Milltronics COMPUFLO III Instruction Manual
Text of the manual
TABLE OF CONTENTS
TITLE
PAGE #
General Information
About the CompuFlo III
1 – 1
About this Manual
General
1 – 2
Conventions
1 – 2
Specifications
CompuFlo III
2 – 1
Options
2 – 2
Installation
CompuFlo III
3 – 1
Interconnection
3 – 1
Hazardous Locations
3 – 1
Start Up
Hardware Set Up
4 – 1
Pre Start Up Checks
4 – 3
Initial Start Up
4 – 3
Programming
General
5 – 1
Keypad
5 – 1
Parameter Entry
5 – 2
Direct Parameter Access
5 – 2
Automatic Parameter Access
5 – 2
Altering Parameter Values
5 – 3
Last Parameter Recall
5 – 3
Parameter Reset
5 – 3
Programming Sequence
5 – 3
Quick Start Procedure
5 – 3
Calibration
General
6 – 1
Initial Calibration References
6 – 1
Zero
6 – 2
Span
6 – 2
Calibration Accuracy
6 – 2
Calibration Alternatives
6 – 3
Auto Zero
6 – 3
Lockout Mode
6 – 3
On-Line Span Calibration
6 – 3
Alternate Test References
6 – 4
ECAL Calibration
6 – 4
PL-368
i
7 – 1
Parameters
7 – 1
Programming Chart
8 – 1
Operation
Initial Operation
9 – 1
Normal Operation
Start Up
9 – 2
Zero Calibration Check
9 – 2
Span Calibration Check
9 – 2
Reset Total
9 – 2
Run
9 – 2
Communication
General
10 – 1
Remote Communication
10 – 2
Host Communication
10 – 2
Serial Printer Communication
10 – 2
Protocol
10 – 3
Data Field Descriptions
10 – 3
Message Requests
10 – 4
Message Responses
10 – 4
Appendices
Alphabetical Parameter Listing
11 – 1
Maintenance and Spare Parts
11 – 2
Error Messages
11 – 3
Trouble Shooting
11 – 4
Quick Start
11 – 5
Start Up
11 – 5
Calibration
11 – 6
Operation
11 – 7
Performance Enhancement
11 – 7
Figures
FIG. 1
Outline and Mounting
12 – 1
FIG. 2
Layout
12 – 2
FIG .3
CompuFlo III / Flowmeter Interconnection
12 – 3
FIG. 4
Power, Auto Zero, & Rate Output Wiring
12 – 4
FIG. 5
Relay Wiring
12 – 5
FIG. 6
Communication Wiring
12 – 6
PL-368
ii
ABOUT THE COMPUFLO
The Milltronics CompuFlo III is a
microprocessor based integrator designed
specifically for bulk dry solids in-line
weighing applications.
The CompuFlo III integrates a signal
proportional to material flowrate (such as
from a Milltronics flowmeter) over time to
provide material totalization.
The CompuFlo III provides:
» Rate and Total displays
» an analog mA output proportional to rate
» a relay contact for remote totalizer or PLC operation
» 2 alarm/control relays based on rate and/or On-line Calibration
» 2 communication ports for computer, PLC, or serial printer connection
The CompuFlo III has three modes of operation;
program, calibrate and run.
The operator programs the CompuFlo III via the
keypad to provide displays and outputs in the
desired units of measure. The CompuFlo III
displays the name, range of acceptable values,
(and additional information/instruction) of the
parameter (programming feature) accessed.
In the calibrate mode, the system Zero (no flow) and Span (100% flowrate) calibration is established. A test
reference (test weight) is used to simulate the force of material impacting the flowmeter sensing plate during
the Span calibration. A material test is normally performed to verify the calibration accuracy. If necessary, the
material test results may be used to correct any deviation in calibration accuracy.
Calibration accuracy may be checked at any time. The results of this check are automatically compared to the
system calibration and the deviation is displayed. The operator may choose to continue operation with the
previous calibration or the results of the calibration check.
All programming and calibration information is stored in non-volatile memory. If desired, the security
parameter may be set to ensure the CompuFlo III programming and calibration is not inadvertently altered in
the run mode.
The run mode is the normal operating mode, providing dynamic measurement displays, analog mA output,
and a variety of other features.
T
1263957
TOTAL
150%
100%
50%
0%
-50%
MULTI SPAN NO: 1
R2:RATE HI R1:SPEED LO
PL-368
1 – 1
ABOUT THIS MANUAL
GENERAL
This instruction manual contains information essential to successful CompuFlo III operation.
SPECIFICATIONS,
includes CompuFlo III environmental, physical, and operational characteristics.
INSTALLATION,
indicates the typical mounting and interconnection procedure.
START UP,
prepares the CompuFlo III for programming.
PROGRAMMING,
details activities required to tailor the CompuFlo III to the particular application.
CALIBRATION,
includes the CompuFlo III input signal to output feature correlation procedure.
PARAMETERS,
describes the function, factory setting, and range of possible settings,
of each parameter.
PROGRAMMING CHART, provides a space to record programmed parameter values for future reference.
OPERATION,
describes initial and normal CompuFlo III operation.
COMMUNICATION,
provides CompuFlo III serial communication information.
APPENDICES,
contains Quick Start, Alphabetical Parameter List, Maintenance and Spare Parts,
Error Messages and Trouble Shooting information.
FIGURES,
includes a complete set of installation and interconnection drawings.
CONVENTIONS
Throughout this instruction manual the following symbols and presentation practices have been utilized:
[1234567ABCDEFG]
alpha numeric characters enclosed within these brackets represents information
displayed by the CompuFlo III display.
[T/h]
units of measure were arbitrarily chosen from the imperial set. The actual units
displayed or otherwise applicable will be dependent upon operator programming.
indicates the following CompuFlo III keypad button is to be pressed.
"RUN" or
alpha numeric characters enclosed within quotation marks or this symbol
represent a key on the CompuFlo III keypad.
Italics
are used to identify the defined word(s) or phrase within a definition statement.
Information of a higher order of importance, is indented from
both left and right margins and in bold print.
I
ENTER
PL-368
1 – 2
» 100/115/200/230 V AC ±10%, jumper
selectable, 50/60 Hz, 65 VA
Fuse:
» FU 1
» 3/4 Amp MDL SLO-BLO or equivalent
» FU 2
» 1/4 Amp MDL SLO-BLO or equivalent
Operating
» -20 to 50°C (-5 to 122°F)
Temperature:
Accuracy:
» 0.1% of span, typical
Resolution:
» 0.02% of span, typical
Inputs:
» Load cell:
» -20 to +45 mV DC per load cell
» 2 load cells max.
» LVDT:
» 0 to 0.75 Vrms, 3 kHz
» Multispan:
» 4 contact inputs for up to 8 spans
» Keypad:
» 20 key sealed membrane with tactile feedback
» On-Line:
» 4-20 mA proportional to weight
(Calibration)
» Auto Zero
» contact input for enable
» Printer:
» contact input for print request
Outputs:
» Load cell:
» 10 V DC, 250 mA max.
(excitation)
» LVDT:
» 2.0 Vrms, 3 kHz, 50 mArms max.
(excitation)
» Analog:
» 4-20 mA,(0-25 mA scaleable), isolated, proportional to rate
» 0.1% resolution
» 750 Ω max. load
» Remote
» SPST sealed relay
Totalizer:
» 1 form "A" contact rated 2A at 250 V AC, 100 VA max.
» 25 msec. minimum contact closure duration
» 15 closures per second max
PL-368
2 – 1
» 2 multipurpose relays for Rate or On-line Calibration
assignment
» 1 Form "C" SPDT contact per relay, rated 5A at 230 V AC
» Communication:
» 1 relay, 4PDT used for communication loop dropout,
rated 1A at 230 V AC
» Display:
» illuminated 256 x 128 dot matrix
Communication:
» 2 serial ports
» RS232C and ± 20 mA current loop
Enclosure:
» NEMA 4 style, steel construction with polycarbonate window
» 330 mm W x 406 mm H x 102 mm D
(13" W x 16" H x 4" D)
Shipping Weight:
» 11.0 Kg (24.3 lbs), no options
OPTIONS
Cable:
» Single load cell, 150m (500 ft) max. 20 AWG, 4 wire shielded,
Belden 8404 or equivalent
» Single load cell, 300m (1000 ft) max. 20 AWG, 6 wire shielded,
Belden 8426 or equivalent
» Dual load cell, 150 m (500 ft) max. 20 AWG, 6 wire shielded,
Belden 8426 or equivalent
» Dual load cell, 300 m (1000 ft) max. 20 AWG, 8 wire shielded,
Belden 8418 or equivalent
» LVDT, 150 m (500 ft) max. 20 AWG, 4 wire shielded,
Belden 8404 or equivalent
Barrier Strips:
» For hazardous location flowmeters
Enclosure Heater:
» Recommended for operating temperatures below -10°C
(14°F) or excessive humidity
Relay:
» Food Grade remote totalizer relay
CVCC:
» For bipolar current loop/RS-232C conversion
BIC-II:
» For 6 port bipolar current loop/RS-232C or RS-422 conversion.
I
PL-368
2 – 2
The CompuFlo III should be mounted in an area that is within the specified temperature range, and that is
suitable for NEMA 4 style enclosures. The front cover should be accessible for keypad operation, display
viewing, and have sufficient room to swing open.
It is advisable to keep the CompuFlo III away from high voltage or current runs, contactors, SCR control
drives and RF interference.
For proper totalizer relay operation, the CompuFlo III must be mounted within 30° from vertical.
Do not mount the CompuFlo III in direct sunlight without the use of a sun shield.
INTERCONNECTION
Remove the enclosure bottom plate prior to drilling or punching cable/conduit entrance(s), to ensure metal
filings do not come in contact with the CompuFlo III electronics.
Load cell or LVDT, rate output, On-Line Calibration input, communication, and low voltage contact wiring may
be run in a common conduit separated from power and high voltage contact wiring. Refer to Figures.
The power ground (TB1-50) is internally connected to SHLD connections (TB1-13,26, TB2-5), and to the
mother board bottom mounting lugs. COM connections (TB1-15,29,32,36,37, and TB2-8) are connected to
power ground via jumper J2 (below TB1, between the mounting lugs). If the COM connections must be
isolated from power ground, remove J2.
Refer to FIGURES
All wiring must be performed in accordance with all governing regulations.
HAZARDOUS LOCATIONS
The CompuFlo III cannot be mounted in an area classed as hazardous. Where the associated flowmeter is
mounted in a hazardous area, barrier strips must be used to isolate the CompuFlo III from the hazardous area
for intrinsic safety. Encapsulated LVDT transducing elements are also available. Contact Milltronics or your
local representative for hazardous application information.
I
PL-368
3 – 1
HARDWARE SET UP
UNIT I.D.
The CompuFlo III identification code factory setting is 00,
as set by SW1 contacts 1 - 4.
When more than one CompuFlo III is connected to a
host computer or PLC, the identification code of each
CompuFlo III must be set to a different value.
O = switch contact open
C = switch contact closed
UNITS OF MEASURE
Two sets of Units are available; Imperial and Metric. Leave SW1 contact 5 (SW1-5) in the open position
for Imperial, or closed for Metric units. Refer to PARAMETERS / P0 - RATE UNITS for the Rate Unit
options available.
SW1-5 must be set to the desired position before initial programming is performed.
To alter the Units of Measure of a programmed CompuFlo III, set SW1-5 as desired,
then perform a Reset. Refer to Parameters / P99 Reset.
LOCKOUT
Leave SW1 contact 6 (SW1-6) in the open position for normal applications. Close SW1-6 for Lockout Mode
operation, after all programming and calibration is complete. Refer to Calibration / Calibration Alternatives.
TOTALIZER RESET
Leave SW1 contact 7 (SW1-7) in the open position for normal operation. When this contact is closed, the
Main Total Display cannot be reset.
TEST MODE
Leave SW1 contact 8 (SW1-8) in the open position for normal operation. The closed position is reserved for
Milltronics service personnel.
IMPERIAL
UNIT I. D. #
MAIN
TOTAL
RESET
LOCKOUT
TEST
METRIC
NORMAL
1
2
4
8
0
0
0
0
SW1
UNIT
SW 1
I. D.
1 2 3 4
08
O O O C
09
C O O C
10
O C O C
11
C C O C
12
O O C C
13
C O C C
14
O C C C
15
C C C C
UNIT
SW 1
I. D.
1 2 3 4
00
O O O O
01
C O O O
02
O C O O
03
C C O O
04
O O C O
05
C O C O
06
O C C O
07
C C C O
PL-368
4 – 1
PORT 2 BAUD RATE
The CompuFlo III TB2 communication port baud rate is independent of the PORT 1 baud rate, and is set by
SW2 contacts 1 and 2. Set the baud as required by the device connected. The factory setting is 300 baud.
O = switch contact open
C = switch contact closed
LANGUAGE
Leave SW2 contact 3 (SW2-3) in the open position for English, or closed for alternate language, CompuFlo III
displays.
REMOTE DISPLAY
Leave SW2 contact 6 (SW2-6) open for normal operation. If a remote mounted terminal is used, SW2-6 of the
remote terminal (only) must be closed.
PORT 2 COMMUNICATION MODE
Leave SW2 contact 7 (SW2-7) open for normal operation, or closed if a serial printer is connected to PORT 2.
TEST/ADJUST MODE
Leave SW2 contact 8 (SW2-8) in the open position for normal operation. In the closed position, a test menu is
displayed.
When the keypad test is selected, a pictorial representation of the keypad is displayed. As each keypad
button is depressed, the display indicates successful operation.
When the display contrast adjustment is selected, pressing "4" increases, and pressing "8" decreases the
display contrast.
NORMAL
SPARE
ENGLISH
ALTERNATE
TB2 BAUD
SERIAL
PRINTER
REMOTE
TERMINAL
TEST /
ADJUST
4
1
4
3
X
X
2
0
0
0
0
SW2
Baud
SW2
Rate
1 2
300
O O
1200
C O
2400
O C
9600
C C
PL-368
4 – 2
PRE START UP CHECKS
After the CompuFlo III has been properly installed and interconnected, the following checks should be
performed prior to connecting power:
»all cable connections are correct and secure.
»the proper voltage has been selected (J1 on the mother board).
»SW1 and SW2 have been set as required.
»the POWER switch is in the OFF position.
Connect power to TB1-51,52 and ground to TB1-50 of the CompuFlo III. Ensure all connections are secure.
Do not operate the CompuFlo III with the
ground (earth) wire disconnected.
INITIAL START UP
Set the CompuFlo III POWER switch to the ON position. The CompuFlo III will enter the following
initialization routine:
COMPUSCALE/FLO III
(REV DATE)
(EPROM 2 REV)
TEST :
(MESSAGES)
PL-368
4 – 3
When the display initialization routine is complete, the display reverts to the last operating mode accessed. If
the CompuFlo III is not programmed, the parameter entry display is accessed.
The CompuFlo III display is divided into the following fields:
FIELD DESCRIPTION
MULTISPAN
current span calibration selected. If Multispan 0 is selected, the field is blank.
RELAY
current relay status (run mode). If relays are not used, or in non-alarm, the field is blank.
FEATURE
parameter number (parameter entry), calibration type (calibrate mode), Rate or Total (run mode)
ECAL
indicates ECAL (simulated rate signal) is on. If ECAL is off, the field is blank.
CYCLE
full cycles remaining before calibration completion (calibrate mode).
CALIB
calibrate mode indicator. When displayed, totalizers are on HOLD (unless otherwise specified).
VALUE
the current value associated with the feature selected.
UNITS
the units of measure associated with the value displayed
AUX 1
parameter name (parameter entry), auxiliary message (calibrate mode), not used (run mode).
AUX 2
parameter value range (parameter entry), additional information or error message (any mode).
BAR GRAPH
represents current rate, displayed as percent of span (run mode).
I
150%
100%
RATE
0%
-50%
FEATURE
ECAL
VALUE
AUX 1
AUX 2
RELAY
CALIB
CYCLE
UNITS
RATE BAR
GRAPH
MULTISPAN
PL-368
4 – 4
Information specific to a particular application is entered into the CompuFlo III memory, via the keypad, prior
to the calibration procedure.
KEYPAD
Button
Operation
Function
parameter entry
numeric entries
parameter entry
increase: analog mA output (P17 and P18 only), ECAL value (P22 only)
parameter entry
decrease: analog mA output (P17 and P18 only), ECAL value (P22 only)
parameter entry
decimal point
parameter entry
negative entry or display previous parameter
any mode
enter the run mode, return to previously selected display
any mode
access parameter for entry or viewing
any mode
access zero calibration, view current zero count
any mode
access span calibration, view current span count
any mode
enter the run mode, select rate or total display
any mode
reset displayed totalizer value to zero (refer to Start Up\Hardware
Set Up\Totalizer Reset)
parameter entry
clear entry
calibrate mode
abort calibration
parameter entry
display parameter value, or store altered parameter value,
or display next parameter
calibrate mode
activate zero or span calibration, or accept calibration results
any mode
with total displayed, switch to alternate total (main or sub)
8
0
–
9
RUN
PAR
ZERO
SPAN
ALT
DISP
RESET
TOTAL
CLEAR
ENTER
4
PL-368
5 – 1
Application information must be entered into the appropriate CompuFlo III memory locations. These locations
are identified by a Parameter Number (P#). The information entered is referred to as a Parameter Value
(Value). To enter information, the operator accesses the desired parameter number, views the parameter
value displayed, and then accepts or alters the current parameter value.
DIRECT PARAMETER ACCESS
To directly access any parameter, followed by the parameter number.
Only valid parameter numbers will be accepted. Refer to PARAMETERS for the list of valid parameter
numbers.
eg.
[PARAMETER
]
is displayed in the FEATURE field, if PARAMETER 0 is desired
[PARAMETER 0
]
is displayed in the FEATURE field,
[RATE UNITS
]
is displayed in the AUX 1 field.
To view the current parameter value and auxiliary messages for the displayed parameter,
[PARAMETER 0
]
is displayed in the FEATURE field
[ 1
]
is displayed in the VALUE field (unless previously altered)
[RATE UNITS
]
is displayed in the AUX 1 field
[1:T/h;2:LT/h;3:lb/h;4:lb/min
]
is displayed in the AUX 2 field (with SW1-5 open)
AUTOMATIC PARAMETER ACCESS
Upon accessing any parameter value, pressing "ENTER" will automatically access the next parameter in the
programming sequence. Pressing "-" will automatically access the previous parameter.
eg.
with the VALUE field of PARAMETER 0 displayed...
[PARAMETER 1
]
is displayed in the FEATURE field
[ 0.0000
]
is displayed in the VALUE field (unless previously altered)
[RATE
]
is displayed in the AUX 1 field
[ENTER VALUE
]
is displayed in the AUX 2 field
all fields associated with PARAMETER 0 are displayed
150%
100%
RATE
0%
-50%
FEATURE
VALUE
AUX 2
UNITS
AUX 1
RATE BAR
GRAPH
Common Parameter Entry Display Fields
0
PAR
ENTER
PAR
ENTER
PL-368
5 – 2
ALTERING PARAMETER VALUES
Once the desired parameter number is accessed, the parameter value may be accepted or altered as
required.
eg.
if the VALUE field of PARAMETER 0 is 1 (T/h), however 2 (LT/h) is desired
[ 2
]
is displayed in the VALUE field
the new value (2) is now stored in memory
LAST PARAMETER RECALL
From the Calibrate or Run mode, the last parameter accessed in the Program mode, may be recalled.
the last parameter accessed is displayed.
PARAMETER RESET
To reset all parameters to factory settings, refer to PARAMETERS/P99 Master Reset.
PROGRAMMING SEQUENCE
Typically, the CompuFlo III is programmed as follows:
a) Referring to PARAMETERS, copy the selected parameter values to the spaces provided on
the PROGRAMMING CHART fold out.
b) Perform a MASTER RESET (P99).
c) Access each parameter ( in sequence from P0) and enter the parameter values
from the PROGRAMMING CHART.
d) Perform a Zero and Span calibration (refer to CALIBRATION)
e) Perform Span Adjust (P8) or Factoring (P9) procedures, as required.
Remember to copy any parameter value alterations onto
the PROGRAMMING CHART for future reference.
QUICK START PROCEDURE
The Quick Start Procedure describes the minimum start up, programming, and calibration requirements of the
CompuFlo III, to obtain successful RUN mode operation for most applications.
If desired, refer to APPENDICES/Quick Start. Parameters which are not included in the procedure may be
programmed after the RUN mode is entered.
I
ENTER
2
ENTER
PAR
PL-368
5 – 3
As material flow characteristics often vary, frequent calibration may be required to maintain calibration
accuracy. Normally, a Zero calibration is performed first, followed by a Span calibration.
When the CompuFlo III is first commissioned, several Zero and Span calibrations are normally performed to
verify the calibration results are repeatable.
A Zero or Span calibration (in progress) may be aborted by .
INITIAL CALIBRATION REFERENCES
The first calibration performed, establishes the Initial Zero and Initial Span calibration references. Subsequent
Zero and Span calibration results are compared to these references. The maximum acceptable deviation
between an Initial Calibration Reference and a subsequent calibration result is 12.0% of span. Otherwise,
[ZERO OUT OF RANGE] or [SPAN OUT OF RANGE] is displayed in the AUX 2 field.
While a calibration in progress is establishing an initial calibration reference, the dynamic count value is
displayed in the VALUE field. Otherwise, the dynamic rate value is displayed.
The initial calibration references may be reset. Refer to Parameters/P77 Initial Zero Reset and P88 Initial
Span Reset. Both initial calibration references (along with other programming) are erased by a Master Reset
(P99).
VALUE
150%
100%
RATE
0%
-50%
CALIB
UNITS
RATE BAR
GRAPH
MULTISPAN
FEATURE
ECAL
AUX 1
AUX 2
CYCLE
CLEAR
PL-368
6 – 1
The average no flow input from the flowmeter is calculated and stored in memory as a Zero count. With no
material flow or Test Weight applied to the flowmeter...
[ZERO] is displayed in the FEATURE field. The current Zero counts are displayed in the
VALUE field. [ENTER: CALIBRATE MODE] is displayed in the AUX 2 field.
to initiate the calibration. [CALIB] is displayed in the CALIB field and [ZERO IN PROGRESS]
is displayed in the AUX 2 field. The time required to complete the calibration (and calibration
accuracy) is dependent upon the Calibration Duration (Refer to Parameters/P30 Calibration
Duration). The number of full calibration cycles remaining until completion, is displayed in
the CYCLE field.
When complete, the deviation from the last Zero calibration is displayed in the VALUE field,
as a percent of span.
to accept the new calibration. Otherwise, investigate the reason for the deviation and
perform the Zero calibration again.
SPAN
The simulated material flow provided by the Test Weight (or number of Test Weights) is calculated and stored
in memory as a Span count. (Refer to Alternate Test References, if a Test Weight is not used.)
With no material flow or Test Weight applied to the flowmeter...
[SPAN] is displayed in the FEATURE field. The current Span counts are displayed in the
VALUE field.
With [CALIB] displayed in the CALIB field, apply the Test Weight to the flowmeter
(as described in the flowmeter manual).
If [CALIB] is not displayed, respond to the CompuFlo III display prompts until this
indicator is obtained, before applying the Test Weight.
to initiate the calibration. The time required to complete the calibration (and calibration
accuracy) is dependent upon the Calibration Duration (Refer to Parameters/P30 Calibration
Duration). The number of full calibration cycles remaining until completion,
is displayed in the CYCLE field.
When complete, the deviation from the last Span calibration, is displayed in the VALUE field,
as a percent of span.
to accept the new calibration. Otherwise, investigate the reason for the deviation
and perform the Span calibration again.
CALIBRATION ACCURACY
With the Initial Zero and Initial Span calibration complete, RUN mode operation is possible, however greater
calibration accuracy may be required. The Test Reference value (P7) is an approximation, based on typical
material flowrate characteristics.
To adjust the Span calibration to suit the actual material flow characteristics encountered, perform a material
test. (Refer to Parameters/P8 Span Adjust). The Test Reference value is automatically adjusted so the Test
Weight will accurately simulate material flow during future Span calibrations.
The CompuFlo III is now ready to be put into service, (refer to Operation).
SPAN
ENTER
ENTER
ENTER
ENTER
ZERO
PL-368
6 – 2
This feature automatically performs a Zero calibration, whenever material flow ceases in the RUN mode.
If the Auto Zero feature is desired, provide a dry contact input to the CompuFlo III terminals TB1-34 and
TB1-37. The contact may be activated by a material feed controlling device such as a motor control, material
control gate, or valve. The contact must be closed when the material feed is stopped.
When the contact is closed, and material flow has stopped (within 4% of span from the current zero reference)
[AUTO ZERO IN PROGRESS] is displayed in the AUX 2 field. The time required for completion is dependent
upon Calibration Duration (P30). The number of full calibration cycles remaining until completion is displayed
in the CYCLE field.
When complete, the Auto Zero is compared to the last operator Zero.
If the Auto Zero is within 2% of span from the last operator zero, the CompuFlo III briefly displays
[CALIBRATION COMPLETE] in the AUX 2 field and the deviation from the current zero reference in the
VALUE field. The Auto Zero is automatically accepted and RUN mode operation continues.
Otherwise, the Auto Zero results are rejected, and operation continues with the previous zero reference.
LOCKOUT MODE
In this mode, parameters may be accessed for viewing. However, if a parameter value alteration is attempted,
the alteration is not permitted and [CERTIFICATION LOCKOUT] is displayed in the AUX 2 field.
To activate the lockout mode, close SW1 contact 6 (SW1-6) after the CompuFlo III is programmed
and calibrated.
The maximum acceptable deviation between the last Zero performed by the operator (before closing this
contact) and any subsequent Zero, is limited to 2% of span. Span calibrations are not permitted in this mode.
ON-LINE SPAN CALIBRATION
The On-Line Calibration feature may be used to routinely check (and adjust if necessary) the Span calibration
in the RUN mode, without interrupting the material flow.
Install a weigh bin (bin or silo equipped to provide a 4-20 mA output proportional to weight) preceding the
flowmeter material infeed. Connect the weigh bin output to the CompuFlo III TB1-18,19 terminals. Install a
material feed control device, preceding the weigh bin.
Calibrate the CompuFlo III for the weigh bin 4-20 mA input (P27).
Access On-Line Parameter Selection (P28) to enter the weigh bin:
reference weight , max limit, high limit, and low limit setpoints.
Assign a relay to the On-Line Calibration function, P51=2 (Relay 1)
or P52=2 (Relay 2). Connect the assigned relay contacts to the
weigh bin material feed control device, such that when the On-Line
relay is energized, the weigh bin material feed is stopped.
When the On-Line Calibration is activated (P29), normal operation
continues until the weigh bin fills to the max limit (e.g. 90%). While
filling, the percent full is displayed in the VALUE field. When the
max limit is reached, the relay assigned the On-Line function,
energizes to stop the weigh bin material feed.
High (e.g. 80%)
reference weight
Low (e.g. 30 %)
feeder
material flow
Max. (e.g. 90%)
PL-368
6 – 3
As material is discharged from the weigh bin, the On-Line totalizer is automatically activated when the high
limit (e.g 80%) is reached. When the low limit (e.g. 30%) is reached, the totalizer is de-activated and the
assigned relay de-energizes, thereby enabling the material feed to the weigh bin.
The CompuFlo III On-Line material total is compared to the weight of material discharged from the weigh bin
between the high and low limits (reference weight). The deviation between these values is displayed as a
percent of span in the VALUE field. The On-Line calibration results may be accepted, or rejected.
ALTERNATE TEST REFERENCES
For most applications, a Test Weight is applied to the flowmeter, to simulate material flow for the Span
calibration. Alternatively, the CompuFlo III internal reference (ECAL), may be used to simulate a flowmeter
input for Span calibrations. ECAL is normally used when applying a Test Weight would be impractical or
inconvenient (especially when the flowmeter is installed in a hazardous area).
When a Test Weight is used exclusively, Test Reference selection (P20) is not required.
When the ECAL reference is selected (P20=1), ECAL is automatically applied when a Span calibration or
Factoring (P9) is activated, and removed when the process is complete or aborted. If a Test Weight and
ECAL are used periodically, the appropriate Test Reference must be selected (P20) before a Span calibration
(or Factoring) is performed.
When the ECAL reference is on, [ECAL] is displayed in the ECAL field.
ECAL CALIBRATION (INITIAL REFERENCE)
With essential parameters (P0, P1,P2,P3,P7, and P21) programmed as required, select the ECAL Test
Reference (P20=1). Access P7 again, [PARAMETER 7E] is displayed. (The "E" indicates the P7 value
displayed is associated with the ECAL Test Reference.)
Perform a Zero and Span calibration. (A Test Weight is not required as ECAL is automatically applied for
Span calibrations when P20=1). To obtain an accurate ECAL/flowmeter signal correlation, perform a material
test. Refer to Parameters/P8 Span Adjust.
Upon the completion of the material test, the new ECAL Test Reference (P7E) value is automatically adjusted
so ECAL will accurately simulate material flow during future Span calibrations.
For best results, if the new P7E value is not between 50% to 100% of the Design Rate (P1) value, perform an
ECAL Adjust. Refer to Parameters/P22 ECAL Adjust.
ECAL CALIBRATION (ALTERNATE REFERENCE)
After the CompuFlo III Span calibration is completed with a Test Weight, ECAL may be used for subsequent
Span calibration checks. Using ECAL as a secondary reference is especially useful, when frequent Span
calibration checks are required but using a Test Weight would be impractical.
Select the ECAL Test Reference (P20=1). Adjust ECAL to the value desired (P22=2). Factor the adjusted
ECAL reference to the current span (P22=2 or P9).
After a primary reference (typically Test Weight) Span calibration deviation is
accepted, Factor the secondary reference (typically ECAL) to the new span.
Remember to select the appropriate Test Reference (P20) before
performing a Span calibration or Factoring procedure.
I
PL-368
6 – 4
(F) indicates the parameter value factory setting (where applicable)
(V) indicates the parameter value may be viewed only.
(E) indicates the parameter value is essential for basic operation.
PARAMETERS
P0
RATE UNITS (E)
Defines the desired Rate display engineering units of measure.
With SW1, contact 5 (SW1-5) in the open position (Imperial units):
enter:
1 = short tons per hour (F)(T/h)
1 T/h = 2000 lb/h
2 = long tons per hour(LT/h)
1 LT/h = 2240 lb/h
3 = pounds per hour(lb/h)
4 = pounds per minute(lb/h)
With (SW1-5) in the closed position (Metric units):
enter:
1 = metric tonnes per hour (F)(t/h)
1 t/h = 1000 kg/h
2 = kilograms per hour(kg/h)
3 = kilograms per minute(kg/m)
The SW1-5 position and the value of P0 should be set before any other programming.
To alter the Rate Units of a programmed CompuFlo III, set SW1-5 as desired, perform a
Reset (refer to Parameters / P99 Reset) and set P0 to the desired value.
P1
RATE (E)
Defines the rate of material flow (in P0 units) which will produce the full scale Rate output. (F=0.0000)
enter:
Design Rate, Range = 0.0001 to 99999
P2
LOCAL TOTAL (E)
Defines the amount of material to be totalized, prior to initiating an internal totalizer (and Main / Sub Total
display) update, (F = 1). The weight portion of the Rate Unit (P0) is assumed.
enter:
.0001
.001
.01
.1
1
10
100
1000
.0002
.002
.02
.2
2
20
200
2000
.0005
.005
.05
.5
5
50
500
5000
If [TOTAL REGISTRATION TOO LOW] is displayed, enter a higher value.
94/04/14
PL-368
7 – 1
REMOTE TOTAL (E)
Defines the amount of material totalized, prior to initiating a remote totalizer relay contact closure, (F = 1). The
weight portion of the Rate Unit (P0) is assumed.
The frequency of remote totalizer contact closures is dependent upon the material flowrate and the Remote
Total value. When a remote totalizer is connected to TB1-48,49, refer to the totalizer manufacturers
instructions to determine the maximum pulse frequency. Lower values increase and higher values decrease
the relay contact closure frequency.
enter:
.0001
.001
.01
.1
1
10
100
1000
.0002
.002
.02
.2
2
20
200
2000
.0005
.005
.05
.5
5
50
500
5000
If [TOTAL REGISTRATION TOO LOW] is displayed, enter a higher value.
P7
TEST REFERENCE (Test Rate) (E)
Defines the simulated material flowrate represented by the Test Reference selected (P20) for the MultiSpan
(P26) selected.
This value is entered in design Rate (P0) units. If a value of 0 is entered, the system design Rate (P1)
value is assumed.
enter:
Test Rate (refer to the associated flowmeter instruction manual for
calculation instructions. F = 0 until P1 is set.)
P8
SPAN ADJUST
Adjusts the test reference calibration results to improve material flowrate measurement accuracy.
% CHANGE -
Calculate the deviation between the CompuFlo III Total and the actual material weight.
A positive value reduces (negative increases) the Rate displayed.
% Span Error = CompuFlo III Total - Actual Material Weight x 100
Actual Material Weight
MATERIAL TEST -
Alternatively, the automatic method may be used. Perform a material test as follows:
a)
With no material flow and the test reference (Test Weight, or ECAL) removed,
b)
Select the material test option, select the HOLD TOTAL or ADD TO TOTAL option
press "ENTER" to activate the Material Test.
c)
Feed a sample of material through the flowmeter press "ENTER" to stop the Material Test.
d)
Enter the actual material sample weight. The Span deviation % is displayed.
e)
Press "ENTER" to complete, (or "CLEAR" to abort), the procedure.
Span Adjust calibrations are improved with larger material samples. Run at the normal flowrate; which should
exceed 50% of the design Rate (P1).
A Span Adjust, utilizing either method, alters the span count of the Multispan number (P26) selected, and
Test Reference (P7) value of the Test Reference selected (P-20). Copy the altered P7 value to the
Programming Chart
enter:
0 = Span Adjust not required (F)
1 = % change, (enter desired adjustment as a percent of span)
2 = material test, (enter the actual material weight)
PL-368
7 – 2
Adjusts the Test Reference value (P7) of the Test Reference selected (P20).
After the CompuFlo III is calibrated utilizing a known Test Reference (e.g. Test Weight representing 20 T/h),
the material flowrate represented by an unknown Test Reference (e.g. alternate Test Weight), may be
established.
This feature may also be used if Span calibrations performed with one Test Reference, tend to consistently
provide greater accuracy than Span calibrations with another Test Reference.
Factoring is not necessarily required after a Span Adjust (P8), as the Test Reference (P7) value of the Test
Reference (P20) for the Multispan Number (P26) selected, is automatically factored by the CompuFlo III.
After performing a Span calibration utilizing the known Test Reference (P20):
a)
With the material flow stopped, apply the unknown Test Reference.
b)
Select the Test Reference to be adjusted (P20).
c)
press "1","ENTER" and wait for the Calibration Duration (P30). When complete,
d)
copy the adjusted Test Reference (P7) value displayed, to the PROGRAMMING CHART.
If [ZERO CALIBRATION REQUIRED] is displayed, perform a Zero calibration
prior to re- attempting the factoring procedure. If a Zero calibration has
been performed very recently, press "CLEAR","ENTER", and proceed.
enter:
0 = Factoring not required (F)
1 = Factoring required (with material flow stopped, and selected test reference applied)
P10
LOW TOTAL CUTOFF
Defines the minimum material flowrate to be processed for Local Total values and Remote Total contact
closures. Range = 0.0 to 100.0.
This feature eliminates the totalizer activity which could occur due to flowmeter vibration or small amounts of
air passing through the flowmeter, when material flow is stopped.
With calibration complete, material flow stopped, and the Rate displayed, observe the highest display value.
Enter the value as a percent of design Rate (P1).
A value of 0 will permit the Total display to count up or down. Remote Total contact closures cease while the
total counts down. The contact closures will resume when the Total display regains the amount by which it
counted down.
enter:
desired value (F = 3.0)
PL-368
7 – 3
RATE DISPLAY DAMPING
Defines the level of damping to be applied to the Rate display. Range = 1 to 999
This may be used to stabilize a fluctuating rate display without affecting accuracy. Higher values provide more
stabilization. Press "RUN" to instantly update the Rate display to the current rate.
enter:
desired value (F = 1)
P14
RATE OUTPUT DAMPING
Defines the level of damping to be applied to the Rate Output. Range = 1 to 999
This may be used to stabilize a fluctuating Rate Output without affecting accuracy. Higher values provide
more stabilization. Rate Output Damping is disabled if the Rate Output Average (P15) feature is utilized.
Press "RUN" to instantly update the Rate Output to the current rate.
enter:
desired value (F = 1)
P15
RATE OUTPUT AVERAGE
Defines the period in seconds between Rate Output updates. The value held, corresponds to the averaged
Rate of the previous period. Range = 0 to 999.
A value of 0 may be entered if Rate output averaging is not desired.
enter:
desired value (F = 0)
P16
RATE BAR GRAPH ASSIGNMENT
Defines the output value the Rate Bar Graph Display represents, as a percent of span.
enter:
0 = Rate Output (P14) (F)
1 = undamped Rate
2 = Rate Display (P11)
P17
RATE OUTPUT MIN
Adjusts the Rate Output reference value for minimum material flowrate. Range = 0 to 4095.
a)
With Change Mode activated and mA meter in series with the load connected to TB1-20,21,
b)
Press "CLEAR" before keying in the estimated reference value, and pressing "ENTER".
c)
Repeat step b) as required to produce the desired minimum Rate Output.
Briefly press "4" (increase by 10’s), or "8" (decrease by 1’s) to fine adjust the reference value, if necessary.
enter:
0 = no adjustment required
1 = Activate Change Mode (F = 631, for 4.00 mA)
PL-368
7 – 4
RATE OUTPUT MAX
Adjusts the Rate Output reference value for maximum material flowrate. Range = 0 to 4095.
a)
With Change Mode activated and mA meter in series with the load connected to TB1-20,21,
b)
Press "CLEAR" before keying in the estimated reference value, and pressing "ENTER".
c)
Repeat step b) as required to produce the desired maximum Rate Output.
Briefly press "4" (increase by 10’s), or "8" (decrease by 1’s) to fine adjust the reference value, if necessary.
enter:
0 = no adjustment required
1 = Activate Change Mode (F = 3160, for 20.00 mA)
P20
TEST REFERENCE SELECTION
Defines the type of test reference selected to represent a material flowrate.
The test reference selected is indicated when the following parameters are accessed:
OPTION
DESCRIPTION
TEST REFERENCE (P7)
SPAN ADJUST (P8)
FACTORING P9
0
Test Weight
[PARAMETER 7]
[PARAMETER 8]
[PARAMETER 9]
1
ECAL
[PARAMETER 7E]
[PARAMETER 8E]
[PARAMETER 9E]
When P20 = 1, ECAL is automatically applied whenever a Span calibration or Factoring procedure is
activated, and removed when the procedure is complete. Refer to Calibration \ Alternate Test References for
ECAL span calibration instructions.
enter:
0 = rate (F)(test weight)
1 = ECAL (electronic reference)
P21
SENSOR TYPE
Defines the type and number of flowmeter transducing elements utilized.
enter:
0 = LVDT (linear variable differential transformer),(F)
1 = 1 load cell
2 = 2 load cells
PL-368
7 – 5
Applies and permits the adjustment of the internal electronic test reference.
Refer to Calibration / Alternate Test References for ECAL Span calibration instructions.
ECAL Adjust cannot be accessed unless the ECAL Test Reference (P20) is selected.
ECAL is adjusted in the RUN mode with no material flow or Test Weight applied to the
flowmeter. When the Adjust option is selected, the simulated flowmeter input is
applied to the CompuFlo III. Record all totalizer values before and after adjusting ECAL.
To adjust ECAL :
a) Enter the RUN mode before accessing P22 and selecting the adjust option.
b) Press "CLEAR" before keying in the estimated reference value, (range = 0 to 4095)
and pressing "ENTER". If Span calibration already exists, entering 0 automatically adjusts
ECAL to 100% of the current span.
c)
Repeat step b) as required while observing the Rate Bar Graph.
d)
Briefly press "4" (increase by 10’s) or "8" (decrease by 1’s) to fine adjust the reference
value, if necessary.
e)
When the Rate Bar Graph indicates the desired simulated Rate, press "ENTER"
f)
Press "ENTER" again to Factor ECAL to the current span and complete the adjustment.
enter :
0 = ECAL off, (if P20 = 1, ECAL will automatically be applied when a Span calibration or
Factoring process is activated, and removed when the process is complete.
1 = ECAL on, (ECAL will be held on except while a Zero calibration is in progress.)
2 = ECAL adjust (adjust as desired, F=2000 when P21=0, 200 when P21=1 or 2).
P25
LINEARIZER
Provides compensation for repeatable non-linear material flow characteristics.
If the material flowrate through the flowmeter is relatively constant during normal operation (except for a few
moments during start up and shut down) linearization should not be required.
In rare cases, electronic linearization may be required if the process monitored demands high accuracy over a
wide range of flowrates.
If the flowmeter linearity seems to vary (beyond acceptable limits) at various material flowrates:
1)
Perform a new Zero and Span calibration (as close as possible
to 100% of P1 Rate) and a Span Adjust (P8).
2)
Apply various Test Weights to the flowmeter to verify mechanical linearity, Non-linear operation with
Test Weights indicates a mechanical flowmeter problem. Investgate and correct.
3)
Referring to the associated flowmeter manual(s), ensure all flowmeter application recommendations
were followed. (If possible, modify the feeder or chute work as recommended).
PL-368
7 – 6
If operation still seems to be non-linear, perform the following tests at 25%, 50%, and 75% of the P1 Rate.
a)
With material flow stopped, reset the Sub Total.
b)
Run a batch of material (larger is better) through the flowmeter, maintaining a constant flowrate.
c)
Record the batch Sub Total
d)
Weigh the material batch (if the actual batch weight is not already known).
If for every flowrate tested, the actual batch weight is equal (or within the accuracy requirements) to the
displayed Sub Total, the actual flowrate to measured flowrate relationship is linear.
Otherwise, enter the % compensation required for each flowrate (automatically selected).
% Compensation = Actual Batch Weight - Sub Total x 100
Sub Total
Turn the linearizer on, and repeat steps a) to d). Adjust the Point 1, 2, and 3 flowrates and % compensation
values as required until the desired results are obtained.
The linearizer values are applied to any Multispan (P26) selected.
enter:
0 = off
1 = on
2 = adjust, enter:
point 1 flowrate (F=25% of (P1) Rate)
point 1 adjustment (F=0%)
point 2 flowrate (F=50% of (P1) Rate)
point 2 adjustment (F=0%)
point 3 flowrate (F=75% of (P1) Rate)
point 3 adjustment (F=0%)
P26
MULTISPAN
Defines the Span calibration result to be used for subsequent measurements. Range = 0 to 8.
This feature may be used to store the Span calibration associated with a number of different material types,
flow characteristics, particle sizes, etc.
To perform a Span calibration for a specific operating condition:
a)
Select the Multispan number to be associated with the current operating condition.
b)
Enter the Test Reference value (P7) for the Test Reference to be used (P20).
c)
Perform a Zero and Span calibration.
d)
Perform a Span Adjust (P8) or Factoring (P9), as required.
To recall the calibration result (when the associated operating condition is re-encountered), select the
appropriate Multispan number. The Multispan number may be selected by providing one or more temporary or
permanent closed contact(s) between the TB1 COM (e.g. TB1-37) and the following TB1 terminals:
PL-368
7 – 7
O = contact open
C= contact closed
For convenience, the Multispan number selection may be provided by a BCD switch connected to the
appropriate TB1-38,39,40,41, and COM contacts.
Alternatively, the Multispan number may be selected via the keypad. If "0" is entered, the MULTISPAN field of
the display is blank and Multispan 1 is utilized.
enter:
desired value, (TB1-38,39,40, and 41 contacts must be open), (F = 0).
P27
ON-LINE: INPUT CALIBRATION
Calibrates the CompuFlo III for the Zero and Span mA input from the bin weighing system. These values
represent the empty and full weight of the On-line calibration weigh bin. Range = 0.000 to 25.00
enter:
0 = On-line calibration not required (F)
1 = Zero calibration (with weigh bin empty, press "ENTER" when the display value is stable.)
2 = Span calibration (with weigh bin full, press "ENTER" when the display value is stable.)
P28
ON-LINE: PARAMETER SELECTION
Defines the actual material weights associated with the On-line calibration.
The reference weight is the actual weight of material contained in the weigh bin between the high and low
limits. Enter the reference weight value in the weight portion of the Rate Units (P0) selected. Enter the max,
high, and low limits as a percent of full weigh bin :
Refer to Calibration / On-Line Span Calibration for complete calibration instructions.
enter :
reference weight, range = 0.000 to 99999 (F = 0)
max limit, (material weight required to stop material feed). Range = 0.000 to 100.0, (F = 0)
high limit, (material weight required to activate totalizer). Range = 0.000 to 100.0 (F = 0)
low limit, (material weight required to de-activate totalizer). Range = 0.000 to 100.0 (F = 0)
93/12/01
MULTISPAN
TB1 TERMINALS CONNECTED TO COM
NUMBER
41
40
39
38
1
O
O
O
C
2
O
O
C
O
3
O
O
C
C
4
O
C
O
O
5
O
C
O
C
6
O
C
C
O
7
O
C
C
C
8
C
O
O
O
PL-368
7 – 8
Activates the On-line calibration.
Upon completion, the On-line calibration may be accepted, or rejected. Refer to Calibration / On-Line Span
Calibration for complete instructions.
enter:
0 = On-Line calibration not required (F)
1 = Activate On-Line calibration
P30
CALIBRATION DURATION
Defines the number of 10 second time periods the CompuFlo III will utilize to perform a Zero or Span
calibration, Factoring (P9), or Verification Totalizer (P31) operation.
Range = 0.01 to 99
A low value reduces calibration time, while a high value increases calibration accuracy.
enter: desired value, (F = 1)
P31
VERIFICATION TOTALIZER
Activates a secondary internal totalizer which totals the amount of material conveyed during the Calibration
Duration (P30). This feature may be used to verify calibration accuracy from the RUN mode without stopping
material flow.
The amount of material totalized by the verification totalizer may be included or excluded from the
totalizer counts.
enter:
0 = verification totalizer off (F)
1 = do not totalize material during the verification.
2 = totalize material during the verification.
P32
VERIFICATION TOTALIZER RESOLUTION
Defines the amount of material weight to be measured, prior to initiating a verification totalizer update. The
weight portion of the Rate Unit (P0) is assumed.
enter:
0 = same as the Local Total (P2) value.(F)
1 = 1/10 of the Local Total (P2) value.
PL-368
7 – 9
Defines the baud rate for PORT 1 data message communication.
The baud rate must be set to the value required by the external device(s) connected to the PORT1 (TB1)
current loop or RS-232C communication connections.
enter:
300
1200
2400
9600 (F)
P41
DATA TRANSMIT INTERVAL
Defines the time lapse in minutes between unsolicited data message transmissions.
Range = 0 to 99999
The Data Transmit Interval may be adjusted as required to control the level of message traffic between the
CompuFlo III and the external device(s) connected to the PORT 1 and/or PORT 2 bipolar current loop or
RS-232C communication connections.
If a value greater than 50,000 is entered, the data message (P42) is transmitted only when the TB1-35,37
contacts are closed.
enter: desired value, (F = 30)
P42
DATA MESSAGE
Defines the ASCII message to be transmitted after every Data Transmit Interval (P41) or when TB1-35,37
contacts are closed.
The current time and date are transmitted with each message. The SYSTEM message includes the value of
parameters P0,1,2,3,7, and 21.
enter:
0 = no message (F)
1 = RATE
2 = MAIN TOTAL
5 = RATE and MAIN TOTAL
9 = SYSTEM
P43
SERIAL PRINTER
Sets the communication mode to suit a serial printer.
enter:
0 = off (F)
1 = on (SW2-7 must be closed for PORT 2/printer communication)
PL-368
7 – 10
Defines the operation of Relay 1 as a Rate Alarm or On-Line calibration prefeed control.
If the Rate Alarm function is selected, the High Limit, Low Limit, and Deadband values are entered as a
percent of span.
The High Limit is the high alarm set point value which will cause the relay to de-energize. If a high limit is not
required, set the high limit to 0.
The Low Limit is the low alarm set point value which will cause the relay to de-energize. If a low limit is not
required, set the low limit to 0.
The Deadband is the amount which the dynamic Rate must exceed the low limit and/or fall below the high
limit before the relay energizes. The deadband value must be less than the difference between the high and
low limit setpoints.
If the On-line calibration function is selected, the Max Limit and Low Limit values are set by On-line:
Parameter Selection (P28). When the Max Limit setpoint value is reached the relay energizes and remains
energized until the Low Limit setpoint value is reached.
enter:
0 = Relay 1 off (F) (always de-energized)
1 = RATE
2 = ON-LINE
If the Rate function was selected, the High Limit may now be set.
enter:
desired High Limit value, (Range = 0.000 to 100.0, F = 98), advances to Low Limit
desired Low Limit value, (Range = 0.000 to 100.0, F = 35), advances to Deadband
desired Deadband value, (Range = 0.000 to 100.0, F = 5)
P52
RELAY 2
Defines the operation of Relay 2 as a Rate Alarm or On-Line calibration prefeed control.
If the Rate Alarm function is selected, the High Limit, Low Limit, and Deadband values must be entered as a
percent of span.
The High Limit is the high alarm set point value which will cause the relay to de-energize. If a high limit is not
required, set the high limit to 0.
The Low Limit is the low alarm set point value which will cause the relay to de-energize. If a low limit is not
required, set the low limit to 0.
The Deadband is the amount which the dynamic value must exceed the low limit and/or fall below the high
limit before the relay energizes. The deadband value must be less than the difference between the high and
low limit setpoints.
If the On-line calibration function is selected, the Max Limit and Low Limit values are set by On-line:
Parameter Selection (P28). When the Max Limit setpoint value is reached the relay energizes and remains
energized until the Low Limit setpoint value is reached.
enter:
0 = Relay 1 off (F) (always de-energized)
1 = RATE
2 = ON-LINE
PL-368
7 – 11
If the Rate function was selected, the High Limit may now be set.
enter:
desired High Limit value, (Range = 0.000 to 100.0, F = 98), advances to Low Limit
desired Low Limit value, (Range = 0.000 to 100.0, F = 35), advances to Deadband
desired Deadband value, (Range = 0.000 to 100.0, F = 5)
P55
100% TEST REFERENCE (V)
Displays the design Rate (P1) value.
P60
SOFTWARE REVISION (V)
Displays the revision number of the software program stored in EPROM 1.
P61
MEMORY TEST (V)
Performs a test on the EPROM 1 memory. Upon completion, [CHECKSUM CORRECT] is displayed to
indicate a successful test.
P63
TOTALIZER CONTACT DURATION
Defines the duration of the remote totalizer relay contact closure in seconds. Range = 0.025 to 8.323
This value is automatically set, based on the Rate (P1) and Remote Total (P3) values entered. If necessary,
adjust this value to provide the duration required by the device connected to TB1-51,52. An entered value is
automatically adjusted to the next higher value permitted.
If the value entered is too high, [TOTAL REGISTRATION TOO LOW] will be displayed. Increase the Remote
Total (P3) value.
When 0 is entered, the system selected value is entered.
enter:
desired value (F = 1, until P1 and P3 values are entered)
P64
ZERO RECORD (V)
Displays the number of operator initiated Zero calibrations performed since the last Master Reset (P99) or
Initial Zero Reset. (F = 0).
P65
SPAN RECORD (V)
Displays the number of operator initiated Span calibrations performed since the last Master Reset (P99) or
Initial Span Reset (P88). (F = 0).
PL-368
7 – 12
Defines the level of operator access permitted.
This feature may be utilized to ensure the programming and/or calibration is not inadvertently altered. Access
to all RUN mode displays and the P66 value is permitted at all Security levels. When a security level is
selected, Security is not invoked until the RUN mode is entered. From the RUN mode, accessing P66
disables Security until the RUN mode is entered again.
enter:
0 = full access permitted (F)
1 = parameter values secured
2 = parameter and Main Total display values secured.
3 = parameter values, Zero and Span calibrations secured.
4 = parameter and Main Total display values, Zero and Span calibrations secured.
P70
CLOCK/CALENDAR
Defines the current Time and Date, to be maintained by the internal clock.
enter:
desired value, (Hours, range = 0 to 23, advances to minutes),
desired value, (Minutes, range = 0 to 59, advances to day),
desired value, (Day, range = 1 to 31, advances to month),
desired value, (Month, range = 1 to 12, advances to year),
desired value, (Year, range = 00 to 99, returns to hours)
P71
TIME (V)
Displays time in twenty-four hour format, (HH:MM).
P72
DATE (V)
Displays date in YY/MM/DD format.
P77
INITIAL ZERO RESET
Performs a Zero Calibration to establish the new Initial Zero count value.
This feature is normally used in response to the [ZERO OUT OF RANGE] message, when the cause of the
deviation is not otherwise correctable. This condition could occur as the result of an intended change in the
Design Parameter values or a mechanical change to the flowmeter assembly.
enter:
0 = not required (F)
1 = Initial Zero Reset
P80
V/F CONVERTER OUTPUT (V)
Displays a reference count proportional to the input level from the flowmeter. Range = 0 to 131,000.
This feature is normally used to verify the integrity of the flowmeter load sensors and cable(s).
PL-368
7 – 13
LOAD CELL A (V)
Displays the input from the load cell connected to TB1-1,2 in mV. Range = 0.00 to 50.00
Access to this parameter may only be gained when SENSOR TYPE (P21) is set to 2. This feature is normally
used to verify the integrity of the load cell after initial installation or subsequent replacement.
P82
LOAD CELL B (V)
Displays the input from the load cell connected to TB1-3,4 in mV. Range = 0.00 to 50.00
Access to this parameter is gained when SENSOR TYPE (P21) is set to any value greater than 0. This
feature is normally used to verify the integrity of the load cell after initial installation or subsequent
replacement.
P85
V/F CONVERTER INPUT (V)
Displays the sum of the amplified load sensor (P21) input voltage(s). Range = -1.00 to 4.00.
P86
ON-LINE CALIBRATION (Input Current) (V)
Displays the CompuFlo III TB1-18,19 mA input from the bin weighing system. Range = 0.00 to 25.00.
P88
INITIAL SPAN RESET
Performs a Span calibration to establish a new Initial Span count value.
This feature is normally used in response to the [SPAN OUT OF RANGE] message, when the cause of the
deviation is not otherwise correctable. This condition could occur as the result of an intended change in the
Design Parameter values or a mechanical change to the flowmeter assembly.
enter:
0 = not required (F)
1 = Initial Span Reset
P90 BALANCING PROCEDURE
Initiates the Load Cell Balancing procedure.
This procedure is only required if the connected flowmeter utilizes two load cell sensing elements and is
equipped with two Test Weight suspension points. This parameter may only be accessed when Sensor Type
is set for 2 load cells (P21 = 2).
Prior to initial calibration or following a load cell replacement, the load cell balancing procedure should be
performed. When the flowmeter load cell signals are balanced, variable material flow patterns have less effect
on flowmeter measurements.
When the load cell balancing procedure is initiated, P91 through P95 must be accessed in sequence. Direct
access to these parameters is not permitted.
PL-368
7 – 14
When the loadcell balancing procedure is completed, perform a Zero and Span calibraton before entering the
Run mode.
enter:
0 = load cell balancing not required (F)
1 = balancing procedure required, (press "1", "ENTER" to advance to P91)
P91 POS B LC (A+B) (V)
Displays the summed load cell input counts.
Apply the Test Weight to a flowmeter Test Weight suspension point. (Refer to the flowmeter instruction
manual for Test Weight application instructions).
enter:
the displayed value (when stable) to advance to P92.
P92 POS B LC (B) (V)
Displays the load cell input counts of one load cell.
Ensure the Test Weight (as applied for P91) is not moved or otherwise disturbed.
enter:
the displayed value to advance to P93.
P93 POS A LC (B) (V)
Displays the load cell input counts of one load cell.
Move the Test Weight to the other flowmeter Test Weight suspension point.
enter:
the displayed value (when stable) to advance to P94.
P94 POS A LC (A+B) (V)
Displays the summed load cell input counts.
Ensure the Test Weight (as applied for P93) is not moved or otherwise disturbed.
enter:
the displayed value to advance to P95.
P95 LOAD CELL BALANCE (V)
Displays the count value, which when entered, will balance the load cell signals.
enter: the displayed value to complete the load cell balance.
PL-368
7 – 15
Initiates a memory reset.
This feature clears memory locations and restores parameter values to their original factory settings. The
implementation of a Reset necessitates CompuFlo III reprogramming and recalibration.
Neither Reset Level affects the Clock/Calendar settings. A Partial Reset maintains the previous, P17, P18,
P20, P21, P22, P27, P40, P41, P42, P43 and load cell balancing settings.
enter:
0 = reset not required (F)
1 = Partial Reset
9 = Master Reset
P100 PARAMETER LIST (V)
Displays parameter names in groups of 10. Pressing "ENTER" advances the display to the next group. This
parameter is not automatically scrolled and therefore must be accessed directly.
I
PL-368
7 – 16
VALID RANGE (F or _ = factory setting)
P0
RATE UNITS
[
]
IMP: 1(T/h),2(LT/h),3(lb/h),4(lb/min) Metric: 1(t/h),2(kg/h),3(kg/min)
P1
RATE
[
]
0.0001 to 99999 (F = 0.000)
P2
LOCAL TOTAL
[
]
1,2,or 5 x .0001 .001,.01,.1,1,10,100,or 1000
P3
REMOTE TOTAL
[
]
1,2,or 5 x .0001 .001,.01,.1,1,10,100,or 1000
P7
TEST REFERENCE
[
]
0.0001 to 99999 (F = 0)
P8
SPAN ADJUST
[
]
0 (off), 1 (%change), 2 (material test)
P9
FACTORING
[
]
0 (off), 1(factor test reference)
P10
LOW TOTAL CUTOFF
[
]
0.0 to 100.0 (F=3.00)
P11
RATE DISPLAY DAMPING
[
]
1 to 999
P14
RATE OUTPUT DAMPING
[
]
1 to 999
P15
RATE OUTPUT AVERAGE
[
]
0 to 99999
P16
RATE BAR GRAPH ASSIGNMENT
[
]
0 (Rate Output, P14), 1 (undamped Rate), 2 (Rate Display, P11)
P17
RATE OUTPUT MIN
[
]
0 to 4095 (F = 631)
P18
RATE OUTPUT MAX
[
]
0 to 4095 (F = 3160)
P20
TEST REFERENCE SELECT
[
]
0 (test weight), 1 (ECAL)
P21
SENSOR TYPE
[
]
0 (LVDT), 1 (1 load cell), 2 (2 load cells)
P22
ECAL ADJUST
[
]
0 (off), 1 (on), 2 (adjust), [ ] count
P25
LINEARIZER
[
]
0 (off), 1 (on), 2 (adjust)
[ ](pt 1),[ ](pt 2),[ ](pt 3) RATE
[ ](pt 1),[ ](pt 2),[ ](pt 3) % COMP
P26
MULTISPAN
[
]
0 to 8 (F = 0)
P27
ON-LINE:INPUT CALIB.
[
]
0 (off), 1 (zero), 2 (span)
P28
ON-LINE:PARAMETER SELECT
[
]
(ref weight)[ ],(max)[ ],(hi)[ ],(lo)[ ]
P29
ON-LINE CALIBRATION
[
]
0 (off), 1 (activate)
P30
CALIBRATION DURATION
[
]
0.1 to 99 (F = 1)
P31
VERIFICATION TOTAL
[
]
0 (off), 1 (HOLD TOTAL), 2 (add to Total)
P32
VERIFICATION TOTAL RES
[
]
0 (same as P2), 1 (P2 x 1/10)
P40
BAUD RATE
[
]
300, 1200, 2400, 9600
P41
DATA TRANSMIT INTERVAL
[
]
0 to 99999 (F = 30)
P42
DATA MESSAGE
[
]
0 (off),1 (Rate),2 (Total),5 (Rate and Total),9 (System)
P43
SERIAL PRINTER
[
]
0 (off), 1 (on)
P51
RELAY 1
[
]
0 (off), 1 (Rate), 2 (On-line)
[ ](hi),[ ](lo),[ ] (deadband) in %
P52
RELAY 2
[
]
0 (off), 1 (Rate), 2 (On-line)
[ ](hi),[ ](lo),[ ] (deadband) in %
P55
100% TEST REFERENCE
[
]
0.0001 to 99999 (F = Rate (P1), display only)
P60
SOFTWARE REVISION
[
]
1.00 to 99.99 (display only)
P61
MEMORY TEST
[
]
Pass or Fail, (display only)
P63
TOTALIZER CONTACT DUR
[
]
0.025 to 8.323 seconds (F = 1 until P1 and P3 are set)
P64
ZERO RECORD
[
]
(display only)
P65
SPAN RECORD
[
]
(display only)
P66
SECURITY LEVEL SELECT
[
]
0(off),1(P#’s),2(P#’s,Total),3(P#’s,Zero,Span),4(P#’s,Total,Zero,Span)
P70
CLOCK/CALENDAR
[
]
hrs(0-23),min(0-59),day(1-31),month(1-12),year(00-99)
P71
TIME
[
]
HH:MM display, (24 hour format)
P72
DATE
[
]
YY/MM/DD format
P77
INITIAL ZERO RESET
[
]
0 (off), 1 (reset)
P80
V/F CONVERTER OUTPUT
[
]
0 to 131,000 counts, (display only)
P81
LOAD CELL A INPUT
[
]
0.00 to 50.00 mV, (display only)
P82
LOAD CELL B INPUT
[
]
0.00 to 50.00 mV, (display only)
P85
V/F CONVERTER INPUT
[
]
-1.00 to 4.00 V, (display only)
P86
ONLINE: MA INPUT
[
]
0 to 25.0 mA, (display only)
P88
INITIAL SPAN RESET
[
]
0 (off), 1 (reset)
P99
RESET
[
]
0 (off), 1 (Partial ), 9 (Master)
P100
PARAMETER LIST
[
]
0 to 99 in groups of 10, (display only)
PL-368
8 – 1
Prior to the initial operation of the CompuFlo III the following checks should be made:
» the test reference should be removed from the flowmeter.
» the totalizer(s) should be reset to zero.
The CompuFlo III is now ready for service.
Ensure the CompuFlo III is in the RUN mode.
To enter the RUN mode,
The CompuFlo III assumes the last RUN mode display accessed.
If necessary,
to display Rate.
Open the material prefeed, ensuring the design Rate is not exceeded.
to display the current material total. Observe the total value incrementing.
A program of calibration checks should be performed frequently at first. The frequency of these checks may
be reduced as time and experience dictate.
All personnel should be instructed on the safe and proper operation of the CompuFlo III and be instructed
when and if a calibration check should be performed, what level of zero and span deviation is acceptable, and
when to reset the totalizer(s).
If desired, a photocopy of the following page may be provided, to personnel responsible for CompuFlo III
daily operation.
ALT
DISP
ALT
DISP
RUN
PL-368
9 – 1
Ensure power is supplied to the CompuFlo III.
When power is first applied, the CompuFlo III will automatically perform a series of tests for about 10 seconds
and then resume operation in the last mode entered.
The following procedures may be performed on a routine basis, as required. Access to the Zero and Span
calibration, and Reset Total functions may be restricted.
ZERO CALIBRATION CHECK
Ensure the flowmeter test reference (Test Weight or ECAL) is removed. With no material flow,
to initiate a zero calibration. When complete (time dependent on programming) the
deviation from the last operator initiated zero calibration is displayed.
if the zero deviation is acceptable.
If the zero deviation is not acceptable, or if [ZERO OUT OF RANGE] is displayed, investigate the reason for
the deviation, correct the condition, and try the zero calibration again.
SPAN CALIBRATION CHECK
If the following features were implemented during system programming, perform the following checks:
FEATURE
CHECK
Test Reference Select (P20)
Ensure the desired Test Reference is selected.
Multispan Number (P26)
Ensure the appropriate Multispan number is selected.
Apply the flowmeter test reference (Test Weight or ECAL). With no material flow,
to initiate a span calibration. When complete (time dependent on programming) the
deviation from the last operator initiated span calibration is displayed.
if the span deviation is acceptable.
If the span deviation is not acceptable, or if [SPAN OUT OF RANGE] is displayed, investigate the reason for
the deviation, correct the condition, and try the span calibration again.
Remove the flowmeter test reference.
RESET TOTAL
If necessary, reset the CompuFlo III totalizer.
to initiate a totalizer reset.
to select the Main or Sub Total.
to reset the selected Total display value to 0.
Refer to the manufacturers instructions to reset the remote totalizer, if any.
RUN
(and then
if necessary) to display Rate.
Activate the material prefeed control device (if any) to begin running material through the flowmeter.
to access the Total display, observe the amount of material run through the flowmeter
since the last Total Reset.
ALT
DISP
ALT
DISP
CLEAR
ENTER
SPAN
ENTER
RUN
RESET
TOTAL
I
ENTER
ENTER
ZERO
ENTER
PL-368
9 – 2
The CompuFlo III may be operated in one of the following serial communication modes:
» Remote (Milltronics Terminal)
» Host (IBM PC compatible computer or PLC)
» Serial Printer
The Bipolar Current Loop may be utilized for cable runs up to 1500 metres (5000 ft). If communication with an
RS-232 device is required, the Milltronics BIC-II or CVCC may be used to convert the Bipolar Current Loop to
RS-232. The BIC-II is also capable of Bipolar Current Loop to RS-422 conversion.
The CompuFlo III RS-232 port may be connected directly to an RS-232 device, where the communication
cable run is less than 15 m (50 ft).
To set the Port 1 communication baud rate to suit the device connected, refer to PARAMETERS/P40. To set
the Port 2 baud rate, refer to START UP/Hardware Set Up.
customer’s
computer
CVCC
or BIC II
( if required )
CompuFlo III
serial
printer
customer’s computer*
(*remote terminal emulation
software available)
OR
remote
terminal
CVCC
( or BIC II )
PL-368
10 – 1
This mode provides complete access to all CompuFlo III functions via a Milltronics remote terminal. To
receive communication from the CompuFlo III PORT 1 or PORT 2 connection, SW2-6 of the remote terminal
must be closed.
Alternatively, a remote terminal emulation software package is available for IBM PC compatible computers
supporting colour graphics (VGA).
If the computer (supporting a parallel printer) is connected to PORT 1, (when P43=1) a printout containing the
Data Message (P42) selected is initiated each time:
» the Data Transmit Interval (P41) lapses
» a dry contact is provided across CompuFlo III TB1-35 and COM (e.g. TB1-36).
HOST COMMUNICATION
Host communication permits up to 16 CompuFlo III’s (serially connected via PORT 1), to communicate with a
computer or Programmable Logic Controller. Refer to Start Up\Hardware Set Up\Unit I.D. Code).
In this mode, data acquisition and analysis is accomplished by a customer supplied software package. Refer
to Protocol.
SERIAL PRINTER COMMUNICATION
Two modes of serial printer operation are available.
The Port 1 mode (similar to previous Milltronics integrator versions) printout is initiated each time :
» a dry contact is provided across pins 7 and 17 of the printer DP25 connector.
» the Printer Test button is pressed.
The printout contains the : time, date, total, and total engineering units.
The Port 2 mode is compatible with any serial printer.
Close the CompuFlo III SW2 contact 7 (SW2-7) and set the Data Transmit Interval (P41), Data Message
(P42) and Serial Printer (P43) parameters as desired. Refer to Parameters.
The printout, containing the Data Message selected, is initiated each time :
» a dry contact is provided across the CompuFlo III TB1-35 and COM (e.g. TB1-36)
» the Data Transmit Interval elapses.
PL-368
10 – 2
Protocol refers to the format, sequence and value of the data fields utilized in Host Mode communication
messages. Each data field of a CompuFlo III message contains one or more bytes of ASCII binary code.
Each byte contains:
» 8 data bits
» no parity bit
» 1 stop bit
DATA FIELD DESCRIPTIONS
The following data fields are utilized in CompuFlo III host mode messages.
somIdentifies the start of a message (STX), ASCII character = 02.
DEVICE
Identifies the CompuFlo III to which the message applies. The device number equals the Unit
I.D. code, as set by SW1 contacts 1 - 4. ASCII characters = 00 to 15.
MTIdentifies the message type transmitted, ASCII characters:
50 = material flow rate
53 = totalized material
READING
Contains the measurement value in the units of measure selected during CompuFlo III
programming. The number of bytes in this data field will vary dependent upon the reading
value. Up to 8 ASCII characters including the decimal point may be transmitted.
UNITS
Three ASCII characters identify the totalizer engineering units (MT = 53 only). The first
character is always a space. The remaining characters may be:
t = Metric Tons
LT = Long Tons
T = Short Tons
kg = Kilograms
lb = Pounds
EOM
Identifies the end of a message (CR), ASCII character = 0D.
+20 mA
-20 mA
0
s
1
2
3
4
5
6
7
8
s
t
s
n
r
t
t
t
t
t
t
a
t
d
d
h
h
h
h
h
o
r
p
t
PL-368
10 – 3
Message requests must be transmitted from the host to the CompuFlo III in the following format.
som DEVICE MT eom
Example:
Data
ASCII
Example
Field
Character
Description
som
02
start of message
DEVICE
01
for CompuFlo III # 1
MT
50
material flow rate request
eom
0D
end of message
MESSAGE RESPONSES
The CompuFlo III response to a flow rate (MT=50) message request will be in the following format.
som DEVICE MT READING eom
Example:
Data
ASCII
Example
Field
Character
Description
som
02
start of message
DEVICE
00
from CompuFlo III# 0
MT
50
material flow rate response
READING
392.5
is 392.5
eom
0D
end of message
The response to a material total (MT=53) message request will be in the following format.
som DEVICE MT READING UNITS eom
Example:
Data
ASCII
Example
Field
Character
Description
som
02
start of message
DEVICE
00
from CompuFlo III# 0
MT
53
material total response
READING
129.2
is 129.2
UNITS
MT
Metric Tonnes
eom
CR
end of message
I
PL-368
10 – 4
ALPHABETICAL PARAMETER LISTING
PARAMETER
PARAMETER
PARAMETER
PARAMETER
NAME
NUMBER
NAME
NUMBER
Balancing Procedure
P90
Parameter List
P100
Baud Rate
P40
Rate Bar Graph Assignment
P16
Calibration Duration
P30
Rate
P1
Clock/Calendar
P70
Rate Output Average
P15
Converter Input (V/F)
P83
Rate Output Max
P18
Converter Output (V/F)
P80
Rate Output Min
P17
Damping, Rate Display
P11
Rate Units
P0
Damping, Rate Output
P14
Record, Zero
P64
Data Transmit Interval
P41
Record, Span
P65
Data Message
P42
Relay 1
P51
Date
P72
Relay 2
P52
ECAL Adjust
P22
Security
P66
Factoring
P9
Sensor Type
P21
Initial Zero Reset
P77
Serial Printer
P43
Initial Span Reset
P88
Software Revision
P60
Linearizer
P25
Span Adjust
P8
Load Cell Balance
P95
Test, Memory
P61
Load Cell Input, A
P81
Test Reference
P7
Load Cell Input, B
P82
Test Reference 100%
P55
Master Reset
P99
Test Reference Selection
P20
Multispan
P26
Time
P71
On-line: Calibration
P29
Total Contact Duration
P63
On-line: Calibration mA
P86
Total, Local
P2
On-line: Input Calibration
P27
Total, Low Cutoff
P10
On-line: Parameter Selection
P28
Total, Remote
P3
POS A LC (A+B)
P94
Total, Verification
P31
POS A LC (B)
P93
Total, Verification Resolution
P32
POS B LC (A+B)
P91
POS B LC (B)
P92
PL-368
11 – 1
MAINTENANCE AND SPARE PARTS
MAINTENANCE
The CompuFlo III requires no maintenance. However a program of periodic preventative maintenance should
be initiated. This should include regular inspection, general cleaning and good housekeeping practices.
Enclosures and printed circuit boards should be cleaned only when the power is disconnected at the main
breaker. The use of a vacuum cleaner to remove foreign material dislodged with a clean dry paint brush is
recommended. Check all electrical connections for signs of corrosion and/or electrical arcing.
The CompuFlo III memory backup and calibrator batteries should be replaced annually. The 3.6 Volt lithium
battery (located on the mother board top right corner) should only be replaced while the CompuFlo III power is
ON. The 9 Volt calibrator battery is located on the back of the CompuFlo III door.
SPARE PARTS
The following list describes the CompuFlo III components which may be ordered as a spare part. The
ITEM # refers to the number which should be included on the purchase order to identify the part required.
DESCRIPTION
ITEM #
Battery, Lithium, 3.6 V, AA, (Memory)
20200031
Battery, Alkaline, 9 Volt, (Calibrator)
20200025
Enclosure Bottom Plate
24650116
Fuse, 0.75A, 250V, Slo-Blo, CSA, (Main)
22550112
For Remote Terminal ordering information, contact Milltronics or your distributor.
PL-368
11 – 2
The following messages may be encountered during CompuFlo III programming, calibration, or operation.
DISPLAY MESSAGE
DESCRIPTION
[ABORTED]
The activated process or procedure was not completed correctly
(or before "CLEAR" was pressed). Retry the feature attempted.
[AUTO ZERO ABORTED]
The Auto Zero was more than 2% of span from the last operator
Zero before SW1-6 was closed. Refer to Calibration/Lockout Mode.
[AUTO ZERO LIMIT EXCEEDED]
The Auto Zero was more than 2% of span from the last operator
Zero. Refer to Calibration/Auto Zero.
[CALIBRATION ABORTED]
"CLEAR" was pressed before the activated calibration was accepted.
[CERTIFICATION LOCKOUT]
Attempted access to a function which is restricted during operation
in the Lockout mode. Refer to Start up/Hardware Set Up/Lockout.
[CHECKSUM ERROR]
Integrator failed Memory Test. Refer to Parameters/P61 Memory Test.
[ENTRY ERROR]
Invalid parameter selection or alteration. Refer to Parameters.
[PARAMETERS NOT ENTERED]
A calibration or run mode operation was attempted before essential
parameter values were entered. Refer to Parameters/P1,P2,P3, and P7.
[REMOTE TOTAL SATURATION]
The systems totalization capabilities were exceeded; the Remote Total
counts are incorrect. Refer to [TOTAL REGISTRATION TOO LOW].
[SECURITY LOCKOUT]
Attempted access to a function which is restricted by Security
(P66). Refer to Parameters/P66 Security.
[SPAN CALIB REQUIRED]
Attempted RUN mode operation prior to accepting an Initial
Span calibration. Refer to Calibration/Span.
[SPAN ERROR]
The attempted calibration (or adjustment) would have exceeded
the systems span capabilities. Investigate and correct before retrying.
[SPAN OUT OF RANGE]
The attempted Span was greater than 12% of span from the Initial
Span. Refer to Parameters/P88 Initial Span Reset.
[TEST REFERENCE VALUE REQUIRED]
A Test Reference value (P7) has not been entered for the current
Test Reference selected (P20). Refer to Parameters.
[TOTAL REGISTRATION TOO LOW]
The value entered exceeds totalization capabilities Refer to
Parameters/P2 Local Total, P3 Remote Total & P63 Contact Duration.
[ZERO CALIB REQUIRED]
Attempted RUN mode operation or Span calibration prior to
accepting an initial Zero calibration. Refer to Calibration/Zero.
[ZERO CALIB REQUIRED]
Span calibration or Factoring (P9) procedure attempted from
[OR PRESS CLEAR]
the RUN mode. Press "CLEAR" only if a Zero has been
performed recently.
[ZERO OUT OF RANGE]
The attempted Zero calibration was greater than 12% span from
the Initial Zero reference. Refer to Parameters/P77 Initial Zero Reset.
PL-368
11 – 3
Every CompuFlo III integrator is subjected to extensive quality assurance procedures to ensure the highest
possible degree of quality, reliability, and performance is achieved.
The following listing indicates the probable cause, and proper course of action to be taken should
the specified fault symptom occur.
SYMPTOM
CAUSE
ACTION
Display blank
»Loss of power
»check power wiring, jumpers, and fuse
»check POWER switch is ON
»check AC supply
»check daughter board HD2-1,4
Will not complete a Zero or Span
» Loss of input signal(s)
» check P80
calibration
» check sensor wiring
» Wrong Design Parameter
» check programming value(s)
Calibration takes too long
» Calibration Duration too long
» reduce P30 value
Zero calibration deviation drifts
» Loose mechanical assembly
» tighten all bolts and clamps
» Sensing head not level
» refer to flowmeter manual
Span calibration deviation drifts
» Loose mechanical assembly
» tighten all bolts and clamps
» Variable material flow patterns
» refer to flowmeter and
application guideline manuals
Accuracy is not within
» Test Reference doesn’t
» perform a new Zero and Span limits
desired limits
represent true operating
calibration, followed by a
conditions
Span Adjust (P8).
» Calibration Duration too short
» increase P30 value *
» On-Line Calibration required
» Refer to Calibration.
* Perform a new Zero and Span calibration and a Span Adjust (P8), after the recommended action.
For more trouble shooting information, refer to the flowmeter and application guideline instruction manuals.
PL-368
11 – 4
Flip the POWER switch to ON. The CompuFlo III will perform a self test for 10 seconds.
MASTER RESET - Prepares the CompuFlo III for initial programming or complete reprogramming.
Proceed to OPERATION if previous programming and calibration is to be retained.
[PARAMETER 99
] Master Reset parameter accessed.
[PARAMETER
] is displayed after 10 seconds.
RATE UNITS - Defines the desired Rate display units of measure.
•
[PARAMETER 0
] Rate Units parameter accessed.
with SW1-5* open with SW1-5* closed
tons/hour (T/h)
for tonnes/hour (t/h)
long tons/hour (LT/h)
for Kilograms/hour (kg/h)
pounds/hour (lb/h)
for Kilograms/minute (kg/min)
pounds/min (lb/min)
* Switch SW1-5 is located on the CompuFlo III mother board, (top left corner).
DESIGN RATE - Defines the material flowrate which will produce the full scale Rate Output.
[PARAMETER 1
]
Design Rate parameter accessed, key in flowrate value,
to store the keyed in value in memory.
LOCAL TOTAL - Defines the material weight (in P0 weight units) required for each Total display update.
[PARAMETER 2
]
Local Total parameter accessed.
Key in one of the following material weight values:
0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000
0.0002, 0.002, 0.02, 0.2, 2, 20, 200, 2000
0.0005, 0.005, 0.05, 0.5, 5, 50, 500, 5000
to store the keyed in value in memory.
ENTER
9
ENTER
2
0
ENTER
ENTER
ENTER
ENTER
3
ENTER
4
ENTER
1
ENTER
2
ENTER
3
ENTER
1
9
9
PAR
PAR
ENTER
ENTER
ENTER
Pl-368
11 – 5
- Defines the material weight required to cause a remote TOTAL relay contact closure.
[PARAMETER 3
]
Remote Total parameter accessed.
Key in one of the following material weight values:
0.0001, 0.001, 0.01, 0.1, 1, 10, 100, 1000
0.0002, 0.002, 0.02, 0.2, 2, 20, 200, 2000
0.0005, 0.005, 0.05, 0.5, 5, 50, 500, 5000
to store the keyed in value in memory.
TEST REFERENCE - Defines the simulated material flowrate (in P0 units) represented by the Test Weight.
[PARAMETER 7
]
Test Reference parameter accessed.
Key in the calculated value, (refer to the flowmeter manual for Test Weight calculation instructions)
to store the keyed in value in memory.
SENSOR TYPE
- Identifies the type of input signal(s) from the flowmeter.
[PARAMETER 21
] Sensor Type parameter accessed.
if an LVDT is connected, or if a single load cell is connected,
or if dual load cells are connected.
CALIBRATION
- Prepares the CompuFlo III for operation.
If [ZERO OUT OF RANGE] or [SPAN OUT OF RANGE] is displayed after a calibration attempt, refer to the
PARAMETERS section for Initial Zero Reset (P77) and/or Initial Span Reset (P88) instructions.
ZERO
With no material flow or test weight(s) applied to the flowmeter,
the zero count value from the last Zero calibration is displayed.
to start the calibration, when complete the deviation from the last Zero is displayed.
to accept the new Zero calibration results.
ENTER
ENTER
ENTER
ENTER
ZERO
ENTER
ENTER
1
2
1
ENTER
ENTER
PAR
2
ENTER
0
ENTER
Pl-368
11 – 6
With no material flow and the test weight(s) applied to the flowmeter,
the span count value from the last Span calibration is displayed.
to start the calibration. When complete the deviation from the last Span is displayed.
to accept the new Span calibration results.
OPERATION
Ensure the test weight is not applied to the flowmeter before opening the material feed.
RATE & TOTAL DISPLAYS
to enter the RUN mode.
(if required) to obtain the Rate display.
to obtain the Total display.
(as required) to obtain the Main Total or Sub Total values.
RESET TOTAL
- Resets the Main or Sub Total value displayed.
the Main or Sub Total value displayed is now 0.
PERFORMANCE ENHANCEMENT
For optimum accuracy, perform Zero and Span calibrations frequently. Read this manual thoroughly
for details on all CompuFlo III features. A material test utilizing the Span Adjust (P8) parameter,
is recommended.
SPAN
ENTER
ENTER
RUN
ALT
DISP
ALT
DISP
RESET
TOTAL
ENTER
CLEAR
I
Pl-368
11 – 7
( 7" )
330 mm
( 13" )
101 mm
( 4" )
435 mm
( 17.1" )
406 mm
( 16" )
enclosure bottom plate
( for cable / conduit entrance )
11 mm dia.
( 0.4" )
4 places
OUTLINE and MOUNTING
FIG. 1
PL-368
12 – 1
COMPUFLO III LAYOUT
SW 1
EPROM 2
calibrator
battery
memory/ clock
battery
voltage
select
jumper
barrier
jumpers
Power
switch
main
fuse
display
EPROM 1
K A
K A
6
4
1
UP
NO
NC
CW
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
+
-
+
-
RCV
XMT
SHLD
RCV
XMT
ECHO
COM
1
20
MILLTRONICS
COMPUSCALE /
3/4 AMP
SLOBLO
MDL
FUSE
ML 51026331
PN 24751325-04
MADE IN CANADA
PETERBOROUGH
COMPUFLO
DISPLAY
DRIVER
SN
RS232
SW2
EPROM 2
TB2
COM
FU1
ONTARIO
COMM PORT 2
CURRENT
STD HAZ’D
HAZ’D STD
FUSE
MDL
SLOBLO
1/4 AMP
PIN 1
J2
FUSE
J1
POWER
EXC FUSE
SENSOR
SPEED
FU2
COM
TIME / DATE / MEMORY
EPROM 1
SW1
2
2
2
3
1
3
ECAL
ACOM4
N15V
P15V
N5V2
N8V
P5V2
P8V
P30VI
P13V
P18V
P5V
P24V
N24V
COMM PORT 1
MDL
SLOBLO
1/4 AMP
CURRENT
RATE
TB1
MA
INSTRUCTION BOOK COMPUFLO I I I PL-368
COMPUSCALE I I I PL-367
LVDT
47
7
PIN 1
V LOAD
OFF
ON
10
PN 24751326-04
65
TOTAL
BATTERY
LITHIUM
3.6 VOLT
ML 51026341
INSTRUCTION BOOK
RATINGS
BOOK FOR RELAY
SEE INSTRUCTION
SN
PETERBOROUGH . ONTARIO
MADE IN CANADA
COMPUSCALE / COMPUFLO
MILLTRONICS
SELECT
VOLTAGE
100VAC
115VAC
200VAC
[ 50/60 HZ VA ]
VAC OPERATION
100/115/200/230/
POSITION J1 FOR
N
L1
L2
GR
TOTAL
RELAYS
R2
R1
SPANS
8
4
2
1
COM
COM
PRINT
A.ZERO
CONST
COM
SIG
SPEED
RS232
LVDT
EXC
SHLD
COM
RCV
XMT
RCV
XMT
RATE
ONLN
EXC
COM
-SIG
SHLD
LOADCELLS
SEN
SEN
EXC
EXC
-
-
+
+
D
C
B
A
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
1
2
3
4
5
6
7
8
9
11
12 13 14
15
16 17
18
19 20
21
22
23
24 25 26
27
28
29
30 31 32
33
34
35
36
37 38 39
40
41
42
43
44
45 46
47 48
49
50
51
52
230VAC
SN
T
1263957
MAIN TOTAL
150%
100%
50%
0%
-50%
SPAN No. (1-8):2
R1:RATE HI R2:RATE LO
MILLTRONICS CALIBRATOR IV PN 24751327-01
ML 51026351
MADE IN CANADA
PETERBOROUGH ONTARIO
R3
Q2
Q1
D1
R2
C1
R1
LD1
U1
C2
C3
CR1
D2
RC1
B1
calibrator
(door mount)
display
board
SW 2
mother
board
93/12/01
FIG. 2
PL-368
12 – 2
COMPUFLO III / FLOWMETER INTERCONNECTION
LVDT
SINGLE LOAD CELL
DUAL LOAD CELLS
1.
Where a flowmeter must be installed in a hazardous area consult Milltronics or your
distributor for wiring instructions.
2.
Where the integrator to load cell flowmeter cable exceeds 150m (500 ft):
A) remove jumpers from CompuFlo III, TB1 - 9,10 and TB1 - 11,12
B) run an additional shielded conductor to the junction box nearest the load cell(s) from:
» CompuFlo III TB1 - 10 to loadcell(s) red
» CompuFlo III TB1 - 11 to loadcell(s) black
CompuFlo III
TB1
CompuFlo III
TB1
CompuFlo III
TB1
FIG. 3
PL-368
12 – 3
POWER, AUTO ZERO & RATE OUTPUT WIRING
POWER
RATE OUTPUT
1.
Ensure the CompuFlo III J1 position matches the power to be applied to TB1 - 51,52.
2.
The Auto Zero contact must be closed when the material feed is stopped,
if Auto Zero calibration is desired.
AUTO ZERO
Voltage
Select
prefeed activated
dry contact
Power
Connection
100/115/200/230
V AC 65 VA
CompuFlo III
TB1
CompuFlo III
TB1
FIG. 4
to mA input of device
750 Ω Max load
PL-368
12 – 4
ALARM / CONTROL RELAYS
REMOTE TOTALIZER RELAY
AC TOTALIZER
DC TOTALIZER
FIG. 5
Relay contacts are shown in
de-energized condition.
(Power OFF and Alarm Status)
to alarm / control devices
CompuFlo III
TB1
48 49
R1
C1
R2
C2
* POWER
SOURCE
CompuScale III
TB1
AC
* Some totalizers have an internal power source.
Shaded area recommended for
inductive load (L)
R1 = R2 = 10 to 30 Ω
C1 = .01 to .1 mFd, 500 V
C2 = .001 to .01 mFd, 500 V
CompuFlo III
TB1
48 49
+
* POWER
SOURCE
CompuScale III
TB1
DC
CompuFlo III
TB1
PL-368
12 – 5
RS - 232
CURRENT LOOP
MULTIPLE CURRENT LOOP
1.
Power may be disconnected from any CompuFlo III in a multiple current loop
without affecting the communication of the other CompuFlo III’s.
FIG.6
to device current loop connection
CompuFlo III
CompuFlo III
to device current loop connection
CompuFlo III
to device RS-232 port
CompuFlo III
to device RS-232 port
TX
TX
RX
RX
to RS-232 device
CompuFlo III
Unit I.D. # 00
CompuFlo III
Unit I.D. # 01
CompuFlo III
Unit I.D. # N
(max N=15)
CVCC or BIC II
PL-368
12 – 6