Fire Alarm Control Panel

LT-1091 Rev 2 Novenber 2015 Releasing Application Guide FM APPLICATIONS MUST HAVE CLASS A INITIATING CIRCUITS ONLY AND 90 HOUR BATTERY STANDBY OPERATION

Table of Contents

1.0 Operating the Panel 3 1.1 Hazard Zones ................................................................................................................ 3 1.2 Counting Zone Type ...................................................................................................... 3 1.3 Abort Type ..................................................................................................................... 3 1.4 Configurable Timers ....................................................................................................... 4 1.5 Hazard Zone States ....................................................................................................... 4 1.5.1 Hazard Idle ..................................................................................................................... 4 1.5.2 Hazard Alarm (pre-discharge) ........................................................................................ 5 1.5.3 Hazard Release ............................................................................................................. 5 1.6 General Operation ......................................................................................................... 5 2.0 Releasing Circuit Wiring 6 2.1 Releasing Circuit Wiring - Class B/Style Y Wiring ......................................................... 6 3.0 Typical Releasing Applications 7 3.1 Pre-Action/Agent Release, Single Activation Application .............................................. 7 3.2 Pre-Action/Agent Release, Double Activation Application ............................................. 8 3.3 Pre-Action/Agent Release, Triple Activation Application ............................................... 9 3.4 Pre-Action/Agent Release, 2 Input Type Activation Application .................................... 10 3.5 Deluge, Single Activation Application ............................................................................ 11 3.6 Deluge, Double Activation Application ........................................................................... 12 3.7 Deluge, Triple Activation Application ............................................................................. 13 3.8 Deluge, 2 Input Type Activation Application .................................................................. 14 4.0 Compatible Solenoids 15

Operating the Panel

1.0 Operating the Panel The TS1 terminal on the power supply board (MD-1011) is dedicated to supply power for releasing devices. For wiring information see LT-1083RCU FX-3500RCU Installation Manual. 1.1 Hazard Zones Hazard zones are configurable by correlating input devices, releasing circuits, (pre)release signals, and manual release and abort switches. 1.2 Counting Zone Type Releasing applications must be configured with one of the following Counting Zone types: 1.3 Abort Type Releasing applications must be configured with one of the following Delay Timer types: Attention: ONLY UL/ULC LISTED MANUAL ABORT AND MANUAL RELEASE SWITCHES, SUCH AS THE MIRCOM SS-2004, ARE PERMITTED FOR USE. Notes: Abort switches are only configurable in Preaction/Agent release applications. Soak Delay timer is only configurable for Deluge applications. Single Activation of any one input device correlated to the hazard zone will initiate the release process. Double Activation of any two input devices correlated to the hazard zone will confirm the alarm and initiate the release process. Triple Activation of any three input devices correlated to the hazard zone will initiate the release process. 2 Input Types Activation of any two different input device types (ion, photo, heat etc.) correlated to the hazard zone will initiate the release process. ULI Press Abort and the timer continues to count down and stops and holds at 10 seconds. Release the ABORT switch and the timer resumes the countdown at 10 seconds. IRI Same as ULI with the following condition: For the Abort switch to function, you must press and hold the Abort switch before the second zone goes into alarm. NYC Pressing the Abort switch causes the control panel to add 90 seconds to the Release Delay Timer (RDT). Pressing and holding the Abort switch stops the Release Delay Timer (RDT) from counting down. Releasing the Abort switch resumes the count down of the RDT. AHJ The timer does not start while you press and hold the Abort switch. Press the Abort switch and the timer resumes counting down. Press the Abort switch again to restore the timer to its full value. Release the Abort switch and the timer resumes counting down. ! i

Operating the Panel

1.4 Configurable Timers Releasing applications may be configured with the following timers: 1.5 Hazard Zone States The escalating Hazard Zone states are as follows: • Hazard Idle • Hazard Alarm • Hazard Release. The states are defined based on the status of Hazard Area input devices, and correlated Abort and Manual Release Switches. 1.5.1 Hazard Idle The Hazard Zone is Idle when: • Release Delay Timer (RDT) is not started. • There are insufficient alarm conditions to activate the Hazard Zone. For more information see Chapter 1.2 Counting Zone Type. • Manual Release Switch is not active. During this state: • The corresponding NAC circuit(s) is off. • Releasing circuit(s) is off. Release Delay Timer (RDT) The amount of time from when the Hazard Zone is activated via correlated input devices until release. The maximum value for the RDT is 60 seconds. Soak Delay Timer (SDT) The amount of time that the releasing circuit will be active. Upon the expiration of Soak Timer, the releasing circuits will be shut off. Only configurable in Deluge applications. The maximum value for the SDT is 600 seconds. Configuring the SDT to 0 seconds causes the releasing circuits to shut off ONLY when the system is reset. Manual Release Delay Timer (MRDT) The amount of time from when the Manual Release Switch is pressed until release. The maximum value for the MRDT is 60 seconds. Attention: Manual Release cannot be aborted once it has been initiated. Use ULC- S528 listed Manual Release such as MS-704(U) and MS-714(U). !

Operating the Panel

1.5.2 Hazard Alarm (pre-discharge) The panel enters the Hazard Alarm state when: • It detects the Hazard area confirming alarm input device. For more information on confirming alarms see Chapter 1.2 Counting Zone Type. OR • For a Single Counting Zone hazard area, a single alarm input device will put the Hazard Zone into the Hazard Alarm state. OR • Manual Release switch is activated. The releasing process continues as follows: • Release Delay Timer (RDT) or Manual Release Delay Timer (MRDT) is started. • Corresponding NAC(s) turns on at Alert rate. 1.5.3 Hazard Release The panel enters the Hazard Release state when: • The Release Delay Timer (RDT) or Manual Release Delay Timer (MRDT) expires. The releasing process continues as follows: • The correlated releasing circuit is activated. • Corresponding NAC(s) switch to Evac rate. 1.6 General Operation • If the Hazard Zone is Idle, activation of a Manual Release Switch starts the Manual Release Delay Timer (MRDT). The expiration of the MRDT activates the releasing circuits. • If the Hazard Zone is active and the configured time for the Manual Release Delay Timer (MRDT) is less than the time remaining on the Release Delay Timer (RDT), once the MRDT expires the MRDT activates and release occurs. If the RDT is less than the MRDT, once the RDT expires the RDT activates and release occurs. • If the Hazard Zone is activated by the Manual Release Switch, it cannot be aborted. • If the Hazard Zone is acivated by any other method, any configured abort switches will operate as described in 1.3 Abort Type. • System Reset will reset all circuits, including releasing circuits. Attention: When using a system that requires the acitvation of two automatic detection devices, detector installation spacing must be reduced to 0.7 times the linear spacing in accordance with National FIre Alarm Code, NFPA 72. Caution: To ensure a Manual Release Switch overrides an Abort Switch, in the FX- 3500RCU configuration software set the Man Rel Priority flag for the Hazard Zone zone to Yes. ! !

Operating the Panel

2.0 Releasing Circuit Wiring INPUT CIRCUIT WIRING: FM APPLICATIONS MUST HAVE CLASS A INITIATING CIRCUITS ONLY AND 90 HOUR BATTERY STANDBY OPERATION Only addressable M500S and MIX-M500SAP supervised output modules can be used as a releasing circuit. If the releasing circuit is wired as Class B, supervision of the solenoid coil is performed by the MP-3500R/W Solenoid EOL. Wiring for the releasing circuit is shown in Figure 1. Solenoid EOL module (MP-3500R/W) is used to supervise the solenoid coil. If the solenoid is already fitted with the directional diode then only the 47K EOL resistor is used. The supervisory current passes through the solenoid coil thus confirming the integrity of the solenoid coil for open coil. The wiring is supervised for the open and short conditions. 2.1 Releasing Circuit Wiring - Class B/Style Y Wiring Figure 1 Releasing Circuit Wiring - Class B or Style Y Wiring (+) (-) MIX-M500MAP MONITOR MODULE EOLR-1A EOL SUPERVSION RELAY RED BLACK VIOLET VIOLET 9 8 7 6 5 4 3 2 1 0 21 0 3 45 6 7 8 9 TENS ONES ADDRESS LOOP 21 0 3 45 6 7 8 9 (+) (-) (-) (+) MIX-M500SAP SUPERVISED CONTROL MODULE SOLENOID COIL MP-3500R/W SOLENOID EOL MODULE 9 8 7 6 5 4 3 2 1 0 21 0 3 45 6 7 8 9 TENS ONES ADDRESS LOOP 21 0 3 45 6 7 8 9 (-) (+) EOLR ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED POWER LINE 24 VDC TWISTED PAIRS RECOMMENDED SPECIAL APPLICATION PER UL864, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP. TS1 + - A LOOP1 B + - + - WARNING! DISCONNECT POWER TO ALL RELEASING DEVICES BEFORE SERVICING THE PANEL SLC LOOP WIRE

Operating the Panel

7 3.0 Typical Releasing Applications 3.1 Pre-Action/Agent Release, Single Activation Application Devices SLC Loop Any Detector in Hazard Zone Releasing Agent Addressable Module Abort Switch Manual Release Switch Logic AND Gate Both inputs are required. Logic Path OR Gate If either input is activated release occurs. Release commences if the following events occur: • a single detector correlated to the Hazard Zone enters alarm • the abort switch is not pressed • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires NOT Gate Input is required to be not activated. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

8 3.2 Pre-Action/Agent Release, Double Activation Application Devices SLC Loop Any Detector in Hazard Zone Releasing Agent Addressable Module Abort Switch Manual Release Switch Logic Logic Path AND Gate Both inputs are required. Release commences if the following events occur: • two detectors correlated to the Hazard Zone enter alarm • the abort switch is not pressed • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. NOT Gate Input is required to be not activated. OR Gate If either input is activated release occurs. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

9 3.3 Pre-Action/Agent Release, Triple Activation Application Devices SLC Loop Any Detector in Hazard Zone Releasing Agent Addressable Module Abort Switch Manual Release Switch Logic Logic Path AND Gate Both inputs are required. NOT Gate Input is required to be not activated. Release commences if the following events occur: • three detectors correlated to the Hazard Zone enter alarm • the abort switch is not pressed • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. OR Gate If either input is activated release occurs. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

10 3.4 Pre-Action/Agent Release, 2 Input Type Activation Application Devices SLC Loop Smoke Detector Heat Detector Releasing Agent Addressable Module Abort Switch Manual Release Switch Logic Logic Path AND Gate Both inputs are required. Release commences if the following events occur: • two detectors of different types correlated to the Hazard Zone enter alarm • the abort switch is not pressed • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. NOT Gate Input is required to be not activated. OR Gate If either input is activated release occurs. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

11 3.5 Deluge, Single Activation Application Devices SLC Loop Any Detector in Hazard Zone Deluge System Addressable Module Manual Release Switch Logic Logic Path OR Gate If either input is activated release occurs. Delay Timer Use FX-3500RCU Configurator to set type. Deluge commences if the following events occur: • a single detector correlated to the Hazard Zone enters alarm • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires.

Operating the Panel

12 3.6 Deluge, Double Activation Application Devices SLC Loop Any Detector in Hazard Zone Deluge System Addressable Module Manual Release Switch Logic Logic Path AND Gate Both inputs are required. OR Gate If either input is activated release occurs. Deluge commences if the following events occur: • two detectors correlated to the Hazard Zone enter alarm • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

13 3.7 Deluge, Triple Activation Application Devices SLC Loop Any Detector in Hazard Zone Deluge System Addressable Module Manual Release Switch Logic Logic Path AND Gate Both inputs are required. NOT Gate Input is required to be not activated. OR Gate If either input is activated release occurs. Deluge commences if the following events occur: • three detectors correlated to the Hazard Zone enter alarm • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

14 3.8 Deluge, 2 Input Type Activation Application Devices SLC Loop Smoke Detector Heat Detector Deluge System Addressable Module Manual Release Switch Logic Logic Path AND Gate Both inputs are required. Deluge commences if the following events occur: • two detectors of different types correlated to the Hazard Zone enter alarm • the delay timer expires OR • the Manual Release Switch is pressed • the delay timer expires. NOT Gate Input is required to be not activated. OR Gate If either input is activated release occurs. Delay Timer Use FX-3500RCU Configurator to set type.

Operating the Panel

4.0 Compatible Solenoids The following table lists the compatible solenoids. Table 1 FX-3500RCU Compatible Solenoids Manufacturer and Series Part Number Extended Description Parker 73212BN4TNLVNOC322C2 Valve Solenoid Siemens 500-697913BG Valve Solenoid ASCO 8210G207 Valve Solenoid T8210A107 Valve Solenoid BSCO 510006 Actuator TSP 17842 Actuator Kidde-Fenwal 486500-01 Actuator TLX Technologies PA0036 Actuator (FM Approved)

CANADA - Main Office

25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113 © Mircom 2013 Printed in Canada Subject to change without prior notice www.mircom.com U.S.A 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113 TECHNICAL SUPPORT North America Tel: (888) Mircom5 (888) 647-2665 International Tel: (905) 647-2665