Samson TROVIS 5572 Mounting And Operating Instructions
Text of the manual
Automation System TROVIS 5500
Room Controller
TROVIS 5572
Mounting and
Operating Instructions
EB 5572 EN
®
Electronics from SAMSON
Firmware version 1.10
Edition February 2007
all-guides
com
Disclaimer of liability
We are constantly developing our products and therefore, reserve the right to change the prod-
uct or the information contained in this document at any time without notice.
We do not assume any liability for the accuracy or completeness of these mounting and operat-
ing instructions. Moreover, we do not guarantee that the buyer can use the product for an in-
tended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for
compensation including lost profits or any other financial loss, except the damage was caused
intentionally or by gross negligence. If an essential term of the contract is breached by negli-
gence, SAMSON’s liability is limited to the foreseeable damage.
Safety instructions
The device may only be assembled, started up or operated by trained and
experienced personnel familiar with the product.
Proper shipping and appropriate storage are assumed.
2
EB 5572 EN
Disclaimer of liability
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1
Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2
Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3
Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4
Programming the time schedule . . . . . . . . . . . . . . . . . . . . . 8
1.5
Selecting the operating mode (presence button) . . . . . . . . . . . . . 9
1.6
Changing temperature set points temporarily . . . . . . . . . . . . . . 10
2
Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1
Activate/deactivate functions . . . . . . . . . . . . . . . . . . . . . 11
2.2
Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3
Calibrating the room sensor . . . . . . . . . . . . . . . . . . . . . . 13
2.4
Checking inputs and outputs . . . . . . . . . . . . . . . . . . . . . . 14
2.5
Reset to default settings . . . . . . . . . . . . . . . . . . . . . . . . 15
3
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1
Heating functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.1
Window contact
. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.2
Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1.3
Vacation period. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2
Cooling functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.1
Window contact
. . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.2
Dew point monitoring . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3
Operating mode override . . . . . . . . . . . . . . . . . . . . . . . 18
3.4
Summer time/winter time changeover . . . . . . . . . . . . . . . . . 18
3.5
Key lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6
Switching outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6
Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 23
7
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.1
Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2
Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.3
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
EB 5572 EN
3
Contents
EB 5572 EN
Arrow keys
(scrolling, changing)
Reset key
Default settings
Enter key (selecting,
confirming)
Radio tower key
(Communication parameter level, test)
Thermometer key
(Control parameter level)
Data sheet key
(configuration level)
Changeover key (short = 1 s)
(time, date, time schedules)
Changeover key (long = 5 s)
(Set points parameter level)
Presence button
(Operating mode: Automatic – Time-of-use – Outside time-of-use)
The room controller is ready for use after performing the connections (section 6) and start-up
(section 2).
1.1
Operating elements
Operating elements when cover is closed
Arrow keys (up and down keys)
Used to select displays and parameters
Manual key
Without any function
Additional operating elements accessible with the cover open
Enter key
Used to confirm a selection or setting
Changeover key
Key pressed for approx. 1 sec.: Open controller time and programmed time
schedule
Key pressed for approx. 5 sec.: Open Set points parameter level (only after en-
tering key number)
Presence button
Used to select operating mode (Automatic – Time-of-use – Outside of time-of-use)
Note that you require a pointed object such as a ball-point pen in order to press the follow-
ing recessed keys:
Thermometer key
Used to access Control parameter level (only after entering key number)
Radio tower key
Used to access Communication parameter level (only after entering key number)
Data sheet key
Used to access configuration level (only after entering key number)
Reset key
Used to reset the room controller to its default settings (delivery state)
(only after entering key number)
EB 5572 EN
5
Operation
Information on the current operation appears on the display of the controller during use:
Set point
Large reading
Actual temperature Small reading on the bottom right of the display
The actual temperature reading changes in steps of 0.5 °C.
Operating mode
No icon outside of time-of-use
during time-of-use
in vacation mode
Presence
Arrow points to
indicating that the automatic operating mode has
been interrupted (refer to section 1.5)
Time schedule
,
changes in automatic operating mode depending on the
programmed time schedule: Time-of-use · Outside of time-of-use
Continuous time-of-use (automatic operating mode interrupted)
Continuously outside of time-of-use (automatic operating mode
interrupted)
Communication
failure
blinks on the display
(only when communication is configured, refer to section 4)
Control station
intervention
RC appears on the display
(only when communication is configured, refer to section 4)
Frost protection
Actual temperature (small) blinks on the display when
– Actual room temperature < 5 °C
– Dew-point monitor alarm
– Window contact
Snow flake icon (blinking)
– Actual room temperature < 5 °C
Snow flake icon (constant)
– Dew-point monitor alarm
6
EB 5572 EN
Operation
all-guides
com
Setting the controller time
The correct time and date needs to be set directly after starting up the controller or after the
power supply has been disconnected for more than 24 hours.
How to proceed:
Open the cover.
Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi-
cates that the time can be changed.
Press this key to enter the editing mode.
The time starts to blink.
Enter the correct time.
Confirm the time.
Select date setting.
Press this key to enter the editing mode.
The date starts to blink.
Enter the correct date.
Confirm the date.
Select year setting.
Press this key to enter the editing mode.
The year starts to blink.
Enter the correct year.
Confirm the year.
Exit the parameter level.
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN
7
Operation
Programming the time schedule
Three times-of-use can be programmed for each day of the week within which the controller
regulates the room temperature to the Set point for time-of-use. If a time-of-use is not required,
set the start and stop times of this time-of-use to the identical time.
Parameters
WE
Range of values
Times-of-use Mon to Fri
Times-of-use Sat and Sun
08:00 to 20:00
00:00 to 00:00
00:00 to 24:00 h in steps of 15 minutes
00:00 to 24:00 h in steps of 15 minutes
How to proceed:
Open cover.
Press key briefly (approx 1 s). The time appears on the display.
An arrow on the right of the display at the same level as the changeover key indi-
cates that the time can be changed.
The date appears on the display.
The year appears on the display.
Select time-of-use setting.
The arrow at the top of display points to
.
Reading: 1–7 = daily, 1 = Monday, 2 = Tuesday, …, 7 = Sunday
Press this key to enter the editing mode.
The start time of the first time-of-use appears on the display.
Set the start time (in 15-minute steps).
Confirm the start time.
The stop time of the first time-of-use appears on the display.
Set the stop time (in 15-minute steps).
Confirm the stop time.
The start time of the second time-of-use appears on the display.
Repeat the instructions highlighted in gray to set the second and third times-of-use. After all the
times-of-use have been programmed:
Exit the parameter level.
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
8
EB 5572 EN
Operation
Selecting the operating mode (presence button)
Press
key repeatedly to cycle through the following operating modes:.
Temporary set point settings (see section 1.6) are reset when the operating mode is changed.
Automatic mode
(
during time-of-use, no icon appears outside of time-of-use; ……)
Depending on the programmed time schedule, the controller regulates the room tem-
perature to the Set point for time-of-use during the time-of-use and to the Set point
for outside of time-of-use outside of the time-of-use.
Time-of-use (
; …)
The controller regulates the room temperature to the Set point for time-of-use regard-
less of the programmed time schedule.
Outside of time-of-use (…)
The controller regulates the room temperature to the Set point for outside of
time-of-use regardless of the programmed time schedule.
The duration of the time-of-use and outside of time-of-use operating mode is set in function
block F02:
Function
WE
Configuration
Resetting operating mode
1
F02*
*
F02 - 0: Operating mode settings for continuous time-of-use/outside of time-of-use
F02 - 1: Operating mode settings for time-of-use/outside of time-of-use that applies until the next
time schedule starts when the operating mode changes back to automatic mode
EB 5572 EN
9
Operation
Changing temperature set points temporarily
During the controller operation, the current set point and the actual temperature appear on the
display.
Use the arrow keys to temporarily change the current set point.
The new temporary set point applies until the next time-of-use starts or until the operating mode
is changed, however, eight hours at the maximum.
The following maximum set point shifts apply:
Set point for time-of-use:
±3 °C
Set point for outside of time-of-use:
+8 °C
Set point for vacation mode:
+8 °C
How to proceed:
Change the set point temporarily in steps of 0.5 °C.
Note!
The temporary set point can also be overwritten by a building control station (GLT) when the
communication is active (see section 4).
10
EB 5572 EN
Operation
The changes described in this section concerning controller configuration can only be per-
formed after the valid key number has been entered.
The valid key number is specified on page 27. To prevent unauthorized access to the key num-
ber, tear out or blank out the key number.
2.1
Activate/deactivate functions
A function is activated and deactivated by selecting the associated function block.
The function blocks are listed in section 7.1.
How to proceed:
Open cover.
Press the data sheet key.
Enter key number.
The configuration level is opened.
Select the function block.
Enter the editing mode.
Fb : _ _ blinks.
Activate the function block.
Reading: Fb : _ _ ON
or
Deactivate the function block.
Reading: Fb : _ _ OFF
Confirm setting.
Repeat the instructions highlighted in gray to set further function blocks.
On completing the controller configuration:
Exit the configuration level (or, alternatively, by pressing
).
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 11
Start-up
all-guides
com
Depending on the active functions, not all the parameters that are specified in the parameter
lists in the appendix are accessible (–> section 7.2).
The parameters are arranged in topics in various parameter levels (PA):
PA Set points:
Set points for time-of-use, outside of time-of-use, and
vacation mode
PA Control:
Control parameters
PA Communication:
Device address, Baud rate, sensor calibration, switching
inputs and outputs
How to proceed:
Open cover.
Select required parameter level:
PA Set points (press key approx. 5 sec.)
PA Control
PA Communication
Enter the key number.
The parameter level is opened.
Select parameter.
Enter the editing mode.
The display starts to blinks.
Set parameter.
Confirm setting.
Repeat the instructions highlighted in gray to set other parameters in the opened parameter
level. On completing all the parameter settings:
Exit the parameter level. Use corresponding key depending on the parameter level:
PA Set points
PA Control
PA Communication
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
12
EB 5572 EN
Start-up
Calibrating the room sensor
If the temperature displayed on the room controller (current temperature on the bottom right of
the display) does not match the actual room temperature, the measured temperature of the
room sensor can be changed and reset. On calibration, the currently displayed sensor temper-
ature needs to be changed to match the directly measured room temperature (reference temper-
ature).
Note!
An incorrectly performed calibration leads to the wrong room temperature measurements and
results in incorrect control performance. Use a thermometer with a high degree of accuracy on
measuring the reference temperature.
How to proceed:
Open cover.
Select Communication parameter level.
Enter the key number.
The parameter level is opened.
The device address appears on the display.
The Baud rate appears on the display.
The transmit/receive test appears on the display.
Select correction value for room sensor
Reading: Measured temperature (small); correction value (large)
Enter the editing mode.
The correction value starts to blink.
Set the temperature difference found.
Confirm the temperature difference.
Exit the parameter level (or, alternatively, by pressing
).
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
EB 5572 EN 13
Start-up
Checking inputs and outputs
The current state of the binary inputs, triacs and analog outputs can be displayed in the Com-
munication parameter level. The state of triacs and analog outputs can be changed manually.
How to proceed:
Open cover.
Select Communication parameter level.
Enter the key number.
The parameter level is opened
Press key 4 times.
The state of the binary input BE1 appears:
E1 0 /E1 1 (BE1 open/closed)
Press the key once to change to the next input or output:
• Binary input BE2 · Reading: E2 0/E2 1 (BE 2 open/closed)
• Triac 1 · Reading: A1 0/A1 1 (triac 1 open/closed)
• Triac 2 · Reading: A2 0/A2 1 (triac 2 open/closed)
• Analog output AA1 · Reading: AA1 0 to AA1 100 (0 to 10 V voltage)
• Analog output AA2 · Reading: AA2 0 to AA2 100 (0 to 10 V voltage)
Changing triac/analog output state:
The output triac 1 (A1), triac 2 (A2), analog output AA1 or analog output AA2 ap-
pear on the controller display.
Enter the editing mode.
Close triac (A_ 1) or raise voltage at the analog output.
or
Open TRIAC (A_ 0) or reduce voltage at the analog output.
Exit the parameter level (or, alternatively, by pressing
).
Note!
If no key is pressed within five minutes, the controller display returns to the set point reading.
14
EB 5572 EN
Start-up
Reset to default settings
All parameters and functions can be reset to their default settings.
How to proceed:
Open cover.
Select default setting menu.
Enter the key number.
The default setting menu is opened.
Enter the editing mode.
Press key.
Confirm the reset.
Exit the default setting menu.
EB 5572 EN 15
Start-up
3.1.1 Window contact
The window contact function depends on the state of binary input BE1:
BE1 = 0:
The heating valve is closed.
The heating valve is opened for five minutes every 20 minutes
BE1 = 1:
Control according to the current operating mode.
3.1.2 Optimization
The controller determines the Advance heating time and Cooling down time depending on the
building characteristics.
The Advance heating time is the time required to achieve the room temperature Set point for
time-of-use already when the time-of-use starts. In optimization mode, heating does not start
when the time-of-use starts, but at an earlier point in time instead.
The Cooling down time is the time required to achieve the room temperature Set point for out-
side of time-of-use already when the time-of-use ends. In optimization mode, heating does not
finish when the outside of time-of-use starts, but at an earlier point in time instead.
Note!
Advance heating time and Cooling down time are restricted by the Maximum advance heating
time and Maximum cooling down time parameters respectively.
Function
WE
Configuration
Optimization
0
F03 - 1
Parameters
WE
Parameter level / Range of values
Maximum advance heating time
360 min
PA Set points / 0 to 360 min
Maximum cooling down time
120 min
PA Set points / 0 to 120 min
16
EB 5572 EN
Functions
all-guides
com
3.1.3 Vacation period
During the programmed Vacation period (start and stop), the controller regulates the room tem-
perature to the Set point for vacation mode.
appears on the display.
The Presence alert function (section 3.3) is not active during the programmed vacation period.
Parameters
WE
Parameter level / Range of values
Set point for vacation mode
15 °C
PA Set points / 5 to 30 °C
Vacation schedule
–
PA Set points / –
3.2
Cooling functions
The cooling valve regulates the temperature to the current set point during the time-of-use.
The following applies for outside of time-of-use:
When F04 - 0: No cooling
When F04 - 1: The temperature is regulated to a raised set point. The setback calculated
from the set point for outside of time-of-use during heating is interpreted
as an increase.
Function
WE
Configuration
Cooling
0
F04*
*
F04 - 0: No cooling outside of time-of-use
F04 - 1: Cooling also outside of time-of-use
3.2.1 Window contact
The Window contact function depends on the state of binary input BE1:
BE1 = 0:
The cooling valve is closed.
BE1 = 1:
Control according to the current operating mode.
3.2.2 Dew point monitoring
The dew point monitoring uses the binary input BE2:
BE2 = 0:
Temperature regulated to Set point for outside of time-of-use.
BE2 = 1:
Cooling is interrupted.
Function
WE
Configuration
Function BE2
0
F01 - 1
EB 5572 EN 17
Functions
Operating mode override
The adjusted operating mode override is processed by binary input BE2:
BE2 = 0:
Control according to the current operating mode.
BE2 = 1:
The temperature is regulated to Set point for time-of-use regardless of the
programmed time schedule or operating mode.
Note!
If the vacation mode is set, the setting F01 - 1 has no function; the controller continues to regu-
late the temperature to Set point for vacation mode.
Function
WE
Configuration
Function BE2
0
F01 - 0
3.4
Summer time/winter time changeover
The time changeover is performed automatically on the last Sunday in March at 02:00 h and on
the last Sunday in October at 03:00 h.
Function
WE
Configuration
Summer time/winter time changeover
1
F06 - 1
3.5
Key lock
When this function is active,
,
,
,
and
keys do not have any function.
Just the set point and actual temperature appear on the controller display. Changes to the oper-
ating mode and time schedule and temporary set point changes cannot be made.
Function
WE
Configuration
Key lock
0
F05 - 1
18
EB 5572 EN
Functions
The operating mode of the switching outputs can be selected in the Control parameter level.
Note!
Changes to the control signal that are smaller than the value set in Min. control signal
parameter are not processed.
Parameter
WE
Parameter level / Range of values
Min. control signal
5 %
PA Control / 1 to 100 %
Three-point stepping output (heating only)
The control loop functions with a PI control algorithm. The heating valve reacts to pulses which
the controller issues when a system deviation exists. In particular, the length of the first pulse de-
pends on the size of the system deviation and the selected Gain KP (the pulse length increases
as KP rises). Pulse length and interval time change continuously until the system deviation is
eliminated. The interval between pulses is influenced considerably by the Reset time TN (the in-
terval increases as TN rises). The Valve transit time TY indicates how long the valve needs to
move through the range from 0 to 100 %.
Parameters
WE
Parameter level / Range of values
Switching outputs function
1
PA Control / Select: 1
Gain KP
1.0
PA Control / 0.1 to 100
Reset time TN
180 s
PA Control / 0 to 1000 s
Valve transit time TY1
45 s
PA Control / 0 to 1000 s
2 x On/off PPM (heating and cooling)
The control signals applied at the 0 to 10 V output that exceed the value entered in the Minimum
control signal parameter, are issued as a pulse width modulated signal with the basic frequency
1/TY1 (heating) or 1/TY2 (cooling).
Parameters
WE
Parameter level / Range of values
Switching outputs function
1
PA Control / Select: 2
Valve transit time TY1
45 s
PA Control / 0 to 1000 s
Valve transit time TY2
45 s
PA Control / 0 to 1000 s
EB 5572 EN 19
Functions
2 x On-off thermostat (heating and cooling)
The output signal (AA1 heating, AA2 cooling) of the controller is switched on or off.
A control signal is issued when the temperature exceeds or falls below the set point, depending
on the controlled variable. If the control signal exceeds the Min. Control signal, the on-off ther-
mostat is switched on or off.
Parameter
WE
Parameter level / Range of values
Switching outputs function
1
PA Control / Select: 3
Triac 1 and triac 2 switched according to the time schedule
Both triacs are switched on together depending on the time schedule or the adjusted operating
mode. Both triacs are closed outside of time-of-use.
Parameter
WE
Parameter level / Range of values
Switching outputs function
1
PA Control / Select: 4
Triac 1 switched according to the time schedule, triac 2 switched according the state of
AA2
Triac 1 switches according to the time schedule or adjusted operating mode.
Triac 2 switches on when the control signal for cooling = 100 % and when a system deviation
(cooling demand) continues to exist. Triac 2 functions in sequence to the control signal for cool-
ing, for example, to connect additional cooling equipment. When the temperature reaches the
set point, triac 2 switches off again.
Parameter
WE
Parameter level / Range of values
Switching outputs function
1
PA Control / Select: 5
20
EB 5572 EN
Functions
The serial system bus interface RS-485 enables the TROVIS 5572 Room Controller to communi-
cate with a control system (GLT). A complete control system can be implemented using a suit-
able software to visualize the process and to enable communication.
The operation of the controller requires a constant bus link (data cable). The bus line is designed
in an open ring structure to connect individual control equipment. The data cable is connected
at the end of the bus line to the control station over a RS-485/RS-232 converter (e.g. CoRe 01).
The bus connection range (cable length) is maximum 1200 m. A maximum of 128 devices can
be connected in such a segment. Repeaters must be used (for example, CoRe 01) to regenerate
the signal level over long distances or when more than 32 devices are connected to one bus
line. A maximum of 246 devices can be addressed and connected to a bus with 8-bit
addressing.
Caution!
You are required to follow the relevant standards and regulations applicable to light-
ning and overvoltage protection on installing the controller.
A transmitting and/or receiving test can be initiated in the Communication parameter level:
RC blinking :
Receiving data telegrams from control station (GLT),
on the display
even when they are intended for other controllers
:
Controller transmitting to control station (GLT)
Description of the parameters that need to be set:
The Device address is used to identify the controller. An address may only be assigned once
within a system.
The Baud rate indicates the transfer rate between control system and controller in a bus system.
Functions
WE
Configuration
16-bit addressing
0
F07*
*
F07 - 0: 8-bit addressing
F07 - 1: 16-bit addressing
EB 5572 EN 21
Communication
all-guides
com
Parameter level / Range of values
Device address
000
PA Communication / 0 to 255 ( 8 bit)
0 to 999 (16 bit)
Baud rate
19200
PA Communication / 19200, 9600
Transmitting/receiving test
–
PA Communication / Display: RC/
5
Installation
Note!
The room controller must be mounted at a height of 1.50 m.
Make sure that the operation of the room controller is not affected by heat sources (radiators,
lights, electrical appliances) or by drafts close to doors or windows.
The room controller should not be covered by curtains or any pieces of furniture.
To mount and wire the room controller, remove the housing from the base.
How to proceed:
1.
Press down the tongue on the bottom of the controller and tip the housing section for-
ward to remove it from the base.
2.
Screw the base to the wall.
3.
Connect the wiring as described in section 6.
4.
Push the top of the housing section onto the base and push it down.
22
EB 5572 EN
Installation
The room controller is operated with a 24 V AC power supply.
Terminal assignment
1
Modbus RS-485 (slave)
Connection to the control station (GLT) or
to a Modbus master interface
2
3
0…10 V output 1
4
0…10 V output 2
5
GND for 0…10 V outputs
6
Binary input BE1
7
Binary input BE2
8
GND for binary inputs
9
Power supply 24 V AC
AC 1
10
AC 2 has GND reference
11
Triac output 1
24 V AC, 1 A
12
13
Triac output 2
24 V AC, 1 A
14
15
RS-485; Modbus (master)
Connection to expansion module(s)
16
EB 5572 EN 23
Electrical connection
Function block list
F
Function block
WE
Description
01 Function BE2
0
F01 - 0:
Operating mode override by BE2
F01 - 1:
Dew point monitoring
02 Resetting the operating
mode
1
F02 - 0:
Time-of-use/outside of time-of-use operating
mode setting continuous
F02 -1 :
Time-of-use/outside of time-of-use operating
mode setting that applies until the next time
schedule starts when the operating mode changes
back to automatic mode
03 Optimization
0
F03 - 0:
Function is not active
F03 - 1:
Optimization; calculation of advance heating time
or cooling down time in heating mode
04 Cooling
0
F04 - 0:
Cooling not active outside of time-of-use
F04 - 1:
Cooling also active outside of time-of-use
05 Key lock
0
F05 - 0:
Function is not active
F05 - 1:
Keys (except for recessed keys) are locked
06 Summer time/winter
time changeover
1
F06 - 0:
Function is not active
F06 - 1:
Automatic time changeover
07 16-bit addressing
0
F07 - 0:
8-bit addressing
F07 - 1:
16-bit addressing
24
EB 5572 EN
Appendix
Set points parameter level
Parameter
WE
Description
01 Set point for time-of-use
21 °C
Adjustment range: 5 to 30 °C
02 Set point for outside of
time-of-use
17 °C
Adjustment range: 5 to 30 °C
03 Set point for vacation
mode
15 °C
Adjustment range: 5 to 30 °C
04 Maximum advance
heating time
360 min
Start value for the calculation: 120 min
Can only selected when the optimization function is active
(F03 - 1).
05 Maximum cooling
down time
120 min
Start value for the calculation: 60 min
Can only selected when the optimization function is active
(F03 - 1).
06 Vacation schedule
–
Control parameter level
Parameter
WE
Description
01 Switching outputs
function
1
Option:
1: Three-point stepping output
2: 2 x On/off PPM
3: 2 x On/off thermostat
4: Triac 1 and triac 2 switched according to the time schedule
5: Triac 1 switched according to the time schedule;
Triac 2 switched acc. to the state of triac 1 and AA2
02 Gain KP
1.0
Adjustment range: 0.1 to 100
03 Reset time TN
180 s
Adjustment range: 0 to 1000 s
04 Derivative-action time TV
0 s
Adjustment range: 0 to 1000 s
05 Valve transit time TY1
45 s
Adjustment range: 0 to 1000 s
06 Valve transit time TY2
45 s
Adjustment range: 0 to 1000 s
07 Min. control signal
5.0 %
Adjustment range: 1.0 to 100 %
EB 5572 EN 25
Appendix
Communication parameter level
Parameter
WE
Description
01 Device address
0
Adjustment range: 0 to 255 (8 bit) 0 to 999 (16 bit)
000 = No communication with control station (GLT)
02 Baud rate
19200
Adjustment range: 9600, 19200
03 Transmitting/receiving
test
RC blinks on display on receiving any data telegram from the
control station(GLT), even if they are intended for other con-
trollers
blinks on display for transmitting to the control station
(GLT)
04 Calibrating the room
sensor
0.0
Adjustment range: –9.9 to + 9.9 °C (in steps of 0.1 °C)
05 Read/test BE1
Reading: E1 0 (open), E1 1 (closed)
06 Read/test BE2
Reading: E2 0 (open), E2 1 (closed)
07 Read/test triac 1
Reading/Adjustment range: A1 0 (open), A1 1 (closed)
08 Read/test triac 2
Reading/Adjustment range: A2 0 (open), A2 1 (closed)
09 Read/test AA1
Reading/Adjustment range: AA1 0 (0 V) to AA1 100 (10 V)
10 Read/test AA2
Reading/Adjustment range: AA2 0 (0 V) to AA2 100 (10 V)
26
EB 5572 EN
Appendix
all-guides
com
1 room sensor (internal)
1 presence button (internal)
2 binary inputs for window contact/dew point and operating mode
override
Outputs
2 triac outputs 24 V AC, 1 A
2 outputs 0 to 10 V
Power supply
24 V AC
Interface
Modbus (RS-485)
Environmental conditions
Operation: 0 to 50 °C
Storage, transportation: –10 to 60 °C
95 % rH, not condensing
Degree of contamination
2 according to VDE 0110
Noise immunity
According to EN 61000-6-1
Noise emission
According to EN 61000-6-3
Power consumption
of room controller
Approx. 0.6 VA
Power consumption
of expansion module
Approx. 1 VA
Maximum load for
analog output
Not smaller than 4.7 kΩ
Dimensions in mm
W x H x D
113 x 91 x 30
EB 5572 EN 27
Appendix
Key number:
1732
SAMSON AG · MESS- UND REGELTECHNIK
Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
Internet: http://www.samson.de
EB 5572 EN
2007-02
Terminal assignment (refer to section 6)
Please note:
The room controller is operated with 24 V AC.
Modbus RS-485
to expansion module
RS-485; Modbus (slave)
Connection to the control
station (GLT) or to a
Modbus master interface
0 … 10 V output 1
0 … 10 V output 2
GND for 0 … 10 V outputs
Binary input BE1
Binary inputs BE2
GND for binary inputs
Power supply 24 V AC
AC 1
AC 2 has GND reference
Triac output 1
24 V AC, 1 A
Triac output 2
24 V AC, 1 A
RS-485; Modbus (master)
Connection to expansion
module(s)