Satel ASD-110 Manual 

Text of the manual

WIRELESS SMOKE AND HEAT DETECTOR

asd110_en 10/11 The ASD-110 multisensor detector can detect the early stages of fire development when there is some visible smoke and/or temperature rise. It can operate as a stand-alone device or as part of the ABAX two-way wireless system. It is supported by the ACU-100 controller with firmware version 3.02 (or l

Note: The alarm memory is cleared after exiting the test mode.

3. Installation The detector is designed for indoor operation. It should be installed on the ceiling, at a minimum distance of 0.5 meters from the walls. Do not install the detector in places with high concentration of dust and/or formation and condensation of water steam. The det

8. Using a soft brush or compressed air, clean the labyrinth in the cover and the base of the

optical chamber, paying attention to the recesses where the LEDs are installed. 9. Replace the cover of the optical chamber. 10. Place the thermistor leads in the respective grooves. 11. Replace the thermistor cover. 12. Secure the electronics board

14. Close the detector enclosure.

5. Battery replacement The detector power supply battery (CR123A 3 V) ensures operation for about 2 years. A low battery status (voltage drop to 2.6 V) is audibly indicated (by a beep every 40 seconds). The information on low battery is sent to the ACU-100 controller / INTEGRA 128-WRL control panel. To replac

Other Security Sensors Manuals