Salda Stouch Technical Manual

Specifications

Brand: Salda
Category: Controller
Model: Stouch (Technical Manual)
File Type: PDF
File Size: —
Pages: 114

Read Online

Read the Salda Stouch Technical Manual online using the built-in PDF viewer.

Text of the manual

Ragainės g. 100, LT-78109 Šiauliai, Lithuania

Tel. (+370 41) 540415 Fax. (+370 41) 540417 [email protected] www.salda.lt Art.-no. P0084_AA_0005 • Sensorinis pultelis • Сенсорный пульт • Sensor controller • Sensorpult • Boîtier de commande tactile • Pannello di controllo touch [ lt ] Psl. 2 [ ru ] Cтр. 20 [ en ] Pg. 39 [ de ] S. 58 [ fr ] P. 77 [ it ] P. 96 Stouch Techninis vadovas Техническое руководство Technical manual Bedienungsanleitung Notice technique Manuale tecnico all-guides com

Stouch valdymo pultelis specialiai sukurtas valdyti:

• SALDA rekuperacines sistemas, kai naudojama įrenginio valdymo automatika su PRV_V21, EKR, MCB arba ECO_v1072 valdikliu; • SALDA oro tiekimo, ištraukimo įrenginius, kai naudojama įrenginio valdymo automatika su ECO_v107 valdikliu; • SALDA ventiliatorius su „EC“ varikliais3; • Modbus protokolu valdomus prietaisus. 1 Įrenginiai: RIS/RIRS 3.0; RIS/RIRS EKO 3.0 2 Įrenginiai: RIRS 200 VER EKO; RIRS 300 VE... EKO 3 Naudojant „EKO“ ventiliatorių valdymui „Stouch“ nuotolinį valdymo pultelį, būtina papildomai naudoti pultelio maitinimo šaltinį bei numatyti jo apsaugą nuo perkrovų ir/arba trumpų jungimų. Valdymo pulteliai garantuoja optimalų eksploatacijos, stebėsenos ir aptarnavimo komfortą bei saugumą. Visos operacijos atliekamos nuotoliniu būdu naudojant valdymo pultelį, kuriame parodomos gedimų ataskaitos ir ap- tarnavimo sąlygos. Ypatybės: • Išskirtinis ir ergonomiškas dizainas; • Plastikinis pultelio korpusas; • Grūdinto stiklo ekranas; • Paprastas naudojimas; • Skirtas virštinkiniam montavimui; • Vieno paspaudimo sensorinis valdymas; • Lengvai valomas; • Skaičių atvaizdavimas ekranėlyje; • Garsinis atsakas į lietimą; • Gali būti prijungtas prie BMS tinklo; • Galima tiesiogiai prijungti prie 0-10 VDC signalu valdomo ventiliatoriaus; • Naudojant 0-10 VDC įėjimą, galima prijungti CO2 arba slėgio jutiklį; • 4 nustatomi greičiai; • Maksimalus ventiliatoriaus greitis, ribotą laiko tarpą (boost); • Blokavimas (užrakinimas) - apsauga nuo vaikų; • Vartotojo meniu galite pakeisti garso, pristabdytosios veiksenos (StandBy), CO2 parametrus. Į pakuotę įeina: Stouch valdymo pultelis, kabelis (13 m), tvirtinimo elementai (sraigtas 3,9x25 DIN 7981 – 2 vnt., nailoninis kaištis 5x25 – 2 vnt., plieninis kalamas kaištis 12x30 – 2 vnt.), techninis vadovas. Matmenys 84 mm 20,5 mm 1,5 mm 84 mm PASTABA: garų surinktuvas atskirai nevaldomas su žemiau įvardintais gaminiais: RIRS 200 V EKO su automatika „Aut. RIRS200VEEC-...k (+ 15..25 oC)“; RIRS 300 V EKO su automatika „Automatika RIRSV 300 VE“. Ši funkcija galima tik įrenginiams su integruota automatika.

1. Atskirkite dangtelį nuo korpuso, kaip pateikta pav. 1, 2;

2. Prie pultelio prijunkite kabelį 2.1- standartinis kabelio jungimas; Montavimas 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 2.2 - specialus jungimas (žiūrėti: “8 kontaktų jungimas”). 3. Pridėkite dangtelį prie sienos norimame aukštyje ir atsižymėkite gręžimo vietas (pav., 3,4); 4. Pažymėtuose vietose išgręžkite 5 mm skyles nailoniniams kaiščiams ir pergręžkite skylę laido nuvedimui į kitą sienos pusę. PASTABA: skylė reikalinga tik tada, jei pajungimo laidas bus jungiamas iš priešingos sienos pusės. Skylės diametrą rinkitės pagal laido jungčių dydį. 5. Įkalkite du nailoninius 5 mm kaiščius į pragręžtas kiaurymes. PASTABA: galima naudoti ir komplekte esančius metalinius kaiščius (pav. 5). 6. Prisukite dangtį prie sienos su komplekte esančiais sraigtais 2,9 x 16 DIN7981C (pav. 6). 60±0,5mm Ø 40 Ø 5 mm

1. Maitinimo šaltinis 24V AC/DC,100 mA (poliariškumas nesvarbus)

2. Maitinimo šaltinis 24V AC/DC 3. GND 4. RS485 B (Modbus) 5. RS485 A (Modbus) 6. GND 7. 0-10 VDC įėjimas (naudojamas slėgio arba CO2 jutikliui). Jutiklis maitinamas nuo atskiro maitinimo šaltinio. 8. 0-10 VDC išėjimas (naudojamas 0..10 VDC ventiliatorių valdymui). Elektrinis pajungimas gali būti atliktas tik kvalifikuoto elektriko pagal, galiojančius tarptautinius ir nacionalinius elektrosaugos, elektros įrenginių įrengimo, reikalavimus. Šis pajungimas naudojamas tuomet, kai netinka standartinis kabelio pajungimas. 2.PASTABA: Maitinimo šaltinis turi būti parenkamas priklausomai nuo pultelio bei oro kokybės keitiklio naudojamos srovės. Maitinimo šaltinis su pulteliu nekomplektuojamas. 8 kontaktų jungimas 1.PASTABA: kai pultelis naudojamas su oro kokybės keitikliu (kurio maitinimo ir analoginio išėjimo GND elektriškai neatskirti), tuomet jų maitinimui turi buti naudojama nuolatine įtampa (DC). DRAUDŽIAMA valdymo pultelio likusį laidą palikti įrenginio automatikos dėžėje! 7. Jeigu prijungimas numatytas iš bet kurios kitos korpuso pusės (kaip parodyta pav. 7), tada korpuse per vidurį reikiamoje pusėje peiliu padarykite išpjovą laidui išvesti. 8. Prijunkite reikalingus laidus korpuse, prakiškite juos pro skylę į kitą sienos pusę arba išveskite į reikiamą pusę ant sienos ir užspauskite korpusą ant dangtelio (pav. 8).

1. Kai pultelis naudojamas su vedinimo įrenginiu kuris yra su integruota automatika

Rekomendacijos pultelio prijungimui prie įrenginių Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - saugiklis G - nuolatinės įtampos (DC) maitinimo šaltinis M1 - EKO ventiliatorių

2. Kai pultelis naudojamas su RIS 150P EKO

M M -RIS 150P EKO3 1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT all-guides com

3. Kai pultelis naudojamas su “EKO” ventiliatoriais

-M1 2,5kW/4A 2970min-1 PE N L +10V Tacho GND 0-10V/PWM -F -F -F -STouch CON1 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8 - 0 - 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A4 N L PE -G 230VAC_24VDC PASTABA: maitnimo šaltinis, apsaugos elementai ir kiti komponentai reikalingi instaliacijai nekomplektuojami su pulteliu.

Ventiliatoriaus greičio nustatymas

B3 Temperatūros nustatymas B4 Padidinti B5 Makslimalus ventiliatoriaus greitis, ribotą laiko tarpą (boost) B6 Pamažinti S1 Segmentinis ekranas L4-L7 Ventiliatoriaus greičio indikacijos Informacija vartotojui • Pultelyje sukurtas paprastas vartotojo meniu garso, temperatūros, miego režimo bei CO2 lygio parametrų nus- tatymui. • Spartusis maksimalaus greičio aktyvavimo mygtukas. • Nustatytos, bei tiekiamo oro temperatūros rodymas skaitmenimis. • Pasirinkto greičio LED indikacija. • Aktyvių gedimų rodymas simboliais: A.01, A.02 ir t.t., bei LED indikacija. • Pultelio miego režimas taupantis energiją. • Galima vėdinimo sistemos išjungimo blokavimo funkcija. • „Apsauga nuo vaikų“ - užrakina pultelį.

Įjungimas 2 sekundes palaikyti B1

Šviečia L1. B1 L1 Išjungimas 2 sekundes palaikyti B1 Užgęsta L1. L1 Pažadinimas iš miego režimo Paliesti bet kurį mygtuką. Miego režime lėtai mirksi L1. B2 B4 B6 L2 Nustatyti ventiliatorių greitį Paliesti B2. Šviečia L2. Greitis reguliuojamas liečiant B4 ir B6 elementus B3 B4 B6 L3 Nustatyti temperatūrą Paliesti B3. Šviečia L3. Temperatūra reguliuojama liečiant B4 ir B6 elementus B4 B6 L4-L7 Keisti pasirinkto nus- tatymo reikšmę Didinti palietus B4, mažinti palietus B6 Segmentiniame ekranėlyje keičiasi skaitmenys. L4, L5, L6, L7 rodo pasirinktą ventiliatorių greitį. B4 B5 B6 L2 Intensyvaus vėdinimo funkcijos(boost) įjungimas / išjungimas 2 sekundes palaikyti B5. Mirksi L2. Segmentiniame ekranėlyje ro domas likęs laikas sekundėmis (virš 600 s laikas rodomas minutėmis). Laikas reguliuo jamas (keičiamas f-jos veikimo būsenoje) liečiant B4 ir B6. Maksimalus BOOST veikimo laikas: 300 min. (5 h). PASTABA: PRV valdikliui laiko negalima reguli- uoti. Jei PRV valdiklyje BOOST laikas nustatytas kaip neribotas, pultelio segmentinis ekranėlis rodo “---”. B1 B4 B6 L4-L7 Gedimų peržiūra ir anuliavimas Anuliuojant 3 sekundes palaikyti B2 ir B3. Paspaudus B1 laikinai nerodomi gedimo kodai. Esant gedimui mirksi L4, L5, L6, L7, bei seg- mentiniame ekranėlyje rodomi gedimo kodai (A.01, A.02 ir t.t.). Gedimų sąrašą peržiūrėti galima liečiant B4 arba B6 myg tukus. Anuliavus gedimo pranešimą, pultelis grįžta į pradinę būseną. Paspaudus B1 vienai minutei nerodomi gedimo kodai, taip leidžiant valdyti temperatūros ir ventiliatorių nustatymus. PASTABA: griežtai draudžiama anuliuoti gedimą nepašalinus jo priežasties. Tai turi atlikti serviso atstovai ar įrenginį aptarnau jantis personalas. B1 L2-L7 Vyksta CO2 prapūtimas Paspaudus B1 laikinai nerodomi indikacija “CO2” Mirksi L2, L3 ir L7, šviečia L4, L5, L6. Seg- mentinis ekranėlis rodo “CO2”. Paspaudus B1 vienai minutei nerodoma indikacija “CO2”, taip leidžiant valdyti temperatūros ir ventiliatorių nustatymus. B2 B3 B5 Įjungaima/išjungiama “apsauga nuo vaikų” 2 sekundes palaikyti B3, B2 ir B5. Neaktyvūs elementai B1, B4 ir B6. Paspaudus neleistiną mygtuką segmentinis ekranėlis rodo „---“ Mirksintis „Con“ užrašas – jungiamasi. Šviečiantis „noC“ užrašas – dingo arba nėra ryšio su valdikliu. PASTABA: šis punktas taikomas kai pultelis naudojamas kaip Modbus master. Ryšio indikacija Ventiliatorių greičių valdymo galimybės • Pagal nustatytus fiksuotus 4 greičius. • Pagal procentini greitį (0,20 - 100 %) tik 0..10 VDC išėjimui bei ECO valdikliui. • Vartotojo meniu greičiai valdomi kas 5 %. • Serviso meniu gali būti konfigūruojami kas 1 % • Dirba pagal 4 greičius, kurių reikšmės nurodytos Paskaliais (Pa) S-touch pultelyje. PASTABA: funkcija galima, kai ventiliatorius ir slėgio daviklis prijungti prie Stouch pultelio. • Intensyvus vėdinimas. Įrenginys vekia maksimaliu našumu (pagal boost konfigūraciją). Maksimalus greitis ap- saugotas laikmačiu, kuris gali būti keičiamas (žr.lentelėje). • Intensyvus vėdinimas (boost) aktyvuojamas sparčiuoju mygtuku. Pasibaigus maksimalaus ventiliatoriaus greičio (boost) nustatytam laikui, automatiškai grįžtama į ankstesnį greitį. • Galima pajungti 0..10 VDC CO2 jutiklį, kuris aktyvuotų maksimalų greitį pagal nurodytus CO2 parametrus.

Norint patekti į vartotojo meniu reikia 3 sekundes laikyti palietus B2, B3.

Vartotojo meniu iš eilės rodomi menių punktų (.01, .02 ir t.t) nustatymai. Meniu punktas pasirenkamas B4 ir B6 elementais. Paspaudus B5 parodoma pasirinkto parametro reikšmė, kurią keisti galima B4 ir B6 elementais. Paspaudus B5 parametras išsaugomas ir grįžtama į meniu. Dėl ribotų segmentinio ekranėlio galimybių .04 ir .05 reikšmės nurodomos 10 kartų mažesnės, t.y. jeigu ekranėlyje rodoma 20, tai reiškia jog tikroji reikšmė yra 20 x 10 = 200. .06 - filtrų laikmatis atstatomas į pradinę būseną 5 sekundes palaikius nuspaustus B2 ir B3 elementus. Filtrų laikmatis taip pat atstatomas į pradinę padėtį anuliuojant gedimo pranešimą. Norint išeiti iš meniu reikia paliesti B1 elementą. Panaudojimo galimybės Šis pultelis gali valdyti kitus (MODBUS protokolu valdomus) pavyzdžiui vėdinimo įrenginius. Tai nustatoma serviso meniu nurodant reikiamus parametrus F.17, F.18, F.19, F.20, F.21 serviso meniu punktuose. Norint valdyti ne tik standartinius įrenginius, F.20 meniu punkte reikia nurodyti „CUSTOM“ bei įrenginių adresus meniu punktu- ose nuo Nr. F.22 iki F.37. Jeigu įrenginiai tokių adresų neturi, nurodytuose meniu punktų laukeliuose reikia įvesti „00:00“. Standartiškai šis pultelis naudojamas su ECO arba PRV valdikliais. PULTELIS (master) MODBUS AHU (slave) 1) Modbus master (pagrindinis) Nr. Pavadinimas Galimos reikšmės Numatyta reikšmė .01 Miego režimas 0 - Išjungtas 1 - 99 užmigimo laikas sekundėmis 0 .02 Garsas 0: Išjungtas 1: 1 – 9 garso tembras 2 .03 Tiekiamos temperatūros rodymas 0: Nerodoma 1: Rodoma pakaitomis su nustatyta 0 .04 CO2 reikalaujama (ppm) 0 – 99 x 10 ppm 20 x 10 .05 CO2 leistinas skirtumas 0 – 99 x 10 ppm 5 x 10 .06 Filtrų laikmatis Rodo dienų skaičių po paskutinio filtrų keitimo. 0 Nuotolinis valdymas (Modbus) Pultelis palaiko pilnai konfigūruojamą Modbus sąsają. Pultelis gali būti ir pagrindiniu ir pagalbiniu įrenginiu mod- bus tinkle, be to, galite jį pilnai valdyti, bei konfigūruoti ne tik per serviso meniu, bet ir per modbus sąsają. Temperatūros nustatymas ir atvaizidavimas • Pultelyje galima nurodyti norimą temperatūrą nuo 15 - 35 °C. • PASTABA: MCB valdiklio valdoma temperatūra yra nuo 0 - 40 °C. (priklauso nuo MCB valdiklio nustatymų). • Galimas tiekiamo oro ir nustatytos temperatūros rodymas pakaitomis (5 sekundes rodoma nustatyta temperatūra, 2 sekundes tiekiamo oro temperatūra)

Panaudojant BMS (Building Management System) sistemą vienu pulteliu galima valdyti kelis įrenginius

sinchroniškai, arba su keliais pulteliais valdyti vieną įrenginį. Naudojant MODBUS protokolą galima keisti visus pultelių parametrus bei stebėti prijungtų jutiklių duomenis. PULTELIS (slave) AHU (slave) BMS AHU (slave) PULTELIS (slave) MODBUS RS485 2) Modbus slave (pagalbinis) 3) Ventiliatoriaus valdymas, kai greitis nustatomas pulteliu ir/arba kompiuteriu per Modbus Naudojant šį pultelį bei CO2 keitiklį galima mažinti patalpoje esančio anglies dvideginio lygį. Serviso meniu pa- sirinkite norimą greičio valdymo būdą (.01), jeigu pasirinkote valdymą pagal nustatytus greičius, tada nurodykite juos: .03, .04, .05, .06 meniu punktuose. PASTABA: oro kokybes keitikliai ir nuotolinis valdymo pultelis (kai valdomas ventiliatorius) turi būti maitinami nuo atskiro maitinimo šaltinio. Su pulteliu jis nekomplektuojamas. PULTELIS (slave) FAN 0...10 VDC MODBUS 4) Slėgio palaikymas, kuris nurodomas pulteliu ir/arba kompiuteriu per Modbus Prijungus 0..10 VDC ventiliatorių ir 0..10 VDC slėgio keitiklį tiesiai prie pultelio galima palaikyti norimą slėgį. Valdymo bei slėgio jutiklio parametrus galima keisti pulteliu. Naudojant pultelį kaip pagalbinį (šiuo principu neval- domas vėdinimo įrenginys) įrenginį yra galimybė valdyti visus parametrus bei stebėti slėgio jutiklio rodmenis. Tam, kad galėtumėme valdyti pagal slėgį, serviso meniu reikia nurodyti šiuos parametrus: • .14 - 1 • .15 ir .16 - pagal slėgio keitiklio parametrus • .11, .12 ir .13 - (PID valdymo koeficientai). Jeigu slėgis palaikomas nekorektiškai, galima šiuos parametrus koreguoti. • .07 - .10 - nurodome fiksuotus greičius Pa. PULTELIS (slave) FAN 0...10 VDC MODBUS slėgio jutiklis 0...10 VDC all-guides com

5) CO2 palaikymas

PULTELIS (master) FAN (vietoje AHU) 0...10 VDC MODBUS CO2 jutiklis 0...10 VDC AHU (slave) Naudojant šį pultelį bei CO2 keitiklį galima mažinti patalpoje esančio anglies dvideginio lygį. Tiesiog prie pačio pultelio reikia prijungti 0..10 VDC CO2 jutiklį ir sukonfigūruoti pultelį. Serviso režime .14 punkte reikia nustatyti 2, o .15 ir .16 nurodome pagal jutiklio specifikaciją. Prijungus CO2 jutiklį ir serviso meniu nustačius nurodytus parametrus, vartotojo meniu reikia nustatyti norimą CO2 lygį (.04) ir leistiną viršyti skirtumą nuo nustatytos (.05) ribos. Viršijus leistiną skirtumą, pultelis automatiškai paleis ventiliatorius maksimaliu (4) greičiu, skaitmeniniame ekranėlyje bus rodomas „CO2“ užrašas. CO2 pasiekus nustatytą lygį (.04), pultelis sugrįš į ankstesnį režimą. PASTABA: oro kokybės keitikliai ir nuotolinis valdymo pultelis (kai valdomas ventiliatorius) turi būti maitinami nuo atskiro maitinimo šaltinio. Su pultleiu jis nekomplektuojamas. Serviso meniu Norint patekti į serviso meniu reikia: 1. Perjungti į būseną „Išjungta“ ( jei pultelis įjungtas, 3 sekundes palaikyti B1 elementą). 2. 3 sekundes palaikyti B1 ir B2. 3. Įvesti apsaugos kodą „022“ su B4, B6 elementais ir patvirtinkite su B5 elementu. Serviso meniu iš eilės rodomi meniu punktų (.01, .02 ir t.t) nustatymai. Meniu punktas pasirenkamas B4 ir B6 elementais. Paspaudus B5 parodoma pasirinkto parametro reikšmė, kurią keisti galima B4 ir B6 elementais. Pas- paudus B5 parametras išsaugomas ir grįžtama į nustatymų meniu. Norint išeiti iš serviso meniu reikia 3 sekundes palaikyti B1 elementą (pultelis perjungiamas į išjungimo būseną). Nr. Pavadinimas Galimos reikšmės Numatyta reikšmė .01 Ventiliatorių valdymas 0: 0..100 % 1: Fiksuotais greičiais 2: Pagal fiksuotus slėgius 1 .02 Išjungimo blokavimas 0: Neblokuojama 1: Ventiliatorius visada pučia minimaliai 1 greičiu 0 .03 1 greitis (%) 0 – 100 20 .04 2 greitis (%) 0 – 100 40 .05 3 greitis (%) 0 – 100 70 .06 4 greitis (boost) (%) 0 – 100 100 .07 1 greitis (Pa) 0 – 999 5 .08 2 greitis (Pa) 0 – 999 10 .09 3 greitis (Pa) 0 – 999 25 .10 4 greitis (boost) (Pa) 0 – 999 40 .11 Slėgio PID – P 0 –999 5 .12 Slėgio PID – I 0 – 999 10 .13 Slėgio PID – D 0 – 999 0 .14 Keitiklis 0: Nėra 1: Slėgio 2: CO2 0 .15 Keitiklio MIN 0 - 250 x 10 0 .16 Keitiklio MAX 1 - 250 x 10 200

Pultelio Modbus master/slave adresas 0: Master

1 - 247: Slave 0 .18 Modbus duomenų perdavimo greitis 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 4 .19 Modbus duomenu paketo nustatymas 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; 1 .20 Valdomas įrenginys (Pultelis automatiškai atpažįsta PRV, EKR, MCB ir ECO plokštes) 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR 0 .21 Valdomo įrenginio Modbus adresas 1 - 247 1 .22 SET Temperature address 00:00 - FF:FF 00:00 .23 SET Fan speed (%) address 00:00 - FF:FF 00:00 .24 SET Fan speed fixed address 00:00 - FF:FF 00:00 .25 SET Pressure address 00:00 - FF:FF 00:00 .26 SET CO2 address 00:00 - FF:FF 00:00 .27 Temperature address 00:00 - FF:FF 00:00 .28 Alarm 1 address 00:00 - FF:FF 00:00 .29 Alarm 2 address 00:00 - FF:FF 00:00 .30 Alarm 3 address 00:00 - FF:FF 00:00 .31 Alarm 4 address 00:00 - FF:FF 00:00 .32 Alarm 5 address 00:00 - FF:FF 00:00 .33 Alarm 6 address 00:00 - FF:FF 00:00 .34 Alarm 7 address 00:00 - FF:FF 00:00 .35 Alarm 8 address 00:00 - FF:FF 00:00 .36 Alarm 9 address 00:00 - FF:FF 00:00 .37 Alarm 10 address 00:00 - FF:FF 00:00 .38 Atkurti pultelio gamyklinius parametrus 0: Ne 1: Taip 0 .39 Modbus (Holding register) tipo parametrų nuskaitymo ir keitimo įrankis 0 - 999 0 .40 Modbus (Coil register) tipo parametrų nuskaitymo ir keitimo įrankis 0 - 999 0 .41 Pultelio versija - - .42 0..10 VDC signalu valdomo ventiliatoriaus paleidimo užlaikymo laikas sekundėmis 0 - 120 0 .43 0..10 VDC Disable / Enable 0: Išjungtas 1: Įjungtas 0 .44 Atkurti PRV valdiklio gamyklinius parametrus PASTABA: pasiekiamas tik prisijungus prie PRV valdiklio 0: Ne 1: Taip 0 .45 Oro srautų valdymo įrankis 0 - 100 0 Atkuriant gamyklinius parametrus reikia pakartotinai įvesti serviso slaptažodį „022“.

F.39 ir F.40 punktuose nurodyto Modbus registrų nuskaitymo ir įrašymo įrankis naudingas tuomet, kai norime nus-

tatyti įrenginio parametrus, kurių pagal nutylėjimą nevaldo pultelis, tačiau tie parametrai pasiekiami per Modbus. F.39 naudojamas Holding tipo registrams, o F.40 naudojamas Coil registrams. Įrankio naudojimas: 1. Nurodomas modbus registro adresas ir užtvirtinamas "MAX" mygtuku. 2. Įrankis nuskaito adreso reikšmę ir parodo segmentiniame ekranėlyje (reikšmė mirksi). 3. Pakeičiame reikšmę "+" ir "-" mygtukų pagalba ir užtvirtiname "MAX" mygtuku. 4. Įrankis įrašo reikšmę į nurodytą registrą ir grįžta į serviso meniu. Modbus registrų nuskaitymo ir įrašymo įrankis Modbus Slave (pagalbinio) adresų lentelė Pavadinimas Galimos reikšmės Tipas Adresas (HEX) Adresas (DEC) Ventiliatorių valdymas 0: 0..100 % 1: Fiksuotais greičiais 2: Pagal fiksuotus slėgius Holding register 0x01 1 Išjungimo blokavimas 0: Neblokuojama 1: Ventiliatorius visada pučia minima- liai 1 greičiu Holding register 0x02 2 1 greitis (%) 0 – 100 Holding register 0x03 3 2 greitis (%) 0 – 100 Holding register 0x04 4 3 greitis (%) 0 – 100 Holding register 0x05 5 4 greitis (boost) (%) 0 – 100 Holding register 0x06 6 1 greitis (Pa) 0 – 999 Holding register 0x07 7 2 greitis (Pa) 0 – 999 Holding register 0x08 8 Dėl riboto segmentinio ekranėlio rodomų simbolių skaičiaus „CUSTOM“ įrenginio modbus adresai įvedami HIGH ir LOW baitais šešioliktainėje sistemoje (HEX). B2 ir B3 mygtukų pagalba pasirenkame HIGH arba LOW baitas, atitinkamai ekranėlyje rodoma „.00“ ir „.00“. F.45 serviso meniu punkte naudingas norint sureguliuoti oro srautus kiekvienam režimui atskirai. Oro srautų valdymo įrankis veikia su MCB ir PRV valdikliais. Įrankio naudojimas: 1. Pasirenkame norimą oro srautą, kurį valdysime - SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3 arba EF.4 (SF ir EF nurodo kuriam ventiliatoriui bus keičiamas oro srauto nustatymas, SF - tiekiamo oro ventiliatorius, EF - ištraukiamo oro ventiliatorius. skaičius nurodo greitį/režimą, kuriam bus keičiamas oro srauto nustatymas). 2. Agregatas perjungiamas i greitį/režimą, kurį pasirinkome. Nuskaityta reikšmė iš valdiklio rodoma segmentin- iame ekranėlyje. 3. B4 ir B6 sensorių pagalba keičiame reikšmes (nuo 0 - 100%), automatiškai keičiasi ir ventiliatorių greitis/oro srautas. 4. B5 sensoriaus pagalba išeiname iš oro srautų keitimo įrankio. Nustatytos reikšmės išsaugojamos valdiklyje. 5. Norėdami pakeisti kitus oro srauto nustatymus, kartoti 1-4 punktus. Oro srautų valdymo įrankis Stouch pulteliai ir kiti Modbus prietaisai gali veikti netinkamai kai PRV automatikoje įjungtas „Compatibility mode“. „Comptaibility mode“ išjungimas Stouch pultelio pagalba: 1. Įeiti į serviso meniu F.40 punktą (Modbus Coil read/write tool). Kaip įeiti į serviso aplinką aprašyta pultelio instrukcijoje. 2. Nurodyti 21 adresą ir paspausti „MAX“ (nurodome „Compatibility mode“ Modbus registrą) 3. Nustatyti „0“ ir paspausti „MAX“ („1“ – įjungtas, „0“ – išjungtas)

3 greitis (Pa) 0 – 999

Holding register 0x09 9 4 greitis (boost) (Pa) 0 – 999 Holding register 0x0A 10 Slėgio PID – P 0 – 999 Holding register 0x0B 11 Slėgio PID – I 0 – 999 Holding register 0x0C 12 Slėgio PID – D 0 – 999 Holding register 0x0D 13 Keitiklis 0: Nėra 1: Slėgio 2: CO2 Holding register 0x0E 14 Keitiklio MIN 0 - 250 x 10 Holding register 0x0F 15 Keitiklio MAX 1 - 250 x 10 Holding register 0x10 16 Pultelio Modbus master/slave adresas 0: Master 1 - 247: Slave Holding register 0x11 17 Modbus duomenų perdavimo greitis 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 Holding register 0x12 18 Modbus duomenu paketo nustatymas 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; Holding register 0x13 19 Valdomas įrenginys 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR Holding register 0x14 20 Valdomo įrenginio Modbus adresas 1 - 247 Holding register 0x15 21 SET Temperature address 00:00 - FF:FF Holding register 0x16 22 SET Fan speed (%) address 00:00 - FF:FF Holding register 0x17 23 SET Fan speed fixed address 00:00 - FF:FF Holding register 0x18 24 SET Pressure address 00:00 - FF:FF Holding register 0x19 25 SET CO2 address 00:00 - FF:FF Holding register 0x1A 26 Temperature address 00:00 - FF:FF Holding register 0x1B 27 Alarm 1 address 00:00 - FF:FF Holding register 0x1E 28 Alarm 2 address 00:00 - FF:FF Holding register 0x1F 29 Alarm 3 address 00:00 - FF:FF Holding register 0x20 30 Alarm 4 address 00:00 - FF:FF Holding register 0x21 31

Alarm 5 address 00:00 - FF:FF

Holding register 0x22 32 Alarm 6 address 00:00 - FF:FF Holding register 0x23 33 Alarm 7 address 00:00 - FF:FF Holding register 0x24 34 Alarm 8 address 00:00 - FF:FF Holding register 0x25 35 Alarm 9 address 00:00 - FF:FF Holding register 0x26 36 Alarm 10 address 00:00 - FF:FF Holding register 0x27 37 Atkurti pultelio gamyklinius parametrus 0: Ne 1: Taip Holding register 0x28 38 Miego režimas 0 - Išjungtas 1 - 99 užmigimo laikas sekundėmis Holding register 0x29 39 Garsas 0: Išjungtas 1: 1 – 9 garso tembras Holding register 0x2A 40 Tiekiamos temperatūros rodymas 0: Nerodoma 1: Rodoma pakaitomis su nustatyta Holding register 0x2B 41 CO2 reikalaujama (ppm) 0 – 99 x 10 ppm Holding register 0x2C 42 CO2 leistinas skirtumas 0 – 99 x 10 ppm Holding register 0x2D 43 SET Temperature 150 – 350 (/10) Holding register 0x2F 44 SET Fan speed (%) 0,20 - 100 Holding register 0x30 45 SET Fan speed fixed 0 - 4 Holding register 0x31 46 SET Pressure 0 – 999 Pa Holding register 0x32 47 Display supply temperature - 500 – 1000 (/10) Holding register 0x34 48 Išsaugoti nustatymus 0: Ne 22: Taip Holding register 0x36 49 0..10 VDC užlaikymas 0 - 120 Holding register 0x37 50 0..10 VDC Disable / Enable 0: Išjungtas 1: Įjungtas Holding register 0x38 51 Current fan speed (%) 0 – 100 % Input register 0x01 1 Current fixed fan speed 0 – 4 Input register 0x02 2 Temperature Setpoint 150 – 350 °C (/10) Input register 0x03 3 Current Temperature - 500 – 1000 (/10) Input register 0x04 4 Pressure Setpoint 0 – 999 Pa Input register 0x05 5 Current pressure 0 – 999 Pa Input register 0x06 6 CO2 Setpoint 0 – 999 ppm Input register 0x07 7 Current CO2 0 – 999 ppm Input register 0x08 8 Alarm 1 address 0/1 Coil 0x01 1 Alarm 2 address 0/1 Coil 0x02 2 Alarm 3 address 0/1 Coil 0x03 3 Alarm 4 address 0/1 Coil 0x04 4 Alarm 5 address 0/1 Coil 0x05 5 all-guides com

Norint išsaugoti konfigūravimo parametrus būtina į 49 registrą įrašyti 22, tuomet nustatymai įrašomi į

EEPROM atmintį, pultelis persikrauna. Indikacija Reikšmė (avarijos aprašymą žiūrėti įrenginio techniniame vadove) A.01 Aktyvuota šilumokaičio priešužšaliminė apsauga A.02 Suveikė išorinė apsauga, pvz. priešgaisrinis įėjimas, užsiteršę filtrai (suveikė slėgio relė), ventiliatoriai A.03 Vandeninio šildytuvo grįžtamo vandens kritinė temperatūra A.04 “P-mA” oro kokybės keitiklio gedimas A.05 Žema įrenginio maitinimo įtampa A.06 Ištraukiamo oro temperatūros jutiklio gedimas A.07 Tiekiamo oro temperatūros jutiklio gedimas A.08 Vandeninio šildytuvo grįžtamo vandens temperatūros jutiklio gedimas A.09 Lauko temperatūros jutiklio gedimas Gedimų pranešimai Kai vėdinimo įrenginys su “ECO” valdikliu Indikacija Reikšmė (avarijos aprašymą žiūrėti įrenginio techniniame vadove) A.01 Aktyvuota šilumokaičio priešužšaliminė apsauga A.02 Suveikė priešgaisrinė apsauga A.03 Užsiteršę filtrai A.04 Ventiliatoriaus gedimas A.05 Žema įrenginio maitnimo įtampa A.06 DTJ100 temperatūros jutiklio gedimas A.07 Šalinamo oro jutiklio temperatūros gedimas A.08 Tiekiamo oro jutiklio temperatūros gedimas A.09 DTJ100 drėgmės jutiklio gedimas A.10 Vandeninio šildytuvo grįžtamo vandens temperatūros jutiklio gedimas A.11 Lauko temperatūros jutiklio gedimas A.12 Perkaitimas A.13 Rotoriaus gedimas A.14 Žemas oro drėgnumas Kai vedinimo įrenginys su “PRV” valdikliu Indikacija Reikšmė A.01 Nutrūkęs rotoriaus diržas A.02 Įjungta židinio apsauga A.03 Įjungta drėgmės reguliavimo funkcija Kai vedinimo įrenginys su “MCB” valdikliu Alarm 6 address 0/1 Coil 0x06 6 Alarm 7 address 0/1 Coil 0x07 7 Alarm 8 address 0/1 Coil 0x08 8 Alarm 9 address 0/1 Coil 0x09 9 Alarm 10 address 0/1 Coil 0x0A 10

Įjungta plokštelinio šilumokaičio priešužšaliminė apsauga

A.05 Plokštelinio šilumokaičio priešužšaliminė apsauga. Sistema išjungta A.06 Plokštelinio šilumokaičio priešužšaliminė apsauga (slėgio relė). Sistema išjungta A.07 Vandeninio šildytuvo priešužšaliminė apsauga. Sistema išjungta A.08 Per žema tiekiamo oro temperatūra A.09 Per aukšta tiekiamo oro temperatūra A.10 Per žema tiekiamo oro temperatūra. Sistema išjungta A.11 Per aukšta tiekiamo oro temperatūra. Sistema išjungta A.12 Pakeiskite tiekiamo oro filtrą (slėgio relė). Sistema išjungta A.13 Pakeiskite ištraukiamo oro filtrą (slėgio relė). Sistema išjungta A.14 Pakeiskite tiekiamo ir ištraukiamo oro filtrus A.15 Pakeiskite tiekiamo ir ištraukiamo oro filtrus. Sistema išjungta A.16 Tiekiamo oro temperatūros jutiklio gedimas. Avarinis režimas A.17 Ištraukiamo oro temperatūros jutiklio gedimas. Avarinis režimas A.18 Šalinamo oro temperatūros jutiklio gedimas. Avarinis režimas A.19 Šviežio oro temperatūros jutiklio gedimas. Avarinis režimas A. 20 Vandeninio šildytuvo vandens temperatūros jutiklio gedimas. Avarinis režimas A. 21 Vandeninio pašildytuvo vandens temperatūros jutiklio gedimas. Avarinis režimas A. 22 Vandeninio aušintuvo vandens temperatūros jutiklio gedimas. Avarinis režimas A. 23 Valdymo dėžės temperatūros jutiklio gedimas. Avarinis režimas A. 24 Tiekiamo oro temperatūros jutiklio gedimas. Sistema išjungta A. 25 Ištraukiamo oro temperatūros jutiklio gedimas. Sistema išjungta A. 26 Šalinamo oro temperatūros jutiklio gedimas. Sistema išjungta A. 27 Šviežio oro temperatūros jutiklio gedimas. Sistema išjungta A. 28 Vandeninio šildytuvo vandens temperatūros jutiklio gedimas. Sistema išjungta A. 29 Vandeninio pašildytuvo vandens temperatūros jutiklio gedimas. Sistema išjungta A. 30 Vandeninio aušintuvo vandens temperatūros jutiklio gedimas. Sistema išjungta A. 31 Valdymo dėžės temperatūros jutiklio gedimas. Sistema išjungta A. 32 Priešgaisrinės sklendės testavimas sėkmingas A. 33 Priešgaisrinės sklendės testavimas nesėkmingas A. 34 Šildytuvo rankinės apsauga A. 35 Šildytuvo automatinės apsauga A. 36 Pašildytuvo rankinės apsauga A. 37 Pašildytuvo automatinės apsauga A.38 Tiekiamo oro ventiliatoriaus apsauga A. 39 Ištraukiamo oro ventiliatoriaus apsauga A. 40 Freoninio aušintuvo apsauga A. 41 Priešgaisrinė apsauga A.42 Tiekiamo oro slėgio apsauga. Sistema išjungta A. 43 Ištraukiamo oro slėgio apsauga. Sistema išjungta A. 44 Nekorektiška konfigūracija A. 45 Intensyvus šildytuvo vėdinimas suveikus rankinei apsaugai

CUSTOM automatikos avarijos (papildyti po CUSTOM

modbus adresų nustatymo) Indikacija Reikšmė A.01 Ventiliatorių klaida A.02 Tiekiamo oro temperatūros jutiklio gedimas A.03 Grįžtamo vandens temperatūros jutiklio gedimas A.04 Lauko temperatūros jutiklio gedimas A.05 Suveikė priešgaisrinė apsauga A.06 Per žema tiekiama temperatūra. ( < -10'C) (A2) A.07 Ventiliatorių perkaitimas. A4 įėjimas (A4) A.08 Jutiklių gedimas A.09 Kritinė grįžtamo vandens temperatūra (A5) A.10 Žema įrenginio maitinimo įtampa (A7) A.11 Perkaitimas. (A6) A.12 Užsiteršę filtrai A.13 Per aukšta tiekiamo oro temperatūra (>40'C) (A6) Kai vedinimo įrenginys su “EKR” valdikliu A. 46 Intensyvus pašildytuvo vėdinimas suveikus rankinei apsaugai A. 47 Vidinės komunikacijos klaida

Пульт управления Stouch создан специально для управления:

• Рекуперационными системами SALDA, когда используется автоматика управления устройством с контроллером PRV_V21, EKR, MCB или ECO_v1072; • Приборами, управляемыми с помощью протокола Modbus. • Вентилятор SALDA с двигателями EC³; • Установки, управляемые с помощью протокола Modbus. Пульты управления гарантируют оптимальные комфортные условия эксплуатации, мониторинга и обслуживания, а также безопасность. Все операции выполняются на расстоянии с помощью пульта дистанционного управления , на котором отображается информация о неисправностях и условия обслуживания. Особенности: • Эксклюзивный и эргономичный дизайн; • Корпус: пластиковый; • Экран: закалённое стекло; • Простота использования; • Предназначен для поверхностного монтажа; • Сенсорное управление одним нажатием; • Легкая чистка; • Изображение цифр на дисплее; • Звуковой ответ на прикосновение; • Может быть подключен к сети BMS; • Может быть непосредственно подключен к вентилятору с управляющим сигналом 0-10 VDC; • С помощью ввода 0-10 VDC можно подключить сенсор CO2 или давления; • Возможность установить 4 скорости; • Максимальная скорость вентилятора в течение ограниченного времени (boost); • Блокировка (замыкание) – защита от детей; • Возможность изменения параметров звука, дежурного режима (StandBy), CO2 в меню пользователя. В комплект входят: Пульт управления Stouch, провод (13 м), крепежные элементы (6 шт.), кабель, винт (3,9 x 25 DIN 7981 – 2 шт.). нейлоновый дюбель 5 x 25 – 2 шт., стальной забиваемый дюбель 12 x 30 – 2 шт., техническое руководство. Размеры 84 mm 20,5 mm 1,5 mm 84 mm ПРИМЕЧАНИЕ: управление вытяжкой не может быть осуществлено с помощью следующих изделий: RIRS 200 V EKO с автоматикой «Aut. RIRS-200VEEC-...k (+15..25 oC)»; RIRS 300 V EKO с автоматикой «Автоматика RIRSV 300 VE». Данная функция возможна только для установок с встроенной автоматикой.

1. Отделите крышку от корпуса, как изображено на рис. 1, 2;

2. Подключите к пульту кабель 2.1- стандартное соединение кабеля Монтаж 2.2 - специальное соединение (смотреть: «8-ми контактное соединение»)). 3. Приложите крышку к стене на нужной высоте и отметьте точки для сверления, pиc. 3, 4; 4. В отмеченных точках высверлите отверстия размером 5 мм для нейлоновых дюбелей и просверлите отверстие для выведения провода на другую сторону стены. ПРИМЕЧАНИЕ: отверстие необходимо лишь в том случае, если соединительный провод будет подключен с другой стороны стены. Подбирайте диаметр отверстия в соответствии с размером контактов кабеля. 5. Вставьте 2 нейлоновых дюбеля рамером 5 мм в высверленные отверстия. ПРИМЕЧАНИЕ: можно использовать прилагаемые в комплекте металлические дюбели, рис. 5. 6. Прикрепите крышку к стене с помощью прилагаемых в комплекте винтов 2,9 x 16 DIN7981C. Pиc. 6. 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 60±0,5mm Ø 40 Ø 5 mm all-guides com

8-ми контактное соединение

1. Источник питания 24V AC/DC, 100 мA 2. Источник питания 24V AC/DC 3. GND 4. RS485 B (Modbus) 5. RS485 A (Modbus) 6. GND 7. Вход 0-10 VDC (используется для датчика давления или CO2) Питание датчика идет от отдельного источника питания. 8. Выход 0-10 VDC (используется для управления вентиляторами 0..10 VDC) Электрическое подключение может выполнять лишь квалифицированный электрик в соответствии с действующими международными и национальными требованиями электробезопасности и требованиями к монтажу электроустановок. ПРИМЕЧАНИЕ 1: Если пульт используется с преобразователем качества воздуха (у которого GND питания и аналогового выхода электрически не разделены), то для их питания должно использоваться постоянное напряжение (DC). ПРИМЕЧАНИЕ 2: Источник питания должен быть подобран в зависимости от тока, потребляемого пультом и преобразователем качества воздуха. Источник питания не входит в комплектацию пульта. Рекомендации по подключению пульта к установкам ВНИМАНИЯ: остальную часть кабеля пульта управления оставлять в щите автоматики запрещено! 7. Если подключение возможно с любой стороны корпуса (как изображено на рис. 7), то в центре корпуса с нужной стороны сделайте прорезь ножом для проведения провода. 8. Подключите нужные провода в корпусе, проведите их через отверстие на другую сторону стены или выведите на нужную сторону на стене и зажмите корпус на крышке, pиc. 8.

1. Когда пульт управления используется с вентиляционным устройством,

который с интегрированной автоматикой Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - предохранитель G - источник питания постоянного напряжения (DC) M1 - вентиляторов EKO Рекомендации по подключению пульта к установкам

2. Когда пульт управления используется с RIS 150P EKO

M M -RIS 150P EKO3 1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT

3. Когда пульт управления используется с “EKO” вентиляторами

-M1 2,5kW/4A 2970min-1 PE N L +10V Tacho GND 0-10V/PWM -F -F -F -STouch CON1 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8 - 0 - 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A4 N L PE -G 230VAC_24VDC ПРИМЕЧАНИЕ: источник питания, элементы защиты и другие компоненты, необходимые для инсталляции, не входят в комплектацию пульта.

Настройка скорости вентилятора

B3 Настройка температуры B4 Увеличить B5 Максимальная скорость вентилятора в течение ограниченного времени (boost) B6 Уменьшить S1 Сегментный дисплей L4-L7 Индикации скорости вентилятора Информация для пользователя • В пульте создано меню пользователя для настройки параметров звука, температуры, дежурного режима и уровня CO2. • Кнопка быстрой активации максимальной скорости. • Численное отображение установленной температуры и температуры приточного воздуха. • LED индикация выбранной скорости. • Отображение неисправностей активных аварий в символах: A.01, A.02 и т.д., а также LED индикация. • Дежурный режим пульта, экономящий электроэнергию. • Возможна функция блокировки выключения вентиляционной системы. • «Защита от детей» – блокирует пульт. all-guides com

ПРИМЕЧАНИЕ: этот пункт применяется, если пульт используется как Modbus master.

Элементы Команда Действие Индикация B1 L1 Включение Держать 2 секунды В1 Горит L1. B1 L1 Выключение Держать 2 секунды В1 Гаснет L1. L1 Пробуждение из дежурного режима Прикоснуться к любой кнопке В дежурном режиме медленно мигает L1. B2 B4 B6 L2 Настройка скорости вентилятора Прикоснуться к В2 Го р и т L 2 . С к о р о с т ь р е г у л и р у ет с я прикосновением к элементам В4 и В6. B3 B4 B6 L3 Настройка температуры Прикоснуться к В3 Горит L3. Температура регулируется прикосновением к элементам В4 и В6. B4 B6 L4-L7 Изменение значения выбранной настройки Увеличение прикосновением к В4, уменьшение прикосновением к В6 На сегментном дисплее меняются цифры. L4, L5, L6, L7 показывают выбранную скорость вентилятора. B4 B5 B6 L2 Включение/ выключение функции интенсивной вентиляции (boost) Держать 2 секунды В5 Мигает L2. На сегментном экране показано оставшееся время в секундах (время свыше 600 с отображается в минутах). Время регулируется (изменяется в состоянии действия функции) прикосновением к B4 и B6. Максимальное время действия BOOST: 300 мин. (5 ч). ПРИМЕЧАНИЕ: Для контроллера PRV время регулировать нельзя. Если на контроллере PRV время BOOST установлено как неограниченное, сегментный экран пульта показывает “---”. B1 B4 B6 L4-L7 Просмотр неисправностей и отмена аварий При отмене 3 секунды удерживать нажатыми B2 и B3. Когда нажат B1, временно не показываются коды неисправности. В случае неисправности мигают L4, L5, L6, L7, а на сегментном экране также отображаются коды неисправности (A.01, A.02 и т. д.). Перечень неисправностей можно просмотреть с помощью прикосновения к кнопкам B4 или B6¬. После отмены сообщения о неисправности пульт возвращается в исходное состояние. При нажатии B1 в течение одной минуты не показываются коды неисправностей, тем самым позволяя управлять установками температуры и вентиляторов. ПРИМЕЧАНИЕ: Строго запрещается отменять неисправность, не устранив ее причину. Это должны сделать представители по сервисному обслуживанию или персонал, обслуживающий устройство. B1 L2-L7 Выполняется продувание СО2 Когда нажат B1, временно не показывается индикация “CO2” Мигают L2, L3 и L7; горят L4, L5, L6. Сегментный экран показывает “CO2”. Когда нажат B1, в течение одной минуты не показывается индикация “C O 2 ”, тем самым позволяя управлять установками температуры и вентиляторов. B2 B3 B5 Включение/ выключение «защиты от детей» Держать 2 секунды В3, В2 и В5 Неактивные элементы В1, В4 и В6. При нажатии неверной кнопки на сегментном дисплее появится „---“. Мигает „Con“ символ - соединяется Сияющий „noC“ символ – пропала или отсутствует связь с контроллером. Индикация связи Возможности управления скоростями вентиляторов • По установленным 4 фиксированным скоростям • В соответствии с процентной скоростью (0,20 – 100 %) только для выхода 0...10 VDC и контроллера ECO. • Скорости в меню пользователя регулируются через каждые 5 % • Скорости в служебном меню могут быть конфигурированы каждый 1 % • По установленным фиксированным 4 значениям давления.

Дистанционное управление (Modbus)

Пульт поддерживает полностью конфигурируемый интерфейс Modbus. Пульт может служить как основным, так и вспомогательным устройством в сети modbus, кроме того, вы можете полностью управлять им и конфигурировать его не только в служебном меню, но и с помощью интерфейса modbus. Меню пользователя Для выхода в меню пользователя нужно 3 секунды держать нажатыми B2, B3. В меню пользователя по порядку отображаются настройки пунктов меню (P.01, P.02 и т.д.). Пункт меню можно выбрать с помощью элементов B4 и B6. При нажатии на B5 появляется значение выбранного параметра, изменить его можно с помощью элементов B4 и B6. При нажатии на B5 происходит сохранение параметра и возврат в меню. В связи с ограниченными возможностями сегментного дисплея значения P.04 и P.05 отображаются в 10 раз меньше, т.е. если на дисплее изображено число 20, это значит, что истинное значение составляет 20 x 10 = 200. .06 - Таймер фильтров восстанавливается в исходное состояние, если 5 секунд удерживать нажатыми элементы B2 и B3. Таймер фильтров также восстанавливается в исходное состояние при отмене сообщения о неисправности. Возможности использования ПУЛЬТ (master) MODBUS Вентиляционное устройство (slave) 1) Modbus master (основной) № Название Возможные значения Предусмотренное значение .01 Дежурный режим 0 – Выключен 1 – 99 время засыпания в секундах 0 .02 Звук 0: Выключен 1: 1 – 9 тембр звука 2 .03 Отображение поступающей температуры 0: Не отображается 1: Отображается попеременно с установленной 0 .04 Требуемый СО2 (ppm) 0 – 99 х 10 ppm 20 x 10 .05 Допустимая разница СО2 0 – 99 х 10 ppm 5 x 10 .06 Таймер фильтров: показывает количество дней после последней замены фильтров. 0 Настройка и отображение температуры • На пульте можно выставить желаемую температуру от 15 до 35 °C. ПРИМЕЧАНИЕ: С помощью контроллера MCB осуществляется управление температурой от 0 до 40 °C (в зависимости от установок контроллера MCB). • Возможно попеременное отображение температуры приточного воздуха и установленной температуры (5 секунд отображается установленная температура, 2 секунды отображается температура приточного воздуха). ПРИМЕЧАНИЕ: по давлению можно управлять только вентилятором, подключенным непосредственно к пульту. Преобразователь давления также должен быть подключен к пульту. Максимальная скорость защищена таймером, который можно менять (см. таблицу). • Интенсивная вентиляция. Установка работает с максимальной мощностью (по конфигурации boost). ксимальная скорость включается быстрой кнопкой. По истечении установленного времени действия • Mаксимальной скорости вентилятора (boost) происходит автоматический возврат к предыдущей скорости. • Можно подключить датчик СО2 0..10 VDC CO2, который будет запускать максимальную скорость в соответствии с заданными параметрами CO2. С помощью данного пульта можно управлять другими устройствами (управляемыми протоколом MOD- BUS) например, вентиляционные установки . Это устанавливается в служебном меню с указанием необходимых параметров в пунктах меню F.17, F.18, F.19, F.20, F.21. Для управления не только стандаp-

тными устройствами в пункте меню F.20 нужно выставить «CUSTOM», а также адреса устройств в пунктах

меню от № F.22 до F.37. Если у устройств нет адресов, в окошках указанных пунктов меню необходимо ввести «00:00». В стандартной версии данный пульт используется с платами управления контроллерами ECO или PRV. Использование системы BMS (Building Management System – Система управления зданием) позволяет с помощью одного пульта синхронно управлять несколькими устройствами или с помощью нескольких пультов управлять одним устройством. С помощью протокола MODBUS можно менять параметры всех пультов и наблюдать за показаниями подключенных датчиков. ПУЛЬТ (slave) вентиляционное устройство (slave) BMS вентиляционное устройство (slave) ПУЛЬТ (slave) MODBUS RS485 2) Modbus slave (вспомогательный) 3) Управление вентилятором, если скорость устанавливается с помощью пульта и/или компьютера через Modbus Используя этот пульт и преобразователь CO2, можно уменьшить уровень углекислого газа в помещении. С помощью данного пульта можно управлять как устройством, так и вентилятором 0..10 VDC. Выберите в служебном меню нужный способ управления скоростью (.01), если вы выбрали управление по установленным скоростям, укажите их в пунктах меню: .03, .04, .05, .06. ПУЛЬТ (slave) ВЕНТИЛЯТОР 0...10 VDC MODBUS 4) Поддержание давления, которое устанавливается с помощью пульта и/или компьютера через Modbus При подключении вентилятора 0..10 VDC и преобразователя давления 0..10 VDC прямо к пульту можно поддерживать нужное давление. Параметры управления и преобразователя давления можно менять с помощью пульта. Использование пульта в качестве вспомогательного устройства („Modbus slave“) дает возможность управлять всеми параметрами и наблюдать за показаниями датчика давления. Для того, чтобы можно было управлять по давлению, в служебном меню нужно указать следующие параметры: • .14 - 1 • .15 и .16 - по параметрам преобразователя давления • .11, .12 ir .13 - (PID коэффициенты управления). Если давление поддерживается неправильно, в данные параметры можно внести исправления. • .07 - .10 - указываем фиксированные скорости в Пa. ПУЛЬТ (slave) ВЕНТИЛЯТОР 0...10 VDC MODBUS датчик давления 0...10 VDC

5) Поддержание CO2

ПУЛЬТ (master) ВЕНТИЛЯТОР (вместо вентиляцион-ного устройства) 0...10 VDC MODBUS датчик СО2 0...10 VDC вентиляционное устройство (slave) Используя этот пульт и преобразователь CO2, можно уменьшить уровень углекислого газа в помещении. Просто к самому пульту нужно подключить датчик СО2 0..10 VDC и сконфигурировать пульт. В служебном режиме в пункте F.14 необходимо выставить 2, а F.15 и F.16 настроить в соответствии со спецификацией датчика. После подключения датчика CO2 и установки указанных параметров в служебном меню необходимо установить нужный уровень СО2 (P.05) и допустимую для превышения разницу с установленным пределом (P.05) в меню пользователя. При превышении допустимой разницы пульт автоматически запустит вентилятор на максимальной (4) скорости, на цифровом дисплее появится надпись «CO2». Когда CO2 достигнет установленного уровня (P.05), пульт вернется в предыдущий режим. Служебное меню Для выхода в служебное меню необходимо: 1. Перейти в состояние „Выключен“ (если пульт включен, подержите элемент B1 нажатым 3 секунды). 2. Подержать нажатыми B1 и B2 3 секунды. 3. Ввести защитный код „022“ с помощью элементов B4, B6 и подтвердить элементом B5. В меню пользователя по порядку отображаются настройки пунктов меню (F.01, F.02 и т.д.). Пункт меню можно выбрать с помощью элементов B4 и B6. При нажатии на B5 появляется значение выбранного параметра, изменить его можно с помощью элементов B4 и B6. При нажатии на B5 происходит сохранение параметра и возврат в меню настроек. Для выхода из служебного меню нужно 3 секунды подержать нажатым элемент В1 (пульт переключается в состояние выключения). ПРИМЕЧАНИЕ: питание преобразователей качества воздуха и пульта дистанционного управления (при управлении вентилятором) должно быть обеспечено от отдельного источника питания. Он не входит в комплектацию пульта. № Название Возможные значения Предусмотренное значение .01 Управление вентиляторами 0: 0..100 % 1: Фиксированными скоростями 2: По фиксированным давлениям 1 .02 Блокировка выключения 0: Не блокируется 1: Вентилятор всегда работает как минимум на 1 скорости 0 .03 1 скорость (%) 0 – 100 20 .04 2 скорость (%) 0 – 100 40 .05 3 скорость (%) 0 – 100 70 .06 4 скорость (boost) (%) 0 – 100 100 .07 1 скорость (Па) 0 – 999 5 .08 2 скорость (Па) 0 – 999 10 .09 3 скорость (Па) 0 – 999 25 .10 4 скорость (boost) (Па) 0 – 999 40 .11 PID давления – P 0 –999 5 .12 PID давления – I 0 – 999 10 .13 PID давления – D 0 – 999 0 .14 Преобразователь 0: Отсутствует 1: Давления 2: СО2 0 .15 Преобразователь МИН. 0 - 250 x 10 0 .16 Преобразователь МАКС. 1 - 250 x 10 200

Адрес пульта Modbus основной/

вспомогательный 0: Master 1 - 247: Slave 0 .18 Скорость передачи данных Modbus 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 4 .19 Установка пакета данных 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; 1 .20 Управляемое устройство (Пульт автоматически распознает платы PRV, EKR, MCB и ECO). 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR 0 .21 Адрес Modbus управляемого устройства 1 - 247 1 .22 Адрес настройки температуры 00:00 - FF:FF 00:00 .23 Адрес настройки скорости вентилятора (%) 00:00 - FF:FF 00:00 .24 Фиксированный адрес настройки скорости вентилятора 00:00 - FF:FF 00:00 .25 Адрес настройки давления 00:00 - FF:FF 00:00 .26 Адрес настройки CO2 00:00 - FF:FF 00:00 .27 Адрес температуры 00:00 - FF:FF 00:00 .28 Адрес сигнала опасности 1 00:00 - FF:FF 00:00 .29 Адрес сигнала опасности 2 00:00 - FF:FF 00:00 .30 Адрес сигнала опасности 3 00:00 - FF:FF 00:00 .31 Адрес сигнала опасности 4 00:00 - FF:FF 00:00 .32 Адрес сигнала опасности 5 00:00 - FF:FF 00:00 .33 Адрес сигнала опасности 6 00:00 - FF:FF 00:00 .34 Адрес сигнала опасности 7 00:00 - FF:FF 00:00 .35 Адрес сигнала опасности 8 00:00 - FF:FF 00:00 .36 Адрес сигнала опасности 9 00:00 - FF:FF 00:00 .37 Адрес сигнала опасности 10 00:00 - FF:FF 00:00 .38 Восстановить заводские параметры пульта 0: Нет 1: Да 0 .39 Инструмент считывания и изменения параметров типа Modbus (Holding register) 0 - 999 0 .40 Инструмент считывания и изменения параметров типа Modbus (Coil register) 0 - 999 0 .41 Версия пульта - - .42 Время задержки запуска вентилятора, управляемого сигналом 0..10 VDC, в секундах 0 - 120 0 .43 0..10 VDC ВКЛ./ВЫКЛ. (ON/OFF) 0: Выключен 1: Включен 0 .44 Восстановить заводские параметры контроллера PRV. ПРИМЕЧАНИЕ: Доступен только при подключении к контроллеру PRV. 0: Нет 1: Да | 0 0 .45 Инструмент управления потоками воздуха. 0 - 100 0 all-guides com

Таблица адресов Modbus Slave (вспомогательного)

Название Возможные значения Тип Адрес (HEX) Адрес (DEC) Управление вентиляторами 0: 0..100 % 1: Фиксированными скоростями 2: По фиксированным давлениям Регистр удерживания 0x01 1 Блокировка выключения 0: Не блокируется 1: Вентилятор всегда работает как минимум на 1 скорости Регистр удерживания 0x02 2 1 скорость (%) 0 – 100 Регистр удерживания 0x03 3 2 скорость (%) 0 – 100 Регистр удерживания 0x04 4 В пунктах F.39 и F.40 указан инструмент для управления и сканирования Modbus, полезен тогда – когда есть потребность установить параметры устройства которых не устанавливает пульт управления, но данные параметры достежимы через Modbus. F.39 нужен для Holding типа регистров, а F.40 для Coil регистров. Пользование устроиством: 1.Указать адрес Modbus и утвердить кнопкой «MAX». 2.Инструмент сканирует адресную значение и указывает на экране (значение мигает). 3.Меняем значение “+” и “-” кнопками и утверждаем «MAX» кнопкой. 4.Инструмент записывает значение в указанный регистр и возвращается в «сервис» меню. Инструмент сканирования и записи регистров Modbus 1. Войти в пункт F.40 меню сервиса (Modbus Coil read/write tool). Описание входа в среду сервиса дано в инструкции по работе пульта. 2. Указать адрес 21 и нажать кнопку «MAX» (указать регистр Modbus режима «Compatibility mode») 3. Установить «0» и нажать кнопку «MAX» («1» – включено, «0» - выключено) Пульты управления Stouch и другие устройства Modbus могут неправильно работать, если в автоматике PRV (ПКД) включен режим Compatibility mode. Режим Compatibility mode можно выключить с помощью пульта S-touch: В пункте F.45 сервисного меню полезен для регулировки потоков воздуха для каждого режима по отдельности. Инструмент управления потоками воздуха действует с контроллерами MCB и PRV. Пользование инструментом: 1. Выбираем желаемый поток воздуха, которым будем управлять – SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3 или EF.4 (SF и EF указывает, для какого вентилятора будет меняться установка потока воздуха, SF – вентилятор приточного воздуха, EF – вентилятор вытяжного воздуха. Число показывает скорость / режим, для которого будет изменяться установка потока воздуха). 2. Агрегат переключается в выбранную скорость / режим. Считанное значение с контроллера отображается на сегментном экране. 3. С помощью сенсоров B4 и B6 изменяем значения (от 0 до 100 %), автоматически изменяется и скорость вентиляторов / поток воздуха. 4. С помощью сенсора B5 выходим из инструмента изменения потоков воздуха. Установленные значения сохраняются в контроллере. 5. Чтобы поменять другие установки потока воздуха, повторяйте действия по пунктам 1-4. Инструмент управления потоками воздуха (заголовок) Для восстановления заводских параметров нужно повторно ввести служебный пароль «022». В связи с ограниченным числом отображаемых на сегментном дисплее символов адреса modbus устройства «CUSTOM» вводятся с помощью старших и младших байтов в шестнадцатеричной системе (HEX). Кнопками B2 и B3 выбираем старший или младший байт, на экране соответственно появляется «H.00» и «L.00».

3 скорость (%) 0 – 100

Регистр удерживания 0x05 5 4 скорость (boost) (%) 0 – 100 Регистр удерживания 0x06 6 1 скорость (Па) 0 – 999 Регистр удерживания 0x07 7 2 скорость (Па) 0 – 999 Регистр удерживания 0x08 8 3 скорость (Па) 0 – 999 Регистр удерживания 0x09 9 4 скорость (boost) (Па) 0 – 999 Регистр удерживания 0x0A 10 PID давления – P 0 – 999 Регистр удерживания 0x0B 11 PID давления – I 0 – 999 Регистр удерживания 0x0C 12 PID давления – D 0 – 999 Регистр удерживания 0x0D 13 Преобразователь 0: Отсутствует 1: Давления 2: СО2 Регистр удерживания 0x0E 14 Преобразователь МИН. 0 - 250 x 10 Регистр удерживания 0x0F 15 Преобразователь МАКС. 1 - 250 x 10 Регистр удерживания 0x10 16 Адрес пульта Modbus основного/ вспомогательного 0: Основной 1 - 247: Вспомогательный Регистр удерживания 0x11 17 Скорость передачи данных Modbus 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 Регистр удерживания 0x12 18 Четность Modbus 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; Регистр удерживания 0x13 19 Управляемое устройство 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR Регистр удерживания 0x14 20 Адрес Modbus управляемого устройства 1 - 247 Регистр удерживания 0x15 21 Адрес настройки температуры 00:00 - FF:FF Регистр удерживания 0x16 22 Адрес настройки скорости вентилятора (%) 00:00 - FF:FF Регистр удерживания 0x17 23 Фиксированный адрес настройки скорости вентилятора 00:00 - FF:FF Регистр удерживания 0x18 24

Адрес настройки давления 00:00 - FF:FF

Регистр удерживания 0x19 25 Адрес настройки СО2 00:00 - FF:FF Регистр удерживания 0x1A 26 Адрес температуры 00:00 - FF:FF Регистр удерживания 0x1B 27 Адрес сигнала опасности 1 00:00 - FF:FF Регистр удерживания 0x1E 28 Адрес сигнала опасности 2 00:00 - FF:FF Регистр удерживания 0x1F 29 Адрес сигнала опасности 3 00:00 - FF:FF Регистр удерживания 0x20 30 Адрес сигнала опасности 4 00:00 - FF:FF Регистр удерживания 0x21 31 Адрес сигнала опасности 5 00:00 - FF:FF Регистр удерживания 0x22 32 Адрес сигнала опасности 6 00:00 - FF:FF Регистр удерживания 0x23 33 Адрес сигнала опасности 7 00:00 - FF:FF Регистр удерживания 0x24 34 Адрес сигнала опасности 8 00:00 - FF:FF Регистр удерживания 0x25 35 Адрес сигнала опасности 9 00:00 - FF:FF Регистр удерживания 0x26 36 Адрес сигнала опасности 10 00:00 - FF:FF Регистр удерживания 0x27 37 Восстановить заводские параметры пульта 0: Да 1: Нет Регистр удерживания 0x28 38 Дежурный режим 0 – Выключен 1 - 99 время засыпания в секундах Регистр удерживания 0x29 39 Звук 0: Выключен 1: 1 – 9 тембр звука Регистр удерживания 0x2A 40 Отображение поступающей температуры 0: Не отображается 1: Отображается попеременно с установленной Регистр удерживания 0x2B 41 Требуемый СО2 (ppm) 0 – 99 x 10 ppm Регистр удерживания 0x2C 42 Допустимая разница СО2 0 – 99 x 10 ppm Регистр удерживания 0x2D 43 SET Temperature 150 – 350 (/10) Регистр удерживания 0x2F 44 SET Fan speed (%) 0,20 - 100 Регистр удерживания 0x30 45 SET Fan speed fixed 0 - 4 Регистр удерживания 0x31 46 SET Pressure 0 – 999 Pa Регистр удерживания 0x32 47 Display supply temperature - 500 – 1000 (/10) Регистр удерживания 0x34 48 Сохранить настройки 0: Нет 22: Да Регистр удерживания 0x36 49

Для сохранения параметров конфигурации необходимо ввести 22 в регистре 49, таким образом

настройки вносятся в память EEPROM, происходит перезагрузка пульта. Индикация Значение (описание аварии смотреть в техническом руководстве к устройству) A.01 Активированная защита теплообменника от замерзания A.02 Сработала внешняя защита напр., противопожарный вход, засорились фильтры (сработало реле давления), вентиляторы A.03 Водяного нагревателя критическая температура возвратной воды A.04 Неисправность преобразователя качества воздуха «P-mA» A.05 Низкое напряжение питания установки A.06 Неисправность датчика температуры вытяжного воздуха A.07 Неисправность датчика приточного воздуха A.08 Неисправность водяного нагревателя датчика температуры возвратной воды A.09 Неисправность датчика наружной температуры Сообщения о неисправности Если вентиляционная установка с контроллером “ECO” 0..10 VDC удержание 0 - 120 Регистр удерживания 0x37 50 0..10 VDC Disable / Enable 0: Выключен 1: Включен Регистр удерживания 0x38 51 Current fan speed (%) 0 – 100 % Регистр входа 0x01 1 Current fixed fan speed 0 – 4 Регистр входа 0x02 2 Temperature Setpoint 150 – 350 °C (/10) Регистр входа 0x03 3 Current Temperature - 500 – 1000 (/10) Регистр входа 0x04 4 Pressure Setpoint 0 – 999 Pa Регистр входа 0x05 5 Current pressure 0 – 999 Pa Регистр входа 0x06 6 CO2 Setpoint 0 – 999 ppm Регистр входа 0x07 7 Current CO2 0 – 999 ppm Регистр входа 0x08 8 Alarm 1 address 0/1 Coil 0x01 1 Alarm 2 address 0/1 Coil 0x02 2 Alarm 3 address 0/1 Coil 0x03 3 Alarm 4 address 0/1 Coil 0x04 4 Alarm 5 address 0/1 Coil 0x05 5 Alarm 6 address 0/1 Coil 0x06 6 Alarm 7 address 0/1 Coil 0x07 7 Alarm 8 address 0/1 Coil 0x08 8 Alarm 9 address 0/1 Coil 0x09 9 Alarm 10 address 0/1 Coil 0x0A 10

Значение (описание аварии смотреть в техническом руководстве к устройству)

A.01 Защита теплообменника от замерзания A.02 Пожарная защита A.03 Засорение фильтров A.04 Неисправность вентилятора A.05 Низкое напряжение A.06 Неисправность датчика температуры DTJ (100) A.07 Неисправность датчика удаляемого воздуха A.08 Неисправность датчика приточного воздуха A.09 Неисправность датчика влажности DTJ (100) A.10 Неисправность датчика температуры возвратной воды A.11 Неисправность датчика наружной температуры A.12 Перегрев A.13 Неисправность ротора A.14 Низкая влажность воздуха Аварии автоматики PRV Индикация Значение (описание аварии смотреть в техническом руководстве к устройству) A.01 Разрыв ремня ротора A.02 Включена защита очага A.03 Включена функция регулирования влажности A.04 Включена защита от замерзания пластинчатого теплообменника A.05 Защита от замерзания пластинчатого теплообменника. Система выключена A.06 Защита от замерзания пластинчатого теплообменника (реле давления). Система выключена A.07 Защита от замерзания водяного нагревателя. Система выключена A.08 Слишком низкая температура приточного воздуха A.09 Слишком высокая температура приточного воздуха A.10 Слишком низкая температура приточного воздуха. Система выключена A.11 Слишком высокая температура приточного воздуха. Система выключена A.12 Замените фильтр приточного воздуха (реле давления). Система выключена A.13 Замените фильтр вытяжного воздуха (реле давления). Система выключена A.14 Замените фильтры приточного и вытяжного воздуха A.15 Замените фильтры приточного и вытяжного воздуха. Система выключена A.16 Неисправность датчика температуры приточного воздуха. Аварийный режим A.17 Неисправность датчика температуры вытяжного воздуха. Аварийный режим A.18 Неисправность датчика температуры удаляемого воздуха. Аварийный режим A.19 Неисправность датчика температуры свежего воздуха. Аварийный режим A. 20 Неисправность датчика температуры воды водяного нагревателя. Аварийный режим Аварии автоматики MCB all-guides com

Неисправность датчика температуры воды водяного подогревателя. Аварийный режим

A. 22 Неисправность датчика температуры воды водяного охладителя. Аварийный режим A. 23 Неисправность датчика температуры контрольной коробки. Аварийный режим A. 24 Неисправность датчика температуры приточного воздуха. Система выключена A. 25 Неисправность датчика температуры вытяжного воздуха. Система выключена A. 26 Неисправность датчика температуры удаляемого воздуха. Система выключена A. 27 Неисправность датчика температуры свежего воздуха. Система выключена A. 28 Неисправность датчика температуры воды водяного нагревателя. Система выключена A. 29 Неисправность датчика температуры воды водяного подогревателя. Система выключена A. 30 Неисправность датчика температуры воды водяного охладителя. Система выключена A. 31 Неисправность датчика температуры контрольной коробки. Система выключена A. 32 Успешное тестирование противопожарной заслонки A. 33 Неуспешное тестирование противопожарной заслонки A. 34 Ручная защита нагревателя A. 35 Автоматическая защита нагревателя A. 36 Ручная защита подогревателя A. 37 Автоматическая защита подогревателя A. 38 Защита вентилятора приточного воздуха A. 39 Защита вентилятора вытяжного воздуха A. 40 Защита фреонового охладителя A. 41 Противопожарная защита A. 42 Защита давления приточного воздуха. Система выключена A. 43 Защита давления вытяжного воздуха. Система выключена A. 44 Некорректная конфигурация A. 45 Интенсивная вентиляция нагревателя при срабатывании ручной защиты A. 46 Интенсивная вентиляция подогревателя при срабатывании ручной защиты A. 47 Ошибка внутренней коммуникации Индикация Значение (описание аварии смотреть в техническом руководстве к устройству) A.01 Ошибка вентиляторов A.02 Неисправность датчика температуры приточного воздуха A.03 Неисправность датчика температуры возвратной воды A.04 Неисправность датчика наружной температуры A.05 Сработала противопожарная защита A.06 Слишком низкая приточная температура. ( < -10’C) (A2) A.07 Перегрев вентиляторов. Вход A4 (A4) A.08 Неисправность датчиков Аварии автоматики EKR

Аварии автоматики CUSTOM (дополнить после определения

адресов modbus CUSTOM) A.09 Критическая температура возвратной воды (A5) A.10 Низкое напряжения питания устройства (A7) A.11 Перегрев. (A6) A.12 Засорение фильтров A.13 Слишком высокая температура приточного воздуха (>40'C) (A6)

Stouch controller is specially designed for control of:

• Salda heat recovery systems, where control boards PRV_V21, EKR, MCB or ECO_v1072 are installed; • SALDA air supply, exhaust units when automatic control is used with ECO_v107 controller; • SALDA fans with EC motors³;; • Devices which are controlled using Modbus protocol. 1 Units: RIS/RIRS 3.0; RIS/RIRS EKO 3.0 2 Units: RIRS 200 VER EKO; RIRS 300 VE... EKO 3 Using the remote controller “Stouch” for “ECO” fans’ control it is necessary to use additional power supply and to provide the protection against overloads and/or short circuits. Remote controllers ensures comfortable operation, monitoring, maintenance and safety. All operations are per- formed remotely by using controller, which shows fault reports and maintenance conditions. Features: • Exceptional and ergonomic design; • Casing: plastic; • Screen: tempered glass; • Easy operation; • Surface mounted; • One touch control; • Easily controlled; • Numbers displayed at screen; • Acoustic response to touch; • Can be connected to BMS network; • Can be directly connected to fan controlled with 0 - 10 VDC signal; • CO2 or pressure sensor can be connected by using 0 - 10 VDC output; • 4 selectable speeds; • Maximum fan speed for limited time period (boost); • Blocking (locking) - protection from children; • In the user menu, parameters of sound, standby menu and CO2 can be changed. Package includes: Stouch controller, cable (13 m), fastening elements (screw 3,9 x 25 DIN 7981-2 pcs. nylon plug 5 x 25 - 2 pcs., hammered steel plug 12 x 30 - 2 pcs.), technical manual. Dimensions NOTE: Remote controllers don’t control cooker hoods separately with following units: RIRS 200 V EKO with “Aut. RIRS-200VEEC-...k (+ 15..25 oC)” automatics; RIRS 300 V EKO with “Automatika RIRSV 300 VE” automatics. This function is possible only with the units that have integrated automatics. 84 mm 20,5 mm 1,5 mm 84 mm

1. Separate the cover form the casing as in pic. 1,2;

2. Connect the cable to the controller 2.1- standard cable connection Installation 2.2 - spec connection (see “8 pin connection”). 3. Put the cover at the intended location on the wall and mark places for the drilling, pic., 3,4; 4. Drill 5 mm holes at the marked places for nylon plugs and the hole throughout the wall to install the cable. NOTE: the hole throughout the wall is necessary to connect the plug in cable from the other side of the wall. The diameter of the hole should correspond the size of cable plugs. 5. Place 2 nylon plugs into 5 mm holes. NOTE: metal plugs included into package also can be used pic. 5. 6. Screw the cover to the wall with the screws 2,9 x 16 DIN7981C included into package. Pic. 6 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 60±0,5mm Ø 40 Ø 5 mm

1. Power supply 24 V AC/DC, 100 mA (polarity is not important)

2. Power supply 24 V AC/DC 3. GND 4. RS485 B (Modbus) 5. RS485 A (Modbus) 6. GND 7. 0-10 VDC input (used for pressure or CO2 sensor). The sensor is powered from a separate power source. 8. 0-10 VDC output (used for control of 0..10 VDC fans). Only competent electrician is allowed to make electrical connections in accordance with the applicable interna- tional and national electrical safety and electrical equipment installation requirements. 1. NOTICE: when the remote controllers are used with air-quality converter (the power supply and analog output GND of witch are not electrically separate), then constant voltage (DC) has to be used for their power supply. 2. NOTICE: The power source must be selected according to the used currents of the remote controller and air quality converter. Power source is not supplied with the remote controller. 8 pin connection 7. If the connection is intended form any side of the casing (as it is shown in pic. 7) than in the middle of the neces- sary casing side make a space for the cable with a knife. 8. Connect the necessary cables in the casing, plug them through the hole to another side of the wall or place to a necessary side of the casing and press the casing on the cover, pic. 8. IT IS FORBIDDEN to leave the remaining remote controller’s cable in the AHU’s control box! all-guides com

1. When control panel is used with air handling unit with integrated automatics

Recommendations for connection of the remote controller to other devices Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - Fuse G - constant voltage (DC) power supply M1 - EKO fans

2. When the remote controller is used with RIS 150P EKO

M M -RIS 150P EKO3 1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT

3. When the remote controller is used with EKO fans

NOTICE: The power source, security elements, and other components necessary for installation are not supplied. -M1 2,5kW/4A 2970min-1 PE N L +10V Tacho GND 0-10V/PWM -F -F -F -STouch CON1 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8 - 0 - 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A4 N L PE -G 230VAC_24VDC

Description of elements

B1 On/Off B2 Fan speed selection B3 Temperature selection B4 Increase B5 Maximum fan speed for limited time (boost) B6 Decrease S1 Segment display L4-L7 Fan speed indications Information for user • Controller allows easy setting of sound, temperature, sleep mode and CO2 level parameters from the user menu. • Fast button for setting maximum speed. • Numerical display of set and supply air temperature. • Selected speed LED indication. • Symbolical display of active alarms: A.01, A.02, etc., and LED indication. • Controller sleep mode to reduce power consumption. • Selectable ventilation system switch off locking feature. • “Child safety feature” - locks the controller.

Switch on Press down for 2 seconds

B1 L1 lights on. B1 L1 Switch off Press down for 2 seconds B1 L1 lights off. L1 Activation from sleep mode Press any button. L1 flashes slowly in sleep mode. B2 B4 B6 L2 Set fan speed Touch B2. L2 lights on. Speed is adjusted by touch- ing elements B4 and B6 B3 B4 B6 L3 Set temperature Touch B3. L3 lights on. Temperature is adjusted by touching elements B4 and B6 B4 B6 L4-L7 Change value of se- lected setting Increase by touching B4, decrease by touching B6 Numbers change in the segment display. L4, L5, L6, L7 shows selected fan speed. B4 B5 B6 L2 Switch on/off the inten- sive ventilation (boost) 2 sekundes palaikyti B5. L2 is blinking. Split screen shows remain- ing time in seconds (if there’re more than 600 sec. then - in minutes). Time can be adjusted by pressing B4 and B5 (in time of processing the function). Maximal BOOST time: 300 minutes (5 hours). Note: Time can’t be adjusted on PRV controller. If unlimited BOOST time is set on PRV controller, then split screen shows “---“. B1 B4 B6 L4-L7 Review and cancel alarms Press B2 and B3 for re- setting By pressing B1 faults are temporary not shown. In case of failure L4, L5, L6, L7 are blinking and failure codes appear on split screen (A.01, A.02 and etc.). List of errors can be reviewed by pressing B4 or B6. After clear- ing fault signal remote controller returns into initial state. By pressing B1 faults are not shown for one minute, thus permitting to adjust temperature and fan settings. Note: it’s strictly forbidden to clear a fault without removing its cause. This must be performed by the service representatives or maintenance personnel. B1 L2-L7 CO2 blow off By pressing B1 indication „CO2“is not shown tem- porary. L2, L3 and L7 are blinking, L4, L5, L6 are shining. Split screen shows “CO2”. By pressing B1 indication “CO2” is not shown for one minute, thus permitting to adjust temperature and fan settings. B2 B3 B5 On/off “Child safety feature” Press down B3, B2 and B5 for 2 seconds. Non active elements B1, B4 and B6. After pressing unavailable button, segment display shows “−−−” Flashing „Con“ – connecting. Shining „noC“ – connection lost or there is no connection with the controller. NOTE: This paragraph applies when the controller is used as a Modbus master. Connection indication Fan speed control options • Selecting 4 preset speeds; • Selecting percentage value of speed (0,20 - 100 %) only for 0...10 VDC output and ECO controller; • User menu speeds are set in intervals of 5 %; • Service menu speeds are set in intervals of 1 %; • Operates in 4 speeds, the values of which are displayed on Stouch in Pascals (Pa). NOTE: the function is available when fan and pressure sensor are connected to Stouch. • Maximum ventilation. The unit operates in maximum speed (according to boost configuration). Maximum speed is limited by timer which can be easily set (see table); all-guides com

In order to reach user menu, press down B2 and B3 for 3 seconds.

In user menu, menu items (P.01, P.02 etc.) settings are displayed sequentially. Menu item is selected using ele- ments B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using elements B4 and B6. Press B5 to save the parameter and to return to menu. Due to limitations of segment display, values of P.04 and P.05 are shown divided by 10, i.e. if 20 is displayed, it means that real value is 20 x 10 = 200. .06 - Filter timer resets by pressing B2 and B3 for more than 5 seconds. Filter timer also resets by clearing fault signal. Touch element B1 to exit menu. Intended use This controller can control other devices (controlled by MODBUS protocol) for example, air handling units. This can be set in service menu by selecting required parameters for service menu items F.17, F.18, F.19, F.20, F.21. To control not only standard devices, select “CUSTOM” in menu item F.20 and device addresses in menu items from F.22 up to F.37. If devices have no such addresses, in fields of given menu items enter “00:00”. Normally, this controller is used with ECO or PRV control boards. CONTROLLER (master) MODBUS AHU (slave) 1) Modbus master (main) No. Name Possible values Default value .01 Sleep mode 0 - Off 1 - 99 sleeping time in seconds 0 .02 Sound 0: Off 1: 1 – 9 sound tone 2 .03 Supply air temperature display 0: Not shown 1: Shown interchangeably with the set temp 0 .04 CO2 required (ppm) 0 – 99 x 10 ppm 20 x 10 .05 CO2 allowed difference 0 – 99 x 10 ppm 5 x 10 .06 Filtrer timer Displaying number of days from the last change of the filters 0 Temperature • Temperature from 15 to 30 C may be set by remote controller. Note: Temperature of MCB controller can be adjusted from 0 up to 40C (it depends on MCB settings). • Supply air and set temperatures can be displayed interchangeably (set temperature is displayed for 5 seconds, then supply air temperature is displayed for 2 seconds) Remote control (Modbus) Controller supports fully configurable Modbus interface. Panel can operate as master and slave device in mod- bus network and also it can be fully controlled and configured not only via service menu but also via modbus interface. • Maximum speed can be activated using fast button. When preset maximum fan speed (boost) time is over, previous speed is automatically restored; • 0..10 VDC CO2 sensor can be connected for activation of maximum speed based on the given CO2 parameters.

Using BMS (Building Management System), several devices can be controlled simultaneously or one device

can be controlled using several controllers. MODBUS protocol allows changing all parameters of controllers and monitoring data of connected sensors. CONTROLLER (slave) AHU (slave) BMS AHU (slave) CONTROLLER (slave) MODBUS RS485 2) Modbus slave 3) Fan control when speed is set using controller and/or computer via Modbus Using this remote controller and CO2 transmitter it is possible to reduce inside carbon dioxide level. This control- ler allows controlling both device and 0..10 VDC fan. In service menu, select desired speed control method (F.01). If control based on preset speeds is selected, then select them in menu items F.03, F.04, F.05, F.06. NOTE: The air quality converters and remote controller (when fan is controlled) must be powered from a sepa- rate power source. It is not supplied with the remote. CONTROLLER (slave) FAN 0...10 VDC MODBUS 4) Pressure control when selected using controller and/or computer via Modbus Desired pressure can be maintained by connecting 0..10 VDC fan and 0..10 VDC pressure converter directly to the controller. Control and pressure sensor parameters can be changed in controller. When controller is used as Modbus slave device (air handling unit is not controlled by this principle), it allows controlling all parameters and monitoring of pressure sensor readings. For pressure based control, select the following parameters in the service menu: • .14 - 1 • .15 and .16 -based on pressure converter parameters • .11, .12 and .13 - (PID control ratios). If pressure is maintained incorrectly, these parameters can be ad- justed. ••.07 - .10 - nurodome fiksuotus greičius Pa. CONTROLLER (slave) FAN 0...10 VDC MODBUS pressure sensor 0...10 VDC

5) CO2 control

CONTROLLER (master) FAN (instead of AHU) 0...10 VDC MODBUS CO2 sensor 0...10 VDC AHU (slave) This controller allows controlling level of carbon dioxide (CO2) in a room. Connect 0..10 VDC CO2 sensor directly to the controller and configure the controller. In service mode, in item F.14 set 2, and F.15 and F.16 should be set based on the sensor specification. After CO2 sensor is connected and required parameters are set in the service menu, select desired CO2 level (P.05) and allowed difference from the set (P.05) limit in the user menu. If allowed difference is exceeded, control- ler will automatically start fans at maximum (4) speed and “CO2” will be shown in digital display. After set CO2 level (P.05) is reached, controller will return to previous mode. NOTE: The air quality converters and remote controller (when fan is controlled) must be powered from a sepa- rate power source. It is not supplied with the remote controller. Service menu To enter service menu: 1. Go to “Off” state (if controller is on, press down element B1 for 3 seconds). 2. Press down B1 and B2 for 3 seconds. 3. Using elements B4 and B6, enter security code “022” and confirm with element B5. In the service menu, settings of menu items (F.01, F.02 etc.) are shown sequentially. Menu item is selected using elements B4 and B6. After pressing B5, value of selected parameter is shown and can be changed using elements B4 and B6. Pressing B5 saves the parameters and returns to the setting menu. To exit the service menu, press down element B1 for 3 seconds (controller goes to switch off state). No. Name Possible values Default value .01 Fan control 0: 0..100 % 1: Fixed speeds 2: Based on fixed pressures 1 .02 Switch of locking 0: Not locked 1: Fan always operates at minimum speed 1 0 .03 Speed 1 (%) 0 – 100 20 .04 Speed 2 (%) 0 – 100 40 .05 Speed 3 (%) 0 – 100 70 .06 Speed 4 (boost) (%) 0 – 100 100 .07 Speed 1 (Pa) 0 – 999 5 .08 Speed 2 (Pa) 0 – 999 10 .09 Speed 3 (Pa) 0 – 999 25 .10 Speed 4 (boost) (Pa) 0 – 999 40 .11 Pressure PID – P 0 –999 5 .12 Pressure PID – I 0 – 999 10 .13 Pressure PID – D 0 – 999 0 .14 Converter 0: No 1: Pressure 2: CO2 0

Converter MIN 0 - 250 x 10

0 .16 Converter MAX 1 - 250 x 10 200 .17 Controller Modbus master/slave address 0: Master 1 - 247: Slave 0 .18 Modbus data transfer rate 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 4 .19 Setting of data package 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; 1 . 20 Operated device (remote controller automati- cally recognizes PRV, EKR, MCB ir ECO control boards). 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR 0 . 21 Modbus address of controlled device 1 - 247 1 . 22 SET Temperature address 00:00 - FF:FF 00:00 . 23 SET Fan speed (%) address 00:00 - FF:FF 00:00 . 24 SET Fan speed fixed address 00:00 - FF:FF 00:00 . 25 SET Pressure address 00:00 - FF:FF 00:00 . 26 SET CO2 address 00:00 - FF:FF 00:00 . 27 Temperature address 00:00 - FF:FF 00:00 . 28 Alarm 1 address 00:00 - FF:FF 00:00 . 29 Alarm 2 address 00:00 - FF:FF 00:00 . 30 Alarm 3 address 00:00 - FF:FF 00:00 . 31 Alarm 4 address 00:00 - FF:FF 00:00 . 32 Alarm 5 address 00:00 - FF:FF 00:00 . 33 Alarm 6 address 00:00 - FF:FF 00:00 . 34 Alarm 7 address 00:00 - FF:FF 00:00 . 35 Alarm 8 address 00:00 - FF:FF 00:00 . 36 Alarm 9 address 00:00 - FF:FF 00:00 . 37 Alarm 10 address 00:00 - FF:FF 00:00 . 38 Restore controller factory settings 0: No 1: Yes 0 . 39 Modbus (Holding register) type parameter reading and changing tool 0 - 999 0 . 40 Modbus (Coil register) type parameter read- ing and changing tool 0 - 999 0 . 41 Control panel version - - . 42 Fan’s controlled by 0..10 VDC signal start delay time in seconds 0 - 120 0

To restore factory settings, service password “022” should be reentered.

Due to limited number of symbols in segment display, modbus addresses of “CUSTOM” device are entered as HIGH and LOW bytes in hexadecimal (HEX) system. Using buttons B2 and B3, select HIGH or LOW bytes, “H.00” and “L.00” are displayed respectively. Modbus register read and record tool indicated in F.39 and F.40 items is useful when you want to set the unit‘s parameters, which by default are not controlled by remote controller, but these parameters are accessible via Modbus. F.39 is used for Holding type registers and F.40 used Coil registers. Using the Tool: 1. Modbus register address is indicated and confirmed by “MAX” button. 2. The tool reads the address value and shows on a segmental display (the value flashes). 3. Change the value with “+” and “-” button and confirm with the MAX button. 4. The tool records the value to indicated register and return to the service menu. Name Possible values Type Address (HEX) Address (DEC) Fan control 0: 0..100 % 1: Fixed speeds 2: Based on fixed pressures Holding register 0x01 1 Switch of locking 0: Not locked 1: Fan always operates at mini- mum speed 1 Holding register 0x02 2 Speed 1 (%) 0 – 100 Holding register 0x03 3 Modbus Slave address table Modbus register read and record tool Stouch control panel and other Modbus devices may not work prop- erly when PRV automation is on the Compatibility mode. “Compatibility mode” can be turned off with Stouch control panel: 1. Go to Service menu item F.40 (Modbus Coil read / write tool). How to enter service interface is described in Stouch technical manual. 2. Specify address 21 and press “MAX” (indicate “Compatibility mode” Modbus register) 3. Set “0” and press “MAX” (“1” - on, “0” - off) . 43 0..10 VDC Disable / Enable 0: OFF 1: ON 0 . 44 Restore factory settings of PRV control board. Note: accessible only by connecting to PRV controller 0: No 1: Yes 0 . 45 Tool for air flow adjustment. 0 - 100 0 Service menu F.45 is used to adjust air flow for different modes. Air flow handling tool operates with MCB and PRV controllers. Tool operation instruction: 1. Select desired air flow, what you want to control: SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3 or EF.4. (SF and EF determine, for which fan airflow will be modified; SF – air supply fan, EF – air exhaust fan. Number determines speed/mode, for which air flow will be modified). 2. Equipment switches to the mode/speed, what was selected. Value from the controller is shown on the split screen. 3. By pressing B4 and B6 you may change values (from 0 up to 100%). Fans speed/airflow changes automatically. 4. By pressing B5 you may exit airflow handling tool. Adjusted settings are saved on controller. 5. In order to change other airflow setting, please repeat steps 1-4. Air flow handling tool all-guides com

Speed 2 (%) 0 – 100

Holding register 0x04 4 Speed 3 (%) 0 – 100 Holding register 0x05 5 Speed 4 (boost) (%) 0 – 100 Holding register 0x06 6 Speed 1 (Pa) 0 – 999 Holding register 0x07 7 Speed 2 (Pa) 0 – 999 Holding register 0x08 8 Speed 3 (Pa) 0 – 999 Holding register 0x09 9 Speed 4 (boost) (Pa 0 – 999 Holding register 0x0A 10 Pressure PID – P 0 – 999 Holding register 0x0B 11 Pressure PID – I 0 – 999 Holding register 0x0C 12 Pressure PID – D 0 – 999 Holding register 0x0D 13 Converter 0: No 1: Pressure 2: CO2 Holding register 0x0E 14 Converter MIN 0 - 250 x 10 Holding register 0x0F 15 Converter MAX 1 - 250 x 10 Holding register 0x10 16 Controller Modbus master/slave address 0: Master 1 - 247: Slave Holding register 0x11 17 Modbus data transfer rate 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 Holding register 0x12 18 Setting of data package 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; Holding register 0x13 19 Controlled device 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR Holding register 0x14 20 Modbus address of controlled device 1 - 247 Holding register 0x15 21 SET Temperature address 00:00 - FF:FF Holding register 0x16 22 SET Fan speed (%) address 00:00 - FF:FF Holding register 0x17 23

SET Fan speed fixed address 00:00 - FF:FF

Holding register 0x18 24 SET Pressure address 00:00 - FF:FF Holding register 0x19 25 SET CO2 address 00:00 - FF:FF Holding register 0x1A 26 Temperature address 00:00 - FF:FF Holding register 0x1B 27 Alarm 1 address 00:00 - FF:FF Holding register 0x1E 28 Alarm 2 address 00:00 - FF:FF Holding register 0x1F 29 Alarm 3 address 00:00 - FF:FF Holding register 0x20 30 Alarm 4 address 00:00 - FF:FF Holding register 0x21 31 Alarm 5 address 00:00 - FF:FF Holding register 0x22 32 Alarm 6 address 00:00 - FF:FF Holding register 0x23 33 Alarm 7 address 00:00 - FF:FF Holding register 0x24 34 Alarm 8 address 00:00 - FF:FF Holding register 0x25 35 Alarm 9 address 00:00 - FF:FF Holding register 0x26 36 Alarm 10 address 00:00 - FF:FF Holding register 0x27 37 Restore controller factory parameters 0: No 1: Yes Holding register 0x28 38 Sleep mode 0 - Off 1 - 99 sleeping time in seconds Holding register 0x29 39 Sound 0: Off 1: 1 – 9 sound tone Holding register 0x2A 40 Supply temperature display 0: Not shown 1: Shown interchangeably with the set temperature Holding register 0x2B 41 CO2 required (ppm) 0 – 99 x 10 ppm Holding register 0x2C 42 CO2 allowed difference 0 – 99 x 10 ppm Holding register 0x2D 43 SET Temperature 150 – 350 (/10) Holding register 0x2F 44 SET Fan speed (%) 0,20 - 100 Holding register 0x30 45 SET Fan speed fixed 0 - 4 Holding register 0x31 46 SET Pressure 0 – 999 Pa Holding register 0x32 47 Display supply temperature - 500 – 1000 (/10) Holding register 0x34 48

Save parameters 0: No

22: Yes Holding register 0x36 49 0..10 VDC holdback 0 – 120 Holding register 0x37 50 0..10 VDC Disable / Enable 0: OFF 1: ON Holding register 0x38 51 Current fan speed (%) 0 – 100 % Input register 0x01 1 Current fixed fan speed 0 – 4 Input register 0x02 2 Temperature Setpoint 150 – 350 °C (/10) Input register 0x03 3 Current Temperature - 500 – 1000 (/10) Input register 0x04 4 Pressure Setpoint 0 – 999 Pa Input register 0x05 5 Current pressure 0 – 999 Pa Input register 0x06 6 CO2 Setpoint 0 – 999 ppm Input register 0x07 7 Current CO2 0 – 999 ppm Input register 0x08 8 Alarm 1 address 0/1 Coil 0x01 1 Alarm 2 address 0/1 Coil 0x02 2 Alarm 3 address 0/1 Coil 0x03 3 Alarm 4 address 0/1 Coil 0x04 4 Alarm 5 address 0/1 Coil 0x05 5 Alarm 6 address 0/1 Coil 0x06 6 Alarm 7 address 0/1 Coil 0x07 7 Alarm 8 address 0/1 Coil 0x08 8 Alarm 9 address 0/1 Coil 0x09 9 Alarm 10 address 0/1 Coil 0x0A 10 Indication Meaning (see device technical manual for alarm description) A.01 Activated heat exchanger antifreeze protection A.02 External protection activated for example, fire emergency exit, filter contamination (pressure rely activated), fans A.03 Return water critical temperature A.04 “P-mA” of water heater A.05 Low unit’s power voltage A.06 Extracted air temperature sensor fault A.07 Supply air temperature sensor fault A.08 Return water temperature sensor fault of water heater A.09 Ambient air temperature sensor fault Alarms ECO automation alarms To save configuration parameters, write 22 to the register 49, then settings are saved to EEPROM mem- ory, controller reloads.

Meaning (see device technical manual for alarm description)

A.01 Heat exchanger antifreeze protection activated A.02 Fire protection activated A.03 Clogged filters A.04 Fan fault A.05 Low voltage A.06 DTJ (100) temperature sensor alarm fault A.07 Exhaust air temperature sensor fault A.08 Supply air temperature sensor fault A.09 DTJ (100) humidity sensor fault A.10 Return water temperature sensor fault A.11 Ambient air temperature sensor fault of water heater A.12 Overheat A.13 Rotor failure A.14 Low air humidity PRV automation alarms Indication Meaning (see device technical manual for alarm description) A.01 Broken rotor belt A.02 Fire place protection is activated A.03 Humidity control function is activated A.04 Anti-frost protection of plate heat exchanger is activated A.05 Anti-frost protection of plate heat exchanger. The system is off. A.06 Anti-frost protection of plate heat exchanger (pressure relay). The system is off. A.07 Anti-frost protection of water heater. The system is off. A.08 Supply air temperature is too low A.09 Supply air temperature is too high A.10 Supply air temperature is too low. The system is off. A.11 Supply air temperature is too high. The system is off. A.12 Please change the supply air filter (pressure relay). The system is off. A.13 Please change the exhaust air filter (pressure relay). The system is off. A.14 Please change the exhaust and supply air filters. A.15 Please change the exhaust and supply air filters. The system is off. A.16 Supply air temperature sensor failure. Emergency mode A.17 Extract air temperature sensor failure. Emergency mode A.18 Exhaust air temperature sensor failure. Emergency mode A.19 Fresh air temperature sensor failure. Emergency mode A. 20 Water heater water temperature sensor failure. Emergency mode MCB automation alarms

Water pre-heater water temperature sensor failure. Emergency mode

A. 22 Water cooler water temperature sensor failure. Emergency mode A. 23 Control box temperature sensor failure. Emergency mode A. 24 Supply air temperature sensor failure. The system is off. A. 25 Extract air temperature sensor failure. The system is off. A. 26 Exhaust air temperature sensor failure. The system is off. A. 27 Fresh air temperature sensor failure. The system is off. A. 28 Water heater water temperature sensor failure. The system is off. A. 29 Water pre-heater water temperature sensor failure. The system is off. A. 30 Water cooler water temperature sensor failure. The system is off. A. 31 Control box temperature sensor failure. The system is off. A. 32 Fire protection damper test is successful A. 33 Fire protection damper test is unsuccessful A. 34 Heater manual protection A. 35 Heater automatic protection A. 36 Pre-heater manual protection A. 37 Pre-heater automatic protection A. 38 Supply air fan protection A. 39 Exhaust air fan protection A. 40 DX cooler protection A. 41 Fire protection A. 42 Supply air pressure protection. The system is off. A. 43 Exhaust air pressure protection. The system is off. A. 44 Incorrect configuration A. 45 Intensive heater cooling by activation of manual protection A. 46 Intensive pre-heater cooling by activation of manual protection A. 47 Internal communication error Indication Meaning (see device technical manual for alarm description) A.01 Fans fault A.02 Supply air temperature sensor fault A.03 Return water temperature sensor fault A.04 Outdoor temperature sensor fault A.05 Fire protection is activated A.06 Supply air temperature is too low ( < -10'C) (A2) A.07 Overheat of fans. A4 input (A4) A.08 Sensors fault A.09 Return water temperature is critical (A5) EKR automation alarms all-guides com

Low power (A7)

A.11 Overheat (A6) A.12 Contaminated filters A.13 Supply air temperature is too high (>40'C) (A6) Indication Meaning A.01 A.02 A.03 A.04 A.05 A.06 A.07 A.08 A.09 A.10 CUSTOM automation alarms (add after setting of CUSTOM modbus addresses)

Das Pult „Stouch“ ist speziell für Bedienung von:

• Rückgewinnungssysteme von SALDA, wenn für Anlage eine Steuerungsautomatik mit Steuerung PRV_V21, EKR, MCB oder ECO_v1072 gebraucht wird; • Geräten, die durch „Modbus“-Protokoll bedient werden, konzipiert. • SALDA Ventilatoren mit EC-Motoren³; • Geräte, die über Modbus-Protokoll gesteuert werden. Bedienpulte gewährleisten einen optimalen Betriebs-, Überwachungs- und Wartungskomfort und Sicherheit. Alle Handlungen werden mit einem Fernbedienungspult ausgeführt, in dem Störungsberichte und Bedingungen für Bedienung gezeigt werden. Eigenschaften • Außergewöhnliches und ergonomisches Design • Gehäuse: Kunststoff; • Bildschirm: vorgespanntes Glas; • Einfacher Gebrauch • Für Überputzmontage bestimmt • Sensorische Bedienung durch einen Druck • Leichte Reinigung • Zahlenabbildung auf dem Bildschirm • Akustische Antwort auf die Berührung • Kann an BMS-Netz angeschlossen werden • Kann direkt an Ventilator, der durch 0 - 10 VDC-Signal bedient wird, angeschlossen werden • Kann durch einen 0 - 10 VDC-Eingang an CO2- oder Druckfühler angeschlossen werden • 4 einstellbare Geschwindigkeiten • Maximale Geschwindigkeit des Ventilators für einen begrenzten Zeitraum (boost) • Blockierung (Absperrung) als Absicherung gegen Kinder • Im Benutzermenü können Parameter für Ton, Bereitschaftsmodus (StandBy) bzw. CO2 geändert werden Im Lieferumfang enthalten: Bedienungspult „Stouch“, Anschlusskabel (13 m), Schrauben 3,9 x 25 DIN 7981 – 2 Stück., Nylon-Stecker 5 x 25 – 2 Stück., Stahl-Stecker 12 x 30 – 2 Stück., technische Handbuch. Abmessungen 84 mm 20,5 mm 1,5 mm 84 mm BEMERKUNG: Dunsthauben werden nicht separat mit folgenden Produkten gesteuert: RIRS 200 V EKO mit Regelung „Aut. RIRS-200VEEC-...k (+ 15..25 oC)“; RIRS 300 V EKO mit Regelung „Automatika RIRSV 300 VE“. Diese Funktion ist nur bei Geräten mit einer integrierten Regelung möglich.

1. Trennen Sie den Deckel vom Gehäuse, siehe Abb. 1, 2;

2. Einen Kabel an das Pult anschließen 2.1 Standartanschluss des Kabels Montage 2.2: spezieller Anschluss, s. 8-Kontakten-Anschluss. 3. Legen Sie den Deckel an die Wand in der gewünschten Höhe und markieren Sie die Bohrungsstellen, siehe Abb. 3, 4; 4. Bohren Sie an markierten Stellen die 5 mm-Öffnungen für Nylonstopfen und bohren Sie eine Öffnung für Kabelverlegung auf die andere Wandseite durch. BEMERKUNG: die Öffnung ist nur dann nötig, wenn der Anschlusskabel von der anderen Wandseite geschlos- sen sein wird. Öffnungsdurchmesser wird laut der Größe von Kabelverbindungen gewählt. 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 60±0,5mm Ø 40 Ø 5 mm

ES IST VERBOTEN, den restlichen Anschlusskabel vom Bedienteil im Schaltschrank des Ger-

ätes bleiben zu lassen! 8-Kontakten-Anschluss 1. 1. Stromversorgung: 24 V AC/DC, 100 mA 2. 2. Stromversorgung 24 V AC/DC 3. 3. GND 4. 4. RS485 B (Modbus) 5. 5. RS485 A (Modbus) 6. 6. GND 7. 0 - 10 VDC - Eingang (für Druck- oder CO2-Fühler). Die Speisung des Fühlers erfolgt durch separate Stromversorgung 8. 0 - 10 VDC - Ausgang (für Bedienung von 0..10 VDC-Ventilatoren). Elektrischer Anschluss kann nur durch qualifizierte Elektrofachkraft laut geltenden internationalen und lokalen Elektroschutzbestimmungen sowie Bestimmungen für Anschluss elektrischer Anlagen ausgeführt werden. 1. ANMERKUNG. Wenn Bedienteil am Bedienteil Luftqualitätssensor angeschlossen ist (bei dem Spei- sung und Analog-Ausgang GND elektrisch nicht getrennt sind), für die Speisung muss permanente Spannung (DC) angeschlossen werden. 2. ANMERKUNG. Netzteil muss entsprechend nach dem von Bedienpult und Luftqualitätsfühler verwen- dete Stromart gewählt werden. Netzteil ist im Lieferumfang nicht enthalten. 5. Schlagen Sie zwei Nylonstopfen in die gebohrten 5 mm-Öffnungen. BEMERKUNG: es können auch Metallstopfen aus dem Lieferumfang verwendet werden, siehe Abb. 5. 6. Schrauben Sie den Deckel mit den Schrauben 2,9 x 16 DIN7981C aus dem Lieferumfang an die Wand, siehe Abb. 6. 7. Wenn der Anschluss von jeder beliebigen Gehäuseseite vorgesehen ist (wie in Abb. 7), machen Sie auf der nötigen Seite in der Gehäusemitte mit dem Messer einen Ausschnitt für die Kabel. 8. Schließen Sie die nötigen Kabel im Gehäuse an, bringen Sie sie durch die Öffnung durch oder führen Sie sie auf nötige Wandseite und drücken Sie das Gehäuse an den Deckel, siehe Abb. 8.

1. Bedienpult mit Lüftungsgerät (nur mit eingebauter Regelung)

Emphelungen zum Anschluss des Bedienteiles an Geräte Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - sicherung G -Gleichspannungsnetzteil (DC) M1 - EKO-Ventilatoren Kanal-CO2-Fühler all-guides com

-RIS 150P EKO3

1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT Kanal-CO2-Fühler 2. Bedienteil mit RIS150 P EKO

3. Bedienteil mit EKO-Ventilatoren

-M1 2,5kW/4A 2970min-1 PE N L +10V Tacho GND 0-10V/PWM -F -F -F -STouch CON1 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8 - 0 - 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A4 N L PE -G 230VAC_24VDC ANMERKUNG. Netzteil, Sicherungen und andere Kompnenten für Instalation sind im Lieferumfang nicht en- thalten! Kanal-CO2-Fühler

Information an Benutzer

• Auf dem Pult einfaches Menü für Ton-, Temperatur-, Ruhezustand- und CO2-Niveau-Einstellung konzipiert • Schnelltaste für Aktivierung der Höchstgeschwindigkeit • Anzeige der eingestellten sowie Zulufttemperatur in Zahlen • LED-Anzeige der ausgewählten Geschwindigkeit • Anzeige der aktiven Störungen in Symbolen: A.01, A.02 usw, sowie LED-Anzeige • Ruhezustand des Pults für das Energiesparen • Ist eine Blockierung der Ausschaltung vom Lüftungssystem möglich • Absicherung gegen Kinder: verriegelt den Pult Bedeutungen der Elemente B1 Ein-/Ausschalten B2 Geschwindigkeitseinstellung vom Ven- tilator B3 Temperatureinstellung B4 Vergrößern B5 Maximale Geschwindigkeit des Venti- lators für einen begrenzten Zeitraum (boost) B6 Verringern S1 Segmentbildschirm L4-L7 Anzeigen der Geschwindigkeiten vom Ventilator

Einschalten B1 drücken und für 2

Sekunden halten L1 leuchtet B1 L1 Ausschalten B1 drücken und für 2 Sekunden halten L1 erlischt L1 Aktivieren aus dem Ruhezustand Beliebige Taste berühren L1 blinkt langsam im Ruhezustand B2 B4 B6 L2 Geschwindigkeit der Ventilatoren einstellen B2 berühren L2 leuchtet; die Geschwindigkeit wird durch Berühren von B4- und B6-Elemente geregelt B3 B4 B6 L3 Temperatur einstellen B3 berühren L3 leuchtet; die Temperatur wird durch Berühren von B4- und B6-Elemente geregelt B4 B6 L4-L7 Gewählte Einstellungs- bedeutung ändern Vergrößerung: B4 berüh- ren, Verringerung: B6 berühren Im Segmentbildschirm ändern sich die Zahlen; L4, L5, L6, L7 zeigen die gewählte Geschwindigkeit der Ventilatoren B4 B5 B6 L2 Ein-/Ausschalten der Funktion für intensive Lüftung (boost) B5 drücken und für 2 Sekunden halten. L2 blinkt. Im Segmentbildschirm wird restliche Zeit in Sekunden gezeigt (nach Überschreitung von 600 s wir die Zeit in Minuten gezeigt). Die Zeit wird durch Antas- ten von B4 und B6 geregelt (im Zustand der Funktionsarbeit geändert). Maximale BOOST-Arbeitszeit: 300 Min. (5 h). HINWEIS: die Zeit der PRV-Steuerung kann nicht geregelt werden. Ist die BOOST-Zeit in der PRV-Steuerung als unbegrenzt eingestellt, zeigt der Segmentbildschirm vom Pult “---”. B1 B4 B6 L4-L7 Übersicht und Annul- lierung der Störungen Zur Löschung B2 und B3 drücken und für 3 Sekunden halten. Nachdem B1 gedrückt wird, werden die Ken- nzahlen von Störungen für kurze Zeit nicht gezeigt. Im Falle einer Störung blinken L4, L5, L6, L7 und im Segmentbildschirm werden Ken- nzahlen von Störungen (A.01, A.02 usw.) gezeigt. Liste der Störungen kann durch Antasten von B4- und B6-Tasten angesehen werden. Nach Löschung der Störungsmit- teilung kehrt der Pult in die Anfangsstellung. Nachdem B1 gedrückt wird, werden die Kennzahlen von Störungen für eine Minute nicht gezeigt und so wird die Steuerung von Temperatur- bzw. Lüftereinstellungen ermöglicht. ANMERKUNG. Löschung der Störung ohne Beseitigung ihrer Ursache ist streng verboten. Das muss durch Servicemitar- beiter oder Bedienpersonal der Anlage ausgeführt werden. B1 L2-L7 Läuft CO2-Spülung Nachdem B1 gedrückt wird, wird die Anzeige “CO2” für kurze Zeit nicht gezeigt L2, L3 und L7 blinken nicht, L4, L5, L6 blinken. Segmentbildschirm zeigt “CO2”. Nachdem B1 gedrückt wird, wird die Anzeige “CO2” nicht gezeigt und so wird die Steuerung von Temperatur- bzw. Lüftereinstellungen ermöglicht. B2 B3 B5 Absicherung gegen Kinder wird ein-/ ausge- schaltet B3, B2 und B5 drücken und für 2 Sekunden halten Inaktive Elemente B1, B4 und B6; nach Drücken einer nicht zugelassenen Taste zeigt der Segmentbildschirm „---“ Anzeige „Con“ blinkt - verbinden Anzeige „noC“ leuchtet - keine Verbindung ANMERKUNG. Diesen Punkt beachten nur wenn Bedienpult als Modbus master verwendet ist. Verbindungsanzeige

• Im Pult kann die gewünschte Temperatur von 15 bis 35°C gezeigt werden. HINWEIS: MCB-Steuerung steuert

die Temperatur von 0 bis 40°C (hängt von Einstellungen der MCB-Steuerung ab). • Mögliche abwechselnde Anzeige der Zuluft- sowie eingestellten Temperatur (für 5 Sekunden wird eingestellte Temperatur und für 2 Sekunden Zulufttemperatur gezeigt) Benutzermenü Fürs Öffnen des Benutzermenüs müssen B2 bzw. B3 berührt und für 3 Sekunden gehalten werden. Im Benutzermenü werden Einstellungen von Menüpunkten nacheinander (P.01, P.02 usw.) gezeigt. Menüpunkt wird durch B4- und B6-Elemente gewählt. Nach Drücken von B5 wird die Bedeutung vom ausgewählten Menü gezeigt, die durch B4- und B6-Elemente geändert werden kann. Nach Drücken von B5 wird der Parameter ges- peichert und man kehrt ins Menü zurück. Wegen begrenzter Möglichkeiten des Segmentbildschirms werden die Werte 10 Mal kleiner gezeigt, d. h. wenn auf dem Bildschirm die Zahl 20 gezeigt wird, bedeutet das, dass echter Wert 20 x 10 = 200 ist. .06 - Zeitmesser der Filter wird auf Anfangsstellung zurückgesetzt, nachdem die Elemente B2 und B3 für 5 Sekunden gedrückt und gehalten werden. Zum Verlassen des Menüs B1-Element berühren. Nutzungsmöglichkeiten Mit diesem Pult können andere Geräte (die durch MODBUS-Protokoll bedient werden) gesteuert werden. Das wird im Servicemenü durch Angabe von nötigen Parametern in Punkten F.17, F.18, F.19, F.20, F.21 des Service- menüs eingestellt werden. Falls man nicht nur Standardgeräte bedienen will, muss man im Menüpunkt F.20 PULT (master) MODBUS AHU (slave) 1) Modbus slave (untergeordnet) zeigt die Tageanzahl nach dem letzten Filterwechsel. Nr. Bezeichnung Mögliche Bedeutungen Vorgesehene Bedeutung .01 Ruhezustand 0: ausgeschaltet 1 - 99: Einschlafzeit in Sekunden 0 .02 Ton 0: ausgeschaltet 1: 1 - 9 Tonfarbe 2 .03 Anzeige der gelieferten Temperatur 0: nicht angezeigt 1: wird abwechselnd mit einges- tellter Temperatur gezeigt 0 .04 CO2 gefordert (ppm) 0 – 99 x 10 ppm 20 x 10 .05 Zugelassener Unterschied von CO2 0 – 99 x 10 ppm 5 x 10 .06 Filter-Betriebsstundenzähler: zeigt die Tageanzahl nach dem letzten Filterwechsel. 0 Fernbedienung (Modbus) Das Pult unterstützt eine völlig konfigurierbare Modbus-Schnittstelle. Das Pult kann als Haupt- und Hilfsgerät im Modbus-Netz funktionieren, es kann nicht nur durch Servicemenü, sondern auch durch Modbus-Schnittstelle völlig bedient und konfiguriert werden. Geschwindigkeitssteuerung der Ventilatoren • Laut fixierten 4 Geschwindigkeitswerten • Laut dem Prozentanteil der Geschwindigkeit (0,20 – 100 %) nur für 0...10 VDC-Ausgang und ECO-Steuerung. • Geschwindigkeiten des Benutzermenüs werden je 5 % gesteuert • Geschwindigkeiten des Servicemenüs werden je 1 % gesteuert • Arbeitet in 4 Stufen, die Werte werden auf Stouch in Pasal (Pa) angezeigt. ANMERKUNG. Funktion ist verfügbar, wenn Ventilator und Druckfühler am Stouch Bedienteil angeschlossen sind. • Maximale Geschwindigkeit wird durch Zeitmesser geschützt, der durch Aktivierung maximaler Geschwindigkeit des Ventilators (boost) leicht geändert werden kann (siehe bitte Tabelle). • Intensivlüftung. Das Gerät arbeitet mit maximaler Geschwindigkeit (nach boost-Einstellung). • Kann 0..10 VDC - Fühler für CO2 angeschlossen werden, der eine maximale Geschwindigkeit laut angege- benen CO2 - Parametern aktivieren würde all-guides com

Unter Benutzung des BMS-Systems (Building Management System) können mehrere Geräte mit einem Pult

synchron oder ein Gerät kann mit mehreren Pulten bedient werden. Unter Benutzung des MODBUS-Protokolls können alle Pultparameter geändert und die Angaben von angeschlossenen Fühlern überwacht werden. PULT (slave) AHU (slave) BMS AHU (slave) PULT (slave) MODBUS RS485 2) Modbus slave (untergeordnet) 3) Bedienung des Ventilators, wenn die Geschwindigkeit mit dem Pult und/oder Computer durch Modbus eingestellt wird ANMERKUNG. Für Luftqualitätsfühler und Bedienteil beim Ventilatorsteuerung wird Stromzufuhr durch ex- ternen Netzteil realisiert. netzteil ist im Lieferumfang nicht enthalten. Mit diesem Pult kann sowohl das Gerät als auch der 0..10 VDC-Ventilator bedient werden. Im Servicemenü gewünschte Bedienart der Geschwindig- keit (F.01) wählen; falls die Bedienung laut eingestellten Geschwindigkeitswerten gewählt ist, diese angeben: Menüpunkte F.03, F.04, F.05, F.06. PULT (slave) VENTILATOR 0...10 VDC MODBUS 4) Druckbehalten, das mit dem Pult und/oder Computer durch Modbus angegeben wird Nach direktem Anschluss des 0..10 VDC-Ventilators oder des 0..10 VDC-Druckwechslers am Pult kann gewün- schter Druck behalten werden. Parameter der Bedienung und der Druckfühlers können mit dem Pult geändert werden. Falls das Pult als Hilfsgerät („Modbus slave“) benutzt wird, ist es möglich, alle Parameter zu bedienen und Anzeigen des Druckfühlers zu überwachen. Damit die Bedienung laut dem Druck möglich wäre, müssen im Servicemenü folgende Parameter angegeben werden:- in diesem fall wird das Lüftungsgerät durch den Pult nicht gesteuert) • .14 - 1 • .15 und .16 - laut Parametern des Druckwechslers • .11, .12 und .13 - (PID-Bedienkoeffizienten). Wenn der Druck unkorrekt behalten wird, können diese Pa- rameter korrigiert werden. • .07 bis .10 - werden fixierte Geschwindigkeiten Pa angegeben. PULT (slave) VENTILATOR 0...10 VDC MODBUS Druckfühler 0...10 VDC CUSTOM sowie Geräteadressen in Menüpunkten von F.22 bis F.37 angeben. Wenn die Geräte diese Adressen nicht besitzen, muss in angegebenen Punktfeldern 00:00 eingegeben werden. Üblicherweise wird dieses Pult mit ECO- oder PRV-Bedienplatten benutzt.

5) Beibehaltung von CO2

PULT (master) VENTILATOR (anstelle von AHU) 0...10 VDC MODBUS CO2 Fühler 0...10 VDC AHU (slave) Mit Hilfe dieses Pults kann Niveau des Kohlendioxids (CO2) im Raum gesteuert werden. Am selben Pult muss der 0..10 VDC-Fühler für CO2 angeschlossen und das Pult konfiguriert werden. Im Punkt F.14 des Servicebetriebs muss die Zahl 2 eingestellt werden, und in F.15 und F.16 wird sie laut Beschreibung des Fühlers angegeben. Nach Anschluss des CO2-Fühlers und der Einstellung von angegebenen Parametern soll im Benutzermenü das gewünschte CO2-Niveau und der Unterschied von der eingestellten (P.05) Grenze, der überschritten werden darf, eingestellt werden. Nach Überschreitung des zugelassenen Unterschieds löst das Pult automatisch die Ventila- toren mit einer maximalen Geschwindigkeit (4) aus und im Bildschirm wird die Aufschrift „CO2“ gezeigt. Nachdem CO2 das eingestellte Niveau erreicht (P.05), kehrt das Pult in frühere Betriebsart zurück. ANMERKUNG. Für Luftqualitätsfühler und Bedienteil beim Ventilatorsteuerung wird Stromzufuhr durch ex- ternen Netzteil realisiert. netzteil ist im Lieferumfang nicht enthalten. Servicemenü Zum Aufruf des Servicemenüs: 1. in den Zustand Ausgeschaltet umschalten (wenn das Pult eingeschaltet ist, Element B1 für 3 Sekunden ge- drückt halten), 2. B1 und B2 für 3 Sekunden gedrückt halten, 3. Sicherheitscode „022“ mit Elementen B4 und B6 eingeben und mit dem Element B5 bestätigen. Im Servicemenü werden die Einstellungen von Menüpunkten (F.01, F.02 usw.) nacheinander gezeigt. Menüpunkt wird mit Elementen B4 und B6 ausgewählt. Nach dem Drücken von B5 wird Parameter gespeichert und man kehrt ins Menü für Einstellungen zurück. Zum Verlassen des Servicemenüs muss das Element B1 gedrückt und für 3 Sekunden gehalten werden (das Pult wird in den Ausschaltungszustand umgeschaltet). Nr. Bezeichnung Mögliche Bedeutungen Vorgesehene Bedeutung .01 Steuerung der Ventilatoren 0: 0..100 % 1: Mit fixierten Geschwindigkeitswerten 2: Laut fixierten Druckwerten 1 .02 Blockierung der Ausschaltung 0: Wird nicht blockiert 1: Der Ventilator bläst immer mit einer minimalen 1. Geschwindigkeit 0 .03 1. Geschwindigkeit (%) 0 – 100 20 .04 2. Geschwindigkeit (%) 0 – 100 40 .05 3. Geschwindigkeit (%) 0 – 100 70 .06 4. Geschwindigkeit (boost) (%) 0 – 100 100 .07 1. Geschwindigkeit (Pa) 0 – 999 5 .08 2. Geschwindigkeit (Pa) 0 – 999 10 .09 3. Geschwindigkeit (Pa) 0 – 999 25 .10 4. Geschwindigkeit (boost) (Pa) 0 – 999 40 .11 PID-P des Drucks 0 –999 5 .12 PID-I des Drucks 0 – 999 10 .13 PID-D des Drucks 0 – 999 0

1: Vom Druck

2: Von CO2 0 .15 MIN des Tauschers 0 - 250 x 10 0 .16 MAX des Tauschers 1 - 250 x 10 200 .17 Adresse von Modbus master/slave (Haupt-/ untergeordnetes Gerät) des Pultes 0: Master 1 - 247: Slave 0 .18 Übergabegeschwindigkeit der Modbus- Daten 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 4 .19 Einstellung des Datenpakets 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; 1 . 20 Gesteuerte Anlage (der Pult erkennt PRV-, EKR-, MCB- und ECO-Platten automatisch) 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR 0 . 21 Modbus-Adresse des gesteuerten Gerätes 1 - 247 1 . 22 SET Temperature address 00:00 - FF:FF 00:00 . 23 SET Fan speed (%) address 00:00 - FF:FF 00:00 . 24 SET Fan speed fixed address 00:00 - FF:FF 00:00 . 25 SET Pressure address 00:00 - FF:FF 00:00 . 26 SET CO2 address 00:00 - FF:FF 00:00 . 27 Temperature address 00:00 - FF:FF 00:00 . 28 Alarm 1 address 00:00 - FF:FF 00:00 . 29 Alarm 2 address 00:00 - FF:FF 00:00 . 30 Alarm 3 address 00:00 - FF:FF 00:00 . 31 Alarm 4 address 00:00 - FF:FF 00:00 . 32 Alarm 5 address 00:00 - FF:FF 00:00 . 33 Alarm 6 address 00:00 - FF:FF 00:00 . 34 Alarm 7 address 00:00 - FF:FF 00:00 . 35 Alarm 8 address 00:00 - FF:FF 00:00 . 36 Alarm 9 address 00:00 - FF:FF 00:00 . 37 Alarm 10 address 00:00 - FF:FF 00:00 . 38 Werkeinstellungen des Pultes herstellen 0: Nein 1: Ja 0 . 39 Modbusparametern (Holding register) ablesen und einstellen 0 - 999 0 . 40 Modbusparametern (Coil register) ablesen und einstellen 0 - 999 0 . 41 Version des Bedienteiles - -

Bei der Herstellung von Werkeinstellungen muss Service-Passwort „022“ wiederholt eingegeben werden.

Wegen der begrenzten Zahl von Symbolen, die auf dem Segmentbildschirm gezeigt werden, werden die Mod- bus-Adressen vom CUSTOM-Gerät mit HIGH- und LOW-Bytes im hexadezimalen System (HEX) eingegeben werden. Mit Hilfe von B2- und B3-Tasten wird HIGH- oder LOW- Byte gewählt, auf dem Bildschirm werden de- mentsprechend „H.00“ und „L.00“ gezeigt. Das Ablesen und Aufhahme von Modbus-Registern, das in Punkten F.39 und F.40 angegeben ist, ist dann hilf- sreich, wenn die Parametern vom Gerät vorhanden, sind aber nur durch Modbus. Modbus zugreifbar. F.39 ist für Register von Holding-Typ, und F.40 für Register von Coil-Typ vorgesehen. Verwendung: 1. Es wird die Adresse von Modbus-Register angegeben und durch “MAX” Taste bestätigt. 2. Information von Modbus-Adresse wird gelesen und erscheint auf dem Bildschirm (Anzeige blinkt). 3. Wert auf dem Bildschirm ist durch Tasten “+” und “-” zu ändern und durch “MAX” Taste zu bestätigen. 4. Wert wird in das angegebe register aufgenommen und Bedienteil kehrt in Service-Menü zurück. Ablesen und Aufnahme von Modbus-Registern Stouch-Pulte und Modbus-Geräte können nicht richtig funktionie- ren, wenn in der PRV-Automatik Compatibility mode eingeschaltet ist. Ausschaltung von Compatibility mode mit Hilfe eines Stouch- Pultes: 1. Im Servicemenü F.40-Punkt wählen (Mdbus Coil read/write tool). Auswahl der Service-Umgebung ist in der Anleitung des Pultes beschrieben; 2. Adresse 21 angeben und MAX drücken (Modbus-Register für Compatibility mode ist angegeben); 3. 0 einstellen und MAX drücken (1 ‒ eingeschaltet, 0 ‒ ausgeschaltet). . 42 Startverzögerungszeit in Sekunden von Venti- lator, der 0...10 VDC geregelt wird 0 - 120 0 . 43 0..10 V DC Aktivieren/Deaktivieren 0: Ausgeschaltet 1: Eingeschaltet 0 . 44 Fabrikeinstellungen von der PRV-Steu- erung zurücksetzen HINWEIS: nur nach Anschluss an PRV- Steuerung erreichbar 0: Nein 1: Ja 0 . 45 Werkzeug für Steuerung von Luftströmen 0 - 100 0 Beim Zurücksetzen der Werkeinstellugen Service-Passwort „002“ wiederholt eingeben. . 45 im Punkt des Servicemenü ist bei Regelung von Luftströmen für jede Betriebsart nützlich. Tool für Steuerung von Luftströmen funktioniert mit MCB- und PRV-Steuereinheiten. Gebrauch des Tools: 1 Gewünschten Luftstrom, der gesteuert sein wird, wählen: SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3 oder EF.4 (SF und EF zeigen an, für welchen Lüfter die Einstellung des Luftstroms geändert wird, SF – Lüfter der Zuluft, EF – Lüfter der Abzugsluft; die Zahl zeigt Geschwindigkeit/Betriebsart, für die die Einstellung des Luftstroms geändert wird). 2 Das Aggregat wird in die gewählte Geschwindigkeit/Betriebsart umgeschaltet. Abgelesener Wert aus der Steu- ereinheit wird auf dem Segmentbildschirm angezeigt. 3 Mit Hilfe der B4- und B6-Sensoren werden die Werte geändert (von 0 bis 100%), Geschwindigkeit/Luftstrom der Lüfter ändert sich automatisch. 4 Das Tool für Änderung von Luftströmen wird mit Hilfe des B5-Sensors verlassen. Eingestellte Werte werden auf der Steuerungseinheit gespeichert. 5 Für Änderung von Einstellungen anderer Luftströme Punkte 1 bis 4 wiederholen. Tool für Steuerung von Luftströmen (Überschrift)

Bezeichnung Mögliche Bedeutungen

Art Adresse (HEX) Adresse (DEC) Steuerung der Ventilatoren 0: 0..100 % 1: mit fester Drehzahl 2: nach festem Druck Holding register 0x01 1 Blockierung der Abschaltung 0: Wird nicht blockiert 1: Der Ventilator bläst immer mini- mal mit der 1. Geschwindigkeit Holding register 0x02 2 1. Geschwindigkeit (%) 0 – 100 Holding register 0x03 3 2. Geschwindigkeit (%) 0 – 100 Holding register 0x04 4 3. Geschwindigkeit (%) 0 – 100 Holding register 0x05 5 4. Geschwindigkeit (boost) (%) 0 – 100 Holding register 0x06 6 1. Geschwindigkeit (Pa) 0 – 999 Holding register 0x07 7 2. Geschwindigkeit (Pa) 0 – 999 Holding register 0x08 8 3. Geschwindigkeit (Pa) 0 – 999 Holding register 0x09 9 4. Geschwindigkeit (boost) (Pa) 0 – 999 Holding register 0x0A 10 PID-P des Drucks 0 – 999 Holding register 0x0B 11 PID-I des Drucks 0 – 999 Holding register 0x0C 12 PID-D des Drucks 0 – 999 Holding register 0x0D 13 Wechslers 0: Kein 1: Vom Druck 2: Von CO2 Holding register 0x0E 14 MIN des Wechslers 0 - 250 x 10 Holding register 0x0F 15 MAX des Wechslers 1 - 250 x 10 Holding register 0x10 16 Adresse von Modbus-Master/- Slave des Pults 0: Master 1 - 247: Slave Holding register 0x11 17 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 Holding register 0x12 18 Einstellung des Datenpakets 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; Holding register 0x13 19 Adressentabelle von Modbus slave (untergeordnet) all-guides com

Modbus-Adresse des gesteuerten

Gerätes 1 - 247 Holding register 0x15 21 SET Temperature address 00:00 - FF:FF Holding register 0x16 22 SET Fan speed (%) address 00:00 - FF:FF Holding register 0x17 23 SET Fan speed fixed address 00:00 - FF:FF Holding register 0x18 24 SET Pressure address 00:00 - FF:FF Holding register 0x19 25 SET CO2 address 00:00 - FF:FF Holding register 0x1A 26 Temperature address 00:00 - FF:FF Holding register 0x1B 27 Alarm 1 address 00:00 - FF:FF Holding register 0x1E 28 Alarm 2 address 00:00 - FF:FF Holding register 0x1F 29 Alarm 3 address 00:00 - FF:FF Holding register 0x20 30 Alarm 4 address 00:00 - FF:FF Holding register 0x21 31 Alarm 5 address 00:00 - FF:FF Holding register 0x22 32 Alarm 6 address 00:00 - FF:FF Holding register 0x23 33 Alarm 7 address 00:00 - FF:FF Holding register 0x24 34 Alarm 8 address 00:00 - FF:FF Holding register 0x25 35 Alarm 9 address 00:00 - FF:FF Holding register 0x26 36 Alarm 10 address 00:00 - FF:FF Holding register 0x27 37 Werkeinstellungen des Pultes herstellen 0: Nein 1: Ja Holding register 0x28 38 Ruhezustand 0: ausgeschaltet 1 - 99: Einschlafzeit in Sekunden Holding register 0x29 39 Ton 0: ausgeschaltet 1: 1 - 9 Tonfarbe Holding register 0x2A 40 Anzeige der Speisungstemperatur 0: Nicht gezeigt 1: Wird nacheinander gezeigt mit eingestellte Holding register 0x2B 41 Geforderter CO2 (ppm) 0 – 99 x 10 ppm Holding register 0x2C 42 Zugelassener CO2-Unterschied 0 – 99 x 10 ppm Holding register 0x2D 43

SET Temperature 150 – 350 (/10)

Holding register 0x2F 44 SET Fan speed (%) 0,20 - 100 Holding register 0x30 45 SET Fan speed fixed 0 - 4 Holding register 0x31 46 SET Pressure 0 – 999 Pa Holding register 0x32 47 Display supply temperature - 500 – 1000 (/10) Holding register 0x34 48 Einstellungen speichern 0: Nein 22: Ja Holding register 0x36 49 0..10 VDC Beibehaltung 0 - 120 Holding register 0x37 50 0..10 VDC Disable / Enable 0: Ausgeschaltet 1: Eingeschaltet Holding register 0x38 51 Current fan speed (%) 0 – 100 % Input register 0x01 1 Current fixed fan speed 0 – 4 Input register 0x02 2 Temperature Setpoint 150 – 350 °C (/10) Input register 0x03 3 Current Temperature - 500 – 1000 (/10) Input register 0x04 4 Pressure Setpoint 0 – 999 Pa Input register 0x05 5 Current pressure 0 – 999 Pa Input register 0x06 6 CO2 Setpoint 0 – 999 ppm Input register 0x07 7 Current CO2 0 – 999 ppm Input register 0x08 8 Alarm 1 address 0/1 Coil 0x01 1 Alarm 2 address 0/1 Coil 0x02 2 Alarm 3 address 0/1 Coil 0x03 3 Alarm 4 address 0/1 Coil 0x04 4 Alarm 5 address 0/1 Coil 0x05 5 Alarm 6 address 0/1 Coil 0x06 6 Alarm 7 address 0/1 Coil 0x07 7 Alarm 8 address 0/1 Coil 0x08 8 Alarm 9 address 0/1 Coil 0x09 9 Alarm 10 address 0/1 Coil 0x0A 10 Falls man Parameter der Konfigurierung speichern will, muss man in den Register 49 die Zahl 22 eingeben, dann werden die Einstellungen im EEPROM-Speicher bleiben und das Pult wird erneut geladen.

Bedeutung (Beschreibung der Störung s. im technischen Handbuch des Geräts)

A.01 Frostschutz des Wärmetauschers ist aktiv A.02 Externe Alarmeldung, z.B. Brandschutz, verschmutzte Filter, Ventilatoren A.03 Kritische Temperatur des Rückwassers A.04 Defekt des Eingangs „P-mA“ A.05 Niedrige Spannung A.06 Abluftfühler defekt A.07 Zuluftfühler defekt A.08 Defekt des Temperaturfühlers für Rückwasser A.09 Außenttemperaturfühler defekt Störungen Störungen der ECO-Automatik Anzeigen Bedeutung (Beschreibung der Störung s. im technischen Handbuch des Geräts) A.01 Frostschutz des Wärmetauschers ist aktiv A.02 Brandschutz A.03 Verschmutzte Filter A.04 Defekt des Ventilators A.05 Niedrige Spannung A.06 Defekt des Temperaturfühlers DTJ (100) A.07 Defekt des Fühlers für Abluft A.08 Defekt des Fühlers für Zuluft A.09 Defekt des Feuchtefühlers DTJ (100) A.10 Defekt des Temperaturfühlers für Rückwasser A.11 Defekt des Fühlers für Außenluft A.12 Überhitzung A.13 Störung des Rotors A.14 Niedrige Lufttemperatur Störungen von PRV-Automatik Anzeigen Bedeutung (Beschreibung der Störung s. im technischen Handbuch des Geräts) A.01 Rotorgurt ist abgerissen A.02 Kaminschutz ist eingeschaltet A.03 Funktion der Feuchtigkeitsregulierung ist eingeschaltet A.04 Frostschutz des Lamellenwärmetauschers ist eingeschaltet A.05 Frostschutz des Lamellenwärmetauschers. System ist ausgeschaltet A.06 Frostschutz des Lamellenwärmetauschers (Druckrelais) System ist ausgeschaltet A.07 Frostschutz des Wassererhitzers. System ist ausgeschaltet Störungen von MCB-Automatik

Temperatur der Zuluft ist zu niedrig

A.09 Temperatur der Zuluft ist zu hoch A.10 Temperatur der Zuluft ist zu niedrig. System ist ausgeschaltet A.11 Temperatur der Zuluft ist zu hoch. System ist ausgeschaltet A.12 Filter der Zuluft (Druckrelais) austauschen System ist ausgeschaltet A.13 Filter der Abzugsluft (Druckrelais) austauschen System ist ausgeschaltet A.14 Filter der Zu- und Abzugsluft austauschen A.15 Filter der Zu- und Abzugsluft austauschen. System ist ausgeschaltet A.16 Störung des Temperatursensors für Zuluft. Notbetrieb A.17 Störung des Temperatursensors für Zuluft. Notbetrieb A.18 Störung des Temperatursensors für Abluft. Notbetrieb A.19 Störung des Temperatursensors für frische Luft. Notbetrieb A. 20 Störung des Sensors für Wassertemperatur vom Wasserheizgerät. Notbetrieb A. 21 Störung des Sensors für Wassertemperatur vom Wassererhitzer. Notbetrieb A. 22 Störung des Sensors für Wassertemperatur vom Wasserkühler. Notbetrieb A. 23 Störung des Temperatursensors vom Steuerungskasten. Notbetrieb A. 24 Störung des Temperatursensors für Zuluft. System ist ausgeschaltet A. 25 Störung des Temperatursensors für Zuluft. System ist ausgeschaltet A. 26 Störung des Temperatursensors für Abluft. System ist ausgeschaltet A. 27 Störung des Temperatursensors für frische Luft. System ist ausgeschaltet A. 28 Störung des Sensors für Wassertemperatur vom Wasserheizgerät. System ist ausgeschaltet A. 29 Störung des Sensors für Wassertemperatur vom Wassererhitzer. System ist ausgeschaltet A. 30 Störung des Sensors für Wassertemperatur vom Wasserkühler. System ist ausgeschaltet A. 31 Störung des Temperatursensors vom Steuerungskasten. System ist ausgeschaltet A. 32 Test der Brandschutzklappe erfolgreich abgelaufen A. 33 Test der Brandschutzklappe nicht erfolgreich abgelaufen A. 34 Schutz des Heizgeräts im Handbetrieb A. 35 Schutz des Heizgeräts im Automatikbetrieb A. 36 Schutz des Erhitzers im Handbetrieb A. 37 Schutz des Erhitzers im Automatikbetrieb A. 38 Schutz des Lüfters für Zuluft A. 39 Schutz des Lüfters für Abluft A. 40 Schutz des Freonkühlers A. 41 Brandschutz A. 42 Schutz des Zuluftdrucks System ist ausgeschaltet A. 43 Schutz des Abluftdrucks System ist ausgeschaltet A. 44 Falsche Konfiguration A. 45 Intensive Lüftung des Heizgeräts nach Anlauf des handbetriebenen Schutzes A. 46 Intensive Lüftung des Erhitzers nach Anlauf des handbetriebenen Schutzes A. 47 Fehler der inneren Kommunikation

Bedeutung (Beschreibung der Störung s. im technischen Handbuch des Geräts)

A.01 Lüfterfehler A.02 Störung des Temperatursensors für Zuluft A.03 Störung des Temperatursensors für Rückwasser. A.04 Störung des Sensors für Lufttemperatur A.05 Brandschutz ist angelaufen A.06 Liefertemperatur ist zu niedrig. ( < -10'C) (A2) A.07 Lüfterüberhitzung. A4-Eingang (A4) A.08 Störung der Sensoren A.09 Kritische Temperatur vom Rückwasser (A5) A.10 Niedrige Versorgungsspannung der Anlage (A7) A.11 Überhitzung. (A6) A.12 Filter sind verschmutzt A.13 Zulufttemperatur zu hoch (>40'C) (A6) Störungen von EKR-Automatik Anzeigen Bedeutung A.01 A.02 A.03 A.04 A.05 A.06 A.07 A.08 A.09 A.10 Störung der CUSTOM-Automatik (nach Einstellung der Adressen vom CUSTOM- Modbus beifügen) all-guides com

Boîtier de commande à distance Stouch est spécifiquement conçu pour contrôler :

• Les systèmes de récupération SALDA, lorsqu’est utilisée une carte de contrôle automatique avec un régulateur PRV_V21, EKR, MCB ou ECO_v1072; • les installations de soufflage et d‘extraction d‘air SALDA lorsqu‘on utilise la régulation avec un régulateur ECO_ v107; • Ventilateurs SALDA avec des moteurs EC³; • Les dispositifs qui sont contrôlés par le protocole Modbus. 1 Centrales de traitement d‘air : RIS/RIRS 3.0; RIS/RIRS EKO 3.0 2 Centrales de traitement d‘air : RIRS 200 VER EKO; RIRS 300 VE... EKO 3 En utilisant le boîtier Stouch pour le contrôle des ventilateurs de la gamme EKO, il est obligatoire utiliser en supplément une source d‘alimentation du boîtier et prévoir sa protection contre les surcharges et/ou des courts- circuits. Les boîtiers de commande à distance assurent la sécurité et le comfort optimisés de fonctionnement, de surveil- lance et de service. Toutes les opérations sont effectuées à distance en utilisant le boîtier de commande sur lequel sont affichés des rapports d’erreurs et les conditions de service. Particularités • Design exclusif et ergonome ; • Caisson : en plastique; • Ecran: verre trempé; • Facile à utiliser ; • Destiné pour montage en applique ; • Commande tactile par un seul appui ; • Nettoyage facile ; • Réponse sonore à un appui ; • Possibilité de brancher sur le réseau GTB ; • Possibilité du branchement direct au ventilateur commandé à l’aide du signal 0 - 10 VDC ; • Possibilité de connecter une sonde de CO2 ou un capteur de pression à l’entrée 0 - 10 VDC. • 4 vitesses prédéfinies; • Vitesse maximale du ventilateur pour un laps de temps déterminé (boost) ; • Verrouillage de sécurité enfants ; • Possibilité de modifier les paramètres du son, du régime de veille (StandBy), du CO2 à partir du menu « utilisateur ». Le kit comprend : Boîtier de commande « Stouch », câble (13 m), éléments de fixation (vis 3.9 x 25 DIN 7981 - 2 unités, tige de nylon 5 x 25 - 2 unités, tige d’acier à enfoncer 12 x 30 - 2 unités), notice technique. Dimensions 84 mm 20,5 mm 1,5 mm 84 mm NOTE: la hotte n’est pas contrôlée séparément avec les unités suivantes: RIRS 200 V EKO avec “Régulation RIRS 200 VEEC - ... k (+ 15..25 oC)”; RIRS 300 V EKO avec “Régulation RIRSV 300 VE”. Cette fonction est disponible uniquement dans des centrales avec une régulation intégrée.

1. Séparez le couvercle du caisson, voir fig. 1, 2;

2. Brancher fiche standard du câble au boîtier 2.1 – fiche standard Installation 2.2 – fiche spécifique (Cf. « Fiche 8 contacts »)). 3. Remettez le couvercle à l’emplacement prévu contre le mur et marquez des lieux pour le forage, fig. 3, 4. 4. Percer des trous de 5 mm aux endroits marqués pour les fiches de nylon et le trou à travers le mur pour installer le câble. NOTE: le trou à travers le mur est nécessaire uniquement dans le cas où il faut brancher la fiche du câble de l’autre côté du mur. Le diamètre du trou doit correspondre à la taille de fiches de câble. 5. Placez deux bouchons en nylon de 5 mm dans des trous. REMARQUE: bouchons métalliques inclus dans le paquet peuvent également être utilisés. Fig. 5. 6. Visser le couvercle sur le mur avec les vis 2,9 x 16 DIN7981C inclus dans le paquet. Fig. 6. 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 60±0,5mm Ø 40 Ø 5 mm

Fiche 8 contacts

1. Source d’alimentation 24 V AC/DC, 100 mA 2. Source d’alimentation 24 V AC/DC 3. GND 4. RS485 B (Modbus) 5. RS485 A (Modbus) 6. GND 7. Entrée 0 - 10 VDC (pour la sonde de CO2 ou le capteur de pression). La sonde est alimentée depuis une source d’alimentation distincte. 8. Sortie 0 - 10 VDC (pour la commande 0..10 VDC du ventilateur) Le branchement électrique ne peut être effectué que par un électricien qualifié conformément aux exigences in- ternationales et nationales en vigueur en matière de sécurité en milieu électrique et de montage des installations et des équipements électriques. REMARQUE: lorsqu'on utilise un boîtier avec un transmetteur de qualité d'air (dont les GND de sortie d'alimentation et analogique ne sont pas électriquement séparés), il est obligatoire d'utiliser la tension constante (DC) pour leur alimentation. IL EST FORMELLEMENT INTERDIT de laisser le câble du panneau de commande dans l’armoire de régulation de la CTA! 7. Si la connexion peut se faire de n’importe quel côté du caisson (comme représenté sur la fig. 7), alors dans le milieu de la face nécessaire du caisson créez un espace pour le câble avec un couteau. 8. Connectez les câbles nécessaires dans le caisson, insérez-les dans le trou vers l’autre côté du mur ou du côté nécessaire du caisson et appuyez le caisson sur le couvercle, fig. 8.

1. Lorsque le boîtier est utilisé avec un dispositif de ventilation avec une régulation intégrée

Recommandations pour la connexion du boîtier aux dispositifs Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - fusible G - tension constante (DC) source d’alimentation M1 - ventilateurs de la gamme EKO Sonde CO2 de la gaine

1 - 24VDC/AC

2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8 - 0 - 10VDC OUT Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A4 N L PE -G 230VAC_24VDC 2. Lorsque le boîtier est utilisé avec une RIS 150P EKO Sonde CO2 de la gaine all-guides com

-RIS 150P EKO3

1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT 3. Lorsque le boîtier est utilisé avec les ventilateurs de la gamme EKO Sonde CO2 de la gaine REMARQUE: source d'alimentation, éléments de sécurité ou autres composants utiles pour l'installation non fournis.

Significations des éléments

B1 Allumer/éteindre B2 Réglage de la vitesse du ventilateur B3 Réglage de la température B4 Augmenter B5 Vitesse maximale du ventilateur, inter- valle de temps limité (Boost) B6 Diminuer S1 Écran segmentaire L4-L7 Indications de vitesse du ventilateur Informations utilisateur • Le menu « utilisateur » du boîtier est conçu pour le réglage facile des paramètres de la température, du régime de veille et du niveau de CO2. • Touche rapide d’activation de la vitesse maximale. • Affichage des valeurs (en chiffres) de la température de consigne et de celle de l’air soufflé. • Indication LED de la vitesse choisie. • Affichage des pannes actives par symboles A.01, A.02 et indications LED. • Régime de veille du boîtier (économie de l’énergie). • Fonction de condamnation de l’arrêt du système de ventilation disponible. • « Sécurité enfants » - verrouillage du boîtier.

Allumer Maintenir 2 secondes B1

L1 éclaire B1 L1 Éteindre Maintenir 2 secondes B1 L1 est éteint L1 Sortir du régime de veille Toucher n’importe quel bouton L1 clignote lentement en régime de veille B2 B4 B6 L2 Régler la vitesse des ventilateurs Toucher B2 L2 éclaire. La vitesse est réglée en tou- chant les éléments B4 et B6 B3 B4 B6 L3 Régler la température Toucher B3 L3 éclaire. La température est réglée en touchant les éléments B4 et B6 B4 B6 L4-L7 Modifier la valeur de réglage choisie Augmenter en touchant B4, diminuer en touchant B6 Les chiffres sur l’écran segmentaire. L4, L5, L6 et L7 indique la vitesse des ventilateurs choisie B4 B5 B6 L2 Allumer/éteindre la fonction de ventilation intense Maintenir 2 secondes B5 L2 clignote. L’écran segmenté indique le temps restant en secondes (au-dessus de 600s, le temps est indiqué en minutes). Le temps est réglé (modifié en position de fonctionnement de la fonction) en touchant B4 et B6. Temps maximal de fonctionnement de BOOST : 300 min. (5 h). NOTE: il est impossible de régler le temps du régulateur PRV. Si le temps de BOOST sur le régulateur PRV est réglé comme illimité, l’écran segmenté du boîtier de contrôle indique «---». B1 B4 B6 L4-L7 Contrôle et annulation des pannes En annulant, maintenir 3 secondes B2 et B3. En appuyant sur B1, les codes de panne ne s’affichent plus temporai- rement. En cas de panne, L4, L5, L6 et L7 clignotent et les codes de panne (A.01, A.02, etc.) sont indiqués sur l’écran seg- menté. La liste des pannes peut être contrôlée en touchant les boutons B4 et B6. Après annulation de la panne, le boîtier revient en position initiale. En appuyant sur B1, les codes de panne ne s’affichent plus une minute, permettant ainsi de régler la température et les ventilateurs. NOTE : il est formellement interdit d’annuler la panne sans supprimer sa cause. Cela doit être effectué par des représentants du SAV ou le personnel de service du dispositif. B1 L2-L7 La purge CO2 fonctionne En appuyant sur B1, l’indication « CO2 » ne s’affiche plus temporaire- ment. L2, L3 et L7 clignotent, L4, L5 et L6 éclairent. L’écran segmenté indique « CO2 ». En appuyant sur B1, l’indication « CO2 » ne s’affiche plus une minute, permet- tant ainsi de régler la température et les ventilateurs. B2 B3 B5 « Sécurité enfants » al- lumée/éteinte Maintenir 2 secondes B3, B2 et B5 Éléments B1, B4 et B6 inactifs. Après avoir appuyé sur un bouton non au- torisé, l’écran segmentaire montre « --- » „Con“ clignote – en phase de connexion. „noC“ allumé – pas de connexion perdue ou pas de communication avec le contrôleur. Indication de connexion NOTE: ce point s'applique quand le boîtier est utilisé comme Modbus maître.

Possibilités de contrôle de la vitesse des ventilateurs

• En fonction de 4 vitesses prédéfinies fixes • Selon une valeur de pourcentage de la vitesse (0,20 à 100 %) seulement pour sortie 0 ... 10 VDC et le contrôleur ECO. • À partir du menu « utilisateur » la vitesse est réglable à l’intervalle de 5 % • À partir du menu « service » la vitesse est réglable à l’intervalle de 1 % • Fonctionne en 4 vitesses, dont les valeurs sont affichées en pascals (Pa) sur S-Touch • NOTE: Cette fonction est disponible lorsque le ventilateur et le capteur de pression sont reliés à S-touch • Fonction “boost”. Le dispositif fonctionne au rendement maximale (en fonction de la configuration “boost”). La vitesse maximale est sécurisée par une minuterie, qui peut être modifiée (cf. le tableau). Communication à distance (Modbus) Le boitier est compatible avec l’interface entièrement paramétrable Modbus. Le boîtier peut être utilisé en tant qu’un dispositif principal ou auxiliaire dans le réseau GTB en Modbus ; en outre il est entièrement contrôlable et paramétrable non seulement à partir du menu « service », mais encore par l’interface Modbus. Menu « utilisateur » Pour accéder au menu « utilisateur », appuyer 3 secondes sur B2, B3. Le menu « utilisateur » fait défiler les réglages des points du menu (p.01, P.02 etc.). Le point du menu est sélec- tionné à l’aide des éléments B4 et B6. L’appui de B5 affiche la valeur du paramètre choisi, qui peut être modifiée à l’aide des éléments B4 et B6. L’appui sur le B5 fait sauvegarder le paramètre choisi et fait retourner au menu. Les ressources limitées de l’afficheur segmentaire ne permettent l’affichage des valeurs P.04, P.05 que di- minués 10 fois, c’est-à-dire, la valeur réelle de l’affichage « 20 » est 20 x 10 = 200. .06 - le minuteur des filtres est remis en position initiale en maintenant appuyé 5 secondes les éléments B2 et B3. Le minuteur des filtres est également remis en position initiale en annulant l’affichage de la panne. Appuyer l’élément B1 pour sortir du menu. Nr. Libellé Valeurs éventuelles Valeur prévue .01 Régime de veille 0 – arrêté 1 - 99 temps de mise en veille en secondes 0 .02 Volume 0: coupé 1: 1 - 9 timbre du son 2 .03 Affichage température de l’air soufflé 0: Non affichée 1: Affichage alternatif avec celle de consigne 0 .04 CO2 requise 0 – 99 x 10 ppm 20 x10 .05 Dépassement CO2 toléré 0 – 99 x 10 ppm 5 x 10 .06 Chronomètre des filtres Timer filtre: l’affichage du nombre de jours depuis le dernier changement des filtres. 0 Réglage et représentation de la température • Possibilité d’indiquer sur le boîtier la température souhaitée entre 15°C et 35°C. NOTE: la température con- trôlée par le régulateur MCB va de 0°C à 40°C (en fonction des réglages du régulateur MCB). • Possibilité d’afficher alternativement la température de l’air soufflé et celle de consigne (5 s d’affichage de la température de consigne et 2 s d’affichage de celle de l’air soufflé). • Fonction de ventilation “boost” activée à l’aide de la touche rapide. Le temps réglé de la rotation maximale du ventilateur (boost) écoulé, le ventilateur reprend automatiquement la vitesse précédente. • Possibilité de connecter la sonde CO2 0..10 VDC, qui active la vitesse maximale du ventilateur en fonction des paramètres CO2 définis.

Dans le cas d’utilisation du système GTB, un boîtier peut commander plusieurs unités simultanément, ou plus-

ieurs boîtiers peuvent commander une seule unité. À l’aide du protocole MODBUS il est possible de modifier tous les paramètres des boîtiers et de contrôler les informations des sondes et capteurs connectés. BOÎTIER (slave) CTA (slave) GTB CTA (slave) BOÎTIER (slave) MODBUS RS485 2) Modbus esclave (auxiliaire) 3) Commande du ventilateur lorsque la vitesse est réglée à l’aide du boîtier ou de l’ordinateur au moyen de l’interface Modbus L’utilisation de ce boîtier ainsi que du convertisseur de CO2 permet de réduire le niveau du dioxyde de carbone dans le local. À partir du menu « service », sélectionner le mode de commande de la vitesse souhaité (F.01). Dans le cas du choix de la commande en fonction des vitesses prédéfinies, indiquer ces vitesses dans les points du menu : F.03, F.04, F05, F.06. BOÎTIER (slave) VENT. 0...10 VDC MODBUS 4) Maintien de la pression, réglée à l’aide du boîtier ou de l’ordinateur au moyen de l’interface Modbus Dans le cas de la connexion directe du ventilateur 0..10 VDC et du variateur de pression 0..10 VDC au boîtier de commande, il est possible de maintenir la pression souhaitée. Les paramètres de commande et ceux du capteur de pression sont modifiables à l’aide du boîtier de commande. L’utilisation du boîtier en tant que le dispositif de ventilation n’est pas contrôlé par ce moyen. Pour la commande en fonction de la pression, il est nécessaire de déterminer dans le menu « service » les paramètres suivants : Fonctionnalités Ce boîtier de commande peut commander les autres unités (commandées à l’aide du protocole MODBUS). Les réglages se font à partir du menu « service » en indiquant les paramètres requis sur les points du menu F.17, F.18, F.19, F.20, F.21. Lors du besoin de commander des dispositifs spécifiques, indiquer « CUSTOM » dans le point du menu F.20 et les adresses des dispositifs dans les points de F.22 à F.37. Dans le cas où ces dispositifs ne possèdent pas d’adresses, saisir dans les champs de ces points du menu « 00:00 ». Généralement ce boîtier est utilisé avec des contrôleurs ECO ou PRV. BOÎTIER (master) MODBUS CTA (slave) 1) Modbus maître (principal) all-guides com

• .14 - 1

• .15 et .16 - en fonction des paramètres du variateur de pression • .11, .12 et .13 - (coefficients régulateur PID). Si la pression est maintenue de manière impropre, ces para- mètres peuvent être corrigés. • .07 - .10 - indiquer les vitesses prédéfinies Pa. 5) Maintien du CO2 BOÎTIER (master) VENT. (au lieu de la CTA) 0...10 VDC MODBUS Capteur de pression 0...10 VDC CTA (slave) L’utilisation de ce boîtier et du converstisseur de CO2 permet de diminuer le niveau du dioxyde de carbone dans le local. Ce boîtier permet de contrôler le niveau de CO2 de l’ambiance. Il suffit de connecter au boîtier la sonde de CO2 0..10 VDC et de configurer le boîtier. Dans le régime « service » régler le point F.14 sur 2 et définir et F.15 et F.16 en fonction de la spécification de la sonde. Une fois la sonde de CO2 connectée et le paramétrage depuis le menu « service » effectué, il est nécessaire de régler le niveau CO2 souhaité (P.05) et la différence tolérée au-dessus du seuil réglé (P.05). La différence tolérée dépassée, le boîtier met automatiquement le ventilateur à la vitesse maximale (4) et l’affichage « CO2 » apparait sur l’afficheur numérique. Lorsque la teneur de CO2 atteint le niveau réglé (P.05), le boîtier reprend le régime initial. NOTE: Les convertisseurs de qualité de l’air ainsi que le boîtier de commande à distance (lorsque le ventilateur est contrôlé) doivent être alimentés depuis une alimentation séparée. Ils ne sont pas fournis avec le boîtier. Menu « service » Pour accéder au menu « service » il est nécessaire de : 1. Mettre le boîtier au régime « Arrêt » (si le boîtier est allumé, appuyer 3 secondes sur l’élément B1). 2. Appuyer 3 secondes sur B1 et B2. 3. Saisir le code de sécurité « 022 » à l’aide des éléments B4, B6 et valider avec l’élément B5. Le menu « service » fait défiler les réglages des points du menu (p.01, P.02 etc.). Le point du menu est sélec- tionné à l’aide des éléments B4 et B6. L’appui de B5 affiche la valeur du paramètre choisi, qui peut être modifiée à l’aide des éléments B4 et B6. L’appui sur le B5 fait sauvegarder le paramètre choisi et fait retourner au menu. Appuyer l’élément B1 3 secondes pour sortir du menu (le boîtier passe au régime « Arrêt »). No. Libellé Valeurs éventuelles Valeur pré- vue .01 Commande des ventilateurs 0: 0..100 % 1: Vitesses prédéfinies 2: En fonction des valeurs de pression prédéfinies 1 .02 Condamnation arrêt 0: Sans condamnation 1: Marche continue du ventilateur à vitesse minimale (1) 0

Vitesse 1 (%) 0 – 100

20 .04 Vitesse 2 (%) 0 – 100 40 .05 Vitesse 3 (%) 0 – 100 70 .06 Vitesse 4 (boost) (%) 0 – 100 100 .07 Vitesse 1 (Pa) 0 – 999 5 .08 Vitesse 2 (Pa) 0 – 999 10 .09 Vitesse 3 (Pa) 0 – 999 25 .10 Vitesse 4 (boost) (Pa) 0 – 999 40 .11 PID de pression – P 0 – 999 5 .12 PID de pression – I 0 – 999 10 .13 PID de pression – D 0 – 999 0 .14 Variateur 0: Néant 1: Pression 2: CO2 0 .15 Variateur MIN 0 - 250 x 10 0 .16 Variateur MAX 1 - 250 x 10 200 .17 Adresse maître / esclave du boîtier 0: Master 1 - 247: Slave 0 .18 Vitesse de transmission de données par Modbus 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 4 .19 Réglage du paquet de données 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2; 1 . 20 Dispositif contrôlé (le boîtier reconnaît automatiquement les panneaux PRV, EKR, MCB et ECO) 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR 0 . 21 Adresse Modbus du dispositif commandé 1 - 247 1 . 22 SET Temperature address 00:00 - FF:FF 00:00 . 23 SET Fan speed (%) address 00:00 - FF:FF 00:00 . 24 SET Fan speed fixed address 00:00 - FF:FF 00:00 . 25 SET Pressure address 00:00 - FF:FF 00:00 . 26 SET CO2 address 00:00 - FF:FF 00:00 . 27 Temperature address 00:00 - FF:FF 00:00 . 28 Alarm 1 address 00:00 - FF:FF 00:00 . 29 Alarm 2 address 00:00 - FF:FF 00:00 . 30 Alarm 3 address 00:00 - FF:FF 00:00 . 31 Alarm 4 address 00:00 - FF:FF 00:00 . 32 Alarm 5 address 00:00 - FF:FF 00:00 . 33 Alarm 6 address 00:00 - FF:FF 00:00

Alarm 7 address 00:00 - FF:FF

00:00 . 35 Alarm 8 address 00:00 - FF:FF 00:00 . 36 Alarm 9 address 00:00 - FF:FF 00:00 . 37 Alarm 10 address 00:00 - FF:FF 00:00 . 38 Rétablir des réglages installés par défaut 0: Non 1: Oui 0 . 39 Outil de lecture et de modification des para- mètres du type Modbus (Holding register) 0 - 999 0 . 40 Outil de lecture et de modification des para- mètres du type Modbus (Coil register) 0 - 999 0 . 41 Version du boîtier - - . 42 Temps de retient en secondes de mise en marche du ventilateur contrôlé par un signal 0 - 10 V 0 - 120 0 . 43 0..10 VDC Désactiver/activer 0: Arrêt 1: Marche 0 . 44 Rétablir les paramètres usine du régulateur PRV NOTE : obtenu uniquement après connexion au régulateur PRV 0 : Non 1 : Oui 0 . 45 Outil de contrôle des flux d’air. 0 - 10 0 Lors de restitution des réglages usine il est nécessaire de ressaisir le mot de passe service « 022 ». En raison de nombre de caractères limité dans l’afficheur segmentaire, les adresses Modbus du dispositif « CUSTOM » sont saisies en bytes HIGH et LOW, dans le système hexadécimal (HEX). À l’aide des touches B2 et B3 sélectionner les bytes HIGH ou LOW, dont l’affichage est respectivement « H.00 » et L.00 ». Outil de lecture et d’enregistrement des registres Modbus visé aux point F.39 et F.40 sert à sélectionner des paramètres du dispositif que le boîtier ne contrôle pas par défaut mais qui sont accessibles par la communication GTC en Modbus. F.39 sert aux registres du type Holding et F. 40 - aux registres Coil. Utilisation de l’outil: 1. On indique l’adresse duregistre Modbus et on fixe avec le bouton MAX “. 2. L’outil analyse la valeur de l’adresse et l’affiche à l’écran segmentaire (la valeur clignote). 3. On modifie la valeur de “+” et “-” à l’aide des boutons et on fixe avec le bouton MAX. 4. L’outil enregistre la valeur dans le registre sélectionné et revient au menu de service. Outil de lecture et d’enregistrement des registres Modbus Le point F.45 du menu de service est utile si on souhaite régler les flux d’air pour chaque régime séparément. L’outil de contrôle des flux d’air fonctionne avec les régulateurs MCB et PRV. Utilisation de l’outil : 1. Nous sélectionnons le flux d’air souhaité que nous règlerons : SF.1, SF.2, SF.3, SF.4, EF.1, EF.2, EF.3 ou EF.4 (SF et EF indiquent pour quel ventilateur le réglage du flux d’air sera modifié, SF – ventilateur de l’air soufflé, EF – ventilateur de l’air repris. Le chiffre indique pour quelle vitesse/ pour quel régime le réglage du flux d’air sera modifié). 2. L’unité passe à la vitesse/au régime que nous avons sélectionné. La valeur scannée du régulateur est indiquée sur l’écran segmenté. 3. À l’aide des capteurs B4 et B6, nous modifions les valeurs (de 0 à 100%), la vitesse/flux d’air des ventilateurs change aussi automatiquement. 4. À l’aide du capteur B5, nous sortons de l’outil de modification des flux d’air. Les valeurs réglées sont sauve- gardées dans le régulateur. 5. Si vous souhaitez modifier les autres réglages du flux d’air, répéter les points 1 à 4. Outil de contrôle des flux d’air (titre)

Libellé Valeurs éventuelles

Type Adresse (HEX) Adresse (DEC) Commande des ventilateurs 0: 0..100 % 1: Vitesses prédéfinies 2: En fonction des valeurs de pression prédéfinies Holding register 0x01 1 Condamnation arrêt 0: Sans condamnation 1: Marche continue du ventilateur à vitesse minimale (1) Holding register 0x02 2 Vitesse 1 (%) 0 – 100 Holding register 0x03 3 Vitesse 2 (%) 0 – 100 Holding register 0x04 4 Vitesse 3 (%) 0 – 100 Holding register 0x05 5 Vitesse 4 (boost) (%) 0 – 100 Holding register 0x06 6 Vitesse 1 (Pa) 0 – 999 Holding register 0x07 7 Vitesse 2 (Pa) 0 – 999 Holding register 0x08 8 Vitesse 3 (Pa) 0 – 999 Holding register 0x09 9 Vitesse 4 (boost) (Pa) 0 – 999 Holding register 0x0A 10 PID de pression – P 0 – 999 Holding register 0x0B 11 PID de pression – I 0 – 999 Holding register 0x0C 12 PID de pression – D 0 – 999 Holding register 0x0D 13 Variateur 0: Néant 1: Pression 2: CO2 Holding register 0x0E 14 Variateur MIN 0 - 250 x 10 Holding register 0x0F 15 Variateur MAX 1 - 250 x 10 Holding register 0x10 16 Pultelio Modbus master/slave adresas 0: Master 1 - 247: Slave Holding register 0x11 17 Tableau d’adresses Modbus Esclave (auxiliaire) 1. Aller dans le menu service au point F.40 (Modbus Coil read/write tool). La façon d’entrer dans l’environnement de service est décrite dans les instructions du boîtier de commande. 2. Indiquer l’adresse 21 et cliquer sur MAX (nous indiquons le registre Modbus de Compatibility mode) 3. Régler 0 et cliquer sur MAX (1 : connecté, 0 : déconnecté) Les boîtiers de commande Stouch et autres outils Modbus peuvent mal fonctionner lorsque Compatibility mode est connecté dans le détendeur-régulateur de pression (PRV) automatique. Déconnexion de Compatibility mode à l’aide du boîtier de com- mande Stouch :

Vitesse de transmission de don-

nées par Modbus 0: 1200 1: 2400 2: 4800 3: 9600 4: 19200 5: 38400 6: 57600 7: 115200 Holding register 0x12 18 Réglage du paquet de données 0:N,8,1; 1:E,8,1; 2:O,8,1; 3:N,8,2; 4:E,8,2; 5:O,8,2 Holding register 0x13 19 Dispositif commandé 0: None 1: Custom 2: ECO 3: PRV 4: MCB 5: EKR Holding register 0x14 20 Adresse Modbus du dispositif commandé 1 - 247 Holding register 0x15 21 SET Temperature address 00:00 - FF:FF Holding register 0x16 22 SET Fan speed (%) address 00:00 - FF:FF Holding register 0x17 23 SET Fan speed fixed address 00:00 - FF:FF Holding register 0x18 24 SET Pressure address 00:00 - FF:FF Holding register 0x19 25 SET CO2 address 00:00 - FF:FF Holding register 0x1A 26 Temperature address 00:00 - FF:FF Holding register 0x1B 27 Alarm 1 address 00:00 - FF:FF Holding register 0x1E 28 Alarm 2 address 00:00 - FF:FF Holding register 0x1F 29 Alarm 3 address 00:00 - FF:FF Holding register 0x20 30 Alarm 4 address 00:00 - FF:FF Holding register 0x21 31 Alarm 5 address 00:00 - FF:FF Holding register 0x22 32 Alarm 6 address 00:00 - FF:FF Holding register 0x23 33 Alarm 7 address 00:00 - FF:FF Holding register 0x24 34 Alarm 8 address 00:00 - FF:FF Holding register 0x25 35 Alarm 9 address 00:00 - FF:FF Holding register 0x26 36 Alarm 10 address 00:00 - FF:FF Holding register 0x27 37 Restituer les réglages usine du boîtier 0: Non 1: Oui Holding register 0x28 38 all-guides com

Régime de veille

0 – Arrêté 1 - 99 temps de mise en veille en s Holding register 0x29 39 Volume 0: Coupé 1: 1-9 timbre du son Holding register 0x2A 40 Affichage température de l’air soufflé 0: Non affichée 1: Affichage alternatif avec celle de consigne Holding register 0x2B 41 CO2 requise (ppm) 0 – 99 x 10 ppm Holding register 0x2C 42 Dépassement CO2 toléré 0 – 99 x 10 ppm Holding register 0x2D 43 SET Temperature 150 – 350 (/10) Holding register 0x2F 44 SET Fan speed (%) 0,20 - 100 Holding register 0x30 45 SET Fan speed fixed 0 - 4 Holding register 0x31 46 SET Pressure 0 – 999 Pa Holding register 0x32 47 Display supply temperature - 500 – 1000 (/10) Holding register 0x34 48 Sauvegarder les réglages 0: Non 22: Oui Holding register 0x36 49 0..10 VDC délai 0 - 120 Holding register 0x37 50 0..10 VDC Désactiver/activer 0: Arrêt 1: Marche Holding register 0x38 51 Current fan speed (%) 0 – 100 % Input register 0x01 1 Current fixed fan speed 0 – 4 Input register 0x02 2 Temperature Setpoint 150 – 350 °C (/10) Input register 0x03 3 Current Temperature - 500 – 1000 (/10) Input register 0x04 4 Pressure Setpoint 0 – 999 Pa Input register 0x05 5 Current pressure 0 – 999 Pa Input register 0x06 6 CO2 Setpoint 0 – 999 ppm Input register 0x07 7 Current CO2 0 – 999 ppm Input register 0x08 8 Alarm 1 address 0/1 Coil 0x01 1 Alarm 2 address 0/1 Coil 0x02 2 Alarm 3 address 0/1 Coil 0x03 3 Alarm 4 address 0/1 Coil 0x04 4 Alarm 5 address 0/1 Coil 0x05 5 Alarm 6 address 0/1 Coil 0x06 6 Alarm 7 address 0/1 Coil 0x07 7 Alarm 8 address 0/1 Coil 0x08 8 Alarm 9 address 0/1 Coil 0x09 9 Alarm 10 address 0/1 Coil 0x0A 10

Pour sauvegarder les paramètres réglés, il est nécessaire de saisir « 22 » dans le registre 49 : les ré-

glages sont mémorisés dans le mémoire EEPROM et le boîtier redémarre. Indication Valeur (pour la description de l’alarme, voir la notice technique de l’unité) A.01 Protection antigel de l’échangeur de chaleur A.02 Déclenchement de la protection extérieure A.03 Température critique de l’eau de retour A.04 Panne entrée ‘P-mA » A.05 Tension basse A.06 Panne de la sonde de l’air repris A.07 Panne de la sonde de l’air soufflé A.08 Panne de la sonde de température de l’eau de retour A.09 Panne de la sonde de température de l’air extérieur Alarmes Alarmes du contrôleur ECO Indication Valeur (pour la description de l’alarme, voir la notice technique de l’unité) A.01 Protection antigel de l’échangeur de chaleur activée A.02 Déclenchement de la protection extérieure, par exemple, entrée anti-incendie, filtres encrassés (relai de pression activé), ventilateurs A.03 Température critique de l’eau de retour de la batterie à eau chaude A.04 Panne du capteur de qualité d’air ‘P-mA A.05 Basse tension de l’alimentation du dispositif A.06 Panne de la sonde de température de l’air soufflé A.07 Panne de la sonde de température de l’air soufflé A.08 Panne de la sonde de température de l’eau de retour de la batterie à eau chaude A.09 Panne de la sonde d’humidité DTJ (100) A.10 Panne de la sonde de température de l’eau de retour A.11 Panne de la sonde de température de l’air extérieur A.12 Surchauffe A.13 Panne du rotor A.14 Faible humidité de l’air Lorsque le dispositif de ventilation comprend un régulateur PRV Indication Valeur (pour la description de l’alarme, voir la notice technique de l’unité) A.01 Courroie du rotor cassée A.02 Protection du foyer activée A.03 Fonction de régulation de l’humidité activée A.04 Protection antigel de l’échangeur à plaques activée Lorsque le dispositif de ventilation comprend un régulateur MCB

Protection antigel de l’échangeur à plaques. Système désactivé

A.06 Protection antigel de l’échangeur à plaques (relais de pression). Système désactivé A.07 Protection antigel de la batterie à eau chaude. Système désactivé A.08 Température trop basse de l’air soufflé A.09 Température trop élevée de l’air soufflé A.10 Température trop basse de l’air soufflé. Système désactivé A.11 Température trop élevée de l’air soufflé. Système désactivé A.12 Remplacer le filtre de l’air soufflé (relais de pression). Système désactivé A.13 Remplacer le filtre de l’air repris (relais de pression). Système désactivé A.14 Remplacer les filtres de l’air soufflé et l’air repris A.15 Remplacer les filtres de l’air soufflé et l’air repris. Système désactivé A.16 Panne de la sonde de température l’air soufflé. Régime de secours A.17 Panne de la sonde de température l’air repris. Régime de secours A.18 Panne de la sonde de température l’air rejeté. Régime de secours A.19 Panne de la sonde de température l’air neuf. Régime de secours A. 20 Panne de la sonde de température de l’eau de la batterie à eau chaude. Régime de secours A. 21 Panne de la sonde de température de l’eau de la batterie de préchauffage à eau chaude. Régime de secours A. 22 Panne de la sonde de température de l’eau de la batterie à eau glacée. Régime de secours A. 23 Panne de la sonde de température du boîtier de commande. Régime de secours A. 24 Panne de la sonde de température de l’air soufflé. Système désactivé A. 25 Panne de la sonde de température de l’air repris. Système désactivé A. 26 Panne de la sonde de température de l’air rejeté. Système désactivé A. 27 Panne de la sonde de température de l’air neuf. Système désactivé A. 28 Panne de la sonde de température de l’eau de la batterie à eau chaude. Système désactivé A. 29 Panne de la sonde de température de l’eau de la batterie de préchauffage à eau chaude. Système désactivé. A. 30 Panne de la sonde de température de l’eau de la batterie à eau glacée. Système désactivé A. 31 Panne de la sonde de température du boîtier de commande. Système désactivé A. 32 Succès du test du clapet anti-incendie A. 33 Échec du test du clapet anti-incendie A.34 Protection manuelle de la batterie A. 35 Protection automatique de la batterie A. 36 Protection manuelle de la batterie de préchauffage A. 37 Protection automatique de la batterie de préchauffage A. 38 Protection du ventilateur de l’air soufflé A. 39 Protection du ventilateur de l’air repris A. 40 Protection de la batterie à détente directe A. 41 Protection anti-incendie A. 42 Protection de la pression de l’air soufflé. Système désactivé

Affichage des pannes

A. 43 Protection de la pression de l’air repris. Système désactivé A. 44 Configuration incorrecte A. 45 Ventilation intense de la batterie après déclenchement de la protection manuelle A. 46 Ventilation intense de la batterie de préchauffage après déclenchement de la protection manuelle A. 47 Erreur de communication interne Indication Valeur (pour la description de l’alarme, voir la notice technique de l’unité) A.01 Erreur des ventilateurs A.02 Panne de la sonde de température de l’air soufflé A.03 Panne de la sonde de température de l’eau de retour A.04 Panne de la sonde de température de l’air extérieur A.05 Déclenchement de la protection anti-incendie A.06 Température trop basse de l’air soufflé (< -10'C) (A2) A.07 Surchauffe des ventilateurs. Entrée A4 (A4) A.08 Panne des sondes A.09 Température critique de l’eau de retour (A5) A.10 Tension basse de l’alimentation du dispositif (A7) A.11 Surchauffe (A6) A.12 Filtres encrassés A.13 Température trop élevée de l’air soufflé (>40'C) (A6) Lorsque le dispositif de ventilation comprend un régulateur EKR

Pannello di controllo Stouch appositamente progettato per comandare:

• Sistemi di recupero SALDA nel caso in cui viene usato impianto di controllo con controllore PRV_V21, EKR, MCB o ECO_v1072; • Unità ventilanti SALDA dotati di scheda elettronica di tipo ECO_v107; • Ventilatori SALDA di serie EKO (con motori „EC“ 3); • Unità ventilanti comandabili tramite il protocollo Modbus. 1 Unità RIS/RIRS 3.0 e RIS/RIRS EKO 3.0. 2 Unità RIRS 200 VER EKO e RIRS 300 VE... EKO. 3 Impiegando il pannello di controllo Stouch per i ventilatori “EKO”, è necessario utilizzare un’alimentatore suple- mentare e provvedere la protezione contro sovraccarichi e/o cortocircuiti. Caratteristiche: • Design esclusivo ed ergonomico; • Alloggio in plastica; • Schermo in vetro temprato; • Facile utilizzo; • Montaggio a parete; • Comando touch; • Facile pulizia; • Visualizzazione dei parametri di funzionamento con display digitale a 3 cifre ; • Tono di tastiera; • Può essere collegato ad una rete BMS; • Può essere collegato direttamente ad un ventilatore comandato tramite il segnale 0 – 10 VDC; • Un ingresso 0 – 10 VDC permette il collegamento ad un sensore di CO2 o di pressione; • 4 velocità selezionabili; • Velocità massima del ventilatore per un temporizzata (boost), con durata impostabile dall’utente; • Blocco– protezione bambini (locking); • Nel menu dell’utente possono essere modificati i parametri dell tono di tastiera, della modalità standby, e i parametri del sensore di CO2. Componenti presenti nell’imballaggio: Pannello di controllo Stouch, cavo (13 m), elementi di fissaggio (viti 3,9 x 25 DIN 7981 – 2 pezzi, tasselli di nylon 5 x 25 – 2 pezzi, tasselli in acciaio per ancoraggio 12 x 30 – 2 pezzi), manuale tecnico. Dimensioni 84 mm 20,5 mm 1,5 mm 84 mm NOTA:Il pannello di controllo Stouch non comanda separatamente la cappa aspirante per le unità RIRS 200 VER EKO dotate di scheda elettronica “Aut. RIRS 200 VE EC-...k(+ 15..25 oC) ” e RIRS 300 VE... EKO dotate di scheda elettronica “RIRSV 300 VE”. Ciò è possibile soltanto con con unità dotate di schede elettroniche. NOTA: i pannelli di controllo STOUCH garantiscono sicurezza e massimo comfort nell’uso, nel controllo e nella manutenzione di unità ventilanti. Tutte le operazioni sono eseguibili mediante il panello STOUCH, compresa la ripetizione degli allarmi e la segnalazione di necessità di manutenzione. all-guides com

Predisporre un corrugato Dn. 25 dalla macchina fino al punto dove si è deciso di installare il panello di comando.

1. Separare il coperchio dal pannello come mostrato in Fig. 2, 2; 2. Collegare il cavo al pannello, esistono 2 modalità di collegamento . 2.1- collegamento standard; Montaggio 2.2 - collegamento speciale (vedere il paragrafo “connessione a 8 contatti”). 3. Posizionare il coperchio alla parete all’altezza desiderata e segnare i punti di perforazione (Fig 3.4.); 4. Nei punti contrassegnati fare i fori da 5 mm per i tasselli 5. Mettere i tasselli da 5 mm nei fori. NOTA: Possono essere utilizzati sia tasselli plastici che metallici forniti (Fig. 5). 6. Avvitare il coperchio alla parete con le viti forniti 2,9 x 16 DIN7981C (Fig. 6). 7. Se l’uscita del cavo è prevista su un lato del pannello (come mostrato in figura 7), allora usare un taglierino per incedere il lato desiderato. 1 4 1 2 3 4 PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM PIN1 - +24V PIN2 - B+ PIN3 - A- PIN4 - COM 60±0,5mm Ø 40 Ø 5 mm

1. Fonte di alimentazione 24 V AC/DC,100 mA (la polarità non è rilevante)

2. Fonte di alimentazione 24 V AC/DC 3. GND 4. RS485 B (Modbus) 5. RS485 A (Modbus) 6. GND Il collegamento elettrico può essere eseguito soltanto da personale qualificato, in conformità ai requisiti delle norme di sicurezza e delle norme di installazione degli impianti elettrici internazionali e nazionali vigenti. Questo tipo di connessione viene usato nel caso in cui non sia possibile eseguire il collegamento standard. NOTA: L’alimentatore deve essere scelto a seconda della corrente utilizzata per il pannello di controllo e per il sensore di qualità dell’aria. L’alimentatore non viene fornito insieme al pannello di controllo. Connessione a 8 contatti 1.NOTA: Se i pannelli di controllo vengono comandati mediante un sensore della qualità dell’aria (in cui la linea di alimentazione e di uscita analogica non sono elettricamente separati), questi andranno alimentati mediante corrente continua (DC). È VIETATO lasciare la parte del cavo di connessione eccedente all’interno dell’unità. 8. Collegare i cavi, precedentemente passati nel corrugato, al panello di comando. Unire il panello al suo coper- chio, fissato a muro, con una leggera pressione (figura 8).

1. Il pannello di controllo viene usato con unità di ventilazione con regolazione integrata

Consigli per collegare il pannello di controllo ai diversi tipi di unità Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A2 -STouch CON1 -F -F AHU RS485_1 L N -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7 - 0 - 10VDC IN 8 - 0 - 10VDC OUT F - Alimentatore con fusibile G - fAlimentatore con cor- rente continua (DC) M1 - ventilatori tipo EKO (EC) Sensore di CO2 da canale S-KCO2 (DSC-G)

2. Il pannello di controllo viene usato con RIS 150P EKO

M M -RIS 150P EKO3 1-PE 2-N 3-L 4-GND 5-0-10VDC IN 6-10VDC OUT -STouch CON1 -F -F Vin GND A B GND AO1 IP54 Duct CO2 transsmiter S-KCO2 (DSC-G) -A3 -F L N PE -G 230VAC_24VDC 1 - 24VDC/AC 2 - 24VAC/DC 3 - GND 4 - RS465-B 5 - RS485-A 6 - GND 7-0-10VDC IN 8-0-10VDC OUT Sensore di CO2 da canale S-KCO2 (DSC-G)