Red Arrow Trading LFACLED502F Installation Instructions
Text of the manual
LED Maintained Emergency
Recessed Fitting
Installation Instructions p.1
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
T: 0800 195 0006 F: 0870 043 3946
E: [email protected] www.redarrowtrading.com
For models: LFACLED502F
Specification
• 220-240V
• 2.5W Wattage
• 6.5W Power consumption
• 50pcs of Ø5 LED
• 297 Lumen output (201lm in emergency mode)
• 6000-7000K Colour temperature
• > 3 Hours emergency duration
• 24 Hours charging time
This installation must be carried out by an electrician.
Please read these instructions carefully before installation.
Leave a copy for the user/maintenance engineer for future reference.
ENSURE FITTING IS CHARGED FOR A MINIMUM OF 24
HOURS PRIOR TO TESTING.
Installation
1. Remove the diffuser from the body by removing the two
screws.
2. Release gear tray by removing the two retaining screws.
3. Cut out hole for fitting, 120 x 340mm, in the ceiling tile.
4. ISOLATE THE A.C. SUPPLY and connect unit. An
unswitched 240V A.C. supply must be connected to the Live
(L). Earth and Neutral (N) terminals on the PCB block. On
Maintained circuits continuous illumination can be achieved
by connecting a link between L and Lsw either locally or
through a remote switch.
5. Place the fitting into the hole and screw the arm screws so
that the arms are fully down.
6. Allow the fitting to rest on the arms.
7. Plug battery lead into connector on the PCB.
8. Locate the bezel under the fitting and secure using the 2
long screws supplied.
9. Re-secure the gear tray into the base of the unit making
sure that the mains cable is not trapped by the PCB etc.
10. Operational check - restore the A.C. supply for 30 minutes
and then remove. The LEDs should illuminate for at least
10 seconds.
11. Restore the A.C. supply and check that the indicator LED
is ‘on.’
Quick Guide
1.
2.
3.
T: 0800 195 0006 F: 0870 043 3946
E: [email protected] www.redarrowtrading.com
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
LED Maintained Emergency
Recessed Fitting
Installation Instructions p.2
For models: LFACLED502F
4.
5.
6.
Operation
Non-Maintained
Lamp normally off and battery on automatic charge (LED ‘on’) when A.C. supply is healthy. Solid state circuitry
automatically switches lamp on when A.C. supply is interrupted.
Maintained
Emergency lamp normally on, when the supply to Lsw is switched on. The battery is on automatic charge (LED ‘on’). Lamp
will switch on or remain on if A.C. supply is interrupted.
Monitoring
Green indicator lamp (LED) normally continuously ‘on’. Indicator lamp goes out if A.C. supply or charger fails.
Battery
Sealed Nickel-Cadmium rechargeable battery pack.
Temperature
Performance figures measured at 25 degrees C.
Fault Finding and Corrective Action
Monitoring LED Not Illuminated
A.C. supply not healthy. Battery not connected. Charger failed.
Unit Not Meeting Required Emergency Period
May need cycling: Discharge then recharge for 24 hours. Re-test, battery pack may need replacing if emergency duration still
not met.
LED Maintained Emergency
Recessed Fitting
Installation Instructions p.3
For models: LFACLED502F
T: 0800 195 0006 F: 0870 043 3946
E: [email protected] www.redarrowtrading.com
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
LEDs Not Fully Illuminated
If the LEDs are not illuminated check connections & if correct either the battery pack or (less likely) the printed circuit
board needs replacing.
RECOMMENDED ROUTINE TEST PROCEDURE
The following test is designed to ensure the continued protection of your premises and occupants. Because of the
possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should whenever
possible, be undertaken at times of least risk, e.g. during daylight hours.
ONCE A DAY
Visual inspection of battery charge led.
ONCE A MONTH
Each unit should be energised from it’s battery for adequate time to ensure, by simulation of a failure of the normal
lighting supply, the emergency mode is functioning correctly.
ONCE A YEAR
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specified
time period. Clean the internal and external surface of the diffuser.
Month
Test
Year 1
Year 2
Year 3
Year 4
Year 5
signed
date
signed
date
signed
date
signed
date
signed
date
1
Functional
2
Functional
3
Functional
4
Functional
5
Functional
6
1 hour
7
Functional
8
Functional
9
Functional
10
Functional
11
Functional
12
1 hour
3 hour
Guarantee
This product is guaranteed for a period of 1 year from the date of purchase. The guarantee is invalid in the case of improper use, tampering, removal of the Q.C. date label, installation in
an improper working environment or installation not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is also invalidated if the luminaire has
been Mega tested. Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept
responsibility for any installation costs associated with the replacement of this product. We reserve the right to alter specifications without prior notice.
Product complies with
all relevant European
standards
Product is suitable for
mounting on flammable
material
F