MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

2 - 11 Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAM 5 MOUNTING & OPERATING INSTRUCTIONS IN STEPS 5 OPERATING INSTRUCTIONS 7 VERIFICATION OF INSTALLATION INSTRUCTIONS 8 MODBUS REGISTER MAPS 9 TRANSPORT AND STORAGE 11 WARRANTY AND RESTRICTIONS 11 MAINTENANCE 11 RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

3 - 11 back to the table of contents SAFETY AND PRECAUTIONS Read all the information, the datasheet, mounting and operating instructions and study the wiring and connection diagram before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product. For safety and licensing (CE) reasons, unauthorised conversion and  / or modifications of the product are inadmissible. The product should not be exposed to abnormal conditions, such as extreme temperatures, direct sunlight or vibrations. Long-term exposure to chemical vapours in high concentration can affect the product performance. Make sure the work environment is as dry as possible; avoid condensation. All installations shall comply with local health and safety regulations and local electrical standards and approved codes. This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions. Avoid contacts with energised electrical parts. Always disconnect the power supply before connecting, servicing or repairing the product. Always verify that you apply appropriate power supply to the product and use appropriate wire size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well. Recycling of equipment and packaging should be taken into consideration and these should be disposed of in accordance with local and national legislation / regulations. In case there are any questions that are not answered, please contact your technical support or consult a professional.  RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

4 - 11 back to the table of contents PRODUCT DESCRIPTION The RMFPM-2R are multifunctional room controllers featuring adjustable temperature, relative humidity and CO2 setpoints. They are Power over Modbus supplied and all parameters and the output are accessible via Modbus RTU. ARTICLE CODES Code Supply Connection RMFPM-2R 24 VDC, PoM RJ45 INTENDED AREA OF USE ■ ■Control of temperature, relative humidity and CO2 levels ■ ■Suitable for residential and commercial buildings ■ ■For indoor use only TECHNICAL DATA ■ ■Selectable temperature, relative humidity and CO2 setpoints ■ ■Ambient light sensor with adjustable ‘active’ and ‘standby’ level ■ ■Bootloader for updating the firmware via Modbus RTU communication ■ ■3 LEDs for status indication ■ ■Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (0—100 % rH); ±30 ppm CO2 ±3 % (0—2.000 ppm CO2), depending on the selected parameter ■ ■Maximum power consumption: 1,2 W ■ ■Nominal power consumption in normal operation: 0,9 W ■ ■Imax: 50 mA ■ ■Enclosure: ► ►rear plate: plastic ABS, black (RAL 9004) ► ►front cover: ASA, ivory (RAL 9010) ■ ■Protection standard: IP30 (according to EN 60529) ■ ■Operating ambient conditions: ► ►temperature: 0—50 °C ► ►rel. humidity: 0—100 % rH, (non-condensing) ■ ■Storage temperature: -10—60 °C STANDARDS ■ ■Low Voltage Directive 2014/35/EC: ► ►EN 60529:1991 Degrees of protection provided by enclosures (IP Code) Amendment AC:1993 to EN 60529 ► ►EN 60730-1:2011 Automatic electrical controls for household and similar use - Part 1: General requirements ■ ■EMC Directive 2014/30/EC: ► ►EN 60730-1:2011 Automatic electrical controls for household and similar use - Part 1: General requirements ► ►EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity for residential, commercial and light industrial environments ► ►EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for residential, commercial and light-industrial environments Amendments A1:2011 and AC:2012 to EN 61000-6-3 RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

5 - 11 back to the table of contents ► ►EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements ► ►EN 61326-2-3:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 2-3: Particular requirements - Test configuration, operational conditions and performance criteria for transducers with integrated or remote signal conditioning ■ ■WEEE 2012/19/EC ■ ■RoHs Directive 2011/65/EC OPERATIONAL DIAGRAM Max range Min range 60 40 100 0 rH Min range 0 0 0 CO2 Min range CO2 Max range Max Min T Min range T Max range rH Max range Input Register 2 [%] 50 100 2.000 rH [%] T [°C] CO2 [ppm] WIRING AND CONNECTIONS RJ45 socket (Power over Modbus) Pin 1 24 VDC Supply voltage Pin 2 Pin 3 A Modbus RTU communication, signal A Pin 4 Pin 5 /B Modbus RTU communication, signal /B Pin 6 Pin 7 GND Ground, supply voltage Pin 8 /B A GND 24 VDC 8 mm 8 mm 8 mm 8 mm RJ45 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 MOUNTING & OPERATING INSTRUCTIONS IN STEPS Before you start mounting the RSMFM-2R room transmitter, read carefully “Safety and Precautions”. Choose a smooth surface (a wall, panel and etc.). Follow these steps: 1. Using a flat screwdriver, remove the front white cover by releasing the snap-fits on its both sides (See Fig. 1 Snap-fits release). RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

6 - 11 back to the table of contents 2. Insert the crimped RJ45 cable through the opening on the rear plate and plug it into the socket (See Fig. 2 Mounting dimensions.) 3. Using suitable fastening materials (not supplied), position the room sensor at least 1,5 m from the floor. When planning the installation, allow enough clearance for maintenance and service. Mount the sensor in a well-ventilated area. Mind the correct mounting position and unit dimensions. See Fig. 2 and Fig. 3. Fig. 1 Snap-fits release Fig. 2 Mounting dimension Fig. 3 Mounting position 2x Ø 6 59,8 9,8 74,5 104,5 20 104,5 25,6 70,5 Correct Incorrect Position at min. 1,5 m from the floor 4. Do the wiring according to the wiring diagram (see Fig. 4). Fig. 4 Wiring 5. Put back the cover and snap it in. 6. Switch on the mains supply. 5. Optional settings To assure correct communication, the NBT needs to be activated in only two devices on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or Sensistant (Holding register 9). RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

7 - 11 back to the table of contents Example 1 Example 2 RX ТX NBT NBT NBT Slave 2 Master Slave n Slave 1 Slave 2 Slave 1 RX ТX NBT NBT Master Slave n NOTE On a Modbus RTU network, two bus terminators (NBTs) need to be activated. ATTENTION  t Do not expose to direct sunlight! OPERATING INSTRUCTIONS Calibration procedure: Sensor calibration is not necessary. In the unlikely event of CO2 sensor element failure, this component can be replaced. All sensor elements are calibrated and tested in our factory. Bootloader Thanks to the bootloader functionality, the sensor firmware can be updated via Modbus RTU communication. To enter ‘Boot mode”, put a jumper onto pins 3 and 4 of the P1 header and restart the power supply (see Fig. 5). Once ‘Boot mode’ is activated, the firmware can be updated via SM Boot application (part of 3SModbus software suite) or Sensistant. Fig. 5 P1 header 1 2 3 4 5 Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus communication parameters 1 2 3 4 5 Put a jumper onto pins 3 and 4 and restart the supply to enter bootloader mode LED indications 1. When the green LED is on, the measured value (temperature, relative humidity or CO2) is between the minimum and maximum alert range values (Fig. 6 - 1). 2. When the yellow LED is on, the measured value (temperature, relative humidity or CO2) is in the alert range (Fig. 6 - 2). 3. When the red LED is on, the measured value (temperature, relative humidity or CO2) is below the minimum measurement range value or above the maximum value. Blinking red LED indicates loss of communication with a sensor (Fig. 6 - 3). RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

8 - 11 back to the table of contents Fig. 6 LED indications 3 2 1 NOTE By default, the LED indication refers to temperature measurements. This can be changed to relative humidity or CO2 values via Modbus Holding Register 79 (see Table Holding registers below). Green LED intensity can be adjusted between 0 and 100 % with step of 10 % according to the value set in Holding register 80. Ambient light sensor The measured light intensity in lux is available in Input Register 41. Additionally, an active and standby level can be defined in Holding registers 35 and 36. Input Register 42 indicates if the measured value is below standby level, above active level or in between both levels: ■ ■If the measured light level is below the Standby level, Input Register 42 indicates “Standby”. ■ ■If the measured ambient light level is above the Active level, Input Register 42 indicates “Active”. ■ ■If the measured ambient light level is between the active and stand-by level, Input Register 42 indicates “Low intensity”. When this feature is used, it is advisable to adjust the active and standby levels in Holding Registers 34 and 35 according to the actual ambient light conditions around the sensor. VERIFICATION OF INSTALLATION INSTRUCTIONS After switching on the power supply one of the LEDs lights up according to the status of the measured variable. If this is not the case, check the connections. RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

9 - 11 back to the table of contents MODBUS REGISTER MAPS INPUT REGISTERS Data type Description Data Values 1 Temperature reading signed int Actual temperature level -300—700 500 = 50,0°C 2 Output value 1 unsigned int Output value 1 0—1.000 0 = 0 % 1.000 = 100 % 3 Temperature alert flag unsigned int Flag indicates that measured Temperature is outside set alert values. Set to '1' when the measured value is outside the Temperature alert values defined by holding registers 13 and 14 0—1 0 = Temperature measurement OK 1 = Temperature measurement too low/high 4 Temperature range limit flag unsigned int Flag indicates that measured temperature is outside set range limit values. Set to '1' when the measured temperature is outside limit range values defined by holding registers 11 and 12 0—1 0 = Temperature range OK 1 = Temperature range too low/high 5 Humidity, temperature sensor fault unsigned int Flag that shows if the communication with temperature & humidity sensor is lost 0—1 0 = No 1 = Yes 6—9 Reserved, return 0. 10 Relative humidity level unsigned int Actual relative humidity level 0—1.000 1.000 = 100,0 % rH 11 Reserved, returns 0. 12 Relative humidity alert flag unsigned int Flag indicates that measured Relative humidity is outside set alert values. Set to '1' when the measured value is outside the Relative humidity alert values defined by holding registers 21 and 22 0 1 0 = Relative humidity measurement OK 1 = Relative humidity measurement too low/ high 13 Relative humidity range limit flag unsigned int Flag indicates that measured Relative humidity is outside set range limit values. Set to '1' when the measured Relative humidity is outside limit range values defined by holding registers 19 and 20 0—1 0 = Relative humidity range OK 1 = Relative humidity range too low/high 14 Humidity, temperature sensor fault unsigned int Flag that shows if the communication with temperature & humidity sensor is lost 0—1 0 = No 1 = Yes 15 Dew point level signed int Calculated dew point -700—700 200 = 20,0°C 16—20 Reserved, return 0. 21 CO2 level unsigned int Actual CO2 level 0—2.000 2.000 = 2.000 ppm 22 Reserved, returns 0 23 CO2 alert flag unsigned int Flag indicates that measured CO2 level is outside set alert values. Set to '1' when the measured value is outside the CO2 values defined by holding registers 25 and 26 0—1 0 = CO2 measurement OK 1 = CO2 measurement too low/high 24 CO2 range limit flag unsigned int Flag indicates that measured CO2 is outside set range limit values. Set to '1' when the measured CO2 is outside limit range values set defined by holding registers 23 and 24 0—1 0 = CO2 range OK 1 = CO2 range too low/high 25 CO2 Sensor fault unsigned int Flag that shows if the communication with the CO2 sensor is lost 0—1 0 = No 1 = Yes 26—40 Reserved, returns 0 41 Ambient light intensity unsigned int Measured ambient light intensity 0—32.000 1.000 = 1.000 lux 42 Active / Standby unsigned int Active or Standby indication according the Active / Standby light level defined by holding registers 35 and 36. If the measured light level is between the two levels the indication is 0 (Low light intensity) 0—2 0 = Low light intensity 1 = Active 2 = Standby 43 Ambient light sensor fault unsigned int Flag that shows if the communication with the ambient light sensor is lost 0—1 0 = No 1 = Yes RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

10 - 11 back to the table of contents HOLDING REGISTERS Data type Description Data Values 1 Device slave address unsigned int Modbus device address 1—247 default: 1 2 Modbus baud rate unsigned int Modbus communication baud rate 0—6 default: 2 0 = 4.800 1 = 9.600 2 = 19.200 3 = 38.400 4 = 57.600 5 = 115.200 6 = 230.400 3 Modbus parity unsigned int Parity check mode 0— 2 default: 1 0 = 8N1 1 = 8E1 2 = 8O1 4 Device type unsigned int Device type. Read only RMFPМ-2R = 1.611 5 HW version unsigned int Hardware version of the device. Read only XXXX 0x0200 = HW version 2.0 6 FW version unsigned int Firmware version of the device. Read only XXXX 0x0200 = FW version 2.0 7—8 Reserved, return 0 9 Modbus network resistor termination (NBT) unsigned int Set device as end device of the line / or not by connecting NBT 0—1 default: 0 0 = NBT disconnected 1 = NBT connected 10 Modbus registers reset unsigned int Resets Modbus Holding registers to default values. When finished this register is automatically reset to '0' 0—1 default: 0 0 = Idle 1 = Reset Modbus Registers 11 Minimum temperature range unsigned int Minimum value of temperature range, cannot be set higher than maximum temperature range minus 5°C 0—Max-50 default: 0 100 = 10,0°C 12 Maximum temperature range unsigned int Maximum value of temperature range, cannot be set less than minimum temperature range plus 5°C Min+50—500 default: 500 500 = 50,0°C 13 Minimum temperature alert unsigned int Minimum temperature alarm value Min. temperature range—Max. temperature alarm default: 0 500 = 50,0°C 14 Maximum temperature alert unsigned int Maximum temperature alarm value Min. temperature alarm—Max. temperature range default: 500 500 = 50,0°C 15—18 Reserved, return 0 19 Minimum relative humidity range unsigned int Minimum value of relative humidity range, cannot be set higher than maximum relative humidity range minus 5% 0—Max-50 default: 0 200 = 20,0 % rH 20 Maximum relative humidity range unsigned int Maximum value of relative humidity range, cannot be set less than minimum relative humidity range plus 5% Min+50—1.000 default: 1.000 850 = 85 % rH 21 Minimum relative humidity alert unsigned int Minimum relative humidity alarm value Min. relative humidity range— Max. relative humidity alarm default: 0 200 = 20,0 % rH 22 Maximum relative humidity alert unsigned int Maximum relative humidity alarm value Min. relative humidity alarm— Max. relative humidity range default: 1.000 850 = 85 % rH 23 Minimum CO2 range unsigned int Minimum CO2 range, cannot be set higher than maximum CO2 range minus 100 ppm 0—Max-100 default: 400 1.000 = 1.000 ppm 24 Maximum CO2 range unsigned int Maximum CO2 range, cannot be set less than minimum CO2 range plus 100 ppm Min+100—2.000 default: 2.000 2.000 = 2.000 ppm 25 Minimum CO2 alert unsigned int Minimum CO2 alarm value Min. CO2 range—Max. CO2 alarm default: 400 400 = 400 ppm 26 Maximum CO2 alert unsigned int Maximum CO2 alarm value Min. CO2 alarm —Max. CO2 range default: 2.000 2.000 = 2.000 ppm 27—34 Reserved, return 0 38 Minimum output value unsigned int. Sets minimum value of output signal expressed as a percentage 0—40 0 39 Maximum output value unsigned int. Sets maximum value of output signal expressed as a percentage 60—100 100 35 Active mode light level unsigned int The ambient light level above which 'Active' is indicated in input register 42 0—32.000 default: 100 100 = 100 lux 36 Standby mode light level unsigned int The ambient light level below which 'Standby' is indicated in input register 42 0—32.000 default: 10 10 = 10 lux 37—39 Reserved, return 0 40 CO2 module self calibration unsigned int Enables or disables the CO2 module self calibration technique. If enabled it is advisable that the CO2 concentration drops to outside level (400 ppm) in a 7 day period. 0—1 default: 1 0 = Disabled 1 = Enabled 41—44 Reserved, return 0 45 Minimum output value unsigned int Set minimum value of output signal in percentage 0—40 default: 0 20 = 20 % 46 Maximum output value unsigned int Set maximum value of output signal in percentage 60—100 default: 100 60 = 60 % RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER

MIW-RMFPM-2R-EN-000 - 28 / 05 / 2019

11 - 11 back to the table of contents HOLDING REGISTERS Data type Description Data Values 47—78 Reserved, return 0 79 LED indication unsigned int LED indication related to one of the parameters 1—3 default: 1 1= Temperature 2 = rH 3 = CO2 80 LED intensity / brightness unsigned int LED intensity (incrementing with step of 10 %) 0—10 default: 5 0 = OFF 1 = 10 % 10 = 100 % If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf TRANSPORT AND STORAGE Avoid shocks and extreme conditions; stock in original packing. WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data. MAINTENANCE In normal conditions this product is maintenance-free. If soiled, clean with a dry or damp cloth. In case of heavy pollution, clean with a non‑aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry. RMFPM-2R MULTIFUNCTIONAL ROOM CONTROLLER