Hoffer Flow Controls CAT3 Operation & User’s Manual

Specifications

Brand: Hoffer Flow Controls
Category: Transmitter
Model: CAT3 (Operation & User’s Manual)
File Type: PDF
File Size: —
Pages: 36

Read Online

Read the Hoffer Flow Controls CAT3 Operation & User’s Manual online using the built-in PDF viewer.

Text of the manual

www.hofferflow.com E-mail: [email protected]

107 Kitty Hawk Lane, P.O. Box 2145, Elizabeth City, NC 27906-2145 800-628-4584 252-331-1997 FAX 252-331-2886 April 2009 Model: CAT3 DC or AC Powered Microprocessor Controlled Transmitter USER’S MANUAL HP-312 July 2019 107 Kitty Hawk Lane ●P.O. Box 2145 ●Elizabeth City, NC 27909 1-800-628-4584 ● (252) 331-1997 ● Fax (252) 331-2886 www.hofferflow.com email: [email protected]

HOFFER FLOW CONTROLS, INC. makes no warranty of any kind with regard to

this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. This manual has been provided as an aid in installing, connecting, calibrating, operating, and servicing this unit. Every precaution for accuracy has been taken in the preparation of this manual; however, HOFFER FLOW CONTROLS, INC. neither assumes responsibility for any omissions or errors that may appear nor assumes liability for any damages that may result from the use of the products in accordance with information contained in the manual. HOFFER FLOW CONTROLS' policy is to provide a user manual for each item supplied. Therefore, all applicable user manuals should be examined before attempting to install or otherwise connect a number of related subsystems. During installation, care must be taken to select the correct interconnecting wiring drawing. The choice of an incorrect connection drawing may result in damage to the system and/or one of the components. Please review the complete model number of each item to be connected and locate the appropriate manual(s) and/or drawing(s). Identify all model numbers exactly before making any connections. A number of options and accessories may be added to the main instrument, which are not shown on the basic user wiring. Consult the appropriate option or accessory user manual before connecting it to the system. In many cases, a system wiring drawing is available and may be requested from HOFFER FLOW CONTROLS. This document contains proprietary information, which is protected by copyright. All rights are reserved. No part of this document may be photocopied, reproduced, or translated to another language without the prior written consent of HOFFER FLOW CONTROLS, INC. HOFFER FLOW CONTROLS’ policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. The information contained in this document is subject to change without notice. Return Requests / Inquiries Direct all warranty and repair requests/inquiries to the Hoffer Flow Controls Customer Service Department, telephone number (252) 331-1997 or 1-800-628- 4584. BEFORE RETURNING ANY PRODUCT(S) TO HOFFER FLOW CONTROLS, PURCHASER MUST OBTAIN A RETURNED MATERIAL AUTHORIZATION (RMA) NUMBER FROM HOFFER FLOW CONTROLS’ CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned RMA number should then be marked on the outside of the return package and on any correspondence. FOR WARRANTY RETURNS, please have the following information available BEFORE contacting HOFFER FLOW CONTROLS: 1. P.O. number under which the product was PURCHASED, 2. Model and serial number of the product under warranty, and 3. Repair instructions and/or specific problems relative to the product. FOR NON-WARRANTY REPAIRS OR CALIBRATIONS, consult HOFFER FLOW CONTROLS for current repair/ calibration charges. Have the following information available BEFORE contacting HOFFER FLOW CONTROLS: 1. P.O. number to cover the COST of the repair/calibration, 2. Model and serial number of the product and 3. Repair instructions and/or specific problems relative to the product.

HOFFER FLOW CONTROLS, INC. ("HFC") warrants HFC's products

("goods") described in the specifications incorporated in this manual to be free from defects in material and workmanship under normal use and service, but only if such goods have been properly selected for the service intended, properly installed and properly operated and maintained. This warranty shall extend for a period of one (1) year from the date of delivery to the original purchaser (or eighteen (18) months if the delivery to the original purchaser occurred outside the continental United States). This warranty is extended only to the original purchaser ("Purchaser"). Purchaser's sole and exclusive remedy is the repair and/or replacement of nonconforming goods as provided in the following paragraphs. In the event Purchaser believes the goods are defective, the goods must be returned to HFC, transportation prepaid by Purchaser, within twelve (12) months after delivery of goods (or eighteen (18) months for goods delivered outside he continental United States) for inspection by HFC. If HFC's inspection determines that the workmanship or materials are defective, the goods will be either repaired or replaced, at HFC's sole determination, free of additional charge, and the goods will be returned, transportation paid by HFC, using he lowest cost transportation available. Prior to returning the goods to HFC, Purchaser must obtain a Returned Material Authorization (RMA) Number from HFC's Customer Service Department within 30 days after discovery of a purported breach of warranty, but no later than the warranty period; otherwise, such claims shall be deemed waived. See the Return Requests/Inquiries Section of this manual. If HFC's inspection reveals the goods are free of defects in material and workmanship or such inspection reveals the goods were improperly used, improperly installed, and/or improperly selected for service intended, HFC will notify the purchaser in writing and will deliver the goods back to Purchaser upon (i) receipt of Purchaser's written instructions and (ii) the cost of transportation. If Purchaser does not respond within thirty (30) days after notice from HFC, the goods will be disposed of in HFC's discretion. HFC does not warrant these goods to meet the requirements of any safety code of any state, municipality, or other jurisdiction, and Purchaser assumes all risk and liability whatsoever resulting from the use thereof, whether used singly or in combination with other machines or apparatus. This warranty shall not apply to any HFC goods or parts thereof, which have been repaired outside HFC's factory or altered in any way, or have been subject to misuse, negligence, or accident, or have not been operated in accordance with HFC's printed instructions or have been operated under conditions more severe than, or otherwise exceeding, those set forth in the specifications for such goods. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. HFC SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE RESULTING, DIRECTLY OR INDIRECTLY, FROM THE USE OR LOSS OF USE OF THE GOODS. WITHOUT LIMITING THE GENERALITY OF THE FOREGOING, THIS EXCLUSION FROM LIABILITY EMBRACES THE PURCHASER'S EXPENSES FOR DOWNTIME OR FOR MAKING UP DOWNTIME, DAMAGES FOR WHICH THE PURCHASER MAY BE LIABLE TO OTHER PERSONS, DAMAGES TO PROPERTY, AND INJURY TO OR DEATH OF ANY PERSONS. HFC NEITHER ASSUMES NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OR USE OF HFC'S GOODS, AND THERE ARE NO ORAL AGREEMENTS OR WARRANTIES COLLATERAL TO OR AFFECTING THE AGREEMENT. PURCHASER'S SOLE AND EXCLUSIVE REMEDY IS THE REPAIR AND/OR REPLACEMENT OF NONCONFORMING GOODS AS PROVIDED IN THE PRECEDING PARAGRAPHS. HFC SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES.

1. Introduction----------------------------------------------------------------- 1

1.1 Model Number Designation --------------------------------------- 3 2. Specifications --------------------------------------------------------------- 7 3. Installation and Operation----------------------------------------------- 9 3.1 Power Supply-------------------------------------------------------- 9 3.2 Flowmeter Input----------------------------------------------------10 3.3 Pulse Output --------------------------------------------------------12 3.4 Analog Output------------------------------------------------------14 3.5 Alarm Outputs------------------------------------------------------16 3.6 Communications Port ---------------------------------------------18 3.7 Wiring ---------------------------------------------------------------19 APPENDIX A - Default Configuration------------------------------------20 APPENDIX B - Declaration--------------------------------------------------22 APPENDIX C - Installation and Conditions for Safe Use Drawings for Certified Systems ----------------------------------------------------------24

The CAT3 is a versatile DC or AC powered microprocessor-based

transmitter, which provides pulse output, analog output and High/Low flow alarm options. Up to 3 circuit boards may be installed to provide a variety of input/output options. The flowmeter input circuitry will accept a variety of signal types including, low level sinusoidal, MCP/RF, pulse and contact closure. Optional 20-point linearization is available to correct for flowmeter non-linearities, improving overall system accuracy. The CAT3 is compatible with all Hoffer turbine flowmeters as well as the H.O.G. series positive displacement flowmeters. CAT3 Block Diagram HIGH ALARM OUT PCA180 ANALOG OUT FLOWMETER INPUT PREAMP CONDITIONED SIGNAL PULSE OUT PCA182 AC/DC OR HIGH ALARM PCA184 LOW ALARM CONVERTER LOW ALARM OUT DAC PULSE OUT INTERFACE ANALOG OUT COM MICROCONTROLLER RS232 PCA183 An RS232 communications port located under the top plate allows CAT3 to be remotely configured using DevConfig 3.0, a PC application program that is included with all units.

The standard unit is packaged in an extruded aluminum enclosure for

wall mounting or may be mounted directly on a flowmeter using an optional NEMA 4X or EX enclosure. An optional bracket is also available for mounting on standard DIN rail.

Model Number Designation

MODEL CAT3-( A )-( B )-( C )-( D )-( E )-( F )-( G) PULSE INPUT LINEARIZED PULSE OUTPUT LINEARIZED ANALOG OUTPUT POWER SUPPLY ALARM OUTPUT ENCLOSURE STYLE SPECIAL FEATURES PULSE INPUT MODEL CAT3-( A )-( )-( )-( )-( )-( )-( ) OPTION ( A ) (1) MAG COIL, PULSE, DRY CONTACT (2) MC3P (3) ISOLATED PULSE, RPM, RPR AND HALL EFFECT COILS LINEARIZED PULSE OUTPUT MODEL CAT3-( )-( B )-( )-( )-( )-( )-( ) OPTION ( B ) (1) 0-5 TTL / CMOS (2) OPEN COLLECTOR (3) OPEN COLLECTOR WITH PULL UP TO V+ (4) AC SQUARE WAVE (5) 0-10V SQUARE WAVE NOTE: NOT RECOMMENDED FOR USE AS A FLOW RATE SIGNAL. MAXIMUM INPUT SENSOR FREQUENCY ALLOWED IS 100HZ. LINEARIZED ANALOG OUTPUT MODEL CAT3-( )-( )-( C )-( )-( )-( )-( ) OPTION ( C ) (1) 4-20 MA (5) 1-5 VDC POWER SUPPLY MODEL CAT3-( )-( )-( )-( D )-( )-( )-( ) OPTION ( D ) (DC) 13-30 VDC (AC) 100-240 VAC NOTE: WHEN (AC) IS SELECTED, THE ALARM OPTION IS NOT AVAILABLE. USE REMOTE ACC39B POWER SUPPLY IF REQUIRED.

MODEL CAT3-( )-( )-( )-( )-( E )-( )-( )

OPTION ( E ) (4) HIGH OPEN COLLECTOR (5) HIGH TTL / CMOS (6) HIGH RELAY ONE SPDT, CONTACT RATED @ 2A 30V (7) LOW OPEN COLLECTOR (8) LOW TTL / CMOS (9) LOW RELAY ONE SPDT, CONTACT RATED @ 2A 30V NOTE: WHEN ALARM OPTION IS SELECTED, (AC) POWER IS NOT AVAILABLE. USE REMOTE ACC39B POWER SUPPLY. ENCLOSURE STYLE MODEL CAT3-( )-( )-( )-( )-( )-( F )-( ) OPTIONS ( F ) (1) GENERAL PURPOSE. 2.6"L X 2.6"H X 2.6"W MINIMUM MOUNTING SPACE. (D) 2" LONG DIN RAIL MOUNT SINGLE UNIT. UP TO 20 CAT3 UNITS CAN BE MOUNTED ON A SINGLE RAIL. ADD 2" PER UNIT. (E3) EXPLOSION-PROOF (ALL CONDUIT PORTS ARE ¾” FNPT) (E3M) EXPLOSION-PROOF (CONDUIT PORTS D2 & D3 = M20 THR’D; (E4)* EXPLOSION-PROOF - FOR USE WITH AC POWERED CAT ONLY (NOT Ex d SYSTEM CERTIFIED) *FOR Ex d CERTIFIED SYSTEM USE E6 OR E6M ENCLOSURE (E6) EXPLOSION-PROOF STAINLESS STEEL (ALL CONDUIT PORTS ARE ¾"FNPT) (E6M) EXPLOSION-PROOF STAINLESS STEEL (M20 NOT AVAILABLE FOR CANADA) NOTE: FOR UL LISTED EXPLOSION-PROOF APPLICATIONS CONTACT FACTORY.

MODEL CAT3-( )-( )-( )-( )-( )-( )-( G )

OPTIONS ( G ) (CE) MARK REQUIRED FOR EUROPE (SP) ANY SPECIAL FEATURES THAT ARE NOT COVERED IN THE MODEL NUMBER, USE A WRITTEN DESCRIPTION OF THE -SP (MIL) DESIGNED TO MEET EMC STDS EN5011-1992 AND EN61326-1:1997 (CFX) 6.75" LONG RISER AND UNION FOR EXPLOSION-PROOF SYSTEM CERTIFIED ENCLOSURES MOUNTED ON TURBINE. USED WITH “X” RISER TURBINE OPTION AND (EXP) OR (EX) SPECIAL FEATURES OPTION UNDER FLOWMETERSAS FOLLOWS: (EXP) FOR CANADIAN INSTALLATION OR (EX) FOR NON-CANADIAN INSTALLATION. NOTE: IF PROCESS TEMP IS < -40°C AND > 79°C, EX-PROOF ENCLOSURE MUST BE MOUNTED REMOTELY. (C) REMOTED MOUNTED FOR EXPLOSION-PROOF SYSTEM CERTIFIED ENCLOSURE. FOR USE WITH (C-EXP) OR (EX) SPECIAL FEATURES UNDER FLOWMETERS AS FOLLOWS: (EXP) FOR CANADIAN INSTALLATION OR (EX) FOR NON-CANADIAN INSTALLATION. NOTE: “X” RISER, CERTIFIED UNION, REDUCER AND ENCLOSURE (TO BE SPECIFIED) MOUNTED ON FLOWMETER (X) NO SPECIAL FEATURES STYLE E3, E3M, E6 AND E6M SYSTEM CERTIFIED RATINGS - CSA/FM: CLASS I, DIV. 1, GR. BCD; CLASS II, DIV. 1, GR. EFG; CLASS III, TYPE 4X, CLASS 1 ZONE 1 AEx db IIB + H2 T6/T5 Gb, Ex d IIB+H2 T6/T5; Gb; Ex tb T80°C/T86°C IIIC Db; IP66 CLASS I, ZONE 21 AEx tb T80°C/T86°C IIIC Db; IP 66 - ATEX/IECEx: II 2 G Ex db IIB + H2, T6/T5 Gb II 2 D Ex tb IIIC T80°C/T86°C Db; IP66 T6: -40°C ≤ Ta ≤ 79°C; T5: -40°C ≤ Ta ≤ 85°C NOTES: 1. IF ENCLOSURE IS MOUNTED ON TURBINE FLOWMETER, RISER MUST BE SPECIFIED ON METER. 2. PULSE SCALING IS SUPPLIED AS A STANDARD IN THE BASE PRISE AND IS SCALED TO THE UNIT MEASURE. 3. WINDOWS® BASED SETUP AND CABLE KIT CONSISTS OF: 1 EA. HIT2A-301 1EA. CABLE MODEL 26886

Input Signal Type:

Magnetic pick up, MCP pick up, Contact Closure, Pulse Input Frequency Range: 0.2 Hz to 4 KHz Signal Level: 10 mV rms to 30 Vdc Power Supply: 13-30 Vdc (Reverse polarity protected) 100-240 Vac (Fuse rating 0.5A, 250 Vac) Analog Output: 4-20mA, 1-5V Analog Output Response Time: 1/8 sec.* Load Resistance: Max 650 Ohms at 24 Vdc Accuracy: +/- 0.02% of full scale @ 20 C Temperature Drift: 40ppm/deg C Pulse Output: 0-5, 0-10V, Open Collector, AC square Internal pull-up resistor 2.7k Ohms Recommended load min. 50k Ohms Maximum Pulse 1, 2, 4, 8, 100, 50% Duty Cycle Frequency: Pulse Scaling: Per flow unit of measure, divide by 1, 10, 100 Hi/Lo Alarm: Relay (2A, 30 Vdc), 0-5V, Open Collector (0.5A, 30 Vdc) Communications: RS232 port for Configuration and diagnostics Operating Temperature: T5 and STD: -40o ≤ Ta ≤ 85o C T6: -40o ≤ Ta ≤ 79o C Humidity: 0-90% Non-condensing Enclosure: Extruded aluminum DIN rail mount Explosion Proof Regulatory: CE compliant *Limited by signal frequency and MST settings. Refer to Section 3.4. Options 20 Point Linearization

Installation and Operation 9

CAT3 HP-312 3. Installation and Operation 3.1 Power Supply DC Power (13-30 VDC) N/C N/C POWER PULSE- N/C ANLG SUPPLY SIG+ DC SIG- + DC+ DC- - PULSE+ AC Power (100-240 VAC) AC power for CAT3 requires an optional circuit board, PCA182. The Alarm option (PCA184) is not available when the AC Power option is equipped. DC- DC+ SIG- PULSE- N/C N/C PULSE+ SIG+ ANLG N/C NEUTRAL HOT L1 L2 PLUG AC MALE PCA180 SW2 1 PCA180 SW2 1

Installation and Operation

HP-312 CAT3 3.2 Flowmeter Input The Preamp circuitry for conditioning the flow signal is located on PCA180. The following drawings illustrate typical connections and switch settings on PCA180 for various input signals. Magnetic Pickup Coil A B Mag Pickup Coil N/C PULSE- N/C N/C SIG+ ANLG SIG- DC+ DC- PULSE+ MCP/RF Coil A B Modulated Carrier Pickup (RF) N/C PULSE- N/C N/C SIG+ ANLG SIG- DC+ DC- PULSE+ C PCA180 SW1 1 PCA180 SW1 1

Installation and Operation 11

CAT3 HP-312 Redi-Pulse (TTL Pulse) B A Redi-Pulse (TTL) Pickup Coil N/C N/C PULSE- N/C ANLG SIG+ SIG- DC+ DC- PULSE+ C Redi-Pulse (Open Collector) A B Redi-Pulse (Open Collector) Pickup Coil N/C PULSE- N/C N/C SIG+ ANLG SIG- DC+ DC- PULSE+ C PCA180 SW1 PCA180 SW1 1 1

Installation and Operation

HP-312 CAT3 3.3 Pulse Output CAT3 provides a Pulse Output option that is scaled per flow unit of measure by a factor of 1, 10 or 100. Pulse output frequency varies with flow rate. The maximum frequency can be set at 1, 2, 4, 8, 100 Hz. The following drawings illustrate typical connections and switch settings for various pulse output options. TTL(0-5V), 0-10V, High Level (DC In), AC Square PULSE INPUT - + USER DCS N/C PULSE- N/C N/C SIG+ ANLG SIG- DC+ DC- PULSE+ 1 PCA180 SW2 TTL(0-5V), 0-10V, AC Square 1 PCA180 SW2 High Level Pulse, AC Square

Installation and Operation 13

CAT3 HP-312 Open Collector, Isolated Pulse PULSE INPUT - + USER DCS N/C PULSE- N/C N/C ANLG SIG+ SIG- DC+ DC- PULSE+ V+ 2.7K 1 PCA180 SW2 Open Collector 1 PCA180 SW2 Isolated Pulse

Installation and Operation

HP-312 CAT3 3.4 Analog Output CAT3 provides an Analog Output option that will output an analog current or voltage that is proportional to the flow rate. Analog Output N/C POWER PULSE- N/C N/C SUPPLY SIG+ ANLG DC SIG- + DC+ LOAD DC- - + - PULSE+ The Microcontroller, located on PCA183, accepts the square- wave output of the preamplifier and performs all of the calculations that are required to control the Loop Driver. After measuring the frequency of the square-wave, the Microcontroller uses the following equations to compute the flow rate and current. xCF x Kfactor frequency flowrate FM 60  PCA183 SW1 4–20 mA Output 1 PCA183 SW1 1-5 V Output 1

Installation and Operation

15 CAT3 HP-312       AF flowrate mAx mA current 16 4 Where: Kfactor = Is dependent on the Flow Calculation Method setting and is either the Average K-Factor or the Linearized K- Factor from the Frequency / K-Factor table. FM = Is the Flow rate Units setting of 0, 1, or 2. Where “0” is for Seconds, “1” is for Minutes, and “2” is for Hours. CF = Is the Correction Factor setting. Where: AF = Is the 20 mA maximum Flow rate value. If the calculated flowrate is greater than the AF setting, the current will be set to 24mA to indicate an “Over-range” condition. After calculating the current, the Microcontroller digitally sends the current information to the Loop Driver. The loop driver, located on PCA183, uses the digital information sent to it by the Microcontroller to set the current of the loop. The Loop Driver also supplies power to the Microcontroller. The analog output response time to reach steady state due to a change in the flow rate is approximately 1/8 of a second. When flow stops, the time for the analog output to return to 4 mA will be between .25 and 8 seconds, depending on the Maximum Sample Time (MST) setting. MST is adjusted using the NB= (DATA) command, where NB is a value between 1 and 80. The default MST setting is NB= 1. Adjusting the MST is only recommended for low flow applications where the minimum input frequency is below 1 Hz.

Installation and Operation

HP-312 CAT3 3.5 Alarm Outputs CAT3 provides an optional High/Low Flow Alarm feature. Alarms require an optional circuit board, PCA184. The Alarm option is not available when the AC Power option is equipped. The drawings below illustrate the typical connections and switch settings for various alarm options. Hi/Lo Alarm Relay SIG+ SIG- DC+ DC- PULSE+ NC1 COM1 NO1 High/Low-Nomally Closed High/Low-Nomally Open High/Low-COM N/C N/C N/C PULSE- ANLG Hi/Lo Alarm TTL(0-5V) SIG+ COM N/C DC+ DC- ANLG PULSE- PULSE+ SIG- N/C ALARM1 USER DCS Indicator Alarm + - N/C 1 PCA184 SW1 1 PCA184 SW1

Installation and Operation

17 CAT3 HP-312 Hi/Lo Alarm Open Collector USER DCS Alarm Indicator 2.7K V+ + - N/C N/C N/C SIG+ ALARM1 DC- SIG- COM ANLG PULSE+ PULSE- DC+ 1 PCA184 SW1

Installation and Operation

HP-312 CAT3 3.6 Communications Port CAT3 is equipped with RS232 serial communication port for changing CAT3 configuration, diagnostics functions, and flow monitoring. Hoffer communication program DevConfig 3.0 must be used to communicate with CAT3. The RS232 serial port connector is located under the top plate of CAT3 and may be accessed by removing the two screws from the top plate. A matching connector is provided with HOFFER HIT2A-301 Communications Cable. CAT3 unit has to be powered from external supply in order to be able to communicate. Additional power for CAT3 communication circuitry is supplied by the RS232 serial port of the computer/terminal. COM port settings must be set as follows: Baud Rate: 2400 Data Bits: 8 Parity: None Stop bits: 1 Handshaking: None HOFFER HIT2A-301 Communications Cable Tx 3 Rx 2 DTR 4 SIG COM 5 CD 1 6 DSR 7 RTS 8 CTS 9 NC DB9 VDC1 VDC2 Pin 2 Pin 1 Molex 0511100660 or Equivalent

Installation and Operation

19 CAT3 HP-312 3.7 Wiring When installing CAT3, it is a good practice to use shielded cables for all input and output signals. The shield should be connected to the earth ground lug on the CAT3. The shield on the opposite end of the cable should be left open. Connections are made to the CAT3 terminal blocks using wire gauges 16 to 28 AWG and 12 to 26 AWG (AC Power), tightening Torque 0.22 to 0.25Nm. This wiring practice is mandatory in order to comply with the requirements for Electromagnetic Compatibility, as per EMC-Directive 2014/30/EU of the Council of European Community.

Appendix A – Default Configuration 21

CAT3 HP-312 FIELD Value FLOW CALC. METHOD 0 (Average) K-FACTOR DECIMAL 3 AVERGAE K-FACTOR 1.00 NUMBER OF POINTS IN K-TABLE 10 FREQUENCY 01 4999.981 FREQUENCY 02 4999.982 FREQUENCY 03 4999.983 FREQUENCY 04 4999.984 FREQUENCY 05 4999.985 FREQUENCY 06 4999.986 FREQUENCY 07 4999.987 FREQUENCY 08 4999.988 FREQUENCY 09 4999.989 FREQUENCY 10 4999.990 FREQUENCY 11 4999.991 FREQUENCY 12 4999.992 FREQUENCY 13 4999.993 FREQUENCY 14 4999.994 FREQUENCY 15 4999.995 FREQUENCY 16 4999.996 FREQUENCY 17 4999.997 FREQUENCY 18 4999.998 FREQUENCY 19 4999.999 FREQUENCY 20 5000.000 K-FACTOR 01 1.00 K-FACTOR 02 1.00 K-FACTOR 03 1.00 K-FACTOR 04 1.00 K-FACTOR 05 1.00 K-FACTOR 06 1.00 K-FACTOR 07 1.00 K-FACTOR 08 1.00 K-FACTOR 09 1.00 K-FACTOR 10 1.00 K-FACTOR 11 1.00 K-FACTOR 12 1.00 K-FACTOR 13 1.00 K-FACTOR 14 1.00 K-FACTOR 15 1.00 K-FACTOR 16 1.00 K-FACTOR 17 1.00 K-FACTOR 18 1.00 K-FACTOR 19 1.00 K-FACTOR 20 1.00 MEASURING UNITS GAL FLOW RATE TIME UNITS MIN MAX SAMPLE TIME 01 ANALOG OUTPUT LOW 0.000 ANALOG OUTPUT HIGH 100.000 PULSE SCALE OFF PULSE FREQUENCY 100 ALARM FUNCTION Off ALARM LEVEL 100.000

Appendix B – Declaration of Conformity 22

HP-312 CAT3 APPENDIX B - Declaration of Conformity

Appendix C - Installation and Safe Use Drawings 24

HP-312 CAT3 APPENDIX C - Installation and Conditions for Safe Use Drawings for Certified Systems