ABB EBS852 Operating Instruction
Text of the manual
Power electronic unit for cabinet
installation
EBS852, EBS862 (Contrac)
Pos: 1 /Titelblätter / Copyright/BA-IA/Aktorik/Antriebe/Leistungselektronik/EBS852, EBS862 (Contrac) @ 20\mod_1209026268421_3101.doc @ 182186
To control Contrac actuators
in areas with explosion protection
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 2 /Titelblätter / Copyright/Copyright-Seite @ 0\mod_1138781938968_3101.doc @ 3122
Power electronic unit for cabinet installation
EBS852, EBS862 (Contrac)
Operating Instruction
42/68-831-EN
07.2008
Rev. A
Manufacturer:
ABB Automation Products GmbH
Schillerstraße 72
32425 Minden
Germany
Tel.: +49 551 905-534
Fax: +49 551 905-555
[email protected]
© Copyright 2008 by ABB Automation Products GmbH
Subject to change without notice
This document is protected by copyright. It assists the user with the safe and efficient operation of the
device. The contents may not be copied or reproduced in whole or in excerpts without prior approval of
the copyright holder.
Pos: 3 /Inhaltsverzeichnis/Inhaltsverzeichnis für alle Dokumente @ 0\mod_1138710310890_3101.doc @ 3129
Contents
EBS852, EBS862 (Contrac)
3
1
Safety....................................................................................................................................................................5
1.1
General Safety Information ............................................................................................................................5
1.2
Proper use......................................................................................................................................................5
1.3
Technical limits...............................................................................................................................................6
1.4
Warranty provision .........................................................................................................................................6
1.5
Labels and symbols........................................................................................................................................6
1.5.1
Symbols and warnings............................................................................................................................6
1.5.2
Name plate for EBS852 electronic unit...................................................................................................7
1.5.3
Name plate for EBS862 electronic unit...................................................................................................8
1.6
Operator liability .............................................................................................................................................9
1.7
Personnel qualification ...................................................................................................................................9
1.8
Returning devices...........................................................................................................................................9
1.9
Disposal........................................................................................................................................................10
1.9.1
Information on WEEE directive 2002/96/EC (Waste Electrical and Electronic Equipment) .................10
1.10 Transport safety information ........................................................................................................................10
1.11 Storage conditions........................................................................................................................................10
1.12 Installation safety information.......................................................................................................................11
1.13 Electrical installation safety information .......................................................................................................11
1.14 Operating safety information ........................................................................................................................11
2
Explosion-protection safety precautions........................................................................................................12
2.1
Operation via frequency transformer............................................................................................................12
2.2
Using the engineering software Save & Restore and ECOM688 ................................................................12
3
Design and function..........................................................................................................................................13
3.1
Modules........................................................................................................................................................14
3.1.1
EBS852 .................................................................................................................................................14
3.1.2
EBS862 .................................................................................................................................................15
4
Installation..........................................................................................................................................................16
4.1
EBS852 ........................................................................................................................................................16
4.2
EBS862 ........................................................................................................................................................17
5
Electrical connection ........................................................................................................................................18
5.1
Actuator assignment and cable cross-sections............................................................................................19
5.1.1
Rotary actuators....................................................................................................................................19
5.1.2
Linear actuators ....................................................................................................................................19
5.2
Cable shield..................................................................................................................................................20
5.2.1
Signal part .............................................................................................................................................20
5.3
Terminal connection diagrams .....................................................................................................................21
5.3.1
Power Electronic Unit EBS852 (Contrac) / EBS862 (Contrac).............................................................21
5.4
Fuses............................................................................................................................................................22
5.4.1
EBS852 .................................................................................................................................................22
EBS852, EBS862 (Contrac)
42/68-831-EN
5.4.2
EBS862 .................................................................................................................................................22
5.4.3
External fuse for EBS862......................................................................................................................22
5.5
Connection elements....................................................................................................................................23
5.5.1
EBS852 .................................................................................................................................................23
5.6
EBS862 ........................................................................................................................................................24
5.7
Cable guide ..................................................................................................................................................25
5.8
Mains distribution .........................................................................................................................................26
5.9
Cable routing in the connector .....................................................................................................................26
6
Local operation..................................................................................................................................................27
6.1
General information on operation.................................................................................................................27
6.2
Operating elements of the service field (ISF)...............................................................................................28
7
Commissioning and service field (ISF) ...........................................................................................................29
7.1
Typical commissioning with the service field (ISF) ......................................................................................29
7.1.1
Status ....................................................................................................................................................29
7.1.2
"Device setup" operating mode.............................................................................................................29
7.1.3
Setup via user interface ........................................................................................................................29
7.1.4
Defining the initial position (0% or 100%) .............................................................................................30
7.1.5
Defining the second position (0% or 100%)..........................................................................................30
7.1.6
Saving your settings..............................................................................................................................30
7.1.7
Correcting your settings ........................................................................................................................31
8
Alarms / Errors...................................................................................................................................................32
8.1
Definition ......................................................................................................................................................32
8.1.1
Alarms ...................................................................................................................................................32
8.1.2
Error ......................................................................................................................................................32
8.2
Alarm diagram..............................................................................................................................................33
8.3
Error diagram ...............................................................................................................................................34
9
Trouble shooting ...............................................................................................................................................35
10 Technical data....................................................................................................................................................36
10.1 General information......................................................................................................................................36
10.2 Technical data for the EBS852 ....................................................................................................................36
10.3 Technical data for the EBS862 ....................................................................................................................37
11 Appendix ............................................................................................................................................................38
11.1 Permits and certifications .............................................................................................................................38
12 Index ...................................................................................................................................................................40
EBS852, EBS862 (Contrac)
5
Pos: 4.1 /Überschriften/1/S - U/Sicherheit @ 0\mod_1129703894050_3101.doc @ 3168
1
Safety
Pos: 4.2 /Sicherheit/Allgemein/Organisatorische Maßnahmen/Hinweise zur Verwendung der Betriebsanleitung @ 18\mod_1203689776329_3101.doc @ 164715
Read these operating instructions carefully prior to installing and commissioning the device.
These instructions are intended as an overview and do not contain detailed information on all
designs for this product or every possible aspect of installation, operation and maintenance.
For additional information or in case specific problems occur that are not discussed adequately
in these instructions, contact the manufacturer. The content of these instructions is neither part
of any previous or existing agreement, promise or legal relationship nor is it intended to change
the same.
All obligations of ABB Automation Products GmbH are created by the relevant sales agreement,
which contains the complete and solely binding warranty regulations. These contractual
warranty provisions are neither extended nor limited by compliance with this manual.
Pos: 4.3 /Sicherheit/Allgemein/Allgemeines zur Sicherheit @ 0\mod_1129703939516_3101.doc @ 3260
1.1
General Safety Information
The “Safety” chapter provides an overview of the safety aspects to be observed for the
operation of the device.
The device is built based on state-of-the-art technology and is operationally safe. It was tested
and left the factory in a proper state. The requirements in the manual as well as the
documentation and certificates must be observed and followed in order to maintain this state for
the period of operation.
The general safety requirements must be complied with completely during operation of the
device. In addition to the general information, the individual chapters of the manual contain
descriptions about processes or procedural instructions with specific safety information.
Only the observance of all safety information enables the optimal protection of personnel as well
as the environment from hazards and the safe and trouble-free operation of the device.
Pos: 4.4 /Überschriften/1.1/1-spaltig/A - C/Bestimmungsgemäße Verwendung @ 1\mod_1147675805609_3101.doc @ 10755
1.2
Proper use
Pos: 4.5 /Sicherheit/Aktorik/Leistungselektroniken/EBS852, EBS862/Bestimmungsgemäße Verwendung @ 20\mod_1209021994812_3101.doc @ 182162
The EBS852 and EBS862 type power electronic units interconnected as illustrated in these
operating instructions are used exclusively to control RHDE... or RSDE... series electrical
actuators. Using these actuators for any other purpose will introduce a risk of personal injury
and can also damage or impair the device's operational reliability.
Pos: 4.6 /Sicherheit/Allgemein/Hinweis zur bestimmungswidrigren Verwendung (Wartung/Reparatur) @ 0\mod_1129707002440_3101.doc @ 3240
Repairs, alterations and enhancements or the installation of replacement parts is only
permissible as far as described in the manual. Further actions must be verified with ABB
Automation Products GmbH. Excluded from this are repairs performed by ABB-authorized
specialist shops.
Pos: 4.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 4.8 /Sicherheit/Allgemein/Technische Grenzwerte BA @ 0\mod_1140156564953_3101.doc @ 3252
1.3
Technical limits
The device is designed for use exclusively within the stated values on the name plate and in the
technical specifications (see "Technical Specifications” chapter and data sheet). These must be
complied with accordingly, e.g.:
• The maximum operating temperature may not be exceeded.
• The permitted operating temperature may not be exceeded.
• The housing protection system must be observed.
Pos: 4.9 /Sicherheit/Allgemein/Gewährleistungsbestimmungen @ 0\mod_1129706207246_3101.doc @ 3261
1.4
Warranty provision
A use contrary to the device’s stipulated use, disregarding of this manual, the use of under-
qualified personnel as well as unauthorized alterations excludes the manufacturer of liability
from any resulting damages. The manufacturer’s warranty expires.
Pos: 4.10 /Überschriften/1.1/1-spaltig/S - U/Schilder und Symbole @ 0\mod_1129721947139_3101.doc @ 3204
1.5
Labels and symbols
Pos: 4.11 /Überschriften/1.1.1/1-spaltig/Symbole und Signalwörter @ 20\mod_1208422698260_3101.doc @ 180868
1.5.1
Symbols and warnings
Pos: 4.12 /Sicherheit/Allgemein/Symbole und Signalwörter @ 20\mod_1208422453167_3101.doc @ 180843
Danger –
One of these symbols in conjunction with the “Danger“ warning indicates an imminent danger.
If it is not avoided, death or serious injury will result.
Warning –
The symbol in conjunction with the “Warning“ message indicates a possibly dangerous
situation. If it is not avoided, death or serious injury could result.
Caution –
The symbol in conjunction with the “Caution“ message indicates a possibly dangerous
situation. If it is not avoided, slight or minor injury can result. May also be used for property
damage warnings.
Notice –
The symbol indicates a possibly damaging situation. If it is not avoided, the product or
something in its area can be damaged.
Important
The symbol indicates operator tips or especially useful information. This is not a message for a
dangerous or damaging situation.
Pos: 4.13 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
7
Pos: 4.14 /Sicherheit/Aktorik/Leistungselektroniken/EBS852, EBS862/Typenschild der Elektronik EBS852 @ 21\mod_1214401545343_3101.doc @ 203403
1.5.2
Name plate for EBS852 electronic unit
1.5.2.1
Name plate for hardware description
Fig. 1
1 Electronic unit type
2 Unit no. / No. of the non-list version
3 Permissible voltage range / Year of
manufacture
4 Permissible line frequency / Max. power
consumption
5 Permissible ambient temperature /
Protection class
6 Specifications for external fuse protection
1.5.2.2
Name plate for software description
1
Für / For
Antrieb / Actuator
2
Nennwerte / Rated Values
M=
3
4
F-Nr. / No.
5
Software Version
6
NL.
°/s=
M00361
Fig. 2
1 Associated actuator
2 Number of the non-list version
3 Installed software version
4 Set force (torque) / Set speed
5 Blank for customer-specific entry
Pos: 4.15 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 4.16 /Sicherheit/Aktorik/Leistungselektroniken/Allgemein/Typenschild der Elektronik EBS862 @ 20\mod_1209028212734_3101.doc @ 182210
1.5.3
Name plate for EBS862 electronic unit
The name plates for the power electronic unit are located on the lower section (mains
connection) as well as on the cover (electronic unit and software). Since the modules are stand-
alone units, order numbers may vary.
1.5.3.1
Name plate on the lower section of the electronic unit
Fig. 3
1 Electronic unit type
2 Unit no. / No. of the non-list version
3 Permissible voltage range / Year of
manufacture
4 Permissible line frequency / Max. power
consumption
5 Permissible ambient temperature /
Protection class
6 Specifications for external fuse protection
1.5.3.2
Name plate on electronic unit cover
Fig. 4
1 Associated actuator
2 Unit no. / No. of the non-list version
3 Year of manufacture
4 Permissible ambient temperature / Protection class
EBS852, EBS862 (Contrac)
9
1.5.3.3
Name plate for software description
1
Für / For
Antrieb / Actuator
2
Nennwerte / Rated Values
M=
3
4
F-Nr. / No.
5
Software Version
6
NL.
°/s=
M00361
Fig. 5
1 Associated actuator
2 Number of the non-list version
3 Installed software version
4 Set force (torque) / Set speed
5 Blank for customer-specific entry
Pos: 4.17 /Sicherheit/Aktorik/Allgemein/Pflichten des Betreibers @ 10\mod_1181723170562_3101.doc @ 105157
1.6
Operator liability
The operators must strictly observe the applicable national regulations in their countries with
regards to installation, function tests, repairs, and maintenance of electrical devices.
Pos: 4.18 /Sicherheit/Allgemein/Organisatorische Maßnahmen/Qualifikation des Personals @ 0\mod_1129728800194_3101.doc @ 3247
1.7
Personnel qualification
The installation, commissioning and maintenance of the device may only be carried out through
trained specialist personell authorized by the plant operator. The specialist personnel must have
read and understood the manual and comply with its instructions.
Pos: 4.19 /Sicherheit/Allgemein/Organisatorische Maßnahmen/Rücksendung von Geräten @ 0\mod_1129730744499_3101.doc @ 3248
1.8
Returning devices
Use the original packaging or a suitably secure packaging for returning the device for repair or
for recalibration. Include the properly filled out return form (see attachment) with the device.
According to EC guidelines for hazardous materials, the owner of hazardous waste is
responsible for its disposal or must observe the following regulations for its shipping:
All delivered devices to ABB Automation Products GmbH must be free from any hazardous
materials (acids, alkali, solvents, etc.).
Pos: 4.20 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 4.21 /Sicherheit/Allgemein/Organisatorische Maßnahmen/Entsorgung @ 10\mod_1176447410937_3101.doc @ 81544
1.9
Disposal
ABB Automation Products GmbH actively promotes environmental consciousness and has an
operational
management
system
in
accordance
with
DIN
EN
ISO
9001:2000,
EN ISO 14001:2004 and OHSAS 18001. Our products and solutions should have minimum
impact on the environment and persons during manufacture, storage, transport, use and
disposal.
This includes the environmentally friendly use of natural resources. Through its publications
ABB conducts an open dialog with the public.
This product/solution is manufactured from materials that can be reused by specialized
recycling companies.
1.9.1
Information on WEEE directive 2002/96/EC (Waste Electrical and Electronic Equipment)
This product/solution is not subject to the WEEE directive 2002/96/EC and relevant national
laws (e.g., ElektroG in Germany).
Dispose of the product/solution directly in a specialized recycling facility and do not use the
municipal garbage. Only privately used products may be disposed of in the municipal garbage
according to the WEEE directive 2002/96/EC. Proper disposal prevents negative effects on
people and the environment, and supports the reuse of valuable raw materials.
If it is not possible to dispose of old equipment properly, ABB Service can accept and dispose of
returns for a fee.
Pos: 4.22 /Überschriften/1.1/1-spaltig/S - U/Sicherheitshinweise zum Transport @ 0\mod_1140166475703_3101.doc @ 3206
1.10 Transport safety information
Pos: 4.23 /Transport/Allgemein/Prüfung @ 0\mod_1129815371197_3101.doc @ 3317
Check the devices for possible damage that may have occurred during transport. Damages in
transit must be recorded on the transport documents. All claims for damages must be claimed
without delay against the shipper and before the installation.
Pos: 4.24 /Überschriften/1.1/1-spaltig/J - L/Lagerbedingungen @ 8\mod_1176907016921_3101.doc @ 84229
1.11 Storage conditions
Pos: 4.25 /Sicherheit/Aktorik/Leistungselektroniken/EBS852, EBS862/Lagerbedingungen @ 20\mod_1211955133656_3101.doc @ 196383
The power electronic units EBS852, EBS862 (Contrac) have an enclosure rating of IP 20. They
must be stored as appropriate for this protection class. Condensation is not permitted.
Moisture content must not exceed an annual average of 75 %.
The permissible storage and transport temperatures must be observed.
If you intend to store or transport the device for a prolonged period, we recommend that you
wrap it in plastic film and add desiccant. Check that the desiccant is still active on a regular
basis.
Pos: 4.26 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
11
Pos: 4.27 /Überschriften/1.1/1-spaltig/S - U/Sicherheitshinweise zur Montage @ 0\mod_1140166528109_3101.doc @ 3208
1.12 Installation safety information
Pos: 4.28 /Sicherheit/Aktorik/Leistungselektroniken/Allgemein/Sicherheitshinweise zur Montage @ 13\mod_1191936460078_3101.doc @ 129206
• Only qualified specialists who have been trained for these tasks are authorized to mount and
adjust the control actuator, and to make the electrical connection.
• When working on the actuator itself or the electronics always observe the locally valid
accident prevention regulations and the regulations concerning the construction of technical
installations.
• Switch off the supply voltage and protect against unintentional startup.
Pos: 4.29 /Überschriften/1.1/1-spaltig/S - U/Sicherheitshinweise zur elektrischen Installation @ 0\mod_1140166567843_3101.doc @ 3207
1.13 Electrical installation safety information
Pos: 4.30 /Sicherheit/Allgemein/Sicherheitshinweise zur elektrischen Installation @ 13\mod_1191930430247_3101.doc @ 128893
The electrical connection may only be performed by authorized specialist personnel according
to the electrical plans.
Comply with electrical connection information in the manual. Otherwise, the electrical protection
class can be affected.
The secure separation of contact-dangerous electrical circuits is only guaranteed when the
connected devices fulfill the requirements of the DIN EN 61140 (VDE 0140 Part 1) (basic
requirements for secure separation).
For secure separation, run the supply lines separated from contact-dangerous electrical circuits
or additionally insulate them.
Pos: 4.31 /Überschriften/1.1/1-spaltig/S - U/Sicherheitshinweise zum Betrieb @ 0\mod_1140166424437_3101.doc @ 3205
1.14 Operating safety information
Pos: 4.32 /Sicherheit/Aktorik/Leistungselektroniken/Allgemein/Sicherheitshinweise zum Betrieb @ 13\mod_1191936932187_3101.doc @ 129254
Before switching on, ensure that the specified environmental conditions in the “Technical
Specifications” chapter or data sheet are complied with and that the power supply voltage
corresponds with the voltage of the electronic unit.
When there is a chance that safe operation is no longer possible, put the device out of operation
and secure against unintended operation.
When mounting the power electronic unit in areas that may be accessed by unauthorized
persons, take the required protective measures.
Pos: 5 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Explosion-protection safety precautions
12
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 6.1 /Überschriften/1/D - F/Ex-technische Sicherheitshinweise @ 9\mod_1181416415484_3101.doc @ 102826
2
Explosion-protection safety precautions
Pos: 6.2 /Überschriften/1.1/1-spaltig/A - C/Betrieb am Frequenzumformer @ 10\mod_1181565595390_3101.doc @ 102922
2.1
Operation via frequency transformer
Pos: 6.3 /Ex-technische Sicherheitshinweise/Aktorik/Antriebe/Allgemein/Betrieb am Frequenzumformer @ 9\mod_1181416045984_3101.doc @ 102803
• The frequency converter (electronic unit) may not installed or used within the hazardous
area.
• Check whether the electronic unit is loaded with the parameters of the actuator it is
connected to.
• Check the electronic unit for proper connection to the correct actuator.
• Setpoint monitoring is activated as default setting when the electronic unit leaves the
manufacturer. Do not de-activate this setting.
• Rapid traverse mode is not allowed on Ex actuators, and the feature cannot be activated
from the user interface.
• The Contrac power electronic unit must be upstream from the motor temperature monitoring
unit SD241-B or similar, certified tripping unit.
Pos: 6.4 /Überschriften/1.1/1-spaltig/A - C/Benutzung der Engineering-Software Save & Restore und ECOM688 @ 17\mod_1199701584187_3101.doc @ 149819
2.2
Using the engineering software Save & Restore and ECOM688
Pos: 6.5 /Ex-technische Sicherheitshinweise/Aktorik/Antriebe/Leistungselektroniken/Benutzung der Engineering Software @ 17\mod_1199701466453_3101.doc @ 149796
Reinstalling the electronic unit software or individual data sections with the engineering software
Save & Restore or ECOM688 may only be performed in compliance with the relevant basic
conditions. It must be ensured, specifically, that the data record imported belongs to the
actuator type. After importing a data record, always check that all parameters for the application
such as speed and torque/force are configured accordingly.
Downdating the actuator operating system (UAPM software version) is not permitted.
Refer to the valid operating instructions for the engineering software ECOM688. The operating
instructions are available for download on the internet.
Pos: 7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Design and function
42/68-831-EN
EBS852, EBS862 (Contrac)
13
Pos: 8.1 /Überschriften/1/A - C/Aufbau und Funktion @ 0\mod_1129797620733_3101.doc @ 3140
3
Design and function
Pos: 8.2 /Aufbau und Funktion/Aktorik/Leistungselektroniken/Allgemein/Ex-Konzept Grafik @ 13\mod_1191847969015_3101.doc @ 128138
Fig. 6: Ex design
Pos: 8.3 /Aufbau und Funktion/Aktorik/Leistungselektroniken/EBS852, EBS862/Funktionsprinzip @ 20\mod_1209029706921_3101.doc @ 182290
Functionality
The electronic units for the Contrac RHDE... and RSDE... series actuators are available in two
sizes for rack mounting. Special parameters can be used to adapt the electronic units to the
type of actuator concerned. The electronic units EBS852, EBS862 (Contrac) are the interface
between actuator / valves and fittings and process control system.
The actuators / valves and fittings are positioned continuously, whatever the type of input signal
(analog or digital). During continuous positioning the motor torque is varied steplessly until the
actuator force and the restoring process forces are balanced.
High positioning accuracy combined with excellent control quality and a long actuator life can
even be achieved under varying load conditions and with short stroke times.
Pos: 8.4 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Design and function
14
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 8.5 /Überschriften/1.1/1-spaltig/A - C/Baugruppen @ 13\mod_1191919723796_3101.doc @ 128776
3.1
Modules
Pos: 8.6 /Aufbau und Funktion/Aktorik/Leistungselektroniken/EBS852, EBS862/Baugruppen EBS852 @ 20\mod_1209124480359_3101.doc @ 182707
3.1.1
EBS852
Fig. 7: EBS852
1 Commissioning and service field (ISF)
2 Transformer
3 Cover for connection space
4 Cable clamps
Fig. 8: EBS852 connection space
1 Commissioning and service field (ISF)
2 Terminals for signal inputs and outputs
3 Terminals for motor connection
4 Mains connection
Pos: 8.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Design and function
42/68-831-EN
EBS852, EBS862 (Contrac)
15
Pos: 8.8 /Aufbau und Funktion/Aktorik/Leistungselektroniken/Allgemein/Baugruppen EBS862 @ 20\mod_1209124473421_3101.doc @ 182683
3.1.2
EBS862
Fig. 9: EBS862
1 Electronic unit, lower section
2 Electronic unit cover
3 Cover for connection space
4 Holes for cable glands
4
5
6
2
1
3
M00355
Fig. 10: EBS862 connection space
1 Commissioning and service field (ISF)
2 Hinge screws
3 Cover screws
4 Mains supply terminals
5 Motor terminals
6 Signal terminals
Pos: 9 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 10.1 /Überschriften/1/M - O/Montage @ 0\mod_1140519732218_3101.doc @ 3159
4
Installation
Pos: 10.2 /Montage/Aktorik/Leistungselektroniken/EBS852, EBS862/Allgemein (Ex) @ 13\mod_1191833352312_3101.doc @ 127608
The electronic unit is installed in the vicinity of the drive outside the hazardous area. Screw-type
terminals are used to connect the two modules on the actuator side and on the electronics side.
The connections are made on the drive for the motor in the motor's Ex d connection space and
for the actuating sensor using Ex e terminals in the actuating sensor's connection space.
A voltage trip unit is also required; this too is installed outside the hazardous area.
Pos: 10.3 /Montage/Aktorik/Leistungselektroniken/Allgemein/Installation @ 13\mod_1191836243781_3101.doc @ 127826
Important
Prior to installation or service activities, the electronic unit and actuator must be disconnected
from the power supply and secured to prevent unintentional startup.
• It must also be possible to disconnect the electronic unit and actuator onsite.
• All signal and motor cables between the actuator and electronic unit must be shielded.
• The shielding must be placed on both housings when connecting the electronic unit and
the actuator.
Pos: 10.4 /Überschriften/1.1/1-spaltig/D - F/EBS852 @ 20\mod_1209539151875_0.doc @ 183041
4.1
EBS852
Pos: 10.5 /Montage/Aktorik/Leistungselektroniken/EBS852, EBS862/Montage EAS822 / EBS852 @ 20\mod_1209538619812_3101.doc @ 183017
1. Mount the module on the rack's vertical mounting rail with screws of property class 8.8
(tensile strength 800 N/mm2 (116032 pounds/square inch), 640 N/mm2
(92826 pounds/square inch).
2. Provide adequate room for installation and make sure the actuator is accessible from all
sides.
3. Cable entries point to the right.
4. Remove the cover from the connection space (Fig. 7, item 3).
5. Insert the cable into the cable entry and make the connection as shown on the
connection diagram.
6. Check that the cable connections are properly seated, tighten the shield clamp, and
replace the cover.
Pos: 10.6 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
17
Pos: 10.7 /Überschriften/1.1/1-spaltig/D - F/EBS862 @ 20\mod_1209539217203_0.doc @ 183087
4.2
EBS862
Pos: 10.8 /Montage/Aktorik/Leistungselektroniken/EBS852, EBS862/Montage EBS862 @ 20\mod_1209538487843_3101.doc @ 182993
Important
The total weight of the EBS862 electronic unit is 40 kg (88 lbs). For this reason, the electronic
unit is equipped with a load-bearing eyelet. If, for technical reasons, the load-bearing eyelet
cannot be used, the two halves of the housing can be installed separately.
Deinstallation the housing halves
1. Place the electronic unit on a horizontal surface.
2. Unscrew and remove the cover screws (Fig. 10, item 3).
3. Open the electronic unit.
4. Disconnect the internal plug connection between the housing halves.
5. Close the housing halves.
6. Unscrew and remove the hinge screw (Fig. 10, item 2).
7. Fold the front section forward while lifting it up and off the hinge pins. The cover of the
electronic unit must be positioned in exactly the right place.
Mounting the housing halves
1. Set the housing halves down on the hinge pins and insert the screw into the upper pin.
The cover of the electronic unit must be positioned in exactly the right place.
2. Restore the internal plug connection.
3. Close the housing, insert the cover screws (Fig. 10, item 3), and connect the cable.
Mounting
1. Mount the module on the rack's vertical mounting rail with screws of property class 8.8
(tensile strength 800 N/mm2 (116032 pounds/square inch), yield strength 640 N/mm2
(92826 pounds/square inch).
2. Provide adequate room for installation and make sure the actuator is accessible from all
sides.
3. The cable glands point down.
4. Remove the cover from the connection space (Fig. 9, item 3).
5. Insert the cable into the cable gland and make the connection as shown on the
connection diagram.
6. Check that the cable connections are properly seated, tighten the cable gland, and
replace the cover.
Pos: 11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 12.1 /Überschriften/1/D - F/Elektrischer Anschluss @ 0\mod_1140620471687_3101.doc @ 3143
5
Electrical connection
Pos: 12.2 /Elektrischer Anschluss/Aktorik/Allgemein/Elektrischer Anschluss Ex @ 10\mod_1181658330812_3101.doc @ 104606
Each actuator requires a Contrac electronic unit which is loaded with the type specific-software.
Carefully consider the instructions for the electronic unit and compare the data labels of the
actuator and the electronic unit in order to ensure a proper hard- and software assignment.
Instructions regarding use in Ex applications
The electrical connection between the Contrac electronic unit and the Contrac actuator can be
established using the cable set (order code 695). The cable harness is not part of the Ex
prototype test certificate and must therefore be tested for safety-relevant functionality within
the complete installation by the installer or operator.
Consider the following issues:
• Consider the local regulation concerning the setup of electrical devices within hazardous
areas. This applies particularly to EN 60079-14 for the setup of the screen and the
potential compensation between the actuator, the electronic unit and the motor protection
unit (see 1) in chapter “Cable shield“, page 20 and chapter “Terminal connection
diagrams“, page 21 ff.
• For the connection of the motor and the position transmitter only use ATEX certified EEx
e cable glands with IP 66 acc. to EN 50019.
• Use a cable socket or a solid wire, bended to a "U", to connect the motor cable.
• Ensure a proper strain relief for all cable connections.
• Protect all cables in the connections chambers against contact with metal components.
Ensure a gap of at least 6 mm (0.24 inch) between all conductive components.
• Remove the desiccant in motor and position sensor.
• Do not change the factory-set position of the motor terminal chamber.
• Seal all not used cable entries with ATEX certified IP 66 plugs.
• Use a certified cut-off unit for the thermal motor monitoring. Permitted units are, e.g.:
- ABB motor temperature monitoring unit SD241-B.
- 3 RN 1011-1 CK 00 , Ex II (2) GD , PTB 01 ATEX 3218, Siemens
Pos: 12.3 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
19
Pos: 12.4 /Überschriften/1.1/1-spaltig/A - C/Antriebszuordnung und Leitungsquerschnitte @ 20\mod_1209547381234_3101.doc @ 183167
5.1
Actuator assignment and cable cross-sections
Pos: 12.5 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Antriebszuordnung/Leitungsquerschnitte Schwenkantriebe Ex @ 20\mod_1209543500093_3101.doc @ 183110
5.1.1
Rotary actuators
Max. current
consumption
1)
Motor cable cross-section / Permissible cable length in
m (ft)
2)
Electronic
unit
Average power
loss of the
electronic unit
115 V
230 V
Actuator
1.5 mm
2
(16 AWG)
2.5 mm
2
(14 AWG)
4 mm
2
(12 AWG)
6 mm
2
(10 AWG)
10 mm
2
(8 AWG)
60 W
1.8 A
0.9 A
RHDE250-10
75 W
2.2 A
1.1 A
RHDE500-10
60 W
5.0 A
2.5 A
RHDE800-10
80 W
5.0 A
2.5 A
RHDE1250-12
80 W
5.0 A
2.5 A
RHDE2500-25
80 W
5.8 A
2.7 A
RHDE4000-40
EBS852
80 W
5.0 A
2.5 A
RHDE8000-80
80 W
-
5.3 A
RHDE2500-10
270
(866)
460
(1476)
-
-
-
100 W
-
10.0 A
RHDE4000-10
160
(513)
270
(866)
430
(1380)
-
-
115 W
-
8.0 A
RHDE8000-15
EBS862
On request
-
12.5 A
RHDE16000-30
70
(225)
120
(385)
190
(610)
280
(898)
460
(1476)
1) At actuator rated power. Current consumption in positioning mode approx. 40 ... 50 % of lmax in each case.
2) Cable length between electronic unit and actuator. Signal cable cross-section 0.5 mm2 (20 AWG).
Pos: 12.6 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Antriebszuordnung/Leitungsquerschnitte Linearantriebe Ex @ 20\mod_1209546356437_3101.doc @ 183143
5.1.2
Linear actuators
Max. current
consumption
1)
Motor cable cross-section / Permissible cable length in
m (ft)
2)
Electronic
unit
Average power
loss of the
electronic unit
115 V
230 V
Actuator
1.5 mm
2
(16 AWG)
2.5 mm
2
(14 AWG)
4 mm
2
(12 AWG)
6 mm
2
(10 AWG)
10 mm
2
(8 AWG)
55 W
2.2 A
1.1 A
RSDE10-5.0
60 W
3.6 A
1.8 A
RSDE10-10,0
60 W
3.6 A
1.8 A
RSDE20-5.0
75 W
4.8 A
2.4 A
RSDE20-7.5
EBS852
75 W
5.0 A
2.5 A
RSDE50-3.0
270
(866)
460
(1476)
-
-
-
EBS862
100 W
-
6.4 A
RSDE50-10.0
160
(513)
270
(866)
430
(1380)
-
-
1) At actuator rated power. Current consumption in positioning mode approx. 40 ... 50 % of lmax in each case.
2) Cable length between electronic unit and actuator. Signal cable cross-section 0.5 mm2 (20 AWG).
Pos: 12.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 12.8 /Überschriften/1.1/1-spaltig/J - L/Kabelschirm @ 10\mod_1181823716656_3101.doc @ 106187
5.2
Cable shield
Pos: 12.9 /Überschriften/1.1.1/1-spaltig/Signalteil @ 10\mod_1182501083765_3101.doc @ 108573
5.2.1
Signal part
Pos: 12.10 /Elektrischer Anschluss/Aktorik/Antriebe/Allgemein/Kabelschirm Anschluss @ 10\mod_1181823021906_3101.doc @ 106144
Fig. 11: Fitting the shield
1. Remove approx. 2 cm of cable sheathing (3) from the end of the cable.
2. Separate the shield and peel it back to its inner sheathing (4).
3. Push the cable through the cable gland and fasten with clamp (1).
4. Make sure that the shielding is touching the clamp and the electronic unit housing (2).
Pos: 12.11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
21
Pos: 12.12 /Überschriften/1.1/1-spaltig/A - C/Anschlusspläne @ 0\mod_1139844727625_3101.doc @ 3179
5.3
Terminal connection diagrams
Pos: 12.13 /Überschriften/1.1.1/1-spaltig/Leistungselektronik EBS852 (Contrac) / EBS862 (Contrac) @ 10\mod_1182165403125_3101.doc @ 107553
5.3.1
Power Electronic Unit EBS852 (Contrac) / EBS862 (Contrac)
Pos: 12.14 /Elektrischer Anschluss/Aktorik/Allgemein/Elektrischer Anschluss Leistungselektronik EBS852 / EBS862 (EX) @ 10\mod_1182165726453_3101.doc @ 107622
Important
The electrical connection is provided by terminals on the actuator and on the electronic unit.
Fig. 12: Electrical connection: Ex actuator analog / digital
Important
* For separate heat supply, protect the heater with 2 … max. 6 A medium time-lag fuses (e.g., Neozed D01CE14).
Pos: 12.15 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Hinweis 1) Potenzialausgleich @ 14\mod_1194425809156_3101.doc @ 136747
Important
For more information regarding footnote 1) see chapter Electrical connection, page 18.
Pos: 12.16 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 12.17 /Überschriften/1.1/1-spaltig/S - U/Sicherungen @ 7\mod_1171889493187_3101.doc @ 68659
5.4
Fuses
Pos: 12.18 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Sicherungen EBS852 @ 20\mod_1209040594296_3101.doc @ 182507
5.4.1
EBS852
Type
Installation location
UV=115 V
UV=230 V
Backup fuse
External
16 A; time-lag
Mains fuse
F1, in connection space
12.5 A; time-
lag
10 A; time-lag
Relay fuse for DO1, DO2,
DO3
F2 ... F4, in connection space
3 x 0.2 A, medium time-lag
Brake fuse
on printed board (power
section)
0.315 A; medium time-lag
DC link fuse
Power board
10 A, super fast-acting
Pos: 12.19 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Sicherungen EBS862 @ 20\mod_1209041142140_3101.doc @ 182530
5.4.2
EBS862
Type
Installation location
UV=230 V
Backup fuse
External
35 A safety fuse 1)
16 A thermal circuit breaker
Relay fuse for DO1, DO2,
DO3
F2 ... F4, in connection space
3 x 0.2 A, medium time-lag
Brake fuse
on printed board (power
section)
0.315 A; medium time-lag
DC link fuse
Power board
15 A; medium time-lag
1) The 35 A safety fuse and the 16 A thermal circuit breaker are included in the delivery scope. The cable cross-section
between the fuse and the electronic unit must be a minimum of 2.5 mm2 (14 AWG).
Pos: 12.20 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Externe Sicherung für EBS862 @ 20\mod_1209039982171_3101.doc @ 182483
5.4.3
External fuse for EBS862
In addition to the internal fuses, the EBS862 power electronic unit needs two other external
fuses, which are delivered separately with the module.
They ensure the safe operation of the EBS862 power electronic under the special starting
conditions.
Important
The cable cross-section between the fuse and the electronic unit must be a minimum of 2.5
mm².
1
2
M00356
Fig. 13
1 External fuse: 35 A
2 External fuse: 16 A
EBS852, EBS862 (Contrac)
23
N
L
PE
35 A
16 A ( )
�
AC 230 V 1~
M00357
Fig. 14
Pos: 12.21 /Überschriften/1.1/1-spaltig/A - C/Anschlusselemente @ 20\mod_1209459742906_3101.doc @ 182825
5.5
Connection elements
Pos: 12.22 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Anschlusselemente EBS852 @ 20\mod_1209042755218_3101.doc @ 182554
t
5.5.1
EBS852
Fig. 15
1 Commissioning and service field (ISF)
2 Signal
3 Motor
4 Mains
5 Terminal
6 Plug
Pos: 12.23 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 12.24 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Anschlusselemente EBS862 @ 20\mod_1209044861125_3101.doc @ 182577
t
5.6
EBS862
Fig. 16
1 Commissioning and service field (ISF)
2 Terminals for mains connection
3 Mains cable
4 Plug for motor cable
5 Motor cable
6 Signal cable
7 Plug for signal cable
Pos: 12.25 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
25
Pos: 12.26 /Überschriften/1.1/1-spaltig/J - L/Kabelführung @ 20\mod_1209463136718_3101.doc @ 182848
5.7
Cable guide
Pos: 12.27 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Kabelführung im Trägergestell @ 20\mod_1209463199906_3101.doc @ 182871
Fig. 17: Cable guide in rack
1 Electronic module
2 Thermally conductive plate
3 Mains distribution
Pos: 12.28 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Kabelführung im Trägergestell (Draufsicht) @ 20\mod_1209468813468_3101.doc @ 182894
Fig. 18: Cable guide and electronic unit mounted in rack (view from above)
1 Front
Pos: 12.29 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 12.30 /Überschriften/1.1/1-spaltig/M - O/Netzverteilung @ 20\mod_1209469245406_3101.doc @ 182940
5.8
Mains distribution
Pos: 12.31 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Netzverteilung @ 20\mod_1209469028859_3101.doc @ 182917
Fig. 19: Mains distribution for Contrac electronic unit in rack
1 Electronic unit
2 max. 16 mm2 (6 AWG)
Pos: 12.32 /Überschriften/1.1/1-spaltig/J - L/Kabelführung im Stecker @ 16\mod_1197963296437_3101.doc @ 145945
5.9
Cable routing in the connector
Pos: 12.33 /Elektrischer Anschluss/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Kabelführung im Stecker @ 20\mod_1210080092328_3101.doc @ 183398
To prevent interference from electromagnetic fields, the signal and power cables in the
connector housing must be routed and connected separately. A metal divider separates the two
cable areas inside the connector. Attach the shielding as shown in Fig. 20.
1
2
3
4
5
M00364
Fig. 20
1 Power cable
2 Signal cable
3 Shield
4 Separator
5 Shield
Pos: 13 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
27
Pos: 14.1 /Überschriften/1/J - L/Lokale Bedienung @ 1\mod_1144311291828_3101.doc @ 5751
6
Local operation
Pos: 14.2 /Überschriften/1.1/1-spaltig/A - C/Allgemeine Informationen zur Bedienung @ 7\mod_1167724521984_3101.doc @ 53616
6.1
General information on operation
Pos: 14.3 /Konfiguration, Parametrierung/Aktorik/Allgemein/Lokale Bedienung/Allgemeine Informationen zur Bedienung @ 7\mod_1166523369281_3101.doc @ 53108
The basic settings "Define end positions" and "Initial diagnosis" can be configured via the
commissioning and service field (ISF). It can be used to adjust the actuator to the working area
and set the direction without using a PC. The actuator can be further parametrized using a
graphic user interface.
Important
The commissioning and service field is located on the electronic unit.
Pos: 14.4 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/EBN853, EBN861/Hinweis ECOM688 @ 17\mod_1199701769718_3101.doc @ 149843
Important
Observe the information about using the engineering software Save & Restore or ECOM688 in
chapter 2.2.
Pos: 14.5 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 14.6 /Überschriften/1.1/1-spaltig/A - C/Bedienelemente des Servicefelds (ISF) @ 7\mod_1167724580593_3101.doc @ 53637
6.2
Operating elements of the service field (ISF)
Pos: 14.7 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Bedienelemente des Servicefelds (ISF) EX @ 13\mod_1191933980187_3101.doc @ 129109
1
2
3
4
5
6
7
8
9
10
M00203
Fig. 21: Commissioning and service field (ISF)
1 Power LED: Displays supply by line
voltage.
2 Accept button (100 %): Press to set the
current position as 100 %; press in
combination with the 4 button to end the
adjustment process.
3 Reset button: Press to restart the
processor and delete any values
assigned positions 0 % and 100 %.
4 Accept button (0 %): Press to set the
current position as 0 %; press in
combination with the 2 button to end the
adjustment process.
5 LED for 0 % position: Depending on the
flash rate, this LED indicates either
adjustment, position saved or error.
6 Write-protection switch (default: ON).
7 RS232 connector: Connection for a PC.
8 Potential switch: Connection of reference
potential either to system or protective
ground (default setting: to system).
9 Travel button: Press to initiate actuator
movement.
10 LED for 100 % position: Depending on
the flash rate, this LED indicates either
adjustment, position saved or error.
Pos: 15 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Commissioning and service field (ISF)
42/68-831-EN
EBS852, EBS862 (Contrac)
29
Pos: 16.1 /Überschriften/1/G - I/Inbetriebnahme und Servicefeld (ISF) @ 5\mod_1167725076390_3101.doc @ 53680
7
Commissioning and service field (ISF)
Pos: 16.2 /Überschriften/1.1/1-spaltig/S - U/Typische Inbetriebnahme mit dem Servicefeld (ISF) @ 7\mod_1167725302531_3101.doc @ 53720
7.1
Typical commissioning with the service field (ISF)
Pos: 16.3 /Konfiguration, Parametrierung/Aktorik/Antriebe/Leistungselektroniken/EBS852, EBS862/Typische Inbetriebnahme mit dem Servicefeld (ISF) EX @ 20\mod_1211783475296_3101.doc @ 195998
Important
The operating range of the actuator is not factory-set. To set the actuator's operating range,
set the write protection switch to "OFF". Once commissioning is complete, set the write
protection switch to "ON".
For information about setting up the mechanical end stops, refer to the operating instructions
for the relevant actuator.
Danger – Serious damage to health / risk to life
Make sure that the actuator can move without posing a risk.
7.1.1
Status
• The electronic unit is connected to the power supply and wired to the actuator.
• Move the write protection switch (6) to the "OFF" position.
• The electronic unit is in "MAN" mode; no signal at digital input 1 (DI 1).
• No error (if an error is pending, the LEDs will flash alternately at 4 Hz).
7.1.2
"Device setup" operating mode
1. Switch the electronic unit to "Device setup" mode. Press and hold down both travel buttons
(9) at the same time for approx. 5 s until both LEDs (items 5 and 10 in Fig. 21) flash in sync
at a rate of 4 Hz.
Important
Once commissioning is complete, set the write protection switch to "ON".
7.1.3
Setup via user interface
Context-sensitive online help can be called at any time via the graphical user interface.
Important
The RS232 communication cable provides a conductive ground connection between the
computer and the Contrac electronic unit. If the PC is grounded, a ground loop may form in the
system.
Commissioning and service field (ISF)
30
EBS852, EBS862 (Contrac)
42/68-831-EN
7.1.4
Defining the initial position (0% or 100%)
2. Use a travel button (9) to move to the desired position.
3. Press the Accept button (2) or (4) to accept the position; if successful, the corresponding
LED will flash at a rate of 1 Hz. The other LED will continue to flash at approx. 4 Hz.
7.1.5
Defining the second position (0% or 100%)
4. Use a button (9) to move to the second position.
5. To accept the position, press the Accept button (2) or (4). If successful, both LEDs(5) and
(10) will flash at a rate of approx. 1 Hz.
7.1.6
Saving your settings
6. Press both Accept buttons (2 + 4) to accept the settings. The LEDs (5 + 10) will stop flashing
after a short period of time to indicate that the setup process is complete.
7. If the range selected for the actuator is too small, both LEDs will start to flash again at 4 Hz
and the setup procedure will have to be repeated with a higher value (min. actuator travel).
(Information regarding actuator travel appears on the name plate.)
Commissioning and service field (ISF)
42/68-831-EN
EBS852, EBS862 (Contrac)
31
7.1.7
Correcting your settings
• If, after accepting the initial value for the settings, you need to make a correction, press the
reset button (3) and repeat the setting procedure.
• If you need to make a correction after saving your settings, you will need to repeat the entire
setup procedure from the beginning.
Function
Signals
Device setup
Switch to Device setup: Press and hold down
both travel buttons for approx. 5 s.
Both LEDs will then flash in sync at 4 Hz.
Approaching an end position: Use the
appropriate button on the ISF.
Both LEDs will continue to flash at 4 Hz during
actuator travel.
Save the initial end position: Press 0% or
100%.
The corresponding LED will flash at approx.
1 Hz, the others will continue to flash at 4 Hz.
Save the second end position: Press 0% or
100%.
The related LED will flash at approx. 1 Hz in
sync with the first LED.
Finish setup: Press 0% and 100% at the same
time.
Both LEDs will light up briefly and then go out.
Operation
Normal operation: MAN / AUT
The LEDs are off.
Positioning via the button on the ISF takes
priority over the control system.
The LEDs are off.
Error (both LEDs flashing alternately at 4 Hz)
Reset: Resets error messages.
If there are no other errors pending, both
LEDs will go out.
Reset if the operating range is overshot:
Press and hold down both travel buttons for 5
s and then press the Reset button.
After approx. 5 s, the LEDs will stop flashing
briefly. Once the reset has been performed,
the electronic unit will be in Setup mode.
Important
After startup, it is recommended that you use the control system to operate the actuator and
check both its response and its signaling behavior.
In order for the actuator to go into automatic mode after startup, there must be a 24 V DC
signal at digital input 1 for actuators with active digital input functions (default setting).
If the digital function is switched off, the actuator will switch to automatic mode immediately on
completion of the setup process.
Pos: 17 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Alarms / Errors
32
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 18.1 /Überschriften/1/A - C/Alarme / Fehler @ 13\mod_1191918058984_3101.doc @ 128661
8
Alarms / Errors
Pos: 18.2 /Überschriften/1.1/1-spaltig/D - F/Definition @ 13\mod_1191918133734_3101.doc @ 128707
8.1
Definition
Pos: 18.3 /Fehlermeldungen/Allgemein/Alarme @ 13\mod_1191907921656_3101.doc @ 128299
8.1.1
Alarms
The actuator or electronic unit is in a critical state (e.g., high temperature), which currently does
not affect the actuator, electronic unit, process or persons. The actuator functions are available.
Previous alarms are stored in the "Saved Alarms" area in the electronic unit. The graphic user
interface use to output the stored alarms.
Pos: 18.4 /Fehlermeldungen/Allgemein/Fehler @ 13\mod_1191908411312_3101.doc @ 128322
8.1.2
Error
The actuator or electronic unit is in a critical state, e.g., positioning time-out, which currently is
impairing the actuator, electronic unit, process or persons. The actuator is switched off and the
actuator functions are no longer available. Previous error messages are stored in the "Saved
Errors" area in the electronic unit. Use the graphic user interface to output the stored errors.
Error messages cannot be reset until the cause of the error has been eliminated.
Pos: 18.5 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Alarms / Errors
42/68-831-EN
EBS852, EBS862 (Contrac)
33
Pos: 18.6 /Überschriften/1.1/1-spaltig/A - C/Alarm Schema @ 13\mod_1191918181968_3101.doc @ 128730
8.2
Alarm diagram
Pos: 18.7 /Fehlermeldungen/Allgemein/Alarm Schema @ 13\mod_1191909106750_3101.doc @ 128345
Setpoint time-out
Transmitter
monitoring
Maintenance
Actuator
temperature
Temperature of
Electronic Unit
upper limit/ lower limit
upper limit/ lower
limit
Lubricant /
Elastom.
Motor / Gear
(high / low)
(high / low)
Monitoring ON
Integr.
controller
ON
Behavior at critical
temp. MAN AUT
&
&
&
&
Actuator Stop
Safety pos. last
setpoint
Actuator
moves in
desired
operating
mode
Alarm Signal
Saved Alarms (Reset
Option)
General Alarm
Display ON
Pos: 18.8 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Alarms / Errors
34
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 18.9 /Überschriften/1.1/1-spaltig/D - F/Fehler Schema @ 13\mod_1191918225828_3101.doc @ 128753
8.3
Error diagram
Pos: 18.10 /Fehlermeldungen/Allgemein/Fehler Schema (2008-06-24 13:47:21) @ 13\mod_1191916378062_3101.doc @ 128588
Positioning time-out
Hardware
Monitoring
Software Monitoring
-
Standstill
-
Min. speed
-
Movement in incorrect
direction
Frequency converter
end positions
Position sensor memory error Flash
error
RAM error
Watchdog monitoring activated
Monitoring ON
&
Error signal
Error message via
actual value ON
&
Saved Failure (Reset
Option)
Analog output
1 ... 3.5 mA with "Low alarm"
21.5 ... 25 mA with "High alarm"
General Failure Display ON
Pos: 18.11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
35
Pos: 18.12 /Überschriften/1/D - F/Fehlerbehebung @ 8\mod_1177421457781_3101.doc @ 86174
9
Trouble shooting
Pos: 18.13 /Fehlermeldungen/Aktorik/Antriebe/Allgemein/Fehlersuche @ 20\mod_1209118101843_3101.doc @ 182650
This chapter only covers hardware-related errors. For additional troubleshooting information,
refer to the online help for the operator interface.
Error
Possible cause
Troubleshooting
Valve cannot be moved by
actuator.
Failure either on the
actuator or the valve (e.g.,
stuffing box tightened too
much).
Disconnect actuator from valve.
If the actuator moves, the valve is
the possible cause.
If the actuator does not move, the
actuator is the possible cause.
Incorrect electronic unit or
incorrect data record.
Compare information on name
plates for actuator and electronic
unit.
Incorrectly configured
electronic unit.
Check/update the settings for the
parametrization software.
No communication with
the control system.
Check wiring.
Incorrect wiring between
actuator and electronic
unit.
Check wiring.
Defective motor/brake.
Check the winding resistance of
the motor and brake.
Check the brake lock.
Binary inputs on the
electronic unit are not
wired.
Make connection.
The actuator does not
respond.
Brake does not release
(no mechanical "click").
Check the brake air gap (approx.
0.25 mm (0.010 inch)) and
electrical connection to the brake.
Check winding resistance of the
brake coil.
Actuator does not run in AUT
mode, although “AUT” is
selected in the user interface.
Digital input 1 (DI1) not
wired.
Make connection.
Check the software settings for
the digital inputs.
LEDs in the commissioning
and service panel (CSP)
flash synchronously.
Actuator is not adjusted
properly.
Adjust actuator.
LEDs flash alternately.
Electronic unit / drive
malfunction.
Malfunction when
approaching the end position.
Actuator in limit range of
positioning sensor.
Drive the actuator beyond the
adjusted end position (either
manually or using the pushbuttons
on the CSP). Disconnect from
valve, if necessary.
Drive the actuator back into the
operating range and connect it to
the valve.
Readjust the actuator for the
operating range.
Pos: 19 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 20.1 /Überschriften/1/S - U/Technische Daten @ 0\mod_1132904574837_3101.doc @ 3169
10 Technical data
Pos: 20.2 /Überschriften/1.1/1-spaltig/A - C/Allgemeine Daten @ 0\mod_1140622753015_3101.doc @ 3177
10.1 General information
Pos: 20.3 /Technische Daten / Datenblatt/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Allgemeine Daten EBS852, EBS862 @ 20\mod_1211783941968_3101.doc @ 196033
Power electronic unit
EBS852 (Contrac)
EBS862 (Contrac)
Protection class
IP 20
Moisture
≤ 75% annual average (condensation not permitted)
Rack air inlet temperature
0 … 45 °C (32 … 110 °F)
Transport and storage temperature
-25 ... 70 °C (-15 ... 158 °F)
Installation position
On vertical support, cable glands pointing to the
right
On vertical support, cable glands pointing down
Coating
2-layer component epoxy (RAL 9005, black)
Electrical connection
Mains supply via terminals; all other connections made via screw-type plug connectors
Weight; approx.
11 kg (24 lb)
40 kg (88 lb)
Pos: 20.4 /Überschriften/1.1/1-spaltig/S - U/Technische Daten EBS852 @ 20\mod_1209030645000_3101.doc @ 182336
10.2 Technical data for the EBS852
Pos: 20.5 /Technische Daten / Datenblatt/Aktorik/Antriebe/Leistungselektroniken/Leistungselektronik EBS852 (Contrac)/Technische Daten EBS852 (Ex) @ 7\mod_1171526417578_3101.doc @ 67454
Supply voltage (standard actuators)
115 V AC (94 … 130 V) or 230 V AC (190 … 260 V); 47.5 … 63 Hz; 1 Ph
Supply voltage
(Ex actuators)
115 V AC (94 … 127 V) or 230 V AC (190 … 253 V); 47.5 … 63 Hz; 1 Ph
lmax. at 115 V
lmax. at 230 V
RHD(E)250-10
1.8 A
0.9 A
RHD(E)500-10
2.2 A
1.1 A
RHD(E)800-10
5.0 A
2.5 A
RHD(E)1250-12
5.0 A
2.5 A
RHD(E)2500-25
5.0 A
2.5 A
RHD(E)4000-40
5.8 A
2.7 A
RHD(E)8000-80
5.0 A
2.5 A
RSD(E)10-5.0
2.2 A
1.1 A
RSD(E)10-10.0
3.6 A
1.8 A
RSD(E)20-5.0
3.6 A
1.8 A
RSD(E)20-7.5
4.8 A
2.4 A
RSD(E)50-3.0
5.0 A
2.5 A
RSD100-1.5
5.0 A
2.5 A
Current at electronic unit [A]
(115 V AC / 230 V AC)
RSD200-0.7
5.0 A
2.5 A
lpos. (115 V + 230 V)
approx. 40 … 50 % of lmax.
External fuse for power electronic unit
16 A; time-lag
External fuse anti-condensation heater
2 ... 6 A; medium time-lag
Analog input
0 / 4 … 20 mA
Analog output
0 / 4 … 20 mA, galvanically isolated
3 binary inputs
BE 1 … BE 3 (DI 1 … DI 3)
Binary 0: -3 … 5 V or open, galvanically separated
Binary 1: 12 … 35 V, galvanically separated
3 binary outputs
BA 1 ... BA 3 (DO 1 … DO 3)
Potential free relay contact,
max. 60 V, 150 mA
Digital communication
RS232 for commissioning and service, optionally FSK / HART®
Default settings
Behavior in 0 / 100 % end position:
set point function:
set point input:
function selection:
actual value:
digital input:
digital output:
positioning time-out
Hold with rated torque / end positions
linear, set point = position value
4 … 20 mA
positioner, parameter: setpoint
4 … 20 mA
BE 1 (DI 1) M / A selection;
BE 2 / 3 (DI 2 / 3) manual intervention +/ -
BA 1 (DO 1) ready for operation;
BA 2 / 3 (DO 2 / 3) end position signal 0 / 100 %
not activated for standard actuators
always activated for actuators in explosion proof design
Voltage output UV
24 V, 15 mA, galvanically isolated; e.g., for scanning external contacts
Transmitter (optional)
Supply for 2-wire transmitter with activated process controller in Contrac
Individual settings
See data sheet 10/68-2.40 or upon request
Pos: 20.6 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
37
Pos: 20.7 /Überschriften/1.1/1-spaltig/S - U/Technische Daten EBS862 @ 20\mod_1209030681359_3101.doc @ 182359
10.3 Technical data for the EBS862
Pos: 20.8 /Technische Daten / Datenblatt/Aktorik/Antriebe/Leistungselektroniken/Leistungselektronik EBS862 (Contrac)/Technische Daten (Ex) @ 7\mod_1171878098843_3101.doc @ 68203
Supply voltage (standard actuators)
230 V AC (190 … 260 V); 47.5 … 63 Hz; 1 Ph
Supply voltage
(Ex actuators)
230 V AC (190 … 253 V); 47.5 … 63 Hz; 1 Ph
lmax..at 230 V
RHD(E)2500-10
5.3 A
RHD(E)4000-10
10.0 A
RHD8000-12
8.0 A
RHDE8000-15
8.0 A
RHD(E)16000-30
12.5 A
RSD(E)50-10.0
6.4 A
RSD100-10.0
12.5 A
Current at electronic unit [A] (AC 230
V AC)
RSD200-5.0
13.0 A
lpos. (230 V)
approx. 40 … 50% of lmax.
External fuse
safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA)
(fuse and circuit breaker are part of shipment)
External fuse for heat supply
2 ... 6 A; medium time-lag
Analog input
0 / 4 … 20 mA
Analog output
0 / 4 … 20 mA, galvanically isolated
3 binary inputs
BE 1 … BE 3 (DI 1 … DI 3)
Binary 0: -3 … 5 V or open, galvanically separated
Binary 1: 12 … 35 V, galvanically separated
3 binary outputs
BA 1 ... BA 3 (DO 1 … DO 3)
Potential free relay contact,
max. 60 V, 150 mA
Digital communication
RS232 for commissioning and service, optionally FSK / HART®
Default settings
Behavior in 0 / 100 % end position:
set point function:
set point input:
function selection:
actual value:
digital input:
digital output:
positioning time-out
Hold with rated torque / end positions
linear, set point = position value
4 … 20 mA
positioner, parameter: setpoint
4 … 20 mA
BE 1 (DI 1) M / A selection;
BE 2 / 3 (DI 2 / 3) manual intervention +/ -
BA 1 (DO 1) ready for operation;
BA 2 / 3 (DO 2 / 3) end position signal 0 / 100 %
not activated for standard actuators
always activated for actuators in explosion proof design
Voltage output UV
24 V, 15 mA, galvanically isolated; e.g., for scanning external contacts
Transmitter (optional)
Supply for 2-wire transmitter with activated process controller in Contrac
Individual settings
See data sheet 10/68-2.40 or upon request
Pos: 21 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 22.1 /Überschriften/1/A - C/Anhang @ 0\mod_1132904773022_3101.doc @ 3134
11 Appendix
Pos: 22.2 /Überschriften/1.1/1-spaltig/V - Z/Zulassungen und Zertifizierungen @ 0\mod_1132230068395_3101.doc @ 3806
11.1 Permits and certifications
Pos: 22.3 /Anhang/Allgemein/Zulassungen und Zertifizierungen (CE) @ 18\mod_1205231786867_3101.doc @ 169127
Zu
Symbol
Description
CE mark
By placing the CE mark on the model plate, ABB Automation Products GmbH
declares its conformance with the following directives:
-
EMC directive 89/336/EEC.
-
Machinery directive 2006/42/EC
Pos: 22.4 /Anhang/Allgemein/Hinweis zum Download-Bereich (Aktorik) @ 10\mod_1182172251781_3101.doc @ 107696
Important
All documentation, declarations of conformity and certificates are available in the download
area of ABB.
www.abb.com/instrumentation
Pos: 22.5 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
39
Pos: 22.6 /Anhang/Allgemein/Rücksendeformular @ 0\mod_1132757486454_3101.doc @ 3820
Statement about the contamination of devices and components
The repair and/or maintenance of devices and components will only be performed when a completely filled out
explanation is present.
Otherwise, the shipment can be rejected. This explanation may only be filled out and signed by authorized
specialist personnel of the operator.
Customer details:
Company:
Address:
Contact person:
Telephone:
Fax:
E-Mail:
Device details:
Type:
Serial no.:
Reason for the return/description of the defect:
Was this device used for working with substances which pose a threat or health risk?
� Yes
� No
If yes, which type of contamination (please place an X next to the applicable items)
biological
�
corrosive/irritating
�
combustible (highly/extremely combustible)
�
toxic
�
explosive
�
other harmful substances
�
radioactive
�
Which substances have had contact with the device?
1.
2.
3.
We hereby certify that the devices/parts shipped were cleaned and are free from any dangerous or poisonous
materials.
City, Date
Signature and company stamp
Pos: 23 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
EBS852, EBS862 (Contrac)
42/68-831-EN
Pos: 24.1 /Überschriften/1/G - I/Index @ 0\mod_1138787046328_3101.doc @ 3151
12 Index
Pos: 24.2 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828
Wechsel ein-auf zweispaltig
Pos: 24.3 /Inhaltsverzeichnis/Index @ 0\mod_1138784494500_3101.doc @ 3128
A
Actuator assignment................................................19
Alarm diagram..........................................................33
Alarms......................................................................32
Alarms / Errors.........................................................32
Appendix..................................................................39
C
Cable cross-section .................................................22
Cable cross-sections ...............................................19
Cable guide..............................................................25
Cable routing in the connector.................................26
Cable shield .............................................................20
CE mark...................................................................39
Commissioning and service field (ISF) ....................29
Connection elements...............................................23
Contrac electronic unit.............................................18
D
Design and function .................................................13
Disposal ...................................................................10
Downloads ...............................................................39
E
ECOM688 ................................................................12
Electrical connection..........................................18, 21
Electrical installation safety information...................11
EMC directive...........................................................39
Error.........................................................................32
Error diagram...........................................................34
Ex applications.........................................................18
Explosion-protection safety precautions..................12
External fuse for EBS862 ........................................22
External fuses ..........................................................22
F
Fuses .......................................................................22
G
General information .................................................37
General information on operation ............................27
General Safety Information........................................5
I
Installation................................................................16
Installation safety information ..................................11
Interference..............................................................26
Internal fuses ...........................................................22
L
Labels and symbols ...................................................6
Local operation ........................................................27
M
Mains distribution.....................................................26
Modules ...................................................................14
Mounting ..................................................................17
Mounting the housing halves...................................17
N
Name plate for EBS852 electronic unit......................7
Name plate for EBS862 electronic unit......................8
O
Operating elements of the service field (ISF) ..........28
Operating safety information....................................11
Operation via frequency transformer .......................12
Operator liability.........................................................9
P
Permits and certifications.........................................39
Personnel qualification...............................................9
Power Electronic Unit EBS852 (Contrac) / EBS862
(Contrac) ..............................................................21
Proper use .................................................................5
R
Returning devices ......................................................9
S
Safety.........................................................................5
Separating the housing halves ................................17
Storage conditions ...................................................10
Symbols and warnings...............................................6
T
Technical data..........................................................37
Technical data for the EBS852................................37
Technical data for the EBS862................................38
EBS852, EBS862 (Contrac)
41
Technical limits ..........................................................6
Terminal connection diagrams.................................21
Transport safety information....................................10
Trouble shooting ......................................................35
Typical commissioning with the service field (ISF)..29
W
Warranty provision.....................................................6
WEEE directive........................................................10
Pos: 24.4 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829
Wechsel ein-auf zweispaltig
Pos: 25 /Rückseiten/Minden_Aktorik @ 2\mod_1151575081640_3101.doc @ 32243
===== Ende der Stückliste =====
ABB has Sales & Customer Support
expertise in over 100 countries worldwide.
www.abb.com/instrumentation
The Company’s policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
Printed in the Fed. Rep. of Germany (07.2008)
© ABB 2008
3KXE181004R4201
42/68-831-EN Rev. A
ABB Limited
Salterbeck Trading Estate
Workington, Cumbria
CA14 5DS
UK
Tel: +44 (0)1946 830 611
Fax: +44 (0)1946 832 661
ABB Inc.
125 E. County Line Road
Warminster, PA 18974
USA
Tel: +1 215 674 6000
Fax: +1 215 674 7183
ABB Automation Products GmbH
Schillerstr. 72
32425 Minden
Germany
Tel: +49 551 905-534
Fax: +49 551 905-555
[email protected]