Trox Technik EM-BAC-MOD-01 Configuration Manual
Read Online
Read the Trox Technik EM-BAC-MOD-01 Configuration Manual online using the built-in PDF viewer.
Text of the manual
Read the instructions prior to performing any task!
Description of data points for BACnet/MS/TP or
Modbus RTU interface for EASYLAB/TROX UNIVERSAL
Firmware from 4.1 onwards
GB/en
A00000063072, 3, GB/en
© TROX GmbH 2017
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
Telephone: +49 2845 202-0
Fax: +49 2845 202-265
email: [email protected]
Internet: http://www.troxtechnik.com
06/2019
Expansion module EM-BAC-MOD-01
2
About this manual
The expansion module EM-BAC-MOD is used to inte-
grate the following devices into a BACnet (MS/TP) or a
Modbus (RTU) network and in this way connect them to
the central BMS:
EASYLAB controller TCU3
EASYLAB adapter modules TAM
TROX UNIVERSAL CONTROLLER
This configuration manual is an addition to the installa-
tion manual and contains information on how to con-
figure EM-BAC-MOD as an interface to the central
BMS.
Illustrations in this manual are mainly for information
and may differ from the actual design of EM-BAC-MOD.
Other applicable documentation
In addition to these instructions, the following docu-
ments apply:
Installation manual for expansion module EM-BAC-
MOD
Documentation on
–
EASYLAB controller TCU3
–
Adapter module TAM
–
TROX UNIVERSAL CONTROLLER
Project-specific wiring documents, if any
TROX Technical Service
To ensure that your request is processed as quickly as
possible, please keep the following information ready:
Product name
TROX order number
Delivery date
Brief description of the fault
Online
www.troxtechnik.com
Phone
+49 2845 202-400
Limitation of liability
The information in this manual has been compiled with
reference to the applicable standards and guidelines,
the state of the art, and our expertise and experience of
many years.
The manufacturer does not accept any liability for dam-
ages resulting from:
Non-compliance with this manual
Incorrect use
Operation or handling by untrained individuals
Unauthorised modifications
Technical changes
Use of non-approved replacement parts
The actual scope of delivery may differ from the infor-
mation in this manual for bespoke constructions, addi-
tional order options or as a result of recent technical
changes.
The obligations agreed in the order, the general terms
and conditions, the manufacturer's terms of delivery,
and the legal regulations in effect at the time the con-
tract is signed shall apply.
We reserve the right to make technical changes.
Defects liability
For details regarding defects liability please refer to
Section VI, Warranty Claims, of the Delivery and Pay-
ment Terms of TROX GmbH.
The Delivery and Payment Terms of TROX GmbH are
available at www.troxtechnik.com.
Copyright
This document, including all illustrations, is protected by
copyright and pertains only to the corresponding
product.
Any use without our consent may be an infringement of
copyright, and the violator will be held liable for any
damage.
This applies in particular to:
Publishing content
Copying content
Translating content
Microcopying content
Saving content to electronic systems and editing it
Supplemental instructions
Expansion module EM-BAC-MOD-01
3
1.1 Correct use.................................................. 5
1.1.1 Incorrect use............................................. 5
1.2 Safety signs................................................. 5
1.3 Residual risks.............................................. 5
1.4 Risk of damage to property......................... 6
1.5 System owner's responsibility.....................
6
1.6 Qualified staff............................................... 6
1.7 Environmental protection............................. 6
2
Configuration..................................................... 7
3
Commissioning.................................................. 8
3.1 Required TCU3 software version ............... 8
4
Interface information......................................... 9
4.1 BACnet interface......................................... 9
4.2 Modbus interface....................................... 16
4.3 Data points – detailed description............. 21
4.3.1 Input variables........................................ 21
4.3.2 Output variables..................................... 26
5
Index................................................................. 38
Table of contents
Expansion module EM-BAC-MOD-01
4
Symbols are used in this manual to alert readers to
areas of potential hazard. Signal words express the
degree of the hazard.
DANGER!
Imminently hazardous situation which is due to live
components and which, if not avoided, will result in
death or serious injury due to electrical voltage.
DANGER!
Imminently hazardous situation which, if not avoided,
will result in death or serious injury.
NOTICE!
Potentially hazardous situation which, if not avoided,
may result in property damage.
ENVIRONMENT!
Environmental pollution hazard.
1.1 Correct use
Expansion module EM-BAC-MOD provides a BACnet
MS/TP or Modbus RTU interface for EASYLAB base
components as well as for the TROX UNIVERSAL
CONTROLLER.
Use the expansion module for the following devices:
EASYLAB controller TCU3
EASYLAB adapter module TAM
TROX UNIVERSAL CONTROLLER
1.1.1 Incorrect use
Do not use the expansion module for areas of applica-
tion that are not described in this manual.
Do not use the expansion module:
outdoors
in wet areas
in areas with potentially explosive atmospheres
Residual risks
Failure of the network interface does not affect the con-
trol function of the volume flow controller but does affect
data exchange with the central BMS. Safety-related
applications require further precautions.
1.2 Safety signs
The following symbols and signs are usually found in
the work area. They apply to the very location where
they are found.
Electrical voltage
Location where a hazard due to electrical voltage exists.
Earthing
This symbol marks all equipotential bonding connection
points on EM-BAC-MOD.
1.3 Residual risks
EM-BAC-MOD is a state-of-the-art product and meets
current safety requirements. Residual risks cannot be
excluded, however, and you should proceed with cau-
tion.
Always observe the safety notes in this manual to
reduce health hazards and prevent any hazardous sit-
uations.
Electric current
DANGER!
Danger of death due to electric current!
Danger of death if live components are touched.
–
Switch off the supply voltage and secure it
against being switched on again before working
on the unit.
–
Only skilled qualified electricians are allowed to
work on live components.
–
Equipotential bonding is required.
Security
Residual risks
Expansion module EM-BAC-MOD-01
5
1.4 Risk of damage to property
Temperature differences
NOTICE!
Risk of damage to property due to large tempera-
ture differences
If EM-BAC-MOD has been kept in an unheated area,
condensation may form and damage the electronic
components beyond repair.
–
Let EM-BAC-MOD warm up to room temperature
before you install it.
Electrostatic charge
NOTICE!
Risk of damage to property due to electrostatic
charge
Electrostatic charge can damage the electronics of
the expansion module.
–
Before you remove the expansion module from
its protective wrapping, touch an equipotentially
bonded metal surface, e.g. a water pipe, for elec-
trical earthing.
–
Avoid skin contact with any components or
printed circuits on the expansion module or the
main PCB.
–
Wear conductive footwear and antistatic clothing.
1.5 System owner's responsibility
System owner's obligations
EM-BAC-MOD is intended for commercial use. The
system owner is therefore subject to the legal obliga-
tions of occupational health and safety regulations.
In addition to the safety notes in this manual, the appli-
cable regulations for safety, accident prevention and
environmental protection must also be complied with.
1.6 Qualified staff
Qualification
The work described in this manual has to be carried out
by individuals with the qualification, training, knowledge
and experience described below:
Network administrator
Network administrators design, install, configure and
maintain the IT infrastructure in companies or organisa-
tions.
Any work has to be carried out by individuals who can
be expected to carry out their assigned duties reliably.
Individuals whose reaction time is delayed due to
alcohol, drugs or other medication must not carry out
any work.
1.7 Environmental protection
The following substances and materials which are
hazardous to the environment are used:
Electrical and electronic parts
Electrical and electronic parts may contain toxic mate-
rials and substances. These parts have to be disposed
of separately from other waste, i.e. taken to your local
reuse and recycling centre or disposed of by a specialist
disposal company.
Batteries
Batteries contain toxic heavy metals. They are haz-
ardous waste and must be taken to a hazardous waste
collection point or disposed of by a specialist company.
Security
Environmental protection
Expansion module EM-BAC-MOD-01
6
Before you use EM-BAC-MOD as a BACnet or Modbus
interface module, you have to configure it to the actual
application. To do so, use the switches on the interface
module.
Fig. 1: EM-BAC-MOD
① Switch to select BACnet MS/TP or Modbus RTU
protocol
② Switches to set the network addresses, 01-99
③ DIP switch to set communication parameters
Setting the protocol type
1.
Use the slide switch ① to set the BACnet MS/TP
or Modbus RTU protocol.
Setting the network address
2.
Use the two address code switches X and Y ② to
set a network address (01 to 99). Address 00 is
reserved for broadcast mode.
A maximum of 32 devices (network addresses)
can be operated on one network segment. Cau-
tion: a different network address must be set for
every device.
Setting the device family
3.
If the device is to be used with an EASYLAB/
TROX UNIVERSAL controller or a adapter module
TAM, use the DIP switch ③ to set switch S1 to
Off.
Communication parameters
4.
Use the DIP switch ③ to set the following parame-
ters:
S2 + S3 - Transmission speed EIA-485
S5 + S6 - Parity
S8
- Terminal resistor
Ask the responsible specialist consultant for the
values to be set.
Setting the transmission speed for BACnet
BACnet
S2
S3
9600 Bd
Off
Off
19200 Bd
On
Off
38400 Bd
Off
On
76800 Bd
On
On
Setting the transmission speed for Modbus
Modbus
S2
S3
9600 Bd
Off
Off
19200 Bd
On
Off
38400 Bd
Off
On
57600 Bd
On
On
Setting parity
Parity
S5
S6
None
Off
Off
None
On
Off
Odd
Off
On
Even
On
On
Terminal resistor for EIA-485 network from
rev. 2
Terminal resistor
S8
Disabled
Off
Enabled
On
Configuration
Expansion module EM-BAC-MOD-01
7
Once you have set the configuration switch to adapt
EM-BAC-MOD to the network, the controller and the
network can be commissioned.
Commissioning a BACnet or Modbus network requires
specialist knowledge as well as special network
adapters and software. Only specialist personnel should
do the commissioning.
3.1 Required TCU3 software version
The expansion module EM-BAC-MOD with firmware 4.1
requires the following software versions:
EASYLAB or adapter module TAM
–
Software version 8.0 or higher
TROX UNIVERSAL CONTROLLER
–
Software version 2.1 or higher
The software version is displayed in the EasyConnect
software, ‘Diagnosis’, ‘Basic Device’ line.
A product sticker on the main PCB also carries the soft-
ware version number (only for version 3 or higher).
With earlier software versions there is no data exchange
between the expansion module EM-BAC-MOD and con-
troller. This means that the network is not able to read
out current values from the controller or to send any
values.
You need not adapt the controller configuration with
the EasyConnect configuration software for the
expansion module to work.
Commissioning
Required TCU3 software version
Expansion module EM-BAC-MOD-01
8
4.1 BACnet interface
Application
The expansion module EM-BAC-MOD supports the fol-
lowing BACnet interface functions in the BACnet pro-
tocol settings:
Native BACnet, i.e. the BACnet interface is imple-
mented on the field module (EASYLAB volume flow
controller)
External hardware components such as physical
gateways are not required
BACnet interface documentation includes the fol-
lowing documents: Protocol Implementation Con-
formance Statement (PICS), BACnet Interoperability
Building Blocks Supported (BIBBS), as well as a
description of the device object and the supported
objects
Abbreviations
EASYLAB:
FH
- Fume cupboard controller
RR
- Room controller for supply air or extract air
(RS, RE, PC)
RR RMF
- Room controller with active room manage-
ment function
EC, SC
- Single controller for supply air or extract air
(EC, SC)
TAM
- Adapter module
TAM
RMF
- Adapter module with active room manage-
ment function
WR
- Defaults for the volume flow controller or
room, from the central BMS
RD
- Data provided by the volume flow con-
troller or room
TROX UNIVERSAL CONTROLLER:
RS/RE
- Volume flow controllers for supply or
extract air
RS/RE
RMF
- Volume flow controller with active room
management function
PR*/PD*
- Room pressure controller or duct for
supply or extract air
PR*/PD*
RMF
- Room pressure controller or duct with
active room management function
BACnet PICS (Protocol Implementation Conformance Statement) – Overview
Principal categories
Values
Date
2019-04-03
Vendor name
TROX GmbH
Vendor identifier
329
Product name
EM-BAC-MOD
Model no.
M536HD7
Application
4.1
Firmware Revison
4.1
BACnet Protocol Revision
12
Standardised Device Profile
BACnet Application Specific Controller (B-ASC)
Segmentation Capability
No
Data Link Layer Options
MS/TP master (Clause 9), Baudrates 9600, 19200,
38400, 76800
Device Address Binding
No
Network Security Options
Non-secure device – capable of operating without
BACnet network security
Character Sets Supported
ISO 10646 (UTF-8)
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
9
Hexadecimal Switches X, Y
Network address
DIP Switch 1
OFF
ON
Controller
EASYLAB TCU3
Other
DIP Switch 2
OFF
ON
OFF
ON
DIP Switch 3
OFF
OFF
ON
ON
Baud rate
9600
19200
38400
76800
BIBBS - BACnet Interoperability Building Blocks Supported
Data Sharing-ReadProperty-B
DS-RP-B
Data Sharing-WriteProperty-B
DS-WP-B
Data Sharing-COV-Unsolicited-B
DS-COVU-B
Device Management-Dynamic Device Binding-B
DM-DDB-B
Device Management-Dynamic Object Binding-B
DM-DOB-B
Device Management-Device Communication Control-B
DM-DCC-B
Device Management-ReinitialiseDevice-B
DM-RD-B
DeviceObject
Property
Value
Access
Object identifier
Device instance; default instance = 32900 + set network
address
WR, RD; E
Object name
Default="EM-BACnet"; project-specific description can be
entered, 62 characters max.
WR, RD; E
Object type
Device (8)
RD
System_Status
OPERATIONAL (0)
RD
Vendor_Name
"TROX GmbH"
RD
Vendor_Identifier
329
RD
Model_Name
"EM-BAC-MOD"
RD
Description
Default = “EASYLAB”; description can be entered, 126 char-
acters max.
WR, RD; E
Location
Default = ""; description can be entered, 62 characters max.
WR, RD; E
Firmware_Revision
“4.1” (EASYLAB)
RD
Application_Software_Version
“4.1” (EASYLAB)
RD
Protocol_Version
1
RD
Protocol_Revision
12
RD
Protocol Services Supported
Who-is, who-has, read-property, write-property, device-com-
munication-control, reinitialise-device
RD
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
10
DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTI-
STATE_VALUE
RD
Object_List
EASYLAB: device, analogue-value 1…36, binary-value 1…
30, multistate-value 1…8
RD
Max_ADPU_Length_Accepted
480
RD
Segmentation_Supported
NO_SEGMENTATION (3)
RD
APDU_Timeout
10000
RD
Number_Of_APDU_Retries
3
RD
Device_Address_Binding
–
RD
Database_Revision
0
RD
Description
Controller Type “EASYLAB”
RD
Max_Master
Default 127
WR, RD; E
Max_Info_Frames
Default 1
WR, RD; E
Multistate Value Objects
In-
stanc
e
Description
Unit
Acc-
ess
Sup-
port
COV
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
1
COVU mode
x
x
x
x
x
x
x
x
WR,
RD
N
2
Mode
x1
x
x
x
x
WR,
RD
3
ModeAct
x
x
x
x
x
x
RD
N
4
RoomModeAct
x
x
x
x
x
x
RD
N
5
SwitchPos
x
RD
N
6
Sunblind
x
x
x
x
WR,
RD
N
7
SC_SetLock-
HighPrio
not used
8
SC_GetLock-
HighPrio
not used
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä on page 9
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
11
Analogue Value Objects
In-
stanc
e
Description
Unit
Unit
Acc-
ess
Sup-
port
COV
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
1
VolflowSet
l/s
(87)
x
x
x
x
x
x
x
RD
N
2
VolflowAct
l/s
(87)
x
x
x
x
x
x
x
x
x
RD
N
3
VolTotalExh
l/s
(87)
x
x
x
x
x
x
x
x
x
x
RD
N
4
VolTotalSup
l/s
(87)
x
x
x
x
x
x
x
x
x
x
RD
N
5
PressSet
pa
(53)
x
x
x
x
RD
N
6
PressAct
pa
(53)
x
x
x
x
RD
N
7
VelocitySet
m/s
(74)
x
RD
N
8
VelocityAct
m/s
(74)
x
RD
N
9
WireSen-
sorPos
%
(98)
x
RD
N
10
DampPos
%
(98)
x
x
x
x
x
x
x
x
RD
N
11
Damp-
PosMax_FH
%
(98)
x
x
x
x
x
x
RD
N
12
Damp-
PosMin_FH
%
(98)
x
x
x
x
x
x
RD
N
13
Damp-
PosMax_RE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
14
Damp-
PosMin_RE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
15
Damp-
PosMax_TE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
16
Damp-
PosMin_TE
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
17
Damp-
PosMax_RS
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
18
Damp-
PosMin_RS
%
(98)
x
x
x
x
x
x
x
x
x
x
RD
N
19
VolOffset_T
%
(98)
x
x
WR,
RD
N
20
VolOffset_P
%
(98)
x
x
WR,
RD
N
Abbreviations Ä on page 9
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
12
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
21
SystemDe-
vices
–
(95)
x
x
x
x
x
x
x
x
x
x
RD
N
22
VolflowExh
l/s
(87)
x
x
x
x
x
x
x
x
x
WR,
RD
N
23
VolflowSup
l/s
(87)
x
x
x
x
x
x
x
x
x
WR,
RD
N
24
SC_SetPos
%
(98)
not used
25
SC_GetPos
%
(98)
not used
26
Damp-
PosMax_EC
%
(98)
x
x
x
x
x
x
RD
N
27
Damp-
PosMin_EC
%
(98)
x
x
x
x
x
x
RD
N
28
Damp-
PosMax_SC
%
(98)
x
x
x
x
x
x
RD
N
29
Damp-
PosMin_SC
%
(98)
x
x
x
x
x
x
RD
N
30
Damp-
PosMax_TS
%
(98)
x
x
x
x
x
x
RD
N
31
Damp-
PosMin_TS
%
(98)
x
x
x
x
x
x
RD
N
32
VolflowSet_R
l/s
(87)
x
x
WR,
RD
N
33
PressSet_R
pa
(57)
x
x
WR,
RD
N
34
Volt_AI2
volt
(5)
x
x
x
x
x
x
RD
N
35
Volt_AI3
volt
(5)
x
x
x
x
x
x
RD
N
36
Volt_AO2
volt
(5)
x
x
x
x
x
x
WR,
RD
N
Abbreviations Ä on page 9
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
13
Binary Value Objects
In-
stanc
e
Description
Unit
Acc-
ess
Sup-
port
COV
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
1
LocalAlarm
(COVU)
x
x
x
x
x
x
x
x
x
x
RD
2
SummaryA-
larm (COVU)
x
x
x
x
x
x
RD
3
PressAlarm
(COVU)
x
x
x
x
x
x
RD
4
ManOP_Dis-
able
x1
x
x
x
x
WR,
RD
5
PressSetSel
x
x
WR,
RD
6
DI1
x
x
x
x
x
x
x
x
x
x
RD
7
DI2
x
x
x
x
x
x
x
x
x
x
RD
8
DI3
x
x
x
x
x
x
x
x
x
x
RD
9
DI4
x
x
x
x
x
x
x
x
x
x
RD
10
DI5
x
x
x
x
x
x
x
x
x
x
RD
11
DI6
x
x
x
x
x
x
x
x
x
x
RD
12
DO1
x
x
x
x
x
x
x
x
x
x
RD
13
DO2
x
x
x
x
x
x
x
x
x
x
RD
14
DO3
x
x
x
x
x
x
x
x
x
x
RD
15
DO4
x
x
x
x
x
x
x
x
x
x
RD
16
DO5
x
x
x
x
x
x
x
x
x
x
RD
17
DO6
x
x
x
x
x
x
x
x
x
x
RD
18
SC_Alarm
not used
19
DO1_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
20
DO2_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
21
DO3_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
22
DO4_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
23
DO5_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
24
DO6_Set
x
x
x
x
x
x
x
x
x
x
WR,
RD
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä on page 9
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
14
Available with equipment function
FH
RR
RR
RMF
EC,
SC
TAM
TAM
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD*
RMF
25
DO1_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
26
DO2_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
27
DO3_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
28
DO4_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
29
DO5_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
30
DO6_SetBy-
Local
x
x
x
x
x
x
x
x
x
x
RD
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä on page 9
Interface information
BACnet interface
Expansion module EM-BAC-MOD-01
15
4.2 Modbus interface
Application
The expansion module EM-BAC-MOD supports the fol-
lowing Modbus interface functions in the Modbus pro-
tocol settings:
Modbus is an open serial master-slave communica-
tion protocol which has become a de facto standard
for the industry
The master (e.g. central BMS) can address a
number of slaves (EASYLAB volume flow control-
lers) and use Modbus functions to request informa-
tion from individual data points
Data access is based on numbered data registers
which the master has to define in order to request
data using Modbus functions
The slave responds by either returning the
requested information or an exception code (error)
Example: The Read Holding Registers func-
tion (register no. 3) returns the volume flow rate
actual value of the addressed controller
General information for a Modbus device can be
read out using the Read Device
Identifikation function
Abbreviations
EASYLAB:
FH
- Fume cupboard controller
RR
- Room controller for supply air or extract air
(RS, RE, PC)
RR RMF
- Room controller with active room manage-
ment function
EC, SC
- Single controller for supply air or extract air
(EC, SC)
TAM
- Adapter module
TAM
RMF
- Adapter module with active room manage-
ment function
WR
- Defaults for the volume flow controller or
room, from the central BMS
RD
- Data provided by the volume flow con-
troller or room
TROX UNIVERSAL CONTROLLER:
RS/RE
- Volume flow controllers for supply or
extract air
RS/RE
RMF
- Volume flow controller with active room
management function
PR*/PD*
- Room pressure controller or duct for
supply or extract air
PR*/PD*
RMF
- Room pressure controller or duct with
active room management function
Modbus functions
Function no.
Designation
Meaning
1 (0x01)
Read Coils
Read states of 1 to 8 bits according to bit list
3 (0x03)
Read Holding Registers
Read several consecutive registers
4 (0x04)
Read Input Registers
Read several consecutive registers
5 (0x05)
Write Single Coil
Write state of a single bit
6 (0x06)
Write Single Register
Write single register
8 (0x08)
Diagnostics
Check Modbus communication
16 (0x10)
Write Multiple Registers
Write several consecutive registers
43 (0x2B)
Read Device Identification
Read identification data for the device
14 (0x0E)
Read Device Identification
Read identification data for the device
Interface information
Modbus interface
Expansion module EM-BAC-MOD-01
16
Illegal Function Code
Unknown function or subfunction code
2
Illegal Data Address
Invalid register address
3
Illegal Data Value
Inconsistent coding for number of registers/bytes, data value
Exception codes (error codes) are returned in case of invalid function or register access.
Register list for Read***Registers and Write***Registers functions
Register
Unit
Acc-
ess
Sup-
port
COV
TCU3
TAM
TROX UNIVERSAL
Available with equipment function
No.
Description
FH
RR
RR-
RMF
EC,
SC
TAM
TAM-
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
0
Mode
x1
x
x
x
x
WR
N
1
ManOP_Disable
x1
x
x
x
x
WR
N
2
ModeAct
x
x
x
x
x
x
RD
N
3
VolflowAct
x
x
x
x
x
x
x
x
RD
N
4
VolflowSet
x
x
x
x
x
x
RD
N
5
VelocityAct
x
RD
N
6
VelocitySet
x
RD
N
7
VolTotalExh
x
x
x
x
x
x
x
x
x
x
RD
N
8
VolTotalSup
x
x
x
x
x
x
x
x
x
x
RD
N
9
VolOffset_T
x
x
WR
N
10
VolOffset_P
x
x
WR
N
11
PressAct
x
x
x
x
RD
N
12
PressSet
x
x
x
x
RD
N
13
PressSetSel
x
x
WR
N
14
DampPos
x
x
x
x
x
x
x
x
RD
N
15
Damp-
PosMax_FH -
Value
x
x
x
x
x
x
RD
N
16
Damp-
PosMax_FH -
Status
x
x
x
x
x
x
RD
N
17
Damp-
PosMin_FH -
Value
x
x
x
x
x
x
RD
N
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä ‘Abbreviations’ on page 9
Interface information
Modbus interface
Expansion module EM-BAC-MOD-01
17
Available with equipment function
No.
Description
FH
RR
RR-
RMF
EC,
SC
TAM
TAM-
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
18
Damp-
PosMin_FH -
Status
x
x
x
x
x
x
RD
N
19
Damp-
PosMax_RE -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
20
Damp-
PosMax_RE -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
21
Damp-
PosMin_RE -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
22
Damp-
PosMin_RE -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
23
Damp-
PosMax_TE -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
24
Damp-
PosMax_TE -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
25
Damp-
PosMin_TE -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
26
Damp-
PosMin_TE -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
27
Damp-
PosMax_RS -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
28
Damp-
PosMax_RS -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
29
Damp-
PosMin_RS -
Value
x
x
x
x
x
x
x
x
x
x
RD
N
30
Damp-
PosMin_RS -
Status
x
x
x
x
x
x
x
x
x
x
RD
N
31
LocalAlarm
x
x
x
x
x
x
x
x
x
x
RD
Y
32
SummaryAlarm
x
x
x
x
x
x
RD
Y
33
PressAlarm
x
x
x
x
x
x
RD
Y
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä ‘Abbreviations’ on page 9
Interface information
Modbus interface
Expansion module EM-BAC-MOD-01
18
Available with equipment function
No.
Description
FH
RR
RR-
RMF
EC,
SC
TAM
TAM-
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
34
WireSensorPos
x
RD
N
35
SwitchPos
x
RD
N
36
RoomModeAct
x
x
x
x
x
x
RD
N
37
SystemDevices
x
x
x
x
x
x
x
x
x
x
RD
N
38
SunBlind
x
x
x
x
WR
N
39
StateDI
x
x
x
x
x
x
x
x
x
x
RD
N
40
StateDO
x
x
x
x
x
x
x
x
x
x
RD
N
41
VolflowExh
x
x
x
x
x
x
x
x
x
WR
N
42
VolflowSup
x
x
x
x
x
x
x
x
x
WR
N
43
SC_SetLockHigh-
Prio
not used
44
SC_GetLockHigh-
Prio
not used
45
SC_SetPos -
Value
not used
46
SC_SetPos -
Status
not used
47
SC_GetPos
not used
48
SC_Alarm
not used
49
DampPosMax_EC
- Value
x
x
x
x
x
x
RD
N
50
DampPosMax_EC
- Status
x
x
x
x
x
x
RD
N
51
DampPosMin_EC
- Value
x
x
x
x
x
x
RD
N
52
DampPosMin_EC
- Status
x
x
x
x
x
x
RD
N
53
DampPosMax_SC
- Value
x
x
x
x
x
x
RD
N
54
DampPosMax_SC
- Status
x
x
x
x
x
x
RD
N
55
DampPosMin_SC
- Value
x
x
x
x
x
x
RD
N
56
DampPosMin_SC
- Status
x
x
x
x
x
x
RD
N
57
DampPosMax_TS
- Value
x
x
x
x
x
x
RD
N
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä ‘Abbreviations’ on page 9
Interface information
Modbus interface
Expansion module EM-BAC-MOD-01
19
Available with equipment function
No.
Description
FH
RR
RR-
RMF
EC,
SC
TAM
TAM-
RMF
RS/
RE
RS/RE
RMF
PR*/
PD*
PR*/PD
*
RMF
58
DampPosMax_TS
- Status
x
x
x
x
x
x
RD
N
59
DampPosMin_TS
- Value
x
x
x
x
x
x
RD
N
60
DampPosMin_TS
- Status
x
x
x
x
x
x
x
x
x
x
RD
N
61
DO_Set
x
x
x
x
x
x
x
x
x
x
WR
N
62
DO_SetByLocal
x
x
x
x
x
x
x
x
x
x
RD
N
63
VolflowSet_R
x
x
WR,
RD
N
64
PressSet_R
x
x
WR,
RD
N
65
Volt_AI2
x
x
x
x
x
x
RD
N
66
Volt_AI3
x
x
x
x
x
x
RD
N
67
Volt_AO2
x
x
x
x
x
x
WR,
RD
N
1 only for individually selected operating mode (stand-alone operation)
Abbreviations Ä ‘Abbreviations’ on page 9
Interface information
Modbus interface
Expansion module EM-BAC-MOD-01
20
4.3 Data points – detailed description
The following is a detailed description of the information
that each data point provides; input variables and output
variables are described separately:
Name of data point
Access as viewed from the central BMS
–
WR – Defaults for the volume flow controller or
room, from the central BMS
–
RD – Data provided by the volume flow con-
troller or room
List of volume flow controller equipment functions
for which the variable is available
–
FH – Fume cupboard controller
–
RR – Room controller for supply air or extract air
(RS, RE, PC)
–
RR RMF – Room controller with active room
management function
–
EC, SC – Single controller for supply air or
extract air (EC, SC)
–
TAM – Adapter module
–
TAM RMF – Adapter module with active room
management function
Unit of measure (applies only to BACnet objects of
type Analogue Value Object)
Function and special functional values with their
meaning
Access to the data point using a BACnet object or
Modbus register
TROX UNIVERSAL CONTROLLER:
RS/RE
- Volume flow controllers for supply or
extract air
RS/RE
RMF
- Volume flow controller with active room
management function
PR*/PD*
- Room pressure controller or duct for
supply or extract air
PR*/PD*
RMF
- Room pressure controller or duct with
active room management function
4.3.1 Input variables
COVO mode (only BACnet)
BMS access: WR RD
Equipment function: FH, RR, RR with RMF, EC, SC,
TAM, TAM with RMF
Function
BACnet control function used to indicate how unsoli-
cited Change of Value notifications (COVU), that are
used to mark some Binary Value Objects, should be
sent
Data point
BACnet: Multistate Value Object - Instance 1
–
1 = no broadcast
–
2 = local broadcast (only local in the MS/TP net-
work of EM-BAC-MOD)
–
3 = global broadcast (in all networks)
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
21
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMFM, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
FH: Operating mode default setting for a single fume
cupboard controller, only with individual operating
mode default setting (stand-alone operation)
RMF: Operating mode default setting for the entire
room
–
The valid binding of the input variable results in a
valid operating mode default setting via BACnet
or Modbus
–
The invalid binding or no setting does not lead to
any operating mode default setting in the con-
troller or room.
–
Which operating mode is then used depends on
the default options available on the controller
Functional values (BACnet / Modbus)
1/0 = No default: The central BMS does not default
an operating mode for the controller or room.
The operating mode is set locally, e.g. on the room
control panel, on the fume cupboard control panel,
or using switch contacts.
If the operating mode is not set locally, the controller
activates standard mode.
2/1 = Standard mode: Normal operation in the day-
time (in Germany: usually according to DIN 1946,
part 7, 25 m³/h extract air per m² main useful floor
area)
3/2 = Reduced operation: Low mode in comparison
to standard mode, e.g. as a night-time setback
4/3 = Increased operation: High mode in compar-
ison to standard mode, e.g. in an emergency
5/4 = Shut-off: Shut-off of the volume flow controller,
e.g. to save energy at night or to shut down the
system
6/5 = OPEN position: Open position of the volume
flow controller
Data point
BACnet: Multistate Value Object – Instance 2
Modbus: Register 0
Sunblind
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Control input signal for shading, connected to the
controller or adapter module
Switch outputs DO5 and DO6 will be used
This BACnet or Modbus default overrides any other
defaults from the local room control panel
Data point
BACnet: Multistate Value Object – Instance 6
–
1 = No default
–
2 = Close blinds (activate switch output DO6)
–
3 = Open blinds (activate switch output DO5)
Modbus: Register 38
–
0 = Close blinds
–
1 = Open blinds
–
0xFF = No default
SC_SetLockHighPrio
Equipment function: not available
VolOffset_T
BMS access: WR RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Signalling of an external volume flow rate shift, e.g.
for adjusting the room air change rate or for external
temperature control
The shift signal is transferred as a percentage value
of a volume flow rate change range that has been
configured in the controller
Data point
BACnet: Analog Value Object – Instance 19
Modbus: Register 9
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
22
BMS access: WR RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100%)
Function
Signalling of a flow rate setpoint shift for external dif-
ferential pressure control
The shift signal is transferred as a percentage value
of a volume flow rate change range that has been
configured in the controller
Data point
BACnet: Analog Value Object – Instance 20
Modbus: Register 10
VolflowExh
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, TAM, TAM with RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Integration of an extract air flow into the room bal-
ance of the system
This default volume flow is considered for all volume
flow calculations (balance and setpoint values)
Data point
BACnet: Analog Value Object – Instance 22
Modbus: Register 41
VolflowSup
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, TAM, TAM with RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Integration of a supply air flow into the room balance
of the system
This default volume flow is considered for all volume
flow calculations (balance and setpoint values)
Data point
BACnet: Analog Value Object – Instance 23
Modbus: Register 42
SC_SetPos
Equipment function: not available
VolflowSet_R
BMS access: WR RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Default setting of volume flow rate setpoint (room),
only for standard mode
Data point
BACnet: Analog Value Object – Instance 32
Modbus: Register 63
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
23
BMS access: WR RD
Equipment function:
EASYLAB
–
not used
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Local default setting of room pressure or duct pres-
sure setpoint value
Data point
BACnet: Analog Value Object – Instance 33
Modbus: Register 64
Volt_AO2
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
Default setting of voltage for analogue output AO2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analog Value Object – Instance 36
Modbus: Register 67
ManOp_Disable
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Enabling/disabling manual control
Upon enabling manual control the corresponding
symbol appears on the control panel.
For further information on manual control please
refer to the EASYLAB design manual.
FH: Operating mode default setting for a fume cup-
board controller, only with individual operating mode
default setting (stand-alone operation)
RMF: operating mode default setting for the entire
room
Functional values
0: Manual control has been enabled on the control
panel.
Operating mode defaults set on DI override BACnet
or Modbus defaults.
1: Manual control has been disabled on the control
panel.
Operating mode default settings from BACnet or
Modbus have the highest priority.
Data point
BACnet: Binary Value Object – Instance 4
Modbus: Bit list - bit 0 or register 1
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
24
BMS access: WR RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
not used
Function
Input for switching between two pressure set points
when differential pressure control of the system is
activated (setpoint values stored in the room man-
agement function).
Functional values
0: Use differential pressure setpoint 1
1: Use differential pressure setpoint 2
Data point
BACnet: Binary Value Object – Instance 5
Modbus: Bit list - bit 1 or register 13
DO*_Set (BACnet) / DO_Set (Modbus)
BMS access: WR RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Control input signal for unused switch outputs DO1
– DO6 of the controller or adapter module
Data point
BACnet: Binary Value Object – Instance 19
(DO1_Set) – Instance 24 (DO6_Set)
–
0 = output inactive
–
1 = output active
Modbus: Register 61 – bit 0 (DO1_Set) – bit 5
(DO6_Set)
–
Bit not set = output inactive
–
Bit set = output active
Interface information
Data points – detailed description > Input variables
Expansion module EM-BAC-MOD-01
25
4.3.2 Output variables
ReadDeviceIdentification (only Modbus)
BMS access: RD
Equipment function: FH, RR, RR with RMF, EC, SC,
TAM, TAM with RMF
Function
Provides status information for the Modbus device
Data point
BACnet : see Device Object description
Ä on page 10
Modbus: Device response
–
Byte 0: Slave Address 1-99
–
Byte 1: Function Code 0x2B
–
Byte 3: Read Device ID Code 0x01
–
Byte 4: Conformity Level 0x01
–
Byte 5: More Follows 0x00
–
Byte 6: Next Object ID 0x00
–
Byte 7: Number of Objects 0x03
–
Byte 8: ID: VendorName 0x00
–
Byte 9: Obj-Length 9
–
Byte 10-18: Obj-Value "TROX GmbH"
–
Byte 19 ID: ProductCode 0x01
–
Byte 20: Obj-Length 23
–
Byte 21-43: Obj-Value "EM-BAC-MOD -
EASYLAB"
–
Byte 44 ID: MajMinRevision 0x02
–
Byte 45: Obj-Length 4
–
Byte 46-49: Obj-Value "V3.0"
ModeAct
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Output of the operating mode of the volume flow
controller
For more information on each operating mode see
the description of the 'Mode' input variableÄ Chapter
4.3.1 ‘Input variables’ on page 21 .
Functional values (BACnet / Modbus)
1/0 = No default
2/1 = Standard mode
3/2 = Reduced operation
4/3 = Increased operation
5/4 = Shut-off
6/5 = OPEN position
Data point
BACnet: Multistate Value Object – Instance 3
Modbus: Register 2
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
26
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of the room operating mode
For more information on each operating mode see
the description of the 'Mode' input variable
Functional values (BACnet / Modbus)
1/0 = No default
2/1 = Standard mode
3/2 = Reduced operation
4/3 = Increased operation
5/4 = Shut-off
6/5 = OPEN position
Data point
BACnet: Multistate Value Object – Instance 4
Modbus: Register 36
SwitchPos
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Function
Output of the current switching step of the fume cup-
board as a numeric value if the fume cupboard con-
troller is equipped with switch contacts for 2-point or
3-point control (FH2P, FH-3P)
Data point
BACnet:
Multistate Value Object – Instance 5
–
1 = invalid state
–
2 = switching step 1
–
3 = switching step 2
–
4 = switching step 3
Modbus:
Register 35
–
0 = invalid state
–
1 = switching step 1
–
2 = switching step 2
–
3 = switching step 3
SC_GetLockHighPrio
Equipment function: not available
VolflowSet
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF
Unit: l/s
Function
Output of the volume flow rate setpoint value for the
volume flow controller
Data point
BACnet: Analog Value Object – Instance 1
Modbus: Register 4
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
27
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the volume flow rate actual value of the
volume flow controller
Data point
BACnet: Analog Value Object – Instance 2
Modbus: Register 3
VolTotalExh
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total extract air volume flow rate of an
room
This includes the extract air volume flow rates of all
fume cupboards and extract air contollers as well as
any additional extract air volume flow rates (constant
and variable) from other controllers.
Data point
BACnet: Analog Value Object – Instance 3
Modbus: Register 7
VolTotalSup
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: l/s
Function
Output of the total supply air flow rate of an room
This includes the supply air volume flow rates of all
supply air controllers as well as any additional supply
air volume flow rates (constant and variable).
Data point
BACnet: Analog Value Object – Instance 4
Modbus: Register 8
PressSet
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the differential pressure control setpoint
value within the system
Data point
BACnet: Analog Value Object – Instance 5
Modbus: Register 12
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
28
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
PR*/PD*, PR*/PD* with RMF
Unit: Pa
Function
Output of the differential pressure control actual
value within the system
The actual value is recorded by a differential pres-
sure transducer connected to the RR with RMF or to
the TAM with RMF.
Data point
BACnet: Analog Value Object – Instance 6
Modbus: Register 11
VelocitySet
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit: m/s
Function
Output of the face velocity setpoint value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog Value Object – Instance 7
Modbus: Register 6
VelocityAct
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit: m/s
Function
Output of the face velocity actual value if the fume
cupboard controller is equipped with a face velocity
transducer (FH-VS)
Data point
BACnet: Analog Value Object – Instance 8
Modbus: Register 5
WireSensorPos
BMS access: RD
Equipment function:
EASYLAB
–
FH
TROX UNIVERSAL
–
not used
Unit/value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the sash position of the fume cupboard as
a percentage value between the closed position
(0 %) and the open position (100 %)
(Applies only if the fume cupboard controller is
equipped with a sash distance sensor (FH-DS, FH-
DV, FH-VD))
Data point
BACnet: Analog Value Object – Instance 9
Modbus: Register 34
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
29
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Number of identified EASYLAB system components
Data point
BACnet: Analog Value Object – Instance 21
Modbus Register 37
SC_GetPos
Equipment function: not available
Volt_AI2
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Output of the voltage at analogue input AI2
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue Value Object – Instance 34
Modbus: Register 65
Volt_AI3
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: V DC
Function
Output of the voltage at analogue input AI3
0 – 10 V DC, in increments of 0.1 V
Data point
BACnet: Analogue Value Object – Instance 35
Modbus: Register 66
LocalAlarm
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Output of a local alarm for a fume cupboard con-
troller, extract air controller, supply air controller,
room controller or TAM
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Functional values
0 = No local alarm
1 = Local alarm
Data point
BACnet: Binary Value Object – Instance 1
Modbus: Bit list - bit 2 or register 31
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
30
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Output of a consolidated alarm
An alarm signal is generated when a controller emits
an alarm or fault message.
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Standard configuration: volume flow rate alarm.
Functional values
0 = No consolidated alarm
1 = Consolidated alarm
Data point
BACnet: Binary Value Object – Instance 2
Modbus: Bit list - bit 3 or register 32
PressAlarm
BMS access: RD
Equipment function:
EASYLAB
–
RR with RMF, TAM with RMF
TROX UNIVERSAL
–
RE/RS with RMF, PR*/PD* with RMF
Function
Output of a room pressure alarm when room pres-
sure control is active
Alarm conditions can be defined using the EasyCon-
nect configuration software.
Functional values
0 = No differential pressure alarm
1 = Differential pressure alarm
Data point
BACnet: Binary Value Object – Instance 3
Modbus: Bit list - bit 4 or register 33
DI* (BACnet), StateDI (Modbus)
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital inputs DI1 – DI6 of the controller or
adapter module
Data point
BACnet:
Binary Value Object – Instance 6 (DI1) – Instance 11
(DI6)
–
0 = inactive
–
1 = active
Modbus:
Register 39, bit 0 (DI1) – bit 5 (DI6)
–
Bit not set = inactive
–
Bit set = active
DO* (BACnet), StateDO (Modbus)
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Status of digital outputs DO1 – DO6 of the controller
or adapter module
Data point
BACnet:
Binary Value Object – Instance 12 (DO1) – Instance
17 (DO6)
–
0 = inactive
–
1 = active
Modbus:
Register 40, bit 0 (DO1) – bit 5 (DO6)
–
Bit not set = inactive
–
Bit set = active
SC_Alarm
Equipment function: not available
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
31
DO*_SetByLocal (BACnet), DO_SetByLocal
(Modbus)
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Function
Feedback from the controller about switch outputs
DO1 … DO6 used by the controller or adapter
module
Data point
BACnet:
Binary Value Object – Instance 25 (DO1_Setby-
Local) – Instance 30 (DO6_SetbyLocal)
–
0 = output inactive
–
1 = output active
Modbus:
Register 62, bit 0 (DO1_Set) – bit 5 (DO6_Set)
–
Bit not set = output inactive
–
Bit set = output active
DampPos
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position1
Data point
BACnet: Analog Value Object – Instance 10
Modbus: Register 14
DampPosMax_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the widest open damper
blade 1, 2, 4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance 11 – value
and event state
Modbus: Register 15 (value) and register 16 (event
state)
DampPosMin_FH
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard controller with the least wide open damper
blade 1, 2, 5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance 12 – value
and event state
Modbus: Register 17 (value) and register 18 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
32
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
blade 1, 2, 4
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance 13 – value
and event state
Modbus: Register 19 (value) and register 20 (event
state)
DampPosMin_RE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: percentage value in 0.5 % increments
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open
damper blade 1, 2, 5
For the evaluation of the damper blade positions in
separate extract air systems (2 fans), i.e. fume cup-
board extract air and room extract air
Data point
BACnet: Analog Value Object – Instance 14 – value
and event state
Modbus: Register 21 (value) and register 22 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
33
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller
with the widest open damper blade 1, 3, 4
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and
room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the
system with the widest open damper blade 1, 3, 4
Data point
BACnet: Analog Value Object – Instance 15 – value
and event state
Modbus: Register 23 (value) and register 24 (event
state)
DampPosMin_TE
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the fume
cupboard, extract air or room extract air controller
with the least wide open damper blade 1, 3, 5
For the evaluation of the damper blade positions in
the extract air system (1 fan) for fume cupboard and
room extract air
For UNIVERSAL: output of the damper blade posi-
tion of the extract air room pressure controller in the
system with the widest closed damper blade 1, 3, 4
Data point
BACnet: Analog Value Object – Instance 16 – value
and event state
Modbus: Register 25 (value) and register 26 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
34
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the widest open damper
blade 1, 4
Data point
BACnet: Analog Value Object – Instance 17 – value
and event state
Modbus: Register 27 (value) and register 28 (event
state)
DampPosMin_RS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit:
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
supply air controller with the least wide open
damper blade 1, 5
Data point
BACnet: Analog Value Object – Instance 18 – value
and event state
Modbus: Register 29 (value) and register 30 (event
state)
DampPosMax_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the widest open damper
blade 1, 4
Data point
BACnet: Analog Value Object – Instance 26 – value
and event state
Modbus: Register 49 (value) and register 50 (event
state)
DampPosMin_EC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the room
extract air controller with the least wide open
damper blade 1, 5
Data point
BACnet: Analog Value Object – Instance 27 – value
and event state
Modbus: Register 51 (value) and register 52 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
35
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the widest open damper blade 1, 4
Data point
BACnet: Analog Value Object – Instance 28 – value
and event state
Modbus: Register 53 (value) and register 54 (event
state)
DampPosMin_SC
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
not used
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
controller with the least wide open damper blade 1, 5
Data point
BACnet: Analog Value Object – Instance 29 – value
and event state
Modbus: Register 55 (value) and register 56 (event
state)
DampPosMax_TS
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the widest open
damper blade 1, 4
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the
system with the widest open damper blade 1, 3, 4
Data point
BACnet: Analog Value Object – Instance 30 – value
and event state
Modbus: Register 57 (value) and register 58 (event
state)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
36
BMS access: RD
Equipment function:
EASYLAB
–
FH, RR, RR with RMF, EC, SC, TAM, TAM with
RMF
TROX UNIVERSAL
–
RE/RS, RE/RS with RMF, PR*/PD*, PR*/PD*
with RMF
Unit: %
Value range:
BACnet: Percentage value in increments of 0.5 %
Modbus: 0–200 (200 corresponds to 100 %)
Function
Output of the damper blade position of the supply air
or room supply air controller with the least wide
open damper blade 1, 5
For UNIVERSAL: output of the damper blade posi-
tion of the supply air duct pressure controller in the
system with the widest closed damper blade 1, 3, 4
Data point
BACnet: Analog Value Object – Instance 31 – value
and event state
Modbus: Register 59 (value) and register 60 (event
state)
1 Damper blade positions DampPos**_** are transmitted
as a percentage value between 0% (closed) and 100%
(open).
2 The output variables DampPosMax_FH, Damp-
PosMin_FH, DampPosMax_EC, and DampPosMin_EC,
as well as DampPosMax_RE and DampPosMin_RE are
provided for the evaluation of the damper blade posi-
tions in separate extract air systems (3 fans) for fume
cupboards, extract air and room extract air.
3 The output variables DampPosMax_TE and Damp-
PosMin_TE are provided for the evaluation of the
damper blade positions in the extract air system (1 fan)
for fume cupboards, extract air and room extract air.
4 Status information for damper blade positions Damp-
PosMax_**
BACnet
–
Functional value = 1: All damper blades in
OPEN position (special operating mode,
value = 100%). Override not possible
–
Functional value = 2: All damper blades in
standard operating mode. Override possible
–
Functional value = 3: At least one damper blade
in OPEN position (special operating mode)
Modbus Register: 16, 20, 24, 28
–
Event state = 0: All damper blades in standard
operating mode. Override possible
–
Event state = –1 (FF): All damper blades in
OPEN position (special operating mode, value
= 100 %). Override not possible
–
Event state = 1: At least one damper blade in
OPEN position (special operating mode)
5 Status information for damper blade positions Damp-
PosMin_**
BACnet
–
Functional value = 1: All damper blades in shut-
off mode (special operating mode, value = 0%).
Override not possible
–
Functional value = 2: All damper blades in
standard operating mode. Override possible
–
Functional value = 3: At least one damper blade
in shut-off mode (special operating mode)
Modbus Register: 18, 22, 26, 30
–
Event state = 0: All damper blades in standard
operating mode. Override possible
–
Event state = –1 (FF): All damper blades in shut-
off mode (special operating mode, value = 0 %).
Override not possible
–
Event state = 1: At least one damper blade in
shut-off mode (special operating mode)
Interface information
Data points – detailed description > Output variables
Expansion module EM-BAC-MOD-01
37
Correct use................................................................... 5
D
Damage to property.....................................................
6
Defects liability............................................................. 3
E
Electric current............................................................. 5
Electrostatic charge...................................................... 6
Environmental protection
Batteries.................................................................. 6
Electrical and electronic parts................................. 6
Rechargable batteries............................................. 6
H
Hotline.......................................................................... 3
I
Incorrect use................................................................
5
Interface information
BACnet.................................................................... 9
L
Limitation of liability...................................................... 3
O
Other applicable documentation..................................
3
Q
Qualification.................................................................
6
R
Residual risks............................................................... 5
S
Security........................................................................ 5
Service......................................................................... 3
Signs............................................................................ 5
Software version..........................................................
8
Staff.............................................................................. 6
Symbols.......................................................................
5
System owner's obligations.......................................... 6
T
Technical service.......................................................... 3
Temperature differences..............................................
6
Index
Expansion module EM-BAC-MOD-01
38
© TROX GmbH 2017
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn
Germany
+49 2845 202-0
+49 2845 202-265
[email protected]
http://www.troxtechnik.com