Goodman ACVC9 Copyright ©2009-2010 Goodman Manufacturing Company, L.P.

RT6612021 Rev. 4 December 2010 This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures performed by an unqualified person. ACVC9/AMVC95 GCVC9/GMVC95 90%-95% Gas Furnace Units • Refer to Service Manual RS6200004 for installation, operation, and t

The model and manufacturing number are used for positive identification of component parts used in manufacturing.

Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Installation and repair of this unit should be p

The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please

use these numbers when requesting service or parts information. AMVC950453BXAA AMVC950704CXAA AMVC950905CXAA AMVC950905DXAA AMVC951155DXAA ACVC90704CXAA ACVC90905DXAA AMVC950453BXAB AMVC950704CXAB AMVC950905DXAB AMVC951155DXAB ACVC90704CXAB ACVC90905DXAB ACVC950714CXAA ACVC950915DXAA The United States Environmen

installation (1 or 2 pipes). The optional Combustion Air

Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC. 2. Line voltage wiring can enter through the right or left side of the furnace. Low voltage wiring can enter through the right or left side of furnace. 3. Conversion kits for propane gas and high altitude natural and propane gas operation are available. See High Alti- tude Derate chart for deta

Goodman ACVC9 quired due to the natural reduction in the density of both the

gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the specified altitude range. High altitude kits are purchased according to the installa- tion altitude and usage of either natural or propane gas. Refer to the chart above for a tabular listing of appropriate altitude ranges and corresponding manufacturer’s h

Two-Stage Gas Valve

2 Gas Line Entrance (Alternate) 3 Pressure Switch(es) 4 Gas Manifold 5 Combustion Air Intake Connection 6 Hot Surface Igniter 7 Rollout Limit 8 Burners 9 Flame Sensor 10 Flue Pipe Connection 11 Flue Pipe 12 Primary Limit 13 Gas Line Entrance 14 Flue Pipe Connection (Alternate) 15 Rubber Elbow 16 Two-Speed Induced Draft Blower 17 Electrical Connection Inlets (Alternat

Goodman ACVC9 NOTE: Airflow area will be reduced by approximately 18% if duct flanges are not unfolded. This could cause performance issues and noise issues.

AIR DISCHARGE AIR DISCHARGE LOW VOLTAGE ELECTRICAL HOLE HIGH VOLTAGE ELECTRICAL HOLE SIDE CUT-OUT LEFT SIDE VIEW SIDE CUT-OUT HIGH VOLTAGE ELECTRICAL HOLE LOW VOLTAGE ELECTRICAL HOLE RIGHT SIDE DRAIN LINE HOLES STANDARD GAS SUPPLY HOLE DRAIN TRAP 19 3/4 AIR INTAKE PIPE 2" PVC

Goodman Furnace Owners Instructions: