Technical Manual
PROGRAMMABLE DISPLAY
GT10
Includes installation guide for GTWIN screen
creation software.
all-guides.co
m
[ALWAYS OBSERVE THESE PRECAUTIONS]
Before installing, operating, servicing or inspecting this product, please make sure
you have read this manual and the explanations of how procedures are carried out,
and make sure the product is used correctly.
This manual uses two safety standard levels: ”WARNING” and ”CAUTION”.
WARNING
Erroneous handling of an item marked with this label can cause fatal or critical
injury to the user.
D If this product is used in applications where accidents involving bodily
injury and/or significant damage may be conceivable, measures should
be taken to ensure adequate safety, such as the use of duplicate safety
mechanisms.
D The functions of the GT10 should not be used to design systems which
may pose a threat to human life or which may cause severe injury or
damage. Designs should include safety mechanisms for use in the
event that switch functions do not function correctly.
D Do not use this product in an environment where combustible gases are
present. This can cause explosion.
D This product contains a secondary battery (lithium and vanadium). Do
not dispose of it by incineration. This can cause it to explode.
CAUTION
Erroneous handling of an item marked with this label can cause injury to the
user, or physical damage to property.
D This product should not be used outside of the stated specifications
ranges for ratings, service life, configuration factors and other
elements. This can cause abnormal generation of heat and smoke.
D The operational force of the touch panel should be kept to 0.98 N or
lower. Operating the touch panel at a higher force could cause damage.
D Never touch terminals while the power supply is on. This can cause
electric shock.
D Never disassemble or alter this product. This can cause electric shock
and smoke generation.
How This Manual Is Configured
GT10 Main Unit
Before Using the GT10 for the First Time
This section describes items that should be confirmed and precautions that should
be observed before the GT10 is used for the first time.
Chapter 1. Specifications
This chapter contains the names and specifications of the various parts of the GT10,
as well as a table of functions, wiring diagrams, and dimensions.
Chapter 2. Installation and Wiring
This chapter explains how the GT10 should be installed and how wiring should be
connected.
Chapter 3. Setup
This chapter describes the setup procedures necessary when using the GT10 for the
first time.
Chapter 4. Connecting and Communicating with the PLC
This chapter explains how to connect the GT10 to the PLC and the FP series by
Matsushita, and how to set up communications between the units.
Chapter 5. GT Configuration Settings
This chapter describes the configuration settings for the GT10, and how they should
be entered.
Chapter 6. Using the Various Functions
Functions such as switching GT10 screens, backlighting, and buzzer control are
explained here.
Chapter 7. Servicing and Maintenance
This chapter describes servicing and maintenance procedures for the GT10, as well
as how optional items are handled.
Chapter 8. Troubleshooting
This explains what to do if there appears to be something wrong with the GT10, or an
error occurs.
Chapter 9. Documentation
This section includes BIN/HEX/BCD code correspondence tables, ASCII code tables,
cable specifications, and other information.
Screen Creation Tool Terminal GTWIN
Before Using Terminal GTWIN for the First Time
This section contains special precautions that should be read if you are using GTWIN
for the first time.
Chapter 1. Preparation
This section explains how to install GTWIN in the personal computer, how to boot it,
and how to exit it.
Table of Contents
ii
Table of Contents
GT10 Main Unit
Before Using the GT10 for the First Time
GT10 Usage Procedures
ix
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirming the Package Contents
xi
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GT10 System Configuration
xv
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Products for the GT10 Series
xvii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
An Overview of GT10 Functions
xviii
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions
xxi
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Specifications
1.1
GT10 Specifications
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1
General Specifications
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2
Display
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.3
Functions
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.4
Touch Key
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.5
Memory (1)
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.6
Memory (2)
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.7
Interface
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
Names and Functions of Parts
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1
GT10 (front)
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
GT10 (rear)
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3
Names and Functions of Parts
7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3
Internal Wiring Connections for Ports
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1
COM. Port
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2
TOOL Port
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.3
Power Supply Terminals
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Dimensional Outline Diagram
11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.1
GT10 Dimensional Outline Diagram
11
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2
Panel Cutout Dimensional Outline Diagram
12
. . . . . . . . . . . . . . . . . . . . .
Table of Contents
GT10
iii
Chapter 2
Installation and Wiring
2.1
Installation
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1
Installation Environment
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2
Installation Method
17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
Wiring the Power Supply
19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Wiring the Power Supply
19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3
Wiring the COM. Port
21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1
Wiring the COM. Port
21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2
Wiring Method
22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3
Precautions Concerning Wiring
22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
Setup
3.1
Setup Procedure for the GT10
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1
Setup Procedure
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2
Entering Settings for the Basic Communication Area to PLC
30
. . . . . . . . . . . . . .
3.2.1
What is the Basic Communication Area?
30
. . . . . . . . . . . . . . . . . . . . . . .
3.2.2
Basic Communication Area Map
32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4
Connecting and Communicating with the PLC
4.1
Connecting the FP0
37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1
Connecting to the COM. Port
37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2
Connecting to the TOOL Port
39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2
Connecting the FP1
40
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1
Connecting to the COM. Port
40
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3
Connecting the FP2/FP2SH
41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.1
Connecting to the COM. Port
41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.2
Connecting to the TOOL Port
42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4
Connecting the FP2/FP2SH Computer Communication Unit
43
. . . . . . . . . . . . . .
4.5
Connecting the FP10SH
44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1
Connecting to the COM. Port
44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.2
Connecting to the TOOL Port
46
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6
Connecting the FP10SH/FP3 Computer Communication Unit
47
. . . . . . . . . . . . .
4.7
Connecting the FP-M
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1
Connecting to the COM. Port
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.2
Connecting to the TOOL Port
50
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents
iv
4.8
Automatic Communication Settings Function
51
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9
Through Function
53
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5
GT10 Configuration Settings
5.1
GT10 Configuration Settings
57
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1
Two Types of GT10 Configuration Settings
57
. . . . . . . . . . . . . . . . . . . . . .
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
58
. . . . . . . .
5.2.1
Opening the GT Configuration Settings
58
. . . . . . . . . . . . . . . . . . . . . . . . .
5.2.2
GT Configuration Settings: “Basic Setup”
59
. . . . . . . . . . . . . . . . . . . . . . .
5.2.3
GT Configuration Settings: “Communication Parameters”
61
. . . . . . . . .
5.2.4
GT Configuration Settings: “Auto-Paging”
64
. . . . . . . . . . . . . . . . . . . . . .
5.2.5
GT Configuration Settings: “Startup Screen Settings”
66
. . . . . . . . . . . . .
5.2.6
GT Configuration Settings: “Setup”
68
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.7
GT Configuration Settings: “Hold PLC Device”
71
. . . . . . . . . . . . . . . . . . .
5.3
Entering Configuration Settings from the GT Main Unit
73
. . . . . . . . . . . . . . . . . . .
5.3.1
What is the System Menu?
73
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2
Bringing Up the System Menu
73
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3
Setting Mode: “Communication Parameters”
(COM. Port / TOOL Port)
74
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4
Setting Mode: “Liquid Crystal Display Contrast Adjustment”
(Contrast)
76
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.5
Setting Mode: “Clock Settings” (Clock)
76
. . . . . . . . . . . . . . . . . . . . . . . . .
5.3.6
Setting Mode: “Memory Initialization” (Clear Memory)
78
. . . . . . . . . . . .
5.3.7
Test Mode: “Self-Diagnosis”
79
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.8
Inhibiting the System Menu Display
80
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6
How the Various Functions Are Used
6.1
Switching Screens
83
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.1
Switching the Screen from the PLC
83
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2
Switching the Screen with the GT Main Unit
84
. . . . . . . . . . . . . . . . . . . . .
6.2
Basic Communication Area to PLC and Bit Device Functions
89
. . . . . . . . . . . . .
6.2.1
Bit Device Functions
89
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
all-guides.co
m
Table of Contents
GT10
v
Chapter 7
Servicing and Maintenance
7.1
What the Internal Secondary Battery Does
93
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1
The Function of the Secondary Battery
93
. . . . . . . . . . . . . . . . . . . . . . . . .
7.2
Replacing the Front Panel Protective Sheet
95
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2.1
About the Front Panel Protective Sheet
95
. . . . . . . . . . . . . . . . . . . . . . . .
7.2.2
Replacing the Front Panel Protective Sheet
95
. . . . . . . . . . . . . . . . . . . . .
7.3
Replacing the Waterproof Packing
96
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.1
About the Waterproof Packing
96
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3.2
Replacing the Waterproof Packing
96
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8
Troubleshooting
8.1
What To Do If Something Unusual Occurs
99
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2
Error Codes and How to Handle Them
102
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2.1
About Error Codes
102
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2.2
GT10 Error Codes
102
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2.3
PLC Error Codes
103
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3
Table of Screen Messages
104
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3.1
Table of GT10 Screen Messages
104
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 9
Documentation
9.1
BIN/HEX/BCD Code Correspondence Table
107
. . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2
ASCII Code Table
108
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3
Basic Communication Area Map
109
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4
Dimensional Outline Diagrams
110
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4.1
GT10 Dimensional Outline Diagram
110
. . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4.2
Panel Cutout Dimensional Outline Diagram
111
. . . . . . . . . . . . . . . . . . . .
9.5
Cable Specifications
112
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.5.1
PLC Communication Cable: Mini-DIN 5-pin Loose-Wire
(AIGT8192)
112
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.5.2
PLC Communication Cable: D-sub 9-pin Loose-Wire Cable
(AIP81842)
112
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents
vi
GTWIN
Before Using Terminal GTWIN for the First Time
Precautions Before Using GTWIN for the First Time
116
. . . . . . . . . . . . . . . . . . . . . . . . .
Usage Environment and GT Main Unit Models that are Supported
116
. . . . . . . .
Special Precautions
117
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important Note About Saving Screen Data Files
117
. . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1
Preparation
1.1
Installing GTWIN
121
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1
Procedure for Installing GTWIN in a Personal Computer
121
. . . . . . . . .
1.2
Booting GTWIN
127
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1
Booting GTWIN
127
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
Selecting the Working Menu
127
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3
Selecting the Model
127
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4
Entering Settings for the Basic Communication Area to PLC
128
. . . . .
1.3
Exiting GTWIN
129
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1
Exiting GTWIN
129
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Procedures for Using GTWIN
130
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before Using the GT10 for the First Time
This section describes items that should be confirmed and precautions that should be
observed before the GT10 is used for the first time. Make sure you read this section
before using the GT10.
GT10 Usage Procedures
ix
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirming the Package Contents
xi
. . . . . . . . . . . . . . . . . . . . . . . .
GT10 System Configuration
xv
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Products for the GT10 Series
xvii
. . . . . . . . . . . . . . . . . . . . . . . . . . .
An Overview of GT10 Functions
xviii
. . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions
xxi
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GT10 Usage Procedures
GT10
ix
GT10 Usage Procedures
If you are using the GT10 for the first time, please follow the procedure outlined below.
Procedure For Using the GT10 For the First Time
1. Confirm the items included with the product.
page xi
Please confirm that all of the items have been included with the product you have
purchased. Products are carefully checked before being shipped, but if you do find
anything missing, please contact your dealer.
2. Confirm the items listed under “Safety Precautions”.
page xxi
Before using your product, please make sure you read the items listed under “Safety
Precautions”, in order to make sure your product is used safely. After reading the
precautions, please make sure the product is used correctly.
3. Install and wire the main unit.
page 15
Install the main unit, and connect the power supply, PLC connection cable and other
wiring. When installing and wiring the product, carefully read the explanation on pages
15 to 18 concerning the installation environment, and make sure the product is installed
correctly, in an appropriate environment. For information on connecting the product to
the FP series PLC, and on entering communications settings, please see page 37 and
subsequent pages.
4. Set up the main unit.
page 27
When the product is shipped from the factory, it is set up with specifications that enable
connection to the FP series PLC. If you plan to use the product without changing these
settings, nosetup isrequired, but if youplanto changethe settings, you willneed to follow
the setup procedure outlined on page 27 and subsequent pages. Particularly with regard
to the basic communication area to the PLC and other devices, please confirm the
settings carefully and change only those that are necessary.
J Main cases in which setup is necessary
·
When the device being connected is a general-purpose serial device (such as
a computer or microcomputer board)
·
When the basic communication area for the device is different from that
set when the product is shipped
5. Check communication with the external device (PLC, etc.).
page 37
Check the connections and communication with the external device. Connections and
communication with devices in the FP series PLC vary depending on the device, so
check the information on page 37 and subsequent pages.
6. Enter the operating environment settings.
page 57
In addition to the setup described at step 4, various detailed settings can be entered for
the GT10 operating environment. Enter any necessary operating environment settings,
referring to page 57 and subsequent pages.
7. Install the screen creation tool.
page 116
Install the Terminal GTWIN screen creation tool in the personal computer. Follow the
instructions on page 116 and subsequent pages to install the software.
all-guides.co
m
GT10 Usage Procedures
x
8. Create the screen contents.
Create the screen contents using the Terminal GTWIN screen creation tool, and send
the screen to the GT10 main unit. For information on creating screens and on operating
GTWIN, please refer to the Help function that comes with GTWIN.
9. Test the operation.
Connect the GT10 containing the screen data to an external device (PLC or
general-purpose serial device), and check the operation contents.
Confirming the Package Contents
GT10
xi
Confirming the Package Contents
Check to make sure the necessary items have been included with the product you have
purchased.
Items Included With the GT10 (AIGT1000B)
Main unit
Set of attachment fittings
Attachment fittings x 4
Attachment screws x 4
Front panel protective sheet
There is a front panel protective sheet,
available as an optional product, attached
to the front panel of the unit.
Installation instructions
Please read these instructions carefully before using the product.
Communication connector
Waterproof packing
One piece of waterproof packing
has been attached to unit.
Confirming the Package Contents
xii
CAUTION
• There is a film over the front panel protective sheet. Remove this film
when using the unit. For instructions on removing the film, see page
95.
• Front panel protective sheets for replacement are available as a
separate purchase (AIGT180). Please see page xvii.
• Waterproof packings for replacement are available as a separate
purchase (AIGT181). Please see page xvii.
Confirming the Package Contents
GT10
xiii
Items Included With the Terminal GTWIN English-language version
(AIGT8001)
Terminal GTWIN CD-ROM
Screen Transfer Cable (AFC8503)
AFC8503
(3 m/9.84 ft)
Software usage license agreement and user card
Read the “Software usage license agreement” carefully, and fill in the user card. Please
return the user card to Matsushita.
GT10 Technical Manual
This is the manual you are currently reading. It contains instructions on installing and
booting GTWIN. Please read it carefully before using your product.
CAUTION
About the software usage license agreement and user card
• Before using GTWIN, read the “Software usage license agreement”
carefully.
• The license agreement comes as a set with the user card. Fill in the
user card, and return it to Matsushita. The user card is necessary in
order to obtain support services such as future version upgrades and
technical support. Don’t forget to return the card in order to be
eligible for such services.
• The serial number needed in order to install GTWIN is found on the
user card. Please make a copy of it before returning the card, and
keep it in a safe place.
Confirming the Package Contents
xiv
Items Included With the PLC Connection Cable (AIGT8192 / AIP81842)
Cable
One of the following two cables has been included with the product you have purchased.
AIGT8192
(2 m/6.56 ft)
AIP81842
(2 m/6.56 ft)
Wiring diagram
The package includes a diagram that shows the internal wiring of the cables pictured
above.
REFERENCE
For information on connecting and wiring the cables shown above and
the PLC, please refer to page 35, Chapter 4, “Connecting and
Communicating With the PLC”.
Items Included With the Front Panel Protective Sheet (AIGT180)
Front panel protective sheet
In order to protect the touch panel on the GT10 and keep it clean, one front panel
protective sheet is included when the unit is shipped. If this front panel protective sheet
is dirty or has become worn, it should be replaced. Replacement sheets are sold
separately, in packages of ten.
Installation instructions
Please read these instructions carefully before installing the product.
REFERENCE
For information on replacing the front panel protective sheet, please
refer to page 95.
all-guides.co
m
GT10 System Configuration
GT10
xv
GT10 System Configuration
The following devices are necessary in order to use the GT10.
Connecting cable
Screen transfer cable
D-sub 9-pin -
mini-DIN 5-pin
(3 m/9.84 ft)
Product No.: AFC8503
* One cable is included
with GTWIN English-lan-
guage version.
Commercially available
personal computer
Screen creation tool
Terminal GTWIN
English-language version
Windows 95/98/2000/NT supported
GTWIN CD-ROM
Screen transfer cable (AFC8503)
GT10 Technical Manual included as
accessory
Product No.: AIGT8001
GT10
STN monochrome liquid crystal display
Product No.: AIGT1000B
Main unit
Communication cable
PLC connecting cable (1)
For connection to TOOL port of FP0 / FP2 /
FP2SH / FP-M
Mini-DIN 5-pin loose-wire cable
(2 m/6.56 ft)
Product No.: AIGT8192
Connecting to the TOOL port of the FP0 /
FP2 / FP2SH / FP-M
Communication cable
PLC connecting cable (2)
For connection to COM. port of FP1 / FP2 / FP2SH / FP-M /
FP10SH, TOOL port of FP10SH, and computer communication unit
of FP2 / FP3
D-sub 9-pin loose-wire cable (2 m/6.56 ft)
Product No.: AIP81842
Connecting to the COM. port of FP1 / FP2 / FP2SH / FP-M / FP10SH,
TOOL port of FP10SH, and computer communication unit of FP2/FP3
GT10 System Configuration
xvi
CAUTION
Connecting to the COM. port of the FP0
Because connecting the unit to the COM. port of the FP0 requires a
loose-wire connection, this cable is not available. For more detailed
information, please see “Connecting the FP0” on page 37.
Products for the GT10 Series
GT10
xvii
Products for the GT10 Series
Products types
Item Name
Contents
Product No.
GT10 main unit
Programmable display unit
GT10 main unit
AIGT1000B
Terminal GTWIN
English-language
version
- “Terminal GTWIN” English-language screen creation tool
(CD-ROM)
- Set of GT10 Technical manuals (English)
AIGT8001
Screen transfer
cable
Cable for transferring cable between GTWIN and GT10
(included with Terminal GTWIN English-language version)
(3 m/9.84 ft)
AFC8503
PLC connecting
cable (1)
For connection to TOOL port of FP0 / FP2 / FP2SH / FP-M
Mini-DIN 5-pin loose-wire cable (2 m/6.56 ft)
AIGT8192
PLC connecting
cable (2)
For connection to COM. port of FP1 / FP2 / FP2SH / FP-M /
FP10SH, TOOL port of FP10SH, and computer communication
unit of FP2 / FP3
D-sub 9-pin loose-wire cable (2 m/6.56 ft)
AIP81842
Front panel
protective sheet
Front panel protective sheet for GT10 (for replacement).
Ten in set.
* 1 sheet included with GT10 when shipped.
AIGT180
Waterproof
packing
Waterproof packing for GT10 (for replacement). Ten in set.
* 1 piece included with GT10 when shipped.
AIGT181
CAUTION
• Connecting to the COM. port of the FP0
Because connecting the unit to the COM. port of the FP0 requires a
loose-wire connection, this cable is not available. For more detailed
information, please see “Connecting the FP0” on page 37.
• About the manual packed with the Terminal GTWIN English-language
version
The manual you are currently reading is included as an accessory
with the Terminal GTWIN English-language version. This manual
contains information only on procedures such as installing GTWIN.
For detailed information on operating GTWIN, please refer to the Help
function in the software.
An Overview of GT10 Functions
xviii
An Overview of GT10 Functions
3 colors can be displayed, to reflect the status
Various messages and graphics can be displayed on the liquid crystal display screen,
which measures 160 x 64 dots, as well as lamps, internal PLC data, graphs, clocks, and
other information. In addition,backlighting isavailableinthree colors, green, orange, and
red, so that information can be color-coded. This makes it easy to grasp information at
a glance.
Red
Green
Orange
High-resolution touch panel provided
A compact touch panel is provided with on-screen switches and a keyboard, letting you
operate the unit simply by touching the screen. This high-resolution touch panel is fitted
with 20 horizontal and 8 vertical segments, so that numerous switches can be used, and
allows maximum flexibility in the switch layout.
An Overview of GT10 Functions
GT10
xix
Screens can be created easily, using special tools
Screen contents can be easily created using the dedicated Terminal GTWIN tool (runs
on Windows 95/98/2000/NT). Screens are put together simply by selecting parts from
a library and positioning them in place.
all-guides.co
m
An Overview of GT10 Functions
xx
Ultra-thin body is only 32 mm/1.26 inch deep
The in-panel depth is a mere 32 mm/1.26 inch (including the fittings), configuring an
ultra-thin body and taking up a bare minimum of space.
32 mm/1.26 inch
Through function is convenient for debugging
If connectionsare made as shown inthe diagram, a convenient“through” functionmakes
it possible to transfer data from the GT10 and carry out PLC debugging at the same time
that communication is going on between the GT10 and the FP series PLC. This
significantly boosts efficiency in the workplace.
PLC
GT10
Cable connected to
COM or TOOL port
of PLC
Screen
transfer
cable
AFC8503
PLC debugging
Screen data
being sent
and received
Screen creation tool GTWIN
FP series programming tool
FPWIN GR
Personal computer
The FPWIN GR and NPST-GR
can be booted on the computer
being used to edit GT10 screens,
and PLC programs edited and
monitored through the GT10.
Maintenance is easier than ever before
LEDs are used for backlighting, eliminating the fuss and bother of replacement. Screen
data is saved to an F-ROM, while other data is backed up by an internal secondary
battery, so nobattery replacement isneeded. Thisassures long-term, stable usewithout
worrying about lost data.
Before installing, operating, servicing or inspecting this product, please make sure you
have read this manual and the installation instructions, and make sure the product is
used correctly.
This manual uses two safety standard levels: “WARNING” and “CAUTION”.
WARNING
Erroneous handling of an item marked with this label can cause fatal or critical injury to
the user.
• If this product is used in applications where accidents involving
bodily injury and/or significant damage may be conceivable,
measures should be taken to ensure adequate safety, such as the
use of duplicate safety mechanisms.
• The functions of the GT10 should not be used to design systems
which may pose a threat to human life or which may cause severe
injury or damage. Designs should include safety mechanisms for
use in the event that switch functions malfunction.
• Do not use this product in an environment where combustible gases
are present. (This can cause explosion.)
• This product contains a secondary battery (lithium and vanadium).
Do not dispose of it by incineration. (This can cause it to explode.)
CAUTION
Erroneous handling of an item marked with this label can cause injury to the user, or
physical damage to property.
• This product should not be used outside of the stated specifications
ranges for ratings, service life, configuration factors and other
elements. (This can cause abnormal generation of heat and
smoke.)
• The operational force of the touch panel should be kept to 0.98 N or
lower. Operating the touch panel at a higher force could cause
damage.
• Never touch terminals while the power supply is on. (This can cause
electric shock.)
• Never disassemble or alter this product. (This can cause electric
shock and smoke generation.)
Maximum attention has been given to quality control of this product; however:
(1) In order to prevent, as much as possible, unexpected situations not covered by these
specifications, please consult us regarding your product’s specifications and demands,
as well as this unit’s operating conditions and installation details.
(2) To avoid the unlikely event of a situation attributed to inferior quality of the unit which
has serious adverse affects on persons or property, the numeric values for guaranteed
characteristics and performance noted in this specifications manual should be
considered the minimum necessary values. As the manufacturer of this unit, we
recommend incorporating additional safety measures such as duplicate circuits
wherever possible.
(3) The quality of this product is guaranteed for one year after purchase, and this
guarantee is limited to the range of items stated in these specifications. In the case of
a defect in the product which is clearly Matsushita’s responsibility, we will offer a
replacement unit or replacement of the defective part(s) of the unit and we will repair the
unit promptly at the place of purchase. The following are not included in the warranty:
1. Other damage resulting from damage to or defects in the supplied product.
2. Problems caused by conditions other than those noted in these specifications
involving use, storage, or shipment (transport) after product delivery.
3. Developments which were unforeseeable given the technology in practical use prior
to product delivery.
4. Earthquake, flood, fire, war, and damage due to other naturally occurring events or
human disasters for which Matsushita bears no responsibility.
This chapter contains the names and specifications of the various parts of the GT10, as
well as a table of functions, wiring diagrams, and dimensions.
1.1
GT10 Specifications
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1
General Specifications
3
. . . . . . . . . . . . . . . . . . . . . .
1.1.2
Display
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.3
Functions
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.4
Touch Key
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.5
Memory (1)
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.6
Memory (2)
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.7
Interface
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
Names and Functions of Parts
6
. . . . . . . . . . . . . . . . . . . . . . .
1.2.1
GT10 (front)
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
GT10 (rear)
6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3
Names and Functions of Parts
7
. . . . . . . . . . . . . . .
1.3
Internal Wiring Connections for Ports
9
. . . . . . . . . . . . . . . . .
1.3.1
COM. Port
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2
TOOL Port
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.3
Power Supply Terminals
10
. . . . . . . . . . . . . . . . . . . .
1.4
Dimensional Outline Diagram
11
. . . . . . . . . . . . . . . . . . . . . . .
1.4.1
GT10 Dimensional Outline Diagram
11
. . . . . . . . . .
1.4.2
Panel Cutout Dimensional Outline Diagram
12
. . .
Operating voltage range
21.6 to 26.4V DC
Power consumption
5 W max.
Ambient temperature
0°C to 40°C/32°F to 104°F (25V DC max. if installed horizontally)
Ambient humidity
20% RH to 85% RH (non condensing)
Storage temperature
-20°C to 60°C/-4°F to 140°F
Storage humidity
10% RH to 85% RH (non condensing)
Vibration resistance
10Hz to 55 Hz (1-minute cycle)
Amplitude: 0.75 mm, 10 min on 3axes
Shock resistance
98 m/s2 min., 4 times on 3axes
Noise immunity
1,000 V [p-p] min., pulse width 50 ns, 1 μs between power supply terminals (based
on noise simulator)
Static noise resistance
5,000 V min. (panel display)
Protective construction
IP65 (in initial status)
Dustproof and drip-proof from front panel only (packing used on panel contact sur-
face)
* When reattaching, replace waterproof packing.
Mass
Approx. 260 g/9.171 oz
1.1.2
Display
Item
Specifications
Display
STN monochrome LCD
Resolution
160 (W) x 64 (H) dots
Displayable area
92.8 (W) x 37.1 (H) mm 3.65(W) inch x 1.46 (H) inch
LCD life
Average: 50,000 hours (at normal temperature of 25°C)
Backlight
3-color LED backlight (green, red, orange) * No replacement necessary
1/4 width, half width, full width characters
Half width and full width characters can be displayed at same width, doubled width,
or quadrupled width
(Widths of 2 x 2 times or more can be displayed in high-quality font display.)
Character types
Alphanumeric characters
Graphics
Straight lines, continuous straight lines, squares, circles, ovals, arcs, elliptic arcs, fan
shapes, elliptic fan shapes, beveled squares, bitmaps
Number of screens
Approx. 160 screens
Screen numbers that can be set: Base screens No. 00 to FF (HEX)
(Number of screens that can be registered varies depending on registered contents.)
Part functions
Messages, lamps, switches, data, bar graphs, clocks, keyboard
Clock functions
Clock built into main unit (can also be displayed with reference to PLC clock)
Contrast adjustment
Contrast can be adjusted using touch panel operation (10 stages)
Automatic communication
settings
Settings for communication between dedicated software and PLC set automatically
by connecting cable
Debugging functions
Through function (PLC can be debugged from personal computer by connecting
computer to TOOL port and PLC to COM. port)
Screen creation
Dedicated software Terminal GTWIN used.
Applicable OS: Windows 95/98/2000/NT (Ver. 4.0 or later )
1.1.4
Touch Key
Item
Specifications
Touch key resolution
20 (W) x 8 (H)
Touch key operation
0.98 N max.
Touch key life
Min. 106
1.1.5
Memory (1)
Screen data and GTWIN Configuration Settings data
Item
Specifications
Memory type
F-ROM
Memory capacity
384 kbytes
1.1.6
Memory (2)
Clock data and PLC device storage data (24 words max.)
Item
Specifications
Memory
SRAM
Memory backup
Backed up by internal secondary battery (charged when power is on)
(Note) When using, set operation mode switch on back of main unit to “ON” position.
Conforms to RS232C
COM.
Port
Conditions for
communications with
external devices
Baud rate: 9600, 19200, 38400, 57600, 76800, 115200 bits/s
Data bits: 7 or 8 bits
Parity: None, Odd, Even
Stop bits: 1 bit
Protocol
FP series supported/general-purpose RS232C supported
Connector
Connector terminal base (5-pin)
Communications ratings
Conforms to RS232C
TOOL
port
Conditions for
communications with
external devices
Baud rate: 9600, 19200, 115200 bits/s
Data bits: 8 bits
Parity: None, Odd, Even
Stop bits: 1 bit
Protocol
Dedicated protocol
Connector
Mini-DIN (5-pin)
Names and Functions of Parts
1.2
Names and Functions of Parts
1.2.1
GT10 (front)
●
Liquid crystal display panel
(touch panel)
1
●Front panel protective sheet
(one sheet is attached to unit when
unit is shipped)
2
1.2.2
GT10 (rear)
●
●
●
●
Power supply terminal
COM. port (PLC/external device connection port)
(1 communication connector provided as accessory
when unit is shipped)
Waterproof packing
(1 piece is attached to unit when
unit is shipped)
TOOL port (connection port for GTWIN
screen creation tool)
7
5
4
3
●6 Operation mode setting switches
Names and Functions of Parts
1.2.3
Names and Functions of Parts
(1) Liquid crystal display panel / touch panel
Various screens are displayed here. A touch panel is provided on the liquid crystal
display panel, and switches can be operated and data entered simply by touching the
panel.
(2) Front panel protective sheet
This protects the touch panel and keeps it clean. One sheet is attached to the panelwhen
the unit is shipped.
(3) Power supply terminal
The operation power supply is connected here.
(4) COM. port (PLC/external device connection port)
A device such as a PLC, a higher-order computer, or a microcomputer board can be
connected to this RS232C port. (One communication connector is provided as an
accessory when the unit is shipped.)
(5) TOOL port (GTWIN connection port)
This port is used to connect a personal computer in which the screen creation tool
GTWIN has been installed, using a dedicated cable (AFC8503).
(6) Operation mode setting switches
With the GT10, screen data and configuration settings data are stored in an internal
F-ROM, so no battery backup is needed. However, data such as clock data and the Hold
PLC Device Data is stored in the internal SRAM, and is backed up by the internal
secondary battery, which is charged when the power supply is turned on.
The operation mode setting switches control the ON/OFF settings for the secondary
battery backup function, the ability to shift to the system menu, and other functions.
Switch no.
Function
OFF
ON
1
SRAM backup using
secondary battery
No
Yes
2
Inhibits system menu shift
Shift possible
Shift inhibited
3
Usage inhibited
Should always be in the OFF position
when unit is used
4
when unit is used
(7) Waterproof packing
This assures that the front panel is waterproof. One piece is provided as an accessory
when the unit is shipped.
ON
OFF
4
3
MODE
1
2
Operation mode setting
switches
(settings when shipped)
all-guides.co
m
Names and Functions of Parts
CAUTION
SRAM backup by the secondary battery
When the unit is shipped, the No. 1 operation mode setting switch is set
to the “OFF” psosition, in order to prevent excessive discharging of the
secondary battery. Before using the unit, turn on the No. 1 operation
mode setting switch on the back of the main unit, to turn on the SRAM
backup function of the secondary battery. For detailed information on
the secondary battery, please see page 93, “What the Internal Secondary
Battery Does”.
1.3 Internal Wiring Connections for Ports
1.3
Internal Wiring Connections for Ports
1.3.1
COM. Port
When connecting the unit to the FP series, there is
no need to wire both the RS and CS.
Wiring and cables should be laid out in such a way
that cables are not affected by external noise. Also,
shielded wiring should be used for cables.
SD
RD
RS
CS
GND
1.3.2
TOOL Port
Pin No.
Contents
1
SG
2
SD
3
RD
4
N.C.
5
(+5 V)
The +5 V of Pin 5 is reserved for the FP
Programmer II. It should not be used for
any other application.
1
2
4
5
3
Internal Wiring Connections for Ports
1.3.3
Power Supply Terminals
Maker
Shape
Model
Applicable wiring
Tightening
torque
Round
1.25-MS3
0.25 mm2 to 1.65 mm2 0.5 N⋅m
JST Mfg.
Front-opening
1.25-B3A
JST Mfg.
Co., Ltd.
Round
2-MS3
1.04 mm2 to 2.63 mm2
Front-opening
2-N3A
Applicable crimp terminals
- The terminal screws are M3 screws. We recommend using crimp terminals for
wiring to terminals.
Open-tip terminals
Round terminals
The tightening torque for terminal base screws should be
between 0.5 and 0.6 N·m, or less. Operating at a higher
force could cause damage.
If crimp terminals are not being used, wire with a diameter
of 0.5 mm2 to 1.25 mm2 should be used for power cables.
In keeping with the European EMC Directive (EMC Direc-
tive 89/336/EEC), the GT10 conforms to European Stan-
dards (EN50081-2:1993, EN50082-2:1995). As a condi-
tion of compatible, a ferrite core should be installed when
wiring to the terminal base (Seiwa Electric Mfg. Co., Ltd.
E04RC281613 or equivalent).
Ferrite core
+24 V
0 V
F.E.
6.0 mm
max.
6.0 mm
max.
Dimensional Outline Diagram
1.4
Dimensional Outline Diagram
1.4.1
GT10 Dimensional Outline Diagram
144/5.67
32/1.26
138.0/5.43
80/3.15
4/0.16
97/3.82
60/2.36
40/1.57
72/2.83
65.8/2.59
9.6/0.38
(7/0.28)
8.5/0.33
2/0.08
(Unit: mm/inch)
(Display unit)
(Display unit)
(Packing)
(7/0.28)
Dimensional Outline Diagram
1.4.2
Panel Cutout Dimensional Outline Diagram
The panel cutout dimensions of the GT10 are as shown below.
/5.47
/2.64
+
0
0
Applicable panel thickness: 1.0 to 6.0/0.002 to 0.236
(Unit: mm/inch)
1
1
+
139
+
0
0.04
67
0
0.04
+
all-guides.co
m
Installation and Wiring
This chapter explains how the GT10 should be installed and how wiring should be
connected.
2.1
Installation
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1
Installation Environment
15
. . . . . . . . . . . . . . . . . . . .
2.1.2
Installation Method
17
. . . . . . . . . . . . . . . . . . . . . . . .
2.2
Wiring the Power Supply
19
. . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Wiring the Power Supply
19
. . . . . . . . . . . . . . . . . . .
2.3
Wiring the COM. Port
21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1
Wiring the COM. Port
21
. . . . . . . . . . . . . . . . . . . . . .
2.3.2
Wiring Method
22
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3
Precautions Concerning Wiring
22
. . . . . . . . . . . . . .
Installation and Wiring
GT10
15
2.1
Installation
2.1
Installation
2.1.1
Installation Environment
When installing and using the GT10, always make sure the following conditions are
observed.
Usage Conditions
When installing the product, make sure it is used within the range of the general
specifications. Do not use in the following environments:
-
Areas where the unit may come in contact with water (the unit is warranted by
IP65 for the installed panel, but this applies to initial values and operation cannot
be guaranteed in areas where the unit is constantly subjected to water or to
extreme temperatures or humidity).
-
Areas where the ambient temperature exceeds the range 0°C to 40°C/32°F to
104°F.
-
Areas where the ambient humidity exceeds 20% RH to 85% RH.
-
If the control panel and other parts are installed in an environment where the air
tends to be poorly ventilated, forced cooling should be used to keep the ambient
temperature of the from going over 40°C/104°F. This prevents the temperature of
the GT10 display unit from rising.
-
Locations where condensation may form because of sudden fluctuations in
temperature.
-
Locations where flammable or corrosive gases are present.
-
Locations where there are high concentrations of dust or iron filings.
-
Locations where substances such as organic solvents (thinner, benzene, etc.) or
strong alkali substances (ammonia, caustic soda, etc.) might adhere to the
product.
-
Locations where the product is subject to extreme vibration and/or impact.
-
Avoid installing the product near high-voltage lines, high-voltage devices, power
lines, power devices, amateur radio sets and other transmitters, and devices that
generate strong current surges.
-
Avoid locations where the display unit is subject to direct sunlight.
Safety Precautions
-
The switch functions of the programmable display unit should not be used to
design systems which may pose a threat to human life or which may cause
severe injury or damage. Designs should include safety mechanisms for use in
the event that switch functions do not function correctly.
Installation and Wiring
16
2.1
Installation
Power Supply Wiring
-
For the power supply, use twisted wire (strand wire).
-
There is sufficient noise resistance to offset power line noise, but we recommend
reducing noise by measures such as installing an insulated transformer.
-
Separate wiring systems should be used for the power supply unit and the
operating unit.
Static Electricity/Noise
-
Keep the GT10 main unit, PLC connecting cable, and other wiring as far away as
possible from machines which are likely to produce noise (welding equipment,
power lines, inverters, motors, etc.).
-
For use in environments where the frequent occurrence of static electricity,
radiation, or induced noise can be expected, the use of shielded cable on all
wiring and grounding of shield (1-point ground) is recommended. When wiring
the equipment, shielded wires should be electrically insulated to signal lines and
signal grounds.
-
If excessive static electricity is applied to the panel surface, the LCD display unit
may be damaged.
Secondary Battery Service Life
-
The service life of the internal secondary battery is just under 2 years when used
in ambient operating temperatures of more than 40°C/104°F or when the
operating voltage exceeds 25V DC. Use caution when using the clock and device
hold area functions.
Other Precautions
-
Do not leave the GT10 connected to the TOOL port of the FP Programmer II.
-
Always operate the touch panel with your fingers. Excessive load (about 98
N/cm2 ) or impact (operating with tools, etc.) will cause damage. Touch panel
operation must be within the standard operating power range. Uniform pressure
should be used to avoid abnormal wear of electrodes which may disable
operation. Operate the unit only by touch.
-
Never dismantle, re-assemble, or alter the unit. Performance cannot be
warranted if this precaution is disregarded.
Installation and Wiring
GT10
17
2.1
Installation
2.1.2
Installation Method
Secure the GT10 to the installation panel using the four fittings and four screws
provided with the unit.
(1) Place the GT10 main unit in the installation panel.
(2) Insert the fittings into the grooves provided in the GT10 main unit, and tighten
the screws to secure the GT10 main unit to the installation panel.
Enlarged view
Four fittings and four screws provided
with the unit
CAUTION
• Screw tightening torque
The screw tightening torque should be 10 N⋅cm to 25 N⋅cm.
• Applicable panel thickness
A panel with a thickness of 1.0 mm to 6.0 mm should be used.
• Installation angle
If the installation angle is between 60 degrees and 0 degrees
(horizontal), the operating voltage should be set to 25V DC or lower.
Installation angle
next page
all-guides.co
m
Installation and Wiring
18
2.1
Installation
• Clearance when the GT10 is installed
When installing the GT10, if other parts are being installed to the
panel or cables are being wired to it, we recommend providing a
clearance of 30 mm to 50 mm/1.18 inch to 1.97 inch around the GT10.
This prevents cables from being damaged, and facilitates the
installation work. Also, make sure that the slits in the main unit are
never obstructed.
Installation and Wiring
GT10
19
2.2
Wiring the Power Supply
2.2
Wiring the Power Supply
2.2.1
Wiring the Power Supply
The power supply should be wired by securely connecting the terminal on the rear of
the main unit to the terminal shown below. Always use crimp terminals for wiring.
+24 V
0 V
(D-type ground)
F. E.
Use twisted wiring for the power supply
In order to minimize influence from noise, the wiring for the power supply should be
twisted.
Insulate the power supply inside a protective circuit
- In order to protect the unit against abnormal voltage from the power supply line, the
power supply should be an insulated type, and should be enclosed within a protective
circuit.
- A non-insulated regulator is used with the GT10.
- If a power supply device without an internal protective circuit is being used, power
should always be supplied to the GT10 through a fuse or a similar protective device.
Keep the power supply voltage within the operating voltage range
Operating voltage range
21.6 to 26.4V DC
Use M3 crimp terminals
- The terminal screws are M3 screws. We recommend using crimp terminals for wiring
to terminals.
Maker
Shape
Model
Applicable
wiring
Tightening
torque
Round
1.25-MS3
0.25 mm2 to
1 65 mm2
0.5 N·m
JST Mfg. Front-opening
1.25-B3A
1.65 mm2
JST Mfg.
Co., Ltd. Round
2-MS3
1.04 mm2 to
2 63 mm2
Front-opening
2-N3A
2.63 mm2
6.0 mm
max.
6.0 mm
max.
The tightening torque for terminal
base screws should be between 0.5
and 0.6 N·m, or less. Operating at a
higher force could cause damage.
If crimp terminals are not being
used, wire with a diameter of 0.5
mm2 to 1.25 mm2 should be used
for power cables.
For precautions concerning con-
formance to European EMC di-
rectives, please see “Power
Supply Terminals” on page 10.
Open-tip terminals
Round terminals
Installation and Wiring
20
2.2
Wiring the Power Supply
Keep the power supply wiring separate
- Wiring to the GT10, PLC, and other power equipment should have separate wiring
systems.
PLC
GT10
Breaker
Power
equipment
Insulated DC
power supply
Installation and Wiring
GT10
21
2.3
Wiring the COM. Port
2.3
Wiring the COM. Port
2.3.1
Wiring the COM. Port
Accessory communication connector/applicable wiring
The communication connector used for the COM. port (provided as an accessory with
the main unit) has a screw-tightening type of terminal base. The wiring shown below
should be used.
Accessory communication connector
The communication connector is made by Fenics Contact Co., Ltd.
No of pins
Fenics Model No.
No. of pins
Model No.
Product No.
5-pin
MC1, 5/5-ST-3,5
1840396
Applicable wiring (twisted wiring)
Size
Conductor Cross-Section Surface Area
AGW#28 to 16
0.08 mm2 to 1.25 mm2
Applicable stick-type terminals with insulated sleeves
If stick-type terminals are used, the models listed below are marketed by Fenics
Contact Co., Ltd.
Maker
Cross-Section Surface
Size
Fenics Co. Model
0.25 mm2
AGW#24
AI 0,25 to 6 YE
Fenics Contact
0.50 mm2
AGW#20
AI 0,50 to 6 WH
Fenics Contact
Co., Ltd.
0.75 mm2
AGW#18
AI 0,75 to 6 GY
1.00 mm2
AGW#18
AI 1 to 6 RD
Crimp tools for stick-type terminals
Maker
Fenics Model No.
Maker
Model No.
Product No.
Fenics Contact Co., Ltd. CRIMPFOX UD6
1204436
Installation and Wiring
22
2.3
Wiring the COM. Port
Use a special tool to tighten the terminal base of the communication connector
Tightening of terminals should be done using a screwdriver made by Fenics Contact
Co., Ltd. (Fenics mfg. no. 1205037, blade width 0.4 x 2.5, model no. SZS 0.4 x 2.5), or
a screwdriver made by Matsushita Electric Works Co., Ltd. (Product number AFP0806).
The tightening torque should be 0.22 N·m to 0.25 N·m or less.
2.3.2
Wiring Method
(1) Remove the sheath from the wire.
7 mm/0.28 inch
(2) Insert the wire all the way into the terminal base, and tighten the screw in the
clockwise direction to secure it.
2.3.3
Precautions Concerning Wiring
The following precautions should be observed, to avoid broken or disconnected wires.
-
When removing the sheath, be careful not to scratch the core wire.
-
Wire the terminal without twisting the core wire.
-
The core wire should be connected without soldering it. Vibration can sometimes
cause soldered connections to break loose.
-
After connecting the wiring, avoid subjecting the cable to stress.
-
Because of the construction of the terminal, tightening the wire in the
counterclockwise direction will cause a faulty connection. If this happens,
disconnect the wire, check the terminal hole, and connect the wire again.
Counterclockwise
Clockwise
all-guides.co
m
Installation and Wiring
GT10
23
2.3
Wiring the COM. Port
REFERENCE
For information on connecting the COM. port of the GT10 with various
PLC units, please see Chapter 4, “Connecting and Communicating With
the PLC”, on page 35.
This chapter describes the setup procedures necessary when using the GT10 for the
first time.
3.1
Setup Procedure for the GT10
27
. . . . . . . . . . . . . . . . . . . . . .
3.1.1
Setup Procedure
27
. . . . . . . . . . . . . . . . . . . . . . . . . .
3.2
Entering Settings for the Basic Communication
Area to PLC
30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1
What is the Basic Communication Area?
30
. . . . .
3.2.2
Basic Communication Area Map
32
. . . . . . . . . . . . .
Setup Procedure for the GT10
3.1
Setup Procedure for the GT10
3.1.1
Setup Procedure
The GT10 should be set up using the procedure outlined below.
(1) Setting the “Configuration File” with GTWIN
The GT10 has an internal file called the “Configuration file”, which is used to determine
various operating environment parameters. When the GT10 is shipped from the factory,
the settings listed below are set for the parameters in the configuration settings file. If
changes are made to these settings, they are made from GTWIN screen creation tool.
(For detailed information on changing settings, see page 58 and subsequent pages.)
If the GT10 is being used without changing the factory settings, the following setup
procedure is not necessary.
Contents of configuration settings when shipped from the factory
Classification
Item
Setting contents
Basic Setup
Area for basic
communication
with PLC
Mode
: GT10 mode
Word area: DT0 to DT2
Bit area
: WR0 to WR2
Communication
parameter
COM. port
Communication speed: 19200 bits/s, data length: 8 bits, stop bit: 1 bit, parity: odd
Retries: 3, error code displayed
(not held)
parameter
settings
TOOL port
Communication speed: 19200 bits/s, data length: 8 bits, stop bit: 1 bit, parity: odd
None
Auto paging
Automatic paging
No
Startup screen
Startup screen
No. 00
Startup screen
settings
Rise delay time
0 seconds
Clock
GT main unit clock / external transmission: No
Other settings
Backlight control
Not turned off automatically
Other settings
Touch operation
sounds
Valid
Hold PLC Device Holds a PLC device Not held
Always confirm “Basic communication area to PLC” under “Basic Setup”
This is an internal device area that comes already provided in the GT10 for the purpose
of communicating with a PLC. If the factory settings are to be changed, the setup
procedure must be carried out. For detailed information, please see page 30.
(2) Connect the GT10 and the personal computer.
After the settings have been entered with GTWIN, connect the computer and the GT10,
using the screen transfer cable.
GTWIN
GT10
Screen transfer cable
(AFC8503)
all-guides.co
m
Setup Procedure for the GT10
(3) Transfer the GT10 Configuration file from GTWIN.
After connections have been completed, use the following procedure to transfer the
GT10 Configuration file from GTWIN.
Boot GTWIN, and select “Transfer” on the “File” menu.
When the transfer function is selected, a dialog box for file transfer is displayed.
At this point, specify the type of data to be transferred, and the direction of
transfer.
Transfer data: “GT10 Configuration”
Transfer direction: “GTWIN →GT main unit”
Enter the above conditions and click on the “OK” button. The system files are
transferred to the GT10.
Setup Procedure for the GT10
When the menu operation as shown at the left page is carried out, the configuration file
is sent to the GT10. During the transfer, a screen like that shown below is displayed.
GTWIN
GT10
Transferring
PC→GT
GT10 Configuration
file being transferred
Screen transfer cable
(AFC8503)
(4) Setup is completed.
If the transfer has been completed without any problems, the setup is completed.
CAUTION
Backup of the GT10 Configuration file
The GT10 Configuration file is stored in the user memory (F-ROM) of the
GT10. This file is deleted if the memory is initialized using the command
on the system menu of the GT10 main unit (see page 78), and will have
to be transferred again.
Entering Settings for the Basic Communication Area to PLC
3.2
Entering Settings for the Basic Communication Area
to PLC
3.2.1
What is the Basic Communication Area?
Communication between the GT10 and PLC is carried out as shown below.
GT10
PLC
Internal PLC devices
Part reference / output device
For part functions
(free device specification)
Basic communication area
For screen switching settings and system
control
(word device / bit device: 3 words each)
Ongoing
Communication
As shown in the illustration, communication is carried out on an ongoing basis between
the GT10 and internal devices in the PLC. Internal PLC devices are divided into the
following two devices:
Basic communication area
This area is for system control, such as screen switching settings. PLC devices belong
to this area on a fixed basis, and communication is constantly being carried out.
Breakdown of the basic communication area
Word devices (DT, FL, etc.)
3 consecutive words
Bit devices (WR, etc.)
3 consecutive words
-
Word devices - - - For reading devices handled in word units (3 consecutive words)
-
Bit devices - - - For reading devices handled in bit units (3 consecutive words)
References and output devices for parts
These are devices that are used in parts functions, and can be freely specified by the
user. Communication is carried out on an ongoing basis only for those that are currently
displayed on the screen and pertain to devices currently in use.
With the GT10, before GTWIN screen creation tool is used to specify the devices for
parts functions, the “basic communication area” must be determined.
DT0 to DT2 and WR0 to WR2 are set as the default values for the basic communication
area, but the initial address can be changed using the following procedure.
CAUTION
The basic communication area should not be used in PLC ladder
programs.
3.2 Entering Settings for the Basic Communication Area to PLC
Settings in GTWIN
Select “Configuration” under “File” on the menu bar, and then select the sub-menu
called “GTWIN Configuration”. This displays the dialog box for the GT10 Basic Setup,
as shown below.
Clicking on the
button in “Basic Communication Area to PLC” displays the device
settings dialog box shown below, where the initial addresses for the word area and bit
area can be changed.
GT10 Configuration
Basic Setup dialog box
Explanation of this function
Key operation in the Device Settings dialog box
Click on the
button to display a pull-down menu, and then select
the device for which settings are to be entered. Use the ten-keys to
enter the address.
The
button acts as a backspace key when entering an address,
and the
button functions as a Clear key.
Entering Settings for the Basic Communication Area to PLC
3.2.2
Basic Communication Area Map
In order for communication to be carried out between the GT10 and PLC, an internal
device area like that shown below is provided in the PLC. This field should not be used
in the ladder programs of PLCs in actual operation.
The starting address “N” of the field shown below is specified in the GT10 configuration
settings of GTWIN screen creation tool, and is then sent to the GT main unit.
Word devices
Word position
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
N+0
Screen no. specified by PLC (area read by GT10 from PLC)
N+1
Usage prohibited
N+2
No. of currently displayed screen (area in which data is written from GT10 to PLC)
Explanation of system area
Screen no. specified by PLC - - - The screen number displayed on the GT10 is
specified from the PLC in hexadecimal format.
No. of currently displayed screen - - - The number of the screen currently
displayed on the GT10 is written to the PLC in hexadecimal format.
Bit devices
Word
position
F
E
D
C
B
A
9 8 7 6 5 4 3 2 1
0
N+0
BZ
Forced-
display flag
Backlight
Valid flag
Backlight
Flashing
Backlight
Color
N+1
Usage prohibited
N+2
BAT
Data Input In
Progress flag
Explanation of system areas
BZ - - - This turns on the buzzer.
Forced-Display flag - - - At the rise when the bit is turned on, the screen specified by
the PLC is forcibly displayed. (This is executed only when at the rise of the bit.)
Backlight Valid flag - - - When the bit is turned on, the backlight flashing/backlight
color control becomes effective.
Backlight Flashing - - - 0: Lighted (normal), 1: Flashing
Backlight Color - - - 00: Off, 01: Green, 10: Red, 11: Orange
BAT - - - This goes on if clock data and Hold PLC Device data held in the SRAM are
not being backed up normally. (This bit also goes on if the SRAM is not backed up by
the internal secondary battery.)
Data Input In Progress flag - - - This is 1 while data is being input, and 0 when data
input has been completed.
all-guides.co
m
3.2 Entering Settings for the Basic Communication Area to PLC
Explanation of this function
• “IOP01” mode
The GT10 is equipped with an IOP01 mode for users with
conventional models (I.O.P. B01C / M01L / D01TL series).Using this
function enables compatibility with earlier models, so that
communication is possible between the GT10 and PLC, except for
one part of the basic communication area.
• Entering settings for the IOP01 mode
Click on the “File” menu in GTWIN, and then select “Configuration”
from the displayed menu. Next, select “GT Configuration” from the
sub-menu. Turn on the radio button for “IOP01 Mode” in the
displayed dialog box.
For information on the displayed dialog box, please see “Basic
Setup” under “GT10 Configuration Settings” on page 59.
Entering Settings for the Basic Communication Area to PLC
• Map of the basic communication area for conventional models
(conventional name: system area)
If the IOP01 mode is set, the basic communication area map for the
GT10 is as follows.
Reference data area
Address
Bit configuration
Address
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
n
BZ
PC
Screen no.
n+1
n+2
T
bit fi ld * N t
1
n+3
Tag bit field * Note 1
(Used to turn tag display on/off, display status screen segments, and display settings)
•
(Used to turn tag display on/off, display status screen segments, and display settings)
•
T
fi ld * N t
1
•
Tag field * Note 1
(Used to switch tags, specify movements, and reference and set data)
•
(Used to switch tags, specify movements, and reference and set data)
Output destination relay
Address
Bit configuration
Address
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
n
System switch out-
put destination
Function switch out-
put destination
Displayed screen data (no. of screen
n
Not supported
* Note 2
Not supported
* Note 2
Displayed screen data (no. of screen
currently displayed)
n+1
BAT SET
n+2
n+3
Output destination relay * Note 1
•
Output destination relay
Note 1
(Used for switch output destinations of tags, segments, and manual switches)
•
1.
Note 1: The tag bit field and tag field under “Reference data
area”, and the output destination relay field under “Output
relay” can be switched just as they are, as device setting
destinations for GT10 parts functions.
2.
Note 2: System switch output destinations and function
switch output destinations provided in conventional models
as the initial addresses under “Output relay” are not
supported with the GT10.
System switches should be replaced with keyboard parts,
and function switches with switch parts.
System field
(fixed at 2
words)
Field for
user use
(fixed at
126 words
maximum)
System field
(fixed at 2
words)
Field for
user use
(fixed at 30
words max-
imum)
Connecting and Communicating with the
PLC
This chapter explains how to connect the GT10 to the FP series PLC, and how to set
up communications between the units.
4.1
Connecting the FP0
37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1
Connecting to the COM. Port
37
. . . . . . . . . . . . . . .
4.1.2
Connecting to the TOOL Port
39
. . . . . . . . . . . . . . .
4.2
Connecting the FP1
40
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1
Connecting to the COM. Port
40
. . . . . . . . . . . . . . .
4.3
Connecting the FP2/FP2SH
41
. . . . . . . . . . . . . . . . . . . . . . . .
4.3.1
Connecting to the COM. Port
41
. . . . . . . . . . . . . . .
4.3.2
Connecting to the TOOL Port
42
. . . . . . . . . . . . . . .
4.4
Connecting the FP2/FP2SH Computer
Communication Unit
43
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5
Connecting the FP10SH
44
. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1
Connecting to the COM. Port
44
. . . . . . . . . . . . . . .
4.5.2
Connecting to the TOOL Port
46
. . . . . . . . . . . . . . .
4.6
Connecting the FP10SH/FP3 Computer
Communication Unit
47
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7
Connecting the FP-M
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1
Connecting to the COM. Port
48
. . . . . . . . . . . . . . .
4.7.2
Connecting to the TOOL Port
50
. . . . . . . . . . . . . . .
4.8
Automatic Communication Settings Function
51
. . . . . . . . . .
4.9
Through Function
53
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting and Communicating with the PLC
GT10
37
4.1
Connecting the FP0
4.1
Connecting the FP0
4.1.1
Connecting to the COM. Port
GT10
Loose-wire connection
FP0 COM. port
FP0 communication format settings
System register no.
Item
Value Set
System register value
412
Selection of target
use of RS232C port
Computer link
K1
413
Data length
8 bits
K3
Parity check
Yes
Parity setting
Odd
Stop bits
1 bit
Line return code
CR
Start code
No STX
414
Baud rate setting
19200 bits/s
H0 * 00
415
Unit number
1
K1
416
Modem connection
No connection
H0
Connecting to the FP0 COM. port
GT10
FP0
S
SD
R
RD
G
SG
PLC side
Pin no.
Abbreviation
SD
SD
RD
RD
RS
RS
CS
CS
GND
GND
GT10 side
Pin no.
Abbreviation
←To set 19200 bits/s
for both the COM.
port and the TOOL
port, “H0100”
should be set.
all-guides.co
m
Connecting and Communicating with the PLC
38
4.1
Connecting the FP0
CAUTION
Because loose wiring is used for connection to the FP0 COM. port, no
dedicated cable is available. The cable should be provided by the
customer. When purchasing a cable, the following precautions should
be observed:
• Shielded wire with a size of AGW#28 to 16 (conductor cross-section
surface area: 0.08 mm2 to 1.25 mm2) should be used for connections.
• For wiring procedures, please refer to “Wiring the COM. Port” on
page 21.
Connecting and Communicating with the PLC
GT10
39
4.1
Connecting the FP0
4.1.2
Connecting to the TOOL Port
AIGT8192
GT10
FP0 TOOL port
FP0 communication format settings
System register no. Item
Value Set
System register
value
410
Unit number
1
K1
411
Data length
8 bits
H0
Modemconnection
No connection
414
Baud rate setting
19200 bits/s
H010X
X is 0 to 6
PLC communication cable: Mini-DIN 5-pin loose-wire cable (AIGT8192)
3
5
4
1
2
7/0.28
30/1.18
2000/78.74
(Unit: mm/inch)
Connector:
Made by JST Mfg. Co., Ltd.: MD-P15B (housing A)
MD-P16A (housing B)
MD-PS8T (shell)
MD-SP2240 x 5 (terminal)
Mini-DIN plug side signals
1
SG
Brown
2
SD
Red
3
RD
Orange
4
- -
- -
5
- -
- -
Pin no.
Abbreviation
Wire color
Specifications
L
Product No.
2 m/6.56 ft
Mini-DIN 5-pin
Single-side
loose wire
AIGT8192
Connecting to the FP0 TOOL port
GT10
3
5
4
1
2
No. 1 (brown)
Pin no. on PLC side
No. 3 (orange)
No. 2 (red)
PLC side
Pin no.
Abbreviation
1
SG
2
SD
3
RD
4
- -
5
-
Abbreviation
GT10 side
Pin no.
SD
SD
RD
RD
RS
RS
CS
CS
GND
GND
←To set 19200 bits/s for both
the COM. port and the TOOL
port, “H0100” should be set.
Connecting and Communicating with the PLC
40
4.2
Connecting the FP1
4.2
Connecting the FP1
4.2.1
Connecting to the COM. Port
AIP81842
GT10
FP1 COM. port
FP1 communication format settings
System register no.
Item
Value Set
System register value
412
Selection of target use of RS232C port
Computer link
K1
413
Data length
8 bits
K3
Parity check
Yes
Parity setting
Odd
Stop bits
1 bit
Line return code
CR
Start code
No STX
414
Baud rate setting
19200 bits/s
K0
415
Unit number
1
K1
416
Modem connection
No connection
H0
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP1 COM. port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
Connecting and Communicating with the PLC
GT10
41
4.3
Connecting the FP2/FP2SH
4.3
Connecting the FP2/FP2SH
4.3.1
Connecting to the COM. Port
AIP81842
GT10
FP2/FP2SH CPU COM. port
FP2/FP2SH communication format settings
System register no.
Item
Value Set
412
Selection of target use of RS232C port
Computer link
413
Data length
8 bits
Parity check
Yes
Parity setting
Odd
Stop bits
1 bit
Line return code
CR
Start code
No STX
414
Baud rate setting
19200 bits/s
415
Unit number
1
416
Modem connection
No connection
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP2/FP2SH COM. port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
Connecting and Communicating with the PLC
42
4.3
Connecting the FP2/FP2SH
4.3.2
Connecting to the TOOL Port
AIGT8192
GT10
FP2/FP2SH CPU TOOL port
FP2/FP2SH communication format settings
System register no.
Item
Value Set
410
Unit number
1
411
Data length
8 bits
411
Modem connection
No connection
414
Baud rate setting
19200 bits/s
PLC communication cable: Mini-DIN 5-pin loose-wire cable (AIGT8192)
3
5
4
1
2
7/0.28
30/1.18
2000/78.74
(Unit: mm/inch)
Connector:
Made by JST Mfg. Co., Ltd.: MD-P15B (housing A)
MD-P16A (housing B)
MD-PS8T (shell)
MD-SP2240 x 5 (terminal)
Mini-DIN plug side signals
1
SG
Brown
2
SD
Red
3
RD
Orange
4
- -
- -
5
- -
- -
Pin no.
Abbreviation
Wire color
Specifications
L
Product No.
2 m/6.56 ft
Mini-DIN 5-pin
Single-side
loose wire
AIGT8192
Connecting to the FP2/FP2SH TOOL port
GT10
3
5
4
1
2
No. 1 (brown)
Pin no. on PLC side
No. 3 (orange)
No. 2 (red)
1
SG
2
SD
3
RD
4
- -
5
- -
PLC side
Pin no.
Abbreviation
SD
SD
RD
RD
RS
RS
CS
CS
GND
GND
GT10 side
Pin no.
Abbreviation
all-guides.co
m
Connecting and Communicating with the PLC
GT10
43
4.4 Connecting the FP2/FP2SH Computer Communication Unit
4.4
Connecting the FP2/FP2SH Computer
Communication Unit
AIP81842
GT10
FP2 computer communication unit
DIP switch settings on reverse side of FP2 computer communication unit
SW No.
Setting contents
Value Set
Switch status
1
Reserved for system
ON
2
COM.1 transfer speed
19200 bits/s
ON
3
p
OFF
4
COM.1 data length
8 bits
ON
5
Reserved for system
ON
6
COM.2 transfer speed
19200 bits/s
ON
7
p
OFF
8
COM.2 data length
8 bits
ON
With the FP2 CCU, the parity check is fixed at “Odd”, and the number of stop bits is fixed at “1 bit”.
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP2 computer communication unit (CCU)
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
If both serial ports of the
FP2 computer commu-
nication unit are being
used, each port should be
set individually as shown
at the left.
Connecting and Communicating with the PLC
44
4.5
Connecting the FP10SH
4.5
Connecting the FP10SH
4.5.1
Connecting to the COM. Port
0
1
DIP SW 1
DIP SW 2
1
AIP81842
J
GT10
FP10SH communication format settings
SW no.
2
3
4
5
6
7
8
Setting port
COM. setting port
Setting
contents
Modem
control
Start
code
End
code
Stop bit
length
Parity
check
Data
length
Value
Set
No
STX
invalid
CR code
1 bit
Odd parity
8 bits
Switch
status
OFF
OFF
OFF
ON
ON
ON
ON
ON
DIP SW 1
SW no.
1
2
3
4
5
6
7
8
Setting port
TOOL port
Memory
COM. setting port
Setting
contents
Transfer
speed
Data
length
Modem
control
Program
memory
protect
Program
memory
select
Transfer speed
Value Set
Not related to GT10 communication
19200 bits/s
Switch
status
Not related to GT10 communication
ON
ON
OFF
DIP SW 2
FP10SH CPU COM. port
Not related to GT10
communication
Unit number setting
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting and Communicating with the PLC
GT10
45
4.5
Connecting the FP10SH
Connecting to the FP10SH COM. port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
Connecting and Communicating with the PLC
46
4.5
Connecting the FP10SH
4.5.2
Connecting to the TOOL Port
AIP81842
J
GT10
SW no.
1
2
3
4
5
6
7
8
Setting port
TOOL port
Memory
COM. setting port
Setting
contents
Transfer
speed
Data
length
Modem
control
Program
memory
protect
Program
memory
select
Transfer speed
Value Set
19200
bits/s
8 bits
No
Not related to GT10
communication
Switch
status
OFF
ON
OFF
DIP SW 2
FP10SH CPU TOOL port
FP10SH communication format settings
DIP SW 1: Not related to
GT10 communication
Unit number setting
Not related to GT10
communication
0 1
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP10SH TOOL port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
Connecting and Communicating with the PLC
GT10
47
4.6 Connecting the FP10SH/FP3 Computer Communication Unit
4.6
Connecting the FP10SH/FP3 Computer
Communication Unit
AIP81842
GT10
FP3 computer communication unit
DIP switch settings on reverse side of FP3 computer communication unit
SW No.
Setting contents
Value Set
Switch status
1
ON
2
Transfer speed
19200 bits/s
OFF
3
p
/
OFF
4
Data length
8 bits
ON
5
Parity check
Odd parity
ON
6
Parity check
Odd parity
OFF
7
Stop bit length
1 bit
OFF
8
Control signals
CS, RS invalid
OFF
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting to the FP3 computer communication unit (CCU)
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
all-guides.co
m
Connecting and Communicating with the PLC
48
4.7
Connecting the FP-M
4.7
Connecting the FP-M
4.7.1
Connecting to the COM. Port
AIP81842
GT10
FP-M COM. port
FP-M communication format settings
System register no.
Item
Value Set
System register value
412
Selection of target use of RS232C port
Computer link
K1
413
Data length
8 bits
K3
Parity check
Yes
Parity setting
Odd
Stop bits
1 bit
Line return code
CR
Start code
No STX
414
Baud rate setting
19200 bits/s
K0
415
Unit number
1
K1
416
Modem connection
No connection
H0
PLC communication cable: D-sub 9-pin loose-wire cable (AIP81842)
1
2
3
4
5
6
7
8
9
L
50/1.97
(Unit: mm/inch)
Made by JAE: DE-C8-J9-F1-1
Made by JAE: DE-9PF-N
10/0.39 (shielded mesh wire section)
Signals on D-sub side
Pin no.
Wire color
Dot mark
1
Brown
Black dot
2
Brown
Red dot
3
Yellow
Black dot
4
Yellow
Red dot
5
Green
Black dot
6
- -
- -
7
Green
Red dot
8
- -
- -
9
- -
- -
Specifications
L
Order no.
D-sub 9-pin
Single-side
loose wiring
AIP81841
AIP81842
1 m/3.28 ft
2 m/6.56 ft
Connecting and Communicating with the PLC
GT10
49
4.7
Connecting the FP-M
Connecting to the FP-M COM. Port
1
FG
SD
RS
SG
CS
RD
2
3
4
5
6
N.C.
7
8
9
N.C.
ER
SD
SD
RD
CS
GND
RS
RD
RS
CS
GND
1
2
3
4
5
6
7
8
9
GT10
Pin no. on PLC side
No. 3 (yellow: black dot mark)
No. 2 (brown: red dot mark)
No. 7 (green: red dot mark)
No. 4 (yellow: red dot mark)
Short wiring here
No. 5 (green: black dot mark)
PLC side
GT10 side
Pin no.
Pin no.
Abbreviation
Abbreviation
Connecting and Communicating with the PLC
50
4.7
Connecting the FP-M
4.7.2
Connecting to the TOOL Port
19200
AIGT8192
GT10
FP-M TOOL port
FP-M communication format settings
System register no.
Item
Value Set
System register value
410
Unit number
1
K1
411
Data length
8 bits
H0
Modem connection
No connection
PLC communication cable: Mini-DIN 5-pin loose-wire cable (AIGT8192)
3
5
4
1
2
7/0.28
30/1.18
2000/78.74
(Unit: mm/inch)
Connector:
Made by JST Mfg. Co., Ltd.: MD-P15B (housing A)
MD-P16A (housing B)
MD-PS8T (shell)
MD-SP2240 x 5 (terminal)
Mini-DIN plug side signals
1
SG
Brown
2
SD
Red
3
RD
Orange
4
- -
- -
5
- -
- -
Pin no.
Abbreviation
Wire color
Specifications
L
Product No.
2 m/6.56 ft
Mini-DIN 5-pin
Single-side
loose wire
AIGT8192
Connecting to the FP-M TOOL port
GT10
3
5
4
1
2
No. 1 (brown)
Pin no. on PLC side
No. 3 (orange)
No. 2 (red)
1
SG
2
SD
3
RD
4
- -
5
- -
PLC side
Pin no.
Abbreviation
SD
SD
RD
RD
RS
RS
CS
CS
GND
GND
GT10 side
Pin no.
Abbreviation
Connecting and Communicating with the PLC
GT10
51
4.8 Automatic Communication Settings Function
4.8
Automatic Communication Settings Function
After turning on the power supply, if there is no response from the PLC connected to
the GT10, the GT10 switches to the automatic setting mode for the communication
conditions. In the automatic setting mode, commands are sent to the PLC while
changing the communication conditions in the sequence shown below.
GT10
PLC
(1) 9600 bits/s, 8 bits, odd parity, 1 stop bit
(2) 19200 bits/s, 8 bits, odd parity, 1 stop bit
(3) 115200 bits/s, 8 bits, odd parity, 1 stop bit
(4) Communication conditions set in GTWIN Configuration Settings
If there is no response from the PLC,
commands are sent to the PLC while
changing the communication conditions.
The GT10, in automatic setting mode, continues to repeat steps (1) to (4) until there is
a response from the PLC. While it is repeating these steps, it is in the “Standby” mode
under “GT10 Configuration” a “Communication Parameters” a “Handle Communication
Error” on GTWIN. For information on how settings are entered, please refer to page 61.
Explanation of this function
• Conditions when the automatic settings mode is in effect
If communication is attempted the specified number of times and
there is no response from the PLC, the GT10 goes into the automatic
settings mode. The number of attempts is specified using the “No. of
Retries” parameter under “GT10 Configuration” →“Communication
Parameters” →“Handle Communication Error” on GTWIN. For
information on how settings are entered, please refer to page 61.
• Automatically set communication conditions
In the automatic settings mode, if there is a response from the PLC,
subsequent communication is carried out under conditions matching
the response. The main unit configuration settings are not updated,
however, even if the communication parameters are different from
those of the main unit configuration settings.
Connecting and Communicating with the PLC
52
4.8
Automatic Communication Settings Function
CAUTION
• An error response from the PLC is taken as a response, and the GT10
does not go into the automatic settings mode.
• If the GT10 is connected to the COM. port of the FP0, FP1, FP2,
FP2SH, or FP-M, the automatic communication settings mode
functions only if the usage objective of the RS232C port is set to
“Computer Link”.
Always set the setting on the PLC side to match “Computer Link”.
For detailed information, please refer to Chapter 4, “Connecting and
Communicating With the PLC”, on page 35.
all-guides.co
m
Connecting and Communicating with the PLC
GT10
53
4.9
Through Function
4.9
Through Function
With the GT10, communication can be set to take place automatically between the
COM. and TOOL ports in a “through function”. When the FP series tool software
installed in the computer connected to the GT10 as shown below is booted, PLC
programs can be edited through the GT10.
The through function does not require any special settings, and is always in the standby
mode.
PLC
GT10
Connected by cable
to the COM. port or
TOOL port of the PLC
Screen
transfer
cable
AFC8503
Screen data
being sent
and received
Screen creation tool GTWIN
FP series programming tool FPWIN GR
Personal computer
The FPWIN GR and NPST-GR are
booted on the computer being used to
edit the GT10 screens, and the PLC
programs can be edited and monitored
through the GT10.
PLC debugging
Connecting and Communicating with the PLC
54
4.9
Through Function
CAUTION
• Precautions when using the through function
The system should be set up so that the interval for communication
retries in the FP series software (FPWIN GR or NPST-GR) (A) is larger
than that of the GT10 COM. port (B), meaning (A) > (B). If the system
is set up so that A = B or A < B, the through function will not work
properly.
• Restrictions on COM. port connections
If the GT10 is connected to the COM. port of the PLC, please be aware
that some functions cannot be used, such as rewriting in the RUN
mode in the FPWIN GR.
• Precautions when connecting the FP Programmer II to the TOOL port
If the FP Programmer II is connected to the TOOL port of the GT10,
the operating voltage of the GT10 should be set to 25V DC or less.
Also, the GT10 should not be left connected to the FP Programmer II
on an ongoing basis.
GT10
FP Programmer II
25V DC max.
GT10 Configuration Settings
This chapter describes the configuration settings for the GT10, and how they should be
entered.
5.1
GT10 Configuration Settings
57
. . . . . . . . . . . . . . . . . . . . . . . .
5.1.1
Two Types of GT10 Configuration Settings
57
. . . .
5.2
Entering Configuration Settings from GTWIN
Screen Creation Tool
58
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1
Opening the GT Configuration Settings
58
. . . . . . .
5.2.2
GT Configuration Settings: “Basic Setup”
59
. . . . .
5.2.3
GT Configuration Settings:
“Communication Parameters”
61
. . . . . . . . . . . . . . .
5.2.4
GT Configuration Settings:
“Auto-Paging”
64
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.5
GT Configuration Settings:
“Startup Screen Settings”
66
. . . . . . . . . . . . . . . . . . .
5.2.6
GT Configuration Settings: “Setup”
68
. . . . . . . . . . .
5.2.7
GT Configuration Settings:
“Hold PLC Device”
71
. . . . . . . . . . . . . . . . . . . . . . . . .
5.3
Entering Configuration Settings from the
GT Main Unit
73
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1
What is the System Menu?
73
. . . . . . . . . . . . . . . . .
5.3.2
Bringing Up the System Menu
73
. . . . . . . . . . . . . . .
next page
GT10 Configuration Settings
56
5.3.3
Setting Mode: “Communication Parameters”
(COM. Port / TOOL Port)
74
. . . . . . . . . . . . . . . . . . .
5.3.4
Setting Mode: “Liquid Crystal Display
Contrast Adjustment” (Contrast)
76
. . . . . . . . . . . . .
5.3.5
Setting Mode: “Clock Settings” (Clock)
76
. . . . . . .
5.3.6
Setting Mode: “Memory Initialization”
(Clear Memory)
78
. . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.7
Test Mode: “Self-Diagnosis”
79
. . . . . . . . . . . . . . . .
5.3.8
Inhibiting the System Menu Display
80
. . . . . . . . . .
GT10 Configuration Settings
GT10
57
5.1
GT10 Configuration Settings
5.1
GT10 Configuration Settings
Before using the GT10 for the first time, it must be set up by entering the GT10
configuration settings indicated below. Always check and enter the settings under “Basic
communication area to PLC”. For instructions on setting up the GT10, see page 30.
5.1.1
Two Types of GT10 Configuration Settings
1. Entering configuration settings from GTWIN screen creation tool
page 58
. .
With this method, GT10 configuration settings are entered from GTWIN screen creation
tool, and the GT10 configuration file is sent to the GT10. Most items can be set using
this method.
GTWIN
GT10
GT10
configuration
file sent
2. Entering configuration settings from the GT main unit
page 73
. . . . . . . . . . . . .
Some of the settings, such as the communication parameters, the internal clock, and
adjustments of the liquid crystal display contrast, can be set using the system menu of
the GT10. Settings are entered using the touch switches on the front of the panel.
GT10
Explanation of this function
Items in the GT10 Configuration Settings
Items that can be set from GTWIN
Items that can be set
either way
Items that can be set from the
GT10 system menu
Title setting
Communication parameters
Clock division setting for the internal
clock
Type of PLC connected
LCD contrast setting
Basic communication area to PLC
Communication parameters
Communication parameters
Memory initialization
Auto-paging screen settings
Self-diagnosis
Startup screen (default screen) settings
Reference destination setting for clock
Backlight control
Touch sounds
Hold PLC device
all-guides.co
m
GT10 Configuration Settings
58
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
5.2
Entering Configuration Settings from GTWIN Screen
Creation Tool
This section describes how configuration settings for the GT10 are entered from GTWIN
screen creation tool.
5.2.1
Opening the GT Configuration Settings
The GT configuration settings are set by selecting [Configuration] on the menu
displayed by clicking with the mouse on [File] or pressing the Alt + F keys. Then select
the “GT Configuration” sub-menu under [Configuration].
Configuration Settings
GTWIN Configuration - - - These are operating environment settings for GTWIN.
GT Configuration - - - These are configuration settings for the GT10. The file is sent
from GTWIN to the GT10 after the settings have been entered.
GT10 Configuration Settings
GT10
59
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.2
GT Configuration Settings: “Basic Setup”
Selecting [Configuration] on the [File] menu of GTWIN and then the sub-menu [GT
Configuration] displays the “Basic Setup” screen shown below.
This is used to specify the basic communication area used for communication between
the GT10 and PLC, and the environment required for GT10 operation.
“Basic Setup” screen
Title - - - The title of the configuration settings file is entered here. Titles are convenient
if each GT10 has its own configuration settings.
PLC Model - - - The model of PLC specified when GTWIN is booted is displayed here.
GT Model - - - The model of GT specified when GTWIN is booted is displayed here.
Basic communication area to PLC
This is used to specify the mode in which communication takes place between the GT10
and PLC, and the internal PLC device used for basic communication.
Modes
Turn on the radio button for either “GT10 Mode” or “IOP01 Mode”.
- GT10 Mode - - - Select this if you are using the GT10 for the first time.
- IOP01 Mode - - - This mode is for users who are using a conventional model (I.O.P.
B01C / M01L / D01TL). If this mode is selected, the basic communication area for
communication between the GT10 and PLC is compatible with conventional models for
the most part, except for a few items.
REFERENCE
For information on the IOP01 mode, please see page 33, “IOP01 Mode”.
GT10 Configuration Settings
60
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
Device used
This specifies the internal PLC device used for basic communication between the GT10
and PLC.
·
Word area - - - This specifies the type of device that reads and writes screen
numbers and other information in word units, and the initial address.
·
Bit area - - - This specifies the type of device that reads and writes backlight
control and other bit information, and the initial address.
The type of device and addresses can be set by clicking on the
buttons for the
various items.
Device settings dialog box
Clicking on the
button displays a pull-down
menu. Select the device for which settings are
to be entered, and use the ten-keys to enter
addresses.
The
button functions as a backspace
key when entering addresses.
The
button acts as a Clear key.
REFERENCE
For detailed information on the basic communication area map, see
“Basic Communication Area Map” on page 32.
Explanation of this function
Standard settings
Clicking on the
button in the “GT Configuration” dialog box displays the
following message. Clicking on [OK] sets the default values (the configuration settings
entered when the unit is shipped) for all of the settings.
For information on the contents of configuration settings entered when the unit is
shipped, see “Contents of configuration settings when shipped from the factory” on
page 27.
GT10 Configuration Settings
GT10
61
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.3
GT Configuration Settings: “Communication Parameters”
Clicking on the “Communication Parameters” tab in the “GT Configuration” dialog box
displays the following screen.
This is where communication parameters for the PLC and personal computer (GTWIN)
connected to the GT10 are set.
“Communication Parameters” screen
COM. port (Connected to PLC/External Device)
This is used to specify the communication speed and transmission format when the
GT10 is connected to an external device (PLC).
Clicking on the
button displays a pull-down menu from which the value to be set can
be selected.
·
Baud Rate - - - Select 9600, 19200, 38400, 57600, 76,800 or 115200 bits/s.
·
Data Length - - - Select either “7 bits” or “8 bits”.
·
Stop Bits - - - This is fixed at “1 bit”.
·
Parity Bit - - - Select “None”, “Odd”, or “Even”.
GT10 Configuration Settings
62
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
Handle Communication Error
Clicking on the
button displays the “Communication Error Remedy” dialog
box. This is used to specify the processing to be used if a communication error occurs.
“Communication Error Remedy” dialog box
For “Retry” and “Waiting”, click the
button and specify the values in the
“Value Set” dialog box that is dis-
played.
For “Display Error Code”, select “Off”,
“On (Hold)”, or “On (Unhold)” by click-
ing the radio button of the desired val-
ue to turn it on.
Retry - - - This specifies the number of retries if a communication error occurs. The
setting range is from 0 to 255 times.
Waiting - - - This specifies the interval between retries if a communication error occurs.
The setting range is from 0 to 255 seconds.
all-guides.co
m
GT10 Configuration Settings
GT10
63
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
“Display Error Code”
This switches the setting for the error code display used if a communication error
occurs.
Off - - - No error code is displayed if a communication error occurs.
On (Hold) - - - An error code is displayed at the upper right of the screen if a
communication error occurs, and continues to be displayed until the power supply is
turned off.
On (Unhold) - - - An error code is displayed at the upper right of the screen if a
communication error occurs, and is cleared when the cause of the error is eliminated.
For contents of error codes, please see “Error Codes and How to Handle Them”
on page 102.
TOOL Port (for GTWIN connection)
This is used to specify the communication speed and transmission format when the
GT10 is connected to a personal computer (GTWIN).
Clicking on the
button displays a pull-down menu from which the value to be set can
be selected.
·
Baud Rate - - - Select 9600, 19200 or 115200 bits/s.
·
Data Length - - - This is fixed at “8 bits”.
·
Stop Bits - - - This is fixed at “1 bit”.
·
Parity Bit - - - Select “None”, “Odd”, or “Even”.
Through function
If the “Forward only to the selected unit” check box is turned on, communication can be
carried out via the through function only with unit numbers for a PLC received from a
higher-order personal computer or higher-order PLC.
GT10 Configuration Settings
64
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.4
GT Configuration Settings: “Auto-Paging”
Clicking on “Auto-Paging” in the “GT Configuration” dialog box displays the screen
shown below. Here, settings can be entered for a functions that automatically switches
the screens displayed on the GT10.
“Auto-Paging” screen
Auto-paging
This is used to specify the “Auto-paging function”, which automatically switches the
specified screen when a given period of time has elapsed.
Off - - - The screen is not switched automatically.
On - - - The screen is switched automatically, in conformance with the specified
contents.
GT10 Configuration Settings
GT10
65
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
Auto-paging settings
If “On” is selected for auto-paging, and the [Setup] button is clicked, a dialog box
containing the following auto-paging settings is displayed.
Clicking on the
button for “Screen No.”, “Time”, or “Jump to” displays a “Value Set”
dialog box. Set the value and click the [Save] button to save values one at a time.
Screen No. - - - This specifies the screen targeted for auto-paging.
Time - - - This specifies the time for which the screen specified above is displayed. The
setting range is from 1 to 255 seconds.
Jump to - - - This specifies the number of the next screen to be displayed.
[Return]
- - -
This
completes
the
auto-paging
settings
and
returns
to
the
“Auto-Paging” dialog box.
[Delete] - - - This deletes screens registered for auto-paging.
[Save] - - - This saves the settings for the screen number, time, and jump destination
as auto-paging settings.
GT10 Configuration Settings
66
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.5
GT Configuration Settings: “Startup Screen Settings”
Clicking on “Start-up Screen” in the “GT Configuration” dialog box displays the screen
shown below. Here, the screen displayed when the GT10 is booted can be specified.
“Start-up Screen” screen
This is used to specify the screen that will be displayed when the GT10 is booted, as
well as the time it will be displayed. Clicking on the
button for each of the items
displays a “Value Set” dialog box where the values can be specified.
Start-up Screen No. - - - This specifies the number of the screen that will be displayed
when the GT10 is booted. Clicking on the
button displays a “Value Set” dialog box
where the value for the start-up screen number can be specified.
Display Time - - - This specifies the time for which the startup screen specified above
will be displayed. The value can be set to any number between 0 and 255 seconds.
Clicking on the
button displays a “Value Set” dialog box where the start-up delay
time can be specified.
Key points
• When the above settings are entered, the screen specified with the
“Startup Screen No.” parameter is displayed for the amount of time
specified with the “Display Time” parameter.
• When the amount of time specified with the “Display Time” parameter
elapses, the screen corresponding to the number stored in the initial
address of the word device under “Basic Communication Area to
PLC” in the “Basic Setup” parameters under “GT Configuration” will
be displayed.
• This function is used when it is necessary to delay the start-up time
when the power supply on the PLC side is turned on.
GT10 Configuration Settings
GT10
67
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
CAUTION
• Communication between the GT10 and the PLC (external device)
cannot be carried out during the time specified by the “Display Time”
parameter.
all-guides.co
m
GT10 Configuration Settings
68
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.6
GT Configuration Settings: “Setup”
Clicking on the “Setup” tab in the “GT Configuration” dialog box displays the screen
shown below. Here, clock functions, backlight control, and other parameters can be
specified.
“Setup” screen
Clock
Clock
This is used to specify the reference destination for the clock displayed with the GT10.
Select one of the radio buttons.
GT Clock - - - When the time is displayed, the internal clock in the GT10 is used as a
reference for the value.
PLC Clock - - - When the time is displayed, the internal clock in the PLC is used as a
reference for the value.
If the “PLC Clock” is referenced for the clock setting, clicking on the
button displays
a screen where the type of device and the address can be specified.
Device Setting dialog box
The
button functions as a backspace
key when entering addresses.
The
button acts as a Clear key.
Click on the
button to display the pull-down
menu, and select the device from that menu.
Enter the address using the ten-keys.
GT10 Configuration Settings
GT10
69
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
Transfer Outside
Clock data displayed in the GT10 can be transferred to an external device such as a
PLC, using this setting.
Off - - - The GT10 clock data is not transferred to an external device.
On - - - The GT10 clock data is transferred to an external device.
If “On” is selected for the above “Transfer Outside” parameter, click on the
button
to specify the output destination and the initial device, and specify the address.
Data storage sequence for internal PLC device
Upper byte
Lower byte
Top address
Minutes data (H00~H59)
Second data (H00~H59)
Top address +1
Day data (H01~H31)
Hour data (H00~H23)
Top address +2
Year data (H00~H99)
Month data (H01~H12)
CAUTION
If “On” is selected for the “Transfer Outside” parameter, the data will be
transferred to the DT90054 as the default device. If this device address
does not exist in the PLC connected to the GT10, however, re-specify
the address so that it matches the model connected to the GT10.
Selecting a device address that does not exist in the PLC will cause an
error (ER61) to occur.
GT10 Configuration Settings
70
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
Backlight control
Auto-Off
This is used to specify the Auto-Off backlight feature.
Off - - - The Auto-Off backlight feature is not used.
On - - - Auto-Off backlight feature is used. This parameter specifies the period of time
that the GT10 is inactive before the backlight goes off automatically.
If “On” is set for the above Auto-Off backlight feature, clicking on the
button displays
a screen where the time until the backlight goes off can be specified. Any time from one
minute to 30 minutes can be specified.
Key points
If the backlight is turned off automatically using the backlight control
function, touching the screen turns it on again. If a touch switch
happens to be located at that point on the screen, it will be invalid until
the backlight has gone on again.
Touch Sounds
This sets the touch sounds corresponding to GT10 screens as either invalid or valid.
Select one of the radio buttons.
Disable - - - Touch sounds are disabled.
Enable - - - Touch sounds are enabled.
GT10 Configuration Settings
GT10
71
5.2 Entering Configuration Settings from GTWIN Screen Creation Tool
5.2.7
GT Configuration Settings: “Hold PLC Device”
Clicking on the “Hold PLC Device” tab in the “GT Configuration” dialog box displays the
screen shown below. “Hold PLC Device” is a function that enables internal PLC device
values to be held on the GT10 side.
“Hold PLC Device” screen
Hold PLC Device
The Hold PLC Device function reads the values for the specified internal PLC device
to the SRAM in the GT10, and backs up the values.
Off - - - PLC devices are not held.
On - - - PLC devices are held (up to 24 words)
If “On” is selected for the above Hold PLC Device setting, “Device” and “Number of
Word” parameters are displayed. Clicking on the
button displays a dialog box like
that shown below, where the type of initial device, the address, and the number of words
can be specified.
Device Setting dialog box
Click on the
button to display the pull-down
menu, and select the device from that menu.
Enter the address using the ten-keys.
The
button functions as a backspace
key when entering addresses.
The
button acts as a Clear key.
GT10 Configuration Settings
72
5.2
Entering Configuration Settings from GTWIN Screen Creation Tool
CAUTION
• Data for PLC devices held in the GT10 will be written to the internal
PLC device the next time that the power supply is turned on.
• If the power supply on the GT10 side is not turned on, the data can be
held for the period of time that the backup with the internal secondary
battery is effective. For information on the internal secondary battery
specifications, see “What the Internal Secondary Battery Does” on
page 93.
all-guides.co
m
GT10 Configuration Settings
GT10
73
5.3 Entering Configuration Settings from the GT Main Unit
5.3
Entering Configuration Settings from the GT Main Unit
5.3.1
What is the System Menu?
The system menu is a dedicated screen on which configuration settings for the GT10
are entered. Some of the items that can be specified here can also be set using GTWIN
screen creation tool and then sent to the GT10, but others, such as the internal clock
and adjustments to the LCD contrast level, can only be set using the system menu. This
section explains how configuration settings are entered using the system menu.
5.3.2
Bringing Up the System Menu
The following procedure is used to bring up the system menu.
(1) Touch the four corners of the LCD touch panel simultaneously.
Touch these four corners at the same time,
and continue pressing them for about one
second.
(2) The initial screen of the system menu is displayed.
The initial screen of the system menu is
displayed on the GT10. Touching either
the [Setting] or [Test] key shifts to the next
screen.
Touching the [ESC] key exits the system
menu and returns to the normal operating
mode.
*.* indicates the ROM version of the GT10 system.
(3) Select the mode.
[Setting]: Setting mode initial screen
This is where configuration settings for the
GT10, such as the contrast, clock, COM. port,
TOOL port, and memory, are specified.
[Test]: Test mode initial screen
This is where GT10 configuration elements
such as the touch switches, backlight,
clock, buzzer, LCD, contrast, and memory
are tested.
GT10 Configuration Settings
74
5.3
Entering Configuration Settings from the GT Main Unit
5.3.3
Setting Mode: “Communication Parameters”
(COM. Port / TOOL Port)
Touching the [Setting] key on the initial screen of the system menu and then
touching the [COM. Port] and [TOOL Port] keys on the setting mode menu displays
the communication parameters setting screen. Here, parameters controlling
communication between the PLC and personal computer (GTWIN) connected to the
GT10 are specified.
COM. port communication parameter settings (PLC communication parameter settings)
Procedure for bringing up the screen
[Initial screen]
[Setting]
[COM. port]
↓
↓
Bitrate: PLC communication speed
This sets the communication speed, or Baud rate, for communication with an external
device (PLC) connected to the GT10.
Each time the [Function] key is pressed, the Baud rate switches in the sequence of
9600, 19200, 38400, 57600, 76800, 115200 bits/s. Set the speed to match that of the
PLC connected to the GT10.
Format: Transmission format
This sets the communication parameters (data length, stop bits, parity) for the external
device (PLC) connected to the GT10.
The items displayed are: Data length / Stop bit / Parity, and each time the [Function] key
is pressed, the display switches in the sequence of: [7/1/None], [7/1/Odd], [7/1/Even],
[8/1/None], [8/1/Odd], [8/1/Even]. Set the parameters to match those of the PLC
connected to the GT10.
Learning the shortcut keys saves time!
[RETURN]To complete the settings and return to the previous screen,
touch the [ESC] key.
Explanation of this function
COM. port communication parameter settings
The default (initial) values for the COM. port communication parameter
settings are: 19200 bits/s, 8/1/Odd.
GT10 Configuration Settings
GT10
75
5.3 Entering Configuration Settings from the GT Main Unit
TOOL Port communication parameter settings (GTWIN communication parameter
settings)
Procedure for bringing up the screen
[Initial screen]
[Setting]
[TOOL Port]
↓
↓
Through function: Through function destination setting
When the through function is being used, this specifies the number of the PLC at the
other end of the connection. Normally, when used in a 1 : 1 configuration, this should
be set to “00”.
Bitrate: GTWIN communication speed
Each time the [Function] key is touched, the Baud rate switches in the sequence of
9600/19200/115200 bits/s. Set the speed to match that of the personal computer
(GTWIN) connected to the GT10.
Format: Transmission format
This sets the communication parameters (data length, stop bits, parity) for the personal
computer (GTWIN) connected to the GT10.
The items displayed are: Data length / Stop bit / Parity, and each time the [Function] key
is pressed, the display switches in the sequence of: [8/1/None], [8/1/Odd], [8/1/Even].
Learning the shortcut keys saves time!
[RETURN]To complete the settings and return to the previous screen,
touch the [ESC] key.
Explanation of this function
TOOL Port communication parameter settings
The default (initial) values for the TOOL Port communication parameter
settings are: 19200 bits/s, 8/1/Odd.
GT10 Configuration Settings
76
5.3
Entering Configuration Settings from the GT Main Unit
5.3.4
Setting Mode: “Liquid Crystal Display Contrast Adjustment”
(Contrast)
Touching [Setting] on the initial screen of the system menu and then the [Contrast] key
of the setting mode menu displays the contrast adjustment screen. The contrast of the
GT10 LCD is adjusted here.
Contrast adjustment screen
Procedure for bringing up the screen
[Initial screen]
[Setting]
[Contrast]
↓
↓
Learning the shortcut keys saves time!
[ADJUST] Touching the [+] key increases the contrast, and touching the
[-] key decreases it.
[RETURN]To complete the settings and return to the previous screen,
touch the [ESC] key.
5.3.5
Setting Mode: “Clock Settings” (Clock)
Touching [Setting] on the initial screen of the system menu and then the [Clock] key of
the setting mode menu displays the clock setting screen. The internal clock of the GT10
is set here.
Clock setting screen
Procedure for bringing up the screen
[Initial screen]
↓
[Setting]
↓
[Clock]
The time displayed on the screen is the current time indicated by the internal clock of
the GT10. Items can be changed by touching the item (year, month, day, hour, minute,
second) and touching the [+] and [-] keys to change the values.