MV Heating MV Airo 4 Instruction Manual
Read Online
Read the MV Heating MV Airo 4 Instruction Manual online using the built-in PDF viewer.
Text of the manual
+44 (0)23 8052 2345
1
MV Heating UK Ltd
MV Airo 4
MV Airo 4
Diesel Powered
Air Heater
Instruction Manual
Ed. 2.01
MV Heating UK Ltd
Unit 6
Second Avenue Business Park
Millbrook
Southampton
SO15 0LP
+44 (0)23 8052 2345
2
MV Heating UK Ltd
Preface
Thank you for purchasing the MV Airo 4 diesel heater (hereinafter referred to
as ‘the heater’). This manual will attempt to describe the structure, working
principle, installation and operation of the heater. For future reference please
keep this manual in a safe and convenient place.
Note
•
This instruction booklet is subject to revision without notice but the
instruction book is in conformity to the purchased product.
•
The manual will attempt to answer any and all questions the user
may have. If you have and further questions or find anything
incorrect within this manual, please contact us directly.
•
Please check that the heater is not damaged when first unpacking it
and contact the dealer immediately if any problems are found.
•
If any problems or faults arise during installation or operation, please
contact us directly or any other customer service station authorised
by our company. We shall do our best to offer you our full support.
+44 (0)23 8052 2345
3
MV Heating UK Ltd
Contents
Uses and Applications ................................................................................................................... 5
Safety Information ................................................................................................................... 6
Technical Data .............................................................................................................................. 7
Kit Contents ............................................................................................................................. 8
MV Airo 4 Dimensions ............................................................................................................. 9
Installation: ................................................................................................................................. 10
Installation Positions .............................................................................................................. 10
Installation Angle ................................................................................................................... 12
Wiring Harness Connector Positions ................................................................................. 13
Installation: Mounting ........................................................................................................... 14
Installation: Ducting and Pipework ........................................................................................ 16
Exhaust System ................................................................................................................. 17
Combustion Air Intake ...................................................................................................... 18
Installation: Fuel Lines ........................................................................................................... 19
Fuel Line Connectors ......................................................................................................... 20
Fuel Line Length and Order ............................................................................................... 21
Fuel Pump Angle for Installation ....................................................................................... 22
Fuel Tank Head ................................................................................................................. 23
Fuel Standpipe .................................................................................................................. 24
Electrics: ..................................................................................................................................... 26
Components .......................................................................................................................... 26
Wiring Diagram ...................................................................................................................... 27
Control Connections .............................................................................................................. 28
Operation: .................................................................................................................................. 30
Rheostat Control .................................................................................................................... 30
+44 (0)23 8052 2345
4
MV Heating UK Ltd
Mini Timer ............................................................................................................................. 30
Manual Start Up and Shut Down ...................................................................................... 32
Pre-setting Heating Time .................................................................................................. 32
Pre-setting Starting and Heating Times ............................................................................ 32
Checking Temperature ...................................................................................................... 33
Converting to Thermostatic Mode .................................................................................... 33
Fault Information .............................................................................................................. 33
Remote Operation ............................................................................................................ 34
Installation Fuel Priming Feature ...................................................................................... 34
LCD Digital 7-Day Timer ......................................................................................................... 35
Changing Language ........................................................................................................... 36
Changing the Date and Time ............................................................................................. 37
Manual On/Off .................................................................................................................. 38
Switching to Thermostatic Mode ...................................................................................... 39
Fan Mode .......................................................................................................................... 39
Pre-setting Heating Times ................................................................................................. 40
Installation Fuel Priming Feature ...................................................................................... 42
Checking Error Codes ........................................................................................................ 43
Resetting Digital Controller to Factory Settings ................................................................ 44
Maintenance............................................................................................................................... 45
Fault Codes: ................................................................................................................................ 46
Rheostat Control .................................................................................................................... 46
Timers .................................................................................................................................... 47
+44 (0)23 8052 2345
5
MV Heating UK Ltd
Uses and Applications
The heater works independently from the vehicle’s engine, but is best fitted
using the vehicle’s battery and fuel tank. An auxiliary battery and/or fuel tank
can be used if necessary.
The heater will operate under normal conditions in most vehicles from
industrial and machinery sectors to leisure craft like yachts and motor homes.
The heater is best uses for heating various cabins and compartments, engine
preheating and glass defrosting.
It is not recommended for constant long-term operation for residential
rooms, garages, holiday homes etc.
Note:
The most common faults that occur are generally down to poor fuel
conditions due to dirty (or empty) fuel tanks or drops in voltage; particularly
in older vehicles like live aboard narrowboats or used, commercial vehicles.
+44 (0)23 8052 2345
6
MV Heating UK Ltd
Safety Information
Follow the installation guidelines carefully to ensure the heater has the
appropriate amount of clearance between surfaces, so as not to become a
fire hazard and that the various parts of the heater that get hot, like the
exhaust, are not exposed or contaminated by possible fuel and oil.
Sufficient ventilation is required allowing proper air-flow to the heater. If the
heater is to be installed in a box or compartment, please ensure an air vent is
installed for this reason. The air must also be fresh and not contaminated by
exhaust fumes or other polluted sources. Make sure that the air intakes and
exhaust do not get blocked by other objects.
Take care to ensure that the exhaust outlet is installed in a way that prevents
fumes entering the vehicle or in the direction of the fresh air intake and
ensure the use of heat shields where necessary to again avoid fire damage.
If work is to be carried out on or around the heater, turn it off at least an hour
before so, so that it is sufficiently cool enough to be handled. If necessary,
wear safety gloves.
The fuel line must not be routed through the passenger compartment or the
driver’s cab in any vehicle. Ensure that they are also installed so that the exits
are not at risk or in danger of becoming a possible fire hazard.
Finally, take care and follow any and all precautions when installing the
heater to minimize injuries to yourself and damage to the heater.
+44 (0)23 8052 2345
7
MV Heating UK Ltd
Technical Data
Heat Power (W)
4000
Fuel
Diesel
Output (W)
900 - 4000
Fuel Consumption (l/h)
0.11 - 0.51
Run Time Power Consumption (w)
8 - 40
Working Temperature
-40°C - 20°C
Weight (kg)
4.5
Variable Output
Current Draw
Position
(Amps)
PO1
0.4
PO2
0.6
PO3
0.8
PO4
1.3
PO5
1.4
PO6
1.9
PO7
2.4
+44 (0)23 8052 2345
8
MV Heating UK Ltd
Kit Contents
The kit includes everything necessary for installation.
Figure I
+44 (0)23 8052 2345
9
MV Heating UK Ltd
1. Main heater unit
2. Main wiring harness
3. Control switch/timer
4. Fuel pump
5. Fuel standpipe
6. Fuel pipe
7. Fuel line connector hose clip
8. Fuel line connector
9. Fuel pump clamp
10. Anti-vibration mount
11. Combustion air pipe
12. Exhaust pipe
13. Combustion air pipe clamp
14. Exhaust pipe clamp
15. Combustion air pipe fixing clamp
16. Exhaust pipe fixing clamp
17. Grill
18. Outlet Cover
19. Temperature probe (optional)
20. Hose clip (optional)
21. Hot air ducting (optional)
22. Out vents (optional)
MV Airo 4 Dimensions
A: Minimum installation clearance for opening the lid and dismantling glow
pin and E.C.U.
B: Minimum installation clearance for the air intake
376
A
B
30
75
90
130
133
25
24
55
7
140
105
44
17
80
150
325
140
105
44
17
80
150
325
DIMENSIONS: mm
376
A
B
30
75
90
130
133
25
24
55
7
140
105
44
17
80
150
325
DIMENSIONS: mm
+44 (0)23 8052 2345
10
MV Heating UK Ltd
Installation:
Installation Positions
Motorhome
Figure II
1. In front of the passenger seat
2. Between the passenger and driver’s seat
3. Under the vehicle floor
4. Under the rear seat
5. Inside the boot
Minivan
Figure III
1. In front of the passenger seat
2. Between the passenger and driver’s seat
3. Under the vehicle floor
4. Under the rear seat
5. Inside the boot
+44 (0)23 8052 2345
11
MV Heating UK Ltd
Crane
Figure IV
1. In seat box
2. On the rear wall
3. In a protective
case
Lorry
Figure V
1. In passenger footwell
2. On the cabin rear wall
3. Under the bed
4. In the tool box
+44 (0)23 8052 2345
12
MV Heating UK Ltd
Installation Angle
All positions suggested are examples. Other locations are possible so long as
they correspond to the proper installation guidelines and requirements.
1. Heater air intake
2. Glow pin position
3. Direction of air flow
Figure VI
Figure VI shows the ideal installation position of the heater; with exhaust
pointing downward. Depending on its location it can be tilted by 30° with the
air flow and hot air outlet facing the bottom. It can also be tilted on its
longitudinal axis by 90° so long as the glow pin position points upward. During
usual operation the heater can deviate by 15° each way with vehicle
movement without impaired function of the heater.
1
30°
3
90°
2
1
+44 (0)23 8052 2345
13
MV Heating UK Ltd
Wiring Harness Connector Positions
The main connector coming off the heater can be moved to the other side of
the heater if necessary. In order to do you must first remove the air inlet grill
by twisting it so it’s clear of its securing lip and then simply pull it off. Next,
remove the top cover by lifting up the two front flaps near the air inlet. You
can then lift out the entire innards of the heater (heat exchanger to fan motor
and all) removing the cable from the rubber securing bush and rerouting it
underneath the fan motor where it can then sit in the cut-out on the opposite
side. Ensure the rubber bush is properly inserted and the heat exchanger is
back securely in position, then simply replace the lid and grill back in position.
Note: Ensure the
bottom cover fits
correctly inside the
groove of the lid.
Figure VII
+44 (0)23 8052 2345
14
MV Heating UK Ltd
Installation: Mounting
The chosen mounting surface should be flat and you will need to drill the
appropriate size hole for the exhaust, combustion air inlet, fuel inlet and
mounting bolts. It is a good idea to mount the heater on the supplied
mounting bracket, particularly if the original mounting surface is thinner than
1.5mm.
A. Mounting Gasket
B. Mounting Plate
Figure VII
Note: The mounting plate shown in figure VII may differ in overall size and
the circular flange may not be present, however the heater footprint will
remain the same.
148
7.5
170
85
125
2
5
25
35.5
7.5
26
12
44
18
55
DIMENSIONS: MM
A
B
+44 (0)23 8052 2345
15
MV Heating UK Ltd
Installation: Mounting (Cont’d)
(Above)
(Above)
Securing the heater to the floor
Securing the heater to the wall
Figure VIII
1. Check that the fan wheel spins freely and
2. Ensure that the mounting surface is
that there is sufficient clearance between the
flat and smooth
heater and the vehicle floor
3. The mounting gasket supplied must be fitted 4. The vehicle wall must be flat and
smooth
5. Mounting bracket
6. M6 Washer
7. M6 Nut
Figure VIII shows the mounting positions on a vehicle’s floor and wall.
1
4
6
5
3
2
1
4
3
6
5
2
1
+44 (0)23 8052 2345
16
MV Heating UK Ltd
Installation: Ducting and Pipework
Figure IX
1. Ducting AND/OR Grill
2. Air inlet on heater body
3. Hot air outlet on heater body
4. 80/90mm hose clip
5. 90mm APK ducting
6. Directional outlet vent
Figure X
A. Heater’s hot air outlet
B. 90-80mm reducer (optional)
C. 80/90mm hose clip
D. 80mm APK ducting
E. 90mm ‘Y’ branch
F. 80mm directional outlet vent
G. 80mm Open/close vent
A
B
C
D
C
E
C
C
D
C
F
D
C
G
1
2
3
4
4
5
6
4
+44 (0)23 8052 2345
17
MV Heating UK Ltd
Installation: Ducting (Cont’d)
Ducting Can be installed as shown on the previous page. Extra outlets can be
installed to fit your own needs however you should ideally not fit more than
the maximum of 4 outlets, to ensure you are receiving sufficient hot air
output.
Exhaust System
Note: Do not work on the exhaust system unless the heater has been
switched off for over an hour and wear safety gloves if necessary. All types of
combustion produce high temperatures and toxic fumes and must be
installed in accordance to these instructions.
The flexible exhaust pipe can be shortened to no less than 20cm and should
not exceed a length of 2m, depending on the installation parameters. Route
the exhaust pipe from the heater to a suitable outlet, ensuring that is securely
fitted to the heater using the clamp supplied in the kit.
As the exhaust gets very hot during operation, it should be installed in such a
way that will not cause damage to the vehicle. So ensure that it has sufficient
clearance of heat sensitive parts; paying close attention to fuel lines (plastic
and copper) and electrical components. Make sure that the outlet ends in
open air and does not point in the direction of travel. The whole system
should also point downwards and if necessary, a 5mm hole should be drilled
near the bottom to drain off any condensation. You should also route the
exhaust so that the fumes are not taken back in by the air intakes of the
heater and ensure that the outlet does not get blocked by anything like road
debris etc.
+44 (0)23 8052 2345
18
MV Heating UK Ltd
Figure XI
1. Heater Body
2. 25mm Combustion Air Inlet
3. Combustion air inlet clamp
4. Combustion air pipe
5. Combustion air silencer OR end cap
6. 24mm Exhaust outlet
7. Exhaust clamp*
8. 24mm Exhaust pipe
9. Exhaust silencer
10. Exhaust end cap
Combustion Air Intake
Like the exhaust pipe the combustion air intake can be shortened to up to
20cm or lengthened to no more than 2m, again depending on installation
conditions. Some models can also be fitted with a combustion air silencer to
reduce the noise of the air intake; this is ultimately down to personal
preference.
In some situations, an air filter may be required (not included) to stop dust or
debris making its way up the air pipe.
*Not required on an application when the silencer is inbuilt, as part of the whole
exhaust system
1
2
3
4
5
6
7
8
10
7
7
8
9
+44 (0)23 8052 2345
19
MV Heating UK Ltd
Installation: Fuel Lines
Note: When installing, priming, repairing fuel lines etc. there is always a risk
of injuries due to flammable and toxic sources. Take all the necessary safety
precautions when fitting any fuel line or fuel line parts.
DO NOT:
•
Smoke
•
Use naked flames
•
Inhale fumes
When working on or near any fuel lines or parts!
DO:
•
Ensure the engine and heater are switched off before attempting any
and all work on the fuel line installation or repair
•
Cut any fuel line with a sharp knife to ensure a clean cut free from
crushes and burrs
•
Make sure the pipe from the fuel pump to the heater is on a gradual
rise
•
Ensure fuel pipes are fastened safely to prevent noise rattle and
securely fitted to prevent any damage
•
Route the fuel pipes so that vehicle vibration and movement will not
have any lasting effects on the service life
•
Route the fuel line away from any and all heat sources. Ensure
adequate clearing from heat sources if it cannot be avoided or use a
suitable heat shield
•
Make sure all connectors are fastened securely to prevent dripping of
fuel, particularly onto hot surfaces or electrical components.
+44 (0)23 8052 2345
20
MV Heating UK Ltd
Fuel Line Connectors
When connecting fuel pipes into rubber connectors always mount them flush
and not on a bend to prevent air bubbles from forming in the fuel line as
shown in Figure XII.
Figure XII
A fuel filter must be fitted for all diesel heaters. Make sure that it is installed
the correct way according to fuel flow as shown in figure XIII.
Note: Fuel filter, pipes and clamps should be replaced after 2 years.
1. Direction of fuel flow
2. Fuel Filter
Figure XIII
0-90°
1
2
1
2
+44 (0)23 8052 2345
21
MV Heating UK Ltd
Fuel Line Length and Order
Figure XIV
1. Fuel tank
2. Fuel Standpipe
3. Fuel connector hose clip
4. Fuel Line
5. Rubber fuel line connector
6. Fuel Filter
7. Fuel pump with anti-vibration mount 8. Damper (optional)
9. Heater body
Figure XIV shows how to install parts of the fuel line in the correct order.
2
3
4
5
6
7
8
9
1
2000-6800mm
500-1200mm
+44 (0)23 8052 2345
22
MV Heating UK Ltd
Fuel Pump Angle for Installation
Note: Fuel line is best installed straight/upward toward heater at fuel pump
end. A damper is only necessary in kits that include one (larger kilowatt
heaters).
Always mount the fuel pump with the pressure side rising upward. The
preferred position is shown in figure XV and should be between 15° and 35°.
Figure XV
A. Between 0° and 15° - Not acceptable
B. Acceptable installation position: Between 15° and 35°
C. Between 35° and 90° - Not acceptable
90°
0°
B
A
C
+44 (0)23 8052 2345
23
MV Heating UK Ltd
Fuel Tank Head
A
B
C
1
2
3
1. Connection to heater body
2. Maximum fuel level
3. Minimum fuel level
Suction height for fuel pump:
A. 3000mm
B. 1000mm (diesel) 500mm (petrol)
C. 2000mm
Figure XVI
+44 (0)23 8052 2345
24
MV Heating UK Ltd
Fuel Standpipe
A fuel standpipe (or suction pipe) will need to be installed in the vehicle’s fuel
tank or an independent fuel tank depending on what the installation calls for.
Sealant is not required to fit the standpipes.
Depending on the standpipe provide in the kit you will need to install the
standpipe in one of two ways.
Standpipe 1: (Part No: AHZ-034)
Figure XVII
Usually supplied in Marine kits and supplied bent, this standpipe is installed
like so:
•
Drill a hole in the top of the vehicle’s fuel tank Φ22 ± 0.2mm in size.
Ensure it is smooth and clean of burrs
•
Remove the top nut and washers and bend the standpipe straight
•
Cut the standpipe down to size if necessary
•
Fit the standpipe by tilting it into position into the newly drilled hole
•
Place the rubber and metal washers back on top followed by the nut
and tighten it securely on top
+44 (0)23 8052 2345
25
MV Heating UK Ltd
Stand pipe 2: (Part No: AHZ-035)
Figure XVIII
Supplied mainly in vehicle kits, this standpipe is installed like so:
•
If possible; remove the sender unit from the vehicle’s fuel tank, this
will make it easier to attach the nut securely back onto the standpipe
•
Drill a Φ6 ± 0.2mm hole into the sender unit
•
Remove the nut from the standpipe and feed it through the hole
ensuring the rubber ‘o’ ring remains on the standpipe ‘head’ side
•
Replace the nut on the standpipe to secure it safely to the sender
unit.
•
Replace the sender unit into the fuel tank.
The bottom of the fuel standpipe should be 30-40mm from the bottom of the
fuel tank to allow enough suction of fuel and at the same time not allow
impurities and sediment to be drawn up the standpipe.
+44 (0)23 8052 2345
26
MV Heating UK Ltd
Electrics:
Components
Make sure that all electrical components are arranged in the vehicle so that
they function correctly under normal heater operations. Firstly, ensure that
no wires are damaged in any way and avoid feeding them through areas that
may cause damage to the loom or cause kinking, jamming or exposure to
heat. If necessary, fit rubber grommets and plugs around the loom in areas
that are not waterproof or may get damaged by road debris. Lastly make sure
all connections are free of corrosion and all firmly connected.
Control Switch & Timer
To install the control switch, simply remove the rotary knob (it is quite stiff)
and secure in a suitable location with the screw provided, then replace the
knob back in the correct location. Alternatively, to fit the mini timer, simply fit
the appropriate screw inside the hole located at the center of the timer. Both
plug into the corresponding black and clear plugs on the loom.
Note: Only one can be installed at a time.
External Temperature Sensor Probe
The external temperature sensor probe plugs into the corresponding blue and
brown wired socket on the diagram and should ideally by mounting at
shoulder height when sat down to ensure correct reading of the air
temperature. It should not be mounted in such a way as to obstruct air flow;
like up high, in the corner of the vehicle cabin or above heat sources.
+44 (0)23 8052 2345
27
MV Heating UK Ltd
11
13
14
2
7
6
4
3
8
9
1
16
5
12
10
Grey/Black
Grey/Black
Convector
motor
Blue/Purple
Blue/Purple
Brown
Brown 1.5
15
Blue
Black
Grey
Red
Red/White
Blue/White
NTC10K
External
Temperature
Sensor
1
2
3
4
X9
1
2
3
4
X10
Control Switch
Push Button
Remote Control
Receiver
Battery
X7
Fuel
Pump
1
2
3
4
X1 BM
Fan
Motor
2
1
X8
2
1
X2 GS
2
1
X3 FW
2
1
X4 UeF
NTC50K
PT1000
Flame/temperature
Overheating sensor
Glow Plug
Brown
Brown 0.5
Brown 1.0
Brown
Brown
Brown
Brown 1.5
Brown
Blue
Green 1.0
Yellow
White
Red 2.5
Brown 2.5
Blue/White
Blue/White
Blue/White
Blue
Red 2.5
20A/10A
Black
Grey
Red
Red
Black
Grey
Red/Yellow
Red/Yellow
Yellow
Yellow
Red
Red/White
Red/White
Red
Brown 2.0
White 2.0
Brown
Green
Blue
Blue 0.5
Yellow 0.5
Red 0.5
Swim
RST
Controller
X6
X5
Wiring Diagram
+44 (0)23 8052 2345
28
MV Heating UK Ltd
To Timer Control
4
3
2
1
GRAY
BLUE
BLACK
UNUSED
4
3
2
1
BLUE/WHITE
RED/YELLOW
BROWN
UNUSED
4
3
2
1
UNUSED
RED/YELLOW
BROWN
4
3
2
1
GRAY
BLUE
BLACK
To Rheostat Control
RED
RED/WHITE
Control Connections
Use a single screw to fix the timer control or rheostat control in place. They
are best installed so that they can be seen and operated easily to identify
working conditions and also for easy access. The black and clear plugs
connect to the corresponding plugs on the loom (below). The remaining
three-pin socket on the timer or rheostat control plugs into the remote
control receiver if one is installed. An adaptor cable may be necessary.
Timer Control Plug
Figure XIX
Rheostat Control Plug
Figure XX
+44 (0)23 8052 2345
29
MV Heating UK Ltd
Wiring Loom Plug for Timer and Rotary Control
Figure XXI
Any surplus wires should be kept in good condition and wrapped in electric
tape to avoid short circuiting.
3
4
1
2
BLACK
BLUE
RED
GRAY
3
4
1
2
BLUE/WHITE
RED/WHITE
RED/YELLOW
BROWN
To Main Wiring Harness
+44 (0)23 8052 2345
30
MV Heating UK Ltd
Operation:
Rheostat Control
1. Variable Output Button and Indictor Light
2. Temperature Button and Indicator Light
3. Fan Only (Cold Air) Button and Indicator Light
4. Control Knob
5. Fixing Screw Hole (Located underneath control knob)
Figure XXIII
The rheostat (or rotary) control works by twisting the control knob to the
desired heat setting, and using the buttons listed to determine the heaters
function. Variable output is simply high to low heat. The temperature button
switches the heater to thermostatic mode (the heater will then switch to a
cool-down cycle automatically once it has reached the selected temperature).
The fan button only switches the fan on for cool air.
°C
1
2
3
5
4
+44 (0)23 8052 2345
31
MV Heating UK Ltd
Mini Timer
1. Display
2. Up Arrow Key
3. ‘P’ Icon
4. ‘Heating’ Icon
5. Down Arrow Key
6. Fixing Screw Hole
Figure XXIV
Functions
•
Adjustable thermostatic mode from 5°C to 35°C
•
Adjustable 7 step heating mode from <1kW to your heaters full
output
•
24-hour countdown set up time
•
Heating time from 15 minutes to 99 hours
•
Fault Information Codes
2
3
6
5
4
1
+44 (0)23 8052 2345
32
MV Heating UK Ltd
Manual Start Up and Shut Down
For immediate start-up press the heating icon to change the standby mode
into the heating mode and the heater will start up immediately.
To adjust the heating temperature in the heating mode simply press the up or
down arrow keys.
To turn the heater off manually, simply re-press the heating icon.
Pre-setting Heating Time
During heating mode, press the ‘P’ button and the down arrow
simultaneously to start a countdown for the heating time.
Adjust the hour with the arrow keys and confirm the time with the ‘P’ button.
Then adjust the minute time again using the arrow keys and confirm again
with the ‘P’ button.
Note: The ‘dot’ in the upper right hand corner of the screen means the time
was set successfully. To cancel press the heating icon.
Pre-setting Starting and Heating Times
Step 1: Press the ‘P’ key in the standby mode to enter the pre-set mode.
Step 2: The time mode will appear. Adjust the hour first with the arrow keys
and press the ‘P’ when complete to move onto the minutes. You can adjust
the minutes in the same way, however ensure you press the ‘heating icon’ to
confirm (the confirmation dot will appear in the upper right hand corner of
the screen), then press the ‘P’ button to move onto the next step
Step 3: Next stage is the temperature/output stage, the two can be adjusted
by pressing the arrow keys simultaneously. The modes can then be adjusted
with the arrow keys. Once adjusted; confirm the selection by pressing the
‘heating icon’ and move onto the next step by pressing the ‘P’ button.
+44 (0)23 8052 2345
33
MV Heating UK Ltd
Step 4: Next step is adjusting the heating time. You can adjust
this in the same way using the arrow keys. The hour first followed by the
minutes, pressing the ‘heating icon’ again to confirm and the ‘P’ key for the
final time to complete the task.
Note: The ‘confirmation dot’ in the upper right hand corner of the screen
must be present each time a step is adjusted to confirm it.
Checking Temperature
Pressing the ‘P’ and ‘up’ arrow button simultaneously whilst in the heating
mode will display the air inlet temperature, or the remote temperature
sensor probe’s temperature if one is fitted.
Note:
•
The display will show 0°C if the temperature is lower than 0°C
•
The display will automatically revert to the heating mode if left idle
for more than 5 seconds
Converting to Thermostatic Mode
Press both arrow keys to manually change from the heating mode to the
thermostatic mode.
Fault Information
The fault display can be accessed by pressing the ‘P’ button during the
heating mode.
Six fault codes can be checked by pressing the arrow keys.
To return to the heating mode, press the heating button.
To eliminate the fault information; press the ‘P’ and heating buttons
simultaneously.
+44 (0)23 8052 2345
34
MV Heating UK Ltd
Remote Operation
When the remote signal had been received, the timer will automatically
switch to the thermostatic mode, with a default temperature of 25°C, the
confirmation dot will appear in the meantime.
To return back to the standby mode, press the heating icon. The confirmation
dot will continue to appear until the remote shutdown signal has been
received.
Installation Fuel Priming Feature
ATTENTION:
•
Not to be used in normal heater operation
•
Disconnect the fuel line from the heater first, to prevent flooding of
the heater and place in a suitable receptacle.
To enter the fuel priming mode, press and hold the ‘P’ icon for more than
three seconds and let go to enter the next step.
Next, press and hold the heating icon for more than three seconds and then
let go. If done correctly the display will read ‘FUEL’ and the pump will begin to
pump quickly. To stop; press the heating icon again.
Press and hold the ‘P’ icon for more than three seconds to return to the
standby mode.
+44 (0)23 8052 2345
35
MV Heating UK Ltd
LCD Digital 7-Day Timer
O
K
Mo
Tu
We
Th
Fr
Sa
Su
P
O
K
Mo
Tu
We
Th
Fr
Sa
Su
P
b
3
5
2
4
6
1
a
e
d
c
f
O
K
Mo
Tu
We
Th
Fr
Sa
Su
P
b
3
5
2
4
6
1
a
e
d
c
f
Figure XXV
1. LCD Screen
a. Days of the week
2. Left Arrow Button
b. Heating Symbol
3. Right Arrow Button
c. Fan Symbol (later models only)
4. Power/Back Button
d. ‘P’ (Timer) Symbol
5. OK Button
e. Clock Symbol
6. Fixing Screw Hole
f. Clock Face
Functions:
•
7 day timer, able to be programmed 3 times daily
•
7 step variable output mode
•
Thermostatic mode from 05°C to 35°C
•
Adjustable cold air fan mode (on later versions)
+44 (0)23 8052 2345
36
MV Heating UK Ltd
Changing Language
The language should be set to English. However, if it
isn’t or the control has been reset to default settings it
will revert to Chinese. Please follow these steps to
convert the language to English.
1. Turn on the control with the power button. Wait for
the symbols to stop flashing, then press the power
button again.
2. Navigate to the clock face symbol at the top of the
control by using the arrow keys. When it is flashing press
both arrow keys simultaneously.
3. P1 now appears.
4. Press ok and C1 will appear.
5. Keep pressing ok slowly until ‘02:oF’ appears.
6. Press any of the arrow keys until the screen reads
‘02:on’
7. Keep pressing ok until back to the P1 menu screen
8. Press power button to return. The language will now
be set to English.
P 1
P 1
P
18:30
P
18:30
P 1
P 1
c 1
c 1
P
18:30
P
18:30
02:8H
02:8H
02:8f
02:8f
一
二
三
四
五
六
日
P
Ih i
一
二
三
四
五
六
日
P
Ih i
P 1
P
18:30
P 1
c 1
P
18:30
02:8H
02:8f
一
二
三
四
五
六
日
P
Ih i
+44 (0)23 8052 2345
37
MV Heating UK Ltd
Changing the Date and Time
1. To change the date and time, navigate to the
clock face symbol and press ok.
2. Select the day of the week it is first using the
arrow keys, and pressing ok to confirm.
3. Select the hour using the arrow keys, and
pressing ok to confirm.
4. Finally, select the minutes in the same way.
5. Once completed, the control will return to
the home screen (displaying the correct time)
NOTE: If the LCD digital timer is disconnected
from the loom, the date and time will need to
be re-entered.
P
18:30
P
18:30
Mo
Tu
We
Th
Fr
Sa
Su
P
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
Mo
P
Mo
P
12:30
Mo
P
12:30
Mo
P
Mo
P
12:05
Mo
P
12:05
P
12:05
P
12:05
P
18:30
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
Mo
P
12:30
Mo
P
12:05
P
12:05
+44 (0)23 8052 2345
38
MV Heating UK Ltd
Manual On/Off
1. To switch the power on manually,
navigate to the heating icon, and press ok
2. The heater will start automatically.
3. Use the arrow keys to adjust the output of
the heater from high to low (07 to 01
respectively)
4. To switch the heater off, simply press the
heater button to return to the home screen.
P
18:30
P
18:30
P
18:30
P
18:30
P
18:30
0 1
0 1
0 1
0 1
07
07
07
07
P
18:30
P
18:30
0 1
07
+44 (0)23 8052 2345
39
MV Heating UK Ltd
Switching to Thermostatic Mode
To switch to thermostatic mode, turn the heater on
manually, as stated in the previous step.
1. Once the heater is on, press and hold the ok
button for three seconds and then release it.
2. The display should change to a temperature
setting which can be adjusted from 05°C to 35°C
using the arrow keys.
3. To adjust back to the variable output mode,
simply press and hold the ok button again for 3
seconds and then release it.
4. To switch the heater off, press the power button
to return to the home screen.
Fan Mode
The fan mode works in the same way as the manual on/off mode. Simply
navigate across to the fan symbol and confirm with OK. The fan will then
automatically switch on and its speed can be adjusted from high to low (07 to
01 respectively) using the arrow keys. To switch it off, press the power
button.
NOTE: Some earlier models will not have this function.
07
07
07
07
35
°c
35
°c
07
07
07
07
P
18:30
P
18:30
07
35
°c
07
P
18:30
+44 (0)23 8052 2345
40
MV Heating UK Ltd
Pre-setting Heating Times
The digital control can be used as a 7-Day timer, and is able to be preset to
switch on up to three times a day.
1. Navigate to the ‘P’ symbol, and press OK.
2. Using the arrow keys select the number 1
(flashing) at the top of the screen, and press OK
– Number 1 is the first heating time.
3. Using the arrow keys, select ‘ON’, as this will
allow the heater to switch on after the
presetting is finished. Press OK to confirm.
4. Select the length of time you want the heater
to run for by using the arrow keys. – L800
represents 800 minutes. Run time can be
selected from 50-990. Press OK to confirm.
5. Select the hour you wish the heater to start at
by using the arrow keys and then pressing OK to
confirm.
P
18:30
P
18:30
P
18:30
P
18:30
P
18:30
123
P
18:30
123
8H
1
8H
1
P
8H
1
P
P
L800
P
L800
1
P
L800
1
P
06:30
P
06:30
1
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
P
18:30
123
8H
1
P
P
L800
1
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
+44 (0)23 8052 2345
41
MV Heating UK Ltd
6. Select the minutes in the same way, and press OK to confirm.
7. The next step is choosing which day of
the week you want the heater to run.
Starting with Monday, use the arrow keys to
change from ‘OFF’ to ‘ON’ and press OK to
confirm. Continue this all the way through
to Sunday.
8. The preset time should now be set. This
will be indicated by the small, underlined
number 1 at the top of the screen.
9. To set the second and third heating
times, simply repeat all the steps but select
2 or 3 instead of 1 (see step 2.) to set those
heating times.
NOTE: To turn any of the preset times off
without altering the set times, simply go
through to step 3 and select ‘OFF’ using the
arrow keys. Then repeatedly press OK until
you have returned to the home screen.
P
06:30
P
06:30
1
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
8H
1
8H
1
P
8H
1
P
Mo
Tu
We
Th
Fr
Sa
Su
8H
1
P
Mo
Tu
We
Th
Fr
Sa
Su
8H
1
P
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
P
18:30
1
P
18:30
1
P
18:30
P
18:30
123
P
18:30
123
P
18:30
123
P
06:30
1
Mo
Tu
We
Th
Fr
Sa
Su
8H
1
P
Mo
Tu
We
Th
Fr
Sa
Su
P
18:30
1
P
18:30
123
+44 (0)23 8052 2345
42
MV Heating UK Ltd
Installation Fuel Priming Feature
ATTENTION:
•
Not to be used in normal heater
operation
•
Disconnect the fuel line from the heater
first, to prevent flooding of the heater
and place in a suitable receptacle.
1. To enter the fuel priming mode, navigate to
the clock face using the arrow keys and press
both arrow keys simultaneously.
2. P1 should appear on the screen.
3. Select P2 by pressing any arrow key, and
confirm with OK.
4. The fuel pump will begin to rapidly pump the
fuel.
5. It will automatically shut down after three
minutes, or press any key to stop the pumping
at any time, and return to the home screen.
P
18:30
P
18:30
P 1
P 1
P2
P2
fuel
fuel
P
18:30
P
18:30
P
18:30
P 1
P2
fuel
P
18:30
+44 (0)23 8052 2345
43
MV Heating UK Ltd
Checking Error Codes
Once an error code has been displayed, and the
problem has been amended, follow these steps
to reset it.
1. Check the error using the arrow keys. Exit by
pressing either OK or the power button.
2. Press both arrow keys to display message
‘dEL’.
3. Press OK to delete all errors or power to go
back. Once the display reads ‘IE00’ then no
errors have been found.
4. Press OK or power to return.
Ie 3 1
Ie 3 1
8e l
8e l
8e l
8e l
Ie 00
Ie 00
P
18:30
P
18:30
Ie 3 1
8e l
Ie 00
P
18:30
+44 (0)23 8052 2345
44
MV Heating UK Ltd
Resetting Digital Controller to Factory Settings
1. Navigate to the clock face on the menu
and simultaneously press both arrow
buttons.
2. P1 should appears on the screen.
3. Using the left arrow key select ‘—01’,
confirm by clicking the ‘OK’ button.
4. The control should now be reset to its
original factory settings.
P
18:30
P
18:30
P 1
P 1
0 1
0 1
P
18:30
P
18:30
一
二
三
四
五
六
日
P
18:30
一
二
三
四
五
六
日
P
18:30
P 1
0 1
P
18:30
一
二
三
四
五
六
日
+44 (0)23 8052 2345
45
MV Heating UK Ltd
Maintenance
Once the heater is installed, it should ideally be turned on a few times to
remove any air trapped in the fuel lines. Also ensure there is no leaking from
the lines and that all electric terminals fit securely together.
You should also regularly:
•
Check the air inlet and outlet for any pollution or foreign objects
blocking the outlets
•
Clean the externals of the heater
•
Check for corrosion or loose connections of circuits and connectors
•
Check the combustion air inlet and exhaust pipe for damage and/or
clogs
•
Check the fuel line for leaks and kinks
To ensure a long life of the heater it is advised that you run it for at least 10
minutes every month, to prevent malfunction of mechanical parts.
After 10 years the heat exchanger, overheat sensor and exhaust should be
replaced by a professional.
If any welding is being attempted on the vehicle, please remove the positive
power supply wire and earth it to protect the controller from any damage.
+44 (0)23 8052 2345
46
MV Heating UK Ltd
Fault Codes:
Rheostat Control
When the ECU had discovered a fault, the rheostat control will flash a fault
code. The control should therefore be ideally placed where it can be clearly
seen and accessed.
The faults will be displayed as short flashes followed by long flashes. To
determine the code, you must count the number of long flashes.
Number of
Long Flashes
Cause of Problem
1
Failure of second start
2
Termination of the third time of combustion
3
Voltage power out of specified range
4
Glow plug temperature increases slowly
5
Air heaters will not flash 5 times
6
Temperature sensor: Broken circuit or short-circuit
7
Fuel pump: Broken circuit or short-circuit
8
Fan motor: Broken circuit, short-circuit or clogged
9
Glow pin: Broken circuit or short-circuit
10
Overheated
11
Overheat sensor: Broken circuit or short-circuit
12
Control switch: Broken circuit or short-circuit
+44 (0)23 8052 2345
47
MV Heating UK Ltd
Timers
1E-02 : Overheat – Check for obstruction or damaged ducting
1E-10 : Ignition failure – Check fuel supply, blocked supply or fuel pump
1E-30 : Voltage too high
1E-31 : Voltage too low – check battery or voltage drop in supply cable
1E-52 : Overheat sensor failure
1E-70 : Fuel pump open circuit or ECU failure
1E-80 : Air motor failure
1E-90 : Glow pin failure
1E-d3: Maintenance Reminder
Thank you for purchasing the MV Airo 4.