RF200 system planning

4 Readers 5 Antennas 6 Transponder 7 System integration 8 System diagnostics 9 Appendix A

Division Process Industries and Drives

Postfach 48 48 90026 NÜRNBERG GERMANY J31069-D0227-U001-A8-7618 Ⓟ 07/2015 Subject to change Copyright © Siemens AG 2010 - 2015. All rights reserved Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

System Manual, 07/2015, J31069-D0227-U001-A9-7618

5 Table of contents 1 Introduction ........................................................................................................................................... 15 1.1 Abbreviations and naming conventions .................................................................................. 16 2 Safety notes .......................................................................................................................................... 17 3 System overview ................................................................................................................................... 19 3.1 RFID components and their function ...................................................................................... 20 3.2 Overview of transponders ....................................................................................................... 23 4 RF200 system planning......................................................................................................................... 25 4.1 Fundamentals of application planning .................................................................................... 25 4.1.1 Selection criteria for SIMATIC RF200 components ................................................................ 25 4.1.2 Transmission window and read/write distance ....................................................................... 25 4.1.3 Width of the transmission window .......................................................................................... 28 4.1.4 Impact of secondary fields ...................................................................................................... 29 4.1.5 Permissible directions of motion of the transponder ............................................................... 32 4.1.6 Operation in static and dynamic mode ................................................................................... 33 4.1.7 Dwell time of the transponder ................................................................................................. 34 4.1.8 Communication between communication module, reader and transponder .......................... 35 4.2 Field data of transponders and readers .................................................................................. 36 4.2.1 Field data ................................................................................................................................ 37 4.2.2 Minimum clearances ............................................................................................................... 44 4.3 Installation guidelines.............................................................................................................. 47 4.3.1 Overview ................................................................................................................................. 47 4.3.2 Reduction of interference due to metal ................................................................................... 47 4.3.3 Effects of metal on different transponders and readers .......................................................... 49 4.3.4 Impact of metal on the transmission window .......................................................................... 50 4.3.4.1 RF210R ................................................................................................................................... 51 4.3.4.2 RF220R ................................................................................................................................... 54 4.3.4.3 RF240R ................................................................................................................................... 56 4.3.4.4 RF250R ................................................................................................................................... 59 4.3.4.5 RF260R ................................................................................................................................... 65 4.3.4.6 RF290R ................................................................................................................................... 67 4.3.5 Installation and connection of 2 to 6 antennas with one RF290R reader ............................... 71 4.3.5.1 Installation options with the antenna splitter (2-4 antennas) .................................................. 72 4.3.5.2 Antenna installation ................................................................................................................. 75 4.3.5.3 Installation options with the antenna multiplexer (2-6 antennas) ........................................... 79 4.3.6 Chemical resistance of the transponders ............................................................................... 80 4.3.6.1 Overview of the transponders and their housing materials .................................................... 80 4.3.6.2 Polyphenylene sulfide (PPS) .................................................................................................. 81 4.3.6.3 Polycarbonate (PC) ................................................................................................................. 82 4.3.6.4 Polyvinyl chloride (PVC) ......................................................................................................... 83 4.3.6.5 Epoxy resin ............................................................................................................................. 83 4.3.6.6 PA6.6 GF30 ............................................................................................................................ 86

Table of contents

SIMATIC RF200 6 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.4 Further information ................................................................................................................. 87 5 Readers ................................................................................................................................................ 89 5.1 SIMATIC RF210R .................................................................................................................. 90 5.1.1 Features ................................................................................................................................. 90 5.1.2 RF210R ordering data ........................................................................................................... 90 5.1.3 Pin assignment RF210R with RS422 interface ...................................................................... 91 5.1.4 Display elements of the RF210R reader ................................................................................ 91 5.1.5 Minimum distance between RF210R readers ........................................................................ 92 5.1.6 Technical specifications of the RF210R reader ..................................................................... 93 5.1.7 Approvals ............................................................................................................................... 94 5.1.8 Dimension drawing ................................................................................................................ 95 5.2 SIMATIC RF210M .................................................................................................................. 96 5.2.1 Features ................................................................................................................................. 96 5.2.2 Ordering data RF210M .......................................................................................................... 96 5.2.3 Installing the RF210M reader ................................................................................................. 97 5.2.4 Pin assignment RF210M with RS-422 interface .................................................................... 97 5.2.5 Display elements of the RF210M reader ............................................................................... 98 5.2.6 Technical specifications of the RF210M reader ..................................................................... 98 5.2.7 Approvals ............................................................................................................................. 100 5.2.8 Dimension drawing .............................................................................................................. 101 5.3 SIMATIC RF220R ................................................................................................................ 102 5.3.1 Features ............................................................................................................................... 102 5.3.2 RF220R ordering data ......................................................................................................... 102 5.3.3 RF220R pin assignment with RS422 interface .................................................................... 103 5.3.4 Display elements of the RF220R reader .............................................................................. 103 5.3.5 Minimum distance between RF220R readers ...................................................................... 104 5.3.6 Technical specifications of the RF220R reader ................................................................... 105 5.3.7 Approvals ............................................................................................................................. 106 5.3.8 Dimension drawing .............................................................................................................. 107 5.4 SIMATIC RF240R ................................................................................................................ 108 5.4.1 Features ............................................................................................................................... 108 5.4.2 RF240R ordering data ......................................................................................................... 108 5.4.3 Pin assignment RF240R ...................................................................................................... 109 5.4.4 Display elements of the RF240R reader .............................................................................. 109 5.4.5 Minimum distance between several RF240R readers ......................................................... 110 5.4.6 Technical specifications of the RF240R reader ................................................................... 111 5.4.7 Approvals ............................................................................................................................. 113 5.4.8 Dimension drawing .............................................................................................................. 114 5.5 SIMATIC RF250R ................................................................................................................ 115 5.5.1 Features ............................................................................................................................... 115 5.5.2 Ordering data RF250R ......................................................................................................... 115 5.5.3 Pin assignment RF250R ...................................................................................................... 116 5.5.4 Display elements of the RF250R reader .............................................................................. 116 5.5.5 Technical specifications of the RF250R reader ................................................................... 117 5.5.6 Approvals ............................................................................................................................. 118 5.5.7 Dimension drawing .............................................................................................................. 120 5.6 SIMATIC RF260R ................................................................................................................ 121 5.6.1 Features ............................................................................................................................... 121 5.6.2 Ordering data for RF260R ................................................................................................... 121

Table of contents

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 7 5.6.3 Pin assignment RF260R ....................................................................................................... 122 5.6.4 Display elements of the RF260R reader ............................................................................... 122 5.6.5 Minimum distance between several RF260R ....................................................................... 123 5.6.6 Technical data of the RF260R reader................................................................................... 124 5.6.7 Approvals .............................................................................................................................. 126 5.6.8 Dimension drawing ............................................................................................................... 127 5.7 SIMATIC RF290R ................................................................................................................. 128 5.7.1 Features ................................................................................................................................ 128 5.7.2 Ordering data RF290R.......................................................................................................... 129 5.7.3 Pin assignment RF290R ....................................................................................................... 130 5.7.4 Display elements of the RF290R reader ............................................................................... 132 5.7.5 Installing the RF290R reader ................................................................................................ 133 5.7.5.1 Wall mounting ....................................................................................................................... 133 5.7.5.2 Installing on the S7-300 standard rail ................................................................................... 134 5.7.5.3 Installation on a DIN rail ........................................................................................................ 134 5.7.6 Technical specifications of the RF290R reader .................................................................... 136 5.7.7 Approvals .............................................................................................................................. 137 5.7.8 Note on the use of the RF290R as a replacement for SLG D10 / SLG D10S ...................... 139 5.7.9 Dimension drawing ............................................................................................................... 140 6 Antennas ............................................................................................................................................ 141 6.1 ANT 3 .................................................................................................................................... 142 6.1.1 Features ................................................................................................................................ 142 6.1.2 Ordering data ........................................................................................................................ 142 6.1.3 Mounting on/in metal............................................................................................................. 143 6.1.4 Operating / limit distances .................................................................................................... 144 6.1.5 Minimum spacing .................................................................................................................. 144 6.1.6 Technical data ....................................................................................................................... 146 6.1.7 Dimension drawing ............................................................................................................... 147 6.2 ANT 8 .................................................................................................................................... 148 6.2.1 Features ................................................................................................................................ 148 6.2.2 Ordering data ........................................................................................................................ 148 6.2.3 Transmission window............................................................................................................ 149 6.2.4 Flush-mounted in metal ........................................................................................................ 149 6.2.5 Minimum spacing .................................................................................................................. 150 6.2.6 Technical data ....................................................................................................................... 151 6.2.7 Dimension drawing ............................................................................................................... 152 6.3 ANT 12 .................................................................................................................................. 153 6.3.1 Features ................................................................................................................................ 153 6.3.2 Ordering data ........................................................................................................................ 153 6.3.3 Transmission window............................................................................................................ 154 6.3.4 Flush-mounted in metal ........................................................................................................ 154 6.3.5 Minimum spacing .................................................................................................................. 155 6.3.6 Technical data ....................................................................................................................... 156 6.3.7 Dimension drawing ............................................................................................................... 157 6.4 ANT 18 .................................................................................................................................. 158 6.4.1 Features ................................................................................................................................ 158 6.4.2 Ordering data ........................................................................................................................ 158 6.4.3 Transmission window............................................................................................................ 159 6.4.4 Flush-mounted in metal ........................................................................................................ 159

Table of contents

SIMATIC RF200 8 System Manual, 07/2015, J31069-D0227-U001-A9-7618 6.4.5 Minimum spacing ................................................................................................................. 160 6.4.6 Technical data ...................................................................................................................... 161 6.4.7 Dimension drawing .............................................................................................................. 162 6.5 ANT 30 ................................................................................................................................. 163 6.5.1 Features ............................................................................................................................... 163 6.5.2 Ordering data ....................................................................................................................... 163 6.5.3 Transmission window ........................................................................................................... 164 6.5.4 Flush-mounted in metal ....................................................................................................... 165 6.5.5 Minimum spacing ................................................................................................................. 165 6.5.6 Technical data ...................................................................................................................... 167 6.5.7 Dimension drawing .............................................................................................................. 168 6.6 ANT D5 ................................................................................................................................ 169 6.6.1 Features ............................................................................................................................... 169 6.6.2 Ordering data ....................................................................................................................... 169 6.6.3 Transmission window ........................................................................................................... 170 6.6.4 Flush-mounted in metal ....................................................................................................... 171 6.6.5 Minimum spacing ................................................................................................................. 171 6.6.6 Technical data ...................................................................................................................... 173 6.6.7 Dimension drawing .............................................................................................................. 174 6.7 ANT D6 ................................................................................................................................ 175 6.7.1 Features ............................................................................................................................... 175 6.7.2 Ordering data ....................................................................................................................... 175 6.7.3 Transmission window ........................................................................................................... 176 6.7.4 Metal-free area ..................................................................................................................... 177 6.7.5 Minimum spacing ................................................................................................................. 177 6.7.6 Technical data ...................................................................................................................... 178 6.7.7 Dimensional diagram ........................................................................................................... 179 6.8 ANT D10 .............................................................................................................................. 180 6.8.1 Features ............................................................................................................................... 180 6.8.2 Ordering data ....................................................................................................................... 180 6.8.3 Transmission window ........................................................................................................... 181 6.8.4 Metal-free area ..................................................................................................................... 182 6.8.5 Minimum spacing ................................................................................................................. 183 6.8.6 Technical data ...................................................................................................................... 184 6.8.7 Dimensional diagram ........................................................................................................... 185 7 Transponder ........................................................................................................................................ 187 7.1 Memory configuration of ISO the transponders ................................................................... 187 7.2 MDS D100 ............................................................................................................................ 188 7.2.1 Characteristics ..................................................................................................................... 188 7.2.2 Ordering data ....................................................................................................................... 189 7.2.3 Metal-free area ..................................................................................................................... 189 7.2.4 Technical data ...................................................................................................................... 191 7.2.5 Dimension drawing .............................................................................................................. 192 7.3 MDS D117 ............................................................................................................................ 193 7.3.1 Features ............................................................................................................................... 193 7.3.2 Ordering data ....................................................................................................................... 193 7.3.3 Mounting in metal ................................................................................................................. 193 7.3.4 Technical specifications ....................................................................................................... 194

Table of contents

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 9 7.3.5 Dimension drawing ............................................................................................................... 195 7.4 MDS D124 ............................................................................................................................ 196 7.4.1 Characteristics ...................................................................................................................... 196 7.4.2 Ordering data ........................................................................................................................ 196 7.4.3 Mounting on metal ................................................................................................................ 197 7.4.4 Technical specifications ........................................................................................................ 198 7.4.5 Use of the MDS D124 in hazardous area ............................................................................. 199 7.4.6 Dimension drawing ............................................................................................................... 201 7.5 MDS D126 ............................................................................................................................ 201 7.5.1 Characteristics ...................................................................................................................... 201 7.5.2 Ordering data ........................................................................................................................ 202 7.5.3 Technical specifications ........................................................................................................ 202 7.5.4 Dimension drawing ............................................................................................................... 203 7.6 MDS D127 ............................................................................................................................ 204 7.6.1 Features ................................................................................................................................ 204 7.6.2 Ordering data ........................................................................................................................ 204 7.6.3 Mounting in metal .................................................................................................................. 205 7.6.4 Technical specifications ........................................................................................................ 206 7.6.5 Dimension drawing ............................................................................................................... 207 7.7 MDS D139 ............................................................................................................................ 208 7.7.1 Characteristics ...................................................................................................................... 208 7.7.2 Ordering data ........................................................................................................................ 208 7.7.3 Metal-free area ...................................................................................................................... 209 7.7.4 Mounting in metal .................................................................................................................. 210 7.7.5 Cleaning the transponder ..................................................................................................... 210 7.7.6 Technical specifications ........................................................................................................ 211 7.7.7 Use of the MDS D139 in hazardous areas ........................................................................... 212 7.7.8 Dimension drawings .............................................................................................................. 214 7.8 MDS D160 ............................................................................................................................ 215 7.8.1 Characteristics ...................................................................................................................... 215 7.8.2 Ordering data ........................................................................................................................ 215 7.8.3 Mounting on metal ................................................................................................................ 216 7.8.4 Technical specifications ........................................................................................................ 217 7.8.5 Dimension drawings .............................................................................................................. 219 7.9 MDS D165 ............................................................................................................................ 220 7.9.1 Features ................................................................................................................................ 220 7.9.2 Ordering data ........................................................................................................................ 220 7.9.3 Technical data ....................................................................................................................... 221 7.9.4 Dimension drawing ............................................................................................................... 222 7.10 MDS D200 ............................................................................................................................ 223 7.10.1 Features ................................................................................................................................ 223 7.10.2 Ordering data ........................................................................................................................ 223 7.10.3 Mounting on metal ................................................................................................................ 224 7.10.4 Technical data ....................................................................................................................... 225 7.10.5 Dimension drawing ............................................................................................................... 227 7.11 MDS D261 ............................................................................................................................ 227 7.11.1 Features ................................................................................................................................ 227 7.11.2 Ordering data ........................................................................................................................ 227

Table of contents

SIMATIC RF200 10 System Manual, 07/2015, J31069-D0227-U001-A9-7618 7.11.3 Technical data ...................................................................................................................... 228 7.11.4 Dimension drawing .............................................................................................................. 229 7.12 MDS D324 ............................................................................................................................ 230 7.12.1 Characteristics ..................................................................................................................... 230 7.12.2 Ordering data ....................................................................................................................... 230 7.12.3 Metal-free area ..................................................................................................................... 231 7.12.4 Technical specifications ....................................................................................................... 232 7.12.5 Dimension drawing .............................................................................................................. 233 7.13 MDS D339 ............................................................................................................................ 234 7.13.1 Characteristics ..................................................................................................................... 234 7.13.2 Ordering data ....................................................................................................................... 234 7.13.3 Mounting on metal ............................................................................................................... 235 7.13.4 Mounting in metal ................................................................................................................. 236 7.13.5 Cleaning the transponder ..................................................................................................... 236 7.13.6 Technical specifications ....................................................................................................... 237 7.13.7 Use of the MDS D339 in hazardous areas .......................................................................... 238 7.13.8 Dimensional drawing ............................................................................................................ 240 7.14 MDS D400 ............................................................................................................................ 241 7.14.1 Features ............................................................................................................................... 241 7.14.2 Ordering data ....................................................................................................................... 241 7.14.3 Mounting on metal ............................................................................................................... 242 7.14.4 Technical specifications ....................................................................................................... 243 7.14.5 Dimension drawing .............................................................................................................. 245 7.15 MDS D421 ............................................................................................................................ 246 7.15.1 Characteristics ..................................................................................................................... 246 7.15.2 Ordering data ....................................................................................................................... 246 7.15.3 Mounting on metal ............................................................................................................... 247 7.15.4 Technical specifications ....................................................................................................... 249 7.15.5 Dimension drawing .............................................................................................................. 250 7.16 MDS D422 ............................................................................................................................ 251 7.16.1 Characteristics ..................................................................................................................... 251 7.16.2 Ordering data ....................................................................................................................... 251 7.16.3 Mounting in metal ................................................................................................................. 251 7.16.4 Technical specifications ....................................................................................................... 252 7.16.5 Dimension drawing .............................................................................................................. 253 7.17 MDS D423 ............................................................................................................................ 254 7.17.1 Characteristics ..................................................................................................................... 254 7.17.2 Ordering data ....................................................................................................................... 254 7.17.3 Mounting on metal ............................................................................................................... 255 7.17.4 Technical specifications ....................................................................................................... 256 7.17.5 Dimensional drawing ............................................................................................................ 258 7.18 MDS D424 ............................................................................................................................ 258 7.18.1 Characteristics ..................................................................................................................... 258 7.18.2 Ordering data ....................................................................................................................... 259 7.18.3 Mounting on metal ............................................................................................................... 259 7.18.4 Technical specifications ....................................................................................................... 260 7.18.5 Dimension drawing .............................................................................................................. 262

Table of contents

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 11 7.19 MDS D425 ............................................................................................................................ 262 7.19.1 Characteristics ...................................................................................................................... 262 7.19.2 Ordering data ........................................................................................................................ 263 7.19.3 Application example of MDS D425 ....................................................................................... 263 7.19.4 Technical specifications ........................................................................................................ 264 7.19.5 Dimension drawing ............................................................................................................... 265 7.20 MDS D426 ............................................................................................................................ 266 7.20.1 Characteristics ...................................................................................................................... 266 7.20.2 Ordering data ........................................................................................................................ 266 7.20.3 Technical specifications ........................................................................................................ 267 7.20.4 Dimension drawing ............................................................................................................... 268 7.21 MDS D428 ............................................................................................................................ 269 7.21.1 Characteristics ...................................................................................................................... 269 7.21.2 Ordering data ........................................................................................................................ 269 7.21.3 Application example .............................................................................................................. 270 7.21.4 Technical specifications ........................................................................................................ 270 7.21.5 Dimension drawing ............................................................................................................... 272 7.22 MDS D460 ............................................................................................................................ 272 7.22.1 Characteristics ...................................................................................................................... 272 7.22.2 Ordering data ........................................................................................................................ 273 7.22.3 Mounting on metal ................................................................................................................ 273 7.22.4 Technical specifications ........................................................................................................ 274 7.22.5 Dimension drawings .............................................................................................................. 275 7.23 MDS D521 ............................................................................................................................ 276 7.23.1 Characteristics ...................................................................................................................... 276 7.23.2 Ordering data ........................................................................................................................ 276 7.23.3 Mounting on metal ................................................................................................................ 276 7.23.4 Technical specifications ........................................................................................................ 279 7.23.5 Dimension drawing ............................................................................................................... 280 7.24 MDS D522 ............................................................................................................................ 281 7.24.1 Characteristics ...................................................................................................................... 281 7.24.2 Ordering data ........................................................................................................................ 281 7.24.3 Mounting in metal .................................................................................................................. 281 7.24.4 Technical specifications ........................................................................................................ 282 7.24.5 Dimension drawing ............................................................................................................... 283 7.25 MDS D522 special variant .................................................................................................... 284 7.25.1 Characteristics ...................................................................................................................... 284 7.25.2 Ordering data ........................................................................................................................ 284 7.25.3 Mounting in metal .................................................................................................................. 285 7.25.4 Installation instructions.......................................................................................................... 286 7.25.5 Technical specifications ........................................................................................................ 287 7.25.6 Dimensional drawing............................................................................................................. 288 7.26 MDS D524 ............................................................................................................................ 289 7.26.1 Characteristics ...................................................................................................................... 289 7.26.2 Ordering data ........................................................................................................................ 289 7.26.3 Mounting on metal ................................................................................................................ 290 7.26.4 Technical specifications ........................................................................................................ 291 7.26.5 Dimension drawing ............................................................................................................... 292

Table of contents

SIMATIC RF200 12 System Manual, 07/2015, J31069-D0227-U001-A9-7618 7.27 MDS D526 ............................................................................................................................ 293 7.27.1 Characteristics ..................................................................................................................... 293 7.27.2 Ordering data ....................................................................................................................... 293 7.27.3 Technical specifications ....................................................................................................... 294 7.27.4 Dimension drawing .............................................................................................................. 295 7.28 MDS D528 ............................................................................................................................ 296 7.28.1 Characteristics ..................................................................................................................... 296 7.28.2 Ordering data ....................................................................................................................... 296 7.28.3 Application example ............................................................................................................. 297 7.28.4 Technical specifications ....................................................................................................... 297 7.28.5 Dimension drawing .............................................................................................................. 299 8 System integration ............................................................................................................................... 301 9 System diagnostics .............................................................................................................................. 305 9.1 Error codes of the RF200 readers ....................................................................................... 305 9.2 Diagnostic functions ............................................................................................................. 306 9.2.1 Reader diagnostics with SLG STATUS ............................................................................... 306 9.2.2 Transponder diagnostics with MDS STATUS ...................................................................... 308 A Appendix ............................................................................................................................................. 309 A.1 Certificates and approvals ................................................................................................... 309 A.2 Accessories .......................................................................................................................... 311 A.2.1 Antenna splitter .................................................................................................................... 311 A.2.2 Antenna multiplexer SIMATIC RF260X ............................................................................... 313 A.2.2.1 Characteristics ..................................................................................................................... 313 A.2.2.2 Ordering data ....................................................................................................................... 313 A.2.2.3 Description ........................................................................................................................... 314 A.2.2.4 Principle of operation ........................................................................................................... 314 A.2.2.5 Connectors ........................................................................................................................... 315 A.2.2.6 Configuration ........................................................................................................................ 316 A.2.2.7 Parameterization .................................................................................................................. 317 A.2.2.8 RF260X commands ............................................................................................................. 318 A.2.2.9 Technical specifications ....................................................................................................... 319 A.2.2.10 Dimensional drawing ............................................................................................................ 320 A.2.3 Wide-range power supply unit for SIMATIC RF systems .................................................... 321 A.2.3.1 Features ............................................................................................................................... 321 A.2.3.2 Scope of supply.................................................................................................................... 322 A.2.3.3 Ordering data ....................................................................................................................... 322 A.2.3.4 Safety Information ................................................................................................................ 322 A.2.3.5 Connecting ........................................................................................................................... 323 A.2.3.6 Technical specifications ....................................................................................................... 324 A.2.3.7 Pin assignment of DC outputs and mains connection ......................................................... 326 A.2.3.8 Dimension drawing .............................................................................................................. 327 A.2.3.9 Certificates and approvals ................................................................................................... 328 A.2.4 Transponder holders ............................................................................................................ 329 A.3 Connecting cable ................................................................................................................. 335 A.3.1 Reader RF2xxR (RS-422) with ASM 456 / RF160C / RF170C / RF180C / RF182C .......... 335 A.3.2 Reader RF2xxR (RS-422) with ASM 475 ............................................................................ 337 A.3.3 Reader RF2xxR (RS-422) with RF120C .............................................................................. 338 A.3.4 Reader RF240R/RF260R/RF290R (RS232) with PC .......................................................... 338

Table of contents

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 13 A.4 Ordering data ........................................................................................................................ 340 A.5 Service & Support ................................................................................................................. 350 Glossary ............................................................................................................................................. 353 Index................................................................................................................................................... 359

System Manual, 07/2015, J31069-D0227-U001-A9-7618

15 Introduction 1 Introduction SIMATIC RF200 is a compact RFID system in the SIMATIC RFID product family. The product range comprises cost-efficient RF readers that are ideal for use in small assembly lines or in intralogistics. SIMATIC RF200 RFID readers only support the RFID standard ISO 15693 and are therefore ideal for operation with the extensive range of ISO 15693 transponders. The readers of the RF200 product family are available with the following interfaces: ● RS-422 for connecting to the communications modules ● RS-232 with a simple ASCII protocol for connection to PCs and third-party controllers ● IO-Link for connection to IO Link masters from Siemens and third-party controllers Readers with an internal antenna have a particularly compact design (RF210R/RF220R/RF240R/RF260R). RF250R and RF290R are designed for operation with external antennas either to achieve longer distances or larger field sizes (RF290R with ANT D5/D6/D10) or to allow installation where there is very little space (RF250R with ANT 3/8/12/18/30). Scope of validity of this document This documentation is valid for all variants of the SIMATIC RF200 system and describes the devices shipped as of July 2015. Registered trademarks SIMATIC ®, SIMATIC RF ®, MOBY ®, RF MANAGER ® and SIMATIC Sensors ® are registered trademarks of Siemens AG. Further information For additional information, refer to the manuals: ● Function manual "Ident profile and Ident blocks" (https://support.industry.siemens.com/cs/us/en/view/106368029) ● Function manual "FB 45" (https://support.industry.siemens.com/cs/ww/en/view/21738808) ● Operating instructions "RF200 IO-Link" (https://support.industry.siemens.com/cs/ww/en/view/60641859) ● System manual "MOBY D" (https://support.industry.siemens.com/cs/ww/en/view/13628689)

1.1 Abbreviations and naming conventions

SIMATIC RF200 16 System Manual, 07/2015, J31069-D0227-U001-A9-7618 ● Operating instructions "RF310M" (https://support.industry.siemens.com/cs/us/en/view/51812642) ● Product information "RF200 command set" (https://support.industry.siemens.com/cs/us/en/view/44864850) History The following issues of the SIMATIC RF200 system manual have been published: Output Note 03/2011 First edition 05/2011 Expansion of the documentation with the addition of the device variant RF260R with RS-232 interface 09/2011 Expansion of the documentation with the device variant RF240R 03/2013 Expansion of the documentation with the device variant RF290R 09/2013 Expansion of the documentation by the following: • the device variant RF250R • the device variants RF240R and RF260R with ASCII interface • Antennas ANT 8, ANT 12, ANT 18 and ANT 30 • Transponders 07/2015 Expansion of the documentation by the following: • ANT 3 antennas • MDS D5xx transponder • Mobile reader RF210R 1.1 Abbreviations and naming conventions The following terms/abbreviations are used synonymously in this document: Write/read device (SLG) Readers Mobile data storage unit (MDS) Transponder, tag Interface module (ASM) Communications module (CM)

System Manual, 07/2015, J31069-D0227-U001-A9-7618

17 Safety notes 2 SIMATIC RFID products comply with the salient safety specifications to IEC, VDE, EN, UL and CSA. If you have questions about the validity of the installation in the planned environment, please contact your service representative. NOTICE Alterations to the devices are not permitted. Failure to observe this requirement shall constitute a revocation of the radio equipment approval, CE approval and manufacturer's warranty. Repairs Repairs may only be carried out by authorized qualified personnel. WARNING Unauthorized opening of and improper repairs to the device may result in substantial damage to equipment or risk of personal injury to the user. System expansion Only install system expansion devices designed for this device. If you install other upgrades, you may damage the system or violate the safety requirements and regulations for radio frequency interference suppression. Contact your technical support team or your sales outlet to find out which system upgrades are suitable for installation. NOTICE If you cause system defects by installing or exchanging system expansion devices, the warranty becomes void.

System Manual, 07/2015, J31069-D0227-U001-A9-7618

19 System overview 3 SIMATIC RF200 is an inductive identification system that is compatible with the ISO 15693 standard and was specially designed for use in industrial production for the control and optimization of material flows. In contrast to SIMATIC RF300, SIMATIC RF200 is intended for RFID applications where performance requirements are not very high, for example with regard to data volume, transfer rate or diagnostics options. SIMATIC RF200 is characterized by particularly favorable prices.

3.1 RFID components and their function

SIMATIC RF200 20 System Manual, 07/2015, J31069-D0227-U001-A9-7618 3.1 RFID components and their function RF200 system components Figure 3-1 RF200 system overview

3.1 RFID components and their function

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 21 Table 3- 1 Possible reader-transponder combinations Tran- sponder RF210R/ RF210M RF220R RF240R RF250R with RF260R RF290R 4) RF310M ANT 3 ANT 8 ANT 12 ANT 18 ANT 30 MDS D100 -- ○ ✓ ○ -- -- -- ○ ✓ ✓ ✓ MDS D117 ○ -- -- -- ✓ ✓ -- -- -- -- ✓ 6) MDS D124 ✓ ✓ ✓ ✓ -- -- ✓ ✓ ✓ ✓ ✓ MDS D126 -- ✓ ✓ ✓ -- -- -- ✓ ✓ ✓ ✓ MDS D127 ✓ -- -- -- ✓ ✓ -- -- -- -- ✓ 6) MDS D139 1) -- ○ ○ ○ -- -- -- ○ ✓ ✓ ✓ MDS D160 2) ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓ ✓ MDS D165 -- ○ ✓ ○ -- -- -- ○ ✓ ✓ ✓ MDS D200 -- ○ ✓ ○ -- -- -- ○ ✓ ✓ ✓ MDS D261 -- ○ ✓ ○ -- -- -- ○ ✓ ✓ ✓ MDS D324 ✓ ✓ ✓ ✓ -- ○ ✓ ✓ ✓ ✓ ✓ MDS D339 -- ○ ○ ○ -- -- -- ○ ✓ ✓ ✓ MDS D400 -- -- ✓ ○ -- -- -- ○ ✓ ✓ ✓ MDS D421 ✓ ○ -- -- ✓ ✓ ✓ -- -- -- ✓ 6) MDS D422 ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ -- -- ✓ 6) MDS D423 ✓ ✓ ✓ ✓ -- -- ✓ ✓ ✓ -- ✓ MDS D424 ✓ ✓ ✓ ✓ -- -- ✓ ✓ ✓ ✓ ✓ MDS D425 ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ -- -- ✓ MDS D426 -- ✓ ✓ ✓ -- -- -- ✓ ✓ ✓ ✓ MDS D428 ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ -- ✓ MDS D460 ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ○ / ✓ 5) ✓ MDS D521 ✓ ○ -- -- ✓ ✓ ✓ -- -- -- ✓ 6)

3.1 RFID components and their function

SIMATIC RF200 22 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Tran- sponder RF210R/ RF210M RF220R RF240R RF250R with RF260R RF290R 4) RF310M ANT 3 ANT 8 ANT 12 ANT 18 ANT 30 MDS D522 3) ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ -- -- ✓ 6) MDS D524 ✓ ✓ ✓ ✓ -- -- ✓ ✓ ✓ ✓ ✓ MDS D526 -- ✓ ✓ ✓ -- -- -- ✓ ✓ ✓ ✓ MDS D528 ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ -- ✓ 1) only with the article number 6GT2600-0AA10 2) only with the article number 6GT2600-0AB10 3) The transponder MDS D522 special variant has the same compatibility as the transponder MDS D522. 4) in conjunction with ANT D5, D6 or D10 5) combination recommended only in conjunction with ANT D5. 6) only in conjunction with RF310M for external antennas (6GT2803-1AC10) ✓ Combination possible -- Combination not possible ○ Combination possible, but not recommended

3.2 Overview of transponders

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 23 3.2 Overview of transponders Overview of typical areas of application of ISO transponders for RF200 Transponder Area of application MDS D100 From simple identification such as electronic barcode replacement or supplementation, through ware- house and distribution logistics, right up to product identification. With this transponder, the maximum ranges are achieved in combination with the SIMATIC RF260R reader. MDS D117 Very compact data carrier that can be cemented into objects where precise positioning is necessary. e.g. tool identification. MDS D124 Application areas in factory automation (e.g. small paintshops to 180°C). MDS D126 Compact and rugged ISO transponder; suitable for identification of transport units in production-related logistics; can also be deployed in harsh conditions. MDS D127 Very compact data carrier that can be screwed into areas where precise positioning is necessary. e.g. tool identification. MDS D139 1) Applications in production automation with high temperature demands (up to +220 °C). Typical application areas: • Paintshops and their preparatory treatments • Primer coat, electrolytic dip area, cataphoresis with the associated drying furnaces • Top coat area with drying furnaces • Washing areas at temperatures > 85 °C • Other applications with higher temperatures MDS D160 2) Typical applications are, for example: • Rented work clothing • Hotel laundry • Surgical textiles • Hospital clothing • Dirt collection mats • Clothing for nursing homes/hostels • Assembly lines with very small workpiece holders MDS D165 Smart label (self-adhesive label) From simple identification such as electronic barcode replacement/supplementation, through warehouse and distribution logistics, right up to product identification MDS D200 From simple identification such as electronic barcode replacement/supplementation, through warehouse and distribution logistics, right up to product identification. MDS D261 Smart label (self-adhesive label) The design of the transponder (self-adhesive label) permits a variety of designs in order to ensure opti- mum dimensioning for the widest variety of applications. From simple identification such as electronic barcode replacement/supplementation, through warehouse and distribution logistics, right up to product identification. MDS D324 Production and distribution logistics as well as in assembly and production lines MDS D339 Applications in production automation with high temperature demands (up to +220 °C). For typical areas of application, see "MDS D139".

3.2 Overview of transponders

SIMATIC RF200 24 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder Area of application MDS D400 Simple identification such as electronic barcode replacement/supplements, from warehouse and distribu- tion logistics right through to product identification. MDS D421 The MDS D421 is designed for tool coding according to DIN 69873. It can be used wherever small data carriers and exact positioning are required, e.g. tool identification, workpiece holders MDS D422 Identification of metallic workpiece holders, workpieces or containers MDS D423 Identification of metallic workpiece holders, workpieces or containers, production automation MDS D424 Production and distribution logistics as well as in assembly and production lines MDS D425 Compact and rugged ISO transponder; suitable for screw mounting. Use in assembly and production lines in the powertrain sector; ideal for mounting on motors, gearboxes, and workpiece holders MDS D426 Compact and rugged ISO transponder; suitable for identification of transport units in production-related logistics; can also be deployed in harsh conditions MDS D428 Compact and rugged ISO transponder; suitable for screw mounting Use in assembly and production lines in the powertrain sector MDS D460 Assembly lines with very small workpiece holders MDS D521 The MDS D521 is constructed for tool coding according to DIN 69873. It can be used wherever small data carriers and exact positioning are required, e.g. tool identification, workpiece holders. MDS D522 Identification of metallic workpiece holders, workpieces or containers MDS D522 Special vari- ants If Identification of metallic workpiece holders or workpieces MDS D524 Production and distribution logistics as well as in assembly and production lines MDS D526 Compact and rugged ISO transponder; suitable for identification of transport units in production-related logistics; can also be deployed in harsh environmental conditions MDS D528 Compact and rugged ISO transponder; suitable for screw mounting Use in assembly and production lines in the powertrain sector 1) Only with the MLFB 6GT2600-0AA10 2) Only with the MLFB 6GT2600-0AB10 Overview of the memory sizes of the ISO transponders for RF200 Transponder Memory size MDS D1xx 112 bytes of EEPROM MDS D2xx 256 bytes of EEPROM MDS D3xx 992 bytes of EEPROM MDS D4xx 2000 bytes FRAM MDS D5xx 8192 bytes FRAM

System Manual, 07/2015, J31069-D0227-U001-A9-7618

25 RF200 system planning 4 4.1 Fundamentals of application planning 4.1.1 Selection criteria for SIMATIC RF200 components Assess your application according to the following criteria, in order to choose the right SIMATIC RF200 components: ● Static or dynamic data transfer ● Data volume to be transferred ● Speed in case of dynamic transfer ● Ambient conditions such as relative humidity, temperature, chemical impacts, etc. 4.1.2 Transmission window and read/write distance The reader generates an inductive alternating field. The field is strongest close to the reader; however, a read/write distance of "zero" between reader and transponder is not recommended. The strength of the field decreases in proportion to the distance from the reader. The distribution of the field depends on the structure and geometry of the antennas in the reader and transponder A prerequisite for the function of the transponder is a minimum field strength at the transponder, which is still barely achieved at distance Sg from the reader.

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 26 System Manual, 07/2015, J31069-D0227-U001-A9-7618 The picture below shows the transmission window of the SIMATIC RF210R and SIMATIC RF220R readers between transponder and reader: Sa Operating distance between transponder and reader Sg Limit distance (maximum clear distance between upper surface of the reader and the tran- sponder, at which the transmission can still function under normal conditions) L Diameter of a transmission window SP Intersection of the axes of symmetry of the transponder Figure 4-1 RF210R/RF220R transmission window

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 27 The figure below shows the transmission window of the SIMATIC RF240R and SIMATIC RF260R readers between transponder and reader: Sa Operating distance between transponder and reader Sg Limit distance (maximum clear distance between upper surface of the reader and the tran- sponder, at which the transmission can still function under normal conditions) L Length of a transmission window M Field centerpoint Figure 4-2 RF240R/RF260R transmission window The transponder can be used as soon as the intersection (SP) of the transponder enters the area of the transmission window.

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 28 System Manual, 07/2015, J31069-D0227-U001-A9-7618 From the diagrams above, it can also be seen that operation is possible within the area between Sa and Sg. The active operating area reduces as the distance increases, and shrinks to a single point at distance Sg. Only static mode should thus be used in the area between Sa and Sg. 4.1.3 Width of the transmission window Determining the width of the transmission window The following approximation formula can be used for practical applications: B: Width of the transmission window L: Length of the transmission window Tracking tolerances The width of the transmission window (B) is particularly important for the mechanical tracking tolerance. The formula for the dwell time is valid without restriction when B is observed.

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 29 4.1.4 Impact of secondary fields Secondary fields in the range from 0 mm to 30% of the limit distance (Sg) generally always exist. They should, however, only be used during configuration in exceptional cases, since the read/write distances are very limited. Exact details of the secondary field geometry cannot be given, since these values depend heavily on the operating distance and the application. When working in dynamic mode, remember that during the transition from the secondary field to the main field the presence of the tag is lost temporarily. It is therefore advisable to select a distance > 30 % of Sg. ① Main field ② Secondary field Figure 4-3 Gap in the field resulting from secondary fields

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 30 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Secondary fields without shielding The following graphic shows typical primary and secondary fields, if no shielding measures are taken. ① Main field ② Secondary field Figure 4-4 Secondary field without shielding In this arrangement, the reader can also read tags via the secondary field. Shielding is required in order to prevent unwanted reading via the secondary field, as shown and described in the following.

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 31 Secondary fields with shielding The following graphic shows typical primary and secondary fields, with metal shielding this time. The metal shielding prevents the reader from detecting tags via the secondary field. ① Main field ② Secondary field Figure 4-5 Secondary field with shielding

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 32 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.1.5 Permissible directions of motion of the transponder Detection area and direction of motion of the transponder The transponder and reader have no polarization axis, i.e. the transponder can come in from any direction, assume any position as parallel as possible to the reader, and cross the transmission window. The figure below shows the active area for various directions of transponder motion: Transmission window Direction of motion of the transponder Detection area L x W Figure 4-6 Detection areas of the reader for different directions of transponder motion

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 33 4.1.6 Operation in static and dynamic mode Operation in static mode If working in static mode, the transponder can be operated up to the limit distance (Sg). The transponder must then be positioned exactly over the reader: Figure 4-7 Operation in static mode Note Note that in a metallic environment the values for the limit distance are reduced. Operation in dynamic mode When working in dynamic mode, the transponder moves past the reader. The transponder can be used as soon as the intersection (SP) of the transponder enters the circle of the transmission window. In dynamic mode, the operating distance (Sa) is of primary importance. [Operating distances, see Chapter Field data of transponders and readers (Page 36)] Figure 4-8 Operation in dynamic mode

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 34 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.1.7 Dwell time of the transponder The dwell time is the time in which the transponder remains within the transmission window of a reader. The reader can exchange data with the transponder during this time. The dwell time is calculated thus: tV: Dwell time of the transponder L: Length of the transmission window vTag: Speed of the transponder (tag) in dynamic mode 0,8: Constant factor used to compensate for temperature impacts and production toler- ances The dwell time can be of any duration in static mode. The dwell time must be sufficiently long to allow communication with the transponder. The dwell time is defined by the system environment in dynamic mode. The volume of data to be transferred must be matched to the dwell time or vice versa. In general: tV:: Dwell time of the data memory within the field of the reader tK: Communication time between transponder and communication module

RF200 system planning

4.1 Fundamentals of application planning SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 35 4.1.8 Communication between communication module, reader and transponder Aids for calculating the data transmission times User-friendly calculation tools are available for the communications modules ASM 456, RF160C, RF170C and RF180C to calculate data transfer times. The calculation tools can be found on the DVD "RFID Systems Software & Documentation", article number 6GT2080- 2AA20. Figure 4-9 User interface of the calculation tool for command processing time

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 36 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Aids for calculating the field data You will also find a tool for calculating field data on the DVD "RFID Systems, Software & Documentation". Using this tool, among other things you can calculate the operating distance (Sa), limit distance (Sg) and transmission window (L). Figure 4-10 User interface of the calculation tool for field data acquisition 4.2 Field data of transponders and readers The following tables show the field data for all SIMATIC RF200 components of transponders and readers. This makes the correct selection of a transponder and reader particularly easy. All the technical specifications listed are typical data and are applicable for an ambient temperature between 0 °C and +50 °C, a supply voltage between 22 and 27 VDC and a metal-free environment. Tolerances of ±20 % are permitted due to production or temperature conditions. If the entire voltage range at the reader of 20 VDC to 30 VDC and/or the entire temperature range of transponders and readers is used, the field data is subject to further tolerances. Note Transmission gaps If the minimum operating distance (Sa) is not observed, a transmission gap can occur in the center of the field. Communication with the transponder is not possible in the transmission gap.

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 37 4.2.1 Field data The limit distances (Sg) and operating distances (Sa) along with the length of the transmission window for each reader-transponder combination are listed in the tables below. Table 4- 1 SIMATIC RF210R field data Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D124 25 1 ... 18 20 MDS D127 1) 3 0 ... 2 2 MDS D160 20 1 ... 10 12 MDS D324 20 1 ... 8 9 MDS D421 5 0 ... 3 4 MDS D422 8 1 ... 9 10 MDS D423 20 2 ... 10 12 MDS D424 24 1 ... 16 18 MDS D425 12 1 ... 6 7 MDS D428 20 1 ... 10 11 MDS D460 8 1 … 8 9 MDS D521 5 0 ... 3 4 MDS D522 8 1 ... 8 9 MDS D522 Special variants 8 1 ... 8 9 MDS D524 20 1 ... 15 17 MDS D528 15 1 ... 10 11 1) The transponder is only suitable for static mode. All dimensions in mm. Table 4- 2 SIMATIC RF220R field data Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D124 35 1 ... 28 31 MDS D126 45 2 ... 30 35 MDS D160 20 1 ... 20 22 MDS D324 30 2 ... 21 25 MDS D422 18 1 ... 12 14 MDS D423 30 2 ...24 28 MDS D424 30 2 ... 25 29 MDS D425 20 1 ... 11 13 MDS D426 40 2 ... 25 30 MDS D428 25 1 ... 18 21 MDS D460 25 1 ... 18 20

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 38 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D522 15 1 ... 10 12 MDS D522 Special variants 15 1 ... 10 12 MDS D524 25 2 ... 22 25 MDS D526 30 2 ... 25 30 MDS D528 20 1 ... 15 20 All dimensions in mm. Table 4- 3 SIMATIC RF240R field data Length of the transmis- sion window (L) Operating distance (Sa) Limit distance (Sg) MDS D100 100 2 ... 84 95 MDS D124 65 2 ... 53 60 MDS D126 80 2 ... 57 65 MDS D160 50 1 ... 33 37 MDS D165 105 2 ... 80 94 MDS D200 90 2 ... 69 78 MDS D261 70 2 ... 60 70 MDS D324 55 1 ... 36 40 MDS D400 95 2 ... 80 90 MDS D422 25 1 ... 12 15 MDS D423 45 2 ... 35 40 MDS D424 75 1 ... 47 53 MDS D425 30 1 ... 15 17 MDS D426 65 2 ... 45 55 MDS D428 50 1 ... 30 34 MDS D460 50 1 ... 30 34 MDS D522 20 1 ... 10 12 MDS D522 Special variants 20 1 ... 10 12 MDS D524 60 1 ... 45 55 MDS D526 60 2 ... 45 55 MDS D528 40 1 ... 30 35 All dimensions in mm.

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 39 Table 4- 4 Field data SIMATIC RF250R, with ANT 3 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D124 40 1 ... 35 48 MDS D126 65 0 ... 47 60 MDS D160 24 1 ... 23 30 MDS D324 32 1 ... 22 35 MDS D422 27 0 ... 12 15 MDS D423 30 2 ... 18 26 MDS D424 37 0 ... 34 48 MDS D425 22 1 ... 12 20 MDS D426 65 0 ... 44 58 MDS D428 30 1 ... 20 32 MDS D460 24 1 ... 21 27 MDS D522 20 1 ... 12 15 MDS D522 Special variants 20 1 ... 12 15 MDS D524 35 1 ... 35 40 MDS D526 45 2 ... 35 45 MDS D528 25 1 ... 20 25 All dimensions in mm. Table 4- 5 Field data SIMATIC RF250R, with ANT 8 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D117 2 0 ... 2 3 MDS D127 3 0 ... 3 4 MDS D421 3 0 ... 3 4 MDS D521 3 0 ... 3 4 All dimensions in mm. Table 4- 6 Field data SIMATIC RF250R, with ANT 12 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D117 3 0 ... 3 4 MDS D127 4 0 ... 4 5 MDS D160 18 0 ... 12 17 MDS D421 10 0 ... 3 4 MDS D422 22 0 ... 7 10 MDS D425 12 0 ... 8 10

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 40 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D428 18 1 ... 8 12 MDS D460 16 1 ... 10 14 MDS D521 5 0 ... 3 4 MDS D522 10 1 ... 7 9 MDS D522 Special variants 10 1 ... 7 9 MDS D528 15 1 ... 8 12 All dimensions in mm. Table 4- 7 Field data SIMATIC RF250R, with ANT 18 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D124 26 0 ... 24 37 MDS D160 22 1 ... 18 26 MDS D324 30 1 ... 18 27 MDS D421 16 0 ... 3 4 MDS D422 24 1 ... 8 14 MDS D423 21 1 ... 15 18 MDS D424 26 1 ... 27 36 MDS D425 19 1 ... 11 16 MDS D428 19 1 ... 18 25 MDS D460 19 1 ... 17 21 MDS D521 6 0 ... 4 5 MDS D522 15 1 ... 10 12 MDS D522 Special variants 15 1 ... 10 12 MDS D524 30 1 ... 25 30 MDS D528 20 1 ... 15 20 All dimensions in mm. Table 4- 8 Field data SIMATIC RF250R, with ANT 30 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D124 40 1 ... 35 48 MDS D126 65 0 ... 47 60 MDS D160 24 1 ... 23 30 MDS D324 32 1 ... 22 35 MDS D422 27 0 ... 12 15 MDS D423 30 2 ... 18 26

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 41 Length of the transmis- sion window (Ld) Operating distance (Sa) Limit distance (Sg) MDS D424 37 0 ... 34 48 MDS D425 22 1 ... 12 20 MDS D426 65 0 ... 44 58 MDS D428 30 1 ... 20 32 MDS D460 24 1 ... 21 27 MDS D522 20 1 ... 12 15 MDS D522 Special variants 20 1 ... 12 15 MDS D524 35 1 ... 35 40 MDS D526 60 2 ... 35 45 MDS D528 25 1 ... 20 25 All dimensions in mm. Table 4- 9 SIMATIC RF260R field data Length of the transmis- sion window (L) Operating distance (Sa) Limit distance (Sg) MDS D100 120 2 ... 110 130 MDS D124 80 2 ... 80 85 MDS D126 110 2 ... 75 100 MDS D139 120 2 ... 80 110 MDS D160 60 2 ... 40 45 MDS D165 120 2 ... 120 135 MDS D200 120 2 ... 100 120 MDS D261 80 2 ... 75 90 MDS D324 80 2 ... 60 70 MDS D339 110 5 ... 65 80 MDS D400 140 2 ... 110 140 MDS D423 55 2 ... 40 45 MDS D424 80 2 ... 60 70 MDS D426 75 2 ... 70 85 MDS D428 50 2 ... 40 45 MDS D460 50 2 ... 40 45 MDS D524 70 2 ... 60 70 MDS D526 80 2 ... 70 85 MDS D528 50 2 ... 35 40 All dimensions in mm.

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 42 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Table 4- 10 Field data SIMATIC RF290R, with ANT D5 (at 4 W) Length of the transmis- sion window (L) Operating distance (Sa) Limit distance (Sg) MDS D100 320 0 ... 400 500 MDS D124 300 0 ... 200 280 MDS D126 320 0 ... 350 400 MDS D139 320 0 ... 400 500 MDS D160 300 0 ... 130 180 MDS D165 320 0 ... 350 450 MDS D200 320 0 ... 400 500 MDS D261 320 0 ... 300 400 MDS D324 300 0 ... 200 280 MDS D339 320 0 ... 300 380 MDS D400 320 0 ... 400 500 MDS D424 300 0 ... 200 280 MDS D426 320 0 ... 300 350 MDS D460 300 0 ... 120 160 MDS D524 300 0 ... 200 280 MDS D526 320 0 ... 300 350 All dimensions in mm. Table 4- 11 Field data SIMATIC RF290R, with ANT D6 (at 4 W) Length of the transmission window (L) Operating distance (Sa) Limit distance (Sg) X direction Y direction MDS D100 520 420 0 ... 550 650 MDS D124 500 400 0 ... 220 300 MDS D126 520 420 0 ... 400 500 MDS D139 520 420 0 ... 500 600 MDS D160 500 400 0 ... 130 180 MDS D165 520 420 0 ... 400 500 MDS D200 520 420 0 ... 500 600 MDS D261 520 420 0 ... 350 450 MDS D324 500 400 0 ... 200 280 MDS D339 520 420 0 ... 400 480 MDS D400 520 420 0 ... 500 650 MDS D424 500 400 0 ... 220 300 MDS D426 520 420 0 ... 350 400 MDS D524 500 400 0 ... 220 300 MDS D526 520 420 0 ... 350 400 All dimensions in mm.

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 43 Table 4- 12 Field data SIMATIC RF290R, with ANT D10 (at 4 W) Length of the transmission window (L) Operating distance (Sa) Limit distance (Sg) X direction Y direction MDS D100 1050 350 0 ... 500 600 MDS D124 1000 300 0 ... 200 280 MDS D126 1050 350 0 ... 400 500 MDS D139 1050 350 0 ... 450 550 MDS D160 1000 300 0 ... 130 180 MDS D165 1050 350 0 ... 350 450 MDS D200 1050 350 0 ... 450 550 MDS D261 1050 350 0 ... 350 450 MDS D324 1000 300 0 ... 200 280 MDS D339 1050 350 0 ... 300 380 MDS D400 1050 350 0 ... 400 500 MDS D424 1000 300 0 ... 200 280 MDS D426 1050 350 0 ... 350 400 MDS D524 1000 300 0 ... 220 300 MDS D526 1050 350 0 ... 350 400 All dimensions in mm.

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 44 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.2.2 Minimum clearances Minimum distance from transponder to transponder The specified distances refer to a metal-free environment. For a metallic environment, the specified minimum distances must be multiplied by a factor of 1.5. Table 4- 13 Minimum clearances for transponders RF210R RF220R RF240R RF260R MDS D100 -- -- -- ≥ 240 MDS D117 ≥ 15 -- -- -- MDS D124 ≥ 25 ≥ 40 ≥ 90 ≥ 180 MDS D126 -- ≥ 50 ≥ 100 ≥ 180 MDS D127 ≥ 15 -- -- -- MDS D139 -- -- -- ≥ 200 MDS D160 ≥ 20 ≥ 25 ≥ 70 ≥ 150 MDS D165 -- -- -- ≥ 240 MDS D200 -- -- -- ≥ 240 MDS D261 -- -- -- ≥ 200 MDS D324 ≥ 25 ≥ 40 ≥ 90 ≥ 180 MDS D339 -- -- -- ≥ 200 MDS D400 -- -- -- ≥ 240 MDS D421 ≥ 10 -- -- -- MDS D422 ≥ 15 ≥ 20 ≥ 50 -- MDS D423 -- -- ≥ 80 ≥ 160 MDS D424 ≥ 25 ≥ 40 ≥ 90 ≥ 180 MDS D425 ≥ 20 ≥ 25 ≥ 75 -- MDS D426 -- ≥ 50 ≥ 90 ≥ 180 MDS D428 ≥ 25 ≥ 25 ≥ 75 ≥ 150 MDS D460 ≥ 20 ≥ 25 ≥ 70 ≥ 150 MDS D521 ≥ 10 -- -- -- MDS D522 ≥ 15 ≥ 20 ≥ 50 -- MDS D522 Special variants ≥ 15 ≥ 20 ≥ 50 -- MDS D524 ≥ 25 ≥ 40 ≥ 90 ≥ 180 MDS D526 -- ≥ 50 ≥ 90 ≥ 180 MDS D528 ≥ 25 ≥ 25 ≥ 75 ≥ 150 All values are in mm, relative to the operating distance (Sa) between reader and transponder, and between transponder edge and transponder edge

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 45 Table 4- 14 Minimum clearances for transponders RF250R 1) RF290R 2) ANT 3 ANT 8 ANT 12 ANT 18 ANT 30 ANT D5 ANT D6 ANT D10 MDS D100 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D117 -- ≥ 30 ≥ 50 -- -- -- -- -- MDS D124 ≥ 100 -- -- ≥ 80 ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D126 ≥ 100 -- -- -- ≥ 100 ≥ 1000 ≥ 1500 ≥ 2000 MDS D127 -- ≥ 40 ≥ 60 -- -- -- -- -- MDS D139 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D160 ≥ 100 -- ≥ 60 ≥ 80 ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D165 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D200 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D261 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D324 ≥ 100 -- -- ≥ 80 ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D339 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D400 -- -- -- -- -- ≥ 1000 ≥ 1500 ≥ 2000 MDS D421 -- ≥ 30 ≥ 40 ≥ 50 -- -- -- -- MDS D422 ≥ 70 -- ≥ 50 ≥ 60 ≥ 70 -- -- -- MDS D423 ≥ 100 -- -- ≥ 80 ≥ 100 -- -- -- MDS D424 ≥ 100 -- -- ≥ 80 ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D425 ≥ 80 -- ≥ 50 ≥ 60 ≥ 80 -- -- -- MDS D426 ≥ 100 -- -- -- ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D428 ≥ 80 -- ≥ 50 ≥ 60 ≥ 80 -- -- -- MDS D460 ≥ 100 -- ≥ 60 ≥ 80 ≥ 100 ≥ 800 -- -- MDS D521 -- ≥ 30 ≥ 40 ≥ 50 -- -- -- -- MDS D522 ≥ 70 -- ≥ 50 ≥ 60 ≥ 70 -- -- -- MDS D522 Special variants ≥ 70 -- ≥ 50 ≥ 60 ≥ 70 -- -- -- MDS D524 ≥ 100 -- -- ≥ 80 ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D526 ≥ 100 -- -- -- ≥ 100 ≥ 800 ≥ 1200 ≥ 1800 MDS D528 ≥ 80 -- ≥ 50 ≥ 60 ≥ 80 -- -- -- 1) Depends on the connected antenna (ANT 3, 8, 12, 18 or 30). 2) Depends on the connected antenna (ANT D5, D6 or D10). All values are in mm, relative to the operating distance (Sa) between reader and transponder, and between transponder edge and transponder edge

RF200 system planning

4.2 Field data of transponders and readers SIMATIC RF200 46 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Minimum distance from reader to reader Table 4- 15 Minimum distances to readers or antennas RF210R to RF210R RF220R to RF220R RF240R to RF240R ANT x to ANT x with RF250R RF260R to RF260R ANT Dx to ANT Dx with RF290R ≥ 60 mm ≥ 100 mm ≥ 120 mm ANT 3: ≥ 100 mm ≥ 150 mm ANT D5: ≥ 2000 mm ANT 8: ≥ 50 mm ANT D10: ≥ 2000 mm ANT 12: ≥ 60 mm ANT 18: ≥ 80 mm ANT 30: ≥ 100 mm All values are in mm Note Effect on inductive fields by not maintaining the minimum distances of the readers If the values fall below those specified in the "minimum distance readers or antennas", there is a risk of the function being affected by inductive fields. In this case, the data transfer time would increase unpredictably or a command would be aborted with an error. Keeping to the values specified in the "Minimum distance readers or antennas" table is therefore essential. If the specified minimum distance cannot be complied with due to the physical configuration, the SET-ANT command can be used to activate and deactivate the HF field of the reader. The application software must be used to ensure that only one reader is active (antenna is switched on) at a time.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 47 4.3 Installation guidelines 4.3.1 Overview The transponder and reader complete with their antennas are inductive devices. Any type of metal in the vicinity of these devices affects their functionality. Some points need to be considered during planning and installation if the values described in the "Field data (Page 37)" section are to retain their validity: ● Minimum spacing between two readers or their antennas ● Minimum distance between two adjacent data memories ● Metal-free area for flush-mounting of readers or their antennas and transponders in metal ● Mounting of multiple readers or their antennas on metal frames or racks The following sections describe the impact on the operation of the RFID system when mounted in the vicinity of metal. 4.3.2 Reduction of interference due to metal Interference due to metal rack Problem A metal rack is located above the transmission window of the reader. This affects the entire field. In par- ticular, the transmission window between reader and transponder is reduced. Remedy: The transmission window is no longer affected if the transponder is mounted differently.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 48 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Flush-mounting Flush-mounting of transponders and readers Problem Flush-mounting of transponders and readers is possible in principle. However, the size of the transmis- sion window is significantly reduced. The following measures can be used to counteract the reduction of the window: Remedy: Enlargement of the non-metallic spacer below the transponder and/or reader. The transponder and/or reader are 10 to 20 mm higher than the metal surround. (The value x ≥ 100 mm is valid, for example, for RF260R. It indicates that, for a distance x ≥ 100 mm, the reader can no longer be significantly affected by metal.) Remedy: Increase the non-metallic distance a, b. The following rule of thumb can be used: • Increase a, b by a factor of 2 to 3 over the values specified for metal-free areas • Increasing a, b has a greater effect for readers or transpond- ers with a large limit distance than for readers or transponders with a small limit distance.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 49 Mounting of several readers on metal frames or racks Any reader mounted on metal couples part of the field to the metal frame. There is normally no interaction as long as the minimum distance D and metal-free areas a, b are maintained. However, interaction may take place if an iron frame is positioned unfavorably. Longer data transfer times or sporadic error messages at the communication module are the result. Mounting of several readers on metal racks Problem: Interaction between readers Remedy Increase the distance D between the two readers. Remedy Introduce one or more iron struts in order to short- circuit the stray fields. Remedy Insert a non-metallic spacer of 20 to 40 millimeter thickness between the reader and the iron frame. This will significantly reduce the induction of stray fields on the rack: 4.3.3 Effects of metal on different transponders and readers Mounting different transponders and readers on metal or flush-mounting Certain conditions have to be observed when mounting the transponders and readers on metal or flush-mounting. For more information, please refer to the descriptions of the individual transponders and readers in the relevant section.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 50 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.3.4 Impact of metal on the transmission window In general, the following points should be considered when mounting RFID components: ● Direct mounting on metal is allowed only in the case of specially approved transponders. ● Flush-mounting of the components in metal reduces the field data; a test is recommended in critical applications. ● When working inside the transmission window, make sure that no metal rail (or similar part) intersects the transmission field. The metal rail would affect the field data. ● With readers with a large antenna surface (e.g. RF260R) for reasons of communication reliability, when the transponders are flush mounted in metal, a metal-free space around the transponders is recommended. This metal-free space should match the size of the antenna surface. The impact of metal on the field data (Sg, Sa, L) is shown in a table in this section. The values in the tables describe field data reduction and show the reduced range as a percentage. The range relates to use in a non-metallic environment. A value of 100% means no influence on the range.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 51 4.3.4.1 RF210R The RF210R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. The following table shows the different arrangements for the reader with and without a metallic environment: Case Diagram Description a) Reader metal-free b) Reader on metal, distance from metal ≥ 12 mm c) Reader in metal, flush against M18 nut d) Reader in metal, all around

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 52 System Manual, 07/2015, J31069-D0227-U001-A9-7618 To avoid any influence on the field data, in Case d, the distance a should be ≥ 10 mm. Table 4- 16 Reduction of field data due to metal, range as %: Transponder and RF210R Transponder Reader without direct metal influence (Case a, b and d) Reader flush- mounted in metal (Case c) MDS D124 1) metal-free 100 82 on metal, distance 15 mm 90 90 flush-mounted in metal; distance all round 15 mm 85 80 MDS D127 flush-mounted in metal; distance all round 0 mm 100 75 MDS D160 1) metal-free 100 95 on metal, distance 10 mm 100 95 MDS D324 1) metal-free 100 90 on metal, distance 15 mm 90 90 flush-mounted in metal; distance all round 25 mm 80 90 MDS D421 metal-free 100 90 flush-mounted in metal; distance all round 0 mm 75 50 MDS D422 metal-free 100 80 flush-mounted in metal; distance all round 0 mm 90 40 MDS D423 metal-free 100 90 on metal, distance 0 mm 110 2) 100 2) flush-mounted in metal; distance all round 10 mm 95 85 MDS D424 1) metal-free 100 60 on metal, distance 15 mm 90 80 flush-mounted in metal; distance all round 25 mm 85 75 MDS D425 metal-free 100 85 on metal, distance 0 mm 100 85 MDS D428 metal-free 100 90 on metal, distance 0 mm 100 80 MDS D460 1) metal-free 100 90 on metal, distance 25 mm 100 90 MDS D521 metal-free 100 90 flush-mounted in metal; distance all round 0 mm 75 50 MDS D522 metal-free 100 80 flush-mounted in metal; distance all round 0 mm 90 40

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 53 Transponder Reader without direct metal influence (Case a, b and d) Reader flush- mounted in metal (Case c) MDS D522 Special variant metal-free 100 80 flush-mounted in metal; distance all round 0 mm 90 40 MDS D524 1) metal-free 100 60 on metal, distance 15 mm 90 80 flush-mounted in metal; distance all round 25 mm 85 75 MDS D528 metal-free 100 90 on metal, distance 0 mm 100 80 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 54 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.3.4.2 RF220R The RF220R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. The following table shows the different arrangements for the reader with and without a metallic environment: Case Diagram Description a) Reader metal-free b) Reader on metal, distance from metal ≥ 12 mm c) Reader in metal, flush against M30 nut d) Reader in metal, all round

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 55 To avoid any influence on the field data, in Case d, the distance a should be ≥ 15 mm. Table 4- 17 Reduction of field data due to metal, range as %: Transponder and RF220R Transponder Reader without direct metal influence (Case a, b and d) Reader flush- mounted in metal (Case c) MDS D124 1) metal-free 100 94 on metal, distance 15 mm 97 89 tag flush-mounted in metal; distance all round 15 mm 86 83 MDS D126 1) metal-free 100 75 on metal, distance 25 mm 85 70 flush-mounted in metal; distance all round 50 mm 80 65 MDS D160 1) metal-free 100 89 on metal, distance 10 mm 100 89 MDS D324 1) metal-free 100 90 on metal, distance 15 mm 97 86 flush-mounted in metal; distance all round 25 mm 93 86 MDS D422 metal-free 100 90 flush-mounted in metal; distance all round 0 mm 85 85 MDS D423 metal-free 100 90 on metal, distance 0 mm 125 2) 115 2) flush-mounted in metal; distance all round 10 mm 80 75 MDS D424 1) metal-free 100 93 on metal, distance 15 mm 96 89 flush-mounted in metal; distance all round 25 mm 86 82 MDS D425 metal-free 100 90 screwed onto metal 100 75 flush-mounted in metal; distance all round 25 mm 95 75 MDS D426 1) metal-free 100 90 on metal, distance 25 mm 90 75 flush-mounted in metal; distance all round 50 mm 80 70 MDS D428 metal-free 100 94 on metal, distance 0 mm 100 94 MDS D460 1) metal-free 100 92 on metal, distance 0 mm 100 92

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 56 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder Reader without direct metal influence (Case a, b and d) Reader flush- mounted in metal (Case c) MDS D522 metal-free 100 90 flush-mounted in metal; distance all round 0 mm 85 85 MDS D522 Special variant metal-free 100 90 flush-mounted in metal; distance all round 0 mm 85 85 MDS D524 1) metal-free 100 93 on metal, distance 0 mm 96 89 flush-mounted in metal; distance all round 0 mm 86 82 MDS D526 1) metal-free 100 90 on metal, distance 25 mm 90 75 flush-mounted in metal; distance all round 50 mm 80 70 MDS D528 metal-free 100 94 on metal, distance 0 mm 100 94 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. 4.3.4.3 RF240R The RF240R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. Figure 4-11 metal-free space RF240R

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 57 To avoid any impact on the field data, the distance a should be ≥ 20 mm. Table 4- 18 Reduction of field data due to metal, range as %: Transponder and RF240R Transponder Reader without direct metal influence Reader on metal (metal plate) Reader flush- mounted in metal (all round 20 mm) MDS D100 1) without metal 100 95 80 on metal, distance 20 mm 95 90 75 flush-mounted in metal; distance all round 20 mm 90 75 70 MDS D124 1) without metal 100 85 75 on metal, distance 15 mm 90 80 75 flush-mounted in metal; distance all round 25 mm 85 70 65 MDS D126 1) without metal 100 80 70 on metal, distance 25 mm 80 75 60 flush-mounted in metal; distance all round 50 mm 70 55 55 MDS D160 1) without metal 100 90 80 on metal, distance 10 mm 90 85 80 MDS D165 without metal 100 95 75 on metal, distance 25 mm 75 70 65 MDS D200 1) without metal 100 95 85 on metal, distance 20 mm 95 80 70 flush-mounted in metal, distance all round 20 mm 70 60 50 MDS D261 without metal 100 90 90 on metal, distance 25 mm 85 80 70 MDS D324 1) without metal 100 90 80 on metal, distance 15 mm 95 85 80 flush-mounted in metal; distance all round 25 mm 90 75 70 MDS D400 1) without metal 100 90 80 on metal, distance 20 mm 80 75 55 flush-mounted in metal, distance all round 20 mm 75 70 50 MDS D422 without metal 100 90 85 flush-mounted in metal; distance all round 0 mm 90 60 40 MDS D423 without metal 100 95 90 on metal, distance 0 mm 150 2) 140 2) 140 2) flush-mounted in metal; distance all round 10 mm 70 60 60

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 58 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder Reader without direct metal influence Reader on metal (metal plate) Reader flush- mounted in metal (all round 20 mm) MDS D424 1) without metal 100 85 80 on metal, distance 15 mm 90 80 75 flush-mounted in metal; distance all round 25 mm 80 70 65 MDS D425 without metal 100 90 85 on metal, distance 0 mm 95 85 80 MDS D426 1) without metal 100 80 70 on metal, distance 25 mm 90 80 70 flush-mounted in metal; Distance all-round 50 mm 85 65 60 MDS D428 without metal 100 90 85 on metal, distance 0 mm 95 85 83 MDS D460 1) without metal 100 90 80 on metal, distance 0 mm 90 85 80 MDS D522 metal-free 100 90 85 flush-mounted in metal; distance all round 0 mm 90 60 40 MDS D522 Special vari- ant metal-free 100 90 85 flush-mounted in metal; distance all round 0 mm 90 60 40 MDS D524 1) metal-free 100 85 80 on metal, distance 0 mm 90 80 75 flush-mounted in metal; distance all round 0 mm 80 70 65 MDS D526 1) metal-free 100 80 70 on metal, distance 25 mm 90 80 70 flush-mounted in metal; distance all round 50 mm 85 65 60 MDS D528 metal-free 100 90 85 on metal, distance 0 mm 95 85 83 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 59 4.3.4.4 RF250R The RF250R reader is operated with the external antennas ANT 3, 8, 12, 18 and 30. The antennas can be flush-mounted in metal. Please allow for a possible reduction in the field data values. Figure 4-12 Metal-free space for ANT 8 / ANT 12 and ANT 18 / ANT 30 Table 4- 19 Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 3 Transponder RF250R with ANT 3 antenna without met- al antenna flush- mounted in metal (all round 20 mm) MDS D124 1) without metal 100 80 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70 MDS D126 1) without metal 100 80 on metal, distance 25 mm 85 75 flush-mounted in metal; distance all round 50 mm 60 50 MDS D160 1) without metal 100 85 on metal, distance 10 mm 95 80 MDS D324 1) without metal 100 80 on metal, distance 15 mm 95 75 flush-mounted in metal; distance all round 25 mm 85 70 MDS D422 without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D423 without metal 100 90 on metal, distance 0 mm 130 2) 110 2) flush-mounted in metal; distance all round 10 mm 80 70 MDS D424 1) without metal 100 85 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 60 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder RF250R with ANT 3 antenna without met- al antenna flush- mounted in metal (all round 20 mm) MDS D425 without metal 100 90 on metal, distance 0 mm 95 75 MDS D426 1) without metal 100 70 on metal, distance 25 mm 90 65 flush-mounted in metal; distance all round 25 mm 55 45 MDS D428 without metal 100 90 on metal, distance 0 mm 100 90 MDS D460 1) without metal 100 85 on metal, distance 10 mm 90 75 MDS D522 without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D522 Special variant without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D524 1) without metal 100 85 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70 MDS D526 1) without metal 100 70 on metal, distance 25 mm 90 65 flush-mounted in metal; distance all round 25 mm 55 45 MDS D528 without metal 100 90 on metal, distance 0 mm 100 90 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. Table 4- 20 Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 8 Transponder RF250R with ANT 8 antenna without met- al antenna flush- mounted in metal MDS D117 without metal 100 85 flush-mounted in metal; distance all round 0 mm 65 55

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 61 Transponder RF250R with ANT 8 antenna without met- al antenna flush- mounted in metal MDS D127 without metal 100 85 flush-mounted in metal; distance all round 0 mm 70 60 MDS D421 without metal 100 85 flush-mounted in metal; distance all round 0 mm 75 70 MDS D521 without metal 100 85 flush-mounted in metal; distance all round 0 mm 75 70 Table 4- 21 Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 12 Transponder RF250R with ANT 12 antenna without met- al antenna flush- mounted in metal (all round 7 mm) MDS D117 without metal 100 85 flush-mounted in metal; distance all round 0 mm 50 40 MDS D127 without metal 100 85 flush-mounted in metal; distance all round 0 mm 65 50 MDS D160 1) without metal 100 90 on metal, distance 10 mm 90 85 MDS D421 without metal 100 90 flush-mounted in metal; distance all round 0 mm 65 45 MDS D422 without metal 100 90 flush-mounted in metal; distance all round 0 mm 90 75 MDS D425 without metal 100 90 on metal, distance 0 mm 115 2) 100 MDS D428 without metal 100 85 on metal, distance 0 mm 110 2) 95 MDS D460 1) without metal 100 95 on metal, distance 10 mm 90 80 flush-mounted in metal; distance all round 0 mm 85 75 MDS D521 without metal 100 90 flush-mounted in metal; distance all round 0 mm 65 45

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 62 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder RF250R with ANT 12 antenna without met- al antenna flush- mounted in metal (all round 7 mm) MDS D522 without metal 100 90 flush-mounted in metal; distance all round 0 mm 90 75 MDS D528 without metal 100 85 on metal, distance 0 mm 110 2) 95 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. Table 4- 22 Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 18 Transponder RF250R with ANT 18 antenna without met- al antenna flush- mounted in metal (all round 10 mm) MDS D124 1) without metal 100 80 on metal, distance 15 mm 100 80 flush-mounted in metal; distance all round 25 mm 95 70 MDS D160 1) without metal 100 90 on metal, distance 10 mm 100 90 MDS D324 1) without metal 100 80 on metal, distance 15 mm 100 80 flush-mounted in metal; distance all round 25 mm 95 75 MDS D421 without metal 100 85 flush-mounted in metal; distance all round 0 mm 65 50 MDS D422 without metal 100 100 flush-mounted in metal; distance all round 0 mm 90 90 MDS D423 without metal 100 85 on metal, distance 0 mm 120 2) 110 2) flush-mounted in metal; distance all round 10 mm 90 75 MDS D424 1) without metal 100 75 on metal, distance 15 mm 95 75 flush-mounted in metal; distance all round 25 mm 95 75

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 63 Transponder RF250R with ANT 18 antenna without met- al antenna flush- mounted in metal (all round 10 mm) MDS D425 without metal 100 90 on metal, distance 0 mm 100 90 MDS D428 without metal 100 85 on metal, distance 0 mm 100 85 MDS D460 1) without metal 100 85 on metal, distance 10 mm 100 85 MDS D521 without metal 100 85 flush-mounted in metal; distance all round 0 mm 65 50 MDS D522 without metal 100 100 flush-mounted in metal; distance all round 0 mm 90 90 MDS D522 Special variant without metal 100 100 flush-mounted in metal; distance all round 0 mm 90 90 MDS D524 1) without metal 100 75 on metal, distance 15 mm 95 75 flush-mounted in metal; distance all round 25 mm 95 75 MDS D528 without metal 100 85 on metal, distance 0 mm 100 85 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. Table 4- 23 Reduction of field data due to metal, range as %: Transponder and RF250R with ANT 30 Transponder RF250R with ANT 30 antenna without met- al antenna flush- mounted in metal (all round 20 mm) MDS D124 1) without metal 100 80 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70 MDS D126 1) without metal 100 80 on metal, distance 25 mm 85 75 flush-mounted in metal; distance all round 50 mm 60 50

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 64 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder RF250R with ANT 30 antenna without met- al antenna flush- mounted in metal (all round 20 mm) MDS D160 1) without metal 100 85 on metal, distance 10 mm 95 80 MDS D324 1) without metal 100 80 on metal, distance 15 mm 95 75 flush-mounted in metal; distance all round 25 mm 85 70 MDS D422 without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D423 without metal 100 90 on metal, distance 0 mm 130 2) 110 2) flush-mounted in metal; distance all round 10 mm 80 70 MDS D424 1) without metal 100 85 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70 MDS D425 without metal 100 90 on metal, distance 0 mm 95 75 MDS D426 1) without metal 100 70 on metal, distance 25 mm 90 65 flush-mounted in metal; distance all round 25 mm 55 45 MDS D428 without metal 100 90 on metal, distance 0 mm 100 90 MDS D460 1) without metal 100 85 on metal, distance 10 mm 90 75 MDS D522 without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D522 Special variant without metal 100 95 flush-mounted in metal; distance all round 0 mm 95 80 MDS D524 1) without metal 100 85 on metal, distance 15 mm 90 75 flush-mounted in metal; distance all round 25 mm 75 70 MDS D526 1) without metal 100 70 on metal, distance 25 mm 90 65 flush-mounted in metal; distance all round 25 mm 55 45

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 65 Transponder RF250R with ANT 30 antenna without met- al antenna flush- mounted in metal (all round 20 mm) MDS D528 without metal 100 90 on metal, distance 0 mm 100 90 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. 4.3.4.5 RF260R The RF260R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. Figure 4-13 metal-free space for RF260R To avoid any impact on the field data, the distance a should be ≥ 20 mm. Table 4- 24 Reduction of field data due to metal, range as %: Transponder and RF260R Transponder Reader with- out direct metal influ- ence Reader on met- al (metal plate) Reader flush- mounted in metal (all round 20 mm) MDS D100 1) without metal 100 85 65 on metal, distance 20 mm 70 65 50 flush-mounted in metal; distance all round 20 mm 65 50 40 MDS D124 1) without metal 100 93 75 on metal, distance 15 mm 95 85 70 flush-mounted in metal; distance all round 25 mm 78 75 65

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 66 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder Reader with- out direct metal influ- ence Reader on met- al (metal plate) Reader flush- mounted in metal (all round 20 mm) MDS D126 1) without metal 100 85 73 on metal, distance 25 mm 75 68 60 flush-mounted in metal; distance all round 50 mm 55 53 40 MDS D139 1) without metal 100 90 75 on metal, distance 30 mm 95 90 75 MDS D160 1) without metal 100 90 75 on metal, distance 10 mm 90 80 80 MDS D165 without metal 100 85 65 on metal, distance 25 mm 65 60 45 MDS D200 1) without metal 100 85 70 on metal, distance 20 mm 70 65 50 flush-mounted in metal, distance all round 20 mm 55 50 45 MDS D261 without metal 100 85 70 on metal, distance 25 mm 80 70 60 MDS D324 1) without metal 100 90 75 on metal, distance 15 mm 90 80 70 flush-mounted in metal; distance all round 25 mm 70 65 55 MDS D339 1) without metal 100 90 75 on metal, distance 30 mm 95 90 75 MDS D400 1) without metal 100 85 70 on metal, distance 20 mm 70 65 50 flush-mounted in metal; distance all round 20 mm 55 50 45 MDS D423 without metal 100 95 85 on metal, distance 0 mm 120 2) 115 2) 110 2) flush-mounted in metal; distance all round 10 mm 75 65 60 MDS D424 1) without metal 100 90 80 on metal, distance 15 mm 90 80 70 flush-mounted in metal; distance all round 25 mm 60 60 50 MDS D426 1) without metal 100 100 73 on metal, distance 25 mm 88 85 68 flush-mounted in metal; distance all round 50 mm 65 55 55 MDS D428 without metal 100 90 90 on metal, distance 0 mm 90 90 85

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 67 Transponder Reader with- out direct metal influ- ence Reader on met- al (metal plate) Reader flush- mounted in metal (all round 20 mm) MDS D460 1) without metal 100 95 90 on metal, distance 10 mm 90 85 80 MDS D524 1) without metal 100 90 80 on metal, distance 15 mm 90 80 70 flush-mounted in metal; distance all round 25 mm 60 60 50 MDS D526 1) without metal 100 100 73 on metal, distance 25 mm 88 85 68 flush-mounted in metal; distance all round 50 mm 65 55 55 MDS D528 without metal 100 90 90 on metal, distance 0 mm 90 90 85 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 2) Values of > 100 % related to non metal surroundings can occur if transponders were developed specifically for mounting in/on metallic surroundings. 4.3.4.6 RF290R The RF290R reader is operated with the external antennas ANT D5, D6 and D10. The antennas can be flush-mounted in metal. Please allow for a possible reduction in the field data values. Figure 4-14 Metal-free space for ANT D5

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 68 System Manual, 07/2015, J31069-D0227-U001-A9-7618 To avoid any influence on the field data, the distance a should be ≥ 150 or 200 mm. Table 4- 25 Reduction of field data due to metal, range as %: Transponder and RF290R with ANT D5 Transponder RF290R with ANT D5 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 150 mm) MDS D100 1) without metal 100 95 on metal, distance 20 mm 65 60 flush-mounted in metal; distance all round 20 mm 45 40 MDS D124 1) without metal 100 95 on metal, distance 15 mm 85 80 flush-mounted in metal; distance all round 25 mm 65 60 MDS D126 1) without metal 100 95 on metal, distance 25 mm 70 65 flush-mounted in metal; distance all round 50 mm 55 50 MDS D139 1) without metal 100 95 on metal, distance 30 mm 90 85 MDS D160 1) without metal 100 95 on metal, distance 10 mm 70 65 MDS D165 without metal 100 95 on metal, distance 25 mm 65 60 MDS D200 1) without metal 100 95 on metal, distance 20 mm 65 60 flush-mounted in metal; distance all round 20 mm 45 40 MDS D261 without metal 100 95 on metal, distance 25 mm 65 60 MDS D324 1) without metal 100 95 on metal, distance 15 mm 75 70 MDS D339 1) without metal 100 95 on metal, distance 30 mm 90 85 MDS D400 1) without metal 100 95 on metal, distance 20 mm 65 60 flush-mounted in metal; distance all round 20 mm 45 40 MDS D424 1) without metal 100 95 on metal, distance 15 mm 75 70

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 69 Transponder RF290R with ANT D5 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 150 mm) MDS D426 1) without metal 100 95 on metal, distance 25 mm 70 65 flush-mounted in metal; distance all round 50 mm 50 45 MDS D460 1) without metal 100 95 on metal, distance 10 mm 70 65 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. Table 4- 26 Reduction of field data due to metal, range as %: Transponder and RF290R with ANT D6 Transponder RF290R with ANT D6 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 200 mm) MDS D100 1) without metal 100 95 on metal, distance 20 mm 65 60 MDS D124 1) without metal 100 95 on metal, distance 25 mm 80 75 MDS D126 1) without metal 100 95 on metal, distance 25 mm 65 60 MDS D139 1) without metal 100 90 on metal, distance 30 mm 80 70 MDS D160 1) without metal 100 90 on metal, distance 25 mm 60 55 MDS D165 without metal 100 95 on metal, distance 20 mm 50 45 MDS D200 1) without metal 100 95 on metal, distance 20 mm 65 60 MDS D261 without metal 100 95 on metal, distance 20 mm 50 45 MDS D324 1) without metal 100 95 on metal, distance 25 mm 75 70 MDS D339 1) without metal 100 90 on metal, distance 30 mm 80 70 MDS D400 1) without metal 100 95 on metal, distance 20 mm 60 55

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 70 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Transponder RF290R with ANT D6 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 200 mm) MDS D424 1) without metal 100 95 on metal, distance 25 mm 75 70 MDS D426 1) without metal 100 95 on metal, distance 25 mm 65 60 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. Table 4- 27 Reduction of field data due to metal, range as %: Transponder and RF290R with ANT D10 Transponder RF290R with ANT D10 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 200 mm) MDS D100 1) without metal 100 95 on metal, distance 20 mm 50 40 MDS D124 1) without metal 100 90 on metal, distance 25 mm 70 60 MDS D126 1) without metal 100 95 on metal, distance 25 mm 65 60 MDS D139 1) without metal 100 90 on metal, distance 30 mm 80 70 MDS D160 1) without metal 100 90 on metal, distance 25 mm 60 55 MDS D165 without metal 100 90 on metal, distance 20 mm 40 30 MDS D200 1) without metal 100 95 on metal, distance 20 mm 50 40 MDS D261 without metal 100 90 on metal, distance 20 mm 40 30 MDS D324 1) without metal 100 90 on metal, distance 25 mm 70 60 MDS D339 1) without metal 100 90 on metal, distance 30 mm 80 70 MDS D400 1) without metal 100 95 on metal, distance 20 mm 50 40 MDS D424 1) without metal 100 90 on metal, distance 25 mm 70 60

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 71 Transponder RF290R with ANT D10 Antenna on metal (metal plate) antenna flush- mounted in metal (all round 200 mm) MDS D426 1) without metal 100 95 on metal, distance 25 mm 70 65 MDS D524 1) without metal 100 90 on metal, distance 25 mm 70 60 MDS D526 1) without metal 100 95 on metal, distance 25 mm 70 65 1) Mounting the transponder on or in metal is only possible with the appropriate spacer or if there is adequate clearance to the metal. 4.3.5 Installation and connection of 2 to 6 antennas with one RF290R reader If several antennas need to be operated on one reader, this can be achieved by using the antenna splitter or the antenna multiplexer RF260X. Note that the antenna splitter is a purely passive device that splits the power at the input to two outputs and therefore halves it. This is possible both in PC mode (RS-232) and CM mode (RS-422). You can cascade the antenna splitters in such a way that up to 4 antennas can be connected at the same time. The antenna multiplexer RF260X works only in PC mode (RS-232) in time division multiplex mode. This means that each antenna operates with full power for a certain time before the device moves on automatically to the next antenna. The antenna multiplexer normally operates in scan mode or buffered read mode which with suitable parameter assignment add the information about the antenna number to the reply of the transponder. You can operate up to six antennas on one reader via the multiplexer.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 72 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.3.5.1 Installation options with the antenna splitter (2-4 antennas) Possible configurations of the antennas The antenna installations described here have been designed for reading smartlabels (transponders) on goods on conveyor belts, conveyor systems or pallets. A prerequisite is that there are no magnetically conducting materials (e.g. metal) in the vicinity of the antenna or the label. Figure 4-15 Possible configuration of RF290R with ANT D5/D6/D10

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 73 Installation examples Figure 4-16 Installation example with 2 ANT D6 (portal) Figure 4-17 Installation example with ANT D6 (C arrangement)

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 74 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Figure 4-18 Installation example with ANT D6 (tunnel) Note The minimum spacings between the antennas for operation with only one reader may be less than the distances described because this configuration has the same phase.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 75 4.3.5.2 Antenna installation Configuring instructions The antenna installation described below enables detection of transponders moving horizontally through the installation. Depending on the installation (antennas exactly opposite each other or offset in parallel), the label is aligned in parallel with the antennas or arbitrarily. The size of the sensing range depends on the label alignment: Note Remember that the entire acquisition range of the antenna is larger than the transmission window in which the transponder is normally configured. This means there can be label alignments where even labels outside the transmission window will be identified. Labels aligned in parallel with the antennas, for example, can also be detected at larger distances beside or outside the antenna range. For this reason, goods with labels must not be stored within a distance of up to 0.5 m from the installation. If this cannot be complied with, the antennas must be shielded. To achieve three-dimensional detection of the labels in the sensing range, the following requirements must be met: • The gate width must be less than or equal to 800 mm. • The antenna size of the labels should be at least the size of an ISO card (85 mm x 54 mm). • The distance from label to label must be greater than 100 mm. The distance from label to label can be reduced if the gate width is correspondingly reduced. This applies especially for distances under 50 mm. • There should be no more than 16 labels within the sensing range of the antennas at the same time. The number of labels can be increased if the gate width is correspondingly reduced and the maximum speed suitably adapted. • The maximum speed of the labels must not exceed 1 m/s. (This depends on the number and alignment of the labels, the number of data blocks to be processed, the data protocol required and the label type). • To the front and sides of the antenna, there must be a distance of more than 150 mm to metal parts. • There must be no interference to the write/read device from other electrical equipment in the surrounding area. Note The RF290R reader is not capable of multitag operation in the CM mode.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 76 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Required components For installation with ● 2 antennas (gate) ● 3 antennas (C arrangement) ● 4 antennas (tunnel) the following components are required: Table 4- 28 Components required for setting up with 2, 3 or 4 antennas Number for installation with Component Article number 2 ant. 3 ant. 4 ant. 1 1 1 Basic device: RF290R (↔ CM or PC) RF290R: 6GT2821-0AC12 optionally: ASM 475: 6GT2002-0GA10 ASM 456: 6GT2002-0ED00 RF170C: 6GT2002-0HD00 RF180C: 6GT2002-0JD00 RF182C: 6GT2002-0JD10 2 3 4 Antenna ANT D5 / D6 / D10 optionally: ANT D5: 6GT2698-5AA10 ANT D6: 6GT2698-5AB00 ANT D10: 6GT2698-5AF00 2 3 4 With ANT D6 if required: cover 6GT2698-5AD00 1 2 3 Antenna splitter 6GT2603-0AC00 1 1 1 Wide-range power supply unit for SIMATIC RF systems (for PC mode only) EU: 6GT2898-0AA00 UK: 6GT2898-0AA10 US: 6GT2898-0AA20 1 1 1 24 V connecting cable, length 5 m (for PC mode only) 6GT2491-1HH50 1 1 1 Connecting cable: RF290R ↔ PC or RF290R ↔ CM 6GT2891-4KH ... optionally: 6GT2891-4F ... 6GT2891-4EH ... Installation information The cables on the antennas and the antenna splitter are 3.3 m or 10.5 m long. The write/read device must be installed in the vicinity of the antennas. If there are greater distances between the write/read device and the antennas, the antenna cable can be increased by 7.2 m with the extension (6GT2691-0DH72). This results in shorter ranges.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 77 Metal-free space To guarantee perfect functioning of the individual installation versions, all larger metal parts in the vicinity of the antennas must be removed. Figure 4-19 Metal-free space, side view (based on the example of a tunnel arrangement on a conveyor belt) a approx. half antenna length b min. 100 mm c max. 600 mm Metal-free space Figure 4-20 Metal-free space, view from above (based on the example of a tunnel arrangement on a conveyor belt) Metal in the vicinity of the antennas If metal in the vicinity of the antennas cannot be avoided, the following must be noted: ● There must be a minimum allround gap of 100 mm between the antenna and metal. Serious loss of sensing range must be expected above 50 mm. There is no discernible influence at distances greater than 150 mm from the metal. ● The influence of the metal depends heavily on its size and shape. Thin metal rods have less influence on the magnetic field than large surfaces. ● Larger metal surfaces (edge length > 50 mm) in parallel with the antennas or labels result in a short-circuit of the magnetic lines of force. As a result, the labels cannot be read. ● Metal parts under the conveyor belt change the direction of the magnetic lines of force. Serious loss of sensing range must be expected as a result. Horizontally aligned labels cannot be read in such cases.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 78 System Manual, 07/2015, J31069-D0227-U001-A9-7618 ● The metal parts must not form closed loops or circuits. If necessary, these must be electrically interrupted at one point. ● The metal parts in the immediate vicinity of the antenna must be grounded in a mesh with a good HF connection. ● Since the write/read device is installed in a metal housing, and the antennas can couple into the cables to the write/read device, it must be installed at a distance of at least 500 mm from the antennas. Notes on installing and laying the antenna cable To suppress possible interference, an EMC hinged ferrite choke must be fitted to the antenna cables (as well as the antenna cable between the reader and the antenna splitter). The coaxial cable must be wound tightly at least four times through the EMC ring core. The maximum distance between the connecting plug for the reader or the antenna splitter and the ring core must be 100 mm. The antenna cable must always be run vertically from the antennas. A minimum distance of 200 mm to the antennas must be observed as the cables continue. Otherwise, performance losses must be expected. There must be a distance of at least 300 mm between antenna cables and parallel power cables. Unrequired cable length must be secured in a bundle with a diameter of 100 to 150 mm. If the standard antenna cable is too short, it can be increased by 7.20 m with the extension. Slight range losses must be expected here. To achieve optimal read ranges, the antenna cable should not be shortened or lengthened.

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 79 4.3.5.3 Installation options with the antenna multiplexer (2-6 antennas) You can operate up to six antennas on one reader via the multiplexer. The data is processed sequentially. Antenna switchover is performed in time-multiplex mode, so by connecting several antennas together, the processing time / activation time per antenna is lengthened accordingly. Figure 4-21 Configuration example of the antenna multiplexer with ANT D5

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 80 System Manual, 07/2015, J31069-D0227-U001-A9-7618 4.3.6 Chemical resistance of the transponders 4.3.6.1 Overview of the transponders and their housing materials The following sections describe the resistance to chemicals of the various transponders. Resistance to chemicals depends on the housing material used to manufacture the transponders. The following table provides an overview of the housing materials of the transponders: Table 4- 29 Overview of the housing materials of the transponders Housing material Transponder Polyphenylene sulfide (PPS) MDS D117 MDS D124 (6GT2600-0AC10) MDS D139 MDS D160 MDS D339 MDS D423 Polycarbonate (PC) MDS D100 (6GT2600-0AD10) Polyvinyl chloride (PVC) MDS D100 (6GT2600-0AD00-0AX0) MDS D200 MDS D400 Epoxy resin MDS D124 (6GT2600-0AC00) MDS D324 MDS D421 MDS D424 MDS D460 MDS D521 MDS D524 PA6 MDS D127 PA6.6 GF30 MDS D126 MDS D422 MDS D425 MDS D426 MDS D428 MDS D522 MDS D526 MDS D528

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 81 Note Chemical substances not listed The following sections describe the resistance of the various transponders to specific substances. If you require information about chemical substances that are not listed, contact Customer Support. 4.3.6.2 Polyphenylene sulfide (PPS) The data memory has special chemical resistance to solutions up to a temperature of 200 °C. A reduction in the mechanical properties has been observed in aqueous solutions of hydrochloric acid (HCl) and nitric acid (HNO3) at 80 °C. The plastic housings are resistant to all types of fuel including methanol. Table 4- 30 Chemical resistance - polyphenylene sulfide (PPS) Substance Test conditions Rating Concentration [%] Temperature [°C] Acetone 55 ℃ عربي n-Butanol (butyl alcohol) 80 ℃ عربي Butanone-2 (methyl ethyl ketone) 60 ℃ عربي n-Butyl acetate 80 ℃ عربي Brake fluid 80 ℃ عربي Calcium chloride (saturated) 80 ℃ عربي Diesel fuel 80 ℃ عربي Diethyl ether 23 ℃ عربي Frigen 113 23 ℃ عربي Anti-freeze 120 ℃ عربي Kerosene 60 ℃ عربي Methanol 60 ℃ عربي Engine oil 80 ℃ عربي Sodium chloride (saturated) 80 ℃ ○○○○ Sodium hydroxide 30% 80 ℃ ○○○○ Sodium hypochlorite (30 or 180 days) 5% 80 ℃ ○○ 5% 80 ℃ - Sodium hydroxide solution 30% 90 ℃ ○○○○ Nitric acid 10% 23 ℃ ○○○○ Hydrochloric acid 10% 80 ℃ - Sulfuric acid 10% 23 ℃ ○○○○ 10% 80 ℃ ○○ 30% 23 ℃ ○○○○ Tested fuels 80 ℃ ○○○○

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 82 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Substance Test conditions Rating Concentration [%] Temperature [°C] FAM testing fluid acc. to DIN 51 604-A Toluene 80 ℃ ○○ 1, 1, 1-Trichloroethane Xylene 80 ℃ ○○○○ Zinc chloride (saturated) 80 ℃ ○○ 75 ℃ ○○○○ Explanation of the rating ○○○○ Resistant ○○○ Practically resistant ○○ Conditionally resistant ○ Less resistant - Not resistant 4.3.6.3 Polycarbonate (PC) Table 4- 31 Chemical resistance - polycarbonate (PPS) Substance Test conditions Rating Concentration [%] Temperature [°C] Mineral lubricants ○○ Aliphatic hydrocarbons ○○○○ Aromatic hydrocarbons - Gasoline - Weak mineral acids ○○○○ Strong mineral acids ○○ Weak organic acids ○○○○ Strong organic acids ○○ Oxidizing acids - Weak alkaline solutions - Strong alkaline solutions - Trichloroethylene - Perchloroethylene - Acetone - Alcohols ○○ Hot water (hydrolysis resistance) -

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 83 Explanation of the rating ○○○○ Resistant ○○○ Practically resistant ○○ Conditionally resistant ○ Less resistant - Not resistant 4.3.6.4 Polyvinyl chloride (PVC) Table 4- 32 Chemical resistance - polyvinyl chloride (PVC) Substance Test conditions Rating Concentration [%] Temperature [°C] Salt water 5 % ○○○○ Sugared water 10 % ○○○○ Acetic acid, w. 5 % ○○○○ Sodium carbonate, w. 5 % ○○○○ Ethyl alcohol, w. 60 % ○○○○ Ethylene glycol 50 % ○○○○ Fuel B (acc. to ISO 1817) ○○○○ Human sweat ○○○○ Explanation of the rating ○○○○ Resistant ○○○ Practically resistant ○○ Conditionally resistant ○ Less resistant - Not resistant w. Water solution 4.3.6.5 Epoxy resin Table 4- 33 Chemical Resistance - epoxy resin Substance Test conditions Rating Concentration [%] Temperature [°C] Allyl chloride 20 ℃ ○○○○ Formic acid 50 % 20 ℃ ○○○○ 100 % 20 ℃ ○○ Ammonia, gaseous 20 ℃ ○○○○

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 84 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Substance Test conditions Rating Concentration [%] Temperature [°C] Ammonia, liquid, water-free 20 ℃ - Ammonium hydroxide 10 % 20 ℃ ○○○○ Ethanol 40 ℃ ○○○○ 60 ℃ ○○○○ Ethyl acrylate 20 ℃ ○○○○ Ethyl glycol 60 ℃ ○○○○ Gasoline, aroma-free 20 ℃ ○○○○ Gasoline, containing benzene 20 ℃ ○○○○ Benzoates (Na–, Ca– among others) 40 ℃ ○○○○ Benzoic acid 20 ℃ ○○○○ Benzene 20 ℃ ○○○○ Borax 60 ℃ ○○○○ Boric acid 20 ℃ ○○○○ Bromine, liquid 20 ℃ - Bromides (K–, Na– among others) 60 ℃ ○○○○ Bromoform 100 % 20 ℃ ○○○○ Bromine water 20 ℃ - Butadiene (1,3–) 20 ℃ ○○○○ Butane, gaseous 20 ℃ ○○○○ Butanol 20 ℃ - Butyric acid 100 % 20 ℃ ○○ Carbonates (ammonium–, Na– among others) 60 ℃ ○○○○ Chlorine, liquid 20 ℃ - Chlorine, gaseous, dry 100 % 20 ℃ - Chlorobenzene 20 ℃ ○○○○ Chlorides (ammonium–, Na– among others) 60 ℃ ○○○○ Chloroform 20 ℃ - Chlorophyll 20 ℃ ○○○○ Chlorosulfuric acid 100 % 20 ℃ - Chlorine water (saturated solution) 20 ℃ ○○ Chromates (K–, Na– among others) Up to 50 % 40 ℃ ○○○○ Chromic acid Up to 30 % 20 ℃ - Chromosulfuric acid 20 ℃ - Citric acid 20 ℃ ○○○○ Cyanamide 20 ℃ ○○○○ Cyanides (K–, Na– among others) 60 ℃ ○○○○ Dextrin, w. 60 ℃ ○○○○ Diethyl ether 20 ℃ ○○○○ Diethylene glycol 60 ℃ ○○○○

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 85 Substance Test conditions Rating Concentration [%] Temperature [°C] Dimethyl ether 20 ℃ ○○○○ Dioxane 20 ℃ - Developer 40 ℃ ○○○○ Acetic acid 100 % 20 ℃ ○○ Ethanol 60 ℃ ○○○○ Fixing bath 40 ℃ ○○○○ Fluorides (ammonium–, K–, Na– among others) 40 ℃ ○○○○ Hydrofluoric acid Up to 40 % 20 ℃ ○○○○ Formaldehyde 50 % 20 ℃ ○○○○ Formamide 100 % 20 ℃ ○○○○ Gluconic acid 20 ℃ ○○○○ Glycerine 60 ℃ ○○○○ Glycol 60 ℃ ○○○○ Urine 20 ℃ ○○○○ Uric acid 20 ℃ ○○○○ Hydroxides (ammonium...) 10 % 20 ℃ ○○○○ Hydroxides (Na–, K–) 40 % 20 ℃ ○○○○ Hydroxides (alkaline earth metal) 60 ℃ ○○○○ Hypochlorites (K–, Na– among others) 60 ℃ ○○○○ Iodides (K–, Na– among others) 60 ℃ ○○○○ Silicic acid 60 ℃ ○○○○ Cresol Up to 90 % 20 ℃ - Methanol 100 % 40 ℃ ○○○○ Methylene chloride 20 ℃ - Lactic acid 100 % 20 ℃ ○○ Mineral oils 40 ℃ ○○○○ Nitrates (ammonium..., K– among others) 60 ℃ ○○○○ Nitroglycerin 20 ℃ - Oxalic acid 20 ℃ ○○○○ Phenol 1 % 20 ℃ ○○○○ Phosphates (ammonium..., Na– among others) 60 ℃ ○○○○ Phosphoric acid 50 % 60 ℃ ○○○○ 85 % 20 ℃ ○○○○ Propanol 20 ℃ ○○○○ Nitric acid 25 % 20 ℃ - Hydrochloric acid 10 % 20 ℃ - Brine 60 ℃ - Sulfur dioxide 100 % 20 ℃ ○○ Carbon disulfide 100 % 20 ℃ -

RF200 system planning

4.3 Installation guidelines SIMATIC RF200 86 System Manual, 07/2015, J31069-D0227-U001-A9-7618 Substance Test conditions Rating Concentration [%] Temperature [°C] Sulfuric acid 40 % 20 ℃ - Sulfurous acid 20 ℃ ○○ Soap solution 60 ℃ ○○○○ Sulphates (ammonium..., Na– among others) 60 ℃ ○○○○ Sulfites (ammonium..., Na– among others) 60 ℃ - Tar, aroma-free 60 ℃ ○○○○ Turpentine 20 ℃ ○○○○ Trichloroethylene 20 ℃ - Hydrogen peroxide 30 % 20 ℃ ○○○○ Tartaric acid 20 ℃ ○○○○ Explanation of the rating ○○○○ Resistant ○○○ Practically resistant ○○ Conditionally resistant ○ Less resistant - Not resistant 4.3.6.6 PA6.6 GF30 Table 4- 34 Chemical resistance - PA6.6 GF30 Substance Test conditions Rating Concentration [%] Temperature [°C] Mineral lubricants ○○○○ Aliphatic hydrocarbons ○○○○ Aromatic hydrocarbons ○○○○ Gasoline ○○○○ Weak mineral acids ○○○ Strong mineral acids - Weak organic acids ○○ Strong organic acids - Oxidizing acids - Weak alkaline solutions ○○ Strong alkaline solutions - Trichloroethylene ○○○○ Perchloroethylene ○○○○ Acetone ○○○○

RF200 system planning

4.4 Further information SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 87 Substance Test conditions Rating Concentration [%] Temperature [°C] Alcohols ○○○○ Hot water (hydrolysis resistance) ○○ Explanation of the rating ○○○○ Resistant ○○○ Practically resistant ○○ Conditionally resistant ○ Less resistant - Not resistant 4.4 Further information Further information on "Fundamentals of application planning" and "EMC" can be found in RF300 system manual (https://support.industry.siemens.com/cs/ww/en/view/21738946).

RF200 system planning

4.4 Further information SIMATIC RF200 88 System Manual, 07/2015, J31069-D0227-U001-A9-7618

System Manual, 07/2015, J31069-D0227-U001-A9-7618

89 Readers 5 NOTICE Pulling and plugging readers Pull or plug the reader only when the power supply is turned off If this is not observed, under certain conditions, the reader will not start up correctly and communication with a transponder will not be possible. Note IO-Link variants of the RF200 readers The IO-Link variants of the readers are not included in the system manual. You will find these in the "SIMATIC RF200 IO-Link (https://support.industry.siemens.com/cs/ww/en/view/60641859)" operating instructions.

5.1 SIMATIC RF210R

SIMATIC RF200 90 System Manual, 07/2015, J31069-D0227-U001-A9-7618 5.1 SIMATIC RF210R 5.1.1 Features SIMATIC RF210R Characteristics Design ① RS422 interface ② Status display Application Identification tasks on assembly lines in harsh in- dustrial environments 5.1.2 RF210R ordering data Article number RF210R with RS422 interface (3964R) 6GT2821-1AC10

5.1 SIMATIC RF210R

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 91 5.1.3 Pin assignment RF210R with RS422 interface Pin Pin Device end 8-pin M12 Assignment 1 + 24 V 2 - Transmit 3 0 V 4 + Transmit 5 + Receive 6 - Receive 7 Unassigned 8 Ground (shield) 5.1.4 Display elements of the RF210R reader Color Meaning green flashing Operating voltage present, reader not initialized or antenna switched off permanently lit Operating voltage present, reader initialized and antenna switched on yellow1) Transponder present flashing red Error has occurred, the type of flashing corresponds to the error code in the table in the section "Error codes". The optical error display is only reset if the corresponding reset parameter ("option_1 = 2") is set (see Product infor- mation "SIMATIC RF200 command set" (https://support.industry.siemens.com/cs/us/en/view/44864850)). 1) Only in the "with presence" mode.

5.1 SIMATIC RF210R

SIMATIC RF200 92 System Manual, 07/2015, J31069-D0227-U001-A9-7618 5.1.5 Minimum distance between RF210R readers RF210R side by side D ≥ 60 mm Figure 5-1 Minimum distance between RF210R readers RF210R face to face D ≥ 100 mm Figure 5-2 Face-to-face distance between two RF210Rs

5.1 SIMATIC RF210R

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 93 5.1.6 Technical specifications of the RF210R reader Table 5- 1 Technical specifications of the RF210R reader 6GT2821-1AC10 Product type designation SIMATIC RF210R Radio frequencies Operating frequency, rated value 13.56 MHz Electrical data Maximum range 20 mm Maximum data transmission rate reader ↔ tran- sponder (tag) ISO tags • Read • approx. 1500 bytes/s • Write • approx. 1500 bytes/s Typical transmission time for user data per byte • for write access • 0.6 ms • for read access • 0.6 ms Baud rate 19200, 57600, 115200 Bd Read/write distances of the reader see section "Field data (Page 37)" Interfaces Electrical connector design M8, 8-pin Standard for interfaces for communication RS-422 Antenna integrated Mechanical specifications Housing • Material • Brass, nickel-plated • Color • Silver Recommended distance to metal 0 mm Supply voltage, current consumption, power loss Supply voltage 24 VDC Typical current consumption 50 mA

5.1 SIMATIC RF210R

SIMATIC RF200 94 System Manual, 07/2015, J31069-D0227-U001-A9-7618 6GT2821-1AC10 Permitted ambient conditions Ambient temperature • During operation • -20 … +70 °C • During transportation and storage • -25 … +85 °C Degree of protection to EN 60529 IP67 Shock-resistant to EN 60721-3-7, Class 7 M3 50 g Vibration-resistant to EN 60721-3-7, Class 7 M3 20 g Torsion and bending load Not permitted Design, dimensions and weights Dimensions (Ø x H) 18 x 83 mm Weight 65 g Type of mounting 2 x nuts M18 Cable length for RS-422 interface, maximum 1000 m LED display design 3-color LED (operating voltage, presence, error) 5.1.7 Approvals FCC information Siemens SIMATIC RF210R (MLFB 6GT2821-1AC10) FCC ID NXW-RF210R This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

5.1 SIMATIC RF210R

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 95 IC information This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Le présent appareil est conforme aux CNR d`Industrie Canada applicables aux appareils radio exempts de licence. L`exploitation est autorisée aux deux conditions suivantes : (1) L`appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l`appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d`en compromettre le fonctionnement. 5.1.8 Dimension drawing Figure 5-3 RF210R dimension drawing Dimensions in mm

5.2 SIMATIC RF210M

SIMATIC RF200 96 System Manual, 07/2015, J31069-D0227-U001-A9-7618 5.2 SIMATIC RF210M 5.2.1 Features SIMATIC RF210M Characteristics Design ① RS422 interface ② Status display Application Reader for hand work and rework places, picking, track and trace, tool Ident 5.2.2 Ordering data RF210M Article number RF210M with RS-422 interface (3964R) 6GT2823-0AA00

5.2 SIMATIC RF210M

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 97 5.2.3 Installing the RF210M reader The following figure shows the completely mounted reader. Note that you can mount the suspension bracket at two different points ①. If you do not mount the handle, we recommend that you close the opening ② with the protective cap. ① Holes for mounting the suspension bracket ② Thread for mounting the handle Figure 5-4 Installing the reader 5.2.4 Pin assignment RF210M with RS-422 interface Pin Pin Device end 8-pin M12 Assignment 1 + 24 V 2 - Transmit 3 0 V 4 + Transmit 5 + Receive 6 - Receive 7 Unassigned 8 Ground (shield)

5.2 SIMATIC RF210M

SIMATIC RF200 98 System Manual, 07/2015, J31069-D0227-U001-A9-7618 5.2.5 Display elements of the RF210M reader Color Meaning green flashing Operating voltage present, reader not initialized or antenna switched off permanently lit Operating voltage present, reader initialized and antenna switched on yellow1) Transponder present flashing red Error has occurred, the type of flashing corresponds to the error code in the table in the section "Error codes". The optical error display is only reset if the corresponding reset parameter ("option_1 = 2") is set (see Product infor- mation "SIMATIC RF200 command set" (https://support.industry.siemens.com/cs/ww/en/view/44864850)). 1) Only in the "with presence" mode. 5.2.6 Technical specifications of the RF210M reader Table 5- 2 Technical specifications of the RF210M reader 6GT2823-0AA00 Product type designation SIMATIC RF210M Radio frequencies Operating frequency, rated value 13.56 MHz Electrical data Maximum range 20 mm Maximum data transmission rate reader ↔ tran- sponder (tag) ISO tags • Read • approx. 1500 bytes/s • Write • approx. 1500 bytes/s Typical transmission time for user data per byte • for write access • 0.6 ms • for read access • 0.6 ms Baud rate 19200, 57600, 115200 Bd Read/write distances of the reader see section "Field data (Page 37)" Interfaces Electrical connector design M8, 8-pin Standard for interfaces for communication RS-422 Antenna integrated

5.2 SIMATIC RF210M

SIMATIC RF200 System Manual, 07/2015, J31069-D0227-U001-A9-7618 99 6GT2823-0AA00 Mechanical specifications Housing • Material • POM • Color • Black Supply voltage, current consumption, power loss Supply voltage 24 VDC Typical current consumption 50 mA Permitted ambient conditions Ambient temperature • During operation • -20 … +50 °C • During transportation and storage • -25 … +60 °C Degree of protection to EN 60529 IP54 Shock-resistant to EN 60721-3-7, Class 7 M3 50 g Vibration-resistant to EN 60721-3-7, Class 7 M3 20 g Design, dimensions and weights Dimensions • Reader with handle (L x W x H) 195 x 26 x 140 mm • Reader without handle (L x W x H) 195 x 26 x 46 mm • Spiral connecting cable (L) 2 m maximum working length 3.5 m Weight 460 g Type of mounting Bracket for for hanging up Cable length for RS-422 interface, maximum 1000 m LED display design 3-color LED (operating voltage, presence, error)

5.2 SIMATIC RF210M

SIMATIC RF200 100 System Manual, 07/2015, J31069-D0227-U001-A9-7618 5.2.7 Approvals FCC information Siemens SIMATIC RF210R (MLFB 6GT2821-1AC10) FCC ID NXW-RF210R This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. IC information This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Le présent appareil est conforme aux CNR d`Industrie Canada applicables aux appareils radio exempts de licence. L`exploitation est autorisée aux deux conditions suivantes : (1) L`appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l`appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d`en compromettre le fonctionnement.