IPBridge Installation Guide

Page 2 Table of Contents 1: INTRODUCTION .................................................................................................................................... 4 1.1 : BEFORE YOU BEGIN .................................................................................................................. 4 1.2 : GENERAL REQUIREMENTS: ................................................................................................... 5 1.3 : POWERNET IP-BRIDGE SPECIFICATIONS: ........................................................................ 6 1.4 : INSTALLER TOOLKIT COMPONENTS ................................................................................. 7 2: PHYSICAL INSTALLATION ................................................................................................................ 8 2.1 : MOUNTING THE IP-BRIDGE .................................................................................................... 8 2.2 : VISUAL STATUS INDICATORS ................................................................................................ 9 2.3 : IP-BRIDGE RESET BUTTON ................................................................................................... 11 3: NETWORK ............................................................................................................................................. 12 3.1 : NETWORK CONFIGURATION ............................................................................................... 12 3.2 : DAISY-CHAINING NETWORK DEVICES ............................................................................ 13 4: IP-BRIDGE POWER .............................................................................................................................. 14 4.1 : PoE POWER ................................................................................................................................. 14 4.1.1 : PoE POWER CALCULATIONS ............................................................................................. 14 4.1.2 : CONTROLLING DOWNSTREAM PoE ................................................................................ 16 4.2 : USING DC POWER .................................................................................................................... 17 4.3 : COMMON ELECTRICAL CONNECTIONS .......................................................................... 18 4.3.1 : INDEX OF TERMINAL CONNECTIONS ............................................................................ 18 4.3.2 : DC POWER FOR THE DOOR COMPONENTS .................................................................. 20 4.3.3 : SIGNAL GROUND CONNECTIONS .................................................................................... 21 5: IP-BRIDGE DOOR OUTPUTS ............................................................................................................. 21 5.1: DOOR LOCK RELAY .................................................................................................................... 22 BACK EMF PROTECTION FOR THE LOCK CIRCUIT ................................................................ 23 5.1.2: IN-RUSH CURRENT PROTECTION FOR THE LOCK CIRCUIT ...................................... 24 5.2: TTL OUTPUTS ................................................................................................................................ 25 5.2.1: TTL’S CONTROLLING A SECONDARY RELAY MODULE .............................................. 26 5.3 : READER DC POWER OUTPUT (10 VDC) ............................................................................. 27 5.4 : READER INDICATOR OUTPUTS ........................................................................................... 27 6: IP-BRIDGE DOOR INPUTS ................................................................................................................. 28 6.1 : WIEGAND DATA INPUT .......................................................................................................... 28 6.2 : WIRING THE REX INPUT ........................................................................................................ 30 6.3 : WIRING THE AUX INPUT ....................................................................................................... 31 6.4 : WIRING THE DOOR SENSOR INPUT ................................................................................... 32 7: CONFIGURATION EXAMPLES ......................................................................................................... 33 7.1 : LOCK STRIKE & WIEGAND DEVICE .................................................................................. 33 7.2 : MAGNETIC LOCK, REX, DOOR SENSOR, & WIEGAND DEVICE ................................. 34 7.3 : LOCK STRIKE & WIEGAND DEVICE WITH TAMPER .................................................... 35 7.4 : CONTROLLING THREE DOORS .......................................................................................... 36 7.5 : 1 DOOR & 1 IP CAMERA ......................................................................................................... 38 7.6 : EXTERNAL POWER W/DAISY-CHAIN ................................................................................ 39

IPBridge Installation Guide

Page 3 Document Version Date of Revision Revision Author Description 5/20/2013 1.00 Shirl Jones Initial Release 8/12/2013 1.01 Shirl Jones Expanded Wiegand Device guidelines 11/13/2013 1.02 Shirl Jones Described PoE Jumper & Reset button location 2/25/2014 1.03 Shirl Jones Enhanced power and grounding instructions 5/9/2017 1.04 Melissa Stenger Updated software information, configuration info and Power instructions

IPBridge Installation Guide

Page 4 1: INTRODUCTION This document is the complete guide for mounting and wiring the ISONAS IP-Bridge product models IP- Bridge-2 and IP-Bridge-3. The IP-Bridge has some special capabilities that support multiple types of input power and daisy chaining multiple IP-Bridge’s together. For this reason, it is essential that you read through this entire guide before attempting an installation. Note: Within the Pure Access Software package, these models use the abbreviated model labels IPBR-2 & IPBR-3. 1.1 : BEFORE YOU BEGIN The following core tasks are involved when installing an ISONAS IP- Bridge: 1.Mount the IP-Bridge in the appropriate indoor location. 2. Supply power to the IP-Bridge unit. This may be accomplished with power being provided on the Ethernet data cable (Power over Ethernet [PoE]) or through an external DC power source (12VDC or 24VDC) 3. Wire the IP-Bridge to the door’s locks and other components required for physical access control. 4. Connect the unit to the data network for communication with the host workstation. This guide discusses each process separately. Understanding all of these processes makes a project much simpler and guarantees success.

IPBridge Installation Guide

Page 5 1.2 : GENERAL REQUIREMENTS:  If PoE is not being used, then use only UL-listed, access control, power- limited power supplies with an ‘AC on’ indicator light clearly visible on the enclosure. ISONAS recommends that Power supplies should provide at least four hours of standby power.  Never connect power supplies to a switch-controlled receptacle.  Install the ISONAS system in accordance with the National Electrical Code NFPA 70. (Local authority has jurisdiction.)  Use only wire or UL-listed cabling recognized as suitable for ISONAS power supply and data communications, in accordance with the National Electrical Code.  Where possible, separate ISONAS equipment and cabling from sources of electromagnetic interference (EMI). Where this is not possible, take other steps to reduce the effect of EMI on cabling or equipment.  Protect input and output terminals adequately from transient signals. Also, connect these terminals to power-limited circuitry.

IPBridge Installation Guide

Page 6 1.3 : POWERNET IP-BRIDGE SPECIFICATIONS: Input Voltage PoE per IEEE 802.3at PoE per IEEE 802.3af 12V DC to 28V DC Current Draw < 0.26 AMPS @ 12VDC < 0.18 AMPS @ 24VDC PoE: 4 Watts Maximum Supplied Power for External Devices PoE-Plus power (IEEE 802.3at) 1.60 AMPS @ 12VDC Maximum Supplied Power for External Devices PoE power (IEEE 802.3af) 0.60 AMPS @ 12VDC Upstream Ethernet Interface TCP/IP Over Ethernet 10 Mbps, auto-negotiate Downstream Ethernet Interface TCP/IP Over Ethernet 10 Mbps, auto-negotiate Supports 30 downstream IP devices Inputs/Outputs For each supported door: 4 Inputs Wiegand; REX; AUX; and Door Sensor 5 Outputs 2 TTL Outputs RED LED; GREEN LED; Beeper Wiegand Data Connection 500 ft Maximum Length Lock Relay 2.00 amp @ 30V DC (Resistive load) 0.03 amp @ 120V AC (Resistive load) Standalone Memory Capacity 20000 Cards / Door 5000 Events / Door 32 Time zones / Door Visual Indicators 6 0r 8 LEDs for Normal Operations Operating Temperatures -40° To 80° Celsius Weight Approximately 14 Ounces Size 6.28 L x 3.55 W x 2.26 H (inches)

IPBridge Installation Guide

Page 7 1.4 : INSTALLER TOOLKIT COMPONENTS Before an installer goes to a customer site, they need to put together their supplies and tool-kit. The ISONAS solution is simpler to install than other Access Control Systems, but materials are still needed. And some of those materials may be different than what you are use to carrying. The list below identifies some important items that you should make sure to bring with you, to the customer’s site. A prepared installer will have: Installer completed the on-line reseller training program. An installer’s Tool Kit should include the following: 1. The copy of the IP-Bridge Installation and Wiring Guide 2. A Volt-Ohm Meter 3. A PoE Injector 4. A Cross-over Cat5/Cat6 cable 5. A straight-thru Cat5/Cat6 patch cable. 6. Basic Ethernet network cable tester (Tests for: Opens, Shorts, Split Pairs, Mis-wires & Reversals) 7. A spare IP-Bridge 8. An extra Daisy-Chain power cord 9. The ISONAS As-Built forms, which is used to record the details of the door's installation. The customer’s site should have Internet access. This enables the use of on-line meeting tools, such as GoToMeeting, during any remote support sessions.

IPBridge Installation Guide

Page 8 2: PHYSICAL INSTALLATION When selecting the location where you are going to mount the ISONAS IP-Bridge, a few guidelines should be observed. 1) The IP-Bridge should be protected from extreme heat and sunlight. It is rated for indoor use, between -40 to 80 degrees C. 2) The IP-Bridge is designed to be mounted on a standard 35 mm DIN Rail. 3) Mounting the IP-Bridge inside of a control cabinet or a NEMA housing is recommended. 4) When planning a project’s DIN rail layout, determine if the door device’s electrical return connections will be terminated by the optional modular DIN terminal blocks. If so, adjust the IP-Bridge’s location on the DIN rail to allow space for the modular terminal blocks. 5) The IP-Bridge should be located within a 500 foot cable length of the devices being controlled. 2.1 : MOUNTING THE IP-BRIDGE The major steps involved with the physical mounting of the IP-Bridge include: 1) Planning the location of the DIN rail(s) a. Typically inside a control cabinet, or NEMA housing. 2) Attaching the DIN rails to housing’s mounting surface 3) Snapping the IP-Bridge to its DIN rail 4) Attaching the optional terminal block(s) 5) Repeat the process, for any additional IP-Bridges

IPBridge Installation Guide

Page 9 2.2 : VISUAL STATUS INDICATORS The IP-Bridge has multiple LED status indicators to assist in monitoring and troubleshooting the status of the unit. LED’s are labeled in Figure 01. LED’s A and B are used to indicate the status of the IP-Bridge itself. The C & D LED pairs indicate the status of individual doors. Figure 01 IP-Bridge Status LED “A” Color LED “B” Color IP-Bridge is not powered on Off Off Power Turned On – Waiting in Boot Loader mode (~10 sec) Red Red Performing All IP work, all mode, duration depends on settings Amber Red IP Work completed (except long DNS lookups), ports/DNS Red Amber Startup Complete. No issues reported. Green Off Startup Complete. Errors reported, check history Green Amber Door Status (occurs once for each supported door) LED “C” Color LED “D” Color Waiting In (Startup) or Performing Boot Load Amber Amber Waiting to be activated (if ever) or door process issue Off Amber Normal Operation Red Off No Door (2-door Bridge)/Deactivated Door Off Off Door is unlocked Green Green Door is in the Lockdown condition Red Red Door is unlocked, for the latch interval Green Off

IPBridge Installation Guide

Page 11 2.3 : IP-BRIDGE RESET BUTTON The PowerNet IP-Bridge has a recessed reset-button located in the position shown on Figure 02. It can be used for two different types of resets. It is helpful to monitoring the amber LAN status LED allows you to determine the status of the reset operation.  Reset CPU: Press, hold (approx. 2 seconds) and release the Reset button. Once the Reset Button is released, all the door status LED’s will turn amber, and in 15 seconds return to the normal display. If the door’s LEDs do not turn amber, then the reset did not occur.  Reset Configuration: Press and hold the Reset button (approx. 10 seconds), until all door status LED’s turn Amber. After the LED’s turn Amber, release the Reset button. Selected IP-Bridge configurations are reset to factory defaults. Setting that are changed include:  IP Address (Default value: 192.168.1.119)  IP Port (Default value: 10001) Subnet Mask (Default value: 255.255.0.0) Gateway (Default value: 0.0.0.0) DHCP Setting (Default value: Off) ACS Server (Default value: SrvrAcs) ACS Server IP (Default value: 0.0.0.0) Clear AES Encryption Configuration Reset the IP-Bridge’s Password. Figure 02

IPBridge Installation Guide

Page 12 3: NETWORK The IP-Bridge is connected to the customer’s network using the “Upstream” RJ45 port. The IP-Bridge network connection auto-detects the speed between 10MB or 100MB, depending on the speed capabilities of the customer’s network. 3.1 : NETWORK CONFIGURATION The ISONAS Configuration utility tool can be used to configure the IP-Bridge’s network settings. Here is more information on configuring IP-Bridges to Pure Access. Items that may be configured include: 1) Is DHCP being used? a. Host computer’s IP Address, or network alias 2) If DHCP is not used: a. Static IP Address. b. Subnet Mask. c. Gateway Address. 3) IP Port used by the IP-Bridge 4) Is “Client Mode” being used? a. Remote Host IP Address or URL b. Remote Host IP Port c. DNS Server IP Address 3.2 : DAISY-CHAINING NETWORK DEVICES The IP-Bridge supplies the functionality of a two-port network switch. It has two physical RJ45 ports or sockets labeled “Upstream” and “Downstream” as shown in Figure 03. The “Upstream” RJ45 port is used to connect to the customer’s network. Some network switches label this as the “uplink” port. The “Downstream” RJ45 port is used to connect to other Ethernet devices; such as additional IP-Bridges, IP based cameras, etc. The network traffic going to/from the connected devices via the “Downstream” Port will be directed by the IP-Bridge through the “Upstream” port. The “Downstream” port will be provided PoE Power; as long as the IP-Bridge is being powered by PoE and sufficient power is available. It is possible to disable the PoE feed going out of the downstream port.

IPBridge Installation Guide

Page 13 Figure 03 4: IP-BRIDGE POWER The IP-Bridge can be powered with PoE, PoE-Plus, or DC power in the range of 12VDC to 28VDC. NOTE: DO NOT power the IP-Bridge with PoE and 24VDC. If you are powering with external power, please ensure your network cable is providing data only. Using PoE and 24VDc will void the warranty. 4.1 : PoE POWER PoE power can used to power the IP-Bridge itself and is commonly used to provide power to the components at the door, such as an electric lock, a Wiegand device, and/or a passive infrared motion detector. The IP-Bridge can be use two types of PoE. PoE ( IEEE 802.3af ) --- 13 watts of power can be supplied to the IP-Bridge, via a PoE network switch that meets the 802.3af standard. 13 watts is enough power for the IP-Bridge itself and a single door’s typical hardware (dumb-reader and lock). PoE-Plus ( IEEE 802.3at ) --- 25.5 watts of power can be supplied to the IP-Bridge, via a PoE network switch that meets the 802.3at standard. The IP-Bridge will auto-adjust to accept the type of PoE being supplied by the network switch.

IPBridge Installation Guide

Page 14 To meet the IP-Bridge’s variable PoE power requirements, the IP-Bridge will classify itself with the PoE source as a “Class 0” PoE device, or “Class 4” PoE-Plus device. The power usage of a Class 0 PoE device can range between 0.4 to 13.0 watts at the device. The power usage of a Class 4 PoE- Plus device can range between 12.95 to 25.5 watts at the device. 4.1.1 : PoE POWER CALCULATIONS When the IP-Bridge is being powered by PoE-Plus, it can supply power to external devices thru three different methods.  The 10VDC output for the Wiegand devices (via the “DC-R” terminal)  The 12VDC output for other devices. (via the “DC” terminal)  PoE power to network devices that are daisy-chained to the IP-Bridge. o Type “B” PoE is supplied downstream. o Jumper Pin adjustment is required (See next section)

IPBridge Installation Guide

Page 15 Table A is a worksheet that will help you calculate how much power is available for the daisy chained “downstream” devices. Figure 04 graphically displays the related power flow. Diagram Label Purpose Milliamps Supplied (mA) Factor Calculated Watts (mA) * (Factor) “A” “DC-R” Output (10VDC) 0.0117 “B” “DC” Output (12VDC) 0.0141 IP-Bridge Power consumed by IP-Bridge’s electronics 4 Total Power Used by IP-Bridge Sum of values listed above PoE Input If using PoE: enter 12.95 watts If using PoE Plus: enter 25.50 watts Answer PoE Wattage Available Downstream Answer = (PoE Input) – (Total Power Used) Table A

IPBridge Installation Guide

Page 16 Figure 04 4.1.2: CONTROLLING DOWNSTREAM PoE The IP-Bridge is able to pass all excess PoE power out the downstream RJ45 connector. This is done with a passive type of PoE, and PoE device-detection is not supported. A jumper pin (JP-1) is used to enable or disable the downstream port’s PoE power feed. JP-1 is located inside the IP-Bridge. Refer to Figure 05. To reach the jumper, use a small screwdriver to pry the cover up at the points indicated (Start at point #1). To enable the provisioning of PoE power out the downstream RJ45 port, place a jumper across pins 2 & 3 of JP-1. Figure 05 Removing the jumper from JP-1 will disable the flow of PoE power out the downstream RJ45 port.

IPBridge Installation Guide

Page 17 4.2 : USING DC POWER The IP-Bridge can be powered by external DC power. The IP-Bridge will accept DC power in the range of 12VDC to 28VDC. The DC power is fed into the IP- Bridge via a special coaxial cable attached to connector “AA” shown Figure 06. The 2nd end of the input power coaxial cable is attached to screw terminals on a standard DC power supply. Figure 06 If multiple IP-Bridges are being installed, the 2nd IP-Bridge can be powered with a short coaxial cable such as the one Isonas sells. One end of the cable is attached to connector “BB” on the 1st IP-Bridge, and then the cable is daisy-chained to connector “AA” on the 2nd IP-Bridge. See Figure 07. Figure 07 When powered with PoE, the input DC coaxial power cord is not required. If two IP-Bridges are daisy-changed, and are using PoE, the coaxial daisy-chain power cord is not required. Please note that the daisy-chained power connection is rated for 4.0 A @ 12VDC (2.0 A @ 24VDC).

IPBridge Installation Guide

Page 18 4.3 : COMMON ELECTRICAL CONNECTIONS 4.3.1 : INDEX OF TERMINAL CONNECTIONS External devices are connected to the IP-Bridge through the screw terminals located on along the sides of the IP-Bridge. A summary of the purpose of each terminal connection is detailed in the table below. Refer to the IP-Bridge’s label for the locations of each terminal connector. Terminal Block Connection Identifier Purpose I/O TTL2 Logic output. Default action is: 5 VDC is output , when in the “Off” state 0 VDC when in the “On” state. Action can be reversed in the software configuration. Supplies 20mA I/O TTL1 Logic output. Default action is: 5 VDC is output , when in the “Off” state 0 VDC when in the “On” state. Action can be reversed in the software configuration. Supplies 20mA I/O REX Logic Input from a Request-to-EXit device Default Action: When connection to “Gnd” is completed, the input goes active. Action can be reversed in the software configuration. I/O DS Logic Input from a Door Status Sensor Default Action: When connection to “Gnd” is opened, the input goes active. Action can be reversed in the software configuration. I/O NC Output. “Normally Closed” connection from IP-Bridge’s door control relay (form C) I/O COM Output. “Common” connection from IP-Bridge’s door control relay (form C) I/O NO Output. “Normally Open” connection from IP-Bridge’s door control relay (form C)

IPBridge Installation Guide

Page 19 Terminal Block Connection Identifier Purpose I/O DC Output: When IP-Bridge is powering from PoE, the “DC” terminal supplies regulated 12 VDC. When IP-Bridge is powering from 12 or 24 VDC, the “DC” terminal supplies the voltage that is input to the IP-Bridge. I/O GND Common Ground Connects with all ground terminals on the IP- Bridge terminal blocks and coaxial cable Reader GND Common Ground Connects with all ground terminals on the IP- Bridge terminal blocks and coaxial cable Reader DC-R Output: Supplies regulated 10 VDC. Reader N/A Not Used Reader AUX Logic Input Default Action: When connection to “Gnd” is completed, the input goes active. Action can be reversed in the configuration. Reader BP Output: Allows control of the Wiegand device’s beeper. {Future Use} Reader W0 Input. Connects to Wiegand data “0” from Wiegand device Reader W1 Input. Connects to Wiegand data “1” from Wiegand device Reader GR Output: Allows control of the Wiegand Green LED. {Future Use} Reader RED Output: Allows control of the Wiegand Red LED. {Future Use}

IPBridge Installation Guide

Page 20 4.3.2 : DC POWER FOR THE DOOR COMPONENTS The IP-Bridge can supply DC power for external devices. This power is made available to each door at the terminal connectors labeled “DC” and “GND”. See Figure 08. Figure 08 The voltage supplied by the “DC” terminal connection is determined by the method that the IP-Bridge is being powered. If the IP-Bridge is powered with PoE, then regulated 12VDC is available on the “DC” terminal connection If the IP-Bridge is powered with DC power, then the input DC voltage is made available on the “DC” terminal connection. For example, if the IP-Bridge is receiving 24VDC thru its coaxial power cord, then the “DC” terminal will supply 24VDC. The “DC” power’s return connection will be attached to the IP-Bridge’s Signal Ground. See the next “Signal Ground Connections ” section of the manual for more information regarding this part of the connection.

IPBridge Installation Guide

Page 21 4.3.3 : SIGNAL GROUND CONNECTIONS In order for the electrical signals going to the door’s components to function, they need to have a connection to the IP-Bridge’s Signal Ground. For some doors, only one or two ground wires are needed, and these wires can easily be directly connected to the IP-Bridge’s “Gnd” terminals. Other installations may require multiple electrical connections, with each requiring a connection to the Signal Ground. To support this, an optional DIN Terminal block can be mounted next to the IP-Bridge. The DIN Terminal Block is connected to one of the IP-Bridge’s Signal Ground terminals. Up to 15 each, 22 gage wires can be connected to a single connection on the DIN terminal block. See Figure 09. Figure 09 5: IP-BRIDGE DOOR OUTPUTS Warning: The IP–Bridge should not be powered until all connections have been made and tested. Remove power prior to changing any connections. The IP-Bridge can control and power multiple items at the door. Control of standard electrical locks is supported. Supplying electrical power and additional logic outputs are also features provided by the IP-Bridge. Controlling light and sound status indicators on the Wiegand device are currently not supported.

IPBridge Installation Guide

Page 22 5.1: DOOR LOCK RELAY The IP-Bridge is equipped with a lock-relay for each door lock supported. The relay is a Form C relay that is rated for 2.0 amps at 30 VDC. Connections to the relay’s “Normally Closed”, “Common”, and “Normally Open” contacts are available on the terminal strip and are labeled as “NC”, “COM” and “NO” respectively. See Figure 10. Figure 10 A block-diagram of the lock-relay is shown in Figure 11. The relay provides a “dry contact”. For many installations, the IP-Bridge will be supplying the DC power for the door lock. For these installs, a wire jumper will be placed between the “DC” and “COM” terminal connections. Figure 11

IPBridge Installation Guide

Page 23 Protect the Digital Output Which type of transient suppressor should you install? This depends mainly on the type of inductive load being switched. Some locks have Back EMF protection built into the lock itself. For Back EMF in low- voltage DC applications, a 1N4007 diode will suffice. However, for protection against other transient voltages (i.e. lightening), we recommend using a fast-switching transient voltage suppressor, such as a bipolar TranZorb. BACK EMF PROTECTION FOR THE LOCK CIRCUIT Most door latches use a relay coil that powers up and down to open and close the door. When power is removed from the coil, the collapse of the magnetic field creates a problem known as Back EMF that can interfere with the IP-Bridge’s operation, and create radio interference. Switching off a typical 12 VDC relay coil can produce a back EMF of 300 volts or more. If this relay is switched via an output, that voltage appears across the terminals of the output. The problem gets worse as switching voltage/current rises. Figure 12 shows the recommended solution. You can virtually eliminate back EMF by installing a transient suppression device (diode). Always check that the diode is correctly rated for the circuit voltage. For optimum performance, the diode should be installed at the lock or close to the lock. Standard diodes have a stripe-band marking on one side. That side of the diode should be connected to the “+” wire of the lock circuit. Figure 12

IPBridge Installation Guide

Page 24 5.1.2: IN-RUSH CURRENT PROTECTION FOR THE LOCK CIRCUIT Some Magnetic Locks with advanced quick-release circuitry will generate an initial surge of current when the lock is turned on. This surge of current can be 20 times greater than the lock’s steady state current requirements. The lock relay is rated for 2 amp of current. This in-rush current can greatly exceed that rating, and shorten the useful life of the IP-Bridge. Figure 13 shows the solution to this. Installing an in-rush suppressor in the lock circuit will prevent any detrimental effects on the IP-Bridge. FFFi Figure 13

IPBridge Installation Guide

Page 25 5.2: TTL OUTPUTS The IP-Bridge supplies two TTL outputs for each door, as shown in Figure 14. The TTL1 and TTL2 leads are logical output leads. In their “normal” state, there is a 5VDC potential on the leads. When the leads “activate”, this voltage potential is removed (0 VDC). These leads are typically used to connect to an alarm system. Certain alarm conditions of the IP-Bridge can be configured to activate these leads. An example would be having TTL2 activate when the door is held open too long. Figure 14 The “TTL” signal’s return connection will be attached to the IP-Bridge’s Signal Ground. See the previous “Signal Ground Connections” section of the manual for more information regarding this part of the connection.

IPBridge Installation Guide

Page 26 5.2.1: TTL’S CONTROLLING A SECONDARY RELAY MODULE The dual Secondary Relay Module (SRM) is available to enhance the IP- Bridge’s ability to control devices located at the door. The SRM provides a set of form-C relay contacts, which are controlled by one of the IP-Bridge’s TTL outputs. The SRM is commonly used to control a device located at the door, in addition to the door’s lock. A diagram of this SRM usage is shown below in Figure 15. Figure 15 SRM’s wiring color code Color Function Purple TTL input to SRM. Connected to the IP-Bridge’s “TTL1” or “TTL2” terminal. Black Signal Ground from IP-Bridge. Connects to IP-Bridge’s “GND” terminal. White / Red SRM Relay Common contact White / Violet SRM Relay Open contact (when TTL is inactive) White / Yellow SRM Relay Closed contact (when TTL is inactive)

IPBridge Installation Guide

Page 27 5.3 : READER DC POWER OUTPUT (10 VDC) The IP-Bridge provides up to 500mA @ 10 VDC regulated power supply for use when powering many Wiegand devices. This 10VDC power is provided on the “DC-R” terminal, and a convenient GND terminal is located adjacent to the DC-R connection. See Figure 16. Figure 16 5.4 : READER INDICATOR OUTPUTS Note: These features are designated for inclusion in future releases of the IP– Bridge. See Figure 17. “BP” Terminal Connection: The “BP” will be an output for controlling a beeper on the remote reader. “GR” Terminal Connection: The “GR” will be an output for controlling a green LED beeper on the remote reader. “RED” Terminal Connection: The “RED” will be an output for controlling a red LED on the remote reader. Figure 17

IPBridge Installation Guide

Page 28 6: IP-BRIDGE DOOR INPUTS Warning: The IP–Bridge should not be powered until all connections have been made and tested. Remove power prior to changing any connections. The IP-Bridge can monitor items located at the door. It supports receiving credential data from a Wiegand device and the control of standard electrical locks. 6.1 : WIEGAND DATA INPUT The IP-Bridge receives the user’s credential information from a Wiegand- based device, such as a card reader. Three (3) Wiegand conductors from the reader are connected to the IP- Bridge’s “W0”, “W1”, and “GND” terminals. The Wiegand ground conductor can be connected to any “GND” terminal on the IP-Bridge. The Wiegand ground connection should be dedicated to the Wiegand signal. A separate wire conductor would be used to ground any other door components to the IP-Bridge. Wiegand signal should be a “driven 5 VDC signal”, provided by the Wiegand device (may be accomplished thru a biasing resistor within the reader) The reader’s “W0” and “W1” terminals are shown in Figure 18. Figure 18 The Wiegand signal’s return connection will be attached to the IP-Bridge’s Signal Ground. See the previous “Signal Ground Connections” section of the manual for more information regarding this part of the connection.

IPBridge Installation Guide

Page 29 Wiegand Data The Wiegand protocol has been used since 1980, so many devices exist that use this protocol. The ISONAS solution can interpret the incoming Wiegand data in one of 3 ways. 1) As a raw 64 bit binary number, so the card format is not a factor. 2) As a HID formatted credential number, with the ISONAS Bit masking processing rules applied 3) As a HID formatted credential, with the ISONAS Data mangle processing rules applied. The recommended system integrator evaluation process is to use either an IP-Bridge or PowerNet w/WIM and test against the existing hardware and credentials. Validate that the reported credentials really uses the Wiegand protocol, and that the existing card format is handled appropriately. If you need assistance, and can supply the appropriate materials to ISONAS, we will test your configuration at the factory Required items include:  A reader that is known to work with the currently installed equipment.  5 working credentials, to verify credential formatting.  Installation instructions for the supplied reader, for power and operation instructions.

IPBridge Installation Guide

Page 30 6.2 : WIRING THE REX INPUT The REX (Request for Exit) signal expected by the ISONAS IP-Bridge is a momentary closure. You can generate this signal with a pushbutton, infrared motion detector, or other simple device. Typically the REX is placed adjacent to the door so that people can press the button and let themselves out the door without setting off the alarm. When pressed, this button tells the ISONAS IP-Bridge that someone wishes to pass through the door, and the latch releases. In the ISONAS Crystal software you can configure how the door responds to the REX button. The momentary switch is directly connected to the ISONAS IP-Bridge. First, connect one conductor from the switch to the IP-Bridge’s “REX” terminal, as shown in Figure 19. Then, connect the switch's other conductor to one of the IP-Bridge’s “GND” terminals. Figure 19 The “REX” input’s return connection will be attached to the IP-Bridge’s Signal Ground. See the previous “Signal Ground Connections” section of the manual for more information regarding this part of the connection. About REX Input The REX input is connected to a “Normally Open” contact on the external device. The REX event is created with the external device closes its contact.

IPBridge Installation Guide

Page 31 About AUX Input The AUX input is connected to a “Normally Open” contact on the external device. The AUX event is created with the external device closes its contact. 6.3 : WIRING THE AUX INPUT In host mode, the AUX Input is another momentary contact closure which functions exactly like the REX button. The AUX Input might be controlled by a relay on an intercom at the door. This would allow the receptionist to unlock the door using the intercom system’s functionality. In the ISONAS Crystal software you can configure how the door responds to the AUX button. In local mode, the door will stay unlocked for the period that the AUX switch is closed. The momentary switch is directly connected to the ISONAS IP-Bridge. First, connect one conductor from the switch to the IP-Bridge’s “REX” terminal, as shown in Figure 20. Then, connect the switch's other conductor to one of the IP-Bridge’s “GND” terminals. Figure 20 The “AUX” input’s return connection will be attached to the IP-Bridge’s Signal Ground. See the previous “Signal Ground Connections” section of the manual for more information regarding this part of the connection.

IPBridge Installation Guide

Page 32 6.4 : WIRING THE DOOR SENSOR INPUT Connecting the ISONAS IP-Bridge to a door sensor allows the Pure Access software to determine whether that door is physically open. Then the Pure Access software can create alarms based on the door’s state. This wiring task is similar to wiring the REX or AUX buttons. The momentary switch is directly connected to the ISONAS IP-Bridge. First, connect one conductor from the switch to the IP-Bridge’s “DS” terminal, as shown in Figure 21. Then, connect the switch's other conductor to one of the IP-Bridge’s “GND” terminals. Figure 21 The “DS” input’s return connection will be attached to the IP-Bridge’s Signal Ground. See the previous “Signal Ground Connections” section of the manual for more information regarding this part of the connection. IMPORTANT: If There's No Door Sense Switch If you choose NOT to install a door sense switch, then you must permanently ground the “DS” terminal to a “GND” terminal, so the system will not see the door as "open." About the Door Sense The door sense is connected to a “Normally Closed” input. No action is taken until the input is opened.

IPBridge Installation Guide

Page 33 7: CONFIGURATION EXAMPLES Several wiring examples are shown below. Please refer to previous detailed sections for more information about each example provided. 7.1 : LOCK STRIKE & WIEGAND DEVICE In Figure 22, a standard lock strike is being powered from the IP-Bridge. The DC power being supplied to the lock is either: 12VDC -- if the IP-Bridge is powered by PoE or 12VDC. Or 24VDC -- if the IP-Bridge is powered by 24VDC. The Wiegand device is being powered with 10VDC from the IP-Bridge. Figure 22

IPBridge Installation Guide

Page 34 7.2 : MAGNETIC LOCK, REX, DOOR SENSOR, & WIEGAND DEVICE In Figure 23, a standard magnetic lock is being powered from the IP-Bridge. A door sensor and REX button are also being used. The DC power being supplied to the lock is either: 12VDC -- if the IP-Bridge is powered by PoE or 12VDC. Or 24VDC -- if the IP-Bridge is powered by 24VDC. The Wiegand device is being powered with 10VDC from the IP-Bridge. Figure 23

IPBridge Installation Guide

Page 35 7.3 : LOCK STRIKE & WIEGAND DEVICE WITH TAMPER In Figure 24, a standard lock strike is being powered from the IP-Bridge. The DC power being supplied to the lock is either: 12VDC -- if the IP-Bridge is powered by PoE or 12VDC. Or 24VDC -- if the IP-Bridge is powered by 24VDC. The Wiegand device is being powered with 10 VDC from the IP-Bridge. The Wiegand device’s Tamper switch is being monitored by the AUX input on the IP-Bridge. Figure 24

IPBridge Installation Guide

Page 36 7.4 : CONTROLLING THREE DOORS In Figure 25, three doors are being controlled. Items of note include:  PoE Plus is providing power for all doors  Standard lock strikes are being used. o 12VDC is powering the lock strikes.  Each door has a door sensor switch installed  Wiegand devices are at each door o The Wiegand devices are being powered with 10 VDC Figure 25

IPBridge Installation Guide

Page 37 The table below describes each door’s connections. Terminal Block Connection Identifier Description I/O DS Connected to the Door Sensor at the door. I/O COM Connected to the “DC” terminal, which supplies 12VDC for the locks I/O NO Connected to the Door Lock I/O DC Connected to the “COM” terminal to supply DC power to the lock, thru the Lock Relay I/O GND Provides return for all connections from the door. Wiegand Device GND Provides return for all connections from the door. Wiegand Device DC-R Output: Supplies regulated 10 VDC for the Wiegand device. Wiegand Device W0 Input. Wiegand data “0” input lead, from the Wiegand device Wiegand Device W1 Input. Wiegand data “1” input lead, from the Wiegand device

IPBridge Installation Guide

Page 38 7.5 : 1 DOOR & 1 IP CAMERA In Figure 26, access-control for a single door and an IP-camera are being supported from a single Cat5/6 cable run. A PoE-Plus injector is providing the power required. Items of note include:  Connections from the door components are the same as described in example 7.4, including: o PoE Plus is providing power for door access and IP camera o Standard lock strike is being used.  12VDC is powering the lock strike. o A door sensor switch is installed o Wiegand device is at the door Figure 26

IPBridge Installation Guide

Page 39 7.6 : EXTERNAL POWER W/DAISY-CHAIN In Figure 27, the daisy-chaining of two IP-Bridges is illustrated. External Power is being used, instead of PoE. High-powered PoE could be used, as long as the total power draw across the two IP-Bridges is under the PoE power limitation. The Ethernet data for both units is supplied with a single network cable connection. The IP traffic for the 2nd unit is passed through the 1st unit.  Connections from the door components are the same as described in example 7.4, including: o Standard lock strikes are being used.  12VDC is powering the lock strike. o A door sensor switch is installed at each door o Wiegand devices are at the doors Figure 27

IPBridge Installation Guide