MR MSENSE BM Operating Instructions Manual

Text of the manual

© All rights reserved by Maschinenfabrik Reinhausen

Dissemination and reproduction of this document and use and disclosure of its content are strictly prohibited unless expressly permitted. Infringements will result in liability for compensation. All rights reserved in the event of the granting of patents, utility models or designs. The product may have been altered since this document was published. We reserve the right to change the technical data, design and scope of supply. Generally the information provided and agreements made when processing the individual quotations and orders are binding. The original operating instructions were written in German.

Table of contents

Maschinenfabrik Reinhausen GmbH 2019 3 5089542/05 EN MSENSE® BM Table of contents 1 Introduction......................................................................................................................... 8 1.1 Manufacturer.......................................................................................................................................  8 1.2 Completeness.....................................................................................................................................  8 1.3 Safekeeping........................................................................................................................................  8 1.4 Notation conventions ..........................................................................................................................  8 1.4.1 Hazard communication system............................................................................................................................. 8 1.4.2 Information system.............................................................................................................................................. 10 1.4.3 Instruction system ............................................................................................................................................... 10 1.4.4 Typographic conventions .................................................................................................................................... 11 2 Safety................................................................................................................................. 12 2.1 Appropriate use ................................................................................................................................  12 2.2 Inappropriate use..............................................................................................................................  12 2.3 Personnel qualification......................................................................................................................  13 2.4 Operator's duty of care .....................................................................................................................  13 3 IT security.......................................................................................................................... 14 4 Product description.......................................................................................................... 17 4.1 Scope of delivery ..............................................................................................................................  17 4.2 Function description..........................................................................................................................  17 4.3 Performance features .......................................................................................................................  18 4.4 Operating modes ..............................................................................................................................  19 4.5 Design...............................................................................................................................................  20 4.5.1 Bushing adapter and bushing coupling unit ........................................................................................................ 21 4.5.2 Control cabinet.................................................................................................................................................... 21 5 Packaging, transport and storage .................................................................................. 27 5.1 Packaging.........................................................................................................................................  27 5.1.1 Suitability............................................................................................................................................................. 27 5.1.2 Markings.............................................................................................................................................................. 28 5.2 Transportation, receipt and handling of shipments...........................................................................  28 5.3 Storage of shipments........................................................................................................................  29 5.4 Unpacking shipments and checking for transportation damages .....................................................  30

Table of contents

Maschinenfabrik Reinhausen GmbH 2019 4 5089542/05 EN MSENSE® BM 6 Mounting ........................................................................................................................... 32 6.1 Preparation .......................................................................................................................................  32 6.2 Installing the bushing adapter...........................................................................................................  32 6.3 Installing the bushing coupling unit...................................................................................................  34 6.4 Fitting the control cabinet to the transformer ....................................................................................  37 6.5 Connecting the device ......................................................................................................................  39 6.5.1 Cable recommendation....................................................................................................................................... 39 6.5.2 Information about connecting serial interfaces RS232 and RS485..................................................................... 40 6.5.3 Information about laying fiber-optic cable ........................................................................................................... 43 6.5.4 Connecting the bushing adapter to the bushing coupling unit ............................................................................ 43 6.5.5 Connecting the bushing coupling unit to the control cabinet............................................................................... 44 6.5.6 Connecting the voltage transformers for the reference system .......................................................................... 49 6.5.7 Connecting additional leads (optional)................................................................................................................ 50 6.5.8 Connecting the power supply.............................................................................................................................. 51 6.6 Checking functional reliability ...........................................................................................................  52 7 Commissioning................................................................................................................. 53 7.1 Determining the capacitance and dissipation factor of the bushings................................................  53 7.2 Establishing connection to visualization ...........................................................................................  53 7.3 Setting the language.........................................................................................................................  55 7.4 Setting date and time........................................................................................................................  56 7.5 Setting the parameters .....................................................................................................................  56 7.5.1 Commissioning wizard ........................................................................................................................................ 56 7.5.2 Setting the parameters manually ........................................................................................................................ 57 7.6 Performing standardization...............................................................................................................  58 7.7 Performing tests................................................................................................................................  58 7.7.1 Performing function tests .................................................................................................................................... 58 7.7.2 Electrical high-voltage tests on the transformer.................................................................................................. 59 7.7.3 Dielectric tests on transformer wiring.................................................................................................................. 59 8 Operation........................................................................................................................... 60 8.1 Establishing connection to visualization ...........................................................................................  60 8.2 Operating concept ............................................................................................................................  61 8.3 General.............................................................................................................................................  63 8.3.1 Activating/deactivating automatic launch of commissioning wizard.................................................................... 63 8.3.2 Setting measured value display .......................................................................................................................... 63

Table of contents

Maschinenfabrik Reinhausen GmbH 2019 5 5089542/05 EN MSENSE® BM 8.3.3 Remote behavior................................................................................................................................................. 64 8.3.4 Accessing online help ......................................................................................................................................... 64 8.3.5 Activating/deactivating the USB interface ........................................................................................................... 64 8.3.6 Set up automatic logout ...................................................................................................................................... 64 8.3.7 Activating/deactivating service user access........................................................................................................ 65 8.4 Configuring the network....................................................................................................................  66 8.5 Setting the transformer data for the reference system (optional) .....................................................  68 8.6 Configuring bushing monitoring........................................................................................................  68 8.6.1 Set the field designation...................................................................................................................................... 69 8.6.2 Configuring capacitance monitoring.................................................................................................................... 69 8.6.3 Configuring dissipation factor monitoring............................................................................................................ 72 8.6.4 Circuit breaker monitoring................................................................................................................................... 75 8.7 Displaying the state of the bushings.................................................................................................  75 8.8 Displaying the capacitance progression ...........................................................................................  76 8.9 Displaying the dissipation factor progression ...................................................................................  77 8.10 Displaying measured value recorder (optional) ................................................................................  77 8.11 Configuring digital inputs and outputs...............................................................................................  79 8.12 Event management...........................................................................................................................  81 8.12.1 Displaying and acknowledging events ................................................................................................................ 81 8.12.2 Configuring events .............................................................................................................................................. 82 8.12.3 Displaying event memory.................................................................................................................................... 83 8.13 SCADA .............................................................................................................................................  84 8.13.1 Configuring IEC 61850 (optional)........................................................................................................................ 85 8.13.2 Configuring IEC 60870-5-101 (optional) ............................................................................................................. 87 8.13.3 Configuring IEC 60870-5-103 (optional) ............................................................................................................. 92 8.13.4 Configuring IEC 60870-5-104 (optional) ............................................................................................................. 95 8.13.5 Configuring Modbus (optional)............................................................................................................................ 97 8.13.6 Configuring DNP3 (optional) ............................................................................................................................. 100 8.14 Configuring syslog ..........................................................................................................................  104 8.15 Time synchronization......................................................................................................................  105 8.15.1 Activating time synchronization using SNTP..................................................................................................... 106 8.15.2 Entering the time server address ...................................................................................................................... 107 8.15.3 Setting the time zone ........................................................................................................................................ 107 8.15.4 Setting synchronization interval ........................................................................................................................ 108 8.15.5 Automatic switchover between daylight saving time and standard time ........................................................... 108 8.15.6 Setting the date and time manually................................................................................................................... 108

Table of contents

Maschinenfabrik Reinhausen GmbH 2019 6 5089542/05 EN MSENSE® BM 8.16 User administration.........................................................................................................................  109 8.16.1 User roles.......................................................................................................................................................... 109 8.16.2 Changing password .......................................................................................................................................... 110 8.16.3 Creating, editing and deleting users.................................................................................................................. 111 8.16.4 Setting access rights to parameters and events ............................................................................................... 113 8.16.5 User authentication via RADIUS (optional)....................................................................................................... 114 8.17 Information about device ................................................................................................................  116 8.17.1 Hardware........................................................................................................................................................... 116 8.17.2 Software............................................................................................................................................................ 117 8.18 Import/export manager ...................................................................................................................  117 8.18.1 Exporting data................................................................................................................................................... 117 8.18.2 Importing data (software version 3.44 and later)............................................................................................... 119 8.19 Linking signals and events..............................................................................................................  120 8.19.1 Linking digital outputs and control system messages....................................................................................... 120 9 Inspection and maintenance ......................................................................................... 123 9.1 Care................................................................................................................................................  123 9.2 Inspection .......................................................................................................................................  123 9.3 Maintenance ...................................................................................................................................  123 10 Fault elimination............................................................................................................. 124 10.1 General faults .................................................................................................................................  124 10.2 Signal lights and digital outputs ......................................................................................................  124 10.3 Human-machine interface...............................................................................................................  125 10.4 Other faults .....................................................................................................................................  125 11 Messages ........................................................................................................................ 127 11.1 Event messages .............................................................................................................................  127 12 Uninstallation.................................................................................................................. 138 12.1 Removing the control cabinet .........................................................................................................  138 12.2 Removing the bushing adapter and bushing coupling unit.............................................................  140 13 Disposal........................................................................................................................... 142 14 Technical data................................................................................................................. 143 14.1 Bushing adapter..............................................................................................................................  143 14.2 Bushing coupling unit......................................................................................................................  146

Table of contents

Maschinenfabrik Reinhausen GmbH 2019 7 5089542/05 EN MSENSE® BM 14.3 Control cabinet................................................................................................................................  147 14.3.1 Connection terminals ........................................................................................................................................ 148 14.3.2 Voltage measurement UI 5-3 ............................................................................................................................ 149 14.3.3 DIO 28-15 digital inputs and outputs................................................................................................................. 150 14.3.4 CPU (central processing unit) I ......................................................................................................................... 151 14.3.5 System networking............................................................................................................................................ 154 14.3.6 Bus extension module....................................................................................................................................... 155 14.4 Connection cable............................................................................................................................  155 15 Appendix ......................................................................................................................... 157 15.1 Measured value log ........................................................................................................................  157 Glossary .......................................................................................................................... 159 List of key words ............................................................................................................ 160

Maschinenfabrik Reinhausen GmbH 2019

8 5089542/05 EN MSENSE® BM 1 Introduction This technical file contains detailed descriptions on the safe and proper in- stallation, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the prod- uct. This technical file is intended solely for specially trained and authorized per- sonnel. 1.1 Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg, Germany Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-mail: [email protected] Further information on the product and copies of this technical file are avail- able from this address if required. 1.2 Completeness This technical file is incomplete without the supporting documents. The following documents are considered supporting documents: ▪ Connection diagrams ▪ Supplement (optional) 1.3 Safekeeping Keep this technical file and all supporting documents ready at hand and ac- cessible for future use at all times. 1.4 Notation conventions This section contains an overview of the symbols and textual emphasis used. 1.4.1 Hazard communication system Warnings in this technical file are displayed as follows.

Maschinenfabrik Reinhausen GmbH 2019

9 5089542/05 EN MSENSE® BM 1.4.1.1 Warning relating to section Warnings relating to sections refer to entire chapters or sections, sub-sec- tions or several paragraphs within this technical file. Warnings relating to sections use the following format: WARNING Type of danger! Source of the danger and outcome. ►Action ►Action 1.4.1.2 Embedded warning information Embedded warnings refer to a particular part within a section. These warn- ings apply to smaller units of information than the warnings relating to sec- tions. Embedded warnings use the following format:  DANGER! Instruction for avoiding a dangerous situation. 1.4.1.3 Signal words and pictograms The following signal words are used: Signal word Definition DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates measures to be taken to prevent damage to property. Table 1: Signal words in warning notices Pictograms warn of dangers: Pictogram Definition Warning of a danger point Warning of dangerous electrical voltage

Maschinenfabrik Reinhausen GmbH 2019

10 5089542/05 EN MSENSE® BM Pictogram Definition Warning of combustible substances Warning of danger of tipping Warning of danger of crushing Table 2: Pictograms used in warning notices 1.4.2 Information system Information is designed to simplify and improve understanding of particular procedures. In this technical file it is laid out as follows: Important information. 1.4.3 Instruction system This technical file contains single-step and multi-step instructions. Single-step instructions Instructions which consist of only a single process step are structured as fol- lows: Aim of action ü Requirements (optional). ►Step 1 of 1. ð Result of step (optional). ð Result of action (optional). Multi-step instructions Instructions which consist of several process steps are structured as follows:

Maschinenfabrik Reinhausen GmbH 2019

11 5089542/05 EN MSENSE® BM Aim of action ü Requirements (optional). 1. Step 1. ð Result of step (optional). 2. Step 2. ð Result of step (optional). ð Result of action (optional). 1.4.4 Typographic conventions The following typographic conventions are used in this technical file: Typographic convention Purpose Example UPPERCASE Operating controls, switches ON/OFF [Brackets] PC keyboard [Ctrl] + [Alt] Bold Software operating controls Press Continue button …>…>… Menu paths Parameter > Control parameter Italics System messages, error messages, signals Function monitoring alarm triggered [► Number of pages]. Cross reference [► 41]. Table 3: Typographic conventions

Maschinenfabrik Reinhausen GmbH 2019

12 5089542/05 EN MSENSE® BM 2 Safety 2.1 Appropriate use The product is a monitoring system and is used to monitor capacitance- graded bushings on power transformers in the Um = 123...420 kV voltage levels (with voltage levels up to 765 kV on request). You can use the product to detect breakdowns at partial capacitances in the bushing and to monitor- ing aging in the bushings. The product is designed solely for use in electrical energy systems and facili- ties. It may be used only if you observe the requirements and conditions listed in this technical file as well as the warnings in this technical file and the warnings posted on the product. This applies across the entire service life of the product, from delivery to installation and operation through to disassem- bly and disposal. The following is considered appropriate use: ▪ Use the product only with the bushings specified in the order. ▪ Use the product only for high-voltage transformer bushings and subject to similar installation conditions and thermal loads. ▪ Use the product only for bushings of the same type (manufacturer, series, technology, model year) ▪ Use the product only for bushings that were not previously damaged. ▪ Operate the product in accordance with this technical file, the agreed- upon delivery conditions and the technical data. ▪ Ensure that all necessary work is performed by qualified personnel only. ▪ Only use the equipment and special tools included in delivery for the in- tended purpose and in accordance with the specifications of this technical file. ▪ Only operate the product in industrial areas. Observe the notes in this technical file regarding electromagnetic compatibility and the technical data. 2.2 Inappropriate use Use is considered to be inappropriate if the product is used other than as de- scribed in the Appropriate use section. In addition, observe the following: ▪ The product is not suited for extending the permitted service life of the bushing specified by the bushing manufacturer. ▪ The product is not a protective device. Do not use it to handle safety-re- lated functions. ▪ Risk of explosion and fire from highly flammable or explosive gases, va- pors, or dusts. Do not operate the product in areas at risk of explosion. ▪ The product is not intended for use in environments subject to strong cor- rosion effects.

Maschinenfabrik Reinhausen GmbH 2019

13 5089542/05 EN MSENSE® BM ▪ Unauthorized or inappropriate changes to the product may lead to per- sonal injury, material damage and operational faults. Only modify the product after consultation with Maschinenfabrik Reinhausen GmbH. ▪ Do not connect the product components to measurement systems from other manufacturers, because this can lead to bushing monitoring errors. 2.3 Personnel qualification The product is designed solely for use in electrical energy systems and facili- ties operated by appropriately trained staff. This staff comprises people who are familiar with the installation, assembly, commissioning and operation of such products. 2.4 Operator's duty of care To prevent accidents, disruptions and damage as well as unacceptable ad- verse effects on the environment, those responsible for transport, installa- tion, operation, maintenance and disposal of the product or parts of the prod- uct must ensure the following: ▪ All warning and hazard notices are complied with. ▪ Personnel are instructed regularly in all relevant aspects of operational safety, the operating instructions and particularly the safety instructions contained therein. ▪ Regulations and operating instructions for safe working as well as the rel- evant instructions for staff procedures in the case of accidents and fires are kept on hand at all times and are displayed in the workplace where applicable. ▪ The product is only used when in a sound operational condition and safety equipment in particular is checked regularly for operational reliability. ▪ Only replacement parts, lubricants and auxiliary materials which are au- thorized by the manufacturer are used. ▪ The specified operating conditions and requirements of the installation lo- cation are complied with. ▪ All necessary devices and personal protective equipment for the specific activity are made available. ▪ The prescribed maintenance intervals and the relevant regulations are complied with. ▪ Installation, electrical connection and commissioning of the product may only be carried out by qualified and trained personnel in accordance with this technical file. ▪ The operator must ensure appropriate use of the product.

3 IT security

Maschinenfabrik Reinhausen GmbH 2019 14 5089542/05 EN MSENSE® BM 3 IT security Observe the following recommendations for secure operation of the product. General ▪ Ensure that only authorized personnel have access to the device. ▪ Only use the device within an ESP (electronic security perimeter). Do not connect the device to the Internet in an unprotected state. Use mecha- nisms for vertical and horizontal network segmenting and security gate- ways (firewalls) at the transition points. ▪ Ensure that the device is only operated by trained personnel who are fa- miliar with IT security. Commissioning Observe the following recommendations for device commissioning: ▪ User IDs must be unique and assignable. Do not use a "Group account" function or the "Auto login" function. ▪ Activate the "Auto logout [►Section 8.3.6, Page 64]" function. ▪ Restrict the rights of the individual user groups as much as is feasible; this helps avoid errors during operations. A user with the "Operator" role, for example, should only perform operations and should not be able to change any device settings. ▪ Delete or disable the default "admin" user ID. This requires first creating a new user account with the "Administrator" role. You can then use it to delete or disable the default "admin" account. ▪ Deactivate service user access [►Section 8.3.7, Page 65]. ▪ Enable SSL/TLS encryption [►Section 8.3, Page 63]; access to the de- vice is then only possible using the SSL/TLS protocol. In addition to en- crypting communication, this protocol also checks the authenticity of the server. ▪ Use TLS version 1.2 or higher wherever possible. ▪ Integrate the device into a public key infrastructure. Create your own SSL certificates for this if necessary and then import it. ▪ Connect the device to a central log server by using the syslog interface [►Section 8.14, Page 104]. Operation Observe the following recommendations during device operation: ▪ Change the password at regular intervals. ▪ Export the security log [►Section 8.18.1, Page 117] at regular intervals. ▪ Check the log files regularly for unauthorized system access and other se- curity-related events.

3 IT security

Maschinenfabrik Reinhausen GmbH 2019 15 5089542/05 EN MSENSE® BM Interfaces The device uses the following interfaces for communication: Figure 1: Interfaces of the CPU assembly Interface Protocol Port Description CAN 1 - - Connection of the DIO assembly CAN 2 - - Communication with other ISM® devices (e.g. parallel operation) COM 1 - - Internal system interface COM 2 - - Serial interface (SCADA) USB - - Import or export of data ETH 1 TCP 102 IEC 61850 ETH 1 TCP 502 Modbus2) ETH 1 TCP 20000 DNP32) ETH 1 UDP 67 DHCP server ETH 2.x TCP 21 FTP1) (only for MR service) ETH 2.x TCP 80 HTTP for web-based visualization1) ETH 2.x TCP 443 HTTPS for web-based visualization1) ETH 2.x TCP 990 FTPS (only for MR service) ETH 2.x TCP 8080 HTTP for web-based visualization1) ETH 2.x TCP 8081 HTTPS for web-based visualization1) Table 4: Interfaces and open ports of the CPU assembly 1) Port is closed if you activate the device's SSL encryption. 2) Default setting; if you have modified the port for the control system proto- col, only the set port is opened.

3 IT security

Maschinenfabrik Reinhausen GmbH 2019 16 5089542/05 EN MSENSE® BM Encryption standards The device supports the following TLS versions: ▪ TLS 1.0 ▪ TLS 1.1 ▪ TLS 1.2 The device uses the following cipher suites for a TLS-secured connection: Key exchange Authentication Encryption Key length Operating mode Hash func- tion TLS ECDHE RSA WITH AES 128 CBC SHA1) DHE SHA265 ECDHE ECDSA GCM SHA256 ECDH 256 CBC SHA1) RSA1) SHA256 GCM SHA384 Table 5: Cipher suite 1) Not available with TLS version >= 1.2 The device uses the SHA256 hash function to save passwords. Also refer to 2 Exporting data [► 117] 2 General [► 63]

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 17 5089542/05 EN MSENSE® BM 4 Product description This chapter contains an overview of the design and function of the product. 4.1 Scope of delivery The following items are included in the delivery: ▪ Control cabinet with MSENSE® BM bushing monitoring ▪ For each bushing to be monitored (3 or 6): – Bushing adapter – Connection cable for the bushing adapter and bushing coupling unit – Bushing coupling unit – Set of fasteners for the bushing coupling unit – Connection cable for the bushing coupling unit and ISM® control cabi- net ▪ Technical documentation Please note the following: ▪ Check the shipment for completeness on the basis of the shipping docu- ments. ▪ Store the parts in a dry place until installation. 4.2 Function description The product is a monitoring system and is used to monitor capacitance graded bushings on power transformers. You can use the product to detect breakdowns at partial capacitances in the bushings and to monitor aging in the bushings. In order to evaluate the state of the bushing, the bushings are equipped with a measuring device with which the system can continuously determine the change in capacitance ΔC1 and the change in dissipation factor Δtanδ of the bushings during operation. In addition, the system records the voltage of the 3-phase reference system.

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 18 5089542/05 EN MSENSE® BM The monitoring system takes advantage of the implemented algorithms to largely compensate for voltage fluctuations and temperature fluctuations in the 3-phase system, thereby ensuring reliable monitoring for the bushings. Figure 2: Operating principle 4.3 Performance features The MSENSE® BM monitoring system monitors the bushings of a power transformer and has the following features: ▪ Monitoring of oil-impregnated paper bushings (OIP) and resin-impreg- nated paper bushings (RIP) at voltage levels of Um = 123...420 kV (with voltage levels up to 765 kV on request) ▪ Optional: Monitoring of 6 bushings, where 3 bushings each form one set (field 1 and field 2) ▪ Online monitoring of the bushing by means of capacitance measurement and dissipation factor measurement – Monitoring the change in capacitance C1 – Monitoring the change in the dissipation factor tanδ – 3-phase reference system (e.g. voltage transformer) – Compensation for temperature fluctuations – Compensation for the effects of weather – Compensation for voltage fluctuations – Compensation for grid asymmetry ▪ Display of the measured and calculated values ▪ Status messages via digital outputs ▪ Web-based visualization ▪ SCADA – IEC 60870-5-101 – IEC 60870-5-103 – IEC 60870-5-104

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 19 5089542/05 EN MSENSE® BM – IEC 61850 (edition 1 and edition 2) – Modbus (RTU, TCP, ASCII) – DNP3 4.4 Operating modes Local mode (LOCAL) In the Local operating mode, you can make entries and input commands us- ing the device's operating controls. You cannot use inputs or the control sys- tem to make entries or enter commands. Remote mode (REMOTE) In the Remote operating mode, you can make entries and carry out com- mands using digital inputs or the control system, depending on the setting of the Remote behavior [►Section 8.3.3, Page 64] parameter.

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 20 5089542/05 EN MSENSE® BM 4.5 Design The complete system consists of the following subassemblies: Figure 3: Design 1 Bushing adapter 2 Connection cable for the bushing adapter and bushing coupling unit 3 Bushing coupling unit 4 Connection cable for the bushing coupling unit and control cabinet 5 Control cabinet with monitoring system

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 21 5089542/05 EN MSENSE® BM 4.5.1 Bushing adapter and bushing coupling unit The bushing adapter is used to pick up the measured voltage at the bushing test tap. The downstream bushing coupling unit is used to adjust the mea- sured voltage. Both components are tuned to the bushings to be monitored in accordance with your order. They may be used only for those bushings. The following components are used: ▪ Bushing adapter (A001...A008) ▪ C002: Bushing coupling unit Type Bushing types A001 Micafil RTKF Micafil RTKG A002 HSP SETFt 1550/420-1800 HSP SETFt 600/123-2000 A003 ABB GOB 1050-750-1100-0.6-B ABB GSA 123-OA/1600/0.5 ABB GSA 52-OA/2000/0.5 A004 Trench COT 750-800 A005 HSP SETFt 750-170-4000 HSP SETFt 1200/245-1250 HSP SETFt 1425-420-1600 HSP SESTFt 1050-245-B E6 B HSP SESTFt 1425-420-B E6 B-1600A HSP EKTG 72.5-800 kV A006 PCORE CSA standard POC ser. 2 ABB GOE, GSB (245...550 kV) A007 PCORE B-81515-57-70 A008 Passoni Villa PNO, POBO, PCTO, PAO < 110 kV Table 6: Bushing adapter 4.5.2 Control cabinet The control cabinet contains the control system for monitoring the bushings as well as various display elements and operating controls.

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 22 5089542/05 EN MSENSE® BM 4.5.2.1 Display elements and operating controls The control cabinet contains the following components: Figure 4: Control cabinet display elements and operating controls 1 Local/Remote switch 2 Signal light (yellow, red) 3 Ethernet interface ETH1.1 (RJ45) 4 Plug socket X19, max. 10 A 5 Fuses F14 and F25 4.5.2.2 Assemblies Depending on configuration, the device may have various assemblies which perform the functions required. The functions of the assemblies are de- scribed in the following sections. You will find more information about the as- semblies in the Technical data [►Section 14, Page 143] section. 4.5.2.2.1 Power supply The G1 PULS DIMENSION QS3.241 assembly supplies power to the de- vice. Figure 5: G1 PULS DIMENSION QS3.241 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 23 5089542/05 EN MSENSE® BM 4.5.2.2.2 CPU (central processing unit) I The CPU I assembly is the central computing unit for the device. It contains the following interfaces: ▪ Internal system interface RS232 (COM1) ▪ Serial interface RS232/485 (COM2) ▪ 3x Ethernet (ETH1, ETH 2.1, ETH 2.2) ▪ USB (USB 2.0) ▪ 2x CAN bus (CAN 1, CAN 2) Figure 6: CPU I assembly 4.5.2.2.3 Voltage measurement The UI 5-3 assembly is used for measuring 3-phase voltage. Figure 7: UI 5-3 assembly

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 24 5089542/05 EN MSENSE® BM 4.5.2.2.4 DIO 28-15 digital inputs and outputs The DIO 28-15 assembly makes 28 inputs and 15 outputs (6 N/O contacts, 9 change-over contacts) available. Figure 8: DIO 28-15 assembly 4.5.2.2.5 Media converter The MC 2-2 assembly is a media converter, which converts 2 electrical con- nections (RJ45) to one fiber-optic cable connection each. Each is converted independently of the other. The following interfaces are available: ▪ 2x RJ45 (ETH12, ETH22) ▪ 2x Duplex-LC (SFP module) (ETH11, ETH21) The media converter is designed to be transparent for the network and does not have its own IP address.

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 25 5089542/05 EN MSENSE® BM Figure 9: MC 2-2 assembly 4.5.2.2.6 Media converter with managed switch The assembly SW 3-3 is a media converter with managed switch. It com- bines two independent functions and provides you with the following inter- faces: ▪ A media converter converts an electric connection (RJ45) into a fiber-optic cable connection – RJ45 (ETH12) – Duplex-LC (SFP module) (ETH11) ▪ Managed switch with redundancy function (PRP or RSTP) – 2x RJ45 (ETH23, ETH24), device-internal connection – 2x Duplex-LC (SFP module) (ETH21, ETH22), redundancy connection The following redundancy functions are available to you according to your order: ▪ PRP (standard setting) ▪ RSTP

4 Product description

Maschinenfabrik Reinhausen GmbH 2019 26 5089542/05 EN MSENSE® BM Figure 10: SW 3-3 assembly 4.5.2.2.7 Bus extension module The assemblies BEM 1 (master) and BES 1 (slave) are bus extension mod- ules which are used to extend the system by one additional busbar with ad- ditional assemblies. Data is transmitted via fiber-optic cable. The assembly BES 1 has a connection for supplying voltage to the additional busbar. Figure 11: Assemblies BEM 1 and BES 1

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2019 27 5089542/05 EN MSENSE® BM 5 Packaging, transport and storage 5.1 Packaging The products are sometimes supplied with sealed packaging and sometimes in a dry state, depending on requirements. Sealed packaging surrounds the packaged goods with plastic foil on all sides. Products that have also been dried are identified by a yellow label on the sealed packaging. In the dry state, delivery is also possible in a transport container. The information in the following sections should be applied as appropriate. 5.1.1 Suitability NOTICE Property damage due to incorrectly stacked crates! Stacking the crates incorrectly can lead to damage to the packaged goods. ►The outer marking on the packaging states if, for example, the on-load tap-changer or selector has been packed upright. Never stack these crates. ►General rule: Do not stack crates above a height of 1.5 m. ►For other crates: Only stack up to 2 equally sized crates on top of one an- other. The packaging is suitable to ensure undamaged and fully functional means of transportation in compliance with local transportation laws and regula- tions. The packaged goods are packed in a sturdy crate. This crate ensures that, when in the intended transportation position, the packaged goods are stabi- lized to prevent impermissible changes in position, and that none of the parts touch the loading surface of the means of transport or touch the ground after unloading. Sealed packaging surrounds the packaged goods with plastic foil on all sides. The packaged goods are protected from humidity using a desiccant. The plastic foil was bonded after the desiccant is added.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2019 28 5089542/05 EN MSENSE® BM 5.1.2 Markings The packaging bears a signature with instructions for safe transport and cor- rect storage. The following symbols apply to the shipment of non-hazardous goods. Adherence to these symbols is mandatory. Protect against moisture Top Fragile Attach lifting gear here Center of mass Table 7: Shipping pictograms 5.2 Transportation, receipt and handling of shipments WARNING Danger of death or severe injury! Danger of death or serious injuries due to tipping or falling load. ►Only transport the crate when closed. ►Do not remove the securing material used in the crate during transport. ►If the product is delivered on a pallet, secure it sufficiently. ►Only trained and authorized persons may select the sling gear and se- cure the load. ►Do not walk under the suspended load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated on the delivery slip. In addition to oscillation stress, jolts must also be expected during trans- portation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate tips over, falls from a certain height (e.g. when slings tear) or is subject to an unbroken fall, damage must be expected regardless of the weight. Every delivered shipment must be checked for the following by the recipient before acceptance (acknowledgment of receipt): ▪ Completeness based on the delivery slip ▪ External damage of any type The checks must take place after unloading when the crate or transport con- tainer can be accessed from all sides.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2019 29 5089542/05 EN MSENSE® BM Visible damage If external transport damage is found upon receipt of the shipment, proceed as follows: ▪ Immediately record the identified transport damage in the shipping docu- ments and have this countersigned by the carrier. ▪ In the event of severe damage, total loss or high damage costs, immedi- ately notify the manufacturer and the relevant insurance company. ▪ After identifying damage, do not modify the condition of the shipment fur- ther and retain the packaging material until an inspection decision has been made by the transport company or the insurance company. ▪ Record the details of the damage immediately on site together with the carrier involved. This is essential for any claim for damages. ▪ Photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation). ▪ NOTICE! If the product is delivered in sealed packaging, inspect this im- mediately. If the sealed packaging is damaged, do not under any circum- stances install or commission the packaged goods. Either re-dry the dried packaged goods as per the operating instructions, or contact the manu- facturer to agree on how to proceed. Failure to do so may result in dam- age to the packaged goods. ▪ Identify the damaged parts. Hidden damage When damages are not determined until unpacking after receipt of the ship- ment (hidden damage), proceed as follows: ▪ Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report. ▪ Observe the time periods applicable to such actions in the respective country. Inquire about these in good time. With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insur- ance terms and conditions. 5.3 Storage of shipments Packaged goods dried by Maschinenfabrik Reinhausen Upon receipt of the shipment, immediately remove the packaged goods dried by Maschinenfabrik Reinhausen from the sealed packaging and store air-tight in dry insulating fluid until used if the packaged goods were not sup- plied in insulating fluid. Non-dried packaged goods Non-dried packaged goods but with a functional sealed packaging can be stored outdoors when the following conditions are complied with.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2019 30 5089542/05 EN MSENSE® BM When selecting and setting up the storage location, ensure the following: ▪ Protect stored goods against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access. ▪ Store the crates on timber beams and planks as a protection against ris- ing damp and for better ventilation. ▪ Ensure sufficient carrying capacity of the ground. ▪ Keep entrance paths free. ▪ Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on. Protect the packaging foil from direct sunlight so that it does not disintegrate under the influence of UV rays, which would cause the packaging to lose its sealing function. If the product is installed more than 6 months after delivery, suitable mea- sures must be taken without delay. The following measures can be used: ▪ Correctly regenerate the drying agent and restore the sealed packaging. ▪ Unpack the packed goods and store in a suitable storage space (well ven- tilated, as dust-free as possible, humidity < 50% where possible). 5.4 Unpacking shipments and checking for transportation damages ▪ NOTICE! Transport the packaged crate to the place where installation will take place. Do not open the sealed packaging until just before installation. Otherwise, damage to the packaged goods may occur due to ineffectively sealed packaging. ▪  WARNING! When unpacking, check the condition of the packaged goods. Place packaged goods in an upright crate and protect against tip- ping out. If this is not done, the packaged goods may be damaged and se- rious injuries may result. ▪ Check completeness of accessories based on the delivery slip. Attachment points for lifting gear WARNING Risk of tipping and danger of falling load! Danger of death and damage to property due to tipping or falling load. ►Only trained and appointed persons may select the sling gear and secure the load. ►Do not walk under the hanging load. ►Use means of transport and lifting gear with a sufficient carrying capacity in accordance with the weight stated in the Technical data [►Section 14, Page 143] section. ▪ Control cabinet: – Retractable brackets on top left and right, opening size 25 x 25 mm.

5 Packaging, transport and storage

Maschinenfabrik Reinhausen GmbH 2019 31 5089542/05 EN MSENSE® BM Figure 12: Lifting-gear limit stop of the control cabinet –  WARNING! The cable angle of the lifting gear must always be less than 45° in relation to the vertical. Otherwise, the control cabinet may be damaged and serious injuries may result. Figure 13: Maximum permissible cable angle for the lifting-gear limit stop of the control cabinet Also refer to 2 Technical data [► 143]

Maschinenfabrik Reinhausen GmbH 2019

32 5089542/05 EN MSENSE® BM 6 Mounting This chapter describes how to correctly install and connect the device. Note the connection diagrams provided. DANGER Electric shock! Risk of fatal injury due to electrical voltage. Always observe the following safety regulations when working in or on electrical equipment. ►Disconnect the equipment. ►Lock the equipment to prevent an unintentional restart. ►Make sure all poles are de-energized. ►Ground and short-circuit. ►Cover or cordon off adjacent energized parts. CAUTION Fire hazard! If you commission the transformer and the bushing's test tap is not grounded, depending on the type of bushing, there is a risk that the bushing will be destroyed and the transformer will catch fire. ►Observe the operating instructions for the bushing. ►Only commission the transformer if the cap for the bushing test tap is fit- ted or if the bushing adapter and bushing coupling unit are fitted and con- nected. NOTICE Damage to the device! Electrostatic discharge may cause damage to the device. ►Take precautionary measures to prevent the build-up of electrostatic charges on work surfaces and personnel. 6.1 Preparation Before installation, check that the serial numbers of the bushing adapter and bushing coupling unit match those on the delivery slip and are appropriate for the bushing you have specified. 6.2 Installing the bushing adapter Carry out the operating steps listed below on all bushings. To install the bushing adapter, proceed as follows: 1. Remove the cap for the bushing test tap. Store the cap in a safe place for possible operation of the bushing later without the monitoring system.

Maschinenfabrik Reinhausen GmbH 2019

33 5089542/05 EN MSENSE® BM 2. Ensure that the test tap and the bushing adapter are dry and free of dirt. If this is not the case, clean and dry them with a cloth. 3. Ensure that the sealing ring of the bushing adapter is present and posi- tioned correctly. Figure 14: Checking the sealing ring (bushing adapter A001 and A002) 4. NOTICE! Install the bushing adapter at the bushing test tap. During the installation, ensure that the tightening torque corresponds to the specifica- tions from the bushing manufacturer regarding installing the cap on the test tap. Otherwise damage to the bushing may result. Figure 15: Installing the bushing adapter (example using bushing adapter A002)

Maschinenfabrik Reinhausen GmbH 2019

34 5089542/05 EN MSENSE® BM 6.3 Installing the bushing coupling unit You can also use your own supporting plate instead of the provided sup- porting plate. In this case, you must ensure that the bushing coupling unit is continuously connected to the transformer tank by a low-resistance connec- tion (e.g. via lock washers under the screw heads of the M4 fixing screws). The necessary dimensions for the holes can be found in the technical data for the bushing coupling unit [►Section 14.2, Page 146]. Carry out the operating steps listed below on all bushings. The bushing coupling unit must be fastened to the bushing flange near the bushing adapter. To do so, proceed as follows: 1. Unscrew the cover bolts for the bushing coupling unit and lift off the cover. Figure 16: Loosening the screws and removing the cover

Maschinenfabrik Reinhausen GmbH 2019

35 5089542/05 EN MSENSE® BM 2. Insert Allen screws with lock washers into the intended holes and fasten the supporting plate on the other side with lock washers and nuts. Figure 17: Fastening the bushing coupling unit to the supporting plate 3. Check whether the jumper is inserted. If not, insert the jumper. Figure 18: Checking the jumper

Maschinenfabrik Reinhausen GmbH 2019

36 5089542/05 EN MSENSE® BM 4. Place the cover on the bushing coupling unit and screw it in place. Figure 19: Fastening the cover 5. Unscrew the fixing screw for the bushing flange. 6. Install the supporting plate on the bushing flange. Figure 20: Installing the supporting plate on the bushing flange

Maschinenfabrik Reinhausen GmbH 2019

37 5089542/05 EN MSENSE® BM 7. Connect the grounding electrode conductor to the supporting plate and transformer. Figure 21: Connecting the grounding electrode conductor 6.4 Fitting the control cabinet to the transformer This section describes how to install the control cabinet on the transformer. The special design with vibration dampers must be used on transformers where the control cabinet is subjected to vibration. The control cabinet has 4 fixing attachments on the rear for securing it. To mount the control cabinet on the transformer, proceed as follows: 1. Attach 4 stud bolts (not supplied by MR) to the transformer tank. Figure 22: Fastening the stud bolts

Maschinenfabrik Reinhausen GmbH 2019

38 5089542/05 EN MSENSE® BM 2. Use the fixing attachments to attach the control cabinet to the stud bolts and align it vertically on the transformer tank. Figure 23: Attaching the control cabinet 3. NOTICE! Secure the control cabinet without subjecting it to mechanical tension. Otherwise, the control cabinet may be damaged. Figure 24: Fastening the control cabinet

Maschinenfabrik Reinhausen GmbH 2019

39 5089542/05 EN MSENSE® BM 4. Connect the grounding cable to the control cabinet and transformer tank, holding it against the control cabinet using a size 36 wrench. Figure 25: Connecting the grounding cable to the control cabinet 6.5 Connecting the device 6.5.1 Cable recommendation Please note the following Maschinenfabrik Reinhausen recommendation when wiring the device. Excessive line capacitance can prevent the relay contacts from breaking the contact current. In control circuits operated with alternating current, take into account the effect of the line capacitance of long control cables on the func- tion of the relay contacts. If you want to route Ethernet connections from a control cabinet or building, we recommend the use of fiber-optic cables (in accordance with the IEC 61850-90-4 recommendation). Cable Assembly, terminal Cable type Conductor cross-sec- tion Max. length Voltage supply X1 Unshielded 2.5 mm² - Voltage measurement X10 (UI 5-3) Shielded 2.5 mm² -

Maschinenfabrik Reinhausen GmbH 2019

40 5089542/05 EN MSENSE® BM Cable Assembly, terminal Cable type Conductor cross-sec- tion Max. length Digital signal inputs DIO 28-15, DIO 42-20 Shielded 1.5 mm2 400 m (<25 Ω/km) Digital signal outputs* DIO 28-15, DIO 42-20 Shielded 1.5 mm2 - RS232, SUB-D CPU I Shielded 0.25 mm2 25 m RS485; SUB-D CPU I Shielded 0.25 mm2 140 m CAN bus CPU I Shielded 0.75 mm² 2,000 m (total CAN bus) Ethernet RJ45 CPU I Min. CAT5, shielded S/FTP - 100 m Ethernet FO MC2-2, SW3-3 Duplex LC, 1310 nm - 2000 m Grounding connection Housing Unshielded 16 mm² - Table 8: Recommendation for connection cables *) Observe line capacitance, see note above. 6.5.2 Information about connecting serial interfaces RS232 and RS485 NOTICE Damage to the device! Using the wrong data cable may damage the device. ►Only use data cables which comply with the description below.

Maschinenfabrik Reinhausen GmbH 2019

41 5089542/05 EN MSENSE® BM RS232 (D-SUB 9-pole) For connecting the device via the RS232 interface (COM2), use a data cable with the following structure: Figure 26: RS232 data cable (9-pole)

Maschinenfabrik Reinhausen GmbH 2019

42 5089542/05 EN MSENSE® BM RS485 (D-SUB 9-pole) To connect the device via the RS485 interface (COM2), use a data cable with the following structure: Figure 27: RS485 data cable D-SUB 9-pole plug connection Only use 9-pole D-SUB plugs with the following characteristics: ▪ Plug housing is metallic or metal-plated ▪ Cable shielding is connected with the plug using one of the two following variants: – Shielding is screwed down with traction relief. – Shielding is soldered with plug housing.

Maschinenfabrik Reinhausen GmbH 2019

43 5089542/05 EN MSENSE® BM Figure 28: Example of a soldered shielding on a plug housing 6.5.3 Information about laying fiber-optic cable To ensure the smooth transfer of data via the fiber-optic cable, you must en- sure that mechanical loads are avoided when laying the fiber-optic cable and later on during operation. Also observe the information from the manufac- turer of the fiber-optic cable and the following instructions: ▪ Radii must not fall below the minimum permissible bend radii (do not bend fiber-optic cable). ▪ The fiber-optic cables must not be over-stretched or crushed. Observe the permissible load values. ▪ The fiber-optic cables must not be twisted. ▪ Be aware of sharp edges because they can damage the fiber-optic cable's coating during laying or can place mechanical loads on the coating later on. ▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re- serve such that the fiber-optic cable is neither bent nor twisted when tight- ened. 6.5.4 Connecting the bushing adapter to the bushing coupling unit The bushing adapter must be connected to the bushing coupling unit with the connection cable provided. To do so, proceed as follows: 1. Ensure that the plug of the connection cable and the connections of the bushing adapter and bushing coupling unit are dry and free of dirt. If this is not the case, clean and dry them with a cloth.

Maschinenfabrik Reinhausen GmbH 2019

44 5089542/05 EN MSENSE® BM 2. Attach the connection cable plug to the bushing adapter and screw it in place. Figure 29: Connecting the connection cable to the bushing adapter 3. Attach the connection cable plug to the bushing coupling unit and screw it in place. Figure 30: Connecting the connection cable to the bushing coupling unit 6.5.5 Connecting the bushing coupling unit to the control cabinet The bushing coupling unit must be connected to the control cabinet with the connection cable provided. To do so, proceed as follows: 1. Remove the cover cap from the U connection of the bushing coupling unit.

Maschinenfabrik Reinhausen GmbH 2019

45 5089542/05 EN MSENSE® BM 2. Ensure that the plug of the connection cable and the U connection of the bushing coupling unit are dry and free of dirt. If this is not the case, clean and dry them with a cloth. 3. Attach the connection cable plug to the U connection of the bushing cou- pling unit and screw it in place. Figure 31: Connecting the connection cable to the bushing coupling unit

Maschinenfabrik Reinhausen GmbH 2019

46 5089542/05 EN MSENSE® BM 4. NOTICE! Laying the connection cable on the transformer to the control cabinet. When laying the cable, observe the minimum permitted bending radius of 50 mm and take precautions to protect the cable from mechani- cal damage (e.g. protective tubes). Otherwise the connection cable may become damaged. Figure 32: Laying the connection cable to the control cabinet 5. Shorten the connection cable to the desired length.

Maschinenfabrik Reinhausen GmbH 2019

47 5089542/05 EN MSENSE® BM Connecting the connection cable in the control cabinet The connection cable must be connected to the terminal in the control cabi- net in accordance with the connection diagram. The cable shielding must be attached to the grounding bar using a shielding terminal. Figure 33: Connection of the connection cable in the control cabinet 1 Connection terminal 2 Shielding terminal 3 Connection cable 1. Remove 50 mm of outer insulation from the cable. Ensure that the shield- ing is not damaged when doing so. Figure 34: Removing the outer insulation

Maschinenfabrik Reinhausen GmbH 2019

48 5089542/05 EN MSENSE® BM 2. Shorten the shielding to a length of 30 mm. Figure 35: Shortening the shielding 3. Remove 13 mm of inner insulation. Figure 36: Removing the inner insulation 4. Connect the connection cable to the terminal in the control cabinet in ac- cordance with the connection diagram.

Maschinenfabrik Reinhausen GmbH 2019

49 5089542/05 EN MSENSE® BM 5. Fit the cable shielding to the grounding bar using a shielding terminal and tighten the shielding terminal with a tightening torque of 3 Nm. Figure 37: Attaching the shielding terminal 6.5.6 Connecting the voltage transformers for the reference system NOTICE Damage to the device! If the voltage transformer and device have different potentials, current may flow across the shielding. This current may damage the device. ►Connect the devices to a potential equalization rail to equalize the poten- tial. ►If both devices have different potentials, only connect the cable's shield- ing to one device. To connect the voltage transformers for the reference system, proceed as follows: 1. Remove the cable insulation and crimp a wire end sleeve to the end. Figure 38: Removing the cable insulation

Maschinenfabrik Reinhausen GmbH 2019

50 5089542/05 EN MSENSE® BM 2. Connect the voltage transformers to terminal X10 in accordance with the connection diagram. UI L1 L2 L3 N VT VT VT L1 L2 L3 N Figure 39: Connecting the voltage transformers for the reference system 3. Fit the shielding for the cables to the control cabinet grounding bar and tighten the shielding terminal with a tightening torque of 3 Nm. Figure 40: Attaching the shielding terminal 6.5.7 Connecting additional leads (optional) Connect additional leads as necessary in accordance with the connection di- agram: ▪ Digital inputs and outputs ▪ Control system ▪ Visualization

Maschinenfabrik Reinhausen GmbH 2019

51 5089542/05 EN MSENSE® BM Routing information for connecting the control system or visualization When connecting the device to a control system or to your network for ac- cessing the visualization, observe the following recommendation on the ca- ble routing in the control cabinet: Figure 41: Recommendation on the cable routing in the control cabinet for the connection of the control system or visualization 6.5.8 Connecting the power supply You may only connect the control cabinet to circuits with an external over- current protection device and an isolating device with all poles disconnected so the equipment can be fully de-energized if required (service, maintenance etc.). Suitable equipment includes isolating devices in accordance with IEC 60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the relevant circuits (voltage, maximum currents) when selecting the circuit breaker type. In addition, observe the following: ▪ It must be easy for the operator to access the isolating device ▪ The isolating device must be labeled for the device and circuits to be iso- lated ▪ The isolating device may not be a part of the power line ▪ The isolating device may not interrupt the main protective conductor You must connect the power supply circuit with a conductor cross-section of at least 2.5 mm2 (AWG 13) and protect it with a C6A or B6A type miniature circuit breaker.

Maschinenfabrik Reinhausen GmbH 2019

52 5089542/05 EN MSENSE® BM To connect the voltage supply, proceed as follows: ►Connect the power supply of the control cabinet to terminal X1 in accor- dance with the connection diagram provided. 6.6 Checking functional reliability To ensure that the device is wired correctly, check its functionality. NOTICE Damage to device and system periphery! An incorrectly connected device can lead to damage to the device and sys- tem periphery. ►Check the entire configuration before commissioning. To check the functionality, proceed as follows: ►Apply voltage to the control cabinet. ð The device's control system boots up; after a brief period, the relay switches the operating contact STATUS OK (DIO 28-15:1B). The device is fully mounted and can be configured. The actions required for this are described in the following chapter.

Maschinenfabrik Reinhausen GmbH 2019

53 5089542/05 EN MSENSE® BM 7 Commissioning 7.1 Determining the capacitance and dissipation factor of the bushings To ensure that the bushings are in the proper condition, Maschinenfabrik Reinhausen GmbH recommends taking an initial measurement on new bushings when commissioning the bushing monitoring. If you are retrofitting the bushing monitoring on bushings already in operation, an initial measure- ment is absolutely essential. To do this, use a suitable measuring device (Schering bridge) to measure the capacitance C1 and dissipation factor tanδ on the fitted bushings. Follow the notes in the operating instructions from the bushing manufacturer. Enter the measured values in the measured value log [►Section 15.1, Page 157]. 7.2 Establishing connection to visualization You can use the ETH1.1 interface or the optional ETH2.2 interface of the CPU assembly to establish the connection to the visualization. The inter- faces do not use a DHCP server. Therefore, you must assign a static IP ad- dress to your PC. To do this, observe the following configuration example: Interface Configuration Standard ETH1.1 IP address: 192.168.165.1 (not adjustable) PC IP address: 192.168.165.100 Subnet mask: 255.255.255.0 Optional ETH2.2 IP address: 192.0.1.203 (factory setting) [►Section 8.4, Page 66] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 9: Interface configuration example

Maschinenfabrik Reinhausen GmbH 2019

54 5089542/05 EN MSENSE® BM Establishing a connection via the ETH1.1 interface To establish a connection via the ETH1.1 interface, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH1.1 interface. Figure 42: Establishing a connection via the front interface 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.168.165.100). 3. Enter the visualization's IP address http://192.168.165.1, or if SSL encryption is active enter https://192.168.165.1, on the PC in the browser. ð The visualization is accessed. Establishing a connection via the ETH2.2 interface on the CPU module (optional) The device is supplied with the IP address 192.0.1.230 at the factory. If you have changed the IP address, you can view the IP address in the Com- munication menu.

Maschinenfabrik Reinhausen GmbH 2019

55 5089542/05 EN MSENSE® BM To connect via the ETH2.2 interface, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.2 interface. Figure 43: Establishing a connection via the ETH2.2 interface on the back 2. Assign a unique IP address to the PC in the same subnet as the device (e.g. 192.0.1.100). 3. Enter the visualization's IP address (e.g. http://192.0.1.230, if SSL encryption is active enter https://192.0.1.230) on the PC in the browser. ð The visualization is accessed. 7.3 Setting the language You can use this parameter to set the display language for the device. The device comes with a maximum of four languages. The following languages are available: English Italian* German Portuguese* French* Russian* Spanish* Chinese* Korean* Polish* *) Language is available as an option

Maschinenfabrik Reinhausen GmbH 2019

56 5089542/05 EN MSENSE® BM To set the language, proceed as follows: 1. Select the Language button in the status bar, or as an alternative go to Settings > General > Language. Figure 44: Setting the language 2. Select the desired language from the list box. 3. Press the Accept button to save the modified parameter. ð The "Restart device" dialog appears. 4. Restart the device to apply the changed language setting. 7.4 Setting date and time You can set the date and time in the following ways: ▪ Manually ▪ Time synchronization via control system (SCADA) ▪ Time synchronization via SNTP time server If you are using a control system, the device automatically synchronizes the date and time with the control system. If you would like to use an SNTP time server, you must set the required parameters. When doing so, observe the information provided in the Time synchroniza- tion [►Section 8.15, Page 105] section. 7.5 Setting the parameters Commissioning the device requires setting some parameters. You can set the necessary parameters with the help of the commissioning assistant or set each parameter individually. 7.5.1 Commissioning wizard If you want the device to help when setting the relevant parameters, you can use the commissioning wizard. The commissioning wizard provides a selec- tion of parameters that you can configure in order. A detailed description of each of the parameters can be found in the Opera- tion [►Section 8, Page 60] chapter. To call up the commissioning wizard, you will need the necessary access rights [►Section 8.16, Page 109]. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin

Maschinenfabrik Reinhausen GmbH 2019

57 5089542/05 EN MSENSE® BM To set the parameters with the help of the commissioning wizard, proceed as follows: 1. Log in as a user with the necessary access rights. 2. Go to Settings > Commissioning wizard. Figure 45: Calling up the commissioning wizard 3. Press the Next button to launch the commissioning wizard. 4. Follow the on-screen instructions. Once you have entered all of the parameters relevant to commissioning, continue with the function test. 7.5.2 Setting the parameters manually If bushing monitoring with the option "Monitoring of 6 bushings" is used, the parameters for both field 1 (F1) and field 2 (F2) must be set. Field 1 and field 2 each describe a set consisting of 3 bushings respectively. If bushing monitoring with the option "Monitoring of 3 bushings" is used, only the pa- rameters for field 1 are displayed. Commissioning the bushing monitoring requires setting the following param- eters: Setting the transformer data for the reference system [►Section 8.5, Page 68] 1. Set primary transformer voltage. 2. Set secondary transformer voltage. Configuring capacitance monitoring [►Section 8.6.2, Page 69] 1. C: Activate capacitance monitoring. 2. C: Set C1 phase L1. 3. C: Set C1 phase L2.

Maschinenfabrik Reinhausen GmbH 2019

58 5089542/05 EN MSENSE® BM 4. C: Set C1 phase L3. 5. C: Set ΔC1 >. 6. C: Set ΔC1 >>. Configuring dissipation factor monitoring [►Section 8.6.3, Page 72] 1. tanδ: Activate dissipation factor monitoring. 2. tanδ: Set Δtanδ >. Setting control system protocol (optional) If you need a control system protocol [►Section 8.13, Page 84], you must set the parameters required for this. More information on this (e.g. data points) can be found in the enclosed supplement for the control system pro- tocol. 7.6 Performing standardization Once you have set all required parameters, you must perform a standardiza- tion for commissioning the device. The standardization is used to compen- sate for measurement tolerances along the measurement chain (bushing, bushing adapter and bushing coupling unit). Follow the notes on this in the following sections: ▪ Configuring capacitance monitoring [►Section 8.6.2, Page 69] ▪ Configuring dissipation factor monitoring [►Section 8.6.3, Page 72] 7.7 Performing tests Please contact Maschinenfabrik Reinhausen GmbH (MR) if any aspect of the tests is not clear. 7.7.1 Performing function tests To check that the monitoring system is functioning correctly, proceed as fol- lows: 1. Check the pending event messages [►Section 8.12.1, Page 81]. If event messages are pending, resolve the cause of the event and acknowledge the event. 2. Optional: Check the control system. ð The monitoring system is ready to function.

Maschinenfabrik Reinhausen GmbH 2019

59 5089542/05 EN MSENSE® BM 7.7.2 Electrical high-voltage tests on the transformer It is essential that you ensure only trained, instructed expert personnel who are familiar with and comply with the pertinent safety and technical regula- tions, who are aware of the potential risks, and who consistently use the oc- cupational safety equipment provided to prevent injury and property damage are assigned to perform such a transformer test. Note the following points before undertaking high voltage tests on the trans- former: ▪ Check that the ground connections on the control cabinet and the control cabinet fixings are free of paint. ▪ Only perform high voltage test if the control cabinet door is closed. ▪ Disconnect external connections to electronic components in the control cabinet to prevent damage from overvoltage. ▪ Remove the bushing adapter and fit the cap of the bushing test tap. ▪ When connecting the control cabinet's supply voltage, only use the bush- ings in the protective housing base intended for lead insertion. ▪ Guide all ground connecting leads to one central connection point (estab- lishment of suitable reference earth). ▪ Disconnect all electronic components before the high voltage test. Before a dielectric test of the wiring, remove all devices with a withstand voltage of < 1,000 V. ▪ Remove leads used for testing before the high voltage test as these func- tion as antennas. ▪ Wherever possible, route the measurement leads and data leads sepa- rately to the energy cables. 7.7.3 Dielectric tests on transformer wiring Note the following points for dielectric testson the transformer wiring: The monitoring system has been put through dielectric tests before delivery. ►Before the dielectric test for the transformer wiring, disconnect the moni- toring system from the section to be tested to rule out increased compo- nent loading for those components fitted in the control cabinet.

Maschinenfabrik Reinhausen GmbH 2019

60 5089542/05 EN MSENSE® BM 8 Operation This chapter describes all the functions and setting options for the device. 8.1 Establishing connection to visualization You can use the ETH2.1 interface or the optional ETH2.2 interface of the CPU assembly to establish the connection to the visualization. The inter- faces do not use any DHCP server. Therefore, you must assign a static IP address to your PC. To do this, observe the following configuration example: Interface Configuration Standard ETH2.1 IP address: 192.168.165.1 (not adjustable) PC IP address: 192.168.165.100 Subnet mask: 255.255.255.0 Optional ETH2.2 IP address: 192.0.1.203 (factory setting) [►Section 8.4, Page 66] Subnet mask: 255.255.255.0 PC IP address: 192.0.1.100 Subnet mask: 255.255.255.0 Table 10: Configuration example of the interfaces To establish a connection, proceed as follows: 1. Connect the PC and device using an Ethernet cable (RJ45 plug) via the ETH2.1 or ETH2.2 interface. Figure 46: Establishing a connection via the ETH2.1 or ETH2.2 interface

Maschinenfabrik Reinhausen GmbH 2019

61 5089542/05 EN MSENSE® BM 2. Assign a unique IP address to the PC. This IP address must be in the same subnet as the device (e.g. ETH2.1: 192.168.165.100). 3. Enter the visualization's IP address (e.g. ETH2.1: http://192.168.165.1, if SSL encryption is active enter https://192.168.165.1) on the PC in the browser. ð The visualization is accessed. 8.2 Operating concept You can operate the device using the web-based ISM™ Intuitive Control In- terface visualization via a PC. User rights and user roles The device is equipped with a rights system and a roles system. The display and access rights to device settings or events can therefore be controlled at user level. You can configure the rights system and roles system to meet your require- ments. You will find more information on user rights and user roles in the User administration [►Section 8.16, Page 109] section. You can only modify the device settings or parameters if you have the nec- essary user rights. Logging on, logging off and changing users The control of access rights to device settings and parameters is user- based. Various users can log in at the same time (e.g. via the visualization) and access the device. To log in as a user, proceed as follows: 1. Select the LOGIN or CHANGE button in the status line. 2. Enter your user name and password and select the OK button. ð The name of the logged-in user appears in the status line. To log out as a user, proceed as follows: ►Press the LOGOUT button in the status line. Navigation If you are operating the device using the web-based visualization, you can navigate by clicking on the appropriate buttons. Example To navigate to the "Date" parameter, proceed as follows: 1. Go to Settings. 2. Go to Parameters. 3. Go to Time synchronization.

Maschinenfabrik Reinhausen GmbH 2019

62 5089542/05 EN MSENSE® BM 4. Select Time. In these operating instructions, the path for navigating to a parameter is al- ways shown in an abridged form: Go to Settings > Parameters > Time syn- chronization. Parameter search You can use the quick search function in the parameter menu to search for a parameter. Enter the name of the desired parameter in the Search entry field. Figure 47: Quick search Expert mode The device has an expert mode for entering the parameters. You can enter the parameters directly into the overview screen of the respective menu in this mode. Figure 48: Expert mode

Maschinenfabrik Reinhausen GmbH 2019

63 5089542/05 EN MSENSE® BM To activate the expert mode, proceed as follows: 1. Go to Settings > Parameters. 2. Select the Expert mode checkbox. ð Expert mode is active. Hiding/showing parameters Depending on how you set the parameters, the device will hide or show ad- ditional parameters related to this function. 8.3 General You can set general parameters in this menu item. Also refer to 2 Setting the language [► 55] 8.3.1 Activating/deactivating automatic launch of commissioning wizard You can use this parameter to set whether the commissioning wizard [►Section 7.5.1, Page 56] is to launch automatically when the device is restarted. 1. Go to Settings > Parameters > System > General > Commissioning wizard. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. 8.3.2 Setting measured value display This parameter lets you set whether the displayed measured values and control parameters are to refer to the primary side or secondary side. To set the measurement transformer display, proceed as follows: 1. Go to Settings > Parameters > General > Measured value display. 2. Select the option you want. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

64 5089542/05 EN MSENSE® BM 8.3.3 Remote behavior You can use this parameter to select the behavior of the device in remote operating mode. You can select the following options: Option Description Hardware only The device accepts commands via digital inputs. SCADA only The device accepts commands via SCADA. Hardware and SCADA The device accepts commands via digital inputs and SCADA. Table 11: Selecting Remote behavior To set the Remote behavior, proceed as follows: 1. Go to Settings > Parameters > General > Remote behavior. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. 8.3.4 Accessing online help The web-based visualization has an online help section. To call up the online help, proceed as follows: 1. Call up the web-based visualization with the PC. 2. Select the MR logo in the status line. ð The online help appears. 8.3.5 Activating/deactivating the USB interface This parameter lets you deactivate the USB interface. You can select the fol- lowing options: ▪ On: USB interface is activated ▪ Off: USB interface is deactivated Proceed as follows to activate/deactivate the USB interface: 1. Go to Settings > Parameters > System > General > USB interface. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. 8.3.6 Set up automatic logout You can change the settings so that the device of a logged-in user automati- cally logs the user out after a certain period of inactivity. You must set the following parameters for this: ▪ Auto logout ▪ Time until auto logout

Maschinenfabrik Reinhausen GmbH 2019

65 5089542/05 EN MSENSE® BM These settings apply to all users. If you have activated the Auto login [►Section 8.16.3, Page 111] function for a user, then this user will not be automatically logged out. To set automatic logout, proceed as follows: 1. Go to Settings > Parameters > General. 2. Select the desired parameter. 3. Set parameter. 4. Press the Accept button to save the modified parameter. Auto logout You can use this parameter to activate automatic logout monitoring. Time until auto logout You can use this parameter to set the time period of inactivity after which a user is automatically logged out. 8.3.7 Activating/deactivating service user access The device is equipped with user access for the Maschinenfabrik Rein- hausen GmbH Technical Service department. This access is for error diag- nostics and troubleshooting in the event of device faults. You can use this parameter to activate or deactivate service user access. Only activate service user access for a limited time period for remedying faults in order to safeguard IT security. If you deactivate the service user access and lose your password for the ad- ministrator role, it is not possible to reset the administrator password. If the administrator password is lost, the device must be reset to the default set- tings. When doing so, all information stored on the device (parameters, measured values, etc.) will be lost. You must be assigned the administrator role in order to set parameters. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin 1. Go to Settings > Parameters > System > General > Service user ac- cess activation. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. 4. Restart the device to apply the change.

Maschinenfabrik Reinhausen GmbH 2019

66 5089542/05 EN MSENSE® BM 8.4 Configuring the network You can configure the ETH 1 and ETH 2.2 network interfaces of the CPU as- sembly in this menu item. You can only set the parameters for ETH 1 if the device is equipped with the optional control system connection via Ethernet (TCP/IP): ▪ IEC 61850 ▪ IEC 60870-5-104 ▪ Modbus (Modbus type TCP active) ▪ DNP3 (DNP3 transmission type TCP active) You can only set the parameters for ETH 2.2 if the device is equipped with the optional interface for visualization. Figure 49: Network settings To configure the network interfaces, proceed as follows: 1. Go to Settings > Parameters > System > Network settings. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. IP address ETH 1/ETH 2.2 You can use this parameter to assign an IP address to the device. Assign IP addresses to both web-based visualization and SCADA (optional) in different subnets. Otherwise you will not be able to establish a connec- tion. Subnet mask ETH 1/ETH 2.2 You can use this parameter to set the subnet mask.

Maschinenfabrik Reinhausen GmbH 2019

67 5089542/05 EN MSENSE® BM Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not be possible to connect to the device. Gateway address ETH 1/ETH 2.2 You can use this parameter to set the gateway's IP address. If you set the value to 0.0.0.0, no gateway is used. Activate SSL/TLS encryption You can use this parameter to set whether access to the visualization should take place over an SSL/TLS-encrypted connection. Set the TLS version You can use this parameter to set the accepted TLS versions. If you would like to establish an encrypted connection to the visualization, you must use an accepted TLS version. You can select the following options: Option Accepted TLS versions >= 1.0 ▪ 1.0 ▪ 1.1 ▪ 1.2 >= 1.1 ▪ 1.1 ▪ 1.2 >= 1.21) ▪ 1.2 Table 12: TLS version 1) This option can be selected only if the TLS versions are supported by the connected peripheral equipment. Visualization release You can set via which interfaces you can access the visualization with this parameter: ▪ Only ETH 2.x ▪ ETH 1 and ETH 2.x You can only set this parameter if the device is equipped with the optional control system connection via Ethernet (TCP/IP) and the optional interface for visualization.

Maschinenfabrik Reinhausen GmbH 2019

68 5089542/05 EN MSENSE® BM 8.5 Setting the transformer data for the reference system (optional) These parameters let you set the transformer data for the reference system. You can only access these parameters when the device allows for the mea- surement of the reference line voltage. If bushing monitoring with the option "Monitoring of 6 bushings" is used, the parameters for both field 1 (F1) and field 2 (F2) must be set. Field 1 and field 2 each describe a set consisting of 3 bushings respectively. If bushing monitoring with the option "Monitoring of 3 bushings" is used, only the pa- rameters for field 1 are displayed. You can set the following parameters: ▪ F1/F2: Primary transformer voltage ref.: Primary transformer voltage of the reference system for field 1 or field 2 ▪ F1/F2: Secondary transformer voltage Ref: Secondary transformer volt- age of the reference system for field 1 or field 2 Figure 50: Setting the transformer data for the reference system To set the transformer data, proceed as follows: 1. Go to Settings > Parameters > Grid > Transformer data. 2. Select the desired parameter and enter the desired value. 3. Press the Accept button to save the modified parameter. 8.6 Configuring bushing monitoring Follow the notes in the following sections when configuring capacitance monitoring and dissipation factor monitoring.

Maschinenfabrik Reinhausen GmbH 2019

69 5089542/05 EN MSENSE® BM 8.6.1 Set the field designation You can use this parameter to set the field designation. The field designation is displayed in the bushing monitoring overview screen [►Section 8.7, Page 75]. You can set a unique field designation for each field. To set the field designation, proceed as follows: 1. Go to Settings > Parameters > Bushing monitoring > Bushing moni- toring field1/field2 > F1/F2: Field designation. 2. Enter the desired value. 3. Press the Accept button to save the modified parameter. 8.6.2 Configuring capacitance monitoring The device monitors the change in difference of capacitance C1 between the phases. If the capacitance C1 of all three bushings changes in the same way (e.g. due to a temperature change), the difference in capacitances ΔC1 re- mains constant.

Maschinenfabrik Reinhausen GmbH 2019

70 5089542/05 EN MSENSE® BM If the capacitance of one or two bushings changes, the difference in capaci- tance also changes. If the difference in capacitance is greater than the set limit value, the device triggers an event message. C1 t Max. Min. Max. Min. Analogsignal 1,5 Pt, rgb(0,147,214) 0,7 Pt, Pfeil (Voll, 4, 30) Arial 9 Pt ΔC1 t ΔC1>> ΔC1> 5 % 10 % L3 L1 L2 L1 L3 L2 1 Figure 51: Capacitance monitoring 1 Status of the bushing (gray: ok, yellow/red: limit value exceeded) C1 Capacitance C1 ΔC1 Capacitance difference ΔC1 ΔC1> Limit value ΔC1> ΔC1>> Limit value ΔC1>> L1, L2, L3 Phase L1, L2, L3 If bushing monitoring with the option "Monitoring of 6 bushings" is used, the parameters for both field 1 (F1) and field 2 (F2) must be set. Field 1 and field 2 each describe a set consisting of 3 bushings respectively. If bushing monitoring with the option "Monitoring of 3 bushings" is used, only the pa- rameters for field 1 are displayed. To monitor the capacitance of the bushings, the following parameters must be set for commissioning the transformer: ▪ F1/F2-C: Activate cap. monitoring ▪ F1/F2-C: C1 Phase L1/L2/L3 ▪ F1/F2-C: ΔC1 > ▪ F1/F2-C: ΔC1 >> ▪ F1/F2-C: Perform standardization

Maschinenfabrik Reinhausen GmbH 2019

71 5089542/05 EN MSENSE® BM Figure 52: Configuring bushing monitoring To set capacitance monitoring, proceed as follows: 1. Go to Settings > Parameters > Bushing monitoring > Bushing moni- toring field1/field2. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. F1/F2-C: Activate capacitance monitoring You can use this parameter to activate or deactivate capacitance monitoring in field 1 or field 2. After being switched on, capacitance monitoring only becomes active once a delay time has elapsed (factory setting of 2 minutes) in order to avoid er- rors resulting from transients. F1/F2-C: C1 Phase L1/L2/L3 You can use these parameters to set the reference capacitance C1 for the bushings of phases L1, L2 and L3 in field 1 and field 2. The reference value is the value you have measured with an external measuring device for com- missioning [►Section 7.1, Page 53]. F1/F2 Limit values C: ΔC1 > and C: ΔC1 >> You can set two limit values for monitoring the bushings in field 1 and field 2: ▪ F1/F2-C: ΔC1 > ▪ F1/F2-C: ΔC1 >> If the limit values are exceeded, the monitoring system triggers an event message and issues a signal at the digital output.

Maschinenfabrik Reinhausen GmbH 2019

72 5089542/05 EN MSENSE® BM Maschinenfabrik Reinhausen recommends the following limit values: F1/F2- C: ΔC1 >: 5%, F1/F2-C: ΔC1 >>: 10% F1/F2-C: Perform standardization You must perform standardization for field 1 and field 2 to commission the monitoring system. The standardization is used to compensate for measure- ment tolerances along the measurement chain (bushing, bushing adapter and bushing coupling unit). Only perform the standardization while commissioning the monitoring sys- tem and with bushings in good condition. Otherwise correct bushing moni- toring functionality cannot be guaranteed. To perform the standardization, proceed as follows: ü The transformer is in a stable state (typical load, no on-load tap-change operation or significant change in the transformer load, thermally stabi- lized). 1. Go to Settings > Parameters > Bushing monitoring > Bushing moni- toring field1/field2 > F1/F2-C: Perform standardization. 2. Select the Yes option. 3. Press the Accept button to perform the standardization. ð The standardization is carried out and the parameter is reset to the No option. 4. Check the event messages [►Section 8.12.1, Page 81] to see if the standardization was performed successfully. If this is not the case, resolve the cause of the error and repeat the standardization. 8.6.3 Configuring dissipation factor monitoring The device monitors the change in the difference of the dissipation factor tanδ between the phases. If the tanδ of all 3 phases changes in the same way (e.g. due to a temperature change), the difference in the dissipation fac- tor Δtanδ remains constant.

Maschinenfabrik Reinhausen GmbH 2019

73 5089542/05 EN MSENSE® BM If the dissipation factor of one or two bushings changes, the difference in the dissipation factor also changes. If the difference in the dissipation factor is greater than the set limit value, the device triggers an event message. tanδ t Max. Min. Max. Min. Analogsignal 1,5 Pt, rgb(0,147,214) 0,7 Pt, Pfeil (Voll, 4, 30) Arial 9 Pt Δtanδ t Δtanδ> L3 L1 L2 L1 L3 L2 1 Figure 53: Dissipation factor monitoring 1 Status of the bushing (gray: ok, yellow/red: limit value exceeded) tanδ Dissipation factor tanδ Δtanδ Dissipation factor differ- ence Δtanδ Δtanδ> Limit value Δtanδ> L1, L2, L3 Phase L1, L2, L3 If bushing monitoring with the option "Monitoring of 6 bushings" is used, the parameters for both field 1 (F1) and field 2 (F2) must be set. Field 1 and field 2 each describe a set consisting of 3 bushings respectively. If bushing monitoring with the option "Monitoring of 3 bushings" is used, only the pa- rameters for field 1 are displayed. To monitor the dissipation factor of the bushings, you must set the following parameters for commissioning the transformer: ▪ F1/F2-tanδ: Activate diss. factor monit. ▪ F1/F2-tanδ: tanδ phase L1/L2/L3 ▪ F1/F2-tanδ: Δtanδ > ▪ F1/F2-tanδ: Perform standardization

Maschinenfabrik Reinhausen GmbH 2019

74 5089542/05 EN MSENSE® BM Figure 54: Configuring bushing monitoring To set dissipation factor monitoring, proceed as follows: 1. Go to Settings > Parameters > Bushing monitoring > Bushing moni- toring field1/field2. 2. Select the desired parameter. 3. Set the parameter. 4. Press the Accept button to save the modified parameter. F1/F2-tanδ: Activate dissipation factor monitoring You can use this parameter to activate or deactivate dissipation factor moni- toring in field 1 or field 2. After being switched on, dissipation factor monitoring only becomes active once a delay time has elapsed (measured value display after approx. 7 min- utes, monitoring after approx. 1 hour) in order to avoid errors resulting from transients. F1/F2-tanδ: tanδ phase L1/L2/L3 You can use these parameters to set the reference dissipation factor tanδ for the bushings of phases L1, L2 and L3 in field 1 or field 2. The reference value is the value you have measured with an external measuring device for commissioning [►Section 7.1, Page 53]. Limit value F1/F2-tanδ: Δtanδ > You can set a limit value for monitoring the bushings in field 1 or field 2. If the limit value is exceeded, the monitoring system triggers an event mes- sage and issues a signal at the digital output.

Maschinenfabrik Reinhausen GmbH 2019

75 5089542/05 EN MSENSE® BM F1/F2-tanδ: Perform standardization You can use this parameter to perform a standardization of the dissipation factor monitoring in field 1 and field 2. This clears all of the measured and calculated values for dissipation factor monitoring. To perform the standardization, proceed as follows: 1. Go to Settings > Parameters > Bushing monitoring > Bushing moni- toring field1/field2 > F1/F2-tanδ: Perform standardization. 2. Select the Yes option. 3. Press the Accept button to perform the standardization. ð The standardization is carried out and the parameter is reset to the No option. 4. Check the event messages [►Section 8.12.1, Page 81] to see if the standardization was performed successfully. 8.6.4 Circuit breaker monitoring You can configure up to 4 digital inputs for monitoring the status messages of the circuit breakers in the reference system. This monitoring function is used for detecting whether the reference system is active (circuit breaker in ON position) or inactive (circuit breaker in OFF position). If circuit breaker monitoring is configured and a circuit breaker is reported to be in the OFF position, the device reacts as follows: ▪ Bushing monitoring is deactivated. ▪ You cannot perform standardization. When configuring this function, refer to the section Configuring digital inputs and outputs [►Section 8.11, Page 79]. If bushing monitoring with the option "Monitoring of 6 bushings" is used, you can configure up to 4 inputs for field 1 (F1) and for field 2 (F2) respectively. If bushing monitoring with the option "Monitoring of 3 bushings" is used, only the inputs for field 1 are displayed. Bushing monitoring is only deactivated for the respective field. 8.7 Displaying the state of the bushings The device displays the current state of the bushings and the following mea- sured values: ▪ Status indicator for the bushing based on the set limit values – Gray: Everything OK – Yellow: The capacitance difference ΔC1 is greater than the limit value ΔC1 > or the dissipation factor difference Δtanδ is greater than the limit value Δtanδ > – Red: The capacitance difference ΔC1 is greater than the limit value ΔC1 >>

Maschinenfabrik Reinhausen GmbH 2019

76 5089542/05 EN MSENSE® BM ▪ C1: Calculated (compensated) bushing capacitance ▪ ∆C1: Percentage deviation of the capacitance difference ΔC1 from the ref- erence capacitance C1 ▪ tanδ: Calculated (compensated) dissipation factor of the bushing ▪ Δtanδ: Dissipation factor difference Δtanδ ▪ U ref: Currently measured reference system voltage If bushing monitoring with the option "Monitoring of 6 bushings" is used, the following values will be displayed in two separate views for field 1 (F1) and field 2 (F2). To display the state of the bushings, proceed as follows: Figure 55: Displaying the state of the bushings ►Go to Information > Bushing monitoring field1/field2. 8.8 Displaying the capacitance progression You can display the temporal progression of the capacitance C1 and the ca- pacitance difference ΔC1 over the last 28 days. To do so, proceed as fol- lows: ►Go to Information > Capacitance C1/ΔC1 field1/field2.

Maschinenfabrik Reinhausen GmbH 2019

77 5089542/05 EN MSENSE® BM Figure 56: Capacitance progression 8.9 Displaying the dissipation factor progression You can display the temporal progression of the dissipation factor tanδ and the dissipation factor difference Δtanδ over the last 28 days. To do so, pro- ceed as follows: ►Go to Information > Dissipation factor tanδ/Δtanδ field1/field2. Figure 57: Dissipation factor progression 8.10 Displaying measured value recorder (optional) You can use the optional measured value recorder function to display the progress of measured values and signals over time. If you access it via the web visualization, you can select a maximum of 10 measured values.

Maschinenfabrik Reinhausen GmbH 2019

78 5089542/05 EN MSENSE® BM To display the measured value recorder, proceed as follows: 1. Go to Recorder. Figure 58: Recorder 2. Select the signals to be displayed in the list. 3. If necessary, set the desired axis for each signal. 4. Enter the start time and end time for the measured value display. 5. Press Display to call up the measured value display (data log). Figure 59: Data log 6. Move the mouse pointer to a measurement point for more information. 7. Use the mouse to produce a selection window or turn the mouse wheel to zoom into or out of the diagram. If necessary, you can move an enlarged diagram with the right mouse button. 8. Press to save the displayed measured values as a csv file.

Maschinenfabrik Reinhausen GmbH 2019

79 5089542/05 EN MSENSE® BM Trend curves If you call up the measured value recorder using a PC, you can display a trend curve instead of the measured values. The trend curve can, for exam- ple, be a moving average over a configurable time period. Figure 60: Creating trend curves To create the trend curves, proceed as follows: 1. Call up the measurement recorder and the desired measured value se- ries. 2. Press the Trend button. 3. Select the desired measured values. 4. Select the desired trend function. 5. Entire the desired time period for the calculation of the trend curve. 6. Press the Accept button to display the trend curves. 8.11 Configuring digital inputs and outputs Upon delivery, the configurable digital inputs and outputs of the device are configured as follows: ▪ Input: High active ▪ Output: Normally open contact (NO) You can change this configuration if necessary. Ensure that the configuration of the digital inputs and outputs is suitable for the functions used. Otherwise malfunctions may occur in the device and the connected periphery. The following information is displayed in tabular form for configuring the digi- tal inputs and outputs. Grayed out elements cannot be changed.

Maschinenfabrik Reinhausen GmbH 2019

80 5089542/05 EN MSENSE® BM Property Options Function Function of the digital input (I: ...) or the digital output (O: ...). You can adjust the designation. Signal type Select signal type: Digital input Configuration DI: High active or low active DO: Normally open (NO), normally closed (NC); Note: If the device is disconnected or in the event of an error, the digital outputs are always open (no bi-stable relay). Assembly/ chan. Channel of the DIO assembly to which the function is linked. Func- tions that are not linked with a channel are identified with "-". Note the connection diagram supplied. Table 13: Configuration of the digital inputs and outputs Figure 61: Configuring digital inputs and outputs The operation described below is only possible if you access the visualiza- tion using a computer. You can only change the configuration of the digital inputs and outputs if you have a Parameter Configurator or Administrator role. When in delivery status, you can log in as the administrator as follows: ▪ User name: admin ▪ Password: admin Creating a backup You need to create a backup to be able to reset the system in the event that any incorrect configuration settings are made. To do so, proceed as follows: 1. Go to Settings > Export. 2. Go to the option Settings to export a backup copy of the current settings. 3. Select the desired Interface (USB or PC). 4. Press the Export button to start the export. Configuring DIO To configure the device's digital inputs and outputs, proceed as follows: 1. Go to menu item Settings > DIO configuration.

Maschinenfabrik Reinhausen GmbH 2019

81 5089542/05 EN MSENSE® BM 2. Where necessary, select the buttons ▲ or ▼ to sort the properties in a column alphabetically. 3. Configure the properties as desired. 4. Press the Accept button. 5. Confirm the security prompt with Yes to save the changes. 8.12 Event management The device is equipped with event management, which allows you to detect various device operating statuses and to adapt the behavior of the device. An overview of all possible events is given in the Event messages chapter. 8.12.1 Displaying and acknowledging events To display the events currently active, proceed as follows: ►Go to Events. ð A list of events currently active appears. Figure 62: Overview of events currently active Acknowledging events Acknowledgeable events must be acknowledged in the event overview so that they are no longer displayed. All other events are automatically removed once the cause is remedied (e.g. limit value no longer infringed). To acknowledge the events, proceed as follows: ►To acknowledge the events, highlight the desired events in the column then press the Acknowledge button. ð The events are acknowledged.

Maschinenfabrik Reinhausen GmbH 2019

82 5089542/05 EN MSENSE® BM 8.12.2 Configuring events The events have the following properties: Property Description Event status Active: Event active. Inactive: Event not active. High active (not configurable) High active: The device issues a signal if the event is ac- tive. Low active: The device issues a signal for as long as the event is not active. If the event is active, the signal is re- set. Can be set multiple times (not configurable) The event can be triggered several times without having been deactivated in the meantime. Acknowledgeable (not configurable) Acknowledgeable events must be acknowledged in the event overview so that they are no longer displayed. All other events are automatically removed once the cause is remedied (e.g. limit value no longer infringed). Event name Brief name of event. If you delete all of the text, the stan- dard text is displayed. Event description Description of event. If you delete all of the text, the stan- dard text is displayed. Event remedy Troubleshooting information for cause of event. If you delete all of the text, the standard text is displayed. Category ▪ Error (red) ▪ Warning (yellow) ▪ Info (grey) This setting affects the color of the Alarm LED and the event symbol in the primary navigation. Message If you activate this option, the event is shown on the dis- play and, if configured accordingly, issued via an output and the control system protocol. Storage If you activate this option, the event is stored in the event memory. Table 14: Properties of events

Maschinenfabrik Reinhausen GmbH 2019

83 5089542/05 EN MSENSE® BM Figure 63: Configuring events To configure an event, proceed as follows: 1. Go to Settings > Events. 2. Select the event to be changed in the list. 3. Select the options you want. 4. Press the Accept button to save the change. 8.12.3 Displaying event memory Past events are stored in the event memory. The following information is dis- played: Column Description # Consecutive number of events No. Event number for clear identification Event category: ▪ Error (red) ▪ Warning (yellow) ▪ Info (gray) Event Event text Time Date and time of event (DD.MM.YYYY, HH:MM:SS/ms) Event coming/going: Event coming Event going Table 15: Event memory To call up the event memory, proceed as follows: 1. Go to Events.

Maschinenfabrik Reinhausen GmbH 2019

84 5089542/05 EN MSENSE® BM 2. Press the Log button. Figure 64: Event memory Filtering events To adjust the display, you can define a filter. To do so, proceed as follows: 1. Press the Filter button. 2. Enter the desired time period. 3. Select the checkbox and enter the desired event number. ð The event text is displayed. 4. Select the desired event categories and the desired event status. 5. Press the Search button to display the desired events. Exporting events You can export the event memory entries currently displayed as a csv file. If you first create a filter, only the filtered entries are exported. To export the events, proceed as follows: ü First connect using Connect PC or connect a storage medium to the USB port on the CPU I [►Section 4.5.2.2.2, Page 23] module. 1. Press the Export button. 2. Select the desired option for data transmission (PC or USB). ð The data is exported. 8.13 SCADA The following section describes how you can configure the device to connect to a control system (SCADA).

Maschinenfabrik Reinhausen GmbH 2019

85 5089542/05 EN MSENSE® BM 8.13.1 Configuring IEC 61850 (optional) If you want to use the IEC 61850 control system protocol, you must set the following parameters. Also refer to the section Configuring the network [►Section 8.4, Page 66]. Figure 65: Setting parameters for IEC 61850 IED name You can use this parameter to assign the device an IED name in order for it to be identified in the IEC 61850 network. The IED name must start with a letter and may contain no more than 11 characters. To set the IED name, proceed as follows: 1. Go to Settings > Parameters > IEC 61850 > IED name. 2. Enter IED name. 3. Press the Accept button to save the modified parameter. Device ID You can use this parameter to assign the device a device ID in order for it to be identified in the IEC 61850 network. To set the device ID, proceed as follows: 1. Go to Settings > Parameters > IEC 61850 > Device ID. 2. Enter a device ID. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

86 5089542/05 EN MSENSE® BM Access point You can use this parameter to assign the access point a name in the IEC 61850 network. To set the access point name, proceed as follows: 1. Go to Settings > Parameters > IEC 61850 > Access point. 2. Enter access point. 3. Press the Accept button to save the modified parameter. Edition You can use this parameter to switch between edition 1 and edition 2 of the IEC 61850 control system protocol. To select the edition of the IEC 61850 control system protocol, proceed as follows: 1. Go to Settings > Parameters > IEC 61850 > Edition. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. Downloading an ICD file You can download the ICD file from the device via the Import/Export Man- ager [►Section 8.18, Page 117]. To do this, you have to establish an Ether- net connection between the device and your PC. For a smooth download with Windows Vista/7/8 operating systems, use Windows Explorer.

Maschinenfabrik Reinhausen GmbH 2019

87 5089542/05 EN MSENSE® BM 8.13.2 Configuring IEC 60870-5-101 (optional) If you want to use the IEC 60870-5-101 control system protocol, you must set the following parameters. Figure 66: Setting parameters for IEC60870-5-101 Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485 To select the serial interface, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Serial interface. 2. Select serial interface. 3. Press the Accept button to save the modified parameter. Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud To set the baud rate, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Baud rate. 2. Select baud rate. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

88 5089542/05 EN MSENSE® BM Transmission procedure You can use this parameter to set the transmission procedure. You can se- lect the following options: ▪ Unbalanced transmission ▪ Balanced transmission To set the transmission procedure, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Transmission pro- cedure. 2. Select transmission procedure. 3. Press the Accept button to save the modified parameter. Octet number of link address You can use this parameter to set how many octets are provided for the link address. To set the octet number of the link address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Octet number of link address. 2. Set octet number of link address. 3. Press the Accept button to save the modified parameter. Link address You can use this parameter to set the link address. To set the link address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Link address. 2. Set link address. 3. Press the Accept button to save the modified parameter. Octet number of ASDU address You can use this parameter to set how many octets are provided for the ASDU address. To set the octet number of the ASDU address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Octet number of ASDU address. 2. Set octet number of ASDU address. 3. Press the Accept button to save the modified parameter. ASDU address You can use this parameter to set the address of the ASDU.

Maschinenfabrik Reinhausen GmbH 2019

89 5089542/05 EN MSENSE® BM To set the ASDU address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > ASDU address. 2. Set ASDU address. 3. Press the Accept button to save the modified parameter. Octet number of information object address You can use this parameter to set how many octets are provided for the ad- dress of the information object. To set the octet number of the information object address, proceed as fol- lows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Octet number of in- formation object address. 2. Set octet number of information object address. 3. Press the Accept button to save the modified parameter. Octet number of cause of transmission You can use this parameter to set how many octets are provided for the cause of transmission. To set the octet number of the cause of transmission, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Octet number of cause of transmission. 2. Set octet number of cause of transmission. 3. Press the Accept button to save the modified parameter. Number of data bits You can use this parameter to set the number of databits. To set the number of data bits, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Number of data bits. 2. Set number of data bits. 3. Press the Accept button to save the modified parameter. Parity You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd To set the parity, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Parity. 2. Select parity.

Maschinenfabrik Reinhausen GmbH 2019

90 5089542/05 EN MSENSE® BM 3. Press the Accept button to save the modified parameter. Number of stop bits You can use this parameter to set the number of stop bits. To set the number of stop bits, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Number of stop bits. 2. Set number of stop bits. 3. Press the Accept button to save the modified parameter. Single character confirmation With this parameter, you can set whether a confirmation is to be sent as sin- gle characters instead of as a complete message. Single character confirma- tion is only possible for requesting data of class 2 (Class 2 Request). To set single character confirmation, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > ASDU single char- acter confirmation. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. RES bit test With this parameter, you can set whether the device is to check the RES bit (Reserved Bit) in the control field. You can select the following options: Option Description On Messages from the master with RES bit = 1 are declined by the device. Off Messages from the master with RES bit = 1 are accepted by the device. Table 16: RES bit test To set the Res bit test, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > ASDU RES bit test. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. ASDU sequence optimization With this parameter, you can set which method is to be used for optimizing the ASDU types. The standard enables optimization in order to be able to transfer multiple value changes in a telegram in a sequence of ascending in- formation object addresses. This is displayed by the sequence bit. The se- lection of ASDU types for which this optimization is allowed is based on the edition of the standard.

Maschinenfabrik Reinhausen GmbH 2019

91 5089542/05 EN MSENSE® BM You can select the following options: Option Description None The device does not optimize the ASDU types. Ed. 1 Optimization in accordance with IEC 60870 Edition 1 (Type 1, 3, 9, 11, 21, 126). Ed. 1 Amendment2 Optimization in accordance with IEC 60870 Edition 1, Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126). Ed. 2 Optimization in accordance with IEC 60870 Edition 2 (Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126). Table 17: ASDU sequence optimization To set the ASDU sequence optimization, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > ASDU sequence op- timization. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 8.15, Page 105]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Section 8.15.5, Page 108]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Section 8.15.3, Page 107]. Table 18: Reference time To set the reference time, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-101 > Reference time. 2. Select the desired option. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

92 5089542/05 EN MSENSE® BM 8.13.3 Configuring IEC 60870-5-103 (optional) If you want to use the IEC 60870-5-103 control system protocol, you must set the following parameters. Figure 67: Setting parameters for IEC60870-5-103 Serial interface You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485 To select the serial interface, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Serial interface. 2. Select serial interface. 3. Press the Accept button to save the modified parameter. Baud rate You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud To set the baud rate, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Baud rate. 2. Select baud rate. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

93 5089542/05 EN MSENSE® BM ASDU address You can use this parameter to set the address of the ASDU. To set the ASDU address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > ASDU address. 2. Set ASDU address. 3. Press the Accept button to save the modified parameter. Number of data bits You can use this parameter to set the number of databits. To set the number of data bits, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Number of data bits. 2. Set number of data bits. 3. Press the Accept button to save the modified parameter. Parity You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd To set the parity, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Parity. 2. Select parity. 3. Press the Accept button to save the modified parameter. Number of stop bits You can use this parameter to set the number of stop bits. To set the number of stop bits, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Number of stop bits. 2. Set number of stop bits. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

94 5089542/05 EN MSENSE® BM DFC compatibility With this parameter, you can set how the device is to use the DFC bit (Data Flow Control) in the control field. You can select the following options: Option Description Standard The device sets the DFC bit in each response to a com- mand. The device thus indicates that the master may not send any further commands. The master must react to the ACD bit (Access Demand) and retrieve the response to the command e.g. via a request for data of class 1 from the slave queue. Alternative The device sets the DFC bit in a response if a second command is received without the master having previ- ously sent a request for data of class 1. Table 19: DFC compatibility To set the DFC compatibility, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > DFC compatibility. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 8.15, Page 105]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Section 8.15.5, Page 108]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Section 8.15.3, Page 107]. Table 20: Reference time To set the reference time, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-103 > Reference time. 2. Select the desired option. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

95 5089542/05 EN MSENSE® BM 8.13.4 Configuring IEC 60870-5-104 (optional) If you want to use the IEC 60870-5-104 control system protocol, you must set the following parameters. Also refer to the section Configuring the net- work [►Section 8.4, Page 66]. Figure 68: Setting parameters for IEC60870-5-104 TCP port You can use this parameter to set the TCP port. To set the TCP port, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-104 > TCP port. 2. Enter the TCP port. 3. Press the Accept button to save the modified parameter. ASDU address You can use this parameter to set the address of the ASDU. To set the ASDU address, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-104 > ASDU address. 2. Set ASDU address. 3. Press the Accept button to save the modified parameter. ASDU sequence optimization With this parameter, you can set which method is to be used for optimizing the ASDU types. The standard enables optimization in order to be able to transfer multiple value changes in a telegram in a sequence of ascending in- formation object addresses. This is displayed by the sequence bit. The se- lection of ASDU types for which this optimization is allowed is based on the edition of the standard.

Maschinenfabrik Reinhausen GmbH 2019

96 5089542/05 EN MSENSE® BM You can select the following options: Option Description None The device does not optimize the ASDU types. Ed. 1 Optimization in accordance with IEC 60870 Edition 1 (Type 1, 3, 9, 11, 21, 126). Ed. 1 Amendment2 Optimization in accordance with IEC 60870 Edition 1, Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126). Ed. 2 Optimization in accordance with IEC 60870 Edition 2 (Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126). Table 21: ASDU sequence optimization To set the ASDU sequence optimization, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-104 > ASDU sequence op- timization. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. Reference time You can use this parameter to set which time is to be transmitted by the con- trol system. The device uses this information for time synchronization [►Section 8.15, Page 105]. You can select the following options: Option Description Local The control system transmits the local time. Note: If you use this option, you must deactivate the au- tomatic changeover between daylight saving time and standard time [►Section 8.15.5, Page 108]. Otherwise the device will use an incorrect time. UTC The control system transmits the time as UTC. The de- vice calculates the local time from UTC and the set time zone [►Section 8.15.3, Page 107]. Table 22: Reference time To set the reference time, proceed as follows: 1. Go to Settings > Parameters > IEC 60870-5-104 > Reference time. 2. Select the desired option. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

97 5089542/05 EN MSENSE® BM 8.13.5 Configuring Modbus (optional) If you want to use the Modbus control system protocol, you must set the cor- responding parameters depending on the Modbus type selected. Also refer to the section Configuring the network [►Section 8.4, Page 66] if you want to use Modbus TCP. Figure 69: Setting parameters for Modbus Modbus type You can use this parameter to set the Modbus type. You can select the fol- lowing options: ▪ RTU ▪ TCP ▪ ASCII To set the Modbus type, proceed as follows: 1. Go to Settings > Parameters > Modbus > Modbus type. 2. Select Modbus type. 3. Press the Accept button to save the modified parameter Modbus address You can use this parameter to set the Modbus address. To set the Modbus address, proceed as follows: 1. Go to Settings > Parameters > Modbus > Modbus address. 2. Enter the Modbus address. 3. Press the Accept button to save the modified parameter. TCP port (only with Modbus TCP) You can use this parameter to set the TCP port.

Maschinenfabrik Reinhausen GmbH 2019

98 5089542/05 EN MSENSE® BM To set the TCP port, proceed as follows: 1. Go to Settings > Parameters > Modbus > TCP port. 2. Enter the TCP port. 3. Press the Accept button to save the modified parameter. Maximum TCP connections (only with Modbus TCP) You can use this parameter to set the maximum number of TCP connec- tions. To set the maximum number of TCP connections, proceed as follows: 1. Go to Settings > Parameters > Modbus > Maximum TCP connections. 2. Enter the maximum number of TCP connections. 3. Press the Accept button to save the modified parameter. TCP Keepalive (only with Modbus TCP) You can use this parameter to activate/deactivate the "TCP Keepalive" func- tion. To activate/deactivate the "TCP Keepalive" function, proceed as follows: 1. Go to Settings > Parameters > Modbus > TCP Keepalive. 2. Select the desired option. 3. Press the Accept button to save the modified parameter. Serial interface (only with Modbus RTU and Modbus ASCII) You can use this parameter to select the serial interface for data transmis- sion. You can select the following options: ▪ RS232 ▪ RS485 To select the serial interface, proceed as follows: 1. Go to Settings > Parameters > Modbus > Serial interface. 2. Select serial interface. 3. Press the Accept button to save the modified parameter. Baud rate (only with Modbus RTU and Modbus ASCII) You can use this parameter to set the serial interface's baud rate. You can select the following options: ▪ 9600 baud ▪ 19200 baud ▪ 38400 baud ▪ 57600 baud ▪ 115200 baud

Maschinenfabrik Reinhausen GmbH 2019

99 5089542/05 EN MSENSE® BM To select the baud rate, proceed as follows: 1. Go to Settings > Parameters > Modbus > Baud rate. 2. Select baud rate. 3. Press the Accept button to save the modified parameter. Number of data bits (only with Modbus RTU and Modbus ASCII) You can use this parameter to set the number of databits. To set the number of data bits, proceed as follows: 1. Go to Settings > Parameters > Modbus > Number of databits. 2. Set the number of data bits. 3. Press the Accept button to save the modified parameter. Parity (only with Modbus RTU and Modbus ASCII) You can use this parameter to set the parity. You can select the following options: ▪ None ▪ Even ▪ Odd To set the parity, proceed as follows: 1. Go to Settings > Parameters > Modbus > Parity. 2. Select parity. 3. Press the Accept button to save the modified parameter. Number of stop bits (only with Modbus RTU and Modbus ASCII) You can use this parameter to set the number of stop bits. To set the number of stop bits, proceed as follows: 1. Go to Settings > Parameters > Modbus > Number of stop bits. 2. Set the number of stop bits. 3. Press the Accept button to save the modified parameter.

Maschinenfabrik Reinhausen GmbH 2019

100 5089542/05 EN MSENSE® BM 8.13.6 Configuring DNP3 (optional) If you would like to use the DNP3 control system protocol, you must set the parameters listed below. Also refer to the section Configuring the network [►Section 8.4, Page 66] if you want to use the DNP3 via TCP. Figure 70: Setting parameters for DNP3 DNP3 transmission type You can use this parameter to set the transmission type. You can select the following options: ▪ TCP ▪ Serial To set the transmission type, proceed as follows: 1. Go to Settings > Parameters > DNP3 > DNP3 transmission type. 2. Select DNP3 transmission type. 3. Press the Accept button to save the modified parameter. TCP port (only with TCP transmission type) You can use this parameter to set the TCP port. To set the TCP port, proceed as follows: 1. Go to Settings > Parameters > DNP3 > TCP port. 2. Enter the TCP port. 3. Press the Accept button to save the modified parameter