Sentera Controls DSTHG-2 Mounting And Operating Instructions
Read Online
Read the Sentera Controls DSTHG-2 Mounting And Operating Instructions online using the built-in PDF viewer.
Text of the manual
Mounting and operating instructions
DSTHX-2
COMBINED TEMPERATURE
AND RELATIVE HUMIDITY DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
2 - 10
Table of contents
SAFETY AND PRECAUTIONS
3
PRODUCT DESCRIPTION
4
ARTICLE CODES
4
INTENDED AREA OF USE
4
TECHNICAL DATA
4
STANDARDS
4
OPERATIONAL DIAGRAMS
5
WIRING AND CONNECTIONS
5
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
5
OPERATING INSTRUCTIONS
8
MODBUS REGISTER MAPS
9
VERIFICATION OF INSTALLATION INSTRUCTIONS
10
TRANSPORT AND STORAGE
10
WARRANTY AND RESTRICTIONS
10
MAINTENANCE
10
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
3 - 10
back to the table of contents
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, mounting and operating instructions and
study the wiring and connection diagram before working with the product. For
personal and equipment safety, and for optimum product performance, make sure you
entirely understand the contents before installing, using, or maintaining this product.
For safety and licensing (CE) reasons, unauthorised conversion and / or modifications
of the product are inadmissible.
The product should not be exposed to abnormal conditions, such as: extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. This product can only be installed by an
engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts; always treat the product as if it is
live. Always disconnect the power supply before connecting, servicing or repairing
the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation / regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
4 - 10
back to the table of contents
PRODUCT DESCRIPTION
The DSTHX-2 series are dual duct transmitters which measure temperature and
relative humidity. They feature a wide range of low voltage power supply and two
analogue / modulating outputs. All parameters are accessible via Modbus RTU.
ARTICLE CODES
Article code
Supply Maximum power
consumption
Nominal power
consumption
Imax
DSTHG-2
18—34 VDC
1,68 W
1,26 W
70 mA
15—24 VAC ±10%
1,8 W
1,35 W
75 mA
DSTHF-2
18—34 VDC
1,68 W
1,26 W
70 mA
INTENDED AREA OF USE
Monitoring duct temperature and relative humidity in HVAC applications
TECHNICAL DATA
■
■Selectable temperature range: -30—70 °C
■
■Selectable relative humidity range: 0—100 %
■
■Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (5—85 % rH), depending on the selected parameter
■
■Modbus RTU communication
■
■Bootloader for updating the firmware via Modbus RTU communication
■
■Minimum airflow velocity required: 1 m/s
■
■Enclosure and probe material:
►
►ASA, grey (RAL9002)
■
■Protection standard: Enclosure: IP54, probe: IP20
■
■Operating ambient conditions:
►
►temperature: 0—50 °C
►
►rel. humidity: 5—85 % rH, (non-condensing)
■
■Storage temperature: -10—60 °C
STANDARDS
■
■EMC Directive 2014/30/EC:
►
►EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►
►EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test
configuration, operational conditions and performance criteria for transducers
with integrated or remote signal conditioning
■
■WEEE Directive 2012/19/EC
■
■RoHs Directive 2011/65/EC
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
5 - 10
back to the table of contents
OPERATIONAL DIAGRAMS
Analogue
output 1 [%]
100
-30
Min
range
Max
range
70
T [°C]
Analogue
output 2 [%]
100
0
Min
range
Max
range
100
rH [%]
WIRING AND CONNECTIONS
Article type
DSTHF-2
DSTHG-2
VIN
18—34 VDC
18—34 VDC
15—24 VAC ±10%
GND
Ground
Common ground
AC ~
A
Modbus RTU (RS485), signal A
Modbus RTU (RS485), signal A
/B
Modbus RTU (RS485), signal /B
Modbus RTU (RS485), signal /B
AO1
Analogue / modulating output 1 for
temperature measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO1
Common ground
AO2
Analogue / modulating output 2 for relative
humidity measurement (0—10 VDC /
0—20 mA / PWM)
Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
GND
Ground AO2
Common ground
Connections
Spring contact terminal blocks, cable cross section: 1,5 mm2
CAUTION
The -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds
together might result in incorrect measurements. Minimum 4 wires are required
to connect -F type sensors.
The -G version is intended for 3-wire connection and features a ‘common ground’.
This means that the ground of the analogue output is internally connected with
the ground of the power supply. For this reason, -G and -F types cannot be
used together on the same network. Never connect the common ground of -G
type articles to other devices powered by a DC voltage. Doing so might cause
permanent damage to the connected devices.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
6 - 10
back to the table of contents
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the DSTHX-2 duct transmitter, read carefully “Safety
and Precautions”.
Follow these steps:
1. When preparing to mount the DSTHX-2, bear in mind that the unit itself must be
installed onto the outer surface of the duct both via fixing the flexible flange or
directly the unit enclosure, while the probe must be inserted inside the duct, see
Fig. 1 and Fig. 2 below.
Fig. 1 Mounting dimensions
With flange
Without flange
60
Ø 12
2x Ø 5
86,8
18,5
42,3
50
285
34,5
4x Ø 4,4
70
66
100
105
80
Fig. 2 Mounting position
Correct
Incorrect
AIR FLOW
AIR FLOW
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
7 - 10
back to the table of contents
2. Having selected the appropriate mounting location, proceed with the following steps:
2.1 Drill a Ø 13 mm hole into the duct and insert the probe. Apply an air-tight
sealing between probe and duct.
2.2 Fix the flange onto the duct outer surface using the self-drilling screws
delivered with the unit. If you do not intend to use the flange, insert the
tube and fix the enclosure onto the duct. Mind the airflow direction (see
Fig. 2 and Fig. 3).
Fig. 3 Mounting requirements
7,5*D(1)
3,5*D
(1)D = Duct diameter
ATTENTION
Installation requirements: The DSTHX-2 must not be installed in turbulent air zones.
Ensure sufficiently long settling zones upstream and downstream of the tapping point.
A settling zone consists of a straight section of pipe or duct with no obstructions. Avoid
installation near filters, cooling coils, fans, etc. The sensor will achieve the optimal
result when the measurement is taken at least 7,5 duct diameters downstream and
at least 3 duct diameters upstream from any turns or flow obstructions.
ATTENTION
Installation of the unit near high EMI-emitting devices may lead to faulty
measurements. Use shielded wiring in areas with high EMI.
ATTENTION
Keep at least 15 cm distance between the sensor lines and the 230 VAC power lines.
2.3 Install the tube at the desired depth and, in case you use the flange, fix it via
the plastic white screw in the flexible flange.
2.4 Unscrew the cover of the unit to remove it and insert the connecting cables
through the cable gland of the unit.
2.5 Do the wiring according to the information in section “Wiring and
connections” adhering to Fig. 4 below.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
8 - 10
back to the table of contents
Fig. 4 Wiring and connections
Analogue / modulating 1 - T
(0—10 VDC / 0—20 mA / PWM)
Modbus
RTU
A
/B
Supply voltage
DSTHF-2: 18—34 VDC
DSTHG-2: 18—34 VDC /
15—24 VAC ±10 %
Analogue / modulating output 2 - rH
(0—10 VDC / 0—20 mA / PWM)
3. Close the enclosure and fix the cover.
4. Switch on the power supply.
5. Customise the factory settings to the desired ones via the 3SModbus software
or Sensistant (if necessary). For the default factory setting see Table Modbus
register maps.
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or
Sensistant (Holding register 9).
Example 1
Example 2
RX
ТX
NBT
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTE
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
CAUTION
Do not expose to direct sunlight!
OPERATING INSTRUCTIONS
Calibration procedure:
Both the relative humidity and temperature sensor elements are factory calibrated.
Recalibration is not necessary.
Bootloader
Thanks to the bootloader functionality, the sensor firmware can be updated via
Modbus RTU communication. To enter “Boot mode”, put a jumper onto pins 3 and
4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is
activated, the firmware can be updated via SM Boot application (part of 3SModbus
software suite) or Sensistant.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
9 - 10
back to the table of contents
Fig. 5 P1 header
1 2 3 4 5
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
1 2 3 4 5
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
MODBUS REGISTER MAPS
MODBUS REGISTER MAP
INPUT REGISTERS
Input Registers
Data type
Description
Data
Values
1
Temperature reading
signed int
Actual temperature level
-300—700
500 = 50,0°C
2
Output value 1 (T)
unsigned int
Output value 1 (T)
0—1.000
0 = 0 %
1.000 = 100 %
3
Temperature alert flag
unsigned int
Flag indicates that measured Temperature is outside set alert values. Set to
'1' when the measured value is outside the Temperature alert values defined
by holding registers 13 and 14
0—1
0 = Temperature measurement OK
1 = Temperature measurement too low/
high
4
Temperature range limit flag
unsigned int
Flag indicates that measured temperature is outside set range limit
values. Set to '1' when the measured temperature is outside limit range
values defined by holding registers 11 and 12
0—1
0 = Temperature range OK
1 = Temperature range too low/high
5
Humidity, temperature sensor fault
unsigned int
Flag that shows if the communication with temperature & humidity sensor
is lost
0—1
0 = No
1 = Yes
6—9
Reserved, return 0
10
Relative humidity level
unsigned int
Actual relative humidity level
0—1.000
1.000 = 100,0 % rH
11
Output value 2 (rH)
unsigned int
Output value 2 (rH)
0—1.000
0 = 0 %
1.000 = 100 %
12
Relative humidity alert flag
unsigned int
Flag indicates that measured Relative humidity is outside set alert
values. Set to '1' when the measured value is outside the Relative
humidity alert values defined by holding registers 21 and 22
0—1
0 = Relative humidity measurement OK
1 = Relative humidity measurement too
low/high
13
Relative humidity range limit flag
unsigned int
Flag indicates that measured Relative humidity is outside set range limit
values. Set to '1' when the measured Relative humidity is outside limit
range values defined by holding registers 19 and 20
0—1
0 = Relative humidity range OK
1 = Relative humidity range too low/high
14
Humidity, temperature sensor fault
unsigned int
Flag that shows if the communication with temperature & humidity
sensor is lost
0—1
0 = No
1 = Yes
15
Dew point level
signed int
Calculated dew point
-700—700
200 = 20,0°C
16—50
Reserved, return 0
HOLDING REGISTERS
Holding Registers
Data type
Description
Data
Values
1
Device slave address
unsigned int
Modbus device address
1—247
default: 1
2
Modbus baud rate
unsigned int
Modbus communication baud rate
0—6
default: 2
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400
4 = 57.600
5 = 115.200
6 = 230.400
3
Modbus parity
unsigned int
Parity check mode
0— 2
default: 1
0 = 8N1
1 = 8E1
2 = 8O1
4
Device type
unsigned int
Device type. Read only
DSTHG-2 = 1.632
DSTHF-2 = 1.633
5
HW version
unsigned int
Hardware version of the device. Read only
XXXX
0x0100 = HW version 1.0
6
FW version
unsigned int
Firmware version of the device. Read only
XXXX
0x0200 = FW version 2.2
7
Reserved, returns 0
8
Modbus safety timeout
unsigned int
After time with no Modbus communication,
outputs are set to 0.
0—60
default: 0
60 = 60 minutes
9
Modbus network resistor
termination (NBT)
unsigned int
Set device as end device of the line / or not by
connecting NBT
0—1
default: 0
0 = NBT disconnected
1 = NBT connected
10
Modbus registers reset
unsigned int
Resets Modbus Holding registers to default
values. When finished this register is
automatically reset to '0'
0—1
default: 0
0 = Idle
1 = Reset Modbus Registers
11
Minimum temperature range
unsigned int
Minimum value of temperature range, cannot
be set higher than maximum temperature
range minus 5°C
-300 - (Max-50)
default: 0
100 = 10,0°C
12
Maximum temperature range
unsigned int
Maximum value of temperature range, cannot
be set less than minimum temperature range
plus 5°C
(Min+50)—700
default: 500
500 = 50,0°C
13
Minimum temperature alert
unsigned int
Minimum temperature alarm value
Min. temperature range —Max.
temperature alarm
default: 0
500 = 50,0°C
14
Maximum temperature alert
unsigned int
Maximum temperature alarm value
Min. temperature alarm —Max.
temperature range
default: 500
500 = 50,0°C
15—18
Reserved, return 0
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER
MIW-DSTHX-2-EN-000 - 23 / 07 / 2019
10 - 10
back to the table of contents
HOLDING REGISTERS
Holding Registers
Data type
Description
Data
Values
19
Minimum relative humidity
range
unsigned int
Minimum value of relative humidity range,
cannot be set higher than maximum relative
humidity range minus 5%
0—(Max-50)
default: 0
200 = 20,0 % rH
20
Maximum relative humidity
range
unsigned int
Maximum value of relative humidity range,
cannot be set less than minimum relative
humidity range plus 5%
(Min+50)—1.000
default: 1.000
850 = 85 % rH
21
Minimum relative humidity
alert
unsigned int
Minimum relative humidity alarm value
Min. relative humidity range—Max.
relative humidity alarm
default: 0
200 = 20,0 % rH
22
Maximum relative humidity
alert
unsigned int
Maximum relative humidity alarm value
Min. relative humidity alarm —Max.
relative humidity range
default: 1.000
850 = 85 % rH
23—40
Reserved, return 0
41
Output 1 type (T)
unsigned int
Select analogue / modulating output 1 type
1—3
default: 1
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
42
Output 1 overwrite (T)
unsigned int
Enables the direct control over the temperature
output.
0—1
default: 0
0 = Disabled
1 = Enabled
43
Output 1 overwrite value (T)
unsigned int
Overwrite value for output 1. Active only if
Holding register 42 is set to 1.
0—1.000
default: 0
0 = 0 %
1.000 = 100 %
44
Internal voltage source
selection Output 1 (T)
unsigned int
Selection of internal voltage source for PWM
output 1.
0—1
default: 0
0 = 3,3 VDC
1 = 12 VDC
45—50
Reserved, return 0
51
Output 2 type (rH)
unsigned int
Select analogue / modulating output 2 type.
1—3
default: 1
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
52
Output 2 overwrite (rH)
unsigned int
Enables the direct control over the relative
humidity output.
0—1
default: 0
0 = Disabled
1 = Enabled
53
Output 2 overwrite value
(rH)
unsigned int
Overwrite value for output 2. Active only if
Holding register 52 is set to 1.
0—1.000
default: 0
0 = 0 %
1.000 = 100 %
54
Internal voltage source
selection Output 2 (rH)
unsigned int
Selection of internal voltage source for PWM
output 2.
0—1
default: 0
0 = 3,3 VDC
1 = 12 VDC
55—80
Reserved, return 0
If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
VERIFICATION OF INSTALLATION INSTRUCTIONS
If your unit does not function as expected, please check the connections.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; store in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. The manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non‑aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.
DSTHX-2
COMBINED T AND rH DUCT
TRANSMITTER