Operating instructions
Temperature regulator
CS 3 S
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 2 of 18
Register
Operating instructions
1.
GENERAL ....................................................................................................................... Page.... 3
Unpacking.........................................................................................................................Page.... 3
Storing ..............................................................................................................................Page.... 3
Storing conditions .............................................................................................................Page.... 3
Directly Use ......................................................................................................................Page.... 3
Discription of the product..................................................................................................Page.... 3
Guide of Conformitation....................................................................................................Page.... 3
2.
GENERAL PLAN ........................................................................................................... Page.... 4
3.
DISCRIPTION, FUNCTIONS AND TECHNICAL DATA ................................................ Page.... 4
4.
FURTHER FUNCTIONS ................................................................................................. Page.... 5
5.
SAFETY PROCEEDINGS IN NORMAL USE................................................................. Page.... 5
6.
HAZARDS BY ELECTRICAL ENERGY......................................................................... Page.... 5
7.
MOUNTING NOTES........................................................................................................ Page.... 5
Mounting regulations
Safety regulations.............................................................................................................Page ... 6
8.
SWITCHBOARD CUT OUT ............................................................................................ Page.... 6
9.
CONNECTIONS .............................................................................................................. Page.... 6
10.
CONNECTING SCHEMA................................................................................................ Page.... 7
11.
GUARANTEED VALUES AND LIABILITY .................................................................... Page.... 7
12.
NOTES ............................................................................................................................ Page.... 8
OPERATORS MANUAL
13.
DISPLAY AND OPERATORS CONTROL ..................................................................... Page.. 10
Front view CS2S...............................................................................................................Page.. 10
14.
MESSAGE BY SWITCH-ON OF THE REGULATOR..................................................... Page.. 11
Regulator Switch on/off ....................................................................................................Page.. 11
Changing of Set point.......................................................................................................Page.. 11
15.
1. PARAMETER FACE ( FLOW SHEET ) ..................................................................... Page.. 12
16.
ALARM TYPE ................................................................................................................. Page.. 14
17.
2. PARAMETER FACE ( FLOW SHEET )...................................................................... Page.. 15
18.
STARTING ...................................................................................................................... Page.. 16
19.
ERROR ALARM ON THE PV-READING ...................................................................... Page.. 17
20.
CLEANING...................................................................................................................... Page.. 17
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 3 of 18
1.
GENERAL
UNPACKING
1.
Indicate visual damages directly to the transporter.
2.
Type and notes on the package must agree with the delievery note.
3.
Unpack the regulator with the sealed synthetic bag. Open the bag first, when the regulator gets
mounted.
4.
the type on the unit, the packing and on the delievery note must correspond.
5.
Control if there is a fastening bow with the unit.
Please inform us by any irregularity.
STORING
Electric radiation, elektrostatical discharge or strong magnetic fields can damage the mounted
microprozessor or other electrical parts.
STORING CONDITIONS
Protect for
• possible mechanical damages.
• humidity
• Heat and directly insolation.
Store temperature
• -20°C to +50°C ( - 20 °F until 120 °F).
Store humidity
• 0 - 85% relative humidity ( Avoid condensation! ).
DIRECTLY USE
Please follow all instructions in this manual.
Fabrication date
The unit identifier is written on the type plate. ( Side of the covering).
The fabrication number is written at the electrical connections.
DISCRIPTION OF THE PRODUCT
TEMPERATURE-REGULATOR WITH DIGITAL DISPLAY
The regulator CS2S contains a control loop with PID-Algorythms for Temperature regulation. With this
regulator and an adequate temperature sensor it is possible to control a heating or cooling system. The
inputs (Sensore) and Alarm types can be adjusted by an intern switch.
The adequate Regulator output is fix and must be point out by order.
As supply you will find an attachment set for easier mounting of the regulator
Additional tool:
Ring sealing for IP54 (coming from the switchboard panel)
Guide of Conformitation:
Europe:
The CS 3 S is CE checked (EN-61010, EN-50082-1, EN-50082-2, EN-55011,
EN-55022) EMC
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 4 of 18
2.
GENERAL PLAN
This Discription concerns to the 48 x 48 x 110 mm-Regulator Type CS2S on microprocessor Base.
Temperature-Regulator with Digital display
Types:
GCS-3A*-R/M**
Regulator output: Relais contact, potential free
GCS-3A*-S/M**
Regulator: Contact free voltage, Driver for SSR-Relais
GCS-3A*-A/M**
Regulator: continuous
* A:
The Alarm type is adjustable via internal switches by the user.
** M:
The Sensor – input is adjustable via internal switches.
Input
Thermo elements:
E, K, J
Specific resistance 100 Ω or less. Sensor break is getting signalized.
The Regulator is switching off the regulator output.
Pt.100 (IEC-751), 3-ConductorMaximum specific resistance of 10 Ω per conductor. Sensor break
Circuit:
and short circuit are getting signalized, The regulator is switching off the
regulator output in both cases.
Display accuracy:
± 0.3 % of Scale range ± 1 Digit
Temperature compensation:
± 1 °C at 25 °C ± 10 °C (± 1 °F at 75 °F ± 50 °F )
Supply voltage:
100 - 240 VAC, 50/60 Hz or 24V AC/DC
Dimensions:
48 x 48 x 110 mm ( B x H x T )
Mounting:
Front tableau assembly, minimum space to other units - 30 mm
Covering:
non-combustible Polycarbonate / Colour: black or grey
Operation:
Front foil
3.
DISCRIPTION, FUNCTIONS AND TECHNICAL DATA
Actual value ( PV )
7 Segment red LED, 4-digit 4 x 8 mm
Theoretical value ( SV )
7 Segment green LED, 4-digit 4 x 8 mm
Actual value accuracy
Within ± 0,3 % of the scale ± 1 Digit
(compensation accuracy ± 1 °C to 25 °C ± 10 °C) (± 1 °F at 75 °F ± 50 °F )
Sample time
250 ms
PID Characteristic curve
Proportional band
(P)
0 - 999 °C / 0 - 99,9 °C
0 – 210 °F
Integral time
(I)
0 - 999 sec
Differential time
(D)
0 - 300 sec
Cycle
1 - 120 sec
Factory adjustment
Solid State Relais 3 sec
Relais
30 sec
PD Regulation charakteristik
Proportional band
(P)
0 - 999 °C / 0 - 99,9 °C
0 – 210 °F
Differential time
(D)
1 - 300 sec
ON / OFF Regulation characteristic
Hysterese 0,1 bis 99,9 °C
0 – 210 °F
Output
Relais
(-R/M)
250 VAC, 3 A resistance load
250 VAC, 1 A inductive load
Solid State
(-S/M)
12 VDC, 40mA short círcuit safe
current
(-A/M)
4-20mA insolated
Load resistor
max. 550 Ohm
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 5 of 18
Heating - defect alarm
The current which is getting used by the consumer is getting measured by the current transformer. The
measurement starts only when the unit is switched on. The Alarm is getting released when the input
Current limit remains.
Range:
20A (Option W12) or 50A (Option W15)
Adjustment:
0,0 - 20,0 A for range 0-20A
0,0 - 50,0 A for range 0-50A
0,0 switches off the functions
Accuracy:
± 5%
Behaviour:
ON / OFF
Output:
Relais
250VAC 3A resistance load
250VAC 1A resistance load
Threaded fastening bow Option BL
Front tableau thickness
1 - 15 mm
4.
FURTHER FUNCTIONS
Regulator output switch off and Display Off.
All exits are getting switched off. The actual value display shows OFF.
Locking functions
Lock 1
Blocking all Parameters (theoretical value, Alarm 1, Alarm 2 and heating defect alarm).
Lock 2
Blocking all Parameters without actual value.
5.
SAFETY PROCEEDINGS IN NORMAL USE
•
Before starting the regulator:
•
Check all Safety installation for there function;
•
Be sure that nobody is in danger.
•
Check regulator at least once at a shift for visual damages and the safety installations for there
functionallity.
6.
HAZARDS BY ELECTRICAL ENERGY
•
Allow only qualified personnel to work on the electrical supply.
•
Check the electrical equipment regulary! Fix loose connections and change burnt parts directly.
•
Keep the switchboard door always closed. Allow only qualified personnel to work at the switchboard.
7.
MOUNTING NOTES
Mounting regulations
Avoid following subjection of environmental conditions:
•
Soot, Dust and corrosive Gases;
•
Air moisture higher than 85% and deeper than 30% relative humidity;
•
Condensation;
•
Evironmental temperature higher than 50°C ( 120 °F )and deeper than 0°C ( 0°F);
•
Vibrations or heavy beats;
•
EMC-load, Installation close to power supplier and high voltage electrical equipment; splashing with
liquids
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 6 of 18
Safety regulations
Do not use the regulator in space travel, aviation, atom reactor, medicine and explosive environment
Due to the used Temperature sensor the regulator can regulate temperatures between -199°C (-199
°F) and + 1820°C ( + 3300 °F ). For any risks of producing such temperatures is only the user liable.
When a damage can occur by a mistake of the regulation a safety switch off must be carry out.
Regulation range
For adjusting the theoretical value in the provided range, the borders for the minimum and maximum
theoretical value must be separated.
Instructions, Manipulation at the unit
The user is responsible to understand the operation instructions and to avoid any kind of manipulation
which influenced the safety of the unit..
8.
SWITCHBOARD CUT OUT
The switchboard cut out for the CS2S is 45 x 45 mm.
The ideal sheet thickness is between 1 - 3 mm.
The minimum distance to other units is 30 mm.
9.
Connections
The connection wires with 1mm2 should equipped with
according 4 mm Cable lugs.
The cable lugs should fasten from left under the
according connecting terminals.
Please see the installation terms.
Mount the touch protecting cap!
4
3
2
1
10
9
8
7
6
5
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 7 of 18
10.
CONNECTING SCHEMA
Power supply:
Please see Sticker at the unit.
24 VAC/DC or 100-240 VAC
If the Voltage of a 24V-unit is 230 VAC
heavy defects appears.
Sensor connections
Thermo elements direct.
Thermoelement with compensation line und Thermobinders!
Pt.100 3-conductor circuit.
At a 2-conductor PT 100 a bridge must be wired at the unit.
The connection resistor should not exceed the value of
10 Ω for each conductor. Otherwise a higher
Temperature gets measured.
11.
GUARANTEED VALUES AND LIABILITY
Basically our Terms of payment and delievery are significant. The manufacturer is by no means liable for
any failures at persons or subjects, if they result of following respond:
•
No intended purpose of the regulator;
•
Inappropriate mounting, initiation, operation and maintenance of the regulator;
•
Initiation of the regulator by defect safety installations or inappropriate mounted and not
functionable safety and protection installations;
•
Not observing the instructions given in the handbook refering transport, mounting, initiation,
operation, maintenance and storing the regulator;
•
Alterations effected without any authorization;
•
Catastrophic cases caused by outside effects and superior force.
2
3
100 - 240 V AC
5
Regulator
output
3
2
1
or 24 V
AC / DC
Alarm 1
4
Alarm 2 or
Heating defect
4
PT 100
Thermo element
5
1
Compensation
conductor
Thermo element
Thermoelement
Pt. 100
3 - conductor
Pt. 100
3 - conductor
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 8 of 18
12.
NOTES
•
Basically for the safe handling and trouble free use of this regulator is the knowledge of safety
instructions.
•
This operation manual, specially the safety instructions, must observed by all persons working with
this regulator.
Also all laws and rules for accident prevention at the working place must be observed.
Hazards by handling of the regulator
The regulator type CS2S correspond to the actual stand of the art and the official safety specification.
But the possibility of hazards for persons and the machine is still existing. Use the regulator only:
•
for its intended purpose
•
in perfect conditions
all hazards which are influencing the safety of the unit must be erased.
Safety rules
•
Organisatoric proceedings.
•
All existing safety installations must be controlled permanently.
Safety installations
•
Before starting the regulator all safety installations must be mounted in accordance with regulations
and operative.
•
Remove safety installations only, when the regulator is:
•
Out of gear;
•
Safe against reinitiation.
Safety arrangements
•
The operation instructions must be placed permanently at the working place.
•
Additional to the operating instructions all general valid and local laws and reglementations for
accident prevention and environment protection must be observed.
Training of personnel
•
The regulator is only to be operated by well skilled and instructed personnel.
•
The responsibility of the personnel for the mounting, initiation, operation, maintenance and repair-
work must be strictly appoint.
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 9 of 18
Operators manual CS 3 S
OPERATORS MANUAL
13.
DISPLAY AND OPERATORS CONTROL
Page
10
Front view CS2S
Page
10
14.
Message by switch-on of the regulator
Page
11
Regulator switch on/off
Page
11
Changing of set point
Page
11
15.
1. PARAMETER FACE ( FLOW SHEET )
Page
12
16.
ALARM TYPE
Page
14
17.
2. PARAMETER FACE ( FLOW SHEET )
Page
15
18.
STARTING
Page
16
19.
ERROR ALARM ON THE PV-READING
Page
17
20.
CLEANING
Page
17
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 10 of
18
13. DISPLAY AND OPERATORS CONTROL
Front view of CS 3 S
1.
Actual value (PV)
2.
Theoretical value (SV)
3.
UP key
4.
DOWN key
5.
MODE- key
6.
ON/OFF key
LED-DISPLAY
7.
Option Heating interrupt alarm
8.
Option Alarm 2
9.
Alarm 1
10. Regulation output
11. Display for Auto tuning
1
11
10
9
8
7
6
5
4
3
2
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 11 of
18
14. MESSAGE BY SWITCH-ON OF THE REGULATOR
When the power supply of the regulator is getting switched on, the unit carries out a self-test. If the
regulator is recognising an internal error, the display is blinking. In this case send the unit back to the
manufacturer.
Pt 100 IEC-751 with point °F
Thermoelement Type E °F
Thermoelement Type K °F
Thermoelement Type J °F
J F
t F
JPF
E F
Japan ( JIS ) Pt 100 without point °F
JPC TJapan ( JIS ) Pt 100 with point °C
Pt 100 IEC-751 without point °C
Thermoelement Type J °C
Thermoelement Type E °C
Thermoelement Type K °C
Japan ( JIS ) Pt 100 °C
Pt 100 IEC-751 with point °C
P C
P C
E C
JPC
J C
t C
P F
The Sensor display shows, which probe type is getting installed. This is very important to control,
because the connection of a wrong thermoelement causes defects.
By operation the theoretical value ( lower display ) and the actual value ( upper Display ) are indicated.
The regulator starts to work directly.
Regulator switch ON / OFF
By operation the regulator can be switched on or off by the key ON/OFF. This key must be pushed for 5
seconds.
A 2
AT
AT
PV
SV
AT
AT
Out
A 1
PV
AT
AT
A 2
A 1
Out
AT
AT
SV
AT
AT
Out
A 1
A 2
PV
Mains ON
WIKA
AT
AT
SV
Mode
Out /
Off
Mode
CS2S
CS2S
Mode
Out /
Off
Mode
CS2S
CS2S
CS2S
CS2S
WIKA
Operation
Sensor display
WIKA
Mode
Out /
Off
Mode
HB
HB
HB
SV
PV
AT
AT
A 2
A 1
Out
AT
SV
AT
A 1
AT
AT
AT
AT
PV
AT
AT
A 2
PV
Out
SV
AT
AT
Out
A 1
A 2
1s
Out /
Off
Mode
Out /
Off
Mode
CS2S
WIKA
CS2S
Operation
WIKA
WIKA
CS2S
Out /
Off
Mode
Regulator switch
ON
Regulator switch
OFF
Out /
Off
1s
CS2S
CS2S
Mode
Out /
Off
Mode
HB
HB
HB
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 12 of
18
Changing the 1st and 2nd theoretical value
A1
A2
OUT
HB
MODE
OUT
A2
A1
HB
SV
WIKA
A2
GCS
PV
OUT
A1
HB
MODE
OUT
OFF
A1
PV
SV
HB
A2
MODE
OUT
OFF
GCS
OUT
PV
SV
PV
SV
A1
OUT
HB
GCS
WIKA
MODE
A2
Operation
GCS
WIKA
WIKA
GCS
MODE
PV
SV
A2
SV
OUT
A1
HB
MODE
WIKA
GCS
OUT
OFF
PV
MODE
OUT
OFF
OUT
OFF
MODE
OUT
OFF
Confirmation and
change of 2nd
theoretical value
Change of 1st
theoretical value
WIKA
Confirmation of theoretical
values and continue of operation
Change of 1st
theoretical value
MODE
1. Push the MODE key.
2. The first theoretical value can be adjusted by the UP/DOWN key.
3. Acknowledge with the MODE key. The new theoretical value appears on the display. The display flips
over to the set up of the second theoretical value.
4. The second theoretical value can be adjusted by the UP/DOWN key.
5. Confirmation with the MODE key.
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 13 of
18
MODE
OUT
A1
HB
A2
OUT
OFF
SV
WIKA
A2
HB
A1
PV
OUT
PV
SV
WIKA
OUT
OFF
MODE
SV
WIKA
PV
OUT
A1
HB
A2
MODE
OUT
OFF
Operation
MODE
15.
Sublevel
By pushing the buttons
The display flips into the sublevel
Self optimation (AT=Autotuning)
The self optimation can be released in the start- and stop phase.
Please see, that the regulator switches two times. First up to 0%,
then to 100% power. Between this time the optimal parameters P, I
and D are getting calculated.
Proportional band range 0 – 999 K / 0 - 99,9 °C
The Proportional band works proportional to the actual- and
theoretical value at the regulation output. (Factory Adjustment
(Factory adjusting FA = 10°C )
Integral time range 0 - 999 Seconds
The integral time appoints the time of the output to change the
power from 0 to 100% and reverse. (FA = 200 sec.)
ATTENTION: I : D at least 4 : 1!
Differential time range 0 - 300 Seconds
The differential time appoints, in which time distance to the actual-
and theoretical value a reaction should happens. (FA = 50 sec.)
ATTENTION: I : D at least 4 : 1!
CYCLE TIME
The cycle time appoints, in which time distance the regulation output
should be switched. ( FA = 1 sec )
Relais= 30 Seconds
SSR = 1 - 3 Seconds
CYCLE TIME
The cycle time appoints, in which time distance the regulation output
should be switched. ( FA = 1 sec )
Relais= 30 Seconds
SSR = 1 - 3 Seconds
HB
CS2S
Out /
Off
Mode
Mode
AT
AT
AT
AT
A 1
Out
A 2
PV
CS2S
SV
WIKA
Mode
Out /
Off
CS2S
HB
Mode
AT
Out
A 1
A 2
AT
AT
AT
WIKA
PV
SV
Mode
Out /
Off
CS2S
HB
Mode
AT
Out
A 1
A 2
AT
AT
AT
WIKA
PV
SV
Mode
Out /
Off
CS2S
HB
Mode
AT
Out
A 1
A 2
AT
AT
AT
WIKA
PV
SV
Mode
HB
CS2S
Out /
Off
Mode
AT
AT
AT
A 2
A 1
Out
AT
WIKA
SV
PV
Out
AT
Mode
Out /
Off
Mode
AT
AT
AT
A 2
A 1
WIKA
SV
PV
HB
CS2S
MODE
Rücksprung
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 14 of
18
Now the regulator parameters are adjusted. If the results will not met the requirements we suggest to
start first the autotuning. The system should be levelled out new. If the result are deficient again, we
suggest following:
1. Double Proportional band
Reduce 2 x Integral- and Differential time. Please see Formula, that I:D should be at least 4:1. By faster
Systems you can adjust following ratio: 5:1; 6:1; 7:1
By starting the regulator the upper LED Display shows the adjusted Sensor.
After approx. 2 sec. the actual value and the theoretical value are shown. The unit is now ready for
regulation.
The control is divided into three levels.
1. Level ( main level ):
- Adjust theoretical value like Flow chart.
- Switch ON/OFF the regulation.
Set-up theoretical value:
1. Push MODE key.
2. Adjust the new theoretical value with the UP and DOWN key. Acknowledge with MODE key.
Switch ON/OFF the regulation.
Push OUT/OFF key for approx. 1 sec.
The upper display shows OFF or once more the actual and the theoretical value.
During regulation the LED shows the actual state with OUT, A1, A2, AT.
When the LED is blinking the output is activated. Is the AT LED blinking the regulator is in optimation
process and should not be disturbed. ( searching in PID Modus for the optimal PID Parameters ).
When the regulator found the Parameters, the blinking of the AT LED stops.
Description:
OUT
Regulator output
A1
Alarm 1
A2
Alarm 2
AT
Auto tuning ( Self optimation )
PV
Process value ( Actual value )
SV
Set value ( theoretical value)
CS
Model
Shinko
Manufacturer
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 15 of
18
m ax
min
16.
ALARM TYPE
In this second face you can put in the appropriate parameters.
Allow only qualified personnel to operate in this face.
Access to the Parameter-face:
You can switch over the parameter face with the UP- and MODE-key.
The Self optimation is reached at the first set point. You can activate the self optimation with the UP-
and DOWN key.
The next parameter is reached by switching over the MODE-key. At the end of the parameter face the
basic mode is reached with the MODE-key.
Regulation parameter
Proportional band
0 to 999°C, by Pt.100 with decimal dot 0 to 99,9°C.
•
Integral time
0 to 999 sec.
•
Differential time
0 to 300 sec.
•
Proportional cycle
1 to 120 sec.
Factory set:
•
Proportional band (P)
10°C.
•
Integral time
(I)
200 sec.
•
Differential time
(D)
50 sec.
•
Proportional cycle
30s at relais output, 3s by output with semiconductor relais.
Important:
To receive a meaningful regulation, the I : D ratio must be at least 4 : 1! Adjust the proportional cycle in
dependance to the output type and the gradient of the controlled system.
Relais output
= 15 - 40 sec.
semiconductor relais
= 1 - 5 sec.
mA Output
= without Proportional cycle!
Attention:
The cycle time at the relais output should not be adjusted under 15 seconds, because a shorter time
increases the wear at the contacts. The gradient is getting calculated of the temperature rise per time.
The inverse time shows the optimal proportional cycle time.
Alarm date:
Alarm 1, Alarm 2 ( Option )
The value can be adjusted in the range of the choosen alarm type and probe.
17.
STARTING
After mounting the CS3S professionally with all safety and mounting directions and after understanding
the operation instructions the starting should execute like this:
1. Check on the PV-display the correctness of the sensor after switching OFF and ON the mains. If the
display is not fitting with the connected sensor, the sensor must be adjusted with the right parameters of
the probe ( page 15 ).
2. The maximum and minimum theoretical value set up for the user can be adjusted in the second
face(Parameter face limit dates). The user can only adjust the theoretical value in this given range.
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 16 of
18
MODE
OUT
OFF
WIKA
MODE
OUT
A1
HB
A2
PV
SV
WIKA
PV
A2
OUT
OFF
SV
H B
A1
OUT
MODE
PV
SV
A2
H B
A1
OUT
OUT
OFF
MODE
SV
WIKA
OUT
A1
H B
A2
WIKA
Operation
MODE
PV
OUT
OFF
MODE
18.
2. PARAMETER LEVEL
3 Seconds pushing
Block level:
Lc1 = All Parameter are blocked against misadjusting.
Lc2 = Only the theoretical value can be adjust.
LC3 = All parameters can be adjusted but not stored after
switching of.
--- = All parameters are free adjustable.
Maximum theoretical value:
The Operator can adjust the theoretical value to the minimum
value. ( Factory adjusting FA = 250 )
Minimum theoretical value:
The Operator can adjust the theoretical value to the minimum
value. ( FA = 0 )
Correction of aktuel value ± 199°C, ± 199,9°C:
If the aktuel value is not equal to the reference measuring
instrument, it can be corrected with this value.
(FA = 0°C )
19.
2. PARAMETEREBENE
3 Second pushing
Selection of sensor
t C
Thermoelement Type K °C
J C
Thermoelement Type J °C
E C
Thermoelement Type E °C
P C
Pt. 100 IEC-751 without point °C
JPC
Japan ( JIS ) Pt. 100 °C
P C
Pt. 100 IEC-751 without point °C
JP C
Japan ( JIS ) with point°C
t F
Thermoelement Type K °F
J F
Thermoelement Type J °F
E F
Thermoelement Type E °F
P F
Pt. 100 IEC-751with point °F
JPF
Japan ( JIS ) Pt. 100 without point °F
PV-Filter Time set up: (0,0s)
By large actual value variation the signal is getting attenuated
(FA = 0,0 sec )
Maximum output:
Normally 100 % output is wanted. The output could be
reduced by faster systems. (FA = 100 %)
MODE
OUT
OFF
MODE
PV
MODE
WIKA
GCS
MODE
A2
SV
OUT
A1
HB
A2
HB
OUT
A1
SV
PV
SV
A2
OUT
OFF
WIKA
GCS
MODE
HB
MODE
WIKA
GCS
PV
MODE
OUT
OFF
OUT
A1
OUT
OFF
MODE
WIKA
GCS
A1
SV
PV
A2
HB
OUT
Regelbetrieb
MODE
PV
MODE
GCS
MODE
A2
SV
OU T
A1
HB
OUT
OFF
MODE
WIKA
A2
HB
OU T
A1
SV
PV
OUT
OFF
WIKA
GCS
MODE
SV
HB
A2
OU T
A1
MODE
MODE
WIKA
GCS
PV
MODE
OUT
OFF
Return
Return
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 17 of
18
Minimum output:
Normally 0 % output is wanted.
Attention: Adjust this value to larger then zero only when
necessary. Heater and cooler are regulating with this
minimum power. (FA = 0 %)
Alarm type selection:
Please see the former page (FA = ÜLD)
Temperature alarm 1 (A1) Select energized / Not energized
Not energized:
Energized:
Alarm hysteresis:
Cares for a Hysterese between pick up and release of the
Alarm relais. (FA = 1,0°C)
Temperature alarm 1 (A1) set up delay time: (0S)
Heating / Cooling:
With this parameter you can switch over the regulator
between heating and cooling.
Set up Offset value Auto tuning (°C)
At this adjusted temperature, which is getting subtracted from
the theoretical value, the regulator starts with an auto tuning
End of input
O UT
A1
OUT
OFF
PV
HB
A2
WIKA
GCS
MODE
SV
PV
MODE
WIKA
GCS
MODE
A2
SV
OUT
A1
HB
OUT
OFF
MODE
A2
OUT
A1
SV
PV
HB
OUT
OFF
WIKA
GCS
MODE
SV
HB
A2
OUT
A1
MODE
MODE
WIKA
GCS
PV
MODE
OUT
OFF
OUT
OFF
MODE
WIKA
GCS
MODE
A2
HB
OUT
A1
SV
PV
HB
PV
SV
A1
OUT
WIKA
A2
MODE
OUT
OFF
HB
A1
OUT
SV
A2
MODE
GCS
MODE
PV
A1
OUT
OUT
OFF
MODE
PV
GCS
WIKA
MODE
A2
HB
SV
MODE
GCS
WIKA
OUT
OFF
Sm-Klebetechnik Vertriebs GmbH
Otto-Hahn-Str. 19a, 52525 Heinsberg
Tel.: +49 2452 / 9172-0; Fax.: +49 2452 / 9172-20
www.sm-klebetechnik.de
Page 18 of
18
3. Cycle and parameter
In the second face the parameters are factory set like this:
P Proportional band
= 10 °C
I Integral time
= 200 s
D Differential time
= 50 s
The proportional cycle ( c ) must be controlled. This adjusting should depends to the regulation output.
By Solid State Exit
c = 1-3 sec
By Relais Exit
c = 15 - 30 sec
by mA
- Exit the parameter is not adjustable.
4.
Optimal regulator results:
The standard parameters for the starting regulation are factory set.
When the system is getting switched ON, the regulator starts with the adjusted basic regulation values.
If a direct regulation result is wanted, the self optimation in parameter face 2 are getting activated. The
regulator is analizing the regulation system and calculating the optimum parameter. This optimation is
also carried out during the process, when Lock 1 and Lock 2 are not adjusted.
20.
ERROR ALARM ON THE PV-READING
Broken probe:
•
When a damage is detected at the thermostat or PT 100, or the adjusted maximum sensor value
exceed 5%, the PV-display shows four blinking lines on the upper side ( ---- )
The regulator switches off the regulation output during this error.
•
When the input remain under the minimum sensor value for 1%, the PV-display shows four blinking
lines on the lower side ( ---- ).
Self diagnosis:
During the start phase the regulator controls itself. In this Phase the adjusted Sensor and the maximum
value are shown!
21.
CLEANING
Clean the regulator front only with a wet rag.
Do not use any kind of solvents in no way!!!