Prefect Control PRE3206 Installation Instructions
Text of the manual
Prefect Control Ltd Unit 2, Church Field Business Park, Church Field Road, Sudbury, Suffolk, CO10 2YF
Tel: 01787 320 604 Fax: 0845 450 3020 Email: [email protected] Website: www.prefectcontrols.com
Due to our policy of continuous improvement, we reserve the right to change specifications without notice
PRE3206 IP66 Photocell
Specification:
SUPPLY VOLTAGE: 220-240 Volts AC 50 Hz
TIME OUT PERIOD: Adjustable 1 hour to 16 hours or AUTO OFF.
LIGHT LEVEL: Adjustment 10 LUX to1000 LUX approximately.
TERMINAL CAPACITY: 2.5mm2
IP RATING: IP 66
MATERIAL: Polystyrene
TYPE: Class 2
TEMPERATURE: -10°C to 35°C
CONFORMITY: EMC-89/336/EEC
Operation:
The PRE3206 twilight switch will turn artificial lighting on when
the ambient light falls below a preset level.
The artificial lighting will then be turned off either when the
ambient light exceeds the preset level (auto off) or after a preset
time delay (timed off).
For example, in the auto off mode the PRE3206 can be used
to switch external security lights on at dusk and automatically
switch them off again at dawn.
In the timed off mode display or sign lighting can be set to
turn on when it gets dark and stay on only for a set time period.
An integral 2 minute time delay prevents nuisance switching
caused by, for example, car headlights or dark clouds.
The unit has a highly accurate adjustable photocell; a selectable
time delay; adjustable switching differential and is mounted in a
vandal resistant IP66 enclosure.
1. Make sure the load is connected and in working order.
2. Isolate the mains supply to the circuit at the main consumer unit.
3. Connect the controller via the terminal block. Live supply to the
L terminal, Neutral to the N terminal.
4. For direct switching applications link L to COM and take the
output from the NO terminal.
5. Set the TIME thumbwheel to AUTO OFF by turning fully
anticlockwise
6. Set the LUX thumbwheel to LATE by turning fully clockwise.
7. Set the DIFF (differential) thumbwheel half way.
8. Power the unit up.
9. The lights will not come on until the ambient light level is very low.
10. Adjust the LUX level and differential using the guide overleaf.
11. Finally set the TIME thumbwheel to AUTO OFF or the desired
time setting.
WARNING! This device works at mains potential. Be sure to take
care when working with electricity.
Installation Instructions:
79
95
95
79
39
15
Prefect Control Ltd Unit 2, Church Field Business Park, Church Field Road, Sudbury, Suffolk, CO10 2YF
Tel: 01787 320 604 Fax: 0845 450 3020 Email: [email protected] Website: www.prefectcontrols.com
Due to our policy of continuous improvement, we reserve the right to change specifications without notice
Wire the PRE3206 product as in the diagram. The unit has a
voltage free changeover output which can be used to switch,
say, a BMS or lighting control system as well as switching a
load directly.
To switch a load directly link the L and COM terminals and take
the output from the NO terminal.
•�
Where�possible�site�the�sensor�as�high�as�possible�on�a�north�
facing vertical surface
•�
Avoid�locating�the�PRE3206�in�direct�sight�of�the�light�that�it�
is controlling.
•�
Ensure�that�all�cable�entry�to�the�enclosure�is�via�suitable�
cable glands and seal with silicone sealant where appropriate.
•�
If�it�is�necessary�to�screw�through�the�rear�of�the�enclosure�
ensure that any holes are covered with the caps provided and
sealed with silicone sealant where appropriate.
ADJUSTING THE LUX LEVEL
1. The best time to set the LUX level is when the unit is just
required to turn on.
2. Leave the TIME and DIFF thumbwheels set as above.
3. Turn the LUX thumbwheel very slowly anticlockwise towards
the EARLY position until the lights come on.
4. There is a 2 minute time delay to prevent nuisance switching.
This is automatically disabled whenever the LUX thumbwheel
is turned, and then re-instated automatically after a further
2 minutes.
5. Turning the LUX thumbwheel to EARLY switches the unit earlier
in the day, i.e. when ambient conditions are lighter. Turning
to LATE switches the unit later in the day, i.e. when ambient
conditions are darker.
ADJUSTING THE DIFFERENTIAL
1. After the unit has turned on, the differential is used to determine
at what level of measured light to switch off again. It is only
relevant in AUTO OFF mode.
2. If the differential is set to minimum the unit will turn off when
the measured light is only a tiny bit greater than the level at
which it turned on.
3. If the differential is set to maximum the unit will turn off then
the measured light is much greater than the level at which it
turned on.
4. If, say, the unit is set to turn on at dusk, set the differential
lower (anticlockwise) if you want the lights to turn off again
early in the morning and set the differential higher (clockwise)
if you want the lights to turn off again when it is much lighter.
5. The differential is also useful if the unit can see the lights
which it is controlling. In this case increasing the differential
will prevent cycling of the lights.
Installation Instructions:
Wiring:
LUX
ADJUSTMENT
LIVE IN
NEUTRAL
CIRCUIT PROTECTION
(IF REQUIRED)
L
N
DIFF
TIME
LUX
COM NC
NO
TIMING
ADJUSTMENT
DIFFERENTIAL
ADJUSTMENT
EARLY
LATE
LUX
AUTO
OFF
16 HRS
TIME
1 HR
TIMED
OFF
MIN
MAX
DIFF
Thumbwheel Settings