Notifier FDM-1 Installation And Maintenance Instructions

Text of the manual

N500-75-00 1 I56-1463-02

FDM-1 Dual Monitor Module INSTALLATION AND MAINTENANCE INSTRUCTIONS Before Installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. General Description The Dual Monitor Module is intended for use in intelligent, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally closed security de- vices. The module has a single panel controlled red LED. Compatibility Requirements To ensure proper operation, this module shall be connected to a compatible Notifier system control panel (list available from Noti- fier). Mounting Mounts directly to 4” square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8”. Surface mounted elec- trical boxes (SMB500) are available from Notifier. Wiring NOTE: All wiring must conform to applicable local codes, or- dinances, and regulations. This module is intended for power limited wiring only. 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1. Note: Monitor module L (using terminals 6 and 7) re- sponds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automatically re- spond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to Figure 2A. Module mounting: Figure 2B: Specifications Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.7 mA (LED on) Average Operating Current: 750µA (LED flashing) EOL Resistance: 47K Ohms Maximum IDC wiring resistance: 1,500 Ohms Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Noncondensing Dimensions: 41/2″ H x 4″ W x 11/4″ D (Mounts to a 4″ square by 21/8″ deep box.) Accessories: SMB500 Electrical Box 12 Clintonville Rd Northford, CT 06472-1653 (203) 484-7161 Figure 1. Removing Rotary Switch Stop: A78-2611-19 A78-2610-14 A78-2318-13 9 8 7 6 5 4 3 2 1 0 TENS ONES ADDRESS LOOP 0 5 67 8 4 3 21 910 11 12 13 14 15 2 0 4 6 8 0 1 2 3 4 9 8 7 6 5 0 TENS ONES ADDRESS LOOP 8 6 4 2 0 5 6 7 8 9 4 3 21 10 11 12 1413 15 avoid duplicate addressing of modules on the system. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. www.PDF-Zoo.com

5 67 8

4 3 21 910 11 12 13 14 15 FROM PANEL OR (+) (—) TO NEXT (+) (—) DEVICE (+) (—) MONITOR CONNECT MODULES TO LISTED COMPATIBLE 32 VDC MAX. SHIELDED-TWISTED PAIR IS RECOMMENDED NOTIFIER CONTROL PANELS ONLY PREVIOUS DEVICE COMMUNICATION LINE MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) RESPONDS AT NEXT HIGHER ADDRESS. ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT. INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS. 47 K EOL RESISTOR ELR-47K MODULE 47 K EOL RESISTOR ELR-47K H L 9 8 7 6 5 4 3 2 1 0 TENS ONES ADDRESS LOOP 2 0 4 6 8 TWO INITIATING DEVICE CIRCUITS (L & H), EACH POWER LIMITED TO 230 A @ 12VDC MAX. ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED N500-75-00 2 I56-1463-02 ©2001 Notifier Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B: A78-2280-39 www.PDF-Zoo.com

Other Control Unit Manuals