Siemens Industry, Inc.
RAA Series
Technical Instructions
Document No. 155-519P25
ET RAA-1
March 2, 2007
Room Thermostats
RAA20…
Description
Two-wire, gas diaphragm-based room thermostats for use in heating and/or cooling
only (two-pipe) systems.
Features
•
Two-point control algorithm (on-off)
•
24 to 120 Vac, 277 Vac operating voltage
•
Two mounting styles: electrical wall box or drywall
•
Wall plate adapter (ARG70) included with electrical wall
RAA Series Room Thermostats
Document Number 155-519P25
March 2, 2007
Page 2
Siemens Industry, Inc.
Table 1. Product Numbers.
Mounting Style
Product
Number
Control
Switch
Scale
Electrical Wall
Box (with wall
box adapter)
RAA10CW
Heating only or cooling only
None
Celsius (concealed)
RAA20UW
Heating only or cooling only
None
Fahrenheit and Celsius
Drywall1
RAA10C
Heating only or cooling only
None
Celsius (concealed)
RAA20U
Heating only
RAA Series Room Thermostats Technical Instructions
Document Number 155-519P25
March 2, 2007
Siemens Industry, Inc.
Page 3
Ambient Conditions
Operation
Temperature
32°F to 122°F (0°C to 50°C)
Relative humidity
<95%
Transport/Storage
Temperature
–4°F to 122°F (–20°C to 50°C)
Relative humidity
<95%
Housing
Material
Plastic
Enclosure rating
NEMA1
Bellows
Environmentally-friendly gas
Wiring
Screw terminals for wires of
2 × 16 AWG
or 1 × 14 AWG
min
RAA Series Room Thermostats Document Number 155-519P25
March 2, 2007
Page 4
Siemens Industry, Inc.
Mounting
Locate the unit where the air temperature can be sensed as accurately as possible. Do
not mount in direct sunlight or near other heat or refrigeration sources.
Mounting height is approximately 60 inches (1.5 m) above the floor.
The unit can be fitted to most commercially available recessed conduit boxes or directly
on the wall.
RAA Series Room Thermostats Technical Instructions
Document Number 155-519P25
March 2, 2007
Siemens Industry, Inc.
Page 5
Drywall Mounting
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the thermostat base and push up to
remove cover.
3. Remove sub-base from back of thermostat.
4. Using the sub-base (packed with thermostat) as a template, mark the hole locations
with a pencil.
5. Drill two 1/4-inch dia
RAA Series Room Thermostats Document Number 155-519P25
March 2, 2007
Page 6
Siemens Industry, Inc.
4 × 4-inch Electrical Wall
Box Mounting
An ARG70 wall plate adapter is required to mount an RAA… thermostat to a 4 × 4-inch
electrical wall box. The ARG70 wall plate adapter is included with electrical wall box
mount models.
1. Loosen the two screws at the bottom of thermostat.
2. Lift the bottom of the thermostat cover from the the