COMPAX-M / COMPAX-S - Option F2
Subject to technical modification. Data based on the technical prior art at the time of printing.
14.01.00 12:56
192-040020 N4
C O M P A X f i e l d b u s i n t e r f a c e
I n t e r b u s - S
from COMPAX software version >V5.0
from Interbus-S – Software version >V2.1
January 2000
W e a u t o m a t e m o t i o n
DIN EN ISO 9001
C
E
R
T
I
F
I
E
D
Q
U
A
L
I
T
Y
S
Y
S
T
E
M
Main Office
Parker Hannifin GmbH
EMD HAUSER
P. O. Box: 77607-1720
Robert-Bosch-Str. 22
D-77656 Offenburg, Germany
Phone: +49 (0)781 509-0
Fax:
+49 (0)781 509-176
http://www.Parker-EMD.com
Great Britain:
Parker Hannifin plc
EMD Digiplan
21 Balena Close
Poole, Dorset
BH17 7DX UK
Phone: +44 (0)1202 69 9000
Fax:
+44 (0)1202 69 5750
http://www.Parker-EMD.com
COMPAX - Option F2: Interbus-S
2
Contents
1.
Introduction.........................................................4
1.1
Addressing ......................................................... 4
1.2
Bus connection.................................................. 4
1.2.1
The bus wiring ....................................... 4
1.5
PDU Length ........................................................ 5
1.6
Communication.................................................. 5
1.3
Identification code (ID-Code) ............................ 5
1.4
Selectable Data Channels ................................. 6
1.4.1
Bus – Setting using the front cover........ 8
1.7
Data types........................................................... 9
1.7.1
Boolean.................................................. 9
1.7.2
Integer.................................................... 9
1.7.3
Unsigned................................................ 9
2.
Object index ......................................................10
2.1
Communication objects: Overview sorted by
Symbol.............................................................. 10
2.2
Communication objects: Overview sorted by
Index ................................................................. 12
2.3
Device identification........................................ 14
2.3.1
FKT_GRUPPE..................................... 14
2.3.2
S31_S39.............................................. 15
2.4
Control.............................................................. 16
2.4.1
Operating mode................................... 16
2.4.2
BETR_ART_AZ.................................... 16
2.4.3
STEUERBYTE..................................... 17
2.4.4
STATUSBYTE ..................................... 17
2.4.5
CPX_STW ........................................... 18
2.4.6
CPX_ZSW ........................................... 19
2.4.7
STEUERWORT ................................... 20
2.4.8
STATUSWORT.................................... 20
2.4.9
Pop-up message processing ............... 21
2.4.10
CONTROL ........................................... 22
2.4.11
COMMAND.......................................... 23
2.4.12
P .......................................................... 23
2.4.13
Px......................................................... 24
2.5
Diagnosis.......................................................... 25
2.5.1
STOERUNG......................................... 25
2.5.2
S30 ...................................................... 26
2.5.3
S6 ........................................................ 26
2.5.4
S10 ...................................................... 26
2.5.5
S9 ........................................................ 27
2.5.6
S11 ...................................................... 27
2.5.7
S23_S26.............................................. 27
2.5.8
S .......................................................... 28
2.6
Torque, current, voltage.................................. 29
2.6.1
MOMENT_MAX ................................... 29
2.6.2
NENNMOMENT................................... 29
2.6.3
MOMENT_IST ..................................... 30
2.6.4
S5 ........................................................ 30
2.6.5
NENNSTROM...................................... 30
2.6.6
ZWK_SPG ........................................... 31
2.6.7
S7_S8.................................................. 31
2.7
Positioning ....................................................... 32
2.7.1
POSA................................................... 32
2.7.2
POSR...................................................33
2.7.3
LAGE_ZIEL..........................................33
2.7.4
S1.........................................................34
2.7.5
LAGE_IST............................................35
2.7.6
S2.........................................................35
2.7.7
S12.......................................................35
2.7.8
REALNULL ..........................................36
2.7.9
GRENZEN............................................36
2.7.10
POS_FENSTER...................................37
2.7.11
SCHLEPP_FEN ...................................37
2.7.12
S3.........................................................38
2.7.13
POLARITAET.......................................38
2.7.14
REF_MODE .........................................38
2.7.15
CAM_CMD...........................................39
2.7.16
WAITPOSA ..........................................39
2.7.17
WAITPOSR..........................................40
2.8
SPEED...............................................................41
2.8.1
SPEED.................................................41
2.8.2
OVERRIDE ..........................................41
2.8.3
POSR0SPEED.....................................42
2.8.4
POSRXSPEEDY..................................42
2.8.5
PRXSDYALZ........................................43
2.8.6
DREHZAHLMAX..................................44
2.8.7
GESCHW_MAX ...................................44
2.8.8
VERF_GESCHW .................................45
2.8.9
S4.........................................................45
2.8.10
GESCHW_IST .....................................46
2.8.11
GESCHW_REF....................................46
2.9
Acceleration......................................................47
2.9.1
RAMPENFORM ...................................47
2.9.2
ACCEL_POS........................................47
2.9.3
ACCEL_NEG .......................................48
2.9.4
RAMPE_POS.......................................48
2.9.5
RAMPE_NEG.......................................49
2.9.6
RAMPE_NOTS ....................................49
2.9.7
RAMPE_REF .......................................50
2.10
Inputs/outputs ..................................................51
2.10.1
INPUT_WORD.....................................51
2.10.2
OUTPUT_WORD.................................51
2.10.3
OUTPUT ..............................................52
2.10.4
OUTPUT_MASK ..................................52
2.10.5
POSROUTPUTP..................................53
2.10.6
POSROUTPUTN..................................53
2.11
Programming....................................................54
2.11.1
N ..........................................................54
2.11.2
Nx.........................................................54
2.11.3
GOTO ..................................................60
2.11.4
START_N.............................................60
2.11.5
START_N_GO .....................................61
2.11.6
TEACH_N ............................................61
2.11.7
CAM_MEM_P ......................................62
2.11.8
CAM_MEM...........................................62
2.11.9
VX ........................................................62
OBJECT_REQ and OBJECT_RSP for 8 byte process
data channel .....................................................64
OBJECT_REQ ...................................................66
OBJECT_RSP....................................................66
2.12
Process data control........................................67
2.12.1
PAD_Steuerung ...................................67
2.12.2
PED_Steuerung ...................................70
2.12.6
PE_SELECT ........................................72
2.12.7
PA_SELECT ........................................73
2.12.8
PA_ENABLE ........................................74
2.12.10 PAD_INI............................................... 76
2.12.3
IN_SELECT......................................... 77
2.12.4
OUT_SELECT..................................... 77
2.12.5
OUT_ENABLE..................................... 78
3.
DRIVECOM-PROFILE 22, from COMPAX
Software-Version 3.01......................................79
4.
COMPAX Parameters for the Interbus-S........81
5.
COMPAX Interbus-S Error messages ............82
6.
Index ..................................................................83
Compatibility
Using the setting P196="0" makes this software version V2.1
compatible with software version V1.15 ... V2.0.
With P196="0", the process data channel is automatically
assigned as follows:
Process input data channel PE with INPUT_WORD
Process output data channel PA with OUTPUT_WORD
Device allocation
This documentation applies for these devices:
♦ COMPAX 10XXSL with the Option F2 (available 04/2000)
♦ COMPAX 25XXS with the Option F2
♦ COMPAX 45XXS with the Option F2
♦ COMPAX 85XXS with the Option F2
♦ COMPAX P1XXM with the Option F2
♦ COMPAX 02XXM with the Option F2
♦ COMPAX 05XXM with the Option F2
♦ COMPAX 15XXM with the Option F2
♦ OMPAX 35XXM with the Option F2
XX:
any characters
F2:
Interbus-S - Option
Key to unit designation
e.g.: COMPAX 0260M:
COMPAX:name
02:
performance class
60:
Variant
e.g. "00": Standard model
M:
Type of device
M: multi-axis unit
S: single-axis unit
HAUSER rating plate
The rating plate is found on the top of the unit and contains
the following information:
equipment
name
part number
serial number
option name
038106 0001 951-160101 Compax 0260M
E2
The communication module Option F2 (IFM9) allows
COMPAX-M/S to contact the Interbus-S by the company
Phoenix. The Interbus-S protocol is based on a summation-
frame message and is optimised for the cyclical and time
equi-distant transmission of process data. The summation-
frame message contains the information for or from all
participants and is simultaneously sent to or received from
all devices. The integration of parameter information in the
cyclical protocol occurs sequentially, i.e. longer data blocks
are broken down into individual, short information units and
inserted in order into the cyclical protocol.
1.1 Addressing
Addressing individual participants occurs via their physical
position in the ring and via central address lists held in the
Master. This removes the need for manual participant
addressing.
1.2 Bus connection
Each COMPAX-M/S with IFM-9 is a 2-cable remote bus
participant.
Connection to the Interbus-S occurs via the 2-cable remote
bus connection on the network module or on the COMPAX-
S.
Mains power module
The X6 connection (Interbus-S IN = incoming remote bus)
is connected via the pre-assembled ribbon cable with
Option F2 of the 1. COMPAX-M/S which is connected to
the network module. If additional COMPAX-M/S are
connected to the network module, the Interbus-S is set up
via ribbon cables from one device to the next.
The X7 connection (Interbus-S OUT = outgoing remote
bus) is connected with the IFM-9 of the last COMPAX-M
which is connected to the network module, if the ribbon
cable short circuit plug is inserted in this device.
1.2.1 The bus wiring
RS 485
POWER SUPPLY
Ξ 6
Ξ 7
Ξ 8
Ρ ε α δ ψ
Ερρορ
ΡΣ 485
ΙΝ
Ο ΥΤ
Χοντρολ
DIGITAL
Statu s
Nu mb er
X6
X8
X10
-
+
Enter
R ea dy
Error
RS232
Inp ut
Ou tpu t
Te st
Control
X9
X11
Value
COMPAX-M
NMD COMPAX-M with option F2
SSC13/..
COMPAX-S with option F2
C O M P A X - S
Σ τ ατ υ σ
Ν υ µ β ε ρ
Ξ 6
Ξ 8
Ξ 10
−
+
Εντερ
Ρε αδ ψ
Ερρορ
ΡΣ 23 2
Ινπυτ
Ο υ τ πυ τ
Τ ε σ τ
Χοντρολ
Ξ 9
Ξ 11
ς α λυ ε
Σ τ ατ υ σ
Ν υ µ β ε ρ
Ξ 6
Ξ 8
Ξ 10
−
+
Εντερ
Ρε αδ ψ
Ερρορ
ΡΣ 23 2
Ινπυτ
Ο υ τ πυ τ
Τ ε σ τ
Χοντρολ
Ξ 9
Ξ 11
ς α λυ ε
Siemens SPS
Siemens SPS
Siemens SPS
Siemens SPS
X1
X2
24 V
GND
ERDE
RS 485
RS 485
E1
E2
E3
E4
E5
E6
E7
E8
E9
E10
E11
A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
E12
E13
E14
E15
E16
E17
E18
E19
E20
E21
E22
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
PLC
COMPAX-S with option F2
∆ΙΓΙΤΑΛ
Στ ατυ σ
Νυ µβε ρ
Ξ6
Ξ8
Ξ10
−
+
Εντ ερ
Ρε α δψ
Ερρορ
ΡΣ232
Ινπυτ
Ου τπυτ
Τε στ
Χοντρολ
Ξ9
Ξ11
ςα λυε
COMPAX-M
∆ΙΓΙΤΑΛ
Στ ατυ σ
Νυ µβε ρ
Ξ6
Ξ8
Ξ10
−
+
Εντ ερ
Ρε α δψ
Ερρορ
ΡΣ232
Ινπυτ
Ου τπυτ
Τε στ
Χοντρολ
Ξ9
Ξ11
ςα λυε
COMPAX-M
∆ΙΓΙΤΑΛ
Στ ατυ σ
Νυ µβε ρ
Ξ6
Ξ8
Ξ10
−
+
Εντ ερ
Ρε α δψ
Ερρορ
ΡΣ232
Ινπυτ
Ου τπυτ
Τε στ
Χοντρολ
Ξ9
Ξ11
ςα λυε
COMPAX-M
C O M P A X - S
The Interbus-S- signals are transferred along the
existing ribbon cable within a COMPAX-M system
network and a network module.
Cable plan SSK13/ :
9-way Sub-D-pin
plug shell with screwed
connection UNC4-40
1
6
2
7
housing
DI2
1
6
2
7
housing
SSC 13/..
1
5
6
9
9-way Sub-D-socket board
plug shell with screwed
connection UNC4-40
1
5
6
9
3
3
5 x 0,25mm + shield
2
5
9
DO2
DO2
DI2
DI1
DO1
DO1
DI1
The bus wiring
5
Connections SSK13/ :
The assignment on the network module or on the
COMPAX-S corresponds to the Interbus-S - standard.
Possible connections with SSK13/..:
! Network module X7 (OUT)
→ Network module X6 (IN)
! Network module X7 (OUT)
→ COMPAX-S X5 (IN)
! COMPAX-S X7 (OUT)
→ Network module X6 (IN)
! COMPAX-S X7 (OUT)
→ COMPAX-S X5 (IN)
! IIPC / SPS
→ COMPAX-S X5 (IN)
! IIPC / SPS
→ Network module X6 (IN)
If there is a direct power supply by COMPAX-M, the
connection is made to the component block
EAM5/01 instead of to the network module.
1.5
PDU Length
64 Byte
Maximum message length through the PCP channel.
1.6 Communication
Option F2 includes the Interbus-S communications
software PCP 1.5 (Peripherals Communication Protocol),
which allows it to transmit, in addition to cyclical process
data, acyclic parameters (2 Byte data channel).
The following services are available:
Context Management
! Initiate
Start communication connection
! Abort
Quit communication connection
! Reject
Reject a service
VFD Support
! Status
Reading the device and user status
! Identify Reading the manufacturer, type and version
Variables Access
! Read
Reading a variable (parameter)
♦ Write
Writing a variable
1.3 Identification code (ID-
Code)
When P196 Bit 0...2 < "4"
227
(0xE3)
When P196 Bit 0...2 = "4"
(Operation without acyclic channel = without PCP-
communication)
3
(0x03)
1.4 Selectable Data Channels
The length of the process data depends on the Interbus-S software version and the COMPAX Parameter P196 (see also page
81).
The described features are not only valid for the process output data (PAD: data for COMPAX) but also for the process input
data (PED: data from COMPAX
Process output data PAD:
Master ⇒
⇒
⇒
⇒ COMPAX
Process input data PED:
Master ⇐
⇐
⇐
⇐ COMPAX
Software-
Version
P196
acyclic data channel
Process data length
cyclic data channel
Data channel structure
(split into bytes))
less than 2.00
x
2 Byte PCP communication
2 bytes (1 word)
PCP
PCP
PD1
PD2
From 2.00
0/1
2 Byte PCP communication
2 bytes (1 word)
PCP
PCP
PD1
PD2
From 2.00
2
2 Byte PCP communication
4 byte (2 words)
PCP
PCP
PD1
PD2
PD3
PD4
From 2.00
3
2 Byte PCP communication
6 byte (3 words)
PCP
PCP
PD1
PD2
PD3
PD4
PD5
PD6
PD1
PD2
PD3
PD4
PD5
PD6
PD7
PD8
From 2.10
Bit 0...2
="1"
no acyclic data channel
(no PCP communication)
8 byte (4 words)
PCP:
acyclic data channel: is used for e.g. configuration.
PD:
cyclic process data: is used e.g. for transferring actual values.
Acyclic data channel (PCP) for parameter data
This data channel will be described via your Interbus-S software. All objects can be transferred through this channel. The
Interbus-S software splits longer objects which are then transferred in several cycles.
Cyclic process data
Only approved objects can be used on the cyclic process data channel. Whether an object has been approved for a PAD or
PED channel is outlined in the respective objective descriptions under the heading PD “depictions” or in the object overview
(page 9 onwards) in the column headed PD.
Assignment of PED and PAD:
There are various ways of loading objects onto the process data channels.
1. Via the COMPAX parameter P135 - P142
These parameters are only accepted by COMPAX after Power off/on.
Setting the process data channels with the COMPAX parameters corresponds to the settings with PED_INI and PAD_INI.
2. Via the objects PE_SELECT and PA_SELECT
These objects allow the PD assignments to be set and/or changed during operation.
Setting: 8 Byte Process data channel (P196 Bit 0...2 ="4")
With P196 Bit 0...2 = "4", the acyclic data channel (PCP) for parameter data is turned off, making a 8 byte-wide process data
channel available.
The process data channel is split into two parts, one of which has two possible assignments, PD1 and PD2, and another part
which can be freely configured for assigning PD3 to PD8.
Assigning PD1 and PD2 with P196 Bit 7
P196 Bit 7="0"
PAD1-2 = STEUERWORT
PED1-2 = STATUSWORT
P196 bit 7 ="1"
PAD1-2 = CPX_STW
PED1-2 = CPX_ZSW
Assigning PD3 to PD8
The assignment is conducted as described above under the heading " Assignment of PED and PAD", but taking into
consideration that the number of bytes to be assigned have all risen by 2.
In addition to this mode of operation (P196 Bit 0...2 ="4"), 2 new objects (for more details see page 64 onwards) are available,
which may be assigned to the process data:
♦ OBJECT_REQ: For PAD for transferral of any object (max. length of data 4 bytes) to COMPAX.
♦ OBJECT_RSP: For PED as an acknowledgement for write access through OBJECT_REQ or as an answer to read access
through OBJECT_REQ.
Selectable Data Channels
1.2.1
The bus wiring
7
If you assign OBJECT_REQ to PAD and OBJECT_RSP to PED
you will have access to all objects with a data length ≤ 4 bytes.
In addition to this fixed PD assignment, a new function which
allows temporary assignment of the PD was created as a further
possibility:
P196 Bit 5="0" OBJECT_REQ and OBJECT_RSP cannot be
temporarily assigned to the PD (this allows a fixed
assignment of the PD; as outlined above).
P196 Bit 5="1" OBJECT_REQ and OBJECT_RSP can be
temporarily assigned to PD.
In addition to a permanent assignment of the
process data (PD3 ... PD8: set for example with
COMPAX parameters P135-P142) with cyclic
values (e.g. target position value and actual
position value), the OBJECT_REQ and
OBJECT_RSP objects can be temporarily
assigned to the PD (e.g. in order to change or read
parameters) to be then re-switched to the set cyclic
values (see page 64 onwards).
The answer/acknowledgement with OBJECT_RSP can also be
turned off by P196 Bit 6. Meaning:
P196 Bit 6="0" OBJECT_RSP automatically assigns the PED as
an answer/acknowledgement for OBJECT_REQ.
P196 Bit 1="1" OBJECT_RSP is not automatically assigned to the PED (as an answer/acknowledgement for OBJECT_REQ).
There is however the possibility of enabling or disabling OBJECT_RSP for the PED temporarily if required, via
the CONTROL object(command number 20 and 21).
Controlling the temporary PD assignment
2 control bits (in STEUERWORT and CPX_STW: "ObjectReqEnable" and "FreezePAD") and a state bit (in STATUSTWORT
and CPX_ZSW: "AckToggle") have been introduced to control the temporary PD assignment.
For more detailed explanations on the objects OBJECT_REQ and OBJECT_RSP, please see page 64.
Overview
P196 Bit 0...2 = "4": 8 byte process data channel
P196 Bit 7="0": PD1/PD2: STEUERWORT/STATUSWORT
P196 Bit 7="1": PD1/PD2: CPX_STW/CPX_ZSW
New objects: OBJECT_REQ, OBJECT_RSP
P196 Bit 5="0": temporary assignment of the PD with
OBJECT_REQ and OBJECT_RSP turned off
P196 Bit 5 ="1": temporary assignment of the PD with
OBJECT_REQ and OBJECT_RSP turned on
P196 Bit 6 ="0": OBJECT_RSP
automatically assigns the PED as
answer/acknowledgement for OBJECT_REQ
P196 Bit 6="1": OBJECT_RSP does not
automatically assigns the PED (as
answer/acknowledgement for
OBJECT_REQ).
OBJECT_RSP through CONTROL="20"
enabled to PED or disabled through
CONTROL="21"
1.4.1 Bus – Setting using the front cover
The bus protocol (P196) can be set using the COMPAX front cover. Procedure:
call smaller
Status
number
without
function
decrease
value
increase
value
choose
Status
number
choose
number of
C-parameter
status
indicator
change
C-parameter
without
function
call higher
Status
number
call smaller
C-parameter
number
call higher
C-parameter
number
Enter
Enter
Enter
A
Enter
B
A
B
Enter
Enter
choice of operation
modes
Meaning:
C parameters
Meaning
Range
COMPAX parameters
Active on
C01
Address of unit
Automatically set!
C02
Baud rate:
Automatically set!
C03
Bus protocol
0...255
P196
Power on!
C04 - C11
reserved
Physically, the types consist of one or more octets (Bytes).
One byte consists of 8 bits (Bit 0 to 7). Bit 0 is the LSB
(Least Significant Bit). A byte can also be depicted
hexadecimally (0x00 ... 0xff).
If a data type consists of n byte, the following applies:
Data byte 1 (Byte in address x)
=
highest value byte
Data byte n (Byte in address x+n-1)
=
lowest value byte
The data coding in this chapter and the value ranges for
the respective data types apply, unless otherwise explicitly
stated in the data description of a COMPAX communication
object.
1.7.1 Boolean
Depiction of the values TRUE and FALSE in a Byte (Octet).
Value
range
TRUE or FALSE
Length
1 Byte
Coding
FALSE is depicted by the value 0x00, TRUE
by the value 0xff
1.7.2 Integer
Integer values are signed quantities.
Type
Value range
Length
Integer8
-128 ... +127
1 Byte
Integer16
-32 768 ... +32 767
2 Byte
Integer32
-2 147 483 647 ... +2 147 483 647
-2 147 483 648 (0x80 00 00 00)
"
Overflow
4 Byte
Coding
Two’s complement
In objects with the data type Integer32 it is possible that its
value lies outside the value range.
If this is the case, the corresponding object has the value -2
147 483 648 (0x80 00 00 00) " Overflow.
E.G. this is possible with the object LAGE_IST, as the
actual travel area of COMPAX M/S lies between +/- 4 000
000.
1.7.3 Unsigned
Unsigned values are unsigned quantities.
Type
Value range
Length
Unsigned8
0...255
1 Byte
Unsigned16
0...65 535
2 Byte
Unsigned32
0...4 294 967 295
4 Byte
Coding
binary
2. Object index
Interbus-S
10
2. Object index
2.1 Communication objects: Overview sorted by Symbol
Command
Symbol
Service
Index
Index
pointer
Sub-
index
Byte
PD
See
page
Deceleration time
ACCEL_NEG
wr
0x5feb
37
0
2
-
48
Acceleration time
ACCEL_POS
wr
0x5fea
36
0
2
-
47
Operation mode display
BETR_ART_AZ
rd
0x6061
66
0
2
-
16
Operation mode selection code
BETRIEBSART
rd/wr
0x6060
65
0
2
-
16
Special commands for COMPAX XX70
CAM_CMD
wr
0x5fcc
6
1...6
4
-
39
Read and write curve memory
CAM_MEM
rd/wr
0x5fcb
5
0
3
-
62
Set and read curve memory pointer
CAM_MEM_P
rd/wr
0x5fca
4
0
2
-
62
Command input in ASCII format
COMMAND
rd/wr
0x5fe6
32
0
20
-
23
Control commands
CONTROL
wr
0x5fe9
35
0
1
A
22
CPX control word
CPX_STW
rd/wr
0x5fd2
12
0
2
A
18
CPX status word
CPX_ZSW
rd
0x5fd3
13
0
2
I
19
Max motor speed value
DREHZAHLMAX
rd/wr
0x6080
81
0
2
-
44
Function group description
FKT_GRUPPE
rd
0x600f
61
1...7
4
-
14
Traverse speed actual value
GESCHW_IST
rd
0x606c
70
0
4
-
46
Max speed value
GESCHW_MAX
rd/wr
0x607f
80
0
4
-
44
Reference run speed
GESCHW_REF
rd/wr
0x6099
88
0
4
-
46
Set and read pointer
GOTO
rd/wr
0x5ff2
44
0
1
-
60
Position limit value min-max
GRENZEN
rd/wr
0x607d
78
1...2
4
-
36
Process input data description
IN_SELECT
rd/wr
0x5ffd
55
0...2
3
-
77
Logic state of the 16 digit. inputs
INPUT_WORD
rd
0x5ff8
50
0
2
I
51
Position actual value
LAGE_IST
rd
0x6064
67
0
4
I
35
Target position default
POSITION_TARGET
rd/wr
0x607a
76
0
4
A
33
Torque actual value
MOMENT_IST
rd
0x6077
74
0
2
-
30
Torque max value
MOMENT_MAX
rd/wr
0x6072
71
0
2
-
29
Read/write program memory (ASCII)
N
rd/wr
0x5ff1
43
1 ... 250
32
-
54
Rated torque motor
NENNMOMENT
rd/wr
0x6076
73
0
2
-
29
Motor nominal current
NENNSTROM
rd/wr
0x6075
72
0
2
-
30
Read/write program memory (binary)
Nx
rd/wr
0x5fd5
15
1 ... 250
20
-
54
Write/read objects via process data channel
OBJECT_REQ
wr
0x5fc5
-
0
6
A
66
write/read acknowledgement/ answer obj. via PDK
OBJECT_RSP
rd
0x5fc6
-
0
6
I
66
Enable process output data
OUT_ENABLE
rd/wr
0x5fff
57
0
1
-
78
Process input data description
OUT_SELECT
rd/wr
0x5ffe
56
0...2
3
-
77
Set or reset a digital output
OUTPUT
wr
0x5ff6
48
1...16
1
-
51
Mask outputs
OUTPUT_MASK
rd/wr
0x5ff5
47
0
2
-
52
Logic state of the 16 digit. Outputs
OUTPUT_WORD
rd/wr
0x5ff7
49
0
2
I/O
51
Reduce traverse speed
OVERRIDE
rd/wr
0x5fee
40
0
1
A
41
Read/write parameters in ASCII format
P
rd/wr
0x5fe7
33
1 ... 250
32
-
23
Enable PA data
PA_ENABLE
rd/wr
0x6002
60
0
1
-
74
PA data description
PA_SELECT
rd/wr
0x6001
59
0...13
19
-
73
Initialise the PA data description
PAD_INI
rd/wr
0x5fd1
11
1...4
3
-
76
PE data description
PE_SELECT
rd/wr
0x6000
58
0...13
19
-
72
Initialise the PE data description
PED_INI
rd/wr
0x5fd0
10
1...4
3
-
75
Polarities
POLARITAET
rd/wr
0x607e
79
0
1
-
38
Positioning window
POS_FENSTER
rd/wr
0x6067
69
0
4
-
37
Absolute positioning
POSA
wr
0x5ff0
42
0
6
-
32
Relative positioning
POSR
wr
0x5fef
41
0
6
-
33
Change traverse speed
POSR0SPEED
wr
0x5fed
39
0
3
-
42
Comparator function (active low)
POSROUTPUTN
wr
0x5fe3
29
1...16
4
-
53
Comparator function (active high)
POSROUTPUTP
wr
0x5fe2
28
1...16
4
-
53
Speed step profile
POSRXSPEEDY
wr
0x5fe4
30
0
8
-
42
Speed step profile with ACCEL
PRXSDYALZ
wr
0x5fc7
1
0
10
-
43
Read/write parameters in binary format
Px
rd/wr
0x5fd4
14
1 ... 250
4
-
24
Communication objects: Overview sorted by Symbol
11
Command
Symbol
Service
Index
Index
pointer
Sub-
index
Byte
PD
See
page
Lag
RAMPE_NEG
rd/wr
0x6084
84
0
4
-
49
Rapid stop
RAMPE_NOTS
rd/wr
0x6085
85
0
4
-
49
Acceleration
RAMPE_POS
rd/wr
0x6083
83
0
4
-
48
Accelerate reference run
RAMPE_REF
rd/wr
0x609a
89
0
4
-
50
Ramp form speed
RAMPENFORM
rd/wr
0x6086
86
0
2
-
47
Reference measurement offset
REALNULL
rd/wr
0x607c
77
0
4
-
36
Reference run selection code
REF_MODE
rd/wr
0x6098
87
0
2
-
38
Status query in ASCII format
S
rd
0x5fe8
34
1...39
32
-
28
Actual position
S1
rd
0x5ff9
51
0
6
-
26
COMPAX operating hours
S10
rd
0x5fdb
21
0
4
-
26
Loop counter for a running REPEAT loop
S11
rd
0x5fda
20
0
2
-
27
Position of the absolute value sensor
S12
rd
0x5fd9
19
0
4
-
35
Target position
S2
rd
0x5fdf
25
0
4
-
27
Diagnosis values
S23_S26
rd
0x5fd8
18
1...4
2
-
27
Contour error
S3
rd
0x5ffa
52
0
2
I
15
Error message
S30
rd
0x5fd7
17
1...2
1
-
26
Device identification
S31_S39
rd
0x5fd6
16
1...9
3
-
15
Current axis process speed
S4
rd
0x5ffc
54
0
2
I
45
Current motor torque
S5
rd
0x5ffb
53
0
2
I
30
Temperature of the power output stage
S6
rd
0x5fde
24
0
2
-
26
Control voltage and intermediate circuit voltage
S7_S8
rd
0x5fdd
23
1...2
2
-
31
Number of axis motion cycles
S9
rd
0x5fdc
22
0
4
-
27
Contour error window
SCHLEPP_FEN
rd/wr
0x6065
68
0
4
-
37
Traverse speed
SPEED
rd/wr
0x5fec
38
0
2
A
41
Run program record N
START_N
wr
0x5ff4
46
0
1
A
60
Start program from record N
START_N_GO
wr
0x5fe5
31
0
1
A
61
Status byte
STATUSBYTE
rd
0x5fcf
9
0
1
I
17
Status word
STATUSWORD
rd
0x6041
64
0
2
I
20
Control byte
STEUERBYTE
rd/wr
0x5fce
8
0
1
A
17
Control word
CONTROLWORD
rd/wr
0x6040
63
0
2
A
19
Fault code
STOERUNG
rd
0x603f
62
0
2
-
25
Transfer current position in record N
TEACH_N
wr
0x5ff3
45
0
1
-
61
Traverse speed
VERF_GESCHW
rd/wr
0x6081
82
0
4
-
45
COMPAX – enter or read variables
VX
rd/wr
0x5fcd
7
40
4
-
62
Synchronisation with automatic reverse travel
WAITPOSA
wr
0x5fe0
26
0
4
-
39
Synchronisation without automatic reverse travel
WAITPOSR
wr
0x5fe1
27
0
4
-
40
Intermediate circuit voltage
ZWK_SPG
rd
0x6079
75
0
2
-
31
Column PD shows whether the respective object can be depicted on the process data channel. The following are explanations
of the abbreviations in column PD:
•
E
Object can be depicted in the process input data.
•
A
Object can be depicted in the process output data.
•
E/A Object can be depicted in the process input and output data.
•
-
not possible to depict on the process data channel.
2. Object index
Interbus-S
12
2.2 Communication objects: Overview sorted by Index
Command
Symbol
Service
Index
Index
Index
Sub-
index
Byte
PD
See
page
Write/read objects via process data channel
OBJECT_REQ
wr
0x5fc5
-
0
6
A
66
Write/read acknowledgement/ answer obj. via PDK
OBJECT_RSP
rd
0x5fc6
-
0
6
I
66
Speed step profile with ACCEL
PRXSDYALZ
wr
0x5fc7
1
0
10
-
43
Set and read curve memory pointer
CAM_MEM_P
rd/wr
0x5fca
4
0
2
-
62
Read and write curve memory
CAM_MEM
rd/wr
0x5fcb
5
0
3
-
62
Special commands for COMPAX XX70
CAM_CMD
wr
0x5fcc
6
1...6
4
-
39
COMPAX – Input or read variables
VX
rd/wr
0x5fcd
7
40
4
-
62
Control byte
STEUERBYTE
rd/wr
0x5fce
8
0
1
A
17
Status byte
STATUSBYTE
rd
0x5fcf
9
0
1
I
17
Initialise the PE data description
PED_INI
rd/wr
0x5fd0
10
1...4
3
-
75
Initialise the PA data description
PAD_INI
rd/wr
0x5fd1
11
1...4
3
-
76
CPX control word
CPX_STW
rd/wr
0x5fd2
12
0
2
A
18
CPX status word
CPX_ZSW
rd
0x5fd3
13
0
2
I
19
Read/write parameter in binary format
Px
rd/wr
0x5fd4
14
1 ... 250
4
-
24
Read/write program memory (binary)
Nx
rd/wr
0x5fd5
15
1 ... 250
20
-
54
Device identification
S31_S39
rd
0x5fd6
16
1...9
3
-
15
Error message
S30
rd
0x5fd7
17
1...2
1
-
26
Diagnosis values
S23_S26
rd
0x5fd8
18
1...4
2
-
27
Position of the absolute value sensor
S12
rd
0x5fd9
19
0
4
-
35
Loop counter for a running REPEAT loop
S11
rd
0x5fda
20
0
2
-
27
COMPAX operating hours
S10
rd
0x5fdb
21
0
4
-
26
Number of axis motion cycles
S9
rd
0x5fdc
22
0
4
-
27
Control voltage and intermediate circuit voltage
S7_S8
rd
0x5fdd
23
1...2
2
-
31
Temperature of power output stage
S6
rd
0x5fde
24
0
2
-
26
Target position
S2
rd
0x5fdf
25
0
4
-
27
Synchronisation with automatic reverse travel
WAITPOSA
wr
0x5fe0
26
0
4
-
39
Synchronisation without automatic reverse travel
WAITPOSR
wr
0x5fe1
27
0
4
-
40
Comparator function (active high)
POSROUTPUTP
wr
0x5fe2
28
1...16
4
-
53
Comparator function (active low)
POSROUTPUTN
wr
0x5fe3
29
1...16
4
-
53
Speed step profile
POSRXSPEEDY
wr
0x5fe4
30
0
8
-
42
Start program from record N
START_N_GO
wr
0x5fe5
31
0
1
A
61
Command input in ASCII format
COMMAND
rd/wr
0x5fe6
32
0
20
-
23
Read/write parameters in ASCII format
P
rd/wr
0x5fe7
33
1 ... 250
32
-
23
Status query in ASCII format
S
rd
0x5fe8
34
1...39
32
-
28
Control commands
CONTROL
wr
0x5fe9
35
0
1
A
22
Acceleration time
ACCEL_POS
wr
0x5fea
36
0
2
-
47
Deceleration time
ACCEL_NEG
wr
0x5feb
37
0
2
-
48
Traverse speed
SPEED
rd/wr
0x5fec
38
0
2
A
41
Change traverse speed
POSR0SPEED
wr
0x5fed
39
0
3
-
42
Reduce traverse speed
OVERRIDE
rd/wr
0x5fee
40
0
1
A
41
Relative positioning
POSR
wr
0x5fef
41
0
6
-
33
Absolute positioning
POSA
wr
0x5ff0
42
0
6
-
32
Read/write program memory (ASCII)
N
rd/wr
0x5ff1
43
1 ... 250
32
-
54
Set and read record pointer
GOTO
rd/wr
0x5ff2
44
0
1
-
60
Transfer current position in record N
TEACH_N
wr
0x5ff3
45
0
1
-
61
Run program record N
START_N
wr
0x5ff4
46
0
1
A
60
Mask outputs
OUTPUT_MASK
rd/wr
0x5ff5
47
0
2
-
52
Set or reset a digital output
OUTPUT
wr
0x5ff6
48
1...16
1
-
51
Logic state of the 16 digit. outputs
OUTPUT_WORD
rd/wr
0x5ff7
49
0
2
I/O
51
Logic state of the 16 digit. inputs
INPUT_WORD
rd
0x5ff8
50
0
2
I
51
Actual position
S1
rd
0x5ff9
51
0
6
-
26
Contour error
S3
rd
0x5ffa
52
0
2
I
15
Current motor torque
S5
rd
0x5ffb
53
0
2
I
30
Current axis process speed
S4
rd
0x5ffc
54
0
2
I
45
Process input data description
IN_SELECT
rd/wr
0x5ffd
55
0...2
3
-
77
Process input data description
OUT_SELECT
rd/wr
0x5ffe
56
0...2
3
-
77
Enable process output data
OUT_ENABLE
rd/wr
0x5fff
57
0
1
-
78
PE data description
PE_SELECT
rd/wr
0x6000
58
0...13
19
-
72
PA data description
PA_SELECT
rd/wr
0x6001
59
0...13
19
-
73
Enable PA data
PA_ENABLE
rd/wr
0x6002
60
0
1
-
74
Function group description
FKT_GRUPPE
rd
0x600f
61
1...7
4
-
14
Fault code
STOERUNG
rd
0x603f
62
0
2
-
25
Control word
CONTROLWORD
rd/wr
0x6040
63
0
2
A
19
Status word
STATUSWORD
rd
0x6041
64
0
2
I
20
Operating mode selection code
BETRIEBSART
rd/wr
0x6060
65
0
2
-
16
Operating mode display
BETR_ART_AZ
rd
0x6061
66
0
2
-
16
Position actual value
LAGE_IST
rd
0x6064
67
0
4
I
35
Contour error window
SCHLEPP_FEN
rd/wr
0x6065
68
0
4
-
37
Positioning window
POS_FENSTER
rd/wr
0x6067
69
0
4
-
37
Traverse speed actual value
GESCHW_IST
rd
0x606c
70
0
4
-
46
Torque max value
MOMENT_MAX
rd/wr
0x6072
71
0
2
-
29
Motor nominal current
NENNSTROM
rd/wr
0x6075
72
0
2
-
30
Rated torque motor
NENNMOMENT
rd/wr
0x6076
73
0
2
-
29
Torque actual value
MOMENT_IST
rd
0x6077
74
0
2
-
30
Intermediate circuit voltage
ZWK_SPG
rd
0x6079
75
0
2
-
31
Target position default
POSITION_TARGET
rd/wr
0x607a
76
0
4
A
33
Reference measurement offset
REALNULL
rd/wr
0x607c
77
0
4
-
36
Position limit value min-max
GRENZEN
rd/wr
0x607d
78
1...2
4
-
36
Polarities
POLARITAET
rd/wr
0x607e
79
0
1
-
38
Max speed
GESCHW_MAX
rd/wr
0x607f
80
0
4
-
44
Max motor speed value
DREHZAHLMAX
rd/wr
0x6080
81
0
2
-
44
Process speed
VERF_GESCHW
rd/wr
0x6081
82
0
4
-
45
Acceleration
RAMPE_POS
rd/wr
0x6083
83
0
4
-
48
Lag
RAMPE_NEG
rd/wr
0x6084
84
0
4
-
49
Rapid stop
RAMPE_NOTS
rd/wr
0x6085
85
0
4
-
49
Ramp form speed
RAMPENFORM
rd/wr
0x6086
86
0
2
-
47
Reference run selection code
REF_MODE
rd/wr
0x6098
87
0
2
-
38
Reference run speed
GESCHW_REF
rd/wr
0x6099
88
0
4
-
46
Reference run acceleration
RAMPE_REF
rd/wr
0x609a
89
0
4
-
50
Column PD shows whether the respective object can be depicted on the process data channel. The following are explanations
of the abbreviations in column PD:
•
E
Object can be depicted in the process input data.
•
A
Object can be depicted in the process output data.
•
E/A
Object can be depicted in the process input and output data.
•
-
not possible to depict on the process data channel.
Objects with an index >0x6000 are COMPAX–specific objects!
2. Object index
Interbus-S
14
2.3 Device identification
2.3.1 FKT_GRUPPE
Function group description
This parameter displays the function groups from which functions are integrated in the device. The parameter is a field with 4*n
entries. Each entry consists of the profile group, the profile version, the function group identifier and the function version.
Object Description
Index
0x600f
Symbol
FKT_GRUPPE
Length
4
Access groups
0
Object code
Array
Elements
7
Password
0
Data type
Octet String
Access rights
Read all
PD Map
Not possible
Data Description
Data byte
Meaning
Data byte
Meaning
1...2
Profile number
3...4
Function groups number
Profile number
Data byte 1
Data byte 2
b15
b12
b11
b4
b3
b0
Profile group
Profile version
Profile group
Meaning
Profile group
Meaning
0x00
No profile (manufacturer specific)
0x07
Encoder
0x01
Sensor/actuator
0x08
Process controller
0x02
DRIVECOM
0x09
Robot control
0x03
reserved
0x0A
Screw control
0x04
Interface components
0x0B
ISO valve terminal
0x05
reserved
0x0C
Weld control
0x06
reserved
0x0D
Operating/display device
Function groups No.
Data byte 3
Data byte 4
b15
b8
b7
b0
Function group identification
Function version
Fn. group
Meaning
Funct. group
Meaning
0x01
Status equipment device control
0x06
Position functions
0x02
General functions
0x07
Torque functions
0x03
Operation mode functions
0x08
Actual value generator
0x04
Speed functions 1
0x09
Factor functions
0x05
Speed functions 2
0x0a
Program functions
Example
Read 3. function group description.
Service
Read request
Param. counter
3
Sub-index
3
Command Code
0x8081
Index
0x600f
000000000000 ... 999999999999
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7,6,5,4]
1011
4 [7,6,5,4]
105
1 [3,2,1,0]
1010
4 [3,2,1,0]
104
2 [7,6,5,4]
109
5 [7,6,5,4]
103
2 [3,2,1,0]
108
5 [3,2,1,0]
102
3 [7,6,5,4]
107
6 [7,6,5,4]
101
3 [3,2,1,0]
106
6 [3,2,1,0]
100
Sub-index
Assignment
Sub-index
Assignment
1
Software version
6
Date, version of bus option
2
Software date
7
Device identification
3
Job number
8
Device family
4
Part number
9
Device
5
Version
In Sub-index 2 and 6, the data bytes are assigned as follows:
Data byte
1
2
3
4
5
6
Assignment
Day
Month
Year
Version
Identifier
2. Object index
Interbus-S
16
2.4 Control
2.4.1 Operating mode
Operation mode selection code.
Selection function that determines the operation mode.
Object Description
Index
0x6060
Symbol
BETRIEBSART
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read/write all
PD Map
Not possible
Data Description
Selection code
Operation mode
Selection code
Operation mode
-2
Reset mode
1
Target position input
-1
Continuous mode
3
Speed input 2
Example
The operation mode "Position target input" must be set.
Service
Write request
Index
0x6060
1. data byte
0x00
Command Code
0x8082
Sub-index
0
2. data byte
0x01
Param. counter
4
Length
2
2.4.2 BETR_ART_AZ
Operation mode display.
This parameter indicates the current operation mode.
The meaning of the displayed value corresponds to the operation mode selection code.
Object Description
Index
0x6061
Symbol
BETR_ART_AZ
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read all
PD Map
Not possible
Allows program start from record 1 - 15.
The record pointer is set to the corresponding program record.
The program can be started, stopped, and continued.
" The machine zero is approached with the record selection = "0000" and "Start".
An error acknowledgement is possible.
Object Description
Index
0x5FCE
Symbol
STEUERBYTE
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read/write all
PD Map
PAD
Data Description
Data byte [Bit]
Assignment
Meaning
1 [7]
Quit (not when P190=22)
Error acknowledge with a positive edge
1 [6]
Stop with ramp P10 without clearing
with a positive edge
1 [5]
Continue ("1") / new start ("0") with Start
Continue:
Continue program
New start:
Prog. start at selected record
1 [4]
Start / Stop
# Start after the response defined in Bit 5
$ Stop
1 [3]
Record select (23)
Note!
1 [2]
Record select (22)
With the record selection = "0000" and "New start",
1 [1]
Record select (23)
the machine zero point is approached
1 [0]
Record select (20)
The "Quit" command is not accepted for P190=22 (DRIVECOM profile 22) (Error message aknowledgement as outlined
in the status chart on page 77).
2.4.4 STATUSBYTE
The status byte shows information about the status of the device as well as messages.
Object Description
Index
0x5FCF
Symbol
STATUSBYTE
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read all
PD Map
PED
Data Description
Data byte [Bit]
Assignment
1 [7]
Machine zero point approached
1 [6]
Idle after stop
1 [5]
Programmed nominal position reached
1 [4]
Motor stalled
1 [3]
Lag error
1 [2]
Ready for start (see below)
1 [1]
Warning
1 [0]
Fault
Meaning of "Ready for Start"
"Ready for Start" is used to control the program and is set
% when the program is halted by a WAIT START instruction
and is waiting for the START signal.
% after an interruption with STOP or BREAK and these
signals no longer occur.
% after a rectified error.
% after power on.
% at the program end with the command END.
"Ready for Start" has no meaning when commands are input
directly.
2. Object index
Interbus-S
18
2.4.5 CPX_STW
Activation of device control commands and setting/resetting of virtual inputs E17...E32
Control of the COMPAX M/S via the CPX control word is only possible when the relevant bits in P221 are set.
The virtual inputs E17...E32 can be queried in the data memory.
Object Description
Index
0x5FD2
Symbol
CPX_STW
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
PAD
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [15...8]
E32...E25
2 [7..0]
E24...E17
Data byte [Bit]
Function without shift
Function with shift
Enable
1 [7..2]
none
None
P222/Bit 7 ... 0
1 [1]
ObjectReqEnable
ObjectReqEnable
see below
1 [0]
FreezePAD
FreezePAD
see below
2 [7..6]
none
None
P221/Bit 7 ... 6
2 [5]
STOP
BREAK
P221/Bit 5
2 [4]
START
None
P221/Bit 4
2 [3]
QUIT (not when P190=22)
Teach real zero
P221/Bit 3
2 [2]
Hand-
Approach real zero (RZ)
P221/Bit 2
2 [1]
Hand+
Approach machine zero (MZ)
P221/Bit 1
2 [0]
SHIFT
P221/Bit 0
&
The functions ObjectReqEnable and FreezePAD are only active in CPX_STW when
PD-Length = 4 and P196 Bit 7 = 1 and P196 Bit 5 = 1 !
For a detailed description, please see page 64
The "Quit" command is not accepted for P190=22 (DRIVECOM profile 22) (Error message aknowledgement as outlined
in the status chart on page 77).
By partially reassigning the input functions to STEUERWORT, the function is limited by the multiple function E1. :
Example: If a function with E1 occupies the control word (e.g. Teach real null), then additional E1 functions (such as the
"QUIT" function) are ignored by the inputs.
Therefore: If you need all the input functions, the function must be completely reassigned, either to the inputs (P221 = 0)
or to the control word (P221 = 63).
Command recognition
The control word is cyclically transmitted from the Interbus Master via the bus.
Note! When a PLC is the Master, the control word may not be present for too short a time.
The PLC and Interbus-S cycles are asynchronous. If the control word is output for just one PLC cycle (scan), data may be lost.
Rectify the problem with:
! A control word which is available for a sufficiently long time
or
! by re-reading the object "CPX_STW". The command has been recognised if the change is in this object.
COMPAX - E/A - Functions over the control word (Data bits 1[1], 1[0], 2[7], ... 2[2])
COMPAX does not recognise a direct reassignment of the E/A functions by removing a function and setting another function
simultaneously; Exception: STOP and BREAK (these are always recognised immediately).
Therefore proceed as follows:
! Remove the previous functions by sending a "null telegram" (allow status to remain until it has been recognised by the
COMPAX).
! When the COMPAX is ready, set a new function.
Example: Switch from Hand+ to Hand-
! Reset Hand+: data bit 1[0] = "0"
! Wait until COMPAX has recognised through the Interbus-S (till "Ready to start" has been set) or Handshake through
CPX_STW.
! Set Hand-: data bit 1[1] = "1"
2.4.6 CPX_ZSW
The CPX status word shows information about the status of the device as well as messages.
COMPAX Software Version 3.64 or above allows the status information S16 and S17 to be assigned to CPX_ZSW via
parameter 203 Bit 0 = 1.
Object description
Index
0x5FD3
Symbol
CPX_ZSW
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read all
PD Map
PED
Data description (P203 Bit 0 = 0)
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
Status A16
2 [7]
Motor stalled
1 [6]
Status A15
2 [6]
Lag error
1 [5]
Status A14
2 [5]
Idle after stop
1 [4]
Status A13
2 [4]
Target position reached
1 [3]
Status A12
2 [3]
Ready for start
1 [2]
Status A11
2 [2]
MN was reached
1 [1]
Status A10
2 [1]
No warning
1 [0]
Status A9/AckToggle
2 [0]
No fault
Data description (P203 Bit 0 = 1)
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
---
2 [7]
2 [6]
0
0
OUTPUT A0 = x
after OUTPUT A0 = 0
1 [6]
RUN ("0"= off or turned off in the event
of an error)
0
1
1
0
after OUTPUT A0 = 1
after OUTPUT A0 = 2
1 [5]
Reserved
2 [5]
Idle after stop
1 [4]
Stop over input E6
2 [4]
Target position reached
1 [3]
Program memory running
2 [3]
Ready for start
1 [2]
Command active
2 [2]
MN was reached
1 [1]
Service password active
2 [1]
No warning
1 [0]
Password 302 active/AckToggle
2 [0]
No fault
&
The status information AckToggle only appears in CPX_ZSW when
PD-Length = 4 and P196 Bit 7 = 1 and OBJECT_REQ is on the PAD channel or can be temporarily assigned to the
PAD channel. (P196 Bit 5 = 1)!
For a description please see page 64onwards.
2. Object index
Interbus-S
20
2.4.7 STEUERWORT
Some bits in the control word influence the status equipment of the device control, enabling functions and determining the
operating status of the devices.
The manufacturer-specific bits (Data byte 1 bits 2...6) serve to activate devices control commands, which are only effective if
P221 is used to provide the appropriate enabling (see CPX_STW).
The SPM bit (Data byte 1 bit 7) is used to acknowledge an existing pop-up message.
Object Description
Index
0x6040
Symbol
STEUERWORT
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read/write all
PD Map
PAD
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
SPM
2 [7]
Reset fault
1 [6]
STOP
2 [6]
Target position relative or absolute
1 [5]
START
2 [5]
1 [4]
Hand-
2 [4]
New set point
1 [3]
Hand+
2 [3]
Enable operation
1 [2]
Approach machine zero (MZ)
2 [2]
Rapid stop
1 [1]
ObjectReqEnable
2 [1]
Disable voltage
1 [0]
FreezePAD
2 [0]
Power on
&
The functions ObjectReqEnable and FreezePAD are only active in STEUERWORT when
PD-Length = 4 and P196 Bit 7 = 0 and P196 Bit 5 = 1 !
For a description, please see page 64.onwards
2.4.8 STATUSWORT
The status word displays information regarding the status of the devices and messages,
when SPM (status word) is not equal to SPM (control word).
The status word displays pop-up messages, when SPM (status word) is not equal to SPM (control word).
Object Description
Index
0x6041
Symbol
STATUSWORT
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
read all
PD Map
PED
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
SPM
2 [7]
Warning
1 [6]
Idle after stop
2 [6]
Switch on disabled
1 [5]
MN was reached
2 [5]
Rapid stop
1 [4]
Actual value acknowledgement
2 [4]
Voltage disabled
1 [3]
Limit value
2 [3]
Fault
1 [2]
Set point reached
2 [2]
Operation enabled
1 [1]
Remote
2 [1]
Switched on
1 [0]
Message/AckToggle
2 [0]
Ready to start
&
The status information AckToggle only appears in STATUSWORT when
PD-Length = 4 and P196 Bit 7 = 0 and OBJECT_REQ is on the PAD channel or can be assigned to the PAD channel
temporarily. (P196 Bit 5 = 1)!
For a description, please see page 64onwards.
Pop-up message processing
21
2.4.9 Pop-up message processing
COMPAX can display the following pop-up messages via the status word:
% an error has occurred.
% the programmed set point has been reached.
% the programmed comparator point has been reached.
The pop-up messages can be enabled individually via P193 (activated).
Pop-up message
Valency
automatic error message
1
automatic "position reached" message
2
automatic comparator switch points report
4
"
"
"
" The required settings can be obtained by inputting the sum of the significants in P193
If the pop-up message processing is active and there is a pop-up message, COMPAX interrupts the normal status display in the
status word, toggles the pop-up message flag "SPM" and displays the actual pop-up message in the status word.
The Master accepts the pop-up message and acknowledges it by toggling the "SPM" in the control word.
"
"
"
" The status word displays a pop-up message, when SPM (status word) is not equal to SPM (control word).
Status word with pop-up messages
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
SPM
2 [7]
1 [6]
2 [6]
1 [5]
Pop-up message identifier
2 [5]
Error No.
1 [4]
2 [4]
or
1 [3]
1
=
error
2 [3]
Comparator No.
1 [2]
2
=
set point reached
2 [2]
1 [1]
3
=
Comparator point reached
2 [1]
1 [0]
2 [0]
2. Object index
Interbus-S
22
2.4.10
CONTROL
Control commands. Compax commands which do not require additional values.
The required commands are activated by reading in the relevant command number.
Object Description
Index
0x5fe9
Symbol
CONTROL
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
write all
PD Map
PAD
Data Description
Comma
nd no.
Function
Comman
d No.
Function
1
Go to machine home
12
Drive dead with opened brake
2
Program start
13
Program jump via external inputs
3
Stop program/positioning
14
Deactivate password protection (GOTO 302)
4
Break off program/positioning
15
Activate password protection
(GOTO 270)
5
Acknowledge error
16
Deactivate password protection (GOTO 620)
6
Read current position as real null
17
Declare curve valid
7
Declare valid
18
Not-Stop with clear
8
Declare configuration valid
19
Not-Stop without clear
9
Traverse speed from external encoder
20
OBJECT_RSP temporarily enabled on PED
10
Drive under torque with opened brake
21
OBJECT_RSP temporarily disabled on PED
11
Drive dead with closed brake
22-24
Not assigned
Example
The drive must approach the machine zero point.
Service
Write request
Index
0x5fe9
Data byte
0x01
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
All COMPAX commands which exist for the RS232 interface can be transferred with this object in plain text (ASCII-String in
upper case letters).
Object Description
Index
0x5fe6
Symbol
COMMAND
Length
20
Access groups
0
Object code
Simple var.
Password
0
Data type
Visible string
Access rights
Read/write all
PD Map
Not possible
Data Description
Coding
ASCII
Value range
0x20 ... 0x7f
Data byte
Assignment
Data byte
Assignment
1
1. character of the command string
20
20. character of the command string
Example
The drive must travel 15.8 mm relative (RS232 command: "POSR15.8").
Service
Write request
Length
20
5. data byte
0x31 ("1")
Command Code
0x8082
1. data byte
0x50 ("P")
6. data byte
0x35 ("5")
Param. counter
13
2. data byte
0x4f ("O")
7. data byte
0x2e (".")
Index
0x5fe6
3. data byte
0x53 ("S")
8. data byte
0x38 ("8")
Sub-index
0
4. data byte
0x52 ("R")
9...20. data byte
0x20 (" ")
2.4.12
P
Write/read COMPAX parameters in ASCII format.
The corresponding parameter is selected using the Sub-index (Sub-index = parameter No.).
Object Description
Index
0x5fe7
Symbol
P
Length
32
Access groups
0
Object code
Array
Elements
250
Password
0
Data type
Visible-String
Access rights
read/write all
PD Map
not possible
Data Description
Data format
ASCII
Value range
0x20 ... 0x7f
Data byte
Assignment
Data byte
Assignment
1
1. character of the ASCII response
32
32. character of the ASCII response
Example
The COMPAX parameter 3 must have the value -1055.88. Command: P003=-1055.88
Service
Write request
2. data byte
0x30 ("0")
9. data byte
0x35 ("5")
Command Code
0x8082
3. data byte
0x30 ("0")
10. data byte
0x35 ("5")
Param. counter
19
4. data byte
0x33 ("3")
11. data byte
0x2e (".")
Index
0x5fe7
5. data byte
0x3D ("=")
12. data byte
0x38 ("8")
Sub-index
3
6. data byte
0x2d ("-")
13. data byte
0x38 ("8")
Length
32
7. data byte
0x31 ("1")
14...32. data byte
0x20 (" ")
1. data byte
0x50 ("P")
8. data byte
0x30 ("0")
2. Object index
Interbus-S
24
2.4.13
Px
Read/write COMPAX parameters in binary format.
The corresponding parameter is selected using the Sub-index (Sub-index = parameter No.).
Object Description
Index
0x5fd4
Symbol
Px
Length
4
Access groups
0
Object code
Array
Elements
250
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
Not possible
Data Description
Parameter
Resolution
Parameter
Resolution
001 .. 005
1 ⇔ 0.001
035 .. 036
1 ⇔ 0.000001
006 .. 010
1
037 .. 049
1 ⇔ 0.001
011 .. 016
1 ⇔ 0.001
050 .. 072
1
017 .. 020
1
073 .. 099
1 ⇔ 0.001
021 .. 022
1 ⇔ 0.000001
100 .. 186
1
023 .. 029
1
187 .. 196
1 ⇔ 0.001
030 .. 034
1 ⇔ 0.001
197 .. 250
1
Example
Parameter 11 must be given the value 5000.
Service
Write request
Sub-index
11
3. data byte
0x4b
Command Code
0x8082
Length
4
4. data byte
0x40
Param. counter
5
1. data byte
0x00
Index
0x5fd4
2. data byte
0x4c
Fault code. If COMPAX is in the "Fault" status, the fault code is given a value not equal to 0.
If COMPAX is not in the "Fault" status, this object then gives the value 0.
Object Description
Index
0x603f
Symbol
STOERUNG
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read all
PD Map
Not possible
Data Description
Data byte [Bit]
Coding
Data byte [Bit]
Coding
1 [7 ... 4]
Main groups
2 [7 ... 0]
Details
1 [3 ... 0]
Subgroups
Fault codes:
Code
COMPAX error
0000h
E00 Stop/no error
6320h
E01 Not configured
6320h
E02 Limits
1000h
E03
1000h
E04
7300h
E05 MN-Ini not found
1000h
E06
8200h
E07 Processor error
8200h
E08 Synchronous stop is enabled
8200h
E09 Drive not working
8611h
E10 Contour error too large
8600h
E11 Prog. position not reached
7320h
E12 Slip error
7300h
E13 Ini 1 not damped
7300h
E14 Ini 2 not bed.
7320h
E15 Error in the 2. position measuring system
6300h
E16 Record number does not exist
6300h
E17 Record number too large
6300h
E18 Record 250 is assigned
6300h
E19 No room in memory
8612h
E20 Target position behind pos. limit stop
8612h
E21 Target position behind neg. limit stop
8500h
E22 MN is not approached
6200h
E23 Command is not allowed
8400h
E24 Speed is invalid
8600h
E25 Position is invalid
6300h
E26 END command missing for REPEAT
6320h
E27 Parameter cannot be written to
1000h
E28
6320h
E29 Motor values missing
5500h
E30 Hardware fault
6320h
E31 Parameter error
6320h
E32 Parameter error
6300h
E33 Data memory error
6300h
E34 Data memory error
5500h
E35 Hardware fault
Code
COMPAX error
5500h
E36 Hardware fault
5111h
E37 Auxiliary voltage +15V missing
5120h
E38 Voltage in the intermediate circuit too high
4210h
E39 Temperature too high
1000h
E40
5410h
E41 Output stage signals error
7303h
E42 Resolver error
2300h
E43 Output loaded
5111h
E44 Pos. auxiliary voltage outside tolerance
5111h
E45 neg. auxiliary voltage outside tolerance
5112h
E46 24V too large
5112h
E47 24V too small
4310h
E48 Thermostatic switch motor indicates error
7121h
E49 Motor/drive indicates disabling
8612h
E50 Limit switch 1 activated
8612h
E51 Limit switch 2 activated
7200h
E52 Error in emergency stop controlling
7120h
E53 Motor loaded
8400h
E54 Speed too high
8000h
E55 External emergency stop
8000h
E56 Emergency stop directly in COMPAX M
5120h
E57 Voltage in the intermediate circuit too low
4200h
E58 Temperature getting too high
1000h
E59
7200h
E60 Slip warning
1000h
E61
1000h
E62
1000h
E63
1000h
E64
7305h
E65 Encoder module not enabled
1000h
E66
1000h
E67
1000h
E68
1000h
E69
1000h
E70
1000h
E71...E255
2. Object index
Interbus-S
26
2.5.2 S30
Error message.
This object contains the error number of the current error and the last occurring error.
If the error number of the current error = 0, there is no error.
Object Description
Index
0x5fd7
Symbol
S30
Length
1
Access groups
0
Object code
Array
Elements
2
Password
0
Data type
Unsigned8
Access rights
Read all
PD Map
Not possible
Data Description
Sub-index
Assignment
Sub-index
Assignment
1
Error number of current error
2
Error number of last error
2.5.3 S6
Temperature of the power output stage.
Object Description
Index
0x5fde
Symbol
S6
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Read all
PD Map
Not possible
Data Description
Unit
degrees Celsius
Resolution
1 ⇔ 0.1°C
2.5.4 S10
COMPAX operating hours
Object Description
Index
0x5fdb
Symbol
S10
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
read all
PD Map
Not possible
Data Description
Unit
Hours
Resolution
1 ⇔ 0.1 h
Number of axis motion cycles.
Object Description
Index
0x5fdc
Symbol
S9
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
read all
PD Map
not possible
2.5.6 S11
Loop counter for a running REPEAT loop.
Object Description
Index
0x5fda
Symbol
S11
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
read all
PD Map
not possible
2.5.7 S23_S26
Status of the drive, the switch, the limits and the output stage.
Object Description
Index
0x5fd8
Symbol
S23-S26
Length
2
Access groups
0
Object code
Array
Elements
4
Password
0
Data type
Octet String
Access rights
read all
PD Map
not possible
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7 ... 0]
Status bits
2 [7 ... 0]
Status bits
Sub-index
Assignment
Sub-index
Assignment
1
Status drive
3
Status limits
2
Status switch
4
Status final step
For explanations of status bits, please see product manual COMPAX-M/S!
2. Object index
Interbus-S
28
2.5.8 S
All Compax status values that exist for the RS232 interface can be read with this object. The response is made available in plain
text (as ASCII string).
The corresponding status is selected using the Sub-index (Sub-index = status No.).
Object Description
Index
0x5fe8
Symbol
S
Length
32
Access groups
0
Object code
Array
Elements
250
Password
0
Data type
Visible-String
Access rights
read all
PD Map
not possible
Data Description
Coding
ASCII
Value range
0x20 ... 0x7f
Data byte
Assignment
Data byte
Assignment
1
1. character of the response string
32
32. character of the response string
Example
Read S23.
Service
Read Request
Param. counter
3
Sub-index
23
Command Code
0x8081
Index
0x5fe8
Torque, current, voltage
2.6.1
MOMENT_MAX
29
2.6 Torque, current, voltage
2.6.1 MOMENT_MAX
Max. torque value.
This value is the maximum permissible torque for the motor.
Object Description
Index
0x6072
Symbol
MOMENT_MAX
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
read/write all
PD Map
not possible
Data Description
Unit
Per-thousands of motor rated torque
Resolution
1 ⇔ 1 per-thousand
Example
The max. torque of the motor should be 400 per-thousands of the motor rated torque.
Service
Write request
Index
0x6072
1. data byte
0x01
Command Code
0x8082
Sub-index
0
2. data byte
0x90
Param. counter
4
Length
2
2.6.2 NENNMOMENT
Rated torque motor.
This value can be found on the rating plate of the motor.
Object Description
Index
0x6076
Symbol
NENNMOMENT
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
Nm
Resolution
1 ⇔ 0.1 Nm
Example
The rated torque of the motor HDX115C6-88S is 5.2 Nm.
Service
Write request
Index
0x6076
1. data byte
0x00
Command Code
0x8082
Sub-index
0
2. data byte
0x34
Param. counter
4
Length
2
2. Object index
Interbus-S
30
2.6.3 MOMENT_IST
Torque actual value.
The torque actual value corresponds to the current torque in the drive motor.
Object Description
Index
0x6077
Symbol
MOMENT_IST
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read all
PD Map
Not possible
Data Description
Unit
Per-thousands of motor rated torque
Resolution
1 ⇔ 1 per-thousand
2.6.4 S5
Current motor torque.
Value in % of the rated torque.
Object Description
Index
0x5ffb
Symbol
S5
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read all
PD Map
PED
Data Description
Unit
%
Resolution
1 ⇔ 1/64%; (6400 ⇔ 100%)
2.6.5 NENNSTROM
Motor nominal current.
This value can be found on the rating plate of the motor.
Object Description
Index
0x6075
Symbol
NENNSTROM
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Read/write all
PD Map
not possible
Data Description
Unit
Ampere
Resolution
1 ⇔ 0.1 A
Example
The nominal current of the motor HDX115C6-88S is 5.1 Ampere.
Service
Write request
Index
0x6075
1. data byte
0x00
Command Code
0x8082
Sub-index
0
2. data byte
0x33
Param. counter
4
Length
2
Torque, current, voltage
2.6.6
ZWK_SPG
31
2.6.6 ZWK_SPG
Intermediate circuit voltage.
This parameter describes the current intermediate circuit voltage in the drive controller.
Object Description
Index
0x6079
Symbol
ZWK_SPG
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
read all
PD Map
not possible
Data Description
Unit
Volt
Resolution
1 ⇔ 1 V
2.6.7 S7_S8
Control voltage and power or intermediate circuit voltage.
Object Description
Index
0x5fdd
Symbol
S7-S8
Length
2
Access groups
0
Object code
Array
Elements
2
Password
0
Data type
Unsigned16
Access rights
read all
PD Map
not possible
Data Description
Unit
Volt
Resolution
1 ⇔ 0.1 V
Sub-index
Assignment
Sub-index
Assignment
1
Control voltage
2
intermediate circuit voltage
Example
Read current intermediate circuit voltage.
Service
Read Request
Param. counter
3
Sub-index
2
Command Code
0x8081
Index
0x5fdd
Length
0
2. Object index
Interbus-S
32
2.7 Positioning
2.7.1 POSA
Absolute positioning. Reference point is real zero (RN).
Positioning is done with the acceleration time (brake time) set by ACCELL-POS (ACCEL-NEG) and the velocity set by SPEED.
If these values were not set, then valid are substitute values: SPEED: Parameter P002; ACCEL: Parameter P006
Object Description
Index
0x5ff0
Symbol
POSA
Length
6
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Write all
PD Map
Not possible
Data Description
Data format
BCD
Unit
mm (or inch)
Value range
-4 000 000 000 ... +4 000 000 000
Resolution
1 ⇔ 0.001 mm (or inch)
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7 ..... 0]
Value sign (0x00 ⇔ +; 0xff ⇔ -)
2 [7,6,5,4]
109
4 [3,2,1,0]
104
2 [3,2,1,0]
108
5 [7,6,5,4]
103
3 [7,6,5,4]
107
5 [3,2,1,0]
102
3 [3,2,1,0]
106
6 [7,6,5,4]
101
4 [7,6,5,4]
105
6 [3,2,1,0]
100
Example
The drive must travel to the absolute position 7350.150 mm.
Service
Write request
Sub-index
0
3. data byte
0x07
Command Code
0x8082
Length
6
4. data byte
0x35
Param. counter
6
1. data byte
0x00
5. data byte
0x01
Index
0x5ff0
2. data byte
0x00
6. data byte
0x50
Relative positioning. Reference point is the current position.
Object Description
Index
0x5fef
Symbol
POSR
Length
6
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Write all
PD Map
Not possible
Data Description
Data format
BCD
Unit
mm (or inch)
Value range
-4 000 000 000 ... +4 000 000 000
Resolution
1 ⇔ 0.001 mm (or inch)
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7 ..... 0]
Value sign (0x00 ⇔ +; 0xff ⇔ -)
2 [7,6,5,4]
109
4 [3,2,1,0]
104
2 [3,2,1,0]
108
5 [7,6,5,4]
103
3 [7,6,5,4]
107
5 [3,2,1,0]
102
3 [3,2,1,0]
106
6 [7,6,5,4]
101
4 [7,6,5,4]
105
6 [3,2,1,0]
100
Example
The drive should travel relative to -37891.210 mm.
Service
Write request
Sub-index
0
3. data byte
0x37
Command Code
0x8082
Length
6
4. data byte
0x89
Param. counter
6
1. data byte
0xff
5. data byte
0x12
Index
0x5fef
2. data byte
0x00
6. data byte
0x10
2.7.3 LAGE_ZIEL
Target position default.
Absolute positioning. Reference point is the real null (RN) or relative positioning: set by the data byte 2 Bit 6 (0 = absolute; 1 =
relative).
Positioning is done with the acceleration time (brake time) set by ACCELL-POS (ACCEL-NEG) and the velocity set by SPEED.
If these values were not set, then valid are substitute values: SPEED: Parameter P002; ACCEL: Parameter P006
Object Description
Index
0x607a
Symbol
LAGE_ZIEL
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
PAD
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
The object "target position" can be assigned to the cyclical process output data channel. Then you can cyclically specify new set
points. The acceptance of a new set point (see also PA_ENABLE Bit 7) requires a handshake. This is done using the following
bits:
! Control word byte 2 bit 4 "new set point" and
! Status word byte 1 bit 4 "acknowledge record point"
2. Object index
Interbus-S
34
Function:
New set point
Set point
acknowledgement
(1)
(3)
(2)
(4)
Transition
1
2
3
4
Meaning
New target value
Set point acknow-
ledgement
New set point
Set point acknow-
ledgement
Conditions
Target val.- acknowledgement. ="0" actual value
can be transferred
Set point acknowledgement ="1" Set point
recognised
New set point ="0"
Target val.- acknowledgement ="0" New target
value can be transferred
Automatic acceptance of the target position from the PAD channel for value changes can be turned off with the Bit 7 from
PA_ENABLE (see page 74).
Example
The drive must travel to the absolute position -1000.000 mm.
Service
Write request
Sub-index
0
3. data byte
0xbd
Command Code
0x8082
Length
4
4. data byte
0xc0
Param. counter
5
1. data byte
0xff
Index
0x607a
2. data byte
0xf0
2.7.4 S1
Actual position
Current position in relation to real zero.
Object Description
Index
0x5ff9
Symbol
S1
Length
6
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read all
PD Map
Not possible
Data Description
Data format
BCD
Unit
mm (or inch)
Value range
-4 000 000 000 ... +4 000 000 000
Resolution
1 ⇔ 0.001 mm (or inch)
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7 ..... 0]
Value sign (0x00 ⇔ +; 0xff ⇔ -)
2 [7,6,5,4]
109
4 [3,2,1,0]
104
2 [3,2,1,0]
108
5 [7,6,5,4]
103
3 [7,6,5,4]
107
5 [3,2,1,0]
102
3 [3,2,1,0]
106
6 [7,6,5,4]
101
4 [7,6,5,4]
105
6 [3,2,1,0]
100
Position actual value.
Current drive position.
Object Description
Index
0x6064
Symbol
LAGE_IST
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read all
PD Map
PED
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
2.7.6 S2
Target position.
End position of the current or last positioning cycle implemented.
Object Description
Index
0x5fdf
Symbol
S2
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
2.7.7 S12
Position of the absolute value sensor (Option A1).
Object Description
Index
0x5fd9
Symbol
S12
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
2. Object index
Interbus-S
36
2.7.8 REALNULL
Reference measurement offset.
Difference between real null point and machine zero point.
After the reference run, all positioning processes refer to the real null point.
Object Description
Index
0x607c
Symbol
REALNULL
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
The real null point should be -500.000 mm.
Service
Write request
Sub-index
0
3. data byte
0x5e
Command Code
0x8082
Length
4
4. data byte
0xe0
Param. counter
5
1. data byte
0xff
Index
0x607c
2. data byte
0xf8
2.7.9 GRENZEN
Position limit value min-max.
The position limit values are software end limits and correspond to the absolute position limits, within which the set values and
actual values (in absolute form) must be moved. Each new target position is checked with these limits. They always refer to the
machine zero point; therefore they must be corrected using the reference measurement offset.
Object Description
Index
0x607d
Symbol
GRENZEN
Length
4
Access groups
0
Object code
Array
Elements
2
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Sub-index
Assignment
Sub-index
Assignment
1
Negative limit stop
2
Positive limit stop
Note the number range for the Integer32 formats (see page 9 under "1.7.2
Integer").
Limits outside -2 147 483 - +2 147 483 units cannot be depicted.
Example
The position limit value min. (neg. limit stop) is set at -1650.000 mm.
Service
Write request
Sub-index
1
3. data byte
0xd2
Command Code
0x8082
Length
4
4. data byte
0x0b
Param. counter
5
1. data byte
0xff
Index
0x607d
2. data byte
0xe6
The positioning window lies symmetrically around the target position.
Once the position actual value lies within this window, the Bit "Position reached" is set in the status word.
Object Description
Index
6067
Symbol
POS_FENSTER
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
The positioning window is set to 15.000 mm.
Service
Write request
Sub-index
0
3. data byte
0x3a
Command Code
0x8082
Length
4
4. data byte
0x98
Param. counter
5
1. data byte
0x00
Index
0x6067
2. data byte
0x00
2.7.11
SCHLEPP_FEN
Contour error window.
The contour error window lies symmetrically around the currently set position set point.
If the current position indicator actual value lies outside this window, a contour error occurs.
Object Description
Index
0x6065
Symbol
SCHLEPP_FEN
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
The contour error window is set to 10.000 mm.
Service
Write request
Sub-index
0
3. data byte
0x27
Command Code
0x8082
Length
4
4. data byte
0x10
Param. counter
5
1. data byte
0x00
Index
0x6065
2. data byte
0x00
2. Object index
Interbus-S
38
2.7.12
S3
Contour error.
Difference between set and actual position in a positioning cycle.
Object Description
Index
0x5ffa
Symbol
S3
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
read all
PD Map
PED
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 1/256 mm (or inch)
2.7.13
POLARITAET
Polarities.
The set point and actual values are multiplied, depending on the polarity, with 1 or -1. This allows the user to reverse the
direction of orientation
Object Description
Index
0x607e
Symbol
POLARITAET
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read/write all
PD Map
Not possible
Data Description
Data bit 7
Assignment
Data bit 7
Assignment
= 1
Reversal of direction (motor left)
= 0
default (motor right)
The other bits are irrelevant for COMPAX.
Example
The motor should turn clockwise.
Service
Write request
Index
0x607e
1. data byte
0x80
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
2.7.14
REF_MODE
Reference run selection code.
Selection function with which the reference run method is written.
Object Description
Index
0x6098
Symbol
REF_MODE
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read/write all
PD Map
Not possible
MN-Ini. approach in direction 1
12
MN-Ini. approach in direction 2
The COMPAX parameter P213 is influenced by this object.
The direction in which the machine zero is approached is also influenced by the COMPAX parameters P212 (machine
zero mode) and P3 (speed of machine zero travel).
Example
The machine zero point initiator is approached with the positive direction in the reference run.
Service
Write request
Index
0x6098
1. data byte
0x00
Command Code
0x8082
Sub-index
0
2. data byte
0x08
Param. counter
4
Length
2
2.7.15
CAM_CMD
Special commands for COMPAX XX70.
The Sub-index is used to select the corresponding command (Sub-index = CAM command).
Object Description
Index
0x5fcc
Symbol
CAM_CMD
Length
4
Access groups
0
Object code
Array
Elements
6
Password
0
Data type
Integer32
Access rights
Write all
PD Map
Not possible
Data Description
Sub-index
Command
Resolution
1
SETC
1
2
SETM
1 ⇔ 0.001
3
SETS
1 ⇔ 0.001
4
POSR CAM
-
5
LOOP
1
6
VF
-
2.7.16
WAITPOSA
Synchronisation with automatic reverse travel (clocked command; COMPAX XX50).
Starting from the rest position of the drive, a complete synchronisation move is carried out.
The value for this object is the processing interval (length of material when cutting).
Object Description
Index
0x5fe0
Symbol
WAITPOSA
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
2. Object index
Interbus-S
40
Example
A cutting length of 205.000 mm is required.
Service
Write request
Sub-index
0
3. data byte
0x20
Command Code
0x8082
Length
4
4. data byte
0xc8
Param. counter
5
1. data byte
0x00
Index
0x5fe0
2. data byte
0x03
2.7.17
WAITPOSR
Synchronisation without automatic reverse travel (clocked command; COMPAX XX50).
Starting from the rest position of the drive, a complete synchronisation move is carried out.
The value for this object is the processing interval (length of material when cutting).
Object Description
Index
0x5fe1
Symbol
WAITPOSR
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
A cutting length of 720.000 mm is required.
Service
Write request
Sub-index
0
3. data byte
0xfc
Command Code
0x8082
Length
6
4. data byte
0x80
Param. counter
5
1. data byte
0x00
Index
0x5fe1
2. data byte
0x0a
Traverse speed in % of the nominal speed (nominal rpm * travel per motor revolution).
The value is valid until a new value is programmed.
The set speed can be reduced by using the OVERRIDE object.
A speed change during the positioning cycle is possible by using the POSR0SPEED object.
Object Description
Index
0x5fec
Symbol
SPEED
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read/write all
PD Map
PAD
Data Description
Unit
%
Resolution
1 ⇔ 1/64%; (6400 ⇔ 100%)
Example
The drive should travel at 75% of the nominal speed.
Service
Write request
Index
0x5fec
1. data byte
0x12
Command Code
0x8082
Sub-index
0
2. data byte
0xc0
Param. counter
4
Length
2
2.8.2 OVERRIDE
Reduce traverse speed.
Software emulation of an external potentiometer on the override input (X11.6).
Object Description
Index
0x5fee
Symbol
OVERRIDE
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
Read/write all
PD Map
PAD
Data Description
Unit
%
Resolution
1 ⇔ 1/255%; (255 ⇔ 100%)
Example
The traverse speed must be reduced by 50%.
Service
Write request
Index
0x5fee
Data byte
0x80
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
2. Object index
Interbus-S
42
2.8.3 POSR0SPEED
Changing traverse speed during a positioning cycle.
Object Description
Index
0x5fed
Symbol
POSR0SPEED
Length
3
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Write all
PD Map
Not possible
Data Description
Data format
BCD
Unit
%
Value range
1 ... 600 000
Resolution
1 ⇔ 0.001 %
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7,6,5,4]
105
2 [3,2,1,0]
102
1 [3,2,1,0]
104
3 [7,6,5,4]
101
2 [7,6,5,4]
103
3 [3,2,1,0]
100
Example
The drive should continue travel at 35% of the nominal speed.
Service
Write request
Index
0x5fed
1. data byte
0x03
Command Code
0x8082
Sub-index
0
2. data byte
0x50
Param. counter
5
Length
3
3. data byte
0x00
2.8.4 POSRXSPEEDY
Speed step profile.
Every revolution step profile can have a maximum of 8 revolution steps. The position value is given as a relative measurement.
It is referenced to the positioning start point.
Object Description
Index
0x5fe4
Symbol
POSRXSPEEDY
Length
8
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Write all
PD Map
Not possible
Data Description
Data byte
Assignment
Data byte
Assignment
1
Highest value byte of the position
4
Lowest value byte of the position
Coding
Complement to two
Unit
mm (or inch)
Value range
-2 147 483 648 ... +2 147 483 647
Resolution
1 ⇔ 0.001 mm (or inch)
Data byte
Assignment
Data byte
Assignment
5
Highest value byte of the speed
8
Lowest value byte of the speed
Coding
binary
Unit
%
Value range
1 ... 600 000
Resolution
1 ⇔ 0.001 %
The drive should continue travel at 33% of the nominal speed after 580 mm.
Service
Write request
Length
8
5. data byte
0x00
Command Code
0x8082
1. data byte
0x00
6. data byte
0x00
Param. counter
7
2. data byte
0x08
7. data byte
0x80
Index
0x5fe4
3. data byte
0xd9
8. data byte
0xe8
Sub-index
0
4. data byte
0xa0
2.8.5
PRXSDYALZ
Speed step profile.
Every revolution step profile can have a maximum of 8 revolution steps. The position value is given as a relative measurement.
It is referenced to the positioning start point.
Object Description
Index
0x5fc7
Symbol
PRXSDYALZ
Length
10
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Write all
PD Map
Not possible
Data Description
Data byte
Assignment
Data byte
Assignment
1
Highest value byte of the position
4
Lowest value byte of the position
Coding
Two’s complement
Unit
mm (or inch)
Value range
-2 147 483 648 ... +2 147 483 647
Resolution
1 ⇔ 0.001 mm (or Inch)
Data byte
Assignment
Data byte
Assignment
5
Highest value byte of the speed
8
Lowest value byte of the speed
Coding
binary
Unit
%
Value range
1 ... 600 000
Resolution
1 ⇔ 0.001 %
Data byte
Assignment
Data byte
Assignment
9
MSB of the ramp time
10
LSB of the ramp time
Coding
binary
Unit
ms
Value range
0 ... 65 000
Resolution
1 ⇔ 1 ms
2. Object index
Interbus-S
44
2.8.6 DREHZAHLMAX
Maximum motor speed value.
The maximum speed is given for both directions of rotation with a resolution of 1 rpm.
These are for the protection of the motor and can be found in the motor data sheet.
Object Description
Index
0x6080
Symbol
DREHZAHLMAX
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
Rpm
Resolution
1 ⇔ 1 rpm
Example
The max. speed of the motor is 6000 rpm.
Service
Write request
Index
0x6080
1. data byte
0x17
Command Code
0x8082
Sub-index
0
2. data byte
0x70
Param. counter
4
Length
2
2.8.7 GESCHW_MAX
Maximum speed
The maximum speed applies to both rotation directions.
Object Description
Index
0x607f
Symbol
GESCHW_MAX
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
%
Resolution
1 ⇔ 0.001 %
Example
The maximum speed is set to 95% of the nominal speed.
Service
Write request
Sub-index
0
3. data byte
0x73
Command Code
0x8082
Length
4
4. data byte
0x18
Param. counter
5
1. data byte
0x00
Index
0x607f
2. data byte
0x01
Given in % of the nominal speed (nominal rpm * travel per motor revolution).
The value is valid until a new value is programmed.
The set speed can be reduced by using the OVERRIDE object.
A speed change during the positioning cycle is possible by using the POSR0SPEED object.
Object Description
Index
0x6081
Symbol
VERF_GESCHW
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
%
Resolution
1 ⇔ 0.001 %
Example
The drive should travel at 66% of the nominal speed.
Service
Write request
Sub-index
0
3. data byte
0x01
Command Code
0x8082
Length
4
4. data byte
0xd0
Param. counter
5
1. data byte
0x00
Index
0x6081
2. data byte
0x01
2.8.9 S4
Current axis process speed.
Value in % of the nominal speed (nominal rpm * travel per motor revolution).
Object Description
Index
0x5ffc
Symbol
S4
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read all
PD Map
PED
Data Description
Unit
%
Resolution
1 ⇔ 1/64%; (6400 ⇔ 100%)
2. Object index
Interbus-S
46
2.8.10
GESCHW_IST
Traverse speed - actual value.
Value in % of the nominal speed (nominal rpm * travel per motor revolution).
Object Description
Index
0x606c
Symbol
GESCHW_IST
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer32
Access rights
Read all
PD Map
Not possible
Data Description
Unit
%
Resolution
1 ⇔ 0.001 %
2.8.11
GESCHW_REF
Reference run speed.
Speed set point for approaching the machine zero point.
Given in % of the nominal speed (nominal rpm * travel per motor revolution).
Object Description
Index
0x6099
Symbol
GESCHW_REF
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Unit
%
Resolution
1 ⇔ 0.001 %
Example
The reference run speed is set to 20% of the nominal speed.
Service
Write request
Sub-index
0
3. data byte
0x4e
Command Code
0x8082
Length
4
4. data byte
0x20
Param. counter
5
1. data byte
0x00
Index
0x6099
2. data byte
0x00
Ramp form speed.
Selection function with which the acceleration process is written.
Object Description
Index
0x6086
Symbol
RAMPENFORM
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Integer16
Access rights
Read/write all
PD Map
Not possible
Data Description
Selection code
Ramp shape
Selection code
Ramp shape
-1
square
2
without jerk
0
linear
Example
The drive must travel with a squared ramp form.
Service
Write request
Index
0x6086
1. data byte
0xff
Command Code
0x8082
Sub-index
0
2. data byte
0xff
Param. counter
4
Length
2
2.9.2 ACCEL_POS
Acceleration time.
Time setting for the acceleration process.
Also the time setting for the deceleration process as long as the object ACCEL-NEG or RAMPE-NEG has not been written to.
The time specification applies to nominal speed (100%).
t
SPEED
100%
ACCEL_POS
a =
•
Object Description
Index
0x5fea
Symbol
ACCEL_POS
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The next positioning process must be implemented with an acceleration time of 1000 ms.
Service
Write request
Index
0x5fea
1. data byte
0x03
Command Code
0x8082
Sub-index
0
2. data byte
0xe8
Param. counter
4
Length
2
2. Object index
Interbus-S
48
2.9.3 ACCEL_NEG
Deceleration time.
Time setting for the deceleration process.
The time specification applies to nominal speed (100%).
t
SPEED
100%
ACCEL_NEG
a =
•
Object Description
Index
0x5feb
Symbol
ACCEL_NEG
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The next positioning process must be implemented with an acceleration time of 2500 ms.
Service
Write request
Index
0x5feb
1. data byte
0x09
Command Code
0x8082
Sub-index
0
2. data byte
0xc4
Param. counter
4
Length
2
2.9.4 RAMPE_POS
Acceleration.
Time setting for the acceleration process.
Also the time setting for the deceleration process as long as the object ACCEL-NEG or RAMPE-NEG has not been written to.
The time specification applies to nominal speed (100%).
t
SPEED
100%
RAMPE_POS
a =
•
Object Description
Index
0x6083
Symbol
RAMPE_POS
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The acceleration time is set to 470 ms.
Service
Write request
Sub-index
0
3. data byte
0x01
Command Code
0x8082
Length
4
4. data byte
0xd6
Param. counter
5
1. data byte
0x00
Index
0x6083
2. data byte
0x00
Time setting for the deceleration process.
The time specification applies to nominal speed (100%).
t
SPEED
100%
RAMPE_NEG
a =
•
Object Description
Index
0x6084
Symbol
RAMPE_NEG
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The deceleration time is set to 1525 ms.
Service
Write request
Sub-index
0
3. data byte
0x05
Command Code
0x8082
Length
4
4. data byte
0xf5
Param. counter
5
1. data byte
0x00
Index
0x6084
2. data byte
0x00
2.9.6 RAMPE_NOTS
Rapid stop.
Time setting for the deceleration process if the command rapid stop (Bit 2 in the control word) is given, a limit switch is activated
or after an emergency stop.
The time specification applies to nominal speed (100%).
t
SPEED
100%
RAMPE_NOTS
a =
•
Object Description
Index
0x6085
Symbol
RAMPE_NOTS
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The braking time for rapid stop is set to 125 ms.
Service
Write request
Sub-index
0
3. data byte
0x00
Command Code
0x8082
Length
4
4. data byte
0x7d
Param. counter
5
1. data byte
0x00
Index
0x6085
2. data byte
0x00
2. Object index
Interbus-S
50
2.9.7 RAMPE_REF
Reference run acceleration.
Acceleration time for approaching the machine zero point.
The time specification applies to nominal speed (100%).
t
SPEED
100%
RAMPE_REF
a =
•
Object Description
Index
0x609a
Symbol
RAMPE_REF
Length
4
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned32
Access rights
Read/write all
PD Map
Not possible
Data Description
Value range
0 ... 65 000
Unit
ms
Resolution
1 ⇔ 1 ms
Example
The acceleration time for the reference run is set to 733 ms.
Service
Write request
Sub-index
0
3. data byte
0x02
Command Code
0x8082
Length
4
4. data byte
0xdd
Param. counter
5
1. data byte
0x00
Index
0x609a
2. data byte
0x00
Logic state of the 16 digital inputs.
Some inputs are assigned fixed control functions.
Input
Assignment
Input
Assignment
1
SHIFT
1 & 3
Find real null (RN)
2
Hand+
1 & 4
Teach real zero
3
Hand-
1 & 5
Reserved
4
Quit
1 & 6
Break
5
START
9...13
Freely assignable in standard model
6
STOP
14
Activate label reference
7...8
Freely assignable in standard model
15
Faster start
1 & 2
Find machine zero (MN)
16
Label input
Object Description
Index
0x5ff8
Symbol
INPUT_WORD
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet String
Access rights
Read all
PD Map
PED
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
Status input 16
2 [7]
Status input 8
1 [0]
Status input 9
2 [0]
Status input 1
2.10.2
OUTPUT_WORD
Logic state of the 16 digital outputs.
Some outputs are assigned a fixed status information.
Output
Assignment
Output
Assignment
1
no fault
5
Programmed nominal position reached
2
No warning
6
Idle after stop
3
Machine zero has been approached
7...15
Freely assignable in standard model
4
Ready for start
16
Label present after max. feed length
This object allows the outputs to be set or reset to default.
Each output which must be influenced via the Interbus-S, must be specifically enabled with the object OUTPUT-MASK. The
output thereby loses any status information which was assigned to it.
Object Description
Index
0x5ff7
Symbol
OUTPUT_WORD
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
PED & PAD
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
Status output 16
2 [7]
Status output 8
1 [0]
Status output 9
2 [0]
Status output 1
2. Object index
Interbus-S
52
2.10.3
OUTPUT
Set or reset a digital output.
The corresponding output is selected using the Sub-index (Sub-index = output no.).
Some outputs have a fixed status information assigned (see OUTPUT-WORD).
Object Description
Index
0x5ff6
Symbol
OUTPUT
Length
1
Access groups
0
Object code
Array
Elements
16
Password
0
Data type
Boolean
Access rights
Write all
PD Map
Not possible
Data Description
Data byte
Function
Data byte
Function
= 0xff (TRUE)
Output [Sub-index] = 1
= 0x00 (FALSE)
Output [Sub-index] = 0
Example
Output 13 must be set.
Service
Write request
Index
0x5ff6
Data byte
0xff
Command Code
0x8082
Sub-index
13
Param. counter
4
Length
1
2.10.4
OUTPUT_MASK
Mask outputs.
Each output which must be influenced via the Interbus-S, must be specifically enabled (masked).
The output thereby loses any status information which was assigned to it.
After Power On, the OUTPUT-MASK has the value 0, i.e. all outputs are disabled for the IBS (not masked).
Object Description
Index
0x5ff5
Symbol
OUTPUT_MASK
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
Not possible
Data Description
Data byte [Bit]
Assignment
Data byte [Bit]
Assignment
1 [7]
Mask output 16
2 [7]
Mask output 8
1 [0]
Mask output 9
2 [0]
Mask output 1
Example
Outputs 9 - 16 must be masked.
Service
Write request
Index
0x5ff5
1. data byte
0xff
Command Code
0x8082
Sub-index
0
2. data byte
0x00
Param. counter
4
Length
2
Comparator function (active high).
Set an unassigned output within a positioning cycle.
The position value is given as a relative measurement. It is referenced to the positioning start point.
A maximum of 8 comparators can be set for a positioning process.
The corresponding output is selected using the Sub-index (Sub-index = output no.).
Object Description
Index
0x5fe2
Symbol
POSROUTPUTP
Length
4
Access groups
0
Object code
Array
Elements
16
Password
0
Data type
Integer32
Access rights
Write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
Output 11 must be set when the drive has travelled 888 mm.
Service
Write request
Sub-index
11
3. data byte
0x65
Command Code
0x8082
Length
4
4. data byte
0x00
Param. counter
5
1. data byte
0x00
Index
0x5fe2
2. data byte
0x04
2.10.6
POSROUTPUTN
Comparator function (active low).
Reset an unassigned output within a positioning cycle.
The position value is given as a relative measurement. It is referenced to the positioning start point.
A maximum of 4 comparators can be set for a positioning process.
The corresponding output is selected using the Sub-index (Sub-index = output no.).
Object Description
Index
0x5fe3
Symbol
POSROUTPUTN
Length
4
Access groups
0
Object code
Array
Elements
16
Password
0
Data type
Integer32
Access rights
Write all
PD Map
Not possible
Data Description
Unit
mm (or inch)
Resolution
1 ⇔ 0.001 mm (or inch)
Example
Output 11 must be reset when the drive has travelled 1888 mm.
Service
Write request
Sub-index
11
3. data byte
0xa7
Command Code
0x8082
Length
4
4. data byte
0x40
Param. counter
5
1. data byte
0x00
Index
0x5fe3
2. data byte
0x13
2. Object index
Interbus-S
54
2.11 Programming
2.11.1
N
Reading and writing the program memory with command records in plain text (ASCII format).
The record number is determined with the sub-index (Sub-index = record No.)
Object Description
Index
0x5ff1
Symbol
N
Length
32
Access groups
0
Object code
Array
Elements
250
Password
0
Data type
Visible string
Access rights
Read/write all
PD Map
Not possible
Data Description
Data format
ASCII
Value range
0x20 ... 0x7f
Data byte 1
1st character of the command record
Data byte 32
32
nd character of the command record
Example
Record 5 must be written with the command "POSA 250".
Service
Write request
Length
20
5. data byte
0x20 (" ")
Command Code
0x8082
1. data byte
0x50 ("P")
6. data byte
0x32 ("2")
Param. counter
19
2. data byte
0x4f ("O")
7. data byte
0x35 ("5")
Index
0x5ff1
3. data byte
0x53 ("S")
8. data byte
0x30 ("0")
Sub-index
5
4. data byte
0x41 ("A")
9...32. data byte
0x20 (" ")
Long, combined commands with 32 characters cannot be completely displayed.
These commands can however be written with the use of command abbreviations.
2.11.2
Nx
Reading and writing the program memory with command records in binary format.
The record number is determined with the Sub-index (Sub-index = record No.)
Object Description
Index
0x5fd5
Symbol
Nx
Length
20
Access groups
0
Object code
Array
Elements
250
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
Not possible
Data Description
Data byte
Assignment
1
Record length (number of relevant record data)
2
1
st character of the record content
...
20
last character of the record contents
COMPAX – Command codes
Definition of the command code
A command code consists of 1 byte.
Sorted by command code
Code
Command
0x20
Empty instruction (No Operation)
0x01
VALIDP / C / F
0x41
POSA value / POSA HOME
0x42
GOSUB
0x43
SETC n
0x45
END
0x47
GOTO
0x49
IF Ex=y ... / IF ERROR ... / IF STOP ...
0x4A
IF < Comparison operator >
...
0x4B
LOOP n
0x4C
ACCEL value
0x4D
SETM Value
0x4F
OUTPUT Ax=y
0x50
Pn=. . .
0x51
SETS
0x52
POSR value / POSR CAM
0x53
SPEED value / SPEED SYNC
0x54
REPEAT Value
0x55
RETURN
0x56
Vn=. . .
0x57
WAIT value / WAIT START
0x61
POSA Parameter
0x6B
LOOP Parameter
0x6C
ACCEL Parameter
0x6D
SETM Parameter
0x72
POSR Parameter
0x73
SPEED Parameter
0x74
REPEAT Parameter
0x77
WAIT Parameter
0xC1
POSA Variable
0xCB
LOOP Variable
0xCC
ACCEL Variable
0xCD
SETM Variable
0xD2
POSR Variable
0xD3
SPEED Variable
0xD4
REPEAT Variable
0xD7
WAIT Variable
Sorted by command code
Code
Command
0x6C
ACCEL Parameter
0xCC
ACCEL Variable
0x4C
ACCEL value
0x45
END
0x42
GOSUB
0x47
GOTO
0x4A
IF
...
0x49
IF Ex=y ... / IF ERROR ... / IF STOP ...
0x20
Empty instruction (No Operation)
0x4B
LOOP n
0x6B
LOOP Parameter
0xCB
LOOP Variable
0x4F
OUTPUT Ax=y
0x50
Pn=. . .
0x61
POSA Parameter
0xC1
POSA Variable
0x41
POSA value / POSA HOME
0x72
POSR Parameter
0xD2
POSR Variable
0x52
POSR value / POSR CAM
0x74
REPEAT Parameter
0xD4
REPEAT Variable
0x54
REPEAT Value
0x55
RETURN
0x43
SETC n
0x6D
SETM Parameter
0xCD
SETM Variable
0x4D
SETM Value
0x51
SETS
0x73
SPEED Parameter
0x3D
SPEED Variable
0x53
SPEED value / SPEED SYNC
0x01
VALIDP / C / F
0x56
Vn=. . .
0x77
WAIT Parameter
0x7D
WAIT Variable
0x57
WAIT VALUE/ WAIT START
2. Object index
Interbus-S
56
Operand codes
An operand consists of 7 bytes; 1 byte for the type indicator and 6 data bytes.
Operand
Type
D1
D2
D3
D4
D5
D6
Parameter
0x50
No.H
Nr.L
0x00
0x00
0x00
0x00
Status
0x53
No.H
Nr.L
0x00
0x00
0x00
0x00
Variable
0x56
No.H
Nr.L
0x00
0x00
0x00
0x00
Constants
0x20
NL
NM
NH
VL
VM
VH
Comparison operator codes
A comparison operator consists of 1 byte.
Comparison operator
Symbols
Code
Equal
=
0x3D
Less than
<
0x3C
More than
>
0x3E
Equal to/less than
<=
0xBC
Equal to/greater than
>=
0xBE
Does not equal
<>
0xBB
Arithmetic operator codes
An arithmetic operator consists of 1 byte.
Arithmetic Operator
Symbols
Code
Addition
+
0x2B
Subtraction
-
0x2D
Multiplication
*
0x2A
Division
/
0x2F
Whole number division
\
0x5C
Modulo calculation
%
0x25
The following set memory – command code table is a result of the application of these codes. All of the
commands are listed individually here!
COMPAX Set memory-command code table
Command
Code
ACCEL Parameter
0x6C
No.H
Nr.L
ACCEL Variable
0xCC
No.H
Nr.L
ACCEL Value
0x4C
MSB
LSB
END
0x45
0x00
GOSUB EXT
0x42
0x00
0x00
GOSUB Value
0x42
MSB
LSB
GOTO EXT
0x47
0x00
0x00
GOTO Value
0x47
MSB
LSB
IF ERROR GOSUB n
0x49
0x00
0xFF
0x31
0x42
n MSB
n LSB
IF Ex=y GOSUB n
0x49
x MSB
x LSB
y
0x42
n MSB
n LSB
IF Ex=yy GOSUB n
0x49
x MSB
x LSB
y1
y2
0x42
n MSB
n LSB
IF Ex= . . .
...
...
...
...
...
...
...
...
IF Ex=yyyyyyyy GOSUB n
0x49
x MSB
x LSB
y1
y2
y3
y4
y5
y6
y7
y8
0x42
n MSB
n LSB
IF Ex=y GOTO n
0x49
x MSB
x LSB
y
0x47
n MSB
n LSB
IF Ex=yy GOTO n
0x49
x MSB
x LSB
y1
y2
0x47
n MSB
n LSB
IF Ex= . . .
...
...
...
...
...
...
...
...
IF Ex=yyyyyyyy GOTO n
0x49
x MSB
x LSB
y1
y2
y3
y4
y5
y6
y7
y8
0x47
n MSB
n LSB
IF GOTO n
0x4A
O1Type
O1D1
O1D2
O1D3
O1D4
O1D5
O1D6
Vglop
O2Type
O2D1
O2D2
O2D3
O2D4
O2D5
O2D6
0x47
n MSB
n LSB
IF < Comparison operator > GOSUB n
0x4A
O1Type
O1D1
O1D2
O1D3
O1D4
O1D5
O1D6
Vglop
O2Type
O2D1
O2D2
O2D3
O2D4
O2D5
O2D6
0x42
n MSB
n LSB
IF STOP GOSUB n
0x49
0x00
0xFE
0x31
0x42
n MSB
n LSB
LOOP n
0x4B
n MSB
n LSB
LOOP Parameter
0x6B
No.H
Nr.L
LOOP Variable
0xCB
No.H
No .L
OUTPUT Ax=y
0x4F
x MSB
x LSB
y
OUTPUT Ax=yy
0x4F
x MSB
x LSB
y1
y2
OUTPUT Ax=. . .
...
...
...
...
...
...
OUTPUT Ax=yyyyyyyy
0x4F
x MSB
x LSB
y1
y2
y3
y4
y5
y6
y7
y8
OUTPUT A0=y
0x4F
0x00
0x00
y
POSA HOME
0x41
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
POSA Parameter
0x61
No.H
Nr.L
0x00
0x00
0x00
0x00
POSA Variable
0x1C
No.H
Nr.L
0x00
0x00
0x00
0x00
POSA Value t
0x41
NL
NM
NH
VL
VM
VH
POSR CAM
0x52
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
POSR Parameter
0x72
No.H
Nr.L
0x00
0x00
0x00
0x00
POSR Variable
0x2D
No.H
Nr.L
0x00
0x00
0x00
0x00
POSR Value
0x52
NL
NM
NH
VL
VM
VH
REPEAT Parameter
0x74
No.H
Nr.L
REPEAT Variable
0x4D
No.H
Nr.L
REPEAT Value t
0x54
MSB
LSB
RETURN
0x55
0x00
SETC n
0x43
n MSB
n LSB
SETM Value
0x4D
NL
NM
NH
VL
VM
VH
SETM Parameter
0x6D
No.H
Nr.L
0x00
0x00
0x00
0x00
SETM Variable
0xCD
No.H
Nr.L
0x00
0x00
0x00
0x00
SETS
0x51
SPEED Parameter
0x73
No.H
Nr.L
0x00
0x00
0x00
0x00
SPEED Variable
0x3D
No.H
Nr.L
0x00
0x00
0x00
0x00
2. Object index
Interbus-S
58
Command
Code
SPEED Value
0x53
NL
NM
NH
VL
VM
VH
SPEED SYNC
0x53
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
VALIDP
0x01
0x56
0x50
VALIDC
0x01
0x56
0x43
VALIDF
0x01
0x56
0x46
WAIT Parameter
0x77
No.H
Nr.L
WAIT Variable
0x7D
No.H
Nr.L
WAIT Value
0x57
MSB
LSB
WAIT START
0x57
0x00
0x00
POSA Value WAIT Value
0x41
NL
NM
NH
VL
VM
VH
0x57
MSB
LSB
POSA . . . WAIT . . .
...
...
...
...
...
...
...
(Combinations examples.: ... Value ... .V12, ... .P40 ... .V10)
...
...
...
...
...
...
...
POSA Variable WAIT Variable
0x1C
No.H
Nr.L
0x00
0x00
0x00
0x00
0x7D
No.H
Nr.L
POSR Value OUTPUT Ax=y
0x52
NL
NM
NH
VL
VM
VH
0x4F
x MSB
x LSB
y
POSR Parameter OUTPUT Ax=y
0x72
No.H
Nr.L
0x00
0x00
0x00
0x00
0x4F
x MSB
x LSB
y
POSR Variable OUTPUT Ax=y
0x2D
No.H
Nr.L
0x00
0x00
0x00
0x00
0x4F
x MSB
x LSB
y
POSR Value t SPEED Value
0x52
NL
NM
NH
VL
VM
VH
0x53
NL
NM
NH
VL
VM
VH
POSR . . . SPEED . . .
...
...
...
...
...
...
...
(Combinations examples.: ... Value ... .V12, ... .P40 ... .V10)
...
...
...
...
...
...
POSR Variable SPEED Variable
0x2D
No.H
Nr.L
0x00
0x00
0x00
0x00
0x3D
No.H
Nr.L
0x00
0x00
0x00
0x00
POSR Value SPEED Value ACCEL Value
0x52
NL
NM
NH
VL
VM
VH
0x53
NL
NM
NH
VL
VM
VH
0x4C
MSB
LSB
POSR ... SPEED ... ACCEL ...
...
...
...
...
...
...
...
(Combinations examples.: ... Value ... .V12 ... .V13, ... .P40 ... .V10 ... .P41)
...
...
...
...
...
...
...
...
POSR Variable SPEED Variable ACCEL Variable
0x2D
No.H
Nr.L
0x00
0x00
0x00
0x00
0x3D
No.H
Nr.L
0x00
0x00
0x00
0x00
0xCC
No.H
Nr.L
POSR Value WAIT Value
0x52
NL
NM
NH
VL
VM
VH
0x57
MSB
LSB
POSR . . . WAIT . . .
...
...
...
...
...
...
...
...
(Combinations examples.: ... Value ... .V12, ... .P40 ... .V10)
...
...
POSR Variable WAIT Variable
0x2D
No.H
Nr.L
0x00
0x00
0x00
0x00
0x7D
No.H
Nr.L
SPEED Value WAIT Value
0x53
NL
NM
NH
VL
VM
VH
0x57
MSB
LSB
SPEED . . . WAIT . . .
...
...
...
...
...
...
...
...
(Combinations examples.: ... Value ... .V12, ... .P40 ... .V10)
...
...
SPEED Variable WAIT Variable
0x3D
No.H
Nr.L
0x00
0x00
0x00
0x00
0x7D
No.H
Nr.L
WAIT POSA Value
0x57
0x00
0x00
0x41
NL
NM
NH
VL
VM
VH
WAIT POSR Value
0x57
0x00
0x00
0x52
NL
NM
NH
VL
VM
VH
Pn= [ ]
0x50
n MSB
n LSB
O1Type
O1D1
O1D2
O1D3
O1D4
O1D5
O1D6
AriOp
O2Type
O2D1
O2D2
O2D3
O2D4
O2D5
O2D6
Vn= [ ]
0x56
n MSB
n LSB
O1Type
O1D1
O1D2
O1D3
O1D4
O1D5
O1D6
AriOp
O2Type
O2D1
O2D2
O2D3
O2D4
O2D5
O2D6
Key:
No.H:
High byte of the parameter/variable number
Nr.L:
Low byte of the parameter/variable number
MSB:
High byte of an integer value
LSB:
Low byte of an integer value
NL:
Low byte of the fractional digit of a value in DSP number format
NM:
Mid byte of the fractional digit of a value in DSP number format
NH:
High byte of the fractional digit of a value in DSP number format
VL:
Low Byte of the integral digit of a value in DSP number format
VM:
Mid Byte of the integral digit of a value in DSP number format
VH:
High byte of the integral digit of a value in DSP number format
O1Type:
Type indicator of the 1. operand
O1D1...O1D6: Data for the 1
st operand
O2Type:
Type indicator of the 2. operand
O2D1...O2D6: Data for the 2
nd operand
Vglop:
Comparison operator
AriOp:
Arithmetic Operator
y (y1, y2, ...)
y=0x30 for "1" and y=0x31 for "0"
2. Object index
Interbus-S
60
2.11.3
GOTO
Set and read record pointer.
Object Description
Index
0x5ff2
Symbol
GOTO
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
Read/write all
PD Map
Not possible
Data Description
Data format
Binary
Unit
Record number
Value range
1 ... 250
Resolution
1
Example
The record pointer is set to command record 18.
Service
Write request
Index
0x5ff2
Data byte
0x12
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
2.11.4
START_N
Run program record N.
Only this record is processed. The record pointer remains at this program record.
Object Description
Index
0x5ff4
Symbol
START_N
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
Write all
PD Map
PAD
Data Description
Data format
Binary
Unit
Record number
Value range
1 ... 250
Resolution
1
Example
Program record 26 must be processed.
Service
Write request
Index
0x5ff4
Data byte
0x1a
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
Start program at record N.
The record pointer is set to the corresponding program record and then the program is started.
Object Description
Index
0x5fe5
Symbol
START_N_GO
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
Write all
PD Map
PAD
Data Description
Data format
Binary
Unit
Record number
Value range
1 ... 250
Resolution
1
Example
The program must be processed from record 50.
Service
Write request
Index
0x5fe5
Data byte
0x32
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
2.11.6
TEACH_N
Take over current position in record N.
The command "POSA current position" is stored in record N.
Object Description
Index
0x5ff3
Symbol
TEACH_N
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned8
Access rights
Write all
PD Map
Not possible
Data Description
Data format
Binary
Unit
Record number
Value range
1 ... 250
Resolution
1
Example
The current position must be stored in record 70.
Service
Write request
Index
0x5ff3
Data byte
0x46
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
2. Object index
Interbus-S
62
2.11.7
CAM_MEM_P
Special command for COMPAX XX70.
Set and read curve memory pointer.
Object Description
Index
0x5fca
Symbol
CAM_MEM_P
Length
2
Access groups
0
Object code
Simple var.
Password
0
Data type
Unsigned16
Access rights
Read/write all
PD Map
Not possible
Data Description
Data format
Binary
Unit
Curve memory number
Value range
1 ... 5460
Resolution
1
2.11.8
CAM_MEM
Special command for COMPAX XX70.
Read and write the curve memory.
The curve memory number is defined by the current value of the curve memory pointer (CAM_MEM_P).
The curve memory pointer is automatically incremented after this object is accessed.
Object Description
Index
0x5fcb
Symbol
CAM_MEM
Length
3
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
Not possible
Data Description
Data byte
1
2
3
Meaning
Record memory contents
Assignment
MSB
...
LSB
2.11.9
VX
Enter or read COMPAX variable.
The corresponding variable is selected using the Sub-index (Sub-index = variable No.).
Sub-index = 40 addresses variable 0 of the COMPAX, with which all variables can be set to the same value.
Object Description
Index
0x5fcd
Symbol
VX
Length
4
Access groups
0
Object code
Array
Elements
40
Password
0
Data type
Integer32
Access rights
Read/write all
PD Map
Not possible
Data description (P196 Bit 4 = "0")
Variable
Resolution
Variable
Resolution
001 .. 005
1 ⇔ 0.001
023 .. 029
1
006 .. 010
1
030 .. 034
1 ⇔ 0.001
011 .. 016
1 ⇔ 0.001
035 .. 036
1 ⇔ 0.000001
017 .. 020
1
037 .. 040
1 ⇔ 0.001
021 .. 022
1 ⇔ 0.000001
Data description (P196 Bit 4 = "1") (New from Interbus-S - Software V2.12 onwards)
Variable
Resolution
001 .. 040
1 ⇔ 0.001
2. Object index
Interbus-S
64
OBJECT_REQ and OBJECT_RSP for 8 byte process data channel
The two new objects OBJECT_REQ and OBJECT_RSP make it possible to access all communication objects (or certain
elements) with a data width of ≤ 4 byte via the process data channel.
The object OBJECT_REQ can be assigned to the PAD channel (PAD3...PAD8):
♦ permanently with P139 = 6276352 (=0x5fc500)
♦ temporarily (if P196 Bit 5 = 1) as follows:
1. Save values of PAD3...PAD8 if necessary (save target values).
2. FreezePAD (STEUERWORT/CPX_STW Data byte1 Bit 1) = 1
This freezes the previous PAD, no more value changes on the PAD are made.
3. Wait until AckToggle(STATUSWORT/CPX_ZSW Data byte1 Bit0) has changed its value.
4. PAD3...PAD8 = 0
5. ObjectReqEnable (STEUERWORT/CPX_STW Data byte1 Bit0) = 1
6. Wait until AckToggle(STATUSWORT/CPX_ZSW Data byte1 Bit0) has changed its value.
PAD3...PAD8 will now be transferred to OBJECT_REQ
7. write and/or read all required objects
8. ObjectReqEnable (STEUERWORT/CPX_STW Data byte1 Bit0) = 0
9. Wait until AckToggle(STATUSWORT/CPX_ZSW Data byte1 Bit0) has changed its value.
10. Reset PAD3...PAD8 to their original target values
11. FreezePAD (STEUERWORT/CPX_STW Data byte1 Bit 1) = 0
12. Wait until AckToggle(STATUSWORT/CPX_ZSW Data byte1 Bit0) has changed its value.
PAD3...PAD8 will now be transferred to the original objects
Object OBJECT_RSP can be assigned to the PED channel (PED3...PED8):
♦ permanently with P135= 6276608 (0x5fc6000)
♦ temporarily parallel with ObjectReqEnable (STEUERWORT/CPX_STW Data byte1 Bit0) = 1 (if P196 Bit 6=0 and P196 Bit 5 =
1))
or separately via the object CONTROL
OBJECT_REQ and OBJECT_RSP for 8 byte process data channel
2.11.9
VX
65
Example: P196 Bit 0..2 = "4" (8 Byte process data),
P196 Bit 7 ="0" (PD1/2 = STEUERWORT / STATUSWORT),
P196 Bit 5 = "1" (OBJECT_REQ and OBJECT_RSP can be temporarily assigned to PD),
P196 Bit 6 = "0" (OBJECT_RSP automatically assigns PED as answer to OBJECT_REQ)
Basic setting for PAD with P139="6322688" (LAGE_ZIEL=PAD3-6) and P142="6289152"
(OUTPUT_WORD=PAD7-8) and for PED with P135="6317056" (LAGE_IST=PED3-6) and P138="6289408"
(INPUT_WORD=PED7-8)
In this example you should make a backup copy of the contents of LAGE_ZIEL and OUTPUT_WORD before you
switch to OBJECT_REQ.
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "0"
1[0] FreezePAD = "0"
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "0"
(angenommener
Anfangszustand)
FreezePAD = "1" COMPAX freezes previous PAD;
does not read from PAD anymore
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "0"
1[0] FreezePAD = "1"
Wait until COMPAX AckToggle = "1" message:
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "1"
Describe PAD with "0" and set ObjectReqEnable = "1"
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "1"
1[0] FreezePAD = "1"
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "0"
Transfer PAD with OBJECT_REQ (P23=200% write)
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "1"
1[0] FreezePAD = "1"
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "1"
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
Set ObjectReqEnable = "0"
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "0"
1[0] FreezePAD = "1"
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
Answer from COMPAX by changing AckToggle
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "0"
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
POSITION_TARGET
Set PAD to the original value and set FreezePAD = "0"
PAD Master ⇒
⇒
⇒
⇒ COMPAX
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
STEUERWORT
1[1] ObjectReqEnable = "0"
1[0] FreezePAD = "0"
POSITION_TARGET
POSITION_TARGET
PED Master ⇐
⇐
⇐
⇐ COMPAX
PED1
PED2
PED3
PED4
PED5
PED6
PED7
PED8
STATUSWORT
1[0] AckToggle = "1"
POSITION_TARGET
POSITION_TARGET
OBJECT_REQ, OBJECT_RSP
This procedure allows you to write and read several objects.
Switch back to cyclic process data:
2. Object index
Interbus-S
66
OBJECT_REQ
Write or read communication via process data channel.
The object is selected with the 7 Bit-wide index pointer (please see footnote); the respective element of an object is selected
with the sub-index. The highest bit of the data byte 1 determines the object access (0 = write; 1 = read).
The acknowledgement for a write-access or the answer for a read-access is passed onto the object OBJECT_RSP.
Every value change in OBJECT_REQ is acknowledged by the complementation of AckToggle (STATUSWORT/CPX_ZSW
Data byte1 Bit 0). If the value change results in the writing or reading of an object, AckToggle is only complemented when the
write/read process is completely finished.
If the index pointer does not equal 0, every value change in OBJECT_REQ results in writing or reading the selected objects or
one of its elements. If an object is described with the same value in succession (z. B. POSR), the index pointer must be set to 0
and then reset to its original value.
Object Description
Index
0x5FC5
Symbol
OBJECT_REQ
Length
6
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Write all
PD Map
PAD
Data Description
Data byte [Bit]
Assignment
Data byte[Bit]
Assignment
1[7]
0 = Object write; 1 = Object read
3
Object-Data byte 1
1 [6 ... 0]
Index(Object) pointer1
4
Object-Data byte 2
5
Object-Data byte 3
2
Sub-index
6
Object-Data byte 4
OBJECT_RSP
Acknowledgement for a write-access or answer to a read-access to an object via OBJECT_REQ.
Object Description
Index
0x5FC6
Symbol
OBJECT_RSP
Length
6
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read all
PD Map
PED
Data Description
Data byte
Assignment -Write-access
Assignment –Read-access
Assignment -error
1
like OBJECT_REQ
like OBJECT_REQ
0xFF
2
like OBJECT_REQ
like OBJECT_REQ
like OBJECT_REQ
3
like OBJECT_REQ
Object data byte 1
Error number
4
like OBJECT_REQ
Object data byte 2
0x00
5
like OBJECT_REQ
Object data byte 3
0x00
6
like OBJECT_REQ
Object data byte 4
0x00
No.:
Meaning
No.:
Meaning
82
Wrong index(object)-pointer.
84
Object cannot be read.
83
Incorrect Sub-index.
85
Object cannot be written.
The specific COMPAX error messages are outlined in the COMPAX product manual.
1 Please ensure that the index pointer and not the index of the required object is entered. You will find the respective index
pointer for the onject in the object overview from page 10onwards.
2.12 Process data control
2.12.1
PAD_Steuerung
67
2.12 Process data control
This function emulates the process data, which are transmitted via the process data channel, on the communication objects.
The COMPAX process data channel has a width of 2, 4 or 6 bytes; depending on the value in parameter 196. Each byte can be
read and written by COMPAX.
The data read by COMPAX from the process data channel are called process output data (PA data). The data written by
COMPAX into the process data channel are called process input data (PE data).
Through the emulation of COMPAX communication objects to the PE data, the latter are cyclically read on the process data
channel. The PA data which are emulated to a COMPAX communication object cyclically describe this object.
The allocation of process data to certain communication objects is determined by the objects "PE_SELECT" and "PA_SELECT"
(the objects "IN_SELECT" and "OUT_SELECT" are previous names).
Both objects "PED_INI" and "PAD_INI" determine which allocation shall be valid after Power-On (this corresponds to the
settings through the COMPAX - Parameter).
The PA data can be enabled or disabled with the objects "OUT_ENABLE" or "PA_ENABLE".
After Power On the PA data are enabled!
2.12.1
PAD_Steuerung
The process output data can be used to cyclically write to the following COMPAX communication objects.
Object name
Description
Index
COMPAX -
Parameter
2
Byte
see
dec
hex
P139 ... P142
Number
page
STEUERBYTE
Control byte
24526
0x5fce
1
17
STEUERWORT
Control word
24640
0x6040
2
19
CPX_STW
COMPAX control word/virtual inputs
24530
0x5fd2
2
18
CONTROL
Control commands
24553
0x5fe9
1
22
LAGE_ZIEL
Target position default
24698
0x607a
4
33
SPEED
Traverse speed
24556
0x5fec
2
41
OVERRIDE
Reduce traverse speed
24558
0x5fee
1
41
OUTPUT_WORD
16 Dig. Set/reset outputs
24567
0x5ff7
2
51
START_N
Execute program record N
24564
0x5ff4
1
60
START_N_GO
Program start beginning at record N
24549
0x5fe5
1
61
OBJECT_REQ
Read and write objects through PAD
24517
0x5fc5
6276352
6
65
Because the PAD channel has a max. length of 8 bytes, it is not possible to have simultaneous access all the objects listed
here. This means you need to make an appropriate selection.
2 Index * 256 + Sub-index
2. Object index
Interbus-S
68
Setting the PAD:
! using the object "Process Output Data Description" (PA_SELECT; see page 73),
or
! using the COMPAX parameters P139, P140, P141, P142 (corresponds to the object PAD_INI; see page 76).
You may place each of the named objects on the PAD channel according to its required bytes.
Set the corresponding COMPAX parameter to the value given for the respective object (see table above).
Length
Possible assignment in the PAD channel
Object:
in byte
PAD1
PAD2
PAD3
PAD4
PAD5
PAD6
PD-Length=8Byte
(P196 Bit 0...2="4")
PAD3
PAD4
PAD5
PAD6
PAD7
PAD8
P139
P140
P141
P142
STEUERBYTE
1
CONTROL
1
OVERRIDE
1
START_N
1
START_N_GO
1
STEUERWORT
2
CPX_STW
2
SPEED
2
OUTPUT_WORD
2
LAGE_ZIEL
4
OBJECT_REQ
6
Please ensure that there is no double assignment on the PAD channel.
Double assigning occurs, for example, if the POSITION_TARGET is in PAD1 - PAD4, and P141 is used to assign PAD3
again. The proper action in this case would be: LAGE_ZIEL on PAD1 - PAD4 via P139 = and P140 = P141 = 0!
PA_SELECT allows the channels to be freely assigned. You will find depictions of the various possibilities of parameters
P139-P142.
PADs disable / enable
The PAD's can be individually disabled and enabled using the object "Enable Process Output Data" (PA_ENABLE see page
74). This means an object is only written with the value from the PAD channel if the corresponding PAD's are also enabled.
After "Power on" the PAD's are enabled, i.e., normally no setting needs to be made here.
After power on, the COMPAX parameters P139, P140, P141 and P142 initialise the objects PA_INI and PA_SELECT and
thereby the PAD channel.
The PAD_INI object can be used to read and write these parameters.
Notes
Note the following when configuring the PAD:
• After Power On, the PAD's are enabled if a valid configuration for the PAD is entered in the COMPAX parameters P139 ...
P142.
• Note the length (number of bytes) of an object. An object can be represented on the PADs if the corresponding number of
PAD bytes are free, i.e. not occupied by any other objects.
• Using the null object (Index and Sub-index = 0) or by setting the corresponding COMPAX parameter to "0", an object can
again be removed (deleted) from the PAD channel.
2.12 Process data control
2.12.1
PAD_Steuerung
69
Example assignments for the PAD's
The POSITION_TARGET and SPEED objects are represented on the PAD's.3
PAD1(3)
PAD2(4)
PAD3(5)
PAD4(6)
PAD5(7)
PAD6(8)
Bit0
PA_ENABLE
Bit1
Bit2
Bit3
Bit4
Bit5
LAGE_ZIEL
SPEED
DB1 (MSB)
DB2
DB3
DB4 (LSB)
DB2 (LSB)
DB1 (MSB)
"1"
"0"
"1"
"0"
"1"
"0"
"1"
"0"
"1"
"0"
"1"
"0"
Object "PA_SELECT" (see page 73)
Using the object "PA_SELECT", the PAD assignment can be changed during operation:
Sub-index
Meaning
value
dec
hex
1
PAD length (not variable)
6
0x06
2
Object index assigned for PAD1 (3)
24698
0x607a
3
Object sub-index assigned for PAD1 (3)
0
0x00
4
Object index assigned for PAD2 (4)
0
0x0000
5
Object sub-index assigned for PAD2 (4)
0
0x00
6
Object index assigned for PAD3 (5)
0
0x0000
7
Object sub-index assigned for PAD3 (5)
0
0x00
8
Object index assigned for PAD4 (6)
0
0x0000
9
Object sub-index assigned for PAD4 (6)
0
0x00
10
Object index assigned for PAD5 (7)
24556
0x5fec
11
Object sub-index assigned for PAD5 (7)
0
0x00
12
Object index assigned for PAD6 (8)
0
0x0000
13
Object sub-index assigned for PAD6 (8)
0
0x00
After changing the PAD - assignment via object "PA_SELECT", PA_ENABLE is set to "0" to avoid an undefined
condition. After a PAD change the PAD's must be manually enabled again using the PA_ENABLE object.
So that this setting of the PAD channel is already available upon power-up, the corresponding COMPAX parameters (P139 ...
P142) resp. PAD_INI are to be assigned as follows:
Sub-index
Meaning
value
(Parameter)
dec
hex
1 (P139)
Object index and sub-index assigned for PAD1 (3)
6322688
0x607a00
2 (P140)
Object index and sub-index assigned for PAD2 (4)
0
0x000000
3 (P141)
Object index and sub-index assigned for PAD3 (5)
0
0x000000
4 (P142)
Object index and sub-index assigned for PAD5 (7)
6286336
0x5fec00
3 The PAD numbers in brackets are valid for a PD length of 8 bytes (P196 Bit 0...2 = "4").
2. Object index
Interbus-S
70
2.12.2
PED_Steuerung
The process input data can be used to cyclically read from the following COMPAX communication objects.
Object name
Description
Index
COMPAX -
Parameter
4
Byte
see
dec
hex
P135 ... P138
Number
page
STATUSBYTE
Status byte
24527
0x5fcf
1
17
STATUSWORT
Status word
24641
0x6041
2
20
CPX_ZSW
COMPAX status word
24531
0x5fd3
2
19
LAGE_IST
Actual position value
24676
0x6064
4
35
INPUT_WORD
Log. state of the 16 dig. inputs
24568
0x5ff8
2
51
OUTPUT_WORD
Log. state of the 16 dig. outputs
24567
0x5ff7
2
51
S3
Lag error
24570
0x5ffa
2
15
S4
Current traverse speed
24572
0x5ffc
2
45
S5
Current motor torque
24571
0x5ffb
2
30
OBJECT_RSP
COMPAX – answer to OBJECT_REQ
24518
0x5fc6
6276608
6
66
Because the PED channel has a max length of 8 byte, it is not possible to read all listed objects simultaneously. This means you
need to make an appropriate selection.
Setting the PED
! via the object "Process Input Data Description",
or
! via the COMPAX parameters P135, P136, P137, P138 (corresponds to the object PED_INI).
You may place each of the named objects on the PED channel according to its required bytes.
Set the corresponding COMPAX parameter to the value given for the respective object (see table above).
Length
Possible assignment in the PED channel
in byte
PED1
PED2
PED3
PED4
PED5
PED6
PD-Length=8Byte
(P196 Bit 0...2="4")
PED3
PED4
PED5
PED6
PED7
PED8
Object:
P135
P136
P137
P138
STEUERBYTE
1
STATUSWORT
2
CPX_ZSW
2
S3
2
S4
2
S5
2
INPUT_WORD
2
OUTPUT_WORD
2
LAGE_IST
4
OBJECT_RSP
6
Ensure that there is no double assignment in the PED channel.
Double assignment occur when e.g. LAGE_IST is on PED1 - PED4 and a further assignment of PED3 (5) is undertaken
via P137.
The proper action in this case would be: POSITION_ACTUAL to PED1 - PED4 using P135 = 6317056 and P136 = P137
= 0!
4 Index * 256 + Sub-index
2.12 Process data control
2.12.2
PED_Steuerung
71
The COMPAX parameters P135, P136, P137 and P138 initiate the object PI_SELECT and thereby the PED channel after the
COMPAX is turned on.
These parameters can be read and written to using the PED_INI object.
PE_SELECT allows the channels to be freely assigned. You will find depictions of the various possibilities of parameters
P135 - P138.
Notes
Note the following when configuring the PED:
• Note the length (number of bytes) of an object. An object can be represented on the PED's only if the corresponding number
of PED bytes is available, i.e. are not occupied by any other objects.
• An object can be removed (deleted) again from the PED channel either by using the null object (Index and Sub-index = 0) or
by setting the corresponding COMPAX parameter to "0".
Example for configuring the PED's
Represent the object INPUT_WORD, S3 and S4 on the PEDs.
PED1 (3)5
PED2 (4)
PED3 (5)
PED4 (6)
PED5 (7)
PED6 (8)
INPUT_WORD
S3
S4
DB1 (MSB)
DB2 (LSB)
DB1 (MSB)
DB2 (LSB)
DB1 (MSB)
DB2 (LSB)
Configure PE_SELECT as follows:
Using the object "PE_SELECT", the PAD assignment can be changed during operation:
Sub-index
Meaning
value
dec
hex
1
PED length (not variable)
6
0x06
2
Object index assigned for PED1 (3)
24568
0x5ff8
3
Object sub-index assigned for PED1 (3)
0
0x00
4
Object index assigned for PED2 (4)
0
0x0000
5
Object sub-index assigned for PED2 (4)
0
0x00
6
Object index assigned for PED3 (5)
24570
0x5ffa
7
Object sub-index assigned for PED3 (5)
0
0x00
8
Object index assigned for PED4 (6)
0
0x0000
9
Object sub-index assigned for PED4 (6)
0
0x00
10
Object index assigned for PED5 (7)
24572
0x5ffc
11
Object sub-index assigned for PED5 (7)
0
0x00
12
Object index assigned for PED6 (8)
0
0x0000
13
Object sub-index assigned for PED6 (8)
0
0x00
To ensure that this setting of the PED channel is present upon Power On, the corresponding COMPAX parameters (P135 ...
P138) or PED_INI must be assigned as follows:
Sub-index
Meaning
value
(Parameter)
dec
hex
1 (P135)
Object index and sub-index assigned for PED1 (3)
6289408
0x5ff800
2 (P136)
Object index and sub-index assigned for PED2 (4)
0
0x000000
3 (P137)
Object index and sub-index assigned for PED3 (5)
6289920
0x5ffa00
4 (P138)
Object index and sub-index assigned for PED5 (7)
6290432
0x5ffc00
5 The PED numbers in brackets are valid for a PD length of 8 bytes (P196 Bit 0...2 = "4").
2. Object index
Interbus-S
72
2.12.6
PE_SELECT
Process Input Data - Description.
This parameter contains the data that define which process input data are emulated on which communication objects.
Communication objects which can be emulated on PED data are designated in the respective object descriptions.
Object Description
Index
0x6000
Symbol
PE_SELECT
Access groups
0
Object code
Record
Password
0
Data type
PDB structure
Access rights
Read/write all
PD Map
not possible
Data Description
Sub-index
Assignment
Data type
Length
1
Length of the process data channel
Unsigned 8
1
2
Device parameter index, which assigns 1
st (3
rd )6 PE data byte
Unsigned16
2
3
Device parameter sub-index, which assigns 1
st (3
rd ) PE data byte
Unsigned 8
1
4
Device parameter index, which assigns 2
nd (4
th ) PE data byte
Unsigned16
2
5
Device parameter sub-index, which assigns 2
nd (4
th ) PE data byte
Unsigned 8
1
6
Device parameter index, which assigns 3
rd (5
th ) PE data byte
Unsigned16
2
7
Device parameter sub-index, which assigns 3
rd (5
th ) PE data byte
Unsigned 8
1
8
Device parameter index, which assigns 4
th (6
th ) PE data byte
Unsigned16
2
9
Device parameter sub-index, which assigns 4
th (6
th ) PE data byte
Unsigned 8
1
10
Device parameter index, which assigns 5
th (7
th ) PE data byte
Unsigned16
2
11
Device parameter sub-index, which assigns 5
th (7
th ) PE data byte
Unsigned 8
1
12
Device parameter index, which assigns 6
th (8
th ) PE data byte
Unsigned16
2
13
Device parameter sub-index, which assigns 6
th (8
th ) PE data byte
Unsigned 8
1
Example
The object "LAGE_IST" must be emulated on the PE data.
PD-Length ≤≤≤≤ 6: The 1
st data byte from "LAGE_IST" assigns the 3
rd byte of the PE data; the 4
th ,5
th , 6
th data byte the others.
PD-Length = 8: The 1
st data byte from "LAGE_IST" assigns the 5
th byte of the PE data; the 6
th ,7
th , 8
th data byte the others.
Service
Write request
Index
0x6000
1. data byte
0x60
Command Code
0x8082
Sub-index
0x06
2. data byte
0x64
Param. counter
5
Length
2
6 The PD numbers in brackets are valid for a PD length of 8 bytes (P196 Bit 0...2 = "4").
2.12 Process data control
2.12.7
PA_SELECT
73
2.12.7
PA_SELECT
Process Output Data - Description.
This parameter contains the data that define which process output data are emulated on which communication objects.
Communication objects which can be emulated on PA data are designated in the respective object descriptions.
Object Description
Index
0x6001
Symbol
PA_SELECT
Access groups
0
Object code
Record
Password
0
Data type
PDB structure
Access rights
read/write all
PD Map
not possible
Data Description
Sub-index
Assignment
Data type
Length
1
Length of the process data channel
Unsigned 8
1
2
Device parameter index, which assigns 1
st (3
rd )7 PA data byte
Unsigned16
2
3
Device parameter sub-index, which assigns 1
st (3
rd ) PA data byte
Unsigned 8
1
4
Device parameter index, which assigns 2
nd (4
th ) PA data byte
Unsigned16
2
5
Device parameter sub-index, which assigns 2
nd (4
th ) PA data byte
Unsigned 8
1
6
Device parameter index, which assigns 3
rd (5
th ) PA data byte
Unsigned16
2
7
Device parameter sub-index, which assigns 3
rd (5
th ) PA data byte
Unsigned 8
1
8
Device parameter index, which assigns 4
th (6
th ) PA data byte
Unsigned16
2
9
Device parameter sub-index, which assigns 4
th (6
th ) PA data byte
Unsigned 8
1
10
Device parameter index, which assigns 5
th (7
th ) PA data byte
Unsigned16
2
11
Device parameter sub-index, which assigns 5
th (7
th ) PA data byte
Unsigned 8
1
12
Device parameter index, which assigns 6
th (8
th ) PA data byte
Unsigned16
2
13
Device parameter sub-index, which assigns 6
th (8
th ) PA data byte
Unsigned 8
1
Example
The object "LAGE_ZIEL" must be emulated on the PA data.
PD-Length ≤≤≤≤ 6: The 1
st data byte from "LAGE_ZIEL" assigns the 2
nd byte of the PA data; the 3
rd ,4
th , 5
th data byte the others.
PD-Length = 6: The 1
st data byte from "LAGE_ZIEL" assigns the 4
th byte of the PA data; the 5
th ,6
th , 7
th data byte the others.
Service
Write request
Index
0x6001
1. data byte
0x60
Command Code
0x8082
Sub-index
0x04
2. data byte
0x7a
Param. counter
5
Length
2
7 The PD numbers in brackets are valid for a PD length of 8 byte (P196 Bit 0...2 = "4").
2. Object index
Interbus-S
74
2.12.8
PA_ENABLE
Enable process output data.
Each bit of this parameter is associated with a byte of the process output data channel.
Meaning:
Bit = 0
the corresponding process data value is disabled
Bit = 1
the corresponding process data value is enabled
If an object takes up several bytes on the PA data channel, the logic state of the bit which is associated with the first byte of this
object is the one used, and the other associated bits are not relevant.
Object Description
Index
0x6002
Symbol
PA_ENABLE
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Octet string
Access rights
Read/write all
PD Map
Not possible
Data Description
Bit
Assignment
Bit
Assignment
7
="1":
autom. Acceptance of a
modified LAGE_ZIEL of the PA
data is disabled
3
4
th (6
th ) byte of the PA data
6
None
2
3
rd (5
th ) byte of the PA data
5
6
th (8
th )8 byte of the PA data
1
2
nd (4
th ) byte of the PA data
4
5
th (7
th ) byte of the PA data
0
1 (3
rd ). byte of the PA data
Bit
Function
Data byte
Function
= 0 (FALSE)
Process data value disabled
= 1 (TRUE)
Process data value enabled
Example
The process data value which assigns the 3
rd (5
th ) byte of the PA data (and other if applicable) should be enabled.
The other process data values are disabled.
Service
Write request
Index
0x6002
Data byte
0x04
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
8 The PD numbers in brackets are valid for a PD length of 8 bytes (P196 Bit 0...2 = "4").
2.12 Process data control
2.12.9
PED_INI
75
2.12.9
PED_INI
Initialising the process input data description.
This object contains the data that define which process input data are emulated on which communication objects after COMPAX
is switched on.
Communication objects which can be emulated on PED data are designated in the respective object descriptions.
Object Description
Index
0x5fd0
Symbol
PED_INI
Length
3
Access groups
0
Object code
Array
Elements
4
Password
0
Data type
Octet String
Access rights
read/write all
PD Map
not possible
Data Description
Sub-index
PE assignment
Data byte 1
Data byte 2
Data byte 3
1
Stipulate object which will assign
the 1
st (3
rd )9 PE data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
2
Stipulate object which will assign
2
nd (4
th ) PE data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
3
Stipulate object which will assign
3
rd (5
th ) PE data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
4
Stipulate object which will assign
5
th (7
th ) PE data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
Example
The object "INPUT-WORD" must be emulated on the PE data after 'Power On'.
The 1
st data byte from "INPUT-WORD" assigns the 5
th (7
th ) byte of the PE data; the 2
nd data byte the others.
Service
Write request
Index
0x5fd0
1. data byte
0x5f
Command Code
0x8082
Sub-index
0x04
2. data byte
0xf8
Param. counter
5
Length
3
3. data byte
0
9 Die PD - Nummern in der Klammer gelten bei einer PD-Length von 8 Byte (P196 Bit 0...2 = "4").
2. Object index
Interbus-S
76
2.12.10
PAD_INI
Initialising the Process Output Data - Description.
This object contains the data that define which process output data are emulated on which communication objects after
COMPAX is switched on.
Communication objects which can be emulated on PA data are designated in the respective object descriptions.
Object Description
Index
0x5fd1
Symbol
PAD_INI
Length
3
Access groups
0
Object code
Array
Elements
4
Password
0
Data type
Octet String
Access rights
read/write all
PD Map
not possible
Data Description
Sub-index
PA assignment
Data byte 1
Data byte 2
Data byte 3
1
Stipulate object which will assign
1
st (3
rd )10 PA data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
2
Stipulate object which will assign
2
nd (4
th ) PA data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
3
Stipulate object which will assign
3
rd (5
th ) PA data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
4
Stipulate object which will assign
5
th (7
th ) PA data byte.
Object Index (High Byte)
Object Index (Low Byte)
Object Sub-index
Example
The object "OUTPUT-WORD" must be emulated on the PE data after 'Power On'.
The 1
st data byte from "OUTPUT_WORD" assigns the 3
rd (5
th ) byte of the PA data; the 2
nd data byte the others.
Service
Write request
Index
0x5fd1
1. data byte
0x5f
Command Code
0x8082
Sub-index
0x03
2. data byte
0xf7
Param. counter
5
Length
3
3. data byte
0
10 Die PD - Nummern in der Klammer gelten bei einer PD-Length von 8 Byte (P196 Bit 0...2 = "4").
2.12 Process data control
2.12.3
IN_SELECT
77
2.12.3
IN_SELECT
Process Input Data - Description.
This object defines, which communication object or communication object element will be depicted on the 1
st (3
rd )11 byte (and if
applicable, the subsequent bytes) process input data of the process data channel..
Object Description
Index
0x5ffd
Symbol
IN_SELECT
Access groups
0
Object code
Record
Password
0
Data type
15
Access rights
read/write all
PD Map
not possible
Data Description
Sub-index
Assignment
Data type
Length
1
Device parameter index, which assigns 1
st (3
rd ) PE data byte
Unsigned16
2
2
Device parameter sub-index, which assigns 1
st (3
rd ) PE data byte
Unsigned 8
1
Example
The object "INPUT-WORD" must be emulated on the PE data.
The 1
st data byte from "INPUT-WORD" assigns the 1
st (3
rd ) byte of the PE data; the 2
nd data byte the others.
Service
Write request
Index
0x5ffd
1. data byte
0x5f
Command Code
0x8082
Sub-index
0x00
2. data byte
0xf8
Param. counter
5
Length
3
3. data byte
0
2.12.4
OUT_SELECT
Process Output Data - Description.
This object defines which communication object or element of a communications object is emulated on the
1. byte (and if necessary on the following bytes) of the process output data of the process data channel.
Object Description
Index
0x5ffe
Symbol
OUT_SELECT
Access groups
0
Object code
Record
Password
0
Data type
15
Access rights
read/write all
PD Map
not possible
Data Description
Sub-index
Assignment
Data type
Length
1
Device parameter index, which assigns 1
st (3
rd ) PA data byte
Unsigned16
2
2
Device parameter sub-index, which assigns 1
st (3
rd ) PA data byte
Unsigned 8
1
Example
The object "OUTPUT-WORD" must be emulated on the PA data.
The 1
st data byte from "OUTPUT-WORD" assigns the 1
st (3
rd ) byte of the PA data; the 2
nd data byte the others.
Service
Write request
Index
0x5ffe
1. data byte
0x5f
Command Code
0x8082
Sub-index
0x00
2. data byte
0xf7
Param. counter
5
Length
3
3. data byte
0
11 Die PD - Nummern in der Klammer gelten bei einer PD-Length von 8 Byte (P196 Bit 0...2 = "4").
Enable process output data.
This parameter is allocated to the 1
st (3
rd )12 byte of the process output data channel.
Meaning:
"OUT_ENABLE" = FALSE
the corresponding process data value is disabled
"OUT_ENABLE" = TRUE
the corresponding process data value is enabled
Object Description
Index
0x5fff
Symbol
OUT_ENABLE
Length
1
Access groups
0
Object code
Simple var.
Password
0
Data type
Boolean
Access rights
read/write all
PD Map
not possible
Data Description
Data byte
Function
Data byte
Function
= 0x00 (FALSE)
Process data value disabled
= 0xff (TRUE)
Process data value enabled
Example
The process data value which assigns 1
st (3
rd ) byte of the PA data (and if necessary the others) should be enabled.
Service
Write request
Index
0x5fff
Data byte
0xff
Command Code
0x8082
Sub-index
0
Param. counter
4
Length
1
12 Die PD - Nummern in der Klammer gelten bei einer PD-Length von 8 Byte (P196 Bit 0...2 = "4").
3 . DRI VECOM-PROFILE 22, from
COMPAX Softw are-Version 3. 01
From program version V3.01onwards, the operating type 'DRIVECOM-PROFIL' is available in all COMPAX variants. It can be
activated via P190=22. Please note that P190 must be at this value by 'Power-On', in order that the turn on procedure defined in
the DRIVECOM profile can run completely (this varies from the normal COMPAX behaviour after ‘Power-on’).
According to DRIVECOM specifications there are a series of statuses that are accepted by the device in sequence. The
corresponding status equipment is integrated in the COMPAX. The conditions are outlined in diagrams and tables in the
documentation 'DRIVECOM-PROFILE technology’. The following description of device statuses is therefore only given as a
supplement to the DRIVECOM documentation:
Conditions diagram
START
NOT READY TO SWITCH ON
xx00h
statusword
SWITCH ON DISABLED
READY TO SWITCH ON
SWITCHED ON
OPERATION ENABLE
FAULT REACTION ACTIVE
FAULT
statusword
statusword
statusword
statusword
statusword
statusword
xx60h*
xx21h
xx23h
xx27h
QUICK STOP ACTIVE
xx07h
xx28h
controlword
xx1x x1xx
controlword
lock voltage
xxxx xx0x
quick stop
xxxx x01x
controlword
lock voltage
xxxx xx0x
controlword
lock voltage
xxxx xx0x
quick stop
xxxx x01x
controlword
shutdown
xxxx x110
controlword
shutdown
xxxx x110
controlword
switch on
xxxx x111
controlword
shutdown
xxxx x110
controlword
operation enable
xxxx 1111
controlword
operation disable
xxxx 0111
controlword
quick stop
xxxx x01x
controlword
reset fault
0xxx xxxx
1xxx xxxx
controlword
lock voltage
xxxx xx0x
The COMPAX command OUTPUT A0=... may not be used for active operating type 'DRIVECOM-PROFIL' .
3. DRIVECOM-PROFILE 22, from COMPAX Software-Version 3.01
Interbus-S
80
Status
Description
NICHT-EINSCHALTBEREIT:
! Self-test is running
! Initialisation is running
! Drive function is disabled
! All functions are disabled
EINSCHALTSPERRE:
! Software/hardware initialisation is terminated
! Communication via all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive function is disabled (motor dead)
! Display shows 'OFF'
EINSCHALTBEREIT:
! Communication through all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive function is disabled (motor dead)
! Display shows 'OFF'
EINGESCHALTET:
! Communication through all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive function is disabled (but motor has current)
! Display shows 'run'
BETRIEB-FREIGEGEBEN:
! Communication through all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive function is enabled (motor has current)
! Display shows 'run'
SCHNELLHALT-AKTIV:
! Communication through all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive implements the STOP function (motor has current)
! Display shows 'run'
STÖRUNG:
! Communication through all interfaces is enabled
! Modifications to parameters, variables, records is possible
! Drive function is disabled
! Display shows 'Exx'
STÖRUNGSREAKTION:
! Error handling only, no static device status
4. COMPAX Parameters for the Interbus-S
No.
Meaning
Minimum
value
Default
value
Maximum
value
When
valid
P190
Set operating type "DRIVECOM profile
22"
="0":
DRIVECOM profile defined turn on procedure inactive
="22": DRIVECOM profile defined turn on procedure active
Power on
P191
Bus time-out
="0":
no response, except error message E73, during a time-out
="1":
stop with E73 and shut down during activation of holding brake
VP
P193
Pop-up messages
="1":
autom. Error message
="2":
autom. "position reached" - message
="4":
autom. comparator switch points report
immediately
P196
Process data length & protocol
Bit 0..2 = 0 PD-Length 1 word, PED/PAD=INPUT/OUTPUT_WORD
Bit 0..2 = 1 PD-Length 1 word
Bit 0..2 = 2 PD-Length 2 words
Bit 0..2 = 3 PD-Length 3 words
Bit 0..2 = 4 PD-Length 4 words; no PCP communication
Bit 4
= 0 Resolution from V1...V40 like P1...P40
Bit 4
= 1 Resolution from V1...V40: 1 ⇔ 0.001
Bit 5
= 0 OBJECT_REQ/RSP can not be assigned to PD temp.
Bit 5
= 1 OBJECT_REQ/RSP can be assigned to PD temp.
Bit 6
= 0 OBJECT_RSP autom. assigns PED3..8 if ObjectReqEnable = 1
Bit 6
= 1 OBJECT_RSP must be assigned to PED3..8 explicitly
Bit 7
= 0 PED/PAD1..2=STATUS/STEUERWORT if PD-Length = 4
Bit 7
= 1 PED/PAD1..2=CPX_ZSW/CPX_STW if PD-Length = 4
Power on
P135
Object index and sub-index which assigns the 1. (3.)13 PE data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P136
Object index and sub-index which assigns the 2. (4.) PE data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P137
Object index and sub-index which assigns the 3. (5.) PE data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P138
Object index and sub-index which assigns the 5. (7.) PE data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P139
Object index and sub-index which assigns the 1. (3.) PA data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P140
Object index and sub-index which assigns the 2. (4.) PA data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P141
Object index and sub-index which assigns the 3. (5.) PA data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P142
Object index and sub-index which assigns the 5. (7.) PA data byte after
turning on. Value: Index •••• 256 + Sub-index
0
0
16777215
Power on
P203
Assigning status S16 and S17 to
CPX_ZSW
Bit 0=0
CPX_ZSW has a standard assignment
Bit 0=1
S16, S17 assigns CPX_ZSW
Bit 1=0
LAGE_IST has a standard assignment
Bit 1=1
S13 assigns LAGE_IST
immediately
P221
Standard functions of the digital inputs accessible from the CONTROLWORD
object. Physical inputs freely available.
Is written by the object INPUT_MASK data byte 2.
0
0
255
immediately
P222
Standard functions of the digital inputs E9...E16 accessible from the
CONTROLWORD object. Physical inputs freely available.
Is written by the object INPUT_MASK data byte 1.
0
0
255
immediately
P223
Outputs A1...A8 are accessible from object OUTPUT_WORD.
Written by the object OUTPUT_MASK data byte 2.
0
0
255
immediately
P224
Outputs A9...A16 are accessible from object OUTPUT_WORD.
Written by the object OUTPUT_MASK data byte 1.
0
0
255
immediately
13 Die PD - Nummern in der Klammer gelten bei einer PD-Length von 8 Byte (P196 Bit 0...2 = "4").
5. COMPAX Interbus-S Error messages
Interbus-S
82
5. COMPAX Interbus-S Error messages
No.
Cause
Remedy / Causes
Acknowl
edge
with
No
power to
drive
E73
Time-out error
The error response is influenced with
P191.
Re-send the characters
1
nein
2
1 No acknowledgement necessary; the error message is cancelled after the next errorless transmission.
2 Depends on P191.
6 . I n d e x
8 byte process data channel..............65
8 Byte Process data channel...............6
Absolute positioning ..........................33
Absolute value sensor .......................36
ACCEL_NEG.....................................49
ACCEL_POS.....................................48
Acceleration.......................................48
AckToggle..............................20, 22, 67
Actual position ...................................35
Arithmetic operator codes..................57
Assignment of PED and PAD ..............6
BETR_ART_AZ .................................17
Boolean ...............................................9
Bus connection....................................4
Bus wiring............................................4
C03......................................................8
CAM_CMD ........................................40
CAM_MEM ........................................63
CAM_MEM_P....................................63
COMMAND........................................24
Command code .................................56
Command code table ........................58
Command codes ...............................56
Command recognition by means
of the control word.............................19
Commands ........................................24
Communication....................................5
Comparator function..........................54
Comparison operator codes ..............57
Compatibility........................................3
COMPAX operating hours .................27
COMPAX Parameters .......................82
COMPAX variable, enter or read.......63
Conditions diagram............................80
Context Management ..........................5
Contour error .....................................39
Contour error window ........................38
Control...............................................17
CONTROL.........................................23
Control commands ............................23
Control voltage ..................................32
CPX_STW .........................................19
CPX_ZSW .........................................20
Cyclic process data .............................6
Data types ...........................................9
Device identification...........................15
Diagnosis...........................................26
DREHZAHLMAX ...............................45
DRIVECOM-PROFILE 22..................80
Error message...................................27
Fault codes........................................26
FKT_GRUPPE...................................15
FreezePAD..................................19, 21
G Device allocation..............................3
GESCHW_IST...................................47
GESCHW_MAX.................................45
GESCHW_REF .................................47
GOTO................................................61
GRENZEN.........................................37
Handshake ........................................34
Identification code................................5
IN_SELECT ...................................... 78
Index-pointer..................................... 10
INPUT_WORD.................................. 52
Inputs/outputs ................................... 52
Integer ................................................ 9
Intermediate circuit voltage............... 32
LAGE_IST......................................... 36
LAGE_ZIEL....................................... 34
Loop counter..................................... 28
MOMENT_IST .................................. 31
MOMENT_MAX................................ 30
Motion cycles of the axis................... 28
N ....................................................... 55
NENNMOMENT................................ 30
NENNSTROM................................... 31
Nx ..................................................... 55
Object index...................................... 10
OBJECT_REQ.................................. 67
OBJECT_RSP .................................. 67
OBJECT_RSP temporarily
disabled on PED............................... 23
OBJECT_RSP temporarily
enabled on PED................................ 23
ObjectReqEnable........................ 19, 21
Operand Codes ................................ 57
OPERATING MODE......................... 17
OUT_ENABLE .................................. 79
OUT_SELECT .................................. 78
OUTPUT........................................... 53
OUTPUT_MASK............................... 53
OUTPUT_WORD.............................. 52
OVERRIDE....................................... 42
P ....................................................... 24
P196 ................................................... 6
P196 Bit 4 ......................................... 64
PA_ENABLE..................................... 75
PA_SELECT..................................... 74
PAD_INI............................................ 77
PAD_Steuerung................................ 68
PADs disable / enable ...................... 69
Parameter data................................... 6
Parameters ....................................... 24
PCP .................................................... 6
PDU Length ........................................ 5
PE_SELECT..................................... 73
PED_INI............................................ 76
PED_Steuerung................................ 71
POLARITAET ................................... 39
Pop-up message processing ............ 22
POS_FENSTER................................ 38
POSA................................................ 33
Position actual value......................... 36
Position limit value min-max ............. 37
Positioning ........................................ 33
Positioning window ........................... 38
POSR................................................ 34
POSR0SPEED ................................. 43
POSROUTPUTN .............................. 54
POSROUTPUTP............................... 54
POSRXSPEEDY............................... 43
Power or intermediate circuit
voltage .............................................. 32
Process data control ......................... 68
Process data length ............................ 6
Programming .................................... 55
PRXSDYALZ..................................... 44
Px...................................................... 25
RAMPE_NEG.................................... 50
RAMPE_NOTS ................................. 50
RAMPE_POS.................................... 49
RAMPE_REF .................................... 51
RAMPENFORM ................................ 48
REALNULL ....................................... 37
REF_MODE ...................................... 39
Reference run selection code ........... 39
Relative positioning........................... 34
S........................................................ 29
S1...................................................... 35
S10.................................................... 27
S11.................................................... 28
S12.................................................... 36
S2...................................................... 36
S23_S26 ........................................... 28
S3...................................................... 39
S30.................................................... 27
S31_S39 ........................................... 16
S4...................................................... 46
S5...................................................... 31
S6...................................................... 27
S7_S8 ............................................... 32
S9...................................................... 28
SCHLEPP_FEN ................................ 38
Selectable Data Channels................... 6
Setting the bus .................................... 8
Setting the PAD ................................ 69
Setting the PED ................................ 71
SPEED.............................................. 42
Speed step profile............................. 43
SSK13................................................. 4
START_N.......................................... 61
START_N_GO .................................. 62
STATUSBYTE................................... 18
STATUSWORT................................. 21
STEUERBYTE .................................. 18
STEUERWORT................................. 21
STOERUNG...................................... 26
Target position .................................. 36
TEACH_N ......................................... 62
Temperature of the power output
stage ................................................. 27
temporary assignment of PD............... 7
Torque............................................... 31
Traverse speed................................. 46
Unsigned............................................. 9
Variables-Access ................................ 5
VERF_GESCHW .............................. 46
VFD-Support....................................... 5
VX ..................................................... 63
WAITPOSA....................................... 40
WAITPOSR....................................... 41
ZWK_SPG ........................................ 32