Manual for Swema 3000
Version 16.09 5.31
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 2
Content
1. Overview............................................................................................ 3
2. Mounting of holder............................................................................ 4
3. Read this before you begin.............................................................. 5
4. MENU 1............................................................................................... 7
5. MENU 2............................................................................................... 8
6. MENU 3............................................................................................... 9
7. Diferent probes for Swema 3000.................................................... 10
8. Swema 3000’s different programs...................................................12
8.1
AP (Average Point) ........................................................................................ 13
�
8.2�
APF�(Average�Point�Flow)��-�Air�flow�in�chanel�and�with�area....................�14
�
8.3�
DPF�(Differential�Pressure�air�Flow)�-�Air�flow�with�K-factor......................�16
�
8.4�
DPK�(Differential�Pressure�K-faktor)�-�K-factor�with�air�flow......................�17
�
8.5�
AF�(Average�Flow)�-�Air�flow�with�spigot......................................................�18
�
8.6�
BP�(Back�Pressure)�-Air�flow�with�compensated�spigot.............................�19
8.7
AS (Auto Sampling) - Sampling of readings................................................. 21
�
8.8�
ASF�(Auto�Sampling�air�Flow)�-�Sampling�with�calculating�air�flow...........�22
�
8.9�
CO�(Comfort)�-�Tensile�index�calculation......................................................�24
8.10 LOG - Logging of readings............................................................................. 25
�
8.11�
LOGP�-�Logging�of�protocol...........................................................................�26
9. Measurement units showed for different measurement............. 27
10.��Note�Book,�Loggings�and�Files....................................................�28
11. SwemaTerminal 2 (PC-Program)................................................... 29
12.��Time�constant�and�filter.................................................................�30
13. Display view and saving of measure values............................... 30
14.��Technical�Data................................................................................ 31
15. Theory.............................................................................................. 35
15.1� Calculating�K-factor.......................................................................................�35
�
15.2� Necessary�straights�before�and�after�measurement�plan..........................�35
�
15.3� Recommended�measuring�points�channel�measurement.........................�36
�
15.4� Values�of�K2-factor.........................................................................................�37
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 3
1. Overview
Display
Function keys
Arrow Key
Enter Key
Display
On / Off
Probe connector
RS232/SwemaTwin connector
USB connector
Battery hatch 2 x AA Batteries
Description of Func-
tion keys
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 4
2. Mounting of holder
Start by remove the rubber list by grabbing it with the ffingers. Push the list approximately 1 cm to
the oppening and pull out the list.
Remove the the list by pull it out. When the list has been removed you can place the holders by
placing it in the opening and pull them to a suitable place.
Now, you can place the sensor. (The image shows a SWA 10 wth a holder)
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 5
3. Read this before you start
Swema 3000 is an universal instrument for measurement of air speeds, air flows, drafts, air humi-
dity, temperatures and differencial pressure. Swema 3000 has a large computing capacity and you
are able to store single or calculated measurement in the memory for print to PC.
Models:
Swema 3000: Basic model
Swema 3000md: Built-in differencial pressure transmitter (-300... 1500 Pa) as well as Built-in baro-
meter & thermo coupple contact. Type-k for density compensating.
Swema 3000mdH+: As Swema 3000md but with a larger differencial pressure area (±10.000 Pa).
Start-up of Swema 3000:
At switch-on of the instrument, it shows an information box within some seconds. Where it shows
which model of Swema 3000 it is, which software version (Firmware) the instrument has as well as
the battery voltage (less than 2.0V the instrument wil shut down itself). If you have a sensor con-
nected, you will also see which type of sensor it is when the calibration comes out as well as the
serie number on the probe (does not apply relative humidity/temp sensor). If you would like to see
the infromation box, a longer time than the seconds shown, then hold the on/off key while switch-
on, the window disappears when the key is realesed.
Sensor:
Swema 3000 has totally replacable sensors which is and separately is, individually calibrated.
When you switch on the instrument with a sensor connected, the Swema 3000 shows the measu-
rements for the current sensor.
When you have or for the first time connected a sensor the instrument does always choose the
default program to the current sensor. Furthermore, the Swema 3000 reads in the calibration and
only does the program available which is current for this particular sensor. Swema 3000 has a
memory for the two last probe types and the intern probe. It remembers which setting you lastly
used when you were using the probe with, in other words mode, time constant and the number of
decimals are the same as the last time you used the probe.
Switch�between�built-in�and�extern�sensor:
With the Swema 3000md/mdH+ it is able to change bet-
ween an extern built-in sensor and the built-in differencial
pressure sensor with the EXT/INT-key�(Function-key to
the far left, see image to the right).
When you are using the built-in differencial pressure
sensor is ”EXT.” going to be shown on the display, where
it means that if you would like to measure with the extern
connected sensor should the EXT-key be pressed. The
key will now change name to ”INT.” (Intern), press it to
measure with the built-in differencial pressure sensor.
If an extern sensor is connected, the instrument will always go to its measuring position at start-up,
if you would like to come to the built-in differencial pressure sensor directly, the extern sensor has
to be connected before the start of the instrument.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 6
Measure with Swema 3000:
If a sensor is connected to the Swema 3000, it will always be directed to
mode after start-up of the instrument. In the mode (i.e. that you are not
inside one of the menus to change setting) it is shown the actual mode from
the sensor on the display.
By pressing the ENTER-key a measurement can start and depending on
which installed mode, it will save the mode to a temporarily memory, a cal-
culation is made or a start of a logging of measurement values.
At mode where measure points are collected, the Swema 3000 shows
mean-, max-, min-value and total measurement points collected. To take
another measurement to e.g. see mean calculation press ENTER again.
Modes:
Swema 3000 helps you to calculate and work in the correct way when you use the different mo-
des. The differemt sensors that exists to Swema 3000 have sometimes their own modes, e.g. for
the differencial pressure sensor the measurement mode DPF (Differencial Pressure air Flow).
Swema 3000 knows which sensor connected and suits the modes so it is suitable to that sensor
type, e.g. DPF is not (Differencial Pressure air Flow) available for a hot wire anemometer.
There are different general modes that you can use in every single sensor: AP (not SWA 03), AS
and LOG.
Function-buttons:
The lower part of the display is divided into 3 squares, and precisely under these squares does 3
function-buttons exist. The function of the buttons depends and this is described in the 3 squares
above.
Change setting and movements in the Menus
To change mode or setting press Menu1 (Function key to the right in mode). Swema 3000 has 3
different menus for different settings. Use UP/DOWN-arrows to move in the Menus and to switch
between the alternatives you have if would like to change something. If something should be chan-
ged press ENTER, right ARROW or SELECT (right Function-button). Use UP/DOWN arrows to
change/set alternative. If you would like to reset main settings, press MAIN (middle Function-but-
ton). When your setting is complete press ENTER, left ARROW or EXIT (left Function button). To
come back to measure mode press EXIT.
Swema 3000 in measu-
rement mode.
Save measurements:
When all the measurement values have been collected, you can choose to save them (press
SAVE) or delete the measurement (press CLEAR).
If it saves the instrument’s measure will the measurement be stored in the first available memory
place in ”Note Book”. Swema 3000 gives a short signal and shows which memory place the mea-
surement was saved. (see Note�Book,�Loggings�and�Files for more information).
OBS!�If�Swema�3000d/md/mdH+,�with�built-in�barometer�and�thermo�coupple�will�the�values�
be�in�mean,�max�&�min�calculated�from�what�the�temperature�and�the�barometer�were�at�
every�single�measurement�point.�If�you�later�save�the�measurement�values,�only�the�mean�
will�be�saved�from�the�temperature�and�the�air�pressure.�The�mean�is�used�later�to�correct�
the�values�who�is�shown�in�the�protocol.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 7
4. MENU 1
Time�constant, in other words the decrease or the inertia on
the instrument (see Time�constant�and�Filter for more infor-
mation).
Atmospheric�pressure�is used when Swema 3000 does cal-
culations for air velocity and air flow.
Swema 3000 is available in three different models, Swema
3000d with a built-in barometer, Swema 3000md with built-in
barometer and differential pressure probe or Swema 3000
without barometer and differential pressure sensor.
In Swema 3000, the atmospheric pressure can be set manually
by moving the marker to ”Atmos.P” with the UP/DOWN-arrow
key. Press ENTER or SET and set the atmospheric pressure
with the UP/DOWN-arrow and with the LEFT/RIGHT-arrow key.
Confirm your choice with ENTER or EXIT.
Swema 3000md / mdH+ automatically compensates for the
air density. To turn of the automatically compensation for the
barometric pressure and set it manually set ”Atmos.P” to ”M”
(Manual) instead of ”A” (Automatic).
Temperature is used when Swema 3000 does calculations for
air velocity and air flow at calulation with a differencial pressu-
re sensor. Swema 3000d/md/mdH+ has the ability to connect
an extra temperature sensor (termometer sensor type-K).
If a termometer sensor is connected does it reach the built-in
differencial pressure sensor in Swema 3000md/mdH+. It is
used so it compensates Swema 3000 automatically for the
temperature the termometer sensor measure.
OBS! The Termometer�sensor�must�be�connected�at�start-
up�of�the�instrument.�If�it�is�not�connect�at�start-up,�the�
instrument�will�not�find�the�termometer�sensor.�If�the�ter-
mometer�sensor�is�disconnected�while�the�instrument�is�
on,�the�temperature�will�show�-270°C�until�the�instrument�
is�restarted�and�the�risk�of�error�compensation�occurs.
If no termometer sensor is connected or at calculating with
Swema 3000 (has no termoelement connector) the tempera-
ture can be manually installed by moving the mark to ”Temp.”
with the UP/DOWN-arrows. Press ENTER or SELECT and
choose temperature with the arrows. Confirm your choice with
ENTER or EXIT.
OBS!�If�a�sensor�with�an�own�temperature�sensor�is�con-
nected�(hot�wire�anemometer,�air�flow�probe,�tensile�
sensor,�and�relative�humidity�&�temperature�sensor)�it�
will always use the temperature as the sensor measures
for�compensations.�If�a�thermo�coupple�is�connected�or�
the�temperature�is�changed�manually,�it�will�not�affect�the�
measurement result.
Highlight the parameter you want to
change and press Enter or SET.
Change the parameter with the arrow keys
and press Enter or EXIT to confirm.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 8
Menu 2
Swema Twin
ON or OFF
Only when you us SwemaTwin, set ON at
your master unit
Communication
USB or RS232
Communicate via USB (cable 764.430) or
RS232 (cable 759.030) to your PC.
Baud Rate
2400, 4800, 9600, 19200 or 57600
Normally 4800 for SwemaTwin, 9600 for
PC-transfer (RS232 cable).
Add Flow
ON or OFF
If set to ON. Swema 3000 will add the
flow from each measurement in one file
and present a total flow.
Protocol
SHORT or LONG
Here you specify if you want a long or
short protocol (note) at PC-printout.
1�Unit�Decimal
0, 1, 2, 3 or 4, Select number of decimals
for the big digits. The number of decimal
on the display will be acording to what
you choose here until a fifth digit is
needed. The display can only show four
big digits on the same row at the same
time. Because of this one decimal will
disapper. When saving a measured
value the number of decimal will be
the same as shown on the display.
2�Unit�Decimal
0, 1 or 2, Select number of decimals for
the small digits
Auto Zero
ON or OFF
When you have a SWA 10 pressure probe
connected or uses a Swema 3000md you
can choose automatic zeroing when you
collect values.
K2�Factor
ON or OFF
Set ON if you want Swema 3000 to calcu-
late with a k2-factor. See APF mode.
ON:
Flow = air velocity * k2 * area
OFF: Flow = air velocity * area
Exponent
Change exponent (ε) in the formula for K
factor measurement. q = k • ∆Pε
Move in the menu with the up/down arrow
keys. Press Enter, Set or right arrow key to
select.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 9
Menu 3
Time/Date Set clock/date
Adjust�Clock�����������Set a value to compensate the clock error
Auto off Set the automatic shut down time
Unit System
SI or US
Set which units you want to use Metric
(SI) or American (US).
Contrast Set display constast
Print Out
Select if you want comma or point separa-
tion at PC-print out. Excel uses either
comma or point.
Language
English, German, Swedish, Finnish,
French, Danish, Norwegian, Dutch or
Polish.
Set the language you wuold like to use.
Change with the up/down arrow keys.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 10
The different probes for Swema 3000
Hot Wire Anemometers
SWA 31 or SWA 31E. Ø 8...10mm, 66 cm long,
SWA 31E extendable up to 116 cm.
0...10 m/s (option 10...30 m/s) and temperature -20...80°C.
Possible measuring modes: AP, APF, AS, ASF, LOG and LOGP.
Extend the probe to the desired length.
Both holes must be clear for air to pass.
OBS!Do�not�pull�the�cable�to�close�
probe.
Orientation advice: Turn the arrow so
that the mark on the bottom part
of the telescope stem points in the
same direction as the arrow.
The air velocity measurement can be
influenced by how the holes are
located in the flow. See graph.
Differential pressure
SWA 07: ±7000Pa,
SWA 10 and Swema 3000md: -100...1500Pa.
SWA 10 has a built in valve that automatically zero checks the pressure.
Possible measuring modes: APF (with pito static pipe), DPF (k-factor),
AP, AS and LOG.
It is important to show zero pressure at the actual zero pressure.
Otherwise there will be an offset influencing all measurements.
The differential pressure probes SWA 07 and 10 and Swema 3000md can be zeroed to display
zero when no pressure is connected. Press the ZERO button when no pressure is connected.
The probe is zeroed for this position. Do not change position when measuring.
Auto Zero ON with SWA 10 or Swema 3000md/mdH+
SWA 10 and Swema 3000md has an inbuilt zero valve. Auto Zero is set to ON by default.
By the built in valve the zero pressure point is automatically checked every time you take a
measurement by pressing ”ENTER”. When working in this way you never need to calibrate zero
manually. Warning: Zeroing may take long time: time constant + 3 sec. If a 4 second time constant
is selected it will take 7 seconds to take a measurement.
Auto Zero OFF with SWA 10 or Swema 3000md
With Auto zero Off no zero check is done automatically. The measurement takes shorter time. Due
to very stable zero point zero checking is sometimes not needed.
See Menu2 to select Auto Zero ON or OFF
SWA 10 has a small position dependence of ±0,3Pa. When you use Auto Zero On and hold the
SWA 10 in firm position during zero point checking this error disappears.
The SWA 07 is sensitive to tilting in the longitudinal direction, a 90° tilt producing a change of 4-5
Pa. It is recomended to use the SWA 07 with the magnet holder Art. No. 760.020. SWA 07 is sen-
sitive for temperature schocks. Avoid holding your hand on the SWA 07. Temperature changes of
this type will cause zero drift that may take 1-2 minutes to dissappear. The temperature compen-
sation works for slow changes. It is possible to log over several hours with minimal zero drift.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 11
Flow�captures
SwemaFlow 65: 2...65 l/s,
SwemaFlow 125: 2...125 l/s and
SwemaFlow 2000: 4...900 l/s.
Possible measuring modes: AF, BP (only with SWF 125), AS, LOG and AP.
Draught probe
SWA 03: 0,05...3,0 m/s (omni directional) and 10...34°C.
SWA 03 fulfils ISO 7726.
Possible measuring modes: CO, AS, LOG and LOGP.
Relative humidity and temperature
All probes 0....100%RH
Temperature: HygroClip2-S -40…..200°C depending on sensor
Possible measuring modes: AP, AS and LOG.
Temperature
Black globe, SWA 53, SWT 315, SWT 215 and with temperature handle SWA 25 also SWT 14, 18,
22, 28, 39, 50, 51 and 53.
-50°C to 280°C depending on probe.
Possible measuring modes: AP, AS and LOG.
CO2
Connect the Airtest to save and log carbon dioxide values.
Possible measuring modes: AP, AS and LOG.
Radio/BlueTooth�modem�for�balancing�of�ventilation
SwemaTwin transfers measured values on the reference valve from one Swema 3000 to another
through radio/BlueTooth modem or 40 meter cable. The flow relation between them is displayed,
which makes adjustment according to the proportional method an easy task for just one person.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 12
The different modes used in Swema 3000
Choose mode by pressing the MENU1 and move the marker to ”Mode” with the UP/DOWN arrow
key. Press ENTER, SET or right ARROW and choose mode with the UP/DOWN arrows. Confirm
your choice with ENTER, EXIT or LEFT. Set the parameter for the current modes in the same way.
Press EXIT to start measuring.
APF (Average Point air Flow) Measured points are taken with ENTER Average, max, min and
measured points are showed on the display. The Swema 3000 calculates the air flow in l/s or m3/h.
Enter the diameter, height x width or area direct. If you choose to indicate the height and width or
diameter of the duct, the Swema 3000 calculates the effective area = the actual area times the
duct factor k2 in accordance with the recommended measurement methods. The duct factor can
be turned off in MENU2. Use the APF mode for measuring the flow in ducts.
DPF (Differential Pressure air Flow). Available with a differntial pressure probe SWA 10 or SWA
07 or with inbuilt manometer on Swema 3000md. The flow in the measurement of pressure drop
across devices is directly obtained in l/s or m3/h.
Insert k- factor, and the Swema 3000 calculates the air flow according to the formula: q = k sqrt(∆P).
The specific k-factor is supplied by the manufacturer of (exhaust and supply) ventilation valves.
AF (Average air Flow) Only available with SwemaFlow 2000, 125 and 65. Average Flow is cal-
culated during selectable measuring time.
BP (Back pressure (air flow)) Only available with SwemaFlow 125. This mode is for measurement
over supply and exhaust valves to compensate the possible drop in air flow created by the flow
capture. BP mode calculates the real flow - the flow not infuenced by the flow capture.
AP (Average Point). By using the ENTER button the average is formed from measurements with
any probe (except SWA03). Average, max, min and number of measured points are shown.
AS (Auto Sampling). The Swema 3000 continuesly collects measured values at the interval set by
the Sampling Rate. Use AS mode for example if you want to measure average velocity, max, min,
and standard deviation at a point.
ASF (Auto Sampling air Flow). Used with SWA 31 to measure in l/s or m3/h through valves.
Sweep over openings in laminar flow hoods/cabinet and over rectangular exhaust and supply
ventilation grilles. Select and enter the height x width or area direct into the Swema 3000.
ASF does not calculte the are with a k2-reduction - ASF is not intended for measuring in ducts.
There we recommend to use APF instead.
CO (Comfort draught of air). Only available with the omni directional draught probe, SWA 03.
CO mode measures average velocity, temperature and standard deviation over a selectable period
of time. DR (Draught Rating) is presented in the automatic saved note. The DR indicates the per-
centage of people that would find the draught unpleasant. The DR is based on experiments con-
ducted at the Technical University in Copenhagen, directed by Professor Fanger. DR is included
as a measure of undesirable air movements in the ISO 7730 standard adopted for indoor climates.
For a complete ISO7730 measurement use the SwemaMultipoint program.
LOG/LOGP Collects readings over a longer time period. Select interval and time constant for LOG.
LOGP is especially developed to be used with SWA 03 draught probe to present the draught rate
(ISO 7730) but can be used for other probes aswell. During a ”Measure Time” the instrument con-
tinuesly measures with the selected Time Constant. When the measure time has passed it stops
and starts again with a new ”Measure Time” at the choosen Protocol interval.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 13
Measures the actual values of the connected probe. Calcula-
tes avgerage and display Max and Min.
What different sensors measures in AP
Differencial�pressure�sensor:
Speed (m/s) & Differencial pressure (Pa). Speed measure-
ment requires that a PST is connected.
Hot wire anemometer:
Speed (m/s) & Temperature (°C)
Air�flow�probe:
Air flow (l/s or m3/h) & Temperature (°C)
Temperature sensor:
Temperature (°C)
Humidity sensor:
Relative humidity (%RF) & Temperature (°C)
For relative humidity sensor dew point is also calculated (°C)
and water contentl (g water / kg dry air) if measure value is
taken (ENTER).
Carbondioxide sensor:
Carbondioxide level (CO2)
Setting for measuring with AP
Time�constant:
2s is recommended as standard. See Time�constant�and�
Filter for more information.
Atmos. P:
The atmospheric pressure affects the result for following sen-
sors:
• Differencial pressure sensor (speed calculations)
• Hot wire anemometer (speed)
• Air flow probe (air flow)
Temperature:
This temperature only affects the differencial pressure sensor
(the speed calculation). For other sensors where temperature
is affecting the measurement results, is the sensor’s own tem-
perature sensor used.
8.1. AP (Average Point)
Possible with all probes except SWA 03.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the up/
down arrow key. Press ENTER or SET and
choose mode with the up/down arrow key.
Confirm your choice with ENTER or EXIT.
Set the parameters and press EXIT to start
measuring.
When measuring, collect values with the
enter button. When values are collected
the display will show average-, maximum-,
minimum-values and number of measure-
ments.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 14
Measuring with APF (Average Point air Flow)
Possible probes are: SWA 31, SWA 31E or SWA 07 or SWA 10 with pito static pipe or Swema 3000md.
Use the APF mode for measuring the flow in ducts.
Swema 3000 calculates the flow in l/s or m3/h by multiplying the
air velocity with the duct area.
OBS!�At�delivery�Swema�3000�is�installed�with�K2-factors�
ON.�The�K2-factor�reduces�the�channel�area�at�measure-
ment�in�channels�with�APF.
Calculation�of�Flow: Air flow = air velocity x k2 x area. At calcla-
tion of flow at measurement in channel, the flow should reduce
with a k2-factor according to the recomended measure methods.
(T09 & NBI-report) due to the air is still alongside the channel
walls. Set the k2-factor to On in Menu2 in Swema 3000 for an
automatic compensation. Set it OFF if you would like to have
some reduce of the channel.
For air velocity measurements connect a Pito static pipe with
differential pressure connections. Connect the middle Pito static
pipe to the plus on the meter and the side connection to the mi-
nus. Swema 3000 calculates the air velocity with the formula:
Velocity = sqrt (2 ∆P /ρ)
∆P= dynamic pressure =total pressure - static pressure (Pa)
ρ= density of air = 1,293 x (B x 273)/(1013 x (273 + t)) (kg/m3)
B = barometric pressure (calculated standard value 1013hPa)
t = Air temperature ºC (calculated standard value 20ºC)
Setting for measuring with APF:
Time Constant:
2s recommended as standard. See Time�constant�and�Filter
for more information.
Diameter (Ø):
Set the diameter of the duct you want to measure. Move the
marker to ”Ø” with the up/down arrow key. Press ENTER or SET
and choose the diameter. Choose among standard diameters
with the up / down arrow key. To set the diameter to your choice
press EDIT and change with the arrow keys. Press EXIT or EN-
TER to confirm.
Height x Width (H x W):
Set the height and width of the duct you want to measure.
Move the marker to ”H x W” with the up/down arrow key. Press
ENTER or SET and choose height with the arrow keys. Press
ENTER or OK and set the width with the arrow keys.
Press ENTER or EXIT to confirm.
Choose mode by pressing the MENU1-
KEY and move the marker to ”Mode” with
the up/down arrow key. Press ENTER or
SET and choose mode with the up/down
arrow key. Confirm with EXIT or ENTER.
Set the parameters and press EXIT to
start measuring.
When measuring, collect values with the
ENTER button. When values are col-
lected the display will show average-,
maximum-, minimum-values and number
of measurements.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 15
Area:
To measure in a channel with free installed area move the
marker to Area and press ENTER. Desirable area can now
be installed with the unit m2. OBS! At measurement with free
installed area no K2 reduction occurs.
Unit:
Select which unit you would like to use Choose between l/s or
m3/h.
Atmosphere: The atmospheric pressure affects the measure-
ment result.
Temperature: This temperature affects the measurement
result at measurement with a differencial pressure sensor
and a PST. At measurement with a hot wire anemometer the
temperature is used as it has been calculated from the sensor
instead.
Measuring
When all parameters are installed, press EXIT to come back
to mode. Swema 3000 shows choosen Ø, HxW or Area on the
bottom of the display.
At calculation with pressure sensor (PST) pressure and flow
are shown.
At measurement with a hot wire anemometer, measured tem-
perature and flow are shown.
Collect measurement values with the ENTER-button. When
measurement values are collected Swema 3000 shows mean-
, max-, min-value and total measure points. When all measure
points are collected you can choose if you would like to save
or delete the measure.
When all measure values are collected
Swema 3000 shows mean-, max-, min-
value och total measure points. Choose if
you wold like to save or delete the mea-
sure.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 16
DPF is used to measure flows over diffusers and orifice plates
with the decompression method. Then the diffuser’s K-factor
is being used and you put it in the Swema 3000 to give a flow
directly to the display. Swema 3000 calculates the flow accor-
ding to the formula:
q�=�k�•�√∆P�
The K-factor has been gotten from the supplier of the diffuser.
Choose always a K-factor which is used to calculate l/s, later
you can choose to show m3/h instead. Here Swema 3000
calculates in m3/h itself.
OBS!�If�the�K-factor�for�the�diffuser�is�being�used�to�cal-
culate�m3/h�the�K-factor�has�to�be�divided�with�3.6�before�
it�is�inputed�in�the�Swema�3000.�If�not,�the�flow�value�will�
show 3.6 times bigger.
Settings for measurement with DPF
Time Constant:
2s is recommended as standard. See Time Constant and
Filter for more information.
K-factor:
Set the K-factor you would like the Swema 3000 should cal-
culate with. Swema 3000 has a memory for 20 K-factors.
Choose which memory place (1-20) by using the UP/DOWN
arrows. Press SET to change the K-facor. Change with the
arrows.
Unit:
Choose which unit you would like to use. Choose between l/s
or m3/h.
Atmos. P: The atmospheric pressure affects the measure
result.
Temperatur: This temperature affects the measure result.
Measuring
When all parameters are installed press EXIT to come to
mode. Swema 3000 shows choosen K-factor, pressure and
flow. In mode you can choose between 20 different K-factors
that you have added in the memory with the help of the UP/
DOWN arrows.
To reset the pressure sensor manually press ZERO at mode.
For automatic reset see Menu2.
Collect measure values with ENTER. When these are collec-
ted, Swema 3000 will show mean-, max-, min-values and total
measure points. When all measure values are collected, you
can choose if you would like to save or delete the measure.
8.3. DPF (Differential�Pressure�air�Flow)�-�Air�Flow�with�K-factor
DPF is available with a differencial pressure sensor.
When measuring, collect values with the
enter button. When values are collected
the display will show average-, maximum-,
minimum-values and number of measure-
ments.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the
up/down arrow key. Press ENTER or SET
and choose mode with the up/down arrow
key. Confirm with EXIT or the ENTER. Set
the parameters and press EXIT to start
measuring.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 17
DPK is available with a differencial pressure sensor.
DPK is used to measure flows over diffusers and orifice plates
with the decompression method. Then the diffusers K-factor
is being used and you put it in the Swema 3000 to give a flow
directly to the display. Swema 3000 calculates the flow accor-
ding to the formula:
k�=�q�/�√∆P�
OBS!�The�K-factor�shown�on�the�display�at�DPK�measure-
ment is always based on a reslut in l/s. If m3/h is installed
as�an�unit�will�the�k-factor�be�calculated�on�which�instal-
led glow equivalant in l/s.
Settings�for�measurement�with�DPK
Time Constant:
2s is recommended as standard. See Time Constant and
Filter for more information.
Flow:
Set the flow you would like Swema 3000 should calculate a
k-factor for. Swema 3000 has a memory for 20 flow values.
Choose which memory place (1-20) you would like to choose
by using the UP/DOWN arrows. Press EDIT to change the
flows value. Change with the arrows.
Unit:
Choose which unit (l/s eller m3/h) as installed flow has. Even
though the flow is written in as m3/h will the k-factor be cal-
culated for the inscribed m3/h flow which is equivalent in l/s.
Atmos. P: The atmospheric pressure affects the measure
result.
Temperature: This temperature affects the measure result.
Measuring
When all parameters are installed press EXIT to come to
mode. Swema 3000 shows choosen K-factor, pressure and
flow. In mode you can choose between 20 different K-factors
that you have added in the memory with the help of the UP/
DOWN arrows.
To reset the pressure senor manually press ZERO at mode.
For automatic reset see Menu2.
8.4.� DPK�(Differential�Pressure�K-faktor) -�K-faktor�with�Air�flow
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 18
8.5 AF (Average�Flow)�-�Air�flow�with�probe
AF is available with air flow probes.
If you use a SwemaFlow 125, we firstly recommend to mea-
sure with the mode BP (Back Pressure) to compensate for the
pressure drop over the probe.
The mean flow is calculated under choosen time interval och
is shown on the display in l/s or m3/h. (time interval = Delay +
Measure Time).
Settings for measuring with AP
Start Delay:
Set the time of delay before measuring, 2 seconds are recom-
mended to stablilitize the flow before measuring.
Sampling Time:
Set the time you would like to averaging.
Flow�factor:
It is possible to multiply the flow with a flow factor. With flow
factor = 1.00 will not the flow change. Warning: The Calibra-
tion is only valid at Flow Factor = 1.
Another flow factor is being used to compensate for e.g. lea-
kage.
Unit:
Choose which unit you would like to use. Choose l/s or m3/h.
Atmos. P: The atmospheric pressure affects the measure
result.
Temperature: This temperature does not affect the measure
result due to the temperature is measured form the sensor
instead.
Measuring
When all parameters are installed press EXIT to come to
mode.
Collect measure values with ENTER or the button on Swema-
Flow 125/2000. When the measure values are collected does
Swema 3000 show mean-, max-, min-value and standard
deviation. When all measure values are collected, you can
choose if you would like to save or delete the measure.
To delete, press CLEAR. To save, press SAVE or hold the but-
ton on the SwemaFlow 125/2000.
When measuring, Start the measuring with
the enter button. Then you can choose if
you want to clear or save your measure-
ment.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the up/
down arrow key. Press ENTER or SET and
choose mode with the up/down arrow key.
Confirm with EXIT or the ENTER.
Set the parameters and press EXIT to start
measuring.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 19
BP is available with SwemaFlow 125 or 125D.
At some air flow measurements with probes (primarly with the
low pressure drops) is it necessary to correct the measure
values for the restrictor of the diffuser that the probe creates.
SwemaFlow 125/D can do this correction for you. By mea-
suring 2 times with and without throttle ring, Swema 3000
calculates the flow witout restricor i.e. the flow from the diffu-
ser without probe. In the same way as in the mode AF, is the
mode BP used averaging under a choosen time period.
Settings for measuring with BP
Start Delay:
Set the time of delay before measuring, 2 seconds are recom-
mended to stabilitize the flow before measuring.
Sampling Time: Set the time you would like to averaging.
Unit: Choose which unit you would like to use. Choose bet-
ween l/s or m3/h.
Flow�Factor:
It is possible to multiply the flow with a flow factor. With Flow
Factor = 1.00 will not the flow change. Warning: The Calibra-
tion is only valid at Flow Factor = 1.
Another flow factor is being used to compensate for e.g. lea-
kage.
Unit: Choose which unit you would like to use. Choose l/s or
m3/h.
Atmos. P: The atmospheric pressure affects the measure
result.
Temperature: This temperature does not affect the measure
result due to the temperature is measured form the sensor
instead.
8.6 BP (Back�Pressure)�-�Air�flow�with�compensated�probe
Measuring
The display shows PO 1. Place the throttle ring on the mea-
sure unit and set the probe over the diffuser. Press ENTER to
start averaging nr. 1.
When ”Point 1” is measured a beep sounds and the display
shows PO 2. In a minute you have to measure ”Point 2” wit-
hout the throttle ring, otherwise the instrument returns to ”Point
1”. Remove the throttle ring and place the probe over the dif-
fuser again. Press ENTER to start averaging nr. 2.
It will be successful without the throttle ring and take the se-
cond measure with throttle ring.
The display shows the actual value ”True” as well as measure
1 & 2.
If the measure value blinks it is to big difference between point
1 and 2 and the result is not trustworthy.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the
up/down arrow key. Press ENTER or SET
and choose mode with the up/down arrow
key. Confirm with EXIT or the ENTER..
Set the parameters and press Exit to start
measuring.
The display will show PO 1.Start with the
throttle ring on and press Enter to collect
the first value,
When ready with the first value the display
will show PO 2.
Remove the throttle ring and collect the
second value by pressing Enter. The but-
ton on SwemaFlow 125 can also be used
as a Enter-button. A long press will save a
measurement.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 20
After PO 2 is measured will Swema 3000 calculate the actual
value. On the display it says True, Max and Min. Max without
throttle ring and Min is with throttle ring and True is the actual
value..
Choose if you would like to save your measurement. To delete,
press CLEAR. To save, press SAVE or hold the button on the
SwemaFlow 125 / 2000.
Placement�of�throttle�ring
At measurement with a throttle ring should this always be
placed after the measure wires with respect on the air flow,
i.e. the air should firstly hit the wires, subsequently the throttle
ring.
After PO 2 is measured the display will
calculate the true value and show it on the
display. The display will also show point 1
& 2. Max is without the ring and Min is with
the ring. Then you can choose if you want
to clear or save your measurement.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 21
Swema 3000 automatically collect measure values. AS does
not save all the values instead mean-, max- & min-value is be-
ing calculated. Use AS if you e.g. would like to measure mean-
, max-, min- velocity and temperature and standard deviation
in one point.
Settings for measuring with AS
Sampling Rate:
The time Swema 3000 uses to collect measure values, avera-
ging and showing the value on the display. It is a floating mean
which is used i.e. if you have e.g. have a measure frequency
at 30s, Swema 3000 collects values 2 times/second within 30
seconds (60 measure values) and shows the mean of them
on the display. After 30 seconds the eldest value is replaced
by a new and a new mean is calculated and shown on the
display etc. In AS, Swema 3000 always collects the measure
values 2 times/second if a measure frequency is at 0.5 sec or
higher choosen. At a lower measure frequency than 0.5 sec
will Swema 3000 collect and update the display according to
choosen measure frequency.
Atmos. P:
The atmospheric pressure affects the measure result for the
following sensor:
• Differencial pressure sensor (Velocity calculation)
• Hot wire anemometer (Velocity)
• Air flow probe (Air flow)
• Tensile sensor (Velocity)
Temperature:
This temperature only affects the differencial pressure sensor
(velocity calculation). For other sensors where temperature
affects the measure result is the sensors own temperature
sensor used.
Measuring
Start measurements with ENTER. A second counter for ac-
counting how long time the measurements has been going
on will be shown in the lower left corner on the display. Under
the measurement are mean, max, min & standard deviation
shown for the collected measure values. Stop the measure-
ment with ENTER. When all the measurement values have
been collected you can choose to save or delete the measure-
ment.
8.7 AS (Auto Sampling) - Sampling of measure values
AS is available to all sensors.
Start and stop the sampling by pressing
Enter. When the sampling are done you
can choose if you want to clear or save
your measurement.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the
up/down arrow key. Press ENTER or SET
and choose mode with the up/down arrow
key. Confirm your choice with ENTER or
EXIT. Set the parameters and press Exit to
start measuring.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 22
Like AS, but Swema 3000 calculates the flow in l/s or m3/h.
Enter the area as height x width or as area directly. In mode
ASF does Swema 3000 calculate the area without channel
reduction (K2-reduction) because it is not made for cannel
measurement. Use ASF e.g. over a intake grille or the opening
to a fume.
Settings for measuring with ASF
Sampling Rate: Same as AS (see AS for more information).
H x W: Set the height and width on the channel you would like
to measure.
Area: Set the area directly.
Unit: Choose which unit you would like to use. Choose bet-
ween l/s or m3/h.
Atmos. P: The atmospheric pressure affects the measure
result.
Temperature: This temperature does not affect the measure
result where the temperature is measured from the sensor
instead.
Measuring
Start measurements with ENTER. A second counter for ac-
counting how long time the measurements has been going on
will be shown in the lower left corner on the display. Under the
measurement are mean, max and min shown for the collected
measure values. Stop the measurement with ENTER. When
all the measurement values are collected, you are able to
save or delete the measurement .
8.8 ASF (Auto Sampling air Flow) -�Sampling�with�air�flow�calculation
ASF is available with hot wire anemometers.
Start and stop the auto sampling flow by
pressing Enter.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the
up/down arrow key. Press ENTER or SET
and choose mode with the up/down arrow
key. Confirm your choice with ENTER or
EXIT. Set the parameters and press Exit to
start measuring.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 23
By slowly sweeping (traversing) the sensor above the surface. e.g. an intake grille or the opening
to a fume, you measure the total flow. Repeat the measurement until you get the same measure
values so that you learn the technique.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 24
The CO mode measures mean velocity, temperature and
standard deviation over three minutes (chooseable time pe-
riod). When the measurement is saved, or at print to PC, does
Swema 3000 calculate DR (Tensile index). DR indicates how
many percent which experiences a tensile. The tensile index is
based on an experiment at the Technical University of Den-
mark in Copenhagen, under the lead of Professor Fanger. DR
includes as dimensions on undesirable air movements in the
standard ISO 7730 for interior climate.
Settings for measuring with CO
Display Time:
The display can be updated with the interval 0,5, 0,25, or 0,1
seconds.
Measure Time:
Here you set over how long time span you would like to av-
eraging. The measure values always collects internally with a
frequency of 0.1s. Of these measure values are mean, max,
min, standard deviation and tensile index calculated from. Ac-
cording to ISO 7730 should 3min be usen as measure time.
Atmos. P: The atmospheric pressure affects the measure
value.
Temperature: This temperature does not affect the measure
result where the temperature has been measured from the
sensor instead.
Measuring
Start the measurement with ENTER. Swema 3000 measures
under a choosen measure time and saves the measurement
on the first available memory place in ”Note Book”. Swema
3000 gives also a short sound and shows the memory place
on the display in some seconds. To see tensile index, press
MENU1 and mark ”Note Book” and press ENTER.
8.9 CO (Comfort)�-�Tensile�index�calculation
CO is only available with the sensor tensile sensor SWA 03.
The measurment is automatically saved in
the note book. To see the draft rate, press
the MENU-key and move the marker to
Note Book and press enter.
Choose mode by pressing the MENU1-
KEY and move the marker to ”Mode” with
the up/down arrow key. Press ENTER or
SET and choose mode with the up/down
arrow key. Confirm your choice with
ENTER or EXIT. Set the parameters and
press EXIT to start measuring.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 25
Collecting measure values according to choosen interval. Use
LOG mode to measure under a longer time span (E.g. varia-
tions in air flow, temperature or pressure under 24 hours). Use
mains adapter if you would like to log more than 12 hours a
row.
Settings for measuring with LOG
Time Constant:
Set time constant i.e. the decrease or slowness on the instru-
ment (see Time Constant and Filter for more information).
Interval:
Set how often Swema 3000 should save a new measure va-
lue. The measure mode who has been saved is the value that
is going to be shown at the display at the middle point.
At LOG with SWA 10 or the built-in differencial pressure
sensor the pressure resets between the log points. Interval
more is 10 sec & ”Auto Reset” turned to ON requires for this.
If faster interval than 10s is desired the ”Auto Reset” has to
be turned to Off, no reset of the pressure sensor will then be
made during the logging.
Tips! If you are intrested in seeing a mean for the interval
instead of the instantaneous measure value which is shown
on the display at the end of the interval (then a log point will
be saved) then set the time constant to the same value as the
interval.
E.g. ”Time Constant” & ”Interval” are set to 15s. A time con-
stant at 15s means that the measure value on the display is a
mean over the latest 15 seconds which when the loggings are
saved gives you a mean during the whole interval.
Atmos. P: The atmospheric pressure affects the measure
result at loggings with hit wire anemometers (velocity), air flow
probes (air flow) and tensile sensors (velocity).
Temperature: This temperature does not affect the measure
result. If the thermo couple is connected (only Swema 3000d/
md/mdH+ has this ability) and you log diffencial pressure, the
temperature measured with the thermo couple will also be log-
ged.
Log�Book
Start and stop the logging with ENTER. Swema 3000 logs
under choosen time span and saves the logged measure
values in a new file. When the logging is done press ENTER
or SAVE, Swema 3000 gives you a short signal and shows
during some second the file number on the display. To see the
latest logged values go to ”Log Book”. To see other logging
files could log file be choosen in ”Files”. If an interval is instal-
led on 10 seconds or more, will the time be shown for the next
logging on the display.
8.10 LOG - Loggning of measure values
LOG is available with all sensors.
Choose mode by pressing the MENU1-KEY
and move the marker to ”Mode” with the up/
down arrow key. Press ENTER or SET and
choose mode with the Up/down arrow key.
Confirm your choice with ENTER or EXIT.
Set the parameters and press Exit to go to
measuring position.
Start and stop the log with the ENTER-
button.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 26
Unlike from LOG you get in LOGP not only individual measure
values without a whole serie with values who have been com-
piled in a protocol containing max, min, mean, standard devia-
tion etc. You choose how long every serie should be (Measure
Time) and how often Swema 3000 should do a measure serie
(Protocol interval).
Settings for measuring with LOGP
Time Constant, i.e. the decrease or slowness on the instru-
ment (see Time Constant and Filter for more information).
Measure Time:
The length on the measure series. Swema 3000 calculates la-
ter standard deviation standardavvikelse, max, min and med-
elvärde during the measure time.
Protocol�Interval:
How often a new measure serie starts. If ”Prot. Interval” is set
to the same time as ”Measure Time”, the measure series will
be logged continuously without pauses between them. If in-
stalled as the image on the right a measure serie will be done
during 5s followed by a paus of 10s (5s Measure Time + 10s
paus = 15s Protocol Intervals) before next measure seire wil
start to be measured.
Atmos. P: The atmospheric pressure will affect the measure
result for air velocity.
Temperature: This temperature only affects the differencial
pressure sensor (velocity calculation). For other sensors
where temperature affects the measurement results are the
sensor’s own temperature sensor being used.
Log�Book
Start and stop the logging with ENTER. Swema 3000 is log-
ging during a choosen time span and saves de logged mea-
sure values i a new file.
A second counter is shown in the bottom left corner on the
display during the measurement of the actual measure serie.
If it is installed a paus between the measure series will the text
LOGP be shown during that paus.
When the logging is done, press ENTER or SAVE, Swema
3000 gives a short signal and shows in some second the file
number on the display. If you save the logging before the first
serie is done, no data will be saved. To see the logged proto-
cols go to ”Log Book”. To see other logging protocols could log
file be choosen in ”Files”.
8.11 LOGP -�Logging�of�protocol
LOGP is available to differencial pressure sensor, hot wire anemometer & tensile sensor.
Start and stop the log with the ENTER-but-
ton.
In this example:
Each serie is set to 3 minutes. After one
serie is finished another one starts after 7
minutes.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 27
Mätprogram
Enhet 1
Enhet 2
AP Note 1
m/s
Pa
APF Note 1
l/s or m3/h
Pa
AS Note 1
m/s
Pa
DPF Note 2
l/s or m3/h
alt.
Pa (if k = 0)
Pa
���������DPK��
k-factor
Pa
LOG Note 3
Pa
-
LOGP
m/s
Pa
Note 1: Velocity/flow calculation requires that a PST is being used.
Note 2: If a k-factor is set to ”0.00” then only Pa will be shown on the display and then on Unit 1’s place
Note 3: If there is a Swema 3000md/mdH+ which has a barometer and a thermo coupple, the measure values will be
shown on the display requires that ”Atmos. P A” is set to ”A” (see Menu1) and that a thermo coupple is connected.
Mode
Unit 1
Unit 2
AP
m/s
°C
APF
l/s or m3/h
°C
AS
m/s
°C
ASF
l/s or m3/h
°C
LOG
m/s
°C
LOGP
m/s
°C
9. Measurement units showed for different measurement
Swema 3000 is able to show 2 measurement units at the same time on the display. The measu-
rement units varies depends on which sensor is being connected and which mode who has been
choosen. For most of the sensors is the direct measure value shown, but at measurement with a
differencial pressure sensor and a hot wire anemometer does it exist mode who shows calculated
values of the measured value of the sensor.
Differencial�pressure�sensor:
Hot wire anemometer:
Mode
Unit 1
Unit 2
All
l/s or m3/h
°C
Air�flow�probes:
Mode
Unit 1
Unit 2
All
m/s
°C
Tensile sensor:
Mode
Unit 1
Unit 2
All
°C
-
Temperature sensors:
Mode
Unit 1
Unit 2
All
%RF
°C
Realtive humidoty sensor:
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 28
10.� Note�Book,�Log�Book�and�Files
To access the Note Book or Log Book press ”MENU1”.
To access ”Note Book” select one of the following modes: AP,
APF, AS, ASF, DPF or CO.
To access ”Log Book” select mode LOG or LOGP.
Note�Book�/�Log�Book
To see the Notes (measurements) in the active file, move the mar-
ker to ”Note Book” or ”Log Book” with the UP/DOWN arrows.
Press Enter, Set or right arrow. Browse between your measu-
rements with the UP/DOWN arrow keys. Connect a PC-cable.
To transfer a note or log file to a PC just press Print. A long
press on print will transfer the complete log book or note book.
For software’s see SwemaTerminal and Swema Multipoint.
Erase with the ERASE-button. If you erase in ”Note Book” you
can choose to either erase the Note or the whole File, in ”Log
Book” you always erase the whole File.
Exit with the EXIT-button.
Files
The files are used if you would like to group your measure-
ments. In ”Files” you can choose to start a new file or investi-
gate the saved measurements in the different files. To access
files move the marker to ”Files” with the UP/DOWN arrows
and press ENTER or SELECT.
Switch between your files with UP/DOWN arrows. When the
file has been choosen press EXIT. Now, you are able to see
the measurements or loggings by going to ”Note Book” or ”Log
Book” as described above.
To create a new file for ”Note Book”, press ENTER when you
are in ”Files”. New files for ”Log Book” is created when a new
logging is done with LOG or LOGP.
To print a full file, press PRINT when you are in ”Files”. Switch
between your files with the UP/DOWN arrows. To print all files,
hold PRINT.
The device is able to delete all files or the last file. To delete
the last file, press ERASE when you are in the last file in ”Fi-
les”. Chooe ”OK” to delete the file or ”ALL” to delete all files. If
you choose ”OK” will the latest file be empty until new measu-
rements have been done, therefore the display will show ”New
empty file N”. Where N is the number of the deleted file. If you
would like to delete another file will file N disapear completely
and file N-1 will be empty.
Press EXIT to exit ”Files”.
Open your Note or Log files by moving the
marker to ”Note Book” or ”Log Book” with
the arrow keys and press Enter.
In the Note Book or Log Book:
Alter between your notes with UP/DOWN
arrow keys.
This is also how the note will look like on
the PC.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 29
SwemaTerminal 2 is a free PC-program that you can use to download and update the software of
Swema 3000 (visit www.swema.com or contact Swema for available updates). SwemaTerminal
2 as well as driver for USB-communication is delivered on CD together with Swema 3000 (even
available for download at www.swema.com).
Follow the instruction on the CO to follow how the program and the USB drive should be installed.
Subsequently, connect the USB-cable with the instrument Swema 3000 and the computer. Turn on
the instrument, open MENU2 and set ”Communication” on ”USB”. Subsequently, start the program
SwemaTerminal 2. Firstly, the contact has to be complete with Swema 3000 by clicking ”Search” in
SwemaTerminal 2, and ”Swema 3000” is shown in the box beneath. Press ”Open”, to the right of
the ”Search” button, and the text ”Device is ready” will now show that Swema 3000 is connected to
SwemaTerminal 2.
The saved measure values in Swema 3000 can now be written to the computer as described in
the chapter ”Note Book, Log Book and Files”. The data from the instrument is read and printed in
the bottom of the text box to the left. The text can now furtherly be read, copied to clipboard, or
cleared. To add, there is a possibilty to open earlier saved data. The data can also be edited in this
window.
The right part (sorts and graphs) of SwemaTerminal 2 is able to be used to sort Log-files and
SWA03/31 Logp-files. Clear the screen by clicking ”Clear input data”. Thereafter choose the file
you would like to use (either SWA Log, SWA03 Logp or SWA31 Logp). Primarly, print the Log- or
Logp-file who has been choosen and later press ”Sort”.
The button in bottom left corner ”Start Logging” instruct Swema 3000 to use the values on the
istrument’s display in the choosen interval, lowest interval possible is 10Hz (0,1s).
Press ”Enter” on the computer’s keyboard and the calibration protocol for the built-in probe to send
to the computer.
Press ”Space” on the computer’s keyboard and the shown values will be printed.
Press ”V” on the computer’s keyboard and the protocol for the instrument to print.
11. SwemaTerminal 2 (PC-Program)
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 30
12. Time Constant and Filter
Swema 3000 always measures continuously with a sampling freaquency at 40Hz. The time con-
stant is the decrease on the shown values.
All sensors at measurement in LOG and LOGP (does always apply for the pressure sensor)
The display shows the mean for the measured values during choosen time constant (rectangular
filter). The pressure sensors have a rectangular filter with under pressure of noise at low pressu-
res, i.e. noise reducement. At logging with LOG and LOGP will all probes get rectagular filter, the
pressure sensors will keep the noise reduction.
Noise reduction: For differencial pressure under 0.4Pa or time constant at 0.25 seconds, that the actual
time constant is 4 seconds.
Under 0.4Pa and a time constant between 0.5 - 8 seconds, that the actual time constant is 8 seconds.
All�sensors�when�you�measure�in�LOG�and�LOGP�(except�the�pressure�sensors)
The calculated values are filtrated (Bessel) before they are shown on the display. After a period on
a time constant will 90% be shown of the change against the end value. After 1.5 time constants will
99% be shown of the change against the end value. After 1.8 time constant will 99.9% be shown of the
change against the end value.
Generally
The Display’s value is updated twice a second except when the time constant is 0.25 or 0.1 se-
condswhen the display is updated with 0.25 respectively 0.1.
The showed values is also used to calculate mean, max, min, standard deviation in AP, APF, DPF,
LOG and LOGP mode.
In CO mode is always 0.1 second value used to do these types of calculations. (independent of
what the time constant is set)
13. Display view and saving of measured values
Small�&�Big�numbers
In mode can both big and small numbers be used. Big numbers are shown normally but someti-
mes the display is not enough, therefore small numbers are shown instead. Small numbers are
shown when the time constant is installed at 0.1 seconds as well as when the whole number does
not fit in, i.e. at a natural number with more than 5 significant figures or a negative whole number
with more than 4 significant figures.
Number�of�decimals
The number of decimals shown in the display is according to what choosen in Menu 2 until a fifth
number is needed, subsequently a decimal disappears becuase the display is only available to
show 4 numbers in the normal mode. At saving of the measure value, the same number of deci-
mals will be saved as it was during the showing.
Saving�of�measure�values�(APF�&�DPF)
If Swema 3000 with built-in barometer and thermo coupple (Swema 3000d & Swema 3000md) is
used will the values in mean, max & min be calculated correspondent for what the temperature
and the barometer were at every single measure point. Subsequently, you save the measure va-
lues, only will the mean of the temperature and the air pressure be saved. The mean values will be
later usen to correct the values that have been shown in the protocol.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 31
Swema 3000 instrument:
Instrument temperature:
0...+50°C
Memory capacity,
Note book - Log book:
approx. 1 600 notes or 14 000 pairs of
values or 20 000 singel values
Interchangeability accuracy:
Negligible in relation to accuracy of probes.
Digital Output:
RS232, send ”:” or ”Space”. Swema 3000 sends the
displayed value (big digits) or (big and small digits)
Transmitting rate max 10 times/second (Time constant 0.1s)
USB
Battery:
2 x 1,5V AA
Battery life with SWA 31 at 1 m/s:
13 hours with NiMH, 17 hours with alkaline
Use the 230V-adapter (764.610) for continuous operation.
Battery with backlight on:
5,5 hours with NiMH, 8,5 hours with alkaline
Instrument Calibration:
Recommended every 5 year
Only on Swema 3000d part no. 764.201 Barometer 600...1200hPa, ±2,5hPa
and Swema 3000dm part no. 764.202
Thermo couple Type K -270...1370°C
±0,3°C at -10...70°C
14.�Technical�Data
The uncertainty of measurement for each probe is stated below as the uncertainty for the probe to-
gether with a calibrated Swema 3000. The uncertainty is stated with coverage probability of 95%.
Included in the uncertainty for each probe is the uncertainty for Swema 3000, interchangeablity,
calibration, temperature dependence, hysteresis and repeatability.
The user should correct the measured values with the correction on the probe calibration protocol
to obtain stated accuracy.
Draught�probe,�SWA�03:
Measuring range of velocity
0,05...3,0 m/s at +10...+34°C
Measuring media
Non condensing, non moist air, <80%RH, non aggressive
gases
Accuracy (m/s) at 23°C:
±0,03 m/s at 0,05... 1,00 m/s
±3% read value at 1,00...3,00 m/s
at 10…34°C:
±0,04 m/s at 0,05... 1,00 m/s
±4%read value at 1,00...3,00 m/s
Response time of velocity sensor:
0,2 sec.
Measuring range of temperature:
+10...+40°C
Accuracy (°C):
±0,3°C at 20°C
±0,5°C at 10...+40°C
Probe Calibration:
Recommended every 6 months.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 32
Temperature sensor (SWT sensor):
Measuring range (sensor dependant):
-50...280°C
Interchangeabiliy accuracy:
max ±0.1°C
Sensors at 20°C:
1DIN 43760 ca ±0.4°C or 1/2DIN 43760 ca ±0.2°C
Total uncertainty at 20 °C:
1DIN 43760 ca ±0.6°C or 1/2DIN 43760 ca ±0.4°C
Calibration:
Recommended every 24th month, with Swema 3000 for
the best result.
Pressure sensor:
Swema 3000md
Swema3000mdH+ SWA 10
SWA 07
Measuring range
-300... 1500 Pa
± 10 000 Pa
-300... 1500 Pa
± 7 000 Pa
Uncertainty at
20°C
±0,3% read value,
lowest ±0,3Pa
±1% read value,
lowest ± 2,5 Pa
±1% read value,
lowest ±0,3Pa
After Reset:
±0,3Pa ±2%
read value
Max load
± 50 000 Pa
± 50 000 Pa
± 20 000 Pa
± 35 000 Pa
Temp dependent:
0,2 Pa/°C
0,2 Pa/°C
0,2 Pa/°C
0,4 Pa/°C
Working tempera-
ture:
0… 50 °C
Long-time stability
Zero point:
Total measure
area:
0,1 %FSO/year
0,1 %FSO/year
Measure media
Not condensed, no moist air, less than 80% relative humidity, no aggressive
gases
Calibration
Recommended every 12th month.
Air�velocity�sensor,�SWA�31:
Ø8mm at the top, Ø10mm first step on the telescopic handle
Measure range velocity:
0,1...10 m/s, option 10...30 m/s at - 10...+ 45°C
Measure media:
Not condensed, no moist air, less than 80%
relative humidity, no aggressive gases
Uncertainty:
At 20°C:
0,10...1,33 m/s 0,04 m/s
1,33...30 m/s 3% of read value
Otherwise:
0,10...1,10 m/s 0,05 m/s
1,10...30 m/s 4,5 % of read value
Measure range temperature:
- 20...+ 80°C
Uncertainty:
± 0,3°C at 20°C
± 1,0°C - 20...+ 80°C
Calibration:
Recommended every 12th month.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 33
Measure�probe,�SwemaFlow�125
Measure range flow:
2-125 l/s (7 - 450 m3/h). The Instrument shows
always zero if the flow is lower than 2 l/s (7m3/h).
Measure media:
Not condensed, no moist air, less than 80%
relative humidity, no aggressive gases
Uncertainty:
± 3% read value, minimum ± 1 l/s
Measuring range temperature:
-10...+50 °C
Uncertainty
At 20°C:
± 0,3 °C
-10...+50 °C:
± 0.5 °C
Calibration:
Recommended every 6th month
The Battery:
SwemaFlow 125 contains loadable batteries of the type nickel-methal hydride (NiMH). A fully char-
ged battery is enough for a normal working day. However, this is controled of which flow measu-
red, the more the higher consumption.
Warning if the battery is about to end.
When the battery is about to end in SwemaFlow 125 will the battery sign start to blink. When the
battery is fully exhausted will the Swema 3000 automatically shut down.
Charge the battery, you can charge it when it suits you.
When you should load the battery you should use the charger that comes with the SwemaFlow
125, to use other chargers causes danger. Connect the charger to the power supply, subsequently
the SwemaFlow 125, a red lamp will be lightened beside the contact on the SwemaFlow 125. If
the red light starts to blink directly, the contact should be connected again. When the battery is
fully charged will the red light start to blink.
If you have Swema 3000 connected to SwemaFlow 125 should Swema 3000 not be on when you
charge SwemaFlow 125.
The battery is secured by an electric circuit as it makes it possible to charge it whenever it suits
you without any damage. It takes approximately 1 hour to charge the battery full when it is empty.
At charging should the instrument’s temperature be between. 10 - 45 °C.
When the battery in Swema 3000 is going out starts the battery sign to light up. When it is totally
empty the Swema 3000 will shut down automatically.
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 34
Relative�Humidity�&�Temperature:
Measure area humidity:
0...100%RF
Accuracy SWA 13 & 16 at 23°C:
± 1,6%RF at 10...90%RF, otherwise ± 2.6%RF
HC2-S & SWHP28_HC2 at 23°C:
± 0,8%RF at 0...100%RF
Measure area temperature:
SWHP 28:
-40…85°C
SWA 13:
-20...60 °C
SWA 16:
-20...150°C
Hygroclip2-S (other models):
-40…85°C (-50…200°C)
Accuracy temperature:
± 0.3 °C
Calibration:
Recommended every 12th month
Calculations:
Dew point and water content (g water / kg dry air)
Analogic�cable�with�output
Analogic cable with a volt signal for each Swema 3000 sensor. Also gives an output for the buit-in
differencial pressure sensor in Swema 3000md and Swema 3000mdH+. Same cable suits for all
sensors. Connected to Swema 3000 left contact. The other end has loose cable ends.
Swema3000md, SWA10:
1mV/Pa, 1,0V = 0Pa
Swema3000mdH+, SWA07:
0,1mV/Pa, 1,0V = 0Pa
SWA31:
100mV/m/s, 5…10mV = 0m/s
SWA03:
1V/m/s, 5…10mV=0m/s
SWA25 Ni100:
10mV/°C, 1,0V=0°C
Pt100-sensor:
1mV/°C, 1,0V=0°C
CO2-cable:
1mV/ppm, 5…10mV=0ppm
SwemaFlow 65, 125, 2000
10mV/l/s, 5…10mV=0l/s
Humidity sensor:
10mV/%RF, 5…10mV=0%RF
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 35
15.2���Necessary�straights�before�and�after�measure�plans
(According to T22 Methods for measurement of air flow inventilation systems)
Round�channels�
Rectangular�channels
Before measure plan
a ≥5 x D
a ≥6 x Dh
After measure plan
a≥2 x D
a ≥2 x Dh
Dh= Hydralic diameter (diameter from corner to corner for rectangular channels)
Use the k-factor to calculate the air flow. Some suppliers calculates the correction formula accordingly:
q = sqrt (Ik ∆P)
In this case you have to calculate: k = sqrt Ik Put in the calculated k in Swema 3000.
If the supplier has not stated a K-factor, you can by yourself calculate in if you have a pressure
drop diagram :
Do like this: q = k sqrt ∆P → k = q / sqrt ∆P.
Go into the diagram for e.g.:
∆P = 100 Pa → sqrt ∆P = sqrt 100 = 10
So, for Ø 100 → 100Pa corresponds 50 l/s
Use the connection above for k: k= 50/10 → 5,0
In this case the k-factor was 5.0. Set k=5,0 in Swema
3000 then you will get the flow directly in l/s, m3/h or
CFM.
If the diagram does not reach 100 Pa, then choose e.g.
25 Pa
(sqrt 25 = 5)
15. Theory
15.1����K-factor�calculation
SE-123 56 FARSTA
Tel: +46 8 94 00 90
Fax: +46 8 93 44 93
[email protected]
www.swema.se 36
15.3��Recommended�measure�points�channel�measurements�������������������������������
From T22 ”Methods for measurement of air flow in ventilation installations”, of the Nordic Ventilation Group and Build-
ning Research Council, 1998, ISBN 91-540-5827-9.
SE-123 56 FARSTA
Tel: 08 94 00 90
Fax: 08 93 44 93
[email protected]
www.swema.se 37
15.4��Values�of�K2-factor
Hot wire anemometer
Circular channels:
Ø ≤ 160 mm » k2 = 0.92
160 < Ø ≤ 400 mm » k2 = 0.96
400 < Ø ≤ 1250 mm » k2 = 0.98
Rectangular channels:
Height>Width » k2 = 0.94
HeightWidth » k2 = 0.94
Height