Key Pages of Document

For installation purposes, please refer to the documentation sent after the pur-

chase-contract. This technical data should be considered as indicative. CLIMAVENETA may modify them at any moment. Rif 0152 0182 0202 0252 0262 0302 0352 0412 0452 0512 0552 0612 1 Liquid line 16 18 22 22 22 22 22 28 28 28 28 35 2 Delivery line 22 22 28 28 28 28 35 35 35 35 35 42 3 - 4 Evaporator (Victaulic connectors) 1” 1/2 1” 1/2 1” 1/2 1” 1/2 1” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 2” 1/2 8. DIMENSIONAL DRAWINGS 0152-061 ...

5.2 HYDRONIC UNIT

Available configurations Hydronic kit with one pump Hydronic kit with two pumps Compact units Plug and Play. The units in the NECS system are fitted standard with a hy- dronic group. This houses all the main hydraulic components, thereby optimising hydraulic and electric installation space, time and cost. The innovative QuickMind control fitted to the units in the NECS system, has been designed to work on systems with a low wa- ter content, offering highly professional alternatives to the in- stallation of systems featuring storage units. For special applications, a tank to i ...

For installation purposes, please refer to the documentation sent after the pur-

chase-contract. This technical data should be considered as indicative. CLIMAVENETA may modify them at any moment. 0604-1604 WITHOUT PUMPS 3 4 5 6 1 2 R1 R2 R4 R3 5 1 2 4 3 6 1 4 B H A C1 C2 C3 C4 3 C1 C2 C3 C4 2 Rif 0604 0704 0804 0904 1004 1104 1204 1404 1604 1 Liquid line 22 22 28 28 28 28 35 35 35 2 Delivery line 28 35 35 35 35 35 42 42 42 3 - 4 Evaporator (Victaulic connectors) 3” 3” 3” 3” 3” 4” 4” 4” 4” USE N°4 LIFTING ROP ...

For installation purposes, please refer to the documentation sent after the pur-

chase-contract. This technical data should be considered as indicative. CLIMAVENETA may modify them at any moment. 0604-1604 WITH PUMPS 3 4 5 6 1 2 R1 R2 R4 R3 5 1 2 4 3 6 1 4 B H A C1 C2 C3 C4 3 C1 C2 C3 C4 2 USE N°4 LIFTING ROPES WITH EQUAL LENGHT ONLY LIFTING SUPPORTING BASEMENT EVAPORATOR WATER INLET EVAPORATOR WATER OUTLET LIQUID LINE CONNECTION DELIVERY LINE CONNECTION POWER INLET MAIN ISOLATOR HANDLE ...

For installation purposes, please refer to the documentation sent after the pur-

chase-contract. This technical data should be considered as indicative. CLIMAVENETA may modify them at any moment. 0604-1604 WITHOUT PUMPS 3 4 5 6 1 2 R1 R2 R4 R3 5 1 2 4 3 6 1 4 B H A C1 C2 C3 C4 3 C1 C2 C3 C4 2 Rif 0604 0704 0804 0904 1004 1104 1204 1404 1604 1 Liquid line 22 22 28 28 28 28 35 35 35 2 Delivery line 28 35 35 35 35 35 42 42 42 3 - 4 Evaporator (Victaulic connectors) 3” 3” 3” 3” 3” 4” 4” 4” 4” USE N°4 LIFTING ROP ...

Size Pf (1) [kW] Q (1) [m3/h] Pump ref. F.L.I. [kW] F.L.A. [A] SA [A] 1 pump KP1 Dpu [kPa] Hu [kPa] 0152 39.5 6.79 I 3.0 5.6 57.6 1037 252,5 203 0182 45.8 7.88 I 3.0 5.6 57.6 664 251,1 208 0202 53.6 9.22 I 3.0 5.6 57.6 481 249,3 205 0252 60.5 10.41 I 3.0 5.6 57.6 360 247,5 204 0262 67.4 11.59 I 3.0 5.6 57.6 360 245,5 191 0302 80.2 13.79 L 2.2 5.0 36.8 154 233,02 207 0352 95.8 15.96 L 2.2 5.0 36.8 108 228,87 203 0412 104.5 17.97 M 3.0 6.0 38.3 108 287,64 253 0452 117.4 20.19 M 3.0 6.0 38.3 81 281,16 246 0512 131.4 22.60 M 3.0 6.0 38.3 63 273,10 236 0552 150.7 25.92 M 3.0 6.0 38.3 43 260,20 223 ...

Liquid chiller with remote condensation

Water-cooled indoor unit for producing chilled water, with con- nection to a remote condenser fi tted with hermetic rotary scroll compressors running on R410A, braised-welded plate exchang- ers and a thermostatic expansion valve. Base and panelling in hot-galvanised and painted sheet steel. 2.1 Standard unit composition Structure Base and frame in hot-galvanised shaped sheet steel with a suitable thickness. External panelling in PET-treated colaminate sheet, suitably thick, built to allow total access to t ...

DIMENSIONS AND WEIGHTS

CLEARANCE (See fol. page) NO PUMPS ONE PUMP TWO PUMPS A [mm] B [mm] H [mm] P [kg] A [mm] B [mm] H [mm] P [kg] A [mm] B [mm] H [mm] P [kg] R1 [mm] R2 [mm] R3 [mm] R4 [mm] 0152 1130 669 1255 270 1673 669 1255 385 1673 669 1255 420 600 600 800 - 0182 1130 669 1255 280 1673 669 1255 395 1673 669 1255 430 600 600 800 - 0202 1130 669 1255 290 1673 669 1255 405 1673 669 1255 440 600 600 800 - 0252 1130 669 1255 295 1673 669 1255 405 1673 669 1255 440 600 600 800 - 0262 1130 669 1255 300 1673 669 1255 415 1673 669 1255 450 60 ...

Mitsubishi Electric CLIMAVENETA NECS-ME Series user guide recommended for: OPTIVIEW YIA D, AQWL, Flotronic II 30GB075-200, NetCol5000-C065, MCW200D.

⚠️ Download Safety

The Chiller Technical bulletin (35 pages) is completely safe to download (last scan date: 06/04/2026).