Series TY-FRB – 5.6 and 8.0 K-factor

Upright and Pendent Intermediate Level Sprinklers Quick Response Page 1 of 6 AUGUST 2018 TFP356 IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Worldwide Contacts www.tyco-fire.com General Description TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are auto- matic sprinklers of the quick response 3 mm frangible bulb type. They are standard spray sprinklers intended for use in fire sprinkler systems designed in accordance with the standard instal- lation rules recognized by the appli- cable listing or approval agency (e.g., UL Listing is based on NFPA require- ments). Both the pendent and upright sprinklers produce a hemispherical water distribution pattern below the deflector. Intermediate level sprinklers are pri- marily designed for use in rack storage sprinkler systems where their thermally sensitive elements must be shielded from the water spray of higher ele- vation sprinklers that could operate earlier during a fire. Intermediate level sprinklers are also used in other appli- cations such as beneath open gridded catwalks. Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion-resistant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit- ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. NOTICE The Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association (NFPA), in addition to the standards of any other authori- ties having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Numbers (SINs) TY3133 – Upright, 5.6K, 1/2 in. NPT TY3231 – Pendent, 5.6K, 1/2 in. NPT TY4133 – Upright, 8.0K, 3/4 in. NPT TY4231 – Pendent, 8.0K, 3/4 in. NPT

Page 2 of 6

Technical Data Approvals UL and C-UL Listed FM and NYC Approved (Refer to Table A for complete approval information, including corrosion-resistant status.) Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficients K=5.6 GPM/psi½ (80,6 LPM/bar½) K=8.0 GPM/psi½ (115,2 LPM/bar½) Temperature Ratings Refer to Table A Finishes Sprinklers: Refer to Table A Physical Characteristics Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper Sealing Assembly . . Beryllium Nickel w/TEFLON Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Glass Compression Screw . . . . . . . . . . . . . . . . .Bronze Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper Shield . . . . . . . . . . . . . . . . . . . . . . . .Plated Steel * ** † † * ** * FIELD ASSEMBLED PENDENT FACTORY ASSEMBLED UPRIGHT 7/16" (11,1 mm) NOMINAL MAKE-IN FACTORY ASSEMBLED UPRIGHT SHIELD WITH SCREW WRENCH FLATS PENDENT SERIES TY-FRB FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) Pipe thread connections per ISO 7-1 can be provided on special request Temperature rating is indicated on Defector, Shield or adjacent to orifce seat on frame Order Pendent Series TY-FRB Sprinkler and Model S2 Shield Package separately for pendent assembly (Ref. Ordering Procedure) 3-1/2" (88,9 mm) DIA. O-RING DEFLECTOR 3-1/2" (88,9 mm) DIA. 1/2" NPT 2-3/16" (55,6 mm) 2-3/8" (60,3 mm) † * * ** * ** † FACTORY ASSEMBLED UPRIGHT FIELD ASSEMBLED PENDENT FACTORY ASSEMBLED UPRIGHT SHIELD WITH SCREW WRENCH FLATS PENDENT SERIES TY-FRB FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) Pipe thread connections per ISO 7-1 can be provided on special request Temperature rating is indicated on Defector, Shield or adjacent to orifce seat on frame Order Pendent Series TY-FRB Sprinkler and Model S2 Shield Package separately for pendent assembly (Ref. Ordering Procedure) DEFLECTOR 3/4" NPT O-RING 3-1/2" (88,9 mm) DIA. 3-1/2" (88,9 mm) DIA. 2-7/16" (61,9 mm) 1/2" (12,7 mm) NOMINAL MAKE-IN 2-5/16" (58,7 mm) FIGURE 1 SERIES TY-FRB UPRIGHT (TY3133) & PENDENT (TY3231) INTERMEDIATE LEVEL SPRINKLERS 5.6K, QUICK RESPONSE, 1/2 INCH NPT FIGURE 2 SERIES TY-FRB UPRIGHT (TY4133) & PENDENT (TY4231) INTERMEDIATE LEVEL SPRINKLERS 8.0K, QUICK RESPONSE, 3/4 INCH NPT

Page 3 of 6

Design Criteria TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers are intended for fire protection systems designed in accordance with the stan- dard installation rules recognized by the applicable listing or approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM Approvals’ Loss Prevention Data Sheets). Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. K-FACTOR SPRINKLER TYPE TEMPERATURE RATING BULB LIQUID COLOR SPRINKLER FINISH NATURAL BRASS* LEAD COATED** 5.6 1/2 in. NPT UPRIGHT (TY3133) 135 °F (57 °C) Orange 1, 2, 3, 4 1, 2, 3, 4 155 °F (68 °C) Red 175 °F (79 °C) Yellow 200 °F (93 °C) Green 286 °F (141 °C) Blue UPRIGHT (TY3231) 135 °F (57 °C) Orange N/A 155 °F (68 °C) Red 175 °F (79 °C) Yellow 200 °F (93 °C) Green 286 °F (141 °C) Blue 8.0 3/4 in. NPT PENDENT (TY4133) 135 °F (57 °C) Orange 1, 2, 3, 4 155 °F (68 °C) Red 175 °F (79 °C) Yellow 200 °F (93 °C) Green 286 °F (141 °C) Blue PENDENT (TY4231) 135 °F (57 °C) Orange N/A 155 °F (68 °C) Red 175 °F (79 °C) Yellow 200 °F (93 °C) Green 286 °F (141 °C) Blue Notes: 1. UL Listed as quick response sprinklers 2. C-UL Listed as quick response sprinklers 3. FM Approved as quick response sprinklers 4. Approved by the City of New York (NYC) under MEA 354-01-E * With zinc plated shield ** Where Lead Coated sprinklers are noted to be UL and C-UL Listed, the sprinklers are Listed as corrosion-resistant sprinklers; where Lead Coated sprinklers are noted to be FM Approved, the sprinklers are Approved as corrosion-resistant sprinklers. N/A – Not Applicable TABLE A 5.6K & 8.0K SERIES TY-FRB UPRIGHT & PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE LABORATORY LISTINGS AND APPROVALS

Page 4 of 6

Installation TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be installed in accordance with this section. NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm) for the 135°F (57°C) to 3/32 in. (2,4 mm) for the 286°F (141°C) tempera- ture ratings. General Instructions A leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 lb-ft (9,5 to 19,0 N∙m). A leak-tight 3/4 in. NPT sprinkler joint should be obtained by applying a minimum-to- maximum torque of 10 to 20 lb-ft (13,4 to 26,8 N∙m). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Upright Sprinklers The Series TY-FRB Intermediate Level Upright Sprinklers must be installed in accordance with the following instructions: Step 1. With pipe thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. Pendent Sprinklers The Series TY-FRB Intermediate Level Pendent Sprinklers must be installed in accordance with the following instructions: Step 1. Thread the Model S2 Shield onto the sprinkler threads with the stamped markings toward the deflector and just to the end of the threads. The final assembly step is easier to accom- plish if the shield is not disengaged by continuing to turn the shield past the threads. Step 2. Roll the O-ring over the sprin- kler threads until it seats against the shield. Step 3. With pipe thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. Step 4. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 3). With reference to Figure 1 or 2, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats. Step 5. Rotate the Model S2 Shield clockwise (looking up) so that it slightly compresses the O-ring between the shield and sprinkler fitting. Care and Maintenance TYCO Series TY-FRB 5.6K and 8.0K Quick Response Upright and Pendent Intermediate Level Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system control valve for maintenance work on the fire protection system that it con- trols, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. Refer to the Instal- lation section for additional information. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been completed, to verify the integrity of the corrosion-resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan- dards of any other authorities having jurisdiction. Contact the installing con- tractor or sprinkler manufacturer with any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. WRENCH RECESS (END "A" USED FOR 1/2" NPT MODELS) WRENCH RECESS (END "B" USED FOR 3/4" NPT MODELS) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH

Page 5 of 6

Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indi- cate the full product name, including description and part number (P/N). Upright Sprinkler Assemblies with NPT Thread Connections (with Shield) Specify: Series TY-FRB Upright Inter- mediate Level Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Table B) Pendent Sprinkler Assemblies with NPT Thread Connections (Shield ordered separately) Specify: Series TY-FRB Pendent Sprinkler, (specify K-factor), Quick Response, (specify) temperature rating, (specify) finish, P/N (specify from Table C) Model S2 Sprinkler Shield Includes S2 Shield and one O-Ring. Specify: Model S2 Sprinkler Shield, (specify) Thread Size, P/N (specify): 1/2 in. NPT . . . . . . . . . . . . . . . . . . 56-070-9-332 3/4 in. NPT . . . . . . . . . . . . . . . . . . 56-070-9-342 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 SIN 333 5.6K UPRIGHT (1/2 in. NPT) TY3133 343 8.0K UPRIGHT (3/4 in. NPT) TY4133 SIN 371 5.6K PENDENT (1/2 in. NPT) TY3231 391 8.0K PENDENT (3/4 in. NPT) TY4231 SPRINKLER FINISH 1 NATURAL BRASS 7 LEAD COATED SPRINKLER FINISH 1 NATURAL BRASS 7 LEAD COATED TEMPERATURE RATING 135 13 °F (57°C) 155 155°F (68°C) 175 175°F (79°C) 200 200°F (93°C) 286 286°F (141°C) TEMPERATURE RATING 135 135°F (57°C) 155 155°F (68°C) 175 175°F (79°C) 200 200°F (93°C) 286 286°F (141°C) P/N 57 — XXX — X — XXX P/N 57 — XXX — X — XXX TABLE B SERIES TY-FRB UPRIGHT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE PART NUMBER SELECTION TABLE C SERIES TY-FRB PENDENT INTERMEDIATE LEVEL SPRINKLERS, QUICK RESPONSE PART NUMBER SELECTION (MODEL S2 PENDENT SHIELD MUST BE SEPARATELY ORDERED)

Page 6 of 6

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.