Ductless Split Heat Pump

Service Manual Design may vary by model number. • Please read this manual before using the heat pump. • Keep this user manual for future reference. PAGE 1 Safety Precautions/Introduction .................................................................................................3 Outdoor Unit Controls and Components .....................................................................................7 Indoor Unit Controls and Components ......................................................................................15 Sequence Of Operation .............................................................................................................21 Error Codes and Problem Solving ..............................................................................................29 Reference Information ..............................................................................................................43 Table of Contents Indoor AW09ES2VHB AW12ES2VHB AW15ES2VHB AW18ES2VHB AW24ES2VHB Outdoor 1U09AP2VHA 1U12AP2VHA 1U15AP2VHA 1U18AP2VHA 1U24AP2VHA

Safety Precautions .............................................................................................................................................................4

Warning and Cautions ......................................................................................................................................................................4 Introduction to System ......................................................................................................................................................5 � Specifications�for�proper�operation�should�be�followed ................................................................................................................5 � Fundamental�Theory�Of�How�System�Works..................................................................................................................................5 Table of Contents

• Read these Safety Precautions carefully to ensure correct installation.

• This manual classifies the precautions by WARNING and CAUTION. • Follow all precautions below. They are all important for ensuring safety and preventing property/equipment damage. ! WARNING: Failure to follow any of WARNING is likely to result in grave consequences such as death or serious injury. ! CAUTION: Failure to follow any of CAUTION may, in some cases, result in grave consequences. • The following safety symbols are used throughout this manual: Observe this instruction Establish an earth connection Never attempt • After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual. ! WARNING • Installation should be performed by the dealer or another professional. Improper installation may cause water leakage, electrical shock, or fire. • Install the heat pump according to the instructions given in this manual. Incomplete installation may cause water leakage, electrical shock, or fire. • Use only the supplied or specified installation parts. Use of other parts may cause the unit to come lose, water leakage, electrical shock, or fire. • Install the heat pump on a solid base that can support the unit’s weight. An inadequate base or incomplete installation may cause injury in the event the unit falls off the base. • Electrical work should be carried out in accordance with the installation manual and national/local electrical wiring codes and rules of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire. • Use a dedicated power circuit. Never use a power supply shared by another appliance. • For wiring, use a cable long enough to cover the entire distance with no splices. Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit. (Failure to do so may cause abnormal heat, electric shock or fire.) • Use only the specified wire types for electrical connections between the indoor and outdoor units. Firmly clamp the interconnecting wires so they receive no external stresses. Incomplete connections or clamping may cause terminal over- heating or fire. • After completing interconnecting and supply wiring connections, shape the cables so that they do not put undue force on the electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire. • If any refrigerant has leaked out during the installation work, ventilate the room. (The refrigerant produces a toxic gas if exposed to flame.) • After all installation is complete, check for and repair any system refrigerant leaks. (The refrigerant produces a toxic gas if exposed to flames.) •When installing or relocating the system, keep the refrigerant circuit free from substances other than the specified refrigerant (R410A), such as air. (The presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.) • During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is still running, and the stop valve is open during pump-down, air will be sucked into the system while the compressor is running. This will cause abnormal pressure and noncondensables added to the system. • Be sure to establish a ground. Do not ground the unit to a utility pipe, arrester, or telephone earth. An complete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the heat pumpheat pump. ! CAUTION • Do not install the heat pump in a place where there is danger of exposure to flammable gas. If the gas builds up around the unit, it may catch fire. • Install drain piping according to the instructions of this manual. Inadequate piping may cause flooding. •Tighten the flare nut according to the specified torque using a torque wrench. If the flare nut is overtightened, the flare nut may eventually crack and cause refrigerant leakage. • Provide adequate measures to prevent the outdoor unit from being used as a shelter by rodents. Rodents making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean. Safety Precautions

Introduction to System

Single Zone Ductless Split System Heat Pumps feature a wall mounted indoor fan/evaporator unit that receives refrigerant from an inverter driven variable speed outdoor condensing unit. The system operation is controlled with a remote control. The outdoor unit features a variable speed rotary compressor, EEV metering device and DC fan motor. These systems use R410A refrigerant and PVE oil. The outdoor units are 208/230 volt rated systems. They come factory charged for up to 25 ft. of interconnecting piping. The indoor units are wall mounted type. They feature a DC blower motor and a DC louver motor. The unit has a room temperature sensor and an evaporator tube temperature sensor. The wall unit is powered by voltage from the outdoor unit. Specifications for proper operation should be followed • The systems are designed to operate in room temperature ranges of 60°F to 86°F in cooling mode and 60°F to 86°F in heat mode. • PVE oil is non reactive to water and will not go into Hydrolysis. There is no need to add a refrigeration drier when servicing or installing this system. • The indoor wall mounted unit receives operating voltage and communication data signals on #14 AWG wire that connects between the indoor and outdoor units. There should not be any splices in the field wiring that goes between terminals 1, 2, 3 and 4. A splice in these wires may cause the system to lose communication between the indoor and outdoor units. The system will then display an error code E7. • The systems come with enough factory charge for up to 25 feet of connecting refrigeration tubing. The tubing connects using flare type fittings at both the indoor and outdoor units. Tubing must be sized per the specifications. Both lines must be insulated. The only method of checking charge or adjusting charge is by weight method explained in this manual (no exceptions). • The condensate system is a gravity type. A field installed condensate pump may be added to the system. Always follow the manufacturer’s installation instructions when installing a condensate pump. • Proper clearances at both indoor and outdoor units must be maintained. Improper clearances cause system conditions that include high refrigerant pressure, low refrigerant pressure and indoor coil freezing problems. Fundamental Theory of How the System Works The indoor unit will sense room temperature at the point where the wall unit is installed. The indoor fan will run continuously when placed in heating or cooling mode operation and will not cycle on and off with the outdoor unit. If it did, room temperature could not be sensed or Introduction maintained. The inverter compressor system in the outdoor unit will vary the refrigerant flow and indoor air volume levels to match the cooling requirement inside the conditioned space. If an abnormal condition is detected by the system’s sensors, the system has the ability to take reactive measures. The amount of refrigerant flow and associated capacity generated by the system will be determined by how fast the system’s variable speed rotary compressor is pumping. The compressor operating speed requirement is determined by the difference between the conditioned space temperature versus the set point established by the homeowner’s remote control. If a large amount of capacity is needed, the compressor will operate at a high frequency speed. As the need for capacity reduces and the temperature of the room nears set point, the compressor will slow down. When set point has been reached, the compressor will shut off but the indoor fan will continue to operate. Once a difference in temperature is sensed between remote control set point temperature and room temperature, the compressor will restart at a new calculated speed. If a system sensor determines there is a need to adjust the frequency signal to prevent a system malfunction, the compressor frequency may be over ridden and a new frequency established. It should be noted that the frequency signal level that is sent to the compressor cannot be determined by a servicing technician. In this manual, system components, operation, sensor functions and diagnostic procedures will be explained in greater detail.

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 7 ENGLISH Outdoor Unit Controls & Components Table of Contents Outdoor Unit Introduction .................................................................................................................................................8 Outdoor Component Identification ....................................................................................................................................8 Outdoor Main Control Board ..............................................................................................................................................9 Terminal Block ..................................................................................................................................................................10 Reactor ............................................................................................................................................................................10 Compressor .....................................................................................................................................................................10 Outdoor Fan Motor ...........................................................................................................................................................10 Discharge Temperature Sensor ........................................................................................................................................11 Defrost Temperature Sensor ............................................................................................................................................11 Outdoor Ambient Temperature Sensor ............................................................................................................................11 Suction Line Temperature Sensor .....................................................................................................................................11 4-Way Valve .....................................................................................................................................................................12 Electronic Expansion Valve ...............................................................................................................................................12 Accumulator ....................................................................................................................................................................12 Filters ...............................................................................................................................................................................12 Electrical Base Pan Heater ................................................................................................................................................12 DIP Switch ........................................................................................................................................................................13

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 8 ENGLISH Outdoor Unit Introduction The outdoor condensing unit models are heat pump systems. The outdoor unit has two circuit boards, a Module board that drives the compressor and a Main Control Board that manages system functions and inverter calculations. Temperature sensors monitor key temperatures throughout the system to manage operational decisions. Outdoor Component Identification 4-Way Valve Accumulator Compressor Defrost Temperature Sensor Discharge Temperature Sensor Electronic Expansion Valve Refrigerant Filters Outdoor Ambient Temperature Sensor Outdoor Fan Motor Power Factor Reactor Suction Line Temperature Sensor Terminal Block Main Control Board (board cover not shown) Module Control Board Fan Blade Base Pan Heater 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 8 4 6 11 12 13 14 1 3 16 2 7 5 9 10 15

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 9 ENGLISH Outdoor Control Board PCB (1) (Outdoor Control PCB) PCB (2) (Module PCB for 09-12K ) PCB (3) (Module PCB for 18-24K ) 2 CN3 - Connector for ground 10 CN36 - Connector for communicate between indoor and outdoor unit 6 CN11 - Connector for four way valve coil 4 CN9, CN8 - Connector for CN2,CN1 on the module board 12 CN50 - Connector for DRED-control 09-12 18-24 8 CN24 - Communication connector for control board and the module board CN1, CN2 - Connector for power N and L CN17, CN47 - Connector for thermistors 7 CN23 - Connector for DC POWER 15V and 5V to the module board 3 CN15 - Connector for electric expansion valves 11 CN28, CN25 - Connector to P and N of the module board 9 CN22 - Connector for fan motor 5 FUSE 1: (25A, 250VAC); FUSE 2:(1A, 250VAC) 13 LED 1 - Constant ON is normal operation, flashing indicates alarm. 14 RV1, RV2, RV3 Varistor 15 CN10 - Connector for the DC power 5V and 15V form the control PCB 18 Base Pan Heater Connection 16 BM2-1, BM2-2 - Defrost DIP Switches 17 CN10 - Connector for the DC power 5V and 15V form the control PCB 23 23 CN11 - Connector for communicate between the control board and the module board 19 CN11 - Connector for communicate between the control board and the module board 24 P (CN1), N (CN5) - Connector for capacitance board 20 P (CN8), N (CN9) - Connector for capacitance board 25 25 LI (CN7), LO (CN6) - Connector for reactor 21 21 LI (CN3), LO (CN4) - Connector for reactor 26 CN2, CN3, CN4 - Connector for the U, V, W wire of the compressor 22 CN5, CN6, CN7 - Connector for the U, V, W wire of the compressor 27 27 1 2 3 16 17 5 4 6 8 9 10 12 13 11 7 18 19 20 22 24 26 1

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 10 ENGLISH Terminal Block Power Factor Reactor The Reactor is an inductive filter that will aid in correction of electrical power factor influence of inverter capacitance. It is unlikely to ever have an electrical failure of this component. The Reactor is electrically connected to the Module Board on terminal connections CN-7 and CN-8. The outdoor unit is powered by 208/230 Volt Single Phase electricity connected at the Outdoor Unit Terminal Block. Terminals 1 and 2 on the outdoor unit terminal connect this voltage to the system. The number 3 terminal is a communication terminal that connects wiring between the indoor and outdoor units. An earth ground source terminal connects the outdoor unit to the line voltage power source. Condensate safety switches should break wire 1. The indoor unit is also powered by the same electrical supply as the outdoor unit. #14 AWG wire is connected to the wiring terminal block at the outdoor unit and is run to the indoor unit wire terminal block. When installing the field supplied wiring, make certain the wire gauge is correct. There should not be any electrical wiring splices between the indoor unit and outdoor unit wire. Wire #3 is used to carry communication data between the indoor and outdoor units. A wiring splice where wires are twisted in a wire nut may cause deformation of the communication of the data signal. If communication is lost between the indoor and outdoor units, an ERROR CODE E7 will occur. Compressor Outdoor Fan Motor The outdoor fan motor is a variable speed motor. The required motor speed is calculated by the Main Control Board. The motor is electrically connected to the Main Control Board via PLUG CN-21. In COOL MODE operation, the motor will slow down as outdoor air temperature falls. In HEAT MODE operation, the motor will increase speed as the outdoor air temperature falls. The compressor is a three phase DC inverter driven Rotary type. The compressor is capable of variable speed operation. The compressor operating frequency will be determined by the temperature difference between set point and room or outdoor air temperature. (Cool Mode versus Heat Mode) The compressor is electrically connected to the Module Board on terminal connections CN-2, CN-3 and CN-4. The compressor has an internal temperature overload that will open if the compressor becomes too hot. Additional protection of the compressor will be provided by the Compressor Discharge Temperature Sensor and Suction Line Temperature Sensor.

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 11 ENGLISH Discharge Temperature Sensor Defrost Temperature Sensor The Defrost Temperature Sensor is a negative coefficient thermistor that will change resistance in response to outdoor coil temperature changes. The Main Control Board monitors the temperature of the outdoor coil to determine when the system is needing to perform a defrost cycle. The sensor also monitors outdoor coil temperature during defrost cycles to determine termination conditions. This sensor connects to the Main Control Board at PLUG CN-19. The Discharge Temperature Sensor is a Negative Coefficient thermistor that senses the temperature of the compressor hot gas. The Main Control Board monitors the temperature of the compressor hot gas and will make inverter speed changes in response to input from this device. This sensor connects to the Main Control Board at PLUG CN-17. Outdoor Ambient Temperature Sensor Suction Line Temperature Sensor The Suction Line Temperature Sensor is a negative coefficient thermistor that senses the temperature of the suction line. The Main Control Board monitors the temperature of the suction line to determine EEV orifice size in an attempt to maintain proper operating superheat. This sensor connects to the Main Control Board at PLUG CN-18. The Outdoor Ambient Temperature Sensor is a negative coefficient thermistor that will change resistance in response to outdoor air temperature changes. The Main Control Board monitors the temperature of the outdoor air to determine outdoor fan speed requirements and inverter speed. The sensor also plays a role in calculation of required defrost conditions. This sensor connects to the Main Control Board at PLUG CN-20.

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 12 ENGLISH 4-Way Valve Electronic Expansion Valve The metering device is an electronic expansion valve type EEV. The valve consists of an electrical operator and a valve body with internal variable size orifice. When operating, the Main Control Board will send pulses of voltage to the electrical operator. The operator will then magnetically move the position of the metering orifice pin to vary its size. The metering device position is determined by input from a Suction Line Temperature Sensor located in the outdoor unit. The EEV will change the internal orifice size to maintain a superheat level of around 10°F. The 4-Way Valve redirects the flow of refrigerant in the piping circuit to allow the system to swap the functions of the indoor and outdoor coils. When de-energized in COOL MODE, the valve will direct the refrigerant hot gas to the outdoor coil. When energized in HEAT MODE, the valve will direct the hot gas to the indoor coil. The valve flow direction capability is controlled by an electrical solenoid. When energized by 240 Volts, line voltage, the solenoid will magnetically move an internal slide within the 4-Way Valve to change the direction of refrigerant flow. The 4-Way Valve is electrically connected to the Main Control Board at PLUG CN-10. Accumulator The Accumulator is located in the suction line circuit at the entrance to the compressor. The accumulator helps prevent liquid refrigerant from entering the compressor during run operation. Refrigerant Filters Electrical Base Pan Heater The system has debris catching filters that protect internal system components from contaminants in the refrigerant. The filter is a permanent part that is not typically replaced. During COOL MODE operation, the valve meters low pressure refrigerant to the indoor coil. During HEAT MODE operation, the valve meters low pressure refrigerant to the outdoor coil. The system has an electrical base pan heater for defrosting.

OUTDOOR UNIT CONTROLS & COMPONENTS

PAGE 13 ENGLISH DIP Switch DIP Switch Settings The outdoor unit PCB board DIP switches are used to control defrost cycle settings. The DIP switches are factory set for Demand Defrost (BM2-1 ON, BM2-2 ON). The DIP switch settings may be adjusted as follow: BM2-1 BM2-2 Description - (Defrost is generally every 45 minutes) OFF OFF Demand defrost for cold climate (default) ON OFF Time defrost at lower frequency (10 Hz lower than the regular defrost) OFF ON Time defrost at higher frequency (10 Hz higher than the regular defrost) ON ON Demand defrost for moderate climate

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 15 ENGLISH Indoor Unit Controls & Components Table of Contents Indoor Unit Introduction ..................................................................................................................................................16 Indoor Component Identification .....................................................................................................................................16 Indoor Control Board ........................................................................................................................................................17 Terminal Block ..................................................................................................................................................................18 Display .............................................................................................................................................................................18 Ambient Temperature Sensor ..........................................................................................................................................18 Coil Temperature Sensor ..................................................................................................................................................18 Louver Motor ...................................................................................................................................................................19 Fan Motor .........................................................................................................................................................................19 Emergency Button ...........................................................................................................................................................19 DIP Switch and DIP Switch Settings ..................................................................................................................................20

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 16 ENGLISH Indoor Component Identification Indoor Unit Introduction The indoor unit is mounted high on the wall to provide air conditioning coverage of a conditioned space. Field installed/supplied condensate pump accessories can be added to these systems. Features of the system include: Variable speed blower operation that speeds up and slows down with changes in demand, Moving louvers to direct air, Indoor air temperature sensing, Evaporator coil temperature sensing, Consumer operation display, Evaporator coil with metering device located in outdoor unit, and an Emergency Operation Switch. Indoor Ambient Temperature Sensor Display Fan Motor Louver Motor 1 2 3 4 Main Control Board Piping Temperature Sensor Terminal Block 5 6 7 5 7 6 4 1 3 2

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 17 ENGLISH Indoor Control Board 2 2 CN27 - Connector for ground 4 4 CN6 - Connector for thermistors 9 9 CN2 - Connector for wiring-control 6 6 CN7 - Connector for display 11 11 CN34 - Connector for Wi-Fi-control RV1 - Varistor 13 13 SW2 – 1-Select remote code A or B, 2-Select room card enable or disable 3,4-Select eeprom code 23, 26, 33 and 35 CN21, CN52 - Connector for power N and L 1 CN11 - Connector for left-right stepper motor 8 8 CN9 - Connector for fan motor 5 5 SW1 - Connector for Emergency operation ON / OFF switch 12 15 15 CN23 - Connector for communication between indoor and outdoor unit 3 3 CN51 - Connector for room card 10 10 CN5 - Connector for up-down stepper motor 7 7 14 14 FUSE1 - Fuse 3.15A/250VAC 12

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 18 ENGLISH Terminal Block Display The indoor unit terminal block receives electrical power from the outdoor unit. There are 4 connections for electrical wires. Terminals 1 and 2 are connected to terminals 1 and 2 of the outdoor unit. This wiring supplies power to the indoor unit. Terminal 3 is a communication wire. The indoor unit sends indoor air temperature, coil temperature and temperature setpoint information to the outdoor unit on this wire. If a splice or break in this wire is present, the indoor unit will not be able to communicate with the outdoor unit. The ERROR CODE will be code E7. The indoor display has an infrared communication circuit that receives operating commands from the remote control. This display will indicate operating modes, error codes, indoor air temperature, timer status and power status. Ambient Temperature Sensor The Room Ambient Temperature Sensor is a negative coefficient thermistor that will decrease in resistance with increases in room air temperature. The sensor is located on a clip mounted to the surface of the indoor coil. The sensor connects to the control board at Plug CN-6. Coil Temperature Sensor The Coil Temperature Sensor is a negative coefficient thermistor that will decrease in resistance with increases in coil temperature. The sensor is located in a socket soldered to the surface of the indoor coil. This sensor will monitor the temperature of the indoor coil in both cooling and heating modes of operation. Should abnormally cold or hot coil temperature be detected by this sensor, the system will take functional corrective steps to correct the condition or report an ERROR CODE. The sensor connects to the control board at Plug CN-6.

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 19 ENGLISH Stepper Motor Louver Fan Motor Emergency Button The Indoor Fan Motor is a variable speed motor. The motor will vary speed with the speed of the compressor inverter. The speed can also be set at the remote control or automatically adjusted using the AUTO fan mode. When in AUTO fan mode, the speed of the fan is calculated using the indoor set temperature and the indoor room ambient temperature. (Outdoor air temperature in heat mode.) The Fan Motor is connected to the indoor control board via PLUG CN-9. If the remote control is non-functional, the Emergency Button can be accessed by swinging open the front of the wall unit. The button is located on the right side. Pushing this button will activate AUTO MODE operation. AUTO MODE activated with this button will maintain 75°F. The system will stay in this mode until commands are received by the indoor unit communication circuit via the remote control. The STEPPER MOTOR moves the louver up or down, and right or left depending upon selections made at the remote control. The motor is connected to the indoor control board at PLUG CN-11.

INDOOR UNIT CONTROLS & COMPONENTS

PAGE 20 ENGLISH DIP Switch Settings The PCB for the indoor unit of the Advanced series of single zone mini-splits has a set of DIP switches that must be set when replacing the PCB. The replacement PCB is shipped with all switches set to the OFF position. Switch settings: SW2-1 Selects remote code A or B. Normally set to the off position for code A operation. If two indoor units are used in the same area and the user wishes to control them separately, switch SW2-1 of the second unit is set to the ON position for code B operation. The wireless remote for the second unit is also set to code B. SW2-2 Selects room card enable or disable. Normally set to the OFF position. Set to the ON position when used in conjunction with a room card interface utilized in hotel rooms. SW-3 & SW-4 Selects eeprom code 23, 26, 33 and 35. Set to identify the tonnage of the unit. Settings: 9K (23) SW-3 OFF SW-4 OFF 12K (26) SW-3 OFF SW-4 ON 15K (33) SW-3 ON SW-4 OFF 18K (33) SW-3 ON SW-4 OFF 24K (35) SW-3 ON SW-4 ON DIP Switch

SEQUENCE OF OPERATION

PAGE 21 ENGLISH Sequence of Operation Table of Contents System Power ..................................................................................................................................................................22 Cool Mode ........................................................................................................................................................................22 � Overview ........................................................................................................................................................................................ 22 Indoor Unit ..................................................................................................................................................................................... 22 Temperature sensors .................................................................................................................................................................... 22 Communication ............................................................................................................................................................................. 22 � Outdoor�unit .................................................................................................................................................................................. 22 Temperature sensors .................................................................................................................................................................... 23 Call to Terminate Cooling ............................................................................................................................................................. 23 � Freeze�protection�function ........................................................................................................................................................... 23 Heat Mode ........................................................................................................................................................................23 � Overview ........................................................................................................................................................................................ 23 � Cold�air�proof�operation ................................................................................................................................................................ 23 � Defrost ........................................................................................................................................................................................... 24 � Automatic�Heating�Temperature�Compensation ....................................................................................................................... 24 Indoor Unit ..................................................................................................................................................................................... 24 Temperature sensors .................................................................................................................................................................... 24 Communication ............................................................................................................................................................................. 24 � Outdoor�unit .................................................................................................................................................................................. 24 Temperature sensors .................................................................................................................................................................... 24 � Call�to�Terminate�Heating ............................................................................................................................................................. 24 Auto Mode........................................................................................................................................................................25 Dry Mode .........................................................................................................................................................................25 Overview ........................................................................................................................................................................................ 25 Indoor Unit ..................................................................................................................................................................................... 25 Temperature sensors .................................................................................................................................................................... 25 Communication ............................................................................................................................................................................. 25 � Outdoor�unit .................................................................................................................................................................................. 25 Temperature sensors .................................................................................................................................................................... 25 Defrost Operation ............................................................................................................................................................26 � Defrosting�Program�Entry�Conditions ......................................................................................................................................... 26 � Conditions�Used�to�Determination�if�Frost�has�Formed ............................................................................................................. 26 � Defrost�Actions ............................................................................................................................................................................. 26 � Defrosting�Exit�Conditions ........................................................................................................................................................... 26 Protection Functions ........................................................................................................................................................26 � TTC�high�temperature�protection ................................................................................................................................................ 26 � Overheating�protection�for�indoor�unit ....................................................................................................................................... 27 Compressor overcurrent protection ........................................................................................................................................... 27 � Anti-freeze�protection�of�the�indoor�heat�exchanger ................................................................................................................. 27 � Anti-freeze�protection�of�the�base�pan........................................................................................................................................ 27

SEQUENCE OF OPERATION

PAGE 22 ENGLISH System Power The 240 Volt AC power for the system connects to terminals 1(N), 2(L), and ground of the outdoor unit terminal block. This terminal block also has terminals to connect power to the indoor unit. The voltage readings between terminals 1(N) and ground, and terminals 2(L) and ground should be 120 VAC. The voltage reading between terminals 1(N) and 2(L) should be 240 VAC. One additional connection on the terminal block (3) is for the communication wire between the indoor and outdoor units. NOTE: Mis-wiring of these connections may cause improper operation or damage to system components. Cool Mode Overview The temperature control range in cooling mode is 60°F - 86°F. The temperature set by the remote control and the indoor unit ambient temperature sensor will determine if a call for cooling is needed. If a call for cooling is justified, the call is communicated from the indoor unit to the outdoor unit. The indoor unit louver will open using a stepper motor, and the indoor fan will operate at the speed last set. The outdoor unit will determine the position of the EEV and speed (frequency) of the compressor. There can be a delay of up to 3 minutes before the outdoor unit fan and compressor start. The speed of the indoor fan can be controlled manually by the user or automatically by the system. The speed can be changed between LOW, MEDIUM, and HIGH. The predeter- mined conditions for automatic control are as follows: (Tr= room temperature Ts= set temperature) High Speed: Tr ≤ Ts + 5.4°F Medium Speed: Ts + 1.8°F ≤ Tr < Ts + 5.4°F Low Speed: Tr ≤ Ts + 1.8°F or when the sensor is off. There will be a 2 second delay when manually controlling the speed. The outdoor unit temperature sensors: outdoor ambient, defrost, suction line, and compressor discharge, used in conjunction with the indoor temperature sensors, indoor ambient and coil, provide information to the outdoor control board to monitor the system and regulate the frequency of the compressor, EEV positioning, and outdoor fan speed to achieve the desired room temperature. When cooling has been satisfied, the outdoor unit compres- sor will turn off, followed by the outdoor fan. The indoor unit fan will continue to run. If the system detects a malfunction, it may shut down or show an error code on the indoor unit display board and/or outdoor unit main board LED. Indoor Unit To enter the cool mode, point the infrared remote control at the indoor unit and press the power button, then press the COOL mode button if not already set to cool mode. The signals received by the infrared receiver are relayed to the main board of the indoor unit to turn the system on and set it to cool mode. The indoor unit main board will activate the display of the indoor unit, illuminating the display, indicating the room tem- perature and current status of the unit. The indoor unit main board will signal the louver stepper mo- tor to open the louver to either a stationary position, or one of several oscillating modes. As the louver opens, the indoor unit main board will power up the indoor fan motor, operating the fan at the speed last set. The indoor fan motor has a feedback circuit which provides the indoor unit main board with information for controlling the speed of the fan motor. Temperature Sensors The indoor unit has two sensors that provide temperature information to the indoor unit main board. The sensors: an indoor ambient temperature sensor, and coil temperature sensor, are used for controlling the system during cool mode. The resistance values of the sensors will vary with tempera- ture. The resistance to temperature values can be found using a temperature / resistance chart specific to the sensor being checked. Communication The indoor and outdoor unit main boards communicate via a digital signal on the wire connected to terminal 3 of each unit. A splice or break in this wire will cause a communication error. When a command is received from the remote control, the indoor unit main board communicates with the outdoor unit main board via the terminal 3 wire to perform the requested function. Outdoor Unit Upon a request for cooling, the outdoor unit main board applies power to the outdoor fan motor and compressor. Depending on system cycling, there may be up to a 3 minute wait period before the compressor and outdoor fan start. WARNING: Do not measure compressor voltages, damage to the volt meter may result. If the ambient room temperature is less than the set tem- perature, yet higher than 2°F below the set temperature, the system will adjust the running frequency of the compressor automatically according to changes in ambient temperature.

SEQUENCE OF OPERATION

PAGE 23 ENGLISH The outdoor unit main board also controls the position of the EEV (Electronic Expansion Valve) to regulate the flow of refrigerant to the indoor unit evaporator coil. Temperature Sensors Four temperature sensors located in the outdoor unit provide temperature information to the outdoor unit main board for control of the system during cool mode. The outdoor ambient temperature sensor provides the tem- perature of the air drawn into the outdoor coil of the outdoor unit. The defrost temperature sensor provides the temperature sensed at the output of the outdoor coil. The suction line temperature sensor provides the tempera- ture sensed at the incoming suction line pipe. The compressor discharge sensor provides the temperature sensed at the discharge pipe of the compressor. Call to Terminate Cooling The system will call to terminate cooling when the indoor am- bient temperature sensor is equal to or lower than 2°F of the room set temperature. The indoor control board will com- municate to the outdoor control board to de-energize the compressor. The outdoor fan will run for 60 seconds before stopping. The indoor fan motor and louver will continue operating after cooling has been terminated. To stop cool mode, press the power button to turn the sys- tem off, or change to another mode. Freeze Protection Function To prevent freezing of the indoor unit coil during cool mode, when the compressor operates continuously for 10 seconds and the temperature of the indoor coil has been below 32°F for 10 seconds, the compressor will stop, and the error will be recorded in the malfunction list. The indoor unit fan will continue to operate. When the temperature of the indoor coil rises to 45°F for more than 3 minutes the compressor will restart and the system will continue functioning. Heat Mode Overview The setpoint control range in heating mode is 60°F - 86°F. The temperature set by the remote control and the indoor unit ambient temperature sensor will determine if a call for heat is needed. If a call for heat is justified, a temperature compen- sation adjustment is automatically added to the operating parameter and the call is communicated from the indoor unit to the outdoor unit. The indoor unit louver will open using a stepper motor. The indoor fan will not operate at this time. The outdoor unit will shift the 4-way valve to the heat mode position and determine the position of the EEV (if equipped) and speed (frequency) of the compressor. There can be a delay of up to 3 minutes before the outdoor unit fan and com- pressor start. (Tr = room temperature Ts = set temperature) If Tr ≤ Ts, the outdoor unit will operate and the indoor fan operates in cold air prevention function If Tr > Ts+, the outdoor unit turns off and the indoor fan oper- ates at heat residue sending mode. If Tr < Ts+, the outdoor unit will restart and the indoor fan operates in cold air proof mode. The speed of the indoor fan can be controlled manually by the user or automatically by the system. The speed can be changed between HIGH, MEDIUM, and LOW. The predeter- mined conditions for automatic control are as follows: High Speed: Tr < Ts Medium Speed: Ts ≤ Tr ≤ Ts + 4°F Low Speed: Tr > Ts + 4°F When the indoor fan is running in automatic mode and there is no delay when the speed switches from high to low, the indoor fan will maintain high speed for a period of 3 minutes before switching to low speed. Cold Air Proof Operation At initial start of heat mode, indoor blower will not be turned on immediately until indoor coil temperature senses a mini- mum temperature. This period usually takes 30 seconds to 3 minutes depending on the outdoor ambient temperature. HSU12�HG(DB)-SM Wiring Diagrams *Indoor fan control manual control: You can choose high, medium, low and automatic speed control. Automatic: When Tr Ts+2�, low speed. When the airflow speed has no delay from the high to low switching, the speed should be d 3 minutes (remain at high speed for 3 minutes.) before the next switch. *Airgate location control: the location for the airgate can be set according to your needs. Coldair proof operation 1. The indoor operation within 4 minutes after the start up is as the following diagram, the can be raised only after the speed has reached a certain level. � � � � � � � � � � 2. 4 minutes after the start up of the indoor fan, the light airflow and the low airflow will be tur set speed airflow. 3. In the cold air proof operation, the fan won’t stop after the start up. 4. During the cold air proof operation, the indoor system will continuously send ‘indoor hi signals to the outdoor system. * Residue heat sending. The indoor fan will send the residue heat at a low speed for 12 seco If other conditions are satisified, when the compressor stops, the indoor system will operate speed. The indoor fan will stop when the coil temperature is below the ‘heat start temp 4’. * Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan and the indoor temperature display won’t change. At the time, any indoor coil malfunctio neglected. When the outdoor defrosting finishes, the coil malfunction will still be neglected compressor has been started up for 30 seconds. The indoor temperature display will not ch the system operates at the cold air proof mode. * Automatic heating temperature compensation: when the system enters the heating m temperature compensation (4) will be added. When the status is switched off, the compen be erased. Heat start temp 1 Heat start temp 2 Heat start temp 3 Heat start temp 4 Set speed Low speed Light speed Fan/off Fan/off Keep the high speed. The fan doesn’t stop 4 minutes after the indoor fan starts, the light or low speed will switch to the set speed. In cold air proof operation, the fan remains on after startup. Residual heat sending: The indoor fan will operate on low speed for 12 seconds. Outdoor unit temperature sensors: Outdoor ambient, defrost, suction line, and compressor discharge, used in conjunction with the indoor temperature sensors, indoor ambient and tube, provide information to the outdoor control board to monitor the system and regulate the frequency of the compressor, EEV positioning, and outdoor fan speed to achieve the desired room temperature.

SEQUENCE OF OPERATION

PAGE 24 ENGLISH When heating has been satisfied, the outdoor unit compres- sor will turn off first and followed by the outdoor fan. The 4-way valve will de-energize 2 minutes after compressor stops. The indoor unit fan will continue to run at minimum speed until indoor coil temperature reaches a minimum tem- perature and it will turn off. If the system detects a malfunc- tion, it may shut down or show an error code on the indoor unit display board and/or outdoor unit main board LED. Defrost When the system initiates a call for defrost, the indoor fan motor stops. The indoor unit display will not change. Any indoor unit malfunctions will be ignored at this time. The sys- tem will cycle through the defrost operation. Any indoor unit malfunctions will be ignored until the compressor restarts and has been operating for 30 seconds. At the conclusion of the defrost cycle, the indoor fan will enter the cold air proof operation. Heat mode resumes. Automatic Heating Temperature Compensation When the system enters heating mode, a temperature com- pensation adjustment is added to the operating parameter. This adjustment is canceled when exiting heat mode. Indoor Unit To enter the heat mode, point the infrared remote controller at the indoor unit and press the power button, then press the HEAT mode button if not already set to heat mode. The signals received by the infrared receiver are relayed to the main board of the indoor unit to turn the system on and set it to heat mode. The indoor unit main board will activate the display on the in- door unit, illuminating the display, indicating the temperature and current status of the unit. The indoor unit main board will signal the louver stepper mo- tor to open the louver to a stationary position. The indoor unit main board will power up the indoor fan motor after the outdoor unit has started and heating of the indoor coil has taken place (see cold air proof operation). The indoor fan motor has a feedback circuit which provides the indoor unit main board with information for controlling the speed of the fan motor. Temperature Sensors The indoor unit has two sensors that provide temperature in- formation to the indoor unit main board. The indoor ambient temperature sensor, and coil temperature sensor, are used for controlling the system during heat mode. The resistance values of the sensors will vary with tempera- ture. The resistance to temperature values can be found using a temperature / resistance chart specific to the sensor being checked. Communication The indoor and outdoor unit main boards communicate via a digital signal on the wire connected to terminal 3C of each unit. A splice or break in this wire will cause a communication error. When a command is received from the remote control, the indoor unit main board communicates with the outdoor unit main board via the terminal 3C wire to perform the requested function. Outdoor Unit Upon a request for heat, the outdoor unit main board applies power to the 4-way valve, outdoor fan motor and compres- sor. Depending on system cycling, there may be up to a 3 minute wait period before the compressor and outdoor fan start.) NOTE: Do not measure compressor voltages, damage to the volt meter may result. If the ambient room temperature is above the set tempera- ture, yet lower than 2°F above the set temperature, the system will adjust the running frequency of the compressor automatically according to changes in ambient temperature. The outdoor unit main board also controls the position of the EEV (Electronic Expansion Valve) to regulate the flow of refrigerant to the unit evaporator coil. Temperature Sensors Four temperature sensors located in the outdoor unit provide temperature information to the outdoor unit main board for control of the system during heat mode. The outdoor ambient temperature sensor provides the tem- perature of the air drawn into the condenser coil. The defrost temperature sensor provides the temperature sensed at the output of the outdoor coil. The suction line temperature sensor provides the tempera- ture sensed at the incoming suction line pipe. The compressor discharge sensor provides the temperature sensed at the discharge pipe of the compressor. Call to Terminate Heating The system will call to terminate heating when the indoor ambient temperature sensor is equal to or higher than 2°F above the room set temperature. The indoor control board will communicate to the outdoor control board to de-ener- gize the compressor. The outdoor fan will run for 60 seconds before stopping. The 4-way valve will de-energize 2 minutes after the compressor stops. To stop heat mode, press the power button to turn the sys- tem off, or change to another mode.

SEQUENCE OF OPERATION

PAGE 25 ENGLISH Auto Mode With the system turned on, press the AUTO button on the remote control. The system will change to the auto mode of operation. As the room is cooled or heated, the system will automati- cally switch between cool mode, fan mode, and heat mode. There is a minimum 15 minute operating time between mode changes. Dry Mode Overview The temperature control range in Dry mode is 60°F - 86°F. This mode is used for the purpose of dehumidification. (Tr = room temperature Ts = set temperature) When Tr > Ts + 4°F, the compressor will turn on and the indoor fan will operate at the set speed. When Ts ≤ Tr ≤ Ts + 4°F, the compressor will operate at the high dry frequency for 10 minutes, then at the low dry mode for 6 minutes. The indoor fan will operate at low speed. When Tr < Ts, the outdoor unit will stop, and the indoor fan will stop for 3 minutes, then operate at the low speed option. Automatic fan speed: When Tr >= Ts + 9°F, High speed When Ts + 5.4°F ≤ Tr < Ts + 9°F, Medium speed When Ts + 3.6°F ≤ Tr < Ts + 5.4°F, Low speed When Tr < Ts + 3.6°F, Light speed Note: TURBO and QUIET mode must be set using the remote controller. If the outdoor fan is stopped, the indoor fan will pause for 3 minutes. If the outdoor fan is stopped for more than 3 minutes, and the compressor is still operating, the system will change to light speed mode. Indoor unit To enter the dry mode, point the infrared remote control at the indoor unit and press the power button, then press the DRY mode button if not already set to dry mode. The signals received by the infrared receiver are relayed to the main board of the indoor unit to turn the system on and set it to dry mode. The indoor unit main board will activate the display of the indoor unit, illuminating the display, indicating the room tem- perature and current status of the unit. The indoor unit main board will signal the louver stepper mo- tor to open the louver to either a stationary position, or one of several oscillating modes. As the louver opens, the indoor unit main board will power up the indoor fan motor, operating the fan at the speed last set. The indoor fan motor has a feedback circuit which provides the indoor unit main board with information for controlling the speed of the fan motor. (See overview section for more information.) Temperature Sensors The indoor unit has two sensors that provide temperature information to the indoor unit main board. An indoor ambient temperature sensor, and coil temperature sensor are used for controlling the system during dry mode. The resistance val- ues of the sensors will vary with temperature. The resistance to temperature values can be found using a temperature / resistance chart specific to the sensor being checked. Communication The indoor and outdoor unit main boards communicate via a digital signal on the wire connected to terminal 3C of each unit. A splice or break in this wire will cause a communication error. When a command is received from the remote control, the indoor unit main board communicates with the outdoor unit main board via the terminal 3C wire to perform the requested function. Outdoor Unit Upon a request for dry mode, the outdoor unit main board applies power to the outdoor fan motor and compressor. Depending on system cycling, there may be up to a 3 minute wait period before the compressor and outdoor fan start.) WARNING: Do not measure compressor voltages, damage to the volt meter may result. The outdoor unit main board also controls the position of the EEV (Electronic Expansion Valve) to regulate the flow of refrigerant to the indoor unit evaporator coil. Temperature Sensors Four temperature sensors located in the outdoor unit provide temperature information to the outdoor unit main board for control of the system during dry mode. The outdoor ambient temperature sensor provides the tem- perature of the air drawn into the outdoor coil of the outdoor unit. The defrost temperature sensor provides the temperature sensed at the output of the outdoor coil.

SEQUENCE OF OPERATION

PAGE 26 ENGLISH The suction line temperature sensor provides the tempera- ture sensed at the incoming suction line pipe. The compressor discharge sensor provides the temperature sensed at the discharge pipe of the compressor. To stop dry mode, press the power button to turn the system off, or change to another mode. Defrost Operation Defrosting Program Entry Conditions Condition 1: For the first time to power on the unit , the compressor should run for 30 min accumulatively and run continuously for 1 min . When meeting the frosting condition, the defrosting is allowed. Condition 2: After the first defrosting , the compressor with heating mode should run for 30 min accumulatively and run continuously for 1 min. and the time interval between de- frosting cycle is more than 45 min. When meeting the frosting condition, the defrosting is allowed. Conditions Used to Determination if Frost has Formed Under the running state of the compressor , by detecting defrost sensor Te and outdoor ambient temperature sen- sor Tao, it can satisfy any of the following conditions for 2 minutes continuously and is considered to meet the frosting conditions Condition 1: Let Tes(condensation temperature) = C×Tao-α, When Tao < 0 32OF then C=0.8 , when Tao≥32OF then C=0.6 , α is set to a constant = 5. Condition 2: Meet condition 1, and ΔT1-T1≥35.6OF, T1 is defined as Δ T1’s minimum value, Δ T1 = T(outdoor ambient temperature )-T (outdoor coil temperature). Defrost Actions • When C×Tao-α≥23OF, then Te≤23OF and the defrost cycle is 45min(Benchmark defrost cycle). • When 14OF ≤C×Tao-α<23OF , then Te≤Tes and defrost cycle is 45min(Benchmark defrost cycle). • When 8.6OF < C×Tao-α ≤14OF , then Te≤Tes and defrost cycle is 65min (Def1 =65min-Benchmark defrost cycle ). • When 5OF ≤C×Tao-α ≤ 8.6OF, then Te≤Tes and defrost cycle is 65min (Def1 =65min-Benchmark defrost cycle ). • When C×Tao-α<5OF, then Te≤ 5OF and defrost cycle is 75min (Def2 =75min-Benchmark defrost cycle ). • When defrosting begins, the compressor stops for 1min first and outdoor fan runs at a high speed, after 50s, the 4-way off and then after 55s , the outdoor fan stops. • The compressor start after 1min, the compressor run- ning for 60s at defrosting frequency 38Hz and then running for 60s defrosting frequency 58Hz and running for 60s at defrosting frequency 88Hz , the final run is 88Hz. • During the defrosting period, the mechanical and electrical current of the compressor and the air vent of the com- pressor are effectively protected. • After entering defrosting, the minimum running time must be guaranteed 2 minutes before exiting defrosting. Defrosting Exit Conditions When any of the following conditions are met, the defrosting operation returns to the heating operation • The temperature of the outdoor coil exceeds 44.6OF for 60 seconds continuously • The temperature of the outdoor coil exceeds 53.6OF for 20 seconds continuously • Continuous 11 minutes for defrosting operation • During defrosting, valve opening remains unchanged at 200, and the opening of defrosting starting valve is con- trolled according to starting oil return Protection Functions TTC High Temperature Protection The compressor discharge pipe sensor (exhaust temp) senses the temperature of the refrigerant exiting the com- pressor. The sensed temperature received from the sensor by the control circuitry will cause the compressor frequency to increase or decrease. (see chart below). If a temperature of >= 230°F is sensed for 20 seconds, an exhaust overheating protection error code will be indicated at the outdoor unit. Abnormal stop Decreasing the frequency rapidly (1HZ/1second) TTC (°F) 230°F 212°F 209°F 199°F 194°F Decreasing the frequency slowly (1HZ/10 seconds) The frequency doesn’t change Increasing the frequency (1HZ/10 seconds) Increasing the frequency (1HZ/1second)

SEQUENCE OF OPERATION

PAGE 27 ENGLISH Anti-Freeze Protection of the Indoor Coil The temperature sensed by the indoor unit coil sensor is used to determine what frequency the compressor is to run at for freeze protection. Tpg_indoor: indoor unit pipe sensor temperature When Tpg_indoor < Tpg1, the frequency of the compressor decreases at the rate of 1HZ / 1 second. When Tpg_indoor < Tpg2, the frequency of the compressor decreases at the rate of 10HZ / 10 seconds. When Tpg_indoor begins to rise again, and Tpg2 ≤ Tpg_indoor ≤ Tpg3, the frequency of the compressor does not change. When Tpg3 < Tpg_indoor Tpg4, the compressor will restart. 59°F // ice_temp_3+5 46°F // ice_temp_3+2 43°F Decreasing slowly Decreasing rapidly ice_temp_1 Stop Keeping the frequency Increasing slowly 32°F 37°F 41°F 43°F 48°F Anti-Freeze Protection of the Base Pan To prevent freezing; the base pan equipped with electrical heater. Its operational conditions are as follows: If outdoor temperature is above 37.4°F, the electrical base pan heater is off. Between 24.8°F and 33.8°F outdoor temperature; the elec- trical base pan heater is off for 20 minutes, then on for 10 minutes. Between 10.4°F and 24.8°F; the electrical base pan heater is off for 15 minutes, then on for 15 minutes. If outdoor tem- perature <10.4°F, the electrical base pan heater is on. Overheating Protection For Indoor Unit The indoor coil sensor senses the temperature of the indoor coil. If the temperature sensed is greater than 133°F, the com- pressor frequency will decrease to prevent overheating of the heat exchanger. If Tc >= 133°F for more than 10 seconds, the compressor will stop and an error code will be indicated at the outdoor unit. If the compressor is off for 3 minutes and Tc <118°F, the com- pressor will restart. If the temperature sensed is lower than 118°F, the protection function is cancelled. HSU12�HG(DB)-SM Wiring Diagrams 25 Domestic Air Conditioner 5.2.5.2�TC high temperature-preventing control of the indoor heating unit� Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running state). The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the temperature is higher than 55�, decrease the rotate speed of the compressor and do the high temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat exchanger is lower than 47�, recover to the normal control. TC The compressor stops Fgh_t1 65� Fgh_t1�2 Fgh_t2�2 N Decreasing the frequency rapidly Fgh_t2 59� P Decreasing the frequency slowly Fgh_t3 55� Fgh_t3�2 Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 51� R Increasing slowly Fgh_t5 47� Fgh_t5—2 Normal N�Decreasing at the speed of 1HZ/1 second P�Decreasing at the speed of 1Hz/10 seconds Q�Continue to keep the last-time instruction cycle R�Increasing at the speed of 1Hz/10seconds Remarks: the outdoor unit 5.2.5.3 The control of preventing the overcurrent of the compressor� �During the starting process of the compressor, if the curren of the compressor is greater than 17A for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only after the the power is off. �During the starting process of the compressor, if the AC current is greater than 12A, the frequency of the compressor decreases at the speed of 1HZ/second. �During the starting process of the compressor, if the AC current is greater than 10A, the frequency of the compressor decreases at the speed of 0.1HZ/second. �During the starting process of the compressor, if the AC current is greater than 9A, the frequency of the compressor increases at the prohibited speed. �During the starting process of the compressor, if the AC current is greater than 8A, the frequency of the compressor increases at the speed of no faster than 0.1HZ/second. 149°F 138°F 131°F 124°F 117°F Compressor Overcurrent Protection If the current draw of the compressor at start-up is greater than the overcurrent point listed on the chart below for ap- proximately 3 seconds, the compressor will stop, and a code will be indicated at the outdoor unit. After 3 minutes the compressor will try to restart. If the overcurrent condition occurs 3 times in 20 minutes, the system will lock-out, and a code will be indicated at the outdoor unit. It will be necessary to remove power to the system to reset the lock-out condi- tion. The frequency of the compressor may change depending on the current draw at start-up. Refer to the chart and current/ Hz table shown below. Greater than current 1: Decreases 1Hz/second Greater than current 2: Decreases 0.1Hz/second Greater than current 3: No change Model Over current Point (Approx.) Decline Speed Current 1 (Approx.) Decline Speed Current 2 (Approx.) Decline Speed Current 3 (Approx.) 09K 11A 8.5A 8A 7A 12K 13A 10A 9.5A 8.5A 15K 15A 12A 11.5A 10.5A 18K 15A 12A 11.5A 10.5A 24K 17A 13.5A 13A 12A

ERROR CODES & PROBLEM SOLVING

PAGE 29 ENGLISH Error Codes & Problem Solving Table of Contents Error Codes and Description Indoor Display ..................................................................................................................... 30 Indoor Unit Display ......................................................................................................................................................................... 30 Indoor AC Fan Motor Malfunction ..................................................................................................................................... 31 Indoor Unit Display ......................................................................................................................................................................... 31 E14 ............................................................................................................................................................................ 31 Outdoor DC Fan Motor Fault ............................................................................................................................................. 32 Outdoor�Unit�Display ..................................................................................................................................................................... 32 LED1 Flashes 9 Times .............................................................................................................................................. 32 IPM Protection ................................................................................................................................................................ 33 Outdoor�Unit�Display ..................................................................................................................................................................... 33 LED1 Flashes 2 Times .............................................................................................................................................. 33 Over-current of the Compressor ...................................................................................................................................... 33 Outdoor�Unit�Display ..................................................................................................................................................................... 33 LED1 Flashes 3 or 24 or 25 Times ........................................................................................................................... 33 The Communication Fault Between IPM and Outdoor PCB ................................................................................................ 34 Outdoor�Unit�Display ..................................................................................................................................................................... 34 LED1 Flash 4 Times .................................................................................................................................................. 34 Power Supply Too High or Too Low ................................................................................................................................... 35 Outdoor�Unit�Display ..................................................................................................................................................................... 35 LED1 Flashes 6 Times .............................................................................................................................................. 35 Overheat Protection for Discharge Temperature .............................................................................................................. 36 Outdoor�Unit�Display ..................................................................................................................................................................... 36 LED1 Flashes 8 Times .............................................................................................................................................. 36 Communication Fault Between Indoor and Outdoor Units ................................................................................................ 36 Indoor Unit Display ......................................................................................................................................................................... 36 E7 .............................................................................................................................................................................. 36 � Outdoor�Unit�Display .....................................................................................................................................................................36 LED1 Flashes 15 Times ............................................................................................................................................ 36 Loss of Synchronism Detection ........................................................................................................................................ 37 Outdoor�Unit�Display ..................................................................................................................................................................... 37 LED1 Flashes 18 or 19 Times .................................................................................................................................. 37 Indoor Unit Overload in Heating Mode .............................................................................................................................. 37 Outdoor�Unit�Display ..................................................................................................................................................................... 37 LED1 Flashes 18 Times ............................................................................................................................................ 37 Checking System Components ........................................................................................................................................ 38 Checking Outdoor Unit Components ............................................................................................................................... 38 Checking�the�Outdoor�Unit�Sensors ............................................................................................................................................. 38 � Checking�the�Reversing�Valve�Coil ................................................................................................................................................ 38 � Checking�the�DC�Fan�Motor ........................................................................................................................................................... 38 � Checking�the�EEV�Stepper�Motor .................................................................................................................................................. 38 � Checking�the�PFC�Reactor ............................................................................................................................................................. 38 � Checking�the�Socket�Protect�Component ....................................................................................................................................39 � Checking�the�Compressor�Windings ............................................................................................................................................. 39 � Checking�the�Electrical�Base�Pan�Heater ......................................................................................................................................39 Checking Indoor Unit Components ................................................................................................................................... 39 Checking�the�Indoor�Unit�Sensors ................................................................................................................................................. 39 � Checking�the�Up/Down�or�Left�Stepper�Motor ............................................................................................................................ 40 � Checking�the�Indoor�DC�Fan�Motor ............................................................................................................................................... 40 Optimizing Performance .................................................................................................................................................. 40 Cleaning the Front Cover .................................................................................................................................................. 40 Troubleshooting Tips ....................................................................................................................................................... 41

ERROR CODES & PROBLEM SOLVING

PAGE 30 ENGLISH Code Indication Description Indoor Outdoor (LED1 flash times) Indoor & Outdoor E7 15 Communication fault between indoor and outdoor units Indoor Malfunction E1 / Room temperature sensor failure E2 / Coil sensor failure E4 / Indoor EEPROM error E14 / Indoor fan motor malfunction Outdoor Malfunction F12 1 Outdoor EEPROM error F1 2 The protection of IPM F22 3 Overcurrent protection of AC electricity for the outdoor model F3 4 Communication fault between the IPM and outdoor PCB F19 6 Power voltage is too high or low F27 7 Compressor has a locked rotor or stopped momentary F4 8 Overheat protection for exhaust temperature F8 9 Outdoor DC fan motor fault F21 10 Defrost temperature sensor failure F7 11 Suction temperature sensor failure F6 12 Ambient temperature sensor failure F25 13 Exhaust temperature sensor failure F11 18 Deviate from the normal for the compressor F28 19 Station detect loop error F2 24 Compressor overcurrent F23 25 Overcurrent protection for single-phase of the compressor F36 39 Outdoor coil temperature sensor failure Indoor Unit Display Error codes will be display on the indoor unit in place of the set temperature. Error Codes and Description Indoor Display

ERROR CODES & PROBLEM SOLVING

PAGE 31 ENGLISH Indoor AC Fan Motor Malfunction Indoor Display E14 This is caused by an indoor motor or indoor PCB fault Spare Parts: Indoor PCB Indoor motor Check voltage at fan plug at PCB. Fan motor is at fault Replace motor Indoor PCB is faulty, change indoor PCB No Yes

ERROR CODES & PROBLEM SOLVING

PAGE 32 ENGLISH Outdoor DC Fan Motor Fault Outdoor Display LED1 Flashes 9 Times This is caused by an outdoor motor or outdoor PCB fault Spare Parts: Outdoor PCB Outdoor motor Turn power off and check whether the outdoor motor plug connection is secure Restore power to the unit and turn system on in Cool mode. Does the fan motor operate? Measure for a voltage of 0-5V between pins 3 and 6 Outdoor motor fault Outdoor PCB fault Re-seat the plug 1. Measure for an approx. voltage of 310V between pins 1 and 3 of the motor connector on the PCB 2. Measure for an approx. voltage of 15VDC between pins 3 and 4 of the motor connector on the PCB 3. Measure for an approx. voltage of 0-6V between pins 3 and 5 of the connector on the PCB No No Yes Yes Yes Yes No No 6 5 4 3 2 1

ERROR CODES & PROBLEM SOLVING

PAGE 33 ENGLISH IPM Protection Outdoor Display LED1 Flashes 2 Times Under this error, please ensure the refrigerant system pressure is normal with no blockages, then replace power module Spare Parts: Power module Refrigerant Turn the unit on. Is the error displayed before the compressor starts? The power module is faulty, replace the module Problem persists? Check for proper refrigerant charge The compressor starts normally, but malfunctions are reported after it has operated for a period of time. No Yes Yes Yes Yes Over-current of the Compressor Outdoor Display LED1 Flashes 3 or 24 or 25 Times Spare Parts: Power module Refrigerant The compressor starts normally, but malfunctions are reported after it has operated for a period of time. Correct the power supply Turn the unit on. Is the error displayed before the compressor starts? Is the power supply voltage normal? Check the refrigerant charge The power module is faulty, replace the power module Yes Yes Yes No No

ERROR CODES & PROBLEM SOLVING

PAGE 34 ENGLISH The Communication Fault Between IPM and Outdoor PCB Outdoor Display LED1 Flash 4 Times Spare Parts: Power module Outdoor PCB 1) Check the plugs of MODULE COM and MODULE POWER on the outdoor PCB and IPM modules for secure connections 2) Check the P & N wires between the outdoor PCB and IPM modules for secure connections Are the connections secure? Replace the power module 1. Measure for an approx. voltage of 5VDC between pins 1 and 2 of the Module Power connector 2. Measure for an approx. voltage of 15VDC between pins 2 and 3 of the Module Power connector Re-seat the connections Replace the outdoor PCB Yes Yes No No

ERROR CODES & PROBLEM SOLVING

PAGE 35 ENGLISH Power Supply Too High or Too Low Outdoor Display LED1 Flashes 6 Times Spare Parts: Power module Turn the unit on. Is the compressor operating normally? The power supply is unstable. Replace power module Replace power module Check the P & N terminals of the power supply on the outdoor PCB. Is the voltage >390V or <150V AC? Verify proper voltage to terminals L1 & L2 of the outdoor unit Correct power source No No No Yes Yes Yes

ERROR CODES & PROBLEM SOLVING

PAGE 36 ENGLISH Overheat Protection for Discharge Temperature Outdoor Display LED1 Flashes 8 Times Spare Parts: Outdoor PCB Exhaust sensor Turn the unit on. Check the exhaust temperature of the compressor. The power supply is unstable. There is loss of refrigerant Check refrigerant charge The outdoor PCB is faulty, replace the PCB Does the temperature exceed 230F shortly after the compressor starts up? Check exhaust temp sensor resistance. Is it correct? The sensor is faulty, replace the sensor No No No Yes Yes Yes Communication Fault Between Indoor and Outdoor Units Indoor Display Outdoor Display E7 LED1 Flashes 15 Times Spare Parts: Indoor PCB Outdoor PCB Power module Correct the wiring between the indoor and outdoor units 1. Check that the wiring connections are securely fastened 2. Check whether the LN wires are reverse connected Check the outdoor PCB LED No Yes LED LED 1 LED 2 Solution ON/OFF OFF ON Outdoor PCB fault ON/OFF ON ON This is caused by Outdoor PCB or Indoor PCB fault. Change one part firstly, it still unsolved, change another one. ON/OFF OFF OFF This is caused by Outdoor PCB or Power module fault. Change one part firstly, if still unsolved change another one.

ERROR CODES & PROBLEM SOLVING

PAGE 37 ENGLISH Loss of Synchronism Detection Outdoor Display LED1 Flashes 18 or 19 Times Spare Parts: Compressor Power module 1. The compressor wiring is incorrect or has bad connections 2. The compressor is damaged Turn the unit on. Does the compressor start? The compressor starts, but soon stops. LED1 on the outdoor PCB starts blinking 18/19 times at a 1Hz rate The power module is faulty, replace the power module The compressor is faulty, replace the compressor Yes Yes Problem Remains No Indoor Unit Overload in Heating Mode Outdoor Display LED1 Flashes 18 Times Spare Parts: Indoor pipe sensor Indoor PCB Refrigerant Recharge to specifications 1. The pipe sensor is faulty 2. The indoor PCB is faulty Clean the air filter Check the system refrigerant charge. Is it over or under charged? Is the malfunction reported after the unit has been operating for a period of time Is the indoor air filter dirty? No No Yes Yes Yes

ERROR CODES & PROBLEM SOLVING

PAGE 38 ENGLISH Checking System Components Checking Outdoor Unit Components NOTE: Component resistance readings shown in this section are for reference only. Actual resistance values may differ based on model being tested. Component readings shown below are based on a model HSU12VHGL-W outdoor unit. significantly different from 2.08K Ohms. Step 3 Re-seat the plug on the connector at the conclusion of the test. Checking the DC Fan Motor Step 1 Disconnect the DC Fan Motor plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 Refer to the chart shown below for plug pin combinations and resistance values. Note: Test is polarity sensitive, adhere to probe placement as shown in chart. Red Test Lead Black Test Lead Red --- Black White Yellow Blue Red --- 3.10 Meg 3.05 Meg 3.28 Meg Charges to infinity --- --- --- --- --- Black 43.85K 145.1K Charges to infinity White 189.0K Charges to infinity Yellow Charges to infinity Blue Step 3 Re-seat the plug on the connector at the conclusion of the test. Checking the EEV Stepper Motor Step 1 Disconnect the EEV Stepper Motor plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 Refer to the chart shown below for plug pin combinations and resistance values. White Yellow Orange Blue Red Grey White --- 92.6Ohm --- 47.0 Ohm --- Yellow --- 93.1 Ohm --- 47.0 Ohm Orange 46.5 Ohm --- Blue 46.8 Ohm Red --- Grey Step 3 Re-seat the plug on the connector at the conclusion of the test. Checking the PFC Reactor Step 1 Disconnect wires from terminals LI and LO of the power module board. Step 2 Using an Ohmmeter, check the resistance value of the PFC Reactor. The resistance value of the coil is 1.30 Ohms max. If the resistance value differs from this value, verify the Testing of the following components requires the use of an Ohmmeter and Temperature Probe. (Temperature probe is used during sensor testing only). NOTE: When using the test probes, probe the back or side contacts of the plug to obtain the reading. Do not try to probe the connector end of the plug as this may damage the contacts of the plug. Checking the Outdoor Unit Sensors NOTE: Use respective temperature / sensor chart for sensor type being tested. Compressor discharge sensor Suction sensor Tube sensor (defrost temperature) Ambient sensor Step 1 Disconnect the sensor plug from the control board for this test. Failure to do so may provide inaccurate readings. Step 2 Using a temperature probe, measure the temperature of the sensor being tested. Step 3 Using an Ohmmeter, check the resistance value of the sensor. Step 4 Referring to the temperature / resistance table for the sensor being checked, verify the resistance value corresponds to the temperature checked in step 2. Replace the sensor if the reading is open, shorted, or outside the specifications of the temperature / resistance table. Step 5 Re-seat the plug on the connector at the conclusion of the test. Checking the Reversing Valve Coil Step 1 Disconnect the reversing valve plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 Using an Ohmmeter, check the resistance value of the coil. The resistance value of the coil is 2.08K Ohms. Replace the valve coil if the reading is open, shorted, or a value

ERROR CODES & PROBLEM SOLVING

PAGE 39 ENGLISH wiring and connections to the PFC Reactor as well as the PFC Reactor itself. Repair or replace as necessary. Step 3 Reconnect the wiring to the module board at the conclusion of the test. Checking the Socket Protect Component Step 1 Disconnect the Socket Protect plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 Using an Ohmmeter, check the resistance value of the Socket Protect component. The resistance reading should be 0 Ohms. If it is not, replace the component. Step 3 Re-seat the plug on the connector at the conclusion of the test. Checking the Compressor Windings Step 1 Disconnect wiring from terminals U (black wire), V (white wire), and W (red wire) of the power module board. Step 2 Using an Ohmmeter, check the resistance value of the compressor windings. Measure between wires U (black wire) and V (white wire), U (black wire) and W (red wire), and V (white wire), and W (red wire). The resistance value of the windings should be nearly balanced. Check the manufacturer reference table for the compressor winding values. Repair or replace as needed. Step 3 Reconnect the wiring to the module board at the conclusion of the test. NOTE: Component resistance readings shown in this section are for reference only. Actual resistance values may differ based on model being tested. Component readings shown below are based on a model HSU12VHGL-G indoor unit. Checking Indoor Unit Components Testing of the following components requires the use of an Ohmmeter and Temperature Probe (Temperature probe is used during sensor testing only). NOTE: When using the test probes, probe the back or side contacts of the plug to obtain the reading. Do not try to probe the connector end of the plug as this may damage the contacts of the plug. Checking the Indoor Unit Sensors NOTE: Use respective temperature / sensor chart for sensor type being tested. Coil sensor Ambient sensor Step 1 Disconnect the sensor plug from the control board for this test. Failure to do so may provide inaccurate readings. Step 2 Using a temperature probe, determine the temperature of the sensor being tested. Step 3 Using an Ohmmeter, check the resistance value of the sensor. Step 4 Referring to the temperature / resistance table for the sensor being checked, verify the resistance value corresponds to the temperature checked in step 2. Replace the sensor if the reading is open, shorted, or outside the specifications of the temperature / resistance table. Step 5 Re-seat the plug on the connector at the conclusion of the test. Checking the Electrical Base Pan Heater If the test range of resistance between the two terminals of electrical base pan heater was between 100 and 500ohm, then the heater is normal. Test the resistance between the two terminals of the heater. If it is open or short circuited, the heater is broken.

ERROR CODES & PROBLEM SOLVING

PAGE 40 ENGLISH Checking the Up/Down or Left Stepper Motor Step 1 Disconnect the Up/Down or Left Stepper Motor plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 There are five wire colors; red, orange, yellow, purple and blue. The resistance between the red wire and any other wire should be 200 to 300Ω approximately. Step 3 Re-seat the plug on the connector at the conclusion of the test. Checking the Indoor DC Fan Motor Step 1 Disconnect the DC Fan Motor plug from the control board connector for this test. Failure to do so may provide inaccurate readings. Step 2 Refer to the chart shown below for plug pin combinations and resistance values. Note: Test is polarity sensitive, adhere to probe placement as shown in chart. Red Test Lead Black Test Lead Pink X X Black White Blue Yellow Pink X X 15.27Meg 15.46 Meg Infinity 15.85 Meg X X X X X X X X X X X Black 108.2K Infinity 241.8K White Infinity 349.5K Blue 5.14 Meg Yellow Step 3 Re-seat the plug on the connector at the conclusion of the test. Optimizing Performance Cleaning the Front Cover 1. Open the front cover by pulling it upward 2. Remove the Filter: Gently push up on the filter’s center tab until it is released from the stopper, and remove the filter in a downward motion. 3. Clean the filter Use a vacuum cleaner to remove dust, or wash the filter with water. After washing, dry the filter completely. 4. Attach the filter Attach the filter so that the “FRONT” label is facing outward. Make sure that the filter is securly attached behind the holding tabs. If the filter is not attached correctly the unit may not achieve maximum efficiency. 5. Close the front cover.

Table of Contents

Outdoor Board Diagram ...................................................................................................................................................44 Outdoor Board Schematic ................................................................................................................................................45 Indoor Board Diagram ......................................................................................................................................................47 Indoor Board Schematic ...................................................................................................................................................48 Module Board Schematic ..................................................................................................................................................50 Room and Pipe Sensor Tables ...........................................................................................................................................51 Ambient, Defrost & Pipe Sensor Tables .............................................................................................................................54 Discharge Sensor Tables ..................................................................................................................................................57

Outdoor Board Diagram

REFERENCE INFORMATION PAGE 56 ENGLISH Outdoor Board Diagram 09K-12K 18K-24K ADVERTENCIA AVERTISSEMENT 1(N) 3(C) 2(L) YEL YEL SOCKET PROTECT CN45 BLOCK AC-L AC-N CN2 CN1 R W B N COM CN36 TERMINAL W Y/G GND G TO INDOOR UNIT POWER G Y/G B BL CN3 PE Y/G Condensor LED2 CN48 B W BOTTOM ELECTRIC HEATER Electrical Shock Hazard Capacitor retains charge after power is disconnected. Confirm voltage at capacitor has dissipated (<10V DC) with hand held ohm meter before servicing. LED light between CN25 and CN28 should be off. Riesgo de Descarga Eléctrica El capacitor retiene carga una vez desconectada la corriente. Confirme que el voltaje del capacitor se haya disipado (<10V DC) apoyando la mano sobre el ohmnímetro antes de realizar el servicio técnico.La luz LED que se encuentra entre CN25 y CN28 deberá estar apagada. Risque de choc électrique Le condensateur conserve sa charge après la coupure de l’alimentation électrique. Avant de procéder à une réparation, vérifiez que le courant au condensateur s’est dissipé (<10VCC) à l’aide d’un ohmmètre manuel. Le voyant DEL entre CN25 et CN28 doit être éteint. Note:The dotted parts are optional. The @ 1and the @ 2cannot exist at the same time, but must keep one of them . B :Black W :White R :Red Y/G :Yellow/Green BR :Brown OR :Orange BL :Blue GR:Gray AMBIENT TEMP.SENSOR DEFROST TEMP.SENSOR COMP.TEMP.SENSOR TC CS HW CN18CN17 CN19 @1 AMBIENT TEMP.SENSOR DEFROST TEMP.SENSOR COMP.TEMP.SENSOR CN17 CS HW TC @2 XQ CN47 TEMP.SENSOR SUCTION 0010581667H R(U) S(V) C(W) B W R DC FAN OUTDOOR PCB MODULE PCB ELECTRIC EXPANSION BL(or W) BL U V W P N AC-L LI AC-N L0 CN25 N P CN28 GR GR AC-N OUT CN9 CN10 AC-L OUT CN11 4-WAY VALVE M CN22 CN15 VALVE A FUSE1 T25A 250VAC CN24 CN23 MODULE COM MODULE POWER CN7 CN10 B BL BL OR CN2 CN8 CN6 CN1 CN5 CN9 CN11 CN3 CN4 REACTOR B M BR(or B) CAP M VALVE MOTOR WARNING OUTDOOR UNIT WIRING DIAGRAM CAP COMPRESSOR Note:The dotted parts are optional. The @ 1and the @ 2cannot exist at the same time , but must keep one of them . B :Black W :White R :Red Y/G :Yellow/Green BR :Brown OR :Orange BL :Blue GR:Gray CN50 DRED LINE AMBIENT TEMP.SENSOR DEFROST TEMP.SENSOR COMP.TEMP.SENSOR TC CS HW CN18CN17 CN19 @1 AMBIENT TEMP.SENSOR DEFROST TEMP.SENSOR COMP.TEMP.SENSOR CN17 CS HW TC @2 XQ CN47 TEMP.SENSOR SUCTION CN48 0010534175H CN3 CN10 B BL BL OR CN5 CN1 CN4 CN8 CN9 CN2 CN11 CN6 CN7 REACTOR B M R(U) S(V) C(W) B W R DC FAN OUTDOOR PCB MODULE PCB ELECTRIC EXPANSION Y/G Y/G 1 2 3(C) BL(or W) BL U V W P N AC-L LI AC-N L0 CN25 N P CN28 M VALVE MOTOR WARNING OUTDOOR UNIT WIRING DIAGRAM CAP COMPRESSOR CN7 CN6 AC-N OUT AC-L OUT BR(or B) BL(or W) BL(or W) BR(or B) AC-N OUT CN9 CN10 AC-L OUT CN11 4-WAY VALVE M CN22 CN15 VALVE A CN3 PE POWER BL(or W) Y/G CN36 COMB COMA N R CN1 CN2 AC-N AC-L FUSE1 T25A 250VAC CN24 CN23 MODULE COM MODULE POWER TO INDOOR UNIT 2 1 GR GR BR(or B) CAP ADVERTENCIA AVERTISSEMENT B W BOTTOM ELECTRIC HEATER LED2 Electrical Shock Hazard Capacitor retains charge after power is disconnected. Confirm voltage at capacitor has dissipated (<10V DC) with hand held ohm meter before servicing. LED light between CN25 and CN28 should be off. Riesgo de Descarga Eléctrica El capacitor retiene carga una vez desconectada la corriente. Confirme que el voltaje del capacitor se haya disipado (<10V DC) apoyando la mano sobre el ohmnímetro antes de realizar el servicio técnico.La luz LED que se encuentra entre CN25 y CN28 deberá estar apagada. Risque de choc électrique Le condensateur conserve sa charge après la coupure de l’alimentation électrique. Avant de procéder à une réparation, vérifiez que le courant au condensateur s’est dissipé (<10VCC) à l’aide d’un ohmmètre manuel. Le voyant DEL entre CN25 et CN28 doit être éteint.

Outdoor Board Schematic

REFERENCE INFORMATION PAGE 57 Outdoor Board Schematic 11.2.OUTDOORUNIT 11.2.1Control Bard Circuit Diagrams 1 3 GND 4 GND 3 GND 2 GND 1 VCC 8 GND 7 SCL 6 SDA 5 IC6 AT24C02B 1 CN2 AC-L 1 CN1 AC-N Black White FUSE1 T25A 250VAC RV1 S14K350 R1 1M R12 100/1W CX1 225/275V L1 8MH/10A RV2 S14K350 RV3 S14K350 CX2 225/275V PTC1 400N CY1 472/250V/275V CY2 472/250V/275V CY3 103/250V/275V CY4 103/250V/275V 1 CN3 PE SA1 RA-362M K5 12V-25A-891P-1A-C K3 12V-5A-892H(N)-1AC-C K4 12V-5A-892H(N)-1AC-C K2 12V-5A-892H(N)-1AC-C K1 12V-5A-892-1CC-C 1 2 3 CN10 Comment: CX4 103/275V 1 2 3 4 5 6 7 8 9 CN12 1 2 3 4 5 CN13 ST COM 1 CN14 1 CN15 C1 2U/450V COM L H C C COM L H C C 1 2 3 4 5 6 7 GND 12V 10 11 12 13 14 15 16 IC7 ULN2003 +12V 1 2 3 4 5 6 CN16 A B C D C10 104/50V +5V +5V R75 2K LED1 P1 2SA1037AK R47 5.1K/1% R49 10K R50 1K +5V C20 102/50V 1 2 3 4 5 6 CN21 C15 103/50V 310V 0V 15V �� �� R33 2.2K R36 1K R34 1K R13 330/1W R35 1K R37 330 ZD2 10V/0.5W ZD3 5.1V/0.5W 4 3 1 2 IC8 PC817A 4 3 1 2 IC9 PC817A E9 47U/25V N1 Comment: 2SC2412K R41 1K R39 10K R38 330 R40 5.1K/1% C14 102/50V XT1 4M C13 104/50V +5V C12 104/50V R63 560 R65 10K R64 10K 1 2 3 CN20 1 2 3 CN18 1 2 CN19 +5V R76 20K/1% R87 4.7K R88 10K R77 1K C24 104/50V C25 104/50V C26 104/50V E14 4.7U/16V E11 4.7U/16V E12 4.7U/16V E13 4.7U/16V +15V R74 10K/1% R73 10K/1% R54 10K C22 102/50V C21 102/50V R82 47K/1% R80 20K/1% R78 20K/1% R79 1K R81 1K R83 1K C23 104/50V CS(White) )etih TQ(W w) olle W(Y H 1 2 3 CN23 5V COM GND Com with Module (Black) 1 2 3 4 5 CN30 ���� 1 2 3 4 CN31 +5V 1 CN8 AC-N OUT 1 CN9 AC-L OUT Two s- pee d AC Fan s-e pee d AC F an Th er ou - r Way F E-valve(White) R55 1K R56 1K R57 1K R58 1K R67 1K R72 1K R71 1K R70 1K +5V 1 2 CN33 SW TEST(BLUE) CX7 104/275V R48 10K XQ(Red) C11 104/50V R62 10K P2 2SA1037AK R60 10K R61 2K R59 2K FUSE2 T1A/250V W B R53 10K R52 10K R51 10K FUCTION TEST(White) TEST/SS COOL HEAT PC GND (�) +5V R85 10K R66 1K R84 4.7K R68 1K R69 1K N3 2SC2412K N4 2SC2412K White ERROR 1 2 3 CN17 D5 LL4148 D6 LL4148 Yellow/Green 1 2 CN32 TEST/SS GND 1 2 CN11 +12V J1 J2 J3 J6 +5V +5V J7 +12V+12V J8 R91 10K J9 J10 C19 104/50V J15 J16 +15V+15V J13 J14 J12 R92 0 R93 0 R94 0 J17 J19 J23 L2 8MH/10A R2 1M CX3 225/275V CY5 472/250V/275V CY6 472/250V/275V J24 J25 J26 J27 J28 J29 J30 J31 J32 J33 N P P N 1 2 CN36 White Black R86 4.7K K6 12V-5A-892H(N)-1AC-C D11 LL4148 N5 2SC2412K R89 10K J27 J34 1 2 4 3 SW1 R95 10K R96 10K +5V VCC 62 VREF 61 AVSS 59 DC-FANSPEED 13 DC FAN PG 36 Indoor Com OUT 41 Indoor Com IN 38 PC COM 37 NC 33 Terminal Pro 28 MODULE COMOUT 27 MODULE COM IN 26 VSS 50 TEST-EN 24 NC 44 COOL-EN 23 HEAT-EN 22 RESET 6 XIN 9 XOUT 7 VSS 8 E-VALVE-A 5 E-VALVE-B 4 E-VALVE-C 2 E-VALVE-D 1 PTC 64 HEAT-1 63 4-WAY 58 FAN 57 H/L FAN SPEED 42 SCL 30 SDA 29 Fan/E-Valve select 47 HEAT-2 60 VSS 49 VSS 48 Fault Light 31 Fre Adjust 46 HW 54 CS 53 XQ 52 TX 51 NC 45 MODE 3 VCC 10 NC 14 NC 15 NC 17 NC 18 NC 19 NC 20 NC 21 NC 25 NC 11 NC 12 NC 16 NC 32 NC 34 NC 35 NC 40 NC 39 NC 43 SW-2 56 SW-1 55 IC5 R5F212A8SNFA 1 2 3 4 CN7 R98 10K +5V MODE RST 5V GND FLASH � R97 10K R46 0 1 CN5 AC-L 1 CN6 AC-N J4 J5 J22 J35 J36 J37 J38 R99 0 J39 J40 CY7 222/250VAC R4 2K CY10 222/250VAC C16 Comment: 102/50V +5V R42 330 R3 2K/2W D1 1N4007 4 3 1 2 IC11 TLP851/PC851 R43 0 R44 1K 4 3 1 2 IC10 TLP421/PS2561 1 CN4 COM J18 J21 � J20 1 CN25 1 CN27 COM heater N6 Comment: 2SC2412K R100 4.7K R101 4.7K R102 0 R103 4.7K R104 0 Vin 1 D Vout 3 IC4 L7805CV R19 47 C3 102/100V +5V +12V T1 Comment: E22034 D8 N P

Outdoor Board Schematic

REFERENCE INFORMATION PAGE 58 Domestic Air Conditioner 1 3 GND 4 GND 3 GND 2 GND 1 VCC 8 GND 7 SCL 6 SDA 5 IC6 AT24C02B P1 2SA1037AK 5.1K/1% R50 1K C20 102/50V C12 104/50V R63 560 R65 10K R64 10K 10K Com with Module (Black) 1 2 3 4 5 CN30 R55 R56 R57 R58 1 2 CN33 C11 104/50V R62 10K P2 2SA1037AK R60 10K 2K 10K 10K 10K FUCTION TEST(White) TEST/SS COOL HEAT PC GND +5V White +12V 1 2 4 3 SW1 10K 10K 10K R46 0 J35 Vin 1 GND 2 Vout 3 IC4 L7805CV C9 104/50V E8 Comment: 100U/16V R29 47 R19 47 C6 104/50V IC3 TL431C C3 102/100V L3 20UH/1A ZD1 IN5948B E5 470U/25V E6 100U/16V E7 470U/25V E3 22U/25V CY9 222/250VAC D7 MBR1100\SB1100 C2 102/100V R18 47 C7 104/50V R22 1K/0.5W C8 104/50V +5V +12V E4 470U/25V R17 330/1W +15V R32 5.1K/1% R30 1K R28 5.1K/1% R31 1K C5 104/50V R25 10K R26 1K R16 2/1W R14 100K/2W R15 15 C4 103/50V 9 10 +5VD T1 Comment: E22034 7 6 4 5 CY8 472/1KV R27 10K 1 3 R24 5.1K/1% CX5 104/275V ADJ 1 FB 2 CS 3 GND 4 HV 8 NC 7 VCC 6 DRV 5 IC1 NCP1200P100 D9 MUR115\MUR130\ER106 D10 ER106 D8 MBR3100\ER302 4 3 1 2 IC2 PC817A R20 220 R21 220 M1 IRFUC20 1 2 3 CN22 �����(�) J11 R90 0 N P 92 Outdoor Board Schematic

Indoor Board Diagram

Indoor Board Diagram R:Red W:White Y:Yellow Y/G:Yellow/Green B:Black BR:Brown BL:Blue PIPING TEMP.SENSOR AMBIENT TEMP.SENSOR SWITCH EMERGENCY INDOOR UNIT DIAGRAM 0010561514H Notes: 1.The dotted parts are optional. 2.The two pins of CN51 should be shorted, when the second channel(RC) of SW2 is selected. UP-DOWN STEPMOTOR M FUSE1 SW1 CN7 T3.15A/250VAC TO OUTDOOR UNIT 1(N) 3(C) (L) 2 W B Y/G GND CN14 CN6 CN10 LEFT STEPMOTOR CN11 CN5' R C0N1 BL (L) CN21 N S CN51 CN9 CN52 CN23 CN34 WIFI CN2 WIRED CONTROLLER FRESH AIR RIGHT STEPMOTOR ROOM CARD CN5 DC FAN MOTOR C0N2 C0N3 R W ION GENERATOR Y/G CN11' DISPLAY BOARD SW2 1 2 3 4 ON POWER SUPPLY BR BL Y/G CN1 (CN5'') Model selection: 09K model-23 code - SW2 - 3 off 4 off 12K model-26 code - SW2 - 3 off 4 on 18K model-33 code - SW2 - 3 on 4 off 24K model-35 code - SW2 - 3 on 4 on Except for this model: AS18ND1HRA/AW18LC2VHB-23 code - SW2 - 3 off 4 off Notes:Before replacing the board,It is necessary to ensure that the machine is matched with the board code. 15K model-33 code - SW2 - 3 on 4 off

Indoor Board Schematic

REFERENCE INFORMATION PAGE 60 Indoor Board Schematic 11.Circuit Diagrams 11.1.INDOOR UNIT A0 1 A1 2 A2 3 VSS 4 SDA 5 SCL 6 TEST 7 VCC 8 IC1 AT24C02B R33 560Ω +5V C11 0.1uF R29 10K R30 10K SCL SDA EEPROM R3 2K C1 0.1uF R11 2K R23 10K R10 10K +5V reset circuit XT1 FCR8.0MC5(��) C3 10nF C7 10nF R25 1K R24 1K R28 4.7K±1% R27 4.7K±1% 1 2 3 4 CN1 +5V E5 4.7uF-50V E3 4.7uF-50V ROOM PIPE ROOM PIPE R18 100Ω/560Ω R17 100Ω/560Ω R21 100Ω/560Ω R31 1K +5V IR SRCK RCK SER COM3 COM2 R6 100Ω R16 100Ω/560Ω GND +5V 1 2 3 4 5 6 7 8 CN32 E7 100uF-16V-105� 1 2 3 4 5 6 7 CN32'' GND IR TIM POW O3 +5V RUN A1 1 A2 2 A3 3 A4 4 A5 5 A6 6 A7 7 GND 8 +12 9 B7 10 B6 11 B5 12 B4 13 B3 14 B2 15 B1 16 IC8 ULN2003A R72 1K R79 1K R80 1K R76 1K C15 0.1uF +12V R70 1K 1 2 3 4 5 CN11 +12V 1 2 3 4 5 CN11' A B C D BUZZ1 PKM13EPY-4002 R50 2K R82 220Ω +12V +5V R4 Comment: 1K R1 Comment: 10K C5 Comment: 0.1uF urgent switch 1 1 2 2 SW1 JTP1288LA 1 2 JP1 TJC8-02 R5 1K R2 10K C16 0.1uF +5V C6 0.1uF E2 100uF-16V-105� SER SRCK GG RCK 5V GND IR DIGH DIGL Display 0011800184/0033 1 2 CN48 B2B-XH-A-R-Red C19 1nF R53 100Ω 12V A B C D 12V 1 1 2 2 SW1' TSVC-1 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 CN32' MODE FLZ RST IR SWITCH BUZZ NET_TX NET_RX PG_BACK PG_OUT CHECK/S_TIME USTEP_A USTEP_B USTEP_C ROOM USTEP_D PIPE A/B RCK SER SRCK REMOTE_RX REMOTE_TX R88 10K 1 2 3 4 CN34 5267-04A R98 100Ω R97 100Ω R89 10K +5V C24 10nF RX TX GND +5V NET_TX net com DIGH DIGL SER SRCK RCK USTEP_A USTEP_B USTEP_C USTEP_D BUZZ FLZ R81 1K 3 4 2 1 K2 892N-1AC-C Red White FLZ 1 CON8 1 CON6 +12V R9 1M CHECK/S_TIME IR R56 4.7K 1 2 CN36 R35 10K +12V C13 10nF R73 10K R38 10K R34 1K R83 10K R43 27Ω R66 10K +5V REMOTE_TX REMOTE_RX remote com 220V_L POWER_N R52 10K R51 10K R55 10K R60 10K +5V R54 10K R49 10K R42 10K SWITCH RST R63 10K R77 10K R65 10K R75 10K R78 10K COMM_TX COMM_RX SETP_MOTOR C18 0.1uF 25/35 +5V R85 10K +5V R86 10K P3_3/SSI 1 P3_4/SDA/SCS 2 MODE 3 P4_3/XCIN 4 P4_4/XCOUT 5 RESET 6 P4-7/XOUT 7 VSS/AVSS 8 P4_6/XIN 9 VCC/AVCC 10 P5_4/TRCIOD 11 P5_3/TRCIOC 12 P5_2/TRCIOB 13 P5_1/TRCIOA/TRCTRG 14 P5_0/TRCCLK 15 P2_7/TRDIOD1 16 P2_6/TRDIOC1 17 P2_5/TRDIOB1 18 P2_4/TRDIOA1 19 P2_3/TRDIOD0 20 P2_2/TRDIOC0 21 P2_1/TRDIOB0 22 P2_0/TRDIOA0/TRDCLK 23 P1_7/TRAIO/INT1 24 P1_6/CLK0 25 P1-5/RXD0(TRAIO)/INT1 26 P1_4/TXD0 27 P8_6 28 P8_5/TRFO12 29 P8_4/TRFO11 30 P8_3/TRFO10/TRF1 31 P8_2/TRFO02 32 P8_2/TRFO01 33 P8_1/TRFO00 34 P6_0/TREO 35 P4_5/INT0 36 P6_6/INT2/TXD1 37 P6_7/INT3/RXD1 38 P6_5/(CLK1)/CLK2 39 P6_4/RXD2 40 P6_3/TXD2 41 P3_1/TRBO 42 P3_0/TRAO 43 P3_6/INT1 44 P3_2/INT2 45 P1_3/KI3/AN11 46 P1_2/KI2/AN10 47 P1_1/KI1/AN9 48 P1_0/KI0/AN8 49 P0_0/AN7 50 P0_1/AN6 51 P0_2/AN5 52 P0_3/AN4 53 P0_4/AN3 54 P6_2 55 P6_1 56 P0_5/AN2/CLK1 57 P0_6/AN1/DA0 58 VSS/AVSS 59 P0_7/AN0/DA1 60 VREF 61 VCC/AVCC 62 P3_7/SSO 63 P3_5/SCL/SSCK 64 IC2 R5F212A7SNFA MODE write online +5V RST MODE +5V DIGH DIGL R32 10K SCL SDA DIG_MODE DIG_MODE 1 2 JP3 TJC8-02 1 2 JP2 TJC8-02 +5V motor PG ��� ����� +15V ��� �� ��� ���� ��� 390Ω VS R64 ��� R59 ��� ��� 10K TLP421 IC3 TLP421 1 2 4 3 IC7 TLP421 +15V ��� 47uF-50V-105� ��� 10K motor out ��� ��� ��� ��� +5V 1 2 3 4 5 6 7 CN26 ��� 4.7uF-50V-105� PG_OUT PG_BACK CON15 200±10mm -Red CON14 200±10mm -black Note�R54,R63,R85,R86 is used for display selection� CON16 200±10mm -black R93 10K R62 10K +5V Note3�R53,R6,R16,R18,R17,R21 note2�SW1,SW1',CN48 select one select accoding to diaplay For change ��� ��� R74 10K R87 4.7K 3 4 2 1 K3 892N-1AC-C +12V HXF HXF 1 CON9 Air fresh blue NET_RX R71 10K �� FK R41 10K R44 10K R45 10K R67 10K R46 10K R47 10K R48 10K R99 2K R100 2K R95 10K R101 10K R92 2K C12 0.1uF C27 0.1uF +5V FK Room Card 1 2 CN20 B2B-XH-A-Green- N8 2SC2412K R40 10K TVS1 HTVSB7.0CA-100 P1 2SA1037AK N1 2SC2412K N2 2SC2412K N4 2SC2412K D4 RLS4148 D6 RLS4148 A/B +5V C20 0.1uF 25/35 C2 0.1uF 1 2 3 4 5 6 7 8 SW2 R96 10K R69 2K R7 2K R8 10K R102 10K R104 2K R37 10K C28 0.1uF R103 20K BM BM LED1 +5V D 4 3 2 1 D +12V ����� ���������������������������������� +5V ���� �������������������� ���� ��������� ���� ��� ���� �������� ���� ������������ ���� ������ ���� ������������� +15V 1 6 2 3 7 T001 ����� ���� ���������� D001 1N5399 D002 1N5399 ���� 0 1 F 275VAC ������ SCK084R72 CON001 CON003 200±10mm -Black CON005 CN001 ���� ������������� ZD003 1N4746A(18V-1W) ���� ���������� RED 310V VCC

Indoor Board Schematic

REFERENCE INFORMATION PAGE 61 ENGLISH Indoor Board Schematic Domestic Air Conditioner 91 ULN2003A C15 0.1uF +12V BUZZ1 PKM13EPY-4002 R50 2K R82 220Ω R88 10K 1 2 3 4 CN34 5267-04A R98 100Ω R97 100Ω R89 10K +5V C24 10nF RX TX GND +5V NET_TX net com 3 4 2 1 K2 892N-1AC-C Red White FLZ 1 CON8 1 CON6 +12V R56 4.7K R83 10K R43 27Ω R66 10K 220V_L POWER_N R74 10K R87 4.7K 3 4 2 1 K3 892N-1AC-C +12V HXF 1 CON9 Air fresh blue NET_RX 2SC2412K N2 2SC2412K N4 2SC2412K D4 RLS4148 D6 RLS4148 1 2 4 3 A B C D 4 3 2 1 D C B A C8 0.1uF-50V A 1 K 2 C 4 E 3 IC4 TLP851/PC851 A 1 K 2 C 4 E 3 IC6 TLP421 R22 2K-1/4W R26 2K-2W R12 100K-1/4W E4 100uF-50V-105� CY3 2.2nF-250VAC 220V_L POWER_N R14 47K-2W R15 47K-2W COMM NEW FREEMATCH COM CIRCUIT 1 2 CN30 RTB-1.5-2P 220V_L FUSE1 T3.15A-250VAC 1 CON1 1 1 2 4 3 2 4 3 LX1 LB2271(32mH-0.35A) Black L ~220VAC CY1 2.2nF-250VAC CY2 2.2nF-250VAC 1 CON13 1 CON2 RV1 TVR14561* CX1 0.1uF-275VAC 1 ���� ��N 1 2 3 4 CN002 80±5mm -Red/Black-4P +5V GND +12V GND +5V C17 0.1uF E1 220uF-25V-105� +12V C4 0.1uF E6 220uF-25V-105� White Switch power supply A 1 K 2 C 4 E 3 ����� ������ +12V Vin 1 GND 2 Vout 3 ����� ���������������������������������� +5V ���� ������������������ ���� ��������������� ���� ������������� ���� �������������������� ���� �������������������� ���� ������� ���� �������� ���� ��������� ���� ��������� ���� ��������������� ���� ������� ���� �������� ���� �������� ���� ������������ ���� ������ ���� �������������������� ���� �������� ���� �������������� ���� ������������� +15V ���� ������������������� 1 6 2 3 5 4 7 T001 BCK-6-FE1901H ����� ���� ����� ���� ���������� ���� ����� D003 1N5399 D004 1N5399 D001 1N5399 D002 1N5399 ���� 0.1uF-275VAC ������ SCK084R72 ZD001 18V -1W ZD002 1N4742A(12V-1W) ���� ��������� ����� CON002 CON001 CON003 200±10mm -Black CON004 200±10mm -Red CON005 1 2 3 4 CN001 80±5mm -Red/Black-4P ���� ������������� ZD003 1N4746A(18V-1W) ���� ���������� 220VAC~/50HZ ���� 0.1uF-275VAC +5V +12V GND GND This Switch power supply is designed for 12W RED BLACK 310V 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 IC003 ICE2A265 VCC R13 330Ω R20 1K R19 10K C9 1nF +5V COMM_RX COMM_TX COMM_TX COMM_RX ��� ���� ��� ���� N5 SS8050LT1H D11 1N4007 ZD1 1N4746A(18V-1W) D12 1N4007

Module Board Schematic

REFERENCE INFORMATION PAGE 62 N 11.2.2 module board Circuit Diagram C009 471 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 IC1 SH7046 IC8 SGH40N60UF 1 2 3 4 BG1 D25BX60B D207 FFA30U60DN C404 474/630VDC C405 104/275V L 5.2MH/15A AC-L AC-N LO LI CN8 CN9 N6 C N7 C RS1 0.015/5W R215 10K RS2 0.02/5W R003 4.7K R001 4.7K R002 4.7K R004 4.7K R006 100 P N CN1 CN5 680U/400V*2 24 20 P N U V W CN2 CN3 CN4 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 VUFB VP UN VVFB VWFB WP UP VP1 VN1 WN VNC VN FO CIN VNC VNO PS21964-AT/AST/PS219A4-ASTX PM1 23 22 21 U V W C008 474 C007 474 C013 104 C005 104 C030 471 C029 471 C201 104 X1 10M R220 82 R219 1K R218 82 R217 1K R009 4.7K R005 4.7K R010 4.7K R007 4.7K 1 2 3 4 5 6 7 CN12 GND 5V MD1 RXD TXD FWP RES IC2 T600D C202 104 C203 104 C207 104 C208 104 IC5 HA17393AF IC6 HA1630D06 IC6 HA1630D06 R221 140 R216 10 R224 4.7K R211 1K R212 9.1K R209 1K R223 330 R210 6.8K R214 100 R207 1K 5V TR1 MMBT9013 5V 15V IC7 TLP251 2 3 5 6 8 4 8 5 6 7 R015 330 R208 6.8K R014 330 R013 330 R018 4.7K R016 1K R012 4.7K R011 4.7K R008 4.7K R019 4.7K R213 100 1 2 3 4 5 6 7 8 IC4 HA1630D06 IC4 HA1630D06 R206 1K R205 1K R203 1K R204 6.2K R201 1K R202 6.2K 1 2 3 4 5 6 7 8 5V 5V 1 2 3 CN11 �� TR2 MMBT9012 PC1 PC817A PC2 PC817A TR3 MMBT9013 C018 103 C016 472 C017 223 C014 102 C036 104 C032 104 C023 224 C015 102 C034 104 C001 104 5V C413 100U/25V D203 US1M D202 US1M D201 US1M C412 22U/25V C411 22U/25V C410 22U/25V 15V 5V 1 2 3 4 5 6 7 8 5V C004 104 C028 103 C020 102 5V IC3 24C04 C205 223 C003 104 C002 104 C006 474 5V R231 4.7K C022 103 R226130K R227130K R228130K R229 4.22K D205 LL4148 D204 LL4148 5V 1 2 3 CN10 ��(�) 15V 5V C501 100U/16V C011 104 C502 100U/25V C012 104 D206 24V/1W 15V R017 4.7K D208 LL4148 C503 4.7U/16V 5V R230 10 5V C406 104/275V C504 100U/25V IC5 HA17393AF R222 330 R225 4.22K C204 104 C019 103 1 2 3 5V R222,R225�������������� 93 Module Board Schematic

Room and Pipe Sensor Tables

Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) -22 -30 165.217 147.9497 132.3678 -1.94 1.75 -20.2 -29 155.5754 139.56 125.0806 -1.93 1.74 -18.4 -28 146.5609 131.7022 118.2434 -1.91 1.73 -16.6 -27 138.1285 124.3392 111.8256 -1.89 1.71 -14.8 -26 130.2371 117.4366 105.7989 -1.87 1.7 -13 -25 122.8484 110.9627 100.1367 -1.85 1.69 -11.2 -24 115.9272 104.8882 94.8149 -1.83 1.67 -9.4 -23 109.441 99.1858 89.8106 -1.81 1.66 -7.6 -22 103.3598 93.8305 85.1031 -1.8 1.64 -5.8 -21 97.6556 88.7989 80.6728 -1.78 1.63 -4 -20 92.3028 84.0695 76.5017 -1.76 1.62 -2.2 -19 87.2775 79.6222 72.5729 -1.74 1.6 -0.4 -18 82.5577 75.4384 68.871 -1.72 1.59 1.4 -17 78.123 71.501 65.3815 -1.7 1.57 3.2 -16 73.9543 67.7939 62.0907 -1.68 1.55 5 -15 70.0342 64.3023 58.9863 -1.66 1.54 6.8 -14 66.3463 61.0123 56.0565 -1.64 1.52 8.6 -13 62.8755 57.911 53.2905 -1.62 1.51 10.4 -12 59.6076 54.9866 50.6781 -1.6 1.49 12.2 -11 56.5296 52.2278 48.2099 -1.58 1.47 14 -10 53.6294 49.6244 45.8771 -1.56 1.46 15.8 -9 50.8956 47.1666 43.6714 -1.54 1.44 17.6 -8 48.3178 44.8454 41.5851 -1.51 1.42 19.4 -7 45.886 42.6525 39.6112 -1.49 1.4 21.2 -6 43.5912 40.58 37.7429 -1.47 1.39 23 -5 41.4249 38.6207 35.9739 -1.45 1.37 24.8 -4 39.3792 36.7676 34.2983 -1.43 1.35 26.6 -3 37.4465 35.0144 32.7108 -1.41 1.33 28.4 -2 35.6202 33.3552 31.2062 -1.38 1.31 30.2 -1 33.8936 31.7844 29.7796 -1.36 1.29 32 0 32.2608 30.2968 28.4267 -1.34 1.28 33.8 1 30.7162 28.8875 27.1431 -1.32 1.26 35.6 2 29.2545 27.5519 25.925 -1.29 1.24 37.4 3 27.8708 26.2858 24.7686 -1.27 1.22 39.2 4 26.5605 25.0851 23.6704 -1.25 1.2 41 5 25.3193 23.9462 22.6273 -1.23 1.18 42.8 6 24.1432 22.8656 21.6361 -1.2 1.16 44.6 7 23.0284 21.8398 20.6939 -1.18 1.14 46.4 8 21.9714 20.8659 19.7982 -1.15 1.12 48.2 9 20.9688 19.9409 18.9463 -1.13 1.09 50 10 20.0176 19.0621 18.1358 -1.11 1.07 51.8 11 19.1149 18.227 17.3646 -1.08 1.05 53.6 12 18.258 17.4331 16.6305 -1.06 1.03 55.4 13 17.4442 16.6782 15.9315 -1.03 1.01 57.2 14 16.6711 15.9601 15.2657 -1.01 0.99 59 15 15.9366 15.277 14.6315 -0.98 0.96 60.8 16 15.2385 14.6268 14.0271 -0.96 0.94 R77° = 10KΩ±3% B77°/122° = 3700K±3%

Room and Pipe Sensor Tables

Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 62.6 17 14.5748 14.0079 13.451 -0.93 0.92 64.4 18 13.9436 13.4185 12.9017 -0.91 0.9 66.2 19 13.3431 12.8572 12.3778 -0.88 0.87 68 20 12.7718 12.3223 11.878 -0.86 0.85 69.8 21 12.228 11.8126 11.4011 -0.83 0.83 71.6 22 11.7102 11.3267 10.9459 -0.81 0.8 73.4 23 11.2172 10.8634 10.5114 -0.78 0.78 75.2 24 10.7475 10.4216 10.0964 -0.75 0.75 77 25 10.3 10 9.7 -0.75 0.75 78.8 26 9.8975 9.5974 9.298 -0.76 0.76 80.6 27 9.5129 9.2132 8.9148 -0.8 0.8 82.4 28 9.1454 8.8465 8.5496 -0.84 0.83 84.2 29 8.7942 8.4964 8.2013 -0.87 0.86 86 30 8.4583 8.1621 7.8691 -0.91 0.9 87.8 31 8.1371 7.8428 7.5522 -0.95 0.93 89.6 32 7.8299 7.5377 7.2498 -0.98 0.97 91.4 33 7.5359 7.2461 6.9611 -1.02 1 93.2 34 7.2546 6.9673 6.6854 -1.06 1.04 95 35 6.9852 6.7008 6.4222 -1.1 1.07 96.8 36 6.7273 6.4459 6.1707 -1.13 1.11 98.6 37 6.4803 6.2021 5.9304 -1.17 1.14 100.4 38 6.2437 5.9687 5.7007 -1.21 1.18 102.2 39 6.017 5.7454 5.4812 -1.25 1.22 104 40 5.7997 5.5316 5.2712 -1.29 1.25 105.8 41 5.5914 5.3269 5.0704 -1.33 1.29 107.6 42 5.3916 5.1308 4.8783 -1.37 1.33 109.4 43 5.2001 4.943 4.6944 -1.41 1.36 111.2 44 5.0163 4.763 4.5185 -1.45 1.4 113 45 4.84 4.5905 4.35 -1.49 1.44 114.8 46 4.6708 4.4252 4.1887 -1.53 1.47 116.6 47 4.5083 4.2666 4.0342 -1.57 1.51 118.4 48 4.3524 4.1145 3.8862 -1.61 1.55 120.2 49 4.2026 3.9686 3.7443 -1.65 1.59 122 50 4.0588 3.8287 3.6084 -1.7 1.62 123.8 51 3.9206 3.6943 3.478 -1.74 1.66 125.6 52 3.7878 3.5654 3.3531 -1.78 1.7 127.4 53 3.6601 3.4416 3.2332 -1.82 1.74 129.2 54 3.5374 3.3227 3.1183 -1.87 1.78 131 55 3.4195 3.2085 3.0079 -1.91 1.82 132.8 56 3.306 3.0989 2.9021 -1.95 1.85 134.6 57 3.1969 2.9935 2.8005 -2 1.89 136.4 58 3.0919 2.8922 2.7029 -2.04 1.93 138.2 59 2.9909 2.7948 2.6092 -2.08 1.97 140 60 2.8936 2.7012 2.5193 -2.13 2.01 141.8 61 2.8 2.6112 2.4328 -2.17 2.05 143.6 62 2.7099 2.5246 2.3498 -2.22 2.09 145.4 63 2.6232 2.4413 2.27 -2.26 2.13 147.2 64 2.5396 2.3611 2.1932 -2.31 2.17

Room and Pipe Sensor Tables

Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 149 65 2.4591 2.284 2.1195 -2.36 2.21 150.8 66 2.3815 2.2098 2.0486 -2.4 2.25 152.6 67 2.3068 2.1383 1.9803 -2.45 2.29 154.4 68 2.2347 2.0695 1.9147 -2.49 2.34 156.2 69 2.1652 2.0032 1.8516 -2.54 2.38 158 70 2.0983 1.9393 1.7908 -2.59 2.42 159.8 71 2.0337 1.8778 1.7324 -2.63 2.46 161.6 72 1.9714 1.8186 1.6761 -2.68 2.5 163.4 73 1.9113 1.7614 1.6219 -2.73 2.54 165.2 74 1.8533 1.7064 1.5697 -2.78 2.58 167 75 1.7974 1.6533 1.5194 -2.83 2.63 168.8 76 1.7434 1.6021 1.471 -2.88 2.67 170.6 77 1.6913 1.5528 1.4243 -2.92 2.71 172.4 78 1.6409 1.5051 1.3794 -2.97 2.75 174.2 79 1.5923 1.4592 1.336 -3.02 2.8 176 80 1.5454 1.4149 1.2942 -3.07 2.84 177.8 81 1.5 1.3721 1.254 -3.12 2.88 179.6 82 1.4562 1.3308 1.2151 -3.17 2.93 181.4 83 1.4139 1.291 1.1776 -3.22 2.97 183.2 84 1.373 1.2525 1.1415 -3.27 3.01 185 85 1.3335 1.2153 1.1066 -3.32 3.06 186.8 86 1.2953 1.1794 1.073 -3.38 3.1 188.6 87 1.2583 1.1448 1.0405 -3.43 3.15 190.4 88 1.2226 1.1113 1.0092 -3.48 3.19 192.2 89 1.188 1.0789 0.9789 -3.53 3.24 194 90 1.1546 1.0476 0.9497 -3.58 3.28 195.8 91 1.1223 1.0174 0.9215 -3.64 3.33 197.6 92 1.091 0.9882 0.8942 -3.69 3.37 199.4 93 1.0607 0.9599 0.8679 -3.74 3.42 201.2 94 1.0314 0.9326 0.8424 -3.8 3.46 203 95 1.003 0.9061 0.8179 -3.85 3.51 204.8 96 0.9756 0.8806 0.7941 -3.9 3.55 206.6 97 0.949 0.8558 0.7711 -3.96 3.6 208.4 98 0.9232 0.8319 0.7489 -4.01 3.64 210.2 99 0.8983 0.8088 0.7275 -4.07 3.69 212 100 0.8741 0.7863 0.7067 -4.12 3.74 213.8 101 0.8507 0.7646 0.6867 -4.18 3.78 215.6 102 0.8281 0.7436 0.6672 -4.23 3.83 217.4 103 0.8061 0.7233 0.6484 -4.29 3.88 219.2 104 0.7848 0.7036 0.6303 -4.34 3.92 221 105 0.7641 0.6845 0.6127 -4.4 3.97 222.8 106 0.7441 0.6661 0.5957 -4.46 4.02 224.6 107 0.7247 0.6482 0.5792 -4.51 4.07 226.4 108 0.7059 0.6308 0.5632 -4.57 4.12 228.2 109 0.6877 0.614 0.5478 -4.63 4.16 230 110 0.67 0.5977 0.5328 -4.69 4.21 231.8 111 0.6528 0.582 0.5183 -4.74 4.26 233.6 112 0.6361 0.5667 0.5043 -4.8 4.31

Room and Pipe Sensor Tables

Ambient, Defrost & Pipe Sensor Tables Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 235.4 113 0.62 0.5518 0.4907 -4.86 4.36 237.2 114 0.6043 0.5374 0.4775 -4.92 4.41 239 115 0.5891 0.5235 0.4648 -4.98 4.45 240.8 116 0.5743 0.51 0.4524 -5.04 4.5 242.6 117 0.56 0.4968 0.4404 -5.1 4.55 244.4 118 0.546 0.4841 0.4288 -5.16 4.6 246.2 119 0.5325 0.4717 0.4175 -5.22 4.65 248 120 0.5194 0.4597 0.4066 -5.28 4.7 Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) -22 -30 165.2170 147.9497 132.3678 -1.94 1.75 -20 -29 155.5754 139.5600 125.0806 -1.93 1.74 -18 -28 146.5609 131.7022 118.2434 -1.91 1.73 -17 -27 138.1285 124.3392 111.8256 -1.89 1.71 -15 -26 130.2371 117.4366 105.7989 -1.87 1.70 -13 -25 122.8484 110.9627 100.1367 -1.85 1.69 -11 -24 115.9272 104.8882 94.8149 -1.83 1.67 -9 -23 109.4410 99.1858 89.8106 -1.81 1.66 -8 -22 103.3598 93.8305 85.1031 -1.80 1.64 -6 -21 97.6556 88.7989 80.6728 -1.78 1.63 -4 -20 92.3028 84.0695 76.5017 -1.76 1.62 -2 -19 87.2775 79.6222 72.5729 -1.74 1.60 0 -18 82.5577 75.4384 68.8710 -1.72 1.59 1 -17 78.1230 71.5010 65.3815 -1.70 1.57 3 -16 73.9543 67.7939 62.0907 -1.68 1.55 5 -15 70.0342 64.3023 58.9863 -1.66 1.54 7 -14 66.3463 61.0123 56.0565 -1.64 1.52 9 -13 62.8755 57.9110 53.2905 -1.62 1.51 10 -12 59.6076 54.9866 50.6781 -1.60 1.49 12 -11 56.5296 52.2278 48.2099 -1.58 1.47 14 -10 53.6294 49.6244 45.8771 -1.56 1.46 16 -9 50.8956 47.1666 43.6714 -1.54 1.44 18 -8 48.3178 44.8454 41.5851 -1.51 1.42 19 -7 45.8860 42.6525 39.6112 -1.49 1.40 21 -6 43.5912 40.5800 37.7429 -1.47 1.39 23 -5 41.4249 38.6207 35.9739 -1.45 1.37 25 -4 39.3792 36.7676 34.2983 -1.43 1.35 27 -3 37.4465 35.0144 32.7108 -1.41 1.33 28 -2 35.6202 33.3552 31.2062 -1.38 1.31 30 -1 33.8936 31.7844 29.7796 -1.36 1.29 32 0 32.2608 30.2968 28.4267 -1.34 1.28 34 1 30.7162 28.8875 27.1431 -1.32 1.26 36 2 29.2545 27.5519 25.9250 -1.29 1.24 37 3 27.8708 26.2858 24.7686 -1.27 1.22 39 4 26.5605 25.0851 23.6704 -1.25 1.20 41 5 25.3193 23.9462 22.6273 -1.23 1.18 43 6 24.1432 22.8656 21.6361 -1.20 1.16

Ambient, Defrost & Pipe Sensor Tables

Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 45 7 23.0284 21.8398 20.6939 -1.18 1.14 46 8 21.9714 20.8659 19.7982 -1.15 1.12 48 9 20.9688 19.9409 18.9463 -1.13 1.09 50 10 20.0176 19.0621 18.1358 -1.11 1.07 52 11 19.1149 18.2270 17.3646 -1.08 1.05 54 12 18.2580 17.4331 16.6305 -1.06 1.03 55 13 17.4442 16.6782 15.9315 -1.03 1.01 57 14 16.6711 15.9601 15.2657 -1.01 0.99 59 15 15.9366 15.2770 14.6315 -0.98 0.96 61 16 15.2385 14.6268 14.0271 -0.96 0.94 63 17 14.5748 14.0079 13.4510 -0.93 0.92 64 18 13.9436 13.4185 12.9017 -0.91 0.90 66 19 13.3431 12.8572 12.3778 -0.88 0.87 68 20 12.7718 12.3223 11.8780 -0.86 0.85 70 21 12.2280 11.8126 11.4011 -0.83 0.83 72 22 11.7102 11.3267 10.9459 -0.81 0.80 73 23 11.2172 10.8634 10.5114 -0.78 0.78 75 24 10.7475 10.4216 10.0964 -0.75 0.75 77 25 10.3000 10.0000 9.7000 -0.75 0.75 79 26 9.8975 9.5974 9.2980 -0.76 0.76 81 27 9.5129 9.2132 8.9148 -0.80 0.80 82 28 9.1454 8.8465 8.5496 -0.84 0.83 84 29 8.7942 8.4964 8.2013 -0.87 0.86 86 30 8.4583 8.1621 7.8691 -0.91 0.90 88 31 8.1371 7.8428 7.5522 -0.95 0.93 90 32 7.8299 7.5377 7.2498 -0.98 0.97 91 33 7.5359 7.2461 6.9611 -1.02 1.00 93 34 7.2546 6.9673 6.6854 -1.06 1.04 95 35 6.9852 6.7008 6.4222 -1.10 1.07 97 36 6.7273 6.4459 6.1707 -1.13 1.11 99 37 6.4803 6.2021 5.9304 -1.17 1.14 100 38 6.2437 5.9687 5.7007 -1.21 1.18 102 39 6.0170 5.7454 5.4812 -1.25 1.22 104 40 5.7997 5.5316 5.2712 -1.29 1.25 106 41 5.5914 5.3269 5.0704 -1.33 1.29 108 42 5.3916 5.1308 4.8783 -1.37 1.33 109 43 5.2001 4.9430 4.6944 -1.41 1.36 111 44 5.0163 4.7630 4.5185 -1.45 1.40 113 45 4.8400 4.5905 4.3500 -1.49 1.44 115 46 4.6708 4.4252 4.1887 -1.53 1.47 117 47 4.5083 4.2666 4.0342 -1.57 1.51 118 48 4.3524 4.1145 3.8862 -1.61 1.55 120 49 4.2026 3.9686 3.7443 -1.65 1.59 122 50 4.0588 3.8287 3.6084 -1.70 1.62 124 51 3.9206 3.6943 3.4780 -1.74 1.66 126 52 3.7878 3.5654 3.3531 -1.78 1.70 127 53 3.6601 3.4416 3.2332 -1.82 1.74 129 54 3.5374 3.3227 3.1183 -1.87 1.78

Ambient, Defrost & Pipe Sensor Tables

Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 131 55 3.4195 3.2085 3.0079 -1.91 1.82 133 56 3.3060 3.0989 2.9021 -1.95 1.85 135 57 3.1969 2.9935 2.8005 -2.00 1.89 136 58 3.0919 2.8922 2.7029 -2.04 1.93 138 59 2.9909 2.7948 2.6092 -2.08 1.97 140 60 2.8936 2.7012 2.5193 -2.13 2.01 142 61 2.8000 2.6112 2.4328 -2.17 2.05 144 62 2.7099 2.5246 2.3498 -2.22 2.09 145 63 2.6232 2.4413 2.2700 -2.26 2.13 147 64 2.5396 2.3611 2.1932 -2.31 2.17 149 65 2.4591 2.2840 2.1195 -2.36 2.21 151 66 2.3815 2.2098 2.0486 -2.40 2.25 153 67 2.3068 2.1383 1.9803 -2.45 2.29 154 68 2.2347 2.0695 1.9147 -2.49 2.34 156 69 2.1652 2.0032 1.8516 -2.54 2.38 158 70 2.0983 1.9393 1.7908 -2.59 2.42 160 71 2.0337 1.8778 1.7324 -2.63 2.46 162 72 1.9714 1.8186 1.6761 -2.68 2.50 163 73 1.9113 1.7614 1.6219 -2.73 2.54 165 74 1.8533 1.7064 1.5697 -2.78 2.58 167 75 1.7974 1.6533 1.5194 -2.83 2.63 169 76 1.7434 1.6021 1.4710 -2.88 2.67 171 77 1.6913 1.5528 1.4243 -2.92 2.71 172 78 1.6409 1.5051 1.3794 -2.97 2.75 174 79 1.5923 1.4592 1.3360 -3.02 2.80 176 80 1.5454 1.4149 1.2942 -3.07 2.84 178 81 1.5000 1.3721 1.2540 -3.12 2.88 180 82 1.4562 1.3308 1.2151 -3.17 2.93 181 83 1.4139 1.2910 1.1776 -3.22 2.97 183 84 1.3730 1.2525 1.1415 -3.27 3.01 185 85 1.3335 1.2153 1.1066 -3.32 3.06 187 86 1.2953 1.1794 1.0730 -3.38 3.10 189 87 1.2583 1.1448 1.0405 -3.43 3.15 190 88 1.2226 1.1113 1.0092 -3.48 3.19 192 89 1.1880 1.0789 0.9789 -3.53 3.24 194 90 1.1546 1.0476 0.9497 -3.58 3.28 196 91 1.1223 1.0174 0.9215 -3.64 3.33 198 92 1.0910 0.9882 0.8942 -3.69 3.37 199 93 1.0607 0.9599 0.8679 -3.74 3.42 201 94 1.0314 0.9326 0.8424 -3.80 3.46 203 95 1.0030 0.9061 0.8179 -3.85 3.51 205 96 0.9756 0.8806 0.7941 -3.90 3.55 207 97 0.9490 0.8558 0.7711 -3.96 3.60 208 98 0.9232 0.8319 0.7489 -4.01 3.64 210 99 0.8983 0.8088 0.7275 -4.07 3.69 212 100 0.8741 0.7863 0.7067 -4.12 3.74 214 101 0.8507 0.7646 0.6867 -4.18 3.78 216 102 0.8281 0.7436 0.6672 -4.23 3.83

Discharge Sensor Tables

Ambient, Defrost & Pipe Sensor Tables Temp. °F Temp. °C Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance (°C) 217 103 0.8061 0.7233 0.6484 -4.29 3.88 219 104 0.7848 0.7036 0.6303 -4.34 3.92 221 105 0.7641 0.6845 0.6127 -4.40 3.97 223 106 0.7441 0.6661 0.5957 -4.46 4.02 225 107 0.7247 0.6482 0.5792 -4.51 4.07 226 108 0.7059 0.6308 0.5632 -4.57 4.12 228 109 0.6877 0.6140 0.5478 -4.63 4.16 230 110 0.6700 0.5977 0.5328 -4.69 4.21 232 111 0.6528 0.5820 0.5183 -4.74 4.26 234 112 0.6361 0.5667 0.5043 -4.80 4.31 235 113 0.6200 0.5518 0.4907 -4.86 4.36 237 114 0.6043 0.5374 0.4775 -4.92 4.41 239 115 0.5891 0.5235 0.4648 -4.98 4.45 241 116 0.5743 0.5100 0.4524 -5.04 4.50 243 117 0.5600 0.4968 0.4404 -5.10 4.55 244 118 0.5460 0.4841 0.4288 -5.16 4.60 246 119 0.5325 0.4717 0.4175 -5.22 4.65 248 120 0.5194 0.4597 0.4066 -5.28 4.70 Temp.(°F) Temp.(°C) Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance -22 -30 14646.0505 12061.7438 9924.4999 -2.96 2.45 -20.2 -29 13654.1707 11267.873 9290.2526 -2.95 2.44 -18.4 -28 12735.8378 10531.3695 8700.6388 -2.93 2.44 -16.6 -27 11885.1336 9847.724 8152.2338 -2.92 2.43 -14.8 -26 11096.6531 9212.8101 7641.8972 -2.91 2.42 -13 -25 10365.4565 8622.8491 7166.7474 -2.9 2.42 -11.2 -24 9687.027 8074.3787 6724.1389 -2.88 2.41 -9.4 -23 9057.2314 7564.2244 6311.6413 -2.87 2.41 -7.6 -22 8472.2852 7089.4741 5927.0206 -2.86 2.4 -5.8 -21 7928.7217 6647.4547 5568.2222 -2.84 2.39 -4 -20 7423.3626 6235.7109 5233.3554 -2.83 2.39 -2.2 -19 6953.293 5851.9864 4920.6791 -2.82 2.38 -0.4 -18 6515.8375 5494.2064 4628.5894 -2.8 2.37 1.4 -17 6108.5393 5160.4621 4355.6078 -2.79 2.37 3.2 -16 5729.1413 4848.9963 4100.3708 -2.77 2.36 5 -15 5375.5683 4558.1906 3861.6201 -2.76 2.35 6.8 -14 5045.9114 4286.5535 3638.1938 -2.75 2.34 8.6 -13 4738.4141 4032.7098 3429.0191 -2.73 2.34 10.4 -12 4451.4586 3795.391 3233.1039 -2.72 2.33 12.2 -11 4183.5548 3573.426 3049.5312 -2.7 2.32 14 -10 3933.3289 3365.7336 2877.4527 -2.69 2.31 15.8 -9 3699.5139 3171.3148 2716.0828 -2.67 2.3 17.6 -8 3480.9407 2989.246 2564.6945 -2.66 2.29 19.4 -7 3276.5302 2818.6731 2422.6139 -2.64 2.28 21.2 -6 3085.2854 2658.8058 2289.2164 -2.63 2.28 23 -5 2906.2851 2508.9126 2163.923 -2.61 2.27 R176° = 50KΩ±3% B77°/176° = 4450K±3%

Discharge Sensor Tables

Temp.(°F) Temp.(°C) Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance 24.8 -4 2738.6777 2368.3158 2046.1961 -2.6 2.26 26.6 -3 2581.6752 2236.3876 1935.5371 -2.58 2.25 28.4 -2 2434.5487 2112.5459 1831.4826 -2.56 2.24 30.2 -1 2296.623 1996.2509 1733.6024 -2.55 2.23 32 0 2167.273 1887.0018 1641.4966 -2.53 2.22 33.8 1 2045.9191 1784.3336 1554.7931 -2.52 2.21 35.6 2 1932.0242 1687.8144 1473.146 -2.5 2.2 37.4 3 1825.0899 1597.0431 1396.2333 -2.48 2.19 39.2 4 1724.654 1511.6468 1323.7551 -2.47 2.17 41 5 1630.287 1431.2787 1255.4324 -2.45 2.16 42.8 6 1541.5904 1355.6163 1191.0048 -2.43 2.15 44.6 7 1458.1938 1284.3593 1130.2298 -2.41 2.14 46.4 8 1379.7528 1217.2282 1072.8813 -2.4 2.13 48.2 9 1305.9472 1153.9626 1018.7481 -2.38 2.12 50 10 1236.4792 1094.32 967.6334 -2.36 2.11 51.8 11 1171.0715 1038.0743 919.3533 -2.35 2.09 53.6 12 1109.4661 985.0146 873.7359 -2.33 2.08 55.4 13 1051.4226 934.944 830.621 -2.31 2.07 57.2 14 996.7169 887.6792 789.8583 -2.29 2.06 59 15 945.1404 843.0486 751.3077 -2.27 2.04 60.8 16 896.4981 800.8922 714.838 -2.26 2.03 62.6 17 850.6086 761.0603 680.3265 -2.24 2.02 64.4 18 807.3024 723.4134 647.658 -2.22 2 66.2 19 766.4212 687.8205 616.7252 -2.2 1.99 68 20 727.8172 654.1596 587.4271 -2.18 1.98 69.8 21 691.3524 622.3161 559.6694 -2.16 1.96 71.6 22 656.8979 592.1831 533.3634 -2.14 1.95 73.4 23 624.3328 563.6604 508.4261 -2.12 1.93 75.2 24 593.5446 536.654 484.7796 -2.1 1.92 77 25 564.4275 511.076 462.351 -2.09 1.9 78.8 26 536.9865 486.9352 441.1516 -2.07 1.89 80.6 27 511.0105 464.05 421.0258 -2.05 1.87 82.4 28 486.4151 442.3499 401.9146 -2.03 1.86 84.2 29 463.1208 421.7683 383.7626 -2.01 1.84 86 30 441.0535 402.243 366.5175 -1.99 1.83 87.8 31 420.1431 383.7151 350.1301 -1.97 1.81 89.6 32 400.3242 366.1295 334.5542 -1.95 1.8 91.4 33 381.535 349.4341 319.746 -1.93 1.78 93.2 34 363.7176 333.5801 305.6645 -1.9 1.76 95 35 346.8176 318.5216 292.2709 -1.88 1.75 96.8 36 330.7839 304.2151 279.5286 -1.86 1.73 98.6 37 315.5682 290.6199 267.4031 -1.84 1.71 100.4 38 301.1254 277.6976 255.862 -1.82 1.7 102.2 39 287.4128 265.4119 244.8745 -1.8 1.68 104 40 274.3905 253.7288 234.4118 -1.78 1.66 105.8 41 262.0206 242.6161 224.4465 -1.76 1.64 107.6 42 250.2676 232.0436 214.9529 -1.74 1.63 109.4 43 239.0983 221.9825 205.9065 -1.71 1.61 111.2 44 228.4809 212.406 197.2844 -1.69 1.59

Discharge Sensor Tables

Temp.(°F) Temp.(°C) Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance 113 45 218.386 203.2887 189.0648 -1.67 1.57 114.8 46 208.7855 194.6066 181.2273 -1.65 1.55 116.6 47 199.6531 186.3369 173.7524 -1.63 1.54 118.4 48 190.9639 178.4584 166.6217 -1.6 1.52 120.2 49 182.6945 170.9508 159.8181 -1.58 1.5 122 50 174.8228 163.7951 153.3249 -1.56 1.48 123.8 51 167.328 156.9733 147.1268 -1.53 1.46 125.6 52 160.1904 150.4683 141.209 -1.51 1.44 127.4 53 153.3914 144.2641 135.5577 -1.49 1.42 129.2 54 146.9136 138.3454 130.1598 -1.47 1.4 131 55 140.7403 132.698 125.0027 -1.44 1.38 132.8 56 134.8559 127.3081 120.0746 -1.42 1.36 134.6 57 129.2457 122.163 115.3645 -1.4 1.34 136.4 58 123.8956 117.2504 110.8618 -1.37 1.32 138.2 59 118.7926 112.5589 106.5564 -1.35 1.3 140 60 113.9241 108.0776 102.4388 -1.32 1.28 141.8 61 109.2784 103.7961 98.5 -1.3 1.26 143.6 62 104.8443 99.7046 94.7315 -1.28 1.23 145.4 63 100.6112 95.7939 91.1253 -1.25 1.21 147.2 64 96.5692 92.0553 87.6735 -1.23 1.19 149 65 92.7088 88.4805 84.369 -1.2 1.17 150.8 66 89.0211 85.0614 81.2048 -1.18 1.15 152.6 67 85.4976 81.7908 78.1744 -1.15 1.12 154.4 68 82.1303 78.6615 75.2715 -1.13 1.1 156.2 69 78.9116 75.6668 72.4902 -1.1 1.08 158 70 75.8343 72.8004 69.8249 -1.08 1.06 159.8 71 72.8916 70.0561 67.2703 -1.05 1.03 161.6 72 70.077 67.4283 64.8213 -1.03 1.01 163.4 73 67.3844 64.9115 62.4731 -1 0.99 165.2 74 64.808 62.5006 60.2211 -0.98 0.96 167 75 62.3423 60.1906 58.0609 -0.95 0.94 168.8 76 59.9821 57.977 55.9885 -0.92 0.92 170.6 77 57.7223 55.8552 53.9998 -0.9 0.89 172.4 78 55.5583 53.821 52.0912 -0.87 0.87 174.2 79 53.4856 51.8706 50.2591 -0.85 0.84 176 80 51.5 50 48.5 -0.85 0.84 177.8 81 49.7063 48.2057 46.7083 -0.85 0.85 179.6 82 47.9835 46.4842 44.9911 -0.89 0.89 181.4 83 46.3286 44.8323 43.3452 -0.93 0.92 183.2 84 44.7385 43.2468 41.7672 -0.96 0.95 185 85 43.2105 41.7248 40.254 -1 0.99 186.8 86 41.7386 40.2604 38.7996 -1.03 1.02 188.6 87 40.3241 38.8545 37.4048 -1.07 1.06 190.4 88 38.9643 37.5045 36.0668 -1.11 1.09 192.2 89 37.6569 36.2078 34.7831 -1.14 1.13 194 90 36.3996 34.9622 33.5513 -1.18 1.16 195.8 91 35.1903 33.7653 32.3689 -1.22 1.19 197.6 92 34.0269 32.6151 31.2338 -1.26 1.23 199.4 93 32.9075 31.5096 30.1438 -1.3 1.27

Discharge Sensor Tables

Temp.(°F) Temp.(°C) Max.(KΩ) Normal(KΩ) Min.(KΩ) Tolerance 201.2 94 31.8302 30.4467 29.097 -1.33 1.3 203 95 30.7933 29.4246 28.0915 -1.37 1.34 204.8 96 29.795 28.4417 27.1254 -1.41 1.37 206.6 97 28.8337 27.4961 26.197 -1.45 1.41 208.4 98 27.9078 26.5864 25.3048 -1.49 1.44 210.2 99 27.016 25.711 24.447 -1.53 1.48 212 100 26.1569 24.8685 23.6222 -1.57 1.52 213.8 101 25.329 24.0574 22.8291 -1.61 1.55 215.6 102 24.5311 23.2765 22.0662 -1.65 1.59 217.4 103 23.762 22.5245 21.3323 -1.69 1.63 219.2 104 23.0205 21.8002 20.6261 -1.73 1.66 221 105 22.3055 21.1025 19.9465 -1.77 1.7 222.8 106 21.6159 20.4303 19.2924 -1.81 1.74 224.6 107 20.9508 19.7825 18.6626 -1.85 1.77 226.4 108 20.3091 19.1582 18.0563 -1.89 1.81 228.2 109 19.6899 18.5564 17.4723 -1.93 1.85 230 110 19.0924 17.9761 16.9098 -1.98 1.89 231.8 111 18.5157 17.4166 16.368 -2.02 1.93 233.6 112 17.959 16.8769 15.8458 -2.06 1.96 235.4 113 17.4214 16.3564 15.3427 -2.1 2 237.2 114 16.9023 15.8542 14.8577 -2.15 2.04 239 115 16.401 15.3696 14.3902 -2.19 2.08 240.8 116 15.9167 14.902 13.9394 -2.23 2.12 242.6 117 15.4489 14.4506 13.5047 -2.27 2.16 244.4 118 14.9968 14.0149 13.0855 -2.32 2.19 246.2 119 14.5599 13.5942 12.6811 -2.36 2.23 248 120 14.1376 13.1879 12.2909 -2.41 2.27 249.8 121 13.7294 12.7955 11.9144 -2.45 2.31 251.6 122 13.3347 12.4165 11.551 -2.5 2.35 253.4 123 12.9531 12.0503 11.2003 -2.54 2.39 255.2 124 12.584 11.6965 10.8617 -2.58 2.43 257 125 12.227 11.3545 10.5348 -2.63 2.47 258.8 126 11.8817 11.024 10.2191 -2.68 2.51 260.6 127 11.5475 10.7046 9.9142 -2.72 2.55 262.4 128 11.2242 10.3957 9.6197 -2.77 2.59 264.2 129 10.9112 10.097 9.3352 -2.81 2.63 266 130 10.6084 9.8082 9.0602 -2.86 2.67 267.8 131 10.3151 9.5288 8.7945 -2.91 2.71 269.6 132 10.0312 9.2586 8.5378 -2.95 2.75 271.4 133 9.7563 8.9971 8.2895 -3 2.8 273.2 134 9.4901 8.7441 8.0495 -3.05 2.84 275 135 9.2322 8.4993 7.8175 -3.09 2.88 276.8 136 8.9824 8.2623 7.5931 -3.14 2.92 278.6 137 8.7404 8.0329 7.376 -3.19 2.96 280.4 138 8.5059 7.8108 7.166 -3.24 3 282.2 139 8.2787 7.5958 6.9629 -3.29 3.04 284 140 8.0584 7.3875 6.7664 -3.33 3.09

DIP Switch Settings

[This�page�intentionally�left�blank.]

GE Appliances, A Haier Company

Appliance Park, Louisville, KY 40225 ©2019 GE Appliances, A Haier Company Issued Date: January 2019 Model#: AW09ES2VHB, 1U09AP2VHA AW12ES2VHB, 1U12AP2VHA AW15ES2VHB, 1U15AP2VHA AW18ES2VHB, 1U18AP2VHA AW24ES2VHB, 1U24AP2VHA

Acondicionador de Aire Split con

Bomba de Calor y sin Conducto Manual de Servicio El diseño podrá variar de acuerdo al número de modelo. • Por favor lea este manual antes de usar el acondicionador de aire con bomba de calor. • Guarde este manual del usuario para referencia futura. PAGE 1 Precauciones de Seguridad/ Introducción ...................................................................................3 Controles y Componentes de la Unidad de Exterior .....................................................................7 Controles y Componentes de la Unidad de Interior ....................................................................15 Secuencia de Uso ......................................................................................................................21 Códigos de Error y Solución de Problemas .................................................................................29 Información de Referencia .........................................................................................................43 Índice Interior AW09ES2VHB AW12ES2VHB AW15ES2VHB AW18ES2VHB AW24ES2VHB Exterior 1U09AP2VHA 1U12AP2VHA 1U15AP2VHA 1U18AP2VHA 1U24AP2VHA

Precauciones de Seguridad .................................................................................................................................................4

Advertencias y Precauciones ...........................................................................................................................................................4 Introducción al Sistema ......................................................................................................................................................5 � Especificaciones�a�seguir�para�un�funcionamiento�correcto .........................................................................................................5 Teoría Fundamental sobre Cómo Funciona el Sistema ..................................................................................................................5 Índice

• Lea estas Precauciones de Seguridad para asegurar la correcta instalación.

• En este manual, las precauciones se clasifican como ADVERTENCIA y PRECAUCIÓN. • Siga todas las precauciones que figuran a continuación. Todas son importantes para mantener la seguridad y evitar daños sobre la propiedad y el equipo. ! ADVERTENCIA: Si no se sigue alguna de las ADVERTENCIAS, es posible que se produzcan consecuencias graves tales como la muerte o lesiones graves. ! PRECAUCIÓN: Si no se sigue alguna PRECAUCIÓN se podrán producir, en algunos casos, consecuencias graves. Los siguientes símbolos de seguridad se utilizan a lo largo de todo este manual: Cumpla con esta instrucción Establezca una conexión a tierra Nunca intente • Luego de completar la instalación, controle que la unidad no presente errores de instalación. Brinde al usuario instrucciones adecuadas en relación al uso y limpieza de la unidad, de acuerdo con el Manual de Funcionamiento. ! ADVERTENCIA • La instalación deberá ser realizada por el distribuidor u otro profesional. Una instalación incorrecta podrá ocasionar pérdidas de agua, descargas eléctricas o incendios. • Instale el acondicionador de aire con bomba de calor de acuerdo con las instrucciones que figuran en este manual. Una instalación incompleta podrá ocasionar pérdidas de agua, descargas eléctricas o incendios. • Use sólo las piezas de instalación suministradas o especificadas. El uso de otras piezas podrá hacer que la unidad se afloje, que haya pérdidas de agua, descargas eléctricas o incendios. • Instale el acondicionador de aire con bomba de calor sobre una base sólida que pueda soportar el peso de la unidad. Una base inadecuada o una instalación incompleta podrán ocasionar lesiones en caso de que la unidad se caiga de su base • El trabajo eléctrico deberá ser realizado de acuerdo con el manual instalación y los códigos y normas de procedimiento de cableado eléctrico nacional y local. Un nivel de capacidad insuficiente o un trabajo eléctrico incompleto podrán ocasionar descargas eléctricas o incendios. • Use un circuito eléctrico dedicado. Nunca use un suministro de corriente compartido con otro electrodoméstico. • Para realizar el cableado, use un cable lo suficientemente largo como para cubrir toda la distancia sin empalmes. No use un prolongador. No agregue otras cargas al suministro de corriente; use un circuito eléctrico dedicado. (Si esto no es realizado de este modo, se podrá producir un nivel de calor anormal, descargas eléctricas o incendios). • Use sólo los tipos de cables especificados para conexiones eléctricas entre las unidades de interior y exterior. De manera firme, sujete con una abrazadera los cables de interconexión de modo que no reciban tensión externa. Las conexiones incomple- tas o la sujeción con una abrazadera podrán ocasionar el sobrecalentamiento de terminales o incendios. • Luego de completar las conexiones del cableado de interconexión y suministro, forme los cables de modo que no ejerzan fuerza indebida sobre las tapas o paneles eléctricos. Instale las tapas sobre los cables. Una instalación incompleta de la tapa podrá ocasionar el sobrecalentamiento de terminales, descargas eléctricas o incendios. • Si hubo pérdidas de algún refrigerante durante el trabajo de instalación, ventile la sala (Si es expuesto a las llamas, el refrigerante produce un gas tóxico). • Luego de completar toda la instalación, controle y repare cualquier pérdida de refrigerante en el sistema. (Si es expuesto a las llamas, el refrigerante produce un gas tóxico). •Al instalar o reubicar el sistema, mantenga el circuito refrigerante libre de sustancias que no sean el refrigerante especificado (R410A), tales como el aire. (La presencia del aire u otra sustancia ajena en el circuito refrigerante ocasionará la elevación anormal de la presión o su ruptura, ocasionando lesiones). • Durante el bombeo, detenga el compresor antes de retirar la tubería del refrigerante. Si el compresor aún se encuentra en funcionamiento y la válvula de detención es abierta durante el bombeo, se succionará aire hacia el sistema mientras el compresor está en funcionamiento. Esto generará una presión anormal y la adición de gases no condensables en el sistema. • Asegúrese de establecer una conexión a tierra. No conecte la unidad a una tubería de servicios, a un descargador o a una conexión telefónica terrestre. Una conexión a tierra incompleta podrá ocasionar descargas eléctricas o incendios. Una alta sobrecarga de corriente proveniente de rayos u otras fuentes podrá ocasionar daños sobre el acondicionador de aire con bomba de calor. ! PRECAUCIÓN • No instale el acondicionador de aire con bomba de calor en un lugar donde haya peligro de exposición a gases inflamables. Si se produce una acumulación de gas en la unidad, ésta se podrá incendiar. • Instale la tubería de drenaje siguiendo las instrucciones de este manual. Una tubería inadecuada podrá ocasionar inundaciones. • Ajuste la tuerca cónica de acuerdo al ajuste especificado utilizando una llave dinamométrica. Si la tuerca cónica se ajusta en exceso, ésta finalmente se podrá sufrir una fisura y ocasionar pérdida de refrigerante. • Brinde las medidas adecuadas para evitar que la unidad externa sea usada como refugio por los roedores. Si los roedores entran en contacto con las piezas eléctricas se podrán producir funcionamientos inadecuados, humo o incendios. Por favor, indíquele al cliente que mantenga limpia el área alrededor de la unidad. Precauciones de Seguridad

Introducción al Sistema

Las Bombas de Calor del Sistema Split sin Conducto y Zona Única cuentan con una unidad de ventilador interior/ evaporador con montaje de pared, que recibe refrigerante de una unidad de condensación externa con velocidad variable a través de un mando de inversión. El funcionamiento del sistema es controlado por medio de un control remoto. La unidad externa cuenta con un compresor de rotación de velocidad variable, un dispositivo de medición de válvulas de expansión electrónica (EEV) y un motor de ventilador de CC (corriente continua). Estos sistemas usan refrigerante R410A y aceite PVE. Las unidades externas son sistemas con voltajes de 208/230. Vienen con carga de fábrica de hasta 25 pies de tubería interconectada. Las unidades de interior poseen montaje de pared. Cuentan con un motor soplador de CC y un motor de rejilla de CC. La unidad cuenta con un sensor de temperatura ambiente y un sensor de temperatura con tubo evaporador. La unidad de pared es alimentada por voltaje proveniente de la unidad exterior. Se deberán seguir las especificaciones para un funcionamiento correcto • Los sistemas fueron diseñados para funcionar en rangos de temperatura de entre 60°F y 86°F en el modo de refrigeración y entre 60°F y 86°F en el modo de calefacción. • El aceite PVE es no reactivo al agua y no entrará en Hidrólisis. No hay necesidad de agregar un secador refrigerante al realizar el servicio técnico o al instalar este sistema. • La unidad con montaje de pared interior recibe un voltaje para su funcionamiento y señales de datos de comunicación en el cable nº 14 AWG, que se conecta entre las unidades interior y exterior. No deberá haber empalmes en el cableado de campo con recorrido entre las terminales 1, 2, 3 y 4. Un empalme en estos cables podrá hacer que el sistema pierda comunicación entre las unidades de interior y exterior. El sistema mostrará luego un código de error E7. • Los sistemas cuentan con suficiente carga de fábrica para hasta 25 pies de conexión de tubería de refrigeración. La tubería se conecta usando accesorios de tipo abocinado, tanto en la unidad de interior como la de exterior. La tubería deberá ser medida de acuerdo con las especificaciones. Ambas tuberías deberán ser aisladas. El único método para controlar la carga o ajustar la misma es a través del método para pesar, explicado en este manual (sin excepciones). • El sistema de condensado es un tipo de gravedad. Una bomba de condensado instalada en el campo podrá ser agregada al sistema. Siempre siga las instrucciones de instalación del fabricante al instalar una bomba de condensado. • Se deberán mantener los espacios libres adecuados tanto en la unidad interior como en la exterior. Los espacios libres inadecuados ocasionan problemas sobre el sistema, los cuales incluyen alta presión en el refrigerante, baja presión en el refrigerante y problemas de refrigeración de la bobina interior. Introducción Teoría Fundamental sobre Cómo Funciona el Sistema La unidad interior sentirá la temperatura de la sala en el punto donde la unidad de pared sea instalada. El ventilador interior funcionará de forma continua se encuentre en el modo de calefacción o refrigeración y no realizará ciclos de encendido y apagado con la unidad exterior. Si lo hiciera, no podría sentir ni mantener la temperatura ambiente. El sistema de inversor compresor de la unidad exterior variará el flujo de refrigerante y los niveles de volumen de aire interior para hacer coincidir el requisito de refrigeración dentro del espacio acondicionado. Si los sensores del sistema detectan una condición anormal, el sistema contará con la habilidad de tomar medidas preventivas. La cantidad de flujo refrigerante y la capacidad asociada generada por el sistema serán determinadas por cuán rápido está bombeando el compresor de rotación con velocidad variable del sistema. El requisito de velocidad de funcionamiento del compresor es determinado por la diferencia entre la temperatura del espacio acondicionado versus el punto de configuración establecido por el control remoto del dueño del hogar. Si se necesita una gran cantidad de capacidad, el compresor funcionará en una velocidad de alta frecuencia. A medida que la necesidad de capacidad se reduzca y la temperatura del ambiente se aproxime al punto de configuración, el compresor reducirá su velocidad. Cuando se haya alcanzado el punto de configuración, el compresor se apagará pero el ventilador interior continuará funcionando. Una vez que se siente una diferencia de temperatura entre la temperatura del punto de configuración del control remoto y la temperatura del ambiente, el compresor se reiniciará en una nueva velocidad calculada. Si un sensor del sistema determina que existe la necesidad de ajustar la señal de frecuencia para evitar un funcionamiento inadecuado del sistema, es posible que la frecuencia del compresor sea anulada y que se establezca una nueva frecuencia. Se deberá observar que el nivel de señal de la frecuencia enviada al compresor no podrá ser determinado por un técnico del servicio. En este manual, los componentes del sistema, el funcionamiento, las funciones del sensor y los procedimientos de diagnóstico serán explicados en mayor detalle.

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 7 Controles y Componentes de la Unidad Exterior Índice Introducción a la Unidad Exterior ........................................................................................................................................8 Identificación del Componente Exterior .............................................................................................................................8 Tablero de Control Principal Exterior ..................................................................................................................................9 Bloque Terminal ...............................................................................................................................................................10 Reactor ............................................................................................................................................................................10 Compresor .......................................................................................................................................................................10 Motor del Ventilador Exterior ...........................................................................................................................................10 Sensor de Temperatura de Descarga ................................................................................................................................11 Sensor de Temperatura de Descongelación ......................................................................................................................11 Sensor de Temperatura Ambiente Exterior .......................................................................................................................11 Sensor de Temperatura de la Tubería de Succión ...............................................................................................................11 Válvula de 4 Vías ...............................................................................................................................................................12 Válvula de Expansión Electrónica .....................................................................................................................................12 Acumulador .....................................................................................................................................................................12 Filtros ..............................................................................................................................................................................12 Calefactor de la Bandeja de la Base Eléctrica .....................................................................................................................12 Interruptor DIP .................................................................................................................................................................13

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 8 Introducción a la Unidad Exterior Los modelos con unidad de condensación exterior son sistemas de bomba de calor. La unidad exterior posee dos tableros de circuitos, un tablero con Módulo que conduce el compresor y un Tablero de Control Principal que maneja las funciones del sistema y los cálculos del inversor. Los sensores de temperatura monitorean las temperaturas claves a través del sistema, a fin de manejar las decisiones de funcionamiento. Identificación del Componente Externo Válvula de 4 Vías Acumulador Compresor Sensor de Temperatura de Descongelación Sensor de Temperatura de Descarga Válvula de Expansión Electrónica Filtros de Refrigerante Sensor de Temperatura Ambiente Exterior Motor del Ventilador Exterior Reactor del Factor de Potencia Sensor de Temperatura de la Tubería de Succión Bloque Terminal Tablero de Control Principal (la tapa del tablero no se muestra) Tablero de Control del Módulo Paleta del Ventilador Calefactor de la Bandeja de la Base 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 8 4 6 11 12 13 14 1 3 16 2 7 5 9 10 15

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 9 Placa de Control Exterior PCB (1) (PCB del Control Exterior) PCB (2) (Módulo de la PCB para 09-12K) 2 CN3 – Conector a tierra 10 CN36 – Conector para la comunicación entre la unidad interior y la exterior 6 CN11 – Conector para la bobina de la válvula de cuatro vías 4 CN9, CN8 – Conector para CN2, CN1 en la placa del módulo 12 CN50 – Conector para el control-DREDl 09-12 18-24 8 CN24 – Conector de comunicación para la placa de control y la placa del módulo CN17, CN47 – Conector para termistores 7 CN23 – Conector para POTENCIA de CC de 15V y 5V a la placa del módulo 3 CN15 – Conector para válvulas de expansión eléctrica 11 CN28, CN25 – Conector a P y N en la placa del módulo 9 CN22 – Conector para el motor del ventilador 5 FUSIBLE 1: (25A, 250VAC); FUSIBLE 2: (1A, 250VAC) 13 LED 1 – ON ( Encendido) constante en funcionamiento normal, el parpadeo indica la alarma. 14 Varistor RV1, RV2, RV3 15 CN10 – Conector para potencia de CC de 5V y 15V desde la PCB de control 18 Conexión del Calefactor de la Bandeja de la Base 16 BM2-1, BM2-2 – Interruptores DIP de Descongelación 17 23 CN11 – Conector para la comunicación entre la placa de control y la placa del módulo 19 P (CN1), N (CN5) – Conector para la placa de capacitancia 20 25 LI (CN7), LO (CN6) – Conector para el reactor 21 21 CN2, CN3, CN4 – Conector para el cable U, V, W del compresor 22 PCB (3) (Módulo de la PCB para 18-24K) CN10 – Conector para potencia de CC de 5V y 15V desde la PCB de control 23 CN11 – Conector para la comunicación entre la placa de control y la placa del módulo 24 P (CN8), N (CN9) – Conector para la placa de capacitancia 25 LI (CN3), LO (CN4) – Conector para el reactor 26 CN5, CN6, CN7 – Conector para el cable U, V, W del compresor 27 27 1 2 3 16 17 5 4 6 8 9 10 12 13 11 7 18 19 20 22 24 26 CN1, CN2 – Conector para encendido N y L 1

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 10 Bloque Terminal Reactor del Factor de Potencia El Reactor es un filtro inductivo que ayudará en la corrección de la influencia del factor de corriente eléctrica de la capacitancia del inversor. Es improbable que alguna vez este componente sufra una falla eléctrica. El Reactor está conectado eléctricamente a la Placa del Módulo en las conexiones terminales CN-7 y CN-8. La unidad exterior es alimentada eléctricamente por una Fase Simple de 208/230 Voltios, conectada al Bloque Terminal de la Unidad Externa. Las terminales 1 y 2 de la terminal de la unidad externa conectan este voltaje al sistema. La terminal número 3 es una terminal de comunicación que conecta el cableado entre las unidades exterior e interior. Una terminal con fuente de conexión a tierra conecta la unidad exterior con la fuente de encendido de la línea voltaje. Los interruptores de seguridad de condensados podrán averiar el cable 1. La unidad interior también está alimentada por el mismo suministro eléctrico que la unidad exterior. El cable nº 14 AWG está conectado al bloque terminal del cableado en la unidad exterior y es conducido hasta el bloque terminal de cables de la unidad interior. Al instalar el cableado suministrado, asegúrese de que el calibre del cable sea el correcto. No deberá haber ningún empalme en el cable eléctrico que va desde la unidad interior hasta la unidad exterior. El cable nº 3 se usa para transportar datos de comunicación entre las unidades interior y exterior. Un empalme en el cableado donde los cables estén retorcidos en un nudo podrá ocasionar una deformación en la comunicación de la señal de datos. Si se pierde la comunicación entre las unidades interior y exterior, aparecerá el CÓDIGO DE ERROR E7. Compresor Motor del Ventilador Exterior El compresor es un inversor de CC de tres fases con conducción de Rotación. El compresor posee la capacidad de funcionar con velocidad variable. La frecuencia de funcionamiento del compresor será determinada por la diferencia de temperatura entre el punto de configuración y la sala o la temperatura del aire exterior. (Modo de Frío versus Modo de Calor) El Reactor está conectado eléctricamente a la Placa del Módulo en las conexiones terminales CN-2, CN-3 y CN-4. El compresor posee una sobrecarga de temperatura interior que se abrirá si éste se calienta demasiado. El compresor recibirá protección adicional por parte del Sensor de Temperatura de Descarga del Compresor y por el Sensor de Temperatura de la Tubería de Succión. El motor del ventilador exterior es un motor de velocidad variable. La velocidad del motor requerida es calculada por la Placa de Control Principal. El motor se encuentra eléctricamente conectado a la Placa de Control Principal a través del ENCHUFE CN-21. En el funcionamiento en COOL MODE (Modo de Frío), el motor reducirá su velocidad a medida que la temperatura del aire descienda. Al funcionar en HEAT MODE (Modo de Calor), el motor incrementará su velocidad a medida que la temperatura del aire exterior descienda.

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 11 Sensor de Temperatura de Descarga Sensor de Temperatura de Descongelación El Sensor de Temperatura de Descongelación es un termistor de coeficiente negativo que cambiará su resistencia en respuesta a los cambios de temperatura de la bobina exterior. La Placa de Control Principal monitorea la temperatura de la bobina exterior, a fin de determinar cuándo es necesario que el sistema realice un ciclo de descongelación. El sensor también monitorea la temperatura de la bobina exterior durante los ciclos de descongelación, a fin de determinar las condiciones de finalización. Este sensor se conecta a la Placa de Control Principal a través del ENCHUFE CN-19. El Sensor de Temperatura de Descarga es un termistor de Coeficiente Negativo que siente la temperatura del gas caliente del compresor. La Placa de Control Principal monitorea la tem- peratura del gas caliente del compresor y realizará cambios en la velocidad del inversor en respuesta al insumo de este dispositivo. Este sensor se conecta a la Placa de Control Principal a través del ENCHUFE CN-17. Sensor de Temperatura Ambiente Exterior Sensor de Temperatura de la Tubería de Succión El Sensor de Temperatura de la Tubería de Succión es un termistor de coeficiente negativo que siente la temperatura de la tubería de succión. La Placa de Control Principal monitorea la temperatura de la tubería de succión, a fin de determinar el tamaño del orificio de la válvula electrónica de expansión, en un intento por mantener un adecuado funcionamiento del sobrecalentamiento. Este sensor se conecta a la Placa de Control Principal a través del ENCHUFE CN-18. El Sensor de Temperatura Ambiente Exterior es un termistor de coeficiente negativo que cambiará su resistencia en respuesta a los cambios de temperatura del aire exterior. La Placa de Control Principal monitorea la temperatura del aire exterior, a fin de determinar los requisitos de velocidad del aire exterior y la velocidad del inversor. El sensor también cumple una función en el cálculo de las condiciones de descongelación requeridas. Este sensor se conecta a la Placa de Control Principal a través del ENCHUFE CN-20.

CONTROLES Y COMPONENTES DE LA UNIDAD EXTERIOR

ESPAÑOL PÁGINA 12 Válvula de 4 Vías Válvula de Expansión Electrónica El dispositivo de medición es una válvula de expansión electrónica de tipo EEV. La válvula consta de un operador eléctrico y un cuerpo de válvula con orificio interior de tamaño variable. Cuando esté en funcionamiento, la Placa de Control Principal enviará pulsos de voltaje al operador eléctrico. Luego, el operador moverá de forma magnética la posición de la clavija del orificio de medición para variar su tamaño. La posición del dispositivo de medición es determinada por el ingreso desde un Sensor de Temperatura de la Tubería de Succión ubicado en la unidad exterior. La válvula de expansión electrónica cambiará el tamaño del orificio interior para mantener un nivel de sobrecalentamiento de aproximadamente 10°F. La Válvula de 4 Vías redirige el flujo de refrigerante a través del circuito de la tubería para permitir que el sistema intercambie las funciones de las bobinas interior y exterior. Cuando esté desactivada en COOL MODE (Modo de Frío), la válvula dirigirá el gas caliente del refrigerante hasta la bobina exterior. Cuando esté activada en HEAT MODE (Modo de Calor), la válvula dirigirá el gas caliente hasta la bobina interior. La capacidad de dirección del flujo de la válvula es controlada por un solenoide eléctrico. Al ser activada por 240 voltios, tensión de red, el solenoide moverá de forma magnética una lámina interior dentro de la Válvula de 4 Vías, a fin de cambiar la dirección del flujo del refrigerante. La Válvula de 4 Vías se encuentra eléctricamente conectada a la Placa de Control Principal a través del ENCHUFE CN-10. Acumulador El Acumulador está ubicado en el circuito de la tubería de succión en la entrada al compresor. El acumulador ayuda a evitar que el líquido refrigerante ingrese al compresor durante el funcionamiento Filtros de Refrigerante Calefactor de la Bandeja de la Base Eléctrica El sistema cuenta con filtros de retención de escombros que protegen los componentes del sistema interior de contaminantes en el refrigerante. El filtro es una parte permanente que típicamente no es reemplazada. Durante el funcionamiento en COOL MODE (Modo de Frío), la válvula mide el refrigerante de baja presión hasta la bobina interior. Durante el funcionamiento en HEAT MODE (Modo de Calor), la válvula mide el refrigerante de baja presión hasta la bobina exterior. El sistema posee un calefactor de la bandeja de la base eléctrica para la descongelación.

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 13 Interruptor DIP Configuraciones del Interruptor DIP Los interruptores DIP del tablero de la PCB de la unidad exterior son usados para controlar las configuraciones del ciclo de descongelación. Los interruptores DIP son configurados de fábrica de acuerdo con la Demanda de Descongelación (BM2-1 ON, BM2-2 ON). Las configuraciones de los interruptores DIP se podrán ajustar del siguiente modo: BM2-1 BM2-2 Descripción – (La descongelación se da generalmente cada 45 minutos) APAGADO APAGADO Demanda de descongelación para climas fríos (por omisión) ENCENDIDO APAGADO Descongelación por tiempo en frecuencia baja (10 Hz más baja que la descongelación regular) APAGADO ENCENDIDO Descongelación por tiempo en una frecuencia más alta (10 Hz más alta que la descongelación regular) ENCENDIDO ENCENDIDO Demanda de descongelación para climas moderados

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 14 [Página�dejada�en�blanco�intencionalmente].

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 15 Controles y Componentes de la Unidad Interior Índice Introducción a la Unidad Interior .......................................................................................................................................16 Identificación del Componente Interior ............................................................................................................................16 Placa de Control Interior ...................................................................................................................................................17 Bloque Terminal ...............................................................................................................................................................18 Pantalla ............................................................................................................................................................................18 Sensor de Temperatura Ambiente ....................................................................................................................................18 Sensor de Temperatura de la Bobina .................................................................................................................................18 Motor de Rejilla.................................................................................................................................................................19 Motor del Ventilador .........................................................................................................................................................19 Botón de Emergencia .......................................................................................................................................................19 Interruptor DIP y Configuraciones del Interruptor DIP ......................................................................................................20

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 16 Identificación del Componente Interior Introducción a la Unidad Interior La unidad interior se encuentra montada a una altura elevada sobre la pared, a fin de brindar una cobertura de acondicionamiento del aire dentro de un espacio condicionado. Se podrán agregar a estos sistemas accesorios de la bomba de condensación instalados/ suministrados en el campo. Las funciones del sistema incluyen: El funcionamiento del soplador de velocidad variable que se acelera o desacelera de acuerdo a los cambios demandados. Rejillas móviles para dirigir el aire, sensor de temperatura del aire interior, sensor de temperatura de la bobina del evaporador, pantalla de funcionamiento del consumidor. Bobina del evaporador con dispositivo de medición ubicada en la unidad exterior, y un Interruptor de Funcionamiento de Emergencia. 1 2 3 4 5 6 7 5 7 6 4 1 3 2 Sensor de Temperatura Ambiente Interior Pantalla Motor del Ventilador Motor de Rejilla Placa de Control Principal Sensor de Temperatura de la Tubería Bloque Terminal

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 17 Placa de Control Interior 2 2 CN27 – Conector a tierra 4 4 CN6 – Conector para termistores 9 9 CN2 – Conector para el control del cableado 6 6 CN7 – Conector para la pantalla 11 11 CN34 – Conector para el control Wi-Fi RV1 – Varistor 13 13 SW2 – 1- Seleccione el código remoto A o B, 2-Seleccione la tarjeta de la sala activada o desactivada 3,4-Seleccione el código eeprom 23, 26, 33 y 35 CN21, CN52 – Conector para encendido N y L 1 CN11 – Conector para motor paso a paso de izquierda a derecha 8 8 CN9 – Conector para el motor del ventilador 5 5 SW1 - Conector para el Interruptor de Encendido/ Apagado de Emergencia 12 15 15 CN23 – Conector para la comunicación entre la unidad interior y la exterior 3 3 CN51 – Conector para la tarjeta de la sala 10 10 CN5 – Conector para motor paso a paso hacia arriba y abajo 7 7 14 14 FUSE1 - Fusible de 3.15A/250VAC 12

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 18 Bloque Terminal Pantalla El bloque terminal de la unidad interior recibe potencia eléctrica desde la unidad exterior. Hay 4 conexiones para los cables eléctricos. Las terminales 1 y 2 están conectadas a las terminales 1 y 2 de la unidad exterior. El cableado le suministra potencia a la unidad interior. La terminal 3 es un cable de comunicación. La unidad interior le envía a la unidad exterior información de la temperatura del aire interior, de la temperatura de la bobina y del punto de configuración de la temperatura a través de este cable. Si este cable posee un empalme o está roto, la unidad interior no podrá tener comunicación con la unidad exterior. El CÓDIGO DE ERROR será el código E7. La pantalla interior posee un circuito de comunicación infrarrojo que recibe órdenes de funcionamiento del control remoto. Esta pantalla indicará los modos de funcionamiento, códigos de error, temperatura del aire interior, estado del temporizador y estado de la potencia. Sensor de Temperatura Ambiente El Sensor de Temperatura Ambiente de la Sala es un termistor de coeficiente negativo que reducirá su resistencia al haber incrementos en la temperatura del aire de la sala. El sensor se encuentra ubicado en un sujetador montado sobre la superficie de la bobina interior. El sensor se conecta a la placa de control a través del Cable CN-6. Sensor de Temperatura de la Bobina El Sensor de Temperatura de la Bobina es un termistor de coeficiente negativo que reducirá su resistencia al haber incrementos en la temperatura de la bobina. El sensor se encuentra ubicado en una ficha soldada sobre la superficie de la bobina interior. Este sensor monitoreará la temperatura de la bobina interior tanto en el modo de refrigeración como en el modo de calefacción. Si el sensor detecta una temperatura atípicamente fría o caliente de la bobina, el sistema realizará pasos de corrección funcionales para corregir el problema o informar un CÓDIGO DE ERROR. El sensor se conecta a la placa de control a través del Cable CN-6.

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 19 Rejilla del Motor Paso a Paso Motor del Ventilador Botón de Emergencia El Motor del Ventilador Interior es un motor de velocidad variable. El motor variará su velocidad de acuerdo con la velocidad del inversor compresor. La velocidad también puede ser configurada desde el control remoto o ser ajustada de forma automática utilizando el modo de ventilador AUTO (Automático). Cuando se encuentre en el modo de ventilador AUTO (Automático), la velocidad del ventilador será calculada usando la temperatura de configuración interior y la temperatura ambiente de la sala interior. (Temperatura del aire exterior en el modo de calor). El Motor del Ventilador se encuentra conectado a la placa de control interior a través del ENCHUFE CN-9. Si el control remoto no funciona, se podrá acceder al Botón de Emergencia abriendo, con un balanceo, el frente de la unidad de pared. El botón se encuentra ubicado del lado derecho. Presionar este botón activará el funcionamiento de AUTO MODE (Modo Automático). Activar AUTO MODE (Modo Automático) con este botón mantendrá una temperatura de 75°F. El sistema permanecerá en este modo hasta que los comandos sean recibidos por el circuito de comunicación de la unidad interior a través del control remoto. El MOTOR PASO A PASO mueve la rejilla hacia arriba y abajo, y de derecha a izquierda dependiendo de las selecciones realizadas desde el control remoto. El motor se encuentra conectado a la placa de control interior a través del ENCHUFE CN-11.

CONTROLES Y COMPONENTES DE LA UNIDAD INTERIOR

ESPAÑOL PÁGINA 20 Configuraciones del Interruptor DIP La PCB de la unidad interior de las series Avanzadas de los mini splits de zona única posee una serie de interruptores DIP que deberán ser configurados al reemplazar la PCB. La PCB de reemplazo es enviada con todos los interruptores configurados en la posición OFF (Apagado). Configuraciones de los interruptores: SW2-1 Selecciona el código remoto A o B. Normalmente configurado en la posición de apagado para el funcionamiento del código A. Si se usan dos unidades interiores en la misma área y el usuario desea controlar las mismas de forma separada, el interruptor SW2-1 de la segunda unidad estará configurado en la posición ON (Encendido) para el funcionamiento del código B. El control remoto inalámbrico de la segunda unidad también está configurado en el código B. SW2-2 Selecciona la tarjeta de la sala activada o desactivada. Normalmente configurada en la posición OFF (Apagado). Configure la posición ON (Encendido) al usar junto con una interface de tarjeta de sala utilizada en habitaciones de hotel. SW-3 & SW-4 Selecciona el código eeprom 23, 26, 33 y 35. Realice esta configuración para identificar el arqueo de la unidad. Configuraciones: 9K (23) SW-3 APAGADO SW-4 APAGADO 12K (26) SW-3 APAGADO SW-4 ENCENDIDO 15K (33) SW-3 ENCENDIDO SW-4 APAGADO 18K (33) SW-3 ENCENDIDO SW-4 APAGADO 24K (35) SW-3 ENCENDIDO SW-4 ENCENDIDO Interruptor DIP

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 21 Secuencia de Funcionamiento Índice Potencia del Sistema ........................................................................................................................................................22 Modo de Frío .....................................................................................................................................................................22 � Información�general ...................................................................................................................................................................... 22 Unidad interior ............................................................................................................................................................................... 22 Sensores de temperatura ............................................................................................................................................................. 22 Comunicación ................................................................................................................................................................................ 22 Unidad exterior. ............................................................................................................................................................................. 27 Sensores de temperatura ............................................................................................................................................................. 23 � Demanda�de�Finalización�de�Refrigeración .................................................................................................................................. 23 � Función�de�protección�de�refrigeración ....................................................................................................................................... 23 Modo de Calor ..................................................................................................................................................................23 � Información�general ...................................................................................................................................................................... 23 � Operación�de�prueba�de�aire�frío .................................................................................................................................................. 23 � Descongelación ............................................................................................................................................................................. 24 � Compensación�de�Temperatura�de�Calefacción�Automática ..................................................................................................... 24 Unidad Interior ............................................................................................................................................................................... 24 Sensores de temperatura ............................................................................................................................................................. 24 Comunicación ................................................................................................................................................................................ 24 Unidad exterior .............................................................................................................................................................................. 24 Sensores de temperatura ............................................................................................................................................................. 24 � Aviso�de�Finalización�de�Calefacción ............................................................................................................................................ 24 Modo Automático .............................................................................................................................................................25 Modo Seco ........................................................................................................................................................................25 � Información�general ...................................................................................................................................................................... 25 Unidad Interior ............................................................................................................................................................................... 25 Sensores de temperatura ............................................................................................................................................................. 25 Comunicación ................................................................................................................................................................................ 25 Unidad exterior .............................................................................................................................................................................. 25 Sensores de temperatura ............................................................................................................................................................. 25 Funcionamiento de la descongelación ...............................................................................................................................26 � Condiciones�de�Ingreso�al�Programa�de�Descongelación ........................................................................................................... 26 Condiciones Usadas para Determinar si se Formó Escarcha ...................................................................................................... 26 � Acciones�para�la�Descongelación ................................................................................................................................................. 26 � Condiciones�para�Salir�de�la�Descongelación .............................................................................................................................. 26 Funciones de Protección ...................................................................................................................................................26 Protección para altas temperatura TTC ...................................................................................................................................... 26 Protección de sobrecalentamiento de la unidad interior ............................................................................................................ 27 � Protección�del�compresor�contra�sobrecargas ........................................................................................................................... 27 � Protección�anti�congelamiento�del�intercambiador�de�calor�interior ......................................................................................... 27 � Protección�anti�congelamiento�de�la�bandeja�de�la�base ............................................................................................................. 27

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 22 Encendido del Sistema La potencia de 240 Volt CA del sistema conecta las terminales 1(N), 2(L), y tierra del bloque terminal de la unidad exterior. Este bloque terminal también cuenta con terminales para conectar la corriente a la unidad interior. Las lecturas de voltaje entre las terminales 1(N) y tierra, y las terminales 2(L) y tierra deberán ser de 120 VAC. La lectura de voltaje entre las terminales 1(N) y 2(L) deberá ser de 240 VAC. Una conexión adicional del bloque terminal (3) es para el cable de comunicación entre las unidades interior y exterior. NOTA: Un cableado incorrecto de estas conexiones podrá ocasionar un funcionamiento inadecuado o daños sobre los componentes del sistema. Modo de Refrigeración Información General El rango del control de temperatura en el modo de refrigeración está entre 60°F y 86°F. La temperatura configurada por el control remoto y el sensor de temperatura ambiente de la unidad interior determinarán si es necesaria una demanda de refrigeración. Si se justifica una demanda de refrigeración, la misma será comunicada desde la unidad interior hacia la unidad exterior. La rejilla de la unidad interior se abrirá usando un motor paso a paso, y el ventilador interior funcionará en la última velocidad configurada. La unidad exterior determinará la posición de la válvula de expansión electrónica (frecuencia) del compresor. Es posible que haya una demora de hasta 3 minutos antes de que el ventilador de la unidad exterior y el compresor se inicien. La velocidad del ventilador interior podrá ser controlada de forma manual por el usuario o de forma automática por el sistema. La velocidad podrá ser modificada entre LOW (Baja), MEDIUM (Media), y HIGH (Alta). Las condiciones predeterminadas para el control automático son las siguientes: (Tr= temperatura de la sala Ts= temperatura configurada) Alta Velocidad: Tr ≤ Ts + 5.4°F Velocidad Media: Ts + 1.8°F ≤ Tr < Ts + 5.4°F Velocidad Baja: Tr ≤ Ts + 1.8°F o cuando el sensor esté apagado. Habrá una demora de 2 segundos cuando la velocidad sea controlada de forma manual. Los sensores de temperatura de la unidad exterior: el ambiente exterior, descongelación, tubería de succión, y la descarga del compresor, usados junto con los sensores de temperatura interior, el ambiente interior y la tubería, brindan información a la placa de control exterior para monitorear el sistema y regular la frecuencia del compresor, el posicionamiento de la válvula de expansión electrónica (EEV), y la velocidad del ventilador exterior para lograr la temperatura ambiente deseada. Una vez que la refrigeración haya sido cubierta, el compresor de la unidad exterior se apagará, seguido por el ventilador exterior. La unidad interior continuará funcionando. Si el sistema detecta un funcionamiento incorrecto, se podrá apagar o mostrar un código de error en la placa de la pantalla de la unidad interior y/o en el LED de la placa principal de la unidad exterior. Unidad Interior Para ingresar al modo de frío, apunte el control remoto infrarrojo hacia la unidad interior y presione el botón de encendido, y luego presione el botón de modo COOL (Frío) si aún no se encuentra configurado en el modo de frío. Las señales recibidas por el receptor infrarrojo son retransmitidas a la placa principal de la unidad interior para encender el sistema y configurarlo en el modo frío. La placa principal de la unidad interior activará la pantalla de la unidad interior, iluminando la pantalla, indicando la temperatura ambiente y el estado actual de la unidad. La placa principal de la unidad interior emitirá una señal al motor paso a paso con rejilla para abrir la rejilla en una posición estacionaria o en uno de varios modos de oscilación. A medida que la rejilla se abra, la placa principal de la unidad interior enviará corriente al motor del ventilador interior, haciendo funcionar el ventilador en la última velocidad configurada. El motor del ventilador interior cuenta con un circuito de retroalimentación que brinda a la placa principal de la unidad interior información para controlar la velocidad del motor del ventilador. Sensores de Temperatura La unidad interior cuenta con dos sensores que brindan información de la temperatura a la placa principal de la unidad interior. Los sensores: un sensor de la temperatura ambiente interior y un sensor de temperatura de la bobina son usados para controlar el sistema durante el modo de frío. Los valores de la resistencia de los sensores variarán con la temperatura. La resistencia a los valores de temperatura se podrán encontrar usando un cuadro de temperatura/ resistencia específica del sensor que está siendo controlado. Comunicación Las placas principales de la unidad interior y exterior se comunican a través de una señal digital en el cable conectado a la terminal 3 de cada unidad. Un empalme o rotura del cable ocasionará un error de comunicación. Cuando un comando sea recibido desde el control remoto, la placa principal de la unidad interior se comunicará con la placa principal de la unidad exterior a través del cable de la terminal 3, a fin de realizar la función requerida. Unidad Exterior Cuando se solicite refrigeración, la placa principal de la unidad exterior enviará potencia al motor del ventilador exterior y al compresor. Dependiendo de los ciclos del sistema, podrá haber un período de hasta 3 minutos de espera antes de que el compresor y el ventilador exterior se inicien. ADVERTENCIA: No mida los voltajes del compresor, ya que se podrán producir daños sobre el medidor. Si la temperatura ambiente de la sala es inferior a la temperatura configurada, pero aún superior a 2°F por debajo de la temperatura configurada, el sistema ajustará la frecuencia de funcionamiento del compresor de forma automática, de acuerdo con los cambios en la temperatura del ambiente. La placa principal de la unidad exterior también controla la

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 23 posición de la EEV (Válvula de Expansión Electrónica) para regular el flujo de refrigerante hasta la bobina del evaporador de la unidad interior. Sensores de Temperatura Cuatro sensores de temperatura ubicados en la unidad exterior brindan información sobre la temperatura a la placa principal de la unidad externa para el control del sistema durante el modo de refrigeración. El sensor de temperatura ambiente exterior brinda la temperatura del aire enviado a la bobina exterior de la unidad exterior. El sensor de temperatura de descongelación brinda la temperatura sentida en la salida de la bobina exterior. El sensor de temperatura de la tubería de succión brinda la temperatura sentida en la tubería de succión entrante. El sensor de descarga del compresor brinda la temperatura sentida en la tubería de descarga del compresor. Demanda de Finalización de la Refrigeración El sistema demandará la finalización de la refrigeración cuando el sensor de temperatura ambiente del interior sea igual a o inferior a 2°F de la temperatura configurada de la sala. La placa de control interior se comunicará con la placa de control exterior para desactivar el compresor. El ventilador exterior funcionará durante 60 segundos antes de detenerse. El motor del ventilador interior y la rejilla continuará funcionando una vez finalizada la refrigeración. Para detener el modo de refrigeración, presione el botón de encendido para apagar el sistema, o pasar a otro modo. Función de Protección contra la Congelación Para evitar la congelación de la bobina de la unidad interior durante el modo de refrigeración, cuando el compresor funcione de forma continua durante 10 segundos y la temperatura de la bobina interior haya estado por debajo de los 32°F durante 10 segundos, el compresor se detendrá y el error será registrado en el listado de funcionamiento incorrecto. El ventilador de la unidad interior continuará funcionando. Cuando la temperatura de la bobina interior se eleve hasta los 45°F durante más de 3 minutos, el compresor se reiniciará y el sistema continuará funcionando. Modo de Calor Información General El rango del control de posición de ajuste en el modo de calefacción está entre 60°F y 86°F. La temperatura configurada por el control remoto y el sensor de temperatura ambiente de la unidad interior determinarán si es necesaria una demanda de calefacción. Si se justifica una demanda de calefacción, se agregará de forma automática un ajuste de compensación de temperatura al parámetro de funcionamiento y la demanda será comunicada desde la unidad interior hasta la unidad exterior. La rejilla de la unidad interior se abrirá usando un motor paso a paso. El ventilador interior no funcionará en este momento. La unidad exterior pasará de la válvula de 4 vías a la posición del modo de calefacción, y determinará la posición de la EEV (Válvula de Expansión Electrónica) (si está equipada con ésta) y la velocidad (frecuencia) del compresor. Es posible que haya una demora de hasta 3 minutos antes de que el ventilador de la unidad exterior y el compresor se inicien. (Tr= temperatura de la sala Ts= temperatura configurada) Si Tr ≤ Ts, la unidad exterior funcionará y el ventilador interior funcionará en la función de prevención de aire frío. Si Tr > Ts+, la unidad exterior se apagará y el ventilador interior funcionará en el modo de envío de calor residual. Si Tr < Ts+, la unidad exterior se reiniciará y el ventilador interior funcionará en el modo de prueba de aire frío. La velocidad del ventilador interior podrá ser controlada de forma manual por el usuario o de forma automática por el sistema. La velocidad podrá ser modificada entre LOW (Baja), MEDIUM (Media), y HIGH (Alta). Las condiciones predeterminadas para el control automático son las siguientes: Alta Velocidad: Tr < Ts Velocidad Media: Ts ≤ Tr ≤ Ts + 4°F Velocidad Baja: Tr > Ts + 4°F Cuando el ventilador interior esté funcionando en el modo automático y no haya retraso cuando la velocidad pase de alta a baja, el ventilador interior se mantendrá en velocidad alta durante un período de 3 minutos antes de pasar a velocidad baja. Funcionamiento a Prueba de Aire Frío Al iniciarse el modo de calefacción, el soplador interior no se en- cenderá de forma inmediata, sino cuando el sensor de tempera- tura de la bobina sienta una temperatura mínima. Normalmente este período tarda entre 30 segundos y 3 minutos, dependiendo de la temperatura ambiente exterior. HSU12�HG(DB)-SM Wiring Diagrams *Indoor fan control manual control: You can choose high, medium, low and automatic speed control. Automatic: When Tr Ts+2�, low speed. When the airflow speed has no delay from the high to low switching, the speed should be d 3 minutes (remain at high speed for 3 minutes.) before the next switch. *Airgate location control: the location for the airgate can be set according to your needs. Coldair proof operation 1. The indoor operation within 4 minutes after the start up is as the following diagram, the can be raised only after the speed has reached a certain level. � � � � � � � � � � 2. 4 minutes after the start up of the indoor fan, the light airflow and the low airflow will be tur set speed airflow. 3. In the cold air proof operation, the fan won’t stop after the start up. 4. During the cold air proof operation, the indoor system will continuously send ‘indoor hi signals to the outdoor system. * Residue heat sending. The indoor fan will send the residue heat at a low speed for 12 seco If other conditions are satisified, when the compressor stops, the indoor system will operate speed. The indoor fan will stop when the coil temperature is below the ‘heat start temp 4’. * Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan and the indoor temperature display won’t change. At the time, any indoor coil malfunctio neglected. When the outdoor defrosting finishes, the coil malfunction will still be neglected compressor has been started up for 30 seconds. The indoor temperature display will not ch the system operates at the cold air proof mode. * Automatic heating temperature compensation: when the system enters the heating m temperature compensation (4) will be added. When the status is switched off, the compen be erased. Heat start temp 1 Heat start temp 2 Heat start temp 3 Heat start temp 4 Set speed Low speed Light speed Fan/off Fan/off Keep the high speed. The fan doesn’t stop 4 minutos luego del inicio del ventilador interior, la velocidad suave o baja pasará a la velocidad configurada. En el funcionamiento a prueba de aire frío, el ventilador permanecerá encendido luego del inicio. Envío de calor residual: El ventilador interior funcionará en velocidad baja durante 12 segundos. Sensores de temperatura de la unidad exterior: el ambiente exterior, descongelación, tubería de succión, y la descarga del compresor, usados junto con los sensores de temperatura interior, el ambiente interior y la tubería, brindan información a la placa de control exterior para monitorear el sistema y regular la frecuencia del compresor, el posicionamiento de la válvula de expansión electrónica (EEV), y la velocidad del ventilador exterior para lograr la temperatura ambiente deseada. Velocidad Configurada Temperatura 1 de inicio de la calefacción Temperatura 2 de inicio de la calefacción Temperatura 3 de inicio de la calefacción Velocidad baja Velocidad suave Ventilador/ apagado Ventilador/ apagado Temperatura 4 de inicio de la calefacción Mantener la velocidad alta. El ventilador no se detiene.

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 24 Una vez que la refrigeración haya sido cubierta, el compresor de la unidad externa se apagará primero, seguido por el ventilador exterior. La válvula de 4 vías se desconectará durante 2 minutos una vez que el compresor se haya detenido. El ventilador de la unidad interior continuará funcionando a una velocidad mínima hasta que la temperatura de la bobina interior alcance una temperatura mínima y luego se apagará. Si el sistema detecta un funcionamiento incorrecto, se podrá apagar o mostrar un código de error en la placa de la pantalla de la unidad interior y/o en el LED de la placa principal de la unidad exterior. Descongelar Cuando el sistema inicie una demanda de descongelación, el motor del ventilador interior se detendrá. La pantalla de la unidad interior no cambiará. Cualquier funcionamiento incorrecto de la unidad interior será ignorado esta vez. El sistema realizará ciclos durante el funcionamiento de la descongelación. Cualquier funcionamiento incorrecto de la unidad interior será ignorado hasta que el compresor se reinicie y haya estado en funcionamiento durante 30 segundos. Al concluir el ciclo de descongelación, el motor interior entrará en el funcionamiento a prueba de aire frío. El modo de calefacción se reiniciará. Compensación de Temperatura de Calefacción Automática Cuando el sistema entre en el modo de calefacción, se agregará un ajuste de compensación de temperatura al parámetro de funcionamiento. Este ajuste será cancelado al salir del modo de calefacción. Unidad Interior Para ingresar al modo de calor, apunte el control remoto infrarrojo hacia la unidad interior y presione el botón de encendido, y luego presione el botón de modo HEAT (Calor) si aún no se encuentra configurado en el modo de calor. Las señales recibidas por el receptor infrarrojo son retransmitidas a la placa principal de la unidad interior para encender el sistema y configurarlo en el modo de calor. La placa principal de la unidad interior activará la pantalla de la unidad interior, iluminando la pantalla, indicando la temperatura ambiente y el estado actual de la unidad. La placa principal de la unidad interior le señalará al motor paso a paso con rejilla la apertura de la rejilla hasta una posición estacionaria. La placa principal de la unidad interior alimentará el motor del ventilador interior luego de que la unidad exterior se haya iniciado y se haya producido la calefacción de la bobina interior (consulte sobre el funcionamiento a prueba de aire frío). El motor del ventilador interior cuenta con un circuito de retroalimentación que brinda a la placa principal de la unidad interior información para controlar la velocidad del motor del ventilador. Sensores de Temperatura La unidad interior cuenta con dos sensores que brindan información de la temperatura a la placa principal de la unidad interior. El sensor de la temperatura ambiente interior y un sensor de temperatura de la bobina son usados para controlar el sistema durante el modo de calor. Los valores de la resistencia de los sensores variarán con la temperatura. La resistencia a los valores de temperatura se podrán encontrar usando un cuadro de temperatura/ resistencia específica del sensor que está siendo controlado. Comunicación Las placas principales de la unidad interior y exterior se comunican a través de una señal digital en el cable conectado a la terminal 3C de cada unidad. Un empalme o rotura de este cable ocasionará un error de comunicación. Cuando un comando sea recibido desde el control remoto, la placa principal de la unidad interior se comunicará con la placa principal de la unidad exterior a través del cable de la terminal 3C, a fin de realizar la función requerida Unidad Exterior Cuando se solicite calefacción, la placa principal de la unidad exterior enviará potencia a la válvula de 4 vías, al motor del ventilador exterior y al compresor. Dependiendo de los ciclos del sistema, podrá haber un período de hasta 3 minutos de espera antes de que el compresor y el ventilador exterior se inicien. NOTA: No mida los voltajes del compresor, ya que se podrán producir daños sobre el medidor. Si la temperatura ambiente de la sala es superior a la temperatura configurada, pero aún superior a 2°F por encima de la temperatura configurada, el sistema ajustará la frecuencia de funcionamiento del compresor de forma automática, de acuerdo con los cambios en la temperatura del ambiente. La placa principal de la unidad exterior también controla la posición de la EEV (Válvula de Expansión Electrónica) para regular el flujo de refrigerante hasta la bobina del evaporador de la unidad interior. Sensores de Temperatura Cuatro sensores de temperatura ubicados en la unidad exterior brindan información sobre la temperatura a la placa principal de la unidad externa para el control del sistema durante el modo de calefacción. El sensor de temperatura ambiente exterior brinda la temperatura del aire enviado a la bobina del condensador. El sensor de temperatura de descongelación brinda la temperatura sentida en la salida de la bobina exterior. El sensor de temperatura de la tubería de succión brinda la temperatura sentida en la tubería de succión entrante. El sensor de descarga del compresor brinda la temperatura sentida en la tubería de descarga del compresor. Demanda de Finalización de la Calefacción El sistema demandará la finalización de la calefacción cuando el sensor de temperatura ambiente del interior sea igual a o superior a 2°F por encima de la temperatura configurada de la sala. La placa de control interior se comunicará con la placa de control exterior para desactivar el compresor. El ventilador exterior funcionará durante 60 segundos antes de detenerse. La válvula de 4 vías se desconectará durante 2 minutos una vez que el compresor se haya detenido. Para detener el modo de calefacción, presione el botón de encendido para apagar el sistema, o pasar a otro modo.

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 25 Modo Automático Con el sistema encendido, presione el botón AUTO (Automático) del control remoto. El sistema pasará al modo automático de funcionamiento. A medida que la sala sea refrigerada o calefaccionada, el sistema alternará de forma automática entre el modo de frío, el modo de ventilación y el modo de calor. Hay un tiempo de funcionamiento mínimo de 15 minutos entre los cambios de modo Modo Seco Información General El rango de control de temperatura en el modo Dry (Seco) es de entre 60°F y 86°F. Este modo es usado con el propósito de deshumidificar. (Tr= temperatura de la sala Ts= temperatura configurada) Cuando Tr > Ts + 4°F, el compresor se encenderá y el ventilador interior funcionará en la velocidad configurada. Cuando Ts ≤ Tr ≤ Ts + 4°F, el compresor funcionará en la frecuencia de secado alto durante 10 minutos, y luego en el modo de secado bajo durante 6 minutos. El ventilador interior funcionará en velocidad baja. Cuando Tr < Ts, la unidad exterior se detendrá, y el ventilador interior se detendrá durante 3 minutos, y luego funcionará en la opción de velocidad baja. Velocidad automática del ventilador: Cuando Tr >= Ts + 9°F, Velocidad alta Cuando Ts + 5.4°F ≤ Tr < Ts + 9°F, Velocidad media Cuando Ts + 3.6°F ≤ Tr < Ts + 5.4°F, Velocidad baja Cuando Tr < Ts + 3.6°F, Velocidad suave Nota: Los modos TURBO (Turbo) y QUIET (Silencioso) se deberán configurar usando el control remoto. Si el ventilador exterior es detenido, éste se pausará durante 3 minutos. Si el ventilador exterior es detenido durante más de 3 minutos, y el compresor aún está en funcionamiento, el sistema pasará al modo de velocidad suave. Unidad interior Para ingresar al modo seco, apunte el control remoto infrarrojo hacia la unidad interior y presione el botón de encendido, y luego presione el botón de modo DRY (Seco) si aún no se encuentra configurado en el modo seco. Las señales recibidas por el receptor infrarrojo son retransmitidas a la placa principal de la unidad interior para encender el sistema y configurarlo en el modo seco. La placa principal de la unidad interior activará la pantalla de la unidad interior, iluminando la pantalla, indicando la temperatura ambiente y el estado actual de la unidad. La placa principal de la unidad interior emitirá una señal al motor paso a paso con rejilla para abrir la rejilla en una posición estacionaria o en uno de varios modos de oscilación. A medida que la rejilla se abra, la placa principal de la unidad interior enviará corriente al motor del ventilador interior, haciendo funcionar el ventilador en la última velocidad configurada. El motor del ventilador interior cuenta con un circuito de retroalimentación que brinda a la placa principal de la unidad interior información para controlar la velocidad del motor del ventilador. (Para más información, consulte la sección de información general). Sensores de Temperatura La unidad interior cuenta con dos sensores que brindan información de la temperatura a la placa principal de la unidad interior. Un sensor de la temperatura ambiente interior y un sensor de temperatura de la tubería son usados para controlar el sistema durante el modo seco. Los valores de la resistencia de los sensores variarán con la temperatura. La resistencia a los valores de temperatura se podrán encontrar usando un cuadro de temperatura/ resistencia específica del sensor que está siendo controlado. Comunicación Las placas principales de la unidad interior y exterior se comunican a través de una señal digital en el cable conectado a la terminal 3C de cada unidad. Un empalme o rotura de este cable ocasionará un error de comunicación. Cuando un comando sea recibido desde el control remoto, la placa principal de la unidad interior se comunicará con la placa principal de la unidad exterior a través del cable de la terminal 3C, a fin de realizar la función requerida. Unidad Exterior Cuando se solicite el modo seco, la placa principal de la unidad exterior enviará potencia al motor del ventilador exterior y al compresor. Dependiendo de los ciclos del sistema, podrá haber un período de hasta 3 minutos de espera antes de que el compresor y el ventilador exterior se inicien. ADVERTENCIA: No mida los voltajes del compresor, ya que se podrán producir daños sobre el medidor de voltaje. La placa principal de la unidad exterior también controla la posición de la EEV (Válvula de Expansión Electrónica) para regular el flujo de refrigerante hasta la bobina del evaporador de la unidad interior. Sensores de Temperatura Cuatro sensores de temperatura ubicados en la unidad exterior le brindan información sobre la temperatura a la placa principal de la unidad exterior para el control del sistema durante el modo seco. El sensor de la temperatura ambiente exterior brinda la temperatura del aire enviado a la bobina exterior de la unidad exterior. El sensor de temperatura de descongelación brinda la temperatura sentida en la salida de la bobina exterior.

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 26 El sensor de temperatura de la tubería de succión brinda la temperatura sentida en la tubería de succión entrante. El sensor de descarga del compresor brinda la temperatura sentida en la tubería de descarga del compresor. Para detener el modo seco, presione el botón de encendido para apagar el sistema, o pase a otro modo. Funcionamiento de la Descongelación Condiciones de Ingreso al Programa de Descongelación Condición 1: Al encender la unidad por primera vez, el compresor deberá funcionar durante 30 minutos de forma acumulativa y durante 1 minuto de forma continua. Al cumplir con las condiciones de descongelación, la misma será permitida. Condición 2: Luego de la primera descongelación, el compresor con el modo de calefacción deberá funcionar durante 30 minutos de forma acumulativa y durante 1 minuto de forma continua, y el intervalo de tiempo entre el ciclo de descongelación será de más de 45 minutos. Al cumplir con esta condición de descongelación, la misma será permitida. Condiciones Usadas para Determinar si se Formó Escarcha Bajo el estado de funcionamiento del compresor, al detectar el sensor de descongelación Te y el sensor de temperatura ambiente exterior Tao, se podrán satisfacer cualquiera de las siguientes condiciones por 2 minutos de forma continua y se considerará que se cumplió con las condiciones de descongelación. Condición 1: Permita que Tes (temperatura de condensación) = C×Tao-α, Cuando Tao < 0 32°F y luego C=0.8 , cuando Tao≥32°F y luego C=0.6 , α es configurado en una constante = 5. Condición 2: Cumpla con la condición 1, y ΔT1-T1≥35.6OF, T1 es identificado como el valor mínimo de Δ T1, Δ T1 = T(temperatura ambiente exterior )-T (temperatura de la bobina exterior). Acciones de Descongelación • Cuando C×Tao-α ≥23°F, y luego Te≤23°F y el ciclo de descon- gelación es de 45 minutos (ciclo de descongelación como punto de referencia). • Cuando 14°F ≤C×Tao-α <23OF, y luego Te≤Tes y el ciclo de descongelación es de 45 minutos (ciclo de descongelación como punto de referencia). • Cuando 8.6°F < C×Tao-α ≤14OF, y luego Te≤Tes y el ciclo de descongelación es de 65 minutos (Def1 =65 min. - ciclo de descongelación como punto de referencia). • Cuando 5°F ≤C×Tao-α ≤ 8.6OF, y luego Te≤Tes y el ciclo de descongelación es de 65 minutos (Def1 =65 min. – ciclo de descongelación como punto de referencia). • Cuando C×Tao-α <5°F, y luego Te≤ 5OF y el ciclo de descon- gelación es de 75 minutos (Def2 =75 min. - ciclo de descongel- ación como punto de referencia). • • Cuando la descongelación se inicie, el compresor se detendrá durante 1 minutos primero y el ventilador exterior funcionará en una velocidad alta, luego de 50 seg., las 4 vías apagadas y luego de 55 seg. el ventilador exterior se apagará. • El compresor se inicia luego de 1 minuto, el compresor fun- ciona durante 60 seg. en la frecuencia de descongelación de 38Hz, y luego funciona durante 60 seg. en la frecuencia de descongelación de 58Hz, y funciona durante 60 seg. en la fre- cuencia de descongelación de 88Hz, y el funcionamiento final es de 88Hz. • Durante el período de descongelación, la corriente mecánica y eléctrica del compresor y la ventilación de aire del compresor se encuentran efectivamente protegidas. • Luego de entrar en la descongelación, se deberá garantizar un tiempo de funcionamiento mínimo de 2 minutos antes de salir de la descongelación. Condiciones de Salida de la Descongelación Cuando se cumpla con cualquiera de las siguientes condiciones, el funcionamiento de la descongelación regresará al funcionamiento de la calefacción. • La temperatura de la bobina exterior supera los 44.6°F durante 60 segundos de forma continua. • La temperatura de la bobina exterior supera los 53.6°F durante 20 segundos de forma continua. • 11 minutos continuos para el funcionamiento de la descongelación • Durante la descongelación, la apertura de la válvula permanece sin modificación en 200, y la apertura de la válvula de inicio de la descongelación es controlada de acuerdo con inicio del retorno del aceite. Funciones de Protección Protección de Temperaturas Altas TTC El sensor de la tubería de descarga del compresor (temperatura de salida) siente la temperatura del refrigerante al salir del com- presor. La temperatura sentida que recibe el sensor por parte del circuito de control hará que la frecuencia del compresor se incremente o reduzca. (lea el siguiente cuadro). Si se siente una temperatura de >= 230°F durante 20 segundos, se indicará un có- digo de error en la protección de sobrecalentamiento de la salida en la unidad exterior. Detención atípica Reducción de la frecuencia rápidamente (1HZ/ 1 segundo) TTC (°F) 230°F 212°F 209°F 199°F 194°F Reducción de la frecuencia lentamente (1HZ/ 10 segundos) La frecuencia no cambia Incremento de la frecuencia (1HZ/ 10 segundos) Incremento de la frecuencia (1HZ/ 1 segundo)

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 27 Protección Anti Congelamiento de la Bobina Interior La temperatura sentida por el sensor de la bobina de la unidad interior es usada para determinar en qué frecuencia del compresor deberá funcionar para la protección contra el congelamiento. Tpg_interior: temperatura del sensor de la tubería de la unidad interior Cuando Tpg_interior < Tpg1, la frecuencia del compresor se reducirá en el promedio de 1HZ / 1 segundo. Cuando Tpg_interior < Tpg2, la frecuencia del compresor se reducirá en el promedio de 10HZ / 10 segundos. Cuando Tpg_interior comience a elevarse nuevamente, y Tpg2 ≤ Tpg_interior ≤ Tpg3, la frecuencia del compresor no cambiará. Cuando Tpg3 < Tpg_interior Tpg4, el compresor se reiniciará. 59°F // ice_temp_3+5 46°F // ice_temp_3+2 43°F Reduciéndose lentamente Reduciendo rápidamente ice_temp_1 Detención Manteniendo la frecuencia Incrementándose lentamente 32°F 37°F 41°F 43°F 48°F Protección Anti Congelamiento de la Bandeja de la Base A fin de evitar el congelamiento, la bandeja de la base está equipada con un calefactor eléctrico. Sus condiciones de funcionamiento son las siguientes: Si la temperatura exterior es superior a los 37.4°F, la bandeja de la base eléctrica estará apagada. Con una temperatura exterior de entre 24.8°F y 33.8°F, el calefactor de la bandeja de la base eléctrica estará apagado durante 20 minutos, y luego encendido durante 10 minutos. Con una temperatura de entre 10.4°F y 24.8°F, el calefactor de la bandeja de la base eléctrica estará apagado durante 15 minutos, y luego encendido durante 15 minutos. Si la temperatura exterior <10.4°F, el calefactor de la bandeja de la base eléctrica estará encendido. Protección de Sobrecalentamiento de la Unidad Interior El sensor de la bobina interior siente la temperatura de la bobina interior. Si la temperatura sentida es superior a 133°F, la frecuencia del compresor se reducirá para evitar el sobrecalentamiento del intercambiador de calor. Si Tc >= 133°F durante más de 10 segundos, el compresor se detendrá y se indicará un código de error en la unidad exterior. Si se apaga el compresor durante 3 minutos y Tc <118°F, el compresor se reiniciará. Si la temperatura sentida es inferior a 118°F, la función de protección será cancelada. HSU12�HG(DB)-SM Wiring Diagrams 25 Domestic Air Conditioner 5.2.5.2�TC high temperature-preventing control of the indoor heating unit� Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running state). The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the temperature is higher than 55�, decrease the rotate speed of the compressor and do the high temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat exchanger is lower than 47�, recover to the normal control. TC The compressor stops Fgh_t1 65� Fgh_t1�2 Fgh_t2�2 N Decreasing the frequency rapidly Fgh_t2 59� P Decreasing the frequency slowly Fgh_t3 55� Fgh_t3�2 Fgh_t4—2 Q Prohibiting increasing the frequency Fgh_t4 51� R Increasing slowly Fgh_t5 47� Fgh_t5—2 Normal N�Decreasing at the speed of 1HZ/1 second P�Decreasing at the speed of 1Hz/10 seconds Q�Continue to keep the last-time instruction cycle R�Increasing at the speed of 1Hz/10seconds Remarks: the outdoor unit 5.2.5.3 The control of preventing the overcurrent of the compressor� �During the starting process of the compressor, if the curren of the compressor is greater than 17A for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only after the the power is off. �During the starting process of the compressor, if the AC current is greater than 12A, the frequency of the compressor decreases at the speed of 1HZ/second. �During the starting process of the compressor, if the AC current is greater than 10A, the frequency of the compressor decreases at the speed of 0.1HZ/second. �During the starting process of the compressor, if the AC current is greater than 9A, the frequency of the compressor increases at the prohibited speed. �During the starting process of the compressor, if the AC current is greater than 8A, the frequency of the compressor increases at the speed of no faster than 0.1HZ/second. 149°F 138°F 131°F 124°F 117°F Protección contra la Sobrecarga del Compresor Si el consumo de corriente del compresor en el inicio es superior al punto de sobrecarga que figura en el siguiente cuadro durante aproximadamente 3 segundos, el compresor se detendrá, y un código será indicado en la unidad exterior. Luego de 3 minutos, el compresor intentará reiniciarse. Si el problema de sobrecarga se produce 3 veces en 20 minutos, el sistema se bloqueará, y un código será indicado en la unidad exterior. Será necesario retirar la corriente del sistema para reiniciar el problema de bloqueo. La frecuencia del compresor podrá cambiar dependiendo del consumo de corriente en el inicio. Consulte el cuadro y la tabla de corriente/ Hz mostrado a continuación. Superior a la corriente 1: Reducción de 1Hz/ segundo Superior a la corriente 2: Reducción de 0.1Hz/ segundo Superior a la corriente 3: Sin cambios Modelo Punto de sobrecarga (aprox.) Disminución de la Velocidad de la Corriente 1 (Aprox.) Disminución de la Velocidad de la Corriente 2 (Aprox.) Disminución de la Velocidad de la Corriente 3 (Aprox.) 09K 11A 8.5A 8A 7A 12K 13A 10A 9.5A 8.5A 15K 15A 12A 11.5A 10.5A 18K 15A 12A 11.5A 10.5A 24K 17A 13.5A 13A 12A N: Reducción de la velocidad de 1Hz/1 segundo P: Reducción de la velocidad de 1Hz/10 segundos Q: Continúa manteniendo la instrucción del ciclo de la última vez R: Incremento de la velocidad de 1Hz/ 10 segundos El compresor se detiene N Reducción de la frecuencia rápidamente P Reducción de la frecuencia lentamente Q Prohibición de incremento de la frecuencia R Incrementándose lentamente

SECUENCIA DE FUNCIONAMIENTO

ESPAÑOL PÁGINA 28 [Página�dejada�en�blanco�intencionalmente].

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 29 Códigos de Error y Solución de Problemas Índice Pantalla Interior de Descripciones y Códigos de Error ....................................................................................................... 30 Pantalla de la Unidad Interior .........................................................................................................................................................30 Funcionamiento Incorrecto del Motor del Ventilador Interior de CA .................................................................................. 31 Pantalla de la Unidad Interior .........................................................................................................................................................31 E14 ............................................................................................................................................................................ 31 Falla del Motor del Ventilador Exterior de CC .................................................................................................................... 32 Pantalla de la Unidad Exterior. ........................................................................................................................................................32 El LED1 Parpadea 9 Veces ....................................................................................................................................... 32 Protección del IPM ............................................................................................................................................................ 33 Pantalla de la Unidad Exterior ........................................................................................................................................................33 El LED1 Parpadea 2 Veces ....................................................................................................................................... 33 Sobrecarga del Compresor ............................................................................................................................................... 33 Pantalla de la Unidad Exterior ........................................................................................................................................................33 El LED1 Parpadea 3 o 24 o 25 Veces ....................................................................................................................... 33 La Falla de Comunicación entre el IPM y la PCB Exterior .................................................................................................... 34 Pantalla de la Unidad Exterior. ........................................................................................................................................................34 El LED1 Parpadea 4 Veces ....................................................................................................................................... 34 Suministro de Corriente Demasiado Alto o Demasiado Bajo ............................................................................................. 35 Pantalla de la Unidad Exterior. ........................................................................................................................................................35 El LED1 Parpadea 6 Veces. ...................................................................................................................................... 35 Protección contra el Sobrecalentamiento de la Temperatura de Descarga ........................................................................ 36 Pantalla de la Unidad Exterior. ........................................................................................................................................................36 El LED1 Parpadea 8 Veces ....................................................................................................................................... 36 Falla de Comunicación entre las Unidades Interior y Exterior ............................................................................................ 36 Pantalla de la Unidad Interior .........................................................................................................................................................36 E7 .............................................................................................................................................................................. 36 Pantalla de la Unidad Exterior. ........................................................................................................................................................6 El LED1 Parpadea 15 Veces. .................................................................................................................................... 36 Detección de Pérdida de Sincronización ............................................................................................................................ 37 Pantalla de la Unidad Exterior. ........................................................................................................................................................37 El LED1 Parpadea 18 o 19 Veces ............................................................................................................................. 37 Sobrecarga de la Unidad Interior en el Modo de Calefacción .............................................................................................. 37 Pantalla de la Unidad Exterior ........................................................................................................................................................37 El LED1 Parpadea 18 Veces ..................................................................................................................................... 37 Control de los Componentes del Sistema ......................................................................................................................... 38 Control de los Componentes de la Unidad Exterio ............................................................................................................ 38 Control de los Sensores de la Unidad Exterior ...........................................................................................................................................38 Control de la Bobina de la Válvula de Inversión ...........................................................................................................................................38 Control del Motor del Ventilador de CC ......................................................................................................................................................38 Control del Motor Paso a Paso con EEV ......................................................................................................................................................38 Control del Reactor PFC ..............................................................................................................................................................................38 Control del Componente de Protección del Tomacorriente .....................................................................................................................38 Control de las Bobinas del Compresor ........................................................................................................................................................39 Control�del�Calefactor�de�Bandeja�con�Base�Eléctrica ...............................................................................................................................39 Control de los Componentes de la Unidad Interior ............................................................................................................ 39 Control de los Sensores de la Unidad Interior ...............................................................................................................................39 � Control�del�Motor�Paso�a�Paso�hacia�Arriba/�Abajo�o�Izquierda ...................................................................................................40 Control del Motor del Ventilador Interior de CC ...........................................................................................................................40 Optimización del Rendimiento ......................................................................................................................................... 40 Limpieza de la Tapa Frontal ............................................................................................................................................... 40 Consejos para la Solución de Problemas ........................................................................................................................... 41

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 30 Indicación de Código Descripción Interior Exterior (tiempos de parpadeo del LED 1) Interior y Exterior E7 15 Falla de comunicación entre las unidad interior y exterior Funcionamiento Incorrecto en la Parte Interior E1 / Falla del sensor de temperatura de la sala E2 / Falla del sensor de la bobina E4 / Error del EEPROM interior E14 / Funcionamiento incorrecto del motor del ventilador interior Funcionamiento Incorrecto en la Parte Exterior F12 1 Error del EEPROM Exterior F1 2 La protección del IPM F22 3 Protección contra la sobrecarga de la electricidad de CA para el modelo exterior F3 4 Falla de comunicación entre el IPM y la PCB exterior F19 6 El voltaje de la corriente es demasiado alto o bajo F27 7 El compresor posee un rotor bloqueado o detenido momentáneamente F4 8 Protección contra el sobrecalentamiento de la temperatura de salida F8 9 Falla del motor del ventilador de CC Exterior F21 10 Falla del sensor de temperatura de descongelación F7 11 Falla del sensor de temperatura de succión F6 12 Falla del sensor de temperatura ambiente F25 13 Falla del sensor de temperatura de salida F11 18 Desvío de la normalidad del compresor F28 19 Detección de error de bucle infinito desde la estación F2 24 Sobrecarga del compresor F23 25 Protección por sobrecarga del compresor de una sola fase F36 39 Falla del sensor de temperatura de la bobina exterior Pantalla de la Unidad Interior Los códigos de error se mostrarán en la unidad interior, en lugar de la temperatura configurada. Pantalla Interior de Descripciones y Códigos de Error

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 31 Funcionamiento Incorrecto del Motor del Ventilador Interior de CA Pantalla Interior E14 Esto es ocasionado por una falla del motor interior o de la PCB interior Lista de Repuestos: PCB interior Motor interior Controle el voltaje del enchufe del ventilador en la PCB. El motor del ventilador presenta una falla Reemplace el motor La PCB interior presenta una falla; cambie la PCB interior No Sí

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 32 Falla del Motor del Ventilador Exterior de CC Pantalla Exterior El LED1 Parpadea 9 Veces Esto es ocasionado por una falla del motor exterior o de la PCB exterior Lista de Repuestos: PCB Exterior Motor exterior Apague el encendido y controle si la conexión del enchufe del motor exterior es segura Restaure la corriente hacia la unidad y encienda el sistema en el modo Cool (Refrigeración). ¿Funciona el motor del ventilador? Mida el voltaje de 0 a 5 V entre las clavijas 3 y 6 Falla del motor exterior Falla de la PCB exterior Reinicie el enchufe 1. Mida un voltaje aproximado de 310V entre las clavijas 1 y 3 del conector del motor en la PCB 2. Mida un voltaje aproximado de 15V CC entre las clavijas 3 y 4 del conector del motor en la PCB 3. Mida un voltaje aproximado de 0 a 6V entre las clavijas 3 y 5 del conector del motor en la PCB No No Sí Sí Sí Sí No No 6 5 4 3 2 1

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 33 Protección del IPM Pantalla Exterior El LED1 Parpadea 2 Veces Bajo este error, por favor asegúrese de que la presión del refrigerante sea normal y sin bloqueos, y luego reemplace el módulo de corriente. Lista de Repuestos: Refrigerante Módulo de potencia Encienda la unidad. ¿Se exhibe el error antes de que se inicie el compresor? El módulo de potencia presenta errores; reemplace el módulo ¿Continúa el problema? Controle que la carga de refrigerante sea apropiada El compresor se inicia normalmente, pero se informan funcionamientos incorrectos luego de haber funcionado durante un período de tiempo. No Sí Sí Sí Sí Sobrecarga del Compresor Pantalla Exterior El LED 1 Parpadea 3 o 24 o 25 Veces Lista de Repuestos: Módulo de potencia Refrigerante El compresor se inicia normalmente, pero se informan funcionamientos incorrectos luego de haber funcionado durante un período de tiempo. Corrija el suministro de potencia Encienda la unidad. ¿Se exhibe el error antes de que se inicie el compresor? ¿Es normal el voltaje del suministro de potencia? Controle la carga de refrigerante El módulo de potencia presenta errores; reemplace el módulo de potencia Sí Sí Sí No No

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 34 La Falla de Comunicación entre el IPM y la PCB Exterior Pantalla Exterior El LED1 Parpadea 4 Veces Lista de Repuestos: Módulo de potencia PCB Exterior 1) Para contar con conexiones seguras, controle los enchufes de MODULE COM (Com. del Módulo) y MODULE POWER (Potencia del Módulo) en los módulos del IPM y la PCB Exterior. 2)Para contar con conexiones seguras, controle los cables P y N entre los módulos del IPM y la PCB exterior. ¿Son las conexiones seguras? Reemplace el módulo de potencia 1. Mida un voltaje aproximado de 5V CC entre las clavijas 1 y 2 del conector de Potencia del Módulo. 2. Mida un voltaje aproximado de 15V CC entre las clavijas 2 y 3 del conector de Potencia del Módulo. Vuelva a realizar las conexiones Reemplace la PCB exterior. Sí Sí No No

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 35 Suministro de Corriente Demasiado Alto o Demasiado Bajo Pantalla Exterior El LED1 Parpadea 6 Veces Lista de Repuestos: Módulo de Potencia Encienda la unidad. ¿Funciona el compresor normalmente? El suministro de corriente es inestable. Reemplace el módulo de potencia. Reemplace el módulo de potencia. Controle las terminales P y N del suministro de corriente en la PCB exterior. ¿Es el voltaje >390V o <150V CA? Verifique el voltaje adecuado en las terminales L1 y L2 de la unidad exterior Fuente de corriente adecuada No No No Sí Sí Sí

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 36 Protección contra el Sobrecalentamiento de la Temperatura de Descarga Pantalla Exterior El LED1 Parpadea 8 Veces Lista de Repuestos: PCB Exterior Sensor de Salida Encienda la unidad. Controle la temperatura de salida del compresor. El suministro de corriente es inestable. Hay pérdida de refrigerante. Controle la carga de refrigerante La PCB exterior presenta fallas; reemplace la PCB. ¿Supera la temperatura los 230°F en breve luego del inicio del compresor? Controle la resistencia del sensor de la temperatura de salida. ¿Es correcto? El sensor presenta fallas; reemplace el sensor. No No No Sí Sí Sí Falla de Comunicación entre las Unidades Interior y Exterior Pantalla Interior Pantalla Exterior E7 El LED1 Parpadea 15 Veces Lista de Repuestos PCB interior PCB Exterior Módulo de potencia Corrija el cableado entre las unidades interior y exterior. 1. Controle que las conexiones del cableado se encuentren ajustadas de forma segura. 2. Controle si los cables LN se encuentran conectados de forma inversa Controle el LED de la PCB exterior No Sí LED LED 1 LED 2 Solución ENCENDIDO/APAGADO APAGADO ENCENDIDO Falla de la PCB exterior ENCENDIDO/APAGADO ENCENDIDO ENCENDIDO Esto es ocasionado por una falla de la PCB Exterior o de la PCB Interior. Primero cambio una pieza; si aún no se resolvió, cambie otra. ENCENDIDO/APAGADO APAGADO APAGADO Esto es ocasionado por una falla de la PCB Exterior o del módulo de potencia. Primero cambio una pieza; si aún no se resolvió, cambie otra.

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 37 Detección de Pérdida de Sincronización Pantalla Exterior El LED1 Parpadea 18 o 19 Veces Lista de Repuestos: Compresor Módulo de potencia 1. El cableado del compresor es incorrecto o posee malas conexiones. 2. El compresor está dañado. Encienda la unidad. ¿Se inicia el compresor? El compresor se inicia, pero pronto se detiene. El LED1 de la PCB exterior comienza a parpadear 18 o 19 veces en un promedio de 1Hz. El módulo de potencia presenta errores; reemplace el módulo de potencia. El compresor presenta fallas; reemplace el compresor. Sí Sí El problema continúa No Sobrecarga de la Unidad Interior en el Modo de Calefacción Pantalla Exterior El LED1 Parpadea 18 Veces Lista de Repuestos: Sensor de la tubería interior PCB interior Refrigerante Realice la recarga siguiendo las especificaciones. 1. El sensor de la tubería presenta fallas. 2. La PCB interior presenta fallas. Limpie del filtro de aire. Controle la carga de refrigerante del sistema. ¿Se encuentra con exceso o falta de carga? ¿Se informó el funcionamiento incorrecto luego de que la unidad estuvo funcionando por un período de tiempo ¿Se encuentra el filtro de aire interior sucio? No No Sí Sí Sí

CÓDIGOS DE ERROR Y SOLUCIÓN DE PROBLEMAS

ESPAÑOL PÁGINA 38 Control de los Componentes del Sistema Control de los Componentes de la Unidad Exterior Paso 3 Vuelva a colocar el enchufe en el conector al finalizar la evaluación. Control del Motor del Ventilador de CC Paso 1 Desconecte el enchufe del Motor del Ventilador de CC del conector del tablero de control para realizar esta evaluación. Si esto no se realiza, podrá haber lecturas imprecisas. Paso 2 Consulte el cuadro que se muestra a continuación para conocer las combinaciones de las clavijas del enchufe y los valores de las resistencias. Nota: La evaluación es sensible a la polaridad; realice la adherencia a la colocación de la sonda como se muestra en el cuadro. Guía de Prueba Roja Guía de Prueba Negra Roja --- Negra Blanca Amarilla Azul Roja --- 3.10 Meg 3.05 Meg 3.28 Meg Se carga hasta el infinito --- --- --- --- --- Negra 43.85K 145.1K Se carga hasta el infinito Blanca 189.0K Se carga hasta el infinito Amarilla Se carga hasta el infinito Azul Paso 3 Vuelva a colocar el enchufe en el conector al finalizar la evaluación. Control del Motor Paso a Paso con EEV Paso 1 Desconecte el enchufe del Motor Paso a Paso con EEV del conector del tablero de control para realizar esta evaluación. Si esto no se realiza, podrá haber lecturas imprecisas. Paso 2 Consulte el cuadro que se muestra a continuación para conocer las combinaciones de las clavijas del enchufe y los valores de las resistencias. Blanca Amarilla Anaranjada Azul Roja Gris Blanca --- 92.6Ohm --- 47.0 Ohm --- Amarilla --- 93.1 Ohm --- 47.0 Ohm Anaranjada 46.5 Ohm --- Azul 46.8 Ohm Roja --- Gris Paso 3 Vuelva a colocar el enchufe en el conector al finalizar la evaluación. Control del Reactor PFC Paso 1 Desconecte los cables de las terminales LI y LO del tablero del módulo de potencia. Paso 2 Usando un Ohmímetro, controle el valor de la resistencia del Reactor PFC. El valor de la resistencia de la bobina es de 1.30 Ohms máx. Si el valor de la resistencia difiere de este valor, verifique el cableado y las conexiones al Reactor PFC como también el Reactor PFC mismo. Repare o realice reparaciones según sea necesario. El control de los siguientes componentes requiere el uso de un Ohmímetro y una Sonda de Temperatura. (La sonda de temperatura se usa durante la evaluación del sensor únicamente). NOTA: Al usar las sondas de evaluación, realice el sondeo de los contactos trasero o lateral del enchufe para obtener la lectura. No intente sondar el extremo del conector del enchufe, ya que esto podrá dañar los contactos del enchufe. Control de los Sensores de la Unidad Exterior NOTA: Use el cuadro de temperatura/ sensor respectivamente para el tipo de sensor que se está evaluando. Sensor de descarga del compresor Sensor de succión Sensor de la tubería (temperatura de congelación) Sensor del ambiente Paso 1 Desconecte el enchufe del sensor del tablero de control para esta evaluación. Si esto no se realiza, podrá haber lecturas imprecisas. Paso 2 Utilizando una sonda de temperatura, mida la temperatura del sensor que se está evaluando. Paso 3 Usando un Ohmímetro, controle el valor de la resistencia del sensor. Paso 4 Consultando la tabla de temperatura/ resistencia del sensor que se está evaluando, verifique que el valor de las resistencias se correspondan con la temperatura controlada en el paso 2. Reemplace el sensor si la lectura es abierta, en cortocircuito, o fuera de las especificaciones de la tabla de temperatura/ resistencia. Paso 5 Vuelva a colocar el enchufe en el conector al finalizar la evaluación. Control de la Bobina de la Válvula de Inversión Paso 1 Desconecte el enchufe de la válvula de inversión del conector del tablero de control para realizar esta evaluación. Si esto no se realiza, podrá haber lecturas imprecisas. Paso 2 Usando un Ohmímetro, controle el valor de la resistencia de la bobina. El valor de la resistencia de la bobina es de 2.08K Ohms. Reemplace la bobina de la válvula si la lectura es abierta, en cortocircuito, o si se trata de una válvula significativamente diferente de aquella de 2.08K Ohms. NOTA: Las lecturas de las resistencias de los componentes mostradas en esta sección sirven sólo como referencia. Los valores de resistencia actual podrán diferir dependiendo del modelo que se está evaluando. Las lecturas de los componentes que se muestran a continuación están basadas en una unidad exterior cuyo modelo es HSU12VHGL-W.