Room Controller TROVIS 5572 Mounting and Operating Instructions EB 5572 EN ® Electronics from SAMSON Firmware version 1.10 Edition February 2007 all-guides com

Disclaimer of liability

We are constantly developing our products and therefore, reserve the right to change the prod- uct or the information contained in this document at any time without notice. We do not assume any liability for the accuracy or completeness of these mounting and operat- ing instructions. Moreover, we do not guarantee that the buyer can use the product for an in- tended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence. If an essential term of the contract is breached by negli- gence, SAMSON’s liability is limited to the foreseeable damage. Safety instructions  The device may only be assembled, started up or operated by trained and experienced personnel familiar with the product.  Proper shipping and appropriate storage are assumed. 2 EB 5572 EN Disclaimer of liability

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.1 Operating elements. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.3 Setting the controller time . . . . . . . . . . . . . . . . . . . . . . . . 7 1.4 Programming the time schedule . . . . . . . . . . . . . . . . . . . . . 8 1.5 Selecting the operating mode (presence button) . . . . . . . . . . . . . 9 1.6 Changing temperature set points temporarily . . . . . . . . . . . . . . 10 2 Start-up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.1 Activate/deactivate functions . . . . . . . . . . . . . . . . . . . . . 11 2.2 Changing parameters . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3 Calibrating the room sensor . . . . . . . . . . . . . . . . . . . . . . 13 2.4 Checking inputs and outputs . . . . . . . . . . . . . . . . . . . . . . 14 2.5 Reset to default settings . . . . . . . . . . . . . . . . . . . . . . . . 15 3 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.1 Heating functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.1.1 Window contact . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.1.2 Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 3.1.3 Vacation period. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.2 Cooling functions . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.2.1 Window contact . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.2.2 Dew point monitoring . . . . . . . . . . . . . . . . . . . . . . . . . 17 3.3 Operating mode override . . . . . . . . . . . . . . . . . . . . . . . 18 3.4 Summer time/winter time changeover . . . . . . . . . . . . . . . . . 18 3.5 Key lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 3.6 Switching outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 4 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 6 Electrical connection. . . . . . . . . . . . . . . . . . . . . . . . . . 23 7 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.1 Function block list . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 7.2 Parameter list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 7.3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 EB 5572 EN 3 Contents

EB 5572 EN

Arrow keys (scrolling, changing) Reset key Default settings Enter key (selecting, confirming) Radio tower key (Communication parameter level, test) Thermometer key (Control parameter level) Data sheet key (configuration level) Changeover key (short = 1 s) (time, date, time schedules) Changeover key (long = 5 s) (Set points parameter level) Presence button (Operating mode: Automatic – Time-of-use – Outside time-of-use)

The room controller is ready for use after performing the connections (section 6) and start-up

(section 2). 1.1 Operating elements Operating elements when cover is closed Arrow keys (up and down keys) Used to select displays and parameters Manual key Without any function Additional operating elements accessible with the cover open Enter key Used to confirm a selection or setting Changeover key Key pressed for approx. 1 sec.: Open controller time and programmed time schedule Key pressed for approx. 5 sec.: Open Set points parameter level (only after en- tering key number) Presence button Used to select operating mode (Automatic – Time-of-use – Outside of time-of-use) Note that you require a pointed object such as a ball-point pen in order to press the follow- ing recessed keys: Thermometer key Used to access Control parameter level (only after entering key number) Radio tower key Used to access Communication parameter level (only after entering key number) Data sheet key Used to access configuration level (only after entering key number) Reset key Used to reset the room controller to its default settings (delivery state) (only after entering key number) EB 5572 EN 5 Operation

Information on the current operation appears on the display of the controller during use:

Set point Large reading Actual temperature Small reading on the bottom right of the display The actual temperature reading changes in steps of 0.5 °C. Operating mode No icon outside of time-of-use during time-of-use in vacation mode Presence Arrow points to indicating that the automatic operating mode has been interrupted (refer to section 1.5) Time schedule ,  changes in automatic operating mode depending on the programmed time schedule:  Time-of-use ·  Outside of time-of-use  Continuous time-of-use (automatic operating mode interrupted)  Continuously outside of time-of-use (automatic operating mode interrupted) Communication failure blinks on the display (only when communication is configured, refer to section 4) Control station intervention RC appears on the display (only when communication is configured, refer to section 4) Frost protection Actual temperature (small) blinks on the display when – Actual room temperature < 5 °C – Dew-point monitor alarm – Window contact Snow flake icon (blinking) – Actual room temperature < 5 °C Snow flake icon (constant) – Dew-point monitor alarm 6 EB 5572 EN Operation all-guides com

Setting the controller time

The correct time and date needs to be set directly after starting up the controller or after the power supply has been disconnected for more than 24 hours. How to proceed: Open the cover. Press key briefly (approx 1 s). The time appears on the display. An arrow on the right of the display at the same level as the changeover key indi- cates that the time can be changed. Press this key to enter the editing mode. The time starts to blink. Enter the correct time. Confirm the time. Select date setting. Press this key to enter the editing mode. The date starts to blink. Enter the correct date. Confirm the date. Select year setting. Press this key to enter the editing mode. The year starts to blink. Enter the correct year. Confirm the year. Exit the parameter level. Note! If no key is pressed within five minutes, the controller display returns to the set point reading. EB 5572 EN 7 Operation

Programming the time schedule

Three times-of-use can be programmed for each day of the week within which the controller regulates the room temperature to the Set point for time-of-use. If a time-of-use is not required, set the start and stop times of this time-of-use to the identical time. Parameters WE Range of values Times-of-use Mon to Fri Times-of-use Sat and Sun 08:00 to 20:00 00:00 to 00:00 00:00 to 24:00 h in steps of 15 minutes 00:00 to 24:00 h in steps of 15 minutes How to proceed: Open cover. Press key briefly (approx 1 s). The time appears on the display. An arrow on the right of the display at the same level as the changeover key indi- cates that the time can be changed. The date appears on the display. The year appears on the display. Select time-of-use setting. The arrow at the top of display points to . Reading: 1–7 = daily, 1 = Monday, 2 = Tuesday, …, 7 = Sunday Press this key to enter the editing mode. The start time of the first time-of-use appears on the display. Set the start time (in 15-minute steps). Confirm the start time. The stop time of the first time-of-use appears on the display. Set the stop time (in 15-minute steps). Confirm the stop time. The start time of the second time-of-use appears on the display. Repeat the instructions highlighted in gray to set the second and third times-of-use. After all the times-of-use have been programmed: Exit the parameter level. Note! If no key is pressed within five minutes, the controller display returns to the set point reading. 8 EB 5572 EN Operation

Selecting the operating mode (presence button)

Press key repeatedly to cycle through the following operating modes:. Temporary set point settings (see section 1.6) are reset when the operating mode is changed. Automatic mode ( during time-of-use, no icon appears outside of time-of-use; ……) Depending on the programmed time schedule, the controller regulates the room tem- perature to the Set point for time-of-use during the time-of-use and to the Set point for outside of time-of-use outside of the time-of-use. Time-of-use ( ; …) The controller regulates the room temperature to the Set point for time-of-use regard- less of the programmed time schedule. Outside of time-of-use (…) The controller regulates the room temperature to the Set point for outside of time-of-use regardless of the programmed time schedule. The duration of the time-of-use and outside of time-of-use operating mode is set in function block F02: Function WE Configuration Resetting operating mode 1 F02* * F02 - 0: Operating mode settings for continuous time-of-use/outside of time-of-use F02 - 1: Operating mode settings for time-of-use/outside of time-of-use that applies until the next time schedule starts when the operating mode changes back to automatic mode EB 5572 EN 9 Operation

Changing temperature set points temporarily

During the controller operation, the current set point and the actual temperature appear on the display. Use the arrow keys to temporarily change the current set point. The new temporary set point applies until the next time-of-use starts or until the operating mode is changed, however, eight hours at the maximum. The following maximum set point shifts apply:  Set point for time-of-use: ±3 °C  Set point for outside of time-of-use: +8 °C  Set point for vacation mode: +8 °C How to proceed: Change the set point temporarily in steps of 0.5 °C. Note! The temporary set point can also be overwritten by a building control station (GLT) when the communication is active (see section 4). 10 EB 5572 EN Operation

The changes described in this section concerning controller configuration can only be per-

formed after the valid key number has been entered. The valid key number is specified on page 27. To prevent unauthorized access to the key num- ber, tear out or blank out the key number. 2.1 Activate/deactivate functions A function is activated and deactivated by selecting the associated function block. The function blocks are listed in section 7.1. How to proceed: Open cover. Press the data sheet key. Enter key number. The configuration level is opened. Select the function block. Enter the editing mode. Fb : _ _ blinks. Activate the function block. Reading: Fb : _ _ ON or Deactivate the function block. Reading: Fb : _ _ OFF Confirm setting. Repeat the instructions highlighted in gray to set further function blocks. On completing the controller configuration: Exit the configuration level (or, alternatively, by pressing ). Note! If no key is pressed within five minutes, the controller display returns to the set point reading. EB 5572 EN 11 Start-up all-guides com

Depending on the active functions, not all the parameters that are specified in the parameter

lists in the appendix are accessible (–> section 7.2). The parameters are arranged in topics in various parameter levels (PA):  PA Set points: Set points for time-of-use, outside of time-of-use, and vacation mode  PA Control: Control parameters  PA Communication: Device address, Baud rate, sensor calibration, switching inputs and outputs How to proceed: Open cover. Select required parameter level: PA Set points (press key approx. 5 sec.) PA Control PA Communication Enter the key number. The parameter level is opened. Select parameter. Enter the editing mode. The display starts to blinks. Set parameter. Confirm setting. Repeat the instructions highlighted in gray to set other parameters in the opened parameter level. On completing all the parameter settings: Exit the parameter level. Use corresponding key depending on the parameter level: PA Set points PA Control PA Communication Note! If no key is pressed within five minutes, the controller display returns to the set point reading. 12 EB 5572 EN Start-up

Calibrating the room sensor

If the temperature displayed on the room controller (current temperature on the bottom right of the display) does not match the actual room temperature, the measured temperature of the room sensor can be changed and reset. On calibration, the currently displayed sensor temper- ature needs to be changed to match the directly measured room temperature (reference temper- ature). Note! An incorrectly performed calibration leads to the wrong room temperature measurements and results in incorrect control performance. Use a thermometer with a high degree of accuracy on measuring the reference temperature. How to proceed: Open cover. Select Communication parameter level. Enter the key number. The parameter level is opened. The device address appears on the display. The Baud rate appears on the display. The transmit/receive test appears on the display. Select correction value for room sensor Reading: Measured temperature (small); correction value (large) Enter the editing mode. The correction value starts to blink. Set the temperature difference found. Confirm the temperature difference. Exit the parameter level (or, alternatively, by pressing ). Note! If no key is pressed within five minutes, the controller display returns to the set point reading. EB 5572 EN 13 Start-up

Checking inputs and outputs

The current state of the binary inputs, triacs and analog outputs can be displayed in the Com- munication parameter level. The state of triacs and analog outputs can be changed manually. How to proceed: Open cover. Select Communication parameter level. Enter the key number. The parameter level is opened Press key 4 times. The state of the binary input BE1 appears: E1 0 /E1 1 (BE1 open/closed) Press the key once to change to the next input or output: • Binary input BE2 · Reading: E2 0/E2 1 (BE 2 open/closed) • Triac 1 · Reading: A1 0/A1 1 (triac 1 open/closed) • Triac 2 · Reading: A2 0/A2 1 (triac 2 open/closed) • Analog output AA1 · Reading: AA1 0 to AA1 100 (0 to 10 V voltage) • Analog output AA2 · Reading: AA2 0 to AA2 100 (0 to 10 V voltage) Changing triac/analog output state: The output triac 1 (A1), triac 2 (A2), analog output AA1 or analog output AA2 ap- pear on the controller display. Enter the editing mode. Close triac (A_ 1) or raise voltage at the analog output. or Open TRIAC (A_ 0) or reduce voltage at the analog output. Exit the parameter level (or, alternatively, by pressing ). Note! If no key is pressed within five minutes, the controller display returns to the set point reading. 14 EB 5572 EN Start-up

Reset to default settings

All parameters and functions can be reset to their default settings. How to proceed: Open cover. Select default setting menu. Enter the key number. The default setting menu is opened. Enter the editing mode. Press key. Confirm the reset. Exit the default setting menu. EB 5572 EN 15 Start-up

3.1.1 Window contact

The window contact function depends on the state of binary input BE1:  BE1 = 0: The heating valve is closed. The heating valve is opened for five minutes every 20 minutes  BE1 = 1: Control according to the current operating mode. 3.1.2 Optimization The controller determines the Advance heating time and Cooling down time depending on the building characteristics. The Advance heating time is the time required to achieve the room temperature Set point for time-of-use already when the time-of-use starts. In optimization mode, heating does not start when the time-of-use starts, but at an earlier point in time instead. The Cooling down time is the time required to achieve the room temperature Set point for out- side of time-of-use already when the time-of-use ends. In optimization mode, heating does not finish when the outside of time-of-use starts, but at an earlier point in time instead. Note! Advance heating time and Cooling down time are restricted by the Maximum advance heating time and Maximum cooling down time parameters respectively. Function WE Configuration Optimization 0 F03 - 1 Parameters WE Parameter level / Range of values Maximum advance heating time 360 min PA Set points / 0 to 360 min Maximum cooling down time 120 min PA Set points / 0 to 120 min 16 EB 5572 EN Functions all-guides com

3.1.3 Vacation period

During the programmed Vacation period (start and stop), the controller regulates the room tem- perature to the Set point for vacation mode. appears on the display. The Presence alert function (section 3.3) is not active during the programmed vacation period. Parameters WE Parameter level / Range of values Set point for vacation mode 15 °C PA Set points / 5 to 30 °C Vacation schedule – PA Set points / – 3.2 Cooling functions The cooling valve regulates the temperature to the current set point during the time-of-use. The following applies for outside of time-of-use: When F04 - 0: No cooling When F04 - 1: The temperature is regulated to a raised set point. The setback calculated from the set point for outside of time-of-use during heating is interpreted as an increase. Function WE Configuration Cooling 0 F04* * F04 - 0: No cooling outside of time-of-use F04 - 1: Cooling also outside of time-of-use 3.2.1 Window contact The Window contact function depends on the state of binary input BE1:  BE1 = 0: The cooling valve is closed.  BE1 = 1: Control according to the current operating mode. 3.2.2 Dew point monitoring The dew point monitoring uses the binary input BE2:  BE2 = 0: Temperature regulated to Set point for outside of time-of-use.  BE2 = 1: Cooling is interrupted. Function WE Configuration Function BE2 0 F01 - 1 EB 5572 EN 17 Functions

Operating mode override

The adjusted operating mode override is processed by binary input BE2:  BE2 = 0: Control according to the current operating mode.  BE2 = 1: The temperature is regulated to Set point for time-of-use regardless of the programmed time schedule or operating mode. Note! If the vacation mode is set, the setting F01 - 1 has no function; the controller continues to regu- late the temperature to Set point for vacation mode. Function WE Configuration Function BE2 0 F01 - 0 3.4 Summer time/winter time changeover The time changeover is performed automatically on the last Sunday in March at 02:00 h and on the last Sunday in October at 03:00 h. Function WE Configuration Summer time/winter time changeover 1 F06 - 1 3.5 Key lock When this function is active, , , , and keys do not have any function. Just the set point and actual temperature appear on the controller display. Changes to the oper- ating mode and time schedule and temporary set point changes cannot be made. Function WE Configuration Key lock 0 F05 - 1 18 EB 5572 EN Functions

The operating mode of the switching outputs can be selected in the Control parameter level.

Note! Changes to the control signal that are smaller than the value set in Min. control signal parameter are not processed. Parameter WE Parameter level / Range of values Min. control signal 5 % PA Control / 1 to 100 % Three-point stepping output (heating only) The control loop functions with a PI control algorithm. The heating valve reacts to pulses which the controller issues when a system deviation exists. In particular, the length of the first pulse de- pends on the size of the system deviation and the selected Gain KP (the pulse length increases as KP rises). Pulse length and interval time change continuously until the system deviation is eliminated. The interval between pulses is influenced considerably by the Reset time TN (the in- terval increases as TN rises). The Valve transit time TY indicates how long the valve needs to move through the range from 0 to 100 %. Parameters WE Parameter level / Range of values Switching outputs function 1 PA Control / Select: 1 Gain KP 1.0 PA Control / 0.1 to 100 Reset time TN 180 s PA Control / 0 to 1000 s Valve transit time TY1 45 s PA Control / 0 to 1000 s 2 x On/off PPM (heating and cooling) The control signals applied at the 0 to 10 V output that exceed the value entered in the Minimum control signal parameter, are issued as a pulse width modulated signal with the basic frequency 1/TY1 (heating) or 1/TY2 (cooling). Parameters WE Parameter level / Range of values Switching outputs function 1 PA Control / Select: 2 Valve transit time TY1 45 s PA Control / 0 to 1000 s Valve transit time TY2 45 s PA Control / 0 to 1000 s EB 5572 EN 19 Functions

2 x On-off thermostat (heating and cooling)

The output signal (AA1 heating, AA2 cooling) of the controller is switched on or off. A control signal is issued when the temperature exceeds or falls below the set point, depending on the controlled variable. If the control signal exceeds the Min. Control signal, the on-off ther- mostat is switched on or off. Parameter WE Parameter level / Range of values Switching outputs function 1 PA Control / Select: 3 Triac 1 and triac 2 switched according to the time schedule Both triacs are switched on together depending on the time schedule or the adjusted operating mode. Both triacs are closed outside of time-of-use. Parameter WE Parameter level / Range of values Switching outputs function 1 PA Control / Select: 4 Triac 1 switched according to the time schedule, triac 2 switched according the state of AA2 Triac 1 switches according to the time schedule or adjusted operating mode. Triac 2 switches on when the control signal for cooling = 100 % and when a system deviation (cooling demand) continues to exist. Triac 2 functions in sequence to the control signal for cool- ing, for example, to connect additional cooling equipment. When the temperature reaches the set point, triac 2 switches off again. Parameter WE Parameter level / Range of values Switching outputs function 1 PA Control / Select: 5 20 EB 5572 EN Functions

The serial system bus interface RS-485 enables the TROVIS 5572 Room Controller to communi-

cate with a control system (GLT). A complete control system can be implemented using a suit- able software to visualize the process and to enable communication. The operation of the controller requires a constant bus link (data cable). The bus line is designed in an open ring structure to connect individual control equipment. The data cable is connected at the end of the bus line to the control station over a RS-485/RS-232 converter (e.g. CoRe 01). The bus connection range (cable length) is maximum 1200 m. A maximum of 128 devices can be connected in such a segment. Repeaters must be used (for example, CoRe 01) to regenerate the signal level over long distances or when more than 32 devices are connected to one bus line. A maximum of 246 devices can be addressed and connected to a bus with 8-bit addressing. Caution! You are required to follow the relevant standards and regulations applicable to light- ning and overvoltage protection on installing the controller. A transmitting and/or receiving test can be initiated in the Communication parameter level:  RC blinking : Receiving data telegrams from control station (GLT), on the display even when they are intended for other controllers  : Controller transmitting to control station (GLT) Description of the parameters that need to be set: The Device address is used to identify the controller. An address may only be assigned once within a system. The Baud rate indicates the transfer rate between control system and controller in a bus system. Functions WE Configuration 16-bit addressing 0 F07* * F07 - 0: 8-bit addressing F07 - 1: 16-bit addressing EB 5572 EN 21 Communication all-guides com

Parameter level / Range of values

Device address 000 PA Communication / 0 to 255 ( 8 bit) 0 to 999 (16 bit) Baud rate 19200 PA Communication / 19200, 9600 Transmitting/receiving test – PA Communication / Display: RC/ 5 Installation Note! The room controller must be mounted at a height of 1.50 m. Make sure that the operation of the room controller is not affected by heat sources (radiators, lights, electrical appliances) or by drafts close to doors or windows. The room controller should not be covered by curtains or any pieces of furniture. To mount and wire the room controller, remove the housing from the base. How to proceed: 1. Press down the tongue on the bottom of the controller and tip the housing section for- ward to remove it from the base. 2. Screw the base to the wall. 3. Connect the wiring as described in section 6. 4. Push the top of the housing section onto the base and push it down. 22 EB 5572 EN Installation

The room controller is operated with a 24 V AC power supply.

Terminal assignment 1 Modbus RS-485 (slave) Connection to the control station (GLT) or to a Modbus master interface 2 3 0…10 V output 1 4 0…10 V output 2 5 GND for 0…10 V outputs 6 Binary input BE1 7 Binary input BE2 8 GND for binary inputs 9 Power supply 24 V AC AC 1 10 AC 2 has GND reference 11 Triac output 1 24 V AC, 1 A 12 13 Triac output 2 24 V AC, 1 A 14 15 RS-485; Modbus (master) Connection to expansion module(s) 16 EB 5572 EN 23 Electrical connection

Function block list

F Function block WE Description 01 Function BE2 0 F01 - 0: Operating mode override by BE2 F01 - 1: Dew point monitoring 02 Resetting the operating mode 1 F02 - 0: Time-of-use/outside of time-of-use operating mode setting continuous F02 -1 : Time-of-use/outside of time-of-use operating mode setting that applies until the next time schedule starts when the operating mode changes back to automatic mode 03 Optimization 0 F03 - 0: Function is not active F03 - 1: Optimization; calculation of advance heating time or cooling down time in heating mode 04 Cooling 0 F04 - 0: Cooling not active outside of time-of-use F04 - 1: Cooling also active outside of time-of-use 05 Key lock 0 F05 - 0: Function is not active F05 - 1: Keys (except for recessed keys) are locked 06 Summer time/winter time changeover 1 F06 - 0: Function is not active F06 - 1: Automatic time changeover 07 16-bit addressing 0 F07 - 0: 8-bit addressing F07 - 1: 16-bit addressing 24 EB 5572 EN Appendix

Set points parameter level

Parameter WE Description 01 Set point for time-of-use 21 °C Adjustment range: 5 to 30 °C 02 Set point for outside of time-of-use 17 °C Adjustment range: 5 to 30 °C 03 Set point for vacation mode 15 °C Adjustment range: 5 to 30 °C 04 Maximum advance heating time 360 min Start value for the calculation: 120 min Can only selected when the optimization function is active (F03 - 1). 05 Maximum cooling down time 120 min Start value for the calculation: 60 min Can only selected when the optimization function is active (F03 - 1). 06 Vacation schedule – Control parameter level Parameter WE Description 01 Switching outputs function 1 Option: 1: Three-point stepping output 2: 2 x On/off PPM 3: 2 x On/off thermostat 4: Triac 1 and triac 2 switched according to the time schedule 5: Triac 1 switched according to the time schedule; Triac 2 switched acc. to the state of triac 1 and AA2 02 Gain KP 1.0 Adjustment range: 0.1 to 100 03 Reset time TN 180 s Adjustment range: 0 to 1000 s 04 Derivative-action time TV 0 s Adjustment range: 0 to 1000 s 05 Valve transit time TY1 45 s Adjustment range: 0 to 1000 s 06 Valve transit time TY2 45 s Adjustment range: 0 to 1000 s 07 Min. control signal 5.0 % Adjustment range: 1.0 to 100 % EB 5572 EN 25 Appendix

Communication parameter level

Parameter WE Description 01 Device address 0 Adjustment range: 0 to 255 (8 bit) 0 to 999 (16 bit) 000 = No communication with control station (GLT) 02 Baud rate 19200 Adjustment range: 9600, 19200 03 Transmitting/receiving test RC blinks on display on receiving any data telegram from the control station(GLT), even if they are intended for other con- trollers blinks on display for transmitting to the control station (GLT) 04 Calibrating the room sensor 0.0 Adjustment range: –9.9 to + 9.9 °C (in steps of 0.1 °C) 05 Read/test BE1 Reading: E1 0 (open), E1 1 (closed) 06 Read/test BE2 Reading: E2 0 (open), E2 1 (closed) 07 Read/test triac 1 Reading/Adjustment range: A1 0 (open), A1 1 (closed) 08 Read/test triac 2 Reading/Adjustment range: A2 0 (open), A2 1 (closed) 09 Read/test AA1 Reading/Adjustment range: AA1 0 (0 V) to AA1 100 (10 V) 10 Read/test AA2 Reading/Adjustment range: AA2 0 (0 V) to AA2 100 (10 V) 26 EB 5572 EN Appendix all-guides com

1 room sensor (internal)

1 presence button (internal) 2 binary inputs for window contact/dew point and operating mode override Outputs 2 triac outputs 24 V AC, 1 A 2 outputs 0 to 10 V Power supply 24 V AC Interface Modbus (RS-485) Environmental conditions Operation: 0 to 50 °C Storage, transportation: –10 to 60 °C 95 % rH, not condensing Degree of contamination 2 according to VDE 0110 Noise immunity According to EN 61000-6-1 Noise emission According to EN 61000-6-3 Power consumption of room controller Approx. 0.6 VA Power consumption of expansion module Approx. 1 VA Maximum load for analog output Not smaller than 4.7 kΩ Dimensions in mm W x H x D 113 x 91 x 30 EB 5572 EN 27 Appendix Key number: 1732

SAMSON AG · MESS- UND REGELTECHNIK

Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 Internet: http://www.samson.de EB 5572 EN 2007-02 Terminal assignment (refer to section 6) Please note: The room controller is operated with 24 V AC. Modbus RS-485 to expansion module RS-485; Modbus (slave) Connection to the control station (GLT) or to a Modbus master interface 0 … 10 V output 1 0 … 10 V output 2 GND for 0 … 10 V outputs Binary input BE1 Binary inputs BE2 GND for binary inputs Power supply 24 V AC AC 1 AC 2 has GND reference Triac output 1 24 V AC, 1 A Triac output 2 24 V AC, 1 A RS-485; Modbus (master) Connection to expansion module(s)