RF200 system planning
4
Readers
5
Antennas
6
Transponder
7
System integration
8
System diagnostics
9
Appendix
A
Division Process Industries and Drives
Postfach 48 48
90026 NÜRNBERG
GERMANY
J31069-D0227-U001-A8-7618
Ⓟ 07/2015 Subject to change
Copyright © Siemens AG 2010 - 2015.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5
Table of contents
1
Introduction ........................................................................................................................................... 15
1.1
Abbreviations and naming conventions .................................................................................. 16
2
Safety notes .......................................................................................................................................... 17
3
System overview ................................................................................................................................... 19
3.1
RFID components and their function ...................................................................................... 20
3.2
Overview of transponders ....................................................................................................... 23
4
RF200 system planning......................................................................................................................... 25
4.1
Fundamentals of application planning .................................................................................... 25
4.1.1
Selection criteria for SIMATIC RF200 components ................................................................ 25
4.1.2
Transmission window and read/write distance ....................................................................... 25
4.1.3
Width of the transmission window .......................................................................................... 28
4.1.4
Impact of secondary fields ...................................................................................................... 29
4.1.5
Permissible directions of motion of the transponder ............................................................... 32
4.1.6
Operation in static and dynamic mode ................................................................................... 33
4.1.7
Dwell time of the transponder ................................................................................................. 34
4.1.8
Communication between communication module, reader and transponder .......................... 35
4.2
Field data of transponders and readers .................................................................................. 36
4.2.1
Field data ................................................................................................................................ 37
4.2.2
Minimum clearances ............................................................................................................... 44
4.3
Installation guidelines.............................................................................................................. 47
4.3.1
Overview ................................................................................................................................. 47
4.3.2
Reduction of interference due to metal ................................................................................... 47
4.3.3
Effects of metal on different transponders and readers .......................................................... 49
4.3.4
Impact of metal on the transmission window .......................................................................... 50
4.3.4.1
RF210R ................................................................................................................................... 51
4.3.4.2
RF220R ................................................................................................................................... 54
4.3.4.3
RF240R ................................................................................................................................... 56
4.3.4.4
RF250R ................................................................................................................................... 59
4.3.4.5
RF260R ................................................................................................................................... 65
4.3.4.6
RF290R ................................................................................................................................... 67
4.3.5
Installation and connection of 2 to 6 antennas with one RF290R reader ............................... 71
4.3.5.1
Installation options with the antenna splitter (2-4 antennas) .................................................. 72
4.3.5.2
Antenna installation ................................................................................................................. 75
4.3.5.3
Installation options with the antenna multiplexer (2-6 antennas) ........................................... 79
4.3.6
Chemical resistance of the transponders ............................................................................... 80
4.3.6.1
Overview of the transponders and their housing materials .................................................... 80
4.3.6.2
Polyphenylene sulfide (PPS) .................................................................................................. 81
4.3.6.3
Polycarbonate (PC) ................................................................................................................. 82
4.3.6.4
Polyvinyl chloride (PVC) ......................................................................................................... 83
4.3.6.5
Epoxy resin ............................................................................................................................. 83
4.3.6.6
PA6.6 GF30 ............................................................................................................................ 86
Table of contents
SIMATIC RF200
6
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.4
Further information ................................................................................................................. 87
5
Readers ................................................................................................................................................ 89
5.1
SIMATIC RF210R .................................................................................................................. 90
5.1.1
Features ................................................................................................................................. 90
5.1.2
RF210R ordering data ........................................................................................................... 90
5.1.3
Pin assignment RF210R with RS422 interface ...................................................................... 91
5.1.4
Display elements of the RF210R reader ................................................................................ 91
5.1.5
Minimum distance between RF210R readers ........................................................................ 92
5.1.6
Technical specifications of the RF210R reader ..................................................................... 93
5.1.7
Approvals ............................................................................................................................... 94
5.1.8
Dimension drawing ................................................................................................................ 95
5.2
SIMATIC RF210M .................................................................................................................. 96
5.2.1
Features ................................................................................................................................. 96
5.2.2
Ordering data RF210M .......................................................................................................... 96
5.2.3
Installing the RF210M reader ................................................................................................. 97
5.2.4
Pin assignment RF210M with RS-422 interface .................................................................... 97
5.2.5
Display elements of the RF210M reader ............................................................................... 98
5.2.6
Technical specifications of the RF210M reader ..................................................................... 98
5.2.7
Approvals ............................................................................................................................. 100
5.2.8
Dimension drawing .............................................................................................................. 101
5.3
SIMATIC RF220R ................................................................................................................ 102
5.3.1
Features ............................................................................................................................... 102
5.3.2
RF220R ordering data ......................................................................................................... 102
5.3.3
RF220R pin assignment with RS422 interface .................................................................... 103
5.3.4
Display elements of the RF220R reader .............................................................................. 103
5.3.5
Minimum distance between RF220R readers ...................................................................... 104
5.3.6
Technical specifications of the RF220R reader ................................................................... 105
5.3.7
Approvals ............................................................................................................................. 106
5.3.8
Dimension drawing .............................................................................................................. 107
5.4
SIMATIC RF240R ................................................................................................................ 108
5.4.1
Features ............................................................................................................................... 108
5.4.2
RF240R ordering data ......................................................................................................... 108
5.4.3
Pin assignment RF240R ...................................................................................................... 109
5.4.4
Display elements of the RF240R reader .............................................................................. 109
5.4.5
Minimum distance between several RF240R readers ......................................................... 110
5.4.6
Technical specifications of the RF240R reader ................................................................... 111
5.4.7
Approvals ............................................................................................................................. 113
5.4.8
Dimension drawing .............................................................................................................. 114
5.5
SIMATIC RF250R ................................................................................................................ 115
5.5.1
Features ............................................................................................................................... 115
5.5.2
Ordering data RF250R ......................................................................................................... 115
5.5.3
Pin assignment RF250R ...................................................................................................... 116
5.5.4
Display elements of the RF250R reader .............................................................................. 116
5.5.5
Technical specifications of the RF250R reader ................................................................... 117
5.5.6
Approvals ............................................................................................................................. 118
5.5.7
Dimension drawing .............................................................................................................. 120
5.6
SIMATIC RF260R ................................................................................................................ 121
5.6.1
Features ............................................................................................................................... 121
5.6.2
Ordering data for RF260R ................................................................................................... 121
Table of contents
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
7
5.6.3
Pin assignment RF260R ....................................................................................................... 122
5.6.4
Display elements of the RF260R reader ............................................................................... 122
5.6.5
Minimum distance between several RF260R ....................................................................... 123
5.6.6
Technical data of the RF260R reader................................................................................... 124
5.6.7
Approvals .............................................................................................................................. 126
5.6.8
Dimension drawing ............................................................................................................... 127
5.7
SIMATIC RF290R ................................................................................................................. 128
5.7.1
Features ................................................................................................................................ 128
5.7.2
Ordering data RF290R.......................................................................................................... 129
5.7.3
Pin assignment RF290R ....................................................................................................... 130
5.7.4
Display elements of the RF290R reader ............................................................................... 132
5.7.5
Installing the RF290R reader ................................................................................................ 133
5.7.5.1
Wall mounting ....................................................................................................................... 133
5.7.5.2
Installing on the S7-300 standard rail ................................................................................... 134
5.7.5.3
Installation on a DIN rail ........................................................................................................ 134
5.7.6
Technical specifications of the RF290R reader .................................................................... 136
5.7.7
Approvals .............................................................................................................................. 137
5.7.8
Note on the use of the RF290R as a replacement for SLG D10 / SLG D10S ...................... 139
5.7.9
Dimension drawing ............................................................................................................... 140
6
Antennas ............................................................................................................................................ 141
6.1
ANT 3 .................................................................................................................................... 142
6.1.1
Features ................................................................................................................................ 142
6.1.2
Ordering data ........................................................................................................................ 142
6.1.3
Mounting on/in metal............................................................................................................. 143
6.1.4
Operating / limit distances .................................................................................................... 144
6.1.5
Minimum spacing .................................................................................................................. 144
6.1.6
Technical data ....................................................................................................................... 146
6.1.7
Dimension drawing ............................................................................................................... 147
6.2
ANT 8 .................................................................................................................................... 148
6.2.1
Features ................................................................................................................................ 148
6.2.2
Ordering data ........................................................................................................................ 148
6.2.3
Transmission window............................................................................................................ 149
6.2.4
Flush-mounted in metal ........................................................................................................ 149
6.2.5
Minimum spacing .................................................................................................................. 150
6.2.6
Technical data ....................................................................................................................... 151
6.2.7
Dimension drawing ............................................................................................................... 152
6.3
ANT 12 .................................................................................................................................. 153
6.3.1
Features ................................................................................................................................ 153
6.3.2
Ordering data ........................................................................................................................ 153
6.3.3
Transmission window............................................................................................................ 154
6.3.4
Flush-mounted in metal ........................................................................................................ 154
6.3.5
Minimum spacing .................................................................................................................. 155
6.3.6
Technical data ....................................................................................................................... 156
6.3.7
Dimension drawing ............................................................................................................... 157
6.4
ANT 18 .................................................................................................................................. 158
6.4.1
Features ................................................................................................................................ 158
6.4.2
Ordering data ........................................................................................................................ 158
6.4.3
Transmission window............................................................................................................ 159
6.4.4
Flush-mounted in metal ........................................................................................................ 159
Table of contents
SIMATIC RF200
8
System Manual, 07/2015, J31069-D0227-U001-A9-7618
6.4.5
Minimum spacing ................................................................................................................. 160
6.4.6
Technical data ...................................................................................................................... 161
6.4.7
Dimension drawing .............................................................................................................. 162
6.5
ANT 30 ................................................................................................................................. 163
6.5.1
Features ............................................................................................................................... 163
6.5.2
Ordering data ....................................................................................................................... 163
6.5.3
Transmission window ........................................................................................................... 164
6.5.4
Flush-mounted in metal ....................................................................................................... 165
6.5.5
Minimum spacing ................................................................................................................. 165
6.5.6
Technical data ...................................................................................................................... 167
6.5.7
Dimension drawing .............................................................................................................. 168
6.6
ANT D5 ................................................................................................................................ 169
6.6.1
Features ............................................................................................................................... 169
6.6.2
Ordering data ....................................................................................................................... 169
6.6.3
Transmission window ........................................................................................................... 170
6.6.4
Flush-mounted in metal ....................................................................................................... 171
6.6.5
Minimum spacing ................................................................................................................. 171
6.6.6
Technical data ...................................................................................................................... 173
6.6.7
Dimension drawing .............................................................................................................. 174
6.7
ANT D6 ................................................................................................................................ 175
6.7.1
Features ............................................................................................................................... 175
6.7.2
Ordering data ....................................................................................................................... 175
6.7.3
Transmission window ........................................................................................................... 176
6.7.4
Metal-free area ..................................................................................................................... 177
6.7.5
Minimum spacing ................................................................................................................. 177
6.7.6
Technical data ...................................................................................................................... 178
6.7.7
Dimensional diagram ........................................................................................................... 179
6.8
ANT D10 .............................................................................................................................. 180
6.8.1
Features ............................................................................................................................... 180
6.8.2
Ordering data ....................................................................................................................... 180
6.8.3
Transmission window ........................................................................................................... 181
6.8.4
Metal-free area ..................................................................................................................... 182
6.8.5
Minimum spacing ................................................................................................................. 183
6.8.6
Technical data ...................................................................................................................... 184
6.8.7
Dimensional diagram ........................................................................................................... 185
7
Transponder ........................................................................................................................................ 187
7.1
Memory configuration of ISO the transponders ................................................................... 187
7.2
MDS D100 ............................................................................................................................ 188
7.2.1
Characteristics ..................................................................................................................... 188
7.2.2
Ordering data ....................................................................................................................... 189
7.2.3
Metal-free area ..................................................................................................................... 189
7.2.4
Technical data ...................................................................................................................... 191
7.2.5
Dimension drawing .............................................................................................................. 192
7.3
MDS D117 ............................................................................................................................ 193
7.3.1
Features ............................................................................................................................... 193
7.3.2
Ordering data ....................................................................................................................... 193
7.3.3
Mounting in metal ................................................................................................................. 193
7.3.4
Technical specifications ....................................................................................................... 194
Table of contents
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
9
7.3.5
Dimension drawing ............................................................................................................... 195
7.4
MDS D124 ............................................................................................................................ 196
7.4.1
Characteristics ...................................................................................................................... 196
7.4.2
Ordering data ........................................................................................................................ 196
7.4.3
Mounting on metal ................................................................................................................ 197
7.4.4
Technical specifications ........................................................................................................ 198
7.4.5
Use of the MDS D124 in hazardous area ............................................................................. 199
7.4.6
Dimension drawing ............................................................................................................... 201
7.5
MDS D126 ............................................................................................................................ 201
7.5.1
Characteristics ...................................................................................................................... 201
7.5.2
Ordering data ........................................................................................................................ 202
7.5.3
Technical specifications ........................................................................................................ 202
7.5.4
Dimension drawing ............................................................................................................... 203
7.6
MDS D127 ............................................................................................................................ 204
7.6.1
Features ................................................................................................................................ 204
7.6.2
Ordering data ........................................................................................................................ 204
7.6.3
Mounting in metal .................................................................................................................. 205
7.6.4
Technical specifications ........................................................................................................ 206
7.6.5
Dimension drawing ............................................................................................................... 207
7.7
MDS D139 ............................................................................................................................ 208
7.7.1
Characteristics ...................................................................................................................... 208
7.7.2
Ordering data ........................................................................................................................ 208
7.7.3
Metal-free area ...................................................................................................................... 209
7.7.4
Mounting in metal .................................................................................................................. 210
7.7.5
Cleaning the transponder ..................................................................................................... 210
7.7.6
Technical specifications ........................................................................................................ 211
7.7.7
Use of the MDS D139 in hazardous areas ........................................................................... 212
7.7.8
Dimension drawings .............................................................................................................. 214
7.8
MDS D160 ............................................................................................................................ 215
7.8.1
Characteristics ...................................................................................................................... 215
7.8.2
Ordering data ........................................................................................................................ 215
7.8.3
Mounting on metal ................................................................................................................ 216
7.8.4
Technical specifications ........................................................................................................ 217
7.8.5
Dimension drawings .............................................................................................................. 219
7.9
MDS D165 ............................................................................................................................ 220
7.9.1
Features ................................................................................................................................ 220
7.9.2
Ordering data ........................................................................................................................ 220
7.9.3
Technical data ....................................................................................................................... 221
7.9.4
Dimension drawing ............................................................................................................... 222
7.10
MDS D200 ............................................................................................................................ 223
7.10.1
Features ................................................................................................................................ 223
7.10.2
Ordering data ........................................................................................................................ 223
7.10.3
Mounting on metal ................................................................................................................ 224
7.10.4
Technical data ....................................................................................................................... 225
7.10.5
Dimension drawing ............................................................................................................... 227
7.11
MDS D261 ............................................................................................................................ 227
7.11.1
Features ................................................................................................................................ 227
7.11.2
Ordering data ........................................................................................................................ 227
Table of contents
SIMATIC RF200
10
System Manual, 07/2015, J31069-D0227-U001-A9-7618
7.11.3
Technical data ...................................................................................................................... 228
7.11.4
Dimension drawing .............................................................................................................. 229
7.12
MDS D324 ............................................................................................................................ 230
7.12.1
Characteristics ..................................................................................................................... 230
7.12.2
Ordering data ....................................................................................................................... 230
7.12.3
Metal-free area ..................................................................................................................... 231
7.12.4
Technical specifications ....................................................................................................... 232
7.12.5
Dimension drawing .............................................................................................................. 233
7.13
MDS D339 ............................................................................................................................ 234
7.13.1
Characteristics ..................................................................................................................... 234
7.13.2
Ordering data ....................................................................................................................... 234
7.13.3
Mounting on metal ............................................................................................................... 235
7.13.4
Mounting in metal ................................................................................................................. 236
7.13.5
Cleaning the transponder ..................................................................................................... 236
7.13.6
Technical specifications ....................................................................................................... 237
7.13.7
Use of the MDS D339 in hazardous areas .......................................................................... 238
7.13.8
Dimensional drawing ............................................................................................................ 240
7.14
MDS D400 ............................................................................................................................ 241
7.14.1
Features ............................................................................................................................... 241
7.14.2
Ordering data ....................................................................................................................... 241
7.14.3
Mounting on metal ............................................................................................................... 242
7.14.4
Technical specifications ....................................................................................................... 243
7.14.5
Dimension drawing .............................................................................................................. 245
7.15
MDS D421 ............................................................................................................................ 246
7.15.1
Characteristics ..................................................................................................................... 246
7.15.2
Ordering data ....................................................................................................................... 246
7.15.3
Mounting on metal ............................................................................................................... 247
7.15.4
Technical specifications ....................................................................................................... 249
7.15.5
Dimension drawing .............................................................................................................. 250
7.16
MDS D422 ............................................................................................................................ 251
7.16.1
Characteristics ..................................................................................................................... 251
7.16.2
Ordering data ....................................................................................................................... 251
7.16.3
Mounting in metal ................................................................................................................. 251
7.16.4
Technical specifications ....................................................................................................... 252
7.16.5
Dimension drawing .............................................................................................................. 253
7.17
MDS D423 ............................................................................................................................ 254
7.17.1
Characteristics ..................................................................................................................... 254
7.17.2
Ordering data ....................................................................................................................... 254
7.17.3
Mounting on metal ............................................................................................................... 255
7.17.4
Technical specifications ....................................................................................................... 256
7.17.5
Dimensional drawing ............................................................................................................ 258
7.18
MDS D424 ............................................................................................................................ 258
7.18.1
Characteristics ..................................................................................................................... 258
7.18.2
Ordering data ....................................................................................................................... 259
7.18.3
Mounting on metal ............................................................................................................... 259
7.18.4
Technical specifications ....................................................................................................... 260
7.18.5
Dimension drawing .............................................................................................................. 262
Table of contents
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
11
7.19
MDS D425 ............................................................................................................................ 262
7.19.1
Characteristics ...................................................................................................................... 262
7.19.2
Ordering data ........................................................................................................................ 263
7.19.3
Application example of MDS D425 ....................................................................................... 263
7.19.4
Technical specifications ........................................................................................................ 264
7.19.5
Dimension drawing ............................................................................................................... 265
7.20
MDS D426 ............................................................................................................................ 266
7.20.1
Characteristics ...................................................................................................................... 266
7.20.2
Ordering data ........................................................................................................................ 266
7.20.3
Technical specifications ........................................................................................................ 267
7.20.4
Dimension drawing ............................................................................................................... 268
7.21
MDS D428 ............................................................................................................................ 269
7.21.1
Characteristics ...................................................................................................................... 269
7.21.2
Ordering data ........................................................................................................................ 269
7.21.3
Application example .............................................................................................................. 270
7.21.4
Technical specifications ........................................................................................................ 270
7.21.5
Dimension drawing ............................................................................................................... 272
7.22
MDS D460 ............................................................................................................................ 272
7.22.1
Characteristics ...................................................................................................................... 272
7.22.2
Ordering data ........................................................................................................................ 273
7.22.3
Mounting on metal ................................................................................................................ 273
7.22.4
Technical specifications ........................................................................................................ 274
7.22.5
Dimension drawings .............................................................................................................. 275
7.23
MDS D521 ............................................................................................................................ 276
7.23.1
Characteristics ...................................................................................................................... 276
7.23.2
Ordering data ........................................................................................................................ 276
7.23.3
Mounting on metal ................................................................................................................ 276
7.23.4
Technical specifications ........................................................................................................ 279
7.23.5
Dimension drawing ............................................................................................................... 280
7.24
MDS D522 ............................................................................................................................ 281
7.24.1
Characteristics ...................................................................................................................... 281
7.24.2
Ordering data ........................................................................................................................ 281
7.24.3
Mounting in metal .................................................................................................................. 281
7.24.4
Technical specifications ........................................................................................................ 282
7.24.5
Dimension drawing ............................................................................................................... 283
7.25
MDS D522 special variant .................................................................................................... 284
7.25.1
Characteristics ...................................................................................................................... 284
7.25.2
Ordering data ........................................................................................................................ 284
7.25.3
Mounting in metal .................................................................................................................. 285
7.25.4
Installation instructions.......................................................................................................... 286
7.25.5
Technical specifications ........................................................................................................ 287
7.25.6
Dimensional drawing............................................................................................................. 288
7.26
MDS D524 ............................................................................................................................ 289
7.26.1
Characteristics ...................................................................................................................... 289
7.26.2
Ordering data ........................................................................................................................ 289
7.26.3
Mounting on metal ................................................................................................................ 290
7.26.4
Technical specifications ........................................................................................................ 291
7.26.5
Dimension drawing ............................................................................................................... 292
Table of contents
SIMATIC RF200
12
System Manual, 07/2015, J31069-D0227-U001-A9-7618
7.27
MDS D526 ............................................................................................................................ 293
7.27.1
Characteristics ..................................................................................................................... 293
7.27.2
Ordering data ....................................................................................................................... 293
7.27.3
Technical specifications ....................................................................................................... 294
7.27.4
Dimension drawing .............................................................................................................. 295
7.28
MDS D528 ............................................................................................................................ 296
7.28.1
Characteristics ..................................................................................................................... 296
7.28.2
Ordering data ....................................................................................................................... 296
7.28.3
Application example ............................................................................................................. 297
7.28.4
Technical specifications ....................................................................................................... 297
7.28.5
Dimension drawing .............................................................................................................. 299
8
System integration ............................................................................................................................... 301
9
System diagnostics .............................................................................................................................. 305
9.1
Error codes of the RF200 readers ....................................................................................... 305
9.2
Diagnostic functions ............................................................................................................. 306
9.2.1
Reader diagnostics with SLG STATUS ............................................................................... 306
9.2.2
Transponder diagnostics with MDS STATUS ...................................................................... 308
A
Appendix ............................................................................................................................................. 309
A.1
Certificates and approvals ................................................................................................... 309
A.2
Accessories .......................................................................................................................... 311
A.2.1
Antenna splitter .................................................................................................................... 311
A.2.2
Antenna multiplexer SIMATIC RF260X ............................................................................... 313
A.2.2.1
Characteristics ..................................................................................................................... 313
A.2.2.2
Ordering data ....................................................................................................................... 313
A.2.2.3
Description ........................................................................................................................... 314
A.2.2.4
Principle of operation ........................................................................................................... 314
A.2.2.5
Connectors ........................................................................................................................... 315
A.2.2.6
Configuration ........................................................................................................................ 316
A.2.2.7
Parameterization .................................................................................................................. 317
A.2.2.8
RF260X commands ............................................................................................................. 318
A.2.2.9
Technical specifications ....................................................................................................... 319
A.2.2.10
Dimensional drawing ............................................................................................................ 320
A.2.3
Wide-range power supply unit for SIMATIC RF systems .................................................... 321
A.2.3.1
Features ............................................................................................................................... 321
A.2.3.2
Scope of supply.................................................................................................................... 322
A.2.3.3
Ordering data ....................................................................................................................... 322
A.2.3.4
Safety Information ................................................................................................................ 322
A.2.3.5
Connecting ........................................................................................................................... 323
A.2.3.6
Technical specifications ....................................................................................................... 324
A.2.3.7
Pin assignment of DC outputs and mains connection ......................................................... 326
A.2.3.8
Dimension drawing .............................................................................................................. 327
A.2.3.9
Certificates and approvals ................................................................................................... 328
A.2.4
Transponder holders ............................................................................................................ 329
A.3
Connecting cable ................................................................................................................. 335
A.3.1
Reader RF2xxR (RS-422) with ASM 456 / RF160C / RF170C / RF180C / RF182C .......... 335
A.3.2
Reader RF2xxR (RS-422) with ASM 475 ............................................................................ 337
A.3.3
Reader RF2xxR (RS-422) with RF120C .............................................................................. 338
A.3.4
Reader RF240R/RF260R/RF290R (RS232) with PC .......................................................... 338
Table of contents
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
13
A.4
Ordering data ........................................................................................................................ 340
A.5
Service & Support ................................................................................................................. 350
Glossary ............................................................................................................................................. 353
Index................................................................................................................................................... 359
System Manual, 07/2015, J31069-D0227-U001-A9-7618
15
Introduction
1
Introduction
SIMATIC RF200 is a compact RFID system in the SIMATIC RFID product family. The
product range comprises cost-efficient RF readers that are ideal for use in small assembly
lines or in intralogistics. SIMATIC RF200 RFID readers only support the RFID standard ISO
15693 and are therefore ideal for operation with the extensive range of ISO 15693
transponders.
The readers of the RF200 product family are available with the following interfaces:
● RS-422 for connecting to the communications modules
● RS-232 with a simple ASCII protocol for connection to PCs and third-party controllers
● IO-Link for connection to IO Link masters from Siemens and third-party controllers
Readers with an internal antenna have a particularly compact design
(RF210R/RF220R/RF240R/RF260R). RF250R and RF290R are designed for operation with
external antennas either to achieve longer distances or larger field sizes (RF290R with ANT
D5/D6/D10) or to allow installation where there is very little space (RF250R with ANT
3/8/12/18/30).
Scope of validity of this document
This documentation is valid for all variants of the SIMATIC RF200 system and describes the
devices shipped as of July 2015.
Registered trademarks
SIMATIC ®, SIMATIC RF ®, MOBY ®, RF MANAGER ® and SIMATIC Sensors ® are registered
trademarks of Siemens AG.
Further information
For additional information, refer to the manuals:
● Function manual "Ident profile and Ident blocks"
(https://support.industry.siemens.com/cs/us/en/view/106368029)
● Function manual "FB 45"
(https://support.industry.siemens.com/cs/ww/en/view/21738808)
● Operating instructions "RF200 IO-Link"
(https://support.industry.siemens.com/cs/ww/en/view/60641859)
● System manual "MOBY D"
(https://support.industry.siemens.com/cs/ww/en/view/13628689)
1.1 Abbreviations and naming conventions
SIMATIC RF200
16
System Manual, 07/2015, J31069-D0227-U001-A9-7618
● Operating instructions "RF310M"
(https://support.industry.siemens.com/cs/us/en/view/51812642)
● Product information "RF200 command set"
(https://support.industry.siemens.com/cs/us/en/view/44864850)
History
The following issues of the SIMATIC RF200 system manual have been published:
Output
Note
03/2011
First edition
05/2011
Expansion of the documentation with the addition of the device variant RF260R with
RS-232 interface
09/2011
Expansion of the documentation with the device variant RF240R
03/2013
Expansion of the documentation with the device variant RF290R
09/2013
Expansion of the documentation by the following:
•
the device variant RF250R
•
the device variants RF240R and RF260R with ASCII interface
•
Antennas ANT 8, ANT 12, ANT 18 and ANT 30
•
Transponders
07/2015
Expansion of the documentation by the following:
•
ANT 3 antennas
•
MDS D5xx transponder
•
Mobile reader RF210R
1.1
Abbreviations and naming conventions
The following terms/abbreviations are used synonymously in this document:
Write/read device (SLG)
Readers
Mobile data storage unit (MDS)
Transponder, tag
Interface module (ASM)
Communications module (CM)
System Manual, 07/2015, J31069-D0227-U001-A9-7618
17
Safety notes
2
SIMATIC RFID products comply with the salient safety specifications to IEC, VDE, EN, UL
and CSA. If you have questions about the validity of the installation in the planned
environment, please contact your service representative.
NOTICE
Alterations to the devices are not permitted.
Failure to observe this requirement shall constitute a revocation of the radio equipment
approval, CE approval and manufacturer's warranty.
Repairs
Repairs may only be carried out by authorized qualified personnel.
WARNING
Unauthorized opening of and improper repairs to the device may result in substantial
damage to equipment or risk of personal injury to the user.
System expansion
Only install system expansion devices designed for this device. If you install other upgrades,
you may damage the system or violate the safety requirements and regulations for radio
frequency interference suppression. Contact your technical support team or your sales outlet
to find out which system upgrades are suitable for installation.
NOTICE
If you cause system defects by installing or exchanging system expansion devices, the
warranty becomes void.
System Manual, 07/2015, J31069-D0227-U001-A9-7618
19
System overview
3
SIMATIC RF200 is an inductive identification system that is compatible with the ISO 15693
standard and was specially designed for use in industrial production for the control and
optimization of material flows.
In contrast to SIMATIC RF300, SIMATIC RF200 is intended for RFID applications where
performance requirements are not very high, for example with regard to data volume,
transfer rate or diagnostics options. SIMATIC RF200 is characterized by particularly
favorable prices.
3.1 RFID components and their function
SIMATIC RF200
20
System Manual, 07/2015, J31069-D0227-U001-A9-7618
3.1
RFID components and their function
RF200 system components
Figure 3-1
RF200 system overview
3.1 RFID components and their function
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
21
Table 3- 1
Possible reader-transponder combinations
Tran-
sponder
RF210R/
RF210M
RF220R RF240R
RF250R
with
RF260R
RF290R 4)
RF310M
ANT 3 ANT 8 ANT 12 ANT 18 ANT 30
MDS
D100
--
○
✓
○
--
--
--
○
✓
✓
✓
MDS
D117
○
--
--
--
✓
✓
--
--
--
--
✓ 6)
MDS
D124
✓
✓
✓
✓
--
--
✓
✓
✓
✓
✓
MDS
D126
--
✓
✓
✓
--
--
--
✓
✓
✓
✓
MDS
D127
✓
--
--
--
✓
✓
--
--
--
--
✓ 6)
MDS
D139 1)
--
○
○
○
--
--
--
○
✓
✓
✓
MDS
D160 2)
✓
✓
✓
✓
--
✓
✓
✓
✓
✓
✓
MDS
D165
--
○
✓
○
--
--
--
○
✓
✓
✓
MDS
D200
--
○
✓
○
--
--
--
○
✓
✓
✓
MDS
D261
--
○
✓
○
--
--
--
○
✓
✓
✓
MDS
D324
✓
✓
✓
✓
--
○
✓
✓
✓
✓
✓
MDS
D339
--
○
○
○
--
--
--
○
✓
✓
✓
MDS
D400
--
--
✓
○
--
--
--
○
✓
✓
✓
MDS
D421
✓
○
--
--
✓
✓
✓
--
--
--
✓ 6)
MDS
D422
✓
✓
✓
✓
--
✓
✓
✓
--
--
✓ 6)
MDS
D423
✓
✓
✓
✓
--
--
✓
✓
✓
--
✓
MDS
D424
✓
✓
✓
✓
--
--
✓
✓
✓
✓
✓
MDS
D425
✓
✓
✓
✓
--
✓
✓
✓
--
--
✓
MDS
D426
--
✓
✓
✓
--
--
--
✓
✓
✓
✓
MDS
D428
✓
✓
✓
✓
--
✓
✓
✓
✓
--
✓
MDS
D460
✓
✓
✓
✓
--
✓
✓
✓
✓
○ / ✓ 5)
✓
MDS
D521
✓
○
--
--
✓
✓
✓
--
--
--
✓ 6)
3.1 RFID components and their function
SIMATIC RF200
22
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Tran-
sponder
RF210R/
RF210M
RF220R RF240R
RF250R
with
RF260R
RF290R 4)
RF310M
ANT 3 ANT 8 ANT 12 ANT 18 ANT 30
MDS
D522 3)
✓
✓
✓
✓
--
✓
✓
✓
--
--
✓ 6)
MDS
D524
✓
✓
✓
✓
--
--
✓
✓
✓
✓
✓
MDS
D526
--
✓
✓
✓
--
--
--
✓
✓
✓
✓
MDS
D528
✓
✓
✓
✓
--
✓
✓
✓
✓
--
✓
1) only with the article number 6GT2600-0AA10
2) only with the article number 6GT2600-0AB10
3) The transponder MDS D522 special variant has the same compatibility as the transponder MDS D522.
4) in conjunction with ANT D5, D6 or D10
5) combination recommended only in conjunction with ANT D5.
6) only in conjunction with RF310M for external antennas (6GT2803-1AC10)
✓ Combination possible
-- Combination not possible
○ Combination possible, but not recommended
3.2 Overview of transponders
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
23
3.2
Overview of transponders
Overview of typical areas of application of ISO transponders for RF200
Transponder
Area of application
MDS D100
From simple identification such as electronic barcode replacement or supplementation, through ware-
house and distribution logistics, right up to product identification. With this transponder, the maximum
ranges are achieved in combination with the SIMATIC RF260R reader.
MDS D117
Very compact data carrier that can be cemented into objects where precise positioning is necessary. e.g.
tool identification.
MDS D124
Application areas in factory automation (e.g. small paintshops to 180°C).
MDS D126
Compact and rugged ISO transponder; suitable for identification of transport units in production-related
logistics; can also be deployed in harsh conditions.
MDS D127
Very compact data carrier that can be screwed into areas where precise positioning is necessary. e.g. tool
identification.
MDS D139 1)
Applications in production automation with high temperature demands (up to +220 °C).
Typical application areas:
•
Paintshops and their preparatory treatments
•
Primer coat, electrolytic dip area, cataphoresis with the associated drying furnaces
•
Top coat area with drying furnaces
•
Washing areas at temperatures > 85 °C
•
Other applications with higher temperatures
MDS D160 2)
Typical applications are, for example:
•
Rented work clothing
•
Hotel laundry
•
Surgical textiles
•
Hospital clothing
•
Dirt collection mats
•
Clothing for nursing homes/hostels
•
Assembly lines with very small workpiece holders
MDS D165
Smart label (self-adhesive label)
From simple identification such as electronic barcode replacement/supplementation, through warehouse
and distribution logistics, right up to product identification
MDS D200
From simple identification such as electronic barcode replacement/supplementation, through warehouse
and distribution logistics, right up to product identification.
MDS D261
Smart label (self-adhesive label)
The design of the transponder (self-adhesive label) permits a variety of designs in order to ensure opti-
mum dimensioning for the widest variety of applications.
From simple identification such as electronic barcode replacement/supplementation, through warehouse
and distribution logistics, right up to product identification.
MDS D324
Production and distribution logistics as well as in assembly and production lines
MDS D339
Applications in production automation with high temperature demands (up to +220 °C).
For typical areas of application, see "MDS D139".
3.2 Overview of transponders
SIMATIC RF200
24
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
Area of application
MDS D400
Simple identification such as electronic barcode replacement/supplements, from warehouse and distribu-
tion logistics right through to product identification.
MDS D421
The MDS D421 is designed for tool coding according to DIN 69873.
It can be used wherever small data carriers and exact positioning are required, e.g. tool identification,
workpiece holders
MDS D422
Identification of metallic workpiece holders, workpieces or containers
MDS D423
Identification of metallic workpiece holders, workpieces or containers, production automation
MDS D424
Production and distribution logistics as well as in assembly and production lines
MDS D425
Compact and rugged ISO transponder; suitable for screw mounting.
Use in assembly and production lines in the powertrain sector; ideal for mounting on motors, gearboxes,
and workpiece holders
MDS D426
Compact and rugged ISO transponder; suitable for identification of transport units in production-related
logistics; can also be deployed in harsh conditions
MDS D428
Compact and rugged ISO transponder; suitable for screw mounting
Use in assembly and production lines in the powertrain sector
MDS D460
Assembly lines with very small workpiece holders
MDS D521
The MDS D521 is constructed for tool coding according to DIN 69873. It can be used wherever small data
carriers and exact positioning are required, e.g. tool identification, workpiece holders.
MDS D522
Identification of metallic workpiece holders, workpieces or containers
MDS D522
Special vari-
ants
If Identification of metallic workpiece holders or workpieces
MDS D524
Production and distribution logistics as well as in assembly and production lines
MDS D526
Compact and rugged ISO transponder; suitable for identification of transport units in production-related
logistics; can also be deployed in harsh environmental conditions
MDS D528
Compact and rugged ISO transponder; suitable for screw mounting
Use in assembly and production lines in the powertrain sector
1) Only with the MLFB 6GT2600-0AA10
2) Only with the MLFB 6GT2600-0AB10
Overview of the memory sizes of the ISO transponders for RF200
Transponder
Memory size
MDS D1xx
112 bytes of EEPROM
MDS D2xx
256 bytes of EEPROM
MDS D3xx
992 bytes of EEPROM
MDS D4xx
2000 bytes FRAM
MDS D5xx
8192 bytes FRAM
System Manual, 07/2015, J31069-D0227-U001-A9-7618
25
RF200 system planning
4
4.1
Fundamentals of application planning
4.1.1
Selection criteria for SIMATIC RF200 components
Assess your application according to the following criteria, in order to choose the right
SIMATIC RF200 components:
● Static or dynamic data transfer
● Data volume to be transferred
● Speed in case of dynamic transfer
● Ambient conditions such as relative humidity, temperature, chemical impacts, etc.
4.1.2
Transmission window and read/write distance
The reader generates an inductive alternating field. The field is strongest close to the reader;
however, a read/write distance of "zero" between reader and transponder is not
recommended.
The strength of the field decreases in proportion to the distance from the reader. The
distribution of the field depends on the structure and geometry of the antennas in the reader
and transponder
A prerequisite for the function of the transponder is a minimum field strength at the
transponder, which is still barely achieved at distance Sg from the reader.
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
26
System Manual, 07/2015, J31069-D0227-U001-A9-7618
The picture below shows the transmission window of the SIMATIC RF210R and
SIMATIC RF220R readers between transponder and reader:
Sa
Operating distance between transponder and reader
Sg
Limit distance (maximum clear distance between upper surface of the reader and the tran-
sponder, at which the transmission can still function under normal conditions)
L
Diameter of a transmission window
SP
Intersection of the axes of symmetry of the transponder
Figure 4-1
RF210R/RF220R transmission window
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
27
The figure below shows the transmission window of the SIMATIC RF240R and SIMATIC
RF260R readers between transponder and reader:
Sa
Operating distance between transponder and reader
Sg
Limit distance (maximum clear distance between upper surface of the reader and the tran-
sponder, at which the transmission can still function under normal conditions)
L
Length of a transmission window
M
Field centerpoint
Figure 4-2
RF240R/RF260R transmission window
The transponder can be used as soon as the intersection (SP) of the transponder enters the
area of the transmission window.
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
28
System Manual, 07/2015, J31069-D0227-U001-A9-7618
From the diagrams above, it can also be seen that operation is possible within the area
between Sa and Sg. The active operating area reduces as the distance increases, and
shrinks to a single point at distance Sg. Only static mode should thus be used in the area
between Sa and Sg.
4.1.3
Width of the transmission window
Determining the width of the transmission window
The following approximation formula can be used for practical applications:
B:
Width of the transmission window
L:
Length of the transmission window
Tracking tolerances
The width of the transmission window (B) is particularly important for the mechanical tracking
tolerance. The formula for the dwell time is valid without restriction when B is observed.
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
29
4.1.4
Impact of secondary fields
Secondary fields in the range from 0 mm to 30% of the limit distance (Sg) generally always
exist.
They should, however, only be used during configuration in exceptional cases, since the
read/write distances are very limited. Exact details of the secondary field geometry cannot be
given, since these values depend heavily on the operating distance and the application.
When working in dynamic mode, remember that during the transition from the secondary
field to the main field the presence of the tag is lost temporarily. It is therefore advisable to
select a distance > 30 % of Sg.
①
Main field
②
Secondary field
Figure 4-3
Gap in the field resulting from secondary fields
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
30
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Secondary fields without shielding
The following graphic shows typical primary and secondary fields, if no shielding measures
are taken.
①
Main field
②
Secondary field
Figure 4-4
Secondary field without shielding
In this arrangement, the reader can also read tags via the secondary field. Shielding is
required in order to prevent unwanted reading via the secondary field, as shown and
described in the following.
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
31
Secondary fields with shielding
The following graphic shows typical primary and secondary fields, with metal shielding this
time.
The metal shielding prevents the reader from detecting tags via the secondary field.
①
Main field
②
Secondary field
Figure 4-5
Secondary field with shielding
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
32
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.1.5
Permissible directions of motion of the transponder
Detection area and direction of motion of the transponder
The transponder and reader have no polarization axis, i.e. the transponder can come in from
any direction, assume any position as parallel as possible to the reader, and cross the
transmission window. The figure below shows the active area for various directions of
transponder motion:
Transmission window
Direction of motion of the transponder
Detection area L x W
Figure 4-6
Detection areas of the reader for different directions of transponder motion
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
33
4.1.6
Operation in static and dynamic mode
Operation in static mode
If working in static mode, the transponder can be operated up to the limit distance (Sg). The
transponder must then be positioned exactly over the reader:
Figure 4-7
Operation in static mode
Note
Note that in a metallic environment the values for the limit distance are reduced.
Operation in dynamic mode
When working in dynamic mode, the transponder moves past the reader. The transponder
can be used as soon as the intersection (SP) of the transponder enters the circle of the
transmission window. In dynamic mode, the operating distance (Sa) is of primary importance.
[Operating distances, see Chapter Field data of transponders and readers (Page 36)]
Figure 4-8
Operation in dynamic mode
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
34
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.1.7
Dwell time of the transponder
The dwell time is the time in which the transponder remains within the transmission window
of a reader. The reader can exchange data with the transponder during this time.
The dwell time is calculated thus:
tV:
Dwell time of the transponder
L:
Length of the transmission window
vTag:
Speed of the transponder (tag) in dynamic mode
0,8:
Constant factor used to compensate for temperature impacts and production toler-
ances
The dwell time can be of any duration in static mode. The dwell time must be sufficiently long
to allow communication with the transponder.
The dwell time is defined by the system environment in dynamic mode. The volume of data
to be transferred must be matched to the dwell time or vice versa. In general:
tV::
Dwell time of the data memory within the field of the reader
tK:
Communication time between transponder and communication module
RF200 system planning
4.1 Fundamentals of application planning
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
35
4.1.8
Communication between communication module, reader and transponder
Aids for calculating the data transmission times
User-friendly calculation tools are available for the communications modules ASM 456,
RF160C, RF170C and RF180C to calculate data transfer times. The calculation tools can be
found on the DVD "RFID Systems Software & Documentation", article number 6GT2080-
2AA20.
Figure 4-9
User interface of the calculation tool for command processing time
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
36
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Aids for calculating the field data
You will also find a tool for calculating field data on the DVD "RFID Systems, Software &
Documentation". Using this tool, among other things you can calculate the operating
distance (Sa), limit distance (Sg) and transmission window (L).
Figure 4-10
User interface of the calculation tool for field data acquisition
4.2
Field data of transponders and readers
The following tables show the field data for all SIMATIC RF200 components of transponders
and readers. This makes the correct selection of a transponder and reader particularly easy.
All the technical specifications listed are typical data and are applicable for an ambient
temperature between 0 °C and +50 °C, a supply voltage between 22 and 27 VDC and a
metal-free environment. Tolerances of ±20 % are permitted due to production or temperature
conditions.
If the entire voltage range at the reader of 20 VDC to 30 VDC and/or the entire temperature
range of transponders and readers is used, the field data is subject to further tolerances.
Note
Transmission gaps
If the minimum operating distance (Sa) is not observed, a transmission gap can occur in the
center of the field. Communication with the transponder is not possible in the transmission
gap.
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
37
4.2.1
Field data
The limit distances (Sg) and operating distances (Sa) along with the length of the
transmission window for each reader-transponder combination are listed in the tables below.
Table 4- 1
SIMATIC RF210R field data
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D124
25
1 ... 18
20
MDS D127 1)
3
0 ... 2
2
MDS D160
20
1 ... 10
12
MDS D324
20
1 ... 8
9
MDS D421
5
0 ... 3
4
MDS D422
8
1 ... 9
10
MDS D423
20
2 ... 10
12
MDS D424
24
1 ... 16
18
MDS D425
12
1 ... 6
7
MDS D428
20
1 ... 10
11
MDS D460
8
1 … 8
9
MDS D521
5
0 ... 3
4
MDS D522
8
1 ... 8
9
MDS D522
Special variants
8
1 ... 8
9
MDS D524
20
1 ... 15
17
MDS D528
15
1 ... 10
11
1) The transponder is only suitable for static mode.
All dimensions in mm.
Table 4- 2
SIMATIC RF220R field data
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D124
35
1 ... 28
31
MDS D126
45
2 ... 30
35
MDS D160
20
1 ... 20
22
MDS D324
30
2 ... 21
25
MDS D422
18
1 ... 12
14
MDS D423
30
2 ...24
28
MDS D424
30
2 ... 25
29
MDS D425
20
1 ... 11
13
MDS D426
40
2 ... 25
30
MDS D428
25
1 ... 18
21
MDS D460
25
1 ... 18
20
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
38
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D522
15
1 ... 10
12
MDS D522
Special variants
15
1 ... 10
12
MDS D524
25
2 ... 22
25
MDS D526
30
2 ... 25
30
MDS D528
20
1 ... 15
20
All dimensions in mm.
Table 4- 3
SIMATIC RF240R field data
Length of the transmis-
sion window (L)
Operating distance (Sa)
Limit distance (Sg)
MDS D100
100
2 ... 84
95
MDS D124
65
2 ... 53
60
MDS D126
80
2 ... 57
65
MDS D160
50
1 ... 33
37
MDS D165
105
2 ... 80
94
MDS D200
90
2 ... 69
78
MDS D261
70
2 ... 60
70
MDS D324
55
1 ... 36
40
MDS D400
95
2 ... 80
90
MDS D422
25
1 ... 12
15
MDS D423
45
2 ... 35
40
MDS D424
75
1 ... 47
53
MDS D425
30
1 ... 15
17
MDS D426
65
2 ... 45
55
MDS D428
50
1 ... 30
34
MDS D460
50
1 ... 30
34
MDS D522
20
1 ... 10
12
MDS D522
Special variants
20
1 ... 10
12
MDS D524
60
1 ... 45
55
MDS D526
60
2 ... 45
55
MDS D528
40
1 ... 30
35
All dimensions in mm.
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
39
Table 4- 4
Field data SIMATIC RF250R, with ANT 3
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D124
40
1 ... 35
48
MDS D126
65
0 ... 47
60
MDS D160
24
1 ... 23
30
MDS D324
32
1 ... 22
35
MDS D422
27
0 ... 12
15
MDS D423
30
2 ... 18
26
MDS D424
37
0 ... 34
48
MDS D425
22
1 ... 12
20
MDS D426
65
0 ... 44
58
MDS D428
30
1 ... 20
32
MDS D460
24
1 ... 21
27
MDS D522
20
1 ... 12
15
MDS D522
Special variants
20
1 ... 12
15
MDS D524
35
1 ... 35
40
MDS D526
45
2 ... 35
45
MDS D528
25
1 ... 20
25
All dimensions in mm.
Table 4- 5
Field data SIMATIC RF250R, with ANT 8
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D117
2
0 ... 2
3
MDS D127
3
0 ... 3
4
MDS D421
3
0 ... 3
4
MDS D521
3
0 ... 3
4
All dimensions in mm.
Table 4- 6
Field data SIMATIC RF250R, with ANT 12
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D117
3
0 ... 3
4
MDS D127
4
0 ... 4
5
MDS D160
18
0 ... 12
17
MDS D421
10
0 ... 3
4
MDS D422
22
0 ... 7
10
MDS D425
12
0 ... 8
10
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
40
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D428
18
1 ... 8
12
MDS D460
16
1 ... 10
14
MDS D521
5
0 ... 3
4
MDS D522
10
1 ... 7
9
MDS D522
Special variants
10
1 ... 7
9
MDS D528
15
1 ... 8
12
All dimensions in mm.
Table 4- 7
Field data SIMATIC RF250R, with ANT 18
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D124
26
0 ... 24
37
MDS D160
22
1 ... 18
26
MDS D324
30
1 ... 18
27
MDS D421
16
0 ... 3
4
MDS D422
24
1 ... 8
14
MDS D423
21
1 ... 15
18
MDS D424
26
1 ... 27
36
MDS D425
19
1 ... 11
16
MDS D428
19
1 ... 18
25
MDS D460
19
1 ... 17
21
MDS D521
6
0 ... 4
5
MDS D522
15
1 ... 10
12
MDS D522
Special variants
15
1 ... 10
12
MDS D524
30
1 ... 25
30
MDS D528
20
1 ... 15
20
All dimensions in mm.
Table 4- 8
Field data SIMATIC RF250R, with ANT 30
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D124
40
1 ... 35
48
MDS D126
65
0 ... 47
60
MDS D160
24
1 ... 23
30
MDS D324
32
1 ... 22
35
MDS D422
27
0 ... 12
15
MDS D423
30
2 ... 18
26
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
41
Length of the transmis-
sion window (Ld)
Operating distance (Sa)
Limit distance (Sg)
MDS D424
37
0 ... 34
48
MDS D425
22
1 ... 12
20
MDS D426
65
0 ... 44
58
MDS D428
30
1 ... 20
32
MDS D460
24
1 ... 21
27
MDS D522
20
1 ... 12
15
MDS D522
Special variants
20
1 ... 12
15
MDS D524
35
1 ... 35
40
MDS D526
60
2 ... 35
45
MDS D528
25
1 ... 20
25
All dimensions in mm.
Table 4- 9
SIMATIC RF260R field data
Length of the transmis-
sion window (L)
Operating distance (Sa)
Limit distance (Sg)
MDS D100
120
2 ... 110
130
MDS D124
80
2 ... 80
85
MDS D126
110
2 ... 75
100
MDS D139
120
2 ... 80
110
MDS D160
60
2 ... 40
45
MDS D165
120
2 ... 120
135
MDS D200
120
2 ... 100
120
MDS D261
80
2 ... 75
90
MDS D324
80
2 ... 60
70
MDS D339
110
5 ... 65
80
MDS D400
140
2 ... 110
140
MDS D423
55
2 ... 40
45
MDS D424
80
2 ... 60
70
MDS D426
75
2 ... 70
85
MDS D428
50
2 ... 40
45
MDS D460
50
2 ... 40
45
MDS D524
70
2 ... 60
70
MDS D526
80
2 ... 70
85
MDS D528
50
2 ... 35
40
All dimensions in mm.
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
42
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Table 4- 10
Field data SIMATIC RF290R, with ANT D5 (at 4 W)
Length of the transmis-
sion window (L)
Operating distance (Sa)
Limit distance (Sg)
MDS D100
320
0 ... 400
500
MDS D124
300
0 ... 200
280
MDS D126
320
0 ... 350
400
MDS D139
320
0 ... 400
500
MDS D160
300
0 ... 130
180
MDS D165
320
0 ... 350
450
MDS D200
320
0 ... 400
500
MDS D261
320
0 ... 300
400
MDS D324
300
0 ... 200
280
MDS D339
320
0 ... 300
380
MDS D400
320
0 ... 400
500
MDS D424
300
0 ... 200
280
MDS D426
320
0 ... 300
350
MDS D460
300
0 ... 120
160
MDS D524
300
0 ... 200
280
MDS D526
320
0 ... 300
350
All dimensions in mm.
Table 4- 11
Field data SIMATIC RF290R, with ANT D6 (at 4 W)
Length of the transmission
window (L)
Operating distance (Sa)
Limit distance (Sg)
X direction
Y direction
MDS D100
520
420
0 ... 550
650
MDS D124
500
400
0 ... 220
300
MDS D126
520
420
0 ... 400
500
MDS D139
520
420
0 ... 500
600
MDS D160
500
400
0 ... 130
180
MDS D165
520
420
0 ... 400
500
MDS D200
520
420
0 ... 500
600
MDS D261
520
420
0 ... 350
450
MDS D324
500
400
0 ... 200
280
MDS D339
520
420
0 ... 400
480
MDS D400
520
420
0 ... 500
650
MDS D424
500
400
0 ... 220
300
MDS D426
520
420
0 ... 350
400
MDS D524
500
400
0 ... 220
300
MDS D526
520
420
0 ... 350
400
All dimensions in mm.
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
43
Table 4- 12
Field data SIMATIC RF290R, with ANT D10 (at 4 W)
Length of the transmission
window (L)
Operating distance (Sa)
Limit distance (Sg)
X direction
Y direction
MDS D100
1050
350
0 ... 500
600
MDS D124
1000
300
0 ... 200
280
MDS D126
1050
350
0 ... 400
500
MDS D139
1050
350
0 ... 450
550
MDS D160
1000
300
0 ... 130
180
MDS D165
1050
350
0 ... 350
450
MDS D200
1050
350
0 ... 450
550
MDS D261
1050
350
0 ... 350
450
MDS D324
1000
300
0 ... 200
280
MDS D339
1050
350
0 ... 300
380
MDS D400
1050
350
0 ... 400
500
MDS D424
1000
300
0 ... 200
280
MDS D426
1050
350
0 ... 350
400
MDS D524
1000
300
0 ... 220
300
MDS D526
1050
350
0 ... 350
400
All dimensions in mm.
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
44
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.2.2
Minimum clearances
Minimum distance from transponder to transponder
The specified distances refer to a metal-free environment. For a metallic environment, the
specified minimum distances must be multiplied by a factor of 1.5.
Table 4- 13
Minimum clearances for transponders
RF210R
RF220R
RF240R
RF260R
MDS D100
--
--
--
≥ 240
MDS D117
≥ 15
--
--
--
MDS D124
≥ 25
≥ 40
≥ 90
≥ 180
MDS D126
--
≥ 50
≥ 100
≥ 180
MDS D127
≥ 15
--
--
--
MDS D139
--
--
--
≥ 200
MDS D160
≥ 20
≥ 25
≥ 70
≥ 150
MDS D165
--
--
--
≥ 240
MDS D200
--
--
--
≥ 240
MDS D261
--
--
--
≥ 200
MDS D324
≥ 25
≥ 40
≥ 90
≥ 180
MDS D339
--
--
--
≥ 200
MDS D400
--
--
--
≥ 240
MDS D421
≥ 10
--
--
--
MDS D422
≥ 15
≥ 20
≥ 50
--
MDS D423
--
--
≥ 80
≥ 160
MDS D424
≥ 25
≥ 40
≥ 90
≥ 180
MDS D425
≥ 20
≥ 25
≥ 75
--
MDS D426
--
≥ 50
≥ 90
≥ 180
MDS D428
≥ 25
≥ 25
≥ 75
≥ 150
MDS D460
≥ 20
≥ 25
≥ 70
≥ 150
MDS D521
≥ 10
--
--
--
MDS D522
≥ 15
≥ 20
≥ 50
--
MDS D522
Special variants
≥ 15
≥ 20
≥ 50
--
MDS D524
≥ 25
≥ 40
≥ 90
≥ 180
MDS D526
--
≥ 50
≥ 90
≥ 180
MDS D528
≥ 25
≥ 25
≥ 75
≥ 150
All values are in mm, relative to the operating distance (Sa) between reader and transponder, and
between transponder edge and transponder edge
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
45
Table 4- 14
Minimum clearances for transponders
RF250R 1)
RF290R 2)
ANT 3
ANT 8
ANT 12
ANT 18
ANT 30
ANT D5
ANT D6
ANT D10
MDS D100
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D117
--
≥ 30
≥ 50
--
--
--
--
--
MDS D124
≥ 100
--
--
≥ 80
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D126
≥ 100
--
--
--
≥ 100
≥ 1000
≥ 1500
≥ 2000
MDS D127
--
≥ 40
≥ 60
--
--
--
--
--
MDS D139
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D160
≥ 100
--
≥ 60
≥ 80
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D165
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D200
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D261
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D324
≥ 100
--
--
≥ 80
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D339
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D400
--
--
--
--
--
≥ 1000
≥ 1500
≥ 2000
MDS D421
--
≥ 30
≥ 40
≥ 50
--
--
--
--
MDS D422
≥ 70
--
≥ 50
≥ 60
≥ 70
--
--
--
MDS D423
≥ 100
--
--
≥ 80
≥ 100
--
--
--
MDS D424
≥ 100
--
--
≥ 80
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D425
≥ 80
--
≥ 50
≥ 60
≥ 80
--
--
--
MDS D426
≥ 100
--
--
--
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D428
≥ 80
--
≥ 50
≥ 60
≥ 80
--
--
--
MDS D460
≥ 100
--
≥ 60
≥ 80
≥ 100
≥ 800
--
--
MDS D521
--
≥ 30
≥ 40
≥ 50
--
--
--
--
MDS D522
≥ 70
--
≥ 50
≥ 60
≥ 70
--
--
--
MDS D522
Special variants
≥ 70
--
≥ 50
≥ 60
≥ 70
--
--
--
MDS D524
≥ 100
--
--
≥ 80
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D526
≥ 100
--
--
--
≥ 100
≥ 800
≥ 1200
≥ 1800
MDS D528
≥ 80
--
≥ 50
≥ 60
≥ 80
--
--
--
1) Depends on the connected antenna (ANT 3, 8, 12, 18 or 30).
2) Depends on the connected antenna (ANT D5, D6 or D10).
All values are in mm, relative to the operating distance (Sa) between reader and transponder, and
between transponder edge and transponder edge
RF200 system planning
4.2 Field data of transponders and readers
SIMATIC RF200
46
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Minimum distance from reader to reader
Table 4- 15
Minimum distances to readers or antennas
RF210R to
RF210R
RF220R to
RF220R
RF240R to
RF240R
ANT x to ANT x
with RF250R
RF260R to
RF260R
ANT Dx to
ANT Dx
with RF290R
≥ 60 mm
≥ 100 mm
≥ 120 mm
ANT 3: ≥ 100 mm
≥ 150 mm
ANT D5:
≥ 2000 mm
ANT 8: ≥ 50 mm
ANT D10:
≥ 2000 mm
ANT 12: ≥ 60 mm
ANT 18: ≥ 80 mm
ANT 30:
≥ 100 mm
All values are in mm
Note
Effect on inductive fields by not maintaining the minimum distances of the readers
If the values fall below those specified in the "minimum distance readers or antennas", there
is a risk of the function being affected by inductive fields. In this case, the data transfer time
would increase unpredictably or a command would be aborted with an error.
Keeping to the values specified in the "Minimum distance readers or antennas" table is
therefore essential.
If the specified minimum distance cannot be complied with due to the physical configuration,
the SET-ANT command can be used to activate and deactivate the HF field of the reader.
The application software must be used to ensure that only one reader is active (antenna is
switched on) at a time.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
47
4.3
Installation guidelines
4.3.1
Overview
The transponder and reader complete with their antennas are inductive devices. Any type of
metal in the vicinity of these devices affects their functionality. Some points need to be
considered during planning and installation if the values described in the "Field data
(Page 37)" section are to retain their validity:
● Minimum spacing between two readers or their antennas
● Minimum distance between two adjacent data memories
● Metal-free area for flush-mounting of readers or their antennas and transponders in metal
● Mounting of multiple readers or their antennas on metal frames or racks
The following sections describe the impact on the operation of the RFID system when
mounted in the vicinity of metal.
4.3.2
Reduction of interference due to metal
Interference due to metal rack
Problem
A metal rack is located above the
transmission window of the reader.
This affects the entire field. In par-
ticular, the transmission window
between reader and transponder is
reduced.
Remedy:
The transmission window is no
longer affected if the transponder is
mounted differently.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
48
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Flush-mounting
Flush-mounting of transponders and readers
Problem
Flush-mounting of transponders and
readers is possible in principle.
However, the size of the transmis-
sion window is significantly reduced.
The following measures can be
used to counteract the reduction of
the window:
Remedy:
Enlargement of the non-metallic
spacer below the transponder
and/or reader.
The transponder and/or reader are
10 to 20 mm higher than the metal
surround.
(The value x ≥ 100 mm is valid, for
example, for RF260R. It indicates
that, for a distance x ≥ 100 mm, the
reader can no longer be significantly
affected by metal.)
Remedy:
Increase the non-metallic distance
a, b.
The following rule of thumb can be
used:
•
Increase a, b by a factor of 2 to 3
over the values specified for
metal-free areas
•
Increasing a, b has a greater
effect for readers or transpond-
ers with a large limit distance
than for readers or transponders
with a small limit distance.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
49
Mounting of several readers on metal frames or racks
Any reader mounted on metal couples part of the field to the metal frame. There is normally
no interaction as long as the minimum distance D and metal-free areas a, b are maintained.
However, interaction may take place if an iron frame is positioned unfavorably. Longer data
transfer times or sporadic error messages at the communication module are the result.
Mounting of several readers on metal racks
Problem: Interaction between readers
Remedy
Increase the distance D between the two readers.
Remedy
Introduce one or more iron struts in order to short-
circuit the stray fields.
Remedy
Insert a non-metallic spacer of 20 to 40 millimeter
thickness between the reader and the iron frame. This
will significantly reduce the induction of stray fields on
the rack:
4.3.3
Effects of metal on different transponders and readers
Mounting different transponders and readers on metal or flush-mounting
Certain conditions have to be observed when mounting the transponders and readers on
metal or flush-mounting. For more information, please refer to the descriptions of the
individual transponders and readers in the relevant section.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
50
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.3.4
Impact of metal on the transmission window
In general, the following points should be considered when mounting RFID components:
● Direct mounting on metal is allowed only in the case of specially approved transponders.
● Flush-mounting of the components in metal reduces the field data; a test is recommended
in critical applications.
● When working inside the transmission window, make sure that no metal rail (or similar
part) intersects the transmission field.
The metal rail would affect the field data.
● With readers with a large antenna surface (e.g. RF260R) for reasons of communication
reliability, when the transponders are flush mounted in metal, a metal-free space around
the transponders is recommended. This metal-free space should match the size of the
antenna surface.
The impact of metal on the field data (Sg, Sa, L) is shown in a table in this section. The
values in the tables describe field data reduction and show the reduced range as a
percentage. The range relates to use in a non-metallic environment. A value of 100% means
no influence on the range.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
51
4.3.4.1
RF210R
The RF210R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
The following table shows the different arrangements for the reader with and without a
metallic environment:
Case
Diagram
Description
a)
Reader metal-free
b)
Reader on metal,
distance from metal ≥ 12 mm
c)
Reader in metal,
flush against M18 nut
d)
Reader in metal,
all around
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
52
System Manual, 07/2015, J31069-D0227-U001-A9-7618
To avoid any influence on the field data, in Case d, the distance a should be ≥ 10 mm.
Table 4- 16
Reduction of field data due to metal, range as %: Transponder and RF210R
Transponder
Reader without direct
metal influence
(Case a, b and d)
Reader flush-
mounted in metal
(Case c)
MDS D124 1)
metal-free
100
82
on metal, distance 15 mm
90
90
flush-mounted in metal;
distance all round 15 mm
85
80
MDS D127
flush-mounted in metal;
distance all round 0 mm
100
75
MDS D160 1)
metal-free
100
95
on metal, distance 10 mm
100
95
MDS D324 1)
metal-free
100
90
on metal, distance 15 mm
90
90
flush-mounted in metal;
distance all round 25 mm
80
90
MDS D421
metal-free
100
90
flush-mounted in metal;
distance all round 0 mm
75
50
MDS D422
metal-free
100
80
flush-mounted in metal;
distance all round 0 mm
90
40
MDS D423
metal-free
100
90
on metal, distance 0 mm
110 2)
100 2)
flush-mounted in metal;
distance all round 10 mm
95
85
MDS D424 1)
metal-free
100
60
on metal, distance 15 mm
90
80
flush-mounted in metal;
distance all round 25 mm
85
75
MDS D425
metal-free
100
85
on metal, distance 0 mm
100
85
MDS D428
metal-free
100
90
on metal, distance 0 mm
100
80
MDS D460 1)
metal-free
100
90
on metal, distance 25 mm
100
90
MDS D521
metal-free
100
90
flush-mounted in metal;
distance all round 0 mm
75
50
MDS D522
metal-free
100
80
flush-mounted in metal;
distance all round 0 mm
90
40
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
53
Transponder
Reader without direct
metal influence
(Case a, b and d)
Reader flush-
mounted in metal
(Case c)
MDS D522
Special variant
metal-free
100
80
flush-mounted in metal;
distance all round 0 mm
90
40
MDS D524 1)
metal-free
100
60
on metal, distance 15 mm
90
80
flush-mounted in metal;
distance all round 25 mm
85
75
MDS D528
metal-free
100
90
on metal, distance 0 mm
100
80
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
54
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.3.4.2
RF220R
The RF220R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
The following table shows the different arrangements for the reader with and without a
metallic environment:
Case
Diagram
Description
a)
Reader metal-free
b)
Reader on metal,
distance from metal ≥ 12 mm
c)
Reader in metal,
flush against M30 nut
d)
Reader in metal,
all round
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
55
To avoid any influence on the field data, in Case d, the distance a should be ≥ 15 mm.
Table 4- 17
Reduction of field data due to metal, range as %: Transponder and RF220R
Transponder
Reader without direct
metal influence
(Case a, b and d)
Reader flush-
mounted in metal
(Case c)
MDS D124 1)
metal-free
100
94
on metal, distance 15 mm
97
89
tag flush-mounted in metal;
distance all round 15 mm
86
83
MDS D126 1)
metal-free
100
75
on metal, distance 25 mm
85
70
flush-mounted in metal;
distance all round 50 mm
80
65
MDS D160 1)
metal-free
100
89
on metal, distance 10 mm
100
89
MDS D324 1)
metal-free
100
90
on metal, distance 15 mm
97
86
flush-mounted in metal;
distance all round 25 mm
93
86
MDS D422
metal-free
100
90
flush-mounted in metal;
distance all round 0 mm
85
85
MDS D423
metal-free
100
90
on metal, distance 0 mm
125 2)
115 2)
flush-mounted in metal;
distance all round 10 mm
80
75
MDS D424 1)
metal-free
100
93
on metal, distance 15 mm
96
89
flush-mounted in metal;
distance all round 25 mm
86
82
MDS D425
metal-free
100
90
screwed onto metal
100
75
flush-mounted in metal;
distance all round 25 mm
95
75
MDS D426 1)
metal-free
100
90
on metal, distance 25 mm
90
75
flush-mounted in metal;
distance all round 50 mm
80
70
MDS D428
metal-free
100
94
on metal, distance 0 mm
100
94
MDS D460 1)
metal-free
100
92
on metal, distance 0 mm
100
92
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
56
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
Reader without direct
metal influence
(Case a, b and d)
Reader flush-
mounted in metal
(Case c)
MDS D522
metal-free
100
90
flush-mounted in metal;
distance all round 0 mm
85
85
MDS D522
Special variant
metal-free
100
90
flush-mounted in metal;
distance all round 0 mm
85
85
MDS D524 1)
metal-free
100
93
on metal, distance 0 mm
96
89
flush-mounted in metal;
distance all round 0 mm
86
82
MDS D526 1)
metal-free
100
90
on metal, distance 25 mm
90
75
flush-mounted in metal;
distance all round 50 mm
80
70
MDS D528
metal-free
100
94
on metal, distance 0 mm
100
94
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
4.3.4.3
RF240R
The RF240R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
Figure 4-11
metal-free space RF240R
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
57
To avoid any impact on the field data, the distance a should be ≥ 20 mm.
Table 4- 18
Reduction of field data due to metal, range as %: Transponder and RF240R
Transponder
Reader without
direct
metal influence
Reader on
metal
(metal plate)
Reader flush-
mounted in metal
(all round
20 mm)
MDS D100 1)
without metal
100
95
80
on metal, distance 20 mm
95
90
75
flush-mounted in metal;
distance all round 20 mm
90
75
70
MDS D124 1)
without metal
100
85
75
on metal, distance 15 mm
90
80
75
flush-mounted in metal;
distance all round 25 mm
85
70
65
MDS D126 1)
without metal
100
80
70
on metal, distance 25 mm
80
75
60
flush-mounted in metal;
distance all round 50 mm
70
55
55
MDS D160 1)
without metal
100
90
80
on metal, distance 10 mm
90
85
80
MDS D165
without metal
100
95
75
on metal, distance 25 mm
75
70
65
MDS D200 1)
without metal
100
95
85
on metal, distance 20 mm
95
80
70
flush-mounted in metal,
distance all round 20 mm
70
60
50
MDS D261
without metal
100
90
90
on metal, distance 25 mm
85
80
70
MDS D324 1)
without metal
100
90
80
on metal, distance 15 mm
95
85
80
flush-mounted in metal;
distance all round 25 mm
90
75
70
MDS D400 1)
without metal
100
90
80
on metal, distance 20 mm
80
75
55
flush-mounted in metal,
distance all round 20 mm
75
70
50
MDS D422
without metal
100
90
85
flush-mounted in metal;
distance all round 0 mm
90
60
40
MDS D423
without metal
100
95
90
on metal, distance 0 mm
150 2)
140 2)
140 2)
flush-mounted in metal;
distance all round 10 mm
70
60
60
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
58
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
Reader without
direct
metal influence
Reader on
metal
(metal plate)
Reader flush-
mounted in metal
(all round
20 mm)
MDS D424 1)
without metal
100
85
80
on metal, distance 15 mm
90
80
75
flush-mounted in metal;
distance all round 25 mm
80
70
65
MDS D425
without metal
100
90
85
on metal, distance 0 mm
95
85
80
MDS D426 1)
without metal
100
80
70
on metal, distance 25 mm
90
80
70
flush-mounted in metal;
Distance all-round 50 mm
85
65
60
MDS D428
without metal
100
90
85
on metal, distance 0 mm
95
85
83
MDS D460 1)
without metal
100
90
80
on metal, distance 0 mm
90
85
80
MDS D522
metal-free
100
90
85
flush-mounted in metal;
distance all round 0 mm
90
60
40
MDS D522
Special vari-
ant
metal-free
100
90
85
flush-mounted in metal;
distance all round 0 mm
90
60
40
MDS D524 1)
metal-free
100
85
80
on metal, distance 0 mm
90
80
75
flush-mounted in metal;
distance all round 0 mm
80
70
65
MDS D526 1)
metal-free
100
80
70
on metal, distance 25 mm
90
80
70
flush-mounted in metal;
distance all round 50 mm
85
65
60
MDS D528
metal-free
100
90
85
on metal, distance 0 mm
95
85
83
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
59
4.3.4.4
RF250R
The RF250R reader is operated with the external antennas ANT 3, 8, 12, 18 and 30. The
antennas can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
Figure 4-12
Metal-free space for ANT 8 / ANT 12 and ANT 18 / ANT 30
Table 4- 19
Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 3
Transponder
RF250R with ANT 3
antenna without met-
al
antenna flush-
mounted in metal
(all round 20 mm)
MDS D124 1)
without metal
100
80
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
MDS D126 1)
without metal
100
80
on metal, distance 25 mm
85
75
flush-mounted in metal;
distance all round 50 mm
60
50
MDS D160 1)
without metal
100
85
on metal, distance 10 mm
95
80
MDS D324 1)
without metal
100
80
on metal, distance 15 mm
95
75
flush-mounted in metal;
distance all round 25 mm
85
70
MDS D422
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D423
without metal
100
90
on metal, distance 0 mm
130 2)
110 2)
flush-mounted in metal;
distance all round 10 mm
80
70
MDS D424 1)
without metal
100
85
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
60
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
RF250R with ANT 3
antenna without met-
al
antenna flush-
mounted in metal
(all round 20 mm)
MDS D425
without metal
100
90
on metal, distance 0 mm
95
75
MDS D426 1)
without metal
100
70
on metal, distance 25 mm
90
65
flush-mounted in metal;
distance all round 25 mm
55
45
MDS D428
without metal
100
90
on metal, distance 0 mm
100
90
MDS D460 1)
without metal
100
85
on metal, distance 10 mm
90
75
MDS D522
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D522
Special variant
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D524 1)
without metal
100
85
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
MDS D526 1)
without metal
100
70
on metal, distance 25 mm
90
65
flush-mounted in metal;
distance all round 25 mm
55
45
MDS D528
without metal
100
90
on metal, distance 0 mm
100
90
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
Table 4- 20
Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 8
Transponder
RF250R with ANT 8
antenna without met-
al
antenna flush-
mounted in metal
MDS D117
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
65
55
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
61
Transponder
RF250R with ANT 8
antenna without met-
al
antenna flush-
mounted in metal
MDS D127
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
70
60
MDS D421
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
75
70
MDS D521
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
75
70
Table 4- 21
Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 12
Transponder
RF250R with ANT 12
antenna without met-
al
antenna flush-
mounted in metal
(all round 7 mm)
MDS D117
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
50
40
MDS D127
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
65
50
MDS D160 1)
without metal
100
90
on metal, distance 10 mm
90
85
MDS D421
without metal
100
90
flush-mounted in metal;
distance all round 0 mm
65
45
MDS D422
without metal
100
90
flush-mounted in metal;
distance all round 0 mm
90
75
MDS D425
without metal
100
90
on metal, distance 0 mm
115 2)
100
MDS D428
without metal
100
85
on metal, distance 0 mm
110 2)
95
MDS D460 1)
without metal
100
95
on metal, distance 10 mm
90
80
flush-mounted in metal;
distance all round 0 mm
85
75
MDS D521
without metal
100
90
flush-mounted in metal;
distance all round 0 mm
65
45
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
62
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
RF250R with ANT 12
antenna without met-
al
antenna flush-
mounted in metal
(all round 7 mm)
MDS D522
without metal
100
90
flush-mounted in metal;
distance all round 0 mm
90
75
MDS D528
without metal
100
85
on metal, distance 0 mm
110 2)
95
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
Table 4- 22
Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 18
Transponder
RF250R with ANT 18
antenna without met-
al
antenna flush-
mounted in metal
(all round 10 mm)
MDS D124 1)
without metal
100
80
on metal, distance 15 mm
100
80
flush-mounted in metal;
distance all round 25 mm
95
70
MDS D160 1)
without metal
100
90
on metal, distance 10 mm
100
90
MDS D324 1)
without metal
100
80
on metal, distance 15 mm
100
80
flush-mounted in metal;
distance all round 25 mm
95
75
MDS D421
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
65
50
MDS D422
without metal
100
100
flush-mounted in metal;
distance all round 0 mm
90
90
MDS D423
without metal
100
85
on metal, distance 0 mm
120 2)
110 2)
flush-mounted in metal;
distance all round 10 mm
90
75
MDS D424 1)
without metal
100
75
on metal, distance 15 mm
95
75
flush-mounted in metal;
distance all round 25 mm
95
75
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
63
Transponder
RF250R with ANT 18
antenna without met-
al
antenna flush-
mounted in metal
(all round 10 mm)
MDS D425
without metal
100
90
on metal, distance 0 mm
100
90
MDS D428
without metal
100
85
on metal, distance 0 mm
100
85
MDS D460 1)
without metal
100
85
on metal, distance 10 mm
100
85
MDS D521
without metal
100
85
flush-mounted in metal;
distance all round 0 mm
65
50
MDS D522
without metal
100
100
flush-mounted in metal;
distance all round 0 mm
90
90
MDS D522
Special variant
without metal
100
100
flush-mounted in metal;
distance all round 0 mm
90
90
MDS D524 1)
without metal
100
75
on metal, distance 15 mm
95
75
flush-mounted in metal;
distance all round 25 mm
95
75
MDS D528
without metal
100
85
on metal, distance 0 mm
100
85
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
Table 4- 23
Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 30
Transponder
RF250R with ANT 30
antenna without met-
al
antenna flush-
mounted in metal
(all round 20 mm)
MDS D124 1)
without metal
100
80
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
MDS D126 1)
without metal
100
80
on metal, distance 25 mm
85
75
flush-mounted in metal;
distance all round 50 mm
60
50
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
64
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
RF250R with ANT 30
antenna without met-
al
antenna flush-
mounted in metal
(all round 20 mm)
MDS D160 1)
without metal
100
85
on metal, distance 10 mm
95
80
MDS D324 1)
without metal
100
80
on metal, distance 15 mm
95
75
flush-mounted in metal;
distance all round 25 mm
85
70
MDS D422
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D423
without metal
100
90
on metal, distance 0 mm
130 2)
110 2)
flush-mounted in metal;
distance all round 10 mm
80
70
MDS D424 1)
without metal
100
85
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
MDS D425
without metal
100
90
on metal, distance 0 mm
95
75
MDS D426 1)
without metal
100
70
on metal, distance 25 mm
90
65
flush-mounted in metal;
distance all round 25 mm
55
45
MDS D428
without metal
100
90
on metal, distance 0 mm
100
90
MDS D460 1)
without metal
100
85
on metal, distance 10 mm
90
75
MDS D522
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D522
Special variant
without metal
100
95
flush-mounted in metal;
distance all round 0 mm
95
80
MDS D524 1)
without metal
100
85
on metal, distance 15 mm
90
75
flush-mounted in metal;
distance all round 25 mm
75
70
MDS D526 1)
without metal
100
70
on metal, distance 25 mm
90
65
flush-mounted in metal;
distance all round 25 mm
55
45
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
65
Transponder
RF250R with ANT 30
antenna without met-
al
antenna flush-
mounted in metal
(all round 20 mm)
MDS D528
without metal
100
90
on metal, distance 0 mm
100
90
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
4.3.4.5
RF260R
The RF260R can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
Figure 4-13
metal-free space for RF260R
To avoid any impact on the field data, the distance a should be ≥ 20 mm.
Table 4- 24
Reduction of field data due to metal, range as %: Transponder and RF260R
Transponder
Reader with-
out direct
metal influ-
ence
Reader on met-
al
(metal plate)
Reader flush-
mounted in metal
(all round 20 mm)
MDS D100 1)
without metal
100
85
65
on metal, distance 20 mm
70
65
50
flush-mounted in metal;
distance all round 20 mm
65
50
40
MDS D124 1)
without metal
100
93
75
on metal, distance 15 mm
95
85
70
flush-mounted in metal;
distance all round 25 mm
78
75
65
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
66
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
Reader with-
out direct
metal influ-
ence
Reader on met-
al
(metal plate)
Reader flush-
mounted in metal
(all round 20 mm)
MDS D126 1)
without metal
100
85
73
on metal, distance 25 mm
75
68
60
flush-mounted in metal;
distance all round 50 mm
55
53
40
MDS D139 1)
without metal
100
90
75
on metal, distance 30 mm
95
90
75
MDS D160 1)
without metal
100
90
75
on metal, distance 10 mm
90
80
80
MDS D165
without metal
100
85
65
on metal, distance 25 mm
65
60
45
MDS D200 1)
without metal
100
85
70
on metal, distance 20 mm
70
65
50
flush-mounted in metal,
distance all round 20 mm
55
50
45
MDS D261
without metal
100
85
70
on metal, distance 25 mm
80
70
60
MDS D324 1)
without metal
100
90
75
on metal, distance 15 mm
90
80
70
flush-mounted in metal;
distance all round 25 mm
70
65
55
MDS D339 1)
without metal
100
90
75
on metal, distance 30 mm
95
90
75
MDS D400 1)
without metal
100
85
70
on metal, distance 20 mm
70
65
50
flush-mounted in metal;
distance all round 20 mm
55
50
45
MDS D423
without metal
100
95
85
on metal, distance 0 mm
120 2)
115 2)
110 2)
flush-mounted in metal;
distance all round 10 mm
75
65
60
MDS D424 1)
without metal
100
90
80
on metal, distance 15 mm
90
80
70
flush-mounted in metal;
distance all round 25 mm
60
60
50
MDS D426 1)
without metal
100
100
73
on metal, distance 25 mm
88
85
68
flush-mounted in metal;
distance all round 50 mm
65
55
55
MDS D428
without metal
100
90
90
on metal, distance 0 mm
90
90
85
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
67
Transponder
Reader with-
out direct
metal influ-
ence
Reader on met-
al
(metal plate)
Reader flush-
mounted in metal
(all round 20 mm)
MDS D460 1)
without metal
100
95
90
on metal, distance 10 mm
90
85
80
MDS D524 1)
without metal
100
90
80
on metal, distance 15 mm
90
80
70
flush-mounted in metal;
distance all round 25 mm
60
60
50
MDS D526 1)
without metal
100
100
73
on metal, distance 25 mm
88
85
68
flush-mounted in metal;
distance all round 50 mm
65
55
55
MDS D528
without metal
100
90
90
on metal, distance 0 mm
90
90
85
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
2) Values of > 100 % related to non metal surroundings can occur if transponders were developed
specifically for mounting in/on metallic surroundings.
4.3.4.6
RF290R
The RF290R reader is operated with the external antennas ANT D5, D6 and D10. The
antennas can be flush-mounted in metal. Please allow for a possible reduction in the field
data values.
Figure 4-14
Metal-free space for ANT D5
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
68
System Manual, 07/2015, J31069-D0227-U001-A9-7618
To avoid any influence on the field data, the distance a should be ≥ 150 or 200 mm.
Table 4- 25
Reduction of field data due to metal, range as %: Transponder and RF290R with ANT
D5
Transponder
RF290R with ANT D5
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 150 mm)
MDS D100 1)
without metal
100
95
on metal, distance 20 mm
65
60
flush-mounted in metal;
distance all round 20 mm
45
40
MDS D124 1)
without metal
100
95
on metal, distance 15 mm
85
80
flush-mounted in metal;
distance all round 25 mm
65
60
MDS D126 1)
without metal
100
95
on metal, distance 25 mm
70
65
flush-mounted in metal;
distance all round 50 mm
55
50
MDS D139 1)
without metal
100
95
on metal, distance 30 mm
90
85
MDS D160 1)
without metal
100
95
on metal, distance 10 mm
70
65
MDS D165
without metal
100
95
on metal, distance 25 mm
65
60
MDS D200 1)
without metal
100
95
on metal, distance 20 mm
65
60
flush-mounted in metal;
distance all round 20 mm
45
40
MDS D261
without metal
100
95
on metal, distance 25 mm
65
60
MDS D324 1)
without metal
100
95
on metal, distance 15 mm
75
70
MDS D339 1)
without metal
100
95
on metal, distance 30 mm
90
85
MDS D400 1)
without metal
100
95
on metal, distance 20 mm
65
60
flush-mounted in metal;
distance all round 20 mm
45
40
MDS D424 1)
without metal
100
95
on metal, distance 15 mm
75
70
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
69
Transponder
RF290R with ANT D5
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 150 mm)
MDS D426 1)
without metal
100
95
on metal, distance 25 mm
70
65
flush-mounted in metal;
distance all round 50 mm
50
45
MDS D460 1)
without metal
100
95
on metal, distance 10 mm
70
65
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
Table 4- 26
Reduction of field data due to metal, range as %: Transponder and RF290R with ANT
D6
Transponder
RF290R with ANT D6
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 200 mm)
MDS D100 1)
without metal
100
95
on metal, distance 20 mm
65
60
MDS D124 1)
without metal
100
95
on metal, distance 25 mm
80
75
MDS D126 1)
without metal
100
95
on metal, distance 25 mm
65
60
MDS D139 1)
without metal
100
90
on metal, distance 30 mm
80
70
MDS D160 1)
without metal
100
90
on metal, distance 25 mm
60
55
MDS D165
without metal
100
95
on metal, distance 20 mm
50
45
MDS D200 1)
without metal
100
95
on metal, distance 20 mm
65
60
MDS D261
without metal
100
95
on metal, distance 20 mm
50
45
MDS D324 1)
without metal
100
95
on metal, distance 25 mm
75
70
MDS D339 1)
without metal
100
90
on metal, distance 30 mm
80
70
MDS D400 1)
without metal
100
95
on metal, distance 20 mm
60
55
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
70
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Transponder
RF290R with ANT D6
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 200 mm)
MDS D424 1)
without metal
100
95
on metal, distance 25 mm
75
70
MDS D426 1)
without metal
100
95
on metal, distance 25 mm
65
60
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
Table 4- 27
Reduction of field data due to metal, range as %: Transponder and RF290R with ANT
D10
Transponder
RF290R with ANT D10
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 200 mm)
MDS D100 1)
without metal
100
95
on metal, distance 20 mm
50
40
MDS D124 1)
without metal
100
90
on metal, distance 25 mm
70
60
MDS D126 1)
without metal
100
95
on metal, distance 25 mm
65
60
MDS D139 1)
without metal
100
90
on metal, distance 30 mm
80
70
MDS D160 1)
without metal
100
90
on metal, distance 25 mm
60
55
MDS D165
without metal
100
90
on metal, distance 20 mm
40
30
MDS D200 1)
without metal
100
95
on metal, distance 20 mm
50
40
MDS D261
without metal
100
90
on metal, distance 20 mm
40
30
MDS D324 1)
without metal
100
90
on metal, distance 25 mm
70
60
MDS D339 1)
without metal
100
90
on metal, distance 30 mm
80
70
MDS D400 1)
without metal
100
95
on metal, distance 20 mm
50
40
MDS D424 1)
without metal
100
90
on metal, distance 25 mm
70
60
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
71
Transponder
RF290R with ANT D10
Antenna on metal
(metal plate)
antenna flush-
mounted in metal
(all round 200 mm)
MDS D426 1)
without metal
100
95
on metal, distance 25 mm
70
65
MDS D524 1)
without metal
100
90
on metal, distance 25 mm
70
60
MDS D526 1)
without metal
100
95
on metal, distance 25 mm
70
65
1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is
adequate clearance to the metal.
4.3.5
Installation and connection of 2 to 6 antennas with one RF290R reader
If several antennas need to be operated on one reader, this can be achieved by using the
antenna splitter or the antenna multiplexer RF260X.
Note that the antenna splitter is a purely passive device that splits the power at the input to
two outputs and therefore halves it. This is possible both in PC mode (RS-232) and CM
mode (RS-422). You can cascade the antenna splitters in such a way that up to 4 antennas
can be connected at the same time.
The antenna multiplexer RF260X works only in PC mode (RS-232) in time division multiplex
mode. This means that each antenna operates with full power for a certain time before the
device moves on automatically to the next antenna. The antenna multiplexer normally
operates in scan mode or buffered read mode which with suitable parameter assignment add
the information about the antenna number to the reply of the transponder. You can operate
up to six antennas on one reader via the multiplexer.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
72
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.3.5.1
Installation options with the antenna splitter (2-4 antennas)
Possible configurations of the antennas
The antenna installations described here have been designed for reading smartlabels
(transponders) on goods on conveyor belts, conveyor systems or pallets.
A prerequisite is that there are no magnetically conducting materials (e.g. metal) in the
vicinity of the antenna or the label.
Figure 4-15
Possible configuration of RF290R with ANT D5/D6/D10
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
73
Installation examples
Figure 4-16
Installation example with 2 ANT D6 (portal)
Figure 4-17
Installation example with ANT D6 (C arrangement)
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
74
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Figure 4-18
Installation example with ANT D6 (tunnel)
Note
The minimum spacings between the antennas for operation with only one reader may be
less than the distances described because this configuration has the same phase.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
75
4.3.5.2
Antenna installation
Configuring instructions
The antenna installation described below enables detection of transponders moving
horizontally through the installation. Depending on the installation (antennas exactly opposite
each other or offset in parallel), the label is aligned in parallel with the antennas or arbitrarily.
The size of the sensing range depends on the label alignment:
Note
Remember that the entire acquisition range of the antenna is larger than the transmission
window in which the transponder is normally configured. This means there can be label
alignments where even labels outside the transmission window will be identified. Labels
aligned in parallel with the antennas, for example, can also be detected at larger distances
beside or outside the antenna range.
For this reason, goods with labels must not be stored within a distance of up to 0.5 m from
the installation. If this cannot be complied with, the antennas must be shielded.
To achieve three-dimensional detection of the labels in the sensing range, the following
requirements must be met:
• The gate width must be less than or equal to 800 mm.
• The antenna size of the labels should be at least the size of an ISO card (85 mm x 54
mm).
• The distance from label to label must be greater than 100 mm. The distance from label to
label can be reduced if the gate width is correspondingly reduced. This applies especially
for distances under 50 mm.
• There should be no more than 16 labels within the sensing range of the antennas at the
same time.
The number of labels can be increased if the gate width is correspondingly reduced and
the maximum speed suitably adapted.
• The maximum speed of the labels must not exceed 1 m/s. (This depends on the number
and alignment of the labels, the number of data blocks to be processed, the data protocol
required and the label type).
• To the front and sides of the antenna, there must be a distance of more than 150 mm to
metal parts.
• There must be no interference to the write/read device from other electrical equipment in
the surrounding area.
Note
The RF290R reader is not capable of multitag operation in the CM mode.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
76
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Required components
For installation with
● 2 antennas (gate)
● 3 antennas (C arrangement)
● 4 antennas (tunnel)
the following components are required:
Table 4- 28
Components required for setting up with 2, 3 or 4 antennas
Number for installation
with
Component
Article number
2 ant.
3 ant.
4 ant.
1
1
1
Basic device:
RF290R (↔ CM or PC)
RF290R: 6GT2821-0AC12
optionally:
ASM 475: 6GT2002-0GA10
ASM 456: 6GT2002-0ED00
RF170C: 6GT2002-0HD00
RF180C: 6GT2002-0JD00
RF182C: 6GT2002-0JD10
2
3
4
Antenna ANT D5 / D6 / D10
optionally:
ANT D5: 6GT2698-5AA10
ANT D6: 6GT2698-5AB00
ANT D10: 6GT2698-5AF00
2
3
4
With ANT D6 if required:
cover
6GT2698-5AD00
1
2
3
Antenna splitter
6GT2603-0AC00
1
1
1
Wide-range power supply unit for
SIMATIC RF systems
(for PC mode only)
EU: 6GT2898-0AA00
UK: 6GT2898-0AA10
US: 6GT2898-0AA20
1
1
1
24 V connecting cable, length 5 m
(for PC mode only)
6GT2491-1HH50
1
1
1
Connecting cable:
RF290R ↔ PC
or
RF290R ↔ CM
6GT2891-4KH ...
optionally:
6GT2891-4F ...
6GT2891-4EH ...
Installation information
The cables on the antennas and the antenna splitter are 3.3 m or 10.5 m long. The
write/read device must be installed in the vicinity of the antennas. If there are greater
distances between the write/read device and the antennas, the antenna cable can be
increased by 7.2 m with the extension (6GT2691-0DH72). This results in shorter ranges.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
77
Metal-free space
To guarantee perfect functioning of the individual installation versions, all larger metal parts
in the vicinity of the antennas must be removed.
Figure 4-19
Metal-free space, side view (based on the example of a tunnel arrangement on a
conveyor belt)
a
approx. half antenna length
b
min. 100 mm
c
max. 600 mm
Metal-free space
Figure 4-20
Metal-free space, view from above (based on the example of a tunnel arrangement on a
conveyor belt)
Metal in the vicinity of the antennas
If metal in the vicinity of the antennas cannot be avoided, the following must be noted:
● There must be a minimum allround gap of 100 mm between the antenna and metal.
Serious loss of sensing range must be expected above 50 mm. There is no discernible
influence at distances greater than 150 mm from the metal.
● The influence of the metal depends heavily on its size and shape. Thin metal rods have
less influence on the magnetic field than large surfaces.
● Larger metal surfaces (edge length > 50 mm) in parallel with the antennas or labels result
in a short-circuit of the magnetic lines of force. As a result, the labels cannot be read.
● Metal parts under the conveyor belt change the direction of the magnetic lines of force.
Serious loss of sensing range must be expected as a result. Horizontally aligned labels
cannot be read in such cases.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
78
System Manual, 07/2015, J31069-D0227-U001-A9-7618
● The metal parts must not form closed loops or circuits. If necessary, these must be
electrically interrupted at one point.
● The metal parts in the immediate vicinity of the antenna must be grounded in a mesh with
a good HF connection.
● Since the write/read device is installed in a metal housing, and the antennas can couple
into the cables to the write/read device, it must be installed at a distance of at least 500
mm from the antennas.
Notes on installing and laying the antenna cable
To suppress possible interference, an EMC hinged ferrite choke must be fitted to the
antenna cables (as well as the antenna cable between the reader and the antenna splitter).
The coaxial cable must be wound tightly at least four times through the EMC ring core. The
maximum distance between the connecting plug for the reader or the antenna splitter and
the ring core must be 100 mm.
The antenna cable must always be run vertically from the antennas. A minimum distance of
200 mm to the antennas must be observed as the cables continue. Otherwise, performance
losses must be expected.
There must be a distance of at least 300 mm between antenna cables and parallel power
cables.
Unrequired cable length must be secured in a bundle with a diameter of 100 to 150 mm.
If the standard antenna cable is too short, it can be increased by 7.20 m with the extension.
Slight range losses must be expected here.
To achieve optimal read ranges, the antenna cable should not be shortened or lengthened.
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
79
4.3.5.3
Installation options with the antenna multiplexer (2-6 antennas)
You can operate up to six antennas on one reader via the multiplexer.
The data is processed sequentially.
Antenna switchover is performed in time-multiplex mode, so by connecting several antennas
together, the processing time / activation time per antenna is lengthened accordingly.
Figure 4-21
Configuration example of the antenna multiplexer with ANT D5
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
80
System Manual, 07/2015, J31069-D0227-U001-A9-7618
4.3.6
Chemical resistance of the transponders
4.3.6.1
Overview of the transponders and their housing materials
The following sections describe the resistance to chemicals of the various transponders.
Resistance to chemicals depends on the housing material used to manufacture the
transponders.
The following table provides an overview of the housing materials of the transponders:
Table 4- 29
Overview of the housing materials of the transponders
Housing material
Transponder
Polyphenylene sulfide (PPS)
MDS D117
MDS D124 (6GT2600-0AC10)
MDS D139
MDS D160
MDS D339
MDS D423
Polycarbonate (PC)
MDS D100 (6GT2600-0AD10)
Polyvinyl chloride (PVC)
MDS D100 (6GT2600-0AD00-0AX0)
MDS D200
MDS D400
Epoxy resin
MDS D124 (6GT2600-0AC00)
MDS D324
MDS D421
MDS D424
MDS D460
MDS D521
MDS D524
PA6
MDS D127
PA6.6 GF30
MDS D126
MDS D422
MDS D425
MDS D426
MDS D428
MDS D522
MDS D526
MDS D528
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
81
Note
Chemical substances not listed
The following sections describe the resistance of the various transponders to specific
substances. If you require information about chemical substances that are not listed, contact
Customer Support.
4.3.6.2
Polyphenylene sulfide (PPS)
The data memory has special chemical resistance to solutions up to a temperature of 200
°C. A reduction in the mechanical properties has been observed in aqueous solutions of
hydrochloric acid (HCl) and nitric acid (HNO3) at 80 °C. The plastic housings are resistant to
all types of fuel including methanol.
Table 4- 30
Chemical resistance - polyphenylene sulfide (PPS)
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Acetone
55 ℃ عربي
n-Butanol (butyl alcohol)
80 ℃ عربي
Butanone-2 (methyl ethyl ketone)
60 ℃ عربي
n-Butyl acetate
80 ℃ عربي
Brake fluid
80 ℃ عربي
Calcium chloride (saturated)
80 ℃ عربي
Diesel fuel
80 ℃ عربي
Diethyl ether
23 ℃ عربي
Frigen 113
23 ℃ عربي
Anti-freeze
120 ℃ عربي
Kerosene
60 ℃ عربي
Methanol
60 ℃ عربي
Engine oil
80 ℃ عربي
Sodium chloride (saturated)
80 ℃
○○○○
Sodium hydroxide
30%
80 ℃
○○○○
Sodium hypochlorite
(30 or 180 days)
5%
80 ℃
○○
5%
80 ℃
-
Sodium hydroxide solution
30%
90 ℃
○○○○
Nitric acid
10%
23 ℃
○○○○
Hydrochloric acid
10%
80 ℃
-
Sulfuric acid
10%
23 ℃
○○○○
10%
80 ℃
○○
30%
23 ℃
○○○○
Tested fuels
80 ℃
○○○○
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
82
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
FAM testing fluid
acc. to DIN 51 604-A
Toluene
80 ℃
○○
1, 1, 1-Trichloroethane
Xylene
80 ℃
○○○○
Zinc chloride (saturated)
80 ℃
○○
75 ℃
○○○○
Explanation of the rating
○○○○
Resistant
○○○
Practically resistant
○○
Conditionally resistant
○
Less resistant
-
Not resistant
4.3.6.3
Polycarbonate (PC)
Table 4- 31
Chemical resistance - polycarbonate (PPS)
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Mineral lubricants
○○
Aliphatic hydrocarbons
○○○○
Aromatic hydrocarbons
-
Gasoline
-
Weak mineral acids
○○○○
Strong mineral acids
○○
Weak organic acids
○○○○
Strong organic acids
○○
Oxidizing acids
-
Weak alkaline solutions
-
Strong alkaline solutions
-
Trichloroethylene
-
Perchloroethylene
-
Acetone
-
Alcohols
○○
Hot water (hydrolysis resistance)
-
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
83
Explanation of the rating
○○○○
Resistant
○○○
Practically resistant
○○
Conditionally resistant
○
Less resistant
-
Not resistant
4.3.6.4
Polyvinyl chloride (PVC)
Table 4- 32
Chemical resistance - polyvinyl chloride (PVC)
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Salt water
5 %
○○○○
Sugared water
10 %
○○○○
Acetic acid, w.
5 %
○○○○
Sodium carbonate, w.
5 %
○○○○
Ethyl alcohol, w.
60 %
○○○○
Ethylene glycol
50 %
○○○○
Fuel B
(acc. to ISO 1817)
○○○○
Human sweat
○○○○
Explanation of the rating
○○○○
Resistant
○○○
Practically resistant
○○
Conditionally resistant
○
Less resistant
-
Not resistant
w.
Water solution
4.3.6.5
Epoxy resin
Table 4- 33
Chemical Resistance - epoxy resin
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Allyl chloride
20 ℃
○○○○
Formic acid
50 %
20 ℃
○○○○
100 %
20 ℃
○○
Ammonia, gaseous
20 ℃
○○○○
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
84
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Ammonia, liquid, water-free
20 ℃
-
Ammonium hydroxide
10 %
20 ℃
○○○○
Ethanol
40 ℃
○○○○
60 ℃
○○○○
Ethyl acrylate
20 ℃
○○○○
Ethyl glycol
60 ℃
○○○○
Gasoline, aroma-free
20 ℃
○○○○
Gasoline, containing benzene
20 ℃
○○○○
Benzoates (Na–, Ca– among others)
40 ℃
○○○○
Benzoic acid
20 ℃
○○○○
Benzene
20 ℃
○○○○
Borax
60 ℃
○○○○
Boric acid
20 ℃
○○○○
Bromine, liquid
20 ℃
-
Bromides (K–, Na– among others)
60 ℃
○○○○
Bromoform
100 %
20 ℃
○○○○
Bromine water
20 ℃
-
Butadiene (1,3–)
20 ℃
○○○○
Butane, gaseous
20 ℃
○○○○
Butanol
20 ℃
-
Butyric acid
100 %
20 ℃
○○
Carbonates (ammonium–, Na– among
others)
60 ℃
○○○○
Chlorine, liquid
20 ℃
-
Chlorine, gaseous, dry
100 %
20 ℃
-
Chlorobenzene
20 ℃
○○○○
Chlorides (ammonium–, Na– among
others)
60 ℃
○○○○
Chloroform
20 ℃
-
Chlorophyll
20 ℃
○○○○
Chlorosulfuric acid
100 %
20 ℃
-
Chlorine water (saturated solution)
20 ℃
○○
Chromates (K–, Na– among others)
Up to 50 %
40 ℃
○○○○
Chromic acid
Up to 30 %
20 ℃
-
Chromosulfuric acid
20 ℃
-
Citric acid
20 ℃
○○○○
Cyanamide
20 ℃
○○○○
Cyanides (K–, Na– among others)
60 ℃
○○○○
Dextrin, w.
60 ℃
○○○○
Diethyl ether
20 ℃
○○○○
Diethylene glycol
60 ℃
○○○○
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
85
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Dimethyl ether
20 ℃
○○○○
Dioxane
20 ℃
-
Developer
40 ℃
○○○○
Acetic acid
100 %
20 ℃
○○
Ethanol
60 ℃
○○○○
Fixing bath
40 ℃
○○○○
Fluorides (ammonium–, K–, Na–
among others)
40 ℃
○○○○
Hydrofluoric acid
Up to 40 %
20 ℃
○○○○
Formaldehyde
50 %
20 ℃
○○○○
Formamide
100 %
20 ℃
○○○○
Gluconic acid
20 ℃
○○○○
Glycerine
60 ℃
○○○○
Glycol
60 ℃
○○○○
Urine
20 ℃
○○○○
Uric acid
20 ℃
○○○○
Hydroxides (ammonium...)
10 %
20 ℃
○○○○
Hydroxides (Na–, K–)
40 %
20 ℃
○○○○
Hydroxides (alkaline earth metal)
60 ℃
○○○○
Hypochlorites (K–, Na– among others)
60 ℃
○○○○
Iodides (K–, Na– among others)
60 ℃
○○○○
Silicic acid
60 ℃
○○○○
Cresol
Up to 90 %
20 ℃
-
Methanol
100 %
40 ℃
○○○○
Methylene chloride
20 ℃
-
Lactic acid
100 %
20 ℃
○○
Mineral oils
40 ℃
○○○○
Nitrates (ammonium..., K– among
others)
60 ℃
○○○○
Nitroglycerin
20 ℃
-
Oxalic acid
20 ℃
○○○○
Phenol
1 %
20 ℃
○○○○
Phosphates (ammonium..., Na– among
others)
60 ℃
○○○○
Phosphoric acid
50 %
60 ℃
○○○○
85 %
20 ℃
○○○○
Propanol
20 ℃
○○○○
Nitric acid
25 %
20 ℃
-
Hydrochloric acid
10 %
20 ℃
-
Brine
60 ℃
-
Sulfur dioxide
100 %
20 ℃
○○
Carbon disulfide
100 %
20 ℃
-
RF200 system planning
4.3 Installation guidelines
SIMATIC RF200
86
System Manual, 07/2015, J31069-D0227-U001-A9-7618
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Sulfuric acid
40 %
20 ℃
-
Sulfurous acid
20 ℃
○○
Soap solution
60 ℃
○○○○
Sulphates (ammonium..., Na– among
others)
60 ℃
○○○○
Sulfites (ammonium..., Na– among
others)
60 ℃
-
Tar, aroma-free
60 ℃
○○○○
Turpentine
20 ℃
○○○○
Trichloroethylene
20 ℃
-
Hydrogen peroxide
30 %
20 ℃
○○○○
Tartaric acid
20 ℃
○○○○
Explanation of the rating
○○○○
Resistant
○○○
Practically resistant
○○
Conditionally resistant
○
Less resistant
-
Not resistant
4.3.6.6
PA6.6 GF30
Table 4- 34
Chemical resistance - PA6.6 GF30
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Mineral lubricants
○○○○
Aliphatic hydrocarbons
○○○○
Aromatic hydrocarbons
○○○○
Gasoline
○○○○
Weak mineral acids
○○○
Strong mineral acids
-
Weak organic acids
○○
Strong organic acids
-
Oxidizing acids
-
Weak alkaline solutions
○○
Strong alkaline solutions
-
Trichloroethylene
○○○○
Perchloroethylene
○○○○
Acetone
○○○○
RF200 system planning
4.4 Further information
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
87
Substance
Test conditions
Rating
Concentration [%]
Temperature [°C]
Alcohols
○○○○
Hot water (hydrolysis resistance)
○○
Explanation of the rating
○○○○
Resistant
○○○
Practically resistant
○○
Conditionally resistant
○
Less resistant
-
Not resistant
4.4
Further information
Further information on "Fundamentals of application planning" and "EMC" can be found in
RF300 system manual (https://support.industry.siemens.com/cs/ww/en/view/21738946).
RF200 system planning
4.4 Further information
SIMATIC RF200
88
System Manual, 07/2015, J31069-D0227-U001-A9-7618
System Manual, 07/2015, J31069-D0227-U001-A9-7618
89
Readers
5
NOTICE
Pulling and plugging readers
Pull or plug the reader only when the power supply is turned off
If this is not observed, under certain conditions, the reader will not start up correctly and
communication with a transponder will not be possible.
Note
IO-Link variants of the RF200 readers
The IO-Link variants of the readers are not included in the system manual. You will find
these in the "SIMATIC RF200 IO-Link
(https://support.industry.siemens.com/cs/ww/en/view/60641859)" operating instructions.
5.1 SIMATIC RF210R
SIMATIC RF200
90
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5.1
SIMATIC RF210R
5.1.1
Features
SIMATIC RF210R
Characteristics
Design
① RS422 interface
② Status display
Application
Identification tasks on assembly lines in harsh in-
dustrial environments
5.1.2
RF210R ordering data
Article number
RF210R with RS422 interface (3964R)
6GT2821-1AC10
5.1 SIMATIC RF210R
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
91
5.1.3
Pin assignment RF210R with RS422 interface
Pin
Pin
Device end
8-pin M12
Assignment
1
+ 24 V
2
- Transmit
3
0 V
4
+ Transmit
5
+ Receive
6
- Receive
7
Unassigned
8
Ground (shield)
5.1.4
Display elements of the RF210R reader
Color
Meaning
green
flashing
Operating voltage present, reader not initialized or antenna switched off
permanently
lit
Operating voltage present, reader initialized and antenna switched on
yellow1)
Transponder present
flashing red
Error has occurred, the type of flashing corresponds to the error code in the
table in the section "Error codes". The optical error display is only reset if the
corresponding reset parameter ("option_1 = 2") is set (see Product infor-
mation "SIMATIC RF200 command set"
(https://support.industry.siemens.com/cs/us/en/view/44864850)).
1) Only in the "with presence" mode.
5.1 SIMATIC RF210R
SIMATIC RF200
92
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5.1.5
Minimum distance between RF210R readers
RF210R side by side
D ≥ 60 mm
Figure 5-1
Minimum distance between RF210R readers
RF210R face to face
D
≥ 100 mm
Figure 5-2
Face-to-face distance between two RF210Rs
5.1 SIMATIC RF210R
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
93
5.1.6
Technical specifications of the RF210R reader
Table 5- 1
Technical specifications of the RF210R reader
6GT2821-1AC10
Product type designation
SIMATIC RF210R
Radio frequencies
Operating frequency, rated value
13.56 MHz
Electrical data
Maximum range
20 mm
Maximum data transmission rate reader ↔ tran-
sponder (tag)
ISO tags
•
Read
•
approx. 1500 bytes/s
•
Write
•
approx. 1500 bytes/s
Typical transmission time for user data per byte
•
for write access
•
0.6 ms
•
for read access
•
0.6 ms
Baud rate
19200, 57600, 115200 Bd
Read/write distances of the reader
see section "Field data (Page 37)"
Interfaces
Electrical connector design
M8, 8-pin
Standard for interfaces for communication
RS-422
Antenna
integrated
Mechanical specifications
Housing
•
Material
•
Brass, nickel-plated
•
Color
•
Silver
Recommended distance to metal
0 mm
Supply voltage, current consumption, power loss
Supply voltage
24 VDC
Typical current consumption
50 mA
5.1 SIMATIC RF210R
SIMATIC RF200
94
System Manual, 07/2015, J31069-D0227-U001-A9-7618
6GT2821-1AC10
Permitted ambient conditions
Ambient temperature
•
During operation
•
-20 … +70 °C
•
During transportation and storage
•
-25 … +85 °C
Degree of protection to EN 60529
IP67
Shock-resistant to EN 60721-3-7, Class 7 M3
50 g
Vibration-resistant to EN 60721-3-7, Class 7 M3
20 g
Torsion and bending load
Not permitted
Design, dimensions and weights
Dimensions (Ø x H)
18 x 83 mm
Weight
65 g
Type of mounting
2 x nuts M18
Cable length for RS-422 interface, maximum
1000 m
LED display design
3-color LED
(operating voltage, presence, error)
5.1.7
Approvals
FCC information
Siemens SIMATIC RF210R (MLFB 6GT2821-1AC10) FCC ID NXW-RF210R
This device complies with part 15 of the FCC rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause
undesired operation.
Caution
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Note
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
5.1 SIMATIC RF210R
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
95
IC information
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is
subject to the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause
undesired operation of the device.
Le présent appareil est conforme aux CNR d`Industrie Canada applicables aux appareils
radio exempts de licence. L`exploitation est autorisée aux deux conditions suivantes :
(1) L`appareil ne doit pas produire de brouillage, et
(2) l'utilisateur de l`appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d`en compromettre le fonctionnement.
5.1.8
Dimension drawing
Figure 5-3
RF210R dimension drawing
Dimensions in mm
5.2 SIMATIC RF210M
SIMATIC RF200
96
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5.2
SIMATIC RF210M
5.2.1
Features
SIMATIC RF210M
Characteristics
Design
① RS422 interface
② Status display
Application
Reader for hand work and rework places, picking,
track and trace, tool Ident
5.2.2
Ordering data RF210M
Article number
RF210M with RS-422 interface (3964R)
6GT2823-0AA00
5.2 SIMATIC RF210M
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
97
5.2.3
Installing the RF210M reader
The following figure shows the completely mounted reader. Note that you can mount the
suspension bracket at two different points ①. If you do not mount the handle, we
recommend that you close the opening ② with the protective cap.
①
Holes for mounting the suspension bracket
②
Thread for mounting the handle
Figure 5-4
Installing the reader
5.2.4
Pin assignment RF210M with RS-422 interface
Pin
Pin
Device end
8-pin M12
Assignment
1
+ 24 V
2
- Transmit
3
0 V
4
+ Transmit
5
+ Receive
6
- Receive
7
Unassigned
8
Ground (shield)
5.2 SIMATIC RF210M
SIMATIC RF200
98
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5.2.5
Display elements of the RF210M reader
Color
Meaning
green
flashing
Operating voltage present, reader not initialized or antenna switched off
permanently
lit
Operating voltage present, reader initialized and antenna switched on
yellow1)
Transponder present
flashing red
Error has occurred, the type of flashing corresponds to the error code in the
table in the section "Error codes". The optical error display is only reset if the
corresponding reset parameter ("option_1 = 2") is set (see Product infor-
mation "SIMATIC RF200 command set"
(https://support.industry.siemens.com/cs/ww/en/view/44864850)).
1) Only in the "with presence" mode.
5.2.6
Technical specifications of the RF210M reader
Table 5- 2
Technical specifications of the RF210M reader
6GT2823-0AA00
Product type designation
SIMATIC RF210M
Radio frequencies
Operating frequency, rated value
13.56 MHz
Electrical data
Maximum range
20 mm
Maximum data transmission rate reader ↔ tran-
sponder (tag)
ISO tags
•
Read
•
approx. 1500 bytes/s
•
Write
•
approx. 1500 bytes/s
Typical transmission time for user data per byte
•
for write access
•
0.6 ms
•
for read access
•
0.6 ms
Baud rate
19200, 57600, 115200 Bd
Read/write distances of the reader
see section "Field data (Page 37)"
Interfaces
Electrical connector design
M8, 8-pin
Standard for interfaces for communication
RS-422
Antenna
integrated
5.2 SIMATIC RF210M
SIMATIC RF200
System Manual, 07/2015, J31069-D0227-U001-A9-7618
99
6GT2823-0AA00
Mechanical specifications
Housing
•
Material
•
POM
•
Color
•
Black
Supply voltage, current consumption, power loss
Supply voltage
24 VDC
Typical current consumption
50 mA
Permitted ambient conditions
Ambient temperature
•
During operation
•
-20 … +50 °C
•
During transportation and storage
•
-25 … +60 °C
Degree of protection to EN 60529
IP54
Shock-resistant to EN 60721-3-7, Class 7 M3
50 g
Vibration-resistant to EN 60721-3-7, Class 7 M3
20 g
Design, dimensions and weights
Dimensions
•
Reader with handle (L x W x H)
195 x 26 x 140 mm
•
Reader without handle (L x W x H)
195 x 26 x 46 mm
•
Spiral connecting cable (L)
2 m
maximum working length 3.5 m
Weight
460 g
Type of mounting
Bracket for for hanging up
Cable length for RS-422 interface, maximum
1000 m
LED display design
3-color LED
(operating voltage, presence, error)
5.2 SIMATIC RF210M
SIMATIC RF200
100
System Manual, 07/2015, J31069-D0227-U001-A9-7618
5.2.7
Approvals
FCC information
Siemens SIMATIC RF210R (MLFB 6GT2821-1AC10) FCC ID NXW-RF210R
This device complies with part 15 of the FCC rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause
undesired operation.
Caution
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Note
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
IC information
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is
subject to the following two conditions:
(1) This device may not cause interference, and
(2) this device must accept any interference, including interference that may cause
undesired operation of the device.
Le présent appareil est conforme aux CNR d`Industrie Canada applicables aux appareils
radio exempts de licence. L`exploitation est autorisée aux deux conditions suivantes :
(1) L`appareil ne doit pas produire de brouillage, et
(2) l'utilisateur de l`appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d`en compromettre le fonctionnement.