Sub channel 1

Sub channel 2 Factory setting Change to Description Page OCMI2 OFF Collector minimum limitation option 2 46 CMIN2 10 °C Minimum collector temperature 2 46 OTCO2 OFF Tube collector function option 2 46 TCST2 07:00 Tube collector starting time 2 46 TCEN2 19:00 Tube collector ending time 2 46 TCRU2 30 s Tube collector runtime 2 46 TCIN2 30 min Tube collector standstill interval 2 46 LLOGI > Loading logic LOGIC PRIO Priority logic 48 PRIO1 1 Priority logic store 1 48 PRIO2 2 Priority logic store 2 48 OSTS OFF Store set option 50 TST1 45 °C Set stor ...

If the store set option is actived along with

the spreaded loading function, the spreaded loading function will only be active until the set temperature of the selected store is reached. Note The absorption store can only be selected in 3-store systems with 3 pumps. Pause control LLOGI / PSPEE Pause speed Selection: ON / OFF Factory setting: OFF If the pause speed is activated, the relay of the store which has been loaded last remains switched on dur- ing the loading break time. Speed is determined by the value adjusted in nLO. LLOGI / PDELA Pump delay Selection: ON / OFF Factory ...

Sub channel 1

Sub channel 2 Factory setting Change to Description Page CFR F 5 °C Antifreeze temperature collector off 48 FRPST 1 Antifreeze store selection 48 LLOGI > Loading logic LOGIC PRIO Priority logic 48 PRIO1 2 Priority logic store 1 48 PRIO2 1 Priority logic store 2 48 OSTS OFF Store set option 50 TST1 45 °C Set store temperature store 1 50 TST2 45 °C Set store temperature store 2 50 TSTS3 45 °C Set store temperature store 3 50 tLB 2 min Loading break time 48 tRUN 15 min Circulation runtime 48 PSPEE OFF Pause speed option 51 PDELA OFF Pump delay o ...

The controller compares the temperature at sen-

sor S1 to the temperatures at sensors S2, S4 and S5. If the measured temperature differences are higher than the adjusted switch-on temperature differences, the pump (R1) will be activated and the correspond- ing store will be loaded up to the adjusted maximum temperature via the valves (R3, R4). In this system, the desired store sequence can be adjusted. Depending on the valve type used, the corresponding valve logic has to be selected. System 5 3-store solar system with valve logic and priority logic Ventillogik 1 2 3 4 Durchflussrichtun ...

Sub channel 1

Sub channel 2 Factory setting Change to Description Page ARR 1 2 System 43 ROSA 0000 16 ROSA number 60 LOAD1 > Loading 1 DT1O 6 K Switch-on temperature difference 1 44 DT1F 4 K Switch-off temperature difference 1 44 DT1S 10 K Set temperature difference 1 44 RIS1 2 K Rise 1 44 S1MAX 60 °C Store maximum limitation 1 44 SMXS1 2 Sensor store max 1 44 LOAD2 > Loading 2 DT2O 6 K Switch-on temperature difference 2 44 DT2F 4 K Switch-off temperature difference 2 44 DT2S 10 K Set temperature difference 2 44 RIS2 2 K Rise 2 44 S2MAX 60 °C Store maximum l ...

The controller compares the temperatures at the col-

lector sensors S1 and S3 to the temperatures at S2 and S4. If one of the measured temperature differenc- es is higher than the adjusted switch-on temperature differences, the corresponding pump (R1, R2) or both pumps will be activated and the corresponding store Sensor/ terminal Designation Description S1 TCOL1 Temperature collector 1 S2 TST1B Temperature store 1 base S3 TCOL2 Temperature collector 2 S4 TST2B Temperature store 2 base S5 Optional sensor for meas- urement purposes or op- tions V40 Relay Description R1 Solar pump collecto ...

Resol DeltaSol BX L user guide recommended for: DeltaSol CS/4, DeltaSol B, DeltaSol MiniPool, FRP12, DeltaSol E.

⚠️ Download Safety

The Control Unit Installation operation and care (72 pages) is completely safe to download (last scan date: 22/03/2026).

Related PDF Instructions for Resol DeltaSol BX L:

Control Unit Equipment: Frequently Requested

Have some Questions about Resol DeltaSol BX L Device?

Get valuable and actionable advices from other Resol DeltaSol BX L device users. Describe your problem or question, regarding the using of DeltaSol BX L, in as much detail as possible, and other users will be able to answer you.