Sentera Controls RMFPM-2R Mounting And Operating Instructions
Read Online
Read the Sentera Controls RMFPM-2R Mounting And Operating Instructions online using the built-in PDF viewer.
Text of the manual
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
2 - 11
Table of contents
SAFETY AND PRECAUTIONS
3
PRODUCT DESCRIPTION
4
ARTICLE CODES
4
INTENDED AREA OF USE
4
TECHNICAL DATA
4
STANDARDS
4
OPERATIONAL DIAGRAM
5
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
5
OPERATING INSTRUCTIONS
7
VERIFICATION OF INSTALLATION INSTRUCTIONS
8
MODBUS REGISTER MAPS
9
TRANSPORT AND STORAGE
11
WARRANTY AND RESTRICTIONS
11
MAINTENANCE
11
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
3 - 11
back to the table of contents
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, mounting and operating instructions and
study the wiring and connection diagram before working with the product. For
personal and equipment safety, and for optimum product performance, make sure you
entirely understand the contents before installing, using, or maintaining this product.
For safety and licensing (CE) reasons, unauthorised conversion and / or
modifications of the product are inadmissible.
The product should not be exposed to abnormal conditions, such as extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. This product can only be installed by an
engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts. Always disconnect the power
supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation / regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
4 - 11
back to the table of contents
PRODUCT DESCRIPTION
The RMFPM-2R are multifunctional room controllers featuring adjustable
temperature, relative humidity and CO2 setpoints. They are Power over Modbus
supplied and all parameters and the output are accessible via Modbus RTU.
ARTICLE CODES
Code
Supply
Connection
RMFPM-2R
24 VDC, PoM
RJ45
INTENDED AREA OF USE
■
■Control of temperature, relative humidity and CO2 levels
■
■Suitable for residential and commercial buildings
■
■For indoor use only
TECHNICAL DATA
■
■Selectable temperature, relative humidity and CO2 setpoints
■
■Ambient light sensor with adjustable ‘active’ and ‘standby’ level
■
■Bootloader for updating the firmware via Modbus RTU communication
■
■3 LEDs for status indication
■
■Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (0—100 % rH); ±30 ppm CO2 ±3 %
(0—2.000 ppm CO2), depending on the selected parameter
■
■Maximum power consumption: 1,2 W
■
■Nominal power consumption in normal operation: 0,9 W
■
■Imax: 50 mA
■
■Enclosure:
►
►rear plate: plastic ABS, black (RAL 9004)
►
►front cover: ASA, ivory (RAL 9010)
■
■Protection standard: IP30 (according to EN 60529)
■
■Operating ambient conditions:
►
►temperature: 0—50 °C
►
►rel. humidity: 0—100 % rH, (non-condensing)
■
■Storage temperature: -10—60 °C
STANDARDS
■
■Low Voltage Directive 2014/35/EC:
►
►EN 60529:1991 Degrees of protection provided by enclosures (IP Code)
Amendment AC:1993 to EN 60529
►
►EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
■
■EMC Directive 2014/30/EC:
►
►EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
►
►EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards - Immunity for residential, commercial and light industrial environments
►
►EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
standards - Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
5 - 11
back to the table of contents
►
►EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►
►EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements - Test
configuration, operational conditions and performance criteria for transducers
with integrated or remote signal conditioning
■
■WEEE 2012/19/EC
■
■RoHs Directive 2011/65/EC
OPERATIONAL DIAGRAM
Max
range
Min
range
60
40
100
0
rH Min range
0
0
0
CO2 Min range
CO2 Max range
Max
Min
T Min range T Max range
rH Max range
Input
Register 2
[%]
50
100
2.000
rH [%]
T [°C]
CO2 [ppm]
WIRING AND CONNECTIONS
RJ45 socket (Power over Modbus)
Pin 1
24 VDC
Supply voltage
Pin 2
Pin 3
A
Modbus RTU communication, signal A
Pin 4
Pin 5
/B
Modbus RTU communication, signal /B
Pin 6
Pin 7
GND
Ground, supply voltage
Pin 8
/B
A
GND
24 VDC
8 mm
8 mm
8 mm
8 mm
RJ45
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the RSMFM-2R room transmitter, read carefully
“Safety and Precautions”. Choose a smooth surface (a wall, panel and etc.).
Follow these steps:
1. Using a flat screwdriver, remove the front white cover by releasing the snap-fits
on its both sides (See Fig. 1 Snap-fits release).
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
6 - 11
back to the table of contents
2. Insert the crimped RJ45 cable through the opening on the rear plate and plug it
into the socket (See Fig. 2 Mounting dimensions.)
3. Using suitable fastening materials (not supplied), position the room sensor at
least 1,5 m from the floor. When planning the installation, allow enough clearance
for maintenance and service. Mount the sensor in a well-ventilated area. Mind
the correct mounting position and unit dimensions. See Fig. 2 and Fig. 3.
Fig. 1 Snap-fits release
Fig. 2 Mounting dimension
Fig. 3 Mounting position
2x Ø 6
59,8
9,8
74,5
104,5
20
104,5
25,6
70,5
Correct
Incorrect
Position at min. 1,5 m
from the floor
4. Do the wiring according to the wiring diagram (see Fig. 4).
Fig. 4 Wiring
5. Put back the cover and snap it in.
6. Switch on the mains supply.
5.
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or
Sensistant (Holding register 9).
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
7 - 11
back to the table of contents
Example 1
Example 2
RX
ТX
NBT
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
NOTE
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
ATTENTION
t
Do not expose to direct sunlight!
OPERATING INSTRUCTIONS
Calibration procedure:
Sensor calibration is not necessary.
In the unlikely event of CO2 sensor element failure, this component can be replaced.
All sensor elements are calibrated and tested in our factory.
Bootloader
Thanks to the bootloader functionality, the sensor firmware can be updated via
Modbus RTU communication. To enter ‘Boot mode”, put a jumper onto pins 3 and
4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is
activated, the firmware can be updated via SM Boot application (part of 3SModbus
software suite) or Sensistant.
Fig. 5 P1 header
1 2
3
4
5
Put a jumper onto pins 1 and 2 and wait
for at least 5 seconds to reset the Modbus
communication parameters
1 2
3
4
5
Put a jumper onto pins 3 and 4 and restart
the supply to enter bootloader mode
LED indications
1. When the green LED is on, the measured value (temperature, relative humidity or
CO2) is between the minimum and maximum alert range values (Fig. 6 - 1).
2. When the yellow LED is on, the measured value (temperature, relative humidity
or CO2) is in the alert range (Fig. 6 - 2).
3. When the red LED is on, the measured value (temperature, relative humidity or
CO2) is below the minimum measurement range value or above the maximum
value. Blinking red LED indicates loss of communication with a sensor (Fig. 6 - 3).
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
8 - 11
back to the table of contents
Fig. 6 LED indications
3
2
1
NOTE
By default, the LED indication refers to temperature measurements. This can be
changed to relative humidity or CO2 values via Modbus Holding Register 79 (see
Table Holding registers below).
Green LED intensity can be adjusted between 0 and 100 % with step of 10 %
according to the value set in Holding register 80.
Ambient light sensor
The measured light intensity in lux is available in Input Register 41. Additionally,
an active and standby level can be defined in Holding registers 35 and 36. Input
Register 42 indicates if the measured value is below standby level, above active
level or in between both levels:
■
■If the measured light level is below the Standby level, Input Register 42 indicates
“Standby”.
■
■If the measured ambient light level is above the Active level, Input Register 42
indicates “Active”.
■
■If the measured ambient light level is between the active and stand-by level, Input
Register 42 indicates “Low intensity”. When this feature is used, it is advisable to
adjust the active and standby levels in Holding Registers 34 and 35 according to
the actual ambient light conditions around the sensor.
VERIFICATION OF INSTALLATION INSTRUCTIONS
After switching on the power supply one of the LEDs lights up according to the
status of the measured variable. If this is not the case, check the connections.
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
9 - 11
back to the table of contents
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type
Description
Data
Values
1
Temperature reading
signed int
Actual temperature level
-300—700
500 = 50,0°C
2
Output value 1
unsigned int
Output value 1
0—1.000
0 = 0 %
1.000 = 100 %
3
Temperature alert flag
unsigned int
Flag indicates that measured Temperature is
outside set alert values. Set to '1' when the
measured value is outside the Temperature alert
values defined by holding registers 13 and 14
0—1
0 = Temperature measurement OK
1 = Temperature measurement too low/high
4
Temperature range limit
flag
unsigned int
Flag indicates that measured temperature is
outside set range limit values. Set to '1' when
the measured temperature is outside limit range
values defined by holding registers 11 and 12
0—1
0 = Temperature range OK
1 = Temperature range too low/high
5
Humidity, temperature
sensor fault
unsigned int
Flag that shows if the communication with
temperature & humidity sensor is lost
0—1
0 = No
1 = Yes
6—9
Reserved, return 0.
10
Relative humidity level
unsigned int
Actual relative humidity level
0—1.000
1.000 = 100,0 % rH
11
Reserved, returns 0.
12
Relative humidity alert flag
unsigned int
Flag indicates that measured Relative humidity
is outside set alert values. Set to '1' when the
measured value is outside the Relative humidity
alert values defined by holding registers 21 and 22
0 1
0 = Relative humidity measurement OK
1 = Relative humidity measurement too low/
high
13
Relative humidity range
limit flag
unsigned int
Flag indicates that measured Relative humidity
is outside set range limit values. Set to '1' when
the measured Relative humidity is outside limit
range values defined by holding registers 19 and
20
0—1
0 = Relative humidity range OK
1 = Relative humidity range too low/high
14
Humidity, temperature
sensor fault
unsigned int
Flag that shows if the communication with
temperature & humidity sensor is lost
0—1
0 = No
1 = Yes
15
Dew point level
signed int
Calculated dew point
-700—700
200 = 20,0°C
16—20
Reserved, return 0.
21
CO2 level
unsigned int
Actual CO2 level
0—2.000
2.000 = 2.000 ppm
22
Reserved, returns 0
23
CO2 alert flag
unsigned int
Flag indicates that measured CO2 level is outside
set alert values. Set to '1' when the measured
value is outside the CO2 values defined by
holding registers 25 and 26
0—1
0 = CO2 measurement OK
1 = CO2 measurement too low/high
24
CO2 range limit flag
unsigned int
Flag indicates that measured CO2 is outside set
range limit values. Set to '1' when the measured
CO2 is outside limit range values set defined by
holding registers 23 and 24
0—1
0 = CO2 range OK
1 = CO2 range too low/high
25
CO2 Sensor fault
unsigned int
Flag that shows if the communication with the
CO2 sensor is lost
0—1
0 = No
1 = Yes
26—40
Reserved, returns 0
41
Ambient light intensity
unsigned int
Measured ambient light intensity
0—32.000
1.000 = 1.000 lux
42
Active / Standby
unsigned int
Active or Standby indication according the
Active / Standby light level defined by holding
registers 35 and 36. If the measured light level
is between the two levels the indication is 0 (Low
light intensity)
0—2
0 = Low light intensity
1 = Active
2 = Standby
43
Ambient light sensor fault
unsigned int
Flag that shows if the communication with the
ambient light sensor is lost
0—1
0 = No
1 = Yes
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
10 - 11
back to the table of contents
HOLDING REGISTERS
Data type
Description
Data
Values
1
Device slave address
unsigned int
Modbus device address
1—247
default: 1
2
Modbus baud rate
unsigned int
Modbus communication baud rate
0—6
default: 2
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400
4 = 57.600
5 = 115.200
6 = 230.400
3
Modbus parity
unsigned int
Parity check mode
0— 2
default: 1
0 = 8N1
1 = 8E1
2 = 8O1
4
Device type
unsigned int
Device type. Read only
RMFPМ-2R = 1.611
5
HW version
unsigned int
Hardware version of the device. Read only
XXXX
0x0200 = HW version 2.0
6
FW version
unsigned int
Firmware version of the device. Read only
XXXX
0x0200 = FW version 2.0
7—8
Reserved, return 0
9
Modbus network
resistor termination
(NBT)
unsigned int
Set device as end device of the line / or not by
connecting NBT
0—1
default: 0
0 = NBT disconnected
1 = NBT connected
10
Modbus registers
reset
unsigned int
Resets Modbus Holding registers to default values. When
finished this register is automatically reset to '0'
0—1
default: 0
0 = Idle
1 = Reset Modbus
Registers
11
Minimum temperature
range
unsigned int
Minimum value of temperature range, cannot be set
higher than maximum temperature range minus 5°C
0—Max-50
default: 0
100 = 10,0°C
12
Maximum
temperature range
unsigned int
Maximum value of temperature range, cannot be set less
than minimum temperature range plus 5°C
Min+50—500
default: 500
500 = 50,0°C
13
Minimum temperature
alert
unsigned int
Minimum temperature alarm value
Min. temperature range—Max.
temperature alarm
default: 0
500 = 50,0°C
14
Maximum
temperature alert
unsigned int
Maximum temperature alarm value
Min. temperature alarm—Max.
temperature range
default: 500
500 = 50,0°C
15—18
Reserved, return 0
19
Minimum relative
humidity range
unsigned int
Minimum value of relative humidity range, cannot be set
higher than maximum relative humidity range minus 5%
0—Max-50
default: 0
200 = 20,0 % rH
20
Maximum relative
humidity range
unsigned int
Maximum value of relative humidity range, cannot be set
less than minimum relative humidity range plus 5%
Min+50—1.000
default: 1.000
850 = 85 % rH
21
Minimum relative
humidity alert
unsigned int
Minimum relative humidity alarm value
Min. relative humidity range—
Max. relative humidity alarm
default: 0
200 = 20,0 % rH
22
Maximum relative
humidity alert
unsigned int
Maximum relative humidity alarm value
Min. relative humidity alarm—
Max. relative humidity range
default: 1.000
850 = 85 % rH
23
Minimum CO2 range
unsigned int
Minimum CO2 range, cannot be set higher than
maximum CO2 range minus 100 ppm
0—Max-100
default: 400
1.000 = 1.000 ppm
24
Maximum CO2 range
unsigned int
Maximum CO2 range, cannot be set less than minimum
CO2 range plus 100 ppm
Min+100—2.000
default: 2.000
2.000 = 2.000 ppm
25
Minimum CO2 alert
unsigned int
Minimum CO2 alarm value
Min. CO2 range—Max. CO2
alarm
default: 400
400 = 400 ppm
26
Maximum CO2 alert
unsigned int
Maximum CO2 alarm value
Min. CO2 alarm —Max. CO2
range
default: 2.000
2.000 = 2.000 ppm
27—34
Reserved, return 0
38
Minimum output
value
unsigned int.
Sets minimum value of output signal expressed as a
percentage
0—40
0
39
Maximum output
value
unsigned int.
Sets maximum value of output signal expressed as a
percentage
60—100
100
35
Active mode light
level
unsigned int
The ambient light level above which 'Active' is indicated
in input register 42
0—32.000
default: 100
100 = 100 lux
36
Standby mode light
level
unsigned int
The ambient light level below which 'Standby' is
indicated in input register 42
0—32.000
default: 10
10 = 10 lux
37—39
Reserved, return 0
40
CO2 module self
calibration
unsigned int
Enables or disables the CO2 module self calibration
technique. If enabled it is advisable that the CO2
concentration drops to outside level (400 ppm) in a 7
day period.
0—1
default: 1
0 = Disabled
1 = Enabled
41—44
Reserved, return 0
45
Minimum output
value
unsigned int
Set minimum value of output signal in percentage
0—40
default: 0
20 = 20 %
46
Maximum output
value
unsigned int
Set maximum value of output signal in percentage
60—100
default: 100
60 = 60 %
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER
MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019
11 - 11
back to the table of contents
HOLDING REGISTERS
Data type
Description
Data
Values
47—78
Reserved, return 0
79
LED indication
unsigned int
LED indication related to one of the parameters
1—3
default: 1
1= Temperature
2 = rH
3 = CO2
80
LED intensity /
brightness
unsigned int
LED intensity (incrementing with step of 10 %)
0—10
default: 5
0 = OFF
1 = 10 %
10 = 100 %
If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. The manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non‑aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completely dry.
RMFPM-2R
MULTIFUNCTIONAL ROOM
CONTROLLER