Local set point is outside of its
limits when Local set point type is re-selected, it can only
be adjusted towards its limits. Once within these limits,
they apply as normal.
Press
to select LOCAL, bALNCE, rEMOtE (or
dUAL). rEMOtE and dUAL are dependent on the
selection made at Second Set Point Type parameter.
Return to the top of Set Points Page or advance to the next
page.
…4
CONFIGURATION
Motorized Valve Control
Information.
•
Motorized valve control with or without feedback – position-proportioning (with
feedback) or boundless (without feedback).
•
Ratio and bias settings can be applied to adjust the range of valve travel (position-
proportioning only).
•
Deadband setting – adjustable to minimize hunting of the motorized valve.
4
CONFIGURATION…
P.I.D. Output
Desired Valve Position
Engineering Range
Ratio Setting
(0.010 to 9.999)
Bias Setting
(within Eng. range)
100
50
0
A 1.0
B 0.5
C –25%
B 0%
Ratio
Bias
Proportional
Bandwidth*
80
20
A 0%
100%
0%
Valve
Travel
Limits
75%
25%
Valve
Travel
Limits
50%
0%
Valve
Travel
Limits
Valve
Open
Valve
Closed
C 0.5
A
B
C
Fig. 4.2 Position-Proportioning Schematic Diagram
Position Feedback Page
This page appears only if P–PrOP is selected at the Control Type parameter in the Set Up
Control Page – see Fig. 3.1 and Section 4.10.
rAtIO
1.00
bIAS
0
dEAdb
1.0
SEtUP
PrCESS
POStN
F–bACK
Page Header – Position Feedback Page
Ratio
Ratio is a scaling factor, i.e. multiplies the position
feedback input by the value set here.
Set the required feedback ratio, between 0.0 and 9.99 in
0.01 increments.
Bias
Bias is an offset as a percentage of the valve travel.
Set the required feedback bias, between –100.0 and
+100.0%.
Deadband
Deadband is set as a percentage of the position feedback
span, between 0.0 and 10.0%, to produce a deadband
around the valve control value. This gives minimum
‘hunting’ of the motorized valve.
Example – if the valve is to be driven to the 50% open
position and the deadband is set to 4.0%, the motor stops
driving when the position feedback is 48%. In this example
the deadband is between 48% and 52%.
Return to the top of the Position Feedback Page or advance
to next page.
Motorized Valve Control without Feedback (Boundless) – Fig. 4.3
A 'boundless' process controller provides an output that is effectively the time derivative of the
required regulator position, i.e. the controller signals the regulator, not where to go to (position
derivative), but in which direction to travel and how far to move, by a series of integral action
pulses. Thus, the controller does not need to know the absolute regulator position and is
unaffected when regulator reaches the upper or lower limit, as determined by the regulator's
limit switches (giving rise to the term 'boundless').
In this system, the final regulator must act as an integrator, integrating both the raise and lower
pulses in direction and duration so that the final position of the regulator reproduces the
required 2 or 3 term control function, and must remain stationary indefinitely in the absence of
raise or lower commands.
When a deviation from set point is introduced the regulator is driven, for a length of time
equivalent to the proportional step. The regulator is then driven by integral action pulses until
the deviation is within the deadband setting.
4.4.1
Calculation for Control Pulses, Steps and Deviation (Boundless Control
only)
Minimum 'ON' time of integral action pulses (for a fixed control deviation).
= Travel Time x Deadband %
% Proportional Band
(in seconds)
Minimum (approximate) time between integral action pulses (for a fixed control deviation)
= Integral Action Time x Deadband %
2 x % Control Deviation
(in seconds)
Duration of the proportional step
= 2 x
% Control Deviation
% Proportional Band
x Travel Time in Seconds
% Control Deviation = Set Point – Process Variable
Span
Fig. 4.3 Boundless Control Action
Proportional
Step
Time
Control
Deviation
Raise
Lower
Time
Integral
Action Pulses
Proportional
Step
Proportional
Step
Integral
Action Pulses
+
–
Regulator Data Page
This page is displayed only when bndLESS is selected at Control Type frame in the Set Up
Control Page – see Fig. 3.1 and Section 4.10.
Page Header – Regulator Data
Regulator Travel Time
This is the time set for the regulator to travel from the fully
open to the fully closed position or from the fully closed to
the fully open position.
Set the value required in seconds, between 1 and 5000
seconds.
Deadband Setting
The deadband is set as a percentage of the engineering
range span to produce a deadband around the control set
point value. This reduces ‘hunting’ of the regulator.
Set the required value, between 0.0 and 10.0%.
Position Feedback Indication Enable
Select INdCtN to enable the Valve Position frame in the
Operating Page – see Section 5.2 of the Operating Guide.
Select NONE to disable the Valve Position frame.
Note. A value is only displayed in the Valve Position
frame if the frame is enabled and the regulator has a
feedback signal.
Return to top of Regulator Data Page,
or
Advance to Set-up Process Variable Input Page.
dAtA
600
dEAdb
1.0
rGL–t
rEGLtr
SEtUP
PrCESS
INdCtN
PSN–Fb
all-guide
s.com
Set Up Process Variable
Information.
•
Universal inputs – mV, mA, V, THC, RTD and resistance.
•
Internal cold junction compensation.
•
Linearization of temperature sensors to allow use of non-linearizing transmitters or any
electrical input.
•
Programmable fault levels and actions.
•
Digital filter reduces the effect of noise on inputs.
4
CONFIGURATION…
Input
Type
Linearizer
Type
Linearizer
Units
Linearizer
Range
Display Range
5/2
3/2
√
RTD
THC N
THC B
THC E
THC J
THC T
THC S
THC R
THC K
None
Programme
Filter
°F
°C
RTD
THC
Current
Voltage
Millivolts
Display Range
High
Value set to 0
Value set low
Value set high
Fault
Detection
Level 10 %
200
0
Display Range
Low
Fault
Detection
Level 10 %
200
220
–20
0
Example – Type K thermocouple Range 0 to 200°F with 10% fault detection levels.
Set Up Process Variable Input Page (COMMANDER 300)
If the custom linearizer is to be used (available on COMMANDER 301 only), refer to Section
4.16.
LNtYPI
NONE
tC-K
tC-r
tC-S
tC-J
tC-L
tC-E
rtd
SQrt
tC-t
3 2
5 2
SQrt
NONE
L–UNtI
dEG C
5 2
3 2
tC-b
tC-N
SEtUP
PrCESS
IntYPI
U.Lt
MAMP
VOLt
ohM
tCPL
rtd
(a)
(b)
Page Header – Set Up Process Variable Input.
Process Variable Input Type
Select the input type required:
MU.Lt
–
Millivolt (≤2000 mV)
MAMP
–
Current
V.OLt
–
Voltage
ohM
–
Resistance
tCPL
–
Thermocouple *
rtd
–
Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Linearizer Type
Select the linearizer type required:
NONE
–
No linearizer
tC-K
–
Type K thermocouple
tC-r
–
Type R thermocouple
tC-S
–
Type S thermocouple
tC-t
–
Type T thermocouple
tC-J
–
Type J thermocouple
tC-L
–
Type L thermocouple
tC-E
–
Type E thermocouple
tC-b
–
Type B thermocouple
tC-N
–
Type N thermocouple
rtd
–
Resistance thermometer
SQrt
–
Square root
3 2
–
x 3/2
5 2
–
x 5/2
Linearizer Units
Select the temperature units required, °C or °F.
Continued on next page.
Continued on page 18.
Set Up Process Variable Input Page
Linearizer Full Scale
Set the range maximum temperature in °C or °F as
selected at Linearizer Units above, within the limits detailed
in Table 4.1. If these limits are exceeded, LIN–Or
(linearizer overrange) is displayed in the Operating Page –
see Table 5.1a of the Operating Guide.
Linearizer Zero
Set the range minimum temperature in °C or °F as selected
at Linearizer Units above, within the limits detailed in Table
4.1.
Continued on next page. (for b and c)
Table 4.1 Temperature Limits
* Accuracy for type B,R and S is not guaranteed below 400°C.
Minimum span below zero Type T 70°C/126°F
THC standard DIN 43710 IEC 584
RTD standard DIN 43760 IEC 751
I000
0
LIN–LO
LIN–HI
(a)
(c)
D
T
R
/
C
H
T
e
p
y
T
s
u
i
s
l
e
C
s
e
e
r
g
e
D
ti
e
h
n
e
r
h
a
F
s
e
e
r
g
e
D
.
n
i
M
.
x
a
M
n
a
p
S
.
n
i
M
.
n
i
M
.
x
a
M
n
a
p
S
.
n
i
M
*
B
e
p
y
T
8
1
–
0
0
8
1
0
1
7
0
2
7
2
3
8
7
2
1
E
e
p
y
T
0
0
1
–
0
0
9
5
4
8
4
1
–
2
5
6
1
1
8
J
e
p
y
T
0
0
1
–
0
0
9
0
5
8
4
1
–
2
5
6
1
0
9
K
e
p
y
T
0
0
1
–
0
0
3
1
5
6
8
4
1
–
2
7
3
2
7
1
1
L
e
p
y
T
0
0
1
–
0
0
9
0
5
8
4
1
–
2
5
6
1
0
9
N
e
p
y
T
0
0
2
–
0
0
3
1
0
9
8
2
3
–
2
7
3
2
2
6
1
*
S
&
R
e
p
y
T
8
1
–
0
0
7
1
0
2
3
0
2
9
0
3
6
7
5
T
e
p
y
T
0
5
2
–
0
0
3
0
6
8
1
4
–
2
7
5
8
0
1
D
T
R
0
0
2
–
0
0
6
5
2
8
2
3
–
2
1
1
1
5
4
Set Up Process Variable Input Page
Input Range Full Scale
Set the input range maximum in electrical units, within the
limits detailed in Table 4.2.
Example – to set an input range full scale of 20mA, enter
200 in the input full scale display and advance to decimal
point display. Set the decimal point one place to give a
value of 20.0.
Decimal Point
Set the decimal point position required for both the range
full scale and range zero values.
Input Range Zero
Set the input range minimum in electrical units, within the
limits detailed in Table 4.2.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
process variable is driven in the direction of the mode
selected.
Select the broken sensor drive required:
NONE
–
No drive
UP
–
Upscale drive
dN
–
Downscale drive.
Continued on the next page.
…4
CONFIGURATION
Table 4.2 Electrical Limits
r–HI–I
dEC–Pt
1000
r–LO–I
0
bSPd
UP
1000
dN
NONE
(b) from page 16
(c) from
page 17
e
p
y
T
t
u
p
n
I
tr
a
t
S
.
n
i
M
e
u
l
a
V
.
x
a
M
n
a
p
S
.
n
i
M
s
tl
o
v
illi
M
0
0
0
2
–
0
0
0
2
5
.
2
s
tl
o
V
0
2
–
0
2
5
2
.
0
s
p
m
a
illi
M
0
0
1
–
0
0
1
5
2
.
0
e
c
n
a
t
s
i
s
e
R
0
0
0
0
8
0
1
Fault Detection Level Percentage, Process Variable
Input
A fault level percentage can be set to detect a deviation
above or below the display limits, e.g. If set at 10.0%, then
if an input goes more than 10% above full scale value or
more than 10% below zero value, a fault is detected.
On some ranges the input circuitry may saturate before the
fault level set is reached. In this case an error is detected at
a level below that which is set.
Control actions and control outputs in the event of a fault
are programmable – see below.
Set the value required, between 0.0 and 100.0% in 0.1%
increments.
Default Control Action
Select the default control action required in the event of a
fault:
NONE
–
No default action.
HOLd
–
The controller reverts to Manual mode
when an error is detected. The control
output is held at the value existing
when the error was detected.
O P
–
The controller reverts to Manual mode
when an error is detected and the
control output value changes to the
Default Control Output value following.
Default Control Output
Set the default output value required in the event of a fault,
between 0.0 and 100.0%.
Programmable Filter
This filters the process variable input, i.e. if the input is
stepped, it smooths the transition between steps and may
also be used for some degree of cleaning of noisy inputs.
The filter time represents the time a step in the input takes
to change the displayed process variable from 10 to 90%
of the step.
Set value required, between 0 and 60 in 1 second
increments.
Mains Filter
Set the frequency of the mains supply used (50 or 60Hz).
Return to top of Process Variable Input Page or advance to
next program page.
FdLP–I
10.0
dEFACt
dEF–OP
0.0
OPP
NONE
HOLd
OPP
NONE
HOLd
0
or
dISPLY
SEtUP
PrGFLt
– – Hrt
FILtEr
rSPt
PAGE
…4.5.1
Set Up Process Variable Input Page
4
CONFIGURATION…
all-guide
s.com
Page Header – Set Up Remote Set Point Input.
Remote Set Point Input Type
Select the input type required:
MVLt
–
Millivot (≤2000mV)
MAMP
–
Current
VOLt
–
Voltage
ohM
–
Resistance
tCPL
–
Thermocouple*
rtd
–
Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Remote Set Point Linearizer Type
Select the linearizer type required:
NONE
–
No linearizer
tC-K
–
Type K thermocouple
tC-r
–
Type R thermocouple
tC-S
–
Type S thermocouple
tC-t
–
Type T thermocouple
tC-J
–
Type J thermocouple
tC-L
–
Type L thermocouple
tC-E
–
Type E thermocouple
tC-b
–
Type B thermocouple
tC-N
–
Type N thermocouple
rtd
–
Resistance thermometer
SQrt
–
Square root
3/2
–
x 3/2
5/2
–
x 5/2
Linearizer Units
Select the temperature units required, °C or °F.
Linearizer Full Scale
Set the range maximum temperature in °C or °F as
selected at Linearizer Units above, within the limits detailed
in Table 4.1. If limits are exceeded, LIN–Or (linearizer
overrange) is displayed in the Operating Page – see Table
5.1a of the Operating Guide.
Continue on next page.
4.6
Set Up Remote Set Point Page
Information.
•
This page is omitted if Remote set point is not selected at Second Set Point Type in Set
Points Page – see Section 4.2.
•
Universal Input.
…4
CONFIGURATION
Set Up Remote Set Point Input Page
r–HI–2
rtd
tc–x
or
dEC–Pt
20.0
r–LO–2
4.0
FdLP–2
10.0
20.0
dEFACt
NONE
LOCAL
dF–SPt
bSPd– 2
UP
dN
NONE
dEF–SPt
500.0
or
SEtUP
dISPLY
PAGE
PSN–Fb
0
LIN–LO
NONE
LOCAL
or
dF-SPt
Linearizer Zero
Set the range minimum temperature in °C or °F as selected
at Linearizer Units above, within the limits detailed in Table
4.1.
Remote Set Point Range Full Scale
Set the remote set point range full scale value within the
limits in Table 4.2 – see page 18.
Decimal Point
Set the decimal point position required for both the range
full scale and range zero values.
Input Range Zero
Set the remote set point range zero value required within
the limits in Table 4.2 – see page 18.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
remote set point is driven according to the Broken Sensor
Protection Drive. Select the drive required: NONE for no
drive, UP for upscale drive or dN for downscale drive.
Fault Detection Level Percentage, Remote Set Point
This frame is as detailed in the Fault Detection Level
Percentage, Process Variable Input frame – see page 19.
Set the value required, between 0.0 and 100.0% in 0.1%
increments.
Default Action (Remote Set Point)
Select the default action required in the event of an error:
NONE
–
No default action.
LOCAL
–
The controller reverts to local mode
when an error is detected and the local
set point value is used.
dF–SPt
–
The controller reverts to local mode
when an error is detected and the set
point value changes to the Default Set
Point value below.
Default Set Point
Set the default set point value required in the event of an
error.
Return to top of Remote Set Point Input Page or advance to
the next programming page.
Set Up Position Feedback Page
Information.
•
This page is only present if P–PrOP or bndLSS is selected at Control Type in the Set
Up Control Page – see Fig. 3.1 and Section 4.10. If bndLSS is selected, Position
Feedback Enable must be set to INdCtN to enable access to this page.
•
Millivolt, current, voltage or resistance input.
•
Programmable fault level and actions.
Page Header – Set Up Position Feedback.
Position Feedback Input Type
Select the input type required:
MVLt
–
Millivolt ≤2000mV
MAMP
–
Current
VOLt
–
Voltage
ohM
–
Resistance
Position Feedback Range Full Scale
Set the position feedback range full scale value, within the
limits of Table 4.2 – see page 18.
Decimal Point Position
Set the decimal point position required for both the position
feedback range full scale and range zero values.
Position Feedback Range Zero
Set the position feedback range zero value, within the
limits of Table 4.2 – see page 18.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
remote set point is driven in the direction of the mode
selected.
Select the broken sensor drive required: NONE for no
drive, UP for upscale drive or dN for downscale drive.
Fault Detection Level Percentage, Position Feedback
Input
A fault level percentage can be set to detect a deviation
above or below the display limits, e.g. If set to 10.0%, then
if the position feedback input deviates by more than 10%
above Full Scale value or 10% below zero value, a fault is
detected. Position feedback action in the event of a fault is
programmable, see Default Action.
Set the value required, between 0.0 and 100.0%.
Continued on next page.
Set Up Position Feedback Page
Default Action
Select the default position feedback action required:
NONE
–
No default action
HOLd
–
The controller reverts to Manual mode and
holds the valve position existing when the
fault was detected.
Return to top of Set Up Position Feedback Input Page.
or
Advance to Set Up Display Page.
dEFACt
HOLd
NONE
PAGE
dISPLY
Set Up Display Page
Information.
•
Set up engineering ranges and units.
•
Programmable increments on deviation bargraph.
•
Adjust display brightness.
…4
CONFIGURATION
Page header – Display Page.
Display Full Scale
Set the display value which represents the maximum
process variable input signal, between –9999 and +9999.
Example – For an input range of 4 to 20mA representing a
pressure range of 50 to 250 bar, set 2500. The decimal
point position is set at the next parameter.
Decimal Point Position
Set the required number of decimal places for both the
display full scale and display zero values. In the example
shown above, set the decimal point position to show
increments of 0.1 bar, i.e. 250.0.
Display Zero
Set the display value which represents the minimum
process variable input signal, between –9999 and +9999.
In the example shown above, set 50.0. The decimal point
position is set automatically.
Percentage Increment Per Bar (Bargraph)
This frame sets the percentage deviation from set point
that each bar of the Deviation Bargraph represents – see
Fig. 4.1 in the Operating Guide.
Set the value required, between 1 and 10% of display
span.
Display Units
Select the required display units, dEG C, dEG F, or NONE
to represent the process variable.
Brightness Adjustment
Select the required display brightness between 4 and 10.
Return to top of Display Page or advance to the next
programming page.
all-guide
s.com
Current Proportioning Output Page
Information.
•
This page is only present when C–PrOP is selected at Control Type frame in Set Up
Control Page – see Fig. 3.1 and Section 4.10.
•
Programmable current control output range.
4
CONFIGURATION…
Page header – Current Proportioning Output.
Current Proportioning Output Maximum
Set the maximum analog output value, between 0.0 and
20.0mA in 0.1mA increments.
Current Proportioning Output Minimum
Set the minimum analog output value, between 0.0 and
20.0mA in 0.1mA increments.
Return to top of Current Proportioning Output Page.
or
Advance to Set Up Control Page.
HtCOOL is with Time
Proportioning
Remote Set Point
Tracking Enable
Operating Page
Set Points Page
Local Set Point Adj.
Enable
I
Local Setpoint
High/Low Limits
Remote Set Point
Ratio/Bias Values
Local Set Point
Value
Set Point Tracking
Enable
Set Point Type
Select
Second Set Point
Type
Second Set Point
High/Low Limits
I
I
I
I
I
I
Set Point Type
Selection
I
I
Access Page
Tuning Password
I
Scale Adjust Page
P
I
R
L
I
Ret
Cool Output Page
Output High/Low
Limit
I
Scale Adjust PV
Input Range
High/Low Limits
I
Scale Adjust RSPT
Range High/Low
Limits
I
Scale Adjust
Position Feedback
Range High/Low
Limits
I
Profile Enable
I
Menu/Program
Select
Program Start/End
Levels
Segment Duration
Segment Start/End
Levels
Program Repeat
Hysteresis
I
I
I
I
I
I
Profile Program Page
Refer to Operating Guide
Section 4.15 Page 48
Section 4.14 Page 45
I
These pages are not displayed for all
Control Type selections – see Section
4.10, Control Type frame in the Set
Up Control Page
Section 4.13, Page 44
Sect
R
I
B
D
I
I
Pos
If P
sel
C
Control Page
I Configuration
Password
To
Secti
Section 4.2, Page 6
Section 4.1, Page 4
If H
P
Serial Page
Transmission Rate
I
Controller
Identification
I
Parity
I
Section 3.1, Page 7 of
the Modbus (RTU)
C o m m u n i c a t i o n s
Option,Operating Guide
See
Note. The Serial Page is always displayed on COMMANDER 310
instruments and only displayed on COMMANDER 300 instruments if a
serial board is fitted.
Set Up PV Page
Process Variable
Input Type
I
Linearizer Type
Broken Sensor
Protection Drive
Linearizer
High/Low Temp
Limits
Fault Detection
Level % PV I/P
Default Control
Action
Default Output
Decimal Point
I
I
I
I
I
I
I
Set Up RSPT Page
Linearizer Units
Input High/Low
Limits
I
I
Programmable
Filter
I
Mains Filter
I
Remote Set Point
Input Type
I
Linearizer Type
Linearizer
High/Low Temp
Limits
Fault Detection
Level % RSPT
Default Action
Default Set Point
Decimal Point
I
I
I
I
I
I
Linearizer Units
RSPT Input
High/Low Limits
I
I
Parameter Type
Retrans. High/Low
Limits
Set Up Control Page
Control Type
I
Second Output
Type
Output High/Low
Limits
Power Fail Mode
Auto to Manual
Power Fail Output
Manual to Manual
Power Fail Output
Auto/Manual
Switch Enable
I
I
I
I
Current
Proportioning
Output High/Low
Limits
I
Set Up PFB Page
Position Feedback
Input Type
I
Input High/Low
Limits
Fault Detection
Level % PFB I/P
Default Action
Decimal Point
I
I
I
I
Display Page
Control Action
I
I
Display High/Low
Limits
I
Decimal Point
Bar Graph %
Increment Per Bar
I
I
I
Display Units
Current Output Page
Power Fail
Indication Enable
I
I
Logic Inputs
I
Configured Output
I
Fixed Dual Set
Points
I
trans. O/P Page
Control Mode
I
tion 4.12, Page 44
Section 4.6, Page 20
Section 4.5.1, Page 16 (C300)
Section 4.16, Page 49 (C301)
Section 4.8, Page 24
Section 4.7, Page 22
If P–Prop is not
selected in Set Up
Control Page
If C–Prop is not
selected in Set Up
Control Page
Section 4.9, Page 25
Section 4.10, Page 28
Ratio Value
Bias Value
Deadband Value
sition F-B Page
Regulator Data Page
Regulator Travel
Time
I
Deadband Setting
I
I Position Feedback
Enable
P–Prop is not
lected in Set Up
Control Page
If BndlSS is not
selected in Set Up
Control Page
Set Up Alarms Page
Alarm Identities
I
Alarm Type
Trip Levels
Hysteresis
Rate Alarm Filter
Relay Assignments
Alarm Message
Enable
I
I
I
I
I
I
Alarm Acknowledge
Type
I
Section 4.11, Page 37
ion 4.3.1, Page 12
Section 4.4.2, Page 14
HtCOOL is with
Current
Proportioning
Set Up Control Page
Information.
•
Control types – Current Proportioning, Time Proportioning (and On/Off), Position-
proportioning (motorized valve control with feedback) and Boundless.
•
Heat/cool function can be selected.
•
Programmable power-up control modes and outputs.
•
Reverse and direct control actions.
•
High and low output limits.
…4
CONFIGURATION
Page Header – Set Up Control.
Control Type
Select the control type required:
C–PrOP – current proportioning – see Fig. 4.4.
t–PrOP – time proportioning – see Fig. 4.4.
P–PrOP – position proportioning – motorized valve
with position feedback – see Fig. 4.6.
bNdLSS – boundless – motorized valve without
position feedback. If bNdLSS selected the
self-tune facility is not available and the
Self-tune Page cannot be accessed – see
Fig. 4.7.
Control Mode
Select the control mode required:
SINGLE – normal control mode, used for all
applications except Heat/Cool.
HtCOOL – Heat/Cool control mode – see Fig. 4.5.
Continued on page 30.
SEtUP
CONtrL
C–MOdE
HtCOOL
C–tYPE
C–PrOP
t–PrOP
P–PrOP
P–PrOP
HtCOOL
bNdLSS
SINGLE
SINGLE
bNdLSS
Fig. 4.4 Standard Control Schematic Diagram
P.I.D.
Control
Terms
On/Off
Control
Process
Variable
Set Point
Time Proportioning
Analog Output
Relay or
Digital Output
4 to 20mA
Relay or
Digital Output
COMMANDER 300
Feedback
Process
Set Up Control Page
4
CONFIGURATION…
Fig. 4.5 Heat/Cool Control Schematic Diagram
Fig. 4.6 Position Proportional Control Schematic Diagram
P.I.D.
Control
Terms
Process
Variable
Set Point
COMMANDER 300
Feedback
Time Proportioning
Analog Output
Time Proportioning
Analog Output
Heat Output
Cool Output
Process
P + D
Control
Terms
Process
Variable
Set Point
COMMANDER 300
Open Relay
Close Relay
Boundless
+
Integral
Valve
Feedback
Process
P.I.D.
Control
Terms
Process
Variable
Set Point
COMMANDER 300
Open Relay
Close Relay
Motorized
Valve
Control
Valve
Position Feedback
Feedback
Process
Fig. 4.7 Boundless Control Schematic Diagram
all-guide
s.com
Set Up Control Page
…4
CONFIGURATION
Second Output Type
Select t–PrOP for time proportioning output or C–PrOP
for analog output.
Power Failure Mode
Select the default power failure mode required following a
power interruption or failure:
LASt
–
restart in the same mode existing prior
to power failure.
MANUAL –
restart in Manual mode. (Not applicable
when
boundless
control
type
is
selected).
AUtO
–
restart in Auto mode.
Auto to Manual Power Fail Output
A control output value can be set when the power down
state is AUtO and the power failure mode is MANUAL.
Set the control output value required following a power
failure, between 0.0 and 100.0% in increments of 0.1%.
Note. This setting has no effect if power failure mode
is AUtO.
Manual to Manual Power Fail Output
This is the control output value required when power down
state is MANUAL and power failure mode is MANUAL.
Set the control output value required following a power
failure, between 0.0 and 100.0% in increments of 0.1%, or
LASt.
LASt
–
the
percentage
control
output
present prior to the power failure is
retained.
Auto Power Fail Output
This is the output value required when the power down
state is AUtO and the power failure mode is AUtO.
Set the output value required following a power failure,
between 0.0 and 100.0% in increments of 0.1 %, or AUtO.
If AUtO is selected normal start-up is restored on power
up. If boundless control type is selected, this parameter
must be set to AUtO.
Continued on next page.
PF M OdE
LASt
MANUAL
AUtO
P–PrOP
OPtYPE
t–PrOP
C–PrOP
bNdLSS
SINGLE
MAN OP
LASt
Aut OP
0.0
AUtO
AMA OP
AUtO
MANUAL
LASt
MANUAL
Power
Failure
Mode
Ht-COOL
or
Power
Failure
Mode
Power
Failure
Mode
LASt
Set Up Control Page
4
CONFIGURATION…
Table 4.3 Power-up and Power-down Control Modes
Power Fail Indication Enable
If the indication is enabled, LINE FAILEd is displayed in
the Operating Page following a power failure.
Select YES to enable or no to disable indication.
Failure Message
The following Operating Page Failure messages can be
enabled or disabled – see Section 5.2 of Operating Guide.
F–INPt – process input failure
F–rSPt – remote set point failure
F–POSN – position feedback failure
Select YES to enable or no to disable.
Auto/Manual Switch Enable/Disable
Select on to enable, or OFF to disable.
If HEAtCL is selected at Control Mode, advance to Control
Action (Heat), otherwise advance to Output High Limit.
Continued on next page.
r
e
w
o
P
li
a
F
e
d
o
M
n
o
e
d
o
M
n
w
o
D
r
e
w
o
P
n
o
e
d
o
M
p
U
r
e
w
o
P
n
o
iti
s
o
P
e
v
l
a
V
(
t
u
p
t
u
O
l
o
rt
n
o
C
p
U
r
e
w
o
P
n
o
o
t
u
A
o
t
u
A
o
t
u
A
si
t
u
p
t
u
o
lo
rt
n
o
c
e
h
t
f
o
t
n
e
n
o
p
m
o
c
la
r
g
e
t
n
I
p
u
-r
e
w
o
p
t
a
n
oit
a
r
e
p
o
s
s
elp
m
u
b
e
vig
o
t
t
e
s
e
r
p
.
e
m
a
rf
o
t
u
A
-
o
t-
o
t
u
A
e
h
t
ni
t
e
s
e
ula
v
e
h
t
t
a
la
u
n
a
M
o
t
u
A
si
t
u
p
t
u
o
lo
rt
n
o
c
e
h
t
f
o
t
n
e
n
o
p
m
o
c
la
r
g
e
t
n
I
p
u
-r
e
w
o
p
t
a
n
oit
a
r
e
p
o
s
s
elp
m
u
b
e
vig
o
t
t
e
s
e
r
p
r
o
(
e
m
a
rf
o
t
u
A
-
o
t-la
u
n
a
M
e
h
t
ni
t
e
s
e
ula
v
e
h
t
t
a
)
T
S
A
L
la
u
n
a
M
o
t
u
A
la
u
n
a
M
r
o
(
e
m
a
rf
t
u
p
t
u
O
la
u
n
a
M
-
o
t-
o
t
u
A
ni
t
e
s
e
ula
V
)
T
S
A
L
la
u
n
a
M
la
u
n
a
M
r
o
e
m
a
rf
t
u
p
t
u
O
la
u
n
a
M
-
o
t-la
u
n
a
M
ni
t
e
s
e
ula
V
T
S
A
L
fi(
n
w
o
d
-r
e
w
o
p
o
t
r
oir
p
e
ula
v
t
u
p
t
u
o
)
d
e
tc
ele
s
ts
a
L
o
t
u
A
o
t
u
A
si
t
u
p
t
u
o
lo
rt
n
o
c
e
h
t
f
o
t
n
e
n
o
p
m
o
c
la
r
g
e
t
n
I
p
u
-r
e
w
o
p
t
a
n
oit
a
r
e
p
o
s
s
elp
m
u
b
e
vig
o
t
t
e
s
e
r
p
r
o
(
e
m
a
rf
o
t
u
A
-
o
t-
o
t
u
A
e
h
t
ni
t
e
s
e
ula
v
e
h
t
t
a
)
T
S
A
L
la
u
n
a
M
la
u
n
a
M
r
o
e
m
a
rf
t
u
p
t
u
O
la
u
n
a
M
-
o
t-la
u
n
a
M
ni
t
e
s
e
ula
V
T
S
A
L
fi(
n
w
o
d
-r
e
w
o
p
o
t
r
oir
p
e
ula
v
t
u
p
t
u
o
)
d
e
tc
ele
s
Set Up Control Page
…4
CONFIGURATION
Output High Limit
This limits the high level of the control output value (or
valve position) when in Automatic mode. If the control
output is above this limit when Automatic mode is selected,
the output is allowed to stay at its current level but is not
allowed to go any higher. Once the control output returns
to, or below, this limit the limit then applies. When the
controller is in Manual mode the output limits do not apply.
Select the output high limit value (or valve position)
required, between 0.0 and 100.0% in 0.1 increments.
Output Low Limit
This limits the low level of the control output value (or valve
position) when in Automatic mode. If the control output is
below this limit when Automatic mode is selected, the
output is allowed to stay at its current level but is not
allowed to go any lower. Once the control output returns to,
or above, this limit the limit then applies. When the
controller is in Manual mode the output limits do not apply.
Select the output low limit value (or valve position)
required, between 0.0 and 100.0% in 0.1 increments.
Control Action
Select the action for the P.I.D. control output:
dir
–
direct acting
rEV
–
reverse acting.
OP–HI
100.0
HEAtCL
OP–LO
0.0
HEAtCL
ACtION
rEV
0
100
%
Output
Reverse Acting
PV
Output
decreases
as process
variable
increases
Eng. Range
0
100
Direct Acting
PV
Output
increases
as process
variable
increases
%
Output
Eng. Range
Continued on next page.
If HEAtCL was selected at Control Mode, advance to
Control Action (Heat), otherwise advance to Logic Input
Type 1.
Control Action (Heat)
Select the action for the heat and P.I.D. control outputs:
dir
–
direct acting
rEV
–
reverse acting.
Control Action (Cool)
Select the action for the cool control output:
dir
–
direct acting
rEV
–
reverse acting.
Continued on next page.
4
CONFIGURATION…
…4.10
Set Up Control Page
0
100
%
Output
Reverse Acting
PV
Output
decreases
as process
variable
increases
Eng. Range
0
100
Direct Acting
PV
Output
increases
as process
variable
increases
%
Output
Eng. Range
ACtN–c
dir
ACtN–h
rEV
HEAtCL
Fig. 4.8 Heat/Cool Control Actions
High O/P
Limit
(Cool)
P.I.D. Output
Cool Output
0%
100%
100%
0%
Heat Output
High O/P
Limit
(Heat)
Heat Output Action – Direct or Reverse
Cool Output Action – Direct
P.I.D. Output
Cool Output
0%
100%
100%
0%
High O/P
Limit
(Heat)
Low O/P
Limit
(Cool)
Heat Output
Heat Output Action – Direct or Reverse
Cool Output Action – Reverse
Set Up Control Page
…4
CONFIGURATION
Heat Output High Limit
This limits the high level of the Heat control output value when
in Automatic mode. If the control output is above this limit
when Automatic mode is selected, the output is allowed to
stay at its current level but is not allowed to go any higher.
Once the control output returns to, or below, this limit the limit
then applies. When the controller is in Manual mode the
output limits do not apply. Select the heat output high limit
value required, between 0.0 and 100.0% in 0.1 increments.
Cool Output High/Low Limit
This limits the high or low level of the Cool control output
when in Automatic mode, depending on the Control Action
(Cool) frame setting (rEV is the low and dIr is the high
setting). If the control output exceeds this limit when
Automatic mode is selected, the output remains at its current
level but is not allowed to go any further away from the limit.
Once the control output returns to, or within, this limit, the limit
then applies. When the controller is in Manual mode the
output limits do not apply. Select the Cool output high (low)
limit required, between 0.0 and 100.0% in 0.1 increments.
Continued on the next page.
Ht–HI
I00.0
CL–HI
100.0
SINGLE
P-PrOP
bNdLSS
all-guide
s.com
Set Up Control Page
4
CONFIGURATION…
Option Board Disable (not applicable on
COMMANDER 310)
If the Option board fails or is removed, press
to set OPtION to OFF. Once set to OFF
this parameter is omitted.
Logic Input Type 1
Refer to Section 4, Figs 4.18 and 4.19 in the Installation
Guide.
Select the logic input type for input 1 (must not be the same
as any other logic input type):
NONE
–
no function available
AUtMAN
–
auto/manual
LOCrE M –
local/remote (dual)
ACK
–
remote alarm acknowledge
F-SPt
–
fixed dual set point
P-Strt
–
program start/hold function
P-rSEt
–
program reset function
P-SKIP
–
segment skip function
If AUtMAN is set then the output reverts to the value set in
Configured Output below, unless configured output is set to
LASt.
If F–SPt is selected two fixed set points are available –
see Fixed Dual Set Point 1 and Fixed Dual Set Point 2 below.
If F–SPt is selected, the adjustable dual set point facility
is disabled and the dual set point is the value of one of the
two fixed set points.
Dual set point must be selected (in Set Points Page –
Section 4.2) in order to enable the use of the fixed set
points.
If dUAL is selected at Set Point Type Selection frame in Set
Points Page the Local/Remote selection becomes Local/
Dual selection.
Logic Input Type 2
Refer to Section 4, Figs. 4.18 and 4.19 in the Installation
Guide.
Select the logic input type for input 2 (must not be the same
as any other logic input type). The selections and their
actions are as for Logic Input 1 above – refer to Logic Input
1 frame for details.
Continued on next page.
Set Up Control Page
…4
CONFIGURATION
Logic Input Type 3 (not available on COMMANDER 310)
Refer to Section 4, Figs. 4.18 and 4.19 in the Installation
Guide.
Select the logic input type for input 3 (must not be the same
as any other logic input type). The selections and their
actions are as for Logic Input 1 – refer to Logic Input 1
frame for details.
Logic Input Type 4 (not available on COMMANDER 310)
Refer to Section 4, Figs. 4.18 and 4.19 in the Installation
Guide.
Select the logic input type for input 4 (must not be the same
as any other logic input type). The selections and their
actions are as for Logic Input 1 – refer to Logic Input 1
frame for details.
Configured Output
Select the configured output, between 0.0 and 100.0% in
0.1% increments, or LASt.
If AUtMAN is selected for any of the logic inputs above, the
manual control output equals the Configured Output,
unless the configured output is LASt.
LASt
–
last auto output, i.e. the manual output
tracks the automatic output. Found
below 0%.
Fixed Dual Set Point 1
If the selection in any of the four logic inputs is F–SPt a
fixed set point may be set. Set the fixed set point required.
Fixed Dual Set Point 2
If the selection in any of the four logic inputs is F–SPt a
fixed set point may be set. Set the fixed set point value
required.
Return to the top of Set Up Control Page or advance to the
next programming page.
LOGIC3
NONE
LOGIC4
NONE
C–OUt
LASt
F–SP–I
800
SEtUP
ALArMS
F–SP–2
200
Set Up Alarms Page
Information.
•
Ten alarms – identified A to K.
•
Three operator acknowledge options.
•
Global alarm acknowledgment by digital input, alarm, logic equation result or real time
event (if option fitted).
•
High/low process alarms.
•
High/low output alarms.
•
High/low deviation alarms.
•
Fast/slow rate of change of process variable alarms.
•
Adjustable hysteresis value to prevent oscillation of alarm state.
4
CONFIGURATION
High Output
Low Output
Control
Output
Trip Point
Alarm On
Alarm Off
Alarm On
Alarm Off
Hysteresis
Hysteresis
Fig. 4.10 High and Low Output with Hysteresis
High
Process
Low
Process
Process Variable
Hysteresis
Trip Point
Alarm On
Alarm Off
Alarm On
Alarm Off
Hysteresis
Fig. 4.9 High and Low Process with Hysteresis
Set Up Alarms Page
…4
CONFIGURATION
Fig. 4.11 High and Low Deviation with Hysteresis
Process
Variable
Hysteresis Value
High Deviation
Negative Trip Value
Alarm Off
Alarm On
Control
Set Point
High Deviation
(Negative Trip)
Process
Variable
Hysteresis Value
High Deviation
Positive Trip
Value
Alarm Off
Alarm On
Control
Set Point
High Deviation
(Positive Trip)
Process
Variable
Hysteresis Value
Low Deviation
Positive Trip Value
Alarm Off
Alarm On
Control
Set Point
Low Deviation
(Positive Trip)
Process
Variable
Hysteresis Value
Low
Deviation
Negative
Trip Value
Alarm Off
Alarm On
Control
Set Point
Low Deviation
(Negative Trip)
A – High Deviation (Positive Trip) with Hysteresis
B – High Deviation (Negative Trip) with Hysteresis
C – Low Deviation (Positive Trip) with Hysteresis
D – Low Deviation (Negative Trip) with Hysteresis
Set Up Alarms Page
Fig. 4.13 Fast Rate Alarms with Hysteresis
Fig. 4.12 Slow Rate Alarms with Hysteresis
4
CONFIGURATION…
10.1
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
Alarm On
Alarm Off
Falling Slow Rate
Rising Slow Rate
1 hour
9.5
T
Alarm On
Alarm Off
1 hour
10.1
1 hour
9.5
1 hour
T
T
T
T = 10.81 +
x 2
1800
10
T = 382 seconds
The maximum time it takes to detect an alarm
condition is present (T), in seconds, is
calculated as follows:
T = 10.81 +
x 2
The time it takes for the alarm state to be
cleared once the alarm condition has been
removed is also equal to T.
1800
Trip Value
Alarm On
Alarm Off
Falling Fast Rate
Alarm On
Alarm Off
Rising Fast Rate
10.1
1 hour
1 hour
9.5
1 hour
9.5
T
T
1 hour
10.1
T
T
Examples shown are for a trip value of 10%/hour on a PV engineering range of 0.0 to 100.0
T = 10.81 +
x 2
1800
10
T = 382 seconds
The maximum time it takes to detect an alarm
condition is present (T), in seconds, is
calculated as follows:
T = 10.81 +
x 2
The time it takes for the alarm state to be
cleared once the alarm condition has been
removed is also equal to T.
1800
Trip Value
all-guide
s.com
Set Up Alarms Page
Page Header – Set Up Alarms.
Alarm Identities
Up to ten alarms (A to K but not I) can be programmed.
Each alarm can be assigned an Alarm Type, a Trip Level
and a Hysteresis setting. Alarm A is the highest priority
and K the lowest.
Note.
The alarm status l.e.d. indicators are:
A1
–
alarms A to E
A2
–
alarms F to K.
Select the Alarm identity.
Alarm Type
An alarm type can be assigned to the alarm identity selected
above – Refer to Figs. 4.9 to 4.13.
Select the alarm type:
NONE
–
no alarm function
HPrC
–
high process
LPrC
–
low process
HdEV
–
high deviation
LdEV
–
low deviation
HOUt
–
high output
LOUt
–
low output
FrtE
–
fast rate
(rate of change of process variable)
SrtE
–
slow rate
(rate of change of process variable)
MOdE
–
mode alarm
PEVt
–
program event
SEVt
–
segment event
(a)
Continued on next page.
(b) From More Alarms to be Programmed frame.
…4
CONFIGURATION
SEtUP
–
ALArMS
ALArM
tYPE
––––
From page 41
Set Up Alarms Page
4
CONFIGURATION…
trIP
––––
– – –
YES
MOrE
HYSt
– – – –
More
alarms
no
Trip Level
Set the trip value required for the alarm selected above.
The following are displayed in engineering units:
HPrC, LPrC, HdEV and LdEU.
HdEV and LdEV alarms have both positive and negative
trip points. Refer to Fig. 4.11.
The following are displayed as percentages:
HOUt and LOUt.
The following are displayed as a percentage of span per
hour between ±0.5 and ±500%:
FrtE and SrtE.
The following are displayed as event numbers:
PEVt (1 to 9) and SEVt (1 to 30).
If the Alarm Type is set to MOdE the displayed characters
are alpha, not numeric. The following codes are
selectable:
AUtO
–
Automatic
MANUAL
–
Manual
L–SPt
–
Local set point
r–SPt
–
Remote set point – only selectable if
Second set point type is Remote set
point
dSPt
–
Dual set point– only selectable if
Second set point type is Dual set point
PVFAIL
–
process variable failure
rSFAIL
–
Remote set point failure
PNFAIL
–
position feedback failure
INFAIL
–
any input failure
P–HOLd
–
alarm activated when program is on
Hold (Profile only)
If AUtO, MANUAL, L–SPt, r–SPt, or d–SPt is selected
and an attempt is made to use that facility (Automatic,
Manual, Local set point, Remote set point, or Dual set
point) the alarm is activated.
Hysteresis
The hysteresis is operational when the alarm is active.
Set the hysteresis value required (in engineering units),
between display full scale and zero, or percentage rate set
on rate alarms, in 0.1% increments. The alarm is activated
at the trip level but is only turned off after the alarm variable
has moved into the safe region by an amount equal to the
hysteresis value. Refer to Figs. 4.9 to 4.13.
More Alarms to be Programmed?
If there are, select YES otherwise select no.
Return to Alarm Identities frame, or advance to the next
parameter.
Continued on next page
Set Up Alarms Page
…4
CONFIGURATION
rELAY2
t–PrOP
– –
– – – – – –
– – – – – –
rELAYI
r–FLtr
POS
rI–ACt
POS
r2–ACt
P–PrOP
bndLSS,
or
second
output
t–PrOP
– – – – – –
rELAY3
POS
r3–ACt
Rate Alarm Filter
The process variable input can be filtered before its rate of
change is calculated to activate any fast or slow rate
alarms. The filter time represents the time a step in the
input takes to change the input to the rate alarm from 10 to
90% of the step. Set value required, between 0 and 60 in
1 second increments.
Alarm Relay 1 Assignment
Up to 6 of the 10 alarms can be assigned to alarm relay 1,
using a logic expression of up to 12 characters. (r = logic
OR, n = logic AND, () are brackets and W is the
terminator).
Select the next character in the expression.
Press
to store the character and return to select the
next character or press
to advance to the next frame.
Relay 1 Action
Select POS for the relay to be energised when the logic
expression is satisfied. Select NEG for the relay to be de-
energised when the logic expression is satisfied.
Alarm Relay 2 Assignment
Up to 6 of the 10 alarms can be assigned to alarm relay 2,
using a logic expression of up to 12 characters. (r = logic
OR, n = logic AND, () are brackets and W is the
terminator).
Select the next character in the expression.
Press
to store the character and return to select the
next character or press
to advance to the next frame.
Relay 2 Action
Select POS for the relay to be energised when the logic
expression is satisfied. Select NEG for the relay to be de-
energised when the logic expression is satisfied.
Alarm Relay 3 Assignment
Up to 6 of the 10 alarms can be assigned to alarm relay 3,
using a logic expression of up to 12 characters. (r = logic
OR, n = logic AND, () are brackets and W is the
terminator). Select the next character in the expression.
Press
to store the character and return to select the
next character or press
to advance to the next frame.
Relay 3 Action
Select POS for the relay to be energised when the logic
expression is satisfied. Select NEG for the relay to be de-
energised when the logic expression is satisfied.
Continued on next page.
Set Up Alarms Page
LAtCH –
if the cause of the alarm no longer exists,
the alarm state remains until it has been
acknowledged.
Return to top of Set Up Alarms Page or advance to
next programming page.
4
CONFIGURATION…
YES
AL–MSGE
rELAY4
– – – – – –
POS
r4–ACt
NONE
OUtPUt
or
OUtPUt
COOL
rEtrAN
ACKNLG
Alarm
Relay
4
Assignment
(not
available
on
COMMANDER 310)
Up to 6 of the 10 alarms can be assigned to alarm relay 4,
using a logic expression of up to 12 characters. (r = logic
OR, n = logic AND, () are brackets and W is the
terminator).
Select the next character in the expression.
Press
to store the character and return to select the
next character or press
to advance to the next frame.
Relay 4 Action (not available on COMMANDER 310)
Select POS for the relay to be energised when the logic
expression is satisfied. Select NEG for the relay to be de-
energised when the logic expression is satisfied.
Alarm Message Enable
Set YES to enable, or no to disable the display of alarm
messages in the Operating Page.
Alarm Acknowledge Type
Alarms may be acknowledged while they are displayed.
Select the alarm acknowledge type:
NONE
– no acknowledge facility.
norMAL – If the cause of the alarm no longer exists,
the alarm state clears, but the display
remains until alarm is acknowledged.
e
s
u
a
c
m
r
a
l
A
.
w
o
n
k
c
A
y
a
l
p
s
i
D
D
E
L
e
t
a
t
S
m
r
a
l
A
t
n
e
s
e
r
P
–
g
nih
s
al
F
g
nih
s
al
F
e
vitc
A
t
n
e
s
e
r
P
s
e
Y
–
y
d
a
e
t
S
e
vitc
A
t
n
e
s
e
r
p
t
o
N
–
–
ff
O
e
vitc
a
n
I
t
n
e
s
e
r
P
–
g
nih
s
al
F
g
nih
s
al
F
e
vitc
A
t
n
e
s
e
r
p
t
o
N
–
g
nih
s
al
F
ff
O
e
vitc
a
n
I
t
n
e
s
e
r
p
t
o
N
s
e
Y
–
ff
O
e
vitc
a
n
I
e
s
u
a
c
m
r
a
l
A
.
w
o
n
k
c
A
y
a
l
p
s
i
D
D
E
L
e
t
a
t
S
m
r
a
l
A
t
n
e
s
e
r
P
–
g
nih
s
al
F
g
nih
s
al
F
e
vitc
A
t
n
e
s
e
r
P
s
e
Y
–
y
d
a
e
t
S
e
vitc
A
t
n
e
s
e
r
p
t
o
N
–
–
ff
O
e
vitc
a
n
I
t
n
e
s
e
r
P
–
g
nih
s
al
F
g
nih
s
al
F
e
vitc
A
t
n
e
s
e
r
p
t
o
N
–
g
nih
s
al
F
g
nih
s
al
F
e
vitc
A
t
n
e
s
e
r
p
t
o
N
s
e
Y
–
ff
O
e
vitc
a
n
I
Retransmission Output Page
Information.
•
Retransmission of process variable, set point, control output or position feedback input.
•
Programmable current output range.
•
Retransmission output can be used for cool output in heat/cool applications.
…4
CONFIGURATION
Page Header – Retransmisson Output.
Parameter Type
Select the parameter type to be re-transmitted, PV
(process variable input), SPt (set point), OUt (output) or
PFb (position feedback).
Retransmission Maximum
Set the maximum retransmission value, between 0.0mA
and 20.0mA in 0.1mA increments.
Retransmission Minimum
Set the minimum retransmission value, between 0.0mA
and 20.0mA in 0.1mA increments.
Return to top of Retransmission Output Page
or
Advance to Scale Adjustment Page.
Page Header – Cool Output Page
Cool Output Maximum
Set the maximum value for the cool output, between
0.0mA and 20.0mA in 0.1mA increments.
Cool Output Minimum
Set the minimum value for the cool output, between 0.0mA
and 20.0mA in 0.1mA increments.
Return to top of Cool Output Page
or
advance to Scale Adjustment Page.
4.13
Cool Output Page
This page is only present if HtCOOL is selected at Control Mode and C-ProP is selected at
Second Output Type in the Set Up Control Page – see Fig. 3.1 and Section 4.10.
OUtPUt
SCALE
20.0
COOL–HI
COOL
4.0
COOL–LO
AdJUSt
all-guide
s.com
Scale Adjustment Page
Information.
•
Process variable, Remote set point and position feedback inputs do not require
recalibrating when the input type or range is changed.
•
Scale Adjustment Reset – removes any previously programmed offset or scale
adjustment settings.
•
System offset errors – can be removed using Offset Adjustment.
•
System scale errors – can be removed using Span Adjustment.
•
Offset/Span Adjustment – can be used to perform spot calibration.
Switch off the power supply. Connect accurate signal sources, suitable for simulation over the
entire input ranges, in place of the process variable signal connections (terminals 10, 11, 12),
remote set point signal connections (terminals 7, 8 and 9) and position feedback connections
(terminals 4, 5 and 6). For thermocouple inputs, connect the millivolt source using appropriate
compensating cable – see Section 4.6.1 of the Installation Guide. For 2-lead resistance
thermometers the resistance box may be connected at the sensor end of the leads or the lead
resistance must be added to the calibration values.
As a general rule, spot calibration values should be:
< 50% of range span value when using Offset Adjustment parameters.
> 50% of range span value when using Span Adjustment parameters.
4
CONFIGURATION…
Page header – Scale Adjustment
Process Variable Scale Adjustment Reset
Set YES and press
to reset the process variable offset
and span values to their nominal values. dONE is
displayed to indicate that these parameters have been
reset.
Process Variable Offset Adjustment
Electrical and resistance thermometer inputs:
Apply the correct input for the spot calibration required.
For RTD inputs, use resistance values obtained from
standard tables.
Thermocouple Inputs:
Measure the ambient temperature at the output terminals
of the signal source (calibrator). From thermocouple tables
obtain the millivolt equivalent of this temperature (a) and
that for the spot calibration temperature (b). Subtract (a)
from (b) and set the signal source to the resultant value.
(The voltage is negative if the spot calibration temperature
is below the measured ambient temperature).
Note. The displayed units are engineering units.
Set the value required. The decimal point position is set
automatically.
Example – If the display range is 50 to 250.0 and a spot
calibration is required at 100.0 and 225, inject a signal
equivalent to 100 and set the display to 100.0.
Continued on next page.
SCALE
PV–rSt
AdJUSt
no
––––
PV–OFS
Scale Adjustment Page
Process Variable Span Adjustment
Proceed as for Process Variable Offset Adjustment and
apply the correct input for the spot calibration required.
The displayed units are engineering units.
Set the value required. The decimal point position is set
automatically.
For the Example above inject a signal equivalent to 225.0
and set the display to 225.0.
Advance to Position Feedback Scale Adjustment Reset
frame (instruments where remote set point is not selected
– see Set Point Selection frame in Set Points Page) or
advance to next frame (instruments with remote set point
selected).
Remote Set Point Scale Adjustment Reset
The next three parameters are only included if the Remote
set point facility is selected.
Set to YES and press
to reset the Remote set point
offset and span adjustments to their nominal values. dONE
is displayed to indicate that these parameters have been
reset.
Remote Set Point Offset Adjustment
Proceed as for Process Variable Offset Adjustment frame
and apply the correct input for the spot calibration required.
The displayed units are engineering units as set in Set Up
Remote Set Point Page – see Section 4.6.
Set the value required. The decimal point position is set
automatically.
Example – If the remote set point range (see Section 4.6)
is 50.0 to 250.0 and a spot calibration is required at 100.0
and 225, inject a signal equivalent to 100 and set the
display to 100.0.
Remote Set Point Span Adjustment
Proceed as for Process Variable Span Adjustment frame
and apply the correct input for the spot calibration required.
Ratio and bias settings are ignored. The displayed units
are engineering units as set in Set Up Remote Set Point Page
– see Section 4.6.
For the example above, inject a signal equivalent to 225
and set the display to 225.0.
Continued on next page.
no
rS–rSt
rS–SPN
––––
PV–SPN
rS–OFS
––––
––––
Scale Adjustment Page
The next three parameters are only included if the position feedback facility is selected.
Position Feedback Scale Adjustment Reset
Set to YES and press
to reset the position feedback
offset and span adjustments to their nominal value. dONE
is displayed to indicate that these parameters have been
reset.
Position Feedback Offset Adjustment
Proceed as for Process Variable Offset Adjustment frame
and apply the correct input for the spot calibration
required. Ratio and bias settings are ignored.
Set the value required. The decimal point position is set
automatically. For resistance inputs use the external
connections to drive the valve to the fully closed position.
Adjust
or
to bring the value displayed to that set in
Position Feedback Range Zero frame in the Set Up Position
Feedback Page. If this value cannot be reached, adjust the
value in Position Feedback Range Zero frame to bring it
within the offset bandwidth of ±10%.
Position Feedback Span Adjustment
Proceed as for Process Variable Span Adjustment frame
and apply the correct input for the spot calibration
required. Ratio and bias settings are ignored.
Set the value required. The decimal point position is set
automatically. For resistance inputs use the external
connections to drive the valve to the fully open position.
Adjust
or
to bring the value displayed to that set in
Position Feedback Range Full Scale frame in the Set Up
Position Feedback Page. If this value cannot be reached,
adjust the value in Position Feedback Range Full Scale
frame to bring it within the span bandwidth of ±10%.
Return to the top of the Scale Adjustment Page.
Tune Password – protects the control settings and prevents unauthorized use of self-
tuning.
•
Configuration Password – protects the controller configuration setup.
…4
CONFIGURATION
Page Header – Access Page.
Configuration Password
The configuration password enables access to all
programming pages (Security Level 2).
Set the required password, between 0 and 1999.
Tuning Password
The tuning password enables access to the Self-tune,
Control, Profile States and Profile Operating Pages in
addition to the Operating Page (Security Level 1).
Set the required password, between 0 and 1999.
Return to top of Access Page
or
return to Operating Page – see Section 5.2 of Operating
Guide.
Set Up Process Variable Input Page (COMMANDER 301 only)
Information.
•
This information is only for the COMMANDER 301 when the custom linearizer function
is used. For normal input setting up, refer to Section 4.5.
•
Up to 20 breakpoint custom linearizer.
•
Cold junction compensation for thermocouple inputs.
Page Header – Set Up Process Variable Input.
Process Variable Input Type
Select the input type required:
MU.Lt
–
Millivolt (≤2000 mV)
MAMP
–
Current
V.OLt
–
Voltage
ohM
–
Resistance
tCPL
–
Thermocouple*
rtd
–
Resistance thermometer
*For thermocouple applications using an external fixed
cold junction, select millivolt input type.
Linearizer Type
Select the custom linearizer:
CUSt
–
Custom linearizer
Linearizer Units
If thermocouple or RTD was selected for Process Variable
Input Type, select the temperature units required, °C or °F.
Continued on next page.
all-guide
s.com
Set Up Process Variable Input Page (COMMANDER 301 only)
Electrical Decimal Point
Enter the number of decimal point positions required for
the electrical input range (0 to 2).
Engineering Decimal Point
Enter the number of decimal point positions required for
the engineering temperature range (0 to 3).
Break Point Selection
Select the break point to be set up and press
to move
to Electrical Break Point.
Note. The engineering range (display range) is set
automatically and cannot be adjusted.
Electrical Break Point
Enter the value in electrical units (Millivolts, Milliamps,
Ohms or Volts), for the break point selected above. It is not
necessary to enter all 20 break points. The instrument
ignores any break point that has an electrical value lower
than the previous one and all the break points which follow
it.
Engineering Break Point
Enter the value in engineering units for the break point
selected above.
Press
to return to the break point selection frame. Note
that the break point selected will automatically be
increased to the next one when this is done.
Continued on the next page.
1
1
ENG–dP
ELECdP
ELECbP
0.0
ENG–bP
0.0
xx
brKPNt
750°C
1 2
3 4
5
6
7
8
9
Electrical
Range
Engineering Range
300°C
Electrical Break Points
Engineering
Break Points
4.0 mA
20.0 mA
Set Up Process Variable Input Page (COMMANDER 301 only)
Cold Junction
If a thermocouple input was selected:
CJ1
Enter the cold junction compensation offset at 25°C/
77°F in microVolts.
This feature allows automatic
temperature compensation of
thermocouple inputs.
It
is
assumed
that
the
thermocouple is referenced to
0 Millivolts at 0°C (32°F).
CJ2 Enter the cold junction compensation offset at
50°C122°F in microVolts.
This feature allows automatic
temperature compensation of
thermocouple inputs.
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
process variable is driven in the direction of the mode
selected.
Select the broken sensor drive required:
NONE
–
No drive
UP
–
Upscale drive
dN
–
Downscale drive.
Continued on the next page.
bSPd
UP
dN
NONE
CJ 50C
xxxx
xxxx
CJ 25C
VOLt
ohM
MAMP
MVLt
For Thermocouple Inputs
All Other
Input Types
0
50°C
25°C
0
50°C
25°C
– – Hrt
FdLP–I
10.0
dEFACt
dEF–OP
0.0
OPP
NONE
HOLd
OPP
NONE
HOLd
0
or
dISPLY
SEtUP
PrOFLt
FILtEr
rSPt
PAGE
…4
CONFIGURATION
…4.16
Set Up Process Variable Input Page (COMMANDER 301 only)
Fault Detection Level Percentage, Process Variable
Input
A fault level percentage can be set to detect a deviation
above or below the display limits, e.g. If set at 10.0%, then
if an input goes more than 10% above full scale value or
more than 10% below zero value, a fault is detected.
On some ranges the input circuitry may saturate before the
fault level set is reached. In this case an error is detected at
a level below that which is set.
Control actions and control outputs in the event of a fault
are programmable – see below.
Set the value required, between 0.0 and 100.0% in 0.1%
increments.
Default Control Action
Select the default control action required in the event of a
fault:
NONE
–
No default action.
HOLd
–
The controller reverts to Manual mode
when an error is detected. The control
output is held at the value existing
when the error was detected.
O P
–
The controller reverts to Manual mode
when an error is detected and the control output value
changes to the Default Control Output value following.
Default Control Output
Set the default output value required in the event of a fault,
between 0.0 and 100.0%.
Programmable Filter
This filters the process variable input, i.e. if the input is
stepped, it smooths the transition between steps and may
also be used for some degree of cleaning of noisy inputs.
The filter time represents the time a step in the input takes
to change the displayed process variable from 10 to 90%
of the step.
Set value required, between 0 and 60 in 1 second
increments.
Mains Filter
Set the frequency of the mains supply being used (50 or
60Hz).
Return to top of Process Variable Input Page or advance to
next program page.
PRODUCTS & CUSTOMER SUPPORT
A Comprehensive Product Range
Analytical Instrumentation
•
Transmitters
On-line pH, conductivity, and dissolved oxygen
transmitters and associated sensing systems.
•
Sensors
pH, redox, selective ion, conductivity and
dissolved oxygen.
•
Laboratory Instrumentation
pH and dissolved oxygen meters and associated
sensors.
•
Water Analyzers
For water quality monitoring in environmental,
power
generation
and
general
industrial
applications including: pH, conductivity, ammonia,
nitrate, phosphate, silica, sodium, chloride,
fluoride, dissolved oxygen and hydrazine.
•
Gas Analyzers
Zirconia,
paramagnetic,
infrared,
thermal
conductivity.
Controllers & Recorders
•
Controllers
Digital display, electronic, pneumatic. Discrete
single-loop and multi-loop controllers which can
be linked to a common display station, process
computer or personal computer.
•
Recorders
Circular and strip-chart types (single and multi-
point) for temperature, pressure, flow and many
other process measurements.
Electronic Transmitters
•
Smart & Analog Transmitters
For draft, differential, gauge and absolute
pressure measurement. Also, liquid level and
temperature.
•
I to P Converters and Field Indicators
Flow Metering
•
Magnetic Flowmeters
Electromagnetic, insertion type probes and
watermeters.
•
Turbine Flowmeters
•
Wedge Flow Elements
•
Mass Flow Meters
Transmitters, sensors, controllers and batch/
display units.
Level Control
•
Submersible, Capacitance & Conductivity.
Pneumatic Instrumentation
•
Transmitters
•
Indicating Controllers
•
Recording Controllers
Customer Support
ABB Instrumentation provides a comprehensive after
sales service via a Worldwide Service Organization.
Contact one of the following offices for details on your
nearest Service and Repair Centre.
United Kingdom
ABB Instrumentation Limited
Tel: +44 (0)1480 475321
Fax: +44 (0)1480 470787
United States of America
ABB Automation Inc.
Instrumentation Division
Tel: +1 215-674-6000
Fax: +1 215-674-7183
Italy
ABB Instrumentation SpA
Tel: +39 (0) 344 58111
Fax: +39 (0) 344 58278
Client Warranty
Prior to installation, the equipment referred to in
this manual must be stored in a clean, dry
environment, in accordance with the Company's
published specification. Periodic checks must be
made on the equipment's condition.
In the event of a failure under warranty, the
following documentation must be provided as
substantiation:
1. A listing evidencing process operation and
alarm logs at time of failure.
2. Copies of operating and maintenance records
relating to the alleged faulty unit.
The Company's policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
© ABB 1999
Printed in UK (10.99)
ABB Instrumentation Ltd
St. Neots
Cambs.
England, PE19 3EU
Tel: +44 (0) 1480 475321
Fax: +44 (0) 1480 217948
ABB Automation Inc.
Instrumentation Division
125 E. County Line Road
Warminster, PA 18974 USA
Tel: +1 215-674-6000
Fax: +1 215-674-7183
ABB Instrumentation SpA
22016 Lenno
Como
Italy
Tel: +39 (0) 344 58111
Fax: +39 (0) 344 58278
all-guide
s.com