Siemens Industry, Inc.
PowersTM Controls
Technical Instructions
Document No. 155-064P25
TH 188-2
April 1, 2005
TH 188 Unit Mounted Thermostat
Description
The TH 188 Unit Mounted Thermostat is a remote bulb, gradual acting pneumatic
instrument that maintains a pre-selected temperature by positioning pneumatic devices
that control a heating or cooling medium.
Replacement thermostats are available for Honeywell models LP916Bxxxx and Johnson
Controls model T-3
TH 188 Unit Mounted Thermostat
Document Number 155-064P25
April 1, 2005
Page 2
Siemens Industry, Inc.
Specifications
Operating
Control action
Heating (DA) and Cooling (RA)
Direct acting only
Reverse acting only
Operating range
60° to 85° F (16° to 29° C)
Operating pressure
30 psi (207 kPa) max.
Sensitivity range
1 to 5.25 psi per degree F
(12 to 65 kPa per degree C)
Factory sensitivity setting
2.25 psi per degree F
(28 kPa per de
TH 188 Unit Mounted Thermostat Technical Instructions
Document Number 155-064P25
April 1, 2005
Siemens Industry, Inc.
Page 3
Accessories
Extension shaft
188-101
Remote bulb mounting kit
808-517
Limit stop kit (25 sets/kit)
188-144
Restrictor replacement kit
five 20 scim (5.5 ml/s) and five 40 scim (11 ml/s)
188-159
Thermostat mounting bracket
188-077
Operation
(See Figure 1).
NOTE: Pressures used refer to thermostats calibrated to Powers pressures. See Tab
TH 188 Unit Mounted Thermostat Document Number 155-064P25
April 1, 2005
Page 4
Siemens Industry, Inc.
Operation,
continued
Figure 1. Thermostat Operation.
Calibration
General
The thermostats are factory calibrated at 72° F (22° C) and 7-1/2 psi (52 kPa) control
pressure.
1. Determine the temperature at the remote bulb.
2. Set pointer to the temperature found. Dial increments are approximately five degrees on
the major divisions wi
TH 188 Unit Mounted Thermostat Technical Instructions
Document Number 155-064P25
April 1, 2005
Siemens Industry, Inc.
Page 5
Calibration,
continued
Single Action
The direct acting or reverse acting thermostat may be calibrated at any pressure. It is
suggested that 7-1/2 psi (52 kPa) be used.
Dual Action
On the HC thermostat, calibration should be at 7-1/2 psi (52 kPa) for both DA and RA. This
is due to the use of one thermal system and a reversing relay to
TH 188 Unit Mounted Thermostat Document Number 155-064P25
April 1, 2005
Page 6
Siemens Industry, Inc.
Calibration,
continued
Heat-Cool Thermostat
Changeover
See Table 1 for air pressures and changeover pressures.
The changeover is a factory adjustment; it is sealed with thread locker and does not
require field adjustment. If for some reason this adjustment is disturbed, re-adjust as
follows: (See Figure 4)
1. Supply the thermostat wi