YOKOGAWA UT32A Technical Information
Read Online
Read the YOKOGAWA UT32A Technical Information online using the built-in PDF viewer.
Text of the manual
UTAdvanced Quick Setting
(Controlling Furnace Temperature with a Motorized Valve)
TI 04L01L01-09EN
Foreword
The contents of this document are subject to change without prior notice as a result of improvements in performance or functionality.
Copying or reproduction by any means of all or any part of the contents of this document without permission is strictly prohibited.
Use of this document is at the users risk.
Technical
Information
This document is subject to change without notice.
TI04L01L01-09EN
2011.12.16 1st Edition (YK)
■ Overview
This is an example wiring and settings using the UTAdvanced Quick Setting function for "temperature
control in a furnace with a motorized valve." For more details, see the user's manual.
■ Relevant models
Position proportional models of the UT32A, UT35A, UT52A, and UT55A
■ System
■ Wiring
Compensating
Thermocouple type K
Opening signal
Thermocouple
type K
Compensating lead wire
Power
supply
OUT
+
-
PV
Normal rotation
Reverse
rotation
COM
100%
0%
Compensating lead wire
Power
supply
OUT
+
-
PV
Normal rotation
Reverse
rotation
COM
100%
0%
UT32A, UT52A position proportional model
UT35A, UT55A position proportional model
This document is subject to change without notice.
TI 04L01L01-09EN 2011.12.16-00
■ Settings
To set PID control, thermocouple type K (range 0.0 to 1000.0°C), and position proportional output, set
the following parameters.
(1) Select the desired parameter with the UP or DOWN key
(2) Press SET/ENTER (the setting value blinks)
(3) Change the setting with the UP or DOWN key
(4) Press SET/ENTER to set the new value (the setting value stops blinking but remains
bright)
● Redoing the Quick Setting
Once functions are configured with the Quick Setting, the Quick Setting function
will not appear after you restart. However, you can redo the Quick Setting by
following the procedure below.
(1) Set the Quick Setting parameter QSM to ON, and re-engage power
(2) Set the PV input type parameter IN to OFF, and re-engage power
Press SET/ENTER to accept the "YES" option.
Quick Setting starts
First, the control type parameter CNt appears.
Set CNT (control type) to PID (initial value).
OFF is displayed for IN (the PV input type).
Set IN (PV input type) to thermocouple type K2.
(K2: -270.0 to 1000.0°C)
Set UNIT (PV input unit) to C: Celsius (inital value)
CONTROLTYPE
STARTQUICK
SETTING
1.
QSM YES
2.
CNt
PID
PV INPUT TYPE
3.
IN
OFF
PV INPUT TYPE
4.
IN
K2
PV INPUT UNIT
5.
UNIt
C
CONTROLTYPE
STARTQUICK
SETTING
1.
QSM YES
2.
CNt
PID
PV INPUT TYPE
3.
IN
OFF
PV INPUT TYPE
4.
IN
K2
PV INPUT UNIT
5.
UNIt
C
Power
Quick Setting
start
This document is subject to change without notice.
TI 04L01L01-09EN 2011.12.16-00
Set RH (maximum value of PV input range) to 1000.0°C.
Set RL (minimum value of PV input range) to 0.0°C (the initial value).
Finally, EXIT is displayed. Select YES and press SET/ENTER to complete the
basic function setup and return to the operating screen. Or, you can select NO
to continue with the Quick Setting.
After finishing the Quick Setting, please adjust the position of the motorized valve.
Revision Information
Document name: Setup Procedure: UTAdvanced Quick Setting (Controlling Furnace Temperature with a
Motorized Valve)
Document number: TI 04L01L01-09EN
First edition: December, 2011
Newly released
MAXIMUM
VALUE OF PV
INPUT RANGE
6.
RH
1000.0
7.
FINISH
8.
EXIt
YES
MINIMUM
VALUE OF PV
INPUT RANGE
RL
0.0