Text of the manual

Rapid City, SD, USA, 07/2009

II-111-233-15P-B Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!

FOLLOW NATIONAL, STATE AND LOCAL CODES. READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION. SymCom’s PumpSaver®Plus is a pump monitor designed to protect single-phase pumps from dry- well, dead-head, jammed impeller, rapid-cycling, overvoltage and undervoltage conditions. The PumpSaver®Plus Model 233P protects 230V, 2 or 3-wire, 1/3 to 3 hp pumps. The PumpSaver®Plus Model 233P-1.5 protects 230V, 2 or 3-wire, 1/3 to 1.5 hp pumps. The PumpSaver®Plus Model 111P protects 115V, 2 or 3-wire, 1/3 to 1 hp pumps. Typical applications include submersible pumps, centrifugal pumps, circulating pumps, cooling pumps, environmental pumps, residential waterwells, commercial waterwells, irrigation wells, and golf course and other sprinkler systems. CONNECTIONS NOTE: Use with UL/CSA listed overload or impedance protected pumps or motors only. 1. Mount the PumpSaver®Plus in a convenient location in or near the pump control box. If the location is wet or dusty a NEMA 3R, 4, or 12 enclosure should be used. The PumpSaver®Plus must be protected by a fuse or circuit breaker (30A RK5 fuse or 30A inverse time breaker max). 2. Connect one line from the fused disconnect to the L1 IN terminal of the PumpSaver®Plus. Run a wire from the L1 OUT terminal to the other in-line controls such as pressure or float switches. 3. Connect the other line from the fused disconnect (ungrounded fused conductor) to the L2 IN terminal of the PumpSaver®Plus. Run a wire from the L2 OUT terminal to the other in-line controls such as pressure or float switches (see Figure 1). 4. Refer to the appropriate wiring diagram for your specific application: • Typical wiring diagram – Figure 1 • Standard 3-wire control box – Figure 2 • Deluxe control box – Figure 3 • 2-Wire pump direct feed – Figure 4 *** WARNING *** PROPER OPERATION REQUIRES FIELD CALIBRATION Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

FIGURE 1: Typical Wiring Diagram

FIGURE 2: Standard Control Box Wiring Diagram Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

FIGURE 3: Deluxe Control Box Wiring Diagram

FIGURE 4: 2-Wire Pump Direct-Feed Wiring Diagram Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

The PumpSaver®Plus monitors pump load in amps and kilowatts. When the current (amps) exceeds

approximately 125% of calibrated current, or power (kW) drops below the adjustable underload trip point, the PumpSaver®Plus—after the trip delay—will turn off the pump. The PumpSaver®Plus will time through the restart delay, and then restart the pump. The calibration is stored in permanent memory—it does not need to be recalibrated if power is lost. CALIBRATION NOTE: The PumpSaver®Plus should be calibrated during normal pumping conditions. 1. Turn the RESTART DELAY/ CALIBRATION knob fully counter-clockwise to the CAL. position. 2. Apply power—the pump will run for approximately 10 seconds then shut off. 3. Set the RESTART DELAY/ CALIBRATION knob to the desired restart delay (dry-well recovery time)—the pump will turn on. CALIBRATING WHILE PUMPING The PumpSaver®Plus can also be calibrated while the pump is running. Turn the RESTART DELAY/ CALIBRATION knob to CAL. while pumping. Wait for the pump to turn off (approximately 10 seconds), then adjust the RESTART DELAY/ CALIBRATION knob to the desired setting. SENSITIVITY The PumpSaver®Plus has an adjustment knob to set the underload trip sensitivity. Setting SENSITIVITY to the middle position (straight up) is equivalent to SymCom’s standard underload trip level. Adjust the SENSITIVITY knob to increase/decrease underload sensitivity up to approximately 10% of the standard trip. It may be necessary to increase the sensitivity if the PumpSaver®Plus does not trip on dry-run or dead-head or it is known that the water level in the well is very low relative to the pump’s capabilities. WARNING: Decreasing the SENSITIVITY may compromise the PumpSaver®Plus’ ability to detect dry-run and/or dead-head conditions. RESET MODE / RESTART DELAY Any restart delay can be by-passed by rotating the RESTART DELAY/ CALIBRATION knob to the RESET position and back to the desired restart delay setting. NOTE: The restart delay setting can be changed at any time. The current and subsequent trips will follow the new restart delay setting. The RESTART DELAY/ CALIBRATION knob can be placed in the RESET position for manual reset. If the PumpSaver®Plus trips off in this mode due to a voltage or load problem, the RESTART DELAY/ CALIBRATION knob must be rotated out of the RESET position to restart the pump. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

RUN HOURS / FAULT HISTORY

The PumpSaver®Plus records pump run hours. Run hours can be displayed by a PumpSaver® Informer (see USING AN INFORMER at the bottom of this page). Run hours and fault history can be cleared on the PumpSaver®Plus. Read the following instructions fully before performing the procedure. NOTE: Turn the SENSITIVITY knob completely to the left (counter-clockwise) or completely to the right (clockwise) when directed. To Reset Run Hours and Clear Fault History: 1. Remove power to the PumpSaver®Plus. 2. Set the RESTART DELAY/ CALIBRATION knob to RESET and the SENSITIVITY knob to the middle (12:00) position. 3. Apply power to the PumpSaver®Plus—the CAL. LIGHT will turn on. 4. Turn the SENSITIVITY knob to the right—the CAL. LIGHT will turn off and the RUN LIGHT will turn on. 5. Turn the SENSITIVITY knob to the left—both lights will turn on. 6. Turn the SENSITIVITY knob to the right. 7. After 10 seconds, the CAL. and RUN LIGHTS will blink twice indicating the run hours and fault history have successfully been cleared. RAPID CYCLING Rapid cycling is defined as more than 4 restarts in a 60-second period. The PumpSaver®Plus is capable of detecting a rapid-cycle condition whether a control device, such as a pressure switch, is installed before* or after it. Upon detecting either form of rapid cycling, the PumpSaver®Plus will lock-out, preventing damage to the pump. To reset the PumpSaver®Plus, remove and re-apply power. RAPID CYCLING (Line Side / Upstream) Rapid cycling of the line side of the PumpSaver®Plus may be caused by several naturally occurring conditions which are indistinguishable from true rapid cycling. For this reason, once tripped, the PumpSaver®Plus will wait 30 minutes and restart. If the restart is successful (the pump runs for more than one minute), the rapid cycle counter will reset to zero. If the PumpSaver®Plus encounters rapid cycle 4 times without a successful restart, it will lock-out and require a manual reset. To reset the PumpSaver®Plus, remove and re-apply power. *Protection against rapid cycling of a control device installed before the PumpSaver®Plus is disabled by default. Read the following instructions fully before performing the procedure to enable this feature. NOTE: Turn the SENSITIVITY knob completely to the left (counter-clockwise) or completely to the right (clockwise) when directed. To Enable Rapid-Cycle Protection when a Control Device is Installed BEFORE the PumpSaver®Plus: (to disable, follow the same procedure) 1. Remove power to the PumpSaver®Plus. 2. Set the RESTART DELAY/ CALIBRATION knob to RESET and the SENSITIVITY knob to the middle (12:00) position. 3. Apply power to the PumpSaver®Plus —the CAL. LIGHT will turn on. 4. Turn the SENSITIVITY knob to the right—the CAL. LIGHT will turn off, RUN LIGHT will turn on. 5. Turn the SENSITIVITY knob to the left—both lights will turn on. 6. Turn the SENSITIVITY knob right—left—right—left—right. 7. After 2 seconds, the CAL. and RUN LIGHTS will blink once indicating line side rapid-cycle Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

protection has been enabled.

RAPID CYCLING (Load Side / Downstream) Load side rapid cycling of the pump will immediately result in a manual lock-out. The pump will not restart automatically. To reset the PumpSaver®Plus, remove and re-apply power. Note: Protection against rapid cycling of a control device installed after the PumpSaver®Plus is always enabled. Disabling line side detection will not disable load side detection. USING AN INFORMER PumpSaver®Plus products are equipped with an infrared LED that will communicate to a SymCom Informer—a handheld, battery-operated, diagnostic tool. The Informer—when directed at the PumpSaver®Plus—will display real-time voltage, current and power; dry-well and overcurrent trip points; calibration voltage; last 20 faults; voltage, current and power at the last fault; highest/lowest voltage and current since calibration; the model number; and the CT size if applicable. The Informer can be used on any single-phase PumpSaver®Plus equipped with an infrared LED transmitter. Contact SymCom for more information at 800-894-0412 or visit our website. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

RUN LIGHT CAL. LIGHT

PROBLEM or FUNCTION CORRECTIVE ACTION On Steady Off RUN: Pump is running—or ready to run—no problems in operation If pump is not running, check for loose wiring and ensure proper function of pressure or float switches. On Steady On Steady CAL: The PumpSaver®Plus is in the calibration process. None Off On Steady CAL COMPLETE: The PumpSaver®Plus has calibrated, the RESTART DELAY/ CALIBRATION knob was left in the CAL. position. Pump is off. Pump will restart as soon as the RESTART DELAY/ CALIBRATION knob is rotated out of the CAL. position. Off Off OFF / MANUAL RESTART: The pump is not running. Either the PumpSaver®Plus has tripped on dry-run, dead-head, or overcurrent while the RESTART DELAY/ CALIBRATION knob was in the RESET position or source power is not present. If knob is in the RESET position, rotate out of RESET—If the CAL. light blinks, check for an overcurrent condition. If the RUN light blinks, look for a dry-run or dead-head condition. If no lights come on, check incoming power for adequate voltage. Blinking Off DRY RUN / DEAD HEAD: The PumpSaver®Plus has shut the pump off due to a dry run or dead head condition. The unit is timing through the restart delay and will try to restart. Check for restricted flow or inadequate supply of liquid. Off Blinking OVERCURRENT: The PumpSaver®Plus has shut the pump off due to an overcurrent condition. The unit is timing through the restart delay and will try to restart if line voltage is at an acceptable level. Check for low or high voltage or jammed pump impellers. If these conditions do not exist, recalibrate the unit while it is drawing higher current (amps should not exceed SFA). Blinking alternately with the CAL. LIGHT Blinking alternately with the RUN LIGHT VOLTAGE FAULT: The PumpSaver®Plus is preventing the pump from starting due to voltage problems. The voltage is being interrogated and the unit will remain in this mode until the voltage is at an acceptable level. If the unit remains in this state for more than 5 seconds, check for high or low voltage. Blinking in unison with the CAL. LIGHT Blinking in unison with the RUN LIGHT RAPID CYCLE: The PumpSaver®Plus has shut down on rapid cycling. Power must be removed and reapplied to reset the unit. Check for a broken bladder in the pressure tank (if used), or check for a defective pressure or float switch. Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

125% of calibration point

Underload (dry-well) Adjustable (70-90% of calibrated run power) Overvoltage 233P, 233P-1.5 265VAC 111P 132.5VAC Undervoltage 233P, 233P-1.5 190VAC 111P 95VAC Number of restarts allowed in 60 second period (rapid-cycling) 4 Trip Delay Times Overcurrent 5 seconds Dry-well 4 seconds Dry-well Optional* 8 seconds Restart Delay Times Over/undervoltage 2 seconds All other faults Manual, 2-225 minutes Input Characteristics Supply Voltage 233P, 233P-1.5 230VAC 111P 115VAC Load Range 233P 1/3 – 3 hp 233P-1.5 1/3 – 1.5 hp 111P 1/3 – 1 hp Frequency 50/60Hz (NOTE: 50Hz will increase all delay timers by 20%) Output Characteristics Output Contact Rating-SPST 233P 3hp @ 240VAC (17 Amps max.) 233P-1.5 1.5hp @ 240VAC (10 Amps max.) 111P 1hp @ 120VAC (16 Amps max.) General Characteristics Operating Temperature -40° to 55°C (-40° to 131°F) Maximum Input Power 5 W Wire Gauge Solid or stranded 10 – 22 AWG Terminal Torque 13 in.-lbs. Standards Passed Electrostatic Discharge (ESD) Surge Immunity IEC 61000-4-2, Level 2, 4kV contact, 6kV air IEC 61000-4-5, Level 4, 4kV line-to-line and line-to- ground Safety Marks cUL Listed UL508 & C22.2 No. 14 Dimensions 2.90” H x 5.26” W x 2.93” D Weight 14 oz. Mounting Methods #8 screws *use part number 233P-UCTD8 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]