Panduit smartzone G5 Operation & User’s Manual
Read Online
Read the Panduit smartzone G5 Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
SMARTZONE G5 USER MANUAL
1
Contents
Section 1 ......................................................................................................................... 4
Intelligent Network Controller ....................................................................................... 4
Connecting the PDU to a LAN Ethernet Port ............................................................... 4
Connecting the PDU to a Computer Serial Port ........................................................... 5
Setup Serial Communication .................................................................................... 6
Section 2 – Remote Configuration .................................................................................. 9
Dynamic Host Configuration Protocol (DHCP) ............................................................ 9
Web Configuration ....................................................................................................... 9
Supported Web Browsers ........................................................................................ 9
Logging in to the Web Interface ............................................................................... 9
Access Types ......................................................................................................... 16
Menu Dropdowns ................................................................................................... 18
Section 3 – Simple Network Management Protocol (SNMP) ......................................... 19
SNMP Configuration .................................................................................................. 19
Configuring Users for SNMP v3 Communications ..................................................... 22
Configuring SNMP Traps ........................................................................................... 24
Section 4 – Local (Access) Configuration ...................................................................... 26
Connecting through a Serial Connection ................................................................... 26
Supported Commands ........................................................................................... 26
Serial Cable Pinout to Create Your Own Cable ......................................................... 27
Radius Authentication ................................................................................................ 27
G5 PDU LDAP Server Settings ................................................................................. 29
Logging in to the CLI .............................................................................................. 32
Section 5 – Remote Access .......................................................................................... 33
Section 6 – Local Display .............................................................................................. 35
OLED Display ............................................................................................................ 35
SMARTZONE G5 USER MANUAL
2
Menu Mode ............................................................................................................ 36
OLED Menu Structure ............................................................................................... 38
Main Menu Selections ............................................................................................ 38
Setup Menu ............................................................................................................ 39
Power Menu ........................................................................................................... 46
Sensors Menu ........................................................................................................... 50
G5 iPDU Outlet Power Sequence Setup ................................................................... 51
Section 7 – Daisy Chain Configuration .......................................................................... 55
Daisy-Chain Overview ............................................................................................... 55
Daisy-Chain Setup Connecting up to 4 PDUs of the same SKU through a single IP
address: ..................................................................................................................... 55
RNA (Redundant Network Access) Functionality ...................................................... 56
RNA Setup ................................................................................................................. 57
Section 8 – Connecting and Configuring Optional Hardware ........................................ 59
Accessory Hardware Overview .................................................................................. 59
Connecting a Temperature Sensor ............................................................................ 62
Connecting a Temperature and Humidity Sensor ...................................................... 63
Connecting a 3-Temperature and 1-Humidity Sensor ................................................ 63
Connecting a Rope Fluid Leak Sensor ...................................................................... 64
Connecting the Open/Closed Door Sensor ................................................................ 65
Connecting the Sensor Hub ....................................................................................... 68
Detecting Environmental Sensors.............................................................................. 68
Configuring Environmental Sensors .......................................................................... 69
Warranty and Regulatory Information............................................................................ 70
Warranty Information ................................................................................................. 70
Regulatory Information .............................................................................................. 70
Support and Other Resources ....................................................................................... 71
Accessing Panduit Support ........................................................................................ 71
Acronyms and Abbreviations ......................................................................................... 72
SMARTZONE G5 USER MANUAL
3
Documentation Feedback ............................................................................................. 73
Appendix A: CLI Commands ......................................................................................... 74
Appendix B: Firmware Update Procedure ..................................................................... 82
USB Method .............................................................................................................. 82
Web Interface Method ............................................................................................... 82
Serial (Command Line Interface) Method .................................................................. 84
FTPs Method ............................................................................................................. 85
Bootloader Mode ....................................................................................................... 85
Firmware Recovery with Bootloader Mode ................................................................ 86
Upgrade Configuration with Bootloader Mode ........................................................... 86
Appendix C: PDU Alarms .............................................................................................. 87
Trap Codes assigned to Alarms List .......................................................................... 89
Appendix D: Horizontal Intelligent Network Controller Replacement ............................. 94
Appendix E: Vertical Intelligent Network Controller Replacement ................................. 96
SMARTZONE G5 USER MANUAL
4
Section 1
Intelligent Network Controller
The Panduit Monitored Input, Monitored & Switched, Monitored per Outlet, and
Monitored & Switched per Outlet PDUs have an integral, hot swappable Intelligent
Network Controller. The Intelligent Network Controller contains the OLED interface,
control buttons, the USB, Ethernet, Serial and Sensor ports, and recessed Reset
Button.
Reset Button
Pressing the Reset Button only reboots the Intelligent Network Controller. It does not
change the Energy (kWh) value and does not affect the output voltage.
Using the Reset Button
Press and hold the Reset Button for 8 seconds to recover from an Intelligent Network
Controller communication failure.
Connecting the PDU to a LAN Ethernet Port
The PDU is defaulted to DHCP. If you are connected to an Ethernet with a DHCP
server, the PDU automatically get an IP address and display it on the LCD screen. If
there is no DHCP server, the default IP address is 192.168.0.1, but again this will be
displayed on the PDU.
Connecting the PDU to a LAN provides communication through an Internet or Intranet
connection. You can monitor the PDU from any computer connected to the same
network. The PDU is set to use DHCP (Dynamic Host Configuration Protocol) by default
when delivered. If IP is successfully assigned, you will see the IP address shown on
OLED display.
1. Locate the Ethernet cable
2. Connect one end of the cable to the Ethernet port on the PDU (see Figure 1).
Connect the other end of the cable to the Ethernet port on the router (or another
LAN device).
SMARTZONE G5 USER MANUAL
5
Connecting the PDU to a Computer Serial Port
If unable to connect to network, you can change the network setting using the serial
interface.
To configure the network setting, perform the following steps:
1. Serial connect the PDU to a computer’s serial port. Set baud rate for a terminal
emulation program
2. Using a CLI command to enable DHCP or set a static IP.
3. Verify access to the Web interface. The Ethernet LED on the PDU front panel
provides communication status by color and display activity. The recessed Reset
button restarts the PDU (see Figure 2 below).
SMARTZONE G5 USER MANUAL
6
Locate the Reset button (figure 2)
Setup Serial Communication
You may configure the network settings using the command line interface (CLI) with a
serial connection. Users can connect serially using the optional RJ45-DB9 cable (or
make your own cable by creating a unique pinout as described below in the “Serial
Cable Pinout to Create Your Own Cable” in Section 4).
1. Verify that the computer has a serial port. If your computer does not have a DB9
serial connector, but does have a USB connector, obtain a USB-to-DB9 Adapter to
convert the USB to a DB9 serial port.
2. Using the optional RJ45-DB9 cable, connect the RJ-45 end to the port labeled
“Serial+RS485-1” on the front panel of your PDU model (see Figure 2). Connect the
DB9 end of the cable to the computer.
3. Open the terminal emulation program (HyperTerminal or PuTTY) on the computer
and select the serial port connection (such as COM1).
4. Set the communications port as follows:
• Bits per second: 115200
• Data bits: 8
SMARTZONE G5 USER MANUAL
7
• Parity: None
• Stop bits: 1
• Flow control: None
(See Port Settings example below)
5. Use the default initial login indicated below. Note that the username and password
are both case sensitive:
• Username: admin
• Password: 12345678 (or your new password)
6. The “Panduit>” prompt appears after you have logged in, ready to enter the CLI
command.
7. To configure network settings, enter the appropriate “net” command and press
Enter. All commands are case sensitive. You can type ? to access the commands.
8. To enable the IPv4 DHCP by default, run:
• net tcpip dhcp
• Enter Y to confirm and the PDU’s Intelligent Network Controller will reboot.
SMARTZONE G5 USER MANUAL
8
9. To set a static IPv4 configuration, run:
• net tcpip static x.x.x.x (ipaddress) x.x.x.x (netmask) x.x.x.x (gateway)
• Example: net tcpip static 192.168.1.100 255.255.255.0 192.168.1.1
• Enter Y to confirm and the PDU’s Intelligent Network Controller will reboot.
SMARTZONE G5 USER MANUAL
9
Section 2 – Remote Configuration
Dynamic Host Configuration Protocol (DHCP)
The PDU is Dynamic Host Configuration Protocol (DHCP) compatible. If the network
does not use a DHCP server, see the CONNECTING THROUGH A SERIAL
CONNECTION section. The PDU automatically obtains an IP address via DHCP, when
connected to a network. Login to the Web interface to configure the PDU and assign a
static IP address (if desired). The PDU automatically gets an IP address and displays it
on the LCD screen. If there is no DHCP server, the default IP address is 192.168.0.1,
but again this will be displayed on the PDU.
1. Connect a standard Ethernet patch cable to the Ethernet port on the PDU.
2. Connect the other end of the Ethernet cable to the LAN.
3. Make sure the Ethernet port on the PDU shows a solid green light on the left and a
flashing yellow light on the right to indicate successful connectivity to the network.
4. Use the menu buttons to look up the IP address of the device on the OLED display
by selecting Setup > Network > IPv4 or IPv6 as applicable.
5. In a standard web browser, enter the PDU IP address and proceed to configure the
PDU as shown in the Web Configuration section.
Web Configuration
Supported Web Browsers
The supported Web browsers are Windows Firefox, Linux Firefox, Windows Internet
Explorer, and Google Chrome.
Logging in to the Web Interface
Logging In
• Open a supported web browser and enter the IP address of the PDU.
o If username and password were configured during the Network Configuration
Setup: enter the username and password in the appropriate fields. Press
Login or Enter.
o If username and password were NOT configured during the Network
Configuration Setup, use the default username: admin and password:
12345678. For security purposes, change the password upon login.
SMARTZONE G5 USER MANUAL
11
Number
Icon
Description
1
The home icon provides an
overview of the PDU with
access to the Dashboard,
Alarms, Identification, and
Control & Manage.
2
The Alarm icon provides
details of the active critical
alarms and active warning
alarms.
3
This icon lets you select a
Language. There are
seven languages available
to choose from: English,
Chinese, French, Italian,
German, Spanish, and
Japanese.
4
This icon provides the logs
of the PDU which can be
viewed and downloaded.
5
The settings icon allows a
user to setup the Network
Settings, System
Management, SNMP
Manager, Email Setup,
Event Notifications, Trap
Receiver, and Thresholds.
6
The search icon allows you
to input key words and
search for the related
results.
7
Information about the PDU
can be found using this
icon. You also can also
click user guide and
license to ask for help.
8
This icon shows who is
logged in (user or admin).
SMARTZONE G5 USER MANUAL
12
Number
Icon
Description
Account passwords can be
changed, and user
accounts managed
through this page.
Power Summary Page
Power PDU Page
SMARTZONE G5 USER MANUAL
14
Landing Page
NOTE: The default user name is admin and the default password is 12345678.
Changing Your Password
In initial login, change the password:
1. The Change Password window opens directly. Enter the current password and
new password twice to confirm. By default, passwords must be between 8 and
32 characters.
2. Click Change Password to complete the password change.
SMARTZONE G5 USER MANUAL
15
After initial login, to change the password:
1. Go to User Name>Change Password.
2. The Change User Password window opens.
SMARTZONE G5 USER MANUAL
16
3. Enter the old password and then new password twice to confirm. By default,
passwords must be between 8 and 32 characters.
4. Click Change Password to complete the password change.
Logging Out
Users should logout after each session to prevent unauthorized changes to the system.
1. Click on the user name icon in the top right corner of the screen (see Introduction
to the Web Menu).
2. Click on Log Out in the drop-down menu.
Access Types
There are two levels of access privileges:
• Full
• Read-Only
The Panduit PDU comes with a standard Full profile and a standard Read Only profile.
The Full profile is typically the system administrator and has the “Admin Role” with full
operating permissions. The default Read Only profile includes the default “User Role”
permissions. All other users must be added by the Full user. Users are defined by their
unique login credentials and by their user role. The level of access privilege determines
what the user will see and what actions the user can perform. The level of access
privilege determines which menu items the user can access or which fields display on
individual setting and configuration dialogs before setting up users, determine the
Roles that will be required. Each user must be given a Role. These Roles define the
permissions granted to the user.
Role
Default Permissions
Full
Full permissions that cannot be modified or deleted.
Read Only
Limited permissions that can be modified or deleted. By
default, these permissions are:
• Change Input Phase Setting
• Change Circuit Breaker Setting
SMARTZONE G5 USER MANUAL
17
• Change Outlet Setting
• Change Own Password
• Change Event Settings
Customized
Permissions for user customized roles can be set as
needed.
User Accounts
Add a user:
1. Go to User Administration>User Accounts.
2. Select Add User to create a new user profile.
3. Use the Settings tab to enter the following information:
• User Name (required)
• Password (required)
• Confirm Password (required)
NOTE: Set password requirements in the required field. By default, passwords must be
8-32 characters in length, and to have at least one numeric character, and at least one
special character.
1. Use the Roles tab to set full or read only privileges.
2. Select Add to save the new user profile.
Modify user profile:
1. Go to User Administration>Users.
2. Select the user name.
3. Select Edit. Make changes to the user profile.
4. Select Update.
SMARTZONE G5 USER MANUAL
18
Delete user profile:
1. Go to User Administration>Users.
2. Select the red X next to user name.
NOTE: To make multiple selections, press Shift + click to highlight multiple profiles.
Menu Dropdowns
Overview
Alarms
Help
Language Logs
Settings
Admin
SMARTZONE G5 USER MANUAL
19
Section 3 – Simple Network Management
Protocol (SNMP)
SNMP Configuration
Setup SNMP
1. Access the Web interface and login.
2. Under SNMP Managers, select SNMP General. The SNMP General page
displays.
3. The SNMP General includes SNMP Access and Version.
SMARTZONE G5 USER MANUAL
20
Setup SNMP Port
1. Access the Web interface and login.
2. Under SNMP Managers, select SNMP Port. The SNMP Port page displays.
SMARTZONE G5 USER MANUAL
21
3. Setup SNMP Port and SNMP Trap Port
Define SNMP V1/V2c User
1. Access the Web interface and login.
2. Under SNMP Manager, select SNMP V1/V2c. The SNMP V1/V2c page displays.
3. Ensure that SNMP V1/V2c is selected in the SNMP Version field.
SMARTZONE G5 USER MANUAL
22
4. In the SNMP V1/V2c panel, in the Community column, select the SNMP V1/V2c
user to configure.
5. Choose one of the following access rights for the selected SNMP V1/V2c user:
• Read Community: the SNMP V1/V2c user can edit “public”.
• Write Community: the SNMP V1/V2c user can edit “private”
6. Click Enable and Update.
Configuring Users for SNMP v3 Communications
1. Access the Web interface and login.
2. Under SNMP Managers, select SNMP V3. The SNMP V3 page displays.
SMARTZONE G5 USER MANUAL
23
3. Ensure that SNMP V3 is selected in the In the SNMP Version field.
4. In the SNMP V3 panel, in the Users column, select the SNMP V3 user to
configure.
5. Select the “Enable SNMPv3 access” checkbox. (Leave this box blank to restrict
SNMP access).
• Choose a Security Level from the dropdown menu:
• NoAuthNoPriv: No authentication and no privacy. This is the default.
• AuthNoPriv: Authentication and no privacy.
• AuthPriv: Authentication and privacy.
SMARTZONE G5 USER MANUAL
24
6. Select the desired authentication.
• “Use Password as Authentication Phrase” or enter a new unique password to
be used for authentication and then enter the new pass phrase again for
confirmation in the Confirm Authentication Pass Phrase field.
• “Use Authentication Pass Phrase as Privacy Pass Phrase” to use the user’s
authentication pass phrase as their privacy pass phrase, or enter a new pass
phrase for privacy in the fields provided: Privacy Pass Phrase, and Confirm
Privacy Pass Phrase.
Configuring SNMP Traps
Setup an SNMP Trap port
1. Access the Web interface and log in.
2. Under SNMP Manager, select SNMP Port.
SMARTZONE G5 USER MANUAL
25
3. Set up SNMP Port and SNMP Trap Port.
4. Set up the SNMPV1 trap name, host, and community.
SMARTZONE G5 USER MANUAL
26
Section 4 – Local (Access) Configuration
Connecting through a Serial Connection
You can access PDU information such as: System configuration, Network
Configuration, User Operation, Device Settings, Power Measurements, Switch Outlets
On/Off through a serial connection by running CLI commands. It also requires a terminal
emulation program such as HyperTerminal.
Communicating through the serial port requires a specialized optional RJ45-DB9 cable
or you can create your own cable as described in the “Serial Cable Pinout to Create
Your Own Cable” section.
To connect the PDU to a computer:
Using the optional RJ45-DB9 cable, connect the RJ-45 end to the port labeled
“Serial+RS485-1” on the front panel of your PDU model. Connect the DB9 end of the
cable to the serial connector on the computer.
Supported Commands
The PDU CLI command set for managing and monitoring the PDU includes the
following commands:
• ? command:
PDU help query
• sys command:
PDU system configure and setting
• net command:
PDU net application configure and setting
• usr command:
PDU user operation
• dev command:
PDU device setting
• pwr command:
PDU power setting
NOTE: Command variables are represented in command input syntax surrounded by
angle braces (< >). Optional parameters are represented in command input syntax
surrounded by straight brackets ([ ]). For data of type array, the 'x' character as index of
array in command input syntax means all indexes. You must be logged into the PDU
before commands can be sent. See Appendix A for a list of all CLI commands.
SMARTZONE G5 USER MANUAL
27
Serial Cable Pinout to Create Your Own Cable
To make your own RJ45-to-DB9 Serial cable, the connections are wired as shown:
Figure: 5
Radius Authentication
1. Go to User Settings > in the admin menu.
2. Go to Radius Configuration and click on the edit pencil.
SMARTZONE G5 USER MANUAL
28
3. Select the Enable button.
4. Enter Server IP address field, Port number field, and Secret field.
5. Click save and your Radius authentication is complete.
SMARTZONE G5 USER MANUAL
29
G5 PDU LDAP Server Settings
To setup LDAP to access the Active Directory (AD) and provide authentication when
logging into the PDU via the Web Interface:
1. Go to User Settings (under the ADMIN Menu) > LDAP Configuration.
2. Select the LDAP Enable checkbox.
3. Use the drop-down menu to choose the Type of LDAP Server. Choose Microsoft
Active Directory.
4. Enter an IP Address of the domain controller/Active Directory (AD) Server.
i.e.: 192.168.1.101 (example)
5. Enter a Port.
Note: For Microsoft, this is typically 389.
6. In the Base DN field, enter in the account to be used to access AD.
i.e. CN=myuser, CN=Users, DC=EMEA, DC=mydomain, DC=com
7. Enter the password in the Bind Password and Confirm Password fields.
8. In the Search User DN field, i.e. DC=subdomain, DC=mydomain,
DC=com 10.
9. In the Login Name Attribute field, enter sAMAccountName (typically)
10. In the User Entry Object Class field, enter person.
With these LDAP settings configured, the Bind is complete. (see screen shot)
SMARTZONE G5 USER MANUAL
30
Once LDAP is configured, the PDU must understand for which group authentication
occurs. A role must be created on the PDU to reference a group within Active Directory
(AD).
1. Within the Active Directory, create a group for the users that you wish to be
PDU administrators. i.e. admins
2. Within the G5 PDU Web Interface, go to User Settings (under admin menu) >
Roles. Enter the Role Name that was created in AD. i.e. admins
3. Enable role privileges as needed. (see screen shot)
SMARTZONE G5 USER MANUAL
31
4. LDAP authentication is ready to use. To test this, just click save, then click on
“LDAP Configuration” again and type an Active Directory user name/password
into the test box. Click Test LDAP Configuration. If a box pops up with all
green “SUCCEEDED” (no X’s), the LDAP is successfully configured.
SMARTZONE G5 USER MANUAL
32
Note: Be sure to login without a domain name.
Logging in to the CLI
The Command Line Interface (CLI) is an alternate method used to manage and control
the PDU status and parameters, as well as basic admin functions. Through the CLI a
user can:
• Reset the PDU
• Display PDU and network properties
• Configure the PDU and network settings
• Switch outlets on/off
• View user information
Logging in with HyperTerminal
To login through HyperTerminal, set the COM settings to the following parameters:
• Bits per second: 115200
• Data bits: 8
• Parity: None
• Stop bits: 1
• Flow control: None
SMARTZONE G5 USER MANUAL
33
Section 5 – Remote Access
Logging in with SSH via PuTTY
1. Ensure SSH has been enabled: On GUI, go to Device Configuration > Network
Service > SSH. Select the Enable SSH Access checkbox. Select OK.
2. Open an SSH client (PuTTY).
3. Enter the IP address in the Host Name field. Select the connection type: SSH
• For SSH, enter 22 in the Port field.
4. Select Open.
5. Enter your Username. Press Enter.
6. Enter your password. Press Enter.
7. You are now logged into the SSH. Refer to the CLI Commands table below for
available commands.
NOTE: SSH connection is not available when serial connection is enabled.
SMARTZONE G5 USER MANUAL
35
Section 6 – Local Display
This section contains operation information for the Panduit Monitored, Switched and
Monitored & Switched PDUs, including:
• OLED panel and control button functions
• Manual selections
OLED Display
The OLED provides information about the PDU and connected devices. The OLED
window flashes red when a critical alarm is active. Basic configuration of some settings
is available through the OLED. Full configuration of all settings is available through the
remote interfaces. The OLED display orientation can be changed using an OLED
setting. The display can be rotated 0° and 180°.
The PDU has a three-button, graphical OLED panel (see Figure 6). Use the buttons to
change the screen display, retrieve specific performance data, or change configuration
values. The display view can also change automatically. For example, the display
changes to show active alarms as they occur, or particular displays update due to a
change in operating state.
SMARTZONE G5 USER MANUAL
36
Figure: 6
The OLED has two modes:
1. Screensaver mode: Screensaver mode cycles through a set sequence of
screens that display current PDU values. Current values are refreshed every ten
seconds. The user cannot select a custom sequence of screens. The
screensaver displays automatically after 30 seconds of inactivity from the start-up
screen, a menu, or a submenu. Values are refreshed every five seconds.
2. Menu mode (OLED main menu): The settings that display under each high level
(main) menu depend on your PDU model.
Menu Mode
The table below summarizes how to use the control buttons on the OLED display.
SMARTZONE G5 USER MANUAL
37
Button
When in Menu Mode
When in Screensaver
Mode
Menu
Select from the sour main
menus.
Returns to the previous
display screen before
entering the screensaver
mode.
Scroll
Scrolls down through the
list of menu items.
NOTE: A highlighted menu
item is ready to be
selected.
Returns to the previous
display screen before
entering the screensaver
mode.
Select
Opens the selected menu.
Returns to the previous
display screen before
entering the screensaver
mode.
LED Unit Status
The LED will change colors depending on the state of the PDU.
LED State
Description
Solid Green
Normal Operation
Solid Red
Critical Alarm
Solid Orange
Warning Alarm
SMARTZONE G5 USER MANUAL
38
OLED Menu Structure
Main Menu Selections
The PDU menu selection hierarchy consists of Setup, Alarms, Power, and Sensors. On
the main menu, scroll down to highlight Setup. Press Select. Scroll down to select a
submenu and press Select to display the submenu options. Press Menu to return to the
previous menu.
SMARTZONE G5 USER MANUAL
39
Setup Menu
The Setup menu provides user configuration options including Network, Device, Screen,
Language, USB, and Units. Depending on the assigned user privileges, only the
available options will be displayed.
Network Submenu
The Network submenu allows you to customize settings for IP address IPv4 or IPv6. On
the Setup menu, scroll down to Network. Press Select to display the options screen.
Scroll down to highlight the selected option from the menu. Press Select to display the
screens to set the values for the selected option. After you select the values, press
Select to set the values as displayed on the screen. Press Menu to return to the
previous menu.
SMARTZONE G5 USER MANUAL
40
Device Submenu
The Device submenu provides the SKU number, Serial number, MAC address and
Firmware version. On the Setup menu, scroll down to highlight Device submenu. Press
Select to display the option screens. After you make the selections, press Select to set
the values as displayed on the screen. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
41
Screen Submenu
The Screen submenu allows you to customize settings for Contrast, Rotate, and Always
on. On the Setup menu, scroll down to highlight Screen. Press Select to display the
screens to set the values for the submenu. After you select the values, press Select to
set the values as displayed on the screen. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
42
Language Submenu
The Language submenu allows you to select the language you need to use. On the
Setup menu, scroll down to highlight Lang. Press Select to display the screens to set
the values for the submenu. After you select the values, press Select to set the values
as displayed on the screen. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
43
USB Submenu
The USB submenu allows you to upload firmware file and download event log or data
log. On the Setup menu, scroll down to highlight USB. Press Select to display the
screens to set the values for the submenu. After you select Yes, press Select to set the
values as displayed on the screen. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
45
Units Submenu
The Units submenu displays the temperature units. On the Setup menu, scroll down to
highlight Units. Press Select to display the screens to set the values for the submenu.
After you select the values, press Select to set the values as displayed on the screen.
Press Menu to return to the previous menu.
Alarms Menu
The Alarms menu filters and displays active alarms for the PDU. Active alarm screens
have priority over other screens. When an alarm occurs, the Active Alarms screen
replaces the current screen and the backlight blinks. On the Main Menu, scroll down to
highlight Alarms. Press Select to display the first active alarm screen. Scroll down if
needed to view active alarm data. When you finish your review, press Menu to return to
the main menu. If the backlight was blinking red to indicate an active alarm, the
backlight returns to normal.
SMARTZONE G5 USER MANUAL
46
.
Power Menu
The Power menu manages device, phase, breaker and outlet. On the Main Menu, scroll
down to highlight Power. Press Select. Scroll down to select a submenu and press
Select to display the submenu options. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
47
Device Submenu
The Device submenu is to display current, voltage and power. On the Power menu,
scroll down to highlight Device. Press Select to display the screens to set the values for
the submenu. Press Menu to return to the previous menu.
Phase Submenu
The Phase submenu is to display the status of 3-Phase. On the Power menu, scroll
down to highlight Phase. Press Select to display the screens to set the values for the
submenu. After you select the values, press Select to set the values as displayed on
the screen. Press Menu to return to the previous menu.
SMARTZONE G5 USER MANUAL
48
Breaker Submenu
The Breaker submenu is to display breakers quantities of single phase (1-Phase) or
three phase (3-Phase) PDUs. On the Power menu, scroll down to highlight Breaker.
Press Select to display the screens to set the values for the submenu. After you select
the values, press Select to set the values as displayed on the screen. Press Menu to
return to the previous menu.
SMARTZONE G5 USER MANUAL
50
Outlet Submenu
The Outlet submenu is to display voltage, current and power from serial number 1 to
number n. On the Power menu, scroll down to highlight Outlet. Press Select to display
the screens to set the values for the submenu. After you select the values, press Select
to set the values as displayed on the screen. Press Menu to return to the previous
menu.
Sensors Menu
The Sensor menu is to display temperature, humidity, door switch, fluid leak etc. On the
Main Menu, scroll down to highlight Sensor. Press Select. Scroll down to select a
submenu and press Select to display the submenu options. Press Menu to return to the
previous menu.
SMARTZONE G5 USER MANUAL
51
NOTE: Maximum of 4 sensors are configured per PDU.
G5 iPDU Outlet Power Sequence Setup
1. From the PDU GUI Home menu select Control & Manage.
SMARTZONE G5 USER MANUAL
53
3. For each Outlet select the Edit pencil.
4. In the Edit Outlet window enter the Delay time (0-7200 seconds) then select
Save.
SMARTZONE G5 USER MANUAL
55
Section 7 – Daisy Chain Configuration
Daisy-Chain Overview
In daisy chain mode, up to four (4) PDUs can be connected via one (1) IP address. This
allows users to gather information and data on all daisy-chained PDUs from the master
PDU. The daisy chain functionality reduces network cost for PDUs. For example, a
standard network switch used in a data center may contain 24 ports. Without using the
daisy chain function, each port would supply network connection to one (1) PDU.
However, if using the daisy chain features, a typical network switch with 24 ports can
supply network connections for up to 96 PDUs.
Daisy-Chain Setup Connecting up to 4 PDUs of the same
SKU through a single IP address:
1. After the initial PDU is configured, connect an Ethernet cord from the RS485-2
port on the configured PDU to the Serial+RS485-1 port on the second PDU in the
daisy chain line.
2. Repeat step 2, connecting PDUs from the RS485-2 port to the Serial+RS485-1
port for up to 4 PDUs.
NOTE: The total length of the Ethernet cords connecting the PDUs must be less than
15m (49 ft.).
3. Go to the Web interface (or management software) to manage and control the
PDUs in the daisy chain.
How to cable for daisy-chain:
1. Locate a CAT-5 cable. Connect one end of the cable to one PDU. Connect the
other end of the cable to the other PDUs. See Figure 3 for the location on the
front panel of each model type.
SMARTZONE G5 USER MANUAL
56
Figure: How to connect cables for daisy-chain, max 4 PDUs can be connected.
2. Monitor the PDUs with the Web interface or SNMP.
RNA (Redundant Network Access) Functionality
RNA allows for secure access of PDU data and statistics on 2 separate, private
networks. RNA must be used with a redundant power delivery design including two rack
PDUs for each IT rack. PDUs used in RNA applications must be the same SKU.
How it Works
• Using RNA, the Master and Slave maintain two separate private networks that do
not overlap.
• RNA works using a redundant power delivery design (i.e., two rack PDUs for
each IT rack).
• Each PDU is separately connected to the Slave or Master’s private
communications network.
• The two PDUs are connected with a data communications bus to allow PDUs to
share user-defined information.
• Each PDU acts like a master PDU to report PDU data to both networks.
SMARTZONE G5 USER MANUAL
57
RNA Setup
To setup RNA mode on two PDUs, the user must (1) configure the PDUs for RNA Mode
(using CLI) and then (2) connect the LAN Network cords and Ethernet cords between
PDUs
To Configure RNA Mode in the CLI
1. Login to the CLI and enter the command ‘dev daisy dna.’
2. The following message will appear:
• Reboot Required for change to take effort.
• System Reboot now, Are you sure? (Y/N)
3. Enter Y to confirm reboot.
4. After reboot, the PDU will be setup to RNA Mode.
5. Repeat this process for the second PDU.
To Connect the PDUs for RNA Setup
After the PDUs are configured for RNA:
1. Connect an Ethernet cable from the Landlord LAN Network to the Ethernet port
of the first PDU. This will have limited access/permissions.
2. Connect an Ethernet cable from the Tenant LAN Network to the Ethernet port of
the second PDU. This will have full access to both PDUs.
3. Connect an Ethernet cable from the Serial+Rs485-1 port on first PDU to the
RS485-2 port on the second PDU.
4. Connect another Ethernet cable from the Rs485-2 port on the first PDU to the
Serial+Rs485-1 port on the second PDU.
5. In RNA mode, the default account username is ‘landlord’ and password is
‘12345678’. This account is configured for proper access and control in RNA
mode.
6. To enable this account, login to the CLI with admin credentials.
7. Enter the command ‘dev daisy dna init’.
8. The following message will appear to confirm the landlord account is enabled:
SUCCESS.
SMARTZONE G5 USER MANUAL
59
Section 8 – Connecting and Configuring Optional
Hardware
Accessory Hardware Overview
Panduit G5 Monitored, Switched, Monitored per Outlet, and Monitored & Switched per
Outlet PDUs can monitor environmental conditions of a rack with the addition of optional
SZ G5 environmental sensors. Conditions such as temperature, humidity, leak
detection, and intrusion can be monitored with the sensors. These are all vital aspects
of maintaining an efficient-working data center atmosphere. Users and administrators to
can monitor the status, view reports, and alarms of specific conditions in and around a
PDU, and server rack. (Note, only SZ G5 type sensors work with the SZ G5 iPDU
controller)
The following sensors are available:
• Environmental Temperature Sensor
• Environmental Temperature and Humidity Sensor
• Environmental 3-Temperature + 1-Humidity Sensor
• Open/Close Door Contact Sensor
• Leak Detection Sensor
• Sensor Port Hub
• Leak Detection Sensor Extension
Sensor
Description
Sensor Measurement
Temperature Sensor
Monitors the temperature
in the rack.
1
Temperature and Humidity
Sensor
Monitors the temperature
and relative humidity in the
rack.
2
3-Temperature + 1-
Humidity Sensor
Monitors the temperature
in three areas using three
separate probes and the
relative humidity using one
probe.
4
SMARTZONE G5 USER MANUAL
60
Sensor
Description
Sensor Measurement
Open/Close Door
Sends an alarm or
notification when a door on
which the sensor is
installed has been opened
more than 10 mm.
1
Rope Fluid Leak Sensor
Monitors for early detection
of liquid with a resistivity of
less than 2MOhms
(including distilled water) in
the monitored area. The kit
includes a 6m rope and
optional additional ropes
can be added with an
option.
1
Sensor Port Hub
Allows for up to three
environmental sensors to
be connected to the PDU.
N/A
Leak Detection Sensor
Extension
The kit includes one
additional 6m length rope
to pair with the leak
detection sensor. A total of
four extensions can be
added to the leak detection
sensor for a total length of
30m.
N/A
The optional environmental sensors can be installed before or after completing the PDU
installation, startup, and can be installed without turning off power to the PDU or the
devices connected. Panduit G5 Monitored, Switched, Monitored per Outlet, and
Monitored & Switched per Outlet PDUs are designed to collect a maximum of eight
environmental sensor measurements per PDU. For example, the Environmental 3-
Temperature + 1-Humidity Sensor collects four sensor measurements. See the table
above for the sensor measurement collected from each environmental sensor.
All Panduit G5 PDUs have two physical sensor ports, and each PDU can collect a total
of eight sensor measurements (or readings). For example, if a PDU has an Open/Close
Door Sensor and an Environmental 3-Temperature + 1-Humidity Sensor connected,
SMARTZONE G5 USER MANUAL
61
both physical sensor ports are used with a total of five sensor measurements recorded.
Up to six physical sensors can be supported per PDU with the addition of the optional
sensor port hub
Figure: Sensor Ports for vertical PDU
SMARTZONE G5 USER MANUAL
62
Figure: Sensor Ports for Horizontal PDU
Connecting a Temperature Sensor
The temperature sensor can be placed on the front or rear door of the rack.
1. Secure the sensor to the perforated area on the rack enclosure door by threading
the cable tie provided through the recessed channel in the sensor box and
through the door.
2. Secure the RJ45 cable along the desired path to the PDU using the remaining
cable ties.
3. Use the RJ45 quick disconnect coupler and an Ethernet cable to extend the
length of the sensor input cable and/or to serve as an easy disconnect point for
the rack door removal.
4. Plug the sensor cable (or the connected Ethernet cable) into the Sensor-1 or
Sensor-2 port on the PDU or into the sensor port hub (if applicable).
SMARTZONE G5 USER MANUAL
63
Connecting a Temperature and Humidity Sensor
This sensor can be placed on the front or rear door of the rack—it reads the
temperature and humidity at the same location.
1. Secure the sensor to the perforated area on the rack enclosure door by threading
the cable tie provided through the recessed channel in the sensor box and
through the door.
2. Secure the RJ45 cable along the desired path to the PDU using the remaining
cable ties.
3. Use the RJ45 quick disconnect coupler and an Ethernet cable to extend the
length of the sensor input cable and/or to serve as an easy disconnect point for
the rack door removal.
4. Plug the sensor cable (or the connected Ethernet cable) into the Sensor-1 or
Sensor-2 port on the PDU or into the sensor port hub (if applicable).
Connecting a 3-Temperature and 1-Humidity Sensor
SMARTZONE G5 USER MANUAL
64
This sensor can be placed on the front or rear door of the rack—it reads the
temperature and humidity at the same location.
1. Secure the sensor to the perforated area on the rack enclosure door by threading
the cable tie provided through the recessed channel in the sensor box and
through the door.
2. Secure the RJ45 cable along the desired path to the PDU using the remaining
cable ties.
3. Secure the two additional temperature probes near the top and the bottom of the
perforated rack enclosure door using the cable ties provided.
4. Use the RJ45 quick disconnect coupler and an Ethernet cable to extend the
length of the sensor input cable and/or to serve as an easy disconnect point for
the rack door removal
5. Plug the sensor cable (or the connected Ethernet cable) into the Sensor-1 or
Sensor-2 port on the PDU.
Connecting a Rope Fluid Leak Sensor
1. Connect the RJ45 jack on the rope fluid leak sensor assembly to a sensor port
on the PDU.
2. Thread the Rope Fluid Leak Sensor cable through the rack and along the desired
path of detection.
3. Secure the Rope Fluid Leak Sensor cable to the rack and ground using the cable
ties and/or adhesive mounting strips provided.
NOTE 1: This kit includes one 6m leak sensor rope. Additional length can be added
using option kit (includes one 6m leak sensor rope extension). Up to four of the 6m
length leak sensor rope extensions can be connected for a total of 30m.
SMARTZONE G5 USER MANUAL
65
NOTE 2: The wire mount, shown below, is for installation on the floor or ground surface.
This MUST be used in the detection area.
NOTE 3: If mounting to a cabinet or wall, use the adhesive-backed mount (provided).
The adhesive-backed mount in the detection area may prevent or delay leakage
notification.
Connecting the Open/Closed Door Sensor
SMARTZONE G5 USER MANUAL
66
This sensor can be placed on the front or rear door of the rack.
1. Adhere magnetic sensor using adhesive strip.
2. Mounting position of the rear door sensor is shown in figure below.
3. Mounting position of sensor on the rear door is shown in the figure below.
4. Stick switch sensor to the inner frame of the rack while aligning it with the
magnetic sensor mounted to the door.
5. Stick switch sensor to rack frame using adhesive. Location can be determined by
the customer, but should be opposite the door hinge.
SMARTZONE G5 USER MANUAL
67
6. Mounting magnetic sensor to the front door. Stick magnetic sensor to inner door
frame aligned with rack sensor using the adhesive strip.
7. Mounting position of sensors to the front door is shown in figure below.
SMARTZONE G5 USER MANUAL
68
Connecting the Sensor Hub
The sensor hub contains four parallel RJ45 ports (labeled 1 through 4 – see illustration
below) for connecting to the PDU and up to three sensors. Any of the RJ45 ports can be
used to connect to the PDU or sensors. The numbered ports help when documenting
which sensor(s) is being used with the PDU.
Figure 4: Sensor Hub Port View
Detecting Environmental Sensors
The sensor serial number is listed in the Web interface when the sensor is detected. To
identify each detected environmental sensor:
1. Open the Dashboard.
2. View the External Sensors section on the Dashboard page.
SMARTZONE G5 USER MANUAL
69
3. In External Sensors, you can see sensor type, name, PDU ID, PDU name and
location.
4. Confirm that the serial number on the sensor device matches the number in the
sensor table.
Configuring Environmental Sensors
To configure the sensor location, alarms, notifications, and details, open the WEB
Interface:
1. Open the Settings.
2. View the Threshold section on the Settings page. Select Threshold to configure
sensors.
a. Go to external sensors.
3. Select Edit button to configure the desired sensors.
4. In the Edit Extension dialog box, type value of up critical, up warning, low
warning, and low critical.
5. Select Save to exit the sensor setup. Repeat this process for additional sensors.
SMARTZONE G5 USER MANUAL
70
Warranty and Regulatory Information
Warranty Information
(http://www.Panduit.com)
Regulatory Information
Safety and regulatory compliance
For important safety, environmental, and regulatory information, see Safety and
Compliance Information at the Panduit website (http://www.Panduit.com)
SMARTZONE G5 USER MANUAL
71
Support and Other Resources
Accessing Panduit Support
• For live assistance, go to the Panduit.com website
• To access documentation and support services, go to the Panduit website.
SMARTZONE G5 USER MANUAL
72
Acronyms and Abbreviations
AC
Alternating Current
KVA
Kilo-volt-ampere
PDU
Power Distribution Unit
iNC
SMARTZONE G5 USER MANUAL
73
Documentation Feedback
Panduit is committed to providing documentation that meets your needs. To help us
improve the documentation, send any errors, suggestions, or comments to
Documentation Feedback ([email protected]). When submitting your feedback, include
the document title, part number, edition, and publication date located on the front cover
of the document. For online help content, include the product name, product version,
help edition, and publication date located on the legal notices page.
SMARTZONE G5 USER MANUAL
74
Appendix A: CLI Commands
Help Commands
Command
Description
Example
Panduit>?
List all available PDU CLI
commands.
Panduit>?
sys PDU system
configure and setting.
net PDU net application
configure and setting.
usr PDU user operation.
dev PDU device setting.
pwr PDU power setting.
System Commands
Command
Description
Example
sys date [year-month-day] Query or set system’s
date.
Panduit>sys date 2013-09-
19
SUCCESS
Panduit>sys date
SUCCESS
Date: 2013-09-19
Time: 03:49:46
sys time [hour:min:sec]
Query or set system’s
time.
Panduit>sys time
Panduit>sys time 14:35:34
sys ntp
Synchronize system date
and time, with ntp server
you set.
>sys ntp 69.25.96.13
NOTE: IP Address must be a
valid ntp, server address
otherwise, executes, failed
SMARTZONE G5 USER MANUAL
75
Command
Description
Example
sys ver
Query system’s version
information including
firmware, bootloader, and
Web.
Panduit>sys ver
SUCCESS
Firmware version: 0.41
Bootloader version: 2.10
LANGUAGE version: 3.01
WEB version: 6.30
sys def
Recover PDU to default
configuration.
Panduit>sys def
SUCCESS
Recover
Press any key to cancel
sys rst
Reset system.
Panduit>sys rst
Reboot required for change
to take effort.
System Reboot now, Are you
sure? (Y/N):Y
sys upd all
Update system’s firmware
with existing pdu bin file.
Panduit>sys upd lan
E801
system will enter upgrade
mode after reboot
System Reboot now, Are you
sure?(Y/N):Y
NOTE 1: There must be a
valid file named Panduit.bin
existing under directory/fw.
NOTE 2: If in daisy chain
configuration, master will
also upgrade its all slave’s
firmware.
sys upd boot
Update system’s
bootloader.
Panduit>sys upd boot
E801
system will enter upgrade
mode after reboot
System Reboot now, Are you
sure?(Y/N):Y
SMARTZONE G5 USER MANUAL
76
Command
Description
Example
NOTE 1: There must be a
valid file named boot.bin
existing under directory/fw.
NOTE 2: If in daisy chain
configuration, master will
also upgrade its all slave’s
bootloader.
sys upd conf
Update system’s
configuration.
Panduit>sys upd conf
E801
system will enter upgrade
mode after reboot
System Reboot now, Are you
sure?(Y/N):Y
NOTE: There must be a valid
file named conf.ini existing
under directory/fw.
sys log del event
Delete event log file.
Panduit>sys log del event,
SUCCESS
sys log edit data [on
[interval] | off]
sys log del data
Delete data log file.
Panduit>sys log del data,
SUCCESS
Panduit>
Network Commands
Command
Description
Example
net ssh [on/off]
Query or on/off SSH.
Panduit>net ssh
SUCCESS,
SSH Port: 22
SSH Server is running
Panduit>net ssh on
SUCCESS
Panduit>net ssh off
SUCCESS
SMARTZONE G5 USER MANUAL
77
Command
Description
Example
net ftps [on/off]
Query or on/off FTPs.
Net ftps
SUCCESS
FTPS Port: 21
Service is running
Is Ftps
net http [on/off]
Query or on/off net http.
Panduit>net http
SUCCESS,
HTTP Port: 80
HTTPS Port: 443
WEB Protocol: HTTP
Panduit>net http off
E801
WEB protocol is changed,
Please reboot to validate
System Reboot now, Are
you sure?(Y/N):Y
net mac
Query MAC address.
Panduit>net mac
SUCCESS
MAC Addr: C8-45-44-66-
2B-26
net tcpip
Query network's IP
information.
Panduit>net tcpip
SUCCESS
IPv4 Addr: 192.168.30.39
net tcpip
Set network to dhcp mode.
Panduit>net tcpip dhcp
E801
Network is reconfigured,
Please reboot to validate
System Reboot now, Are
you sure?(Y/N): Y
net tcpip
Set static IP, mask and
gateway.
Panduit>net tcpip static
192.168.30.39
255.255.255.0
192.168.30.1
E801
Network is reconfigured,
Please reboot to validate
SMARTZONE G5 USER MANUAL
78
Command
Description
Example
System Reboot now, Are
you sure?(Y/N): Y
User Commands
Command
Description
Example
User List
List all users account
existing.
Panduit>usr list
SUCCESS
Usr Role
-------------------------
admin admin
user user
User unlock
Unlock specified user.
Panduit>usr unlock user
SUCCESS
Panduit>usr unlock admin
SUCCESS
NOTE: 1. Account would
be locked temporarily if
login failure excess
“Maximum number of
failed logins”. Use this
command to unlock it.
Device Commands
Command
Description
Example
dev usb [on|off]
Query or on/off USB.
Panduit>dev usb
Panduit>dev usb off
Panduit>dev usb on
dev daisy [dna|qna]
Query or set daisy chain
mode.
Panduit>dev daisy
SUCCESS
daisy chain unit number: 1
daisy chain address list:
000
SMARTZONE G5 USER MANUAL
79
Command
Description
Example
Daisy Mode: DNA
Panduit>dev daisy qna
E801
System Reboot now, Are
you sure?(Y/N): N
dev daisy init
Initialize daisychain.
Panduit>dev daisy qna init
E801
System Reboot now, Are
you sure?(Y/N):N
dev outlet status
Query all outlets' status
with specified PDUID.
Panduit>Dev outlet 1
status
SUCCESS
Relay Outlet Status
Outlet#1: Close Outlet#2:
Close Outlet#3: Close
Outlet#4: Close
Outlet#5: Close Outlet#6:
Close Outlet#7: Close
Outlet#8: Close
Outlet#9: Close Outlet#10:
Close Outlet#11: Close
Outlet#12: Close
NOTE 1: For M pdu, this
command is in valid.
NOTE 2: PDUID index
from 1; if in daisy chain,
the master's PDUID is 1,
others is ,2,3,
dev outlet
[on|off]
Query or set specified
PDUID and outlet-index's
outlet status.
Panduit> dev outlet 1 1 off
SUCCESS
NOTE: For Monitored
PDUs, this command is
invalid.
dev sensor
List all sensors equipped.
Panduit> dev sensor
SUCCESS
SMARTZONE G5 USER MANUAL
80
Command
Description
Example
Sensor count 4
------------------------
Name Type, SN Value
-------------------------
T1,TEMP 012345678 27.5
T3,TEMP 012345678 27.2
T2,TEMP 012345678 27.3
RH HUMI 012345678 44
dev ver
Query
sensor/power/delay's
firmware version.
Panduit> dev ver 1
Panduit> dev ver 15
Panduit> dev ver 35
NOTE: relay: start from 1
power: start from 15
sensor: start from 35
Power Commands
Command
Description
Example
pwr unit [idx]
Query device information,
Query specified index
unit’s electric information.
Panduit> pwr unit
SKU: P9S20A , , , ,
Serial: , , , , ,
FuncType: PDU Monitored
Rating :220-240V, 16A,
3.5-3.8kVA, 50/60Hz
Mac :C8:45:44:66:2B:26
Tcpip :192:168:30:38
Panduit>pwr unit 1
SUCCESS
PDU UNIT 1 power
Feature
voltage: 0V
current : 0.0A
active power: 0W
apparent power: 0W
SMARTZONE G5 USER MANUAL
81
Command
Description
Example
power factor: 0.00
energy: 0.000kWh
pwr phase [idx]
Query specified phase’s
electric information.
Panduit> pwr phase 1
SUCCESS
PDU PHASE 1 power
Feature
voltage: 0V
current : 0.0A
active power: 0W
apparent power: 0W
power factor: 0.00
energy: 0.000kWh
pwr cb [idx]
Query specified circuit
breaker’s
Electric information.
Panduit> pwr cb 1
SUCCESS
PDU CB 1 power Feature
voltage: 0V
current : 0.0A
active power: 0W
apparent power: 0W
power factor: 0.00
energy: 0.000kWh
pwr outlet [idx]
Query specified outlet’s
electric information.
Panduit> pwr outlet 1
SUCCESS
PDU OUTLET 1 power
Feature
voltage: 0V
current : 0.0A
active power: 0W
apparent power: 0W
NOTE: For Monitored
PDUs, this command is
invalid.
SMARTZONE G5 USER MANUAL
82
Appendix B: Firmware Update Procedure
USB Method
1. Go to www.Panduit.com and download the most recent Firmware version,
‘Panduit.FW’. Save this file to a USB drive.
2. Insert the USB drive into the USB port of the Intelligent Network Controller.
3. Enter USB mode on the PDU: Press Select. Go to Setup>USB>Yes. Select Yes
to confirm entering USB mode.
4. Select F/W Up>Yes to upload the new Firmware.
5. The OLED will show the Firmware update progress.
6. When the update is complete, remove the USB.
7. From the USB Menu, select Quit to exit USB mode. Select Yes to confirm exit.
8. The PDU will automatically reboot.
9. To confirm that the Firmware was uploaded successfully, go to
Setup>Device>Firmware.
Web Interface Method
1. Open the User interface in a web browser by entering the PDU IP address.
2. Login to with Administration credentials.
3. Go to System Management >Update Firmware.
4. In the Firmware Update dialog box, browse to Panduit.FW firmware file.
SMARTZONE G5 USER MANUAL
83
NOTE: the firmware file must be named Panduit.FW or Panduitvxx.FW.
5. Select Upload. The system will update the newest firmware to the Intelligent
Network Controller.
SMARTZONE G5 USER MANUAL
84
6. When the upload is finished, the system will reboot automatically.
Serial (Command Line Interface) Method
To access a PDU, directly connect to serial connection.
1. Copy the Panduit.fw file in /(root) directory using ftp.
2. Connect to the PDU via Serial using hypertrm. Press Enter.
3. Login by using a role with administration privileges.
4. Enter the command: sys upd all
5. The CLI will show the message: Success
6. It will show the message: System will enter upgrade mode after reboot, System
Reboot now, Are you sure? (Y/N)
7. Enter: Y
8. When the upgrade is finished, the system will reboot automatically.
SMARTZONE G5 USER MANUAL
85
FTPs Method
To access a PDU using a FTPs program, FTPs must be enabled through the PDU Web
Interface or CLI. In the Web Interface, go to Network Settings >SSH/FTPs
Configuration. Select the check box to enable FTPs Access. In the CLI, login as an
administrator and use the command net tcpip FTPs open
1. Login to a FTPs program with a role with administration privileges.
2. Transfer the updated Panduit.fw file to the folder labeled fw. Close the FTPs.
3. Connect to the PDU via SSH using a program such as HyperTerm or PuTTY.
4. Login using a role with administration privileges.
5. Enter the command sys upd all.
6. It will show the message: System will enter upgrade mode after reboot, System
Reboot now, Are you sure? (Y/N).
7. Enter Y.
8. When the upload is finished, the system will reboot automatically. It is not always
required to update Web or Bootloader files when the Firmware is updated.
However, a user can upload these file types in SSH:
a. Login to a FTPs program.
b. Overwrite the outdated files with the updated web files (found on the
customer login at www.Panduit.com or from your regional sales manager).
Bootloader Mode
1. Go to www.Panduit.com and download the most recent Firmware version,
‘Panduit.bin’. Save this file to a USB drive.
2. Insert the USB drive into the USB port of the Intelligent Network Controller.
3. Enter USB mode on the PDU: Press Select. Go to Setup>USB>Yes. Select
Yes to confirm entering USB mode.
4. Select F/W Up>Yes to upload the new Firmware.
5. The OLED will show the Firmware update progress.
6. When the update is complete, remove the USB.
SMARTZONE G5 USER MANUAL
86
7. From the USB Menu, select Quit to exit USB mode. Select Yes to confirm
exit.
8. The PDU will automatically reboot.
9. To confirm that the firmware was uploaded successfully, go to
Setup>Device>Firmware.
Firmware Recovery with Bootloader Mode
Firmware, configuration files, and bootloader files can be updated following the steps
above, but each update type must be done separately. Web files can be updated in
conjunction with any of the other updates. I.e., a user can update Firmware and Web
files in a single step. But firmware and configuration files must be done separately.
Upgrade Configuration with Bootloader Mode
To make the PDU accessible through the USB port on the unit, you must:
1. Go to Device Configuration > USB Settings.
2. Select the Enable USB Access Checkbox.
To upload configuration, you must:
1. Copy conf.ini to USB.
2. Insert USB to PDU.
3. Enter USB mode in OLED device.
4. Select Conf up.
5. After the operation is completed, remove USB, and quit USB mode.
SMARTZONE G5 USER MANUAL
87
Appendix C: PDU Alarms
PDU Unit
PDU Unit Active Power Above upper
critical
PDU Unit Active Power Above upper
warning
PDU Unit Active Power Below lower
warning
PDU Unit Active Power Below Lower
critical
Input Phase
Input Phase X Voltage Above upper
critical
Input Phase X Voltage Above upper
warning
Input Phase X Voltage Below lower
warning
Input Phase X Voltage Below lower critical
Input Phase X Current Above upper critical
Input Phase X Current Above upper
warning
Input Phase X Current Below lower
warning
Input Phase X Current Below lower critical
Circuit Breaker
Circuit Breaker X Current Above upper
critical
Circuit Breaker X Current Above upper
warning
Circuit Breaker X Current Below lower
warning
Circuit Breaker X Current Below lower
critical
Circuit Breaker Status ON
Circuit Breaker Status OFF
Outlet
Outlet X Active Power Above upper critical
Outlet X Active Power Above upper
warning
Outlet X Active Power Below lower
warning
Outlet X Active Power Below lower critical
SMARTZONE G5 USER MANUAL
88
Outlet X Immediate ON
Outlet X Delayed ON
Outlet X Immediate OFF
Outlet X Delayed OFF
Outlet X Immediate REBOOT
Outlet X Delayed REBOOT
Outlet X Cancel Pending Command
External Sensor
External Sensor X (numerical) Above
upper critical
External Sensor X (numerical) Above
upper warning
External Sensor X (numerical) Below
lower warning
External Sensor X (numerical) Below
lower critical
External Sensor X (state) Alarmed
External Sensor X (state) Communication
Lost
System
System Event log Cleared
System Data log Cleared
System PDU configuration file Imported
System PDU configuration file Exported
System Firmware update completed
System Firmware update failed
System Firmware update started
System Firmware Validation failed
System an LDAP error occurred
System Network interface link state is up
System Sending SMTP message failed
System Intelligent Network Controller reset
System Intelligent Network Controller start
System Communication Lost
Daisy Chain state changed
USB Port
User Activity
User Activity User X Authentication failure
User Activity User X User logged in
User Activity User X Session timeout
User Activity User X User blocked
SMARTZONE G5 USER MANUAL
89
User Administration
User Administration Password changed
User Administration Password settings
changed
User Administration User added
User Administration User deleted
User Administration User modified
Trap Codes assigned to Alarms List
Trap codes assigned for critical alarms:
Trap Class Trap Code
Trap Description
Critical
1
The PDU unit active power is ABOVE critical threshold value.
2
The PDU unit active power is BELOW critical threshold value.
3-5
The phase (1-3) voltage is ABOVE critical threshold value.
6-8
The phase (1-3) voltage is BELOW critical threshold value.
9-11
The phase (1-3) current is ABOVE critical threshold value.
12-14
The phase (1-3) current is BELOW critical threshold value
15-26
The circuit breaker (1-12) current is ABOVE critical threshold
value
27-38
The circuit breaker (1-12) current is BELOW critical threshold
value
39-50
The circuit breaker (1-12) is in OFF state
51-98
The outlet (1-48) active power is ABOVE critical threshold
value
99-146
The outlet (1-48) active power is BELOW critical threshold
value
SMARTZONE G5 USER MANUAL
90
147-154
The sensor (1-8) temperature/humidity is ABOVE critical
threshold value
155-162
The sensor (1-8) temperature/humidity is BELOW critical
threshold value
163-170
The sensor (1-8) contact state is in alarm.
183
User authentication failed.
186
Power or relay communication lost to main board
193
Firmware update failed.
Trap codes assigned for warning alarms:
Trap Class Trap
Code
Trap Description
Warning
200
The PDU unit active power is ABOVE warning threshold
value.
201
The PDU unit active power is BELOW warning threshold
value.
202-204
The phase (1-3) voltage is ABOVE warning threshold value.
205-207
The phase (1-3) voltage is BELOW warning threshold value.
208-210
The phase (1-3) current is ABOVE warning threshold value.
211-213
The phase 1 current is BELOW warning threshold value.
214-225
The circuit breaker (1-12) current is ABOVE warning
threshold value.
226-237
The circuit breaker (1-12) current is BELOW warning
threshold value.
238-249
The circuit breaker (1-12) is in OFF state.
SMARTZONE G5 USER MANUAL
91
250-297
The outlet (1-48) active power is ABOVE warning threshold
value.
298-345
The outlet (1-48) active power is BELOW warning threshold
value.
346-353
The sensor (1-8) temperature/humidity is ABOVE warning
threshold value.
354-361
The sensor (1-8) temperature/humidity is BELOW warning
threshold value.
Trap codes assigned for information alarms:
Trap Class
Trap
Code
Trap Description
Informational
380-391
The circuit breaker (1-12) is in ON state.
392-439
The outlet (1-48) IMMEDIATE ON occurred.
440-487
The outlet (1-48) DELAYED ON occurred.
488-535
The outlet (1-48) IMMEDIATE OFF occurred.
536-583
The outlet (1-48) DELAYED OFF occurred.
584-631
The outlet (1-48) IMMEDIATE REBOOT occurred.
632-679
The outlet (1-48) DELAYED REBOOT occurred.
680-727
The outlet (1-48) Cancel Pending Commands occurred.
728-735
The sensor (1-8) contact state is in cleared.
740
Event log Cleared.
741
Data log Cleared.
742
PDU configuration file Imported.
SMARTZONE G5 USER MANUAL
92
743
PDU configuration file Exported.
744
Firmware update completed.
745
Firmware update started.
746
An LDAP error occurred.
747
Network interface link state is up.
748
Communication Module reset.
749
Communication Module start.
750
Daisy Chain state changed.
751
USB Port Enabled
752
User xxx logged in.
753
User xxx session timeout.
754
User xxx blocked.
755
User xxx password changed.
756
User password settings changed.
757
User xxx added.
758
User xxx deleted.
759
User xxx modified.
Trap codes assigned for information alarms:
Trap Class Trap
Code
Trap Description
Clear
770
The PDU unit active power is alarm clear.
771-773
The phase (1-3) voltage alarm cleared
774-776
The phase (1-3) current alarm cleared
SMARTZONE G5 USER MANUAL
93
777-788
The circuit breaker (1-12) current alarm cleared
789-836
The outlet (1-48) active power current alarm cleared.
837-844
The sensor (1-8) temperature/humidity alarm cleared.
SMARTZONE G5 USER MANUAL
94
Appendix D: Horizontal Intelligent Network
Controller Replacement
1. Unscrew the left and right captive nuts on the Intelligent Network Controller by
turning them counter clockwise.
2. Pull out the Intelligent Network Controller from the PDU.
SMARTZONE G5 USER MANUAL
95
3. Insert the new Intelligent Network Controller.
4. Align the Intelligent Network Controller and tighten the captive nuts by turning
them clockwise.
SMARTZONE G5 USER MANUAL
96
Appendix E: Vertical Intelligent Network
Controller Replacement
1. Use a T10 Torx screwdriver to remove the top and bottom screws from the
Intelligent Network Controller.
2. Disconnect the existing signal wire from the Intelligent Network Controller.
Connect the signal wire to the new Intelligent Network Controller.
SMARTZONE G5 USER MANUAL
97
3. Replace and tighten the two screws on the replacement Intelligent Network
Controller into the PDU.
Signal wire